Service Guide Factory Checkout AK-CC 550A ADAP-KOOL® Refrigeration Control System Service Guide | Factory Checkout, AK-CC 550A Sensor Checks Physical check of each sensor. 1. Hold each sensor at probe to create a rise in reading. At case controller. verify reading has risen for expected sensor input as follows: Sensor Location 550A Sensor Designation Parameter Coil Outlet S2 U20 Return Air S3 U12 Discharge Air S4 U16 Defrost Termination S5 U09 2. Allow sensor to return to ambient temperature. Repeat process for all sensors on case controller, testing only one sensor at a time. Relay Checks Change of state check via controller menus. 1. Change parameter r12 to ‘-1-‘ 2. Cycle parameters to ‘on’ as shown below for each function (where used), and confirm component is operational. Function Parameter Fans U59 Defrost Heaters U60 Door Heaters U61 Case Lights U63 3. To test EEV relay and wiring (DO1, terminals 5&6), change parameter U23 to 50%. Operation can then be verified via a coil tester or through an audible ‘clicking’ noise heard in 3 second intervals. 4. Return parameter r12 to ‘0’ when complete. Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. 2 | AX278851874155en-000101 © Danfoss | ADAP-KOOL® | 2018.08
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project