INSTALLATION
Install the sensor on the side wall of the skylight well
as shown in the Wiring diagram. The sensor housing is
equipped with a ½" NPT nipple and will thread into any
suitable box or fitting, or mount into a ½" knockout. This
sensor is also suitable for use in atrium or clerestory
applications where high sunlight levels are common.
MAINTENANCE
At least once every two months wipe the lens clean
with a non-scratching clean cloth. Check the housing
for damage and that no moisture has penetrated the
sensor, as this will likely render it inoperable.
DLM Local Network
Example 1
LMPS-6000
Skylight
Photocell
LMIO-301
SPECIFICATIONS:
Footcandle range LMPS-6000 . . . . . . . . . . . 24 - 6000 fc
Calibration . . . . . .None, controlled by system software
Input voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24VDC
Sensor output . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10VDC
Peak current . . . . . . . . . . . . . . . . . . . .4.5 mA Maximum
Slew rate . . . . .1 minute full scale response time filter
Operating temperature -40˚F to 140˚F (-40˚C to 60˚C)
Wire color code
Red . . . . . . . . . . . . . . . . . . . . Input Voltage +24 VDC
Black . . . . . . . . . . . Input Return/Output Common
Yellow . . . . . . . . . . . . . . . . . 1-10VDC Output Signal
Housing
UV stabilized plastic with dome lens
Mounting . . . . . . . . . . . . . . . . . . . . . ½" NPT x .69" stem
Overall dimensions . . . . . . . . . . . . .2.55"L x 1.28"D
Line Voltage
WIRING
LMRJ Cables
Switch
Connect the sensor to the LMIO-301 as shown.
LMRC-3xx
Room Controller
w/ Network
J-Box
Bridge
0-10 Volt
Ballast
0-10 Volt
Ballast
Skylight
Well
LM-MSTP Wire
Occupancy Sensor
Vertical
Orientation
Option
Segment Manager
or BACnet BAS
Example 2
LMPS-6000
Skylight
Photocell
LMIO-301
LMPS-6000
Skylight Photocell
LMRC-102
Room
Controller
Line Voltage
1
LMRJ Cables
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
2
J-Box
Switch
LM-MSTP
Wire
LMIO-301
Loads
LMIO-301 Terminals
1
2
3
4
5
6
7
8
9
10
Segment Manager
or BACnet BAS
Common (Black)
Occupancy Sensor
+24VDC Input Voltage (Red)
1-10VDC Output Signal (Yellow)
LMBC-300
Network Bridge
2800 De La Cruz Blvd.
Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com
6/2010
13822r1
Please
Recycle
Installation Instructions
DESCRIPTION
The LMPS-6000 is a daylight sensor specifically
designed to be used in conjunction with a LMIO-301
DLM Photocell Input Module. The LMIO-301 converts
the 10 VDC signal from the photocell sensor to a digital
signal that is shared across the DLM Local Network.
The signal is forwarded as a BACnet object via a DLM
network bridge to the segment network for load control
via a DLM segment manager or BACnet compatible
Building Automation System (BAS).