AMX RE-DM6 lighting controls Quick Start Guide

AMX RE-DM6 lighting controls Quick Start Guide
QUICK START GUIDE
RE-DM6 Radia Eclipse 6 Dimmer Module (120 VAC/240 VAC)
Overview
RE-DM6 SPECIF ICATIONS (CONT.)
The RE-DM6 RADIA Eclipse 6-Channel Integrated Dimmer Module (120V: FG706-03;
240V: FG706-04) controls up to six circuits with six 1200-watt onboard dimmers
(FIG. 1). The RE-DM6 is designed for use with the RDA series of enclosures, in an AMX
Lighting™ modular digital dimming system. The RE-DM6 is controlled by AxLink or by
dry (contact) closures.
Power Devices
Idle current draw:
75 mA @ 120 VAC, 50 mA @ 240 VAC, 100 mA @ 13.5 VDC
Certifications:
•
•
•
•
Mounting points (x4)
FCC
CE
UL North America
IEC-60950 Safety
Operating Temp Range: 0° to 40°C (32° to 104°F)
Jumper
Line In
High Voltage
Connections
Neutral
Included Accessories:
• 2 4-pin captive 3.5mm wire connectors (41-5047)
• 4 #8-32x1/2” F-point mounting screws
Required Enclosures:
•
•
•
•
Load out
Chokes
RDA-ENC2 (FG606-10)
RDA-ENC4 (FG606-11)
RDA-ENC6/6B (FG606-12/13/15)
RDA-ENC12B (FG606-14/16)
Suggested Installation Loads
DIMMED
CLASS 1 WIRING
SWITCHED
Incandescent
Motors
Neon, cold-cathode
Fans
Caution: Pre-Installation Notes
CLASS 2 WIRING
External +12
Aux Power
AxLink Address
DIP Switch
4-Pin Connectors to
RDM Series Modules
AxLink Connector
Dry Closures
FIG. 1 RE-DM6 6-CHANNEL INTEGRATED DIMMER MODULE
Specif ications
RE-DM6 SPECIF ICATIONS
Dimensions (HW):
5.75" x 10.0" (146.05 mm x 254.00 mm)
Weight:
4.5 lbs (2.04 kg)
Line input:
• 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W, one feed
• 120, 120/240, 240 VAC, single phase, 3W+G, 50/60 Hz,
4800 W, dual feed
Output:
•
•
•
•
1200 W max. per channel @120, 240 VAC
2400 W max. total, all 6 channels on with single 2400 W feed
4800 W max. total, all 6 channels on with dual 2400 W feeds
Line input #1 goes to dimmer 1, 3, and 5; line input #2 goes to
dimmer 2, 4 and 6
• All electrical ratings are for continuous duty
Wire rating:
Use only copper wires rated at 75°C (167°F) min.
Torque terminals:
To 20 in-lbs (2.3 N/M)
Maximum wire size:
10 AWG (4 mm²)
Wire stripping length:
0.5" (13 mm)
AxLink Port:
4-pin 3.5mm green captive wire connector - AxLink
communication signaling with 12VDC power in.
Aux Power:
2-pin 3.5mm green captive wire connector. This is a 12VDC power
input that supplies additional power to the Radia PCB and
connected Radia modules.
Dry Contacts:
• Emergency fire alarm relay connection - Closed relay activates
preset 126. Other control is locked out until relay opens.
Supports daisy chaining of up to 20 dimmers for this
connection, with a maximum current requirement of 200mA
when daisy-chained.
• Failsafe connection - Works with a toggle switch - opening the
switch triggers preset 128, closing the switch triggers preset
127. Supports daisy chaining of up to 20 dimmers for this
connection with a maximum current requirement of 200mA
when daisy-chained.
BTU/hr:
300 single feed (2400 W); 600 dual feed (4800 W)
WARNING: This unit should be installed only by qualif ied electrical personnel, and in
compliance with all national electrical codes, local codes and ordinances. To prevent
possible personal injury or death, disconnect power to the enclosure at the breaker box
before attempting to work with any AMX Lighting modules.
• All Class 1 and 2 wiring must be connected to their dedicated terminals.
• Class 1 wiring should be connected through the top of the enclosure, and Class 2
wiring through the bottom.
• Load conductors must be same size as line conductors, regardless of connected
load.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm)
clearance around the top and bottom.
• Test loads for shorts before connecting.
• Class 2 wiring must be rated 300V or higher.
• For indoor use only.
• AC lighting loads only.
• For more information, refer to the RE-DM6 instruction manual available at
www.amx.com.
Radia Lighting System Conf iguration Pages
The AMX Radia Web pages provide a simple interface for users of the Radia Duet
module. The web pages reside on the AMX master when running the Radia Duet module
and may be accessed through Internet Explorer or Mozilla Firefox. The RE-DM6 may
also be configured using NetLinx code or a terminal. For more information, refer to the
RE-DM6 instruction manual available at www.amx.com.
High-Voltage Connections
Each AMX Lighting module has its high-voltage connectors marked on its circuit board.
Line, load, and neutrals are also clearly marked.
Load
Line in
Load
Neutral
FIG. 2 HIGH-VOLTAGE CONNECTIONS
Line-in Connections
•
•
Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.
Jumping Line 1 and Line 2 provides a single 2400 W input (FIG. 3).
Dual 2400 W Inputs without jumper
Single 2400 W Input with jumper
FIG. 3 LINE-IN CONNECTIONS
Low-Voltage Connections
Connecting AxLink
The low-voltage area in the AMX Lighting controllers contain connections and DIP
switches for AxLink and dry closures. On the controller cards, low-voltage power for the
board is supplied either by line power, optional auxiliary power supply (RDA-PSM), or
the +12 VDC pin on the AxLink connector.
Connect the 4-pin captive-wire AxLink connector from the RE-DM6 to the Central
Controller for AxLink control of the dimming system (FIG. 5).
AxLink address DIP switch
RE-DM6
PWR
AXP
AXM
GND
PWR
AXP
AXM
GND
Central
Controller
FIG. 5 CONNECTING AXLINK
AxLink connector
Dry contact closures
Auxiliary power IN
FIG. 4 LOW-VOLTAGE CONNECTIONS AND DIP SWITCHES
WARNING: Disconnect the main power to the AMX Lighting controller at the breaker box
before rewiring the low voltage connections.
Setting AxLink Address Numbers
Set the AxLink address number (1-255) for the RE-DM6. This number must match the
number in your Axcess program.
Note: By turning all switches off, all circuits will go to 100 percent so that the installer
can test the high-voltage connections without having connections to a control system.
Dry Closure Connections
Dry contact closures from other equipment can be connected to the Radia Eclipse
dimmer module to provide direct manual control of lighting loads (FIG. 6).
FAILSAFE
RE-DM6
Failsafe switch
GND
EMERGENCY
Alarm system
GND
FIG. 6 DRY CLOSURE CONNECTIONS
Each dry contact closure has two pins: ground and contact. To activate each dry
closure, connect the ground and contact.
Lighting Application Drawings
Example A
Single Input
120 or 240 VAC 1Ø
Single-phase, six load
FIG. 7 EXAMPLE A
Example B
Dual Input
120, 120/240, 240 VAC 1Ø
Single-phase, six load
FIG. 8 EXAMPLE B
Last Revised: 11/09/2015
© 2015 Harman. All rights reserved. Radia Eclipse, AMX, AV FOR AN IT WORLD, HARMAN, and their respective logos are registered trademarks of
HARMAN. Oracle, Java and any other company or brand name referenced may be trademarks/registered trademarks of their respective companies.
AMX does not assume responsibility for errors or omissions. AMX also reserves the right to alter specifications without prior notice at any time.
The AMX Warranty and Return Policy and related documents can be viewed/downloaded at www.amx.com.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 AMX.com | 800.222.0193 | 469.624.8000 | +1.469.624.7400 | fax 469.624.7153
AMX (UK) LTD, AMX by HARMAN - Unit C, Auster Road, Clifton Moor, York, YO30 4GD United Kingdom • +44 1904-343-100 • www.amx.com/eu/
93-0706-02
REV: D