Legrand FSP-2x1 Data Sheet

Legrand FSP-2x1 Data Sheet
WATTSTOPPER®
| FSP-2X1
HIGH/LOW/OFF PIR FIXTURE INTEGRATED OUTDOOR
PHOTO/MOTION SENSOR
Models
FSP-201, 12–32VDC
Use with dim-to-off driver or ballast
or with Wattstopper power pack
FSP-211, 120/277VAC, 230–240VAC
(single phase), 50/60Hz
FSP-221, 100–347VAC (single phase)
or 208/230/480VAC (phase-to-phase)
Specifications and Features
FSP-211
*
FSP-201
FSP-221
Current consumption (FSP-201):
15 mA max.
0-10V sinking current: 50mA
Product Overview
The FSP-2x1 series are passive
infrared (PIR) outdoor sensors that
raise or lower the electric lighting level
to high, low or off based on motion
and/ or daylight contribution. Typically,
once the sensor stops detecting
movement and the time delay elapses,
lights will first fade to low mode, and
eventually switch off. When motion is
detected, the sensor ramps the light
level to high mode unless the daylight
contribution is sufficient. The integral
photocell can also switch the lights
on and off for dusk to dawn control so
that lighting remains on overnight even
without motion detection.
These slim, low-profile sensors are
designed for installation inside the
bottom of a light fixture body and is UL
listed for use in wet and cold locations.
Initial setup and subsequent sensor
adjustments are made using a wireless
handheld configuration tool (FSIR-100).
This tool enables adjustment of sensor
parameters including high/low mode,
sensitivity, time delay, cut off and more.
The FSIR-100 can read current
parameter settings and stores up to
six sensor parameter profiles to speed
commissioning of multiple sensors.
*PEP designation applies
to FSP-211 only
FSP-2x1 sensor module
PIR Sensor
Load Ratings (FSP-311, FSP-321):
@ 120V 0–800W tungsten, ballast, LED
driver; 1/6hp motor
@ 230–240V 0–300W ballast, LED driver
@ 277V 0–1200W ballast, LED driver;
1/6hp motor
@ 347/480V 0–1200W ballast, LED
driver, 1/6hp motor (FSP-321 only)
Light Sensor
Three interchangeable lenses for
mounting between 8’ and 40’
Remote setup and adjustment with
handheld wireless configuration tool
Adjustable high and low modes (high:
0 to 10V, low: off, 0 to 9.8V)
Adjustable time delay (30 seconds, 5 to
30 minutes)
Adjustable cut off delay (none, 1 to 60
minutes, 1 to 5 hours)
Adjustable sensitivity (low, med, max)
Adjustable setpoints: hold off setpoint
(none, 1 to 250 fc, auto); photocell on/
off setpoint (1 to 250 fc)
Adjustable ramp and fade times
(1 to 60 seconds)
Lead length (FSP-221): 36” (91.44cm)
Operating temperature: -40°F to
+167°F (-40°C to +75°C)
Weight: FSP-201, 2.1 oz (59 g);
FSP-211 2.8 oz (80 g),
FSP-221, 5.5 oz (155 g)
UL and cUL listed; CE; TUV listed
IP66 rated
Motion Indicator
Red LED
Sensor Protection Cap
IR Transmitter
FSIR-100 is FCC Part 15 compliant
Five year warranty
Materials
IR Receiver
Polycarbonate, flame retardant, UV
resistant, Impact resistant, Recyclable
Meets materials restrictions of RoHS
Factory Defaults
NOTE: Remove Cap before use
1
WWW.LEGRAND.US/WATTSTOPPER
High mode:
Low mode:
Time delay:
Cut off:
Setpoint:
Sensitivity:
Ramp up time:
Fade down time:
Photocell On/Off:
10V
1V
5 minutes
1 hour
Disabled
Max
Disabled
Disabled
Disabled
WATTSTOPPER®
Dimensions
1.4”
35mm
1.7”
44mm
0.9”
23mm
.65”
16mm
0.6”
15mm
1.1”
29mm
1.6”
41mm
1.7”
42mm
1.3”
33mm
3.7”
3.9” 94mm
99mm
3.8”
96mm
30'
20'
10'
0'
FSP-201 & FSP-211
60 ft
FSP-221
10'
Coverage
20'
30'
20'
20'
10'
0'
10'
20'
10'
FSP-L2 top and side
coverage patterns
0'
0'
60 ft
8'
10'
24'
11' 7' 3' 0' 3' 7' 11'
24'
20'
20'
10'
0'
10'
20'
20'
Ceiling
0'
FSP-L3 top and side
coverage patterns
0'
8'
10'
24'
11' 7' 3' 0' 3' 7' 11'
24'
5'
0'
40 ft
10'
10'
15'
20'
20'
10'
0'
10'
20'
20'
20' 18' 15' 12' 9'
6'
3' 0' 3'
6'
10'
10'
9' 12' 15' 18' 20'
50'
FSP-L7 top and side
coverage patterns
25'
0'
100 ft
0'
15'
27'
25'
40'
50'
WWW.LEGRAND.US/WATTSTOPPER
50'
25'
0'
25'
50'
40'
30'
20'
0'
20'
30'
40'
50'
50'
2
WATTSTOPPER®
Dimensions of Lens Options
2.33"
59.2mm
3.2"
81.3mm
2.33”
59.2mm
0.78"
19.7mm
0.78”
19.7mm
1.04"
26.4mm
FSP-L2 dimensions
FSP-L3 dimensions
FSP-L7 dimensions
FSP‑L2-S, FSP-L3-S, and FSP-L7-S Dimensions
The FSP-Lx-S models include a shroud, which blocks high-angle light coming from the fixture, to improve photocell
performance. With the shroud attached, the dimensions for all three lenses are identical
FSP-L2-S and FSP-L3-S
FSP-L7-S
4.3”
(110mm)
4.3”
(110mm)
1.06”
(27mm)
1.06”
(27mm)
Installing the FSP-2x1 Sensor in Light Fixture
1. Determine an appropriate mounting location inside
the light fixture. Allow a minimum distance of 0.2”
(5.1mm) from the end of the sensor to the wall of
the fixture.
4. Align the locking features between the sensor and
lens module and push the lens module forward until
the 0-ring seals firmly. Turn the lens module clockwise to lock in place.
2. Drill a 1.31” (33.3mm) diameter hole through the
sheet metal in the bottom of the fixture.
5. Connect load, supply and control wires
3. Place the rubber gasket on the threaded collar, and
install the sensor face down, parallel to the mounting surface. Ensure the rubber gasket touches the
inside surface of the fixture. Install the tightening nut
securely against the fixture and torque to 25-30 in-lbs
to maintain IP rating.
WWW.LEGRAND.US/WATTSTOPPER
6. Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the
tightening nut on the FSP-2x1
NOTE: An optional shroud with integrated lens can be
installed instead of the collar and a regular lens.
The shroud blocks high-angle light coming from
the fixture, to improve photocell performance.
WATTSTOPPER®
FSP-201/211
LED
Controller
Tightening Nut
Lens Assembly
FSP-201/211
Inside Fixture
Wall
0.2” (minimum)
Rubber
Gasket
Outside
Fixture Wall
Tightening Nut
(or Optional Collar)
Tightening Nut
(or Optional Collar)
Rubber
Gasket
Fixture
Wall
Lens Assembly
FSP-201 & FSP-211
Inside Fixture
Wall
Tightening Nut
(or Optional Collar)
Rubber
Gasket
Outside
Fixture Wall
Tightening Nut
(or Optional Collar)
Rubber
Gasket Fixture
Wall
Lens Assembly
FSP-221
NOTE: The outside fixture wall thickness should be no greater than 0.125” (3.18mm) for optimal sensor mounting and security.
Sequence of Operation
1. Dimming: When motion is detected within the sensor’s coverage area, the sensor sends a signal to ramp the load up
to the selectable High Mode level unless the ambient light level is higher than the selected setpoint. When no motion
is detected for the duration of the time delay setting (factory preset at 5 minutes), the lights will go to the selectable
Low Mode level based on the signal from the sensor. If desired, a cut off time delay (factory preset at 1 hour) will
trigger to eventually turn the lights OFF.
2. Non dimming: When motion is detected within the sensor’s coverage area, the sensor sends a signal to turn the load
ON unless the ambient light level is higher than the selected setpoint. When no motion is detected for the duration of
the time delay setting (factory preset at 5 minutes), the lights will go OFF based on the signal from the sensor.
3. Dusk to dawn control: When photocell on/off is enabled, and the ambient light falls below the photocell setpoint, the
sensor ramps the load up to the selectable High Mode level. If no motion is detected for the duration of the time delay
setting (factory preset at 5 minutes), the lights will go to the selectable Low Mode level. If the cut off time delay is
disabled, the load will remain on, at High or Low level, based on motion detection, until the ambient light increases
above the photocell setpoint.
3
WWW.LEGRAND.US/WATTSTOPPER
WATTSTOPPER®
Adjustable Control Parameters
Power
On/Off
Figure 2. The FSIR-100 is a
convenient handheld remote tool for
setting up the FSP-2x1. Adjustable
settings can be changed as needed
for specific applications.
Sensor Configuration
New Setting
Current Settings
Test Mode
Recall Profiles
FSIR-100
Back
Left
Down
Home/Main Menu
Up
Right/Next
Select
1. High Mode: When the sensor
detects motion the dimming
control output ramps up to
the selected HIGH light level
(default is 10V).
2. Low Mode: After the sensor
stops detecting motion and
the time delay expires the
dimming control output fades
down to the selected LOW
light level (default is 1V).
3. Time Delay: The selected
time period that must elapse
after the last time the sensor
detects motion for the
electric lights to fade to LOW
mode (default is 5 minutes).
4. Cut Off: The time period that
must elapse after the lights
fade to LOW mode and the
sensor detects no motion for
the electric lights to turn OFF
(default is 1 hour).
5. Sensitivity: The response of
the PIR detector to motion
within the sensor’s coverage
area (default is max).
6. Setpoint: When enabled,
the selectable ambient light
level threshold that will hold
the electric lights off or at
LOW level when the sensor
detects motion (default is
disabled).
FSP-201 Settings
High Mode:
< 1 0 Vo l t s >
Low Mode:
< 1 Vo l t s >
Time Delay:
<5 Min>
Cut Off:
<1 hour>
Sensitivity:
<Max>
Setpoint:
<Dis>
NEXT
SEND
Press the Left/Right Arrow
to Increase or Decrease Volts
FSP-201 Settings
High Mode:
< 1 0 Vo l t s >
Low Mode:
< 1 Vo l t s >
Time Delay:
<5 Min>
Cut Off:
<1 hour>
Sensitivity:
<Max>
Setpoint:
<Dis>
NEXT
SEND
Press the Left/Right Arrow
to Increase or Decrease Volts
FSP-201 Settings
High Mode:
< 1 0 Vo l t s >
Low Mode:
< 1 Vo l t s >
Time Delay:
<5 Min>
Cut Off:
<1 hour>
Sensitivity:
<Max>
Setpoint:
<Dis>
NEXT
SEND
Press the Left/Right Arrow
to Raise or Lower Time Delay
FSP-201 Settings
High Mode:
< 1 0 Vo l t s >
Low Mode:
< 1 Vo l t s >
Time Delay:
<5 Min>
Cut Off:
<1 hour>
Sensitivity:
<Max>
Setpoint:
<Dis>
NEXT
SEND
Press the Left/Right Arrow to
Increase or Decrease Cut Off
FSP-201 Settings
High Mode:
< 1 0 Vo l t s >
Low Mode:
< 1 Vo l t s >
Time Delay:
<5 Min>
Cut Off:
<1 hour>
Sensitivity:
<Max>
Setpoint:
<Dis>
NEXT
SEND
Press the Left/Right Arrow
to Increase or Decrease
FSP
-201 Settings
Sensitivity
High Mode:
Low Mode:
Time Delay:
Cut Off:
Sensitivity:
Setpoint:
NEXT
< 1 0 Vo l t s >
< 1 Vo l t s >
<5 Min>
<1 hour>
<Max>
<Dis>
SEND
Press the Left/Right Arrow
to Increase or Decrease
Setpoint
The Auto option invokes an automatic calibration
procedure to establish an appropriate setpoint based
upon the contribution of the electric light. As part of
this procedure, the controlled load is turned on for two
minutes to warm up the lamp, and then switched off
and on eight times, terminating in an off state. After this
process, a new setpoint value is automatically calculated.
WWW.LEGRAND.US/WATTSTOPPER
7. Photocell On/Off: When
FSP-201 Settings
enabled, the sensor will
Ramp Up:
<Dis>
Fade Down:
<Dis>
force the load OFF after the
Photocell:
<Dis>
light level has exceeded the
PRIOR
S AV E
SEND
selected photocell setpoint
for at least a minute. It will
also force the load ON when the light level goes below
the setpoint, even if no motion is detected (default if
disabled).
Once ON (initially at High), the load will dim to Low
following the Time Delay, and to OFF following the Cut
Off time. To ensure dusk to dawn control, Cut Off must
be disabled.
The photocell On/Off setpoint is automatically set to
maintain a deadband of at least 10 fc above the Hold Off
Setpoint to prevent cycling if the two features are used
together.
8. Ramp Up Time: Time period for light level to increase
from LOW to HIGH (default is disabled; lights switch
instantly).
9. Fade Down Time: Time
period for light level to
decrease from HIGH to LOW
(default is disabled; lights
switch instantly).
FSP-201 Settings
Ramp Up:
Fade Down:
Photocell:
<Dis>
<Dis>
<Dis>
PRIOR
SEND
S AV E
Left/Right Arrow to
10. Lock Settings: Time delayed Press Fthe
SP-201 Settings
Increase or Decrease Sec
IR communication lock
Ramp Up:
<Dis>
Fade Down:
initiated from the FSIR-100
<Dis>
Photocell:
<Dis>
to prevent unauthorized
PRIOR
S AV E
SEND
changes of FSP-2x1
parameters until power is
Press the Left/Right Arrow to
Increase or Decrease Sec
cycled to the sensor (default is disabled).
To lock settings, select Lock Delay, set a time, and
press SEND to send the parameter change to FSP-2x1.
After the countdown, FSP-2x1 will no longer respond
to the FSIR-100. If additional configuration is required,
cycle the power to the FSP-2x1 off and then back on. To
disable the lock parameter after the power cycle, select
Lock Delay, select Disable, and press SEND.
4
WATTSTOPPER®
Wiring Diagrams
Ground
Neutral
Line
Neutral
Ground
Dimming
Ballast/Driver
Dim-to-Off
Ballast/Driver
Line
+VDC Output (Red)
Ground (Green)
BZ-200 Power Pack
120 – 277 VAC (1φ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
16A E-Ballast/CFL
1HP @ 120/240VAC
20A 120VAC Plug Load – Receptacle
Ground (Green)
UL 2043 Plenum Rated
LISTED
Appliance
Control
88T9
Neut.
White
Hot
Black
Green
Ground
Power Pack
Red
Red
Blue
0-10V – (Gray)
Red
Class 2 Output
24 VDC, 225 mA
Black
COM/GND (Black)
Switch
Lighting
Load
Control
Any 3-Wire
24VDC
Sensor
Common
+24VDC
www.legrand.com • 800.879.8585
0-10V + (Violet)
Class 2
16094r1
wiring only
0-10V – (Gray)
CTRL (Blue)
0-10V + (Violet)
+VDC (Red)
COM (Black)
FSP-201
GRND
FSP-201
(violet)
High/Low PIR Occupancy Sensor
12-32 VDC, 15mA
DIM(grey)
CTRL
DIM+
COM
Appliance Control
88T9
18-20 AWG Solid CU Wire Only
800.879.8585
www.legrand.us
(violet)
COM
Appliance Control
88T9
18-20 AWG Solid CU Wire Only
+VDC
800.879.8585
www.legrand.us
+VDC
14-18 AWG Solid CU Wire Only
14-18 AWG Solid CU Wire Only
FSP-201 wiring with dimming ballast or LED
driver and power pack for on/off control.
LINE
NEUTRAL
LINE
NEUTRAL
FSP-201 typical wiring with dim-to-off
ballast or LED driver with auxiliary output.
NEUTRAL
NEUTRAL
LOAD
LOAD
LINE
NEUT
LOAD
LOAD
14-18 AWG Solid CU Wire Only
FSP-211
14-18 AWG Solid CU Wire Only
FSP-211
High/Low PIR
Occupancy Sensor
230-240V~, 50/60 Hz
300W max ballast
5E4, 40T75
Dimming
Driver
LINE
DIM(grey)
CTRL
NEUT
GRND
DIM+
High/Low PIR Occupancy Sensor
12-32 VDC, 15mA
High/Low PIR
Occupancy Sensor
230-240V~, 50/60 Hz
300W max ballast
5E4, 40T75
Non-Dimming
Driver
μ
μ
LISTED
Appliance
Control
88T9
E101196
LISTED
Appliance
Control
88T9
E101196
120V/277V, 50/60 Hz: UL/cUL
800W/1200W Max Tungsten,
Ballasts or LED Driver
1/6 HP
120V/277V, 50/60 Hz: UL/cUL
800W/1200W Max Tungsten,
Ballasts or LED Driver
1/6 HP
www.legrand.us/wattstopper
*GROUND
(violet)
(grey)
DIM+
GRND
(violet)
(grey)
DIM+
GRND
DIM-
NOTE: The FSP-211 must be
properly grounded.
DIM-
18-20 AWG Solid CU Wire Only
www.legrand.us/wattstopper
18-20 AWG Solid CU Wire Only
* GROUND
GRAY (-)
VIOLET (+)
FSP-211 wiring with dimming ballast or LED driver.
FSP-211 wiring with non-dimming ballast or LED driver.
Class 1
Dim (+)
Violet
Dimming
Load
Load
(Red)
Neutral or
Phase B
White with
Black Stripes
Violet
Neutral or
White Phase B
Black
Line or
Phase A
FSP-221 wiring with dimming ballast or LED driver
WWW.LEGRAND.US/WATTSTOPPER
Load
(Red)
Gray
Dim (-)
Gray
5
Neutral or
Phase B
White with
Black Stripes
Non-Dimming
Load
Neutral or
White Phase B
Black
Line or
Phase A
FSP-221 wiring with non-dimming load
Pub. No. 28372r1 11/2018
WATTSTOPPER®
Ordering Information
Catalog #
Master Pack Details
Master
Case dimensions (inches)
Pack
Quantity Length Width Height
FSP-201
100
21.14
19.72
10.31
Weight
(pounds)
Inner Pack Details
Inner
Case dimensions (inches)
Pack
Width
Height
Quantity Length
Weight
(pounds)
15.80
50
6.80
20.67
9.44
9.76
FSP-211
100
21.14
19.72
10.31
24.2
50
20.67
9.44
9.76
10.8
FSP-221
40
19.3
12.8
11.7
10.4
20
18.8
12.3
5.3
9
FSIR-100
40
12.83
14.02
10.04
21.84
10
9.44
6.10
6.69
5.24
FSP-L2
400
16.14
15.35
18.74
21.6
100
15.50
7.32
8.60
4.82
FSP-L3
400
16.14
15.35
18.74
20.3
100
15.50
7.32
8.60
4.82
FSP-L7
100
23.82
16.22
9.69
10.74
50
23.03
7.72
8.58
4.72
Catalog #
Color
Description
Voltage
FSP-201
White
Fixture mount, passive infrared motion sensor, low voltage
12-32 VDC
FSP-211
White
Fixture mount, passive infrared motion sensor
120-277VAC, 50/60Hz
FSP-221
White
Fixture mount PIR sensor, extended voltage
100-347VAC or 208/230/480VAC
FSIR-100
Black
Remote Handheld Configuration Tool
Three standard 1.5V AAA alkaline
batteries (included)
FSP-L2
White
360° lens, maximum coverage 48’ diameter from 8’ height
FSP-L2-B
Black
FSP-L2-BR
Brown
FSP-L2-G
Grey
FSP-L2-S
White
360° lens, maximum coverage 48’ diameter from 8’ height, with shroud; Minimizes high-angle light contribution
to photocell
FSP-L3
White
360° lens, maximum coverage 40’ diameter from 20’ height
FSP-L3-B
Black
FSP-L3-BR
Brown
FSP-L3-G
Grey
FSP-L3-S
White
360° lens, maximum coverage 40’ diameter from 20’ height, with shroud; Minimizes high-angle light
contribution to photocell
FSP-L7
White
360° lens, maximum coverage 100’ diameter from 40’ height
FSP-L7-B
Black
FSP-L7-BR
Brown
FSP-L7-G
Grey
FSP-L7-S
White
FSP-C1-W
White
FSP-C1-B
Black
FSP-C1-BR
Brown
FSP-C1-G
Gray
FSP-C2-W
White
FSP-C2-B
Black
FSP-C2-BR
Brown
FSP-C2-G
Gray
360° lens, maximum coverage 100’ diameter from 40’ height, with shroud; Minimizes high-angle light
contribution to photocell
Small collar, for use with FSP-L2 and FSP-L3 lenses
(Optional aesthetic collar to transition from fixture housing to lens)
Note: Not used with lenses that include shroud
Large collar, for use with FSP-L7 lens
(Optional aesthetic collar to transition from fixture housing to lens)
Note: Not used with lens that includes shroud
Note: Unless used with a driver or ballast with a low voltage power supply, the FSP-201 requires a Wattstopper power pack (ordered separately) to operate.
FSP-Lx series lens required for operation; order lens separately.
FSIR-100 required for configuration; order separately.
Information supplied above is subject to change.
Harmonization code: 8538908080. Country of origin: China.
WWW.LEGRAND.US/WATTSTOPPER
Pub. No. 28372r1 11/2018
6
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement