Fujitsu ARXK24GCLH Installation Manual

Add to My manuals
19 Pages

advertisement

Fujitsu ARXK24GCLH Installation Manual | Manualzz
‫ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ )ﺍﻟﻧﻭﻉ ﺍﻷﻧﺑﻭﺑﻲ(‬
‫ﻋﺭﺑﻲ‬
‫‪TM‬‬
‫ﻟﻣﻭﻅﻔﻲ ﺍﻟﺻﻳﺎﻧﺔ ﺍﻟﻣﻌﺗﻣﺩﻳﻥ ﻓﻘﻁ‪.‬‬
‫‪ARXK07GALH‬‬
‫‪ARXK09GALH‬‬
‫‪ARXK12GALH‬‬
‫‪ARXK14GALH‬‬
‫‪ARXK18GALH‬‬
‫‪ARXK24GALH‬‬
‫)ﺑﺩﻭﻥ ﻣﺿﺧﺔ ﺻﺭﻑ(‬
‫‪ARXK07GCLH‬‬
‫‪ARXK09GCLH‬‬
‫‪ARXK12GCLH‬‬
‫‪ARXK14GCLH‬‬
‫‪ARXK18GCLH‬‬
‫‪ARXK24GCLH‬‬
‫)ﺑﻣﺿﺧﺔ ﺻﺭﻑ(‬
‫ﺭﺍﺟﻊ ﻣﻠﺻﻕ ﺍﻟﺗﻘﻧﻳﻥ ﻟﻣﻌﺭﻓﺔ ﺍﻟﺭﻗﻡ ﺍﻟﻣﺳﻠﺳﻝ ﻭﻋﺎﻡ ﻭﺷﻬﺭ ﺍﻟﺗﺻﻧﻳﻊ‪.‬‬
‫ﺻﻧﻊ ﻓﻲ ﺟﻣﻬﻭﺭﻳﺔ ﺍﻟﺻﻳﻥ ﺍﻟﺷﻌﺑﻳﺔ‬
‫ﺭﻗﻡ ﺍﻟﺻﻧﻑ ‪9381858019-02‬‬
‫‪2017/8/8 13:09:02‬‬
‫‪9381858019-02_IM_AR.indd 1‬‬
‫ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ‬
‫ﺭﻗﻡ ﺍﻟﺻﻧﻑ ‪9381858019-02‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻓﻲ ﻧﻅﺎﻡ ‪) VRF‬ﺍﻟﻧﻭﻉ ﺍﻷﻧﺑﻭﺑﻲ(‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺗﺷﻳﺭ ﻫﺫﻩ ﺍﻟﻌﻼﻣﺔ ﺇﻟﻰ ﺍﻹﺟﺭﺍءﺍﺕ‪ ،‬ﺍﻟﺗﻲ ﻓﻲ ﺣﺎﻟﺔ ﻋﺩﻡ ﺗﻧﻔﻳﺫﻫﺎ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪ ،‬ﻗﺩ ﺗﺅﺩﻱ‬
‫ﺿﺭﺭ ﺷﺧﺻﻲ ﻟﻠﻣﺳﺗﺧﺩﻡ ﺃﻭ ﺗﻠﻑ ﻓﻲ ﺍﻟﻣﻣﺗﻠﻛﺎﺕ‪.‬‬
‫ﺍﻗﺭﺃ ﺑﻌﻧﺎﻳﺔ ﺟﻣﻳﻊ ﻣﻌﻠﻭﻣﺎﺕ ﺍﻷﻣﺎﻥ ﻗﺑﻝ ﺍﺳﺗﺧﺩﺍﻡ ﺃﻭ ﺗﺭﻛﻳﺏ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء‪.‬‬
‫ﻻ ﺗﺣﺎﻭﻝ ﺗﺭﻛﻳﺏ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﺃﻭ ﺟﺯء ﻣﻥ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﺑﻧﻔﺳﻙ‪.‬‬
‫ﺍﻟﻣﺣﺗﻭﻳﺎﺕ‬
‫ﻳﺟﺏ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺑﻭﺍﺳﻁﺔ ﻓﻧﻲ ﻣﻌﺗﻣﺩ ﻟﺩﻳﻪ ﺷﻬﺎﺩﺓ ﺃﻫﻠﻳﺔ ﻟﻠﺗﻌﺎﻣﻝ ﻣﻊ ﺳﻭﺍﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪ .‬ﺭﺍﺟﻊ ﺍﻟﻠﻭﺍﺋﺢ ﻭﺍﻟﻘﻭﺍﻧﻳﻥ ﺍﻟﻣﻌﻣﻭﻝ ﺑﻬﺎ ﻓﻲ‬
‫ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫‪.1‬‬
‫ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﺳﻼﻣﺔ‪1 ..............................................................................................................‬‬
‫ﻳﺟﺏ ﺇﺟﺭﺍء ﺍﻟﺗﺭﻛﻳﺏ ﻭﻓ ًﻘﺎ ﻟﻠﻭﺍﺋﺢ ﺍﻟﻣﻌﻣﻭﻝ ﺑﻬﺎ ﻓﻲ ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ ﻭﻭﻓ ًﻘﺎ ﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﺗﺭﻛﻳﺏ ﻣﻥ ﺍﻟﻣﺻ ﱢﻧﻊ‪.‬‬
‫‪.2‬‬
‫ﻧﺑﺫﺓ ﻋﻥ ﻫﺫﺍ ﺍﻟﻣﻧﺗﺞ ‪1 .............................................................................................................‬‬
‫‪ .1.2‬ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﺳﺗﺧﺩﺍﻡ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪1 ............................................................................ R410A‬‬
‫‪ .2.2‬ﺍﻷﺩﺍﺓ ﺍﻟﺧﺎﺻﺔ ﻟـ ‪1 ............................................................................................. R410A‬‬
‫‪ .3.2‬ﺍﻟﻣﻠﺣﻘﺎﺕ ‪2 .................................................................................................................‬‬
‫‪ .4.2‬ﺍﻷﺟﺯﺍء ﺍﻻﺧﺗﻳﺎﺭﻳﺔ ‪2 ......................................................................................................‬‬
‫ﻫﺫﻩ ﺍﻟﻭﺣﺩﺓ ﺗﺷﻛﻝ ﺟﺯ ًء ﻣﻥ ﺍﻟﻣﺟﻣﻭﻋﺔ ﺍﻟﺗﻲ ﻳﺗﺄﻟﻑ ﻣﻧﻬﺎ ﻣﻛﻳﻑ ﺍﻟﻬﻭﺍء‪ .‬ﻭﻳﺟﺏ ﻋﺩﻡ ﺗﺭﻛﻳﺑﻬﺎ ﻭﺣﺩﻫﺎ ﺃﻭ ﻣﻊ ﺃﺟﺯﺍء ﻏﻳﺭ ﻣﻌﺗﻣﺩﺓ‬
‫ﻣﻥ ﺍﻟﻣﺻ ﱢﻧﻊ‪.‬‬
‫‪.3‬‬
‫ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ ‪2 .................................................................................................................‬‬
‫‪ .1.3‬ﺍﺧﺗﻳﺎﺭ ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ ‪2 ...................................................................................................‬‬
‫‪ .2.3‬ﺃﺑﻌﺎﺩ ﺍﻟﺗﺭﻛﻳﺏ ‪3 ...........................................................................................................‬‬
‫‪ .3.3‬ﺗﺛﺑﻳﺕ ﺍﻟﻭﺣﺩﺓ ‪3 ............................................................................................................‬‬
‫‪.4‬‬
‫ﺗﺭﻛﻳﺏ ﺍﻟﻣﺎﺳﻭﺭﺓ‪5 ................................................................................................................‬‬
‫‪ .1.4‬ﺍﺧﺗﻳﺎﺭ ﻣﺎﺩﺓ ﺍﻟﻣﺎﺳﻭﺭﺓ‪5 ....................................................................................................‬‬
‫‪ .2.4‬ﻣﺗﻁﻠﺑﺎﺕ ﺍﻟﻣﺎﺳﻭﺭﺓ‪5 .......................................................................................................‬‬
‫‪ .3.4‬ﻭﺻﻠﺔ ﺗﻔﻠﻳﺞ )ﻭﺻﻠﺔ ﺍﻟﻣﺎﺳﻭﺭﺓ(‪6 .........................................................................................‬‬
‫‪ .4.4‬ﺗﺭﻛﻳﺏ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ‪6 ...................................................................................................‬‬
‫‪.5‬‬
‫ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ ‪7 .......................................................................................................‬‬
‫‪ .A1.5‬ﻁﺭﺍﺯ ‪7 ...........................................................................................ARXK**GCLH‬‬
‫‪ .B1.5‬ﻁﺭﺍﺯ ‪7 ...........................................................................................ARXK**GALH‬‬
‫‪ .2.5‬ﺗﺭﻛﻳﺏ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺻﺭﻑ‪7 ................................................................................................‬‬
‫‪.6‬‬
‫ﺍﻷﺳﻼﻙ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ‪9 .............................................................................................................‬‬
‫‪ .1.6‬ﺍﻟﻣﺗﻁﻠﺏ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ‪9 ......................................................................................................‬‬
‫‪ .2.6‬ﻁﺭﻳﻘﺔ ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‪10 ...............................................................................................‬‬
‫‪ .3.6‬ﺃﺳﻼﻙ ﺍﻟﻭﺣﺩﺓ‪10 ..........................................................................................................‬‬
‫‪ .4.6‬ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‪11 .......................................................................................................‬‬
‫‪ .5.6‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ ﻭﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‪11 ...........................................................‬‬
‫‪ .6.6‬ﺍﻟﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‪13 .................................................................................‬‬
‫‪ .7.6‬ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ ‪) IR‬ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ( ‪14 .................................................................................‬‬
‫‪ .8.6‬ﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‪14 ........................................................................‬‬
‫‪ .9.6‬ﺭﺑﻁ ﻛﺑﻝ ﺍﻷﺟﺯﺍء ﺍﻻﺧﺗﻳﺎﺭﻳﺔ ‪14 .........................................................................................‬‬
‫‪.7‬‬
‫ﺇﻋﺩﺍﺩ ﺍﻟﻣﺟﺎﻝ‪15 ..................................................................................................................‬‬
‫‪ .1.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ‪15 ..........................................................................................................‬‬
‫‪ .2.7‬ﺇﻋﺩﺍﺩ ﺭﻣﺯ ﻣﺧﺻﺹ‪16 ..................................................................................................‬‬
‫‪ .3.7‬ﻭﺿﻊ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ‪16 ..................................................................................................‬‬
‫‪ .4.7‬ﺗﺑﺩﻳﻝ ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ‪16 .................................................................................‬‬
‫‪ .5.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ‪17 ..........................................................................................................‬‬
‫‪.8‬‬
‫ﺍﻟﺗﺷﻐﻳﻝ ﺍﻻﺧﺗﺑﺎﺭﻱ ‪17 ...........................................................................................................‬‬
‫‪ .1.8‬ﺗﺷﻐﻳﻝ ﺍﺧﺗﺑﺎﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ )ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ( ‪17 .....................................................‬‬
‫‪ .2.8‬ﺗﺷﻐﻳﻝ ﺍﺧﺗﺑﺎﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ‪17 .....................................................................‬‬
‫‪.9‬‬
‫ﻗﺎﺋﻣﺔ ﺍﻟﻔﺣﺹ ‪17 .................................................................................................................‬‬
‫‪ .10‬ﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ ‪18 ..................................................................................................................‬‬
‫ﺍﺣﺭﺹ ﺩﺍﺋﻣًﺎ ﻋﻠﻰ ﺍﺳﺗﺧﺩﺍﻡ ﺧﻁ ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﻣﻧﻔﺻﻝ ﻣﺣﻣﻲ ﺑﻘﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻳﻌﻣﻝ ﻋﻠﻰ ﺟﻣﻳﻊ ﺍﻷﺳﻼﻙ ﺑﻣﺳﺎﻓﺔ ﺑﻳﻥ ﺃﺟﺯﺍء ﺍﻟﺗﻼﻣﺱ‬
‫ﺗﺑﻠﻎ ‪ 3‬ﻣﻡ ﻟﻬﺫﻩ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﻳﺟﺏ ﺗﺄﺭﻳﺽ ﺍﻟﻭﺣﺩﺓ ﺑﺷﻛﻝ ﺻﺣﻳﺢ ﻭﻳﺟﺏ ﺗﺯﻭﻳﺩ ﺧﻁ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﺑﻘﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻓﺭﻗﻲ ﻣﻥ ﺃﺟﻝ ﺣﻣﺎﻳﺔ ﺍﻷﺷﺧﺎﺹ‪.‬‬
‫ﺍﻟﻭﺣﺩﺍﺕ ﻟﻳﺳﺕ ﻣﻘﺎﻭﻣﺔ ﻟﻼﻧﻔﺟﺎﺭ ﻭﺑﺎﻟﺗﺎﻟﻲ ﻳﺟﺏ ﻋﺩﻡ ﺗﺭﻛﻳﺑﻬﺎ ﻓﻲ ﺃﺟﻭﺍء ﻗﺎﺑﻠﺔ ﻟﻼﻧﻔﺟﺎﺭ‪.‬‬
‫ﺗﺟﻧﺏ ﻣﻁﻠ ًﻘﺎ ﻟﻣﺱ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺑﻌﺩ ﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ ﻣﺻﺩﺭ ﺍﻟﻁﺎﻗﺔ ﻣﺑﺎﺷﺭﺓ‪ .‬ﻓﻘﺩ ﺗﺣﺩﺙ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ‪ .‬ﺑﻌﺩ ﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ‬
‫ﺍﻟﻁﺎﻗﺔ‪ ،‬ﺩﺍﺋﻣًﺎ ﺍﻧﺗﻅﺭ ‪ 5‬ﺩﻗﺎﺋﻕ ﻗﺑﻝ ﻟﻣﺱ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬
‫ﻻ ﺗﺣﺗﻭﻱ ﻫﺫﻩ ﺍﻟﻭﺣﺩﺓ ﻋﻠﻰ ﺃﺟﺯﺍء ﻳﻣﻛﻥ ﺻﻳﺎﻧﺗﻬﺎ ﺑﻭﺍﺳﻁﺔ ﺍﻟﻣﺳﺗﺧﺩﻡ‪ .‬ﺍﺣﺭﺹ ﺩﺍﺋﻣًﺎ ﻋﻠﻰ ﺍﺳﺗﺷﺎﺭﺓ ﻣﻭﻅﻔﻲ ﺍﻟﺻﻳﺎﻧﺔ ﺍﻟﻣﻌﺗﻣﺩﻳﻥ‬
‫ﺑﺷﺄﻥ ﺍﻹﺻﻼﺣﺎﺕ‪.‬‬
‫ﻋﻧﺩ ﺍﻟﻧﻘﻝ‪ ،‬ﺍﺳﺗﺷﺭ ﻣﻭﻅﻔﻲ ﺍﻟﺻﻳﺎﻧﺔ ﺍﻟﻣﻌﺗﻣﺩﻳﻥ ﺑﺷﺄﻥ ﻓﺻﻝ ﺗﻭﺻﻳﻝ ﺍﻟﻭﺣﺩﺓ ﻭﺗﺭﻛﻳﺑﻬﺎ‪.‬‬
‫‪ .2‬ﻧﺑﺫﺓ ﻋﻥ ﻫﺫﺍ ﺍﻟﻣﻧﺗﺞ‬
‫‪ .1.2‬ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﺳﺗﺧﺩﺍﻡ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪R410A‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻻ ﺗﺩﺧﻝ ﺃﻱ ﻣﺎﺩﺓ ﺧﻼﻑ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺍﻟﻣﻭﺻﻭﻑ ﻓﻲ ﺩﻭﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺩﺧﻭﻝ ﺍﻟﻬﻭﺍء ﺇﻟﻰ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪ ،‬ﻓﺳﻭﻑ ﻳﺻﺑﺢ ﺍﻟﺿﻐﻁ ﻓﻲ ﺩﻭﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ ﻣﺭﺗﻔﻌًﺎ ﺑﺻﻭﺭﺓ ﻏﻳﺭ ﻋﺎﺩﻳﺔ ﻭﻳﺳﺑﺏ ﻛﺳﺭ ﺍﻟﻣﻭﺍﺳﻳﺭ‪.‬‬
‫ﺇﺫﺍ ﻛﺎﻥ ﻫﻧﺎﻙ ﺗﺳﺭﻳﺏ ﻓﻲ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﺃﻧﻪ ﻻ ﻳﺗﺟﺎﻭﺯ ﺣﺩ ﺍﻟﺗﺭﻛﻳﺯ‪.‬‬
‫ﺇﺫﺍ ﺗﺟﺎﻭﺯ ﺗﺳﺭﻳﺏ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺣﺩ ﺍﻟﺗﺭﻛﻳﺯ‪ ،‬ﻓﻳﻣﻛﻥ ﺃﻥ ﻳﺅﺩﻱ ﺇﻟﻰ ﺣﻭﺍﺩﺙ ﻣﺛﻝ ﻧﻘﺹ ﺍﻷﻛﺳﺟﻳﻥ‪.‬‬
‫ﻻ ﺗﻠﻣﺱ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺍﻟﻣﺗﺳﺭﺏ ﻣﻥ ﻭﺻﻼﺕ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ ﺃﻭ ﻣﻧﻁﻘﺔ ﺃﺧﺭﻯ‪ .‬ﻳﺅﺩﻱ ﻟﻣﺱ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﻣﺑﺎﺷﺭﺓ ﺇﻟﻰ ﺍﻹﺻﺎﺑﺔ‬
‫ﺑﻠﺳﻌﺎﺕ ﺻﻘﻳﻊ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺣﺩﻭﺙ ﺗﺳﺭﻳﺏ ﻟﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺃﺛﻧﺎء ﺍﻟﺗﺷﻐﻳﻝ‪ ،‬ﻗﻡ ﺑﺈﺧﻼء ﺍﻟﻣﻛﺎﻥ ﻋﻠﻰ ﺍﻟﻔﻭﺭ ﻭﺗﻬﻭﻳﺔ ﺍﻟﻣﻧﻁﻘﺔ ﺑﺎﻟﻛﺎﻣﻝ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﻣﻼﻣﺳﺔ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﻟﻠﻬﺏ‪ ،‬ﻓﺳﻭﻑ ﻳﻧﺗﺞ ﻏﺎﺯ ﺳﺎﻡ‪.‬‬
‫‪ .2.2‬ﺍﻷﺩﺍﺓ ﺍﻟﺧﺎﺻﺔ ﻟـ ‪R410A‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻟﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ ﺗﺳﺗﺧﺩﻡ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪ ،R410A‬ﺍﺳﺗﺧﺩﻡ ﺍﻷﺩﻭﺍﺕ ﺍﻟﻣﺧﺻﺻﺔ ﻭﻣﻭﺍﺩ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺍﻟﺗﻲ ﺗﻡ ﺗﺻﻧﻳﻌﻬﺎ ﺧﺻﻳﺻًﺎ‬
‫ﻟﻼﺳﺗﺧﺩﺍﻡ ﻣﻊ ‪.R410A‬‬
‫ﻧﻅﺭً ﺍ ﻷﻥ ﺿﻐﻁ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪ R410A‬ﻳﻛﻭﻥ ﺃﻋﻠﻰ ﺑﻣﻘﺩﺍﺭ ‪ 1.6‬ﻣﺭﺓ ﻣﻥ ﺳﺎﺋﻝ ‪ ،R22‬ﻳﻣﻛﻥ ﺃﻥ ﻳﺗﺳﺑﺏ ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﺳﺗﺧﺩﺍﻡ‬
‫ﻣﻭﺍﺩ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺍﻟﻣﺧﺻﺻﺔ ﺃﻭ ﺍﻟﺗﺭﻛﻳﺏ ﻏﻳﺭ ﺍﻟﺻﺣﻳﺢ ﺇﻟﻰ ﺣﺩﻭﺙ ﺗﻣﺯﻕ ﺃﻭ ﺇﺻﺎﺑﺔ‪.‬‬
‫ﻋﻼﻭﺓ ﻋﻠﻰ ﺫﻟﻙ‪ ،‬ﻳﻣﻛﻥ ﺃﻥ ﻳﺗﺳﺑﺏ ﻓﻲ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺗﺳﺭﺏ ﺍﻟﻣﻳﺎﻩ ﺃﻭ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﺍﺳﻡ ﺍﻷﺩﺍﺓ‬
‫ﻣﺣﺗﻭﻳﺎﺕ ﺍﻟﺗﻐﻳﻳﺭ‬
‫ﻣﺷﻌﺏ ﺍﻟﻌﺩﺍﺩ‬
‫ﺍﻟﺿﻐﻁ ﻛﺑﻳﺭ ﻭﻻ ﻳﻣﻛﻥ ﻗﻳﺎﺳﻪ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻋﺩﺍﺩ )‪ (R22‬ﺍﻟﺗﻘﻠﻳﺩﻱ‪ .‬ﻟﻣﻧﻊ ﺧﻠﻁ ﺳﻭﺍﺋﻝ ﺗﺑﺭﻳﺩ‬
‫ﺃﺧﺭﻯ ﻋﻥ ﻁﺭﻳﻕ ﺍﻟﺧﻁﺄ‪ ،‬ﺗﻡ ﺗﻐﻳﻳﺭ ﻗﻁﺭ ﻛﻝ ﻣﻧﻔﺫ‪.‬‬
‫ﻳﻭﺻﻰ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻣﺷﻌﺏ ﻋﺩﺍﺩ ﺑﻧﻁﺎﻕ ﻋﺭﺽ ﺿﻐﻁ ﻣﺭﺗﻔﻊ ‪ -0.1‬ﺇﻟﻰ ‪ 5.3‬ﻣﻳﺟﺎﺑﺎﺳﻛﺎﻝ‬
‫ﻭﻧﻁﺎﻕ ﻋﺭﺽ ﺿﻐﻁ ﻣﻧﺧﻔﺽ ‪ -0.1‬ﺇﻟﻰ ‪ 3.8‬ﻣﻳﺟﺎﺑﺎﺳﻛﺎﻝ‪.‬‬
‫ﺧﺭﻁﻭﻡ ﺍﻟﺷﺣﻥ‬
‫ﻟﺯﻳﺎﺩﺓ ﻣﻘﺎﻭﻣﺔ ﺍﻟﺿﻐﻁ‪ ،‬ﺗﻡ ﺗﻐﻳﻳﺭ ﻣﺎﺩﺓ ﺍﻟﺧﺭﻁﻭﻡ ﻭﺣﺟﻡ ﺍﻟﻘﺎﻋﺩﺓ‪.‬‬
‫• ﺗﺣﺗﻭﻱ ﺍﻟﺗﺣﺫﻳﺭﺍﺕ ﻭﺍﻻﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﺩﻟﻳﻝ ﻋﻠﻰ ﻣﻌﻠﻭﻣﺎﺕ ﻫﺎﻣﺔ ﺗﺗﻌﻠﻕ ﺑﺳﻼﻣﺗﻙ‪ .‬ﻋﻠﻳﻙ ﺍﻟﺗﺄﻛﺩ ﻣﻥ ﺍﺗﺑﺎﻋﻬﺎ‪.‬‬
‫ﻣﺿﺧﺔ ﺍﻟﺗﻔﺭﻳﻎ‬
‫• ﻳﺭﺟﻰ ﺗﻘﺩﻳﻡ ﻫﺫﺍ ﺍﻟﺩﻟﻳﻝ ﺇﻟﻰ ﺟﺎﻧﺏ ﺩﻟﻳﻝ ﺍﻟﺗﺷﻐﻳﻝ ﺇﻟﻰ ﺍﻟﻌﻣﻳﻝ‪.‬‬
‫ﺍﻁﻠﺏ ﻣﻥ ﺍﻟﻌﻣﻳﻝ ﺍﻻﺣﺗﻔﺎﻅ ﺑﻬﻣﺎ ﻓﻲ ﺍﻟﻣﺗﻧﺎﻭﻝ ﻟﻼﺳﺗﺧﺩﺍﻡ ﻓﻲ ﺍﻟﻣﺳﺗﻘﺑﻝ‪ ،‬ﻣﺛﻝ ﺗﻐﻳﻳﺭ ﻣﻛﺎﻥ ﺍﻟﻭﺣﺩﺓ ﺃﻭ ﺇﺻﻼﺣﻬﺎ‪.‬‬
‫ﻳﻣﻛﻥ ﺍﺳﺗﺧﺩﺍﻡ ﻣﺿﺧﺔ ﺍﻟﺗﻔﺭﻳﻎ ﺍﻟﺗﻘﻠﻳﺩﻳﺔ )‪ (R22‬ﻣﻥ ﺧﻼﻝ ﺗﺭﻛﻳﺏ ﻣﻬﺎﻳﺊ ﻣﺿﺧﺔ ﺗﻔﺭﻳﻎ‪.‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺃﻥ ﺯﻳﺕ ﺍﻟﻣﺿﺧﺔ ﻻ ﻳﺗﺩﻓﻕ ﻋﻛﺳﻳًﺎ ﻓﻲ ﺍﻟﻧﻅﺎﻡ‪ .‬ﺍﺳﺗﺧﺩﻡ ﺯﻳﺕ ﻗﺎﺩﺭ ﻋﻠﻰ‬
‫ﺍﻻﻣﺗﺻﺎﺹ ﺍﻟﻣﻔﺭﻍ ﺑﻘﻳﻣﺔ ‪ -100.7‬ﻛﻳﻠﻭﺑﺎﺳﻛﺎﻝ )‪ 5‬ﻁﻥ‪ -755 ،‬ﻣﻡ ﺯﺋﺑﻕ(‪.‬‬
‫ﻭﺣﺩﺓ ﺍﻛﺗﺷﺎﻑ ﺗﺳﺭﻳﺏ ﺍﻟﻐﺎﺯ‬
‫ﻭﺣﺩﺓ ﺍﻛﺗﺷﺎﻑ ﺗﺳﺭﻳﺏ ﻏﺎﺯ ﺧﺎﺻﺔ ﻟﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪ R410A‬ﻣﻥ ‪.HFC‬‬
‫‪ .1‬ﺍﺣﺗﻳﺎﻁﺎﺕ ﺍﻟﺳﻼﻣﺔ‬
‫• ﺗﺄﻛﺩ ﻣﻥ ﻗﺭﺍءﺓ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻫﺫﺍ ﺑﺎﻟﻛﺎﻣﻝ ﻗﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﺗﺷﻳﺭ ﻫﺫﻩ ﺍﻟﻌﻼﻣﺔ ﺇﻟﻰ ﺍﻹﺟﺭﺍءﺍﺕ‪ ،‬ﺍﻟﺗﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻧﻔﻳﺫﻫﺎ ﺑﺷﻛﻝ ﻏﻳﺭ ﺻﺣﻳﺢ‪ ،‬ﻗﺩ ﺗﺅﺩﻱ ﺇﻟﻰ‬
‫ﺍﻟﻭﻓﺎﺓ ﺃﻭ ﺍﻹﺻﺎﺑﺔ ﺍﻟﺧﻁﻳﺭﺓ ﻟﻠﻣﺳﺗﺧﺩﻡ‪.‬‬
‫ﺍﻁﻠﺏ ﻣﻥ ﺍﻟﻣﻭﺯﻉ ﺃﻭ ﻣﺳﺅﻭﻝ ﺍﻟﺗﺭﻛﻳﺏ ﺍﻟﻣﺗﺧﺻﺹ ﺗﺭﻛﻳﺏ ﻫﺫﻩ ﺍﻟﻭﺣﺩﺓ ﻭﻓ ًﻘﺎ ﻟﻬﺫﺍ ﺍﻟﺩﻟﻳﻝ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﺗﺗﺳﺑﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﻣﺭﻛﺑﺔ ﺑﺷﻛﻝ ﻏﻳﺭ ﺻﺣﻳﺢ ﻓﻲ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺗﺳﺭﺏ ﺍﻟﻣﻳﺎﻩ ﺃﻭ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺑﺷﻛﻝ ﻳﺧﺎﻟﻑ ﺍﻟﺗﻌﻠﻳﻣﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻲ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﻓﺳﻭﻑ ﺗﺑﻁﻝ ﺍﻟﺿﻣﺎﻥ‪.‬‬
‫ﻻ ﺗﻘﻡ ﺑﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ ﺇﻻ ﺑﻌﺩ ﺍﺳﺗﻛﻣﺎﻝ ﺟﻣﻳﻊ ﺍﻷﻋﻣﺎﻝ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﻳﺅﺩﻱ ﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ ﻗﺑﻝ ﺍﺳﺗﻛﻣﺎﻝ ﺍﻟﻌﻣﻝ ﺇﻟﻰ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺍﻟﺗﻌﺭﺽ ﻟﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺳﺭﻳﺏ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺃﺛﻧﺎء ﺗﻧﻔﻳﺫ ﺍﻟﻌﻣﻝ‪ ،‬ﻓﻌﻠﻳﻙ ﺗﻬﻭﻳﺔ ﺍﻟﻣﻧﻁﻘﺔ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﻣﻼﻣﺳﺔ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﻟﻠﻬﺏ‪ ،‬ﻓﺳﻭﻑ ﻳﻧﺗﺞ ﻏﺎﺯ ﺳﺎﻡ‪.‬‬
‫ﻳﺟﺏ ﺗﻧﻔﻳﺫ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻭﻓ ًﻘﺎ ﻟﻣﻌﺎﻳﻳﺭ ﺗﻭﺻﻳﻼﺕ ﺍﻷﺳﻼﻙ ﺍﻟﻭﻁﻧﻳﺔ ﻭﻋﻥ ﻁﺭﻳﻕ ﺷﺧﺹ ﻣﺧﻭﻝ ﻓﻘﻁ‪.‬‬
‫ﺑﺎﺳﺗﺛﻧﺎء ﻓﻲ ﺣﺎﻟﺔ ﺍﻟﻁﻭﺍﺭﺉ‪ ،‬ﺗﺟﻧﺏ ﻣﻁﻠ ًﻘﺎ ﻓﺻﻝ ﺍﻟﺗﻳﺎﺭ ﺍﻟﺭﺋﻳﺳﻲ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﻗﺎﻁﻊ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻔﺭﻋﻲ ﻟﻠﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺃﺛﻧﺎء‬
‫ﺍﻟﺗﺷﻐﻳﻝ‪ .‬ﺳﻭﻑ ﻳﺅﺩﻱ ﺫﻟﻙ ﺇﻟﻰ ﺗﻌﻁﻝ ﺍﻟﺿﺎﻏﻁ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫ﻗﻡ ﺃﻭﻻ ﺑﺈﻳﻘﺎﻑ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻣﻥ ﺧﻼﻝ ﺗﺷﻐﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﺃﻭ ﺍﻟﻣﺣﻭﻝ ﺃﻭ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ ﺛﻡ ﻗﻡ ﺑﻔﺻﻝ ﺍﻟﻘﺎﻁﻊ‪.‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺍﻟﺗﺷﻐﻳﻝ ﻣﻥ ﺧﻼﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﺃﻭ ﺍﻟﻣﺣﻭﻝ ﺃﻭ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ‪.‬‬
‫ﻋﻧﺩ ﺗﺻﻣﻳﻡ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‪ ،‬ﺿﻌﻪ ﻓﻲ ﻣﻛﺎﻥ ﺑﺣﻳﺙ ﻻ ﻳﻣﻛﻥ ﻟﻠﻣﺳﺗﺧﺩﻣﻳﻥ ﺑﺩء ﺍﻟﺟﻬﺎﺯ ﻭﺇﻳﻘﺎﻓﻪ ﻓﻲ ﺍﻷﻏﺭﺍﺽ ﺍﻟﻳﻭﻣﻳﺔ‪.‬‬
‫‪Ar-1‬‬
‫‪2017/8/8 13:09:02‬‬
‫‪9381858019-02_IM_AR.indd Sec1:1‬‬
‫‪ .3.2‬ﺍﻟﻣﻠﺣﻘﺎﺕ‬
‫ﺍﻻﺳﻡ ﻭﺍﻟﺷﻛﻝ‬
‫ﺍﻻﺳﺗﻌﻣﺎﻝ‬
‫ﺍﻟﻛﻣﻳﺔ‬
‫ﻟﺗﺭﻛﻳﺏ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ‬
‫ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ‬
‫ﺗﺣﺫﻳﺭ‬
‫‪1‬‬
‫ﻷﻏﺭﺍﺽ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﺍﺳﺗﺧﺩﺍﻡ ﺍﻷﺟﺯﺍء ﺍﻟﻣﻘﺩﻣﺔ ﻣﻥ ﺍﻟﻣﺻ ﱢﻧﻊ ﺃﻭ ﺍﻷﺟﺯﺍء ﺍﻷﺧﺭﻯ ﺍﻟﻣﻭﺻﻭﻓﺔ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﻳﺅﺩﻱ ﺍﺳﺗﺧﺩﺍﻡ ﺃﺟﺯﺍء ﻏﻳﺭ ﻣﺣﺩﺩﺓ ﺇﻟﻰ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺳﻘﻭﻁ ﺍﻟﻭﺣﺩﺓ ﺃﻭ ﺗﺳﺭﻳﺏ ﺍﻟﻣﺎء ﺃﻭ ﺍﻟﺗﻌﺭﺽ ﻟﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻳﺗﻡ ﺗﺯﻭﻳﺩ ﺃﺟﺯﺍء ﺍﻟﺗﺭﻛﻳﺏ ﺍﻟﺗﺎﻟﻳﺔ‪ .‬ﺍﺳﺗﺧﺩﻣﻬﺎ ﺣﺳﺏ ﺍﻟﺣﺎﺟﺔ‪.‬‬
‫ﻳﻌﺯﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ‬
‫ﻋﺎﺯﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪B‬‬
‫ﺍﺣﺗﻔﻅ ﺑﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻓﻲ ﻣﻛﺎﻥ ﺁﻣﻥ ﻭﻻ ﺗﺗﺧﻠﺹ ﻣﻥ ﺃﻱ ﻣﻠﺣﻘﺎﺕ ﺃﺧﺭﻯ ﺣﺗﻰ ﻳﺗﻡ ﺍﺳﺗﻛﻣﺎﻝ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫‪1‬‬
‫ﻻ ﺗﺗﺧﻠﺹ ﻣﻥ ﺃﻱ ﻣﻠﺣﻘﺎﺕ ﻻﺯﻣﺔ ﻟﻠﺗﺭﻛﻳﺏ ﺣﺗﻰ ﻳﺗﻡ ﺍﺳﺗﻛﻣﺎﻝ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﺍﻻﺳﻡ ﻭﺍﻟﺷﻛﻝ‬
‫ﺍﻻﺳﺗﻌﻣﺎﻝ‬
‫ﺍﻟﻛﻣﻳﺔ‬
‫ﺩﻟﻳﻝ ﺍﻟﺗﺷﻐﻳﻝ‬
‫ﺍﻟﻭﺻﻑ‬
‫‪1‬‬
‫ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ‬
‫‪ .4.2‬ﺍﻷﺟﺯﺍء ﺍﻻﺧﺗﻳﺎﺭﻳﺔ‬
‫)ﻫﺫﺍ ﺍﻟﻛﺗﺎﺏ(‬
‫ﺍﻻﺳﺗﻌﻣﺎﻝ‬
‫ﺍﻟﻁﺭﺍﺯ‬
‫ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ ‪IR‬‬
‫‪UTB-*WC‬‬
‫ﻟﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪.‬‬
‫ﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ‬
‫‪UTY-XSZX‬‬
‫ﻣﺳﺗﺷﻌﺭ ﺣﺭﺍﺭﺓ ﺍﻟﻐﺭﻓﺔ‬
‫‪UTY-XWZXZC‬‬
‫ﻟﻭﻅﻳﻔﺔ ﺍﻹﺧﺭﺍﺝ‬
‫)ﻁﺭﻑ ﺍﻹﺧﺭﺍﺝ ‪(CNB01 /‬‬
‫‪UTY-XWZXZB‬‬
‫ﻟﻭﻅﻳﻔﺔ ﺇﺩﺧﺎﻝ ﺍﻟﺗﺣﻛﻡ‬
‫)ﻁﺭﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ ‪(CNA01 /‬‬
‫‪UTY-XWZXZD‬‬
‫ﻟﻭﻅﻳﻔﺔ ﺇﺩﺧﺎﻝ ﺍﻟﺗﺣﻛﻡ‬
‫)ﻁﺭﻑ ﺍﻟﺗﻼﻣﺱ ﺍﻟﺟﺎﻑ ‪(CNA02 /‬‬
‫‪UTY-XWZXZ7‬‬
‫ﻟﻭﻅﻳﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ ﻣﻥ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ‬
‫)ﻁﺭﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ ‪(CNA03 /‬‬
‫‪UTY-XWZXZE‬‬
‫ﻟﻭﻅﻳﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ ﻣﻥ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ‬
‫)ﻁﺭﻑ ﺍﻟﺗﻼﻣﺱ ﺍﻟﺟﺎﻑ ‪(CNA04 /‬‬
‫‪1‬‬
‫ﻟﻌﻣﻝ ﻓﺗﺣﺎﺕ ﺍﻟﺳﻘﻑ ﻭﺃﻳﺿًﺎ ُﺗﺳﺗﺧﺩﻡ ﻛﻌﺑﻭﺓ ﺗﻐﻠﻳﻑ‬
‫ﻗﺎﻟﺏ )ﺟﺯء ﻋﻠﻭﻱ ﻛﺭﺗﻭﻧﻲ(‬
‫ﻁﻘﻡ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺧﺎﺭﺟﻲ‬
‫‪1‬‬
‫ﻟﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻓﻠﻛﺔ‬
‫ﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ‬
‫‪8‬‬
‫ﻟﻭﺻﻠﺔ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺟﺎﻧﺏ ﺍﻟﺩﺍﺧﻠﻲ )ﻣﺎﺳﻭﺭﺓ ﻛﺑﻳﺭﺓ(‬
‫ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ )ﻛﺑﻳﺭ(‬
‫‪UTD-GXT*-W‬‬
‫ﻟﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ‬
‫‪ .3‬ﺃﻋﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‬
‫‪ .1.3‬ﺍﺧﺗﻳﺎﺭ ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ‬
‫‪1‬‬
‫ﻳﻌﺗﺑﺭ ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ ﺍﻷﻭﻟﻲ ﻫﺎﻣًﺎ ﻧﻅﺭً ﺍ ﻷﻧﻪ ﻣﻥ ﺍﻟﺻﻌﺏ ﺗﺣﺭﻳﻙ ﺍﻟﻭﺣﺩﺓ ﺑﻌﺩ ﺍﻟﺗﺭﻛﻳﺏ‪.‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻟﻭﺻﻠﺔ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺟﺎﻧﺏ ﺍﻟﺩﺍﺧﻠﻲ )ﻣﺎﺳﻭﺭﺓ ﺻﻐﻳﺭﺓ(‬
‫ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ )ﺻﻐﻳﺭ(‬
‫ﺍﺧﺗﺭ ﺃﻣﺎﻛﻥ ﺗﺭﻛﻳﺏ ﻳﻣﻛﻧﻬﺎ ﺗﺣﻣﻝ ﻭﺯﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪ .‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺍﺕ ﺑﺈﺣﻛﺎﻡ ﺑﺣﻳﺙ ﻻ ﺗﺗﻌﺭﺽ ﻟﻼﻧﻘﻼﺏ‬
‫ﺃﻭ ﺍﻟﺳﻘﻭﻁ‪.‬‬
‫‪1‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺭﺑﻁ ﻛﺑﻝ ﺍﻟﻧﻘﻝ ﻭﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻣﺗﻭﺳﻁ(‬
‫‪2‬‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻛﺑﻳﺭ(‬
‫ﻟﺗﺛﺑﻳﺕ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‪.‬‬
‫‪4‬‬
‫ﻣﺭﺷﺢ )ﺻﻐﻳﺭ(‬
‫‪2‬‬
‫‪(AR07/09/‬‬
‫)‪12/14/24‬‬
‫ﻻ ﺗﺭﻛﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﺍﻟﻣﻧﺎﻁﻕ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫• ﺍﻟﻣﻧﻁﻘﺔ ﺫﺍﺕ ﻣﺣﺗﻭﻯ ﻣﻠﻭﺣﺔ ﻣﺭﺗﻔﻊ‪ ،‬ﻣﺛﻝ ﺳﺎﺣﻝ ﺍﻟﺑﺣﺭ‪.‬‬
‫ﺳﻭﻑ ﺗﺅﺩﻱ ﺇﻟﻰ ﺗﺩﻫﻭﺭ ﺣﺎﻟﺔ ﺍﻷﺟﺯﺍء ﺍﻟﻣﻌﺩﻧﻳﺔ‪ ،‬ﻣﻣﺎ ﻳﺗﺳﺑﺏ ﻓﻲ ﺗﻌﻁﻝ ﺍﻷﺟﺯﺍء ﺃﻭ ﺣﺩﻭﺙ ﺗﺳﺭﻳﺏ ﻣﻳﺎﻩ ﻟﻠﻭﺣﺩﺓ‪.‬‬
‫• ﻣﻧﻁﻘﺔ ﻣﻠﻳﺋﺔ ﺑﺯﻳﺕ ﻣﻌﺩﻧﻲ ﺃﻭ ﺗﺣﺗﻭﻱ ﻋﻠﻰ ﻣﻘﺩﺍﺭ ﻛﺑﻳﺭ ﻣﻥ ﺍﻟﺯﻳﺕ ﺃﻭ ﺍﻟﺑﺧﺎﺭ ﺍﻟﻣﺗﻁﺎﻳﺭ‪ ،‬ﻣﺛﻝ ﺍﻟﻣﻁﺑﺦ‪.‬‬
‫ﺳﻭﻑ ﺗﺅﺩﻱ ﺇﻟﻰ ﺗﺩﻫﻭﺭ ﺣﺎﻟﺔ ﺍﻷﺟﺯﺍء ﺍﻟﺑﻼﺳﺗﻳﻛﻳﺔ‪ ،‬ﻣﻣﺎ ﻳﺗﺳﺑﺏ ﻓﻲ ﺳﻘﻭﻁ ﺍﻷﺟﺯﺍء ﺃﻭ ﺣﺩﻭﺙ ﺗﺳﺭﻳﺏ ﻣﻳﺎﻩ ﻟﻠﻭﺣﺩﺓ‪.‬‬
‫• ﻣﻧﻁﻘﺔ ﺗﻧﺑﻌﺙ ﻣﻧﻬﺎ ﻣﻭﺍﺩ ﺗﺅﺛﺭ ﺳﻠﺑًﺎ ﻋﻠﻰ ﺍﻟﺟﻬﺎﺯ‪ ،‬ﻣﺛﻝ ﻏﺎﺯ ﻛﺑﺭﻳﺗﻲ‪ ،‬ﺃﻭ ﻏﺎﺯ ﺍﻟﻛﻠﻭﺭ ﺃﻭ ﺣﻣﺽ ﺃﻭ ﻣﺎﺩﺓ ﻗﻠﻭﻳﺔ‪.‬‬
‫ﺳﻭﻑ ﺗﺅﺩﻱ ﺇﻟﻰ ﺗﺂﻛﻝ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺍﻟﻧﺣﺎﺳﻳﺔ ﻭﺍﻟﻭﺻﻼﺕ ﺍﻟﻣﻠﺣﻭﻣﺔ‪ ،‬ﻣﻣﺎ ﻳﺗﺳﺑﺏ ﻓﻲ ﺗﺳﺭﻳﺏ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪.‬‬
‫• ﻣﻧﻁﻘﺔ ﺗﺅﺩﻱ ﺇﻟﻰ ﺗﺳﺭﻳﺏ ﻏﺎﺯ ﻗﺎﺑﻝ ﻟﻼﺷﺗﻌﺎﻝ‪ ،‬ﺃﻭ ﺗﺣﺗﻭﻱ ﻋﻠﻰ ﺃﻟﻳﺎﻑ ﻛﺭﺑﻭﻧﻳﺔ ﻣﻌﻠﻘﺔ ﺃﻭ ﻏﺑﺎﺭ ﻗﺎﺑﻝ ﻟﻼﺷﺗﻌﺎﻝ‪ ،‬ﺃﻭ ﻣﻭﺍﺩ ﻣﺗﻁﺎﻳﺭﺓ‬
‫ﻗﺎﺑﻠﺔ ﻟﻼﺷﺗﻌﺎﻝ ﻣﺛﻝ ﻣﺭﻗﻕ ﺍﻟﻁﻼء ﺃﻭ ﺍﻟﺑﻧﺯﻳﻥ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺳﺭﻳﺏ ﺍﻟﻐﺎﺯ ﻭﺍﺳﺗﻘﺭﺍﺭﻩ ﺣﻭﻝ ﺍﻟﻭﺣﺩﺓ‪ ،‬ﻓﻘﺩ ﻳﺅﺩﻱ ﺇﻟﻰ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫• ﻣﻧﻁﻘﺔ ﻳﻣﻛﻥ ﺃﻥ ﺗﺗﺑﻭﻝ ﻓﻳﻪ ﺍﻟﺣﻳﻭﺍﻧﺎﺕ ﻋﻠﻰ ﺍﻟﻭﺣﺩﺓ ﺃﻭ ﻳﺗﻡ ﺗﻛﻭﻳﻥ ﺍﻷﻣﻭﻧﻳﺎ ﻓﻳﻬﺎ‪.‬‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﺃﻏﺭﺍﺽ ﺧﺎﺻﺔ ﻣﺛﻝ ﺗﺧﺯﻳﻥ ﺍﻟﻁﻌﺎﻡ‪ ،‬ﺃﻭ ﺗﺭﺑﻳﺔ ﺍﻟﺣﻳﻭﺍﻧﺎﺕ ﺃﻭ ﺯﺭﺍﻋﺔ ﺍﻟﻧﺑﺎﺗﺎﺕ ﺃﻭ ﺣﻔﻅ ﺍﻷﺟﻬﺯﺓ ﺍﻟﺩﻗﻳﻘﺔ ﺃﻭ‬
‫ﺍﻷﻋﻣﺎﻝ ﺍﻟﻔﻧﻳﺔ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﺗﺗﺳﺑﺏ ﻓﻲ ﺗﺩﻧﻲ ﺟﻭﺩﺓ ﺍﻷﺷﻳﺎء ﺍﻟﻣﺣﻔﻭﻅﺔ ﺃﻭ ﺍﻟﻣﺧﺯﻧﺔ‪.‬‬
‫ﻻ ﺗﺭﻛﻳﺑﻬﺎ ﻓﻲ ﻣﻛﺎﻥ ﺣﻳﺙ ﻳﻭﺟﺩ ﺧﻁﺭ ﺗﺳﺭﻳﺏ ﻏﺎﺯ ﻗﺎﺑﻝ ﻟﻼﺷﺗﻌﺎﻝ‪.‬‬
‫ﻻ ﺗﺭﻛﺏ ﺍﻟﻭﺣﺩﺓ ﺑﺎﻟﻘﺭﺏ ﻣﻥ ﻣﺻﺩﺭ ﺣﺭﺍﺭﺓ ﺃﻭ ﺑﺧﺎﺭ ﺃﻭ ﻏﺎﺯ ﻗﺎﺑﻝ ﻟﻼﺷﺗﻌﺎﻝ‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺑﺣﻳﺙ ﻻ ﻳﺗﺳﺑﺏ ﺍﻟﺻﺭﻑ ﻓﻲ ﺃﻱ ﻣﺷﻛﻠﺔ‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻭﻛﺑﻝ ﺍﻟﻧﻘﻝ ﻭﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻋﻠﻰ ﺑﻌﺩ ‪ 1‬ﻣﺗﺭ ﻋﻠﻰ ﺍﻷﻗﻝ ﻣﻥ ﺃﺟﻬﺯﺓ‬
‫ﺍﺳﺗﻘﺑﺎﻝ ﺍﻟﺗﻠﻳﻔﺯﻳﻭﻥ ﺃﻭ ﺍﻟﺭﺍﺩﻳﻭ‪ .‬ﻭﺍﻟﻐﺭﺽ ﻣﻥ ﺫﻟﻙ ﻫﻭ ﻣﻧﻊ ﺗﺩﺍﺧﻝ ﺍﺳﺗﻘﺑﺎﻝ ﺍﻟﺗﻠﻳﻔﺯﻳﻭﻥ ﺃﻭ ﺿﻭﺿﺎء ﺍﻟﺭﺍﺩﻳﻭ‪.‬‬
‫)ﺣﺗﻰ ﻟﻭ ﻗﻣﺕ ﺑﺎﻟﺗﺭﻛﻳﺏ ﻋﻠﻰ ﺑﻌﺩ ﺃﻛﺛﺭ ﻣﻥ ‪ 1‬ﻣﺗﺭ‪ ،‬ﻓﻣﻥ ﺍﻟﻣﻣﻛﻥ ﺃﻥ ﺗﺗﻠﻘﻰ ﺿﻭﺿﺎء ﻓﻲ ﺑﻌﺽ ﺍﻟﻅﺭﻭﻑ‪(.‬‬
‫ﺇﺫﺍ ﻛﺎﻥ ﻣﻥ ﺍﻟﻣﻣﻛﻥ ﺍﻗﺗﺭﺍﺏ ﺃﻁﻔﺎﻝ ﺃﻗﻝ ﻣﻥ ‪ 10‬ﺳﻧﻭﺍﺕ ﻣﻥ ﺍﻟﻭﺣﺩﺓ‪ ،‬ﺍﺗﺧﺫ ﺇﺟﺭﺍءﺍﺕ ﻭﻗﺎﺋﻳﺔ ﺑﺣﻳﺙ ﻻ ﻳﻣﻛﻧﻬﻡ ﺍﻟﻭﺻﻭﻝ ﻟﻠﻭﺣﺩﺓ‪.‬‬
‫ﻣﺭﺷﺢ )ﻛﺑﻳﺭ(‬
‫‪(AR18) 2‬‬
‫‪(AR24) 1‬‬
‫ﺧﺭﻁﻭﻡ ﺻﺭﻑ‬
‫ﻟﺗﺭﻛﻳﺏ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺻﺭﻑ ‪VP25‬‬
‫)ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ‪ ،32‬ﺍﻟﻘﻁﺭ ﺍﻟﺩﺍﺧﻠﻲ ‪(25‬‬
‫‪1‬‬
‫‪Ar-2‬‬
‫‪2017/8/8 13:09:01‬‬
‫‪9381858019-02_IM_AR.indd Sec1:2‬‬
‫• ﺣﺩﺩ ﻣﻭﺿﻊ ﺍﻟﺗﺭﻛﻳﺏ ﻣﻊ ﺍﻟﻌﻣﻳﻝ ﻛﺎﻟﺗﺎﻟﻲ‪:‬‬
‫‪ .3.3‬ﺗﺛﺑﻳﺕ ﺍﻟﻭﺣﺩﺓ‬
‫)‪ (1‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻓﻲ ﻣﻛﺎﻥ ﻗﻭﻱ ﺑﻣﺎ ﻳﻛﻔﻲ ﻟﺗﺣﻣﻝ ﻭﺯﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫)‪ (2‬ﻳﺟﺏ ﻋﺩﻡ ﺇﻋﺎﻗﺔ ﻣﻧﺎﻓﺫ ﺍﻹﺩﺧﺎﻝ ﻭﺍﻹﺧﺭﺍﺝ‪ ،‬ﻭﻳﺟﺏ ﺇﺗﺎﺣﺔ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﻓﻲ ﻛﺎﻓﺔ ﺃﻧﺣﺎء ﺍﻟﻐﺭﻓﺔ‪.‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﻓﻲ ﻣﻛﺎﻥ ﻳﻣﻛﻧﻪ ﺗﺣﻣﻝ ﺣﻣﻝ ﻳﻌﺎﺩﻝ ‪ 5‬ﺃﻣﺛﺎﻝ ﻭﺯﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺭﺋﻳﺳﻳﺔ ﻋﻠﻰ ﺍﻷﻗﻝ ﻭﻻ ﻳﺿﺧﻡ ﺍﻟﺻﻭﺕ ﺃﻭ‬
‫ﺍﻻﻫﺗﺯﺍﺯ‪ .‬ﺇﺫﺍ ﻟﻡ ﻳﻛﻥ ﻣﻛﺎﻥ ﺍﻟﺗﺭﻛﻳﺏ ﻗﻭﻳًﺎ ﺑﻣﺎ ﻳﻛﻔﻲ‪ ،‬ﻓﻘﺩ ﺗﺳﻘﻁ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺗﺳﺑﺏ ﺇﺻﺎﺑﺎﺕ‪.‬‬
‫)‪ (3‬ﺍﺗﺭﻙ ﺍﻟﻣﺳﺎﻓﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺻﻳﺎﻧﺔ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء‪.‬‬
‫)‪ (4‬ﻣﻛﺎﻥ ﻳﻣﻛﻥ ﻟﻠﻭﺣﺩﺓ ﻣﻧﻪ ﺗﻭﺯﻳﻊ ﺍﻟﻬﻭﺍء ﺑﺎﻟﺗﺳﺎﻭﻱ ﻓﻲ ﻛﺎﻓﺔ ﺃﻧﺣﺎء ﺍﻟﻐﺭﻓﺔ‪.‬‬
‫ﺇﺫﺍ ﺗﻡ ﺗﻧﻔﻳﺫ ﺍﻟﻌﻣﻝ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺇﻁﺎﺭ ﺍﻟﻠﻭﺣﺔ ﻓﻘﻁ‪ ،‬ﻓﻬﻧﺎﻙ ﺧﻁﺭ ﺑﺄﻥ ﺗﺻﺑﺢ ﺍﻟﻭﺣﺩﺓ ﻣﻔﻛﻭﻛﺔ‪ .‬ﻳﺟﺏ ﺗﻭﺧﻲ ﺍﻟﺣﺫﺭ‪.‬‬
‫)‪ (5‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﻣﻛﺎﻥ ﻳﻣﻛﻥ ﺇﺟﺭﺍء ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﺑﺳﻬﻭﻟﺔ‪.‬‬
‫)‪ (6‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﻣﻛﺎﻥ ﻳﺳﻬﻝ ﻣﻧﻪ ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﺍﻟﻭﺻﻼﺕ‪.‬‬
‫‪ .1.3.3‬ﻣﺛﺎﻝ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ‬
‫)‪ (7‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﻣﻛﺎﻥ ﻳﺳﻬﻝ ﻣﻧﻪ ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻷﻧﺑﻭﺑﺔ ﺍﻟﺗﻲ ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ‪.‬‬
‫)‪ (1‬ﺟﺎﻧﺏ ﺍﻹﺩﺧﺎﻝ‬
‫• ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻷﻧﺑﻭﺏ ﻓﻲ ﻓﻠﻧﺷﺔ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺗﻲ ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻔﻠﻧﺷﺔ ﻓﻲ ﺍﻟﺟﺳﻡ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺑﺭﺍﻏﻲ ﺍﻟﻠﻭﻟﺑﺔ ﺍﻟﺗﻲ ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ‪.‬‬
‫• ﻗﻡ ﺑﻠﻑ ﻓﻠﻧﺷﺔ ﺍﻹﺩﺧﺎﻝ ﺍﻟﻣﺗﺻﻠﺔ ﺑﺎﻷﻧﺑﻭﺏ ﺑﺷﺭﻳﻁ ﺃﻟﻣﻧﻳﻭﻡ ﺃﻭ ﻏﻳﺭﻩ ﻟﺗﺟﻧﺏ ﺗﺳﺭﻳﺏ ﺍﻟﻬﻭﺍء‪.‬‬
‫)‪ (8‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﻣﻛﺎﻥ ﻻ ﻳﺗﻡ ﻓﻳﻪ ﺗﺿﺧﻳﻡ ﺍﻟﺿﻭﺿﺎء ﺃﻭ ﺍﻻﻫﺗﺯﺍﺯﺍﺕ‪.‬‬
‫)‪ (9‬ﺧﺫ ﻓﻲ ﺍﻻﻋﺗﺑﺎﺭ ﺃﻋﻣﺎﻝ ﺍﻟﺻﻳﺎﻧﺔ ﻭﺍﺗﺭﻙ ﺍﻟﻣﺳﺎﻓﺎﺕ ﺍﻟﻼﺯﻣﺔ‪ .‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﻓﻲ ﻣﻛﺎﻥ ﻳﺗﻳﺢ ﺇﺯﺍﻟﺔ ﺍﻟﻣﺭﺷﺢ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫‪ .2.3‬ﺃﺑﻌﺎﺩ ﺍﻟﺗﺭﻛﻳﺏ‬
‫ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﺍﻷﻧﺑﻭﺏ ﻓﻲ ﺟﺎﻧﺏ ﺍﻹﺩﺧﺎﻝ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻣﺭﺷﺢ ﺍﻟﻣﺭﻓﻕ ﻭﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻣﺭﺷﺢ ﺍﻟﺫﻱ ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ ﻓﻲ ﻓﺗﺣﺔ‬
‫ﺍﻹﺩﺧﺎﻝ ﺑﺈﺣﻛﺎﻡ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﺇﻣﻛﺎﻧﻳﺔ ﺍﻟﻭﺻﻭﻝ ﻟﻠﺻﻳﺎﻧﺔ ﻷﻏﺭﺍﺽ ﺍﻟﻔﺣﺹ‪.‬‬
‫ﻻ ﺗﺿﻊ ﺃﻱ ﺃﺳﻼﻙ ﺃﻭ ﺇﺿﺎءﺓ ﻓﻲ ﻣﺳﺎﺣﺔ ﺍﻟﺧﺩﻣﺔ‪ ،‬ﻧﻅﺭً ﺍ ﻷﻧﻬﺎ ﺗﻌﻳﻕ ﺍﻟﺧﺩﻣﺔ‪.‬‬
‫ﺃﺑﻌﺎﺩ ﺍﻟﺗﺭﻛﻳﺏ‬
‫)‪ (2‬ﺟﺎﻧﺏ ﺍﻹﺧﺭﺍﺝ‬
‫• ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻷﻧﺑﻭﺏ ﻣﻊ ﺿﺑﻁ ﺍﻟﺟﺯء ﺍﻟﺩﺍﺧﻠﻲ ﻟﻔﻠﻧﺷﺔ ﺍﻹﺧﺭﺍﺝ‪.‬‬
‫• ﻗﻡ ﺑﻠﻑ ﻓﻠﻧﺷﺔ ﺍﻹﺧﺭﺍﺝ ﺍﻟﻣﺗﺻﻠﺔ ﺑﺎﻷﻧﺑﻭﺏ ﺑﺷﺭﻳﻁ ﺃﻟﻣﻧﻳﻭﻡ ﺃﻭ ﻏﻳﺭﻩ ﻟﺗﺟﻧﺏ ﺗﺳﺭﻳﺏ ﺍﻟﻬﻭﺍء‪.‬‬
‫• ﻗﻡ ﺑﻌﺯﻝ ﺍﻷﻧﺑﻭﺏ ﻟﺗﺟﻧﺏ ﺗﻛﺛﻑ ﺍﻟﻧﺩﻯ‪.‬‬
‫ﺳﻘﻑ ﻗﻭﻱ ﻭﻣﺗﻳﻥ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﺟﺎﻧﺏ‬
‫ﺍﻷﻳﺳﺭ‬
‫ﺍﻟﺟﺎﻧﺏ‬
‫ﺍﻷﻳﻣﻥ‬
‫ﻟﻣﻧﻊ ﺍﻷﺷﺧﺎﺹ ﻣﻥ ﻟﻣﺱ ﺍﻷﺟﺯﺍء ﺩﺍﺧﻝ ﺍﻟﻭﺣﺩﺓ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﺗﺭﻛﻳﺏ ﺷﺑﻛﺎﺕ ﻋﻠﻰ ﻣﻧﺎﻓﺫ ﺍﻹﺩﺧﺎﻝ ﻭﺍﻹﺧﺭﺍﺝ‪ .‬ﻳﺟﺏ ﺗﺻﻣﻳﻡ ﺍﻟﺷﺑﻛﺎﺕ‬
‫ﺑﺣﻳﺙ ﻻ ﻳﻣﻛﻥ ﺇﺯﺍﻟﺗﻬﺎ ﺑﺩﻭﻥ ﺃﺩﻭﺍﺕ‪.‬‬
‫ﺗﺣﻘﻕ ﻣﻥ ﺃﻥ ﺃﻋﻣﺎﻝ ﺗﺭﻛﻳﺏ ﺍﻷﻧﺑﻭﺏ ﻻ ﺗﺗﺟﺎﻭﺯ ﻧﻁﺎﻕ ﺍﻟﺿﻐﻁ ﺍﻟﺧﺎﺭﺟﻲ ﺍﻟﺛﺎﺑﺕ ﻟﻠﺟﻬﺎﺯ‪.‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﻋﺯﻝ ﺍﻷﻧﺎﺑﻳﺏ ﻟﺗﺟﻧﺏ ﺗﻛﺛﻑ ﺍﻟﻧﺩﻱ‪.‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﻭﺿﻊ ﻋﺎﺯﻝ ﺑﻳﻥ ﺍﻷﻧﺎﺑﻳﺏ ﻭﺍﻟﺣﻭﺍﺋﻁ ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺗﺧﺩﺍﻡ ﺃﻧﺎﺑﻳﺏ ﻣﻌﺩﻧﻳﺔ‪.‬‬
‫ﻳﺭﺟﻰ ﺗﻭﺿﻳﺢ ﻁﺭﻕ ﺍﻟﻣﻧﺎﻭﻟﺔ ﻭﺍﻟﻐﺳﻝ ﻟﻠﻣﻭﺍﺩ ﺍﻟﻣﺷﺗﺭﺍﺓ ﻣﺣﻠﻳًﺎ ﻟﻠﻌﻣﻳﻝ‪.‬‬
‫‪ 400‬ﻣﻡ ﺃﻭ‬
‫ﺃﻛﺛﺭ‬
‫‪ 150‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪1‬‬
‫ﻟﻣﻧﻊ ﺍﻷﺷﺧﺎﺹ ﻣﻥ ﻟﻣﺱ ﺍﻷﺟﺯﺍء ﺩﺍﺧﻝ ﺍﻟﻭﺣﺩﺓ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﺗﺭﻛﻳﺏ ﺷﺑﻛﺎﺕ ﻋﻠﻰ ﻣﻧﺎﻓﺫ ﺍﻹﺩﺧﺎﻝ ﻭﺍﻹﺧﺭﺍﺝ‪ .‬ﻳﺟﺏ ﺗﺻﻣﻳﻡ ﺍﻟﺷﺑﻛﺎﺕ‬
‫ﺑﺣﻳﺙ ﻻ ﻳﻣﻛﻥ ﺇﺯﺍﻟﺗﻬﺎ ﺑﺩﻭﻥ ﺃﺩﻭﺍﺕ‪.‬‬
‫‪ 400 1‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ ﻋﻧﺩ ﺍﻟﺗﺻﺭﻳﻑ ﻣﻥ ﻣﺎﺳﻭﺭﺓ ﺻﺭﻑ‬
‫ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﺍﻷﻧﺑﻭﺏ ﺑﻣﻧﻔﺫ ﺇﺧﺭﺍﺝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﻋﺯﻝ ﻣﻧﻔﺫ ﺍﻹﺧﺭﺍﺝ ﻭﺑﺭﺍﻏﻲ ﺍﻟﺗﺭﻛﻳﺏ ﻟﻣﻧﻊ ﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ ﻣﻥ‬
‫ﺣﻭﻝ ﺍﻟﻣﻧﻔﺫ‪.‬‬
‫• ﻋﻧﺩ ﺳﺣﺏ ﺍﻟﻬﻭﺍء ﻣﻥ ﺍﻟﺧﻠﻑ‬
‫‪ 300‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫ﻗﻡ ﺇﻋﺩﺍﺩ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﻟﻁﺭﺍﺯ ‪ AR07/09/12‬ﻋﻠﻰ ﻗﻳﻣﺔ ‪ 0‬ﺇﻟﻰ ‪ 30‬ﺑﺎﺳﻛﺎﻝ‪.‬‬
‫ﻗﻡ ﺇﻋﺩﺍﺩ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﻟﻁﺭﺍﺯ ‪ AR14/18/24‬ﻋﻠﻰ ﻗﻳﻣﺔ ‪ 0‬ﺇﻟﻰ ‪ 50‬ﺑﺎﺳﻛﺎﻝ‪.‬‬
‫‪ 5‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 225‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫ﻫﻭﺍء‬
‫‪ 20‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 2500‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫)ﻓﻲ ﺣﺎﻟﺔ ﻋﺩﻡ ﻭﺟﻭﺩ ﺳﻘﻑ(‬
‫ﺍﻟﻭﺻﻭﻝ ﻟﻠﺧﺩﻣﺔ‬
‫ﺍﻟﺳﻘﻑ‬
‫ﺃﻋﺩ ﺗﺭﻛﻳﺏ ﺍﻟﻐﻁﺎء ﻛﻣﺎ ﻳﻠﻲ‪.‬‬
‫• ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﺑﺭﺍﻏﻲ ﺛﻡ ﺇﺯﺍﻟﺔ ﺍﻟﻐﻁﺎء‪.‬‬
‫• ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻐﻁﺎء ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺑﺭﺍﻏﻲ ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﺃﺩﻧﺎﻩ‪.‬‬
‫ﺑﺭﻏﻲ‬
‫ﺍﻟﻁﺭﺍﺯ‬
‫‪AR07/09/12/14‬‬
‫‪6‬‬
‫‪AR18‬‬
‫‪7‬‬
‫‪AR24‬‬
‫‪8‬‬
‫ﺑﺭﻏﻲ‬
‫ﻏﻁﺎء‬
‫ﺍﻷﺭﺿﻳﺔ‬
‫• ﻋﻧﺩ ﺳﺣﺏ ﺍﻟﻬﻭﺍء ﻣﻥ ﺃﺳﻔﻝ‬
‫‪ 100‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 5‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫ﻫﻭﺍء‬
‫‪ 225‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 20‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫ﺍﻟﻭﺻﻭﻝ ﻟﻠﺧﺩﻣﺔ‬
‫ﺍﻟﺳﻘﻑ‬
‫ﺍﺿﺑﻁ ﺍﺗﺟﺎﻩ ﺍﻟﻬﻭﺍء ﻓﻲ ﺍﻟﻐﺭﻓﺔ ﺗﺑﻌًﺎ ﻟﺷﻛﻝ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ‪.‬‬
‫]ﻣﻧﻅﺭ ﻋﻠﻭﻱ[‬
‫ﻣﺳﺎﺣﺔ ﺍﻟﺧﺩﻣﺔ‬
‫‪ 400‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 100‬ﻣﻡ‬
‫ﺃﻭ ﺃﻛﺛﺭ‬
‫‪ 300‬ﻣﻡ ﺃﻭ‬
‫ﺃﻛﺛﺭ*‬
‫ﻫﻭﺍء‬
‫ﺻﻧﺩﻭﻕ‬
‫ﺍﻟﺗﺣﻛﻡ‬
‫ﺍﻟﻭﺻﻭﻝ ﻟﻠﺧﺩﻣﺔ‬
‫ﻫﻭﺍء‬
‫*‪ :‬ﺃﻋﻠﻰ ﻣﻥ ‪ 100‬ﻣﻡ ﻋﻧﺩ ﺳﺣﺏ ﺍﻟﻬﻭﺍء ﻣﻥ ﺃﺳﻔﻝ‬
‫‪Ar-3‬‬
‫‪2017/8/8 13:09:00‬‬
‫‪9381858019-02_IM_AR.indd Sec1:3‬‬
‫‪.2.3.3‬‬
‫ﺍﻹﺩﺧﺎﻝ ﺍﻟﺟﺎﻧﺑﻲ ‪ -‬ﺍﻹﺧﺭﺍﺝ ﺍﻟﺟﺎﻧﺑﻲ‬
‫ﻣﺎﺩﺓ ﺍﻟﻌﺯﻝ )ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺷﺭﻳﻁ ﺃﻟﻣﻧﻳﻭﻡ‬
‫ﻓﻠﻧﺷﺔ )ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺗﺭﻛﻳﺏ ﺍﻟﻣﺭﺷﺣﺎﺕ‬
‫• ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻣﺭﺷﺣﺎﺕ ﻓﻲ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﻫﻭﺍء‬
‫ﻣﺭﺷﺢ )ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫ﺷﺑﻛﺔ ﺍﻟﺳﺣﺏ‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺃﻧﺑﻭﺏ )ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫ﻫﻭﺍء‬
‫ﺍﻹﺩﺧﺎﻝ ﺍﻟﺟﺎﻧﺑﻲ ‪ -‬ﺍﻹﺧﺭﺍﺝ ﺍﻟﺟﺎﻧﺑﻲ )ﺃﻧﺑﻭﺏ(‬
‫ﻓﻠﻧﺷﺔ )ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺷﺭﻳﻁ ﺃﻟﻣﻧﻳﻭﻡ‬
‫ﺑﺭﻏﻲ ﻟﻭﻟﺑﻳﺔ ﻟﺗﻭﺻﻳﻝ ﺍﻟﻔﻠﻧﺷﺔ‬
‫)‪ M4 × 10‬ﻣﻡ‪/‬ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻣﺎﺩﺓ ﺍﻟﻌﺯﻝ )ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺷﺭﻳﻁ ﺃﻟﻣﻧﻳﻭﻡ‬
‫ﻓﻠﻧﺷﺔ )ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻣﺭﺷﺢ‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫ﻣﺭﺷﺢ )ﻣﻠﺣﻘﺎﺕ(‬
‫ﻫﻭﺍء‬
‫‪ 2 :AR07/09/12/14/18‬ﻣﺭﺷﺢ‬
‫‪ 3 :AR24‬ﻣﺭﺷﺢ‬
‫ﺃﻧﺑﻭﺏ )ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫ﺷﺑﻛﺔ ﺍﻟﺳﺣﺏ‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺍﻟﻣﺭﺷﺢ ﺍﻟﻭﺣﺩﺓ‬
‫ﻫﻭﺍء‬
‫ﺍﻹﺩﺧﺎﻝ ﺍﻟﺳﻔﻠﻲ ‪ -‬ﺍﻹﺧﺭﺍﺝ ﺍﻟﺟﺎﻧﺑﻲ‬
‫ﺃﻧﺑﻭﺏ )ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫ﺍﻟﻣﺭﺷﺢ‬
‫ﻫﻭﺍء‬
‫‪ .3.3.3‬ﺣﻔﺭ ﺛﻘﻭﺏ ﻟﻠﻣﺳﺎﻣﻳﺭ ﻭﺗﺭﻛﻳﺏ ﺍﻟﻣﺳﺎﻣﻳﺭ‬
‫• ﺑﺎﺳﺗﺧﺩﺍﻡ ﻗﺎﻟﺏ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﻗﻡ ﺑﺣﻔﺭ ﺛﻘﻭﺏ ﻟﻠﻣﺳﺎﻣﻳﺭ )‪ 4‬ﺛﻘﻭﺏ(‪.‬‬
‫ﻫﻭﺍء‬
‫ﺟﺎﻧﺏ ﺍﻹﺧﺭﺍﺝ‬
‫‪ 25‬ﻣﻡ‬
‫ﺷﺑﻛﺔ ﺍﻟﺳﺣﺏ‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻗﺎﺑﻝ ﺍﻟﺗﺭﻛﻳﺏ‬
‫ﻣﻭﺿﻊ ﺍﻟﺣﻔﺭ ﻟﻠﻣﺳﺎﻣﻳﺭ‬
‫‪ 19‬ﻣﻡ‬
‫‪A‬‬
‫‪ 198‬ﻣﻡ‬
‫‪ 25‬ﻣﻡ‬
‫ﻫﻭﺍء‬
‫ﺟﺎﻧﺏ ﺍﻹﺩﺧﺎﻝ‬
‫‪ 15‬ﻣﻡ‬
‫‪B‬‬
‫‪ 11‬ﻣﻡ‬
‫‪ 38‬ﻣﻡ‬
‫‪P200‬‬
‫‪ 295‬ﻣﻡ‬
‫‪ 130‬ﻣﻡ‬
‫‪ 109‬ﻣﻡ‬
‫‪ 70‬ﻣﻡ‬
‫‪ 11‬ﻣﻡ‬
‫‪A‬‬
‫‪AR07/09/12/14‬‬
‫‪AR18‬‬
‫‪AR24‬‬
‫‪A‬‬
‫‪ 650‬ﻣﻡ‬
‫‪ 850‬ﻣﻡ‬
‫‪ 1050‬ﻣﻡ‬
‫‪B‬‬
‫‪ P200×2=400‬ﻣﻡ‬
‫‪ P200×3=600‬ﻣﻡ‬
‫‪ P200×4=800‬ﻣﻡ‬
‫‪A‬‬
‫‪AR07/09/12/14‬‬
‫‪AR18‬‬
‫‪AR24‬‬
‫‪ 752‬ﻣﻡ‬
‫‪ 952‬ﻣﻡ‬
‫‪ 1152‬ﻣﻡ‬
‫‪Ar-4‬‬
‫‪2017/8/8 13:08:59‬‬
‫‪9381858019-02_IM_AR.indd Sec1:4‬‬
‫‪ .4.3.3‬ﺗﺛﺑﻳﺕ ﺍﻟﻭﺣﺩﺓ‬
‫‪ .4‬ﺗﺭﻛﻳﺏ ﺍﻟﻣﺎﺳﻭﺭﺓ‬
‫)‪ (1‬ﺗﻌﻠﻳﻕ ﺍﻟﻭﺣﺩﺓ‬
‫ﺧﻁﺎﻑ ﺗﻌﻠﻳﻕ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺗﻭﺥ ﺍﻟﺣﺫﺭ ﺣﺗﻰ ﻻ ﺗﺩﺧﻝ ﻣﺎﺩﺓ ﻏﺭﻳﺑﺔ )ﺍﻟﺯﻳﺕ ﺃﻭ ﺍﻟﻣﻳﺎﻩ ﺃﻭ ﻏﻳﺭﻩ( ﻓﻲ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺧﻼﻑ ﻁﺭﺍﺯﺍﺕ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ‪ .R410A‬ﺃﻳﺿًﺎ‪،‬‬
‫ﻋﻧﺩ ﺗﺧﺯﻳﻥ ﺍﻟﻣﻭﺍﺳﻳﺭ‪ ،‬ﻗﻡ ﺑﺳﺩ ﺍﻟﻔﺗﺣﺎﺕ ﺑﺈﺣﻛﺎﻡ ﻣﻥ ﺧﻼﻝ ﺍﻟﻘﺭﺹ ﺃﻭ ﺍﻟﺭﺑﻁ ﺃﻭ ﻏﻳﺭﻩ‪.‬‬
‫ﻣﺳﻣﺎﺭ ﺍﻟﺗﻌﻠﻳﻕ‬
‫ﺻﺎﻣﻭﻟﺔ ‪A‬‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻋﻧﺩ ﻟﺣﺎﻡ ﺍﻟﻣﻭﺍﺳﻳﺭ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﻧﻔﺦ ﻏﺎﺯ ﺍﻟﻧﻳﺗﺭﻭﺟﻳﻥ ﺍﻟﺟﺎﻑ ﻋﺑﺭﻫﺎ‪.‬‬
‫‪ .1.4‬ﺍﺧﺗﻳﺎﺭ ﻣﺎﺩﺓ ﺍﻟﻣﺎﺳﻭﺭﺓ‬
‫ﻓﻠﻛﺔ‬
‫)ﻣﻠﺣﻘﺎﺕ(‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺻﺎﻣﻭﻟﺔ ‪B‬‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ‬
‫ﻣﺣﻠﻳًﺎ(‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﻣﻭﺍﺳﻳﺭ ﻣﻭﺟﻭﺩﺓ ﻣﻥ ﻧﻅﺎﻡ ﺗﺑﺭﻳﺩ ﺁﺧﺭ ﺃﻭ ﺧﺎﺻﺔ ﺑﺳﺎﺋﻝ ﺗﺑﺭﻳﺩ ﺁﺧﺭ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻣﻭﺍﺳﻳﺭ ﺫﺍﺕ ﺟﻭﺍﻧﺏ ﺩﺍﺧﻠﻳﺔ ﻭﺧﺎﺭﺟﻳﺔ ﻧﻅﻳﻔﺔ ﺑﺩﻭﻥ ﺃﻱ ﺗﻠﻭﺙ ﻳﺅﺩﻱ ﺇﻟﻰ ﻣﺷﻛﻠﺔ ﺃﺛﻧﺎء ﺍﻻﺳﺗﺧﺩﺍﻡ‪ ،‬ﻣﺛﻝ ﺍﻟﺭﺻﺎﺹ ﺃﻭ‬
‫ﺍﻷﻛﺳﻳﺩ ﺃﻭ ﺍﻟﻐﺑﺎﺭ ﺃﻭ ﺑﻘﺎﻳﺎ ﺍﻟﻘﻁﻊ ﺃﻭ ﺍﻟﺯﻳﺕ ﺃﻭ ﺍﻟﻣﺎء‪.‬‬
‫ﻣﺳﻣﺎﺭ ﺍﻟﺗﻌﻠﻳﻕ‬
‫ﻣﻥ ﺍﻟﺿﺭﻭﺭﻱ ﺍﺳﺗﺧﺩﺍﻡ ﻣﻭﺍﺳﻳﺭ ﻧﺣﺎﺱ ﻋﺩﻳﻣﺔ ﺍﻻﻟﺗﺣﺎﻡ‪.‬‬
‫ﺍﻟﻣﺎﺩﺓ‪ :‬ﻣﻭﺍﺳﻳﺭ ﻧﺣﺎﺱ ﻋﺩﻳﻣﺔ ﺍﻻﻟﺗﺣﺎﻡ ﻣﺧﺗﺯﻟﺔ ﺑﺎﻟﻔﺳﻔﻭﺭ‬
‫ﻳﻭﺻﻰ ﺑﺄﻥ ﻳﻛﻭﻥ ﻣﻘﺩﺍﺭ ﺍﻟﺯﻳﺕ ﺍﻟﻣﺗﺑﻘﻲ ﺃﻗﻝ ﻣﻥ ‪ 40‬ﻣﺟﻡ‪ 10/‬ﻣﺗﺭ‪.‬‬
‫ﺧﻁﺎﻑ ﺗﻌﻠﻳﻕ‬
‫ﺻﺎﻣﻭﻟﺔ ‪A‬‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﻣﻭﺍﺳﻳﺭ ﻧﺣﺎﺱ ﺗﻌﺭﺿﺕ ﻟﻠﺗﻠﻑ ﺃﻭ ﺍﻟﻛﺳﺭ ﺃﻭ ﺗﻐﻳﺭ ﻟﻭﻥ ﺃﺟﺯﺍﺋﻬﺎ )ﺧﺎﺻﺔ ﺍﻟﺳﻁﺢ ﺍﻟﺩﺍﺧﻠﻲ(‪ .‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﻳﺗﻌﺭﺽ‬
‫ﺻﻣﺎﻡ ﺍﻟﺗﻭﺳﻌﺔ ﺃﻭ ﺍﻷﻧﺑﻭﺏ ﺍﻟﺷﻌﺭﻱ ﻟﻼﻧﺳﺩﺍﺩ ﺑﺎﻟﻣﻠﻭﺛﺎﺕ‪.‬‬
‫ﻓﻠﻛﺔ‬
‫)ﻣﻠﺣﻘﺎﺕ(‬
‫ﺍﻟﻭﺣﺩﺓ‬
‫ﻳﺅﺩﻱ ﺍﺧﺗﻳﺎﺭ ﺍﻟﻣﻭﺍﺳﻳﺭ ﻏﻳﺭ ﺍﻟﺻﺣﻳﺣﺔ ﺇﻟﻰ ﺗﺭﺍﺟﻊ ﺍﻷﺩﺍء‪ .‬ﻧﻅﺭً ﺍ ﻷﻥ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﺍﻟﺫﻱ ﻳﺳﺗﺧﺩﻡ ‪ R410A‬ﻳﺗﻌﺭﺽ ﻟﺿﻐﻁ‬
‫ﺃﻋﻠﻰ ﻣﻥ ﺍﺳﺗﺧﺩﺍﻡ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺍﻟﺗﻘﻠﻳﺩﻱ )‪ ،(R22‬ﻣﻥ ﺍﻟﺿﺭﻭﺭﻱ ﺍﺧﺗﻳﺎﺭ ﻣﻭﺍﺩ ﻣﻧﺎﺳﺑﺔ‪.‬‬
‫ﺻﺎﻣﻭﻟﺔ ‪B‬‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫• ﻳﺗﻡ ﺗﻭﺿﻳﺢ ﺳﻣﺎﻛﺔ ﻣﻭﺍﺳﻳﺭ ﺍﻟﻧﺣﺎﺱ ﺍﻟﻣﺳﺗﺧﺩﻣﺔ ﻣﻊ ‪ R410A‬ﻓﻲ ﺍﻟﺟﺩﻭﻝ‪.‬‬
‫• ﻻ ﺗﺳﺗﺧﺩﻡ ﻣﻭﺍﺳﻳﺭ ﻧﺣﺎﺱ ﺃﺭﻓﻊ ﻣﻥ ﺗﻠﻙ ﺍﻟﻣﺑﻳﻧﺔ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺣﺗﻰ ﻟﻭ ﻛﺎﻧﺕ ﻣﺗﺎﺣﺔ ﻓﻲ ﺍﻟﺳﻭﻕ‪.‬‬
‫ﺳﻣﺎﻛﺔ ﻣﻭﺍﺳﻳﺭ ﺍﻟﻧﺣﺎﺱ ﺍﻟﻣﻠﺩﻧﺔ )‪(R410A‬‬
‫‪ 20‬ﻣﻡ‬
‫ﺃﻭ ﺃﻗﻝ‬
‫‪ 20‬ﻣﻡ ﺃﻭ‬
‫ﺃﻗﻝ‬
‫ﺇﺫﺍ ﻛﺎﻥ ﻁﻭﻝ ﻣﺳﻣﺎﺭ ﺍﻟﺗﻌﻠﻳﻕ ﻳﺯﻳﺩ ﻋﻥ ‪ 20‬ﻣﻡ‪ ،‬ﻓﻠﻥ ﻳﻛﻭﻥ ﻣﻼﺋﻣًﺎ ﻟﻸﻋﻣﺎﻝ ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ﻟﻠﻣﺎﺳﻭﺭﺓ ]ﻣﻡ )ﺑﻭﺻﺔ([‬
‫‪(1/4) 6.35‬‬
‫ﺍﻟﺳﻣﺎﻛﺔ ]ﻣﻡ[‬
‫‪0.80‬‬
‫‪(3/8) 9.52‬‬
‫‪0.80‬‬
‫‪(1/2) 12.70‬‬
‫‪(5/8) 15.88‬‬
‫‪(3/4) 19.05‬‬
‫‪0.80‬‬
‫‪1.00‬‬
‫‪1.20‬‬
‫• ﻓﺗﺢ ﻭﻏﻠﻕ ﻏﻁﺎء ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ‬
‫• ﺍﺳﺗﺑﺩﺍﻝ ﻣﺿﺧﺔ ﺍﻟﺻﺭﻑ‬
‫‪ .2.4‬ﻣﺗﻁﻠﺑﺎﺕ ﺍﻟﻣﺎﺳﻭﺭﺓ‬
‫)‪ (2‬ﺿﺑﻁ ﺍﻟﻣﺳﺗﻭﻯ‬
‫ﺿﺑﻁ ﺍﻟﻣﺳﺗﻭﻯ ﻓﻲ ﺍﻻﺗﺟﺎﻩ ﺍﻷﻓﻘﻲ ﻟﻠﻘﺎﻋﺩﺓ ﻓﻲ ﺃﻋﻠﻰ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺍﻟﺳﻘﻑ‬
‫ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻭﺻﻑ ﻁﻭﻝ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺗﻭﺻﻳﻝ ﺃﻭ ﺍﻟﺗﻌﺭﻑ ﻋﻠﻰ ﻓﺭﻕ ﺍﻻﺭﺗﻔﺎﻉ ﺍﻟﺧﺎﺻﺔ ﺑﻬﺎ‪.‬‬
‫• ﺍﺳﺗﺧﺩﻡ ﻣﻭﺍﺳﻳﺭ ﺫﺍﺕ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﻣﻘﺎﻭﻡ ﻟﻠﻣﺎء‪.‬‬
‫ﺍﻟﻣﺳﺗﻭﻯ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻣﺣﻅﻭﺭ‬
‫‪ 10‬ﻣﻡ ﺃﻭ ﺃﻗﻝ‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺣﻭﻝ ﻛﻝ ﻣﻥ ﻣﻭﺍﺳﻳﺭ ﺍﻟﻐﺎﺯ ﻭﺍﻟﺳﺎﺋﻝ‪ .‬ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﻟﻘﻳﺎﻡ ﺑﺫﻟﻙ ﻗﺩ ﻳﺅﺩﻱ ﺇﻟﻰ ﺗﺳﺭﻳﺏ ﻓﻲ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﺑﻣﻘﺎﻭﻣﺔ ﺣﺭﺍﺭﺓ ﺗﺯﻳﺩ ﻋﻥ ‪ 120‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ )ﻁﺭﺍﺯ ﺍﻟﺩﻭﺭﺓ ﺍﻟﻌﻛﺳﻳﺔ ﻓﻘﻁ(‬
‫ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻙ‪ ،‬ﺇﺫﺍ ﻛﺎﻥ ﻣﺳﺗﻭﻯ ﺍﻟﺭﻁﻭﺑﺔ ﻓﻲ ﻣﻛﺎﻥ ﺗﺭﻛﻳﺏ ﻣﺎﺳﻭﺭﺓ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﻣﻥ ﺍﻟﻣﺗﻭﻗﻊ ﺃﻥ ﻳﺗﺟﺎﻭﺯ ‪ ،70%‬ﻓﻘﻡ ﺑﺗﺭﻛﻳﺏ‬
‫ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﺣﻭﻝ ﻣﺎﺳﻭﺭﺓ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪ .‬ﻭﺇﺫﺍ ﻛﺎﻥ ﻣﺳﺗﻭﻯ ﺍﻟﺭﻁﻭﺑﺔ ﺍﻟﻣﺗﻭﻗﻊ ‪ 70‬ﺇﻟﻰ ‪ ،80%‬ﺍﺳﺗﺧﺩﻡ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﺑﺳُﻣﻙ‬
‫‪ 15‬ﻣﻡ ﺃﻭ ﺃﻛﺑﺭ ﻭﺇﺫﺍ ﻛﺎﻧﺕ ﺍﻟﺭﻁﻭﺑﺔ ﺍﻟﻣﺗﻭﻗﻌﺔ ﺗﺗﺟﺎﻭﺯ ‪ ،80%‬ﺍﺳﺗﺧﺩﻡ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﺑﺳُﻣﻙ ‪ 20‬ﻣﻡ ﺃﻭ ﺃﻛﺑﺭ‪ .‬ﺇﺫﺍ ﻟﻡ ﻳﻛﻥ ﺍﻟﻌﺎﺯﻝ‬
‫ﺍﻟﺣﺭﺍﺭﻱ ﺑﺎﻟﺳُﻣﻙ ﺍﻟﻣﺣﺩﺩ‪ ،‬ﻗﺩ ﻳﺗﻛﻭﻥ ﺗﻛﺛﻑ ﻋﻠﻰ ﺳﻁﺢ ﺍﻟﻌﺎﺯﻝ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻙ‪ ،‬ﺍﺳﺗﺧﺩﻡ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﺑﻘﺩﺭﺓ ﺗﻭﺻﻳﻝ ﺣﺭﺍﺭﺓ‬
‫‪ 0.045‬ﻭﺍﺕ‪)/‬ﻣﻳﻠﻲ ﻛﻳﻠﻔﻥ( ﺃﻭ ﺃﻗﻝ )ﻋﻧﺩ ‪ 20‬ﺩﺭﺟﺔ ﻣﺋﻭﻳﺔ(‪.‬‬
‫ﺟﻳﺩ‬
‫ﺧﺭﻁﻭﻡ ﺻﺭﻑ‬
‫ﻗﻡ ﺑﻌﻣﻝ ﻣﻳﻭﻝ ﻁﻔﻳﻑ ﻓﻲ ﺍﻟﺟﺎﻧﺏ ﺍﻟﺫﻱ ﻳﺗﻡ ﻓﻳﻪ ﺗﻭﺻﻳﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ‪ .‬ﻳﺟﺏ ﺃﻥ ﻳﻛﻭﻥ ﺍﻟﻣﻳﻝ ﺿﻣﻥ ﻧﻁﺎﻕ ‪ 0‬ﺇﻟﻰ ‪ 10‬ﻣﻡ‪.‬‬
‫ﺍﻟﻣﺳﺗﻭﻯ‬
‫ﻫﻭﺍء‬
‫ﻣﺣﻅﻭﺭ‬
‫‪ 5‬ﻣﻡ ﺃﻭ ﺃﻗﻝ‬
‫ﺟﻳﺩ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺍﺗﺭﻙ ﻣﺳﺎﻓﺔ ‪ 100‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ ﺑﻳﻥ ﻣﻧﻔﺫ ﺍﻹﺩﺧﺎﻝ ﻭﺍﻟﺳﻘﻑ‪.‬‬
‫ﺛﺑﺕ ﺍﻟﻭﺣﺩﺓ ﺑﺈﺣﻛﺎﻡ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺻﻣﺎﻭﻳﻝ ‪ A‬ﻭ ‪.B‬‬
‫‪Ar-5‬‬
‫‪2017/8/8 13:08:59‬‬
‫‪9381858019-02_IM_AR.indd Sec1:5‬‬
‫ﻋﻧﺩ ﺭﺑﻁ ﺻﺎﻣﻭﻟﺔ ﺍﻟﺗﻔﻠﻳﺞ ﺑﺷﻛﻝ ﺻﺣﻳﺢ ﺑﺎﻟﻳﺩ‪ ،‬ﺃﻣﺳﻙ ﻗﺎﺭﻧﺔ ﺟﺎﻧﺏ ﺍﻟﺟﺳﻡ ﺑﻣﻔﺗﺎﺡ ﻣﻧﻔﺻﻝ‪ ،‬ﺛﻡ ﺃﺭﺑﻁ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻣﻔﺗﺎﺡ ﺭﺑﻁ‪) .‬ﺭﺍﺟﻊ‬
‫ﺍﻟﺟﺩﻭﻝ ﺍﻟﺗﺎﻟﻲ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻋﺯﻡ ﺭﺑﻁ ﺻﺎﻣﻭﻟﺔ ﺍﻟﺗﻔﻠﻳﺞ‪(.‬‬
‫‪ .3.4‬ﻭﺻﻠﺔ ﺗﻔﻠﻳﺞ )ﻭﺻﻠﺔ ﺍﻟﻣﺎﺳﻭﺭﺓ(‬
‫ﺍﺭﺑﻁ ﺑﻣﻔﺗﺎﺣﻳﻥ ‪.2‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﺍﺭﺑﻁ ﺍﻟﺻﻣﺎﻭﻳﻝ ﺍﻟﻣﻔﻠﺟﺔ ﺑﻣﻔﺗﺎﺡ ﺭﺑﻁ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻁﺭﻳﻕ ﺍﻟﺭﺑﻁ ﺍﻟﻣﺣﺩﺩﺓ‪ .‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻳﻣﻛﻥ ﺃﻥ ﺗﻧﻛﺳﺭ ﺍﻟﺻﻣﺎﻭﻳﻝ ﺍﻟﻣﻔﻠﺟﺔ ﺑﻌﺩ ﻓﺗﺭﺓ‬
‫ﻁﻭﻳﻠﺔ‪ ،‬ﻣﻣﺎ ﻳﺗﺳﺑﺏ ﻓﻲ ﺗﺳﺭﺏ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﻭﺗﻛﻭﻳﻥ ﻏﺎﺯ ﺧﻁﺭ ﻓﻲ ﺣﺎﻟﺔ ﺍﺗﺻﺎﻝ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺑﺎﻟﻠﻬﺏ‪.‬‬
‫ﻣﻔﺗﺎﺡ ﺗﺛﺑﻳﺕ‬
‫ﺻﺎﻣﻭﻟﺔ ﻣﻔﻠﺟﺔ‬
‫ﻣﻔﺗﺎﺡ ﺭﺑﻁ‬
‫‪ .1.3.4‬ﺍﻟﺗﻔﻠﻳﺞ‬
‫ﺍﺳﺗﺧﺩﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻳﺞ ﺧﺎﺻﺔ ﺑـ ‪.R410A‬‬
‫)‪(1‬‬
‫)‪(2‬‬
‫)‪(3‬‬
‫)‪(4‬‬
‫ﺍﻗﻁﻊ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺗﻭﺻﻳﻝ ﺣﺳﺏ ﺍﻟﻁﻭﻝ ﺍﻟﺿﺭﻭﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻗﺎﻁﻊ ﻣﻭﺍﺳﻳﺭ‪.‬‬
‫ﺃﻣﺳﻙ ﺍﻟﻣﺎﺳﻭﺭﺓ ﻷﺳﻔﻝ ﺑﺣﻳﺙ ﻻ ﺗﺩﺧﻝ ﻗﺻﺎﺻﺎﺕ ﺍﻟﻘﻁﻊ ﻓﻲ ﺍﻟﻣﺎﺳﻭﺭﺓ ﻭﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﺏ‪.‬‬
‫ﺃﺩﺧﻝ ﺍﻟﺻﺎﻣﻭﻟﺔ ﺍﻟﻣﻔﻠﺟﺔ )ﺍﺳﺗﺧﺩﻡ ﺩﺍﺋﻣًﺎ ﺍﻟﺻﺎﻣﻭﻟﺔ ﺍﻟﻣﻔﻠﺟﺔ ﺍﻟﻣﻠﺣﻘﺔ ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺍﻟﺧﺎﺭﺟﻳﺔ ﻋﻠﻰ ﺍﻟﺗﻭﺍﻟﻲ( ﻓﻲ‬
‫ﺍﻟﻣﺎﺳﻭﺭﺓ ﻭﻗﻡ ﺑﺗﻧﻔﻳﺫ ﻋﻣﻠﻳﺔ ﺍﻟﺗﻔﻠﻳﺞ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻳﺞ‪ .‬ﺍﺳﺗﺧﺩﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻳﺞ ﺧﺎﺻﺔ ﺑـ ‪ ،R410A‬ﻗﺩ ﻳﺣﺩﺙ ﺗﺳﺭﻳﺏ ﻓﻲ‬
‫ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ ﺇﺫﺍ ﺗﻡ ﺍﺳﺗﺧﺩﺍﻡ ﺻﻣﺎﻭﻳﻝ ﺗﻔﻠﻳﺞ ﺃﺧﺭﻯ‪.‬‬
‫ﻗﻡ ﺑﺣﻣﺎﻳﺔ ﺍﻟﻣﻭﺍﺳﻳﺭ ﻣﻥ ﺧﻼﻕ ﻗﺭﺻﻬﺎ ﺃﻭ ﻟﺻﻘﻬﺎ ﻟﻣﻧﻊ ﺩﺧﻭﻝ ﺍﻷﺗﺭﺑﺔ ﺃﻭ ﺍﻟﻐﺑﺎﺭ ﺃﻭ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫ﺍﻓﺣﺹ ﻣﺎ ﺇﺫﺍ ﺗﻡ ﺗﻔﻠﻳﺞ ]‪ [L‬ﺑﺷﻛﻝ ﻣﺗﺳﻕ ﺃﻡ ﻻ‬
‫ﻭﺃﻧﻪ ﻟﻡ ﻳﺗﻌﺭﺽ ﻟﻠﻛﺳﺭ ﺃﻭ ﺍﻟﺧﺩﺵ‪.‬‬
‫ﻣﺎﺳﻭﺭﺓ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)ﺟﺎﻧﺏ ﺍﻟﺟﺳﻡ(‬
‫ﻣﺎﺳﻭﺭﺓ ﺗﻭﺻﻳﻝ‬
‫ﺻﺎﻣﻭﻟﺔ ﻣﻔﻠﺟﺔ ]ﻣﻡ )ﺑﻭﺻﺔ([‬
‫‪ (1/4) 6.35‬ﻗﻁﺭ‬
‫‪ (3/8) 9.52‬ﻗﻁﺭ‬
‫‪ (1/2) 12.70‬ﻗﻁﺭ‬
‫‪ (5/8) 15.88‬ﻗﻁﺭ‬
‫‪ (3/4) 19.05‬ﻗﻁﺭ‬
‫‪B‬‬
‫ﻋﺯﻡ ﺍﻟﺭﺑﻁ ]ﻧﻳﻭﺗﻥ ﻣﺗﺭ )ﻛﺟﻡ ﻗﻭﺓ·ﺳﻡ([‬
‫‪ 16‬ﺇﻟﻰ ‪ 160) 18‬ﺇﻟﻰ ‪(180‬‬
‫‪ 32‬ﺇﻟﻰ ‪ 320) 42‬ﺇﻟﻰ ‪(420‬‬
‫‪ 49‬ﺇﻟﻰ ‪ 490) 61‬ﺇﻟﻰ ‪(610‬‬
‫‪ 63‬ﺇﻟﻰ ‪ 630) 75‬ﺇﻟﻰ ‪(750‬‬
‫‪ 90‬ﺇﻟﻰ ‪ 900) 110‬ﺇﻟﻰ ‪(1,100‬‬
‫ﻗﺎﻟﺏ‬
‫‪A‬‬
‫‪L‬‬
‫‪ .4.4‬ﺗﺭﻛﻳﺏ ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ‬
‫ﻣﺎﺳﻭﺭﺓ‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻣﺎﺩﺓ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺑﻌﺩ ﺗﻧﻔﻳﺫ ﻓﺣﺹ ﺗﺳﺭﻳﺏ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ )ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﺍﻟﺗﻔﺎﺻﻳﻝ(‪.‬‬
‫ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ﻟﻠﻣﺎﺳﻭﺭﺓ‬
‫]ﻣﻡ )ﺑﻭﺻﺔ([‬
‫ﺍﻟﺑُﻌﺩ ‪] A‬ﻣﻡ[‬
‫ﺃﺩﺍﺓ ﺍﻟﺗﻔﻠﻳﺞ ﻟـ ‪ ،R410A‬ﻣﻥ ﻧﻭﻉ‬
‫ﺍﻟﻘﺎﺑﺽ‬
‫‪(1/4) 6.35‬‬
‫‪(3/8) 9.52‬‬
‫‪(1/2) 12.70‬‬
‫‪(5/8) 15.88‬‬
‫‪(3/4) 19.05‬‬
‫‪ 0‬ﺇﻟﻰ ‪0.5‬‬
‫‪.1.4.4‬‬
‫‪0‬‬
‫ﺍﻟﺑﻌﺩ‬
‫‪] B-0.4‬ﻣﻡ[‬
‫‪9.1‬‬
‫‪13.2‬‬
‫‪16.6‬‬
‫‪19.7‬‬
‫‪24.0‬‬
‫ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﺃﺩﻭﺍﺕ ﺍﻟﺗﻔﻠﻳﺞ ﺍﻟﺗﻘﻠﻳﺩﻳﺔ )‪ (R22‬ﻟﺗﻔﻠﻳﺞ ﻣﻭﺍﺳﻳﺭ ‪ ،R410A‬ﻳﺟﺏ ﺃﻥ ﻳﻛﻭﻥ ﺍﻟﺑﻌﺩ ‪ A‬ﺃﻛﺑﺭ ﺑﻣﻘﺩﺍﺭ ‪ 0.5‬ﻣﻡ ﺗﻘﺭﻳﺑًﺎ ﻣﻥ‬
‫ﺍﻟﺑﻌﺩ ﺍﻟﻣﺑﻳﻥ ﻓﻲ ﺍﻟﺟﺩﻭﻝ )ﻟﻠﺗﻔﻠﻳﺞ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺃﺩﻭﺍﺕ ﺗﻔﻠﻳﺞ ‪ (R410A‬ﻭﺫﻟﻙ ﻟﺗﺣﻘﻳﻕ ﺍﻟﺗﻔﻠﻳﺞ ﺍﻟﻣﺣﺩﺩ‪ .‬ﺍﺳﺗﺧﺩﻡ ﻣﻘﻳﺎﺱ ﺳﻣﺎﻛﺔ ﻟﻘﻳﺎﺱ ﺍﻟﺑُﻌﺩ‬
‫‪ .A‬ﻳﻭﺻﻰ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻳﺞ ﺧﺎﺻﺔ ﺑـ ‪.R410A‬‬
‫ﺍﻟﻌﺭﺽ ﻋﺑﺭ‬
‫ﺍﻟﻣﺳﻁﺣﺎﺕ‬
‫ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ﻟﻠﻣﺎﺳﻭﺭﺓ ]ﻣﻡ‬
‫)ﺑﻭﺻﺔ([‬
‫ﺍﻟﻌﺭﺽ ﻋﺑﺭ ﻣﺳﻁﺣﺎﺕ ﺍﻟﺻﺎﻣﻭﻟﺔ‬
‫ﺍﻟﻣﻔﻠﺟﺔ ]ﻣﻡ[‬
‫‪(1/4) 6.35‬‬
‫‪17‬‬
‫‪(3/8) 9.52‬‬
‫‪22‬‬
‫‪(1/2) 12.70‬‬
‫‪26‬‬
‫‪(5/8) 15.88‬‬
‫‪29‬‬
‫‪(3/4) 19.05‬‬
‫‪36‬‬
‫• ﺍﻋﺯﻝ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ )ﻣﻠﺣﻘﺎﺕ( ﺣﻭﻝ ﻣﺎﺳﻭﺭﺓ ﺍﻟﻐﺎﺯ ﻭﻣﺎﺳﻭﺭﺓ ﺍﻟﺳﺎﺋﻝ ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫• ﺑﻌﺩ ﺗﺭﻛﻳﺏ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‪ ،‬ﻗﻡ ﺑﻠﻑ ﻛﻼ ﻣﻥ ﺍﻟﻧﻬﺎﻳﺗﻳﻥ ﺑﺷﺭﻳﻁ ﻓﻳﻧﻳﻠﻲ ﺑﺣﻳﺙ ﻻ ﺗﻭﺟﺩ ﻫﻧﺎﻙ ﺃﻱ ﻓﺟﻭﺓ‪.‬‬
‫• ﺑﻌﺩ ﺗﺭﻛﻳﺏ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‪ ،‬ﻗﻡ ﺑﺗﺛﺑﻳﺗﻪ ﺑﺎﺳﺗﺧﺩﺍﻡ ‪ 2‬ﺍﺛﻧﻳﻥ ﻣﻥ ﺭﻭﺍﺑﻁ ﺍﻟﻛﺑﻼﺕ )ﺍﻟﻛﺑﻳﺭﺓ( ﻭﺍﺣﺩﺓ ﻋﻠﻰ ﻛﻝ ﻧﻬﺎﻳﺔ ﻟﻠﻌﺎﺯﻝ‪.‬‬
‫• ﺗﺄﻛﺩ ﻣﻥ ﺃﻥ ﺭﻭﺍﺑﻁ ﺍﻟﻛﺑﻼﺕ ﺗﻁﻭﻕ ﻣﺎﺳﻭﺭﺓ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ‪.‬‬
‫ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‬
‫)ﻣﻠﺣﻘﺎﺕ(‬
‫ﻗﻡ ﺑﺗﻐﻁﻳﺔ ﻫﺫﺍ ﺍﻟﺟﺯء ﺑﻌﺎﺯﻝ‬
‫ﺣﺭﺍﺭﻱ‪.‬‬
‫ﻋﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﺓ‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻛﺑﻳﺭ(‬
‫)ﻣﻠﺣﻘﺎﺕ(‬
‫ﺗﻧﺑﻳﻪ‬
‫‪ .2.3.4‬ﺛﻧﻲ ﺍﻟﻣﻭﺍﺳﻳﺭ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫ﻋﺎﺯﻝ ﺣﺭﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‬
‫ﺑﻌﺩ ﻓﺣﺹ ﺗﺳﺭﻳﺏ ﺍﻟﻐﺎﺯ )ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ(‪ ،‬ﻗﻡ ﺑﺗﻧﻔﻳﺫ ﻫﺫﺍ ﺍﻟﻘﺳﻡ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺷﻛﻳﻝ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺎﻟﻳﺩ‪ ،‬ﺗﻭﺥ ﺍﻟﺣﺫﺭ ﺣﺗﻰ ﻻ ﺗﺗﻠﻔﻬﺎ‪.‬‬
‫ﻻ ﺗﺛﻧﻲ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺯﺍﻭﻳﺔ ﺗﺯﻳﺩ ﻋﻥ ‪ 90‬ﺩﺭﺟﺔ‪.‬‬
‫ﻋﻧﺩ ﺛﻧﻲ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺷﻛﻝ ﻣﺗﻛﺭﺭ ﺃﻭ ﺗﻣﺩﻳﺩﻫﺎ‪ ،‬ﺳﻭﻑ ﺗﺻﺑﺢ ﺍﻟﻣﺎﺩﺓ ﻣﺗﺻﻠﺑﺔ‪ ،‬ﻣﻣﺎ ﻳﺻﻌﺏ ﺛﻧﻳﻬﺎ ﺃﻭ ﺗﻣﺩﻳﺩﻫﺎ ﻣﺭﺓ ﺃﺧﺭﻯ‪.‬‬
‫ﻻ ﺗﺛﻧﻲ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺗﻣﺩﻫﺎ ﻷﻛﺛﺭ ﻣﻥ ‪ 3‬ﻣﺭﺍﺕ‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ ﺣﻭﻝ ﻛﻝ ﻣﻥ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺍﻟﻛﺑﻳﺭﺓ )ﺍﻟﻐﺎﺯ( ﻭﺍﻟﺻﻐﻳﺭﺓ )ﺍﻟﺳﺎﺋﻝ(‪ .‬ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﻟﻘﻳﺎﻡ ﺑﺫﻟﻙ ﻗﺩ ﻳﺅﺩﻱ ﺇﻟﻰ‬
‫ﺗﺳﺭﻳﺏ ﻓﻲ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺗﻔﺎﺩﻱ ﻛﺳﺭ ﺍﻟﻣﺎﺳﻭﺭﺓ‪ ،‬ﺗﺟﻧﺏ ﻋﻣﻝ ﺛﻧﻳﺎﺕ ﺣﺎﺩﺓ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺛﻧﻲ ﺍﻟﻣﺎﺳﻭﺭﺓ ﻋﺩﺓ ﻣﺭﺍﺕ ﻓﻲ ﻧﻔﺱ ﺍﻟﻣﻛﺎﻥ‪ ،‬ﻓﺳﻭﻑ ﺗﻧﻛﺳﺭ‪.‬‬
‫‪ .3.3.4‬ﺗﻭﺻﻳﻝ ﺍﻟﻣﺎﺳﻭﺭﺓ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺗﺭﻛﻳﺏ ﺍﻟﻣﺎﺳﻭﺭﺓ ﻣﻘﺎﺑﻝ ﺍﻟﻣﻧﻔﺫ ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪ .‬ﺇﺫﺍ ﻛﺎﻥ ﺍﻟﺗﻭﺳﻳﻁ ﻏﻳﺭ ﺻﺣﻳﺢ‪ ،‬ﻓﻼ ﻳﻣﻛﻥ ﺭﺑﻁ ﺻﺎﻣﻭﻟﺔ‬
‫ﺍﻟﺗﻔﻠﻳﺞ ﺑﺷﻛﻝ ﺳﻠﺱ‪ .‬ﻓﻲ ﺣﺎﻟﺔ ﺇﺩﺍﺭﺓ ﺻﺎﻣﻭﻟﺔ ﺍﻟﺗﻔﻠﻳﺞ ﺑﺎﻟﻘﻭﺓ‪ ،‬ﺳﻭﻑ ﺗﺗﻠﻑ ﺍﻟﺗﺳﻧﻳﻧﺎﺕ‪.‬‬
‫ﻻ ﺗﻘﻡ ﺑﺈﺯﺍﻟﺔ ﺻﻣﻭﻟﺔ ﺍﻟﺗﻔﻠﻳﺞ ﻣﻥ ﻣﺎﺳﻭﺭﺓ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻣﺑﺎﺷﺭﺓ ﻗﺑﻝ ﺗﻭﺻﻳﻝ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺗﻭﺻﻳﻝ‪.‬‬
‫ﺃﻣﺳﻙ ﻣﻔﺗﺎﺡ ﺍﻟﺭﺑﻁ ﻣﻥ ﻣﻘﺑﺿﻪ‪ ،‬ﻭﺍﺣﺗﻔﻅ ﺑﻪ ﻓﻲ ﺯﺍﻭﻳﺔ ﻗﺎﺋﻣﺔ ﻣﻊ ﺍﻟﻣﺎﺳﻭﺭﺓ‪ ،‬ﻣﻥ ﺃﺟﻝ ﺭﺑﻁ ﺻﺎﻣﻭﻟﺔ ﺍﻟﺗﻔﻠﻳﺞ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺣﻳﺙ ﻳﻣﻛﻥ ﺇﺯﺍﻟﺔ ﻏﻁﺎء ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ ﺑﺳﻬﻭﻟﺔ ﻷﺟﻝ ﺍﻟﺻﻳﺎﻧﺔ ﻋﻧﺩ ﺍﻟﺣﺎﺟﺔ‪.‬‬
‫ﻣﻥ ﺃﺟﻝ ﻣﻧﻊ ﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ ﻓﻲ ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﻋﺯﻝ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﺷﻛﻝ ﺟﻳﺩ‪.‬‬
‫‪Ar-6‬‬
‫‪2017/8/8 13:08:59‬‬
‫‪9381858019-02_IM_AR.indd Sec1:6‬‬
‫‪ .B1.5‬ﻁﺭﺍﺯ ‪ARXK**GALH‬‬
‫‪ .5‬ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ‬
‫• ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻣﻧﻔﺫ ﺍﻟﺻﺭﻑ ﻋﻠﻰ ﺍﻟﺟﺎﻧﺏ ﺍﻷﻳﺳﺭ ﻟﻠﻭﺣﺩﺓ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﻏﻁﺎء ﺍﻟﺻﺭﻑ ﺛﻡ ﺗﺭﻛﻳﺑﻪ ﻓﻲ ﻣﻧﻔﺫ ﺻﺭﻑ ﺍﻟﺟﺎﻧﺏ ﺍﻷﻳﻣﻥ‪.‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻻ ﺗﺩﺧﻝ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ ﻓﻲ ﺍﻟﺑﻼﻋﺔ ﺍﻟﺗﻲ ﻳﺗﻛﻭﻥ ﻓﻳﻬﺎ ﻏﺎﺯ ﻛﺑﺭﻳﺗﻳﺗﻲ‪) .‬ﻗﺩ ﻳﺣﺩﺙ ﺗﺂﻛﻝ ﻟﻠﻣﺑﺎﺩﻝ ﺍﻟﺣﺭﺍﺭﻱ(‬
‫ﻏﻁﺎء ﺍﻟﺻﺭﻑ‬
‫ﻗﻡ ﺑﻌﺯﻝ ﺍﻷﺟﺯﺍء ﺑﺷﻛﻝ ﺻﺣﻳﺢ ﺑﺣﻳﺙ ﻻ ﻳﺣﺩﺙ ﺗﻘﻁﻳﺭ ﻟﻠﻣﻳﺎﻩ ﻣﻥ ﺃﺟﺯﺍء ﺍﻟﺗﻭﺻﻳﻝ‪.‬‬
‫ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻓﺣﺹ ﺍﻟﺗﺻﺭﻳﻑ ﺍﻟﺻﺣﻳﺢ ﺑﻌﺩ ﺍﻟﺗﺭﻛﻳﺏ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﺟﺯء ﺍﻟﻣﺭﺋﻲ ﻣﻥ ﻣﻧﻔﺫ ﺍﻟﺗﺻﺭﻳﻑ ﺍﻟﺷﻔﺎﻑ ﻭﺍﻟﻣﺧﺭﺝ ﺍﻟﻧﻬﺎﺋﻲ ﻟﻣﺎﺳﻭﺭﺓ‬
‫ﺍﻟﺗﺻﺭﻳﻑ ﻋﻠﻰ ﺍﻟﺟﺳﻡ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻻ ﺗﺿﻊ ﻣﺎﺩﺓ ﻻﺻﻘﺔ ﻋﻠﻰ ﻣﻧﻔﺫ ﺍﻟﺗﺻﺭﻳﻑ ﺑﺎﻟﺟﺳﻡ‪.‬‬
‫)ﺍﺳﺗﺧﺩﻡ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ﺍﻟﻣﻠﺣﻕ ﻭﻗﻡ ﺑﺎﻟﺗﻭﺻﻳﻝ ﺑﻣﺎﺳﻭﺭﺓ ﺍﻟﺻﺭﻑ(‬
‫• ﺍﺳﺗﺧﺩﺍﻡ ﻣﺎﺳﻭﺭﺓ ﺑﻭﻟﻳﻔﻳﻧﻳﻝ ﻛﻠﻭﺭﻳﺩ ﺻﻠﺑﺔ ﻋﺎﻣﺔ )‪] (VP25‬ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ‪ 32‬ﻣﻡ[‪.‬‬
‫• ﻻ ﺗﻧﻔﺫ ﻋﻣﻠﻳﺔ ﺭﻓﻊ ﺃﻭ ﺍﺣﺗﺑﺎﺱ ﺃﻭ ﻧﻔﺫ ﻫﻭﺍﺋﻲ‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ )‪ 1/100‬ﺃﻭ ﺃﻛﺛﺭ(‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﺩﻋﺎﻣﺎﺕ ﻋﻧﺩ ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﻁﻭﻳﻠﺔ‪.‬‬
‫• ﺍﺳﺗﺧﺩﻡ ﻣﺎﺩﺓ ﻋﺎﺯﻟﺔ ﺣﺳﺏ ﺍﻟﺣﺎﺟﺔ‪ ،‬ﻟﻣﻧﻊ ﺗﻌﺭﺽ ﺍﻟﻣﻭﺍﺳﻳﺭ ﻟﻠﺗﺟﻣﺩ‪.‬‬
‫• ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﻁﺭﻳﻘﺔ ﺗﺗﻳﺢ ﺇﺯﺍﻟﺔ ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫‪ .A1.5‬ﻁﺭﺍﺯ ‪ARXK**GCLH‬‬
‫• ﺍﺳﺗﺧﺩﺍﻡ ﻣﺎﺳﻭﺭﺓ ﺑﻭﻟﻳﻔﻳﻧﻳﻝ ﻛﻠﻭﺭﻳﺩ ﺻﻠﺑﺔ ﻋﺎﻣﺔ )‪] (VP25‬ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ‪ 32‬ﻣﻡ[‪.‬‬
‫• ﻻ ﺗﻧﻔﺫ ﻋﻣﻠﻳﺔ ﺭﻓﻊ ﺃﻭ ﺍﺣﺗﺑﺎﺱ ﺃﻭ ﻧﻔﺫ ﻫﻭﺍﺋﻲ‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ )‪ 1/100‬ﺃﻭ ﺃﻛﺛﺭ(‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﺩﻋﺎﻣﺎﺕ ﻋﻧﺩ ﺗﺭﻛﻳﺏ ﻣﻭﺍﺳﻳﺭ ﻁﻭﻳﻠﺔ‪.‬‬
‫• ﺍﺳﺗﺧﺩﻡ ﻣﺎﺩﺓ ﻋﺎﺯﻟﺔ ﺣﺳﺏ ﺍﻟﺣﺎﺟﺔ‪ ،‬ﻟﻣﻧﻊ ﺗﻌﺭﺽ ﺍﻟﻣﻭﺍﺳﻳﺭ ﻟﻠﺗﺟﻣﺩ‪.‬‬
‫• ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺍﻟﻣﻭﺍﺳﻳﺭ ﺑﻁﺭﻳﻘﺔ ﺗﺗﻳﺢ ﺇﺯﺍﻟﺔ ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫ﺟﻳﺩ‬
‫ﺟﻳﺩ‬
‫ﻓﺟﻭﺓ ‪ 1.5‬ﺇﻟﻰ ‪ 2‬ﻣﺗﺭ‬
‫ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ ‪ 2.5‬ﺇﻟﻰ‬
‫‪ 5.0‬ﻣﻡ‬
‫ﻓﺟﻭﺓ ‪ 1.5‬ﺇﻟﻰ ‪ 2‬ﻣﺗﺭ‬
‫ﺍﻟﺩﻋﺎﻣﺔ‬
‫ﺍﻟﺩﻋﺎﻣﺔ‬
‫‪ 100‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‬
‫ﻣﺎﺳﻭﺭﺓ ﻣﻌﺩﺓ ﻣﺣﻠﻳًﺎ‬
‫‪] VP25‬ﺍﻟﻘﻁﺭ‬
‫ﺍﻟﺧﺎﺭﺟﻲ ‪ 32‬ﻣﻡ‬
‫ﺃﻭ ﺃﻛﺛﺭ[‬
‫‪ 700‬ﻣﺗﺭ ﺃﻭ ﺃﻗﻝ‬
‫‪] VP25‬ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ‬
‫‪ 32‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ[‬
‫ﺣﺩ ﺃﻗﺻﻰ ‪ 300‬ﻣﻡ‬
‫ﻣﺎﺳﻭﺭﺓ ﻣﻌﺩﺓ ﻣﺣﻠﻳًﺎ‬
‫ﻣﺣﻅﻭﺭ‬
‫ﺃﻓﻘﻲ ﺃﻭ ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ‬
‫ﺍﺣﺗﺑﺎﺱ‬
‫ﻣﺣﻅﻭﺭ‬
‫ﻧﺯﻑ ﺍﻟﻬﻭﺍء‬
‫ﺭﻓﻊ‬
‫ﺭﻓﻊ‬
‫ﻧﺯﻑ ﺍﻟﻬﻭﺍء‬
‫ﺍﺗﺑﻊ ﺍﻹﺟﺭﺍءﺍﺕ ﺍﻟﺗﺎﻟﻳﺔ ﻹﻧﺷﺎء ﺗﺭﻛﻳﺑﺎﺕ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ ﺍﻟﻣﺭﻛﺯﻳﺔ‪.‬‬
‫ﺍﺣﺗﺑﺎﺱ‬
‫‪ VP30‬ﺃﻭ ﺃﻛﺛﺭ‬
‫]ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ‪ 38‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ[‬
‫ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ‬
‫‪ 1/100‬ﺃﻭ ﺃﻛﺛﺭ‬
‫ﺍﺗﺑﻊ ﺍﻹﺟﺭﺍءﺍﺕ ﺍﻟﺗﺎﻟﻳﺔ ﻹﻧﺷﺎء ﺗﺭﻛﻳﺑﺎﺕ ﻣﻭﺍﺳﻳﺭ ﺍﻟﺻﺭﻑ ﺍﻟﻣﺭﻛﺯﻳﺔ‪.‬‬
‫‪ .2.5‬ﺗﺭﻛﻳﺏ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺻﺭﻑ‬
‫‪ VP30‬ﺃﻭ ﺃﻛﺛﺭ ]ﺍﻟﻘﻁﺭ ﺍﻟﺧﺎﺭﺟﻲ ‪ 38‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ[‬
‫ﺍﻧﺣﺩﺍﺭ ﻷﺳﻔﻝ ‪ 1/100‬ﺃﻭ ﺃﻛﺛﺭ‬
‫)‪ (1‬ﺗﺄﻛﺩ ﻣﻥ ﺍﺳﺗﺧﺩﺍﻡ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ﺍﻟﻣﺭﻓﻕ ‪ 1‬ﻭﺭﺑﺎﻁ ﺍﻟﺧﺭﻁﻭﻡ ‪2‬‬
‫‪ 2‬ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ )ﻣﻠﺣﻘﺎﺕ(‬
‫‪ 1‬ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ )ﻣﻠﺣﻘﺎﺕ(‬
‫‪ 700‬ﻣﺗﺭ ﺃﻭ ﺃﻗﻝ‬
‫ﺟﺎﻧﺏ ‪ PVC‬ﺍﻟﺻﻠﺏ‬
‫ﺧﺭﻁﻭﻡ‬
‫ﺻﺭﻑ‬
‫ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ‬
‫‪ 4‬ﻣﻡ ﺃﻭ ﺃﻗﻝ‬
‫‪ 20‬ﻣﻡ‬
‫‪Ar-7‬‬
‫‪2017/8/8 13:08:58‬‬
‫‪9381858019-02_IM_AR.indd Sec1:7‬‬
‫ﺷﻕ‬
‫‪ 1‬ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ‬
‫‪ 2‬ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ‬
‫ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ‬
‫ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ‬
‫ﻟﻑ ﺍﻟﻌﺎﺯﻝ ﺣﻭﻝ‬
‫ﺍﻟﻭﺻﻠﺔ‪.‬‬
‫ﻗﻣﺏ ﺗﺛﺑﻳﺕ ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ ‪ 2‬ﻋﻧﺩ ﺍﻟﻣﻭﺿﻊ ﺍﻟﺫﻱ ﻳﻛﻭﻥ ﻓﻳﻪ ﺃﻓﻘﻳًﺎ ﻣﻘﺎﺑﻝ‬
‫ﺍﻷﺭﺽ‪.‬‬
‫ﻳﺟﺏ ﺿﺑﻁ ﻣﻭﺿﻊ ﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ ‪ 2‬ﻋﻧﺩ ﺍﻟﺟﺎﻧﺏ ﺍﻷﻳﻣﻥ ﻣﻥ ﺧﺭﻁﻭﻡ‬
‫ﺍﻟﺻﺭﻑ ‪ 1‬ﻛﻣﺎ ﻓﻲ ﺍﻟﺷﻛﻝ‪.‬‬
‫)‪ (2‬ﺗﺄﻛﺩ ﻣﻥ ﺗﻭﺻﻳﻝ ﻣﺎﺳﻭﺭﺓ ﺍﻟﺻﺭﻑ ﺑﻼﺻﻕ )ﻛﻠﻭﺭﻳﺩ ﺍﻟﺑﻭﻟﻲ ﻓﻳﻧﻳﻝ( ﺑﺣﻳﺙ ﻻ ﻳﻛﻭﻥ ﻫﻧﺎﻙ ﺗﺳﺭﻳﺏ‪.‬‬
‫• ﺍﻹﻧﻬﺎء‬
‫ﺗﺣﺩﺩ ﻣﻥ ﻋﺩﻡ ﻭﺟﻭﺩ ﻓﺟﻭﺓ ﺑﻳﻥ ﺍﻟﻭﺣﺩﺓ ﻭﻋﺎﺯﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ‪.‬‬
‫• ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻣﺿﺧﺔ ﺍﻟﺻﺭﻑ‪.‬‬
‫ﻣﻧﻁﻘﺔ ﻭﺿﻊ‬
‫ﺍﻟﻼﺻﻕ‬
‫ﻣﺎﺳﻭﺭﺓ ﻭﺻﻠﺔ )ﻳﺗﻡ‬
‫ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﺍﻟﺧﻁﻭﺓ ‪3‬‬
‫ﻣﺎﺳﻭﺭﺓ ﺻﺭﻑ )‪(VP25‬‬
‫)ﻳﺗﻡ ﺷﺭﺍﺅﻫﺎ ﻣﺣﻠﻳًﺎ(‬
‫ﻻ ﺗﻐﻁﻲ ﻧﺎﻓﺫﺓ ﺍﻟﻠﻭﺣﺔ‪.‬‬
‫‪ 4‬ﻣﻡ ﺃﻭ ﺃﻗﻝ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻻ ﺗﻘﻡ ﺑﺗﻭﺻﻳﻝ ﻓﺗﺣﺔ ﺍﻟﺻﺭﻑ ﺑﻼﺻﻕ‪ .‬ﺍﺳﺗﺧﺩﺍﻡ ﺍﻟﻼﺻﻕ ﻗﺩ ﻳﺅﺩﻱ ﺇﻟﻰ ﺍﻟﺗﻠﻑ ﻭﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫• ﻋﻧﺩ ﻋﺩﻡ ﺍﺳﺗﺧﺩﺍﻡ ﻣﺿﺧﺔ ﺻﺭﻑ‪) .‬ﺗﺻﺭﻳﻑ ﻁﺑﻳﻌﻲ(‬
‫)‪ (3‬ﺑﻌﺩ ﺗﺭﻛﻳﺏ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪ ،1‬ﺗﺣﻘﻕ ﻣﻣﺎ ﺇﺫﺍ ﻛﺎﻥ ﺍﻟﺗﺻﺭﻳﻑ ﻳﺗﻡ ﺑﺷﻛﻝ ﺳﻠﺱ ﺃﻡ ﻻ‪.‬‬
‫ﻻ ﺗﻐﻁﻲ ﻏﻁﺎء‬
‫ﺻﻧﺩﻭﻕ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺗﻔﺎﺩﻱ ﺗﻁﺑﻳﻕ ﻗﻭﺓ ﻣﻔﺭﻁﺔ ﻋﻠﻰ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪ ،1‬ﺗﺟﻧﺏ ﺍﻻﻧﺣﻧﺎءﺍﺕ ﺃﻭ ﺍﻟﺛﻧﻲ‪) .‬ﺍﻻﻧﺣﻧﺎء ﺃﻭ ﺍﻟﺛﻧﻲ ﻗﺩ ﻳﺅﺩﻱ ﺇﻟﻰ ﺗﺳﺭﻳﺏ ﻟﻠﻣﻳﺎﻩ‪(.‬‬
‫)‪ (4‬ﺑﻌﺩ ﻓﺣﺹ ﺍﻟﺗﺻﺭﻳﻑ‪ ،‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻋﺎﺯﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪ B 3‬ﻟﻠﻌﺯﻝ‪ ،‬ﺑﺎﺗﺑﺎﻉ ﺍﻟﺗﻌﻠﻳﻣﺎﺕ ﻛﻣﺎ ﻓﻲ ﺍﻷﺷﻛﺎﻝ‪.‬‬
‫ﻟﺗﻔﺎﺩﻱ ﺣﺩﻭﺙ ﻓﺭﺍﻍ ﺑﻳﻥ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪ 1‬ﻭﺭﺍﺑﻁ ﺍﻟﺧﺭﻁﻭﻡ ‪ ،2‬ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ ﻋﻠﻰ ﻋﺎﺯﻝ ﺧﺭﻁﻭﻡ ﺍﻟﺻﺭﻑ ‪.B 3‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﻋﺩﻡ ﻭﺟﻭﺩ‬
‫ﻣﺳﺎﻓﺔ‪.‬‬
‫ﻣﻼﺣﻅﺔ‪ :‬ﻓﺣﺹ ﻭﺟﻭﺩ ﺍﻟﺗﺳﺭﻳﺏ )ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻣﺿﺧﺔ ﺻﺭﻑ(‬
‫ﺍﺳﻛﺏ ﺣﻭﺍﻟﻲ ‪ 1‬ﻟﺗﺭ ﻣﻥ ﺍﻟﻣﺎء ﻣﻥ ﺍﻟﻣﻭﺿﻊ ﺍﻟﻣﻭﺿﺢ ﻓﻲ ﺍﻟﺷﻛﻝ ﺍﻟﺗﻭﺿﻳﺣﻲ ﺃﻭ ﻣﻥ ﻓﺗﺣﺔ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﺇﻟﻰ‬
‫ﺩﺭﺝ ﺍﻟﻧﺩﻯ‪ .‬ﺍﻓﺣﺹ ﻭﺟﻭﺩ ﺃﻱ ﺷﻲء ﻏﻳﺭ ﻋﺎﺩﻱ ﻣﺛﻝ ﺍﻟﺿﻭﺿﺎء ﺍﻟﻐﺭﻳﺑﺔ ﻭﻣﺎ ﺇﺫﺍ ﻛﺎﻧﺕ ﻣﺿﺧﺔ ﺍﻟﺻﺭﻑ ﺗﻌﻣﻝ‬
‫ﺑﺷﻛﻝ ﻋﺎﺩﻱ ﺃﻡ ﻻ‪.‬‬
‫‪ 3‬ﻋﺎﺯﻝ ﺧﺭﻁﻭﻡ‬
‫ﺍﻟﺻﺭﻑ ‪) B‬ﻣﻠﺣﻘﺎﺕ(‬
‫• ﺍﻟﺧﻁﻭﺓ ‪ - 1‬ﺍﻟﺧﻁﻭﺓ ‪3‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻌﺯﻝ‬
‫ﻣﻘﺎﺑﻝ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﺍﻟﻭﺣﺩﺓ‬
‫ﺷﻕ‬
‫ﻣﻼﺣﻅﺔ‪ :‬ﻓﺣﺹ ﻭﺟﻭﺩ ﺍﻟﺗﺳﺭﻳﺏ )ﻋﻧﺩ ﻋﺩﻡ ﺍﺳﺗﺧﺩﺍﻡ ﻣﺿﺧﺔ ﺻﺭﻑ(‬
‫ﻗﻡ ﺑﺳﻛﺏ ﺣﻭﺍﻟﻲ ‪ 1‬ﻟﺗﺭ ﻣﻥ ﺍﻟﻣﻳﺎﻩ ﻣﻥ ﻣﺧﺭﺝ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﺇﻟﻰ ﺩﺭﺝ ﺍﻟﻧﺩﻯ‪ .‬ﺍﻓﺣﺹ ﻭﺟﻭﺩ ﺃﻱ ﺷﻲء ﻏﻳﺭ‬
‫ﻋﺎﺩﻱ ﻣﺛﻝ ﺍﻟﺿﻭﺿﺎء ﺍﻟﻐﺭﻳﺑﺔ‪.‬‬
‫ﺍﻟﺧﻁﻭﺓ ‪1‬‬
‫ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ‬
‫ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺗﺻﺭﻳﻑ ﻣﻳﺎﻩ ﺍﻟﺻﺭﻑ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪.‬‬
‫ﺷﻕ‬
‫ﺍﺿﻐﻁ ﺑﺈﺣﻛﺎﻡ‬
‫ﺍﻟﺧﻁﻭﺓ ‪2‬‬
‫‪Ar-8‬‬
‫‪2017/8/8 13:08:58‬‬
‫‪9381858019-02_IM_AR.indd Sec1:8‬‬
‫‪ .1.6‬ﺍﻟﻣﺗﻁﻠﺏ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ‬
‫‪ .6‬ﺍﻷﺳﻼﻙ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﺗﺣﺫﻳﺭ‬
‫ﻳﺟﺏ ﺗﻧﻔﻳﺫ ﺍﻷﻋﻣﺎﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﻓ ًﻘﺎ ﻟﻬﺫﺍ ﺍﻟﺩﻟﻳﻝ ﻭﺑﻭﺍﺳﻁﺔ ﺷﺧﺹ ﻣﻌﺗﻣﺩ ﺑﻣﻭﺟﺏ ﺍﻟﻠﻭﺍﺋﺢ ﺍﻟﻭﻁﻧﻳﺔ ﺃﻭ ﺍﻹﻗﻠﻳﻣﻳﺔ‪ .‬ﺗﺄﻛﺩ ﻣﻥ ﺍﺳﺗﺧﺩﺍﻡ‬
‫ﺩﺍﺋﺭﺓ ﻛﻬﺭﺑﺎﺋﻳﺔ ﻣﺧﺻﺻﺔ ﻟﻠﻭﺣﺩﺓ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﺗﺅﺩﻱ ﺩﺍﺋﺭﺓ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻏﻳﺭ ﺍﻟﻛﺎﻓﻳﺔ ﺃﻭ ﺍﻷﻋﻣﺎﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺍﻟﻣﻧﻔﺫﺓ ﺑﺷﻛﻝ ﻏﻳﺭ ﺻﺣﻳﺢ ﺇﻟﻰ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺍﻟﺗﻌﺭﺽ‬
‫ﻟﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻣﻌﺩﻝ ﺍﻟﺟﻬﺩ‬
‫‪ 230‬ﻓﻭﻟﺕ‬
‫ﻧﻁﺎﻕ ﺍﻟﺗﺷﻐﻳﻝ‬
‫‪ 198‬ﺇﻟﻰ ‪ 264‬ﻓﻭﻟﺕ )‪ 50‬ﻫﺭﺗﺯ(‬
‫‪ 198‬ﺇﻟﻰ ‪ 253‬ﻓﻭﻟﺕ )‪ 60‬ﻫﺭﺗﺯ(‬
‫• ﺣﺩﺩ ﻧﻭﻉ ﻭﺣﺟﻡ ﻛﺑﻝ ﺍﻟﻁﺎﻗﺔ ﻭﻓ ًﻘﺎ ﻟﻠﻘﻭﺍﻋﺩ ﺍﻟﻣﺗﻌﻠﻘﺔ ﺍﻟﻣﺣﻠﻳﺔ ﻭﺍﻟﻭﻁﻧﻳﺔ‪.‬‬
‫• ﻳﺟﺏ ﺃﻥ ﺗﺗﻔﻕ ﻣﻭﺍﺻﻔﺎﺕ ﺃﺳﻼﻙ ﻛﺑﻝ ﺍﻟﻁﺎﻗﺔ ﻭﺍﻟﺗﻔﺭﻳﻌﺎﺕ ﻣﻊ ﺍﻟﻘﺎﻧﻭﻥ ﺍﻟﻣﺣﻠﻲ‪.‬‬
‫ﻗﺑﻝ ﺑﺩء ﺍﻟﻌﻣﻝ‪ ،‬ﺗﺣﻘﻕ ﻣﻥ ﺃﻧﻪ ﻻ ﻳﺟﺭﻱ ﺗﺯﻭﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺇﻟﻰ ﺟﻣﻳﻊ ﺍﻟﻭﺣﺩﺍﺕ‪.‬‬
‫• ﺃﻗﺻﻰ ﻁﻭﻝ ﻟﻠﺳﻠﻙ‪ :‬ﺍﺿﺑﻁ ﺍﻟﻁﻭﻝ ﺑﺣﻳﺙ ﻳﻛﻭﻥ ﺍﻧﺧﻔﺎﺽ ﺍﻟﺟﻬﺩ ﺃﻗﻝ ﻣﻥ ‪ .2%‬ﻗﻡ ﺑﺯﻳﺎﺩﺓ ﻗﻁﺭ ﺍﻟﺳﻠﻙ ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﺍﻟﻁﻭﻝ ﺃﻛﺑﺭ‪.‬‬
‫ﺑﺎﻟﻧﺳﺑﺔ ﻟﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‪ ،‬ﺍﺳﺗﺧﺩﻡ ﻧﻭﻉ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﻭﺻﻭﻑ‪ ،‬ﻭﻗﻡ ﺑﺗﻭﺻﻳﻠﻪ ﺑﺈﺣﻛﺎﻡ‪ ،‬ﻣﻊ ﺍﻟﺗﺄﻛﺩ ﻣﻥ ﻋﺩﻡ ﻭﺟﻭﺩ ﻗﻭﻯ ﺧﺎﺭﺟﻳﺔ‬
‫ﻟﻠﻛﺑﻼﺕ ﺗﺅﺛﺭ ﻋﻠﻰ ﺗﻭﺻﻳﻼﺕ ﺍﻟﻁﺭﻑ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﺗﺅﺩﻱ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﻭﺻﻠﺔ ﺑﺷﻛﻝ ﻏﻳﺭ ﺻﺣﻳﺢ ﺃﻭ ﻣﺣﻛﻡ ﺇﻟﻰ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺯﻳﺎﺩﺓ ﺳﺧﻭﻧﺔ ﺍﻟﻁﺭﻑ ﺃﻭ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ‬
‫ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻳﺟﺏ ﺗﺭﻛﻳﺏ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻓﻲ ﻛﻝ ﻧﻅﺎﻡ ﺗﺑﺭﻳﺩ‪ .‬ﻻ ﺗﺳﺗﺧﺩﻡ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻓﻲ ﻧﻅﺎﻡ ﺗﺑﺭﻳﺩ ﻣﺧﺗﻠﻑ‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻏﻁﺎء ﺍﻟﺻﻧﺩﻭﻕ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ﺑﺈﺣﻛﺎﻡ ﻋﻠﻰ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﻳﺳﺑﺏ ﺍﻟﺻﻧﺩﻭﻕ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ ﺍﻟﻣﺭﻛﺏ ﺑﺷﻛﻝ ﻏﻳﺭ ﺻﺣﻳﺢ ﺣﻭﺍﺩﺙ ﺧﻁﻳﺭﺓ ﻣﺛﻝ ﺍﻟﺻﺩﻣﺔ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﺍﻟﺣﺭﻳﻕ ﻋﻥ ﻁﺭﻳﻕ‬
‫ﺍﻟﺗﻌﺭﺽ ﻟﻠﻐﺑﺎﺭ ﺃﻭ ﺍﻟﻣﻳﺎﻩ‪.‬‬
‫ﺭﺍﺟﻊ ﺍﻟﺟﺩﻭﻝ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻣﻭﺍﺻﻔﺎﺕ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ ﻟﻛﻝ ﺣﺎﻟﺔ ﺗﺭﻛﻳﺏ‪ .‬ﻗﻡ ﺑﺗﻧﻔﻳﺫ ﺍﻷﺳﻼﻙ ﺍﻟﻌﺎﺑﺭﺓ ﻟﻠﻁﺎﻗﺔ ﺿﻣﻥ ﻧﻁﺎﻕ ﻧﻔﺱ ﻧﻅﺎﻡ‬
‫ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ‪ .‬ﻋﻧﺩ ﺗﻧﻔﻳﺫ ﺃﺳﻼﻙ ﻋﺎﺑﺭﺓ‪ ،‬ﻗﻡ ﺑﻌﻣﻝ ﺗﻭﺻﻳﻼﺕ ﻟﻠﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﺣﻳﺙ ﺗﺣﻘﻕ ﺍﻟﺷﺭﻭﻁ ‪ A‬ﻭ‪ B‬ﺃﺩﻧﺎﻩ‪.‬‬
‫‪ .A‬ﻣﺗﻁﻠﺑﺎﺕ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫ﺍﻟﻁﺭﺍﺯ‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﺃﻛﻣﺎﻡ ﻓﻲ ﺃﻱ ﻓﺗﺣﺎﺕ ﻳﺗﻡ ﺗﻧﻔﻳﺫﻫﺎ ﻓﻲ ﺍﻟﺟﺩﺭﺍﻥ ﻷﺟﻝ ﺗﻣﺩﻳﺩ ﺍﻷﺳﻼﻙ‪ .‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﺗﺣﺩﺙ ﺩﺍﺋﺭﺓ ﻗﺻﺭ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻛﺑﻼﺕ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﻣﺿﻣﻧﺔ ﻭﻛﺑﻼﺕ ﺍﻟﻁﺎﻗﺔ ﺃﻭ ﺍﻟﻛﺑﻼﺕ ﺍﻟﺗﻲ ﻳﺣﺩﺩﻫﺎ ﺍﻟﻣﺻ ﱢﻧﻊ‪ .‬ﻳﻣﻛﻥ ﺃﻥ ﺗﺅﺩﻱ ﺍﻟﺗﻭﺻﻳﻼﺕ ﻏﻳﺭ ﺍﻟﺻﺣﻳﺣﺔ‬
‫ﺃﻭ ﺍﻟﻌﺯﻝ ﻏﻳﺭ ﺍﻟﻛﺎﻓﻲ ﺃﻭ ﺗﺟﺎﻭﺯ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﻣﻭﺡ ﺑﻪ ﺇﻟﻰ ﺣﺩﻭﺙ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻻ ﺗﻌﺩﻝ ﻛﺑﻼﺕ ﺍﻟﻁﺎﻗﺔ ﺃﻭ ﺗﺳﺗﺧﺩﻡ ﻛﺑﻼﺕ ﺗﻣﺩﻳﺩ ﺃﻭ ﺗﺳﺗﺧﺩﻡ ﺃﻱ ﺗﻔﺭﻳﻌﺎﺕ ﻓﻲ ﺍﻷﺳﻼﻙ‪ .‬ﻳﻣﻛﻥ ﺃﻥ ﺗﺅﺩﻱ ﺍﻟﺗﻭﺻﻳﻼﺕ ﻏﻳﺭ ﺍﻟﺻﺣﻳﺣﺔ‬
‫ﺃﻭ ﺍﻟﻌﺯﻝ ﻏﻳﺭ ﺍﻟﻛﺎﻓﻲ ﺃﻭ ﺗﺟﺎﻭﺯ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﻣﻭﺡ ﺑﻪ ﺇﻟﻰ ﺣﺩﻭﺙ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻗﻡ ﺑﻣﻁﺎﺑﻘﺔ ﺃﺭﻗﺎﻡ ﺍﻟﻣﺟﻣﻭﻋﺔ ﺍﻟﻁﺭﻓﻳﺔ ﻭﺃﻟﻭﺍﻥ ﻛﺑﻼﺕ ﺍﻟﺗﻭﺻﻳﻝ ﻣﻊ ﺗﻠﻙ ﺍﻟﺧﺎﺻﺔ ﺑﺎﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ‪ .‬ﻗﺩ ﺗﺅﺩﻱ ﺍﻟﺗﻭﺻﻳﻼﺕ ﺍﻟﺧﺎﻁﺋﺔ‬
‫ﻟﻸﺳﻼﻙ ﺇﻟﻰ ﺍﺣﺗﺭﺍﻕ ﺍﻟﻣﻛﻭﻧﺎﺕ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻼﺕ ﺍﻟﺗﻭﺻﻳﻝ ﻓﻲ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻁﺭﻓﻳﺔ ﺑﺈﺣﻛﺎﻡ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻙ‪ ،‬ﻗﻡ ﺑﺗﺛﺑﻳﺕ ﺍﻟﻛﺑﻼﺕ ﻣﻥ ﺧﻼﻝ ﻣﺎﺳﻛﺎﺕ ﺍﻷﺳﻼﻙ‪.‬‬
‫ﺍﻟﺗﻭﺻﻳﻼﺕ ﻏﻳﺭ ﺍﻟﺻﺣﻳﺣﺔ‪ ،‬ﺳﻭﺍء ﻓﻲ ﺍﻷﺳﻼﻙ ﺃﻭ ﻓﻲ ﺃﻁﺭﺍﻑ ﺍﻷﺳﻼﻙ‪ ،‬ﺗﺅﺩﻱ ﺇﻟﻰ ﺍﻟﺗﻌﻁﻝ ﺃﻭ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﺍﺣﺭﺹ ﺩﺍﺋﻣًﺎ ﻋﻠﻰ ﺗﺛﺑﻳﺕ ﺍﻟﻐﻁﺎء ﺍﻟﺧﺎﺭﺟﻲ ﻟﻛﺑﻝ ﺍﻟﺗﻭﺻﻳﻝ ﻣﻊ ﻣﺷﺑﻙ ﺍﻟﻛﺑﻝ‪) .‬ﻓﻲ ﺣﺎﻟﺔ ﺧﺩﺵ ﺍﻟﻌﺎﺯﻝ‪ ،‬ﻓﻘﺩ ﻳﺣﺩﺙ ﺗﻔﺭﻳﻎ ﻛﻬﺭﺑﺎﺋﻲ(‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺳﺭﻳﺏ ﺍﻷﺭﺿﻲ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻙ‪ ،‬ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺳﺭﻳﺏ ﺍﻷﺭﺿﻲ ﺑﺣﻳﺙ ﻳﺗﻡ ﻓﺻﻝ ﺇﻣﺩﺍﺩ‬
‫ﻁﺎﻗﺔ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺗﺭﺩﺩ ﺍﻟﺭﺋﻳﺳﻲ ﺑﺎﻟﻛﺎﻣﻝ ﻓﻲ ﻧﻔﺱ ﺍﻟﻭﻗﺕ‪ .‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﺗﺣﺩﺙ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ ﺃﻭ ﺣﺭﻳﻕ‪.‬‬
‫ﻗﻡ ﺩﺍﺋﻣًﺎ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻝ ﺍﻷﺭﺿﻲ )ﺍﻟﺗﺄﺭﻳﺽ(‪.‬‬
‫ﻳﻣﻛﻥ ﺃﻥ ﺗﺗﺳﺑﺏ ﺃﻋﻣﺎﻝ ﺍﻟﺗﺄﺭﻳﺽ )ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻷﺭﺽ( ﻏﻳﺭ ﺍﻟﺻﺣﻳﺣﺔ ﺇﻟﻰ ﺻﺩﻣﺎﺕ ﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬
‫ﻗﻡ ﺑﺗﺭﻛﻳﺏ ﻛﺑﻼﺕ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺑﺣﻳﺙ ﻻ ﺗﺗﻼﻣﺱ ﻣﺑﺎﺷﺭﺓ ﻣﻊ ﻳﺩﻙ‪.‬‬
‫ﻗﻡ ﺑﺗﻧﻔﻳﺫ ﺃﻋﻣﺎﻝ ﺗﻭﺻﻳﻼﺕ ﺍﻷﺳﻼﻙ ﻭﻓ ًﻘﺎ ﻟﻠﻣﻌﺎﻳﻳﺭ ﺑﺣﻳﺙ ﻳﻣﻛﻥ ﺗﺷﻐﻳﻝ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﺑﺄﻣﺎﻥ ﻭﺑﺷﻛﻝ ﺇﻳﺟﺎﺑﻲ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻝ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺈﺣﻛﺎﻡ ﻓﻲ ﺍﻟﻠﻭﺣﺔ ﺍﻟﻁﺭﻓﻳﺔ‪ .‬ﻳﻣﻛﻥ ﺃﻥ ﻳﺅﺩﻱ ﺍﻟﺗﺭﻛﻳﺏ ﻏﻳﺭ ﺍﻟﺟﻳﺩ ﺇﻟﻰ ﻧﺷﻭﺏ ﺣﺭﻳﻕ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﻠﻑ ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‪ ،‬ﻓﻳﺟﺏ ﺍﺳﺗﺑﺩﺍﻟﻪ ﺑﻭﺍﺳﻁﺔ ﺍﻟﻣﺻ ﱢﻧﻊ ﺃﻭ ﻭﻛﻳﻠﺔ ﺍﻟﺻﻳﺎﻧﺔ ﺍﻟﺧﺎﺹ ﺑﻪ ﺃﻭ ﺃﺷﺧﺎﺹ ﻣﺅﻫﻠﻳﻥ ﻋﻠﻰ ﻧﺣﻭ‬
‫ﻣﻣﺎﺛﻝ ﻣﻥ ﺃﺟﻝ ﺗﻔﺎﺩﻱ ﺍﻟﺧﻁﺭ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻭﺣﺩﺓ ﺑﺎﻷﺭﺽ )ﺍﻟﺗﺄﺭﻳﺽ(‪.‬‬
‫ﻻ ﺗﻘﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻛﺑﻝ ﺍﻷﺭﺿﻲ )ﺍﻟﺗﺄﺭﻳﺽ( ﺑﻣﺎﺳﻭﺭﺓ ﻏﺎﺯ ﺃﻭ ﻣﺎﺳﻭﺭﺓ ﻣﻳﺎﻩ ﺃﻭ ﻗﺿﻳﺏ ﺍﻟﺑﺭﻕ ﺃﻭ ﺳﻠﻙ ﺃﺭﺿﻲ )ﺗﺄﺭﻳﺽ( ﻟﻠﻬﺎﺗﻑ‪.‬‬
‫ﻗﺩ ﻳﺅﺩﻱ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻷﺭﺽ )ﺍﻟﺗﺄﺭﻳﺽ( ﻏﻳﺭ ﺍﻟﺻﺣﻳﺢ ﺇﻟﻰ ﺻﺩﻣﺔ ﻛﻬﺭﺑﺎﺋﻳﺔ‪.‬‬
‫ﻻ ﺗﻘﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻼﺕ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﺑﺄﻁﺭﺍﻑ ﺍﻟﻧﻘﻝ ﺃﻭ ﺃﻁﺭﺍﻑ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪ ،‬ﻧﻅﺭً ﺍ ﻷﻥ ﺫﻟﻙ ﻳﺗﻠﻑ ﺍﻟﻣﻧﺗﺞ‪.‬‬
‫ﺗﺟﻧﺏ ﻣﻁﻠ ًﻘﺎ ﺭﺑﻁ ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻭﻛﺑﻝ ﺍﻟﻧﻘﻝ ﻭﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻌًﺎ‪.‬‬
‫ﺍﻓﺻﻝ ﻫﺫﻩ ﺍﻟﻛﺑﻼﺕ ﺑﻣﺳﺎﻓﺔ ‪ 50‬ﻣﻡ ﺃﻭ ﺃﻛﺛﺭ‪.‬‬
‫ﻳﺅﺩﻱ ﺭﺑﻁ ﻫﺫﻩ ﺍﻟﻛﺑﻼﺕ ﻣﻌًﺎ ﻳﺅﺩﻱ ﺇﻟﻰ ﺳﻭء ﺍﻟﺗﺷﻐﻳﻝ ﺃﻭ ﺍﻟﺗﻌﻁﻝ‪.‬‬
‫‪ARXK07GALH‬‬
‫‪ 0.33‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK09GALH‬‬
‫‪ARXK12GALH‬‬
‫‪ 0.43‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK14GALH‬‬
‫‪ 0.80‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK18GALH‬‬
‫‪ 0.93‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK24GALH‬‬
‫‪ 1.03‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK07GCLH‬‬
‫‪ 0.34‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK09GCLH‬‬
‫‪ 0.34‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK12GCLH‬‬
‫‪ 0.44‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK14GCLH‬‬
‫‪ 0.81‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪ARXK18GCLH‬‬
‫‪ 0.94‬ﺃﻣﺑﻳﺭ‬
‫‪ARXK24GCLH‬‬
‫‪ 1.04‬ﺃﻣﺑﻳﺭ‪.‬‬
‫ﻋﻧﺩ ﺗﻧﻔﻳﺫ ﺃﺳﻼﻙ ﻋﺎﺑﺭﺓ ﻟﻠﻁﺎﻗﺔ‪ ،‬ﺍﺣﺭﺹ ﻋﻠﻰ ﺃﻥ ﺗﻛﻭﻥ ﺍﻟﻘﻳﻣﺔ ﺍﻹﺟﻣﺎﻟﻳﺔ ﻟـ ‪ MCA‬ﻟﻭﺣﺩﺍﺕ ‪ RB‬ﺍﻟﻣﺗﺻﻠﺔ ﻭﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻻ‬
‫ﺗﺗﺟﺎﻭﺯ ‪ 15‬ﺃﻣﺑﻳﺭ‪ .‬ﺑﺎﻟﻧﺳﺑﺔ ﻟﻘﻳﻣﺔ ‪ MCA‬ﻟﻭﺣﺩﺓ ‪ ،RB‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ ‪.RB‬‬
‫ﺇﺫﺍ ﻛﺎﻧﺕ ﻗﺩﺭﺓ ﻭﺣﺩﺍﺕ ‪ RB‬ﺍﻟﻣﺗﺻﻠﺔ ﻭﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺗﺗﺟﺎﻭﺯ ﺍﻟﺣﺩ ﺍﻟﺳﺎﺑﻕ‪ ،‬ﻋﻠﻳﻙ ﺇﻣﺎ ﺇﺿﺎﻓﺔ ﻗﻭﺍﻁﻊ ﺩﺍﺋﺭﺓ ﺃﻭ ﺍﺳﺗﺧﺩﺍﻡ ﻗﺎﻁﻊ‬
‫ﺩﺍﺋﺭﺓ ﺑﻘﺩﺭﺓ ﺃﻛﺑﺭ‪.‬‬
‫‪ .B‬ﻣﺗﻁﻠﺑﺎﺕ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺳﺭﻳﺏ ﺍﻷﺭﺿﻲ‬
‫* ﺃﻗﺻﻰ ﻋﺩﺩ "ﻟﻠﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ" ﺃﻭ "ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ‪ +‬ﻭﺣﺩﺍﺕ‬
‫‪ "RB‬ﺍﻟﻘﺎﺑﻠﺔ ﻟﻠﺗﻭﺻﻳﻝ‬
‫ﻗﺩﺭﺓ ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫‪ 30‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ‪ 0.1 ،‬ﺛﺎﻧﻳﺔ ﺃﻭ ﺃﻗﻝ‬
‫‪ 44‬ﺃﻭ ﺃﻗﻝ‬
‫‪ 100‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ‪ 0.1 ،‬ﺛﺎﻧﻳﺔ ﺃﻭ ﺃﻗﻝ‬
‫‪ 45‬ﺇﻟﻰ ‪** 148‬‬
‫* ﻧﻭﻉ ﻣﺿﺧﺔ ﺍﻟﺗﺩﻓﺋﺔ‪ :‬ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ‪ ،‬ﻧﻭﻉ ﺍﺳﺗﺭﺩﺍﺩ ﺍﻟﺗﺩﻓﺋﺔ‪ :‬ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻭﺣﺩﺍﺕ ‪.RB‬‬
‫** ﺇﺫﺍ ﻟﻡ ﻳﺗﻡ ﺗﻭﻓﻳﺭ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻗﺩﺭﺓ ‪ 100‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ‪ ،‬ﻓﻘﻡ ﺑﺗﻘﺳﻳﻡ ﻛﻣﻳﺔ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺇﻟﻰ ﻣﺟﻣﻭﻋﺎﺕ ﺻﻐﻳﺭﺓ ﻣﻥ ‪ 44‬ﺃﻭ ﺃﻗﻝ‬
‫ﻭﻗﻡ ﺑﺗﻭﻓﻳﺭ ﻗﺎﻁﻊ ﺩﺍﺋﺭﺓ ﻗﺩﺭﺓ ‪ 30‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﻟﻛﻝ ﻣﺟﻣﻭﻋﺔ‪.‬‬
‫‪.1.1.6‬‬
‫ﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﻛﺑﻼﺕ‬
‫ﺍﺗﺑﻊ ﺍﻟﻣﻭﺍﺻﻔﺎﺕ ﺍﻟﺗﺎﻟﻳﺔ ﻟﻣﺻﺩﺭ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻭﻛﺑﻝ ﺍﻟﻧﻘﻝ ﻭﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﺣﺟﻡ ﺍﻟﻛﺑﻝ ﺍﻟﻣﻭﺻﻰ‬
‫ﺑﻪ )ﻣﻡ‪(2‬‬
‫ﻧﻭﻉ ﺍﻟﻛﺑﻝ‬
‫‪2.5‬‬
‫ﻧﻭﻉ ‪IEC57 60245‬‬
‫ﺃﻭ ﻣﺎ ﻳﻌﺎﺩﻟﻪ‪.‬‬
‫‪ 2‬ﻛﺑﻝ ‪ +‬ﺃﺭﺿﻲ )ﺗﺄﺭﻳﺽ(‬
‫ﻛﺑﻝ ﻣﺗﻭﺍﻓﻕ ﻣﻊ‬
‫‪LONWORKS‬‬
‫ﺳﻠﻙ ﻣﻘﺎﺱ ‪ 22‬ﺣﺳﺏ ﺍﻟﻣﻘﻳﺎﺱ ﺍﻷﻣﺭﻳﻛﻲ‬
‫)‪ (AWG‬ﺍﻟﻣﺳﺗﻭﻯ ‪ (NEMA) 4‬ﺛﻧﺎﺋﻲ‬
‫ﺍﻟﻣﺭﻛﺯ ﻏﻳﺭ ﻗﻁﺑﻲ‪ ،‬ﻭﺑﻣﺭﻛﺯ ﻣﺻﻣﺕ‬
‫ﺛﻧﺎﺋﻲ ﻣﻠﻔﻭﻑ ﺑﻘﻁﺭ ‪ 0.65‬ﻣﻡ‬
‫• ﺍﻓﺻﻝ ﺍﻟﻁﺎﻗﺔ )ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ(‪.‬‬
‫• ﺍﻟﻣﺱ ﺍﻟﺟﺯء ﺍﻟﻣﻌﺩﻧﻲ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻣﺩﺓ ﺗﺯﻳﺩ ﻋﻥ ‪ 10‬ﺛﻭﺍﻧﻲ ﻟﺗﻔﺭﻳﻎ ﺍﻟﻛﻬﺭﺑﺎء ﺍﻻﺳﺗﺎﺗﻳﻛﻳﺔ ﺍﻟﻣﺷﺣﻭﻧﺔ ﻓﻲ ﺍﻟﺟﺳﻡ‪.‬‬
‫‪ 20‬ﺃﻣﺑﻳﺭ‬
‫‪ :MCA‬ﺃﺩﻧﻰ ﻗﺩﺭﺓ ﺃﻣﺑﻳﺭﻳﺔ ﻟﻠﺩﺍﺋﺭﺓ‬
‫‪ :MFA‬ﺍﻟﻘﺩﺭﺓ ﺍﻷﻣﺑﻳﺭﻳﺔ ﻟﻠﻣﺻﻬﺭ ﺍﻟﺭﺋﻳﺳﻲ‬
‫ﻋﻧﺩ ﺍﻟﺗﻌﺎﻣﻝ ﻣﻊ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‪ ،‬ﻓﺈﻥ ﺍﻟﻛﻬﺭﺑﺎء ﺍﻟﺳﺎﻛﻧﺔ ﺍﻟﻣﺷﺣﻭﻧﺔ ﻓﻲ ﺍﻟﺟﺳﻡ ﻗﺩ ﺗﺳﺑﺏ ﺗﻌﻁﻝ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‪ .‬ﺍﺗﺑﻊ ﺍﻻﺣﺗﻳﺎﻁﺎﺕ‬
‫ﺍﻟﺗﺎﻟﻳﺔ‪:‬‬
‫• ﻗﻡ ﺑﺈﻧﺷﺎء ﻭﺻﻠﺔ ﺃﺭﺿﻳﺔ )ﺗﺄﺭﻳﺽ( ﻟﻠﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺍﻟﺧﺎﺭﺟﻳﺔ ﻭﺍﻷﺟﻬﺯﺓ ﺍﻟﻁﺭﻓﻳﺔ‪.‬‬
‫‪MCA‬‬
‫‪ 0.33‬ﺃﻣﺑﻳﺭ‪.‬‬
‫‪MFA‬‬
‫ﻛﺑﻝ ﺍﻟﻧﻘﻝ‬
‫‪0.33‬‬
‫• ﻻ ﺗﻠﻣﺱ ﺃﻁﺭﺍﻑ ﺍﻷﺟﺯﺍء ﺃﻭ ﺍﻟﻘﻭﺍﻟﺏ ﻓﻲ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‪.‬‬
‫ﻣﻼﺣﻅﺔ‬
‫ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ )ﻧﻭﻉ ﺛﻧﺎﺋﻲ‬
‫ﺳﻠﻙ(‬
‫‪ 0.33‬ﺇﻟﻰ ‪1.25‬‬
‫ﻛﺑﻝ ‪ PVC‬ﻣﻐﻠﻑ*‬
‫ﻛﺑﻝ ﺛﻧﺎﺋﻲ ﻣﻠﻔﻭﻑ‪ ،‬ﻣﺯﺩﻭﺝ ﺍﻟﻣﺭﻛﺯ‬
‫ﻏﻳﺭ ﻗﻁﺑﻲ‬
‫ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ )ﻧﻭﻉ ﺛﻼﺛﻲ‬
‫ﺍﻷﺳﻼﻙ(‬
‫‪0.33‬‬
‫ﻛﺑﻝ ‪ PVC‬ﻣﻐﻠﻑ*‬
‫ﻣﺭﻛﺯ ﺛﻼﺛﻲ ﺍﻷﻗﻁﺎﺏ‬
‫*‪ :‬ﺍﺳﺗﺧﺩﻡ ﻛﺑﻝ ﻣﻐﻠﻑ ﻭﻓ ًﻘﺎ ﻟﻠﻘﻭﺍﻋﺩ ﺍﻟﻣﺣﻠﻳﺔ ﻟﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫‪Ar-9‬‬
‫‪2017/8/8 13:08:57‬‬
‫‪9381858019-02_IM_AR.indd Sec1:9‬‬
‫ﺗﺣﺫﻳﺭ‬
‫‪ .2.6‬ﻁﺭﻳﻘﺔ ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‬
‫ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻛﺑﻼﺕ ﺑﻣﺭﻛﺯ ﻣﺻﻣﺕ‪ ،‬ﻻ ﺗﺳﺗﺧﺩﻡ ﻁﺭﻑ ﺣﻠﻘﻲ‪ .‬ﺇﺫﺍ ﻛﻧﺕ ﺗﺳﺗﺧﺩﻡ ﻛﺑﻼﺕ ﺑﻣﺭﻛﺯ ﻣﺻﻣﺕ ﺫﺍﺕ ﻁﺭﻑ ﺣﻠﻘﻲ‪ ،‬ﻓﺈﻥ‬
‫ﺭﺑﺎﻁ ﺍﻟﺿﻐﻁ ﻟﻠﻁﺭﻑ ﺍﻟﺣﻠﻘﻲ ﻗﺩ ﻳﺗﻠﻑ ﻭﻳﺳﺑﺏ ﺳﺧﻭﻧﺔ ﻏﻳﺭ ﻋﺎﺩﻳﺔ ﻟﻠﻛﺑﻼﺕ‪.‬‬
‫ﻣﺛﺎﻝ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﺃﻭ ﻭﺣﺩﺓ ‪1* RB‬‬
‫‪ .B‬ﻟﻸﺳﻼﻙ ﺍﻟﻣﺟﺩﻭﻟﺔ‬
‫)‪ (1‬ﺍﺳﺗﺧﺩﻡ ﺃﻁﺭﺍﻑ ﺣﻠﻘﻳﺔ ﺑﺄﻛﻣﺎﻡ ﻋﺎﺯﻟﺔ ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ﺍﻟﺷﻛﻝ ﺍﻟﺗﺎﻟﻲ ﻟﻠﺗﻭﺻﻳﻝ ﺑﺎﻟﻣﺟﻣﻭﻋﺔ ﺍﻟﻁﺭﻓﻳﺔ‪.‬‬
‫ﺍﻟﻧﻘﻝ‬
‫)‪ (2‬ﻗﻡ ﺑﺗﻌﺷﻳﻕ ﺍﻷﻁﺭﺍﻑ ﺍﻟﺣﻠﻘﻳﺔ ﺑﺈﺣﻛﺎﻡ ﺑﺎﻟﻛﺑﻼﺕ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺃﺩﺍﺓ ﻣﻧﺎﺳﺑﺔ ﺑﺣﻳﺙ ﻻ ﺗﺻﺑﺢ ﺍﻟﻛﺑﻼﺕ ﻣﻔﻛﻭﻛﺔ‪.‬‬
‫)‪ (3‬ﺍﺳﺗﺧﺩﻡ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﺣﺩﺩﺓ‪ ،‬ﻭﻗﻡ ﺑﺗﻭﺻﻳﻠﻬﺎ ﺑﺈﺣﻛﺎﻡ‪ ،‬ﺛﻡ ﺛﺑﺗﻬﺎ ﺑﺣﻳﺙ ﻻ ﻳﻛﻭﻥ ﻫﻧﺎﻙ ﺃﻱ ﺷﺩ ﻋﻠﻰ ﺍﻷﻁﺭﺍﻑ‪.‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫*‪2‬‬
‫*‪3‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ‬
‫ﺑﻌﺩ‬
‫*‪3‬‬
‫*‪2‬‬
‫*‪3‬‬
‫)‪ (4‬ﺍﺳﺗﺧﺩﻡ ﻣﻔﻙ ﻣﻧﺎﺳﺏ ﻟﺭﺑﻁ ﺑﺭﺍﻏﻲ ﺍﻷﻁﺭﺍﻑ‪.‬‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﻣﻔﻙ ﺻﻐﻳﺭ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﻳﺗﻠﻑ ﺭﺃﺱ ﺍﻟﺑﺭﻏﻲ ﻭﻳﻣﻧﻊ ﺭﺑﻁ ﺍﻟﺑﺭﺍﻏﻲ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪.‬‬
‫ﺍﻟﻧﻘﻝ‬
‫*‪ 2‬ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫)‪ (5‬ﻻ ﺗﺭﺑﻁ ﺍﻟﺑﺭﺍﻏﻲ ﺍﻟﻁﺭﻓﻳﺔ ﺑﺷﻛﻝ ﻣﻔﺭﻁ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﻳﻧﻛﺳﺭ ﺍﻟﺑﺭﻏﻲ‪.‬‬
‫)‪ (6‬ﺭﺍﺟﻊ ﺍﻟﺟﺩﻭﻝ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻋﺯﻡ ﺭﺑﻁ ﺍﻟﺑﺭﻏﻲ‪.‬‬
‫)‪ (7‬ﻳﺭﺟﻰ ﻋﺩﻡ ﺗﺛﺑﻳﺕ ‪ 2‬ﻛﺑﻠﻲ ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺑﺭﻏﻲ ‪ 1‬ﻭﺍﺣﺩ‪.‬‬
‫ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫)ﺍﻟﺭﺋﻳﺳﻳﺔ(‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫)ﺍﻟﻔﺭﻋﻳﺔ(‬
‫*‪ :1‬ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻧﻅﺎﻡ ﺍﺳﺗﺭﺩﺍﺩ ﺍﻟﺗﺩﻓﺋﺔ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻟﻭﺣﺩﺓ ‪.RB‬‬
‫*‪ :2‬ﻗﻡ ﺑﺗﺄﺭﻳﺽ )ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻷﺭﺽ( ﻟﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺇﺫﺍ ﻛﺎﻧﺕ ﺗﺗﺿﻣﻥ ﻛﺑﻝ ﺗﺄﺭﻳﺽ )ﺃﺭﺿﻲ(‪.‬‬
‫*‪ :3‬ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻥ ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻟﺳﻠﻙ‪ ،‬ﻻ ﻳﺗﻡ ﺍﺳﺗﺧﺩﺍﻡ ‪.Y3‬‬
‫)ﺃﺳﻼﻙ ﻋﺎﺑﺭﺓ ﻹﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ(‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﻧﺯﻉ ‪ 10‬ﻣﻡ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ُﻛﻡ‬
‫ﺑﺭﻏﻲ ﺑﺣﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺑﺭﻏﻲ ﺑﺣﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﺍﻟﻛﺑﻝ‬
‫ﻁﺭﻑ ﺣﻠﻘﻲ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﻁﺭﻑ ﺣﻠﻘﻲ‬
‫ﻁﺭﻑ ﺣﻠﻘﻲ‬
‫ﺻﻧﺩﻭﻕ‬
‫ﺳﺣﺏ‬
‫ﻣﺟﻣﻭﻋﺔ ﻁﺭﻓﻳﺔ‬
‫ﺍﻟﻛﺑﻝ‬
‫ﻗﺎﻁﻊ ﺍﻟﺩﺍﺋﺭﺓ‬
‫ﺻﻧﺩﻭﻕ ﺳﺣﺏ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﻗﻡ ﺑﺗﺄﺭﻳﺽ )ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻷﺭﺽ( ﻟﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺇﺫﺍ ﻛﺎﻧﺕ ﺗﺗﺿﻣﻥ ﺳﻠﻙ ﺗﺄﺭﻳﺽ )ﺃﺭﺿﻲ(‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﺳﻠﻙ ﺍﻷﺭﺿﻲ )ﺍﻟﺗﺄﺭﻳﺽ( ﻟﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺑﺎﻟﻁﺭﻑ ﺍﻷﺭﺿﻲ )ﺍﻟﺗﺄﺭﻳﺽ( ﻓﻲ ﻛﺑﻝ ﺍﻟﻧﻘﻝ‪.‬‬
‫ﺗﺣﺫﻳﺭ‬
‫ﺍﺳﺗﺧﺩﻡ ﺃﻁﺭﺍﻑ ﺣﻠﻘﻳﺔ ﻭﺍﺭﺑﻁ ﺑﺭﺍﻏﻲ ﺍﻷﻁﺭﺍﻑ ﺣﺳﺏ ﺍﻟﻌﺯﻡ ﺍﻟﻣﺣﺩﺩ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﺗﺻﺩﺭ ﺳﺧﻭﻧﺔ ﺯﺍﺋﺩﺓ ﻏﻳﺭ ﻋﺎﺩﻳﺔ ﻭﻣﻥ‬
‫ﺍﻟﻣﺣﺗﻣﻝ ﺃﻥ ﺗﺳﺑﺏ ﺗﻠﻑ ﺷﺩﻳﺩ ﺩﺍﺧﻝ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫‪ .3.6‬ﺃﺳﻼﻙ ﺍﻟﻭﺣﺩﺓ‬
‫ﻋﺯﻡ ﺍﻟﺭﺑﻁ‬
‫ﻗﺑﻝ ﺗﻭﺻﻳﻝ ﺍﻟﻛﺑﻝ ﺑﺎﻟﻣﺟﻣﻭﻋﺔ ﺍﻟﻁﺭﻓﻳﺔ‪.‬‬
‫ﺑﺭﻏﻲ ‪) M4‬ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‪(GND ،N ،L/‬‬
‫‪ 1.3.6‬ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫‪ 1.2‬ﺇﻟﻰ ‪ 1.8‬ﻧﻳﻭﺗﻥ ﻣﺗﺭ )‪ 12‬ﺇﻟﻰ ‪ 18‬ﻛﺟﻡ ﻗﻭﺓ ﺳﻡ(‬
‫ﺍﺿﺑﻁ ﻁﻭﻝ ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻟﺗﺟﻧﺏ ﺍﻟﺷﺩ ﺍﻟﻣﻔﺭﻁ ﻣﻥ ﺧﻼﻝ ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ﺍﻟﺷﻛﻝ ﺍﻟﺗﺎﻟﻲ‪.‬‬
‫‪2.3.6‬‬
‫‪ 20‬ﻣﻡ‬
‫ﻛﺑﻝ ﺍﻟﻧﻘﻝ ﻭﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﻛﺑﻝ ﺍﻟﻧﻘﻝ‬
‫ﻛﺑﻝ ﺍﻟﺗﺄﺭﻳﺽ )ﺍﻷﺭﺿﻲ(‬
‫‪ 25‬ﻣﻡ‬
‫‪ 30‬ﻣﻡ‬
‫ﻛﺑﻝ ﻣﻐﻠﻑ )ﺑﺩﻭﻥ ﺭﻗﺎﻗﺔ(‬
‫‪ 40‬ﻣﻡ‬
‫‪ .A‬ﻟﻸﺳﻼﻙ ﺑﻣﺭﻛﺯ ﻣﺻﻣﺕ‬
‫ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫)‪ (1‬ﻟﺗﻭﺻﻳﻝ ﺍﻟﻁﺭﻑ ﺍﻟﻛﻬﺭﺑﺎﺋﻲ‪ ،‬ﺍﺗﺑﻊ ﺍﻟﻣﺧﻁﻁ ﺃﺩﻧﺎﻩ ﻭﻗﻡ ﺑﺎﻟﺗﻭﺻﻳﻝ ﺑﻌﺩ ﻋﻣﻝ ﻁﻳﺔ ﺣﻭﻝ ﻁﺭﻑ ﺍﻟﻛﺑﻝ‪.‬‬
‫ﻟﻠﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫)‪ (2‬ﺍﺳﺗﺧﺩﻡ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﺣﺩﺩﺓ‪ ،‬ﻭﻗﻡ ﺑﺗﻭﺻﻳﻠﻬﺎ ﺑﺈﺣﻛﺎﻡ‪ ،‬ﺛﻡ ﺛﺑﺗﻬﺎ ﺑﺣﻳﺙ ﻻ ﻳﻛﻭﻥ ﻫﻧﺎﻙ ﺃﻱ ﺷﺩ ﻋﻠﻰ ﺍﻷﻁﺭﺍﻑ‪.‬‬
‫ﻟﻠﻧﻭﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫‪ 20‬ﻣﻡ‬
‫)‪ (3‬ﺍﺳﺗﺧﺩﻡ ﻣﻔﻙ ﻣﻧﺎﺳﺏ ﻟﺭﺑﻁ ﺑﺭﺍﻏﻲ ﺍﻷﻁﺭﺍﻑ‪.‬‬
‫‪ 20‬ﻣﻡ‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﻣﻔﻙ ﺻﻐﻳﺭ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﻳﺗﻠﻑ ﺭﺃﺱ ﺍﻟﺑﺭﻏﻲ ﻭﻳﻣﻧﻊ ﺭﺑﻁ ﺍﻟﺑﺭﺍﻏﻲ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪.‬‬
‫)‪ (4‬ﻻ ﺗﺭﺑﻁ ﺍﻟﺑﺭﺍﻏﻲ ﺍﻟﻁﺭﻓﻳﺔ ﺑﺷﻛﻝ ﻣﻔﺭﻁ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﻳﻧﻛﺳﺭ ﺍﻟﺑﺭﻏﻲ‪.‬‬
‫)‪ (5‬ﺭﺍﺟﻊ ﺍﻟﺟﺩﻭﻝ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻋﺯﻡ ﺭﺑﻁ ﺍﻟﺑﺭﻏﻲ‪.‬‬
‫• ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻼﺕ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻭﻛﺑﻼﺕ ﺍﻟﻧﻘﻝ ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ‪.A .Fig‬‬
‫)‪ (6‬ﻳﺭﺟﻰ ﻋﺩﻡ ﺗﺛﺑﻳﺕ ‪ 2‬ﻛﺑﻠﻲ ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺑﺭﻏﻲ ‪ 1‬ﻭﺍﺣﺩ‪.‬‬
‫‪A .Fig‬‬
‫ﻧﺯﻉ ‪ 25‬ﻣﻡ‬
‫ﺟﻳﺩ‬
‫ﻣﺣﻅﻭﺭ‬
‫ﺣﻠﻘﺔ‬
‫ﺑﺭﻏﻲ ﺑﺣﻠﻘﺔ‬
‫ﺧﺎﺻﺔ‬
‫ﻁﺭﻑ ﺍﻟﻛﺑﻝ‬
‫)ﺣﻠﻘﺔ(‬
‫ﺍﻟﻛﺑﻝ‬
‫ﺑﺭﻏﻲ ﺑﺣﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﻁﺭﻑ ﺍﻟﻛﺑﻝ‬
‫)ﺣﻠﻘﺔ(‬
‫ﺗﻭﺻﻳﻝ ﻓﻲ ﺟﺎﻧﺏ ‪ 1‬ﻭﺍﺣﺩ‬
‫ﻗﻁﺭ ﻣﺧﺗﻠﻑ‬
‫ﻣﺟﻣﻭﻋﺔ ﻁﺭﻓﻳﺔ‬
‫ﺍﻟﻛﺑﻝ‬
‫ﺗﺣﺫﻳﺭ‬
‫ﺍﺭﺑﻁ ﺑﺭﺍﻏﻲ ﺍﻷﻁﺭﺍﻑ ﺣﺳﺏ ﺍﻟﻌﺯﻡ ﺍﻟﻣﺣﺩﺩ‪ ،‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﺗﺻﺩﺭ ﺳﺧﻭﻧﺔ ﺯﺍﺋﺩﺓ ﻏﻳﺭ ﻋﺎﺩﻳﺔ ﻭﻣﻥ ﺍﻟﻣﺣﺗﻣﻝ ﺃﻥ ﺗﺳﺑﺏ ﺗﻠﻑ‬
‫ﺷﺩﻳﺩ ﺩﺍﺧﻝ ﺍﻟﻭﺣﺩﺓ‪.‬‬
‫ﺭﻗﻡ ﺍﻟﻁﺭﻑ‬
‫ﺑﺭﻏﻲ ‪) M3‬ﻛﺑﻝ ﺍﻟﻧﻘﻝ‪(X2 ،X1/‬‬
‫)ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪(Y2 ،Y1 /‬‬
‫ﻋﺯﻡ ﺍﻟﺭﺑﻁ‬
‫‪ 0.5‬ﺇﻟﻰ ‪ 0.6‬ﻧﻳﻭﺗﻥ ﻣﺗﺭ‬
‫)‪ 5‬ﺇﻟﻰ ‪ 6‬ﻛﺟﻡ ﻗﻭﺓ ﺳﻡ(‬
‫‪Ar-10‬‬
‫‪2017/8/8 13:08:57‬‬
‫‪9381858019-02_IM_AR.indd Sec1:10‬‬
‫ﺗﻧﺑﻳﻪ‬
‫‪ .5.6‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ ﻭﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‬
‫ﻟﺗﻘﺷﻳﺭ ﺍﻟﻐﻼﻑ ﻣﻥ ﻋﻠﻰ ﺍﻟﻛﺑﻝ ﺍﻟﺭﺋﻳﺳﻲ‪ ،‬ﺍﺳﺗﺧﺩﻡ ﺃﺩﺍﺓ ﻣﺧﺻﺻﺔ ﻻ ﺗﺗﻠﻑ ﺍﻟﻛﺑﻝ ﺍﻟﻣﻭﺻﻝ‪.‬‬
‫ﻋﻧﺩ ﺗﺭﻛﻳﺏ ﺑﺭﻏﻲ ﻋﻠﻰ ﺍﻟﻣﺟﻣﻭﻋﺔ ﺍﻟﻁﺭﻓﻳﺔ ﻻ ﺗﻘﻁﻊ ﺍﻟﻛﺑﻝ ﻣﻥ ﺧﻼﻝ ﺍﻟﺭﺑﻁ ﺍﻟﻣﻔﺭﻁ ﻟﻠﺑﺭﻏﻲ‪ .‬ﻣﻥ ﻧﺎﺣﻳﺔ ﺃﺧﺭﻯ‪ ،‬ﻳﺅﺩﻱ ﺍﻟﺑﺭﻏﻲ‬
‫ﻏﻳﺭ ﺍﻟﻣﺭﺑﻭﻁ ﺑﺈﺣﻛﺎﻡ ﺇﻟﻰ ﻋﻁﻝ ﻓﻲ ﺍﻟﺗﻭﺻﻳﻝ‪ ،‬ﻣﻣﺎ ﻳﺅﺩﻱ ﺇﻟﻰ ﺗﻌﻁﻝ ﺍﻻﺗﺻﺎﻝ‪.‬‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫‪SW1‬‬
‫‪SW2‬‬
‫‪SW3‬‬
‫‪SW4‬‬
‫)‪ (1‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻐﻁﺎء‪.‬‬
‫)‪ (2‬ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻝ ﺍﻟﺗﻭﺻﻳﻝ‪.‬‬
‫ﻏﻁﺎء‬
‫‪)ON‬ﺗﺷﻐﻳﻝ( ‪)OFF‬ﺇﻳﻘﺎﻑ(‬
‫‪ .4.6‬ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ‬
‫ﺍﻟﻣﺯﺩﻭﺟﺔ )‪(SET 2‬‬
‫ﻁﺭﻑ ﺍﻟﺗﻼﻣﺱ ﺍﻟﺟﺎﻑ‬
‫ﺑﺭﻏﻲ‬
‫)‪(CNA04‬‬
‫)‪(CNA02‬‬
‫ﻁﺭﻑ ﺍﻹﺧﺭﺍﺝ‬
‫)‪(CNB01‬‬
‫ﻁﺭﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻋﻧﺩ ﺗﺑﺩﻳﻝ ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ )‪ ،(SW1‬ﺗﺄﻛﺩ ﻣﻥ ﺇﻳﻘﺎﻑ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﺇﻟﻰ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪ .‬ﺧﻼﻑ ﺫﻟﻙ‪ ،‬ﻗﺩ ﺗﺗﻠﻑ ﻟﻭﺣﺔ‬
‫ﺍﻟﻛﻣﺑﻳﻭﺗﺭ ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫)‪ (1‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫•‬
‫•‬
‫‪ :Y3،Y2،Y1‬ﻛﺑﻝ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫)‪(CNA01‬‬
‫)‪(CNA03‬‬
‫ﻳﻣﻛﻥ ﺗﺷﻐﻳﻝ‪/‬ﺇﻳﻘﺎﻑ‪ ،‬ﺃﻭ ﻋﻣﻝ ﺇﻳﻘﺎﻑ ﻁﻭﺍﺭﺉ‪ ،‬ﺃﻭ ﺇﻳﻘﺎﻑ ﺇﺟﺑﺎﺭﻱ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ ﺭﻗﻡ ‪CNA01‬‬
‫ﺃﻭ ‪ CNA02‬ﺑﺎﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫ﻳﻣﻛﻥ ﺍﺧﺗﻳﺎﺭ ﻭﺿﻊ "ﺗﺷﻐﻳﻝ‪/‬ﺇﻳﻘﺎﻑ" ﺃﻭ "ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ" ﺃﻭ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ" ﻣﻊ ﺇﻋﺩﺍﺩ ﻭﻅﻳﻔﺔ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫ﻳﻣﻛﻥ ﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺇﺟﺑﺎﺭﻳًﺎ ﻋﻥ ﻁﺭﻳﻕ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ ﺑﻭﺍﺳﻁﺔ ﺍﺳﺗﺧﺩﺍﻡ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ ﺭﻗﻡ ‪ CNA03‬ﺃﻭ‬
‫‪ CNA04‬ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫ﻳﺟﺏ ﺍﺳﺗﺧﺩﺍﻡ ﻛﺑﻝ ﺛﻧﺎﺋﻲ ﻣﻠﻔﻭﻑ )ﻣﻘﺎﺱ ‪ .(AWG22‬ﺃﻗﺻﻰ ﻁﻭﻝ ﻟﻠﻛﺑﻝ ‪ 150‬ﻣﺗﺭ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻛﺑﻝ ﺇﺩﺧﺎﻝ ﻭﺇﺧﺭﺍﺝ ﺧﺎﺭﺟﻲ ﺑﺎﻷﺑﻌﺎﺩ ﺍﻟﺧﺎﺭﺟﻳﺔ ﺍﻟﻣﻧﺎﺳﺑﺔ‪ ،‬ﺗﺑﻌًﺎ ﻟﻌﺩﺩ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﺭﺍﺩ ﺗﺭﻛﻳﺑﻬﺎ‪.‬‬
‫ﻳﺟﺏ ﺃﻥ ﺗﻛﻭﻥ ﻭﺻﻠﺔ ﺍﻟﺳﻠﻙ ﻣﻧﻔﺻﻠﺔ ﻋﻥ ﺧﻁ ﻛﺑﻝ ﺍﻟﻁﺎﻗﺔ‪.‬‬
‫ﺍﺧﺗﻳﺎﺭ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﺳﺗﺧﺩﻡ ﺃﺣﺩ ﺃﻧﻭﺍﻉ ﺍﻷﻁﺭﺍﻑ ﻫﺫﻩ ﺗﺑﻌًﺎ ﻟﻼﺳﺗﻌﻣﺎﻝ‪) .‬ﻻ ﻳﻣﻛﻥ ﺍﺳﺗﺧﺩﺍﻡ ﻛﻼ ﺍﻟﻧﻭﻋﻳﻥ ﻣﻥ ﺍﻷﻁﺭﺍﻑ ﻓﻲ ﻧﻔﺱ ﺍﻟﻭﻗﺕ‪(.‬‬
‫● ﻁﺭﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ )]‪([CNA03] ،[CNA01‬‬
‫ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﻣﻥ ﺍﻟﺿﺭﻭﺭﻱ ﺗﺯﻭﻳﺩ ﺍﻟﻁﺎﻗﺔ ﻓﻲ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺫﻱ ﺗﺭﻳﺩ ﺗﻭﺻﻳﻠﻪ‪ ،‬ﺍﺳﺗﺧﺩﺍﻡ ﻁﺭﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ )]‪،[CNA01‬‬
‫]‪.([CNA03‬‬
‫‪ :X2 ،X1‬ﻛﺑﻝ ﺍﻟﻧﻘﻝ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﺃﺭﺿﻲ‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺣﻣﻝ‬
‫‪CNA01‬‬
‫*‪a‬‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫‪ :N ،L‬ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫*‪ 1‬ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‬
‫‪ 12‬ﺇﻟﻰ ‪ 24‬ﻓﻭﻟﺕ‬
‫*‪b‬‬
‫ﻣﺷﺑﻙ ﺍﻟﻛﺑﻝ‬
‫*‪a‬‬
‫‪CNA03‬‬
‫ﻟﻠﻧﻭﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫ﻟﻠﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫ﺗﻭﺻﻳﻝ ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ‬
‫‪:Y1‬ﻏﻳﺭ ﻗﻁﺑﻲ‬
‫‪:Y2‬ﻏﻳﺭ ﻗﻁﺑﻲ‬
‫‪:Y3‬ﻻ ﺗﻘﻡ ﺑﺗﻭﺻﻳﻠﻪ*‪1‬‬
‫‪:Y1‬ﺃﺣﻣﺭ‬
‫‪:Y2‬ﺃﺑﻳﺽ‬
‫‪:Y3‬ﺃﺳﻭﺩ‬
‫ﺇﻋﺩﺍﺩ ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ‬
‫ﺍﻟﻣﺯﺩﻭﺟﺔ )‪(SW1‬‬
‫‪ 2‬ﺳﻠﻙ‬
‫)ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ(‬
‫‪ 3‬ﺳﻠﻙ‬
‫*‪ :1‬ﻓﻲ ﺣﺎﻟﺔ ﺗﻭﺻﻳﻝ ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻑﻥﻋ ﻡﻛﺣﺗﻟﺍ ﺓﺩﺣﻭ ﻥﺈﻓ ‪ Y3،‬ﻑﺭﻁﻟﺍ ﻱ‬
‫ﺏﻋﺩ ﻣﻥ ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ ﻟﻥ ﺗﻌﻣﻝ‪.‬‬
‫*‪a‬‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ‬
‫ﺍﻟﻣﺯﺩﻭﺟﺔ‬
‫)‪(SW1‬‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪3‬‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺣﻣﻝ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺣﻣﻝ‬
‫ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‬
‫*‪ 1‬ﺍﺟﻌﻝ ﻣﺻﺩﺭ ﺍﻟﻁﺎﻗﺔ ‪ 12‬ﺇﻟﻰ ‪ 24‬ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ‪ .‬ﺣﺩﺩ ﻗﺩﺭﺓ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻣﻊ ﻓﺎﺋﺽ ﻛﺑﻳﺭ ﻟﻠﺣﻣﻝ ﺍﻟﻣﺗﺻﻝ‪.‬‬
‫ﻻ ﺗﺳﺗﺧﺩﻡ ﺟﻬﺩًﺍ ﻳﺗﺟﺎﻭﺯ ‪ 24‬ﻓﻭﻟﺕ ﻓﻲ ﺍﻟﻣﺳﺎﻣﻳﺭ ‪ 1-2‬ﻭ‪.1-3‬‬
‫*‪ a‬ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﻣﻭﺡ ﺑﻪ ﻫﻭ ‪ 5‬ﺇﻟﻰ ‪ 10‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﺗﻳﺎﺭ ﻣﺑﺎﺷﺭ‪) .‬ﺍﻟﻣﻭﺻﻰ ﺑﻪ‪ 5 :‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ(‬
‫ﻗﻡ ﺑﺗﻭﻓﻳﺭ ﻣﻘﺎﻭﻣﺔ ﺣﻣﻝ ﺑﺣﻳﺙ ﻳﺻﺑﺢ ﺍﻟﺗﻳﺎﺭ ‪ 10‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ ﺃﻭ ﺃﻗﻝ‪.‬‬
‫ﺣﺩﺩ ﻣﻼﻣﺳﺎﺕ ﺗﺳﺗﺧﺩﻡ ﺗﻳﺎﺭً ﺍ ﻣﻧﺧﻔﺿًﺎ ﻟﻠﻐﺎﻳﺔ )ﺍﻟﻣﺳﺗﺧﺩﻣﺔ ﻋﻧﺩ ‪ 12‬ﻓﻭﻟﺕ ‪ 1‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ ﺃﻭ ﺃﻗﻝ(‪.‬‬
‫*‪ b‬ﺍﻟﻘﻁﺑﻳﺔ ﺗﻛﻭﻥ ]‪ [+‬ﻟﻠﻣﺳﺎﺭ ‪ 1‬ﻭ ]‪ [-‬ﻟﻠﻣﺳﻣﺎﺭ ‪ 2‬ﻭ‪ .3‬ﻗﻡ ﺑﺎﻟﺗﻭﺻﻳﻝ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‪.‬‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻣﺗﻭﺳﻁ(‬
‫)ﻣﻠﺣﻘﺎﺕ(‬
‫ﺗﺟﻧﺏ ﺗﻐﻁﻳﺔ ﻣﺩﺧﻝ ﺍﻟﻬﻭﺍء‬
‫ﺑﺎﻷﺳﻼﻙ‪.‬‬
‫ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫ﺗﺟﻧﺏ ﻣﻼﻣﺳﺔ ﺍﻟﺳﻘﻑ ﺑﺎﻷﺳﻼﻙ‪.‬‬
‫ﺍﻟﺳﻘﻑ‬
‫ﻻ ﺗﻘﻡ ﺑﺭﺑﻁ ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻭﺍﻟﻛﺑﻼﺕ ﺍﻷﺧﺭﻯ ﻣﻌًﺎ‪.‬‬
‫‪Ar-11‬‬
‫‪2017/8/8 13:08:57‬‬
‫‪9381858019-02_IM_AR.indd Sec1:11‬‬
‫ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﻓﻲ ﺃﻁﺭﺍﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ ﻟﻌﺩﺓ ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ ﻣﻊ ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ ﻋﻣﻝ ﺗﻔﺭﻳﻌﺔ ﺧﺎﺭﺝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻟﺗﻲ‬
‫ﺗﺳﺗﺧﺩﻡ ﺻﻧﺩﻭﻕ ﺳﺣﺏ ﺃﻭ ﻏﻳﺭﻩ‪ ،‬ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ﺍﻟﻣﺛﺎﻝ ﺍﻟﺗﺎﻟﻲ‪.‬‬
‫● ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﻫﻭ ﻭﺿﻊ "ﺗﺷﻐﻳﻝ‪/‬ﺇﻳﻘﺎﻑ"‪.‬‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﺣﺯ"[‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ‬
‫‪ 12‬ﺇﻟﻰ ‪ 24‬ﻓﻭﻟﺕ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺍﻟﻘﻧﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫‪CNA01‬‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺣﻣﻝ‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺣﻣﻝ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﺗﺷﻐﻳﻝ ← ﺇﻳﻘﺎﻑ‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﻧﺑﺽ"[‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫‪CNA01‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺍﻟﻘﻧﺎﺓ‪1‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﺍﻟﻘﻧﺎﺓ ‪2‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺇﻳﻘﺎﻑ‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫* ﺍﻷﻣﺭ ﺍﻷﺧﻳﺭ ﻟﻪ ﺍﻷﻭﻟﻭﻳﺔ‪.‬‬
‫* ﺗﻌﻣﻝ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺿﻣﻥ ﻧﻔﺱ ﻣﺟﻣﻭﻋﺔ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻓﻲ ﻧﻔﺱ ﺍﻟﻭﺿﻊ‪.‬‬
‫ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‬
‫‪CNA01‬‬
‫● ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﻫﻭ ﻭﺿﻊ "ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ"‪.‬‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﺣﺯ"[‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫● ﻁﺭﻑ ﺍﻻﺗﺻﺎﻝ ﺍﻟﺟﺎﻑ )]‪([CNA04] ،[CNA02‬‬
‫ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﻣﻥ ﻏﻳﺭ ﺍﻟﺿﺭﻭﺭﻱ ﺗﺯﻭﻳﺩ ﺍﻟﻁﺎﻗﺔ ﺇﻟﻰ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺫﻱ ﺗﺭﻳﺩ ﺗﻭﺻﻳﻠﻪ‪ ،‬ﺍﺳﺗﺧﺩﺍﻡ ﻁﺭﻑ ﺍﻻﺗﺻﺎﻝ ﺍﻟﺟﺎﻑ‬
‫)]‪.([CNA04] ،[CNA02‬‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ‬
‫ﺗﺷﻐﻳﻝ ← ﺇﻳﻘﺎﻑ‬
‫ﻋﺎﺩﻱ‬
‫ﺍﻟﻘﻧﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﻧﺑﺽ"[‬
‫‪CNA02‬‬
‫*‪d‬‬
‫*‪c‬‬
‫ﻗﻧﺎﺓ ‪2‬‬
‫ﺃﺭﺿﻲ‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫*‪c‬‬
‫ﻗﻧﺎﺓ ‪1‬‬
‫ﺍﻟﻘﻧﺎﺓ‪1‬‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﺍﻟﻘﻧﺎﺓ ‪2‬‬
‫*‪c‬‬
‫ﻗﻧﺎﺓ ‪3‬‬
‫‪CNA04‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫* ﺗﺗﻭﻗﻑ ﺟﻣﻳﻊ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻟﻧﻔﺱ ﻧﻅﺎﻡ ﺍﻟﺗﺑﺭﻳﺩ ﻋﻧﺩ ﺗﺷﻐﻳﻝ ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ‪.‬‬
‫ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‬
‫● ﻋﻧﺩﻣﺎ ﻳﻛﻭﻥ ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﻫﻭ ﻭﺿﻊ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ"‪.‬‬
‫*‪ c‬ﺣﺩﺩ ﻣﻼﻣﺳﺎﺕ ﺗﺳﺗﺧﺩﻡ ﺗﻳﺎﺭً ﺍ ﻣﻧﺧﻔﺿًﺎ ﻟﻠﻐﺎﻳﺔ )ﺍﻟﻣﺳﺗﺧﺩﻣﺔ ﻋﻧﺩ ‪ 12‬ﻓﻭﻟﺕ ‪ 1‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ ﺃﻭ ﺃﻗﻝ(‪.‬‬
‫*‪ d‬ﺍﻷﺳﻼﻙ ﻣﺧﺗﻠﻔﺔ ﻋﻥ ﺃﻁﺭﺍﻑ ﺗﻁﺑﻳﻕ ﺍﻟﺟﻬﺩ‪ .‬ﻛﻥ ﺣﺫﺭً ﺍ ﻋﻠﻰ ﻭﺟﻪ ﺍﻟﺧﺻﻭﺹ ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ‪.‬‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﺣﺯ"[‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺄﻁﺭﺍﻑ ﺍﻟﺗﻭﺻﻳﻝ ﺍﻟﺟﺎﻑ ﻟﻌﺩﺓ ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ ﻣﻊ ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‪ ،‬ﻗﻡ ﺑﻌﺯﻝ ﻛﻝ ﻭﺣﺩﺓ ﺩﺍﺧﻠﻳﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻣﺭﺣﻝ ﺃﻭ‬
‫ﻏﻳﺭﻩ‪ ،‬ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ﺍﻟﻣﺛﺎﻝ ﺍﻟﺗﺎﻟﻲ‪.‬‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ‬
‫ﺍﻟﻘﻧﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﺗﺷﻐﻳﻝ ← ﺇﻳﻘﺎﻑ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﻋﺎﺩﻱ‬
‫ﻋﺎﺩﻱ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﻧﺑﺽ"[‬
‫‪K1‬‬
‫‪K4‬‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫‪CNA02‬‬
‫ﺍﻟﻘﻧﺎﺓ‪1‬‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻟﻠﻣﺭﺣﻝ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫‪K2‬‬
‫‪K5‬‬
‫‪CNA02‬‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﺍﻟﻘﻧﺎﺓ ‪2‬‬
‫ﻋﺎﺩﻱ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫* ﻋﻧﺩ ﺗﻧﺷﻳﻁ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ‪ ،‬ﺗﺗﻭﻗﻑ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻳﺗﻡ ﺗﻘﻳﻳﺩ ﻋﻣﻠﻳﺔ "ﺍﻹﻳﻘﺎﻑ‪/‬ﺍﻟﺗﺷﻐﻳﻝ" ﻋﻥ ﻁﺭﻳﻕ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ‬
‫ﺑﻌﺩ‪.‬‬
‫* ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻭﻅﻳﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ ﻣﻊ ﺗﺷﻛﻳﻝ ﻣﺟﻣﻭﻋﺔ ﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪ ،‬ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻧﻔﺱ ﺍﻟﺟﻬﺎﺯ ﺑﻛﻝ ﻭﺣﺩﺓ ﺩﺍﺧﻠﻳﺔ ﺩﺍﺧﻝ‬
‫ﺍﻟﻣﺟﻣﻭﻋﺔ‪.‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫• ﺗﺣﺩﻳﺩ ﺃﺳﻠﻭﺏ ﺍﻟﻭﻅﺎﺋﻑ‬
‫ﻳﻣﻛﻥ ﺍﺧﺗﻳﺎﺭ ﻭﺿﻊ "ﺗﺷﻐﻳﻝ‪/‬ﺇﻳﻘﺎﻑ" ﺃﻭ "ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ" ﺃﻭ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ" ﻣﻊ ﺇﻋﺩﺍﺩ ﻭﻅﻳﻔﺔ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫‪K3‬‬
‫ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫‪K6‬‬
‫● ﻭﻅﻳﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ ﻣﻥ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ‬
‫‪CNA02‬‬
‫]ﺍﻹﺩﺧﺎﻝ "ﺣﺯ" ﻓﻘﻁ[‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫‪ :K6 - K1‬ﻣﺭﺣﻝ‬
‫)ﺟﻬﺎﺯ ﻟﻠﺗﻳﺎﺭ ﺍﻟﻣﺳﺗﻣﺭ(‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻷﻣﺭ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺷﻐﻳﻝ‬
‫ﺇﻳﻘﺎﻑ ﺑﻭﺍﺳﻁﺔ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ‬
‫ﺍﻟﻘﻧﺎﺓ ‪ 3‬ﻟـ ‪ CNA03‬ﺃﻭ ‪CNA04‬‬
‫ﺗﺷﻐﻳﻝ ← ﺇﻳﻘﺎﻑ‬
‫ﻋﺎﺩﻱ‬
‫ﻣﻼﺣﻅﺔ‪:‬‬
‫ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻌﺩﺓ ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ ﻣﺑﺎﺷﺭﺓ‪ ،‬ﺳﻭﻑ ﻳﺳﺑﺏ ﺍﻟﺗﻌﻁﻝ‪.‬‬
‫ﺳﻠﻭﻙ ﺍﻟﺗﺷﻐﻳﻝ‬
‫ﺣﺯ‬
‫● ﻧﻭﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﻳﻣﻛﻥ ﺍﺧﺗﻳﺎﺭ ﻧﻭﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‪.‬‬
‫ﻭﻳﺗﻡ ﺗﺑﺩﻳﻠﻬﺎ ﻣﻥ ﺧﻼﻝ ﻣﻔﺗﺎﺡ ﻣﺑﺩﻟﺔ ﻣﺯﺩﻭﺟﺔ ﻋﻠﻰ ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ ]ﺇﻋﺩﺍﺩ ‪[SW2 2‬‬
‫ﻧﻭﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺇﻳﻘﺎﻑ )ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ(‬
‫ﺣﺯ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﻧﺑﺽ‬
‫ﻧﺑﺽ‬
‫ﻋﺭﺽ ﺍﻟﻧﺑﺽ ﻳﺟﺏ ﺃﻥ ﻳﻛﻭﻥ‬
‫ﺃﻁﻭﻝ ﻣﻥ ‪ 200‬ﻣﻳﻠﻲ ﺛﺎﻧﻳﺔ‪.‬‬
‫‪Ar-12‬‬
‫‪2017/8/8 13:08:56‬‬
‫‪9381858019-02_IM_AR.indd Sec1:12‬‬
‫)‪ (2‬ﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫ﺗﻧﺑﻳﻪ‬
‫*‬
‫ﻳﺟﺏ ﺍﺳﺗﺧﺩﺍﻡ ﻛﺑﻝ ﺛﻧﺎﺋﻲ ﻣﻠﻔﻭﻑ )ﻣﻘﺎﺱ ‪ .(22AWG‬ﺃﻗﺻﻰ ﻁﻭﻝ ﻟﻠﻛﺑﻝ ‪ 25‬ﻣﺗﺭ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻛﺑﻝ ﺇﺩﺧﺎﻝ ﻭﺇﺧﺭﺍﺝ ﺧﺎﺭﺟﻲ ﺑﺎﻷﺑﻌﺎﺩ ﺍﻟﺧﺎﺭﺟﻳﺔ ﺍﻟﻣﻧﺎﺳﺑﺔ‪ ،‬ﺗﺑﻌًﺎ ﻟﻌﺩﺩ ﺍﻟﻛﺑﻼﺕ ﺍﻟﻣﺭﺍﺩ ﺗﺭﻛﻳﺑﻬﺎ‪.‬‬
‫ﺟﻬﺩ ﺍﻹﺧﺭﺍﺝ‪ :‬ﻣﺭﺗﻔﻊ ‪ 12 ±2‬ﻓﻭﻟﺕ‪ ،‬ﻣﻧﺧﻔﺽ ‪ 0‬ﻓﻭﻝ‪.‬‬
‫ﺍﻟﺗﻳﺎﺭ ﺍﻟﻣﺳﻣﻭﺡ ﺑﻪ‪ 50 :‬ﻣﻳﻠﻲ ﺃﻣﺑﻳﺭ‬
‫ﻟﺣﻣﺎﻳﺔ ﻋﺯﻝ ﺍﻟﻛﺑﻝ ﺑﻌﺩ ﻋﻣﻝ ﻓﺗﺣﺔ ﻣﺛﻘﻭﺑﺔ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﻲ ﻣﻥ ﺣﺎﻓﺔ ﺍﻟﻔﺗﺣﺔ‪.‬‬
‫‪ .6.6‬ﺍﻟﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‬
‫ﺍﺧﺗﻳﺎﺭ ﺍﻹﺧﺭﺍﺝ‬
‫● ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﻣﺅﺷﺭ ﺃﻭ ﻏﻳﺭﻩ ﻣﺑﺎﺷﺭﺓ‬
‫ﻁﺭﻳﻘﺔ ﺍﻟﺗﻭﺻﻳﻝ‬
‫• ﺃﻁﺭﺍﻑ ﺍﻟﺗﻭﺻﻳﻝ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻣﺅﺷﺭ‬
‫ﺍﻟﺗﺷﻐﻳﻝ‬
‫ﻣﺅﺷﺭ‬
‫ﺍﻟﺧﻁﺄ‬
‫‪CNB‬‬
‫‪01‬‬
‫ﻣﺅﺷﺭ ﺣﺎﻟﺔ ﻣﺭﻭﺣﺔ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻁﺭﻑ ﺍﻟﻣﺳﺗﺷﻌﺭ ﻋﻥ‬
‫ﺑﻌﺩ )‪(CN8‬‬
‫ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‬
‫● ﻋﻧﺩ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻭﺣﺩﺓ ﻣﺟﻬﺯﺓ ﺑﻣﺻﺩﺭ ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ‬
‫ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺗﺻﻝ ‪1‬‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺗﺻﻝ ‪2‬‬
‫‪CNB‬‬
‫‪01‬‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺗﺻﻝ ‪3‬‬
‫ﻣﺭﺣﻝ )ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ(‬
‫• ﺗﺭﺗﻳﺏ ﺍﻷﺳﻼﻙ‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻭﺣﺩﺓ ﻣﺗﺻﻠﺔ‬
‫ﺳﻠﻭﻙ ﺍﻟﺗﺷﻐﻳﻝ‬
‫ﺍﻟﻣﻭﺻﻝ‬
‫ﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ ‪1‬‬
‫ﺍﻟﻣﺳﺎﻣﻳﺭ ‪1-2‬‬
‫ﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ ‪2‬‬
‫ﺍﻟﻣﺳﺎﻣﻳﺭ ‪1-3‬‬
‫‪CNB01‬‬
‫ﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ ‪3‬‬
‫ﺍﻟﻣﺳﺎﻣﻳﺭ ‪1-4‬‬
‫ﺟﻬﺩ ﺍﻹﺧﺭﺍﺝ‬
‫ﺍﻟﺣﺎﻟﺔ‬
‫‪ 0‬ﻓﻭﻟﺕ‬
‫ﺇﻳﻘﺎﻑ‬
‫‪ 12‬ﻓﻭﻟﺕ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ‬
‫ﺗﺷﻐﻳﻝ‬
‫‪ 0‬ﻓﻭﻟﺕ‬
‫ﻋﺎﺩﻱ‬
‫‪ 12‬ﻓﻭﻟﺕ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ‬
‫ﺧﻁﺄ‬
‫‪ 0‬ﻓﻭﻟﺕ‬
‫ﺇﻳﻘﺎﻑ ﻣﺭﻭﺣﺔ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫‪ 12‬ﻓﻭﻟﺕ ﺗﻳﺎﺭ ﻣﺳﺗﻣﺭ‬
‫ﺗﺷﻐﻳﻝ ﻣﺭﻭﺣﺔ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)‪ (3‬ﻁﺭﻕ ﺍﻟﺗﻭﺻﻳﻝ‬
‫• ﺗﻌﺩﻳﻝ ﺍﻟﺳﻠﻙ‬
‫ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻌﺎﺯﻝ ﻣﻥ ﺍﻟﺳﻠﻙ ﺍﻟﻣﻠﺣﻕ ﺑﻣﻭﺻﻝ ﻁﻘﻡ ﺍﻟﺳﻠﻙ‪.‬‬
‫ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻌﺎﺯﻝ ﻣﻥ ﺍﻟﻛﺑﻝ ﺍﻟﺫﻱ ﺗﻡ ﺷﺭﺍﺅﻩ ﻓﻲ ﺍﻟﻣﻭﻗﻊ‪ .‬ﺍﺳﺗﺧﺩﻡ ﻣﻭﺻﻝ ﻏﻠﻳﻅ ﻣﻌﺯﻭﻝ ﻣﻥ ﺍﻟﻧﻭﻉ ﺍﻟﻣﺟﻌﺩ ﻟﺭﺑﻁ ﻛﺑﻝ ﺍﻟﻣﺟﺎﻝ ﻣﻊ ﺳﻠﻙ ﺍﻟﻁﻘﻡ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﺳﻠﻙ ﻣﻊ ﺳﻠﻙ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻟﻠﺣﺎﻡ‪.‬‬
‫ﻫﺎﻡ‪ :‬ﺗﺄﻛﺩ ﻣﻥ ﻋﺯﻝ ﺍﻟﺗﻭﺻﻳﻝ ﺑﻳﻥ ﺍﻷﺳﻼﻙ‪.‬‬
‫ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ‬
‫ﺳﻠﻙ ﺇﺩﺧﺎﻝ‪/‬ﺇﺧﺭﺍﺝ ﺧﺎﺭﺟﻲ‬
‫ﻳﺗﻡ ﺷﺭﺍﺅﻩ ﻣﺣﻠﻳًﺎ‬
‫• ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻣﻭﺻﻝ ﺍﻟﻣﻭﺟﻭﺩ ﻭﺍﺳﺗﺑﺩﻟﻪ ﺑﻣﻭﺻﻝ ﺍﻟﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ )ﻣﻊ ﺍﻟﺗﺄﻛﺩ ﻣﻥ ﺍﺳﺗﺧﺩﺍﻡ ﺍﻟﻣﻭﺻﻝ ﺍﻟﺻﺣﻳﺢ(‪.‬‬
‫• ﻳﺟﺏ ﻋﺯﻝ ﺍﻟﻣﻭﺻﻝ ﺍﻷﺻﻠﻲ ﻟﺿﻣﺎﻥ ﺃﻧﻪ ﻻ ﻳﺗﺻﻝ ﺑﺩﺍﺋﺭﺓ ﻛﻬﺭﺑﻳﺔ ﺃﺧﺭﻯ‪.‬‬
‫• ﺍﺳﺗﺧﺩﻡ ﻓﺗﺣﺔ ﻣﺧﺭﻭﻁﻳﺔ ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻛﺑﻝ ﺇﺧﺭﺍﺝ ﺧﺎﺭﺟﻲ‪.‬‬
‫*‪‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺣﻣﺎﻳﺔ ﻋﺯﻝ ﺍﻟﻛﺑﻝ ﺑﻌﺩ ﻋﻣﻝ ﻓﺗﺣﺔ ﻣﺛﻘﻭﺑﺔ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﻲ ﻣﻥ ﺣﺎﻓﺔ ﺍﻟﻔﺗﺣﺔ‪.‬‬
‫ﻗﻡ ﺑﻠﺣﺎﻡ ﻭﻋﺯﻝ ﺍﻷﺟﺯﺍء ﺍﻟﻣﺗﺻﻠﺔ‪.‬‬
‫• ﺃﻁﺭﺍﻑ ﺍﻟﺗﻭﺻﻳﻝ ﻭﺗﺭﺗﻳﺑﺎﺕ ﺍﻷﺳﻼﻙ‬
‫ﻓﻲ ﺍﻟﺷﻛﻝ ﺍﻟﺗﺎﻟﻲ‪ ،‬ﺗﻡ ﺗﻭﺻﻳﻝ ﺟﻣﻳﻊ ﺍﻟﻣﻭﺻﻼﺕ ﺍﻟﻣﻣﻛﻧﺔ ﻷﺟﻝ ﺍﻟﺗﻭﺿﻳﺢ‪.‬‬
‫ﻓﻲ ﺍﻟﺗﺭﻛﻳﺏ ﺍﻟﻔﻌﻠﻲ‪ ،‬ﻻ ﻳﻣﻛﻧﻙ ﺗﻭﺻﻳﻝ ﺟﻣﻳﻊ ﺍﻟﻣﻭﺻﻼﺕ ﻣﺭﺓ ﻭﺍﺣﺩﺓ‪.‬‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﺍﻹﻋﺩﺍﺩ ﻟﺗﺻﺣﻳﺢ ﺣﺭﺍﺭﺓ ﺍﻟﻐﺭﻓﺔ‬
‫ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻛﻣﺎ ﻫﻭ ﻣﺑﻳﻥ ﺃﺩﻧﺎﻩ‪.‬‬
‫• ﺭﻗﻡ ﺍﻟﻭﻅﻳﻔﺔ "‪:"30‬‬
‫ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﺭﻗﻡ ﺍﻹﻋﺩﺍﺩ ﻋﻠﻰ "‪) ."00‬ﺍﻻﻓﺗﺭﺍﺿﻲ(‬
‫• ﺭﻗﻡ ﺍﻟﻭﻅﻳﻔﺔ "‪:"31‬‬
‫ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﺭﻗﻡ ﺍﻹﻋﺩﺍﺩ ﻋﻠﻰ "‪."02‬‬
‫* ﺭﺍﺟﻊ "‪ .5.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ" ﻟﻣﻌﺭﻓﺔ ﺍﻟﺗﻔﺎﺻﻳﻝ ﺣﻭﻝ ﺭﻗﻡ ﺍﻟﻭﻅﻳﻔﺔ ﻭﺭﻗﻡ ﺍﻹﻋﺩﺍﺩ‬
‫‪Ar-13‬‬
‫‪2017/8/8 13:08:56‬‬
‫‪9381858019-02_IM_AR.indd Sec1:13‬‬
‫• ﺗﺭﺗﻳﺏ ﺍﻷﺳﻼﻙ‬
‫‪ .7.6‬ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ ‪) IR‬ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫• ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻁﺭﻳﻘﺔ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﻳﺭﺟﻰ ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﺃﻭ ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ ‪.IR‬‬
‫ﻁﺭﻳﻘﺔ ﺍﻟﺗﻭﺻﻳﻝ‬
‫• ﺃﻁﺭﺍﻑ ﺍﻟﺗﻭﺻﻳﻝ‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻁﺭﻑ ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ‬
‫)‪IR(CN18‬‬
‫• ﺗﺭﺗﻳﺏ ﺍﻷﺳﻼﻙ‬
‫ﺍﻟﻘﻠﺏ‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫*‪‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺣﻣﺎﻳﺔ ﻋﺯﻝ ﺍﻟﻛﺑﻝ ﺑﻌﺩ ﻋﻣﻝ ﻓﺗﺣﺔ ﻣﺛﻘﻭﺑﺔ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﻲ ﻣﻥ ﺣﺎﻓﺔ ﺍﻟﻔﺗﺣﺔ‪.‬‬
‫‪ .9.6‬ﺭﺑﻁ ﻛﺑﻝ ﺍﻷﺟﺯﺍء ﺍﻻﺧﺗﻳﺎﺭﻳﺔ‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻣﺗﻭﺳﻁ‪/‬ﻣﻠﺣﻘﺎﺕ(‬
‫ﺍﻟﻣﺳﺗﺷﻌﺭ ﻋﻥ ﺑﻌﺩ‪ ،‬ﻭﻭﺣﺩﺓ ﺍﻻﺳﺗﻘﺑﺎﻝ ﻭﺷﺑﻛﺔ‬
‫ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ‬
‫ﺭﺍﺑﻁ ﺍﻟﻛﺑﻝ )ﻣﺗﻭﺳﻁ‪/‬ﻣﻠﺣﻘﺎﺕ(‬
‫ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ ﻭﺍﻹﺧﺭﺍﺝ ﺍﻟﺧﺎﺭﺟﻲ‬
‫ﺗﺟﻧﺏ ﺗﻐﻁﻳﺔ ﻣﺩﺧﻝ ﺍﻟﻬﻭﺍء ﺑﺎﻷﺳﻼﻙ‪.‬‬
‫ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫ﺍﺳﺗﺧﺩﻡ ‪ 7‬ﺃﺳﻧﺎﻥ ﻟﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻻﺳﺗﻘﺑﺎﻝ‪.‬‬
‫ﺃﻭﻻ‪ ،‬ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﻛﺑﻝ ﻭﺣﺩﺓ ﺍﻻﺳﺗﻘﺑﺎﻝ ﻓﻲ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ ﺍﻟﺧﺎﺻﺔ ﺑﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‪.‬‬
‫ﻗﻡ ﺑﺗﻭﺻﻳﻝ ﺍﻟﻘﻠﺏ ﺍﻟﻣﻭﺟﻭﺩ ﺑﻳﻥ ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻭﺍﻟﻣﺷﺑﻙ‪.‬‬
‫ﺍﺳﺗﺧﺩﻡ ﻓﺗﺣﺔ ﻣﺧﺭﻭﻁﻳﺔ ﻋﻧﺩ ﺍﺳﺗﺧﺩﺍﻡ ﻛﺑﻝ ﺇﺧﺭﺍﺝ ﺧﺎﺭﺟﻲ‪.‬‬
‫*‪‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺣﻣﺎﻳﺔ ﻋﺯﻝ ﺍﻟﻛﺑﻝ ﺑﻌﺩ ﻋﻣﻝ ﻓﺗﺣﺔ ﻣﺛﻘﻭﺑﺔ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﻲ ﻣﻥ ﺣﺎﻓﺔ ﺍﻟﻔﺗﺣﺔ‪.‬‬
‫ﺗﺟﻧﺏ ﻣﻼﻣﺳﺔ ﺍﻟﺳﻘﻑ ﺑﺎﻷﺳﻼﻙ‪.‬‬
‫ﺍﻟﺳﻘﻑ‬
‫ﻻ ﺗﻘﻡ ﺑﺭﺑﻁ ﻛﺑﻝ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻭﺍﻟﻛﺑﻼﺕ ﺍﻷﺧﺭﻯ ﻣﻌًﺎ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻟﺣﻣﺎﻳﺔ ﻋﺯﻝ ﺍﻟﻛﺑﻝ ﺑﻌﺩ ﻋﻣﻝ ﻓﺗﺣﺔ ﻣﺛﻘﻭﺑﺔ‪ ،‬ﻗﻡ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻭﺍﺋﻲ ﻣﻥ ﺣﺎﻓﺔ ﺍﻟﻔﺗﺣﺔ‪.‬‬
‫‪ .8.6‬ﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ )ﺃﺟﺯﺍء ﺍﺧﺗﻳﺎﺭﻳﺔ(‬
‫ﻁﺭﻳﻘﺔ ﺍﻟﺗﻭﺻﻳﻝ‬
‫• ﺃﻁﺭﺍﻑ ﺍﻟﺗﻭﺻﻳﻝ‬
‫ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻁﺭﻑ ﺷﺑﻛﺔ ﻓﺗﺣﺔ‬
‫ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ‬
‫)‪(CN12‬‬
‫‪Ar-14‬‬
‫‪2017/8/8 13:08:55‬‬
‫‪9381858019-02_IM_AR.indd Sec1:14‬‬
‫‪A Table‬‬
‫‪ .7‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺟﺎﻝ‬
‫ﺍﻟﻌﻧﻭﺍﻥ‬
‫ﺛﻣﺔ ‪ 3‬ﻁﺭﻕ ﻹﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ﻣﻥ ﺧﻼﻝ ﺇﻋﺩﺍﺩ ﺍﻟﻣﺟﺎﻝ ﻛﺎﻟﺗﺎﻟﻲ‪.‬‬
‫ﻗﻡ ﺑﺎﻹﻋﺩﺍﺩ ﺑﻭﺍﺳﻁﺔ ﺃﻱ ﻣﻥ ﺍﻟﻁﺭﻕ‪.‬‬
‫ﻳﺗﻡ ﺗﻭﺿﻳﺢ ﻛﻝ ﻁﺭﻳﻘﺔ ﺇﻋﺩﺍﺩ ﻓﻲ )‪ (1‬ﺇﻟﻰ )‪ (3‬ﺃﺩﻧﺎﻩ‪.‬‬
‫)‪ (1‬ﺇﻋﺩﺍﺩﺍﺕ ‪ ........ SW AD REF ،AD IU‬ﻫﺫﻩ ﺍﻟﻘﺳﻡ )‪ .1.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ(‬
‫)‪ (2‬ﺇﻋﺩﺍﺩﺍﺕ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ‪ ..................‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ ﻭﺍﻟﻼﺳﻠﻛﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻣﻌﻠﻭﻣﺎﺕ‬
‫ﺍﻹﻋﺩﺍﺩ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ‪) .‬ﺇﻋﺩﺍﺩ ‪ SW AD REF ،AD IU‬ﻋﻠﻰ ‪(0‬‬
‫)‪ (3‬ﺇﻋﺩﺍﺩﺍﺕ ﺍﻟﻌﻧﻭﺍﻥ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ ‪ ........................‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻣﻌﻠﻭﻣﺎﺕ ﺍﻹﻋﺩﺍﺩ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ‪.‬‬
‫)ﺇﻋﺩﺍﺩ ‪ SW AD REF ،AD IU‬ﻋﻠﻰ ‪(0‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ ﻗﺑﻝ ﺗﻧﻔﻳﺫ ﺇﻋﺩﺍﺩ ﺍﻟﻣﺟﺎﻝ‪.‬‬
‫‪ .1.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ‬
‫ﻁﺭﻳﻘﺔ ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ﺍﻟﻳﺩﻭﻳﺔ‬
‫• ﻓﻲ ﺣﺎﻟﺔ ﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ‪ ،‬ﻳﻣﻛﻥ ﺃﻳﺿًﺎ ﺇﻋﺩﺍﺩ ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻋﻧﻭﺍﻥ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ ﻋﻥ ﻁﺭﻳﻕ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ‬
‫ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪.‬‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺍﺳﺗﺧﺩﻡ ﻣﻔﻙ ﻣﻌﺯﻭﻝ ﻹﻋﺩﺍﺩ ﻣﻔﺎﺗﻳﺢ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ‪.‬‬
‫ﻣﺛﺎﻝ ﺍﻟﻣﻔﺗﺎﺡ‬
‫ﺍﻟﺩﻭﺍﺭ‪"0" :‬‬
‫ﺍﻟﻌﻧﻭﺍﻥ‬
‫‪REF AD SW‬‬
‫ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﻣﺛﺎﻝ ﺍﻟﻣﻔﺗﺎﺡ‬
‫ﺍﻟﺩﻭﺍﺭ‪"0" :‬‬
‫ﺇﻋﺩﺍﺩ ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ‬
‫× ‪10‬‬
‫ﺇﻋﺩﺍﺩ ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ‬
‫‪IU AD SW‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫×‪1‬‬
‫×‪1‬‬
‫× ‪10‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪1‬‬
‫‪0‬‬
‫‪1‬‬
‫‪1‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪0‬‬
‫‪2‬‬
‫‪2‬‬
‫‪0‬‬
‫‪2‬‬
‫‪3‬‬
‫‪0‬‬
‫‪3‬‬
‫‪3‬‬
‫‪0‬‬
‫‪3‬‬
‫‪4‬‬
‫‪0‬‬
‫‪4‬‬
‫‪4‬‬
‫‪0‬‬
‫‪4‬‬
‫‪5‬‬
‫‪0‬‬
‫‪5‬‬
‫‪5‬‬
‫‪0‬‬
‫‪5‬‬
‫‪6‬‬
‫‪0‬‬
‫‪6‬‬
‫‪6‬‬
‫‪0‬‬
‫‪6‬‬
‫‪7‬‬
‫‪0‬‬
‫‪7‬‬
‫‪7‬‬
‫‪0‬‬
‫‪7‬‬
‫‪8‬‬
‫‪0‬‬
‫‪8‬‬
‫‪8‬‬
‫‪0‬‬
‫‪8‬‬
‫‪9‬‬
‫‪0‬‬
‫‪9‬‬
‫‪9‬‬
‫‪0‬‬
‫‪9‬‬
‫‪10‬‬
‫‪1‬‬
‫‪0‬‬
‫‪10‬‬
‫‪1‬‬
‫‪0‬‬
‫‪11‬‬
‫‪1‬‬
‫‪1‬‬
‫‪11‬‬
‫‪1‬‬
‫‪1‬‬
‫‪12‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪99‬‬
‫‪1‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪9‬‬
‫‪2‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪9‬‬
‫‪12‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪63‬‬
‫‪1‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪6‬‬
‫‪2‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪3‬‬
‫ﻻ ﺗﻘﻡ ﺑﺈﻋﺩﺍﺩ ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ )‪ (IU AD SW‬ﻋﻠﻰ ‪ 64‬ﺇﻟﻰ ‪.99‬‬
‫ﻓﻘﺩ ﻳﺅﺩﻱ ﺇﻟﻰ ﺍﻟﺗﻌﻁﻝ‪.‬‬
‫)‪ (3‬ﻋﻧﻭﺍﻥ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫‪ (i‬ﺍﻟﻧﻭﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(RC AD SW‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﻋﺩﺓ ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ ﺑـ ‪ 1‬ﻭﺣﺩﺓ ﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺳﻠﻛﻳﺔ‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ﻓﻲ ‪ RC AD SW‬ﺿﻣﻥ ﺗﺳﻠﺳﻝ ﻣﻥ ‪.0‬‬
‫ﺍﻹﻋﺩﺍﺩ‬
‫ﻧﻁﺎﻕ ﺍﻹﻋﺩﺍﺩ‬
‫ﻋﻧﻭﺍﻥ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻹﻋﺩﺍﺩ‬
‫ﻧﻁﺎﻕ ﺍﻹﻋﺩﺍﺩ‬
‫ﻧﻭﻉ ﺍﻟﻣﻔﺗﺎﺡ‬
‫ﻣﺛﺎﻝ ﺍﻹﻋﺩﺍﺩ‬
‫‪0‬‬
‫‪ 0‬ﺇﻟﻰ ‪15‬‬
‫ﻧﻭﻉ ﺍﻟﻣﻔﺗﺎﺡ‬
‫‪RC AD‬‬
‫ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫‪ 0‬ﺇﻟﻰ ‪63‬‬
‫ﻣﺛﺎﻝ ﺍﻹﻋﺩﺍﺩ‬
‫‪2‬‬
‫ﻋﻧﻭﺍﻥ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‬
‫‪ 0‬ﺇﻟﻰ ‪99‬‬
‫ﻣﺛﺎﻝ ﺍﻹﻋﺩﺍﺩ‬
‫‪63‬‬
‫ﻣﺛﺎﻝ‬
‫‪IU AD × 10‬‬
‫‪IU AD × 1‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﻭﺻﻳﻝ ‪ 4‬ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ‪.‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫‪RC AD SW‬‬
‫‪3‬‬
‫‪REF AD × 10‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫‪RC AD SW‬‬
‫‪2‬‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫‪RC AD SW‬‬
‫‪0‬‬
‫‪RC AD SW‬‬
‫‪1‬‬
‫‪REF AD × 1‬‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ‬
‫)‪ (1‬ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(IU AD × 1‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(IU AD × 10‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﻋﻧﺩ ﺗﻭﺻﻳﻝ ﻋﺩﺓ ﻭﺣﺩﺍﺕ ﺩﺍﺧﻠﻳﺔ ﺑﻧﻅﺎﻡ ﺗﺑﺭﻳﺩ ‪ 1‬ﻭﺣﺩ‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ﻓﻲ ‪ IU AD SW‬ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ‪.A Table‬‬
‫)‪ (2‬ﻋﻧﻭﺍﻥ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(REF AD × 1‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(REF AD × 10‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺗﺧﺩﺍﻡ ﻋﺩﺓ ﺃﻧﻅﻣﺔ ﺗﺑﺭﻳﺩ‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ‪ REF AD SW‬ﻛﻣﺎ ﻫﻭ ﻣﻭﺿﺢ ﻓﻲ ‪ A Table‬ﻟﻛﻝ ﻧﻅﺎﻡ ﺗﺑﺭﻳﺩ‪.‬‬
‫ﻗﻡ ﺑﺎﻹﻋﺩﺍﺩ ﻋﻠﻰ ﻧﻔﺱ ﻋﻧﻭﺍﻥ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ ﻣﺛﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ‪.‬‬
‫• ﻓﻲ ﺍﻟﺣﺎﻟﺔ ﺍﻟﻌﻣﻝ ﻓﻲ ﺑﻳﺋﺔ ﻳﻣﻛﻥ ﻓﻳﻬﺎ ﺍﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪ ،‬ﻳﻣﻛﻥ ﺃﻳﺿًﺎ ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﺎﻭﻳﻥ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫• ﻓﻲ ﺣﺎﻟﺔ ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻋﻧﻭﺍﻥ ﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‬
‫ﻋﻠﻰ "‪."00‬‬
‫‪RC AD SW‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫ﺍﻟﻌﻧﻭﺍﻥ‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫‪RC AD SW‬‬
‫‪8‬‬
‫‪9‬‬
‫‪A‬‬
‫‪B‬‬
‫‪C‬‬
‫‪D‬‬
‫‪E‬‬
‫‪F‬‬
‫ﺍﻟﻌﻧﻭﺍﻥ‬
‫‪8‬‬
‫‪9‬‬
‫‪10‬‬
‫‪11‬‬
‫‪12‬‬
‫‪13‬‬
‫‪14‬‬
‫‪15‬‬
‫‪ (ii‬ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫ﺍﻟﻣﻔﺗﺎﺡ ﺍﻟﺩﻭﺍﺭ )‪...(RC AD SW‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ "‪"0‬‬
‫ﻧﻅﺭً ﺍ ﻷﻧﻪ ﻳﺗﻡ ﺗﻛﻭﻳﻥ ﺇﻋﺩﺍﺩﺍﺕ ﻋﻧﻭﺍﻥ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺗﻠﻘﺎﺋﻳًﺎ‪ ،‬ﻓﻼ ﻳﻠﺯﻣﻙ ﺗﻛﻭﻳﻧﻬﺎ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺍﻟﺗﻛﻭﻳﻥ ﺍﻟﻳﺩﻭﻱ‪ ،‬ﻣﻥ ﺍﻟﺿﺭﻭﺭﻱ ﺗﻛﻭﻳﻥ ﻛﻼ ﻣﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫ﻟﻣﻌﺭﻓﺔ ﺍﻟﺗﻔﺎﺻﻳﻝ‪ ،‬ﻳﺭﺟﻰ ﻣﺭﺍﺟﻌﺔ ﺩﻟﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫)ﻟﻣﺯﻳﺩ ﻣﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ ﺣﻭﻝ ﺍﻹﻋﺩﺍﺩ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪(.‬‬
‫‪Ar-15‬‬
‫‪2017/8/8 13:08:55‬‬
‫‪9381858019-02_IM_AR.indd Sec1:15‬‬
‫‪ .2.7‬ﺇﻋﺩﺍﺩ ﺭﻣﺯ ﻣﺧﺻﺹ‬
‫‪ .4.7‬ﺗﺑﺩﻳﻝ ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء‬
‫ﻳﺅﺩﻱ ﺍﺧﺗﻳﺎﺭ ﺭﻣﺯ ﻣﺧﺻﺹ ﺇﻟﻰ ﻣﻧﻊ ﺍﻟﺧﻠﻁ ﺑﻳﻥ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ‪.‬‬
‫)ﻳﻣﻛﻧﻙ ﺇﻋﺩﺍﺩ ﺣﺗﻰ ‪ 4‬ﺭﻣﻭﺯ‪(.‬‬
‫ﻗﻡ ﺑﺗﻧﻔﻳﺫ ﺍﻹﻋﺩﺍﺩ ﻟﻛﻝ ﻣﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫ﻋﻧﺩ ﺗﺭﻛﻳﺏ ﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ )ﺍﻷﺟﺯﺍء ﺍﻻﺧﺗﻳﺎﺭﻳﺔ(‪ ،‬ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﻋﻠﻰ "‪) "Valid‬ﺻﺎﻟﺢ(‪.‬‬
‫ﻳﻣﻛﻥ ﺗﺷﻐﻳﻝ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﻓﻲ ﺷﺑﻛﺔ ﻓﺗﺣﺔ ﺍﻟﺗﻬﻭﻳﺔ ﺍﻟﺗﻠﻘﺎﺋﻳﺔ ﺑﻭﺍﺳﻁﺔ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺣﻳﻧﻣﺎ ﺗﻛﻭﻥ ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ‬
‫ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﺻﺎﻟﺣﺔ‪.‬‬
‫• ﻁﺭﻳﻘﺔ ﺍﻟﺗﺭﻛﻳﺏ‬
‫ﺗﻐﻳﻳﺭ ﺍﻟﺭﻣﺯ‬
‫‪D‬‬
‫‪D‬‬
‫‪B‬‬
‫‪C‬‬
‫‪B‬‬
‫‪C‬‬
‫ﺍﻟﺗﺑﺎﺱ‬
‫‪A‬‬
‫ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ ‪ SET 4 SW2‬ﻭ‪ SW2‬ﻣﻥ ﺧﻼﻝ ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ‪.D Table‬‬
‫ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ‬
‫‪A‬‬
‫ﺇﻋﺩﺍﺩ ﺭﻣﺯ ﻣﺧﺻﺹ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻗﻡ ﺑﺈﻋﺩﺍﺩ ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ ‪ SET 3 SW1‬ﻭ‪ SW2‬ﻣﻥ ﺧﻼﻝ ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ‪.B Table‬‬
‫ﺗﺷﻐﻳﻝ‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ "‪"SET 4‬‬
‫ﺇﻳﻘﺎﻑ‬
‫‪SW SW SW SW‬‬
‫‪4‬‬
‫‪3‬‬
‫‪2 1‬‬
‫‪D Table‬‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ‬
‫ﺍﻟﻣﺯﺩﻭﺟﺔ‬
‫‪SET 4 SW2‬‬
‫ﺗﺷﻐﻳﻝ‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ‬
‫"‪"SET 3‬‬
‫ﺇﻳﻘﺎﻑ‬
‫ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء "‪) "Invalid‬ﻏﻳﺭ ﺻﺎﻟﺢ(‬
‫)ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ(‬
‫ﺗﺷﻐﻳﻝ‬
‫ﻭﻅﻳﻔﺔ ﻓﺗﺣﺔ ﺍﺗﺟﺎﻩ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء "‪) "Valid‬ﺻﺎﻟﺢ(‬
‫ﺇﻳﻘﺎﻑ‬
‫‪SW SW SW SW‬‬
‫‪1‬‬
‫‪2 3‬‬
‫‪4‬‬
‫‪B Table‬‬
‫ﺍﻟﺭﻣﺯ ﺍﻟﻣﺧﺻﺹ‬
‫‪) A‬ﺇﻋﺩﺍﺩ ﺍﻟﻣﺻﻧﻊ(‬
‫‪B‬‬
‫‪C‬‬
‫‪D‬‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ ‪SET3‬‬
‫‪SW1‬‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﻣﻔﺗﺎﺡ ﺍﻟﻣﺑﺩﻟﺔ ﺍﻟﻣﺯﺩﻭﺟﺔ ‪SET3‬‬
‫‪SW2‬‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺷﻐﻳﻝ‬
‫ﺗﺷﻐﻳﻝ‬
‫‪ .3.7‬ﻭﺿﻊ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ‬
‫ﺗﻧﺑﻳﻪ‬
‫ﺇﺫﺍ ﻟﻡ ﻳﺗﻁﺎﺑﻕ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﺍﻟﻣﻁﺑﻕ ﻣﻊ ﻭﺿﻊ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ‪ ،‬ﻋﻧﺩﺋﺫ ﻳﻣﻛﻥ ﺗﻐﻳﻳﺭ ﻭﺿﻊ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﺇﻟﻰ ﻭﺿﻊ ﺁﺧﺭ ﻳﺩﻭﻳًﺎ‪.‬‬
‫ﺍﻟﻧﻁﺎﻕ ﺍﻟﻣﻭﺻﻰ ﺑﻪ ﻟﻠﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﺍﻟﺧﺎﺭﺟﻲ‬
‫‪ 0 :AR07/09/12‬ﺇﻟﻰ ‪ 30‬ﺑﺎﺳﻛﺎﻝ‬
‫‪ 0 :AR14/18/24‬ﺇﻟﻰ ‪ 50‬ﺑﺎﺳﻛﺎﻝ‬
‫ﻣﻥ ﺍﻟﺿﺭﻭﺭﻱ ﺇﻋﺩﺍﺩ ﻭﺿﻊ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﻟﻛﻝ ﺍﺳﺗﺧﺩﺍﻡ ﻟﻠﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ‪.‬‬
‫ﻳﻣﻛﻥ ﺇﻋﺩﺍﺩ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﻓﻲ ﺍﻟﻣﻭﻗﻊ‪.‬‬
‫ﻳﺗﻡ ﺗﻭﺿﻳﺢ ﺍﻟﻌﻼﻗﺔ ﺑﻳﻥ ﻗﻳﻡ ﺍﻟﺿﺑﻁ ﻭﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺍﻟﺗﺎﻟﻲ‪.‬‬
‫• ﻳﻣﻛﻥ ﺗﻧﻔﻳﺫ ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ ﻭﺍﻟﻼﺳﻠﻛﻳﺔ‪.‬‬
‫)ﺗﻌﺗﺑﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻥ ﺍﻷﺟﻬﺯﺓ ﺍﻻﺧﺗﻳﺎﺭﻳﺔ(‬
‫• ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ ﻭﺍﻟﻼﺳﻠﻛﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻣﻌﻠﻭﻣﺎﺕ ﺍﻹﻋﺩﺍﺩ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ‪.‬‬
‫ﺭﻗﻡ ﺍﻟﻭﻅﻳﻔﺔ‬
‫‪26‬‬
‫ﺭﻗﻡ ﺍﻹﻋﺩﺍﺩ‬
‫ﺇﻋﺩﺍﺩ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ‬
‫‪00‬‬
‫‪ 0‬ﺑﺎﺳﻛﺎﻝ‬
‫‪01‬‬
‫‪ 10‬ﺑﺎﺳﻛﺎﻝ‬
‫‪02‬‬
‫‪ 20‬ﺑﺎﺳﻛﺎﻝ‬
‫‪03‬‬
‫‪ 30‬ﺑﺎﺳﻛﺎﻝ‬
‫‪04‬‬
‫‪ 40‬ﺑﺎﺳﻛﺎﻝ‬
‫‪05‬‬
‫‪ 50‬ﺑﺎﺳﻛﺎﻝ‬
‫‪31‬‬
‫‪ 10 : AR07/09/12‬ﺑﺎﺳﻛﺎﻝ‬
‫‪ 15 : AR14/18/24‬ﺑﺎﺳﻛﺎﻝ‬
‫ﻳﺻﺑﺢ ﺇﻋﺩﺍﺩ ﺍﻟﺿﻐﻁ ﺍﻟﺛﺎﺑﺕ "‪ 30‬ﺑﺎﺳﻛﺎﻝ" ﺇﺫﺍ ﺗﻡ ﺇﻋﺩﺍﺩ ‪ AR07/09/12‬ﻋﻠﻰ "‪ "04‬ﺣﺗﻰ "‪."05‬‬
‫‪Ar-16‬‬
‫‪2017/8/8 13:08:55‬‬
‫‪9381858019-02_IM_AR.indd Sec1:16‬‬
‫‪ .5.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫‪ .8‬ﺍﻟﺗﺷﻐﻳﻝ ﺍﻻﺧﺗﺑﺎﺭﻱ‬
‫ﻳﻣﻛﻥ ﺗﻧﻔﻳﺫ ﺇﻋﺩﺍﺩ ﺍﻟﻭﻅﻳﻔﺔ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ ﻭﺍﻟﻼﺳﻠﻛﻳﺔ‪.‬‬
‫)ﺗﻌﺗﺑﺭ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻥ ﺍﻷﺟﻬﺯﺓ ﺍﻻﺧﺗﻳﺎﺭﻳﺔ(‬
‫ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ ﻭﺍﻟﻼﺳﻠﻛﻳﺔ ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﻣﻌﻠﻭﻣﺎﺕ ﺍﻹﻋﺩﺍﺩ ﺍﻟﺗﻔﺻﻳﻠﻳﺔ‪.‬‬
‫ﺭﺍﺟﻊ "‪ .1.7‬ﺇﻋﺩﺍﺩ ﺍﻟﻌﻧﻭﺍﻥ" ﻟﻠﺗﻌﺭﻑ ﻋﻠﻰ ﺇﻋﺩﺍﺩﺍﺕ ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻭﺩﺍﺋﺭﺓ ﺍﻟﺗﺑﺭﻳﺩ‪.‬‬
‫ﻗﻡ ﺑﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻗﺑﻝ ﺑﺩء ﺍﻹﻋﺩﺍﺩ‪.‬‬
‫* ﻳﺗﻡ ﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ ﻓﻲ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺗﻲ ﺗﻘﻭﻡ ﺑﺗﻬﻳﺋﺔ ‪ ،EEV‬ﻟﺫﺍ ﺗﺄﻛﺩ ﻣﻥ ﺇﺟﺭﺍء ﺍﺧﺗﺑﺎﺭ ﻣﻧﻊ ﺗﺳﺭﻳﺏ ﺍﻟﻬﻭﺍء ﻋﻠﻰ ﺍﻟﻣﻭﺍﺳﻳﺭ‬
‫ﻭﺍﻟﺗﻔﺭﻳﻎ ﻗﺑﻝ ﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ‪.‬‬
‫* ﺃﻳﺿًﺎ ﺃﻓﺣﺹ ﻣﺭﺓ ﺃﺧﺭﻯ ﻟﻠﺗﺄﻛﺩ ﻣﻥ ﻋﺩﻡ ﺍﺭﺗﻛﺎﺏ ﺧﻁﺄ ﻓﻲ ﺗﻭﺻﻳﻼﺕ ﺍﻷﺳﻼﻙ ﻗﺑﻝ ﺗﺷﻐﻳﻝ ﺍﻟﻁﺎﻗﺔ‪.‬‬
‫‪ .1.8‬ﺗﺷﻐﻳﻝ ﺍﺧﺗﺑﺎﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ )ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ(‬
‫• ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺗﺧﺩﺍﻡ ﻟﻭﺣﺔ ﺍﻟﻛﻣﺑﻳﻭﺗﺭ ﻟﻠﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ ﻓﻲ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻻﺧﺗﺑﺎﺭﻱ‪.‬‬
‫‪ .2.8‬ﺗﺷﻐﻳﻝ ﺍﺧﺗﺑﺎﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫• ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺍﻟﺗﺭﻛﻳﺏ ﻟﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻥ ﺃﺟﻝ ﺗﻧﻔﻳﺫ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻻﺧﺗﺑﺎﺭﻱ ﺑﺎﺳﺗﺧﺩﺍﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻼﺳﻠﻛﻳﺔ‪.‬‬
‫• ﻋﻧﺩ ﺇﺟﺭﺍء ﺗﺷﻐﻳﻝ ﺍﺧﺗﺑﺎﺭ ﻟﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء‪ ،‬ﺗﻭﻣﺽ ﻣﺅﺷﺭﺍﺕ ‪) OPERATION‬ﺗﺷﻐﻳﻝ( ﻭ‪) TIMER‬ﺍﻟﻣﺅﻗﺕ( ﺑﺑﻁء ﻓﻲ ﻧﻔﺱ‬
‫ﺍﻟﻭﻗﺕ‪.‬‬
‫ﺗﻔﺎﺻﻳﻝ ﺍﻟﻭﻅﻳﻔﺔ‬
‫ﺭﻗﻡ ﺍﻹﻋﺩﺍﺩ‬
‫ﺍﻟﻭﻅﻳﻔﺔ‬
‫ﺭﻗﻡ ﺍﻟﻭﻅﻳﻔﺔ‬
‫ﻓﺎﺻﻝ ﻣﺅﺷﺭ ﺍﻟﻣﺭﺷﺢ‬
‫‪11‬‬
‫ﺗﺷﻐﻳﻝ ﻣﺅﺷﺭ‬
‫ﺍﻟﻣﺭﺷﺢ‬
‫‪13‬‬
‫ﺍﻁﻼﻕ ﺣﺭﺍﺭﺓ ﺍﻟﻬﻭﺍء‬
‫ﺍﻟﺑﺎﺭﺩ‬
‫‪30‬‬
‫ﺍﻁﻼﻕ ﺣﺭﺍﺭﺓ ﺍﻟﻬﻭﺍء‬
‫ﺍﻟﺳﺎﺧﻥ‬
‫‪31‬‬
‫ﺇﻋﺎﺩﺓ ﺍﻟﺗﺷﻐﻳﻝ‬
‫ﺍﻟﺗﻠﻘﺎﺋﻲ‬
‫‪40‬‬
‫ﻣﻧﻊ ﺍﻟﻬﻭﺍء‬
‫ﺍﻟﺑﺎﺭﺩ‬
‫‪43‬‬
‫ﺗﺣﻛﻡ‬
‫ﺧﺎﺭﺟﻲ‬
‫‪46‬‬
‫ﻫﺩﻑ ﺗﻘﺭﻳﺭ ﺍﻟﺧﻁﺄ‬
‫‪47‬‬
‫ﺇﻋﺩﺍﺩ ﺍﻟﻣﺭﻭﺣﺔ ﻋﻧﺩ‬
‫ﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ ﺍﻟﺗﺑﺭﻳﺩ‬
‫ﺑﻭﺍﺳﻁﺔ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ‪.‬‬
‫‪49‬‬
‫)ﻣﺣﻅﻭﺭ(‬
‫‪60‬‬
‫‪00‬‬
‫)ﻣﺣﻅﻭﺭ(‬
‫‪61‬‬
‫‪00‬‬
‫)ﻣﺣﻅﻭﺭ(‬
‫‪62‬‬
‫‪00‬‬
‫‪ 00‬ﻗﻳﺎﺳﻲ‬
‫ﺍﻻﻓﺗﺭﺍﺿﻲ‬
‫○‬
‫‪ 01‬ﻁﻭﻳﻝ‬
‫‪ 02‬ﻗﺻﻳﺭ‬
‫‪ 00‬ﺗﻣﻛﻳﻥ‬
‫‪ 00‬ﻗﻳﺎﺳﻲ‬
‫○‬
‫‪ 02‬ﺿﺑﻁ )‪(2‬‬
‫○‬
‫‪ 01‬ﺿﺑﻁ )‪(1‬‬
‫‪ 02‬ﺿﺑﻁ )‪(2‬‬
‫‪ 03‬ﺿﺑﻁ )‪(3‬‬
‫‪ 00‬ﺗﻣﻛﻳﻥ‬
‫‪ 01‬ﺗﻌﻁﻳﻝ‬
‫○‬
‫‪ 00‬ﻣﻧﺧﻔﺽ ﻟﻠﻐﺎﻳﺔ‬
‫○‬
‫ﺍﺗﺑﺎﻉ ﺍﻹﻋﺩﺍﺩ‬
‫‪ 01‬ﻋﻠﻰ ﻭﺣﺩﺓ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫‪ 00‬ﺑﺩء‪/‬ﺇﻳﻘﺎﻑ‬
‫○‬
‫‪ 01‬ﺇﻳﻘﺎﻑ ﺍﻟﻁﻭﺍﺭﺉ‬
‫ﺍﻹﻳﻘﺎﻑ‬
‫‪02‬‬
‫ﺍﻹﺟﺑﺎﺭﻱ‬
‫‪ 00‬ﺍﻟﻛﻝ‬
‫ﻋﺭﺽ ﻓﻲ ﻭﺣﺩﺓ‬
‫‪ 01‬ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻟﻣﺭﻛﺯﻳﺔ ﻓﻘﻁ‬
‫ﺍﺗﺑﺎﻉ ﺍﻹﻋﺩﺍﺩ‬
‫‪ 00‬ﻋﻠﻰ ﻭﺣﺩﺓ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫○‬
‫○‬
‫‪ 01‬ﺇﻳﻘﺎﻑ‬
‫○‬
‫○‬
‫○‬
‫‪ .9‬ﻗﺎﺋﻣﺔ ﺍﻟﻔﺣﺹ‬
‫ﺍﻧﺗﺑﻪ ﻋﻠﻰ ﻭﺟﻪ ﺍﻟﺧﺻﻭﺹ ﺇﻟﻰ ﻋﻧﺎﺻﺭ ﺍﻟﻔﺣﺹ ﺍﻟﺗﺎﻟﻳﺔ ﻋﻧﺩ ﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ )ﻭﺣﺩﺍﺕ( ﺍﻟﺩﺍﺧﻠﻳﺔ‪ .‬ﺑﻌﺩ ﺍﺳﺗﻛﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﺗﺄﻛﺩ ﻣﻥ‬
‫ﻓﺣﺹ ﺍﻟﻌﻧﺎﺻﺭ ﺍﻟﺗﺎﻟﻳﺔ ﻣﺭﺓ ﺃﺧﺭﻯ‪.‬‬
‫ﻋﻧﺎﺻﺭ ﺍﻟﻔﺣﺹ‬
‫ﺗﻣﻛﻳﻥ ﻣﺅﺷﺭ ﺍﻟﻣﺭﺷﺢ‪ .‬ﺍﻹﻋﺩﺍﺩ ‪ 02‬ﻟﻼﺳﺗﺧﺩﺍﻡ ﻣﻊ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﻣﺭﻛﺯﻳﺔ‪.‬‬
‫‪ 01‬ﺿﺑﻁ )‪(1‬‬
‫‪ 00‬ﻗﻳﺎﺳﻲ‬
‫ﺿﺑﻁ ﺇﺧﻁﺎﺭ ﻓﺎﺻﻝ ﺗﻧﻅﻳﻑ ﺍﻟﻣﺭﺷﺢ‪ .‬ﺇﺫﺍ ﻛﺎﻥ‬
‫ﺍﻹﺧﻁﺎﺭ ﻣﺑﻛﺭً ﺍ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﻗﻡ ﺑﺎﻟﺗﻐﻳﻳﺭ ﺇﻟﻰ ﺍﻹﻋﺩﺍﺩ ‪.01‬‬
‫ﺇﺫﺍ ﻛﺎﻥ ﺍﻹﺧﻁﺎﺭ ﻣﺗﺄﺧﺭً ﺍ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﻗﻡ ﺑﺎﻟﺗﻐﻳﻳﺭ ﺇﻟﻰ‬
‫ﺍﻹﻋﺩﺍﺩ ‪.02‬‬
‫○‬
‫‪ 01‬ﺗﻌﻁﻳﻝ‬
‫ﻋﺭﺽ ﻓﻲ‬
‫ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫‪02‬‬
‫ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻟﻣﺭﻛﺯﻳﺔ ﻓﻘﻁ‬
‫ﺍﻟﺗﻔﺎﺻﻳﻝ‬
‫ﺿﺑﻁ ﺣﺭﺍﺭﺓ ﺇﻁﻼﻕ ﺍﻟﻬﻭﺍء ﺍﻟﺑﺎﺭﺩ‪ .‬ﻟﺗﻘﻠﻳﻝ ﺣﺭﺍﺭﺓ‬
‫ﺍﻹﻁﻼﻕ‪ ،‬ﺍﺳﺗﺧﺩﻡ ﺍﻹﻋﺩﺍﺩ ‪ .01‬ﻟﺭﻓﻊ ﺣﺭﺍﺭﺓ ﺍﻹﻁﻼﻕ‪،‬‬
‫ﺍﺳﺗﺧﺩﻡ ﺍﻹﻋﺩﺍﺩ ‪.02‬‬
‫ﺿﺑﻁ ﺣﺭﺍﺭﺓ ﺇﻁﻼﻕ ﺍﻟﻬﻭﺍء ﺍﻟﺳﺎﺧﻥ‪ .‬ﻟﺗﻘﻠﻳﻝ ﺣﺭﺍﺭﺓ‬
‫ﺍﻹﻁﻼﻕ ﺑﻣﻘﺩﺍﺭ ‪ 6‬ﺩﺭﺟﺎﺕ ﻣﺋﻭﻳﺔ‪ ،‬ﺍﺳﺗﺧﺩﻡ ﺍﻹﻋﺩﺍﺩ‬
‫‪ .01‬ﻟﺗﻘﻠﻳﻝ ﺣﺭﺍﺭﺓ ﺍﻹﻁﻼﻕ ﺑﻣﻘﺩﺍﺭ ‪ 4‬ﺩﺭﺟﺎﺕ ﻣﺋﻭﻳﺔ‪،‬‬
‫ﺍﺳﺗﺧﺩﻡ ﺍﻹﻋﺩﺍﺩ ‪ .02‬ﻟﺭﻓﻊ ﺣﺭﺍﺭﺓ ﺍﻹﻁﻼﻕ‪ ،‬ﺍﺳﺗﺧﺩﻡ‬
‫ﺍﻹﻋﺩﺍﺩ ‪.03‬‬
‫ﺗﻣﻛﻳﻥ ﺃﻭ ﺗﻌﻁﻳﻝ ﺇﻋﺎﺩﺓ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﻠﻘﺎﺋﻲ ﻟﻠﻧﻅﺎﻡ ﺑﻌﺩ‬
‫ﺍﻧﻘﻁﺎﻉ ﺍﻟﻁﺎﻗﺔ‪.‬‬
‫* ﺗﻌﺗﺑﺭ ﺇﻋﺎﺩﺓ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺗﻠﻘﺎﺋﻲ ﻭﻅﻳﻔﺔ ﻁﺎﺋﺭﺓ ﻣﺛﻝ‬
‫ﺍﻻﺳﺗﺧﺩﺍﻡ ﻓﻲ ﺣﺎﻟﺔ ﺍﻧﻘﻁﺎﻉ ﺍﻟﻁﺎﻗﺔ ﻭﻏﻳﺭﻩ‪.‬‬
‫ﻻ ﺗﻘﻡ ﺑﺗﺷﻐﻳﻝ ﻭﺇﻳﻘﺎﻑ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﻭﺍﺳﻁﺔ ﻫﺫﻩ‬
‫ﺍﻟﻭﻅﻳﻔﺔ ﻓﻲ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﻌﺎﺩﻱ‪.‬‬
‫ﺗﺄﻛﺩ ﻣﻥ ﺍﻟﺗﺷﻐﻳﻝ ﺑﻭﺍﺳﻁﺔ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﺃﻭ ﺍﻟﻣﺣﻭﻝ‬
‫ﺃﻭ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺧﺎﺭﺟﻲ‪.‬‬
‫ﺇﺫﺍ ﻟﻡ ﻳﺗﻡ ﺍﻟﺗﻧﻔﻳﺫ ﺑﺷﻛﻝ ﺻﺣﻳﺢ‬
‫ﻫﻝ ﺗﻡ ﺗﺭﻛﻳﺏ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺑﺷﻛﻝ ﺻﺣﻳﺢ؟‬
‫ﺍﻻﻫﺗﺯﺍﺯ‪ ،‬ﺍﻟﺿﻭﺿﺎء‪ ،‬ﺍﺣﺗﻣﺎﻝ ﺳﻘﻭﻁ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻫﻝ ﻛﺎﻥ ﻫﻧﺎﻙ ﻓﺣﺹ ﻟﺗﺳﺭﻳﺑﺎﺕ ﺍﻟﻐﺎﺯ )ﻣﻭﺍﺳﻳﺭ ﺳﺎﺋﻝ ﺍﻟﺗﺑﺭﻳﺩ(؟‬
‫ﻋﺩﻡ ﻭﺟﻭﺩ ﺗﺑﺭﻳﺩ‪ ،‬ﺗﺩﻓﺋﺔ‬
‫ﻫﻝ ﺗﻡ ﺍﺳﺗﻛﻣﺎﻝ ﺃﻋﻣﺎﻝ ﺍﻟﻌﺯﻝ ﺍﻟﺣﺭﺍﺭﻱ؟‬
‫ﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ‬
‫ﻫﻝ ﻳﺗﻡ ﺗﺻﺭﻳﻑ ﺍﻟﻣﻳﺎﻩ ﺑﺳﻬﻭﻟﺔ ﻣﻥ ﺍﻟﻭﺣﺩﺍﺕ ﺍﻟﺩﺍﺧﻠﻳﺔ؟‬
‫ﺗﺳﺭﻳﺏ ﺍﻟﻣﻳﺎﻩ‬
‫ﻫﻝ ﺟﻬﺩ ﻣﺻﺩﺭ ﺇﻣﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻫﻭ ﻧﻔﺳﻪ ﺍﻟﻣﺑﻳﻥ ﻋﻠﻰ ﻣﻠﺻﻕ‬
‫ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ؟‬
‫ﻋﺩﻡ ﺍﻟﺗﺷﻐﻳﻝ‪ ،‬ﺃﻭ ﻋﺩﻡ ﺍﻟﺗﺩﻓﺋﺔ ﺃﻭ ﺍﻟﺗﻠﻑ‬
‫ﺑﺳﺑﺏ ﺍﻻﺣﺗﺭﺍﻕ‬
‫ﻫﻝ ﺗﻡ ﺗﻭﺻﻳﻝ ﺍﻷﺳﻼﻙ ﻭﺍﻟﻣﻭﺍﺳﻳﺭ ﺟﻣﻳﻌًﺎ ﺑﺷﻛﻝ ﺻﺣﻳﺢ؟‬
‫ﻋﺩﻡ ﺍﻟﺗﺷﻐﻳﻝ‪ ،‬ﺃﻭ ﻋﺩﻡ ﺍﻟﺗﺩﻓﺋﺔ ﺃﻭ ﺍﻟﺗﻠﻑ‬
‫ﺑﺳﺑﺏ ﺍﻻﺣﺗﺭﺍﻕ‬
‫ﻫﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﻣﺗﺻﻠﺔ ﺑﺎﻷﺭﺽ )ﻣﺅﺭﺿﺔ(؟‬
‫ﺩﺍﺋﺭﺓ ﻗﺻﺭ‬
‫ﻫﻝ ﻛﺑﻝ ﺍﻟﺗﻭﺻﻳﻝ ﺑﺎﻟﺳﻣﺎﻛﺔ ﺍﻟﻣﺣﺩﺩﺓ؟‬
‫ﻋﺩﻡ ﺍﻟﺗﺷﻐﻳﻝ‪ ،‬ﺃﻭ ﻋﺩﻡ ﺍﻟﺗﺩﻓﺋﺔ ﺃﻭ ﺍﻟﺗﻠﻑ‬
‫ﺑﺳﺑﺏ ﺍﻻﺣﺗﺭﺍﻕ‬
‫ﻫﻝ ﺍﻟﻣﺩﺍﺧﻝ ﻭﺍﻟﻣﺧﺎﺭﺝ ﺧﺎﻟﻳﺔ ﻣﻥ ﺍﻟﻌﻭﺍﺋﻕ؟‬
‫ﻋﺩﻡ ﻭﺟﻭﺩ ﺗﺑﺭﻳﺩ‪ ،‬ﺗﺩﻓﺋﺔ‬
‫ﻫﻝ ﻳﺗﻡ ﺑﺩء ﻭﺇﻳﻘﺎﻑ ﺗﺷﻐﻳﻝ ﺗﻛﻳﻳﻑ ﺍﻟﻬﻭﺍء ﺑﻭﺍﺳﻁﺔ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ ﺃﻭ ﺟﻬﺎﺯ ﺧﺎﺭﺟﻲ؟‬
‫ﻻ ﻳﻭﺟﺩ ﺗﺷﻐﻳﻝ‬
‫ﺧﺎﻧﺔ‬
‫ﺍﻻﺧﺗﻳﺎﺭ‬
‫ﺑﻌﺩ ﺍﺳﺗﻛﻣﺎﻝ ﺍﻟﺗﺭﻛﻳﺏ‪ ،‬ﻫﻝ ﺗﻡ ﺗﻭﺿﻳﺢ ﺍﻟﺗﺷﻐﻳﻝ ﺍﻟﺻﺣﻳﺢ‬
‫ﻭﺍﻟﻣﻌﺎﻟﺟﺔ ﻟﻠﻌﻣﻳﻝ؟‬
‫ﻳﻣﻧﻊ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء ﺍﻟﺑﺎﺭﺩ ﻣﻊ ﺟﻌﻝ ﺗﺩﻓﻕ ﺍﻟﻬﻭﺍء‬
‫ﻣﻧﺧﻔﺿًﺎ ﻋﻧﺩ ﺑﺩء ﺗﺷﻐﻳﻝ ﺍﻟﺗﺩﻓﺋﺔ‪ .‬ﻟﻼﺳﺗﺟﺎﺑﺔ ﻟﻠﺗﻬﻭﻳﺔ‪،‬‬
‫ﻗﻡ ﺑﺎﻹﻋﺩﺍﺩ ﻋﻠﻰ ‪.01‬‬
‫ﺍﻟﺳﻣﺎﺡ ﻟﻭﺣﺩﺓ ﺗﺣﻛﻡ ﺧﺎﺭﺟﻳﺔ ﺑﺑﺩء ﺃﻭ ﺇﻳﻘﺎﻑ ﺍﻟﻧﻅﺎﻡ‪ ،‬ﺃﻭ‬
‫ﺗﻧﻔﻳﺫ ﺇﻳﻘﺎﻑ ﻁﻭﺍﺭﺉ‪.‬‬
‫* ﻓﻲ ﺣﺎﻟﺔ ﺗﻧﻔﻳﺫ ﺇﻳﻘﺎﻑ ﻁﻭﺍﺭﺉ ﻣﻥ ﻭﺣﺩﺓ ﺗﺣﻛﻡ‬
‫ﺧﺎﺭﺟﻳﺔ‪ ،‬ﺳﻭﻑ ﻳﺗﻡ ﺗﻌﻁﻳﻝ ﺟﻣﻳﻊ ﺃﻧﻅﻣﺔ ﺍﻟﺗﺑﺭﻳﺩ‪.‬‬
‫* ﺇﺫﺍ ﺗﻡ ﺇﻋﺩﺍﺩ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺑﺎﺭﻱ‪ ،‬ﺳﺗﺗﻭﻗﻑ ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ ﻣﻥ ﺧﻼﻝ ﺍﻹﺩﺧﺎﻝ ﺇﻟﻰ ﺃﻁﺭﺍﻑ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﺧﺎﺭﺟﻲ‪ ،‬ﻭﻳﺗﻡ ﺗﻘﻳﻳﺩ ﻭﻅﻳﻔﺔ ﺍﻟﺑﺩء ﺍﻹﻳﻘﺎﻑ ﻣﻥ ﻭﺣﺩﺓ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫ﺗﻐﻳﻳﺭ ﺍﻟﻬﺩﻑ ﻟﺭﻓﻊ ﺗﻘﺎﺭﻳﺭ ﺍﻷﺧﻁﺎء‪ .‬ﻳﻣﻛﻥ ﺭﻓﻊ ﺗﻘﺎﺭﻳﺭ‬
‫ﺑﺎﻷﺧﻁﺎء ﺇﻟﻰ ﺟﻣﻳﻊ ﺍﻷﻣﺎﻛﻥ‪ ،‬ﺃﻭ ﻓﻲ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ‬
‫ﺑﻌﺩ ﺍﻟﻣﺭﻛﺯﻳﺔ ﻓﻘﻁ‪.‬‬
‫ﻋﻧﺩ ﺍﻹﻋﺩﺍﺩ ﻋﻠﻰ ‪ ،01‬ﺗﺗﻭﻗﻑ ﺍﻟﻣﺭﻭﺣﺔ ﻋﻧﺩ‬
‫ﺍﻹﻳﻘﺎﻑ ﺑﻭﺍﺳﻁﺔ ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ ﻓﻲ ﻋﻣﻠﻳﺔ ﺍﻟﺗﺑﺭﻳﺩ‪ .‬ﻣﻥ‬
‫ﺍﻟﺿﺭﻭﺭﻱ ﺗﻭﺻﻳﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ‬
‫)ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ ﻭﺍﻟﻧﻭﻉ ﺛﻼﺛﻲ ﺍﻻﺳﻼﻙ( ﻭﺗﺑﺩﻳﻝ‬
‫ﺍﻟﺗﺭﻣﻭﺳﺗﺎﺕ ﺍﻟﺧﺎﺹ ﺑﻬﺎ‪.‬‬
‫‪Ar-17‬‬
‫‪2017/8/8 13:08:55‬‬
‫‪9381858019-02_IM_AR.indd Sec1:17‬‬
‫ﻋﺭﺽ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ‬
‫‪ .10‬ﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ‬
‫*‪) UTY-RNKYT / UTY-RNK‬ﺍﻟﻧﻭﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ(‬
‫ﺭﻣﺯ ﺍﻟﺧﻁﺄ‬
‫ﺇﺫﺍ ﻛﻧﺕ ﺗﺳﺗﺧﺩﻡ ﻭﺣﺩﺓ ﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻣﻥ ﻧﻭﻉ ﺳﻠﻛﻲ‪ ،‬ﺳﻭﻑ ﺗﻅﻬﺭ ﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ ﻋﻠﻰ ﺷﺎﺷﺔ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪ .‬ﺇﺫﺍ ﻛﻧﺕ‬
‫ﺗﺳﺗﺧﺩﻡ ﻭﺣﺩﺓ ﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﻻﺳﻠﻛﻳﺔ‪ ،‬ﻓﺈﻥ ﺍﻟﻣﺻﺑﺎﺡ ﻋﻠﻰ ﻭﺣﺩﺓ ﺍﻟﻛﺎﺷﻑ ﺍﻟﺿﻭﺋﻲ ﺳﻭﻑ ﺗﺻﺩﺭ ﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ ﻋﻥ ﻁﺭﻳﻕ ﺃﻧﻣﺎﻁ‬
‫ﺍﻟﻭﻣﻳﺽ‪ .‬ﺭﺍﺟﻊ ﺃﻧﻣﺎﻁ ﻭﻣﻳﺽ ﺍﻟﻣﺻﺑﺎﺡ ﻭﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ ﻓﻲ ﺍﻟﺟﺩﻭﻝ ﺍﻟﺗﺎﻟﻲ‪.‬‬
‫ﻣﺅﺷﺭﺍﺕ ﺍﻟﺧﻁﺄ‬
‫ﻣﺻﺑﺎﺡ‬
‫‪OPERATION‬‬
‫)ﺗﺷﻐﻳﻝ( )ﺃﺧﺿﺭ(‬
‫ﻣﺻﺑﺎﺡ ‪TIMER‬‬
‫)ﺍﻟﻣﺅﻗﺕ(‬
‫)ﺍﻟﺑﺭﺗﻘﺎﻟﻲ(‬
‫ﻣﺻﺑﺎﺡ ‪FILTER‬‬
‫)ﺍﻟﻣﺭﺷﺢ(‬
‫)ﺍﻷﺣﻣﺭ(‬
‫ﺭﻣﺯ ﺍﻟﺧﻁﺄ ﺑﻭﺣﺩﺓ‬
‫ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻟﺳﻠﻛﻳﺔ‬
‫ﻣﺣﺗﻭﻳﺎﺕ ﺍﻟﺧﻁﺄ‬
‫*‪) UTY-RNR*Z‬ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ(‬
‫)‪(1‬‬
‫)‪(2‬‬
‫ﺧﻁﺄ ﺍﺗﺻﺎﻝ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ‬
‫ﻋﻥ ﺑﻌﺩ‬
‫)‪(1‬‬
‫)‪(4‬‬
‫ﺧﻁﺄ ﺍﺗﺻﺎﻝ ﺍﻟﺷﺑﻛﺔ‬
‫)‪(1‬‬
‫)‪(6‬‬
‫ﺧﻁﺄ ﺍﺗﺻﺎﻝ ﺍﻟﻭﺣﺩﺓ ﺍﻟﻁﺭﻓﻳﺔ‬
‫)‪(2‬‬
‫)‪(6‬‬
‫ﺧﻁﺄ ﺇﻋﺩﺍﺩ ﻋﻧﻭﺍﻥ ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)‪(2‬‬
‫)‪(9‬‬
‫ﺧﻁﺄ ﻓﻲ ﺭﻗﻡ ﻭﺣﺩﺓ ﺍﻻﺗﺻﺎﻝ‬
‫ﻓﻲ ﻧﻅﺎﻡ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻟﺳﻠﻛﻳﺔ‬
‫)‪(3‬‬
‫)‪(1‬‬
‫ﺇﻣﺩﺍﺩ ﻁﺎﻗﺔ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻏﻳﺭ ﻋﺎﺩﻱ‬
‫)‪(3‬‬
‫)‪(2‬‬
‫ﺧﻁﺄ ﻟﻭﺣﺔ ﻛﻣﺑﻳﻭﺗﺭ ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻟﺭﺋﻳﺳﻳﺔ‬
‫)‪(3‬‬
‫)‪(10‬‬
‫ﺧﻁﺄ ﻓﻲ ﺩﺍﺋﺭﺓ ﺍﺗﺻﺎﻝ ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ )ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‬
‫ﺍﻟﺳﻠﻛﻳﺔ(‬
‫)‪(4‬‬
‫)‪(1‬‬
‫ﺧﻁﺄ ﻓﻲ ﺗﺭﻣﻭﺳﺗﺎﺕ ﺣﺭﺍﺭﺓ‬
‫ﺍﻟﻐﺭﻓﺔ ﺑﺎﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)‪(4‬‬
‫)‪(2‬‬
‫ﺧﻁﺄ ﺗﺭﻣﻭﺳﺗﺎﺕ ﺣﺭﺍﺭﺓ ﺍﻟﻣﺑﺎﺩﻝ‬
‫ﺍﻟﺣﺭﺍﺭﻱ ﺑﺎﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)‪(5‬‬
‫)‪(1‬‬
‫ﺧﻁﺄ ﻓﻲ ﻣﻭﺗﻭﺭ ﻣﺭﻭﺣﺔ ﺍﻟﻭﺣﺩﺓ‬
‫ﺍﻟﺩﺍﺧﻠﻳﺔ ‪1‬‬
‫)‪(5‬‬
‫)‪(2‬‬
‫ﺧﻁﺄ ﻣﻠﻑ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫)ﺻﻣﺎﻡ ﺍﻟﺗﻭﺳﻌﺔ(‬
‫)‪(5‬‬
‫)‪(3‬‬
‫ﺗﺻﺭﻳﻑ ﻣﻳﺎﻩ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ‬
‫ﻏﻳﺭ ﻋﺎﺩﻱ‬
‫)‪(9‬‬
‫)‪(15‬‬
‫ﺧﻁﺄ ﻣﺗﻧﻭﻉ ﻓﻲ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺧﺎﺭﺟﻳﺔ‬
‫)‪(13‬‬
‫)‪(1‬‬
‫ﺧﻁﺄ ﻭﺣﺩﺓ ‪RB‬‬
‫ﺍﻟﻣﺱ ]‪) [Next Page‬ﺍﻟﺻﻔﺣﺔ ﺍﻟﺗﺎﻟﻳﺔ( )ﺃﻭ ]‪[previous page‬‬
‫)ﺍﻟﺻﻔﺣﺔ ﺍﻟﺳﺎﺑﻘﺔ( ﻟﻠﺗﺑﺩﻳﻝ ﺇﻟﻰ ﻣﻌﻠﻭﻣﺎﺕ ﺍﻟﻭﺣﺩﺓ ﺍﻟﺩﺍﺧﻠﻳﺔ ﺍﻷﺧﺭﻯ‪.‬‬
‫ﺃﻳﻘﻭﻧﺔ ﺍﻟﺧﻁﺄ‬
‫ﺍﻟﻣﺱ ]‪) [Error Information‬ﻣﻌﻠﻭﻣﺎﺕ ﺍﻟﺧﻁﺄ(‪ .‬ﺍﻟﻣﺱ ]‪) [Status‬ﺍﻟﺣﺎﻟﺔ(‪.‬‬
‫ﺗﺗﻭﺍﻓﺭ ﺍﻷﻋﺩﺍﺩ ﻣﻥ ﺭﻗﻣﻳﻥ ﻣﻊ ﺭﻣﺯ ﺍﻟﺧﻁﺄ ﻓﻲ ﺍﻟﺟﺩﻭﻝ‬
‫ﺍﻟﺳﺎﺑﻕ‪.‬‬
‫ﻟﻣﺯﻳﺩ ﻣﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫*‪) UTY-RLR‬ﺍﻟﻧﻭﻉ ﺛﻧﺎﺋﻲ ﺍﻷﺳﻼﻙ(‬
‫ﺃﻳﻘﻭﻧﺔ ﺍﻟﺧﻁﺄ‬
‫ﺭﻣﺯ ﺍﻟﺧﻁﺄ‬
‫ﻟﻣﺯﻳﺩ ﻣﻥ ﺍﻟﻣﻌﻠﻭﻣﺎﺕ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻳﻝ ﺗﺭﻛﻳﺏ ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ‪.‬‬
‫ﻟﻠﺣﺻﻭﻝ ﻋﻠﻰ ﺗﻔﺎﺻﻳﻝ ﺣﻭﻝ ﻋﻼﻣﺎﺕ ﺭﻣﻭﺯ ﺍﻟﺧﻁﺄ‪ ،‬ﻳﺭﺟﻰ ﺍﻟﺭﺟﻭﻉ ﺇﻟﻰ ﺩﻟﻳﻝ "ﻭﺣﺩﺓ ﺍﺳﺗﻘﺑﺎﻝ‪ "IR‬ﺃﻭ "ﻭﺣﺩﺓ ﺍﻟﺗﺣﻛﻡ ﻋﻥ ﺑﻌﺩ ﺍﻟﺳﻠﻛﻳﺔ"‪.‬‬
‫ﻭﺿﻊ ﺍﻟﻌﺭﺽ‬
‫‪ 0.5 :‬ﺛﺎﻧﻳﺔ ﺗﺷﻐﻳﻝ ‪ 0.5 /‬ﺛﺎﻧﻳﺔ ﺇﻳﻘﺎﻑ‬
‫‪ 0.1 :‬ﺛﺎﻧﻳﺔ ﺗﺷﻐﻳﻝ ‪ 0.1 /‬ﺛﺎﻧﻳﺔ ﺇﻳﻘﺎﻑ‬
‫) ( ‪ :‬ﻋﺩﺩ ﺍﻟﻭﻣﻳﺽ‬
‫‪Ar-18‬‬
‫‪2017/8/8 13:08:54‬‬
‫‪9381858019-02_IM_AR.indd Sec1:18‬‬