York YCUL Air-Cooled Scroll Condensing Unit User guide

York YCUL Air-Cooled Scroll Condensing Unit User guide
FORM 150.63-EG5 (1017)
MODEL YCUL
AIR-COOLED SCROLL CONDENSING UNITS
STYLE E
50 and 60Hz
15 – 80 TON
50 – 280 kW
R-410A
FORM 150.63-EG5 (1017)
Nomenclature
YC
U
L
0045
E
E
46
X
DESIGN
LEVEL
REFRIGERANT
E = R-410a
SCROLL
COMPRESSOR
UNIT
HIGH EFFICIENCY UNIT
NOMINAL CAPACITY
YORK SCROLL
E
ACROSSTHE-LINE
START
VOLTAGE CODE
-17 = 208-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
Performance data provided in this document was created in accordance with Johnson Controls software:
YORKworks version 13.02 and DXCHILL version 6.04.
Approvals
• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1
• AHRI Standard 550/590.
• UL 1995 – Heating and Cooling Equipment
• ASHRAE 15 – Safety Code for Mechanical Refrigeration
• ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning
Equipment and Systems
• N.E.C. – National Electrical Code
• OSHA – Occupational Safety and Health Act
2
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Table Of Contents
INTRODUCTION....................................................................................................................................................... 5
MICROCOMPUTER CONTROL CENTER............................................................................................................... 6
OPTIONS AND ACCESSORIES............................................................................................................................... 9
SELECTION DATA.................................................................................................................................................. 12
RATINGS................................................................................................................................................................. 18
PHYSICAL DATA.................................................................................................................................................... 36
DIMENSIONS.......................................................................................................................................................... 38
ISOLATOR DETAILS.............................................................................................................................................. 46
ELECTRICAL NOTES............................................................................................................................................ 49
ELECTRICAL DATA - 50 & 60HZ........................................................................................................................... 50
CIRCUIT BREAKER CALCULATIONS.................................................................................................................. 53
APPLICATION DATA.............................................................................................................................................. 54
GUIDE SPECIFICATIONS...................................................................................................................................... 56
JOHNSON CONTROLS
3
FORM 150.63-EG5 (1017)
THIS PAGE INTENTIONALLY LEFT BLANK.
4
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Introduction
YORK Air-Cooled Scroll Condensing Units are the perfect refrigeration com­ponents for all
air conditioning applications that use DX central station air han­dling. They are designed
for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors, an air cooled condenser, and a weather resistant microprocessor control center, all
mounted on a formed steel base.
GENERAL
The 15 - 80 Ton (50 - 280 kW) YCUL models are shipped complete from the factory ready
for installation and use.
The unit is pressure-tested, evacuated and given a nitrogen holding charge and includes
an initial oil charge (R-410A refrigerant supplied by others). After assembly, a operational
test is performed to assure that each control device operates correctly.
The unit structure is heavy-gauge, galvanized steel. This galvanized steel is coated with
baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray testing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with
NFPA 70 (National Elec­tric Code), ASHRAE/ANSI 15 Safety code for mechanical refrigeration, and are cETL listed. All units are produced at an ISO 9000-registered facility.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll compressors. The YCUL compressors
incorporate a scroll design that is compliant in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir
provides greater liquid tolerance. Compressor crankcase heaters are also included for
extra protection against liquid migration.
CONDENSER
Coils – Fin and tube condenser coils of seamless, internally-enhanced, high-condensingcoefficient, corrosion resistant copper tubes are arranged in staggered rows, mechanically expanded into aluminum fins. Integral subcooling is included. The design working
pressure of the coil is 650 PSIG (45 barg).
Low Sound Fans – The condenser fans are composed of corrosion resistant aluminum
hub and composite blades molded into a low noise airfoil section. They are designed for
maximum efficiency and are statically and dynamically balanced for vibration-free operation. They are directly driven, and positioned for vertical air discharge. The fan guards are
constructed of heavy-gauge, rust-resistant, PVC (polyvinyl chloride)-coated steel wire.
Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current protected. They feature ball bearings that are double-sealed and permanently lubricated.
JOHNSON CONTROLS
5
FORM 150.63-EG5 (1017)
MicroComputer Control Center
All controls are contained in a NEMA 3R powder painted steel cabinet with a gasketed
door and includes:
Liquid Crystal Display with Light Emitting Diode backlight­ing for outdoor viewing:
• Two display lines
• Twenty characters per line
Color coded 12-button non-tactile keypad with sections for:
DISPLAY/PRINT of typical information:
• Suction temperatures (optional)
• Ambient temperature
• System pressures (each circuit)
• Operating hours and starts (each compressor)
• Print calls up to the liquid crystal display:
• Operating data for the systems
• History of fault shutdown data for up to the last six fault shutdown conditions
• An RS-232 port, in conjunction with this press-to-print button, is provided to permit
the capability of hard copy print-outs via a separate printer (by others).
ENTRY section to:
• ENTER setpoints or modify system values SETPOINTS updating can be performed
to:
• Suction pressure setting
• Suction pressure control zone
• Remote reset temperature range
• Set daily schedule/holiday for start/stop
• Manual override for servicing
• Low and high ambient cutouts
• Number of compressors
• Low suction pressure cutout
• High discharge pressure cutout
• Anti-recycle timer (compressor start cycle time)
6
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
MicroComputer Control Center (Cont'd)
• Anti-coincident timer (delay compressor starts) UNIT section to:
• Set clock
• Set options
• Set unit option
Set unit control for Discharge Air Temperature Control or for Suction Pressure Control
(requires Suction Pres­sure Transducers – standard.
UNIT ON/OFF switch
The microprocessor control center is capable of display­ing the following:
• Suction temperatures (optional)
• Low ambient temperature cutout setting
• Outdoor air temperature
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• System discharge pressure
• Discharge Air Temperature Reset via a YORK ISN DDC or Building Automation System (by oth ers) via:
• a pulse width modulated (PWM) input as standard
• a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S.
interface option
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
• No cooling load condition
• Day, date and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control (Discharge Air Temperature control
only)
• Automatic lead/lag of compressors within a system
• Compressor starts & operating hours (each compressor)
• Status of hot gas valves, and fan operation
• Run permissive status
JOHNSON CONTROLS
7
FORM 150.63-EG5 (1017)
MicroComputer Control Center (Cont'd)
• Number of compressors running
• Liquid solenoid valve status
• Load & unload timer status
Provisions are included for: pumpdown at shutdown; optional remote discharge air temperature reset and two steps of demand load limiting from an external building automation
system. Unit alarm contacts are standard.
Programmed setpoints are retained in lithium battery-backed RTC memory for 5 years
minimum. The operating program is stored in non-volatile memory (EPROM) to eliminate
chiller failure due to AC power failure/battery discharge.
• Native communication capability for BACnet (MS/TP) and Modbus
• Optional communciation available for N2 and LON via eLink option
POWER PANEL
Each panel contains:
• Compressor power terminals
• Compressor motor starting contactors per International Electrotechnical Commission
• Control power terminals to accept incoming for 115-1-60 control power
• Fan contactors & overload current protection
The power wiring is routed through liquid-tight conduit to the compressors and fans.
8
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Options and Accessories
All options and accessories are factory installed unless otherwise noted.
ELECTRICAL OPTIONS:
Compressor Power Connections – Single-point terminal block connection(s) are provided as standard. The following power connections are available as options. (See electrical data for specific voltage and options availability.)
Single-Point Supply Terminal Block – (standard on YCUL models). Includes enclosure, terminal-block and interconnecting wiring to the compressors. Separate external
protection must be supplied, by others, in the incoming compressor-power wiring. (Do not
include this option if either the Single Point Non Fused Disconnect Switch or Single-Point
Circuit Breaker options have been included.)
Single-Point Non-Fused Disconnect Switch – Unit-mounted disconnect switch with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to
isolate the unit power voltage for servicing. Separate external fusing must be supplied,
by others in the power wiring, which must comply with the National Electrical Code and/
or local codes.
Single-Point Circuit Breaker – A unit mounted circuit breaker with external, lockable
handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power
voltage for servicing. (This option includes the Single-Point Power connection.)
Control Transformer – Converts unit power voltage to 115-1-60 or 115-1-50 for 50Hz
units (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wiring
between the transformer and the control panel.
Power Factor Correction Capacitors – Will correct unit compressor power factors to a
0.90-0.95.
CONTROL OPTIONS:
Ambient Kit (Low) – Units will operate to 25°F (-4°C). This accessory includes all necessary components to permit chiller operation to 0°F (-18°C). (This option includes the
Discharge Pressure Transducer / Readout Capability option.) For proper head pressure
control in applications below 25°F (-4°C), where wind gusts may exceed five mph, it is
recommended that Optional Condenser Louvered Enclosure Panels also be included.
Ambient Kit (High) – Required if units are to operate when the ambient temperature is
above 110°F (43°C). Includes discharge pressure transducers. (This option includes the
Discharge Pressure Transducer/Readout Capability option.)
Building Automation System Interface – The factory addition of a Printed Circuit Board
to accept a 4-20 milliamp, 0-10VDC or contact closure input to reset the leaving chiller liquid temperature from a Building Automation System. (Only one of following options can be
offered on a unit at a time: BAS, Remote Control Panel or Multi-unit Sequence Control.)
(The standard unit capabilities include remote start/stop, remote water temperature reset
via a PWM input signal or up to two steps of demand (load) limiting depending on model.
The standard control panel can be directly connected to a Johnson Controls Building Automated System via the standard onboard RS485 communication port.)
JOHNSON CONTROLS
9
FORM 150.63-EG5 (1017)
Options and Accessories (Cont'd)
Language Lcd And Keypad Display – Spanish, French, and German unit LCD controls
and keypad display available. Standard language is English.
Discharge Pressure Transducers And Readout Capability – The addition of pressure
transducers allows models to sense and display discharge pressure. This is recommended for brine chilling applications. (This option is included with either the low or high ambient kits.)
Suction Pressure Transducers – Permits unit to sense and display suction pressure.
This capability is standard on YCUL models.
Motor Current Module – Capable of monitoring compressor motor current. Provides
extra protection against compressor reverse rotation, phase-loss and phase imbalance.
Option consists of one module per electrical system.
Multi-Unit Sequencing – A separate sequencing control center is provided to handle
sequencing control of up to eight chillers in parallel based on mixed liquid temperature
(interconnecting wiring by others). (Only one of following options can be offered on a unit
at a time: BAS, Remote Control Panel or Multi-Unit Sequence Control.)
COMPRESSOR AND PIPING OPTIONS:
Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicago
code requirements.
Service Isolation Valve – Service isolation valves are standard to unit. This includes a
system high pressure relief valve or internal compressor relief mechanism in compliance
with ASHRAE 15.
Hot Gas By-Pass – Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit
and operating conditions) by introducing an artificial load on the cooler. Hot gas by-pass
is installed on only refrigerant system 1 on two-circuited units.
CONDENSER AND CABINET OPTIONS:
Condenser coil protection against corrosive environments is available by choosing any of
the following options. For additional application recommendations, refer to Form 150.12ES1.
Pre-Coated Fin Condenser Coils – The unit's coils are constructed with epoxy coated
aluminum fins. This can provide corrosion resistance comparable to copper-fin coils in
typical seashore locations. Either these or the post-coated coils (below), are recommended for units being installed at the seashore or where salt spray may hit the unit.
Post-Coated Dipped Condenser Coils – The unit's coils are constructed with dippedcured condenser coils. This is the choice for corrosive applications (with the exception of
strong alkalies, oxidizers and wet bromine, chlorine and fluorine in concentrations greater
than 100 ppm).
Copper Fin Condenser Coils – The unit's coils are constructed with copper fins. (This
is not recommended for units in areas where they may be exposed to acid rain.)
10
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Options and Accessories (Cont'd)
Enclosure Panels (Unit) – Tamperproof enclosure panels prevent unauthorized access
to units. Enclosure panels can provide an aesthetically pleasing alternative to expensive
fencing. Additionally, for proper head pressure control, Johnson Controls recommends
the use of :
Louvered Panels (Full Unit) – Louvered panels surround the front, back, and sides
of the unit. They prevent unauthorized access and visually screen unit components.
Unrestricted air flow is permitted through generously sized louvered openings. This
option is applicable for any outdoor design ambient temperature up to 115°F (46°C).
Sound Attenuation – One or both of the following sound attenuation options are recommended for residential or other similar sound-sensitive locations. Louvered Panels can
be ordered for winter applications where wind gusts may exceed five miles per hour. The
following types of enclosure options are available:
Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by
an acoustic sound blanket. The sound blankets are made with one layer of acoustical
absorbent textile fiber of 5/8” (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8” (3mm). Both are closed by two sheets of welded PVC, reinforced for
temperature and UV resistance.
Ultra Quiet Fans – Lower RPM, 8-pole fan motors are used with steeper-pitch fans.
Vibration Isolators – Level adjusting, spring type 1” (25.4mm) or seismic deflection or
neoprene pad isolators for mounting under unit base rails. (Field-Mounted.)
JOHNSON CONTROLS
11
FORM 150.63-EG5 (1017)
Selection Data
The ratings shown on pages 14 through 25 are based on unit operation in a well designed
and properly piped system.
SELECTION RULES
The following selection rules apply to YCUL chiller selection.
1. Capabilities are based on Refrigerant R-410A.
2. Ratings may interpolated, but must not be extrapolated.
3. Ratings shown are at saturated suction temperatures corresponding to pressures
at the compressor. In actual practice, suction line pressure drop has the effect of
reducing compressor capacity, forcing the compressor to operate at a lower suction
pressure to maintain the desired evaporator temperature.
For normal air conditioning applications, size the suction line for a pressure drop of 3
PSI (0.2 bar), corresponding to 2°F (1.1°C), for R-410A refrigerant. Thus, the evaporator
temperature will be approximately 2°F (1.1°C) higher than the compressor suction temperature. Line loss must be taken into consideration when selecting the evaporator.
SELECTION PROCEDURE
The air-cooled condensing unit may be selected from the Ratings on pages 14 through
25, if the ambient air temperature at the condenser and the saturated suction temperature
at the compressor are known. The ambient air temperature is a known design parameter,
but the suction temperature at the compressor, in many cases, is known only within certain allowable limits. The actual compressor operating suction temperature and the overall
performance of the system will depend directly upon the choice of the evaporator. Starting
with a preliminary evaporator selection at a nominal evaporator temperature and using
data supplied by the evaporator manufacturer, enter the ratings tables and select a unit
to meet the required cooling load at a suction temperature at least 2°F (1.1°C) below the
evaporator temperature. The 2°F (1.1°C) allows for normal suction line loss.
If more accurate selection is required, the evaporator capacity should be plotted against
the condensing unit capacity to determine the balanced system performance. Again, it is
necessary to factor in the suction line loss.
After the system balance point has been determined, the compressor KW input may be
interpolated from the ratings tables.
SAMPLE SELECTION
Select an R-410A Air-Cooled Condensing Unit with a matched central station air handling
unit having the following operating conditions:
Design Conditions
1. An air handling unit with two large DX coils (one per circuit) having a total cooling
load of 600 MBH (50 tons).
12
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Selection Data (Cont'd)
2. The coil suction temperature required 45°F.
3. The design outdoor ambient temperature is 95°F.
4. The power supply is 460V/3∅/60 hz.
Selection
1. Enter the YCUL0055EE Rating Table (page 12).
2. The model YCUL0055EE will provide 51.6 tons with 48.9 compressor KW input at
95°F ambient air and 45°F suction pressure.
3. Calculate the compressor Kw input for the specific design conditions of 50 tons and
95°F ambient air.
4. KW
=
50
51.6
X 48.9 KW = 47.4 KW
The YCUL0055EE is the suitable selection for the design capacity.
REFRIGERANT PIPING
General – When the unit has been located in its final position, the unit piping may be
connected. Normal installation precautions should be observed in order to receive maximum operating efficiencies. System piping should conform to the York DX piping guide
form 050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and
installation is the responsibility of the user.
JOHNSON CONTROLS ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM
OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN.
Filter driers and sight glasses are shipped loose for field installation on each refrigerant
circuit. Field refrigerant piping can be connected to the condensing unit.
All expansion valves, liquid line solenoid valves, refrigerant and refrigerant piping are
supplied and installed by others.
Table 4 - REFRIGERANT LINE CONNECTIONS on page 16 lists refrigerant line connections sizes per unit model number.
JOHNSON CONTROLS
13
FORM 150.63-EG5 (1017)
Selection Data (Cont'd)
REFRIGERANT LINE SIZING
Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops, prevent compressor oil from being “trapped” in the refrigerant piping,
and ensure proper flow of liquid refrigerant to the thermal expansion valve. Considerations should be given to:
1. Suction line pressure drop due to refrigerant flow.
2. Suction line refrigerant velocity for oil return.
3. Liquid line pressure drop due to refrigerant flow.
4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line.
Table 2 - MISCELLANEOUS LIQUID LINE PRESSURE DROPS on page 15 provides
the pressure drops for given pipe sizes for both liquid and suction lines. The pressure
drops given are per 100 equivalent ft. (30.5 m) of refrigerant piping. These friction losses
do not include any allowances for strainer, filter drier, solenoid valve, isolation valve or
fittings
Nominal pressure drop for solenoids, sight glass, and driers are shown in Table 2 - MISCELLANEOUS LIQUID LINE PRESSURE DROPS on page 15,
Table 1 - FITTING EQUIVALENT LENGTHS* on page 15 includes approximate equivalent lengths for copper fittings.
To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line
pressure drop should never exceed 50 psi (3.4 bar). Refrigerant vapor in the liquid line
will measurably reduce valve capacity and poor system performance can be expected.
To allow adequate oil return to the compressor, suction risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure
oil return up the suction riser.
Evaporator Below Condensing Unit - On a system where the evaporator is located below the condensing unit, the suction line must be sized for both pressure drop and oil return. In some cases a double suction riser must be installed to ensure reliable oil return at
reduced loads. Table 3 - REFRIGERATION PIPING CHARGES on page 15 indicates
when a double suction riser should be used for listed pipe sizes to provide adequate oil
return at reduced loads. The calculated information was based on maintaining a minimum
of 1000 fpm (5.08 m/s) refrigerant vapor velocity.
Condenser Below Evaporator - When the condensing unit is located below the evaporator, the liquid line must be designed for both friction loss and static head loss due the
vertical rise. The value of static head loss of 5 PSI/ft (3.4 kPa/30 cm) must be added to
the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc.
OIL TRAPS
All horizontal suction lines should be pitched at least 1/4" per foot (2 cm/m) in the direction
of the refrigerant flow to aid in the return of oil to the compressor. All suction lines with a
vertical rise exceeding 3 feet (.91 meters) should have a “P” trap at the bottom and top
of the riser. Suction lines with a vertical rise exceeding 25 feet (7.6 meters) should be
trapped every 15 feet (4.6 meters).
14
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Selection Data (Cont'd)
REFRIGERANT CHARGE
The condensing unit is charged with a dry nitrogen holding charge. The remaining operating charge for the condensing unit, evaporator coil, and refrigerant piping must be weighed
in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of
refrigerant charge should be verified by subcooling values (refer to section on Pre-Startup
for checking subcooling).
REFRIGERANT PIPING REFERENCE
For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2.
Table 1 - FITTING EQUIVALENT LENGTHS*
PIPE DIAMETER
3/4” (19mm)
7/8” (22mm)
1-1/8” (29mm)
1-3/8” (35mm)
1-5/8” (41mm)
2-1/8” (54mm)
2-5/8” (67mm)
SHORT RADIUS ELL
6.5ft. (2m)
7.8 ft. (2.4m)
2.7ft. (.8m)
3.2 ft. (1m)
3.8 ft. (1.2m)
5.2 ft. (1.6m)
6.5 ft (20m)
LONG RADIUS ELL
4.5 ft.(1.4m)
5.3 ft (1.6m)
1.9 ft. (.6m)
2.2 ft. (.7m)
2.6 ft. (.8m)
3.4 ft. (1m)
4.2 ft. (1.3m)
*Copper Fitting Equivalent Lengths
Table 2 - MISCELLANEOUS LIQUID LINE PRESSURE DROPS
SOLENOID VALVE
FILTER/DRIER
SIGHT GLASS
2-3 PSI (13.8 - 20.7kPa)
2-3 PSI (13.8 - 20.7kPa)
0.5PSI (3.4 kPa)
Table 3 - REFRIGERATION PIPING CHARGES
JOHNSON CONTROLS
SIZE
ID
1-3/8
1-5/8
2-1/8
2-5/8
1.3
1.5
2.0
2.5
3/4
7/8
1-1/8
1-3/8
0.7
0.8
1.0
1.3
R-410A SUCT @ 36 DEG LIQ @ 105 DEG
SUCTION LINES
DENSITY LB/
CU FT
OZ./FT.
CU FT
0.0
2.1
0.3
0.0
2.1
0.4
0.0
2.1
0.7
0.0
2.1
1.1
LIQUID LINES
0.0
60.9
2.4
0.0
60.9
3.3
0.0
60.9
5.6
0.0
60.9
8.5
GRAMS/30 CM
8.1
11.5
20.0
30.9
66.8
92.8
158.3
241.1
15
FORM 150.63-EG5 (1017)
Selection Data (Cont'd)
Table 4 - REFRIGERANT LINE CONNECTIONS
YCUL
TONS
0020EE
0024EE
0031EE
0035EE
17.0
20.1
27.0
30.9
0045EE
41.6
0051EE
44.1
0055EE
51.6
0065EE
59.5
0072EE
73.5
SYSTEM
NUMBER
1
1
1
1
1
2
1
2
1
2
1
2
1
2
COPPER TYPE L
INCHES OD
SUCTION
LIQUID
1-5/8
1-5/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-1/8
2-3/8
2-1/8
7/8
7/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
NOMINAL TONS
UNLOADED
8.5
10.1
12.3
15.5
10.4
10.4
11.7
10.4
12.9
12.9
14.9
14.9
21.9
14.9
Refrigerant Piping Notes
1. Based on R-410A at the nominal capacity of the unit or system, an ambient temperature of 95°F (35°C) and a suction temperature of 45°F
(7.2°C).
2. Suction line sizes were calculated based on a nominal maximum pressure drop to 3 PSI/100 ft. (20.7 kPa/30.5 m). When calculating suction line pressure drop for a specific application, it should be noted that system capacity decreases as suction line pressure drop increases.
3. Nominal Tons (KW) Unloaded is based on one compressor (per system) operating at design conditions.
4. Based on minimum compressor staging for the given pipe size, a double suction riser should be used to ensure proper oil return to the
compressor on all vertical suction risers. Oil returning up the riser moves up the inner surface of the pipe and depends on the mass velocity
of the refrigerant vapor at the wall surface to move the oil up the vertical rise.
5. Hot gas bypass lines are typically 7/8” for lines up to 40 feet and 1-1/8” for lines over 40 feet in length (12 meters). The field connections
sizes are 7/8” for the optional factory mounted hot gas bypass valve. Note: Hot gas bypass is only available for refrigerant system number
1.
6. For more information, please refer to either the York DX Piping Guide (Form 050.40-ES2) or the ASHRAE Refrigertion Handbook.
16
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
THIS PAGE INTENTIONALLY LEFT BLANK.
JOHNSON CONTROLS
17
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units)
MODEL: YCUL0020EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
16.2
16.8
17.4
18.0
18.6
19.2
19.9
20.5
21.2
21.9
22.6
75.0
KW
13.6
13.7
13.9
14.0
14.2
14.3
14.5
14.7
14.8
15.0
15.2
EER
13.3
13.7
14.0
14.4
14.7
15.1
15.4
15.7
16.1
16.4
16.7
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
15.8
14.4
12.3
15.3
15.3
11.2
14.8
16.3
14.6
12.6
15.8
15.4
11.5
15.3
16.9
14.7
12.9
16.4
15.6
11.9
15.9
17.5
14.8
13.2
16.9
15.7
12.2
16.4
18.1
15.0
13.6
17.5
15.9
12.5
17.0
18.7
15.1
13.9
18.1
16.0
12.8
17.6
19.3
15.3
14.2
18.7
16.2
13.1
18.1
19.9
15.5
14.5
19.3
16.4
13.4
18.7
20.6
15.7
14.8
20.0
16.5
13.7
19.4
21.3
15.8
15.1
20.6
16.7
14.0
20.0
21.9
16.0
15.4
21.3
16.9
14.2
20.6
90.0
KW
16.3
16.4
16.5
16.7
16.8
17.0
17.1
17.3
17.5
17.7
17.9
EER
10.3
10.6
10.9
11.1
11.4
11.7
12.0
12.3
12.6
12.8
13.1
TONS
14.3
14.8
15.3
15.9
16.4
17.0
17.5
18.1
18.7
19.3
19.9
95.0
KW
17.3
17.4
17.5
17.7
17.8
18.0
18.1
18.3
18.5
18.7
18.9
EER
9.4
9.6
9.9
10.2
10.5
10.7
11.0
11.3
11.5
11.8
12.0
EER
13.4
13.7
14.0
14.4
14.7
15.0
15.3
15.6
16.0
16.3
16.6
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
18.9
17.4
12.3
18.2
18.5
11.2
17.6
19.5
17.6
12.6
18.9
18.7
11.5
18.2
20.2
17.8
12.9
19.5
18.8
11.8
18.8
20.9
18.0
13.2
20.2
19.0
12.1
19.5
21.6
18.2
13.5
20.9
19.2
12.4
20.2
22.3
18.4
13.8
21.6
19.4
12.7
20.8
23.0
18.6
14.1
22.3
19.6
13.0
21.5
23.8
18.8
14.4
23.0
19.9
13.2
22.2
24.5
19.0
14.7
23.7
20.1
13.5
22.9
25.3
19.2
15.0
24.5
20.3
13.8
23.7
26.0
19.4
15.3
25.2
20.5
14.0
24.4
90.0
KW
19.6
19.8
20.0
20.2
20.4
20.6
20.8
21.0
21.3
21.5
21.7
EER
10.2
10.5
10.8
11.1
11.3
11.6
11.9
12.1
12.4
12.6
12.9
TONS
16.9
17.5
18.1
18.8
19.4
20.1
20.7
21.4
22.1
22.8
23.5
95.0
KW
20.8
21.0
21.2
21.4
21.6
21.8
22.0
22.3
22.5
22.7
23.0
EER
9.3
9.5
9.8
10.0
10.3
10.6
10.8
11.1
11.3
11.5
11.8
EER
12.6
12.9
13.2
13.6
13.9
14.2
14.5
14.9
15.2
15.5
15.8
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
24.9
22.6
11.7
24.2
23.8
10.9
23.5
25.8
22.8
12.0
25.1
24.0
11.2
24.3
26.8
23.0
12.3
26.0
24.2
11.5
25.2
27.7
23.3
12.6
26.9
24.5
11.8
26.1
28.7
23.5
13.0
27.8
24.7
12.1
27.0
29.6
23.8
13.3
28.8
25.0
12.4
27.9
30.6
24.1
13.6
29.8
25.2
12.7
28.9
31.7
24.4
13.9
30.8
25.5
12.9
29.8
32.7
24.7
14.2
31.8
25.8
13.2
30.8
33.8
25.0
14.5
32.8
26.1
13.5
31.8
34.8
25.3
14.8
33.9
26.5
13.8
32.8
90.0
KW
25.1
25.3
25.5
25.7
26.0
26.2
26.5
26.8
27.1
27.4
27.7
EER
10.0
10.3
10.6
10.9
11.2
11.5
11.7
12.0
12.3
12.6
12.8
TONS
22.7
23.6
24.4
25.3
26.1
27.0
27.9
28.9
29.8
30.8
31.8
95.0
KW
26.4
26.6
26.9
27.1
27.3
27.6
27.8
28.1
28.4
28.7
29.0
EER
9.3
9.5
9.8
10.1
10.3
10.6
10.9
11.1
11.4
11.7
11.9
MODEL: YCUL0024EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
19.5
20.2
20.9
21.6
22.3
23.0
23.7
24.5
25.2
26.0
26.8
75.0
KW
16.5
16.7
16.8
17.0
17.2
17.4
17.6
17.8
18.0
18.2
18.4
MODEL: YCUL0031EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
18
TONS
25.6
26.6
27.5
28.5
29.5
30.5
31.5
32.5
33.6
34.7
35.8
75.0
KW
21.5
21.7
21.9
22.2
22.4
22.7
23.0
23.3
23.6
23.9
24.2
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units) (Cont'd)
MODEL: YCUL0020EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
13.8
14.3
14.8
15.3
15.8
16.4
16.9
17.5
18.1
18.6
19.2
100.0
KW
18.4
18.5
18.6
18.8
18.9
19.1
19.2
19.4
19.6
19.7
19.9
EER
8.5
8.8
9.0
9.3
9.5
9.8
10.0
10.3
10.5
10.8
11.0
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
13.2
19.5
7.7
12.7
20.8
13.7
19.7
8.0
13.1
20.9
14.2
19.8
8.2
13.6
21.0
14.7
19.9
8.4
14.1
21.2
15.2
20.1
8.7
14.6
21.3
15.7
20.2
8.9
15.1
21.4
16.3
20.4
9.1
15.6
21.6
16.8
20.5
9.4
16.2
21.7
17.4
20.7
9.6
16.7
21.9
18.0
20.9
9.9
17.3
22.1
18.5
21.0
10.1
17.8
22.2
EER
7.0
7.2
7.4
7.6
7.9
8.1
8.3
8.5
8.8
9.0
9.2
TONS
12.1
12.5
13.0
13.5
7.5
7.8
8.1
8.4
8.7
9.0
9.3
115.0
KW
22.1
22.2
22.4
22.5
9.7
9.7
9.8
9.8
9.8
9.9
9.9
EER
6.3
6.5
6.7
6.9
8.5
8.7
9.0
9.3
9.6
9.9
10.2
EER
8.4
8.6
8.9
9.1
9.3
9.6
9.8
10.1
10.3
10.5
10.7
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
15.4
23.6
7.5
14.7
25.1
16.0
23.8
7.8
15.3
25.3
16.6
23.9
8.0
15.8
25.4
17.2
24.1
8.2
16.4
25.6
17.8
24.3
8.4
17.0
25.8
18.5
24.5
8.7
17.6
26.0
19.1
24.7
8.9
18.2
26.2
19.7
25.0
9.1
18.9
26.4
20.4
25.2
9.3
10.8
11.1
21.0
25.4
9.6
11.2
11.2
21.7
25.7
9.8
11.5
11.2
EER
6.8
7.0
7.2
7.4
7.6
7.8
8.0
8.2
10.7
11.0
11.3
TONS
14.0
8.0
8.3
8.6
8.9
9.3
9.6
10.0
10.3
10.7
11.1
115.0
KW
26.7
11.4
11.4
11.5
11.5
11.6
11.7
11.7
11.8
11.9
11.9
EER
6.0
7.7
8.0
8.3
8.6
8.8
9.1
9.4
9.7
10.0
10.3
EER
8.5
8.8
9.0
9.3
9.5
9.8
10.0
10.3
10.5
10.8
11.0
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
21.1
29.5
7.8
20.3
31.1
21.9
29.7
8.0
21.0
31.3
22.7
29.9
8.3
21.8
31.5
23.5
30.1
8.5
22.6
31.8
24.3
30.3
8.8
23.4
32.0
25.2
30.6
9.0
24.2
32.2
26.0
30.8
9.2
25.0
32.5
26.9
31.1
9.5
25.8
32.8
27.8
31.4
9.7
26.7
33.0
28.7
31.7
9.9
27.6
33.3
29.6
32.0
10.2
28.5
33.6
EER
7.1
7.4
7.6
7.8
8.0
8.2
8.5
8.7
8.9
9.1
9.3
TONS
19.4
20.1
20.9
21.6
22.4
23.2
24.0
24.8
25.6
26.4
27.3
115.0
KW
32.9
33.1
33.3
33.5
33.8
34.0
34.3
34.5
34.8
35.1
35.4
EER
6.5
6.7
6.9
7.1
7.3
7.5
7.7
7.9
8.1
8.3
8.5
MODEL: YCUL0024EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
16.2
16.8
17.4
18.0
18.6
19.3
19.9
20.6
21.3
21.9
22.6
100.0
KW
22.2
22.4
22.5
22.7
22.9
23.1
23.4
23.6
23.8
24.1
24.3
MODEL: YCUL0031EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
21.9
22.7
23.6
24.4
25.2
26.1
27.0
27.9
28.8
29.8
30.7
100.0
KW
27.9
28.1
28.3
28.5
28.8
29.0
29.3
29.6
29.9
30.2
30.5
JOHNSON CONTROLS
19
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units) (Cont'd)
MODEL: YCUL0035EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
29.4
30.4
31.5
32.6
33.8
34.9
36.1
37.3
38.5
39.8
41.1
75.0
KW
24.9
25.1
25.4
25.7
26.0
26.4
26.7
27.1
27.5
27.9
28.4
EER
12.6
13.0
13.3
13.6
14.0
14.3
14.6
14.9
15.2
15.4
15.7
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
28.6
26.2
11.7
27.7
27.7
10.8
26.9
29.6
26.5
12.1
28.7
27.9
11.1
27.8
30.6
26.7
12.4
29.7
28.2
11.4
28.8
31.7
27.0
12.7
30.8
28.4
11.8
29.9
32.8
27.3
13.0
31.9
28.7
12.1
30.9
34.0
27.6
13.3
33.0
29.0
12.3
32.0
35.1
28.0
13.6
34.1
29.4
12.6
33.1
36.3
28.3
13.9
35.2
29.7
12.9
34.2
37.5
28.7
14.2
36.4
30.1
13.2
35.3
38.7
29.1
14.5
37.6
30.5
13.5
36.5
40.0
29.5
14.7
38.8
30.9
13.8
37.6
90.0
KW
29.3
29.5
29.8
30.0
30.3
30.6
30.9
31.3
31.6
32.0
32.4
EER
10.0
10.3
10.6
10.8
11.1
11.4
11.7
12.0
12.2
12.5
12.8
TONS
26.0
26.9
27.9
28.9
29.9
30.9
32.0
33.1
34.2
35.3
36.5
95.0
KW
31.0
31.3
31.5
31.8
32.0
32.3
32.6
33.0
33.3
33.7
34.0
EER
9.2
9.4
9.7
10.0
10.2
10.5
10.8
11.0
11.3
11.6
11.8
EER
13.0
13.4
13.8
14.1
14.5
14.9
15.3
15.8
16.2
16.6
17.0
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
38.3
32.4
12.1
37.1
34.2
11.2
35.9
39.7
32.6
12.5
38.5
34.4
11.6
37.3
41.1
32.8
12.8
39.9
34.6
11.9
38.7
42.5
33.0
13.2
41.3
34.8
12.3
40.1
44.0
33.2
13.6
42.8
35.0
12.6
41.5
45.5
33.4
14.0
44.2
35.3
13.0
42.9
47.0
33.7
14.4
45.7
35.5
13.4
44.4
48.5
33.9
14.7
47.3
35.8
13.7
45.9
50.1
34.1
15.1
48.8
36.0
14.1
47.5
51.7
34.4
15.5
50.4
36.3
14.4
49.0
53.3
34.6
15.9
52.0
36.5
14.8
50.6
90.0
KW
36.2
36.4
36.6
36.8
37.1
37.3
37.6
37.8
38.1
38.3
38.6
EER
10.3
10.7
11.0
11.3
11.7
12.0
12.4
12.7
13.0
13.4
13.7
TONS
34.7
36.0
37.3
38.7
40.1
41.6
43.0
44.5
46.0
47.5
49.1
95.0
KW
38.4
38.6
38.8
39.1
39.3
39.5
39.8
40.0
40.3
40.6
40.9
EER
9.4
9.8
10.1
10.4
10.7
11.1
11.4
11.7
12.0
12.3
12.7
EER
12.8
13.2
13.6
13.9
14.3
14.7
15.1
15.5
15.8
16.2
16.6
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
40.8
35.5
11.9
39.5
37.5
11.0
38.2
42.2
35.8
12.2
41.0
37.8
11.3
39.6
43.7
36.0
12.6
42.4
38.0
11.7
41.1
45.3
36.3
13.0
43.9
38.3
12.0
42.6
46.8
36.6
13.3
45.5
38.6
12.4
44.1
48.4
36.9
13.7
47.1
38.9
12.7
45.6
50.1
37.2
14.0
48.7
39.2
13.0
47.2
51.7
37.5
14.4
50.3
39.5
13.4
48.8
53.4
37.8
14.8
51.9
39.8
13.7
50.4
55.2
38.1
15.1
53.6
40.2
14.1
52.0
56.9
38.4
15.5
55.4
40.5
14.4
53.7
90.0
KW
39.7
39.9
40.2
40.5
40.8
41.1
41.4
41.7
42.0
42.4
42.7
EER
10.1
10.4
10.8
11.1
11.4
11.7
12.1
12.4
12.7
13.0
13.3
TONS
36.9
38.3
39.7
41.1
42.6
44.1
45.6
47.2
48.8
50.4
52.1
95.0
KW
42.1
42.3
42.6
42.9
43.1
43.4
43.7
44.1
44.4
44.7
45.1
EER
9.3
9.6
9.9
10.2
10.5
10.8
11.1
11.4
11.7
12.0
12.3
MODEL: YCUL0045EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
39.4
40.8
42.2
43.6
45.1
46.6
48.1
49.7
51.2
52.9
54.5
75.0
KW
30.8
31.0
31.2
31.4
31.6
31.8
32.0
32.2
32.4
32.7
32.9
MODEL: YCUL0051EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
20
TONS
42.0
43.5
45.0
46.6
48.2
49.8
51.4
53.1
54.9
56.6
58.4
75.0
KW
33.7
34.0
34.2
34.5
34.8
35.0
35.3
35.6
35.9
36.2
36.6
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units) (Cont'd)
MODEL: YCUL0035EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
25.1
26.0
26.9
27.9
28.9
29.9
30.9
32.0
33.0
34.1
35.2
100.0
KW
32.9
33.1
33.4
33.6
33.9
34.2
34.5
34.8
35.1
35.5
35.9
EER
8.4
8.6
8.9
9.1
9.4
9.6
9.9
10.1
10.4
10.6
10.9
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
24.2
34.9
7.6
23.2
37.0
25.0
35.1
7.9
24.1
37.3
26.0
35.4
8.1
25.0
37.5
26.9
35.6
8.4
25.9
37.8
27.8
35.9
8.6
26.8
38.1
28.8
36.2
8.8
27.7
38.3
29.8
36.5
9.1
28.7
38.6
30.8
36.8
9.3
29.7
38.9
31.9
37.1
9.5
30.7
39.3
32.9
37.5
9.8
31.7
39.6
34.0
37.8
10.0
32.7
40.0
EER
7.0
7.2
7.4
7.6
7.8
8.0
8.3
8.5
8.7
8.9
9.1
TONS
22.3
23.1
23.9
13.1
13.6
14.1
14.6
15.2
15.7
16.3
16.8
115.0
KW
39.3
39.5
39.8
17.6
17.6
17.7
17.8
17.9
18.0
18.1
18.2
EER
6.3
6.5
6.7
7.6
7.9
8.2
8.4
8.7
9.0
9.3
9.5
EER
8.6
8.9
9.2
9.5
9.8
10.1
10.4
10.7
11.0
11.3
11.6
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
31.9
43.6
7.8
30.5
46.5
33.2
43.7
8.1
31.8
46.6
34.5
43.9
8.4
33.0
46.8
35.8
44.1
8.6
34.3
47.0
37.2
44.4
8.9
35.6
47.2
38.6
44.6
9.2
37.0
47.4
40.0
44.8
9.5
38.4
47.7
41.4
45.1
9.8
39.7
47.9
42.8
45.4
10.1
41.2
48.2
44.3
45.7
10.4
42.6
48.5
45.8
46.0
10.7
44.1
48.8
EER
7.0
7.3
7.6
7.8
8.1
8.4
8.6
8.9
9.2
9.5
9.7
TONS
29.1
30.3
31.5
32.8
34.0
35.3
36.7
38.0
39.4
40.8
42.2
115.0
KW
49.6
49.7
49.9
50.1
50.2
50.5
50.7
50.9
51.2
51.5
51.8
EER
6.3
6.6
6.8
7.1
7.3
7.6
7.8
8.1
8.3
8.6
8.8
EER
8.5
8.8
9.0
9.3
9.6
9.9
10.2
10.5
10.8
11.0
11.3
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
34.0
47.5
7.7
32.6
50.5
35.4
47.7
8.0
33.9
50.7
36.7
47.9
8.2
35.2
50.9
38.1
48.2
8.5
36.5
51.1
39.5
48.5
8.8
37.9
51.4
40.9
48.7
9.0
39.3
51.7
42.4
49.1
9.3
40.7
52.0
43.9
49.4
9.6
42.2
52.3
45.4
49.7
9.9
43.6
52.6
46.9
50.0
10.1
45.1
53.0
48.5
50.4
10.4
46.7
53.3
EER
7.0
7.2
7.5
7.7
8.0
8.2
8.5
8.7
9.0
9.2
9.5
TONS
31.0
32.3
33.6
34.9
36.2
37.6
39.0
40.4
41.8
43.3
44.7
115.0
KW
53.7
53.9
54.1
54.3
54.6
54.8
55.1
55.4
55.8
56.1
56.4
EER
6.3
6.5
6.7
7.0
7.2
7.5
7.7
7.9
8.2
8.4
8.7
MODEL: YCUL0045EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
33.3
34.6
36.0
37.3
38.7
40.1
41.5
43.0
44.5
46.0
47.5
100.0
KW
40.9
41.1
41.3
41.5
41.7
42.0
42.2
42.5
42.8
43.1
43.4
MODEL: YCUL0051EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
35.5
36.8
38.2
39.6
41.1
42.5
44.0
45.6
47.1
48.7
50.3
100.0
KW
44.7
44.9
45.2
45.4
45.7
46.0
46.3
46.6
47.0
47.3
47.7
JOHNSON CONTROLS
21
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units) (Cont'd)
MODEL: YCUL0055EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
48.8
50.6
52.5
54.4
56.3
58.3
60.3
62.4
64.5
66.7
68.9
75.0
KW
38.1
38.4
38.8
39.2
39.6
40.0
40.5
41.0
41.4
41.9
42.5
EER
13.1
13.4
13.8
14.2
14.6
15.0
15.3
15.7
16.1
16.5
16.8
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
47.5
40.1
12.2
46.1
42.3
11.3
44.7
49.2
40.5
12.5
47.8
42.6
11.6
46.3
51.0
40.8
12.9
49.5
43.0
12.0
48.0
52.8
41.2
13.2
51.3
43.4
12.3
49.7
54.7
41.6
13.6
53.1
43.8
12.6
51.5
56.6
42.0
13.9
55.0
44.2
13.0
53.3
58.6
42.5
14.3
56.9
44.6
13.3
55.1
60.6
42.9
14.7
58.8
45.0
13.6
57.0
62.7
43.4
15.0
60.8
45.5
14.0
59.0
64.8
43.9
15.4
62.9
46.0
14.3
60.9
67.0
44.4
15.7
65.0
46.5
14.7
63.0
90.0
KW
44.6
44.9
45.3
45.7
46.1
46.5
46.9
47.3
47.8
48.3
48.8
EER
10.5
10.8
11.1
11.4
11.7
12.0
12.3
12.7
13.0
13.3
13.6
TONS
43.3
44.9
46.5
48.2
49.9
51.6
53.4
55.2
57.1
59.0
60.9
95.0
KW
47.1
47.4
47.8
48.1
48.5
48.9
49.3
49.8
50.2
50.7
51.2
EER
9.7
9.9
10.2
10.5
10.8
11.1
11.4
11.7
12.0
12.3
12.6
EER
12.8
13.1
13.4
13.7
14.1
14.4
14.7
15.0
15.2
15.5
15.8
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
55.0
48.7
11.9
53.4
51.2
11.1
51.8
57.0
49.2
12.2
55.4
51.6
11.4
53.7
59.0
49.7
12.5
57.3
52.2
11.7
55.6
61.0
50.2
12.9
59.3
52.7
12.0
57.5
63.1
50.8
13.2
61.3
53.3
12.3
59.5
65.2
51.4
13.5
63.4
53.9
12.5
61.5
67.3
52.1
13.7
65.5
54.5
12.8
63.5
69.5
52.8
14.0
67.6
55.2
13.1
65.6
71.7
53.5
14.3
69.7
55.9
13.4
67.7
74.0
54.2
14.6
71.9
56.6
13.6
69.8
76.3
55.0
14.8
74.2
57.4
13.9
72.0
90.0
KW
53.8
54.3
54.8
55.4
55.9
56.5
57.2
57.8
58.5
59.2
60.0
EER
10.3
10.6
10.8
11.1
11.4
11.7
11.9
12.2
12.4
12.7
12.9
TONS
50.1
51.9
53.7
55.6
57.5
59.5
61.5
63.5
65.5
67.6
69.7
95.0
KW
56.7
57.2
57.7
58.2
58.8
59.4
60.0
60.7
61.3
62.1
62.8
EER
9.5
9.7
10.0
10.3
10.5
10.8
11.1
11.3
11.6
11.8
12.0
EER
12.9
13.2
13.6
13.9
14.2
14.5
14.9
15.2
15.5
15.8
16.1
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
67.9
61.1
12.0
65.8
64.2
11.1
63.7
70.4
61.8
12.3
68.2
64.9
11.4
66.1
72.9
62.5
12.6
70.7
65.6
11.7
68.5
75.5
63.2
12.9
73.2
66.4
12.0
70.9
78.1
64.0
13.3
75.8
67.1
12.3
73.4
80.8
64.8
13.6
78.4
67.9
12.6
75.9
83.5
65.6
13.9
81.0
68.8
12.9
78.5
86.3
66.4
14.2
83.8
69.6
13.2
81.2
89.2
67.3
14.5
86.5
70.5
13.4
83.9
92.1
68.2
14.7
89.4
71.4
13.7
86.6
95.1
69.2
15.0
92.2
72.4
14.0
89.4
90.0
KW
67.7
68.3
69.0
69.8
70.6
71.4
72.2
73.1
73.9
74.9
75.8
EER
10.3
10.6
10.8
11.1
11.4
11.7
11.9
12.2
12.5
12.7
13.0
TONS
61.6
63.9
66.2
68.6
71.0
73.5
76.0
78.6
81.2
83.9
86.6
95.0
KW
71.4
72.1
72.8
73.5
74.3
75.1
75.9
76.8
77.7
78.6
79.6
EER
9.5
9.7
10.0
10.3
10.5
10.8
11.0
11.3
11.5
11.8
12.0
MODEL: YCUL0065EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
56.5
58.5
60.6
62.7
64.8
66.9
69.1
71.4
73.6
75.9
78.3
75.0
KW
46.4
46.9
47.4
48.0
48.6
49.2
49.8
50.5
51.2
52.0
52.8
MODEL: YCUL0072EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
22
TONS
69.9
72.5
75.1
77.7
80.4
83.2
86.0
88.9
91.8
94.8
97.8
75.0
KW
58.2
58.9
59.6
60.4
61.1
61.9
62.7
63.5
64.4
65.3
66.2
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - English Units) (Cont'd)
MODEL: YCUL0055EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
41.8
43.4
44.9
46.5
48.2
49.9
51.6
53.3
55.1
57.0
58.8
100.0
KW
49.7
50.1
50.4
50.8
51.2
51.6
52.0
52.4
52.9
53.3
53.8
EER
8.9
9.2
9.4
9.7
10.0
10.3
10.5
10.8
11.1
11.4
11.7
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
40.3
52.5
8.2
38.8
55.5
41.8
52.9
8.4
40.2
55.9
43.3
53.2
8.7
41.7
56.2
44.9
53.6
8.9
43.2
56.6
46.5
54.0
9.2
44.7
57.0
48.1
54.4
9.4
46.2
57.4
49.7
54.8
9.7
47.8
57.8
51.4
55.2
10.0
49.5
58.2
53.2
55.6
10.2
51.1
58.6
54.9
56.1
10.5
52.8
59.1
56.7
56.6
10.8
54.6
59.6
EER
7.5
7.7
7.9
8.2
8.4
8.7
8.9
9.1
9.4
9.6
9.9
TONS
37.1
38.5
39.9
41.4
42.8
44.3
45.9
47.4
49.1
50.7
52.4
115.0
KW
58.7
59.0
59.4
59.8
60.1
60.5
60.9
61.4
61.8
62.3
62.7
EER
6.8
7.0
7.2
7.5
7.7
7.9
8.1
8.4
8.6
8.8
9.0
EER
8.7
9.0
9.2
9.5
9.7
10.0
10.2
10.4
10.7
10.9
11.1
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
46.5
63.1
8.0
44.6
66.6
48.2
63.6
8.2
46.2
67.1
49.9
64.1
8.5
47.9
67.6
51.7
64.6
8.7
49.6
68.1
53.5
65.1
8.9
51.4
68.6
55.3
65.7
9.2
53.1
69.2
57.2
66.3
9.4
54.9
69.8
59.1
66.9
9.6
56.8
70.4
61.0
67.6
9.9
58.6
71.1
63.0
68.3
10.1
60.5
71.8
64.9
69.0
10.3
62.5
72.5
EER
7.3
7.5
7.7
8.0
8.2
8.4
8.6
8.8
9.0
9.3
9.5
TONS
42.6
44.2
45.9
47.5
49.2
50.9
52.6
54.4
56.2
58.0
59.9
115.0
KW
70.3
70.8
71.3
71.8
72.3
72.9
73.5
74.1
74.8
75.4
76.2
EER
6.6
6.8
7.1
7.3
7.5
7.7
7.9
8.1
8.3
8.5
8.7
EER
8.7
8.9
9.2
9.4
9.7
9.9
10.2
10.4
10.7
10.9
11.1
AIR TEMPERATURE ON - CONDENSER (°F)
105.0
110.0
TONS
KW
EER
TONS
KW
57.3
79.8
7.9
55.1
84.5
59.4
80.4
8.2
57.2
85.1
61.6
81.1
8.4
59.3
85.8
63.8
81.9
8.6
61.4
86.5
66.1
82.6
8.9
63.6
87.3
68.4
83.4
9.1
65.9
88.1
70.8
84.2
9.3
68.2
88.9
73.2
85.1
9.6
70.5
89.8
75.7
86.0
9.8
72.9
90.7
78.2
86.9
10.0
75.4
91.6
80.8
87.9
10.2
77.9
92.6
EER
7.3
7.5
7.7
7.9
8.1
8.3
8.6
8.8
9.0
9.2
9.4
TONS
52.9
54.9
56.9
59.0
45.4
47.1
48.8
50.5
52.3
38.8
40.2
115.0
KW
89.5
90.2
90.9
91.6
62.0
62.4
62.9
63.4
63.8
41.8
42.1
EER
6.6
6.8
7.0
7.2
7.9
8.2
8.4
8.7
8.9
9.6
9.9
MODEL: YCUL0065EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
48.3
50.1
51.9
53.7
55.6
57.4
59.4
61.3
63.3
65.3
67.4
100.0
KW
59.8
60.3
60.8
61.3
61.8
62.4
63.0
63.7
64.4
65.1
65.8
MODEL: YCUL0072EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
59.5
61.7
63.9
66.2
68.6
71.0
73.4
75.9
78.5
81.1
83.7
100.0
KW
75.4
76.1
76.8
77.5
78.3
79.1
79.9
80.8
81.7
82.6
83.6
JOHNSON CONTROLS
23
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units)
MODEL YCUL0020EE
SST
(°F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
14.8
15.3
15.8
16.1
16.4
16.9
17.4
18.0
18.8
75.0
KW
11.1
11.2
11.3
11.4
11.5
11.6
11.8
12.0
12.2
EER
15.3
15.6
16.0
16.1
16.3
16.6
16.9
17.2
17.6
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
14.4
11.7
14.0
13.9
12.4
12.9
13.5
14.9
11.9
14.4
14.4
12.6
13.2
14.0
15.4
12.0
14.7
14.9
12.7
13.5
14.4
15.6
12.1
14.8
15.1
12.8
13.6
14.7
15.9
12.1
15.0
15.4
12.8
13.8
14.9
16.4
12.3
15.3
15.9
13.0
14.1
15.4
16.9
12.4
15.6
16.4
13.1
14.4
15.9
17.4
12.6
15.9
16.9
13.3
14.6
16.4
18.3
12.9
16.3
17.7
13.6
15.0
17.2
90.0
KW
13.2
13.3
13.4
13.5
13.6
13.7
13.9
14.1
14.3
EER
11.8
12.1
12.4
12.5
12.6
12.9
13.2
13.4
13.8
TONS
13.0
13.5
13.9
14.2
14.4
14.9
15.4
15.8
16.6
95.0
KW
14.0
14.1
14.2
14.3
14.4
14.5
14.7
14.9
15.1
EER
10.7
11.0
11.3
11.4
11.6
11.8
12.1
12.3
12.7
EER
14.8
15.2
15.5
15.7
15.9
16.2
16.5
16.8
17.3
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
17.0
14.5
13.6
16.5
15.4
12.4
15.9
17.6
14.6
13.9
17.0
15.6
12.7
16.4
18.2
14.8
14.2
17.6
15.7
13.0
17.0
18.5
14.9
14.4
17.9
15.8
13.1
17.3
18.8
15.0
14.5
18.2
15.9
13.3
17.6
19.4
15.1
14.8
18.8
16.0
13.6
18.1
20.0
15.3
15.1
19.4
16.2
13.9
18.7
20.6
15.5
15.4
20.0
16.4
14.2
19.3
21.6
15.7
15.9
20.9
16.7
14.6
20.2
90.0
KW
16.4
16.5
16.7
16.8
16.8
17.0
17.2
17.4
17.6
EER
11.2
11.5
11.8
12.0
12.1
12.4
12.7
12.9
13.3
TONS
15.3
15.8
16.4
16.6
16.9
17.5
18.0
18.6
19.5
95.0
KW
17.4
17.6
17.7
17.8
17.9
18.1
18.2
18.4
18.7
EER
10.2
10.4
10.7
10.8
11.0
11.2
11.5
11.8
12.2
EER
14.5
14.8
15.2
15.4
15.6
15.9
16.3
16.7
17.2
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
22.2
18.1
13.4
21.6
19.2
12.4
21.0
23.0
18.3
13.8
22.4
19.3
12.8
21.8
23.8
18.4
14.2
23.2
19.5
13.1
22.5
24.2
18.5
14.3
23.6
19.6
13.3
22.9
24.6
18.6
14.5
24.0
19.6
13.5
23.3
25.4
18.8
14.9
24.8
19.8
13.8
24.1
26.3
19.0
15.2
25.6
20.0
14.1
24.9
27.1
19.2
15.6
26.4
20.2
14.5
25.7
28.5
19.5
16.1
27.7
20.5
15.0
27.0
90.0
KW
20.3
20.5
20.6
20.7
20.8
20.9
21.1
21.3
21.6
EER
11.4
11.8
12.1
12.3
12.4
12.8
13.1
13.4
13.9
TONS
20.4
21.1
21.8
22.2
22.6
23.3
24.1
24.9
26.2
95.0
KW
21.5
21.7
21.8
21.9
22.0
22.1
22.3
22.5
22.8
EER
10.5
10.8
11.1
11.3
11.4
11.7
12.0
12.4
12.8
MODEL YCUL0024EE
SST
(°F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
17.6
18.2
18.8
19.1
19.4
20.0
20.6
21.3
22.3
75.0
KW
13.6
13.8
13.9
14.0
14.1
14.3
14.4
14.6
14.9
MODEL YCUL0031EE
SST
(°F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
24
TONS
22.8
23.6
24.4
24.8
25.2
26.1
26.9
27.8
29.2
75.0
KW
17.2
17.3
17.5
17.6
17.7
17.9
18.1
18.3
18.7
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units) (Cont'd)
MODEL YCUL0020EE
SST
(F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
12.6
13.0
13.4
13.7
13.9
14.4
14.8
15.3
16.0
100.0
KW
14.9
15.0
15.1
15.2
15.3
15.4
15.6
15.7
16.0
EER
9.8
10.0
10.3
10.4
10.5
10.8
11.0
11.3
11.6
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
12.1
15.8
8.8
11.6
16.9
12.5
15.9
9.1
12.0
17.0
12.9
16.1
9.3
12.4
17.1
13.2
16.1
9.4
12.6
17.1
13.4
16.2
9.6
12.8
17.2
13.8
16.3
9.8
13.3
17.4
14.3
16.5
10.0
13.7
17.5
14.7
16.7
10.3
14.2
17.7
15.4
16.9
10.6
14.9
17.9
EER
8.0
8.2
8.4
8.5
8.7
8.9
9.1
9.3
9.6
TONS
11.0
11.5
11.9
12.1
12.3
12.7
7.1
7.3
7.7
115.0
KW
18.0
18.1
18.2
18.2
18.3
18.4
7.9
8.0
8.0
EER
7.1
7.4
7.6
7.7
7.8
8.0
10.0
10.3
10.7
EER
9.2
9.4
9.7
9.8
9.9
10.2
10.4
10.7
11.0
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
14.0
19.8
8.3
13.3
21.0
14.5
19.9
8.5
13.8
21.2
15.0
20.1
8.7
14.3
21.3
15.3
20.1
8.9
14.6
21.4
15.5
20.2
9.0
14.8
21.5
16.1
20.4
9.2
15.3
21.7
16.6
20.5
9.4
15.9
21.8
17.1
20.7
9.7
16.4
22.0
18.0
21.0
10.0
9.5
9.2
EER
7.4
7.6
7.8
8.0
8.1
8.3
8.5
8.7
11.7
TONS
7.0
7.3
7.5
7.7
7.8
8.1
8.4
8.7
9.1
115.0
KW
9.5
9.5
9.5
9.5
9.6
9.6
9.6
9.7
9.7
EER
8.4
8.6
8.9
9.1
9.2
9.5
9.9
10.2
10.6
EER
9.6
9.9
10.2
10.3
10.5
10.8
11.1
11.3
11.8
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
19.0
24.3
8.8
18.3
25.7
19.7
24.4
9.0
18.9
25.9
20.4
24.5
9.3
19.6
26.0
20.7
24.6
9.4
20.0
26.1
21.1
24.7
9.6
20.3
26.2
21.8
24.9
9.8
21.0
26.4
22.6
25.0
10.1
21.7
26.5
23.3
25.2
10.4
22.5
26.7
24.5
25.5
10.8
23.6
27.0
EER
8.0
8.2
8.5
8.6
8.7
9.0
9.2
9.5
9.9
TONS
17.5
18.2
18.8
19.2
19.5
20.2
20.9
21.6
22.7
115.0
KW
27.3
27.5
27.6
27.7
27.8
28.0
28.1
28.3
28.6
EER
7.2
7.5
7.7
7.8
7.9
8.2
8.4
8.6
9.0
MODEL YCUL0024EE
SST
(F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
14.7
15.2
15.7
16.0
16.2
16.8
17.3
17.9
18.8
100.0
KW
18.6
18.7
18.9
18.9
19.0
19.2
19.3
19.5
19.8
MODEL YCUL0031EE
SST
(F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
19.7
20.4
21.1
21.5
21.8
22.6
23.4
24.1
25.3
100.0
KW
22.9
23.0
23.1
23.2
23.3
23.4
23.6
23.8
24.1
JOHNSON CONTROLS
25
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units) (Cont'd)
MODEL YCUL0035EE
SST
(°F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
26.7
27.7
28.6
29.1
29.6
30.5
31.5
32.5
34.1
75.0
KW
20.7
20.9
21.1
21.2
21.3
21.5
21.8
22.0
22.5
EER
14.3
14.7
15.0
15.2
15.4
15.7
16.1
16.4
16.9
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
26.1
21.8
13.3
25.3
23.1
12.2
24.6
26.9
22.0
13.6
26.2
23.3
12.6
25.4
27.9
22.2
14.0
27.1
23.5
12.9
26.3
28.3
22.3
14.1
27.6
23.6
13.1
26.7
28.8
22.4
14.3
28.0
23.7
13.2
27.2
29.7
22.7
14.6
28.9
23.9
13.5
28.1
30.7
22.9
15.0
29.9
24.1
13.9
29.0
31.7
23.2
15.3
30.9
24.4
14.2
30.0
33.2
23.6
15.8
32.3
24.8
14.6
31.4
90.0
KW
24.5
24.7
24.9
25.0
25.1
25.3
25.5
25.7
26.1
EER
11.3
11.6
11.9
12.0
12.2
12.5
12.8
13.1
13.5
TONS
23.8
24.6
25.5
25.9
26.3
27.2
28.1
29.0
30.4
95.0
KW
25.9
26.1
26.3
26.4
26.5
26.7
27.0
27.2
27.6
EER
10.3
10.6
10.9
11.0
11.2
11.5
11.8
12.0
12.5
EER
14.2
14.6
15.1
15.5
15.9
16.3
16.8
17.2
17.6
18.0
18.4
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
31.7
25.9
13.1
30.8
27.6
12.0
29.8
32.9
26.1
13.5
31.9
27.7
12.4
30.9
34.1
26.2
13.9
33.1
27.9
12.8
32.0
35.3
26.4
14.3
34.3
28.0
13.1
33.2
36.5
26.6
14.7
35.5
28.2
13.5
34.4
37.8
26.8
15.1
36.7
28.4
13.9
35.6
39.1
27.0
15.5
38.0
28.6
14.3
36.9
40.4
27.2
15.9
39.3
28.8
14.7
38.1
41.7
27.4
16.3
40.6
29.0
15.1
39.4
43.1
27.7
16.7
41.9
29.3
15.5
40.7
44.5
28.0
17.1
43.3
29.5
15.9
42.1
90.0
KW
29.4
29.5
29.7
29.8
30.0
30.2
30.4
30.6
30.8
31.0
31.3
EER
10.9
11.3
11.7
12.0
12.4
12.8
13.2
13.5
13.9
14.3
14.6
TONS
28.7
29.8
30.9
32.1
33.3
34.4
35.7
36.9
38.2
39.5
40.8
95.0
KW
31.4
31.5
31.6
31.8
31.9
32.1
32.3
32.5
32.7
32.9
33.1
EER
9.9
10.3
10.6
11.0
11.3
11.7
12.0
12.4
12.8
13.1
13.5
EER
13.9
14.3
14.7
15.2
15.6
16.0
16.4
16.9
17.3
17.7
18.1
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
33.8
28.4
12.8
32.7
30.2
11.7
31.7
35.0
28.6
13.2
33.9
30.4
12.1
32.9
36.3
28.8
13.6
35.2
30.6
12.5
34.1
37.6
29.0
14.0
36.5
30.8
12.9
35.3
38.9
29.2
14.4
37.8
31.0
13.2
36.6
40.3
29.4
14.8
39.1
31.2
13.6
37.9
41.7
29.7
15.2
40.4
31.4
14.0
39.2
43.1
29.9
15.6
41.8
31.7
14.4
40.5
44.5
30.2
16.0
43.2
31.9
14.8
41.9
46.0
30.4
16.4
44.7
32.2
15.1
43.3
47.5
30.7
16.8
46.2
32.5
15.5
44.8
90.0
KW
32.2
32.3
32.5
32.7
32.9
33.1
33.3
33.6
33.8
34.1
34.4
EER
10.7
11.1
11.4
11.8
12.1
12.5
12.9
13.2
13.6
13.9
14.3
TONS
30.6
31.7
32.9
34.1
35.3
36.6
37.9
39.2
40.6
41.9
43.3
95.0
KW
34.3
34.4
34.6
34.8
35.0
35.2
35.4
35.6
35.9
36.1
36.4
EER
9.8
10.1
10.4
10.8
11.1
11.4
11.8
12.1
12.4
12.8
13.1
MODEL YCUL0045EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
32.6
33.8
35.0
36.2
37.5
38.8
40.1
41.4
42.8
44.2
45.6
75.0
KW
24.3
24.5
24.7
24.8
25.0
25.2
25.5
25.7
25.9
26.2
26.5
MODEL YCUL0051EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
26
TONS
34.8
36.0
37.3
38.7
40.0
41.4
42.8
44.3
45.8
47.3
48.8
75.0
KW
26.8
26.9
27.1
27.3
27.5
27.8
28.0
28.3
28.5
28.8
29.1
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units) (Cont'd)
MODEL YCUL0035EE
SST
(F)
40.0
42.0
44.0
45.0
46.0
48.0
50.0
52.0
55.0
TONS
23.0
23.8
24.6
25.0
25.5
26.3
27.2
28.1
29.5
100.0
KW
27.5
27.7
27.9
28.0
28.1
28.3
28.6
28.8
29.2
EER
9.4
9.7
10.0
10.1
10.2
10.5
10.8
11.0
11.4
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
22.2
29.2
8.6
21.3
31.0
22.9
29.4
8.8
22.0
31.2
23.7
29.6
9.1
22.8
31.4
24.1
29.7
9.2
23.2
31.5
24.5
29.8
9.3
23.6
31.6
25.4
30.0
9.6
24.4
31.8
26.2
30.2
9.8
25.2
32.1
27.1
30.5
10.1
26.1
32.3
28.4
30.8
10.5
27.4
32.7
EER
7.8
8.0
8.3
8.4
8.5
8.7
9.0
9.2
9.5
TONS
20.4
21.1
21.9
22.3
22.6
23.4
24.2
25.0
26.3
115.0
KW
32.8
33.1
33.3
33.4
33.5
33.7
34.0
34.2
34.6
EER
7.1
7.3
7.5
7.6
7.7
7.9
8.1
8.4
8.7
EER
9.0
9.3
9.7
10.0
10.3
10.7
11.0
11.3
11.7
12.0
12.3
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
26.5
35.8
8.1
25.3
38.3
27.5
35.9
8.4
26.3
38.4
28.6
36.0
8.7
27.3
38.5
29.7
36.1
9.0
28.4
38.6
30.8
36.3
9.4
29.5
38.7
31.9
36.4
9.7
30.6
38.8
33.1
36.6
10.0
31.7
39.0
34.3
36.7
10.3
32.9
39.1
35.5
36.9
10.6
34.1
39.3
36.7
37.1
10.9
35.3
39.5
38.0
37.3
11.2
36.5
39.7
EER
7.3
7.6
7.9
8.2
8.4
8.7
9.0
9.3
9.6
9.9
10.2
TONS
24.0
25.0
26.1
27.1
28.1
29.2
30.3
31.4
32.6
33.8
35.0
115.0
KW
41.0
41.0
41.1
41.2
41.3
41.4
41.6
41.7
41.9
42.1
42.3
EER
6.5
6.8
7.0
7.3
7.6
7.8
8.1
8.4
8.7
8.9
9.2
EER
8.9
9.2
9.5
9.8
10.1
10.4
10.7
11.1
11.4
11.7
12.0
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
28.2
38.9
8.0
27.0
41.5
29.3
39.1
8.3
28.0
41.6
30.4
39.2
8.6
29.1
41.8
31.6
39.4
8.9
30.3
42.0
32.8
39.6
9.2
31.4
42.2
34.0
39.8
9.5
32.6
42.4
35.2
40.0
9.8
33.8
42.6
36.4
40.2
10.1
35.0
42.8
37.7
40.5
10.4
36.2
43.0
39.0
40.7
10.6
37.5
43.3
40.3
41.0
10.9
38.8
43.5
EER
7.2
7.5
7.8
8.0
8.3
8.6
8.8
9.1
9.4
9.7
9.9
TONS
25.7
26.7
27.8
28.9
30.0
31.1
32.3
33.4
34.6
35.9
37.1
115.0
KW
44.3
44.4
44.6
44.7
44.9
45.1
45.3
45.5
45.8
46.0
46.3
EER
6.5
6.7
7.0
7.2
7.5
7.7
8.0
8.2
8.5
8.7
9.0
MODEL YCUL0045EE
SST
(F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
27.6
28.7
29.8
30.9
32.1
33.2
34.4
35.6
36.9
38.1
39.4
100.0
KW
33.5
33.6
33.7
33.9
34.0
34.2
34.3
34.5
34.7
34.9
35.2
MODEL YCUL0051EE
SST
(F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
29.4
30.5
31.7
32.9
34.1
35.3
36.6
37.8
39.2
40.5
41.9
100.0
KW
36.5
36.7
36.8
37.0
37.2
37.4
37.6
37.8
38.1
38.3
38.6
JOHNSON CONTROLS
27
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units) (Cont'd)
MODEL YCUL0055EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
40.0
41.4
42.9
44.4
45.9
47.5
49.1
50.8
52.4
54.1
55.9
75.0
KW
29.7
30.0
30.2
30.5
30.8
31.1
31.4
31.7
32.1
32.5
32.9
EER
14.3
14.7
15.1
15.5
15.9
16.3
16.7
17.1
17.5
17.9
18.2
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
39.0
31.4
13.2
37.9
33.3
12.2
36.8
40.4
31.7
13.6
39.3
33.5
12.6
38.2
41.8
31.9
14.0
40.7
33.7
13.0
39.6
43.3
32.1
14.4
42.2
33.9
13.4
41.0
44.8
32.4
14.8
43.6
34.2
13.8
42.4
46.4
32.7
15.2
45.2
34.5
14.1
43.9
47.9
33.0
15.6
46.7
34.7
14.5
45.4
49.5
33.3
16.0
48.3
35.0
14.9
46.9
51.2
33.6
16.4
49.9
35.4
15.2
48.5
52.9
34.0
16.7
51.5
35.7
15.6
50.1
54.6
34.4
17.1
53.2
36.1
16.0
51.7
90.0
KW
35.3
35.5
35.7
35.9
36.2
36.4
36.7
37.0
37.3
37.6
37.9
EER
11.3
11.6
12.0
12.4
12.7
13.1
13.4
13.8
14.1
14.5
14.8
TONS
35.7
37.0
38.4
39.7
41.2
42.6
44.1
45.6
47.1
48.7
50.2
95.0
KW
37.5
37.6
37.9
38.1
38.3
38.5
38.8
39.1
39.4
39.7
40.0
EER
10.4
10.7
11.0
11.4
11.7
12.0
12.4
12.7
13.1
13.4
13.7
EER
13.7
14.1
14.5
14.9
15.3
15.6
16.0
16.4
16.7
17.1
17.4
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
45.0
38.5
12.7
43.7
40.8
11.7
42.4
46.6
38.8
13.1
45.3
41.1
12.1
44.0
48.2
39.1
13.5
46.9
41.4
12.4
45.5
49.9
39.4
13.8
48.5
41.7
12.8
47.1
51.6
39.8
14.2
50.2
42.0
13.1
48.8
53.3
40.1
14.5
51.9
42.4
13.5
50.4
55.1
40.5
14.9
53.7
42.7
13.8
52.1
57.0
40.9
15.3
55.4
43.1
14.2
53.9
58.8
41.4
15.6
57.3
43.5
14.5
55.6
60.7
41.8
15.9
59.1
44.0
14.8
57.5
62.7
42.3
16.3
61.0
44.4
15.1
59.3
90.0
KW
43.2
43.5
43.8
44.1
44.5
44.8
45.2
45.5
45.9
46.4
46.8
EER
10.8
11.1
11.5
11.8
12.1
12.4
12.8
13.1
13.4
13.7
14.0
TONS
41.1
42.6
44.1
45.7
47.2
48.9
50.5
52.2
54.0
55.7
57.5
95.0
KW
45.9
46.2
46.5
46.8
47.1
47.4
47.8
48.2
48.6
49.0
49.4
EER
9.9
10.2
10.5
10.8
11.1
11.4
11.7
12.0
12.3
12.7
13.0
EER
13.7
14.1
14.4
14.8
15.1
15.5
15.8
16.2
16.5
16.9
17.2
AIR TEMPERATURE ON - CONDENSER (°F)
80.0
85.0
TONS KW
EER TONS KW
EER TONS
56.8
49.9
12.7
55.1
52.6
11.7
53.4
58.9
50.3
13.0
57.1
53.1
12.0
55.3
61.0
50.8
13.4
59.1
53.6
12.3
57.3
63.1
51.3
13.7
61.2
54.1
12.7
59.3
65.3
51.9
14.0
63.3
54.7
13.0
61.4
67.5
52.4
14.4
65.5
55.2
13.3
63.5
69.8
53.0
14.7
67.7
55.8
13.6
65.7
72.1
53.6
15.0
70.0
56.4
13.9
67.9
74.4
54.3
15.4
72.3
57.0
14.2
70.1
76.8
54.9
15.7
74.6
57.7
14.5
72.4
79.3
55.6
16.0
77.0
58.4
14.8
74.7
90.0
KW
55.6
56.1
56.6
57.1
57.7
58.2
58.8
59.4
60.1
60.7
61.4
EER
10.8
11.1
11.4
11.7
12.0
12.3
12.6
12.9
13.2
13.4
13.7
TONS
51.6
53.5
55.4
57.4
59.4
61.5
63.6
65.7
67.9
70.1
72.4
95.0
KW
58.9
59.4
59.9
60.4
61.0
61.5
62.1
62.7
63.4
64.0
64.7
EER
9.9
10.1
10.4
10.7
11.0
11.3
11.6
11.8
12.1
12.4
12.7
MODEL YCUL0065EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
46.1
47.8
49.5
51.2
52.9
54.7
56.5
58.4
60.3
62.3
64.2
75.0
KW
36.4
36.7
37.0
37.4
37.7
38.1
38.5
39.0
39.4
39.9
40.4
MODEL YCUL0072EE
SST
(°F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
28
TONS
58.5
60.6
62.7
64.9
67.1
69.4
71.7
74.1
76.5
79.0
81.5
75.0
KW
47.3
47.8
48.3
48.8
49.3
49.9
50.5
51.1
51.7
52.4
53.1
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - English Units) (Cont'd)
MODEL YCUL0055EE
SST
(F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
34.5
35.8
37.1
38.5
39.8
41.2
42.7
44.1
45.6
47.1
48.7
100.0
KW
39.8
40.0
40.2
40.4
40.6
40.9
41.1
41.4
41.7
42.0
42.3
EER
9.5
9.8
10.1
10.4
10.7
11.1
11.4
11.7
12.0
12.3
12.7
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
33.3
42.2
8.7
32.0
44.8
34.5
42.4
8.9
33.2
45.1
35.8
42.7
9.2
34.5
45.3
37.1
42.9
9.5
35.7
45.5
38.5
43.1
9.8
37.0
45.7
39.8
43.3
10.1
38.4
46.0
41.2
43.6
10.4
39.7
46.2
42.6
43.9
10.7
41.1
46.5
44.1
44.1
11.0
42.5
46.8
45.6
44.4
11.3
43.9
47.1
47.1
44.7
11.6
45.4
47.4
EER
7.9
8.2
8.4
8.7
9.0
9.2
9.5
9.8
10.1
10.4
10.6
TONS
30.7
31.9
33.1
34.3
35.6
36.9
38.2
39.5
40.9
42.3
43.7
115.0
KW
47.6
47.8
48.1
48.3
48.5
48.8
49.1
49.3
49.6
49.9
50.2
EER
7.2
7.4
7.6
7.9
8.1
8.4
8.7
8.9
9.2
9.4
9.7
EER
9.1
9.3
9.6
9.9
10.2
10.5
10.8
11.0
11.3
11.6
11.9
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
38.2
51.7
8.3
36.8
54.8
39.6
52.0
8.5
38.1
55.2
41.1
52.3
8.8
39.5
55.5
42.6
52.6
9.0
40.9
55.8
44.1
53.0
9.3
42.4
56.2
45.6
53.3
9.6
43.9
56.5
47.2
53.7
9.8
45.4
56.9
48.8
54.0
10.1
47.0
57.3
50.4
54.4
10.4
48.6
57.7
52.1
54.8
10.6
50.2
58.1
53.8
55.2
10.9
51.8
58.5
EER
7.5
7.7
8.0
8.2
8.5
8.7
9.0
9.2
9.5
9.7
10.0
TONS
35.2
36.5
37.9
39.3
40.7
42.1
43.6
45.1
46.6
48.2
49.8
115.0
KW
58.2
58.5
58.9
59.2
59.6
60.0
60.3
60.7
61.1
61.5
61.9
EER
6.8
7.0
7.2
7.5
7.7
7.9
8.1
8.4
8.6
8.8
9.1
EER
9.0
9.3
9.5
9.8
10.1
10.3
10.6
10.9
11.1
11.4
11.6
AIR TEMPERATURE ON - CONDENSER (F)
105.0
110.0
TONS
KW
EER
TONS
KW
48.0
66.2
8.2
46.1
70.2
49.7
66.7
8.5
47.8
70.7
51.6
67.2
8.7
49.6
71.3
53.4
67.7
8.9
51.4
71.8
55.3
68.3
9.2
53.2
72.4
57.2
68.9
9.4
55.1
73.0
59.2
69.5
9.7
57.0
73.6
61.2
70.1
9.9
59.0
74.2
63.3
70.7
10.2
61.0
74.9
65.4
71.4
10.4
63.0
75.5
67.6
72.1
10.7
65.1
76.2
EER
7.5
7.7
7.9
8.1
8.4
8.6
8.8
9.1
9.3
9.5
9.7
TONS
44.2
45.8
47.5
49.3
51.1
52.9
40.7
42.1
43.6
45.1
46.7
115.0
KW
74.6
75.1
75.7
76.2
76.8
77.4
51.9
52.2
52.6
52.9
53.3
EER
6.8
7.0
7.2
7.4
7.6
7.8
8.8
9.0
9.3
9.5
9.8
MODEL YCUL0065EE
SST
(F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
39.7
41.1
42.6
44.1
45.7
47.3
48.9
50.5
52.2
53.9
55.7
100.0
KW
48.7
49.0
49.3
49.6
49.9
50.3
50.6
51.0
51.4
51.8
52.2
MODEL YCUL0072EE
SST
(F)
35.0
37.0
39.0
41.0
43.0
45.0
47.0
49.0
51.0
53.0
55.0
TONS
49.8
51.6
53.5
55.4
57.4
59.4
61.4
63.5
65.6
67.8
70.0
100.0
KW
62.4
62.9
63.4
63.9
64.5
65.1
65.7
66.3
66.9
67.6
68.3
JOHNSON CONTROLS
29
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - SI Units)
MODEL:YCUL0020EE
AIR TEMPERATURE ON - CONDENSER (°C)
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
62.5
64.4
66.4
68.4
70.4
72.5
74.6
76.8
25.0
KW
14.3
14.5
14.6
14.8
14.9
15.1
15.2
15.4
COP
4.1
4.2
4.3
4.3
4.4
4.5
4.6
4.7
KW
59.2
61.1
62.9
64.8
66.7
68.7
70.7
72.8
30.0
KW
15.9
16.0
16.2
16.3
16.5
16.6
16.8
17.0
KW
52.1
53.8
55.4
57.1
58.9
60.6
62.4
64.3
40.0
KW
19.7
19.8
20.0
20.1
20.2
20.4
20.5
20.7
COP
2.5
2.6
2.6
2.7
2.8
2.8
2.9
3.0
KW
48.3
49.8
51.4
53.0
29.5
30.5
31.4
32.4
45.0
KW
22.0
22.1
22.2
22.3
9.5
9.6
9.6
9.7
COP
2.1
2.2
2.2
2.3
2.80
2.88
2.96
3.04
KW
70.6
72.8
74.9
77.2
79.4
81.7
84.0
86.3
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
19.3
3.5
66.0
21.4
2.9
61.1
19.4
3.6
68.0
21.6
3.0
63.1
19.6
3.6
70.1
21.8
3.1
65.0
19.8
3.7
72.2
22.0
3.1
67.1
20.0
3.8
74.4
22.2
3.2
69.1
20.2
3.9
76.6
22.4
3.3
71.2
20.4
3.9
78.8
22.6
3.3
73.2
20.6
4.0
81.0
22.8
3.4
75.4
40.0
KW
23.8
24.0
24.2
24.4
24.6
24.8
25.0
25.2
COP
2.5
2.5
2.6
2.6
2.7
2.8
2.8
2.9
KW
56.0
31.9
33.0
34.1
35.2
36.3
37.5
38.7
45.0
KW
26.6
11.3
11.3
11.4
11.4
11.5
11.5
11.6
COP
2.0
2.60
2.68
2.76
2.84
2.91
2.99
3.07
KW
94.1
97.0
100.0
103.0
106.1
109.3
112.5
115.8
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
24.7
3.4
88.8
27.1
3.0
83.3
24.9
3.5
91.6
27.3
3.0
85.9
25.2
3.6
94.4
27.5
3.1
88.6
25.4
3.6
97.3
27.8
3.2
91.3
25.6
3.7
100.2 28.0
3.2
94.0
25.9
3.8
103.2 28.3
3.3
96.9
26.2
3.9
106.3 28.5
3.4
99.7
26.5
3.9
109.3 28.8
3.4
102.6
40.0
KW
29.8
30.0
30.2
30.5
30.7
30.9
31.2
31.5
COP
2.5
2.6
2.7
2.7
2.8
2.9
2.9
3.0
KW
77.4
79.8
82.3
84.9
87.5
90.1
92.8
95.5
45.0
KW
32.8
33.0
33.2
33.5
33.7
33.9
34.2
34.5
COP
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.6
KW
107.7
111.0
114.5
118.0
121.6
125.2
128.9
132.7
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
28.8
3.4
101.6 31.8
2.9
95.3
29.0
3.5
104.8 32.0
3.0
98.3
29.3
3.6
108.1 32.3
3.1
101.4
29.6
3.6
111.4
32.5
3.1
104.6
29.9
3.7
114.8
32.8
3.2
107.8
30.2
3.8
118.2
33.1
3.3
111.0
30.5
3.9
121.8 33.4
3.3
114.4
30.9
3.9
125.4 33.8
3.4
117.8
40.0
KW
35.2
35.5
35.7
36.0
36.3
36.6
36.9
37.2
COP
2.5
2.6
2.6
2.7
2.7
2.8
2.9
2.9
KW
88.7
91.6
94.5
97.5
53.4
55.1
56.9
58.7
45.0
KW
39.1
39.4
39.6
39.9
17.5
17.5
17.6
17.7
COP
2.1
2.2
2.2
2.3
2.61*
2.68*
2.76*
2.83*
MODEL:YCUL0024EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
74.9
77.2
79.4
81.7
84.0
86.4
88.8
91.2
25.0
KW
17.4
17.6
17.7
17.9
18.1
18.3
18.4
18.6
COP
4.1
4.2
4.2
4.3
4.4
4.5
4.6
4.6
MODEL:YCUL0031EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
99.1
102.1
105.3
108.5
111.8
115.1
118.5
121.9
25.0
KW
22.6
22.8
23.1
23.3
23.6
23.8
24.1
24.4
COP
3.9
4.0
4.0
4.1
4.2
4.3
4.4
4.5
MODEL:YCUL0035EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
30
KW
113.5
117.0
120.7
124.3
128.1
131.9
135.8
139.8
25.0
KW
26.2
26.5
26.8
27.1
27.4
27.8
28.1
28.5
COP
3.9
4.0
4.1
4.1
4.2
4.3
4.4
4.4
COP
3.5
3.6
3.7
3.7
3.8
3.9
4.0
4.1
KW
55.8
57.5
59.3
61.1
62.9
64.8
66.6
68.6
35.0
KW
17.7
17.8
18.0
18.1
18.2
18.4
18.6
18.7
COP
3.0
3.1
3.1
3.2
3.3
3.3
3.4
3.5
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - SI Units) (Cont'd)
MODEL: YCUL0045EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
151.9
156.5
161.2
166.0
170.9
175.8
180.9
186.0
25.0
KW
32.0
32.2
32.4
32.6
32.8
33.0
33.2
33.4
COP
4.0
4.1
4.2
4.4
4.5
4.6
4.7
4.8
KW
144.5
149.0
153.7
158.4
163.2
168.0
173.0
178.0
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
35.2
3.5
136.2 39.1
3.1
127.1
35.4
3.6
140.6 39.3
3.1
131.4
35.6
3.7
145.1 39.5
3.2
135.8
35.8
3.8
149.7 39.7
3.3
140.2
36.1
3.9
154.4 39.9
3.4
144.7
36.3
4.0
159.1 40.2
3.5
149.3
36.5
4.1
163.9 40.4
3.6
153.9
36.7
4.2
168.8 40.7
3.7
158.6
40.0
KW
43.6
43.8
44.0
44.2
44.5
44.7
45.0
45.2
COP
2.6
2.7
2.7
2.8
2.9
3.0
3.0
3.1
KW
117.4
121.5
125.7
129.9
134.2
138.6
143.0
147.6
45.0
KW
48.8
49.0
49.2
49.4
49.6
49.8
50.1
50.3
COP
2.2
2.2
2.3
2.4
2.4
2.5
2.6
2.6
KW
153.6
158.4
163.4
168.4
173.5
178.7
184.0
189.3
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
38.7
3.5
144.6 42.9
3.0
135.1
39.0
3.6
149.3 43.1
3.1
139.6
39.2
3.6
154.0 43.4
3.2
144.1
39.5
3.7
158.9 43.7
3.2
148.7
39.8
3.8
163.8 43.9
3.3
153.4
40.1
3.9
168.8 44.2
3.4
158.2
40.4
4.0
173.8 44.5
3.5
163.1
40.7
4.1
179.0 44.8
3.6
168.0
40.0
KW
47.6
47.9
48.1
48.4
48.7
49.0
49.3
49.6
COP
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.0
KW
125.0
129.3
133.6
138.0
142.5
147.0
151.7
156.4
45.0
KW
53.0
53.3
53.5
53.8
54.0
54.3
54.6
54.9
COP
2.1
2.2
2.3
2.3
2.4
2.5
2.5
2.6
KW
179.3
185.0
190.9
196.8
202.9
209.1
215.5
221.9
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
43.8
3.6
169.4 48.1
3.1
159.0
44.2
3.6
174.7 48.5
3.2
164.0
44.5
3.7
180.2 48.8
3.2
169.2
44.9
3.8
185.8 49.2
3.3
174.4
45.3
3.9
191.6 49.6
3.4
179.8
45.7
4.0
197.4 50.0
3.5
185.3
46.1
4.1
203.4 50.4
3.6
190.9
46.6
4.2
209.4 50.8
3.6
196.5
40.0
KW
53.0
53.4
53.7
54.1
54.5
54.9
55.3
55.7
COP
2.7
2.7
2.8
2.9
2.9
3.0
3.1
3.2
KW
148.0
152.7
157.6
162.5
167.5
172.6
177.8
183.1
45.0
KW
58.5
58.8
59.2
59.5
59.9
60.3
60.7
61.1
COP
2.3
2.3
2.4
2.5
2.5
2.6
2.6
2.7
MODEL: YCUL0051EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
162.0
167.0
172.1
177.3
182.5
187.9
193.4
198.9
25.0
KW
35.2
35.5
35.7
36.0
36.2
36.5
36.8
37.1
COP
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
MODEL: YCUL0055EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
189.0
195.1
201.3
207.6
214.0
220.6
227.4
234.2
25.0
KW
40.0
40.4
40.7
41.1
41.5
42.0
42.4
42.8
COP
4.1
4.1
4.2
4.3
4.4
4.5
4.6
4.7
JOHNSON CONTROLS
31
FORM 150.63-EG5 (1017)
Ratings - R-410A (60Hz - SI Units)
MODEL: YCUL0065EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
218.1
224.7
231.5
238.3
245.3
252.4
259.5
266.8
25.0
KW
48.9
49.4
49.9
50.5
51.1
51.8
52.4
53.1
COP
3.9
4.0
4.1
4.2
4.2
4.3
4.4
4.5
KW
207.3
213.6
220.1
226.6
233.3
240.0
246.9
253.8
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
53.2
3.5
195.6 58.2
3.0
183.2
53.7
3.5
201.7 58.7
3.1
189.0
54.3
3.6
207.8 59.3
3.2
194.8
54.8
3.7
214.1 59.8
3.2
200.7
55.4
3.8
220.4 60.4
3.3
206.7
56.0
3.8
226.8 61.0
3.4
212.8
56.7
3.9
233.3 61.6
3.4
218.9
57.4
4.0
239.9 62.3
3.5
225.2
40.0
KW
63.9
64.4
64.9
65.4
66.0
66.6
67.2
67.9
COP
2.6
2.7
2.7
2.8
2.8
2.9
3.0
3.0
KW
170.1
175.5
181.0
186.5
192.2
197.9
203.7
209.6
45.0
KW
70.3
70.8
71.3
71.8
72.3
72.9
73.5
74.1
COP
2.2
2.3
2.3
2.4
2.4
2.5
2.5
2.6
KW
255.8
263.8
272.1
280.4
288.9
297.6
306.4
315.4
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
67.0
3.5
241.1 73.5
3.0
226.2
67.7
3.5
248.8 74.2
3.1
233.4
68.4
3.6
256.6 74.9
3.1
240.8
69.2
3.7
264.6 75.6
3.2
248.4
69.9
3.8
272.6 76.4
3.3
256.0
70.7
3.8
280.8 77.2
3.4
263.8
71.5
3.9
289.2 78.0
3.4
271.8
72.4
4.0
297.8 78.9
3.5
279.9
40.0
KW
81.0
81.6
82.4
83.1
83.9
84.7
85.5
86.3
COP
2.6
2.6
2.7
2.8
2.8
2.9
3.0
3.0
KW
210.9
217.7
224.7
231.8
239.0
183.6
189.4
195.3
45.0
KW
89.5
90.2
90.9
91.6
92.4
62.2
62.7
63.1
COP
2.2
2.3
2.3
2.4
2.4
2.7
2.7
2.8
MODEL: YCUL0072EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
32
KW
270.1
278.6
287.3
296.0
305.0
314.1
323.3
332.7
25.0
KW
61.5
62.2
62.9
63.6
64.3
65.1
65.9
66.7
COP
4.0
4.1
4.1
4.2
4.3
4.4
4.5
4.5
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - SI Units)
MODEL:YCUL0020EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
52.4
54.0
55.6
57.2
58.9
60.6
62.3
64.0
25.0
KW
11.4
11.5
11.6
11.8
11.9
12.0
12.2
12.4
COP
4.4
4.5
4.6
4.6
4.7
4.8
4.9
5.0
KW
49.6
51.1
52.6
54.2
55.7
57.3
59.0
60.6
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
12.6
3.8
46.6
14.0
3.2
43.6
12.7
3.8
48.1
14.2
3.3
44.9
12.9
3.9
49.5
14.3
3.3
46.3
13.0
4.0
51.0
14.4
3.4
47.7
13.1
4.1
52.5
14.6
3.5
49.2
13.3
4.1
54.0
14.7
3.5
50.6
13.4
4.2
55.6
14.9
3.6
52.1
13.6
4.3
57.1
15.0
3.7
53.6
40.0
KW
15.7
15.8
15.9
16.0
16.2
16.3
16.5
16.6
COP
2.7
2.7
2.8
2.9
2.9
3.0
3.1
3.1
KW
40.3
41.6
43.0
44.3
45.7
47.1
48.5
49.9
45.0
KW
17.6
17.7
17.8
17.9
18.0
18.1
18.3
18.4
COP
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.6
KW
58.5
60.3
62.1
64.0
65.8
67.7
69.6
71.6
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
15.7
3.6
54.7
17.5
3.0
50.6
15.8
3.7
56.4
17.6
3.1
52.2
15.9
3.8
58.1
17.8
3.2
53.9
16.1
3.8
59.9
17.9
3.2
55.5
16.2
3.9
61.6
18.1
3.3
57.2
16.4
4.0
63.4
18.2
3.4
58.9
16.5
4.1
65.3
18.4
3.4
60.6
16.7
4.1
67.1
18.5
3.5
62.4
40.0
KW
19.6
19.7
19.9
20.0
20.1
20.3
20.5
20.6
COP
2.5
2.6
2.6
2.7
2.8
2.8
2.9
2.9
KW
46.3
47.9
49.4
28.2
29.1
30.0
31.0
31.9
45.0
KW
21.9
22.1
22.2
9.3
9.4
9.4
9.4
9.5
COP
2.1
2.1
2.2
2.9
2.9
3.0
3.1
3.2
KW
77.0
79.4
81.9
84.4
86.9
89.5
92.2
94.9
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
19.5
3.6
72.9
21.6
3.1
68.5
19.6
3.7
75.2
21.7
3.2
70.7
19.7
3.8
77.6
21.9
3.3
72.9
19.9
3.9
79.9
22.0
3.4
75.2
20.0
4.0
82.4
22.1
3.5
77.5
20.2
4.1
84.9
22.3
3.5
79.9
20.4
4.2
87.4
22.5
3.6
82.3
20.6
4.3
90.0
22.6
3.7
84.8
40.0
KW
24.0
24.2
24.3
24.4
24.6
24.7
24.9
25.0
COP
2.7
2.7
2.8
2.9
3.0
3.0
3.1
3.2
KW
63.9
65.9
68.1
70.2
72.4
74.6
76.9
79.2
45.0
KW
26.8
26.9
27.0
27.2
27.3
27.5
27.6
27.8
COP
2.2
2.3
2.4
2.4
2.5
2.6
2.6
2.7
KW
90.1
92.9
95.7
98.6
101.5
104.5
107.6
110.6
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
23.5
3.6
85.1
26.0
3.1
79.9
23.6
3.7
87.8
26.2
3.1
82.4
23.8
3.8
90.5
26.4
3.2
85.0
24.0
3.8
93.2
26.6
3.3
87.6
24.2
3.9
96.0
26.8
3.4
90.2
24.4
4.0
98.9
27.0
3.5
92.9
24.6
4.1
101.8 27.2
3.5
95.7
24.8
4.2
104.8 27.4
3.6
98.5
40.0
KW
29.0
29.1
29.3
29.5
29.7
29.9
30.1
30.3
COP
2.6
2.7
2.7
2.8
2.9
2.9
3.0
3.1
KW
74.3
76.7
79.1
81.5
84.1
86.6
89.2
91.9
45.0
KW
32.2
32.4
32.6
32.8
33.0
33.2
33.4
33.6
COP
2.2
2.3
2.3
2.4
2.4
2.5
2.5
2.6
MODEL YCUL0024EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
62.1
64.0
65.9
67.8
69.7
71.7
73.7
75.8
25.0
KW
14.1
14.2
14.3
14.5
14.6
14.8
14.9
15.1
COP
4.3
4.3
4.4
4.5
4.6
4.7
4.8
4.8
MODEL YCUL0031EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
80.8
83.3
85.9
88.5
91.1
93.8
96.6
99.4
25.0
KW
17.6
17.8
17.9
18.1
18.3
18.4
18.6
18.8
COP
4.2
4.3
4.4
4.5
4.6
4.7
4.7
4.8
MODEL YCUL0035EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
94.7
97.6
100.5
103.6
106.6
109.7
112.9
116.2
25.0
KW
21.2
21.4
21.6
21.8
22.0
22.2
22.5
22.7
COP
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
JOHNSON CONTROLS
33
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - SI Units) (Cont'd)
MODEL: YCUL0045EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
126.1
130.0
134.1
138.2
142.3
146.6
150.9
155.3
25.0
KW
25.4
25.6
25.8
26.0
26.2
26.4
26.6
26.9
COP
4.4
4.5
4.6
4.7
4.8
5.0
5.1
5.2
KW
119.8
123.6
127.5
131.5
135.5
139.6
143.8
148.1
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
28.4
3.8
112.8
31.8
3.2
105.3
28.5
3.9
116.5
31.9
3.3
108.8
28.7
4.0
120.3 32.1
3.4
112.4
28.9
4.1
124.1 32.2
3.5
116.1
29.1
4.2
128.0 32.4
3.6
119.8
29.3
4.3
132.0 32.6
3.7
123.7
29.5
4.4
136.0 32.8
3.8
127.5
29.7
4.5
140.1 33.0
3.9
131.5
40.0
KW
35.7
35.8
35.9
36.1
36.2
36.4
36.6
36.7
COP
2.7
2.8
2.9
3.0
3.0
3.1
3.2
3.3
KW
97.1
100.5
104.0
107.5
111.1
114.7
118.4
122.1
45.0
KW
40.1
40.2
40.4
40.5
40.6
40.8
40.9
41.1
COP
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
KW
127.4
131.5
135.7
139.9
144.3
148.7
153.2
157.8
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
31.2
3.7
120.0 34.8
3.2
112.0
31.3
3.8
123.9 35.0
3.2
115.7
31.5
3.9
127.9 35.1
3.3
119.5
31.7
4.0
131.9 35.3
3.4
123.4
31.9
4.1
136.0 35.5
3.5
127.3
32.2
4.2
140.3 35.8
3.6
131.4
32.4
4.3
144.6 36.0
3.7
135.5
32.6
4.4
148.9 36.2
3.8
139.6
40.0
KW
38.9
39.1
39.3
39.5
39.7
39.9
40.1
40.3
COP
2.7
2.7
2.8
2.9
3.0
3.1
3.1
3.2
KW
103.5
107.0
110.7
114.3
118.1
121.9
125.8
129.8
45.0
KW
43.6
43.8
43.9
44.1
44.3
44.5
44.7
45.0
COP
2.2
2.3
2.4
2.4
2.5
2.6
2.6
2.7
KW
147.5
152.1
156.9
161.7
166.6
171.6
176.7
181.9
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
34.3
3.9
139.8 38.1
3.3
131.5
34.5
4.0
144.2 38.3
3.4
135.8
34.8
4.1
148.8 38.5
3.5
140.1
35.0
4.2
153.4 38.7
3.6
144.5
35.3
4.3
158.1 39.0
3.7
149.0
35.6
4.4
162.9 39.2
3.8
153.6
35.9
4.5
167.8 39.5
3.9
158.2
36.2
4.5
172.8 39.8
4.0
163.0
40.0
KW
42.4
42.6
42.8
43.0
43.2
43.5
43.7
44.0
COP
2.8
2.9
3.0
3.1
3.2
3.2
3.3
3.4
KW
122.7
126.7
130.8
135.0
139.3
143.6
148.1
152.6
45.0
KW
47.2
47.4
47.6
47.8
48.1
48.3
48.6
48.8
COP
2.4
2.5
2.5
2.6
2.7
2.8
2.8
2.9
MODEL: YCUL0051EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
134.4
138.7
143.0
147.5
152.0
156.6
161.3
166.1
25.0
KW
28.0
28.2
28.4
28.6
28.8
29.0
29.3
29.5
COP
4.3
4.4
4.5
4.6
4.7
4.9
5.0
5.1
MODEL: YCUL0055EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
34
KW
154.6
159.5
164.4
169.4
174.5
179.7
185.0
190.4
25.0
KW
31.1
31.4
31.6
31.9
32.2
32.5
32.8
33.2
COP
4.4
4.5
4.6
4.7
4.8
4.9
5.0
5.1
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Ratings - R-410A (50Hz - SI Units) (Cont'd)
MODEL: YCUL0065EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
178.2
183.7
189.3
195.0
200.8
206.7
212.7
218.9
25.0
KW
38.2
38.5
38.8
39.2
39.5
39.9
40.4
40.8
COP
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
KW
169.7
175.0
180.3
185.8
191.4
197.1
202.8
208.7
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
42.2
3.7
160.6 46.8
3.2
150.8
42.4
3.8
165.6 47.1
3.3
155.6
42.8
3.9
170.7 47.4
3.3
160.5
43.1
4.0
176.0 47.7
3.4
165.4
43.4
4.0
181.3 48.0
3.5
170.5
43.8
4.1
186.7 48.4
3.6
175.7
44.2
4.2
192.2 48.7
3.7
180.9
44.6
4.3
197.8 49.1
3.7
186.3
40.0
KW
52.0
52.3
52.6
52.9
53.3
53.6
54.0
54.3
COP
2.7
2.8
2.8
2.9
3.0
3.1
3.1
3.2
KW
140.5
145.0
149.6
154.3
159.1
164.0
168.9
174.0
45.0
KW
57.8
58.2
58.5
58.8
59.2
59.5
59.9
60.2
COP
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.7
KW
214.0
220.7
227.5
234.4
241.5
248.7
256.0
263.5
AIR TEMPERATURE ON - CONDENSER (°C)
30.0
35.0
KW
COP
KW
KW
COP
KW
54.7
3.7
201.8 60.4
3.1
189.3
55.2
3.7
208.2 60.9
3.2
195.3
55.7
3.8
214.7 61.4
3.3
201.5
56.2
3.9
221.3 61.9
3.4
207.7
56.7
4.0
228.0 62.5
3.4
214.1
57.3
4.1
234.9 63.0
3.5
220.6
57.9
4.2
241.9 63.6
3.6
227.2
58.5
4.2
249.0 64.2
3.7
234.0
40.0
KW
67.0
67.5
68.0
68.5
69.1
69.6
70.2
70.8
COP
2.7
2.7
2.8
2.9
2.9
3.0
3.1
3.1
KW
176.2
181.9
187.8
193.7
199.7
205.9
158.0
162.9
45.0
KW
74.4
74.9
75.5
76.0
76.6
77.2
51.5
51.8
COP
2.3
2.3
2.4
2.4
2.5
2.5
2.9
2.9
MODEL: YCUL0072EE
SST
(°C)
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
KW
225.7
232.7
239.8
247.1
254.5
262.0
269.6
277.4
25.0
KW
49.8
50.3
50.8
51.3
51.8
52.4
53.0
53.6
COP
4.2
4.3
4.4
4.5
4.6
4.7
4.7
4.8
JOHNSON CONTROLS
35
FORM 150.63-EG5 (1017)
Physical Data
60Hz
YCUL
LENGTH (IN.)
WIDTH (IN.)
HEIGHT (IN.)
NOMINAL TONS
NUMBER OF
0020EE
109.8
44.7
46.1
17
0024EE
109.8
44.7
46.1
20.1
0031EE
118.6
44.7
50
27
0035EE
118.6
44.7
50
30.9
0045EE
144.8
90.6
47.8
41.6
0051EE
144.8
90.6
47.8
44.1
0055EE
148.8
90.6
62.6
51.6
0065EE
148.8
90.6
62.6
59.5
0072EE
153.6
90.6
62.6
73.5
1
1
1
1
2
2
2
2
2
17
25
40
45
35/35
40/35
45/45
50/50
65/65
1.8
1.8
1.7
2.2
1.8/1.8
1.8/1.8
1.7/1.7
1.7/1.7
2.3/2.2
1454
1567
1798
2034
2942
2968
3196
3208
4097
1597
1781
2004
2240
3300
3326
3673
3685
4703
1471
1592
1838
2079
2967
3001
3233
3245
4142
1614
1806
2044
2285
3325
3359
3710
3722
4748
8
8
–
–
–
–
10
10
–
–
–
–
13
13
–
–
–
–
15
15
–
–
–
–
10
10
–
10
10
–
12
12
–
10
10
–
13
13
–
13
13
–
15
15
–
15
15
–
20
20
–
15
15
–
35
35
44
44
87
87
116
116
128
CKT. 1
2
2
2
2
2
2
3
3
3
CKT. 2
–
–
–
–
2
2
3
3
3
17
17
13
13
17
17
17
17
13
CKT. 1
2
2
2
2
2
2
2
2
2
CKT. 2
–
–
–
–
2
2
2
2
2
FAN POWER HP/FAN
2
2
2
2
2
2
2
2
2
REFRIGERANT CIRCUITS
REFRIG. CHG, OPT, R-410A (LBS)
CKT1/CKT2
OIL CHARGE, GALLONS CKT1/CKT2
ALUM. FIN COILS,
SHIPPING
LBS
COPPER FIN COILS,
WEIGHT
LBS
ALUM. FIN COILS,
OPERATING
LBS
COPPER FIN COILS,
WEIGHT
LBS
COMP. 1
COMP. 2
NOMINAL
COMP. 3
COMP.
COMP. 4
CAPACITY
COMP. 5
COMP. 6
TOTAL FACE AREA
FT2
CONDENSER
NUMBER OF
ROWS DEEP
FINS PER INCH
CONDENSER
FANS, LOW
SOUND
CONDENSER
FANS, ULTRA
QUIET
36
NUMBER OF
FANS
FAN RPM
1150
1150
1150
1150
1150
1150
1150
1150
1150
TOTAL CHILLER CFM
10670
10670
24600
24600
39500
39500
43333
43333
43333
CKT. 1
NA
NA
NA
NA
2
2
2
2
2
CKT. 2
NA
NA
NA
NA
2
2
2
2
2
FAN POWER HP/FAN
NA
NA
2
2
2
2
2
2
2
FAN RPM
NA
NA
850
850
850
850
850
850
850
TOTAL CHILLER CFM
NA
NA
24600
24600
39500
39500
43333
43333
43333
NUMBER OF
FANS
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Physical Data (Cont'd)
50Hz
YCUL
LENGTH (MM)
WIDTH (MM)
HEIGHT (MM)
NOMINAL KW
NUMBER OF
0020EE
2788.7
1135.4
1169.9
49.9
0024EE
2788.7
1135.4
1169.9
58.4
0031EE
3012.4
1135.4
1270
78.1
0035EE
3012.4
1135.4
1270
91.1
0045EE
3677.9
2301.2
1214.1
146.3
0051EE
3677.9
2301.2
1214.1
155.1
0055EE
3779.5
2301.2
1590
181.5
0065EE
3779.5
2301.2
1590
209.3
0072EE
3901.4
2301.2
1590
258.5
1
1
1
1
2
2
2
2
2
7.7
11.3
18.1
20.4
6.8
6.8
6.4
8.3
6.8/6.8
6.8/6.8
6.4/6.4
6.4/6.4
8.7/8.3
659.5
710.8
815.6
922.6
1334.5
1346.3
1449.7
1455.1
1858.4
724.4
807.8
909
1016
1496.9
1508.6
1666
1671.5
2133.2
667.2
722.1
833.7
943
1345.8
1361.2
1466.5
1471.9
1878.8
732.1
819.2
927.1
1036.5
1508.2
1523.6
1682.8
1688.3
2153.7
25
25
–
–
–
–
30
30
–
–
–
–
42.2
42.2
–
–
–
–
45.7
45.7
–
–
–
–
35.1
35.1
–
35.1
35.1
–
8.1
42.2
42.2
–
35.1
35.1
–
8.1
45.7
45.7
–
45.7
45.7
–
10.8
52.7
52.7
–
52.7
52.7
–
10.8
70.3
70.3
–
52.7
52.7
–
11.9
CKT. 1
2
2
2
2
2
2
3
3
3
CKT. 2
–
–
–
–
2
2
3
3
3
17
17
13
13
17
17
17
17
13
CKT. 1
2
2
2
2
2
2
2
2
2
CKT. 2
–
–
–
–
2
2
2
2
2
REFRIGERANT CIRCUITS
REFRIG. CHG, OPT, R-410A (KG)
CKT1/CKT2
OIL CHARGE, LITERS CKT1/CKT2
ALUM. FIN COILS,
SHIPPING
KG
COPPER FIN COILS,
WEIGHT
KG
ALUM. FIN COILS,
OPERATING
KG
COPPER FIN COILS,
WEIGHT
KG
COMP. 1
COMP. 2
NOMINAL
COMP. 3
COMP.
COMP. 4
CAPACITY
COMP. 5
COMP. 6
TOTAL FACE AREA M2
CONDENSER
NUMBER
OF ROWS
DEEP
FINS PER INCH
CONDENSER
FANS, LOW
SOUND
CONDENSER
FANS, ULTRA
QUIET
NUMBER
OF FANS
15.9/15.9 18.1/15.9 20.4/20.4 22.7/22.7 29.5/29.5
FAN POWER KW/FAN
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
FAN RPM
950
950
950
950
950
950
950
950
950
TOTAL CHILLER L/S
NUMBER
OF FANS
4195
4195
9672
9672
18641.7
18641.7
20450.7
20450.7
20450.7
CKT. 1
NA
NA
NA
NA
2
2
2
2
2
CKT. 2
NA
NA
NA
NA
2
2
2
2
2
FAN POWER KW/FAN
NA
NA
1.5
1.5
1.5
1.5
1.5
1.5
1.5
FAN RPM
NA
NA
690
690
690
690
690
690
690
TOTAL CHILLER L/S
NA
NA
9672
9672
18641.7
18641.7
20450.7
20450.7
20450.7
JOHNSON CONTROLS
37
FORM 150.63-EG5 (1017)
Dimensions
All dimensions in English unless otherwise noted
5/8” DIA MOUNTING HOLES (TYP)
LD19644
38
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in English unless otherwise noted
UNIT DIMENSIONS
60 HZ MODEL
LENGTH
L
WIDTH
W
HEIGHT
H
F
P
SUCTION IN 1
CONNECTION
SUCTION IN 2
SIZES
LIQUID OUT 1 / 2
SYSTEM 1
SUCTION IN
LIQUID OUT
DIMMENSIONS
SUCTION IN
LIQUID OUT
SYSTEM 2
D1
D2
DIMMENSIONS
D3
D4
I1
I2
I3
I4
ISOLATOR
I5
LOCATION
I6
DIMENSIONS
I7
I8
A
B
R1
R2
RIGGING HOLE
LOCATIONS
R3
R4
X
UNIT COG
Y
JOHNSON CONTROLS
YCUL0020EE
109.79
44.7
46.06
YCUL0024EE
109.79
44.7
46.06
YCUL0031EE
118.6
44.7
50
YCUL0035EE
118.6
44.7
50
12.7
1.6
12.7
1.6
16.7
2.1
16.7
2.1
0.9
37.7
31.7
0.9
37.7
31.7
1.1
6.2
23.1
1.1
3.9
34.6
30.4
6.0
30.4
6.0
28.9
6.5
19.8
5.8
17
104.2
17
104.2
17
113.3
17
113.3
1.1
43.3
15.6
97.1
1.1
43.3
15.6
97.1
1.1
43.3
15.6
105.1
1.1
43.3
15.6
105.1
58.6
22.9
58.5
22.9
63.1
22.9
67.1
23.1
39
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in SI unless otherwise noted
5/8” DIA MOUNTING HOLES (TYP)
LD19644
40
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in SI unless otherwise noted
UNIT DIMENSIONS
50 HZ MODEL
LENGTH
L
WIDTH
W
HEIGHT
H
F
P
SUCTION IN 1
CONNECTION
SUCTION IN 2
SIZES
LIQUID OUT 1 / 2
SYSTEM 1
SUCTION IN
LIQUID OUT
DIMMENSIONS
SUCTION IN
LIQUID OUT
SYSTEM 2
D1
D2
DIMMENSIONS
D3
D4
I1
I2
I3
I4
ISOLATOR
I5
LOCATION
I6
DIMENSIONS
I7
I8
A
B
R1
R2
RIGGING HOLE
LOCATIONS
R3
R4
X
UNIT COG
Y
JOHNSON CONTROLS
YCUL0020EE
2788.7
1135.4
1169.9
YCUL0024EE
2788.7
1135.4
1169.9
YCUL0031EE
3012.4
1135.4
1270.0
YCUL0035EE
3012.4
1135.4
1270.0
322.6
40.6
322.6
40.6
424.2
53.3
424.2
53.3
22.9
957.6
805.2
22.9
957.6
805.2
27.9
157.5
586.7
27.9
99.1
878.8
772.2
152.4
772.7
152.4
734.1
165.1
503
147.3
431.8
2646.7
431.8
2646.7
431.8
2877.8
431.8
2877.8
27.9
1099.8
396.2
2466.3
27.9
1099.8
396.2
2466.3
27.9
1099.8
396.2
2669.5
27.9
1099.8
396.2
2669.5
1488.4
581.7
1485.9
581.7
1602.7
581.7
1704.3
586.7
41
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in English unless otherwise noted
LD19645
42
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in English unless otherwise noted
UNIT DIMENSIONS
60 HZ MODEL
LENGTH
L
WIDTH
W
HEIGHT
H
F
P
SUCTION IN 1
CONNECTION SUCTION IN 2
SIZES
LIQUID OUT
1/2
SUCTION IN
SYSTEM 1
DIMENSIONS
LIQUID OUT
SUCTION IN
SYSTEM 2
DIMENSIONS
LIQUID OUT
D1
D2
D3
D4
I1
I2
I3
I4
ISOLATOR
I5
LOCATION
I6
DIMENSIONS
I7
I8
A
B
R1
R2
RIGGING HOLE
LOCATIONS
R3
R4
X
UNIT COG
Y
JOHNSON CONTROLS
YCUL0045EE
144.8
90.6
47.8
YCUL0051EE
144.8
90.6
47.8
YCUL0055EE
148.8
90.6
62.6
YCUL0065EE
148.8
90.6
62.6
YCUL0072EE
153.6
90.6
62.6
13.6
2.1
13.6
2.1
28.5
2.1
28.5
2.1
28.5
2.3
2.1
1.1
1.1
1.1
1.1
1.1
48.7
72.9
41.6
17.3
19.6
6.4
48.7
72.9
41.6
17.3
19.7
6.4
52.7
85.1
35.1
14.1
24
9.1
13.8
44.4
85.1
35.1
14.1
9.7
9.1
13.8
53.7
77.6
33.3
15
6.8
5.3
9.2
9.8
135
9.8
135
9.8
135
9.8
135
9.8
143.8
1.1
89.5
15.1
130.9
1.1
89.5
15.1
130.9
1.1
89.5
15.1
130.9
1.1
89.5
15.1
130.8
1.1
89.5
15.1
137.6
59.6
43.6
59.2
43.5
61.9
42.2
61.5
42.2
59.7
44.9
43
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in SI unless otherwise noted
LD19645
44
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Dimensions (Cont'd)
All dimensions in SI unless otherwise noted
UNIT DIMENSIONS
50 HZ MODEL
LENGTH
L
WIDTH
W
HEIGHT
H
F
P
SUCTION IN 1
CONNECTION SUCTION IN 2
SIZES
LIQUID OUT
1/2
SUCTION IN
SYSTEM 1
DIMENSIONS
LIQUID OUT
SUCTION IN
SYSTEM 2
DIMENSIONS
LIQUID OUT
D1
D2
D3
D4
I1
I2
I3
I4
ISOLATOR
I5
LOCATION
I6
DIMENSIONS
I7
I8
A
B
R1
R2
RIGGING HOLE
LOCATIONS
R3
R4
X
UNIT COG
Y
JOHNSON CONTROLS
YCUL0045EE
3677.9
2301.2
1214.1
YCUL0051EE
3677.9
2301.2
1214.1
YCUL0055EE
3779.5
2301.2
1590.0
YCUL0065EE
3779.5
2301.2
1590.0
YCUL0072EE
3901.4
2301.2
1590.0
345.4
53.3
345.4
53.3
723.9
53.3
723.9
53.3
723.9
58.4
53.3
27.9
27.9
27.9
27.9
27.9
1237.0
1851.7
1056.6
439.4
497.8
162.6
1237.0
1851.7
1056.6
439.4
500.4
162.6
1338.6
2161.5
891.5
358.1
609.6
231.1
350.5
1127.8
2161.5
891.5
358.1
246.4
231.1
350.5
1364.0
1971.0
845.8
381.0
172.7
134.6
233.7
248.9
3429.0
248.9
3429.0
248.9
3429.0
248.9
3429.0
248.9
3652.5
27.9
2273.2
383.5
3324.9
27.9
2273.2
383.5
3324.9
27.9
2273.2
383.5
3324.9
27.9
2273.2
383.5
3322.3
27.9
2273.2
383.5
3495.0
1513.8
1107.4
1503.7
1104.9
1572.3
1071.9
1562.1
1071.9
1516.4
1140.5
45
FORM 150.63-EG5 (1017)
Isolator Details
TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR (Y2RS-)
1-1/8”
5/8”
2-3/4”
2-3/4”
3/8” GAP
8
P 4
3/4”
TYP. (4)
3/4”
7/8”
STOP &
4
8-3/8”
OPER.
HEIGHT
4
8
LD18442
MODEL Y2RSI-2D SEISMICALLY RESTRAINED VIBRATION ISOLATOR FOR 2" DEFLECTION
RATED
ALLOWABLE
RATED LOAD
SEISMIC MOUNT
SPRING RATE SOLID LOAD
DEFLECTION
COLOR CODE
G RATING
SIZE
(LBS/IN)
(LBS)
(LBS)
(IN)
HORIZONTAL
Y2RSI-2D-150
150
2.4
62
234
WHITE
34.7
Y2RSI-2D-320
320
2.3
140
490
YELLOW
16.3
Y2RSI-2D-460
460
2.3
200
688
GREEN
11.3
Y2RSI-2D-710
710
2.2
330
1072
DK BROWN
7.3
Y2RSI-2D-870
870
1.9
460
1312
RED
6
Y2RSI-2D-1200N
1200
1.9
638
1818
RED/BLACK
4.3
Y2RSI-2D-1450
1450
1.8
900
2450
TAN
3.6
Y2RSI-2D-1690
1690
1.7
1140
2892
PINK
3.1
Y2RSI-2D-2000N
2000
1.7
1318
3342
PINK/BLACK
2.6
Y2RSI-2D-2640N
2640
1.5
1854
4283
PINK/GRAY
2
PINK/GRAY/
Y2RSI-2D-2870N
3080
1.5
2004
4629
1.7
ORANGE
PINK/GRAY/DK
Y2RSI-2D-3280N
3740
1.8
2134
4930
1.4
BROWN
46
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Isolator Details (Cont'd)
ONE INCH DEFLECTION SPRING ISOLATOR (CPX-X-)
EQUIPMENT
BASE
(BY OTHERS)
POSITIONING
PIN
LD18443
MOUNT
TYPE
CP1
CP2
W
3
3
D
5/8
5/8
DIMENSION DATA (INCHES)
L
B
C
7–3/4
6–1/2
4–3/4
10–1/2
9–1/4
7–3/4
MODEL
NUMBER
CP1-1D-85
CP1-1D-120
CP1-1D-175
CP1-1D-250
CP1-1D-340
CP1-1D-510
CP1-1D-675
CP1-1D-900
CP1-1D-1200
CP1-1D-1360
CP1-1D-1785N
RATED CAPACITY
(LBS.)
85
120
175
250
340
510
675
900
1200
1360
1785
DEFLECTION
RATED (IN)
1.360
1.200
1.170
1.400
1.130
1.020
1.320
1.020
0.900
0.770
0.880
MODEL
NUMBER
CP2-1D-1020
CP2-1D-1350
CP2-1D-1800
CP2-1D-2400
CP2-1D-2720
CP2-1D-3570N
RATED CAPACITY
(LBS.)
1020
1350
1800
2400
2720
3570
DEFLECTION
RATED (IN)
1.020
1.320
1.020
0.900
0.770
0.880
JOHNSON CONTROLS
T
1/2
9/16
H
5–5/8
6
COLOR CODE
LT. PURPLE
DK. YELLOW
DK. BLUE
YELLOW
RED
BLACK
DK. PURPLE
DK. GREEN
GRAY
WHITE
GRAY/RED
COLOR CODE
BLACK
DK. PURPLE
DK. GREEN
GRAY
WHITE
GRAY / RED
47
FORM 150.63-EG5 (1017)
Isolator Details (Cont'd)
ELASTOMERIC ISOLATOR
RD-3
DW
DW
CD
CD
MOLDED
DURULENE
MOLDED
DURULENE
HF
HF
Ø = AD Thru
Typ 2 Places
L
BT
R = 0.280 Slot
Typ 2 Places
BT
AL
W
L
AL
W
LD17304
MOUNT
TYPE
RD3-WR
RD4-WR
L
5.5
(139.7)
6.25
(158.7)
RD3
RD3-BROWN-WR
RD3-BRICK RED-WR
RD3-LIME-WR
RD3-CHARCOAL-WR
RD4
RD4-BROWN-WR
RD4-BRICK RED-WR
RD4-LIME-WR
RD4-CHARCOAL-WR
48
W
3.38
(85.85)
4.63
(117.60)
HF
2.88
(73.15)
2.75
(69.85)
DIMENSION DATA INCHES (mm)
AL
AD
BT
4.13
0.56
0.25
(104.90)
(14.22)
(6.35)
5
0.56
0.38
(127)
(14.22)
(9.65)
RATED CAPACITY
LBS (KG)
250 (113)
525 (238)
750 (340)
1100 (499)
RATED DEFLECTION
IN (MM)
0.5 (12)
0.5 (12)
0.5 (12)
0.5 (12)
RATED CAPACITY
LBS (KG)
1500 (680)
2250 (1021)
3000 (1361)
4000 (1814)
RATED DEFLECTION
IN (MM)
0.5 (12)
0.5 (12)
0.5 (12)
0.5 (12)
CD
1/2-13 UNC X 1
1/2-13 UNC X 1
DW
2.5
(63.5)
3
(76.2)
DURO (± 5)
40
50
60
70
DURO (± 5)
40
50
60
70
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Electrical Notes
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the
largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430‑24. If the optional Factory Mounted Control Transformer
is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: ‑17, add 2.5 amps; ‑28, add 2.3 amps; ‑40, add
1.5 amps, ‑46, add 1.3 amps; ‑58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load
amps for all loads included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor
plus 100% of the rated load amps for all other loads included in the circuit to avoid
nuisance trips at start‑up due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation
at ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based
on 225% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit. Otherwise, HACR‑type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the
rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can
be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on
the National Electrical Code, using copper connectors only. Field wiring must also
comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field
grounding conductor per N.E.C. Table 250‑95. A control circuit grounding lug is also
supplied.
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100,
and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break
Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
JOHNSON CONTROLS
49
FORM 150.63-EG5 (1017)
Electrical Data - 50 & 60Hz
YCUL0020 - YCUL0072
WIRING WITHOUT PUMP See Notes on page 47.
MINIMUM
MIN N/F
CIRCUIT
YCAL VOLT HZ
DISC
AMPS
SW
MCA
0020
0024
0031
0035
0045
0051
0055
0065
0072
50
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
101
94
54
45
45
36
108
100
58
48
48
39
136
136
81
65
64
55
151
140
81
68
67
54
224
209
121
102
99
80
228
212
123
103
101
81
248
248
132
106
114
96
268
267
171
114
130
112
324
301
175
146
143
115
150
100
60
60
60
60
150
150
60
60
60
60
150
150
100
100
100
60
200
150
100
100
100
60
250
250
150
150
150
100
250
250
150
150
150
100
400
400
150
150
150
150
400
400
200
150
150
150
400
400
200
200
200
150
MIN
DUAL
ELEM
FUSE
125
110
60
50
50
40
125
125
70
60
60
45
175
150
90
80
80
70
175
175
90
80
80
60
250
225
150
110
110
90
250
225
150
110
110
90
300
300
150
125
125
110
300
300
200
125
150
125
350
350
200
175
175
125
MAX
DUAL
ELEM
FUSE
MAX CB
125
125
70
60
60
50
150
125
80
60
60
50
175
175
110
90
90
70
200
175
110
90
90
70
250
250
150
110
110
90
250
250
150
110
110
90
300
300
150
125
125
110
300
300
200
125
150
125
400
350
200
175
175
125
SYSTEM 1
COMPR 1 COMPR 2
SYSTEM 2
COMPR 1 COMPR 2
FAN
FAN
RLA LRA RLA LRA QTY FLA LRA RLA LRA RLA LRA QTY FLA LRA
42.2
39
22.5
18.6
18.6
14.9
45.4
42
24.2
20
20
16
55.8
55.8
36
26.9
26.9
23.7
59.9
55.5
32
26.4
26.4
21.1
45.4
42.0
24.2
20.0
20.0
16.0
47.0
43.5
25.1
20.7
20.7
16.6
51.3
51.3
26.9
21.8
23.1
19.9
55.8
55.8
36.0
23.7
26.9
23.7
76.9
71.2
41.1
33.9
33.9
27.1
250
250
155
114
114
100
250
250
155
125
125
100
425
425
239
198
198
148
425
425
239
198
187
148
250
250
155
125
125
100
250
250
155
125
125
100
300
300
139
140
150
109
425
425
239
198
187
148
505
505
280
225
225
180
42.2
39
22.5
18.6
18.6
14.9
45.4
42
24.2
20
20
16
51.3
51.3
26.9
23.1
23.1
19.9
59.9
55.5
32
26.4
26.4
21.1
45.4
42.0
24.2
20.0
20.0
16.0
47.0
43.5
25.1
20.7
20.7
16.6
51.3
51.3
26.9
21.8
23.1
19.9
55.8
55.8
36.0
23.7
26.9
23.7
76.9
71.2
41.1
33.9
33.9
27.1
250
250
155
114
114
100
250
250
155
125
125
100
300
300
189
150
150
109
425
425
239
198
187
148
250
250
155
125
125
100
250
250
155
125
125
100
300
300
139
140
150
109
425
425
239
198
187
148
505
505
280
225
225
180
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7.6
7.4
4.5
4
3.4
2.9
7.6
7.4
4.5
4
3.4
2.9
7.6
7.4
4.5
4
3.4
2.9
7.6
7.4
4.5
4
3.4
2.9
7.6
7.4
4.5
4.0
3.4
2.9
7.6
7.4
4.5
4.0
3.4
2.9
7.6
7.4
4.5
3.4
4.0
2.9
7.6
7.4
4.5
3.4
4.0
2.9
7.6
7.4
4.5
4.0
3.4
2.9
30.9
37
22.3
19
17.2
14.6
30.9
37
22.3
19
17.2
14.6
30.9
37
22.3
19
17.2
14.6
30.9
37
22.3
19
17.2
14.6
30.9
37.0
22.3
19.0
17.2
14.6
30.9
37.0
22.3
19.0
17.2
14.6
44.0
19.1
23.1
17.5
19.0
15.3
44.0
19.1
23.1
17.5
19.0
15.3
30.9
37.0
22.3
19.0
17.2
14.6
45.4
42.0
24.2
20.0
20.0
16.0
45.4
42.0
24.2
20.0
20.0
16.0
51.3
51.3
26.9
21.8
23.1
19.9
55.8
55.8
36.0
23.7
26.9
23.7
59.9
55.5
32.0
26.4
26.4
21.1
250
250
155
125
125
100
250
250
155
125
125
100
300
300
139
140
150
109
425
425
239
198
187
148
425
425
239
198
187
148
45.4
42.0
24.2
20.0
20.0
16.0
45.4
42.0
24.2
20.0
20.0
16.0
51.3
51.3
26.9
21.8
23.1
19.9
55.8
55.8
36.0
23.7
26.9
23.7
59.9
55.5
32.0
26.4
26.4
21.1
250
250
155
125
125
100
250
250
155
125
125
100
300
300
139
140
150
109
425
425
239
198
187
148
425
425
239
198
187
148
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7.6
7.4
4.5
4.0
3.4
2.9
7.6
7.4
4.5
4.0
3.4
2.9
7.6
7.4
4.5
3.4
4.0
2.9
7.6
7.4
4.5
3.4
4.0
2.9
7.6
7.4
4.5
4.0
3.4
2.9
30.9
37.0
22.3
19.0
17.2
14.6
30.9
37.0
22.3
19.0
17.2
14.6
44.0
19.1
23.1
17.5
19.0
15.3
44.0
19.1
23.1
17.5
19.0
15.3
30.9
37.0
22.3
19.0
17.2
14.6
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Electrical Data - 50 & 60Hz (Cont'd)
LUG RANGE
YCAL HZ VOLT
0020
0024
0031
0035
0045
0051
0055
0065
0072
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
60
60
60
50
60
60
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
200
230
380
400
460
575
FIELD WIRING LUGS6
TERMINAL BLOCK (STD)
FIELD WIRING LUGS6
NF DISC. SWITCH (OPT)
FIELD WIRING LUGS6
CIRCUIT BREAKER (OPT)
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
6 AWG – 350 kcmil
6 AWG – 350 kcmil
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
6 AWG – 350 kcmil
6 AWG – 350 kcmil
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
6 AWG – 350 kcmil
6 AWG – 350 kcmil
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
6 AWG – 350 kcmil
6 AWG – 350 kcmil
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
6 AWG – 350 kcmil
6 AWG – 350 kcmil
14 AWG – 2/0
14 AWG-2/0, PB-0800
14 AWG – 2/0
14 AWG – 2/0
4 AWG – 500 kcmil
4 AWG – 500 kcmil
6 AWG – 350 kcmil
6 AWG-350kcmil, PB-0801
6 AWG – 350 kcmil
6 AWG – 350 kcmil
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
4 AWG – 300 kcmil
4 AWG – 300 kcmil
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
4 AWG – 300 kcmil
4 AWG – 300 kcmil
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
4 AWG – 300 kcmil
4 AWG – 300 kcmil
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
4 AWG – 300 kcmil
4 AWG – 300 kcmil
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
4 AWG – 300 kcmil
4 AWG – 300kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
4 AWG – 300 kcmil
250 kcmil – 500 kcmil
250 kcmil – 500 kcmil
6 AWG – 350 kcmil
6 AWG – 350 kcmil
6 AWG – 350 kcmil
6 AWG – 350 kcmil
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
6 AWG – 350MCM
6 AWG – 350MCM
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
6 AWG – 350MCM
6 AWG – 350MCM
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
6 AWG – 350MCM
6 AWG – 350MCM
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
6 AWG – 350MCM
6 AWG – 350MCM
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
14 AWG – 1/0
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
*(2) 3/0 – 250 kcmil
*(2) 3/0 – 250 kcmil
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
250 kcmil – 500 kcmil
250 kcmil – 500 kcmil
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
6 AWG – 350MCM
JOHNSON CONTROLS
51
FORM 150.63-EG5 (1017)
Electrical Data - 50 & 60Hz (Cont'd)
UNIT VOLTAGE
MODELS W/O
CONTROL
TRANSFORMER
MODELS W/
CONTROL
TRANSFORMER
CONTROL
POWER
MCA1
115-1-60/50
-17
UNIT
VOLTAGE
OVER CURRENT PROTECTION2
NF DISC SW
MIN
MAX
15A
10A
15A
30 A / 240V
200-1-60
15A
10A
15A
30 A / 240V
-28
230-1-60
15A
10A
15A
30 A / 240V
-40
380-1-60
15A
10A
15A
30 A / 480V
-46
460-1-60
15A
10A
15A
30 A / 480V
-50
380/415-1-60
15A
10A
15A
30A / 415V
-58
575-1-60
15A
10A
15A
30 A / 600V
1. Minimum #14 AWG, 75°C, Copper Recommended
2. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
VOLTAGE CODE
-17
-28
-40
-46
-50
-58
LEGEND
ACR
C.B.
D.E.
DISC SW
FACT MOUNT CB
FLA
HZ
MAX
MCA
MIN
MIN
RLA
S.P. WIRE
UNIT MTD SERV SW
LRA
52
UNIT POWER
200-3-60
230-3-60
380/415-3-60
460-3-60
380/415-3-50
575-3-60
MIN.
180
207
342
414
342
517
MAX.
220
253
440
506
440
633
LINE ACROSS THE LINE START
CIRCUIT BREAKER
DUAL ELEMENT FUSE
DISCONNECT SWITCH
FACTORY MOUNTED CIRCUIT BREAKER
FULL LOAD AMPS
HERTZ
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MINIMUM
NF MINIMUM NON FUSED
RATED LOAD AMPS
SINGLE POINT WIRING
UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT
LOCKED ROTOR AMPS
SWITCH)
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Circuit Breaker Calculations
Max Dual Elem Fuse Max CB (MOP)
= 2.25 x Current of largest motor + ∑ (remaining FLAs or RLAs)
For this name plate the formula below was used:
= 2.25 * RLACpr1 + RLACpr2 + RLACpr3 + Qty* RLAFans + 0.49 + FLAPump
This formula will calculate the ACTUAL MOP but a table is referenced to provide the appropriate MOP.
ACTUAL
MINIMUM
MAXIMUM
COLUMN
COLUMN
COLUMN
Using an approximate match, look up the value of the
A
B*
C
calculated ACTUAL MOP in Column A. Find the largest
0
15
0
value i.e. less than or equal to the value in Column A.
15
20
15
Once found, the value in Column C which shares the
20
25
20
same row is the valued USED in the system. e.g. e.g.
25
30
25
Using the same example that was used to calculate the
30
35
30
MCA, calculate the MOP:Ans. ACTUAL = 2.25*20.4 +
35
40
35
20.4 + 0 + 2*2.6 + 5.29
= 45.9 + 30.89
40
45
40
45
50
45
= 76.79Comparing against values in Column A: 70 < 76.79
50
60
50
< 80, therefore the USED MOP found in Column C is 70.
60
70
60
70
80
70
80
90
80
90
100
90
100
110
100
110
125
110
125
150
125
150
175
150
175
200
175
200
225
200
225
250
225
250
300
250
300
350
300
350
400
350
*NOTE: Column B is used if one were calculating the Minimum Dual Elem Fuse which is not relevant to this exercise.
JOHNSON CONTROLS
53
FORM 150.63-EG5 (1017)
Application Data
UNIT LOCATION
The YCUL Condensing Units are designed for outdoor installation. When selecting a site
for installation, be guided by the following conditions:
1. For outdoor locations of the unit, select a place having an adequate supply of fresh
air for the condenser.
2. Avoid locations beneath windows or between structures where normal operating
sounds may be objection­able.
3. Installation sites may be either on a roof, or at ground level. (See FOUNDATION,
below.)
4. The condenser fans are the propeller-type, and are not recommended for use with
duct work in the condenser air stream.
5. When it is desirable to surround the unit(s), it is recom­mended that the screening
be able to pass the required chiller CFM without exceeding 0.1” of water external
static pressure.
6. Protection against corrosive environments is available by supplying the units with
either copper fin, cured phenolic, or epoxy coating on the condenser coils. The phenolic or epoxy coils should be offered with any units being installed at the seashore
or where salt spray may hit the unit.
In installations where winter operation is intended and snow accumulations are expected,
additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in DIMEN­SION DRAWINGS. When the
available space is less, the unit(s) must be equipped with the discharge pressure transducer option to permit high pressure unloading in the event that air recirculation were to
occur.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of supporting the entire operating weight of the equipment. Operating weights are given in the
PHYSICAL DATA tables.
Roof Locations – Choose a spot with adequate struc­tural strength to safely support the
entire weight of the unit and service personnel. Care must be taken not to damage the roof
during installation. If the roof is “bonded”, consult the building contractor or architect for
special installation requirements. Roof installations should incorporate the use of springtype isolators to minimize the transmission of vibration into the building structure.
Ground Level Installations – It is important that the units be installed on a substantial
base that will not settle, causing strain on the refrigerant lines and resulting in possible
leaks. A one-piece concrete slab with footers extending below the frost line is highly recommended, particularly in areas where winters are long and very cold. Additionally, the
slab should not be tied to the main build­ing foundation as noises will telegraph.
54
JOHNSON CONTROLS
Application Data (Cont'd)
FORM 150.63-EG5 (1017)
Mounting holes (11/16” diameter) are provided in the steel channel for bolting the unit to
its foundation. See DIMENSION DRAWINGS.
For ground level installations, precautions should be taken to protect the unit from tampering by or injury to unau­thorized persons. Screws on access panels will prevent casual
tampering; however, further safety precautions, such as unit enclosure options, a fencedin enclosure, or locking devices on the panels may be advisable. Check local authorities
for safety regulations.
REFRIGERANT PIPING
When sizing refrigerant pipe for split system air condition­ing, consideration must be given
to the: (1) Suction line pressure drop due to friction, (2) Liquid line pressure drop due to
friction, (3) Suction line velocity for oil return, and (4) Liquid line pressure drop due to vertical rise. Refer to DESIGN PARAMETERS for friction losses for both the suction and liquid
lines for the condensing unit.
On a system where the evaporator blower is located below the condensing unit, the suction line must be sized for both pressure drop and oil return.
When the condensing unit is located below the evapora­tor blower, the liquid line must be
designed for pressure drop due to friction loss and vertical rise. If the pressure drop due to
vertical rise and friction loss exceeds 30 psig (2.1 barg), some refrigerant will flash before
it reaches the thermal expansion valve.
All horizontal suction lines should be pitched at least 1/4 inch (6 mm) per foot in the direction of the refrigerant flow to aid the return of oil to the compressor. All suction lines with
a vertical rise exceeding 3 feet (1 m) should have a ‘P’ trap at the bottom and the top to
facilitate oil return. Suction lines with a vertical rise exceeding 25 feet (7.6 m) should be
trapped every 15 feet (4.6 m) to provide drain points for the oil when the circuit is deactivated. When the circuit is reactivated, oil will return to the compressor more quickly and
in smaller slugs.
For more details, refer to ASHRAE Refrigeration Hand­book, System Practices for Halocarbon Refrigerants.
JOHNSON CONTROLS
55
FORM 150.63-EG5 (1017)
Guide Specifications
PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, Division 1,
and Drawings apply to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, condensing
units of the scheduled capacities as shown and indicated on the Drawings, including
but not limited to:
1. Condensing Unit package
2. Electrical power and control connections
3. DX Central Station Air Handling connections
1.02 QUALITY ASSURANCE
A. Products shall be Designed, Tested, and installed in compliance with applicable sections of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration
2. ASHRAE 90.1 - Energy efficiency compliance.
3. ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
4. Conform to Intertek Testing Services, formerly ETL, for construction of condensing
units and provide E.T.L./c E.T.L. Listing label.
5. Manufactured in facility registered to ISO 9002.
B. Factory Test: Condensing Unit shall be pressure tested, evacuated and given a nitrogen holding charge and an initial oil charge, and shall be factory operational run tested
to assure each control device operates properly.
C. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of one year from date of initial
start-up or eighteen (18) months from date of shipment, whichever occurs first.
1.03 DELIVERY AND HANDLING
A. Unit shall be delivered to job site fully assembled, and given nitrogen holding charge
and a full oil charge by the Manufacturer. (R-410A refrigerant supplied by others).
B. Unit shall be stored and handled per Manufacturer’s instructions.
56
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
PART 2 - PRODUCTS
2.01 CONDENSING UNITS MATERIALS AND COMONENTS
A. General: Install and commission, as shown on the schedules and plans, factory assembled, charged, and tested air cooled scroll compressor condensing unit as specified herein. Condensing Unit shall be designed, selected, and constructed using a
refrigerant with Flammability rating of “1”, as defined by ANSI/ASHRAE STANDARD
- 34 Number Designation and Safety Classification of Refrigerants. Condensing Unit
shall include, but is not limited to: not less than two refrigerant circuits, scroll compressors, air-cooled condenser, refrigerant, lubrication system, interconnecting wiring,
safety and operating controls including capacity controller, control center, motor starting components, and special features as specified herein or required for safe, automatic operation.
B. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000
hour, 5% salt spray test, yields minimum ASTM 1654 rating of “6”.
2.02 COMPRESSORS
A. Compressors: Shall be hermetic, scroll-type, including:
1. Compliant design for axial and radial sealing.
2. Refrigerant flow through the compressor with 100% suction cooled motor.
3. Large suction side free volume and oil sump to provide liquid handling capability.
4. Compressor crankcase heaters to provide extra liquid migration protection.
5. Annular discharge check valve and reverse vent assembly to provide low pressure
drop, silent shutdown and reverse rotation protection.
6. Initial Oil charge.
7. Oil Level sightglass.
8. Vibration isolator mounts for compressors.
9. Brazed-type connections for fully hermetic refrigerant circuits.
2.03 REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All unit piping will be
copper, with brazed joints. The liquid line will include a field connection shutoff valve with
charging port located on each condenser circuit. Suction line connections are provided
on each refrigeration circuit. Filter drier and sight glass are shipped loose for field installation on each refrigerant circuit. All expansion valves and liquid line solenoid valves and
refrigerant field piping are supplied by others.
JOHNSON CONTROLS
57
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
2.04 HEAT EXCHANGERS
A. Air Cooled Condenser:
1. Coils: Internally enhanced, seamless copper tubes, mechanically expanded into
aluminum alloy fins with full height collars. Subcooling coil an integral part of condenser. Design working pressure shall be 650 psig (45 barg).
2. Fans: Shall be dynamically and statically balanced, direct drive, corrosion resistant
glass fiber reinforced composite blades molded into low noise, full airfoil cross section, providing vertical air discharge from extended orifices for efficiency and low
sound. Each fan in its own compartment to prevent cross flow during fan cycling.
Guards of heavy gauge PVC (polyvinyl chloride) coated steel.
3. Fan Motors: High efficiency, direct drive, 6 pole, 3 phase, insulation class “F”,
current-protected, Totally Enclosed Air-Over (TEAO), rigid mounted, with double
sealed, permanently lubricated, ball bearings.
2.05 CONTROLS
A. General: Automatic start, stop, operating, and protection sequences across the range
of scheduled conditions and transients.
B. Microprocessor Enclosure: Rain and dust tight NEMA 3R/12 (IP55) powder painted
steel cabinet with hinged, latched, and gasket sealed door.
C. Microprocessor Control Center:
1. Condensing Unit control is set for Discharge Air Temperature Control
2. Automatic control of compressor start/stop, anti-coincidence and anti-recycle timers, automatic pump-down shut-down, condenser fans, unit alarm contacts, and
condensing unit operation from 0°F to 125°F (-18°C to 52°C) ambient. Automatic
reset to normal chiller operation after power failure.
3. Software stored in non-volatile memory, with programmed set-points retained in
lithium battery-backed real time clock (RTC) memory for minimum 5 years.
4. Forty character liquid crystal display, descriptions in English (or Spanish, French,
Italian, or German), numeric data in English (or Metric) units. Sealed keypad with
sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch.
5. Programmable Set-points (within Manufacturer limits): display language; suction pressure setting and control range, remote reset temperature range, set daily
schedule/holiday for start/stop, manual override for servicing, low and high ambient cutouts, number of compressors, low suction pressure cutout, high discharge
pressure cutout, anti-recycle timer (compressor start cycle time), and anticoincident
timer (delay compressor starts).
6. Display Data: Suction temperatures (optional), low ambient temperature cutout setting, outdoor air temperature, English or metric data, suction pressure cutout setting,
each system suction pressure, discharge pressure (optional), discharge air reset via
Building Automation System (by others) via a 4-20milliamp or 0-10 VDC input with
58
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
optional BAS interface, anti-recycle timer status for each system, anti-coincident
system start timer condition, compressor run status, no cooling load condition, day,
date and time, daily start/stop times, holiday status, automatic or manual system
lead/lag control (when controlling based on Discharge Air Temperature only), automatic lead/lag of compressors within a system, compressor starts/operating hours
(each), status of hot gas valves, and fan operation, run permissive status, number
of compressors running, liquid solenoid valve status, load & unload timer status.
7. System Safeties: Shall cause individual compressor systems to perform auto shut
down; manual reset required after the third trip in 90 minutes. Includes: high discharge pressure, low suction pressure, high pressure switch, and motor protector.
Compressor motor protector shall protect against damage due to high input current
or thermal overload of windings.
8. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low
ambient, or under voltage.
9. Alarm Contacts: Low ambient, low voltage, low battery, and (per compressor circuit): high discharge pressure, and low suction pressure.
10. High Ambient Control: Permits unit operation above 115°F (46°C) ambient.
D. Manufacturer shall provide any controls not listed above, necessary for automatic condensing unit operation. Mechanical Contractor shall provide field control wiring necessary to interface sensors to the condensing unit control system.
2.06 POWER CONNECTION AND DISTRIBUTION
A. Power Panels:
1. NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged,
latched, and gasket sealed outer doors. Provide main power connection(s), control
power connections, compressor and fan motor start contactors, current overloads,
and factory wiring.
2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage,
and connect to individual terminal blocks per compressor. Separate disconnecting
means and/or external branch circuit protection (by Contractor) required per applicable local or national codes.
B. Exposed compressor, control and fan motor power wiring shall be routed through liquid
tight conduit.
2.07 ACCESSORIES AND OPTIONS
Some accessories and options supercede standard product features. Your YORK representative will be pleased to provide assistance.
A. Microprocessor controlled, Factory installed Across-the-Line type compressor motor
starters as standard.
B. Outdoor Ambient Temperature Control
1. Low Ambient Control: Permits unit operation to 0°F (-18°C) ambient. Standard unit
controls to 32°F (0°C) ambient.
JOHNSON CONTROLS
59
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
C. Power Supply Connections:
1. Single Point Power Supply: Single point Terminal Block for field connection and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring, which must comply with the National
Electric Code and/or local codes.
2. Single Point: Single point Non-Fused Disconnect(s) and lockable external handle
(in compliance with Article 440-14 of N.E.C.) can be supplied to isolate the unit
power voltage for servicing. Separate external fusing must be supplied, by others,
in the in coming power wiring, which must comply with the National Electric Code
and/or local codes.
3. Single Point Circuit Breaker: Single point Terminal Block with Circuit Breaker and
lockable external handle (in compliance with Article 44014 of N.E.C.) can be supplied to isolate power voltage for servicing. Incoming power wiring must comply with
the National Electric Code and/or local codes.
D. Pressure & Temperature Transducers and Sensors
1. Discharge Pressure Transducers: Permits unit to sense and display discharge pressure.
2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.
3. Suction Temperature Sensors: Permits units to sense and display suction temperature.
E. Control Power Transformer: Converts unit power voltage to 120-1-60 or 120-1-50 for
50Hz units (500 VA capacity). Factory mounting includes primary- and secondary-wiring between the transformer and the control panel.
F. Motor Current Module: Capable of monitoring compressor motor current. Provides extra protection against compressor reverse rotation, phase-loss and phase imbalance.
Options consists of one module per electrical system. (Factory mounted)
G. Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.90-0.95.
H. Condenser Coil Environmental Protection:
1. Pre-Coated: Epoxy coated aluminum fin stock to guard from corrosive agents and
insulate against galvanic potential. For mild seashore or industrial locations
2. Copper Fin: Provide copper fins in lieu of aluminum.
3. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and
other corrosive applications (with the exception of strong alkalis, oxidizers, and wet
bromine, chlorine and fluorine in concentrations greater than 100ppm).
I. Protective Condensing Unit Panels (Factory or Field Mounted):
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabinet, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, coated to resist corrosion,
to protect condenser coils from incidental damage and restrict unauthorized access
to internal components.
60
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect
condenser coils from incidental damage,visually screen internal components, and
prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces,
painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated
to resist corrosion, around base of machine to restrict unauthorized access.
J. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve
in compliance with ASHRAE15. (Factory-mounted.)
K. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the minimum step of unloading to as low as 5% capacity (depending on both the unit & operating conditions) by introducing an artificial load. Hot gas by-pass is installed on only
refrigerant system 1 on two circuited units.
L. Microprocessor Membrane Keypad Graphics on in lieu of Standard English:
1. French language.
2. German language.
3. Spanish language.
4. Italian language.
M. Chicago Code Relief Valves to meet Chicago Code requirements.
N. Building Automation System (EMS) Reset Interface: Condensing Unit to accept 4 to
20mA, 0 to 10 VDC, input to reset the discharge air temperature.
O. Sound Reduction (Factory Mounted):
1. Low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets
P. Vibration Isolation (Field Mounted):
1. Neoprene Pad Isolators.
2. 1 Inch Deflection Spring Isolators: Level adjustable, spring and cage type isolators
for mounting under the unit base rails.
3. 2 Inch Deflection Seismic Isolators: Level adjustable, restrained mounts in rugged
welded steel housing with vertical and horizontal limit stops. Housings shall be designed to withstand a minimum 1.0g accelerated force in all directions to 2 inches.
JOHNSON CONTROLS
61
FORM 150.63-EG5 (1017)
Guide Specifications (Cont'd)
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: Rig and Install in full accordance with Manufacturers requirements, Project
drawings, and Contract documents.
B. Location: Locate condensing unit as indicated on drawings, including cleaning and
service maintenance clearance per Manufacturer instructions. Adjust and level condensing unit on support structure.
C. Components: Installing Contractor shall provide and install all auxiliary devices and
accessories for fully operational condensing unit.
D. Electrical: Coordinate electrical requirements and connections for all power feeds with
Electrical Contractor (Division 16).
E. Controls: Coordinate all control requirements and connections with Controls Contractor.
F. Finish: Installing Contractor shall paint damaged and abraded factory finish with touchup paint matching factory finish.
62
JOHNSON CONTROLS
FORM 150.63-EG5 (1017)
Notes
JOHNSON CONTROLS
63
Printed on recycled paper
Form 150.63-EG5 (1017) Supersedes: 150.63-EG5 (715)
© 2015 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com