Service Guide
Factory Checkout
AK-CC 550A
ADAP-KOOL® Refrigeration Control System
Service Guide | Factory Checkout, AK-CC 550A
Sensor Checks
Physical check of each sensor.
1. Hold each sensor at probe to create a rise in reading. At case
controller. verify reading has risen for expected sensor input as
follows:
Sensor Location
550A Sensor Designation
Parameter
Coil Outlet
S2
U20
Return Air
S3
U12
Discharge Air
S4
U16
Defrost Termination
S5
U09
2. Allow sensor to return to ambient temperature. Repeat process
for all sensors on case controller, testing only one sensor at a
time.
Relay Checks
Change of state check via controller menus.
1. Change parameter r12 to ‘-1-‘
2. Cycle parameters to ‘on’ as shown below for each function
(where used), and confirm component is operational.
Function
Parameter
Fans
U59
Defrost Heaters
U60
Door Heaters
U61
Case Lights
U63
3. To test EEV relay and wiring (DO1, terminals 5&6), change
parameter U23 to 50%. Operation can then be verified via a coil
tester or through an audible ‘clicking’ noise heard in 3 second
intervals.
4. Return parameter r12 to ‘0’ when complete.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2 | AX278851874155en-000101
© Danfoss | ADAP-KOOL® | 2018.08

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement