Legrand 2400 Series Small Raceway Entrance End Fitting - V2410A Installation Instruction

Legrand 2400 Series Small Raceway Entrance End Fitting - V2410A Installation Instruction
V2410A Entrance
End Fitting
Installation Instructions
V2400B
V2410A
Entrance
End Fitting
2 1/2"
END FEEDING FROM FLEXIBLE OR RIGID METAL CONDUIT
Mount V2400 Base and harness on surface with No. 10 Panhead screws.
Insert V2410A Entrance End Fitting base into end of V2400B raceway base. Assemble
1/2" connector (not supplied) in V2410A and bring in feed cable with wires extending
at least 2 1/2" beyond connector.
Connect green conductor in feed which is connected directly to the service grounding
terminal, using approved method for equipment grounding connections. Connect black
and white harness wires to black and white feed wires with W30 Wire Connectors
(available separately) inserting only conductors of same color in a connector. See
“W30 Wire Connectors . . . How to Use” DO NOT USE W30 WIRE CONNECTORS
WITH GROUND WIRES. Any unused wire leads must be individually closed up with a
wire nut. DO NOT CONNECT UNUSED LEADS TOGETHER.
Snap V2410A Fitting Cover onto raceway base. Cut raceway cover to fit and snap onto
raceway base.
W30 Wire Connectors . . . How to Use
W30 pressure type connectors
(available separately) are for common connection of 2, 3, or 4 No. 12
or No. 14 solid conductors:
NOT TO BE USED TO CONNECT GROUNDING CONDUCTORS.
The Wiremold Company
In U.S.:
60 Woodlawn Street • West Hartford, CT 06133-2500
1-800-621-0049 • FAX 860-232-2062
©1996 The Wiremold Company