‫ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ‬
‫ﺭﻗﻢ ﺍﻟﺼﻨﻒ ‪9371022451‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻓﻲ ﻧﻈﺎﻡ ‪] VRF‬ﺍﻟﻨﻮﻉ ﺍﻟﺸﺮﻳﻄﻲ )ﻋﻠﻰ ﺷﻜﻞ ﻋﻠﻴﺒﺔ([‬
‫ﺍﻟﻤﺤﺘﻮﻳﺎﺕ‬
‫‪ .1‬ﺍﺣﺘﻴﺎﻃﺎﺕ ﺍﻟﺴﻼﻣﺔ ‪1 ...............................................................‬‬
‫‪ .2‬ﻧﺒﺬﺓ ﻋﻦ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ‪1 ...............................................................‬‬
‫‪ .1.2‬ﺍﺣﺘﻴﺎﻃﺎﺕ ﺍﺳﺘﺨﺪﺍﻡ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪1 .............................. R410A‬‬
‫‪ .2.2‬ﺍﻷﺩﺍﺓ ﺍﻟﺨﺎﺻﺔ ﻟـ ‪1 ............................................... R410A‬‬
‫‪ .3.2‬ﺍﻟﻤﻠﺤﻘﺎﺕ‪2 ...................................................................‬‬
‫‪ .4.2‬ﺍﻷﺟﺰﺍء ﺍﻻﺧﺘﻴﺎﺭﻳﺔ ‪2 ........................................................‬‬
‫‪ .3‬ﺃﻋﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ‪2 ...................................................................‬‬
‫‪ .1.3‬ﺍﺧﺘﻴﺎﺭ ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ ‪2 .....................................................‬‬
‫‪ .2.3‬ﺃﺑﻌﺎﺩ ﺍﻟﺘﺮﻛﻴﺐ‪3 ..............................................................‬‬
‫‪ .3.3‬ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ‪3 .............................................................‬‬
‫‪ .4‬ﺗﺮﻛﻴﺐ ﺍﻟﻤﺎﺳﻮﺭﺓ ‪5 .................................................................‬‬
‫‪ .1.4‬ﺍﺧﺘﻴﺎﺭ ﻣﺎﺩﺓ ﺍﻟﻤﺎﺳﻮﺭﺓ ‪5 .....................................................‬‬
‫‪ .2.4‬ﻣﺘﻄﻠﺒﺎﺕ ﺍﻟﻤﺎﺳﻮﺭﺓ ‪5 ........................................................‬‬
‫‪ .3.4‬ﻭﺻﻠﺔ ﺗﻔﻠﻴﺞ )ﻭﺻﻠﺔ ﺍﻟﻤﺎﺳﻮﺭﺓ(‪5 ...........................................‬‬
‫‪ .4.4‬ﺗﺮﻛﻴﺐ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ‪6 .....................................................‬‬
‫‪ .5‬ﺗﺮﻛﻴﺐ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺼﺮﻑ‪6 .........................................................‬‬
‫‪ .6‬ﺍﻷﺳﻼﻙ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ‪7 ...............................................................‬‬
‫‪ .1.6‬ﺍﻟﻤﺘﻄﻠﺐ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ‪8 ........................................................‬‬
‫‪ .2.6‬ﻃﺮﻳﻘﺔ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‪8 ...................................................‬‬
‫‪ .3.6‬ﺃﺳﻼﻙ ﺍﻟﻮﺣﺪﺓ‪8 ..............................................................‬‬
‫‪ .4.6‬ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‪9 ...........................................................‬‬
‫‪ .5.6‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺨﺎﺭﺟﻲ ﻭﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ )ﺃﺟﺰﺍء ﺍﺧﺘﻴﺎﺭﻳﺔ( ‪10 ..............‬‬
‫‪ .7‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺠﺎﻝ ‪12 .....................................................................‬‬
‫‪ .1.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ ‪12 ..............................................................‬‬
‫‪ .2.7‬ﺇﻋﺪﺍﺩ ﺭﻣﺰ ﻣﺨﺼﺺ‪13 ......................................................‬‬
‫‪ .3.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ‪14 ..............................................................‬‬
‫‪ .8‬ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‪15 ..............................................................‬‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺗﺸﻴﺮ ﻫﺬﻩ ﺍﻟﻌﻼﻣﺔ ﺇﻟﻰ ﺍﻹﺟﺮﺍءﺍﺕ‪ ،‬ﺍﻟﺘﻲ ﻓﻲ ﺣﺎﻟﺔ ﻋﺪﻡ ﺗﻨﻔﻴﺬﻫﺎ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪ ،‬ﻗﺪ ﺗﺆﺩﻱ‬
‫ﺿﺮﺭ ﺷﺨﺼﻲ ﻟﻠﻤﺴﺘﺨﺪﻡ ﺃﻭ ﺗﻠﻒ ﻓﻲ ﺍﻟﻤﻤﺘﻠﻜﺎﺕ‪.‬‬
‫ﺍﻗﺮﺃ ﺑﻌﻨﺎﻳﺔ ﺟﻤﻴﻊ ﻣﻌﻠﻮﻣﺎﺕ ﺍﻷﻣﺎﻥ ﻗﺒﻞ ﺍﺳﺘﺨﺪﺍﻡ ﺃﻭ ﺗﺮﻛﻴﺐ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء‪.‬‬
‫ﻻ ﺗﺤﺎﻭﻝ ﺗﺮﻛﻴﺐ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﺃﻭ ﺟﺰء ﻣﻦ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﺑﻨﻔﺴﻚ‪.‬‬
‫ﻳﺠﺐ ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺑﻮﺍﺳﻄﺔ ﻓﻨﻲ ﻣﻌﺘﻤﺪ ﻟﺪﻳﻪ ﺷﻬﺎﺩﺓ ﺃﻫﻠﻴﺔ ﻟﻠﺘﻌﺎﻣﻞ ﻣﻊ ﺳﻮﺍﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪ .‬ﺭﺍﺟﻊ ﺍﻟﻠﻮﺍﺋﺢ ﻭﺍﻟﻘﻮﺍﻧﻴﻦ ﺍﻟﻤﻌﻤﻮﻝ ﺑﻬﺎ ﻓﻲ‬
‫ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫ﻭﻓﻘﺎ ﻟﻠﻮﺍﺋﺢ ﺍﻟﻤﻌﻤﻮﻝ ﺑﻬﺎ ﻓﻲ ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ ً‬
‫ﻳﺠﺐ ﺇﺟﺮﺍء ﺍﻟﺘﺮﻛﻴﺐ ً‬
‫ﻭﻭﻓﻘﺎ ﻟﺘﻌﻠﻴﻤﺎﺕ ﺍﻟﺘﺮﻛﻴﺐ ﻣﻦ ﺍﻟﻤﺼﻨﱢﻊ‪.‬‬
‫ﻫﺬﻩ ﺍﻟﻮﺣﺪﺓ ﺗﺸﻜﻞ ﺟﺰ ًء ﻣﻦ ﺍﻟﻤﺠﻤﻮﻋﺔ ﺍﻟﺘﻲ ﻳﺘﺄﻟﻒ ﻣﻨﻬﺎ ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍء‪ .‬ﻭﻳﺠﺐ ﻋﺪﻡ ﺗﺮﻛﻴﺒﻬﺎ ﻭﺣﺪﻫﺎ ﺃﻭ ﻣﻊ ﺃﺟﺰﺍء ﻏﻴﺮ ﻣﻌﺘﻤﺪﺓ‬
‫ﻣﻦ ﺍﻟﻤﺼﻨﱢﻊ‪.‬‬
‫ﺍﺣﺮﺹ ﺩﺍﺋﻤًﺎ ﻋﻠﻰ ﺍﺳﺘﺨﺪﺍﻡ ﺧﻂ ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ ﻣﻨﻔﺼﻞ ﻣﺤﻤﻲ ﺑﻘﺎﻃﻊ ﺩﺍﺋﺮﺓ ﻳﻌﻤﻞ ﻋﻠﻰ ﺟﻤﻴﻊ ﺍﻷﺳﻼﻙ ﺑﻤﺴﺎﻓﺔ ﺑﻴﻦ ﺃﺟﺰﺍء ﺍﻟﺘﻼﻣﺲ‬
‫ﺗﺒﻠﻎ ‪ 3‬ﻣﻢ ﻟﻬﺬﻩ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫ﻳﺠﺐ ﺗﻮﺻﻴﻞ ﺍﻟﻮﺣﺪﺓ ﺑﺸﻜﻞ ﺻﺤﻴﺢ ﺑﺎﻷﺭﺽ )ﺍﻟﺘﺄﺭﻳﺾ( ﻭﻳﺠﺐ ﺗﺰﻭﻳﺪ ﺧﻂ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﺑﻘﺎﻃﻊ ﺩﺍﺋﺮﺓ ﻓﺮﻗﻲ ﻣﻦ ﺃﺟﻞ ﺣﻤﺎﻳﺔ‬
‫ﺍﻷﺷﺨﺎﺹ‪.‬‬
‫ﺍﻟﻮﺣﺪﺍﺕ ﻟﻴﺴﺖ ﻣﻘﺎﻭﻣﺔ ﻟﻼﻧﻔﺠﺎﺭ ﻭﺑﺎﻟﺘﺎﻟﻲ ﻳﺠﺐ ﻋﺪﻡ ﺗﺮﻛﻴﺒﻬﺎ ﻓﻲ ﺃﺟﻮﺍء ﻗﺎﺑﻠﺔ ﻟﻼﻧﻔﺠﺎﺭ‪.‬‬
‫ً‬
‫ﺗﺠﻨﺐ‬
‫ﻣﻄﻠﻘﺎ ﻟﻤﺲ ﺍﻟﻤﻜﻮﻧﺎﺕ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺑﻌﺪ ﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ ﻣﺼﺪﺭ ﺍﻟﻄﺎﻗﺔ ﻣﺒﺎﺷﺮﺓ‪ .‬ﻓﻘﺪ ﺗﺤﺪﺙ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ‪ .‬ﺑﻌﺪ ﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ‬
‫ﺍﻟﻄﺎﻗﺔ‪ ،‬ﺩﺍﺋﻤًﺎ ﺍﻧﺘﻈﺮ ‪ 5‬ﺩﻗﺎﺋﻖ ﻗﺒﻞ ﻟﻤﺲ ﺍﻟﻤﻜﻮﻧﺎﺕ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ‪.‬‬
‫ﻻ ﺗﺤﺘﻮﻱ ﻫﺬﻩ ﺍﻟﻮﺣﺪﺓ ﻋﻠﻰ ﺃﺟﺰﺍء ﻳﻤﻜﻦ ﺻﻴﺎﻧﺘﻬﺎ ﺑﻮﺍﺳﻄﺔ ﺍﻟﻤﺴﺘﺨﺪﻡ‪ .‬ﺍﺣﺮﺹ ﺩﺍﺋﻤًﺎ ﻋﻠﻰ ﺍﺳﺘﺸﺎﺭﺓ ﻣﻮﻇﻔﻲ ﺍﻟﺼﻴﺎﻧﺔ ﺍﻟﻤﻌﺘﻤﺪﻳﻦ‬
‫ﺑﺸﺄﻥ ﺍﻹﺻﻼﺣﺎﺕ‪.‬‬
‫ﻋﻨﺪ ﺍﻟﻨﻘﻞ‪ ،‬ﺍﺳﺘﺸﺮ ﻣﻮﻇﻔﻲ ﺍﻟﺼﻴﺎﻧﺔ ﺍﻟﻤﻌﺘﻤﺪﻳﻦ ﺑﺸﺄﻥ ﻓﺼﻞ ﺗﻮﺻﻴﻞ ﺍﻟﻮﺣﺪﺓ ﻭﺗﺮﻛﻴﺒﻬﺎ‪.‬‬
‫‪ .2‬ﻧﺒﺬﺓ ﻋﻦ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ‬
‫‪ .1.2‬ﺍﺣﺘﻴﺎﻃﺎﺕ ﺍﺳﺘﺨﺪﺍﻡ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪R410A‬‬
‫ﺗﺤﺬﻳﺮ‬
‫ﻻ ﺗﺪﺧﻞ ﺃﻱ ﻣﺎﺩﺓ ﺧﻼﻑ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺍﻟﻤﻮﺻﻮﻑ ﻓﻲ ﺩﻭﺭﺓ ﺍﻟﺘﺒﺮﻳﺪ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺩﺧﻮﻝ ﺍﻟﻬﻮﺍء ﺇﻟﻰ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪ ،‬ﻓﺴﻮﻑ ﻳﺼﺒﺢ ﺍﻟﻀﻐﻂ ﻓﻲ ﺩﻭﺭﺓ ﺍﻟﺘﺒﺮﻳﺪ ﻣﺮﺗﻔﻌًﺎ ﺑﺼﻮﺭﺓ ﻏﻴﺮ ﻋﺎﺩﻳﺔ ﻭﻳﺴﺒﺐ ﻛﺴﺮ ﺍﻟﻤﻮﺍﺳﻴﺮ‪.‬‬
‫ﺇﺫﺍ ﻛﺎﻥ ﻫﻨﺎﻙ ﺗﺴﺮﻳﺐ ﻓﻲ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪ ،‬ﺗﺄﻛﺪ ﻣﻦ ﺃﻧﻪ ﻻ ﻳﺘﺠﺎﻭﺯ ﺣﺪ ﺍﻟﺘﺮﻛﻴﺰ‪.‬‬
‫ﺇﺫﺍ ﺗﺠﺎﻭﺯ ﺗﺴﺮﻳﺐ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺣﺪ ﺍﻟﺘﺮﻛﻴﺰ‪ ،‬ﻓﻴﻤﻜﻦ ﺃﻥ ﻳﺆﺩﻱ ﺇﻟﻰ ﺣﻮﺍﺩﺙ ﻣﺜﻞ ﻧﻘﺺ ﺍﻷﻛﺴﺠﻴﻦ‪.‬‬
‫ﻻ ﺗﻠﻤﺲ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺍﻟﻤﺘﺴﺮﺏ ﻣﻦ ﻭﺻﻼﺕ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﺒﺮﻳﺪ ﺃﻭ ﻣﻨﻄﻘﺔ ﺃﺧﺮﻯ‪ .‬ﻳﺆﺩﻱ ﻟﻤﺲ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻣﺒﺎﺷﺮﺓ ﺇﻟﻰ ﺍﻹﺻﺎﺑﺔ‬
‫ﺑﻠﺴﻌﺎﺕ ﺻﻘﻴﻊ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺣﺪﻭﺙ ﺗﺴﺮﻳﺐ ﻟﺴﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺃﺛﻨﺎء ﺍﻟﺘﺸﻐﻴﻞ‪ ،‬ﻗﻢ ﺑﺈﺧﻼء ﺍﻟﻤﻜﺎﻥ ﻋﻠﻰ ﺍﻟﻔﻮﺭ ﻭﺗﻬﻮﻳﺔ ﺍﻟﻤﻨﻄﻘﺔ ﺑﺎﻟﻜﺎﻣﻞ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﻣﻼﻣﺴﺔ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻟﻠﻬﺐ‪ ،‬ﻓﺴﻮﻑ ﻳﻨﺘﺞ ﻏﺎﺯ ﺳﺎﻡ‪.‬‬
‫‪ .2.2‬ﺍﻷﺩﺍﺓ ﺍﻟﺨﺎﺻﺔ ﻟـ ‪R410A‬‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺧﺼﻴﺼﺎ‬
‫ﻟﺘﺮﻛﻴﺐ ﻭﺣﺪﺓ ﺗﺴﺘﺨﺪﻡ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪ ، R410A‬ﺍﺳﺘﺨﺪﻡ ﺍﻷﺩﻭﺍﺕ ﺍﻟﻤﺨﺼﺼﺔ ﻭﻣﻮﺍﺩ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺍﻟﺘﻲ ﺗﻢ ﺗﺼﻨﻴﻌﻬﺎ‬
‫ً‬
‫ﻟﻼﺳﺘﺨﺪﺍﻡ ﻣﻊ ‪.R410A‬‬
‫ﻧﻈﺮﺍ ﻷﻥ ﺿﻐﻂ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪ R410A‬ﻳﻜﻮﻥ ﺃﻋﻠﻰ ﺑﻤﻘﺪﺍﺭ ‪ 1.6‬ﻣﺮﺓ ﻣﻦ ﺳﺎﺋﻞ ‪ ،R22‬ﻳﻤﻜﻦ ﺃﻥ ﻳﺘﺴﺒﺐ ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﺳﺘﺨﺪﺍﻡ‬
‫ً‬
‫ﻣﻮﺍﺩ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺍﻟﻤﺨﺼﺼﺔ ﺃﻭ ﺍﻟﺘﺮﻛﻴﺐ ﻏﻴﺮ ﺍﻟﺼﺤﻴﺢ ﺇﻟﻰ ﺣﺪﻭﺙ ﺗﻤﺰﻕ ﺃﻭ ﺇﺻﺎﺑﺔ‪.‬‬
‫ﻋﻼﻭﺓ ﻋﻠﻰ ﺫﻟﻚ‪ ،‬ﻳﻤﻜﻦ ﺃﻥ ﻳﺘﺴﺒﺐ ﻓﻲ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺗﺴﺮﺏ ﺍﻟﻤﻴﺎﻩ ﺃﻭ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﺍﺳﻢ ﺍﻷﺩﺍﺓ‬
‫ﻣﺤﺘﻮﻳﺎﺕ ﺍﻟﺘﻐﻴﻴﺮ‬
‫‪ .9‬ﺍﻟﺘﺸﻐﻴﻞ ﺍﻻﺧﺘﺒﺎﺭﻱ‪15 ...............................................................‬‬
‫‪ .1.9‬ﺗﺸﻐﻴﻞ ﺍﺧﺘﺒﺎﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ )ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ( ‪15 .........‬‬
‫‪ .2.9‬ﺗﺸﻐﻴﻞ ﺍﺧﺘﺒﺎﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ‪15 .........................‬‬
‫ﻣﺸﻌﺐ ﺍﻟﻌﺪﺍﺩ‬
‫ﺍﻟﻀﻐﻂ ﻛﺒﻴﺮ ﻭﻻ ﻳﻤﻜﻦ ﻗﻴﺎﺳﻪ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻋﺪﺍﺩ )‪ (R22‬ﺍﻟﺘﻘﻠﻴﺪﻱ‪ .‬ﻟﻤﻨﻊ ﺧﻠﻂ ﺳﻮﺍﺋﻞ ﺗﺒﺮﻳﺪ‬
‫ﺃﺧﺮﻯ ﻋﻦ ﻃﺮﻳﻖ ﺍﻟﺨﻄﺄ‪ ،‬ﺗﻢ ﺗﻐﻴﻴﺮ ﻗﻄﺮ ﻛﻞ ﻣﻨﻔﺬ‪.‬‬
‫ﻳﻮﺻﻰ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻣﺸﻌﺐ ﻋﺪﺍﺩ ﺑﻨﻄﺎﻕ ﻋﺮﺽ ﺿﻐﻂ ﻣﺮﺗﻔﻊ ‪ -0.1‬ﺇﻟﻰ ‪ 5.3‬ﻣﻴﺠﺎﺑﺎﺳﻜﺎﻝ‬
‫ﻭﻧﻄﺎﻕ ﻋﺮﺽ ﺿﻐﻂ ﻣﻨﺨﻔﺾ ‪ -0.1‬ﺇﻟﻰ ‪ 3.8‬ﻣﻴﺠﺎﺑﺎﺳﻜﺎﻝ‪.‬‬
‫ﺧﺮﻃﻮﻡ ﺍﻟﺸﺤﻦ‬
‫ﻟﺰﻳﺎﺩﺓ ﻣﻘﺎﻭﻣﺔ ﺍﻟﻀﻐﻂ‪ ،‬ﺗﻢ ﺗﻐﻴﻴﺮ ﻣﺎﺩﺓ ﺍﻟﺨﺮﻃﻮﻡ ﻭﺣﺠﻢ ﺍﻟﻘﺎﻋﺪﺓ‪.‬‬
‫‪ .10‬ﻗﺎﺋﻤﺔ ﺍﻟﻔﺤﺺ‪15 .....................................................................‬‬
‫ﻣﻀﺨﺔ ﺍﻟﺘﻔﺮﻳﻎ‬
‫ﻳﻤﻜﻦ ﺍﺳﺘﺨﺪﺍﻡ ﻣﻀﺨﺔ ﺍﻟﺘﻔﺮﻳﻎ ﺍﻟﺘﻘﻠﻴﺪﻳﺔ )‪ (R22‬ﻣﻦ ﺧﻼﻝ ﺗﺮﻛﻴﺐ ﻣﻬﺎﻳﺊ ﻣﻀﺨﺔ ﺗﻔﺮﻳﻎ‪.‬‬
‫ﺗﺄﻛﺪ ﻣﻦ ﺃﻥ ﺯﻳﺖ ﺍﻟﻤﻀﺨﺔ ﻻ ﻳﺘﺪﻓﻖ ﻋﻜﺴﻴًﺎ ﻓﻲ ﺍﻟﻨﻈﺎﻡ‪ .‬ﺍﺳﺘﺨﺪﻡ ﺯﻳﺖ ﻗﺎﺩﺭ ﻋﻠﻰ ﺍﻻﻣﺘﺼﺎﺹ‬
‫ﺍﻟﻤﻔﺮﻍ ﺑﻘﻴﻤﺔ ‪ -100.7‬ﻛﻴﻠﻮﺑﺎﺳﻜﺎﻝ )‪ 5‬ﻃﻦ‪ -755 ,‬ﻣﻢ ﺯﺋﺒﻖ(‪.‬‬
‫ﻭﺣﺪﺓ ﺍﻛﺘﺸﺎﻑ ﺗﺴﺮﻳﺐ ﺍﻟﻐﺎﺯ‬
‫ﻭﺣﺪﺓ ﺍﻛﺘﺸﺎﻑ ﺗﺴﺮﻳﺐ ﻏﺎﺯ ﺧﺎﺻﺔ ﻟﺴﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪ R410A‬ﻣﻦ ‪.HFC‬‬
‫‪ .11‬ﺭﻣﻮﺯ ﺍﻟﺨﻄﺄ‪16 ......................................................................‬‬
‫‪ .1‬ﺍﺣﺘﻴﺎﻃﺎﺕ ﺍﻟﺴﻼﻣﺔ‬
‫• ﺗﺄﻛﺪ ﻣﻦ ﻗﺮﺍءﺓ ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺑﺎﻟﻜﺎﻣﻞ ﻗﺒﻞ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫• ﺗﺤﺘﻮﻱ ﺍﻟﺘﺤﺬﻳﺮﺍﺕ ﻭﺍﻻﺣﺘﻴﺎﻃﺎﺕ ﺍﻟﻮﺍﺭﺩﺓ ﻓﻲ ﻫﺬﺍ ﺍﻟﺪﻟﻴﻞ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎﺕ ﻫﺎﻣﺔ ﺗﺘﻌﻠﻖ ﺑﺴﻼﻣﺘﻚ‪ .‬ﻋﻠﻴﻚ ﺍﻟﺘﺄﻛﺪ ﻣﻦ ﺍﺗﺒﺎﻋﻬﺎ‪.‬‬
‫• ﻳﺮﺟﻰ ﺗﻘﺪﻳﻢ ﻫﺬﺍ ﺍﻟﺪﻟﻴﻞ ﺇﻟﻰ ﺟﺎﻧﺐ ﺩﻟﻴﻞ ﺍﻟﺘﺸﻐﻴﻞ ﺇﻟﻰ ﺍﻟﻌﻤﻴﻞ‪.‬‬
‫ﺍﻃﻠﺐ ﻣﻦ ﺍﻟﻌﻤﻴﻞ ﺍﻻﺣﺘﻔﺎﻅ ﺑﻬﻤﺎ ﻓﻲ ﺍﻟﻤﺘﻨﺎﻭﻝ ﻟﻼﺳﺘﺨﺪﺍﻡ ﻓﻲ ﺍﻟﻤﺴﺘﻘﺒﻞ‪ ،‬ﻣﺜﻞ ﺗﻐﻴﻴﺮ ﻣﻜﺎﻥ ﺍﻟﻮﺣﺪﺓ ﺃﻭ ﺇﺻﻼﺣﻬﺎ‪.‬‬
‫ﺗﺸﻴﺮ ﻫﺬﻩ ﺍﻟﻌﻼﻣﺔ ﺇﻟﻰ ﺍﻹﺟﺮﺍءﺍﺕ‪ ،‬ﺍﻟﺘﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻨﻔﻴﺬﻫﺎ ﺑﺸﻜﻞ ﻏﻴﺮ ﺻﺤﻴﺢ‪ ،‬ﻗﺪ ﺗﺆﺩﻱ‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺇﻟﻰ ﺍﻟﻮﻓﺎﺓ ﺃﻭ ﺍﻹﺻﺎﺑﺔ ﺍﻟﺨﻄﻴﺮﺓ ﻟﻠﻤﺴﺘﺨﺪﻡ‪.‬‬
‫ﺍﻃﻠﺐ ﻣﻦ ﺍﻟﻤﻮﺯﻉ ﺃﻭ ﻣﺴﺆﻭﻝ ﺍﻟﺘﺮﻛﻴﺐ ﺍﻟﻤﺘﺨﺼﺺ ﺗﺮﻛﻴﺐ ﻫﺬﻩ ﺍﻟﻮﺣﺪﺓ ً‬
‫ﻭﻓﻘﺎ ﻟﻬﺬﺍ ﺍﻟﺪﻟﻴﻞ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﺗﺘﺴﺒﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﻤﺮﻛﺒﺔ ﺑﺸﻜﻞ ﻏﻴﺮ ﺻﺤﻴﺢ ﻓﻲ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺗﺴﺮﺏ ﺍﻟﻤﻴﺎﻩ ﺃﻭ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺑﺸﻜﻞ ﻳﺨﺎﻟﻒ ﺍﻟﺘﻌﻠﻴﻤﺎﺕ ﺍﻟﻮﺍﺭﺩﺓ ﻓﻲ ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ‪ ،‬ﻓﺴﻮﻑ ﺗﺒﻄﻞ ﺍﻟﻀﻤﺎﻥ‪.‬‬
‫ﻻ ﺗﻘﻢ ﺑﺘﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ ﺇﻻ ﺑﻌﺪ ﺍﺳﺘﻜﻤﺎﻝ ﺟﻤﻴﻊ ﺍﻷﻋﻤﺎﻝ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﻳﺆﺩﻱ ﺗﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ ﻗﺒﻞ ﺍﺳﺘﻜﻤﺎﻝ ﺍﻟﻌﻤﻞ ﺇﻟﻰ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺍﻟﺘﻌﺮﺽ ﻟﺼﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺴﺮﻳﺐ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺃﺛﻨﺎء ﺗﻨﻔﻴﺬ ﺍﻟﻌﻤﻞ‪ ،‬ﻓﻌﻠﻴﻚ ﺗﻬﻮﻳﺔ ﺍﻟﻤﻨﻄﻘﺔ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﻣﻼﻣﺴﺔ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻟﻠﻬﺐ‪ ،‬ﻓﺴﻮﻑ ﻳﻨﺘﺞ ﻏﺎﺯ ﺳﺎﻡ‪.‬‬
‫ﻳﺠﺐ ﺗﻨﻔﻴﺬ ﺃﻋﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ ً‬
‫ﻭﻓﻘﺎ ﻟﻤﻌﺎﻳﻴﺮ ﺗﻮﺻﻴﻼﺕ ﺍﻷﺳﻼﻙ ﺍﻟﻮﻃﻨﻴﺔ ﻭﻋﻦ ﻃﺮﻳﻖ ﺷﺨﺺ ﻣﺨﻮﻝ ﻓﻘﻂ‪.‬‬
‫ﺑﺎﺳﺘﺜﻨﺎء ﻓﻲ ﺣﺎﻟﺔ ﺍﻟﻄﻮﺍﺭﺉ‪ ،‬ﺗﺠﻨﺐ ً‬
‫ﻣﻄﻠﻘﺎ ﻓﺼﻞ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺮﺋﻴﺴﻲ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﻗﺎﻃﻊ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻔﺮﻋﻲ ﻟﻠﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺃﺛﻨﺎء ﺍﻟﺘﺸﻐﻴﻞ‪.‬‬
‫ﺳﻮﻑ ﻳﺆﺩﻱ ﺫﻟﻚ ﺇﻟﻰ ﺗﻌﻄﻞ ﺍﻟﻀﺎﻏﻂ ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺗﺴﺮﻳﺐ ﺍﻟﻤﻴﺎﻩ‪ .‬ﻗﻢ ﺃﻭﻻ ﺑﺈﻳﻘﺎﻑ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻣﻦ ﺧﻼﻝ ﺗﺸﻐﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﺃﻭ ﺍﻟﻤﺤﻮﻝ ﺃﻭ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺨﺎﺭﺟﻲ ﺛﻢ ﻗﻢ ﺑﻔﺼﻞ ﺍﻟﻘﺎﻃﻊ‪ .‬ﺗﺄﻛﺪ ﻣﻦ ﺍﻟﺘﺸﻐﻴﻞ ﻣﻦ ﺧﻼﻝ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﺃﻭ ﺍﻟﻤﺤﻮﻝ ﺃﻭ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﺨﺎﺭﺟﻲ‪ .‬ﻋﻨﺪ ﺗﺼﻤﻴﻢ ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‪ ،‬ﺿﻌﻪ ﻓﻲ ﻣﻜﺎﻥ ﺑﺤﻴﺚ ﻻ ﻳﻤﻜﻦ ﻟﻠﻤﺴﺘﺨﺪﻣﻴﻦ ﺑﺪء ﺍﻟﺠﻬﺎﺯ ﻭﺇﻳﻘﺎﻓﻪ ﻓﻲ ﺍﻷﻏﺮﺍﺽ ﺍﻟﻴﻮﻣﻴﺔ‪.‬‬
‫‪Ar-1‬‬
‫‪3/14/2016 4:32:19 PM‬‬
‫‪9371022451_IM_AR.indd 1‬‬
‫‪ .3.2‬ﺍﻟﻤﻠﺤﻘﺎﺕ‬
‫‪ .4.2‬ﺍﻷﺟﺰﺍء ﺍﻻﺧﺘﻴﺎﺭﻳﺔ‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺍﻟﻮﺻﻒ‬
‫ﺍﻻﺳﺘﻌﻤﺎﻝ‬
‫ﺍﻟﻄﺮﺍﺯ‬
‫ﻷﻏﺮﺍﺽ ﺍﻟﺘﺮﻛﻴﺐ‪ ،‬ﺗﺄﻛﺪ ﻣﻦ ﺍﺳﺘﺨﺪﺍﻡ ﺍﻷﺟﺰﺍء ﺍﻟﻤﻘﺪﻣﺔ ﻣﻦ ﺍﻟﻤﺼﻨﱢﻊ ﺃﻭ ﺍﻷﺟﺰﺍء ﺍﻷﺧﺮﻯ ﺍﻟﻤﻮﺻﻮﻓﺔ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﻳﺆﺩﻱ ﺍﺳﺘﺨﺪﺍﻡ ﺃﺟﺰﺍء ﻏﻴﺮ ﻣﺤﺪﺩﺓ ﺇﻟﻰ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺳﻘﻮﻁ ﺍﻟﻮﺣﺪﺓ ﺃﻭ ﺗﺴﺮﻳﺐ ﺍﻟﻤﺎء ﺃﻭ ﺍﻟﺘﻌﺮﺽ ﻟﺼﺪﻣﺔ‬
‫ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫‪UTY-XWZXZC‬‬
‫ﻟﻮﻇﻴﻔﺔ ﺍﻹﺧﺮﺍﺝ‬
‫)ﻃﺮﻑ ﺍﻹﺧﺮﺍﺝ ‪(CNB01 /‬‬
‫ﻳﺘﻢ ﺗﺰﻭﻳﺪ ﺃﺟﺰﺍء ﺍﻟﺘﺮﻛﻴﺐ ﺍﻟﺘﺎﻟﻴﺔ‪ .‬ﺍﺳﺘﺨﺪﻣﻬﺎ ﺣﺴﺐ ﺍﻟﺤﺎﺟﺔ‪.‬‬
‫‪UTY-XWZXZB‬‬
‫ﻟﻮﻇﻴﻔﺔ ﺇﺩﺧﺎﻝ ﺍﻟﺘﺤﻜﻢ‬
‫)ﻃﺮﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ ‪(CNA01 /‬‬
‫‪UTY-XWZXZD‬‬
‫ﻟﻮﻇﻴﻔﺔ ﺇﺩﺧﺎﻝ ﺍﻟﺘﺤﻜﻢ‬
‫)ﻃﺮﻑ ﺍﻟﺘﻼﻣﺲ ﺍﻟﺠﺎﻑ ‪(CNA02 /‬‬
‫‪UTY-XWZXZ7‬‬
‫ﻟﻮﻇﻴﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ ﻣﻦ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‬
‫)ﻃﺮﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ ‪(CNA03 /‬‬
‫‪UTY-XWZXZE‬‬
‫ﻟﻮﻇﻴﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ ﻣﻦ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‬
‫)ﻃﺮﻑ ﺍﻟﺘﻼﻣﺲ ﺍﻟﺠﺎﻑ ‪(CNA04 /‬‬
‫ﺍﺣﺘﻔﻆ ﺑﺪﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﻓﻲ ﻣﻜﺎﻥ ﺁﻣﻦ ﻭﻻ ﺗﺘﺨﻠﺺ ﻣﻦ ﺃﻱ ﻣﻠﺤﻘﺎﺕ ﺃﺧﺮﻯ ﺣﺘﻰ ﻳﺘﻢ ﺍﺳﺘﻜﻤﺎﻝ ﺃﻋﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫ﺍﻻﺳﻢ ﻭﺍﻟﺸﻜﻞ‬
‫ﺍﻟﻜﻤﻴﺔ‬
‫ﻃﻘﻢ ﺍﻟﺘﻮﺻﻴﻞ ﺍﻟﺨﺎﺭﺟﻲ‬
‫ﺍﻻﺳﺘﻌﻤﺎﻝ‬
‫ﺩﻟﻴﻞ ﺍﻟﺘﺸﻐﻴﻞ‬
‫‪1‬‬
‫ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ‬
‫)ﻫﺬﺍ ﺍﻟﻜﺘﺎﺏ(‬
‫‪ .3‬ﺃﻋﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ‬
‫ﻧﻈﺮﺍ ﻷﻧﻪ ﻣﻦ ﺍﻟﺼﻌﺐ ﺗﺤﺮﻳﻚ ﺍﻟﻮﺣﺪﺓ ﺑﻌﺪ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫ﻳﻌﺘﺒﺮ ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ ﺍﻷﻭﻟﻲ ﻫﺎﻣًﺎ ً‬
‫‪1‬‬
‫‪ .1.3‬ﺍﺧﺘﻴﺎﺭ ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ‬
‫ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ )ﻛﺒﻴﺮ(‬
‫ﻟﺘﺜﺒﻴﺖ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﻮﺻﻴﻞ )ﻛﺒﻴﺮ ﻭﺻﻐﻴﺮ(‬
‫ﺗﺤﺬﻳﺮ‬
‫‪4‬‬
‫ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ )ﻣﺘﻮﺳﻂ(‬
‫ﺍﺧﺘﺮ ﺃﻣﺎﻛﻦ ﺗﺮﻛﻴﺐ ﻳﻤﻜﻨﻬﺎ ﺗﺤﻤﻞ ﻭﺯﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪ .‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺍﺕ ﺑﺈﺣﻜﺎﻡ ﺑﺤﻴﺚ ﻻ ﺗﺘﻌﺮﺽ‬
‫ﻟﻼﻧﻘﻼﺏ ﺃﻭ ﺍﻟﺴﻘﻮﻁ‪.‬‬
‫ﺗﻨﺒﻴﻪ‬
‫ﻟﺮﺑﻂ ﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫‪2‬‬
‫ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‬
‫)ﺻﻐﻴﺮ(‬
‫ﻟﻮﺻﻠﺔ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺠﺎﻧﺐ ﺍﻟﺪﺍﺧﻠﻲ )ﺻﻐﻴﺮ(‬
‫‪1‬‬
‫ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‬
‫)ﻛﺒﻴﺮ(‬
‫ﻟﻮﺻﻠﺔ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺠﺎﻧﺐ ﺍﻟﺪﺍﺧﻠﻲ )ﻛﺒﻴﺮ(‬
‫ﻻ ﺗﺮﻛﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﺍﻟﻤﻨﺎﻃﻖ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫• ﺍﻟﻤﻨﻄﻘﺔ ﺫﺍﺕ ﻣﺤﺘﻮﻯ ﻣﻠﻮﺣﺔ ﻣﺮﺗﻔﻊ‪ ،‬ﻣﺜﻞ ﺳﺎﺣﻞ ﺍﻟﺒﺤﺮ‪.‬‬
‫ﺳﻮﻑ ﺗﺆﺩﻱ ﺇﻟﻰ ﺗﺪﻫﻮﺭ ﺣﺎﻟﺔ ﺍﻷﺟﺰﺍء ﺍﻟﻤﻌﺪﻧﻴﺔ‪ ،‬ﻣﻤﺎ ﻳﺘﺴﺒﺐ ﻓﻲ ﺗﻌﻄﻞ ﺍﻷﺟﺰﺍء ﺃﻭ ﺣﺪﻭﺙ ﺗﺴﺮﻳﺐ ﻣﻴﺎﻩ ﻟﻠﻮﺣﺪﺓ‪.‬‬
‫• ﻣﻨﻄﻘﺔ ﻣﻠﻴﺌﺔ ﺑﺰﻳﺖ ﻣﻌﺪﻧﻲ ﺃﻭ ﺗﺤﺘﻮﻱ ﻋﻠﻰ ﻣﻘﺪﺍﺭ ﻛﺒﻴﺮ ﻣﻦ ﺍﻟﺰﻳﺖ ﺃﻭ ﺍﻟﺒﺨﺎﺭ ﺍﻟﻤﺘﻄﺎﻳﺮ‪ ،‬ﻣﺜﻞ ﺍﻟﻤﻄﺒﺦ‪.‬‬
‫ﺳﻮﻑ ﺗﺆﺩﻱ ﺇﻟﻰ ﺗﺪﻫﻮﺭ ﺣﺎﻟﺔ ﺍﻷﺟﺰﺍء ﺍﻟﺒﻼﺳﺘﻴﻜﻴﺔ‪ ،‬ﻣﻤﺎ ﻳﺘﺴﺒﺐ ﻓﻲ ﺳﻘﻮﻁ ﺍﻷﺟﺰﺍء ﺃﻭ ﺣﺪﻭﺙ ﺗﺴﺮﻳﺐ ﻣﻴﺎﻩ ﻟﻠﻮﺣﺪﺓ‪.‬‬
‫• ﻣﻨﻄﻘﺔ ﺗﻨﺒﻌﺚ ﻣﻨﻬﺎ ﻣﻮﺍﺩ ﺗﺆﺛﺮ ﺳﻠﺒًﺎ ﻋﻠﻰ ﺍﻟﺠﻬﺎﺯ‪ ،‬ﻣﺜﻞ ﻏﺎﺯ ﻛﺒﺮﻳﺘﻲ‪ ،‬ﺃﻭ ﻏﺎﺯ ﺍﻟﻜﻠﻮﺭ ﺃﻭ ﺣﻤﺾ ﺃﻭ ﻣﺎﺩﺓ ﻗﻠﻮﻳﺔ‪.‬‬
‫ﺳﻮﻑ ﺗﺆﺩﻱ ﺇﻟﻰ ﺗﺂﻛﻞ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺍﻟﻨﺤﺎﺳﻴﺔ ﻭﺍﻟﻮﺻﻼﺕ ﺍﻟﻤﻠﺤﻮﻣﺔ‪ ،‬ﻣﻤﺎ ﻳﺘﺴﺒﺐ ﻓﻲ ﺗﺴﺮﻳﺐ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪.‬‬
‫• ﻣﻨﻄﻘﺔ ﺗﺆ ﺩ ﻱ ﺇ ﻟﻰ ﺗﺴﺮ ﻳﺐ ﻏﺎ ﺯ ﻗﺎ ﺑﻞ ﻟﻼ ﺷﺘﻌﺎ ﻝ ‪ ،‬ﺃ ﻭ ﺗﺤﺘﻮ ﻱ ﻋﻠﻰ ﺃ ﻟﻴﺎ ﻑ ﻛﺮ ﺑﻮ ﻧﻴﺔ ﻣﻌﻠﻘﺔ ﺃ ﻭ‬
‫ﻏﺒﺎ ﺭ ﻗﺎ ﺑﻞ ﻟﻼ ﺷﺘﻌﺎ ﻝ ‪ ،‬ﺃ ﻭ ﻣﻮ ﺍ ﺩ ﻣﺘﻄﺎ ﻳﺮ ﺓ ﻗﺎ ﺑﻠﺔ ﻟﻼ ﺷﺘﻌﺎ ﻝ ﻣﺜﻞ ﻣﺮ ﻗﻖ ﺍ ﻟﻄﻼ ء ﺃ ﻭ ﺍ ﻟﺒﻨﺰ ﻳﻦ ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﺴﺮﻳﺐ ﺍﻟﻐﺎﺯ ﻭﺍﺳﺘﻘﺮﺍﺭﻩ ﺣﻮﻝ ﺍﻟﻮﺣﺪﺓ‪ ،‬ﻓﻘﺪ ﻳﺆﺩﻱ ﺇﻟﻰ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫• ﻣﻨﻄﻘﺔ ﻳﻤﻜﻦ ﺃﻥ ﺗﺘﺒﻮﻝ ﻓﻴﻪ ﺍﻟﺤﻴﻮﺍﻧﺎﺕ ﻋﻠﻰ ﺍﻟﻮﺣﺪﺓ ﺃﻭ ﻳﺘﻢ ﺗﻜﻮﻳﻦ ﺍﻷﻣﻮﻧﻴﺎ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﺃﻏﺮﺍﺽ ﺧﺎﺻﺔ ﻣﺜﻞ ﺗﺨﺰﻳﻦ ﺍﻟﻄﻌﺎﻡ‪ ،‬ﺃﻭ ﺗﺮﺑﻴﺔ ﺍﻟﺤﻴﻮﺍﻧﺎﺕ ﺃﻭ ﺯﺭﺍﻋﺔ ﺍﻟﻨﺒﺎﺗﺎﺕ ﺃﻭ ﺣﻔﻆ ﺍﻷﺟﻬﺰﺓ ﺍﻟﺪﻗﻴﻘﺔ‬
‫ﺃﻭ ﺍﻷﻋﻤﺎﻝ ﺍﻟﻔﻨﻴﺔ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﺗﺘﺴﺒﺐ ﻓﻲ ﺗﺪﻧﻲ ﺟﻮﺩﺓ ﺍﻷﺷﻴﺎء ﺍﻟﻤﺤﻔﻮﻇﺔ ﺃﻭ ﺍﻟﻤﺨﺰﻧﺔ‪.‬‬
‫‪1‬‬
‫ﻻ ﺗﺮﻛﻴﺒﻬﺎ ﻓﻲ ﻣﻜﺎﻥ ﺣﻴﺚ ﻳﻮﺟﺪ ﺧﻄﺮ ﺗﺴﺮﻳﺐ ﻏﺎﺯ ﻗﺎﺑﻞ ﻟﻼﺷﺘﻌﺎﻝ‪.‬‬
‫ﻟﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻗﺎﻟﺐ‬
‫)ﺟﺰء ﻋﻠﻮﻱ ﻛﺮﺗﻮﻧﻲ(‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺑﺤﻴﺚ ﻻ ﻳﺘﺴﺒﺐ ﺍﻟﺼﺮﻑ ﻓﻲ ﺃﻱ ﻣﺸﻜﻠﺔ‪.‬‬
‫‪1‬‬
‫ﻓﻠﻜﺔ‬
‫ﻻ ﺗﺮﻛﺐ ﺍﻟﻮﺣﺪﺓ ﺑﺎﻟﻘﺮﺏ ﻣﻦ ﻣﺼﺪﺭ ﺣﺮﺍﺭﺓ ﺃﻭ ﺑﺨﺎﺭ ﺃﻭ ﻏﺎﺯ ﻗﺎﺑﻞ ﻟﻼﺷﺘﻌﺎﻝ‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻭﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻋﻠﻰ ﺑﻌﺪ ‪ 1‬ﻣﺘﺮ ﻋﻠﻰ ﺍﻷﻗﻞ ﻣﻦ ﺃﺟﻬﺰﺓ‬
‫ﺍﺳﺘﻘﺒﺎﻝ ﺍﻟﺘﻠﻴﻔﺰﻳﻮﻥ ﺃﻭ ﺍﻟﺮﺍﺩﻳﻮ‪ .‬ﻭﺍﻟﻐﺮﺽ ﻣﻦ ﺫﻟﻚ ﻫﻮ ﻣﻨﻊ ﺗﺪﺍﺧﻞ ﺍﺳﺘﻘﺒﺎﻝ ﺍﻟﺘﻠﻴﻔﺰﻳﻮﻥ ﺃﻭ ﺿﻮﺿﺎء ﺍﻟﺮﺍﺩﻳﻮ‪.‬‬
‫)ﺣﺘﻰ ﻟﻮ ﻗﻤﺖ ﺑﺎﻟﺘﺮﻛﻴﺐ ﻋﻠﻰ ﺑﻌﺪ ﺃﻛﺜﺮ ﻣﻦ ‪ 1‬ﻣﺘﺮ‪ ،‬ﻓﻤﻦ ﺍﻟﻤﻤﻜﻦ ﺃﻥ ﺗﺘﻠﻘﻰ ﺿﻮﺿﺎء ﻓﻲ ﺑﻌﺾ ﺍﻟﻈﺮﻭﻑ‪(.‬‬
‫ﻟﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﺇﺫﺍ ﻛﺎﻥ ﻣﻦ ﺍﻟﻤﻤﻜﻦ ﺍﻗﺘﺮﺍﺏ ﺃﻃﻔﺎﻝ ﺃﻗﻞ ﻣﻦ ‪ 10‬ﺳﻨﻮﺍﺕ ﻣﻦ ﺍﻟﻮﺣﺪﺓ‪ ،‬ﺍﺗﺨﺬ ﺇﺟﺮﺍءﺍﺕ ﻭﻗﺎﺋﻴﺔ ﺑﺤﻴﺚ ﻻ ﻳﻤﻜﻨﻬﻢ ﺍﻟﻮﺻﻮﻝ ﻟﻠﻮﺣﺪﺓ‪.‬‬
‫‪8‬‬
‫ﺣﺪﺩ ﻣﻮﺿﻊ ﺍﻟﺘﺮﻛﻴﺐ ﻣﻊ ﺍﻟﻌﻤﻴﻞ ﻛﺎﻟﺘﺎﻟﻲ‪:‬‬
‫ﻋﺎﺯﻝ‬
‫ﻟﺘﺮﻛﻴﺐ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫‪1‬‬
‫)‪ (1‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻓﻲ ﻣﻜﺎﻥ ﻗﻮﻱ ﺑﻤﺎ ﻳﻜﻔﻲ ﻟﺘﺤﻤﻞ ﻭﺯﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫)‪ (2‬ﻳﺠﺐ ﻋﺪﻡ ﺇﻋﺎﻗﺔ ﻣﻨﺎﻓﺬ ﺍﻹﺩﺧﺎﻝ ﻭﺍﻹﺧﺮﺍﺝ‪ ،‬ﻭﻳﺠﺐ ﺇﺗﺎﺣﺔ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﻓﻲ ﻛﺎﻓﺔ ﺃﻧﺤﺎء ﺍﻟﻐﺮﻓﺔ‪.‬‬
‫)‪ (3‬ﺍﺗﺮﻙ ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﻼﺯﻣﺔ ﻟﺼﻴﺎﻧﺔ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء‪.‬‬
‫ﻟﺘﺮﻛﻴﺐ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫‪) VP25‬ﻗﻄﺮ ﺧﺎﺭﺟﻲ ‪ ,32‬ﻗﻄﺮ ﺩﺍﺧﻠﻲ ‪(25‬‬
‫ﺧﺮﻃﻮﻡ ﺻﺮﻑ‬
‫‪1‬‬
‫)‪ (4‬ﻣﻜﺎﻥ ﻳﻤﻜﻦ ﻟﻠﻮﺣﺪﺓ ﻣﻨﻪ ﺗﻮﺯﻳﻊ ﺍﻟﻬﻮﺍء ﺑﺎﻟﺘﺴﺎﻭﻱ ﻓﻲ ﻛﺎﻓﺔ ﺃﻧﺤﺎء ﺍﻟﻐﺮﻓﺔ‪.‬‬
‫)‪ (5‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻳﻤﻜﻦ ﺇﺟﺮﺍء ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ )ﺃﻭ ﻭﺣﺪﺓ ‪ (RB‬ﺑﺴﻬﻮﻟﺔ‪.‬‬
‫)‪ (6‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻳﺴﻬﻞ ﻣﻨﻪ ﺗﺮﻛﻴﺐ ﻣﻮﺍﺳﻴﺮ ﺍﻟﻮﺻﻼﺕ‪.‬‬
‫ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ‬
‫ﻟﺘﺮﻛﻴﺐ ﺧﺮﻃﻮﻡ ﺍﻟﺼﺮﻑ‬
‫)‪ (7‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻳﺴﻬﻞ ﻣﻨﻪ ﺗﺮﻛﻴﺐ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺼﺮﻑ‪.‬‬
‫)‪ (8‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻻ ﻳﺘﻢ ﻓﻴﻪ ﺗﻀﺨﻴﻢ ﺍﻟﻀﻮﺿﺎء ﺃﻭ ﺍﻻﻫﺘﺰﺍﺯﺍﺕ‪.‬‬
‫‪1‬‬
‫)‪ (9‬ﺧﺬ ﻓﻲ ﺍﻻﻋﺘﺒﺎﺭ ﺃﻋﻤﺎﻝ ﺍﻟﺼﻴﺎﻧﺔ ﻭﺍﺗﺮﻙ ﺍﻟﻤﺴﺎﻓﺎﺕ ﺍﻟﻼﺯﻣﺔ‪ .‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻳﺘﻴﺢ ﺇﺯﺍﻟﺔ ﺍﻟﻤﺮﺷﺢ‪.‬‬
‫ﻟﺘﺮﻛﻴﺐ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫ﻋﺎﺯﻝ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫‪1‬‬
‫‪Ar-2‬‬
‫‪3/14/2016 4:32:19 PM‬‬
‫‪9371022451_IM_AR.indd 2‬‬
‫‪ .1.3.3‬ﺿﺒﻂ ﻣﻮﺿﻊ ﻓﺘﺤﺔ ﺍﻟﺴﻘﻒ ﻭﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ‬
‫‪ .2.3‬ﺃﺑﻌﺎﺩ ﺍﻟﺘﺮﻛﻴﺐ‬
‫)‪ (1‬ﻣﻮﺍﺿﻊ ﻓﺘﺤﺎﺕ ﺍﻟﺴﻘﻒ ﻭﻣﻴﻮﻝ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ ﻭﺍﻟﻤﻮﺍﺳﻴﺮ ﻭﺍﻟﻘﻨﻮﺍﺕ‪) .‬ﺍﻟﻮﺣﺪﺓ‪ :‬ﻣﻢ(‬
‫ﻳﺘﻢ ﺗﻮﺿﻴﺢ ﺍﺭﺗﻔﺎﻉ ﺍﻟﺴﻘﻒ ﻓﻲ ﺍﻟﺸﻜﻞ‪.‬‬
‫• ﻓﺘﺤﺔ ﺍﻟﺴﻘﻒ ﻭﻣﻴﻮﻝ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ‪.‬‬
‫‪ 256‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ )‪(AUXD18,24‬‬
‫‪ 298‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ )‪(AUXA30,36,45,54‬‬
‫‪ 950‬ﻣﻢ )ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ(‬
‫ﺳﻘﻒ ﻗﻮﻱ ﻭﻣﺘﻴﻦ‬
‫‪ 20‬ﺇﻟﻰ ‪ 45‬ﻣﻢ‬
‫‪ 860‬ﺇﻟﻰ ‪ 910‬ﻣﻢ )ﻓﺘﺤﺔ ﺍﻟﺴﻘﻒ(‬
‫‪ 840‬ﻣﻢ )ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ(‬
‫‪ 20‬ﺇﻟﻰ ‪ 45‬ﻣﻢ‬
‫‪ 1500‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‬
‫‪ 3000‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‬
‫‪ 20‬ﺇﻟﻰ ‪ 45‬ﻣﻢ‬
‫‪ 795‬ﻣﻢ )ﻣﻴﻮﻝ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ(‬
‫‪ 1800‬ﻣﻢ ﺇﻟﻰ ‪H‬‬
‫‪ 1000‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‬
‫‪ 950‬ﻣﻢ )ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ(‬
‫‪ 860‬ﺇﻟﻰ ‪ 910‬ﻣﻢ‬
‫)ﻓﺘﺤﺔ ﺍﻟﺴﻘﻒ(‬
‫‪ 80‬ﻣﻢ‬
‫ﻭﺿﻊ ﺍﻟﺴﻘﻒ ﺍﻟﻤﺮﺗﻔﻊ‬
‫‪3,500‬‬
‫‪3,500‬‬
‫‪3,600‬‬
‫‪4,200‬‬
‫‪4,200‬‬
‫‪4,200‬‬
‫‪ 130‬ﻣﻢ‬
‫ﺍﻟﻮﺿﻊ ﺍﻟﻘﻴﺎﺳﻲ‬
‫‪3,000‬‬
‫‪3,000‬‬
‫‪3,200‬‬
‫‪3,200‬‬
‫‪3,200‬‬
‫‪3,200‬‬
‫‪ 130‬ﻣﻢ‬
‫ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ‬
‫‪AUXD‬‬
‫‪18‬‬
‫‪AUXD‬‬
‫‪24‬‬
‫‪AUXA‬‬
‫‪30‬‬
‫‪AUXA‬‬
‫‪36‬‬
‫‪AUXA‬‬
‫‪45‬‬
‫‪AUXA‬‬
‫‪54‬‬
‫‪ 840‬ﻣﻢ )ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ(‬
‫‪ :H‬ﺃﻗﺼﻰ ﺍﺭﺗﻔﺎﻉ ﻣﻦ ﺍﻷﺭﺽ ﺇﻟﻰ ﺍﻟﺴﻘﻒ‬
‫‪) H‬ﻣﻢ(‬
‫‪ 699‬ﻣﻢ‬
‫)ﻣﻴﻮﻝ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ(‬
‫ﺍﻟﻌﺎﺋﻖ‬
‫ﺍﻷﺭﺿﻴﺔ‬
‫‪ 20‬ﺇﻟﻰ ‪ 45‬ﻣﻢ‬
‫* ﺗﺄﻛﺪ ﻣﻦ ﺿﺒﻂ ﺇﻋﺪﺍﺩﺍﺕ ﺍﻟﻮﻇﻴﻔﺔ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ً‬
‫ﻭﻓﻘﺎ ﻻﺭﺗﻔﺎﻉ ﺳﻘﻒ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫ﺇﻋﺪﺍﺩ ﺍﺗﺠﺎﻩ ﺗﻮﺯﻳﻊ ﺍﻟﻬﻮﺍء‬
‫‪ 50‬ﻣﻢ‬
‫‪ 200‬ﻣﻢ‬
‫‪ 130‬ﻣﻢ‬
‫• ﻳﻤﻜﻦ ﺍﺧﺘﻴﺎﺭ ﺍﺗﺠﺎﻩ ﺗﻮﺯﻳﻊ ﺍﻟﻬﻮﺍء ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﺃﺩﻧﺎﻩ‪.‬‬
‫‪A‬‬
‫‪B‬‬
‫‪ 40‬ﻣﻢ‬
‫‪ 10‬ﻣﻢ‬
‫‪ 140‬ﺇﻟﻰ ‪ 145‬ﻣﻢ‬
‫‪ 50‬ﺇﻟﻰ ‪ 100‬ﻣﻢ‬
‫‪ 4‬ﺍﺗﺠﺎﻫﺎﺕ‬
‫‪ 3‬ﺍﺗﺠﺎﻫﺎﺕ‬
‫‪ 100‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‬
‫ﺍﻟﻄﺮﺍﺯ‬
‫* ﺣﺪﺩ ﺃﻓﻀﻞ ﺍﺗﺠﺎﻩ ﻫﻮﺍء ﻣﻨﺎﺳﺐ ﻣﻦ ‪ 3‬ﺃﻭ ‪ 4‬ﺍﺗﺠﺎﻫﺎﺕ ﺗﺒﻌًﺎ ﻟﺸﻜﻞ ﺍﻟﻐﺮﻓﺔ ﻭﻣﻮﺿﻊ ﺍﻟﺘﺮﻛﻴﺐ‪.‬‬
‫* ﻋﻨﺪ ﺗﻐﻴﻴﺮ ﻋﺪﺩ ﺍﻟﻤﻨﺎﻓﺬ‪ ،‬ﻧﻮﺻﻲ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻃﻘﻢ ﻟﻮﺣﺔ ﻏﺎﻟﻖ ﻣﻨﻔﺬ ﺍﻟﻬﻮﺍء‪ ،‬ﻹﻏﻼﻕ ﺍﻟﻤﻨﻔﺬ‪.‬‬
‫ﻧﻈﺮﺍ‬
‫* ﺑﺎﻟﻨﺴﺒﺔ ﻟﻨﻤﻂ ﺇﻏﻼﻕ ﻣﻌﻴﻦ‪ ،‬ﻳﺮﺟﻰ ﺍﻟﺮﺟﻮﻉ ﺇﻟﻰ ﺩﻟﻴﻞ ﻃﻘﻢ ﻟﻮﺣﺔ ﻏﺎﻟﻖ ﻣﻨﻔﺬ ﺍﻟﻬﻮﺍء‪) .‬ﻗﻢ ﺑﺬﻟﻚ ﻗﺒﻞ ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ ً‬
‫ﻷﻧﻪ ﻳﺘﻢ ﺗﺮﻛﻴﺒﻬﺎ ﻋﻠﻰ ﺍﻟﺠﺴﻢ‪(.‬‬
‫‪AUXD18/24‬‬
‫‪AUXA30/36/45/54‬‬
‫‪A‬‬
‫‪B‬‬
‫‪256‬‬
‫‪246‬‬
‫‪298‬‬
‫‪288‬‬
‫• ﻣﻮﺍﺿﻊ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺘﺒﺮﻳﺪ ﻭﻣﻮﺍﺳﻴﺮ ﺍﻟﺼﺮﻑ‪.‬‬
‫‪ 10‬ﻣﻢ‬
‫‪ 80‬ﻣﻢ‬
‫‪ .3.3‬ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ‬
‫ﺗﺤﺬﻳﺮ‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﻓﻲ ﻣﻜﺎﻥ ﻳﻤﻜﻨﻪ ﺗﺤﻤﻞ ﺣﻤﻞ ﻳﻌﺎﺩﻝ ‪ 5‬ﺃﻣﺜﺎﻝ ﻭﺯﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺮﺋﻴﺴﻴﺔ ﻋﻠﻰ ﺍﻷﻗﻞ ﻭﻻ ﻳﻀﺨﻢ ﺍﻟﺼﻮﺕ‬
‫ﺃﻭ ﺍﻻﻫﺘﺰﺍﺯ‪ .‬ﺇﺫﺍ ﻟﻢ ﻳﻜﻦ ﻣﻜﺎﻥ ﺍﻟﺘﺮﻛﻴﺐ ﻗﻮﻳًﺎ ﺑﻤﺎ ﻳﻜﻔﻲ‪ ،‬ﻓﻘﺪ ﺗﺴﻘﻂ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺗﺴﺒﺐ ﺇﺻﺎﺑﺎﺕ‪.‬‬
‫ﺇﺫﺍ ﺗﻢ ﺗﻨﻔﻴﺬ ﺍﻟﻌﻤﻞ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺇﻃﺎﺭ ﺍﻟﻠﻮﺣﺔ ﻓﻘﻂ‪ ،‬ﻓﻬﻨﺎﻙ ﺧﻄﺮ ﺑﺄﻥ ﺗﺼﺒﺢ ﺍﻟﻮﺣﺪﺓ ﻣﻔﻜﻮﻛﺔ‪ .‬ﻳﺠﺐ ﺗﻮﺧﻲ ﺍﻟﺤﺬﺭ‪.‬‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﻐﺎﺯ‬
‫‪ 60‬ﻣﻢ‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺴﺎﺋﻞ‬
‫‪ 278‬ﻣﻢ‬
‫‪ 358‬ﻣﻢ‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫‪ 180‬ﻣﻢ‬
‫‪ 140‬ﻣﻢ‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫)ﺗﻮﺻﻴﻞ ﺑﺨﺮﻃﻮﻡ‬
‫ﺍﻟﺼﺮﻑ ﺍﻟﻤﺮﻓﻖ(‬
‫‪ 200‬ﻣﻢ‬
‫‪Ar-3‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 3‬‬
‫‪ .2.3.3‬ﺗﺤﻀﻴﺮﺍﺕ ﺍﻟﺘﻌﻠﻴﻖ‬
‫• ﻣﻮﺍﺿﻊ ﻗﻨﻮﺍﺕ ﺍﻟﺘﻮﺯﻳﻊ ﻭﻣﺪﺧﻞ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‪.‬‬
‫• ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ ﺑﺈﺣﻜﺎﻡ ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ﺍﻟﺸﻜﻞ ﺃﻭ ﺑﻄﺮﻳﻘﺔ ﺃﺧﺮﻯ‪.‬‬
‫ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻗﻨﺎﺓ ﺍﻟﺘﻮﺯﻳﻊ‬
‫• ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ ﻓﻲ ﻣﻜﺎﻥ ﻗﺎﺩﺭ ﻋﻠﻰ ﺗﺤﻤﻞ ﻭﺯﻥ ‪ 490‬ﻧﻴﻮﺗﻦ ﻟﻜﻞ ﻣﺴﻤﺎﺭ ﻋﻠﻰ ﺍﻷﻗﻞ‪.‬‬
‫ﻣﻮﺿﻊ ﻣﺪﺧﻞ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‬
‫ﻣﺜﺒﺖ ﺍﻟﻔﺘﺤﺔ‬
‫ﺧﺮﺳﺎﻧﺔ ﺳﺪﺍﺩﺓ ﺍﻟﻔﺘﺤﺔ‬
‫ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻗﻨﺎﺓ ﺍﻟﺘﻮﺯﻳﻊ‬
‫ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻗﻨﺎﺓ ﺍﻟﺘﻮﺯﻳﻊ‬
‫ﻭﻟﻴﺠﺔ‬
‫ﻣﺴﻤﺎﺭ ﺗﻌﻠﻴﻖ ‪M10‬‬
‫)ﻳﺘﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ(‬
‫ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻗﻨﺎﺓ ﺍﻟﺘﻮﺯﻳﻊ‬
‫‪ .3.3.3‬ﺗﺮﻛﻴﺐ ﺍﻟﺠﺴﻢ‬
‫• ﻣﺨﻄﻂ ﺗﻔﺼﻴﻠﻲ ﻟﻤﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻗﻨﺎﺓ ﺍﻟﺘﻮﺯﻳﻊ )‪ 4‬ﺟﻮﺍﻧﺐ(‬
‫‪ 100‬ﻣﻢ‬
‫‪ 100‬ﻣﻢ‬
‫)‪ (1‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﺼﺎﻣﻮﻟﺔ ﻭﺍﻟﻔﻠﻜﺔ )ﺍﻟﺘﻲ ﻳﺘﻢ ﺗﺤﻀﻴﺮﻫﺎ ﻓﻲ ﺍﻟﻤﻮﻗﻊ( ﻓﻲ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ‪.‬‬
‫‪ 83‬ﻣﻢ‬
‫‪ 83‬ﻣﻢ‬
‫‪ 185‬ﻣﻢ‬
‫)‪ (2‬ﻗﻢ ﺑﺘﻌﻠﻴﻖ ﺍﻟﺠﺴﻢ ﻓﻲ ﻣﺴﻤﺎﺭ ﺍﻟﺘﻌﻠﻴﻖ‪.‬‬
‫ﻗﻄﻊ‬
‫)‪ (3‬ﺍﺿﺒﻂ ﺃﺑﻌﺎﺩ ﺳﻄﺢ ﺍﻟﺴﻘﻒ ﻣﻦ ﺍﻟﺠﺴﻢ‪.‬‬
‫‪ 90‬ﻣﻢ‬
‫ﺑﻌﺪ ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‪ ،‬ﻳﻤﻜﻨﻚ ﻋﻤﻞ ﺗﻀﺒﻴﻄﺎﺕ ﻋﻠﻰ ﺍﺭﺗﻔﺎﻉ ﺍﻟﺠﺴﻢ‪ .‬ﻟﻤﻌﺮﻓﺔ ﺍﻟﺘﻔﺎﺻﻴﻞ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‪.‬‬
‫ﺗﺤﺬﻳﺮ‬
‫ﻗﻢ ﺑﻌﻤﻞ ﺍﻟﺮﺑﻂ ﺍﻟﻨﻬﺎﺋﻲ ﻣﻦ ﺧﻼﻝ ﺭﺑﻂ ﺍﻟﺼﺎﻣﻮﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ ﺑﺈﺣﻜﺎﻡ‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﺠﺴﻢ ﺃﻓﻘﻴًﺎ ﻭﺍﺿﺒﻂ ﺍﻻﺭﺗﻔﺎﻉ ﺃﺳﻔﻞ ﺍﻟﺠﺴﻢ ﻭﺳﻄﺢ ﺍﻟﺴﻘﻒ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪.‬‬
‫ﻓﺘﺤﺔ ‪ × 10‬ﻗﻄﺮ ‪ 2.5‬ﻣﻢ‬
‫‪ 352‬ﻣﻢ‬
‫• ﻣﻮﺿﻊ ﻣﺪﺧﻞ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‬
‫‪ 250‬ﻣﻢ‬
‫ﻣﺴﻤﺎﺭ ﺗﻌﻠﻴﻖ‬
‫)ﻳﺘﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ(‬
‫ﻗﻄﺮ ‪ 88‬ﻣﻢ‬
‫ﻗﻄﺮ ‪ 70‬ﻣﻢ‬
‫ﻣﻴﻞ ﻓﺘﺤﺔ ﺑﻴﺮﻟﻨﺞ‬
‫‪ 185‬ﻣﻢ‬
‫ﻗﻄﻊ‬
‫ﺻﺎﻣﻮﻟﺔ ‪A‬‬
‫)ﻳﺘﻢ ﺷﺮﺍﺅﻫﺎ ﻣﺤﻠﻴًﺎ(‬
‫ﻓﻠﻜﺔ‬
‫)ﺍﻟﻤﻠﺤﻘﺎﺕ(‬
‫‪ 30‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‬
‫ﺑﻌﺪ ﺗﺜﺒﻴﺖ ﺍﻟﺠﺴﻢ‪ ,‬ﺍﺭﺑﻂ ﺍﻟﺼﻤﺎﻭﻳﻞ‪.‬‬
‫ﻓﺘﺤﺔ ‪ × 4‬ﻗﻄﺮ ‪ 2.5‬ﻣﻢ‬
‫ﻣﻼﺣﻈﺔ‪:‬‬
‫ﻳﺠﺐ ﺗﻄﺒﻴﻖ ﺍﻟﻌﺰﻝ ﺍﻟﺼﺤﻴﺢ ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﻗﻨﻮﺍﺕ ﺍﻟﺘﻮﺯﻳﻊ ﻭﻣﺪﺧﻞ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‪.‬‬
‫ﺻﺎﻣﻮﻟﺔ ‪) B‬ﺻﺎﻣﻮﻟﺔ ﻣﺰﺩﻭﺟﺔ(‬
‫)ﻳﺘﻢ ﺷﺮﺍﺅﻫﺎ ﻣﺤﻠﻴًﺎ(‬
‫ﻓﻠﻜﺔ‬
‫)ﺍﻟﻤﻠﺤﻘﺎﺕ(‬
‫ﻋﺎﺯﻝ‬
‫‪ 10‬ﺇﻟﻰ ‪ 15‬ﻣﻢ‬
‫‪ .4.3.3‬ﺿﺒﻂ ﺍﻟﻤﺴﺘﻮﻯ‬
‫• ﺍﺳﺘﺨﺪﻡ ﻣﻴﺰﺍﻥ ﻣﻴﺎﻩ‪ ،‬ﺃﻭ ﺧﺮﻃﻮﻡ ﻣﻴﺎﻩ ﻣﻠﻲء ﺑﺎﻟﻤﺎء‪ ،‬ﻭﻗﻢ ﺑﻌﻤﻞ ﺿﺒﻂ ﺩﻗﻴﻖ ﺑﺤﻴﺚ ﻳﻜﻮﻥ ﺍﻟﺠﺴﻢ ﻣﺴﺘﻮﻳًﺎ‪.‬‬
‫• ﻳﺆﺩﻱ ﺍﻟﺘﺮﻛﻴﺐ ﺍﻟﻤﺎﺋﻞ ﺣﻴﻦ ﻳﻜﻮﻥ ﺟﺎﻧﺐ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ ﻋﺎﻟﻴًﺎ ﺇﻟﻰ ﺗﻌﻄﻞ ﻣﻔﺘﺎﺡ ﺍﻟﻄﻔﻮ ﻭﻗﺪ ﻳﺴﺒﺐ ﺗﺴﺮﺏ ﻓﻲ ﺍﻟﻤﻴﺎﻩ‪.‬‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫ﻣﻮﺿﻊ ﻣﺪﺧﻞ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‬
‫* ﻋﻨﺪ ﺍﻣﺘﺼﺎﺹ ﺍﻟﻬﻮﺍء ﺍﻟﻨﻘﻲ‪ ،‬ﻳﺮﺟﻰ ﻓﺼﻞ ﺍﻟﻌﺎﺯﻝ ﺍﻟﻤﻠﺤﻖ ﺑﻮﻋﺎء ﺍﻟﺼﺮﻑ‪.‬‬
‫)‪ (2‬ﺇﻋﺪﺍﺩ ﻣﻮﺍﺿﻊ ﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ ﻭﻓﺘﺤﺎﺕ ﺍﻟﺴﻘﻒ‪.‬‬
‫ﺧﺮﺍﻃﻴﻢ ﻓﻴﻨﻴﻞ‬
‫• ﺍﺳﺘﺨﺪﻡ ﻗﺎﻟﺐ ﺗﺮﻛﻴﺐ )ﺍﻟﺴﻄﺢ ﺍﻟﻌﻠﻮﻱ ﻟﻠﻌﺒﻮﺓ( ﻹﻋﺪﺍﺩ ﻣﻮﺍﺿﻊ ﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ ﻭﻓﺘﺤﺎﺕ ﺍﻟﺴﻘﻒ ﻭﺧﺮﻡ ﺍﻟﺜﻘﻮﺏ‪.‬‬
‫)‪ (3‬ﻫﻴﻜﻞ ﺍﻟﺘﻌﻠﻴﻖ‪.‬‬
‫• ﺣﺪﺩ ﻫﻴﻜﻞ ﻗﻮﻱ ﻟﻤﻜﺎﻥ ﺍﻟﺘﻌﻠﻴﻖ‪.‬‬
‫• ﺇﺫﺍ ﻟﺰﻡ ﺍﻷﻣﺮ‪ ،‬ﻗﻢ ﺑﺘﻘﻮﻳﺔ ﻣﺴﺎﻣﻴﺮ ﺍﻟﺘﻌﻠﻴﻖ ﺑﻤﺎﺩﺓ ﺩﻋﻢ ﻋﻤﻮﺩﻳﺔ ﻣﻀﺎﺩﺓ ﻟﻠﺰﻻﺯﻝ ﻟﻤﻨﻊ ﺍﻻﻫﺘﺰﺍﺯ‪.‬‬
‫• ﺍﺳﺘﺨﺪﻡ ﻣﺴﺎﻣﻴﺮ ﺗﻌﻠﻴﻖ ﻣﻘﺎﺱ ‪ M8‬ﺇﻟﻰ ‪.M10‬‬
‫‪Ar-4‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 4‬‬
‫‪ .4‬ﺗﺮﻛﻴﺐ ﺍﻟﻤﺎﺳﻮﺭﺓ‬
‫‪ .3.4‬ﻭﺻﻠﺔ ﺗﻔﻠﻴﺞ )ﻭﺻﻠﺔ ﺍﻟﻤﺎﺳﻮﺭﺓ(‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺗﻮﺥ ﺍﻟﺤﺬﺭ ﺣﺘﻰ ﻻ ﺗﺪﺧﻞ ﻣﺎﺩﺓ ﻏﺮﻳﺒﺔ )ﺍﻟﺰﻳﺖ ﺃﻭ ﺍﻟﻤﻴﺎﻩ ﺃﻭ ﻏﻴﺮﻩ( ﻓﻲ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺑﺨﻼﻑ ﻃﺮﺍﺯﺍﺕ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ‪.R410A‬‬
‫ً‬
‫ﺃﻳﻀﺎ‪ ،‬ﻋﻨﺪ ﺗﺨﺰﻳﻦ ﺍﻟﻤﻮﺍﺳﻴﺮ‪ ،‬ﻗﻢ ﺑﺴﺪ ﺍﻟﻔﺘﺤﺎﺕ ﺑﺈﺣﻜﺎﻡ ﻣﻦ ﺧﻼﻝ ﺍﻟﻘﺮﺹ ﺃﻭ ﺍﻟﺮﺑﻂ ﺃﻭ ﻏﻴﺮﻩ‪.‬‬
‫ﺍﺭﺑﻂ ﺍﻟﺼﻤﺎﻭﻳﻞ ﺍﻟﻤﻔﻠﺠﺔ ﺑﻤﻔﺘﺎﺡ ﺭﺑﻂ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻃﺮﻳﻖ ﺍﻟﺮﺑﻂ ﺍﻟﻤﺤﺪﺩﺓ‪ .‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻳﻤﻜﻦ ﺃﻥ ﺗﻨﻜﺴﺮ ﺍﻟﺼﻤﺎﻭﻳﻞ ﺍﻟﻤﻔﻠﺠﺔ ﺑﻌﺪ‬
‫ﻓﺘﺮﺓ ﻃﻮﻳﻠﺔ‪ ،‬ﻣﻤﺎ ﻳﺘﺴﺒﺐ ﻓﻲ ﺗﺴﺮﺏ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻭﺗﻜﻮﻳﻦ ﻏﺎﺯ ﺧﻄﺮ ﻓﻲ ﺣﺎﻟﺔ ﺍﺗﺼﺎﻝ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺑﺎﻟﻠﻬﺐ‪.‬‬
‫ﻋﻨﺪ ﻟﺤﺎﻡ ﺍﻟﻤﻮﺍﺳﻴﺮ‪ ،‬ﺗﺄﻛﺪ ﻣﻦ ﻧﻔﺦ ﻏﺎﺯ ﺍﻟﻨﻴﺘﺮﻭﺟﻴﻦ ﺍﻟﺠﺎﻑ ﻋﺒﺮﻫﺎ‪.‬‬
‫‪ .1.3.4‬ﺍﻟﺘﻔﻠﻴﺞ‬
‫ﺍﺳﺘﺨﺪﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻴﺞ ﺧﺎﺻﺔ ﺑـ ‪.R410A‬‬
‫‪ .1.4‬ﺍﺧﺘﻴﺎﺭ ﻣﺎﺩﺓ ﺍﻟﻤﺎﺳﻮﺭﺓ‬
‫)‪ (1‬ﺍﻗﻄﻊ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﻮﺻﻴﻞ ﺣﺴﺐ ﺍﻟﻄﻮﻝ ﺍﻟﻀﺮﻭﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻗﺎﻃﻊ ﻣﻮﺍﺳﻴﺮ‪.‬‬
‫ﺗﻨﺒﻴﻪ‬
‫)‪ (2‬ﺃﻣﺴﻚ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻷﺳﻔﻞ ﺑﺤﻴﺚ ﻻ ﺗﺪﺧﻞ ﻗﺼﺎﺻﺎﺕ ﺍﻟﻘﻄﻊ ﻓﻲ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻭﻗﻢ ﺑﺈﺯﺍﻟﺔ ﺃﻱ ﺷﻮﺍﺋﺐ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﻣﻮﺍﺳﻴﺮ ﻣﻮﺟﻮﺩﺓ ﻣﻦ ﻧﻈﺎﻡ ﺗﺒﺮﻳﺪ ﺁﺧﺮ ﺃﻭ ﺧﺎﺻﺔ ﺑﺴﺎﺋﻞ ﺗﺒﺮﻳﺪ ﺁﺧﺮ‪.‬‬
‫)‪ (3‬ﺃﺩﺧﻞ ﺍﻟﺼﺎﻣﻮﻟﺔ ﺍﻟﻤﻔﻠﺠﺔ )ﺍﺳﺘﺨﺪﻡ ﺩﺍﺋﻤًﺎ ﺍﻟﺼﺎﻣﻮﻟﺔ ﺍﻟﻤﻔﻠﺠﺔ ﺍﻟﻤﻠﺤﻘﺔ ﻓﻲ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺍﻟﺨﺎﺭﺟﻴﺔ )ﺃﻭ ﻭﺣﺪﺓ ‪ (RB‬ﻋﻠﻰ‬
‫ﺍﺳﺘﺨﺪﻡ ﻣﻮﺍﺳﻴﺮ ﺫﺍﺕ ﺟﻮﺍﻧﺐ ﺩﺍﺧﻠﻴﺔ ﻭﺧﺎﺭﺟﻴﺔ ﻧﻈﻴﻔﺔ ﺑﺪﻭﻥ ﺃﻱ ﺗﻠﻮﺙ ﻳﺆﺩﻱ ﺇﻟﻰ ﻣﺸﻜﻠﺔ ﺃﺛﻨﺎء ﺍﻻﺳﺘﺨﺪﺍﻡ‪ ،‬ﻣﺜﻞ ﺍﻟﺮﺻﺎﺹ ﺃﻭ‬
‫ﺍﻷﻛﺴﻴﺪ ﺃﻭ ﺍﻟﻐﺒﺎﺭ ﺃﻭ ﺑﻘﺎﻳﺎ ﺍﻟﻘﻄﻊ ﺃﻭ ﺍﻟﺰﻳﺖ ﺃﻭ ﺍﻟﻤﺎء‪.‬‬
‫ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺍﺳﺘﺨﺪﺍﻡ ﻣﻮﺍﺳﻴﺮ ﻧﺤﺎﺱ ﻋﺪﻳﻤﺔ ﺍﻻﻟﺘﺤﺎﻡ‪.‬‬
‫ﺍﻟﻤﺎﺩﺓ‪ :‬ﻣﻮﺍﺳﻴﺮ ﻧﺤﺎﺱ ﻋﺪﻳﻤﺔ ﺍﻻﻟﺘﺤﺎﻡ ﻣﺨﺘﺰﻟﺔ ﺑﺎﻟﻔﺴﻔﻮﺭ‬
‫ﻳﻮﺻﻰ ﺑﺄﻥ ﻳﻜﻮﻥ ﻣﻘﺪﺍﺭ ﺍﻟﺰﻳﺖ ﺍﻟﻤﺘﺒﻘﻲ ﺃﻗﻞ ﻣﻦ ‪ 40‬ﻣﺠﻢ‪ 10/‬ﻣﺘﺮ‪.‬‬
‫ﺍﻟﺘﻮﺍﻟﻲ( ﻓﻲ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻭﻗﻢ ﺑﺘﻨﻔﻴﺬ ﻋﻤﻠﻴﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻴﺞ‪ .‬ﺍﺳﺘﺨﺪﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻴﺞ ﺧﺎﺻﺔ ﺑـ ‪ .R410A‬ﻗﺪ ﻳﺤﺪﺙ ﺗﺴﺮﻳﺐ‬
‫ﻟﺴﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺘﺨﺪﺍﻡ ﺻﻤﺎﻭﻳﻞ ﻣﻔﻠﺠﺔ ﺃﺧﺮﻯ‪.‬‬
‫)‪ (4‬ﻗﻢ ﺑﺤﻤﺎﻳﺔ ﺍﻟﻤﻮﺍﺳﻴﺮ ﻣﻦ ﺧﻼﻕ ﻗﺮﺻﻬﺎ ﺃﻭ ﻟﺼﻘﻬﺎ ﻟﻤﻨﻊ ﺩﺧﻮﻝ ﺍﻷﺗﺮﺑﺔ ﺃﻭ ﺍﻟﻐﺒﺎﺭ ﺃﻭ ﺍﻟﻤﻴﺎﻩ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﻣﻮﺍﺳﻴﺮ ﻧﺤﺎﺱ ﺗﻌﺮﺿﺖ ﻟﻠﺘﻠﻒ ﺃﻭ ﺍﻟﻜﺴﺮ ﺃﻭ ﺗﻐﻴﺮ ﻟﻮﻥ ﺃﺟﺰﺍﺋﻬﺎ )ﺧﺎﺻﺔ ﺍﻟﺴﻄﺢ ﺍﻟﺪﺍﺧﻠﻲ(‪ .‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﻳﺘﻌﺮﺽ‬
‫ﺻﻤﺎﻡ ﺍﻟﺘﻮﺳﻌﺔ ﺃﻭ ﺍﻷﻧﺒﻮﺏ ﺍﻟﺸﻌﺮﻱ ﻟﻼﻧﺴﺪﺍﺩ ﺑﺎﻟﻤﻠﻮﺛﺎﺕ‪.‬‬
‫ﺍﻓﺤﺺ ﻣﺎ ﺇﺫﺍ ﺗﻢ ﺗﻔﻠﻴﺞ ]‪ [L‬ﺑﺸﻜﻞ ﻣﺘﺴﻖ ﺃﻡ ﻻ ﻭﺃﻧﻪ‬
‫ﻟﻢ ﻳﺘﻌﺮﺽ ﻟﻠﻜﺴﺮ ﺃﻭ ﺍﻟﺨﺪﺵ‪.‬‬
‫‪B‬‬
‫ﻧﻈﺮﺍ ﻷﻥ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﺍﻟﺬﻱ ﻳﺴﺘﺨﺪﻡ ‪ R410A‬ﻳﺘﻌﺮﺽ ﻟﻀﻐﻂ‬
‫ﻳﺆﺩﻱ ﺍﺧﺘﻴﺎﺭ ﺍﻟﻤﻮﺍﺳﻴﺮ ﻏﻴﺮ ﺍﻟﺼﺤﻴﺤﺔ ﺇﻟﻰ ﺗﺮﺍﺟﻊ ﺍﻷﺩﺍء‪ً .‬‬
‫ﺃﻋﻠﻰ ﻣﻦ ﺍﺳﺘﺨﺪﺍﻡ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﺍﻟﺘﻘﻠﻴﺪﻱ )‪ ،(R22‬ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺍﺧﺘﻴﺎﺭ ﻣﻮﺍﺩ ﻣﻨﺎﺳﺒﺔ‪.‬‬
‫ﻗﺎﻟﺐ‬
‫• ﻳﺘﻢ ﺗﻮﺿﻴﺢ ﺳﻤﺎﻛﺔ ﻣﻮﺍﺳﻴﺮ ﺍﻟﻨﺤﺎﺱ ﺍﻟﻤﺴﺘﺨﺪﻣﺔ ﻣﻊ ‪ R410A‬ﻓﻲ ﺍﻟﺠﺪﻭﻝ‪.‬‬
‫‪A‬‬
‫• ﻻ ﺗﺴﺘﺨﺪﻡ ﻣﻮﺍﺳﻴﺮ ﻧﺤﺎﺱ ﺃﺭﻓﻊ ﻣﻦ ﺗﻠﻚ ﺍﻟﻤﺒﻴﻨﺔ ﻓﻲ ﺍﻟﺠﺪﻭﻝ ﺣﺘﻰ ﻟﻮ ﻛﺎﻧﺖ ﻣﺘﺎﺣﺔ ﻓﻲ ﺍﻟﺴﻮﻕ‪.‬‬
‫‪L‬‬
‫ﻣﺎﺳﻮﺭﺓ‬
‫ﺳﻤﺎﻛﺔ ﻣﻮﺍﺳﻴﺮ ﺍﻟﻨﺤﺎﺱ ﺍﻟﻤﻠﺪﻧﺔ )‪(R410A‬‬
‫ﺍﻟﺴﻤﺎﻛﺔ ]ﻣﻢ[‬
‫‪0.80‬‬
‫ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ﻟﻠﻤﺎﺳﻮﺭﺓ ]ﻣﻢ )ﺑﻮﺻﺔ([‬
‫‪(1/4) 6.35‬‬
‫‪(3/8) 9.52‬‬
‫‪0.80‬‬
‫‪(1/2) 12.70‬‬
‫‪(5/8) 15.88‬‬
‫‪(3/4) 19.05‬‬
‫‪0.80‬‬
‫‪1.00‬‬
‫‪1.20‬‬
‫‪ .2.4‬ﻣﺘﻄﻠﺒﺎﺕ ﺍﻟﻤﺎﺳﻮﺭﺓ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻭﺻﻒ ﻃﻮﻝ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻬﺎ ﻭﻓﺮﻕ ﺍﻻﺭﺗﻔﺎﻉ‪.‬‬
‫ﺍﺳﺘﺨﺪﻡ ﻣﻮﺍﺳﻴﺮ ﺫﺍﺕ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﻣﻘﺎﻭﻡ ﻟﻠﻤﺎء‪.‬‬
‫ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ﻟﻠﻤﺎﺳﻮﺭﺓ‬
‫]ﻣﻢ )ﺑﻮﺻﺔ([‬
‫ﺍﻟﺒُﻌﺪ ‪] A‬ﻣﻢ[‬
‫ﺃﺩﺍﺓ ﺍﻟﺘﻔﻠﻴﺞ ﻟـ ‪ ،R410A‬ﻣﻦ ﻧﻮﻉ‬
‫ﺍﻟﻘﺎﺑﺾ‬
‫‪(1/4) 6.35‬‬
‫‪(3/8) 9.52‬‬
‫‪(1/2) 12.70‬‬
‫‪(5/8) 15.88‬‬
‫‪(3/4) 19.05‬‬
‫‪ 0‬ﺇﻟﻰ ‪0.5‬‬
‫ﺍﻟﺒﻌﺪ ‪] B-00.4‬ﻣﻢ[‬
‫‪9.1‬‬
‫‪13.2‬‬
‫‪16.6‬‬
‫‪19.7‬‬
‫‪24.0‬‬
‫ﻋﻨﺪ ﺍﺳﺘﺨﺪﺍﻡ ﺃﺩﻭﺍﺕ ﺍﻟﺘﻔﻠﻴﺞ ﺍﻟﺘﻘﻠﻴﺪﻳﺔ )‪ (R22‬ﻟﺘﻔﻠﻴﺞ ﻣﻮﺍﺳﻴﺮ ‪ ،R410A‬ﻳﺠﺐ ﺃﻥ ﻳﻜﻮﻥ ﺍﻟﺒﻌﺪ ‪ A‬ﺃﻛﺒﺮ ﺑﻤﻘﺪﺍﺭ ‪ 0.5‬ﻣﻢ ﺗﻘﺮﻳﺒًﺎ ﻣﻦ‬
‫ﺍﻟﺒﻌﺪ ﺍﻟﻤﺒﻴﻦ ﻓﻲ ﺍﻟﺠﺪﻭﻝ )ﻟﻠﺘﻔﻠﻴﺞ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺃﺩﻭﺍﺕ ﺗﻔﻠﻴﺞ ‪ (R410A‬ﻭﺫﻟﻚ ﻟﺘﺤﻘﻴﻖ ﺍﻟﺘﻔﻠﻴﺞ ﺍﻟﻤﺤﺪﺩ‪ .‬ﺍﺳﺘﺨﺪﻡ ﻣﻘﻴﺎﺱ ﺳﻤﺎﻛﺔ ﻟﻘﻴﺎﺱ‬
‫ﺍﻟﺒُﻌﺪ ‪ .A‬ﻳﻮﺻﻰ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺃﺩﺍﺓ ﺗﻔﻠﻴﺞ ﺧﺎﺻﺔ ﺑـ ‪.R410A‬‬
‫ﺍﻟﻌﺮﺽ ﻋﺒﺮ‬
‫ﺍﻟﻤﺴﻄﺤﺎﺕ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺣﻮﻝ ﻛﻞ ﻣﻦ ﻣﻮﺍﺳﻴﺮ ﺍﻟﻐﺎﺯ ﻭﺍﻟﺴﺎﺋﻞ‪ .‬ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﻟﻘﻴﺎﻡ ﺑﺬﻟﻚ ﻗﺪ ﻳﺆﺩﻱ ﺇﻟﻰ ﺗﺴﺮﻳﺐ ﻓﻲ ﺍﻟﻤﻴﺎﻩ‪.‬‬
‫ﺍﺳﺘﺨﺪﻡ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﺑﻤﻘﺎﻭﻣﺔ ﺣﺮﺍﺭﺓ ﺗﺰﻳﺪ ﻋﻦ ‪ 120‬ﺩﺭﺟﺔ ﻣﺌﻮﻳﺔ )ﻃﺮﺍﺯ ﺍﻟﺪﻭﺭﺓ ﺍﻟﻌﻜﺴﻴﺔ ﻓﻘﻂ(‬
‫ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻚ‪ ،‬ﺇﺫﺍ ﻛﺎﻥ ﻣﺴﺘﻮﻯ ﺍﻟﺮﻃﻮﺑﺔ ﻓﻲ ﻣﻜﺎﻥ ﺗﺮﻛﻴﺐ ﻣﺎﺳﻮﺭﺓ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ ﻣﻦ ﺍﻟﻤﺘﻮﻗﻊ ﺃﻥ ﻳﺘﺠﺎﻭﺯ ‪ ,% 70‬ﻓﻘﻢ‬
‫ﺑﺘﺮﻛﻴﺐ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﺣﻮﻝ ﻣﺎﺳﻮﺭﺓ ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪ .‬ﻭﺇﺫﺍ ﻛﺎﻥ ﻣﺴﺘﻮﻯ ﺍﻟﺮﻃﻮﺑﺔ ﺍﻟﻤﺘﻮﻗﻊ ‪ 70‬ﺇﻟﻰ ‪ ,% 80‬ﺍﺳﺘﺨﺪﻡ ﻋﺎﺯﻝ‬
‫ﺑﺴﻤﻚ ‪ 20‬ﻣﻢ ﺃﻭ ﺃﻛﺒﺮ‪.‬‬
‫ﺑﺴﻤﻚ ‪ 15‬ﻣﻢ ﺃﻭ ﺃﻛﺒﺮ ﻭﺇﺫﺍ ﻛﺎﻧﺖ ﺍﻟﺮﻃﻮﺑﺔ ﺍﻟﻤﺘﻮﻗﻌﺔ ﺗﺘﺠﺎﻭﺯ ‪ ,% 80‬ﺍﺳﺘﺨﺪﻡ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ُ‬
‫ﺣﺮﺍﺭﻱ ُ‬
‫ﺑﺎﻟﺴﻤﻚ ﺍﻟﻤﺤﺪﺩ‪ ،‬ﻗﺪ ﻳﺘﻜﻮﻥ ﺗﻜﺜﻒ ﻋﻠﻰ ﺳﻄﺢ ﺍﻟﻌﺎﺯﻝ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻚ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ‬
‫ﺇﺫﺍ ﻟﻢ ﻳﻜﻦ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ُ‬
‫ﺑﻘﺪﺭﺓ ﺗﻮﺻﻴﻞ ﺣﺮﺍﺭﺓ ‪ 0.045‬ﻭﺍﺕ‪)/‬ﻣﻴﻠﻲ ﻛﻴﻠﻔﻦ( ﺃﻭ ﺃﻗﻞ )ﻋﻨﺪ ‪ 20‬ﺩﺭﺟﺔ ﻣﺌﻮﻳﺔ(‪.‬‬
‫ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ﻟﻠﻤﺎﺳﻮﺭﺓ‬
‫]ﻣﻢ )ﺑﻮﺻﺔ([‬
‫ﺍﻟﻌﺮﺽ ﻋﺒﺮ ﻣﺴﻄﺤﺎﺕ ﺍﻟﺼﺎﻣﻮﻟﺔ ﺍﻟﻤﻔﻠﺠﺔ‬
‫]ﻣﻢ[‬
‫‪(1/4) 6.35‬‬
‫‪17‬‬
‫‪(3/8) 9.52‬‬
‫‪22‬‬
‫‪(1/2) 12.70‬‬
‫‪26‬‬
‫‪(5/8) 15.88‬‬
‫‪29‬‬
‫‪(3/4) 19.05‬‬
‫‪36‬‬
‫‪ .2.3.4‬ﺛﻨﻲ ﺍﻟﻤﻮﺍﺳﻴﺮ‬
‫• ﻓﻲ ﺣﺎﻟﺔ ﺗﺸﻜﻴﻞ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺑﺎﻟﻴﺪ‪ ،‬ﺗﻮﺥ ﺍﻟﺤﺬﺭ ﺣﺘﻰ ﻻ ﺗﺘﻠﻔﻬﺎ‪.‬‬
‫• ﻻ ﺗﺜﻨﻲ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺑﺰﺍﻭﻳﺔ ﺗﺰﻳﺪ ﻋﻦ ‪ 90‬ﺩﺭﺟﺔ‪.‬‬
‫• ﻋﻨﺪ ﺛﻨﻲ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺑﺸﻜﻞ ﻣﺘﻜﺮﺭ ﺃﻭ ﺗﻤﺪﻳﺪﻫﺎ‪ ،‬ﺳﻮﻑ ﺗﺼﺒﺢ ﺍﻟﻤﺎﺩﺓ ﻣﺘﺼﻠﺒﺔ‪ ،‬ﻣﻤﺎ ﻳﺼﻌﺐ ﺛﻨﻴﻬﺎ ﺃﻭ ﺗﻤﺪﻳﺪﻫﺎ ﻣﺮﺓ ﺃﺧﺮﻯ‪.‬‬
‫• ﻻ ﺗﺜﻨﻲ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺗﻤﺪﻫﺎ ﻷﻛﺜﺮ ﻣﻦ ‪ 3‬ﻣﺮﺍﺕ‪.‬‬
‫ﺗﻨﺒﻴﻪ‬
‫ﻟﺘﻔﺎﺩﻱ ﻛﺴﺮ ﺍﻟﻤﺎﺳﻮﺭﺓ‪ ،‬ﺗﺠﻨﺐ ﻋﻤﻞ ﺛﻨﻴﺎﺕ ﺣﺎﺩﺓ‪.‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺛﻨﻲ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻋﺪﺓ ﻣﺮﺍﺕ ﻓﻲ ﻧﻔﺲ ﺍﻟﻤﻜﺎﻥ‪ ،‬ﻓﺴﻮﻑ ﺗﻨﻜﺴﺮ‪.‬‬
‫‪Ar-5‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 5‬‬
‫‪ .3.3.4‬ﺗﻮﺻﻴﻞ ﺍﻟﻤﺎﺳﻮﺭﺓ‬
‫‪ .5‬ﺗﺮﻛﻴﺐ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺼﺮﻑ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺗﺄﻛﺪ ﻣﻦ ﺗﺮﻛﻴﺐ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻣﻘﺎﺑﻞ ﺍﻟﻤﻨﻔﺬ ﻓﻲ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪ .‬ﺇﺫﺍ ﻛﺎﻥ ﺍﻟﺘﻮﺳﻴﻂ ﻏﻴﺮ ﺻﺤﻴﺢ‪،‬‬
‫ﻓﻼ ﻳﻤﻜﻦ ﺭﺑﻂ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺸﻜﻞ ﺳﻠﺲ‪ .‬ﻓﻲ ﺣﺎﻟﺔ ﺇﺩﺍﺭﺓ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺎﻟﻘﻮﺓ‪ ،‬ﺳﻮﻑ ﺗﺘﻠﻒ ﺍﻟﺘﺴﻨﻴﻨﺎﺕ‪.‬‬
‫ﺗﺤﺬﻳﺮ‬
‫ﻻ ﺗﺪﺧﻞ ﻣﻮﺍﺳﻴﺮ ﺍﻟﺼﺮﻑ ﻓﻲ ﺍﻟﺒﻼﻋﺔ ﺍﻟﺘﻲ ﻳﺘﻜﻮﻥ ﻓﻴﻬﺎ ﻏﺎﺯ ﻛﺒﺮﻳﺘﻴﺘﻲ‪) .‬ﻗﺪ ﻳﺤﺪﺙ ﺗﺂﻛﻞ ﻟﻠﻤﺒﺎﺩﻝ ﺍﻟﺤﺮﺍﺭﻱ(‬
‫ﻻ ﺗﻘﻢ ﺑﺈﺯﺍﻟﺔ ﺻﻤﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﻣﻦ ﻣﺎﺳﻮﺭﺓ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻣﺒﺎﺷﺮﺓ ﻗﺒﻞ ﺗﻮﺻﻴﻞ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﻮﺻﻴﻞ‪.‬‬
‫ﻗﻢ ﺑﻌﺰﻝ ﺍﻷﺟﺰﺍء ﺑﺸﻜﻞ ﺻﺤﻴﺢ ﺑﺤﻴﺚ ﻻ ﻳﺤﺪﺙ ﺗﻘﻄﻴﺮ ﻟﻠﻤﻴﺎﻩ ﻣﻦ ﺃﺟﺰﺍء ﺍﻟﺘﻮﺻﻴﻞ‪.‬‬
‫ﻧﻈﺮﺍ ﻷﻥ ﺫﻟﻚ ﻳﻘﻠﻞ ﻋﻤﺮ ﺍﻟﻮﺣﺪﺍﺕ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﺯﻳﺖ ﻣﻌﺪﻧﻲ ﻋﻠﻰ ﺍﻟﺠﺰء ﺍﻟﻤﻔﻠﺞ‪ .‬ﺍﺣﺮﺹ ﻋﻠﻰ ﻣﻨﻊ ﺩﺧﻮﻝ ﺯﻳﺖ ﻣﻌﺪﻧﻲ ﻓﻲ ﺍﻟﻨﻈﺎﻡ ً‬
‫ﺍﻓﺤﺺ ﺍﻟﺘﺼﺮﻳﻒ ﺍﻟﺼﺤﻴﺢ ﺑﻌﺪ ﺍﻟﺘﺮﻛﻴﺐ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺍﻟﺠﺰء ﺍﻟﻤﺮﺋﻲ ﻣﻦ ﻣﻨﻔﺬ ﺍﻟﺘﺼﺮﻳﻒ ﺍﻟﺸﻔﺎﻑ ﻭﺍﻟﻤﺨﺮﺝ ﺍﻟﻨﻬﺎﺋﻲ ﻟﻤﺎﺳﻮﺭﺓ‬
‫ﺍﻟﺘﺼﺮﻳﻒ ﻋﻠﻰ ﺍﻟﺠﺴﻢ‪.‬‬
‫ﺃﻣﺴﻚ ﻣﻔﺘﺎﺡ ﺍﻟﺮﺑﻂ ﻣﻦ ﻣﻘﺒﻀﻪ‪ ،‬ﻭﺍﺣﺘﻔﻆ ﺑﻪ ﻓﻲ ﺯﺍﻭﻳﺔ ﻗﺎﺋﻤﺔ ﻣﻊ ﺍﻟﻤﺎﺳﻮﺭﺓ‪ ،‬ﻣﻦ ﺃﺟﻞ ﺭﺑﻂ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪.‬‬
‫)‪ (1‬ﺍﻧﺰﻉ ﺍﻷﻏﻄﻴﺔ ﻭﺍﻟﺴﺪﺍﺩﺍﺕ ﻣﻦ ﺍﻟﻤﻮﺍﺳﻴﺮ‪.‬‬
‫ﺗﻨﺒﻴﻪ‬
‫)‪ (2‬ﻗﻢ ﺑﺘﻮﺳﻴﻂ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻣﻘﺎﺑﻞ ﺍﻟﻤﻨﻔﺬ ﻓﻲ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪ ،‬ﺛﻢ ﺃﺩﺭ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺎﻟﻴﺪ‪.‬‬
‫ﻻ ﺗﻀﻊ ﻣﺎﺩﺓ ﻻﺻﻘﺔ ﻋﻠﻰ ﻣﻨﻔﺬ ﺍﻟﺘﺼﺮﻳﻒ ﺑﺎﻟﺠﺴﻢ‪) .‬ﺍﺳﺘﺨﺪﻡ ﺧﺮﻃﻮﻡ ﺍﻟﺼﺮﻑ ﺍﻟﻤﻠﺤﻖ ﻭﻗﻢ ﺑﺎﻟﺘﻮﺻﻴﻞ ﺑﻤﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ(‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﻮﺻﻴﻞ )ﻏﺎﺯ(‬
‫• ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ ﻣﻊ ﺍﻧﺤﺪﺍﺭ ﻷﺳﻔﻞ )‪ 1/100‬ﺇﻟﻰ ‪ (1/50‬ﺑﺤﻴﺚ ﻻ ﺗﻜﻮﻥ ﻫﻨﺎﻙ ﺍﻧﺨﻔﺎﺿﺎﺕ ﺃﻭ ﺍﺣﺘﺒﺎﺳﺎﺕ ﻓﻲ‬
‫ﺍﻟﻤﺎﺳﻮﺭﺓ‪ .‬ﻗﺪ ﻳﺆﺩﻱ ﺍﻟﺘﺼﺮﻳﻒ ﻏﻴﺮ ﺍﻟﺴﻠﺲ ﺑﺴﺒﺐ ﺗﺪﻓﻖ ﺍﻟﻤﻴﺎﻩ ﺍﻟﻤﺘﺮﺍﻛﻤﺔ ﻓﻲ ﺍﻟﻤﺎﺳﻮﺭﺓ ﺇﻟﻰ ﺍﻧﺴﺪﺍﺩ ﺍﻟﺼﺮﻑ‪.‬‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺘﻮﺻﻴﻞ‬
‫)ﺳﺎﺋﻞ(‬
‫• ﺍﺳﺘﺨﺪﺍﻡ ﻣﺎﺳﻮﺭﺓ ﺑﻮﻟﻴﻔﻴﻨﻴﻞ ﻛﻠﻮﺭﻳﺪ ﺻﻠﺒﺔ ﻋﺎﻣﺔ )‪] (VP25‬ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ‪ 32‬ﻣﻢ[‪.‬‬
‫• ﻋﻨﺪﻣﺎ ﺗﻜﻮﻥ ﺍﻟﻤﺎﺳﻮﺭﺓ ﻃﻮﻳﻠﺔ‪ ,‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺩﻋﺎﻣﺎﺕ‪.‬‬
‫• ﻻ ﺗﻨﻔﺬ ﻋﻤﻠﻴﺔ ﻧﺰﻑ ﻫﻮﺍﺋﻲ‪ .‬ﻓﻘﺪ ﻳﻨﻔﺠﺮ ﺍﻟﺼﺮﻑ‪.‬‬
‫• ﺍﺣﺮﺹ ﺩﺍﺋﻤًﺎ ﻋﻠﻰ ﻋﻤﻞ ﻋﺰﻝ ﺣﺮﺍﺭﻱ ﻟﻠﺠﺎﻧﺐ ﺍﻟﺪﺍﺧﻠﻲ ﻟﻤﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‪.‬‬
‫• ﺇﺫﺍ ﻛﺎﻥ ﻣﻦ ﻏﻴﺮ ﺍﻟﻤﻤﻜﻦ ﻋﻤﻞ ﺍﻧﺤﺪﺍﺭ ﻛﺎﻑ‪ ,‬ﻗﻢ ﺑﻌﻤﻞ ﺭﻓﻊ ﻟﻠﺼﺮﻑ‪.‬‬
‫ﺣﺠﻢ ﺍﻟﻤﺎﺳﻮﺭﺓ‬
‫)‪ (3‬ﻋﻨﺪ ﺭﺑﻂ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ ﺑﺸﻜﻞ ﺻﺤﻴﺢ ﺑﺎﻟﻴﺪ‪ ،‬ﺃﻣﺴﻚ ﻗﺎﺭﻧﺔ ﺟﺎﻧﺐ ﺍﻟﺠﺴﻢ ﺑﻤﻔﺘﺎﺡ ﻣﻨﻔﺼﻞ‪ ،‬ﺛﻢ ﺃﺭﺑﻂ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻣﻔﺘﺎﺡ ﺭﺑﻂ‪.‬‬
‫)ﺭﺍﺟﻊ ﺍﻟﺠﺪﻭﻝ ﺍﻟﺘﺎﻟﻲ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻋﺰﻡ ﺭﺑﻂ ﺻﺎﻣﻮﻟﺔ ﺍﻟﺘﻔﻠﻴﺞ‪(.‬‬
‫‪) VP25‬ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ‪ 32‬ﻣﻢ(‬
‫ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ‬
‫‪ 1.5‬ﺇﻟﻰ ‪ 2‬ﻣﺘﺮ‬
‫ﺗﺮﻛﻴﺒﺎﺕ ﺍﻟﺘﻌﻠﻴﻖ‬
‫ﺍﺭﺑﻂ ﺑﻤﻔﺘﺎﺣﻴﻦ ‪.2‬‬
‫ﻣﻔﺘﺎﺡ ﺗﺜﺒﻴﺖ‬
‫ﺻﺎﻣﻮﻟﺔ ﻣﻔﻠﺠﺔ‬
‫ﻣﻔﺘﺎﺡ ﺭﺑﻂ‬
‫‪) VP25‬ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ‪ 32‬ﻣﻢ(‬
‫ﺍﻧﺤﺪﺍﺭ ﻷﺳﻔﻞ ‪ 1/100‬ﺇﻟﻰ ‪1/50‬‬
‫ﻧﻮﻉ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)ﺟﺎﻧﺐ ﺍﻟﺠﺴﻢ(‬
‫ﻣﺎﺳﻮﺭﺓ ﺗﻮﺻﻴﻞ‬
‫ﻋﺰﻡ ﺍﻟﺮﺑﻂ ]ﻧﻴﻮﺗﻦ ﻣﺘﺮ )ﻛﺠﻢ ﻗﻮﺓ·ﺳﻢ([‬
‫‪ 16‬ﺇﻟﻰ ‪ 160) 18‬ﺇﻟﻰ ‪(180‬‬
‫‪ 32‬ﺇﻟﻰ ‪ 320) 42‬ﺇﻟﻰ ‪(420‬‬
‫‪ 49‬ﺇﻟﻰ ‪ 490) 61‬ﺇﻟﻰ ‪(610‬‬
‫‪ 63‬ﺇﻟﻰ ‪ 630) 75‬ﺇﻟﻰ ‪(750‬‬
‫‪ 90‬ﺇﻟﻰ ‪ 900) 110‬ﺇﻟﻰ ‪(1,100‬‬
‫ﺻﺎﻣﻮﻟﺔ ﻣﻔﻠﺠﺔ ]ﻣﻢ )ﺑﻮﺻﺔ([‬
‫‪ (1/4) 6.35‬ﻗﻄﺮ‬
‫‪ (3/8) 9.52‬ﻗﻄﺮ‬
‫‪ (1/2) 12.70‬ﻗﻄﺮ‬
‫‪ (5/8) 15.88‬ﻗﻄﺮ‬
‫‪ (3/4) 19.05‬ﻗﻄﺮ‬
‫ﻣﺤﻈﻮﺭ‪:‬‬
‫ﺍﺣﺘﺒﺎﺱ‬
‫ﻧﺰﻑ ﺍﻟﻬﻮﺍء‬
‫ﺭﻓﻊ‬
‫ﻋﻨﺪ ﺭﻓﻊ ﺍﻟﺼﺮﻑ‪:‬‬
‫• ﻳﺠﺐ ﺃﻥ ﻳﻜﻮﻥ ﺍﺭﺗﻔﺎﻉ ﺍﻟﻤﺎﺳﻮﺭﺓ ﺍﻟﻤﺎﺋﻠﺔ ﺃﻗﻞ ﻣﻦ ‪ 850‬ﻣﻢ ﻣﻦ ﺍﻟﺴﻘﻒ‪ .‬ﻳﺆﺩﻱ ﺍﻟﺒُﻌﺪ ﺍﻟﻤﺮﺗﻔﻊ ﺑﺸﻜﻞ ﺃﻛﺒﺮ ﻣﻦ ﻫﺬﺍ ﺍﻟﻨﻄﺎﻕ ﺇﻟﻰ‬
‫ﺍﻟﺘﺴﺮﻳﺐ‪.‬‬
‫• ﺍﺭﻓﻊ ﺍﻟﻤﺎﺳﻮﺭﺓ ﺭﺃﺳﻴًﺎ ﻋﻨﺪ ﻣﻮﺿﻊ ‪ 300‬ﻣﻢ ﺃﻭ ﺃﻗﻞ ﻣﻦ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫ﺍﻧﺤﺪﺍﺭ ﻷﺳﻔﻞ ‪1/100‬‬
‫ﺇﻟﻰ ‪1/50‬‬
‫‪ .4.4‬ﺗﺮﻛﻴﺐ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ‬
‫‪ 300‬ﻣﻢ ﺃﻭ ﺃﻗﻞ‬
‫‪) VP25‬ﺍﻟﻘﻄﺮ ﺍﻟﺨﺎﺭﺟﻲ ‪ 32‬ﻣﻢ(‬
‫ﺇﻋﺪﺍﺩ ﻣﺤﻠﻲ‬
‫ﺗﻨﺒﻴﻪ‬
‫‪ 850‬ﻣﻢ ﺃﻭ ﺃﻗﻞ‬
‫ﺑﻌﺪ ﻓﺤﺺ ﺗﺴﺮﻳﺐ ﺍﻟﻐﺎﺯ )ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ(‪ ,‬ﻗﻢ ﺑﺘﻨﻔﻴﺬ ﻫﺬﺍ ﺍﻟﻘﺴﻢ‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺣﻮﻝ ﻛﻞ ﻣﻦ ﺍﻟﻤﻮﺍﺳﻴﺮ ﺍﻟﻜﺒﻴﺮﺓ )ﺍﻟﻐﺎﺯ( ﻭﺍﻟﺼﻐﻴﺮﺓ )ﺍﻟﺴﺎﺋﻞ(‪ .‬ﺍﻹﺧﻔﺎﻕ ﻓﻲ ﺍﻟﻘﻴﺎﻡ ﺑﺬﻟﻚ ﻗﺪ ﻳﺆﺩﻱ‬
‫ﺇﻟﻰ ﺗﺴﺮﻳﺐ ﻓﻲ ﺍﻟﻤﻴﺎﻩ‪.‬‬
‫ﺃﻓﻘﻲ ﺃﻭ ﺍﻧﺤﺪﺍﺭ ﻷﺳﻔﻞ‬
‫ﺑﻌﺪ ﻓﺤﺺ ﺗﺴﺮﻳﺒﺎﺕ ﺍﻟﻐﺎﺯ‪ ،‬ﻗﻢ ﺑﺎﻟﻌﺰﻝ ﻣﻦ ﺧﻼﻝ ﻟﻒ ﺍﻟﻌﺎﺯﻝ ﺣﻮﻝ ‪ 2‬ﺟﺰﺋﻲ ﻗﺎﺭﻧﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ )ﺍﻟﻐﺎﺯ ﻭﺍﻟﺴﺎﺋﻞ(‪ ،‬ﺑﺎﺳﺘﺨﺪﺍﻡ‬
‫ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‪.‬‬
‫ﺑﻌﺪ ﺗﺮﻛﻴﺐ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﻟﻠﻘﺎﺭﻧﺔ‪ ،‬ﻗﻢ ﺑﻠﻒ ﻛﻼ ﻣﻦ ﺍﻟﻨﻬﺎﻳﺘﻴﻦ ﺑﺸﺮﻳﻂ ﻓﻴﻨﻴﻠﻲ ﺑﺤﻴﺚ ﻻ ﺗﻮﺟﺪ ﻫﻨﺎﻙ ﺃﻱ ﻓﺠﻮﺓ‪.‬‬
‫ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ‬
‫ﻟﻠﻘﺎﺭﻧﺔ‬
‫)ﺍﻟﻤﻠﺤﻘﺎﺕ(‬
‫ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ )ﻛﺒﻴﺮ(‬
‫)ﻣﻠﺤﻘﺎﺕ(‬
‫‪) VP30‬ﻗﻄﺮ ﺧﺎﺭﺟﻲ ‪ 38‬ﻣﻢ( ﺃﻭ ﺃﻛﺜﺮ ﺍﻧﺤﺪﺍﺭ ‪ 850‬ﻣﻢ ﺃﻭ ﺃﻗﻞ‬
‫ﺳﻔﻠﻲ ‪ 1/100‬ﺇﻟﻰ ‪1/50‬‬
‫ﺑﺪﻭﻥ ﻓﺠﻮﺓ‬
‫ﺍﻟﺠﺴﻢ‬
‫ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ‬
‫ﻟﻠﻘﺎﺭﻧﺔ‬
‫ﺗﺄﻛﺪ ﻣﻦ ﺗﺮﺍﻛﺐ ﺍﻟﻌﺎﺯﻝ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﻳﺠﺐ ﺍﻟﺮﺑﻂ ﺑﺈﺣﻜﺎﻡ ﻣﻘﺎﺑﻞ ﺍﻟﺠﺴﻢ ﺑﺪﻭﻥ ﺃﻱ ﻓﺠﻮﺓ‪.‬‬
‫‪Ar-6‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 6‬‬
‫ﺇﺟﺮﺍء ﺍﻟﻌﻤﻞ‬
‫‪ .6‬ﺍﻷﺳﻼﻙ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ‬
‫)‪ (1‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺧﺮﻃﻮﻡ ﺍﻟﺼﺮﻑ ﺍﻟﻤﺮﻛﺐ ﻓﻲ ﻣﻨﻔﺬ ﺍﻟﺼﺮﻑ ﺑﺎﻟﺠﺴﻢ‪ .‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ ﻣﻦ ﺃﻋﻠﻰ ﺍﻟﺨﺮﻃﻮﻡ ﺿﻤﻦ ﻣﻨﻄﻘﺔ‬
‫ﺍﻟﻌﺮﺽ ﺍﻟﺮﺳﻮﻣﻴﺔ‪ .‬ﺛﺒﺖ ﺑﺈﺣﻜﺎﻡ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ‪.‬‬
‫ﺗﺤﺬﻳﺮ‬
‫)‪ (2‬ﺍﺳﺘﺨﺪﻡ ﻣﺎﺩﺓ ﻻﺻﻘﺔ ﻓﻴﻨﻴﻠﻴﺔ ﻟﻠﺼﻖ ﻣﺎﺳﻮﺭﺓ ﺍﻟﺼﺮﻑ )ﻣﺎﺳﻮﺭﺓ ‪ PVC‬ﻃﺮﺍﺯ ‪ (VP25‬ﻭﺍﻟﺘﻲ ﻳﺘﻢ ﺇﻋﺪﺍﺩﻫﺎ ﻓﻲ ﺍﻟﻤﻮﻗﻊ ﺃﻭ‬
‫ﺍﻟﻤﺄﺧﺬ ﺍﻟﻤﺮﻓﻘﻲ‪.‬‬
‫)ﺿﻊ ﺍﻟﻤﺎﺩﺓ ﺍﻟﻼﺻﻘﺔ ﺍﻟﻤﻠﻮﻧﺔ ﺑﺎﻟﺘﺴﺎﻭﻱ ﺣﺘﻰ ﺧﻂ ﺍﻟﻘﻴﺎﺱ ﻭﻣﺎﻧﻊ ﺍﻟﺘﺴﺮﻳﺐ(‬
‫ﻳﺠﺐ ﺗﻨﻔﻴﺬ ﺍﻷﻋﻤﺎﻝ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ً‬
‫ﻭﻓﻘﺎ ﻟﻬﺬﺍ ﺍﻟﺪﻟﻴﻞ ﻭﺑﻮﺍﺳﻄﺔ ﺷﺨﺺ ﻣﻌﺘﻤﺪ ﺑﻤﻮﺟﺐ ﺍﻟﻠﻮﺍﺋﺢ ﺍﻟﻮﻃﻨﻴﺔ ﺃﻭ ﺍﻹﻗﻠﻴﻤﻴﺔ‪ .‬ﺗﺄﻛﺪ ﻣﻦ ﺍﺳﺘﺨﺪﺍﻡ‬
‫ﺩﺍﺋﺮﺓ ﻛﻬﺮﺑﺎﺋﻴﺔ ﻣﺨﺼﺼﺔ ﻟﻠﻮﺣﺪﺓ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﺗﺆﺩﻱ ﺩﺍﺋﺮﺓ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻏﻴﺮ ﺍﻟﻜﺎﻓﻴﺔ ﺃﻭ ﺍﻷﻋﻤﺎﻝ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻟﻤﻨﻔﺬﺓ ﺑﺸﻜﻞ ﻏﻴﺮ ﺻﺤﻴﺢ ﺇﻟﻰ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ‬
‫ﺍﻟﺘﻌﺮﺽ ﻟﺼﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﻗﺒﻞ ﺑﺪء ﺍﻟﻌﻤﻞ‪ ،‬ﺗﺤﻘﻖ ﻣﻦ ﺃﻧﻪ ﻻ ﻳﺠﺮﻱ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺇﻟﻰ ﺟﻤﻴﻊ ﺍﻟﻮﺣﺪﺍﺕ‪.‬‬
‫)‪ (3‬ﺍﻓﺤﺺ ﻭﺟﻮﺩ ﺗﺴﺮﻳﺐ‪) .‬ﺭﺍﺟﻊ ﺍﻟﺮﺳﻢ ﺍﻟﺘﺨﻄﻴﻄﻲ ﺍﻟﻤﻨﻔﺼﻞ(‬
‫ﺑﺎﻟﻨﺴﺒﺔ ﻟﺘﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﻧﻮﻉ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﻮﺻﻮﻑ‪ ،‬ﻭﻗﻢ ﺑﺘﻮﺻﻴﻠﻪ ﺑﺈﺣﻜﺎﻡ‪ ،‬ﻣﻊ ﺍﻟﺘﺄﻛﺪ ﻣﻦ ﻋﺪﻡ ﻭﺟﻮﺩ ﻗﻮﻯ ﺧﺎﺭﺟﻴﺔ‬
‫ﻟﻠﻜﺒﻼﺕ ﺗﺆﺛﺮ ﻋﻠﻰ ﺗﻮﺻﻴﻼﺕ ﺍﻟﻄﺮﻑ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﺗﺆﺩﻱ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﻮﺻﻠﺔ ﺑﺸﻜﻞ ﻏﻴﺮ ﺻﺤﻴﺢ ﺃﻭ ﻣﺤﻜﻢ ﺇﻟﻰ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺯﻳﺎﺩﺓ ﺳﺨﻮﻧﺔ ﺍﻟﻄﺮﻑ ﺃﻭ ﺻﺪﻣﺔ‬
‫ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫)‪ (4‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ‪.‬‬
‫)‪ (5‬ﺍﺳﺘﺨﺪﻡ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺍﻟﻤﺮﻓﻖ ﻟﻌﺰﻝ ﻣﻨﻔﺬ ﺍﻟﺼﺮﻑ ﻭﺃﺟﺰﺍء ﺍﻟﺮﺑﻂ ﺑﺎﻟﺠﺴﻢ‪.‬‬
‫ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ ﺍﻟﻤﺮﻓﻖ‬
‫)ﻣﻠﺤﻘﺎﺕ(‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺃﻭﺟﻪ ﺍﻟﻤﻘﺒﺾ‬
‫ﻷﻋﻠﻰ‬
‫ﻣﺎﺳﻮﺭﺓ ﻓﻴﻨﻴﻞ ﻣﻌﺪﺓ ﻣﺤﻠﻴًﺎ‬
‫ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﻟﺨﺮﻃﻮﻡ‬
‫ﺍﻟﺼﺮﻑ ﺍﻟﻤﺮﻓﻖ‬
‫)ﻣﻠﺤﻘﺎﺕ(‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻏﻄﺎء ﺍﻟﺼﻨﺪﻭﻕ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ ﺑﺈﺣﻜﺎﻡ ﻋﻠﻰ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﻳﺴﺒﺐ ﺍﻟﺼﻨﺪﻭﻕ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ ﺍﻟﻤﺮﻛﺐ ﺑﺸﻜﻞ ﻏﻴﺮ ﺻﺤﻴﺢ ﺣﻮﺍﺩﺙ ﺧﻄﻴﺮﺓ ﻣﺜﻞ ﺍﻟﺼﺪﻣﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﺍﻟﺤﺮﻳﻖ ﻋﻦ‬
‫ﻃﺮﻳﻖ ﺍﻟﺘﻌﺮﺽ ﻟﻠﻐﺒﺎﺭ ﺃﻭ ﺍﻟﻤﻴﺎﻩ‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺃﻛﻤﺎﻡ ﻓﻲ ﺃﻱ ﻓﺘﺤﺎﺕ ﻳﺘﻢ ﺗﻨﻔﻴﺬﻫﺎ ﻓﻲ ﺍﻟﺠﺪﺭﺍﻥ ﻷﺟﻞ ﺗﻤﺪﻳﺪ ﺍﻷﺳﻼﻙ‪ .‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﺗﺤﺪﺙ ﺩﺍﺋﺮﺓ ﻗﺼﺮ‪.‬‬
‫ﺍﺳﺘﺨﺪﻡ ﻛﺒﻼﺕ ﺍﻟﺘﻮﺻﻴﻞ ﺍﻟﻤﻀﻤﻨﺔ ﻭﻛﺒﻼﺕ ﺍﻟﻄﺎﻗﺔ ﺃﻭ ﺍﻟﻜﺒﻼﺕ ﺍﻟﺘﻲ ﻳﺤﺪﺩﻫﺎ ﺍﻟﻤﺼﻨﱢﻊ‪ .‬ﻳﻤﻜﻦ ﺃﻥ ﺗﺆﺩﻱ ﺍﻟﺘﻮﺻﻴﻼﺕ ﻏﻴﺮ ﺍﻟﺼﺤﻴﺤﺔ‬
‫ﺃﻭ ﺍﻟﻌﺰﻝ ﻏﻴﺮ ﺍﻟﻜﺎﻓﻲ ﺃﻭ ﺗﺠﺎﻭﺯ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻪ ﺇﻟﻰ ﺣﺪﻭﺙ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﻻ ﺗﻌﺪﻝ ﻛﺒﻼﺕ ﺍﻟﻄﺎﻗﺔ ﺃﻭ ﺗﺴﺘﺨﺪﻡ ﻛﺒﻼﺕ ﺗﻤﺪﻳﺪ ﺃﻭ ﺗﺴﺘﺨﺪﻡ ﺃﻱ ﺗﻔﺮﻳﻌﺎﺕ ﻓﻲ ﺍﻷﺳﻼﻙ‪ .‬ﻳﻤﻜﻦ ﺃﻥ ﺗﺆﺩﻱ ﺍﻟﺘﻮﺻﻴﻼﺕ ﻏﻴﺮ ﺍﻟﺼﺤﻴﺤﺔ‬
‫ﺃﻭ ﺍﻟﻌﺰﻝ ﻏﻴﺮ ﺍﻟﻜﺎﻓﻲ ﺃﻭ ﺗﺠﺎﻭﺯ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻪ ﺇﻟﻰ ﺣﺪﻭﺙ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﺧﺮﻃﻮﻡ ﺍﻟﺼﺮﻑ ﺍﻟﻤﺮﻓﻖ‬
‫)ﻣﻠﺤﻘﺎﺕ(‬
‫ﻗﻢ ﺑﻤﻄﺎﺑﻘﺔ ﺭﻗﻢ ﺍﻟﻤﺠﻤﻮﻋﺔ ﺍﻟﻄﺮﻓﻴﺔ ﻭﺃﻟﻮﺍﻥ ﻛﺒﻼﺕ ﺍﻟﺘﻮﺻﻴﻞ ﻣﻊ ﺗﻠﻚ ﺍﻟﺨﺎﺻﺔ ﺑﺎﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ )ﺃﻭ ﻭﺣﺪﺓ ‪ .(RB‬ﻗﺪ ﺗﺆﺩﻱ‬
‫ﺍﻟﺘﻮﺻﻴﻼﺕ ﺍﻟﺨﺎﻃﺌﺔ ﻟﻸﺳﻼﻙ ﺇﻟﻰ ﺍﺣﺘﺮﺍﻕ ﺍﻟﻤﻜﻮﻧﺎﺕ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ‪.‬‬
‫ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﻣﺮﻓﻖ‬
‫)ﺍﻟﻤﻠﺤﻘﺎﺕ(‬
‫ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﻛﺒﻼﺕ ﺍﻟﺘﻮﺻﻴﻞ ﻓﻲ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻄﺮﻓﻴﺔ ﺑﺈﺣﻜﺎﻡ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻚ‪ ،‬ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﺍﻟﻜﺒﻼﺕ ﻣﻦ ﺧﻼﻝ ﻣﺎﺳﻜﺎﺕ ﺍﻷﺳﻼﻙ‪.‬‬
‫ﺍﻟﺘﻮﺻﻴﻼﺕ ﻏﻴﺮ ﺍﻟﺼﺤﻴﺤﺔ‪ ،‬ﺳﻮﺍء ﻓﻲ ﺍﻷﺳﻼﻙ ﺃﻭ ﻓﻲ ﺃﻃﺮﺍﻑ ﺍﻷﺳﻼﻙ‪ ،‬ﺗﺆﺩﻱ ﺇﻟﻰ ﺍﻟﺘﻌﻄﻞ ﺃﻭ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫ﺍﺣﺮﺹ ﺩﺍﺋﻤًﺎ ﻋﻠﻰ ﺗﺜﺒﻴﺖ ﺍﻟﻐﻄﺎء ﺍﻟﺨﺎﺭﺟﻲ ﻟﻜﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ ﻣﻊ ﻣﺸﺒﻚ ﺍﻟﻜﺒﻞ‪) .‬ﻓﻲ ﺣﺎﻟﺔ ﺧﺪﺵ ﺍﻟﻌﺎﺯﻝ‪ ،‬ﻓﻘﺪ ﻳﺤﺪﺙ ﺗﻔﺮﻳﻎ ﻛﻬﺮﺑﺎﺋﻲ(‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺴﺮﻳﺐ ﺍﻷﺭﺿﻲ‪ .‬ﺑﺎﻹﺿﺎﻓﺔ ﺇﻟﻰ ﺫﻟﻚ‪ ،‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺴﺮﻳﺐ ﺍﻷﺭﺿﻲ ﺑﺤﻴﺚ ﻳﺘﻢ ﻓﺼﻞ ﺇﻣﺪﺍﺩ‬
‫ﻃﺎﻗﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺘﺮﺩﺩ ﺍﻟﺮﺋﻴﺴﻲ ﺑﺎﻟﻜﺎﻣﻞ ﻓﻲ ﻧﻔﺲ ﺍﻟﻮﻗﺖ‪ .‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﺗﺤﺪﺙ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﺣﺮﻳﻖ‪.‬‬
‫ﻗﻢ ﺩﺍﺋﻤًﺎ ﺑﺘﻮﺻﻴﻞ ﻛﺒﻞ ﺍﻷﺭﺿﻲ )ﺍﻟﺘﺄﺭﻳﺾ(‪.‬‬
‫ﻳﻤﻜﻦ ﺃﻥ ﺗﺘﺴﺒﺐ ﺃﻋﻤﺎﻝ ﺍﻟﺘﺄﺭﻳﺾ )ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻷﺭﺽ( ﻏﻴﺮ ﺍﻟﺼﺤﻴﺤﺔ ﺇﻟﻰ ﺻﺪﻣﺎﺕ ﻛﻬﺮﺑﺎﺋﻴﺔ‪.‬‬
‫ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻛﺒﻼﺕ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺑﺤﻴﺚ ﻻ ﺗﺘﻼﻣﺲ ﻣﺒﺎﺷﺮﺓ ﻣﻊ ﻳﺪﻙ‪.‬‬
‫ﻗﻢ ﺑﺘﻨﻔﻴﺬ ﺃﻋﻤﺎﻝ ﺗﻮﺻﻴﻼﺕ ﺍﻷﺳﻼﻙ ً‬
‫ﻭﻓﻘﺎ ﻟﻠﻤﻌﺎﻳﻴﺮ ﺑﺤﻴﺚ ﻳﻤﻜﻦ ﺗﺸﻐﻴﻞ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﺑﺄﻣﺎﻥ ﻭﺑﺸﻜﻞ ﺇﻳﺠﺎﺑﻲ‪.‬‬
‫ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﻛﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺈﺣﻜﺎﻡ ﻓﻲ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻄﺮﻓﻴﺔ‪ .‬ﻳﻤﻜﻦ ﺃﻥ ﻳﺆﺩﻱ ﺍﻟﺘﺮﻛﻴﺐ ﻏﻴﺮ ﺍﻟﺠﻴﺪ ﺇﻟﻰ ﻧﺸﻮﺏ ﺣﺮﻳﻖ‪.‬‬
‫)‪ (a‬ﻣﻨﻈﺮ ﻋﻠﻮﻱ‬
‫)‪ (b‬ﻣﻨﻈﺮ ﺟﺎﻧﺒﻲ‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﻠﻒ ﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‪ ،‬ﻓﻴﺠﺐ ﺍﺳﺘﺒﺪﺍﻟﻪ ﺑﻮﺍﺳﻄﺔ ﺍﻟﻤﺼﻨﱢﻊ ﺃﻭ ﻭﻛﻴﻠﺔ ﺍﻟﺼﻴﺎﻧﺔ ﺍﻟﺨﺎﺹ ﺑﻪ ﺃﻭ ﺃﺷﺨﺎﺹ ﻣﺆﻫﻠﻴﻦ ﻋﻠﻰ‬
‫ﻧﺤﻮ ﻣﻤﺎﺛﻞ ﻣﻦ ﺃﺟﻞ ﺗﻔﺎﺩﻱ ﺍﻟﺨﻄﺮ‪.‬‬
‫‪VP25‬‬
‫ﻣﻨﻄﻘﺔ ﻭﺿﻊ ﺍﻟﻼﺻﻖ‬
‫‪ 35‬ﻣﻢ‬
‫ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﺍﻟﻮﺣﺪﺓ ﺑﺎﻷﺭﺽ )ﺍﻟﺘﺄﺭﻳﺾ(‪.‬‬
‫ﻻ ﺗﻘﻢ ﺑﺘﻮﺻﻴﻞ ﺍﻟﻜﺒﻞ ﺍﻷﺭﺿﻲ )ﺍﻟﺘﺄﺭﻳﺾ( ﺑﻤﺎﺳﻮﺭﺓ ﻏﺎﺯ ﺃﻭ ﻣﺎﺳﻮﺭﺓ ﻣﻴﺎﻩ ﺃﻭ ﻗﻀﻴﺐ ﺍﻟﺒﺮﻕ ﺃﻭ ﺳﻠﻚ ﺃﺭﺿﻲ )ﺗﺄﺭﻳﺾ(‬
‫ﻟﻠﻬﺎﺗﻒ‪.‬‬
‫ﻗﺪ ﻳﺆﺩﻱ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻷﺭﺽ )ﺍﻟﺘﺄﺭﻳﺾ( ﻏﻴﺮ ﺍﻟﺼﺤﻴﺢ ﺇﻟﻰ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ‪.‬‬
‫‪ 5‬ﺇﻟﻰ ‪ 10‬ﻣﻢ‬
‫‪ 20‬ﻣﻢ‬
‫)‪ (c‬ﻣﻨﻈﺮ ﻋﻠﻮﻱ‬
‫‪ 4‬ﻣﻢ ﺃﻭ ﺃﻗﻞ‬
‫ﺧﻂ ﺍﻟﻌﺪﺍﺩ‬
‫)‪ (d‬ﻣﻨﻈﺮ ﻓﺘﺤﺔ ﺍﻟﺨﺮﻃﻮﻡ‬
‫ﻗﻢ ﺑﻠﻒ ﺍﻟﻌﺎﺯﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺍﻟﻤﺮﻓﻖ‬
‫ﺣﻮﻝ ﺭﺍﺑﻂ ﺍﻟﺨﺮﻃﻮﻡ‬
‫ﺗﺄﻛﺪ ﻣﻦ ﺃﻥ‬
‫ﺍﻟﻤﺤﺎﺫﺍﺓ ﻣﻦ ﺃﻋﻠﻰ‬
‫ﻧﻈﺮﺍ ﻷﻥ ﺫﻟﻚ ﻳﺘﻠﻒ ﺍﻟﻤﻨﺘﺞ‪.‬‬
‫ﻻ ﺗﻘﻢ ﺑﺘﻮﺻﻴﻞ ﻛﺒﻼﺕ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﺑﺄﻃﺮﺍﻑ ﺍﻟﻨﻘﻞ ﺃﻭ ﺃﻃﺮﺍﻑ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪ً ،‬‬
‫ً‬
‫ﻣﻄﻠﻘﺎ ﺭﺑﻂ ﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻭﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﻛﺒﻞ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻌًﺎ‪ .‬ﺍﻓﺼﻞ ﻫﺬﻩ ﺍﻟﻜﺒﻼﺕ ﺑﻤﺴﺎﻓﺔ ‪ 50‬ﻣﻢ ﺃﻭ ﺃﻛﺜﺮ‪ .‬ﻳﺆﺩﻱ‬
‫ﺗﺠﻨﺐ‬
‫ﺭﺑﻂ ﻫﺬﻩ ﺍﻟﻜﺒﻼﺕ ﻣﻌًﺎ ﻳﺆﺩﻱ ﺇﻟﻰ ﺳﻮء ﺍﻟﺘﺸﻐﻴﻞ ﺃﻭ ﺍﻟﺘﻌﻄﻞ‪.‬‬
‫ﻋﻨﺪ ﺍﻟﺘﻌﺎﻣﻞ ﻣﻊ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‪ ,‬ﻓﺈﻥ ﺍﻟﻜﻬﺮﺑﺎء ﺍﻟﺴﺎﻛﻨﺔ ﺍﻟﻤﺸﺤﻮﻧﺔ ﻓﻲ ﺍﻟﺠﺴﻢ ﻗﺪ ﺗﺴﺒﺐ ﺗﻌﻄﻞ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‪ .‬ﺍﺗﺒﻊ‬
‫ﺍﻻﺣﺘﻴﺎﻃﺎﺕ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫• ﻗﻢ ﺑﺈﻧﺸﺎء ﻭﺻﻠﺔ ﺃﺭﺿﻴﺔ )ﺗﺄﺭﻳﺾ( ﻟﻠﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺍﻟﺨﺎﺭﺟﻴﺔ ﻭﺍﻷﺟﻬﺰﺓ ﺍﻟﻄﺮﻓﻴﺔ‪.‬‬
‫• ﺍﻓﺼﻞ ﺍﻟﻄﺎﻗﺔ )ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ(‪.‬‬
‫• ﺍﻟﻤﺲ ﺍﻟﺠﺰء ﺍﻟﻤﻌﺪﻧﻲ ﻟﻠﻮﺣﺪﺍﺕ ﺍﻟﺨﺎﺭﺟﻴﺔ ﻟﻤﺪﺓ ﺗﺰﻳﺪ ﻋﻦ ‪ 10‬ﺛﻮﺍﻧﻲ ﻟﺘﻔﺮﻳﻎ ﺍﻟﻜﻬﺮﺑﺎء ﺍﻻﺳﺘﺎﺗﻴﻜﻴﺔ ﺍﻟﻤﺸﺤﻮﻧﺔ ﻓﻲ ﺍﻟﺠﺴﻢ‪.‬‬
‫• ﻻ ﺗﻠﻤﺲ ﺃﻃﺮﺍﻑ ﺍﻷﺟﺰﺍء ﺃﻭ ﺍﻟﻘﻮﺍﻟﺐ ﻓﻲ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‪.‬‬
‫ﺗﺄﻛﺪ ﻣﻦ ﻋﺪﻡ ﻭﺟﻮﺩ ﻓﺠﻮﺍﺕ‬
‫ﻣﻼﺣﻈﺔ‪ :‬ﻓﺤﺺ ﻭﺟﻮﺩ ﺗﺴﺮﻳﺐ‬
‫ﺍﺳﻜﺐ ﺣﻮﺍﻟﻲ ‪ 1‬ﻟﺘﺮ ﻣﻦ ﺍﻟﻤﺎء ﻣﻦ ﺍﻟﻤﻮﺿﻊ ﺍﻟﻤﻮﺿﺢ ﻓﻲ ﺍﻟﺸﻜﻞ ﺍﻟﺘﻮﺿﻴﺤﻲ ﺃﻭ ﻣﻦ ﻓﺘﺤﺔ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﺇﻟﻰ ﺩﺭﺝ ﺍﻟﻨﺪﻯ‪ .‬ﺍﻓﺤﺺ‬
‫ﻭﺟﻮﺩ ﺃﻱ ﺷﻲء ﻏﻴﺮ ﻋﺎﺩﻱ ﻣﺜﻞ ﺍﻟﻀﻮﺿﺎء ﺍﻟﻐﺮﻳﺒﺔ ﻭﻣﺎ ﺇﺫﺍ ﻛﺎﻧﺖ ﻣﻀﺨﺔ ﺍﻟﺼﺮﻑ ﺗﻌﻤﻞ ﺑﺸﻜﻞ ﻋﺎﺩﻱ ﺃﻡ ﻻ‪.‬‬
‫‪Ar-7‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 7‬‬
‫‪ .2.6‬ﻃﺮﻳﻘﺔ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‬
‫‪ .1.6‬ﺍﻟﻤﺘﻄﻠﺐ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ‬
‫ﻣﻌﺪﻝ ﺍﻟﺠﻬﺪ‬
‫‪ 230‬ﻓﻮﻟﺖ‬
‫ﻧﻄﺎﻕ ﺍﻟﺘﺸﻐﻴﻞ‬
‫‪ 198‬ﺇﻟﻰ ‪ 264‬ﻓﻮﻟﺖ )‪(50 Hz‬‬
‫ﻣﺜﺎﻝ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﺃﻭ ﻭﺣﺪﺓ ‪1* RB‬‬
‫‪ 198‬ﺇﻟﻰ ‪ 253‬ﻓﻮﻟﺖ )‪(60 Hz‬‬
‫ﺍﻟﻨﻘﻞ‬
‫• ﺣﺪﺩ ﻧﻮﻉ ﻭﺣﺠﻢ ﻛﺒﻞ ﺍﻟﻄﺎﻗﺔ ً‬
‫ﻭﻓﻘﺎ ﻟﻠﻘﻮﺍﻋﺪ ﺍﻟﻤﺘﻌﻠﻘﺔ ﺍﻟﻤﺤﻠﻴﺔ ﻭﺍﻟﻮﻃﻨﻴﺔ‪.‬‬
‫• ﻳﺠﺐ ﺃﻥ ﺗﺘﻔﻖ ﻣﻮﺍﺻﻔﺎﺕ ﺃﺳﻼﻙ ﻛﺒﻞ ﺍﻟﻄﺎﻗﺔ ﻭﺍﻟﺘﻔﺮﻳﻌﺎﺕ ﻣﻊ ﺍﻟﻘﺎﻧﻮﻥ ﺍﻟﻤﺤﻠﻲ‪.‬‬
‫• ﺃﻗﺼﻰ ﻃﻮﻝ ﻟﻠﺴﻠﻚ‪ :‬ﺍﺿﺒﻂ ﺍﻟﻄﻮﻝ ﺑﺤﻴﺚ ﻳﻜﻮﻥ ﺍﻧﺨﻔﺎﺽ ﺍﻟﺠﻬﺪ ﺃﻗﻞ ﻣﻦ ‪ .% 2‬ﻗﻢ ﺑﺰﻳﺎﺩﺓ ﻗﻄﺮ ﺍﻟﺴﻠﻚ ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﺍﻟﻄﻮﻝ ﺃﻛﺒﺮ‪.‬‬
‫ﻳﺠﺐ ﺗﺮﻛﻴﺐ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﻓﻲ ﻛﻞ ﻧﻈﺎﻡ ﺗﺒﺮﻳﺪ‪ .‬ﻻ ﺗﺴﺘﺨﺪﻡ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﻓﻲ ﻧﻈﺎﻡ ﺗﺒﺮﻳﺪ ﻣﺨﺘﻠﻒ‪.‬‬
‫ﺭﺍﺟﻊ ﺍﻟﺠﺪﻭﻝ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻣﻮﺍﺻﻔﺎﺕ ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ ﻟﻜﻞ ﺣﺎﻟﺔ ﺗﺮﻛﻴﺐ‪ .‬ﻗﻢ ﺑﺘﻨﻔﻴﺬ ﺍﻷﺳﻼﻙ ﺍﻟﻌﺎﺑﺮﺓ ﻟﻠﻄﺎﻗﺔ ﺿﻤﻦ ﻧﻄﺎﻕ ﻧﻔﺲ ﻧﻈﺎﻡ‬
‫ﺳﺎﺋﻞ ﺍﻟﺘﺒﺮﻳﺪ‪ .‬ﻋﻨﺪ ﺗﻨﻔﻴﺬ ﺃﺳﻼﻙ ﻋﺎﺑﺮﺓ‪ ،‬ﻗﻢ ﺑﻌﻤﻞ ﺗﻮﺻﻴﻼﺕ ﻟﻠﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺑﺤﻴﺚ ﺗﺤﻘﻖ ﺍﻟﺸﺮﻭﻁ ‪ A‬ﻭ‪ B‬ﺃﺩﻧﺎﻩ‪.‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪ .A‬ﻣﺘﻄﻠﺒﺎﺕ ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫‪*3‬‬
‫‪MCA‬‬
‫ﺍﻟﻄﺮﺍﺯ‬
‫‪AUXD18GATH‬‬
‫‪ 0.32‬ﺃﻣﺒﻴﺮ‬
‫‪AUXD24GATH‬‬
‫‪ 0.38‬ﺃﻣﺒﻴﺮ‬
‫‪AUXA30GATH‬‬
‫‪ 0.51‬ﺃﻣﺒﻴﺮ‬
‫‪AUXA36GATH‬‬
‫‪ 0.64‬ﺃﻣﺒﻴﺮ‬
‫‪AUXA45GATH‬‬
‫‪ 0.83‬ﺃﻣﺒﻴﺮ‬
‫‪AUXA54GATH‬‬
‫‪ 0.94‬ﺃﻣﺒﻴﺮ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪*2‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫‪*2‬‬
‫‪*3‬‬
‫ﺍﻟﻨﻘﻞ‬
‫‪ *2‬ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫‪*3‬‬
‫‪MFA‬‬
‫ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫‪ 20‬ﺃﻣﺒﻴﺮ‬
‫ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫)ﺍﻟﻔﺮﻋﻴﺔ(‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫)ﺍﻟﺮﺋﻴﺴﻴﺔ(‬
‫*‪ :1‬ﻋﻨﺪ ﺍﻟﺘﻮﺻﻴﻞ ﺑﻨﻈﺎﻡ ﺍﺳﺘﺮﺩﺍﺩ ﺍﻟﺘﺪﻓﺌﺔ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﻟﻮﺣﺪﺓ ‪.RB‬‬
‫*‪ :2‬ﻗﻢ ﺑﺘﺄﺭﻳﺾ )ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻷﺭﺽ( ﻟﻮﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺇﺫﺍ ﻛﺎﻧﺖ ﺗﺘﻀﻤﻦ ﻛﺒﻞ ﺗﺄﺭﻳﺾ )ﺃﺭﺿﻲ(‪.‬‬
‫*‪ :3‬ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻦ ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻟﺴﻠﻚ‪ ،‬ﻻ ﻳﺘﻢ ﺍﺳﺘﺨﺪﺍﻡ ‪.Y3‬‬
‫‪ :MCA‬ﺃﺩﻧﻰ ﻗﺪﺭﺓ ﺃﻣﺒﻴﺮﻳﺔ ﻟﻠﺪﺍﺋﺮﺓ‬
‫‪ :MFA‬ﺃﻗﺼﻰ ﻗﺪﺭﺓ ﺃﻣﺒﻴﺮﻳﺔ ﻟﻠﻤﺼﻬﺮ‬
‫ﻋﻨﺪ ﺗﻨﻔﻴﺬ ﺃﺳﻼﻙ ﻋﺎﺑﺮﺓ ﻟﻠﻄﺎﻗﺔ‪ ،‬ﺍﺣﺮﺹ ﻋﻠﻰ ﺃﻥ ﺗﻜﻮﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻹﺟﻤﺎﻟﻴﺔ ﻟـ ‪ MCA‬ﻟﻮﺣﺪﺍﺕ ‪ RB‬ﺍﻟﻤﺘﺼﻠﺔ ﻭﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻻ‬
‫ﺗﺘﺠﺎﻭﺯ ‪ 15‬ﺃﻣﺒﻴﺮ‪ .‬ﺑﺎﻟﻨﺴﺒﺔ ﻟﻘﻴﻤﺔ ‪ MCA‬ﻟﻮﺣﺪﺓ ‪ ،RB‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﻭﺣﺪﺓ ‪.RB‬‬
‫ﺇﺫﺍ ﻛﺎﻧﺖ ﻗﺪﺭﺓ ﻭﺣﺪﺍﺕ ‪ RB‬ﺍﻟﻤﺘﺼﻠﺔ ﻭﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺗﺘﺠﺎﻭﺯ ﺍﻟﺤﺪ ﺍﻟﺴﺎﺑﻖ‪ ،‬ﻋﻠﻴﻚ ﺇﻣﺎ ﺇﺿﺎﻓﺔ ﻗﻮﺍﻃﻊ ﺩﺍﺋﺮﺓ ﺃﻭ ﺍﺳﺘﺨﺪﺍﻡ ﻗﺎﻃﻊ‬
‫ﺩﺍﺋﺮﺓ ﺑﻘﺪﺭﺓ ﺃﻛﺒﺮ‪.‬‬
‫)ﺃﺳﻼﻙ ﻋﺎﺑﺮﺓ ﻹﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ(‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫‪ .B‬ﻣﺘﻄﻠﺒﺎﺕ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺴﺮﻳﺐ ﺍﻷﺭﺿﻲ‬
‫* ﺃﻗﺼﻰ ﻋﺪﺩ "ﻟﻠﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ" ﺃﻭ "ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ‪ +‬ﻭﺣﺪﺍﺕ‬
‫‪ "RB‬ﺍﻟﻘﺎﺑﻠﺔ ﻟﻠﺘﻮﺻﻴﻞ‬
‫ﻗﺪﺭﺓ ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫‪ 30‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ‪ 0.1 ,‬ﺛﺎﻧﻴﺔ ﺃﻭ ﺃﻗﻞ‬
‫‪ 44‬ﺃﻭ ﺃﻗﻞ‬
‫‪ 100‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ‪ 0.1 ,‬ﺛﺎﻧﻴﺔ ﺃﻭ ﺃﻗﻞ‬
‫‪ 45‬ﺇﻟﻰ ‪** 148‬‬
‫ﺻﻨﺪﻭﻕ‬
‫ﺳﺤﺐ‬
‫ﻗﺎﻃﻊ ﺍﻟﺪﺍﺋﺮﺓ‬
‫ﺻﻨﺪﻭﻕ ﺳﺤﺐ‬
‫* ﻧﻮﻉ ﻣﻀﺨﺔ ﺍﻟﺘﺪﻓﺌﺔ‪ :‬ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ‪ ,‬ﻧﻮﻉ ﺍﺳﺘﺮﺩﺍﺩ ﺍﻟﺘﺪﻓﺌﺔ‪ :‬ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻭﺣﺪﺍﺕ ‪.RB‬‬
‫** ﻓﻲ ﺣﺎﻟﺔ ﻋﺪﻡ ﺗﻮﻓﻴﺮ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﺑﻘﺪﺭﺓ ‪ 100‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ‪ ،‬ﻗﻢ ﺑﺘﻘﺴﻴﻢ ﻣﻘﺪﺍﺭ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺇﻟﻰ ﻣﺠﻤﻮﻋﺎﺕ ﺻﻐﻴﺮﺓ ﺗﺘﺄﻟﻒ ﻣﻦ‬
‫‪ 44‬ﻭﺣﺪﺓ ﺃﻭ ﺃﻗﻞ ﻭﺍﺣﺮﺹ ﻋﻠﻰ ﺗﻮﻓﻴﺮ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﺑﻘﺪﺭﺓ ‪ 30‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﻟﻜﻞ ﻣﺠﻤﻮﻋﺔ‪.‬‬
‫‪ .1.1.6‬ﻣﻮﺍﺻﻔﺎﺕ ﺍﻟﻜﺒﻼﺕ‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫‪ .3.6‬ﺃﺳﻼﻙ ﺍﻟﻮﺣﺪﺓ‬
‫• ﻗﺒﻞ ﺗﻮﺻﻴﻞ ﺍﻟﻜﺒﻞ ﺑﺎﻟﻤﺠﻤﻮﻋﺔ ﺍﻟﻄﺮﻓﻴﺔ‪.‬‬
‫ﺣﺠﻢ ﺍﻟﻜﺒﻞ ﺍﻟﻤﻮﺻﻰ ﺑﻪ )ﻣﻢ‪(2‬‬
‫ﻧﻮﻉ ﺍﻟﻜﺒﻞ‬
‫ﻣﻼﺣﻈﺔ‬
‫ﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫‪2.5‬‬
‫ﻧﻮﻉ ‪IEC57 245‬‬
‫ﺃﻭ ﻣﺎ ﻳﻌﺎﺩﻟﻪ‪.‬‬
‫‪ 2‬ﻛﺒﻞ ‪ +‬ﺃﺭﺿﻲ )ﺗﺄﺭﻳﺾ(‬
‫ﻛﺒﻞ ﺍﻟﻨﻘﻞ‬
‫‪0.33‬‬
‫ﻛﺒﻞ ﻣﺘﻮﺍﻓﻖ ﻣﻊ‬
‫‪LONWORKS‬‬
‫ﺳﻠﻚ ﻣﻘﺎﺱ ‪ 22‬ﺣﺴﺐ ﺍﻟﻤﻘﻴﺎﺱ‬
‫ﺍﻷﻣﺮﻳﻜﻲ )‪ (AWG‬ﺍﻟﻤﺴﺘﻮﻯ ‪4‬‬
‫)‪ (NEMA‬ﺛﻨﺎﺋﻲ ﺍﻟﻤﺮﻛﺰ ﻏﻴﺮ‬
‫ﻗﻄﺒﻲ‪ ،‬ﻭﺑﻤﺮﻛﺰ ﻣﺼﻤﺖ ﺛﻨﺎﺋﻲ‬
‫ﻣﻠﻔﻮﻑ ﺑﻘﻄﺮ ‪ 0.65‬ﻣﻢ‬
‫ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫)ﻧﻮﻉ ﺛﻨﺎﺋﻲ ﺳﻠﻚ(‬
‫‪ 0.33‬ﺇﻟﻰ ‪1.25‬‬
‫ﻛﺒﻞ ‪ PVC‬ﻣﻐﻠﻒ*‬
‫ﻛﺒﻞ ﺛﻨﺎﺋﻲ ﻣﻠﻔﻮﻑ‪ ،‬ﻣﺰﺩﻭﺝ‬
‫ﺍﻟﻤﺮﻛﺰ ﻏﻴﺮ ﻗﻄﺒﻲ‬
‫ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫)ﻧﻮﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ(‬
‫‪0.33‬‬
‫ﻛﺒﻞ ‪ PVC‬ﻣﻐﻠﻒ*‬
‫ﻣﺮﻛﺰ ﺛﻼﺛﻲ ﺍﻷﻗﻄﺎﺏ‬
‫‪ .1.3.6‬ﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‬
‫‪ 20‬ﻣﻢ‬
‫ﻛﺒﻞ ﺍﻟﺘﺄﺭﻳﺾ )ﺍﻷﺭﺿﻲ(‬
‫‪ 30‬ﻣﻢ‬
‫‪ .A‬ﻟﻸﺳﻼﻙ ﺑﻤﺮﻛﺰ ﻣﺼﻤﺖ‬
‫)‪ (1‬ﻟﺘﻮﺻﻴﻞ ﺍﻟﻄﺮﻑ ﺍﻟﻜﻬﺮﺑﺎﺋﻲ‪ ،‬ﺍﺗﺒﻊ ﺍﻟﻤﺨﻄﻂ ﺃﺩﻧﺎﻩ ﻭﻗﻢ ﺑﺎﻟﺘﻮﺻﻴﻞ ﺑﻌﺪ ﻋﻤﻞ ﻃﻴﺔ ﺣﻮﻝ ﻃﺮﻑ ﺍﻟﻜﺒﻞ‪.‬‬
‫)‪ (2‬ﺍﺳﺘﺨﺪﻡ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﺤﺪﺩﺓ‪ ،‬ﻭﻗﻢ ﺑﺘﻮﺻﻴﻠﻬﺎ ﺑﺈﺣﻜﺎﻡ‪ ،‬ﺛﻢ ﺛﺒﺘﻬﺎ ﺑﺤﻴﺚ ﻻ ﻳﻜﻮﻥ ﻫﻨﺎﻙ ﺃﻱ ﺷﺪ ﻋﻠﻰ ﺍﻷﻃﺮﺍﻑ‪.‬‬
‫*‪ :‬ﺍﺳﺘﺨﺪﻡ ﻛﺒﻞ ﻣﻐﻠﻒ ً‬
‫ﻭﻓﻘﺎ ﻟﻠﻘﻮﺍﻋﺪ ﺍﻟﻤﺤﻠﻴﺔ ﻟﻜﺒﻼﺕ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫)‪ (3‬ﺍﺳﺘﺨﺪﻡ ﻣﻔﻚ ﻣﻨﺎﺳﺐ ﻟﺮﺑﻂ ﺑﺮﺍﻏﻲ ﺍﻷﻃﺮﺍﻑ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﻣﻔﻚ ﺻﻐﻴﺮ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﻳﺘﻠﻒ ﺭﺃﺱ ﺍﻟﺒﺮﻏﻲ ﻭﻳﻤﻨﻊ ﺭﺑﻂ ﺍﻟﺒﺮﺍﻏﻲ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪.‬‬
‫)‪ (4‬ﻻ ﺗﺮﺑﻂ ﺍﻟﺒﺮﺍﻏﻲ ﺍﻟﻄﺮﻓﻴﺔ ﺑﺸﻜﻞ ﻣﻔﺮﻁ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﻳﻨﻜﺴﺮ ﺍﻟﺒﺮﻏﻲ‪.‬‬
‫)‪ (5‬ﺭﺍﺟﻊ ﺍﻟﺠﺪﻭﻝ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻋﺰﻡ ﺭﺑﻂ ﺍﻟﺒﺮﻏﻲ‪.‬‬
‫)‪ (6‬ﻻ ﺗُﺜﺒﺖ ﻛﺒﻠﻲ ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ )‪ (2‬ﺃﻭ ﺃﻛﺜﺮ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺑﺮﻏﻲ ﻭﺍﺣﺪ )‪.(1‬‬
‫ﻧﺰﻉ ‪ 25‬ﻣﻢ‬
‫ﺣﻠﻘﺔ‬
‫ﺑﺮﻏﻲ‬
‫ﺑﺤﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﺍﻟﻜﺒﻞ‬
‫ﻃﺮﻑ ﺍﻟﻜﺒﻞ )ﺣﻠﻘﺔ(‬
‫ﺑﺮﻏﻲ‬
‫ﺑﺤﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﻃﺮﻑ ﺍﻟﻜﺒﻞ )ﺣﻠﻘﺔ(‬
‫ﻣﺠﻤﻮﻋﺔ ﻃﺮﻓﻴﺔ‬
‫ﺍﻟﻜﺒﻞ‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﺃﺳﻼﻙ ﻓﺮﻋﻴﺔ‪ .‬ﻓﻘﺪ ﺗﺘﺴﺒﺐ ﻓﻲ ﺻﺪﻣﺔ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺃﻭ ﺣﺮﻳﻖ‪.‬‬
‫‪Ar-8‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 8‬‬
‫ﺗﺤﺬﻳﺮ‬
‫ﻋﺰﻡ ﺍﻟﺮﺑﻂ‬
‫ﻋﻨﺪ ﺍﺳﺘﺨﺪﺍﻡ ﻛﺒﻼﺕ ﺑﻤﺮﻛﺰ ﻣﺼﻤﺖ‪ ،‬ﻻ ﺗﺴﺘﺨﺪﻡ ﻃﺮﻑ ﺣﻠﻘﻲ‪ .‬ﺇﺫﺍ ﻛﻨﺖ ﺗﺴﺘﺨﺪﻡ ﻛﺒﻼﺕ ﺑﻤﺮﻛﺰ ﻣﺼﻤﺖ ﺫﺍﺕ ﻃﺮﻑ ﺣﻠﻘﻲ‪،‬‬
‫ﻓﺈﻥ ﺭﺑﺎﻁ ﺍﻟﻀﻐﻂ ﻟﻠﻄﺮﻑ ﺍﻟﺤﻠﻘﻲ ﻗﺪ ﻳﺘﻠﻒ ﻭﻳﺴﺒﺐ ﺳﺨﻮﻧﺔ ﻏﻴﺮ ﻋﺎﺩﻳﺔ ﻟﻠﻜﺒﻼﺕ‪.‬‬
‫‪ 0.5‬ﺇﻟﻰ ‪ 0.6‬ﻧﻴﻮﺗﻦ ﻣﺘﺮ‬
‫)‪ 5‬ﺇﻟﻰ ‪ 6‬ﻛﺠﻢ ﻗﻮﺓ ﺳﻢ(‬
‫ﺑﺮﻏﻲ ‪) M3‬ﺍﻟﻨﻘﻞ ‪(X1, X2 /‬‬
‫)ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ‪(Y1, Y2, Y3 /‬‬
‫ﺗﻨﺒﻴﻪ‬
‫‪ .B‬ﻟﻸﺳﻼﻙ ﺍﻟﻤﺠﺪﻭﻟﺔ‬
‫ﻟﺘﻘﺸﻴﺮ ﺍﻟﻐﻼﻑ ﻣﻦ ﻛﺒﻞ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺮﺋﻴﺴﻲ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﺃﺩﺍﺓ ﻣﺨﺼﺼﺔ ﻻ ﺗﺘﻠﻒ ﻛﺒﻞ ﺍﻟﻤﻮﺻﻞ‪.‬‬
‫)‪ (1‬ﺍﺳﺘﺨﺪﻡ ﺃﻃﺮﺍﻑ ﺣﻠﻘﻴﺔ ﺑﺄﻛﻤﺎﻡ ﻋﺎﺯﻟﺔ ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ﺍﻟﺸﻜﻞ ﺍﻟﺘﺎﻟﻲ ﻟﻠﺘﻮﺻﻴﻞ ﺑﺎﻟﻤﺠﻤﻮﻋﺔ ﺍﻟﻄﺮﻓﻴﺔ‪.‬‬
‫ﻋﻨﺪ ﺗﺮﻛﻴﺐ ﺑﺮﻏﻲ ﻋﻠﻰ ﺍﻟﻤﺠﻤﻮﻋﺔ ﺍﻟﻄﺮﻓﻴﺔ ﻻ ﺗﻘﻄﻊ ﺍﻟﻜﺒﻞ ﻣﻦ ﺧﻼﻝ ﺍﻟﺮﺑﻂ ﺍﻟﻤﻔﺮﻁ ﻟﻠﺒﺮﻏﻲ‪ .‬ﻣﻦ ﻧﺎﺣﻴﺔ ﺃﺧﺮﻯ‪ ،‬ﻳﺆﺩﻱ ﺍﻟﺒﺮﻏﻲ‬
‫ﻏﻴﺮ ﺍﻟﻤﺮﺑﻮﻁ ﺑﺈﺣﻜﺎﻡ ﺇﻟﻰ ﻋﻄﻞ ﻓﻲ ﺍﻟﺘﻮﺻﻴﻞ‪ ،‬ﻣﻤﺎ ﻳﺆﺩﻱ ﺇﻟﻰ ﺗﻌﻄﻞ ﺍﻻﺗﺼﺎﻝ‪.‬‬
‫)‪ (2‬ﻗﻢ ﺑﺘﻌﺸﻴﻖ ﺍﻷﻃﺮﺍﻑ ﺍﻟﺤﻠﻘﻴﺔ ﺑﺈﺣﻜﺎﻡ ﺑﺎﻟﻜﺒﻼﺕ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺃﺩﺍﺓ ﻣﻨﺎﺳﺒﺔ ﺑﺤﻴﺚ ﻻ ﺗﺼﺒﺢ ﺍﻟﻜﺒﻼﺕ ﻣﻔﻜﻮﻛﺔ‪.‬‬
‫)‪ (3‬ﺍﺳﺘﺨﺪﻡ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﺤﺪﺩﺓ‪ ،‬ﻭﻗﻢ ﺑﺘﻮﺻﻴﻠﻬﺎ ﺑﺈﺣﻜﺎﻡ‪ ،‬ﺛﻢ ﺛﺒﺘﻬﺎ ﺑﺤﻴﺚ ﻻ ﻳﻜﻮﻥ ﻫﻨﺎﻙ ﺃﻱ ﺷﺪ ﻋﻠﻰ ﺍﻷﻃﺮﺍﻑ‪.‬‬
‫‪ .4.6‬ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‬
‫)‪ (4‬ﺍﺳﺘﺨﺪﻡ ﻣﻔﻚ ﻣﻨﺎﺳﺐ ﻟﺮﺑﻂ ﺑﺮﺍﻏﻲ ﺍﻷﻃﺮﺍﻑ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﻣﻔﻚ ﺻﻐﻴﺮ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﻳﺘﻠﻒ ﺭﺃﺱ ﺍﻟﺒﺮﻏﻲ ﻭﻳﻤﻨﻊ ﺭﺑﻂ ﺍﻟﺒﺮﺍﻏﻲ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪.‬‬
‫)‪ (1‬ﻗﻢ ﺑﺈﺯﺍﻟﺔ ﻏﻄﺎء ﺻﻨﺪﻭﻕ ﺍﻟﺘﺤﻜﻢ ﻭﺗﺮﻛﻴﺐ ﻛﻞ ﻛﺒﻞ ﺗﻮﺻﻴﻞ‪.‬‬
‫)‪ (5‬ﻻ ﺗﺮﺑﻂ ﺍﻟﺒﺮﺍﻏﻲ ﺍﻟﻄﺮﻓﻴﺔ ﺑﺸﻜﻞ ﻣﻔﺮﻁ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﻳﻨﻜﺴﺮ ﺍﻟﺒﺮﻏﻲ‪.‬‬
‫* ﻗﻢ ﺑﻤﻞء ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ ﻭﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺑﻤﻌﺠﻮﻥ ﺃﻭ ﻋﺎﺯﻝ ﺣﺮﺍﺭﻱ ﺑﺤﻴﺚ ﻻ‬
‫ﺗﺪﺧﻞ ﺍﻟﺤﺸﺮﺍﺕ ﺃﻭ ﺍﻟﻐﺒﺎﺭ ﺇﻟﻰ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫)‪ (6‬ﺭﺍﺟﻊ ﺍﻟﺠﺪﻭﻝ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻋﺰﻡ ﺭﺑﻂ ﺍﻟﺒﺮﻏﻲ‪.‬‬
‫)‪ (7‬ﻻ ﺗُﺜﺒﺖ ﻛﺒﻠﻲ ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ )‪ (2‬ﺃﻭ ﺃﻛﺜﺮ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺑﺮﻏﻲ ﻭﺍﺣﺪ )‪.(1‬‬
‫ﻃﺮﻑ ﺣﻠﻘﻲ‬
‫ﻧﺰﻉ ‪ 10‬ﻣﻢ‬
‫* ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‬
‫ﻹﺩﺧﺎﻝ ﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‪.‬‬
‫ُﻛﻢ‬
‫ﻣﺸﺒﻚ ﻛﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ‬
‫ﺑﺮﻏﻲ‬
‫ﺑﺤﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﺑﺮﻏﻲ‬
‫ﺑﺤﻠﻘﺔ ﺧﺎﺻﺔ‬
‫ﺍﻟﻜﺒﻞ‬
‫ﻃﺮﻑ ﺣﻠﻘﻲ‬
‫ﻃﺮﻑ ﺣﻠﻘﻲ‬
‫ﻣﺠﻤﻮﻋﺔ ﻃﺮﻓﻴﺔ‬
‫ﺍﻟﻜﺒﻞ‬
‫‪ 1‬ﻏﻄﺎء ﺍﻷﺳﻼﻙ‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺍﺳﺘﺨﺪﻡ ﺃﻃﺮﺍﻑ ﺣﻠﻘﻴﺔ ﻭﺍﺭﺑﻂ ﺑﺮﺍﻏﻲ ﺍﻷﻃﺮﺍﻑ ﺣﺴﺐ ﺍﻟﻌﺰﻡ ﺍﻟﻤﺤﺪﺩ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﺗﺼﺪﺭ ﺳﺨﻮﻧﺔ ﺯﺍﺋﺪﺓ ﻏﻴﺮ ﻋﺎﺩﻳﺔ ﻭﻣﻦ‬
‫ﺍﻟﻤﺤﺘﻤﻞ ﺃﻥ ﺗﺴﺒﺐ ﺗﻠﻒ ﺧﻄﻴﺮ ﺩﺍﺧﻞ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫ﻟﻮﺣﺔ ﻃﺮﻓﻴﺔ ﻟﻠﻄﺎﻗﺔ‬
‫‪ 2‬ﻏﻄﺎء ﺻﻨﺪﻭﻕ ﺍﻟﺘﺤﻜﻢ‬
‫ﻋﺰﻡ ﺍﻟﺮﺑﻂ‬
‫‪ 1.2‬ﺇﻟﻰ ‪ 1.8‬ﻧﻴﻮﺗﻦ ﻣﺘﺮ‬
‫)‪ 12‬ﺇﻟﻰ ‪ 18‬ﻛﺠﻢ ﻗﻮﺓ ﺳﻢ(‬
‫ﺑﺮﻏﻲ ‪M4‬‬
‫)ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ‪(L, N, GND /‬‬
‫* ﻣﻨﻔﺬ ﺗﻮﺻﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫‪ .2.3.6‬ﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﻛﺒﻞ ﺍﻟﻨﻘﻞ‬
‫ﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﺍﻟﻮﺣﺪﺓ ﺍﻟﻄﺮﻓﻴﺔ ﻟﻮﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﻹﺩﺧﺎﻝ ﻛﺒﻞ ﺍﻟﻨﻘﻞ ﻭﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫‪ 30‬ﻣﻢ‬
‫)‪ (2‬ﻳﺮﺟﻰ ﺭﺑﻂ ﻛﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺈﺣﻜﺎﻡ ﻭﻛﺒﻞ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ‪.‬‬
‫‪ 40‬ﻣﻢ‬
‫ﻛﺒﻞ ﻣﻐﻠﻒ )ﺑﺪﻭﻥ ﺭﻗﺎﻗﺔ(‬
‫ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﻟﻠﻨﻮﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫ﻟﻠﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫‪ 30‬ﻣﻢ‬
‫‪ 30‬ﻣﻢ‬
‫• ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﻛﺒﻼﺕ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻭﻛﺒﻼﺕ ﺍﻟﻨﻘﻞ ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ‪.C .Fig‬‬
‫‪C .Fig‬‬
‫ﻣﺤﻈﻮﺭ‬
‫ﺗﻮﺻﻴﻞ ﻓﻲ ﺟﺎﻧﺐ ‪ 1‬ﻭﺍﺣﺪ‬
‫ﺟﻴﺪ‬
‫ﻗﻄﺮ ﻣﺨﺘﻠﻒ‬
‫ﺗﺤﺬﻳﺮ‬
‫ﺍﺭﺑﻂ ﺑﺮﺍﻏﻲ ﺍﻷﻃﺮﺍﻑ ﺣﺴﺐ ﺍﻟﻌﺰﻡ ﺍﻟﻤﺤﺪﺩ‪ ،‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﺗﺼﺪﺭ ﺳﺨﻮﻧﺔ ﺯﺍﺋﺪﺓ ﻏﻴﺮ ﻋﺎﺩﻳﺔ ﻭﻣﻦ ﺍﻟﻤﺤﺘﻤﻞ ﺃﻥ ﺗﺴﺒﺐ ﺗﻠﻒ‬
‫ﺧﻄﻴﺮ ﺩﺍﺧﻞ ﺍﻟﻮﺣﺪﺓ‪.‬‬
‫‪Ar-9‬‬
‫‪3/14/2016 4:32:18 PM‬‬
‫‪9371022451_IM_AR.indd 9‬‬
‫ﺗﻨﺒﻴﻪ‬
‫‪ .5.6‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺨﺎﺭﺟﻲ ﻭﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ )ﺃﺟﺰﺍء ﺍﺧﺘﻴﺎﺭﻳﺔ(‬
‫ﻋﻨﺪ ﺗﺒﺪﻳﻞ ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ )‪ ,(SW1‬ﺗﺄﻛﺪ ﻣﻦ ﺇﻳﻘﺎﻑ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﺇﻟﻰ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪ .‬ﺧﻼﻑ ﺫﻟﻚ‪ ،‬ﻗﺪ ﺗﺘﻠﻒ ﻟﻮﺣﺔ‬
‫ﺍﻟﻜﻤﺒﻴﻮﺗﺮ ﻓﻲ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻟﻮﺣﺔ ﻛﻤﺒﻴﻮﺗﺮ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ‬
‫ﺍﻟﻤﺰﺩﻭﺟﺔ )‪(SET 2‬‬
‫ﻃﺮﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ‬
‫)‪(CNA03‬‬
‫ﺗﺸﻐﻴﻞ ﺇﻳﻘﺎﻑ‬
‫ﻣﺸﺒﻚ ﺍﻟﻜﺒﻞ‬
‫)‪(CNA01‬‬
‫‪SW1‬‬
‫‪SW2‬‬
‫‪SW3‬‬
‫‪SW4‬‬
‫‪:N ،L‬‬
‫ﻛﺒﻞ ﺇﻣﺪﺍﺩ‬
‫ﺍﻟﻄﺎﻗﺔ‬
‫ﻃﺮﻑ ﺍﻹﺧﺮﺍﺝ‬
‫)‪(CNB01‬‬
‫ﺃﺭﺿﻲ )ﺗﺄﺭﻳﺾ(‬
‫)‪(CNA04‬‬
‫)‪(CNA02‬‬
‫ﻃﺮﻑ ﺍﻟﺘﻼﻣﺲ ﺍﻟﺠﺎﻑ‬
‫)‪ (1‬ﺍﻹﺩﺧﺎﻝ ﺍﻟﺨﺎﺭﺟﻲ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫•‬
‫•‬
‫‪:X2 ،X1‬‬
‫ﻛﺒﻞ ﺍﻟﻨﻘﻞ‬
‫ﻳﻤﻜﻦ ﺗﺸﻐﻴﻞ‪/‬ﺇﻳﻘﺎﻑ‪ ،‬ﺃﻭ ﻋﻤﻞ ﺇﻳﻘﺎﻑ ﻃﻮﺍﺭﺉ‪ ،‬ﺃﻭ ﺇﻳﻘﺎﻑ ﺇﺟﺒﺎﺭﻱ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ ﺭﻗﻢ ‪ CNA01‬ﺃﻭ‬
‫‪ CNA02‬ﺑﺎﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻳﻤﻜﻦ ﺍﺧﺘﻴﺎﺭ ﻭﺿﻊ "ﺗﺸﻐﻴﻞ‪/‬ﺇﻳﻘﺎﻑ" ﺃﻭ "ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ" ﺃﻭ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ" ﻣﻊ ﺇﻋﺪﺍﺩ ﻭﻇﻴﻔﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻳﻤﻜﻦ ﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺇﺟﺒﺎﺭﻳًﺎ ﻋﻦ ﻃﺮﻳﻖ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ ﺑﻮﺍﺳﻄﺔ ﺍﺳﺘﺨﺪﺍﻡ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ ﺭﻗﻢ ‪ CNA03‬ﺃﻭ‬
‫‪ CNA04‬ﻓﻲ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻳﺠﺐ ﺍﺳﺘﺨﺪﺍﻡ ﻛﺒﻞ ﺛﻨﺎﺋﻲ ﻣﻠﻔﻮﻑ )ﻣﻘﺎﺱ ‪ .(AWG22‬ﺃﻗﺼﻰ ﻃﻮﻝ ﻟﻠﻜﺒﻞ ‪ 150‬ﻣﺘﺮ‪.‬‬
‫ﺍﺳﺘﺨﺪﻡ ﻛﺒﻞ ﺇﺩﺧﺎﻝ ﻭﺇﺧﺮﺍﺝ ﺧﺎﺭﺟﻲ ﺑﺎﻷﺑﻌﺎﺩ ﺍﻟﺨﺎﺭﺟﻴﺔ ﺍﻟﻤﻨﺎﺳﺒﺔ‪ ،‬ﺗﺒﻌًﺎ ﻟﻌﺪﺩ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﺮﺍﺩ ﺗﺮﻛﻴﺒﻬﺎ‪.‬‬
‫ﻳﺠﺐ ﺃﻥ ﺗﻜﻮﻥ ﻭﺻﻠﺔ ﺍﻟﺴﻠﻚ ﻣﻨﻔﺼﻠﺔ ﻋﻦ ﺧﻂ ﻛﺒﻞ ﺍﻟﻄﺎﻗﺔ‪.‬‬
‫ﺍﺧﺘﻴﺎﺭ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﺳﺘﺨﺪﻡ ﺃﺣﺪ ﺃﻧﻮﺍﻉ ﺍﻷﻃﺮﺍﻑ ﻫﺬﻩ ﺗﺒﻌًﺎ ﻟﻼﺳﺘﻌﻤﺎﻝ‪) .‬ﻻ ﻳﻤﻜﻦ ﺍﺳﺘﺨﺪﺍﻡ ﻛﻼ ﺍﻟﻨﻮﻋﻴﻦ ﻣﻦ ﺍﻷﻃﺮﺍﻑ ﻓﻲ ﻧﻔﺲ ﺍﻟﻮﻗﺖ‪(.‬‬
‫● ﻃﺮﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ )]‪([CNA03] ،[CNA01‬‬
‫ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ )ﻣﺘﻮﺳﻂ(‬
‫)ﺍﻟﻤﻠﺤﻘﺎﺕ(‬
‫ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﻓﻲ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺬﻱ ﺗﺮﻳﺪ ﺗﻮﺻﻴﻠﻪ‪ ،‬ﺍﺳﺘﺨﺪﺍﻡ ﻃﺮﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ )]‪،[CNA01‬‬
‫]‪.([CNA03‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺤﻤﻞ‬
‫‪CNA01‬‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ‬
‫)‪(SW1‬‬
‫*‪b‬‬
‫‪ :Y1‬ﻏﻴﺮ ﻗﻄﺒﻲ‬
‫‪ :Y2‬ﻏﻴﺮ ﻗﻄﺒﻲ‬
‫‪ :Y3‬ﻻ ﺗﻘﻢ ﺑﺘﻮﺻﻴﻠﻪ *‪1‬‬
‫ﻟﻠﻨﻮﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫*‪a‬‬
‫‪ :Y1‬ﺃﺣﻤﺮ‬
‫‪ :Y2‬ﺃﺑﻴﺾ‬
‫‪ :Y3‬ﺃﺳﻮﺩ‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺤﻤﻞ‬
‫‪CNA03‬‬
‫‪ 3‬ﺳﻠﻚ‬
‫*‪a‬‬
‫*‪ :1‬ﻓﻲ ﺣﺎﻟﺔ ﺗﻮﺻﻴﻞ ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻓﻲ ﺍﻟﻄﺮﻑ ‪ ،Y3‬ﻓﺈﻥ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻦ ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ‬
‫ﺍﻷﺳﻼﻙ ﻟﻦ ﺗﻌﻤﻞ‪.‬‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪3‬‬
‫ﺇﻋﺪﺍﺩ ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ )‪ 2 (SW1‬ﺳﻠﻚ )ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ(‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺤﻤﻞ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫ﻟﻠﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫ﺗﻮﺻﻴﻞ ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫*‪a‬‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫‪:Y3،Y2،Y1‬‬
‫ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫*‪ 1‬ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﺘﻤﺮ‬
‫‪ 12‬ﺇﻟﻰ ‪ 24‬ﻓﻮﻟﺖ‬
‫ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‬
‫)‪ (3‬ﻳﺮﺟﻰ ﺗﺜﺒﻴﺖ ﻛﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ ﺑﻤﺸﺒﻚ ﻛﺒﻞ‪ .‬ﺛﻢ ﻗﻢ ﺑﺘﺮﻛﺐ ﻏﻄﺎء ﺍﻷﺳﻼﻙ ﺑﺎﻟﺒﺮﺍﻏﻲ‪.‬‬
‫)‪(c‬‬
‫*‪ 1‬ﺍﺟﻌﻞ ﻣﺼﺪﺭ ﺍﻟﻄﺎﻗﺔ ‪ 12‬ﺇﻟﻰ ‪ 24‬ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ‪ .‬ﺣﺪﺩ ﻗﺪﺭﺓ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻣﻊ ﻓﺎﺋﺾ ﻛﺒﻴﺮ ﻟﻠﺤﻤﻞ ﺍﻟﻤﺘﺼﻞ‪.‬‬
‫ﻻ ﺗﺴﺘﺨﺪﻡ ﺟﻬ ًﺪﺍ ﻳﺘﺠﺎﻭﺯ ‪ 24‬ﻓﻮﻟﺖ ﻓﻲ ﺍﻟﻤﺴﺎﻣﻴﺮ ‪ 2-1‬ﻭ‪.3-1‬‬
‫*‪ a‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻪ ﻫﻮ ‪ 5‬ﺇﻟﻰ ‪ 10‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﺗﻴﺎﺭ ﻣﺒﺎﺷﺮ‪) .‬ﺍﻟﻤﻮﺻﻰ ﺑﻪ‪ 5 :‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ(‬
‫ﻗﻢ ﺑﺘﻮﻓﻴﺮ ﻣﻘﺎﻭﻣﺔ ﺣﻤﻞ ﺑﺤﻴﺚ ﻳﺼﺒﺢ ﺍﻟﺘﻴﺎﺭ ‪ 10‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ ﺃﻭ ﺃﻗﻞ‪.‬‬
‫ً‬
‫ﻣﻨﺨﻔﻀﺎ ﻟﻠﻐﺎﻳﺔ )ﺍﻟﻤﺴﺘﺨﺪﻣﺔ ﻋﻨﺪ ‪ 12‬ﻓﻮﻟﺖ ‪ 1‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ ﺃﻭ ﺃﻗﻞ(‪.‬‬
‫ﺗﻴﺎﺭﺍ‬
‫ﺣﺪﺩ ﻣﻼﻣﺴﺎﺕ ﺗﺴﺘﺨﺪﻡ ً‬
‫*‪ b‬ﺍﻟﻘﻄﺒﻴﺔ ﺗﻜﻮﻥ ]‪ [+‬ﻟﻠﻤﺴﺎﺭ ‪ 1‬ﻭ ]‪ [-‬ﻟﻠﻤﺴﻤﺎﺭ ‪ 2‬ﻭ‪ .3‬ﻗﻢ ﺑﺎﻟﺘﻮﺻﻴﻞ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‪.‬‬
‫ﻋﻨﺪ ﺍﻟﺘﻮﺻﻴﻞ ﻓﻲ ﺃﻃﺮﺍﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ ﻟﻌﺪﺓ ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ ﻣﻊ ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‪ ،‬ﺗﺄﻛﺪ ﻣﻦ ﻋﻤﻞ ﺗﻔﺮﻳﻌﺔ ﺧﺎﺭﺝ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺍﻟﺘﻲ‬
‫ﺗﺴﺘﺨﺪﻡ ﺻﻨﺪﻭﻕ ﺳﺤﺐ ﺃﻭ ﻏﻴﺮﻩ‪ ،‬ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ﺍﻟﻤﺜﺎﻝ ﺍﻟﺘﺎﻟﻲ‪.‬‬
‫ﺍﺭﺑﻂ ﺑﺈﺣﻜﺎﻡ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﻻ ﺗﺤﺰﻡ ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺃﻭ ﺗﻤﺪﺩ ﻛﺒﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺑﺸﻜﻞ ﻣﺘﻮﺍﺯﻱ ﻣﻊ ﺳﻠﻚ ﺗﻮﺻﻴﻞ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ )ﺇﻟﻰ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ( ﻭﻛﺒﻞ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ‪ .‬ﻓﻘﺪ ﻳﺴﺒﺐ ﻋﻄﻞ ﻓﻲ ﺍﻟﺘﺸﻐﻴﻞ‪.‬‬
‫‪CNA01‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺤﻤﻞ‬
‫‪CNA01‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫)‪ (4‬ﻗﻢ ﺑﺘﺮﻛﻴﺐ ﻏﻄﺎء ﺻﻨﺪﻭﻕ ﺍﻟﺘﺤﻜﻢ‪.‬‬
‫ﻣﻘﺎﻭﻣﺔ‬
‫ﺍﻟﺤﻤﻞ‬
‫ﺟﻬﺎﺯ‬
‫ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫ﺗﻔﺎﺻﻴﻞ )‪(c‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﺘﻤﺮ‬
‫‪ 12‬ﺇﻟﻰ ‪ 24‬ﻓﻮﻟﺖ‬
‫ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‬
‫‪CNA01‬‬
‫‪Ar-10‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 10‬‬
‫]"ﺽﺏﻥ" ﻝﺍﺥﺩﺇﻝﺍ ﺓﻝﺍﺡ ﻱﻑ[‬
‫● ﻃﺮﻑ ﺍﻻﺗﺼﺎﻝ ﺍﻟﺠﺎﻑ )]‪([CNA04] ،[CNA02‬‬
‫ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﻣﻦ ﻏﻴﺮ ﺍﻟﻀﺮﻭﺭﻱ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺇﻟﻰ ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺬﻱ ﺗﺮﻳﺪ ﺗﻮﺻﻴﻠﻪ‪ ،‬ﺍﺳﺘﺨﺪﺍﻡ ﻃﺮﻑ ﺍﻻﺗﺼﺎﻝ ﺍﻟﺠﺎﻑ )]‪،[CNA02‬‬
‫]‪.([CNA04‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺍﻷﻣﺮ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﻘﻨﺎﺓ‪1‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ‬
‫ﺍﻟﻘﻨﺎﺓ ‪2‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﻋﺎﺩﻱ‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫‪CNA02‬‬
‫*‪c‬‬
‫*‪c‬‬
‫ﻗﻨﺎﺓ ‪1‬‬
‫ﻗﻨﺎﺓ ‪2‬‬
‫ﺃﺭﺿﻲ‬
‫* ﺗﺘﻮﻗﻒ ﺟﻤﻴﻊ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻟﻨﻔﺲ ﻧﻈﺎﻡ ﺍﻟﺘﺒﺮﻳﺪ ﻋﻨﺪ ﺗﺸﻐﻴﻞ ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ‪.‬‬
‫*‪d‬‬
‫● ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ ﻫﻮ ﻭﺿﻊ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ"‪.‬‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﺣﺰ"[‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‬
‫ﺍﻷﻣﺮ‬
‫ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺍﻟﻘﻨﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ً‬
‫ﻣﻨﺨﻔﻀﺎ ﻟﻠﻐﺎﻳﺔ )ﺍﻟﻤﺴﺘﺨﺪﻣﺔ ﻋﻨﺪ ‪ 12‬ﻓﻮﻟﺖ ‪ 1‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ ﺃﻭ ﺃﻗﻞ(‪.‬‬
‫ﺗﻴﺎﺭﺍ‬
‫*‪ c‬ﺣﺪﺩ ﻣﻼﻣﺴﺎﺕ ﺗﺴﺘﺨﺪﻡ ً‬
‫ﺣﺬﺭﺍ ﻋﻠﻰ ﻭﺟﻪ ﺍﻟﺨﺼﻮﺹ ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ‪.‬‬
‫*‪ d‬ﺍﻷﺳﻼﻙ ﻣﺨﺘﻠﻔﺔ ﻋﻦ ﺃﻃﺮﺍﻑ ﺗﻄﺒﻴﻖ ﺍﻟﺠﻬﺪ‪ .‬ﻛﻦ ً‬
‫ﺗﺸﻐﻴﻞ ← ﺇﻳﻘﺎﻑ‬
‫ﻋﻨﺪ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺄﻃﺮﺍﻑ ﺍﻟﺘﻮﺻﻴﻞ ﺍﻟﺠﺎﻑ ﻟﻌﺪﺓ ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ ﻣﻊ ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‪ ،‬ﻗﻢ ﺑﻌﺰﻝ ﻛﻞ ﻭﺣﺪﺓ ﺩﺍﺧﻠﻴﺔ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻣﺮﺣﻞ ﺃﻭ‬
‫ﻏﻴﺮﻩ‪ ،‬ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ﺍﻟﻤﺜﺎﻝ ﺍﻟﺘﺎﻟﻲ‪.‬‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﻋﺎﺩﻱ‬
‫]"ﺽﺏﻥ" ﻝﺍﺥﺩﺇﻝﺍ ﺓﻝﺍﺡ ﻱﻑ[‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺍﻷﻣﺮ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻘﻨﺎﺓ‪1‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ‬
‫ﺍﻟﻘﻨﺎﺓ ‪2‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﻋﺎﺩﻱ‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫‪K1‬‬
‫‪K4‬‬
‫‪CNA02‬‬
‫* ﻋﻨﺪ ﺗﻨﺸﻴﻂ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ‪ ،‬ﺗﺘﻮﻗﻒ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻳﺘﻢ ﺗﻘﻴﻴﺪ ﻋﻤﻠﻴﺔ "ﺍﻹﻳﻘﺎﻑ‪/‬ﺍﻟﺘﺸﻐﻴﻞ" ﻋﻦ ﻃﺮﻳﻖ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫* ﻋﻨﺪ ﺍﺳﺘﺨﺪﺍﻡ ﻭﻇﻴﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ ﻣﻊ ﺗﺸﻜﻴﻞ ﻣﺠﻤﻮﻋﺔ ﺗﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪ ،‬ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﻧﻔﺲ ﺍﻟﺠﻬﺎﺯ ﺑﻜﻞ ﻭﺣﺪﺓ ﺩﺍﺧﻠﻴﺔ ﺩﺍﺧﻞ‬
‫ﺍﻟﻤﺠﻤﻮﻋﺔ‪.‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻟﻠﻤﺮﺣﻞ‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫‪K2‬‬
‫‪K5‬‬
‫‪CNA02‬‬
‫• ﺗﺤﺪﻳﺪ ﺃﺳﻠﻮﺏ ﺍﻟﻮﻇﺎﺋﻒ‬
‫ﻳﻤﻜﻦ ﺍﺧﺘﻴﺎﺭ ﻭﺿﻊ "ﺗﺸﻐﻴﻞ‪/‬ﺇﻳﻘﺎﻑ" ﺃﻭ "ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ" ﺃﻭ "ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ" ﻣﻊ ﺇﻋﺪﺍﺩ ﻭﻇﻴﻔﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫● ﻭﻇﻴﻔﺔ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ ﻣﻦ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‬
‫]ﺍﻹﺩﺧﺎﻝ "ﺣﺰ" ﻓﻘﻂ[‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪K3‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ ﺑﻮﺍﺳﻄﺔ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‬
‫ﺗﺸﻐﻴﻞ ← ﺇﻳﻘﺎﻑ‬
‫ﻋﺎﺩﻱ‬
‫ﺍﻟﻘﻨﺎﺓ ‪ 3‬ﻟـ ‪ CNA03‬ﺃﻭ ‪CNA04‬‬
‫ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ‪1‬‬
‫‪K6‬‬
‫ﺍﻷﻣﺮ‬
‫‪CNA02‬‬
‫ﺟﻬﺎﺯ ﺍﻹﺩﺧﺎﻝ ‪2‬‬
‫)‪ (2‬ﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ‬
‫‪ :K1 - K6‬ﻣﺮﺣﻞ‬
‫)ﺟﻬﺎﺯ ﻟﻠﺘﻴﺎﺭ ﺍﻟﻤﺴﺘﻤﺮ(‬
‫• ﻳﺠﺐ ﺍﺳﺘﺨﺪﺍﻡ ﻛﺒﻞ ﺛﻨﺎﺋﻲ ﻣﻠﻔﻮﻑ )ﻣﻘﺎﺱ ‪ .(22AWG‬ﺃﻗﺼﻰ ﻃﻮﻝ ﻟﻠﻜﺒﻞ ‪ 25‬ﻣﺘﺮ‪.‬‬
‫• ﺍﺳﺘﺨﺪﻡ ﻛﺒﻞ ﺇﺩﺧﺎﻝ ﻭﺇﺧﺮﺍﺝ ﺧﺎﺭﺟﻲ ﺑﺎﻷﺑﻌﺎﺩ ﺍﻟﺨﺎﺭﺟﻴﺔ ﺍﻟﻤﻨﺎﺳﺒﺔ‪ ،‬ﺗﺒﻌًﺎ ﻟﻌﺪﺩ ﺍﻟﻜﺒﻼﺕ ﺍﻟﻤﺮﺍﺩ ﺗﺮﻛﻴﺒﻬﺎ‪.‬‬
‫ﻣﻼﺣﻈﺔ‪:‬‬
‫• ﺟﻬﺪ ﺍﻹﺧﺮﺍﺝ‪ :‬ﻣﺮﺗﻔﻊ ‪ ±2 12‬ﻓﻮﻟﺖ‪ ،‬ﻣﻨﺨﻔﺾ ‪ 0‬ﻓﻮﻝ‪.‬‬
‫ﻋﻨﺪ ﺍﻟﺘﻮﺻﻴﻞ ﺑﻌﺪﺓ ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ ﻣﺒﺎﺷﺮﺓ‪ ،‬ﺳﻮﻑ ﻳﺴﺒﺐ ﺍﻟﺘﻌﻄﻞ‪.‬‬
‫• ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻪ‪ 50 :‬ﻣﻴﻠﻲ ﺃﻣﺒﻴﺮ‬
‫ﺳﻠﻮﻙ ﺍﻟﺘﺸﻐﻴﻞ‬
‫ﺣﺰ‬
‫● ﻧﻮﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﻳﻤﻜﻦ ﺍﺧﺘﻴﺎﺭ ﻧﻮﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‪.‬‬
‫ﻭﻳﺘﻢ ﺗﺒﺪﻳﻠﻬﺎ ﻣﻦ ﺧﻼﻝ ﻣﻔﺘﺎﺡ ﻣﺒﺪﻟﺔ ﻣﺰﺩﻭﺟﺔ ﻋﻠﻰ ﻟﻮﺣﺔ ﻛﻤﺒﻴﻮﺗﺮ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ ]ﺇﻋﺪﺍﺩ ‪[SW2 2‬‬
‫● ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﻣﺆﺷﺮ ﺃﻭ ﻏﻴﺮﻩ ﻣﺒﺎﺷﺮﺓ‬
‫ﻧﺒﺾ‬
‫ﻧﻮﻉ ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺇﻳﻘﺎﻑ )ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ(‬
‫ﺣﺰ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﻧﺒﺾ‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫ﻋﺮﺽ ﺍﻟﻨﺒﺾ ﻳﺠﺐ ﺃﻥ ﻳﻜﻮﻥ‬
‫ﺃﻃﻮﻝ ﻣﻦ ‪ 200‬ﻣﻴﻠﻲ ﺛﺎﻧﻴﺔ‪.‬‬
‫ﻣﺆﺷﺮ‬
‫ﺍﻟﺘﺸﻐﻴﻞ‬
‫ﻣﺆﺷﺮ‬
‫ﺍﻟﺨﻄﺄ‬
‫‪CNB‬‬
‫‪01‬‬
‫● ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ ﻫﻮ ﻭﺿﻊ "ﺗﺸﻐﻴﻞ‪/‬ﺇﻳﻘﺎﻑ"‪.‬‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﺣﺰ"[‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺍﺧﺘﻴﺎﺭ ﺍﻹﺧﺮﺍﺝ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﻣﺆﺷﺮ ﺣﺎﻟﺔ ﻣﺮﻭﺣﺔ ﺍﻟﻮﺣﺪﺓ‬
‫ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻷﻣﺮ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺗﺸﻐﻴﻞ ← ﺇﻳﻘﺎﻑ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‬
‫ﺍﻟﻘﻨﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫● ﻋﻨﺪ ﺍﻟﺘﻮﺻﻴﻞ ﺑﻮﺣﺪﺓ ﻣﺠﻬﺰﺓ ﺑﻤﺼﺪﺭ ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ‬
‫ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ‬
‫]ﻓﻲ ﺣﺎﻟﺔ ﺍﻹﺩﺧﺎﻝ "ﻧﺒﺾ"[‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺘﺼﻞ ‪1‬‬
‫ﺍﻷﻣﺮ‬
‫ﺍﻟﻘﻨﺎﺓ‪1‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺍﻟﻘﻨﺎﺓ ‪2‬‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺘﺼﻞ ‪2‬‬
‫‪CNB‬‬
‫‪01‬‬
‫‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫ﺟﻬﺎﺯ‬
‫ﻣﺘﺼﻞ ‪3‬‬
‫* ﺍﻷﻣﺮ ﺍﻷﺧﻴﺮ ﻟﻪ ﺍﻷﻭﻟﻮﻳﺔ‪.‬‬
‫* ﺗﻌﻤﻞ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺿﻤﻦ ﻧﻔﺲ ﻣﺠﻤﻮﻋﺔ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻓﻲ ﻧﻔﺲ ﺍﻟﻮﺿﻊ‪.‬‬
‫ﻣﺮﺣﻞ )ﻳﺘﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ(‬
‫ﻭﺣﺪﺓ ﻣﺘﺼﻠﺔ‬
‫● ﻋﻨﺪﻣﺎ ﻳﻜﻮﻥ ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ ﻫﻮ ﻭﺿﻊ "ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ"‪.‬‬
‫]"ﺯﺡ" ﻝﺍﺥﺩﺇﻝﺍ ﺓﻝﺍﺡ ﻱﻑ[‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺍﻷﻣﺮ‬
‫ﺇﺷﺎﺭﺓ ﺍﻹﺩﺧﺎﻝ‬
‫ﺇﻳﻘﺎﻑ ← ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ‬
‫ﺗﺸﻐﻴﻞ ← ﺇﻳﻘﺎﻑ‬
‫ﻋﺎﺩﻱ‬
‫ﺍﻟﻘﻨﺎﺓ‪ 1‬ﻟـ ‪ CNA01‬ﺃﻭ ‪CNA02‬‬
‫‪Ar-11‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 11‬‬
‫ﺳﻠﻮﻙ ﺍﻟﺘﺸﻐﻴﻞ‬
‫‪A .Fig‬‬
‫ﺍﻟﻤﻮﺻﻞ‬
‫ﺟﻬﺪ ﺍﻹﺧﺮﺍﺝ‬
‫ﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ ‪1‬‬
‫ﺍﻟﻤﺴﺎﻣﻴﺮ ‪2-1‬‬
‫ﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ ‪2‬‬
‫ﺍﻟﻤﺴﺎﻣﻴﺮ ‪3-1‬‬
‫‪CNB01‬‬
‫ﺍﻹﺧﺮﺍﺝ ﺍﻟﺨﺎﺭﺟﻲ ‪3‬‬
‫ﺍﻟﻤﺴﺎﻣﻴﺮ ‪4-1‬‬
‫ﺍﻟﺤﺎﻟﺔ‬
‫‪ 0‬ﻓﻮﻟﺖ‬
‫ﺇﻳﻘﺎﻑ‬
‫‪ 12‬ﻓﻮﻟﺖ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ‬
‫ﺗﺸﻐﻴﻞ‬
‫‪ 0‬ﻓﻮﻟﺖ‬
‫ﻋﺎﺩﻱ‬
‫‪ 12‬ﻓﻮﻟﺖ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ‬
‫ﺧﻄﺄ‬
‫‪ 0‬ﻓﻮﻟﺖ‬
‫ﺇﻳﻘﺎﻑ ﻣﺮﻭﺣﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪ 12‬ﻓﻮﻟﺖ ﺗﻴﺎﺭ ﻣﺴﺘﻤﺮ‬
‫ﺗﺸﻐﻴﻞ ﻣﺮﻭﺣﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)‪ (3‬ﻃﺮﻕ ﺍﻟﺘﻮﺻﻴﻞ‬
‫ﺑﺮﻏﻲ‬
‫• ﺗﻌﺪﻳﻞ ﺍﻟﺴﻠﻚ‬
‫ﻗﻢ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻌﺎﺯﻝ ﻣﻦ ﺍﻟﺴﻠﻚ ﺍﻟﻤﻠﺤﻖ ﺑﻤﻮﺻﻞ ﻃﻘﻢ ﺍﻟﺴﻠﻚ‪.‬‬
‫ﻗﻢ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻌﺎﺯﻝ ﻣﻦ ﺍﻟﻜﺒﻞ ﺍﻟﺬﻱ ﺗﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ‪ .‬ﺍﺳﺘﺨﺪﻡ ﻣﻮﺻﻞ ﻏﻠﻴﻆ ﻣﻌﺰﻭﻝ ﻣﻦ ﺍﻟﻨﻮﻉ ﺍﻟﻤﺠﻌﺪ ﻟﺮﺑﻂ ﻛﺒﻞ ﺍﻟﻤﺠﺎﻝ ﻣﻊ ﺳﻠﻚ‬
‫ﺍﻟﻄﻘﻢ‪.‬‬
‫ﻗﻢ ﺑﺘﻮﺻﻴﻞ ﺍﻟﺴﻠﻚ ﻣﻊ ﺳﻠﻚ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻟﻠﺤﺎﻡ‪.‬‬
‫ﻫﺎﻡ‪ :‬ﺗﺄﻛﺪ ﻣﻦ ﻋﺰﻝ ﺍﻟﺘﻮﺻﻴﻞ ﺑﻴﻦ ﺍﻷﺳﻼﻙ‪.‬‬
‫ﺃﺟﺰﺍء ﺍﺧﺘﻴﺎﺭﻳﺔ‬
‫ﺳﻠﻚ ﺇﺩﺧﺎﻝ‪/‬ﺇﺧﺮﺍﺝ ﺧﺎﺭﺟﻲ‬
‫ﻏﻄﺎء‬
‫ﻣﺜﺎﻝ ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ‪"0" :‬‬
‫ﻳﺘﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ‬
‫ﻗﻢ ﺑﻠﺤﺎﻡ ﻭﻋﺰﻝ ﺍﻷﺟﺰﺍء ﺍﻟﻤﺘﺼﻠﺔ‪.‬‬
‫• ﺃﻃﺮﺍﻑ ﺍﻟﺘﻮﺻﻴﻞ ﻭﺗﺮﺗﻴﺒﺎﺕ ﺍﻷﺳﻼﻙ‬
‫ﻣﺜﺎﻝ ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ‪:‬‬
‫"‪"0‬‬
‫ﻓﻲ ﺍﻟﺸﻜﻞ ﺍﻟﺘﺎﻟﻲ‪ ،‬ﺗﻢ ﺗﻮﺻﻴﻞ ﺟﻤﻴﻊ ﺍﻟﻤﻮﺻﻼﺕ ﺍﻟﻤﻤﻜﻨﺔ ﻷﺟﻞ ﺍﻟﺘﻮﺿﻴﺢ‪.‬‬
‫ﻓﻲ ﺍﻟﺘﺮﻛﻴﺐ ﺍﻟﻔﻌﻠﻲ‪ ,‬ﻻ ﻳﻤﻜﻨﻚ ﺗﻮﺻﻴﻞ ﺟﻤﻴﻊ ﺍﻟﻤﻮﺻﻼﺕ ﻣﺮﺓ ﻭﺍﺣﺪﺓ‪.‬‬
‫ﺭﺍﺑﻂ ﺍﻟﻜﺒﻞ )ﻳﺘﻢ ﺷﺮﺍﺅﻩ ﻣﺤﻠﻴًﺎ(‪:‬‬
‫ﺭﺑﻂ ﻓﻲ ﻛﺒﻞ ﺍﻟﻨﻘﻞ‬
‫ﺧﻄﺎﻑ‬
‫ﻧﻮﻉ ﺍﻟﻤﻔﺘﺎﺡ‬
‫ﺍﻹﻋﺪﺍﺩ‬
‫ﻧﻄﺎﻕ ﺍﻹﻋﺪﺍﺩ‬
‫ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪ 0‬ﺇﻟﻰ ‪63‬‬
‫ﻣﺜﺎﻝ ﺍﻹﻋﺪﺍﺩ‬
‫‪2‬‬
‫ﻋﻨﻮﺍﻥ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‬
‫‪ 0‬ﺇﻟﻰ ‪99‬‬
‫ﻣﺜﺎﻝ ﺍﻹﻋﺪﺍﺩ‬
‫‪63‬‬
‫‪IU AD × 10‬‬
‫‪CNA04‬‬
‫‪CNA03 CNA02‬‬
‫‪CNA01‬‬
‫‪CNB01‬‬
‫ﻛﺒﻞ ﺍﻟﻨﻘﻞ‬
‫‪ .7‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺠﺎﻝ‬
‫‪REF AD × 10‬‬
‫ﺛﻤﺔ ‪ 3‬ﻃﺮﻕ ﻹﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ ﻣﻦ ﺧﻼﻝ ﺇﻋﺪﺍﺩ ﺍﻟﻤﺠﺎﻝ ﻛﺎﻟﺘﺎﻟﻲ‪.‬‬
‫ﻗﻢ ﺑﺎﻹﻋﺪﺍﺩ ﺑﻮﺍﺳﻄﺔ ﺃﻱ ﻣﻦ ﺍﻟﻄﺮﻕ‪.‬‬
‫ﻳﺘﻢ ﺗﻮﺿﻴﺢ ﻛﻞ ﻃﺮﻳﻘﺔ ﺇﻋﺪﺍﺩ ﻓﻲ )‪ (1‬ﺇﻟﻰ )‪ (3‬ﺃﺩﻧﺎﻩ‪.‬‬
‫)‪ (1‬ﺇﻋﺪﺍﺩﺍﺕ ‪ ..... IU AD, REF AD SW‬ﻫﺬﻩ ﺍﻟﻘﺴﻢ )‪ .1.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ(‬
‫)‪ (2‬ﺇﻋﺪﺍﺩﺍﺕ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ‪ .............‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ ﻭﺍﻟﻼﺳﻠﻜﻴﺔ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ‬
‫ﻣﻌﻠﻮﻣﺎﺕ ﺍﻹﻋﺪﺍﺩ ﺍﻟﺘﻔﺼﻴﻠﻴﺔ‪) .‬ﺇﻋﺪﺍﺩ ‪IU AD, REF AD SW‬‬
‫ﻋﻠﻰ ‪(0‬‬
‫)‪ (3‬ﺇﻋﺪﺍﺩﺍﺕ ﺍﻟﻌﻨﻮﺍﻥ ﺍﻟﺘﻠﻘﺎﺋﻴﺔ ‪ ...................‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎﺕ ﺍﻹﻋﺪﺍﺩ ﺍﻟﺘﻔﺼﻴﻠﻴﺔ‪) .‬ﺇﻋﺪﺍﺩ ‪IU‬‬
‫‪ AD, REF AD SW‬ﻋﻠﻰ ‪(0‬‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺗﺄﻛﺪ ﻣﻦ ﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ ﻗﺒﻞ ﺗﻨﻔﻴﺬ ﺇﻋﺪﺍﺩ ﺍﻟﻤﺠﺎﻝ‪.‬‬
‫‪IU AD × 1‬‬
‫‪REF AD × 1‬‬
‫)‪ (1‬ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(IU AD × 1‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(IU AD × 10‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﻋﺪﺓ ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ ﺑﻨﻈﺎﻡ ﺗﺒﺮﻳﺪ ‪ 1‬ﻭﺣﺪ‪ ،‬ﻗﻢ ﺑﺈﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ ﻓﻲ ‪ IU AD SW‬ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ‪.A Table‬‬
‫)‪ (2‬ﻋﻨﻮﺍﻥ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(IU AD × 1‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(IU AD × 10‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺘﺨﺪﺍﻡ ﻋﺪﺓ ﺃﻧﻈﻤﺔ ﺗﺒﺮﻳﺪ‪ ،‬ﻗﻢ ﺑﺈﻋﺪﺍﺩ ‪ REF AD SW‬ﻛﻤﺎ ﻫﻮ ﻣﻮﺿﺢ ﻓﻲ ‪ A Table‬ﻟﻜﻞ ﻧﻈﺎﻡ ﺗﺒﺮﻳﺪ‪.‬‬
‫ﻗﻢ ﺑﺎﻹﻋﺪﺍﺩ ﻋﻠﻰ ﻧﻔﺲ ﻋﻨﻮﺍﻥ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ ﻣﺜﻞ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ‪.‬‬
‫• ﻓﻲ ﺍﻟﺤﺎﻟﺔ ﺍﻟﻌﻤﻞ ﻓﻲ ﺑﻴﺌﺔ ﻳﻤﻜﻦ ﻓﻴﻬﺎ ﺍﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﻼﺳﻠﻜﻴﺔ‪ ،‬ﻳﻤﻜﻦ ً‬
‫ﺃﻳﻀﺎ ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﺎﻭﻳﻦ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫• ﻓﻲ ﺣﺎﻟﺔ ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﻼﺳﻠﻜﻴﺔ‪ ،‬ﻗﻢ ﺑﺈﻋﺪﺍﺩ ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻋﻨﻮﺍﻥ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‬
‫ﻋﻠﻰ "‪."00‬‬
‫)ﻟﻤﺰﻳﺪ ﻣﻦ ﺍﻟﻤﻌﻠﻮﻣﺎﺕ ﺣﻮﻝ ﺍﻹﻋﺪﺍﺩ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﻼﺳﻠﻜﻴﺔ‪(.‬‬
‫‪ .1.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ‬
‫ﺗﻨﺒﻴﻪ‬
‫ﺍﺳﺘﺨﺪﻡ ﻣﻔﻚ ﻣﻌﺰﻭﻝ ﻹﻋﺪﺍﺩ ﻣﻔﺎﺗﻴﺢ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ‪.‬‬
‫• ﻗﻢ ﺑﺈﺯﺍﻟﺔ ﺍﻟﻐﻄﺎء ﻣﻦ ﺧﻼﻝ ﺍﻟﺮﺟﻮﻉ ﺇﻟﻰ ‪ A .Fig‬ﺃﺩﻧﺎﻩ‪ .‬ﻭﻗﻢ ﺑﺘﺮﻛﻴﺐ ﺍﻟﻐﻄﺎء ﺑﻌﺪ ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ‪.‬‬
‫‪Ar-12‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 12‬‬
‫ﺇﻋﺪﺍﺩ ﺭﻣﺰ ﻣﺨﺼﺺ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪A Table‬‬
‫ﺇﻋﺪﺍﺩ ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ‬
‫ﺍﻟﻌﻨﻮﺍﻥ‬
‫ﺍﻟﻌﻨﻮﺍﻥ‬
‫‪REF AD SW‬‬
‫ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‬
‫‪× 10‬‬
‫‪×1‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫‪8‬‬
‫‪9‬‬
‫‪10‬‬
‫‪11‬‬
‫‪12‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪1‬‬
‫‪1‬‬
‫‪1‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫‪8‬‬
‫‪9‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪99‬‬
‫‪9‬‬
‫‪9‬‬
‫ﺇﻋﺪﺍﺩ ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ‬
‫ﻗﻢ ﺑﺈﻋﺪﺍﺩ ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ ‪ SET 3 SW1‬ﻭ‪ ،SW2‬ﻣﻦ ﺧﻼﻝ ﺍﻟﺮﺟﻮﻉ ﺇﻟﻰ ‪.B Table‬‬
‫‪IU AD SW‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪× 10‬‬
‫‪×1‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫‪8‬‬
‫‪9‬‬
‫‪10‬‬
‫‪11‬‬
‫‪12‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪0‬‬
‫‪1‬‬
‫‪1‬‬
‫‪1‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪5‬‬
‫‪6‬‬
‫‪7‬‬
‫‪8‬‬
‫‪9‬‬
‫‪0‬‬
‫‪1‬‬
‫‪2‬‬
‫‪.‬‬
‫‪.‬‬
‫‪.‬‬
‫‪63‬‬
‫‪6‬‬
‫‪3‬‬
‫ﺗﺸﻐﻴﻞ‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ‬
‫"‪"SET 3‬‬
‫ﺇﻳﻘﺎﻑ‬
‫‪SW SW SW SW‬‬
‫‪1‬‬
‫‪2‬‬
‫‪3‬‬
‫‪4‬‬
‫‪B Table‬‬
‫ﻻ ﺗﻘﻢ ﺑﺈﻋﺪﺍﺩ ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ )‪ (IU AD SW‬ﻋﻠﻰ ‪ 64‬ﺇﻟﻰ ‪.99‬‬
‫ﻓﻘﺪ ﻳﺆﺩﻱ ﺇﻟﻰ ﺍﻟﺘﻌﻄﻞ‪.‬‬
‫)‪ (3‬ﻋﻨﻮﺍﻥ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫‪ (i‬ﺍﻟﻨﻮﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(RC AD SW‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﻋﺪﺓ ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ ﺑـ ‪ 1‬ﻭﺣﺪﺓ ﺗﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺳﻠﻜﻴﺔ‪ ،‬ﻗﻢ ﺑﺈﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ ﻓﻲ ‪ RC AD SW‬ﺿﻤﻦ ﺗﺴﻠﺴﻞ ﻣﻦ ‪.0‬‬
‫ﻧﻄﺎﻕ ﺍﻹﻋﺪﺍﺩ‬
‫ﺍﻹﻋﺪﺍﺩ‬
‫ﻋﻨﻮﺍﻥ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ ‪SET 3 SW1‬‬
‫ﻣﻔﺘﺎﺡ ﺍﻟﻤﺒﺪﻟﺔ ﺍﻟﻤﺰﺩﻭﺟﺔ ‪SET 3 SW2‬‬
‫‪) A‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ(‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺍﻟﺮﻣﺰ ﺍﻟﻤﺨﺼﺺ‬
‫‪B‬‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫‪C‬‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ‬
‫‪D‬‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﻧﻮﻉ ﺍﻟﻤﻔﺘﺎﺡ‬
‫ﻣﺜﺎﻝ ﺍﻹﻋﺪﺍﺩ‬
‫‪0‬‬
‫‪ 0‬ﺇﻟﻰ ‪15‬‬
‫‪RC AD‬‬
‫ﻣﺜﺎﻝ‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺗﻮﺻﻴﻞ ‪ 4‬ﻭﺣﺪﺍﺕ ﺩﺍﺧﻠﻴﺔ‪.‬‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪RC AD SW‬‬
‫‪3‬‬
‫‪RC AD SW‬‬
‫‪2‬‬
‫‪RC AD SW‬‬
‫‪1‬‬
‫‪RC AD SW‬‬
‫‪0‬‬
‫ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﻋﻦ ﺑﻌﺪ‬
‫‪RC AD SW‬‬
‫ﺍﻟﻌﻨﻮﺍﻥ‬
‫‪0‬‬
‫‪0‬‬
‫‪1‬‬
‫‪1‬‬
‫‪2‬‬
‫‪2‬‬
‫‪3‬‬
‫‪3‬‬
‫‪4‬‬
‫‪4‬‬
‫‪5‬‬
‫‪5‬‬
‫‪6‬‬
‫‪6‬‬
‫‪7‬‬
‫‪7‬‬
‫‪RC AD SW‬‬
‫ﺍﻟﻌﻨﻮﺍﻥ‬
‫‪8‬‬
‫‪8‬‬
‫‪9‬‬
‫‪9‬‬
‫‪A‬‬
‫‪10‬‬
‫‪B‬‬
‫‪11‬‬
‫‪C‬‬
‫‪12‬‬
‫‪D‬‬
‫‪13‬‬
‫‪E‬‬
‫‪14‬‬
‫‪F‬‬
‫‪15‬‬
‫‪ (ii‬ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺪﻭﺍﺭ )‪...(RC AD SW‬ﺇﻋﺪﺍﺩ ﺍﻟﻤﺼﻨﻊ "‪"0‬‬
‫ﻧﻈﺮﺍ ﻷﻧﻪ ﻳﺘﻢ ﺗﻜﻮﻳﻦ ﺇﻋﺪﺍﺩﺍﺕ ﻋﻨﻮﺍﻥ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺗﻠﻘﺎﺋﻴًﺎ‪ ،‬ﻓﻼ ﻳﻠﺰﻣﻚ ﺗﻜﻮﻳﻨﻬﺎ‪.‬‬
‫ً‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺍﻟﺘﻜﻮﻳﻦ ﺍﻟﻴﺪﻭﻱ‪ ،‬ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺗﻜﻮﻳﻦ ﻛﻼ ﻣﻦ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪ .‬ﻟﻤﻌﺮﻓﺔ ﺍﻟﺘﻔﺎﺻﻴﻞ‪ ،‬ﻳﺮﺟﻰ‬
‫ﻣﺮﺍﺟﻌﺔ ﺩﻟﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫‪ .2.7‬ﺇﻋﺪﺍﺩ ﺭﻣﺰ ﻣﺨﺼﺺ‬
‫ﻳﺆﺩﻱ ﺍﺧﺘﻴﺎﺭ ﺭﻣﺰ ﻣﺨﺼﺺ ﺇﻟﻰ ﻣﻨﻊ ﺍﻟﺨﻠﻂ ﺑﻴﻦ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ‪.‬‬
‫)ﻳﻤﻜﻨﻚ ﺇﻋﺪﺍﺩ ﺣﺘﻰ ‪ 4‬ﺭﻣﻮﺯ‪(.‬‬
‫ﻗﻢ ﺑﺘﻨﻔﻴﺬ ﺍﻹﻋﺪﺍﺩ ﻟﻜﻞ ﻣﻦ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫ﺗﻐﻴﻴﺮ ﺍﻟﺮﻣﺰ‬
‫‪D‬‬
‫‪D‬‬
‫‪C‬‬
‫‪C‬‬
‫‪B‬‬
‫‪B‬‬
‫‪A‬‬
‫‪A‬‬
‫ﺍﻟﺘﺒﺎﺱ‬
‫ﺍﻟﻮﺣﺪﺓ‬
‫ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﻋﻦ ﺑﻌﺪ‬
‫‪Ar-13‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 13‬‬
‫ﺍﻟﻮﻇﻴﻔﺔ‬
‫‪ .3.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ‬
‫•‬
‫•‬
‫•‬
‫•‬
‫ﻳﻤﻜﻦ ﺗﻨﻔﻴﺬ ﺇﻋﺪﺍﺩ ﺍﻟﻮﻇﻴﻔﺔ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ ﻭﺍﻟﻼﺳﻠﻜﻴﺔ‪.‬‬
‫)ﺗﻌﺘﺒﺮ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻦ ﺍﻷﺟﻬﺰﺓ ﺍﻻﺧﺘﻴﺎﺭﻳﺔ(‬
‫ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ ﻭﺍﻟﻼﺳﻠﻜﻴﺔ ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎﺕ ﺍﻹﻋﺪﺍﺩ ﺍﻟﺘﻔﺼﻴﻠﻴﺔ‪.‬‬
‫ﺭﺍﺟﻊ "‪ .1.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ" ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﺇﻋﺪﺍﺩﺍﺕ ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‪.‬‬
‫ﻗﻢ ﺑﺘﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻗﺒﻞ ﺑﺪء ﺍﻹﻋﺪﺍﺩ‪.‬‬
‫* ﻳﺘﻢ ﺗﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ ﻓﻲ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺘﻲ ﺗﻘﻮﻡ ﺑﺘﻬﻴﺌﺔ ‪ ،EEV‬ﻟﺬﺍ ﺗﺄﻛﺪ ﻣﻦ ﺇﺟﺮﺍء ﺍﺧﺘﺒﺎﺭ ﻣﻨﻊ ﺗﺴﺮﻳﺐ ﺍﻟﻬﻮﺍء ﻋﻠﻰ ﺍﻟﻤﻮﺍﺳﻴﺮ ﻭﺍﻟﺘﻔﺮﻳﻎ‬
‫ﻗﺒﻞ ﺗﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ‪.‬‬
‫* ً‬
‫ﺃﻳﻀﺎ ﺃﻓﺤﺺ ﻣﺮﺓ ﺃﺧﺮﻯ ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﻋﺪﻡ ﺍﺭﺗﻜﺎﺏ ﺧﻄﺄ ﻓﻲ ﺗﻮﺻﻴﻼﺕ ﺍﻷﺳﻼﻙ ﻗﺒﻞ ﺗﺸﻐﻴﻞ ﺍﻟﻄﺎﻗﺔ‪.‬‬
‫ﺭﻗﻢ ﺍﻟﻮﻇﻴﻔﺔ‬
‫ﺍﻻﻓﺘﺮﺍﺿﻲ‬
‫ﺭﻗﻢ ﺍﻹﻋﺪﺍﺩ‬
‫)ﻣﺤﻈﻮﺭ(‬
‫‪60‬‬
‫‪00‬‬
‫○‬
‫)ﻣﺤﻈﻮﺭ(‬
‫‪61‬‬
‫‪00‬‬
‫○‬
‫)ﻣﺤﻈﻮﺭ(‬
‫‪62‬‬
‫‪00‬‬
‫○‬
‫ﺍﻟﺘﻔﺎﺻﻴﻞ‬
‫‪ .1.3.7‬ﺍﺳﻢ ﺍﻟﺰﺭ ﻭﺍﻟﻮﻇﻴﻔﺔ‬
‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﻮﻇﻴﻔﺔ‬
‫ﺍﻟﻮﻇﻴﻔﺔ‬
‫ﺭﻗﻢ ﺍﻟﻮﻇﻴﻔﺔ‬
‫ﻓﺎﺻﻞ ﻣﺆﺷﺮ‬
‫ﺍﻟﻤﺮﺷﺢ‬
‫‪11‬‬
‫ﺗﺸﻐﻴﻞ ﻣﺆﺷﺮ‬
‫ﺍﻟﻤﺮﺷﺢ‬
‫‪13‬‬
‫ﺗﺪﻓﻖ ﻫﻮﺍء ﺍﻟﺴﻘﻒ‬
‫‪20‬‬
‫ﺍﺗﺠﺎﻩ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء‬
‫ﺍﻟﺮﺃﺳﻲ‬
‫‪23‬‬
‫ﺍﻃﻼﻕ ﺣﺮﺍﺭﺓ‬
‫ﺍﻟﻬﻮﺍء ﺍﻟﺒﺎﺭﺩ‬
‫‪30‬‬
‫ﺍﻃﻼﻕ ﺣﺮﺍﺭﺓ‬
‫ﺍﻟﻬﻮﺍء ﺍﻟﺴﺎﺧﻦ‬
‫‪31‬‬
‫ﺇﻋﺎﺩﺓ ﺍﻟﺘﺸﻐﻴﻞ‬
‫ﺍﻟﺘﻠﻘﺎﺋﻲ‬
‫‪40‬‬
‫ﻣﻨﻊ ﺍﻟﻬﻮﺍء ﺍﻟﺒﺎﺭﺩ‬
‫‪43‬‬
‫ﺗﺤﻜﻢ ﺧﺎﺭﺟﻲ‬
‫‪46‬‬
‫ﻫﺪﻑ ﺗﻘﺮﻳﺮ‬
‫ﺍﻟﺨﻄﺄ‬
‫‪47‬‬
‫ﺇﻋﺪﺍﺩ ﺍﻟﻤﺮﻭﺣﺔ‬
‫ﻋﻨﺪ ﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ‬
‫ﺍﻟﺘﺒﺮﻳﺪ ﺑﻮﺍﺳﻄﺔ‬
‫ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‪.‬‬
‫‪49‬‬
‫ﺭﻗﻢ ﺍﻹﻋﺪﺍﺩ‬
‫‪00‬‬
‫ﻗﻴﺎﺳﻲ‬
‫‪01‬‬
‫ﻃﻮﻳﻞ‬
‫‪02‬‬
‫ﻗﺼﻴﺮ‬
‫‪00‬‬
‫ﺗﻤﻜﻴﻦ‬
‫‪01‬‬
‫ﺗﻌﻄﻴﻞ‬
‫‪02‬‬
‫ﻋﺮﺽ ﻓﻲ ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﺍﻟﻤﺮﻛﺰﻳﺔ ﻓﻘﻂ‬
‫‪00‬‬
‫ﻗﻴﺎﺳﻲ‬
‫‪01‬‬
‫ﺳﻘﻒ ﻣﺮﺗﻔﻊ‬
‫‪00‬‬
‫ﻗﻴﺎﺳﻲ‬
‫‪01‬‬
‫ﺭﻓﻊ‬
‫‪00‬‬
‫ﻗﻴﺎﺳﻲ‬
‫‪01‬‬
‫ﺿﺒﻂ )‪(1‬‬
‫‪02‬‬
‫ﺿﺒﻂ )‪(2‬‬
‫‪00‬‬
‫ﻗﻴﺎﺳﻲ‬
‫‪01‬‬
‫ﺿﺒﻂ )‪(1‬‬
‫‪02‬‬
‫ﺿﺒﻂ )‪(2‬‬
‫‪03‬‬
‫ﺿﺒﻂ )‪(3‬‬
‫‪00‬‬
‫ﺗﻤﻜﻴﻦ‬
‫‪01‬‬
‫ﺗﻌﻄﻴﻞ‬
‫‪ 00‬ﻣﻨﺨﻔﺾ ﻟﻠﻐﺎﻳﺔ‬
‫ﺍﻻﻓﺘﺮﺍﺿﻲ‬
‫○‬
‫‪00‬‬
‫‪01‬‬
‫ﺇﻳﻘﺎﻑ ﺍﻟﻄﻮﺍﺭﺉ‬
‫‪02‬‬
‫ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ‬
‫‪00‬‬
‫ﺍﻟﻜﻞ‬
‫‪01‬‬
‫ﻋﺮﺽ ﻓﻲ ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﺍﻟﻤﺮﻛﺰﻳﺔ ﻓﻘﻂ‬
‫ﺍﺗﺒﺎﻉ ﺍﻹﻋﺪﺍﺩ ﻋﻠﻰ ﻭﺣﺪﺓ‬
‫‪00‬‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫‪ 01‬ﺇﻳﻘﺎﻑ‬
‫ﺿﺒﻂ ﺇﺧﻄﺎﺭ ﻓﺎﺻﻞ ﺗﻨﻈﻴﻒ ﺍﻟﻤﺮﺷﺢ‪ .‬ﺇﺫﺍ ﻛﺎﻥ‬
‫ﻣﺒﻜﺮﺍ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﻗﻢ ﺑﺎﻟﺘﻐﻴﻴﺮ ﺇﻟﻰ ﺍﻹﻋﺪﺍﺩ‬
‫ﺍﻹﺧﻄﺎﺭ ً‬
‫‪ .01‬ﺇﺫﺍ ﻛﺎﻥ ﺍﻹﺧﻄﺎﺭ‬
‫ﻣﺘﺄﺧﺮﺍ ﻟﻠﻐﺎﻳﺔ‪ ،‬ﻗﻢ ﺑﺎﻟﺘﻐﻴﻴﺮ‬
‫ً‬
‫ﺇﻟﻰ ﺍﻹﻋﺪﺍﺩ ‪.02‬‬
‫○‬
‫ﺗﻤﻜﻴﻦ ﻣﺆﺷﺮ ﺍﻟﻤﺮﺷﺢ‪ .‬ﺍﻹﻋﺪﺍﺩ ‪ 02‬ﻟﻼﺳﺘﺨﺪﺍﻡ‬
‫ﻣﻊ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﻤﺮﻛﺰﻳﺔ‪.‬‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪FILTER‬‬
‫○‬
‫ﺗﻨﻈﻴﻢ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﻋﻠﻰ ﺣﺴﺐ ﺍﺣﺘﻴﺎﺟﺎﺕ ﻣﻜﺎﻥ‬
‫ﺍﻟﺘﺮﻛﻴﺐ‪ .‬ﻋﻨﺪ ﺍﻹﻋﺪﺍﺩ ﻋﻠﻰ ‪ ,01‬ﻳﻜﻮﻥ ﺗﺪﻓﻖ‬
‫ﺍﻟﻬﻮﺍء ﻗﻮﻳًﺎ‪) .‬ﺍﻟﻨﻮﻉ ﻋﻠﻰ ﺷﻜﻞ ﻋﻠﻴﺒﺔ ﻓﻘﻂ(‬
‫○‬
‫ﺿﺒﻂ ﺍﺗﺠﺎﻩ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﺍﻟﺮﺃﺳﻲ‪ .‬ﻳﺘﻢ ﺿﺒﻂ ﺟﻤﻴﻊ‬
‫ﻓﺘﺤﺎﺕ ﺍﺗﺠﺎﻩ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﻣﻌًﺎ‪.‬‬
‫)ﺍﻟﻨﻮﻉ ﻋﻠﻰ ﺷﻜﻞ ﻋﻠﻴﺒﺔ ﻓﻘﻂ(‬
‫)ﺍﻟﻤﺮﺷﺢ( )ﺍﻷﺣﻤﺮ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪TIMER‬‬
‫)ﺍﻟﻤﺆﻗﺖ()ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪OPERATION‬‬
‫)ﺍﻟﺘﺸﻐﻴﻞ( )ﺍﻷﺧﻀﺮ(‬
‫○‬
‫ﺿﺒﻂ ﺣﺮﺍﺭﺓ ﺇﻃﻼﻕ ﺍﻟﻬﻮﺍء ﺍﻟﺒﺎﺭﺩ‪ .‬ﻟﺘﻘﻠﻴﻞ ﺣﺮﺍﺭﺓ‬
‫ﺍﻹﻃﻼﻕ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﺍﻹﻋﺪﺍﺩ ‪ .01‬ﻟﺮﻓﻊ ﺣﺮﺍﺭﺓ‬
‫ﺍﻹﻃﻼﻕ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﺍﻹﻋﺪﺍﺩ ‪.02‬‬
‫○‬
‫ﺿﺒﻂ ﺣﺮﺍﺭﺓ ﺇﻃﻼﻕ ﺍﻟﻬﻮﺍء ﺍﻟﺴﺎﺧﻦ‪ .‬ﻟﺘﻘﻠﻴﻞ‬
‫ﺣﺮﺍﺭﺓ ﺍﻹﻃﻼﻕ ﺑﻤﻘﺪﺍﺭ ‪ 6‬ﺩﺭﺟﺎﺕ ﻣﺌﻮﻳﺔ‪،‬‬
‫ﺍﺳﺘﺨﺪﻡ ﺍﻹﻋﺪﺍﺩ ‪ .01‬ﻟﺘﻘﻠﻴﻞ ﺣﺮﺍﺭﺓ ﺍﻹﻃﻼﻕ‬
‫ﺑﻤﻘﺪﺍﺭ ‪ 4‬ﺩﺭﺟﺎﺕ ﻣﺌﻮﻳﺔ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﺍﻹﻋﺪﺍﺩ ‪.02‬‬
‫ﻟﺮﻓﻊ ﺣﺮﺍﺭﺓ ﺍﻹﻃﻼﻕ‪ ،‬ﺍﺳﺘﺨﺪﻡ ﺍﻹﻋﺪﺍﺩ ‪.03‬‬
‫ﺯﺭ ‪MANUAL AUTO‬‬
‫)ﻳﺪﻭﻱ ﺗﻠﻘﺎﺋﻲ(‬
‫)ﺍﺧﺘﻴﺎﺭﻱ(‬
‫‪ .2.3.7‬ﻓﺤﺺ ﺇﻋﺪﺍﺩﺍﺕ ﺍﻟﻮﻇﻴﻔﺔ‬
‫• ﺍﺿﻐﻂ ﻣﻊ ﺍﻻﺳﺘﻤﺮﺍﺭ ﻋﻠﻰ ﺯﺭ "‪) "MANUAL AUTO‬ﺗﻠﻘﺎﺋﻲ ﻳﺪﻭﻱ( ﻋﻠﻰ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻟﻤﺪﺓ ‪ 3‬ﺛﻮﺍﻧﻲ ﻟﻔﺤﺺ ﺇﻋﺪﺍﺩﺍﺕ‬
‫ﺍﻟﻮﻇﻴﻔﺔ‪ .‬ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﻓﺼﻞ ﺍﻟﻄﺎﻗﺔ ﻣﻦ ﺃﺟﻞ ﺍﻟﻌﻮﺩﺓ ﺇﻟﻰ ﻭﺿﻊ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﻌﺎﺩﻱ‪.‬‬
‫)‪ (1‬ﺇﺷﺎﺭﺓ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﻋﻨﻮﺍﻥ ﻧﻈﺎﻡ ﺍﻟﺘﺒﺮﻳﺪ‬
‫○‬
‫ﺗﻤﻜﻴﻦ ﺃﻭ ﺗﻌﻄﻴﻞ ﺇﻋﺎﺩﺓ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﺘﻠﻘﺎﺋﻲ ﻟﻠﻨﻈﺎﻡ‬
‫ﺑﻌﺪ ﺍﻧﻘﻄﺎﻉ ﺍﻟﻄﺎﻗﺔ‪.‬‬
‫○‬
‫ﻳﻤﻨﻊ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء ﺍﻟﺒﺎﺭﺩ ﻣﻊ ﺟﻌﻞ ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍء‬
‫ً‬
‫ﻣﻨﺨﻔﻀﺎ ﻋﻨﺪ ﺑﺪء ﺗﺸﻐﻴﻞ ﺍﻟﺘﺪﻓﺌﺔ‪ .‬ﻟﻼﺳﺘﺠﺎﺑﺔ‬
‫ﻟﻠﺘﻬﻮﻳﺔ‪ ,‬ﻗﻢ ﺑﺎﻹﻋﺪﺍﺩ ﻋﻠﻰ ‪.01‬‬
‫○‬
‫ﺍﻟﺴﻤﺎﺡ ﻟﻮﺣﺪﺓ ﺗﺤﻜﻢ ﺧﺎﺭﺟﻴﺔ ﺑﺒﺪء ﺃﻭ ﺇﻳﻘﺎﻑ‬
‫ﺍﻟﻨﻈﺎﻡ‪ ،‬ﺃﻭ ﺗﻨﻔﻴﺬ ﺇﻳﻘﺎﻑ ﻃﻮﺍﺭﺉ‪.‬‬
‫* ﻓﻲ ﺣﺎﻟﺔ ﺗﻨﻔﻴﺬ ﺇﻳﻘﺎﻑ ﻃﻮﺍﺭﺉ ﻣﻦ ﻭﺣﺪﺓ ﺗﺤﻜﻢ‬
‫ﺧﺎﺭﺟﻴﺔ‪ ،‬ﺳﻮﻑ ﻳﺘﻢ ﺗﻌﻄﻴﻞ ﺟﻤﻴﻊ ﺃﻧﻈﻤﺔ‬
‫ﺍﻟﺘﺒﺮﻳﺪ‪.‬‬
‫ﺍﺗﺒﺎﻉ ﺍﻹﻋﺪﺍﺩ ﻋﻠﻰ ﻭﺣﺪﺓ‬
‫‪01‬‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﺑﺪء‪/‬ﺇﻳﻘﺎﻑ‬
‫ﺍﻟﺘﻔﺎﺻﻴﻞ‬
‫ﻧﻤﻂ ﺍﻹﺷﺎﺭﺓ‬
‫ﻧﻤﻂ ﺍﻹﺷﺎﺭﺓ‬
‫ﺍﺳﻢ ﺍﻟﻤﺆﺷﺮ‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪) OPERATION‬ﺍﻟﺘﺸﻐﻴﻞ( )ﺍﻷﺧﻀﺮ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪) TIMER‬ﺍﻟﻤﺆﻗﺖ()ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﻣﺆﺷﺮ ‪) FILTER‬ﺍﻟﻤﺮﺷﺢ(‬
‫ﻣﺼﺒﺎﺡ )ﺃﺣﻤﺮ(‬
‫ﺍﻟﻌﻨﻮﺍﻥ‪ :‬ﻣﻨﺰﻟﺔ ﺃﺣﺎﺩﻳﺔ )‪ 0.5‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 0.5/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫• ﻣﺜﺎﻝ ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)ﻣﺜﺎﻝ( ﺍﻟﻌﻨﻮﺍﻥ‪24 :‬‬
‫‪ 1‬ﺩﻭﺭﺓ ‪ 12‬ﺛﺎﻧﻴﺔ‬
‫* ﺇﺫﺍ ﺗﻢ ﺇﻋﺪﺍﺩ ﺍﻹﻳﻘﺎﻑ ﺍﻹﺟﺒﺎﺭﻱ‪ ،‬ﺳﺘﺘﻮﻗﻒ‬
‫ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻣﻦ ﺧﻼﻝ ﺍﻹﺩﺧﺎﻝ ﺇﻟﻰ‬
‫ﺃﻃﺮﺍﻑ ﺍﻹﺩﺧﺎﻝ ﺍﻟﺨﺎﺭﺟﻲ‪ ،‬ﻭﻳﺘﻢ ﺗﻘﻴﻴﺪ‬
‫ﻭﻇﻴﻔﺔ ﺍﻟﺒﺪء ﺍﻹﻳﻘﺎﻑ ﻣﻦ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ‬
‫ﺑﻌﺪ‪.‬‬
‫○‬
‫ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ‬
‫ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﻭﻣﻴﺾ )‪ 1.0‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 1.0/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺍﻟﻌﻨﻮﺍﻥ‪ :‬ﻣﻨﺰﻟﺔ ﻋﺸﺮﻳﺔ )‪ 0.5‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 0.5/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫ﻋﻨﻮﺍﻥ ﺩﺍﺋﺮﺓ ﺍﻟﺘﺒﺮﻳﺪ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺗﺸﻐﻴﻞ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫‪ 10‬ﺛﺎﻧﻴﺔ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫‪ 8‬ﺛﺎﻧﻴﺔ‬
‫ﺗﻐﻴﻴﺮ ﺍﻟﻬﺪﻑ ﻟﺮﻓﻊ ﺗﻘﺎﺭﻳﺮ ﺍﻷﺧﻄﺎء‪ .‬ﻳﻤﻜﻦ ﺭﻓﻊ‬
‫ﺗﻘﺎﺭﻳﺮ ﺑﺎﻷﺧﻄﺎء ﺇﻟﻰ ﺟﻤﻴﻊ ﺍﻷﻣﺎﻛﻦ‪ ،‬ﺃﻭ ﻓﻲ ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﻤﺮﻛﺰﻳﺔ ﻓﻘﻂ‪.‬‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) OPERATION‬ﺍﻟﺘﺸﻐﻴﻞ(‬
‫)ﺍﻷﺧﻀﺮ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪TIMER‬‬
‫)ﺍﻟﻤﺆﻗﺖ()ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪FILTER‬‬
‫)ﺍﻟﻤﺮﺷﺢ(‬
‫)ﺃﺣﻤﺮ(‬
‫• ﻣﺜﺎﻝ ﻋﻨﻮﺍﻥ ﻧﻈﺎﻡ ﺍﻟﺘﺒﺮﻳﺪ‬
‫○‬
‫ﻋﻨﺪ ﺍﻹﻋﺪﺍﺩ ﻋﻠﻰ ‪ ,01‬ﺗﺘﻮﻗﻒ ﺍﻟﻤﺮﻭﺣﺔ ﻋﻨﺪ‬
‫ﺍﻹﻳﻘﺎﻑ ﺑﻮﺍﺳﻄﺔ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ ﻓﻲ ﻋﻤﻠﻴﺔ‬
‫ﺍﻟﺘﺒﺮﻳﺪ‪ .‬ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺗﻮﺻﻴﻞ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ )ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ‬
‫ﻭﺍﻟﻨﻮﻉ ﺛﻼﺛﻲ ﺍﻻﺳﻼﻙ( ﻭﺗﺒﺪﻳﻞ ﺍﻟﺘﺮﻣﻮﺳﺘﺎﺕ‬
‫ﺍﻟﺨﺎﺹ ﺑﻬﺎ‪.‬‬
‫)ﻣﺜﺎﻝ( ﺍﻟﻌﻨﻮﺍﻥ‪30 :‬‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1‬ﺩﻭﺭﺓ ‪ 12‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 1.0‬ﺛﺎﻧﻴﺔ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫‪ 9‬ﺛﺎﻧﻴﺔ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) OPERATION‬ﺍﻟﺘﺸﻐﻴﻞ(‬
‫ﺇﻳﻘﺎﻑ )ﺍﻷﺧﻀﺮ(‬
‫ﺗﺸﻐﻴﻞ ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) TIMER‬ﺍﻟﻤﺆﻗﺖ(‬
‫ﺇﻳﻘﺎﻑ )ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﺗﺸﻐﻴﻞ ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) FILTER‬ﺍﻟﻤﺮﺷﺢ(‬
‫ﺇﻳﻘﺎﻑ‬
‫)ﺍﻷﺣﻤﺮ(‬
‫‪Ar-14‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 14‬‬
‫• ﺗﻔﺎﺻﻴﻞ ﺍﻹﻋﺪﺍﺩ‬
‫‪ .8‬ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‬
‫ﺭﻗﻢ ﺍﻟﻮﻇﻴﻔﺔ‬
‫ﺭﻗﻢ ﺍﻹﻋﺪﺍﺩ‬
‫ﺍﻟﻌﻨﺼﺮ‬
‫‪01‬‬
‫ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫‪ 00‬ﺇﻟﻰ ‪63‬‬
‫‪02‬‬
‫ﻋﻨﻮﺍﻥ ﺍﻟﺘﺒﺮﻳﺪ‬
‫‪ 00‬ﺇﻟﻰ ‪99‬‬
‫ﻟﻼﺳﺘﺨﺪﺍﻡ ﻣﻊ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪ ،‬ﻗﻢ ﺑﺈﻋﺪﺍﺩ ﺟﻤﻴﻊ ﺍﻟﻤﻔﺎﺗﻴﺢ ﺍﻟﺪﻭﺍﺭﺓ ﻋﻠﻰ ‪ ,0‬ﻭﺭﺍﺟﻊ "‪ .1.7‬ﺇﻋﺪﺍﺩ ﺍﻟﻌﻨﻮﺍﻥ" ﻟﻠﺘﻌﺮﻑ ﻋﻠﻰ ﺍﻟﺘﻔﺎﺻﻴﻞ‪.‬‬
‫ﻳﺘﻢ ﺇﻋﺪﺍﺩ ﺟﻤﻴﻊ ﺍﻟﻌﻨﺎﻭﻳﻦ ﻋﻠﻰ ‪ 0‬ﻓﻲ ﺍﻟﻤﺼﻨﻊ‪.‬‬
‫)‪ (2‬ﺃﺧﺮﻯ‬
‫• ﺍﻟﺘﺸﻐﻴﻞ ﺗﺒﻌًﺎ ﻟﺪﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‪.‬‬
‫• ﺗﺄﻛﺪ ﻣﻦ ﻋﺪﻡ ﻭﺟﻮﺩ ﻓﺠﻮﺓ ﺑﻴﻦ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ ﻭﺍﻟﻮﺣﺪﺓ ﺍﻟﺮﺋﻴﺴﻴﺔ ﺑﻌﺪ ﺗﺮﻛﻴﺐ ﺷﺒﻜﺔ ﺍﻟﻌﻠﻴﺒﺔ‪.‬‬
‫‪ .9‬ﺍﻟﺘﺸﻐﻴﻞ ﺍﻻﺧﺘﺒﺎﺭﻱ‬
‫‪ .1.9‬ﺗﺸﻐﻴﻞ ﺍﺧﺘﺒﺎﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ )ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ(‬
‫ﻧﻤﻂ ﺍﻹﺷﺎﺭﺓ‬
‫ﻧﻤﻂ ﺍﻹﺷﺎﺭﺓ‬
‫ﺍﺳﻢ ﺍﻟﻤﺆﺷﺮ‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪) OPERATION‬ﺍﻟﺘﺸﻐﻴﻞ( )ﺍﻷﺧﻀﺮ(‬
‫ﺭﻗﻢ ﺍﻟﻮﻇﻴﻔﺔ; ﻣﻨﺰﻟﺔ ﻋﺸﺮﻳﺔ‬
‫)‪ 0.5‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 0.5/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪) TIMER‬ﺍﻟﻤﺆﻗﺖ()ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﺭﻗﻢ ﺍﻟﻮﻇﻴﻔﺔ; ﻣﻨﺰﻟﺔ ﺃﺣﺎﺩﻳﺔ )‪ 0.5‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 0.5/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪) FILTER‬ﺍﻟﻤﺮﺷﺢ( )ﺍﻷﺣﻤﺮ(‬
‫ﺭﻗﻢ ﺍﻹﻋﺪﺍﺩ‪ 0) :‬ﺇﻟﻰ ‪ 0.5) (9‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ‪ 0.5/‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ(‬
‫• ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﻓﻲ ﺣﺎﻟﺔ ﺍﺳﺘﺨﺪﺍﻡ ﻟﻮﺣﺔ ﺍﻟﻜﻤﺒﻴﻮﺗﺮ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ﻓﻲ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻻﺧﺘﺒﺎﺭﻱ‪.‬‬
‫‪ .2.9‬ﺗﺸﻐﻴﻞ ﺍﺧﺘﺒﺎﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫• ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ ﻟﻮﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻦ ﺃﺟﻞ ﺗﻨﻔﻴﺬ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻻﺧﺘﺒﺎﺭﻱ ﺑﺎﺳﺘﺨﺪﺍﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫• ﻋﻨﺪ ﺇﺟﺮﺍء ﺗﺸﻐﻴﻞ ﺍﺧﺘﺒﺎﺭ ﻟﺘﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء‪ ،‬ﺗﻮﻣﺾ ﻣﺆﺷﺮﺍﺕ ‪) OPERATION‬ﺗﺸﻐﻴﻞ( ﻭ‪) TIMER‬ﺍﻟﻤﺆﻗﺖ( ﺑﺒﻂء ﻓﻲ‬
‫ﻧﻔﺲ ﺍﻟﻮﻗﺖ‪.‬‬
‫)ﻣﺜﺎﻝ( ﺍﻟﻮﻇﻴﻔﺔ‪ ,31 :‬ﺭﻗﻢ ﺍﻹﻋﺪﺍﺩ‪2 :‬‬
‫‪ 1‬ﺩﻭﺭﺓ ‪ 12‬ﺛﺎﻧﻴﺔ‬
‫‪ 9‬ﺛﺎﻧﻴﺔ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫‪ 11‬ﺛﺎﻧﻴﺔ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫‪ 10‬ﺛﺎﻧﻴﺔ‬
‫‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ ‪ 0.5‬ﺛﺎﻧﻴﺔ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﺗﺸﻐﻴﻞ‬
‫ﺇﻳﻘﺎﻑ‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ ‪OPERATION‬‬
‫)ﺍﻟﺘﺸﻐﻴﻞ( )ﺍﻷﺧﻀﺮ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) TIMER‬ﺍﻟﻤﺆﻗﺖ(‬
‫)ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﻣﺼﺒﺎﺡ ﻣﺆﺷﺮ‬
‫‪) FILTER‬ﺍﻟﻤﺮﺷﺢ(‬
‫)ﺍﻷﺣﻤﺮ(‬
‫‪ .10‬ﻗﺎﺋﻤﺔ ﺍﻟﻔﺤﺺ‬
‫ﺍﻧﺘﺒﻪ ﻋﻠﻰ ﻭﺟﻪ ﺍﻟﺨﺼﻮﺹ ﺇﻟﻰ ﻋﻨﺎﺻﺮ ﺍﻟﻔﺤﺺ ﺍﻟﺘﺎﻟﻴﺔ ﻋﻨﺪ ﺗﺮﻛﻴﺐ ﻭﺣﺪﺓ )ﻭﺣﺪﺍﺕ( ﺍﻟﺪﺍﺧﻠﻴﺔ‪ .‬ﺑﻌﺪ ﺍﺳﺘﻜﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ‪ ،‬ﺗﺄﻛﺪ ﻣﻦ‬
‫ﻓﺤﺺ ﺍﻟﻌﻨﺎﺻﺮ ﺍﻟﺘﺎﻟﻴﺔ ﻣﺮﺓ ﺃﺧﺮﻯ‪.‬‬
‫ﻋﻨﺎﺻﺮ ﺍﻟﻔﺤﺺ‬
‫ﺇﺫﺍ ﻟﻢ ﻳﺘﻢ ﺍﻟﺘﻨﻔﻴﺬ ﺑﺸﻜﻞ ﺻﺤﻴﺢ‬
‫ﻫﻞ ﺗﻢ ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺑﺸﻜﻞ ﺻﺤﻴﺢ?‬
‫ﺍﻻﻫﺘﺰﺍﺯ‪ ،‬ﺍﻟﻀﻮﺿﺎء‪ ،‬ﺍﺣﺘﻤﺎﻝ ﺳﻘﻮﻁ ﺍﻟﻮﺣﺪﺓ‬
‫ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫ﻫﻞ ﻛﺎﻥ ﻫﻨﺎﻙ ﻓﺤﺺ ﻟﺘﺴﺮﻳﺒﺎﺕ ﺍﻟﻐﺎﺯ )ﻣﻮﺍﺳﻴﺮ ﺳﺎﺋﻞ‬
‫ﺍﻟﺘﺒﺮﻳﺪ(?‬
‫ﻋﺪﻡ ﻭﺟﻮﺩ ﺗﺒﺮﻳﺪ‪ ،‬ﺗﺪﻓﺌﺔ‬
‫ﻫﻞ ﺗﻢ ﺍﺳﺘﻜﻤﺎﻝ ﺃﻋﻤﺎﻝ ﺍﻟﻌﺰﻝ ﺍﻟﺤﺮﺍﺭﻱ؟‬
‫ﺗﺴﺮﻳﺐ ﺍﻟﻤﻴﺎﻩ‬
‫ﻫﻞ ﻳﺘﻢ ﺗﺼﺮﻳﻒ ﺍﻟﻤﻴﺎﻩ ﺑﺴﻬﻮﻟﺔ ﻣﻦ ﺍﻟﻮﺣﺪﺍﺕ ﺍﻟﺪﺍﺧﻠﻴﺔ؟‬
‫ﺗﺴﺮﻳﺐ ﺍﻟﻤﻴﺎﻩ‬
‫ﻫﻞ ﺟﻬﺪ ﻣﺼﺪﺭ ﺇﻣﺪﺍﺩ ﺍﻟﻄﺎﻗﺔ ﻫﻮ ﻧﻔﺴﻪ ﺍﻟﻤﺒﻴﻦ ﻋﻠﻰ‬
‫ﻣﻠﺼﻖ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ؟‬
‫ﻋﺪﻡ ﺍﻟﺘﺸﻐﻴﻞ‪ ،‬ﺃﻭ ﻋﺪﻡ ﺍﻟﺘﺪﻓﺌﺔ ﺃﻭ ﺍﻟﺘﻠﻒ ﺑﺴﺒﺐ‬
‫ﺍﻻﺣﺘﺮﺍﻕ‬
‫ﻫﻞ ﺗﻢ ﺗﻮﺻﻴﻞ ﺍﻷﺳﻼﻙ ﻭﺍﻟﻤﻮﺍﺳﻴﺮ ﺟﻤﻴﻌًﺎ ﺑﺸﻜﻞ ﺻﺤﻴﺢ؟‬
‫ﻋﺪﻡ ﺍﻟﺘﺸﻐﻴﻞ‪ ،‬ﺃﻭ ﻋﺪﻡ ﺍﻟﺘﺪﻓﺌﺔ ﺃﻭ ﺍﻟﺘﻠﻒ ﺑﺴﺒﺐ‬
‫ﺍﻻﺣﺘﺮﺍﻕ‬
‫ﻫﻞ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻣﺘﺼﻠﺔ ﺑﺎﻷﺭﺽ )ﻣﺆﺭﺿﺔ(?‬
‫ﺩﺍﺋﺮﺓ ﻗﺼﺮ‬
‫ﻫﻞ ﻛﺒﻞ ﺍﻟﺘﻮﺻﻴﻞ ﺑﺎﻟﺴﻤﺎﻛﺔ ﺍﻟﻤﺤﺪﺩﺓ?‬
‫ﻋﺪﻡ ﺍﻟﺘﺸﻐﻴﻞ‪ ،‬ﺃﻭ ﻋﺪﻡ ﺍﻟﺘﺪﻓﺌﺔ ﺃﻭ ﺍﻟﺘﻠﻒ ﺑﺴﺒﺐ‬
‫ﺍﻻﺣﺘﺮﺍﻕ‬
‫ﻫﻞ ﺍﻟﻤﺪﺍﺧﻞ ﻭﺍﻟﻤﺨﺎﺭﺝ ﺧﺎﻟﻴﺔ ﻣﻦ ﺍﻟﻌﻮﺍﺋﻖ؟‬
‫ﻋﺪﻡ ﻭﺟﻮﺩ ﺗﺒﺮﻳﺪ‪ ،‬ﺗﺪﻓﺌﺔ‬
‫ﻫﻞ ﻳﺘﻢ ﺑﺪء ﻭﺇﻳﻘﺎﻑ ﺗﺸﻐﻴﻞ ﺗﻜﻴﻴﻒ ﺍﻟﻬﻮﺍء ﺑﻮﺍﺳﻄﺔ ﻭﺣﺪﺓ‬
‫ﺗﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺃﻭ ﺟﻬﺎﺯ ﺧﺎﺭﺟﻲ?‬
‫ﻻ ﻳﻮﺟﺪ ﺗﺸﻐﻴﻞ‬
‫ﺧﺎﻧﺔ ﺍﻻﺧﺘﻴﺎﺭ‬
‫ﺑﻌﺪ ﺍﺳﺘﻜﻤﺎﻝ ﺍﻟﺘﺮﻛﻴﺐ‪ ،‬ﻫﻞ ﺗﻢ ﺗﻮﺿﻴﺢ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﺼﺤﻴﺢ‬
‫ﻭﺍﻟﻤﻌﺎﻟﺠﺔ ﻟﻠﻌﻤﻴﻞ؟‬
‫‪Ar-15‬‬
‫‪3/14/2016 4:32:17 PM‬‬
‫‪9371022451_IM_AR.indd 15‬‬
‫ﻋﺮﺽ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ‬
‫‪ .11‬ﺭﻣﻮﺯ ﺍﻟﺨﻄﺄ‬
‫ﺇﺫﺍ ﻛﻨﺖ ﺗﺴﺘﺨﺪﻡ ﻭﺣﺪﺓ ﺗﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻣﻦ ﻧﻮﻉ ﺳﻠﻜﻲ‪ ،‬ﺳﻮﻑ ﺗﻈﻬﺮ ﺭﻣﻮﺯ ﺍﻟﺨﻄﺄ ﻋﻠﻰ ﺷﺎﺷﺔ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪ .‬ﺇﺫﺍ ﻛﻨﺖ‬
‫ﺗﺴﺘﺨﺪﻡ ﻭﺣﺪﺓ ﺗﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﻻﺳﻠﻜﻴﺔ‪ ،‬ﻓﺈﻥ ﺍﻟﻤﺼﺒﺎﺡ ﻋﻠﻰ ﻭﺣﺪﺓ ﺍﻟﻜﺎﺷﻒ ﺍﻟﻀﻮﺋﻲ ﺳﻮﻑ ﺗﺼﺪﺭ ﺭﻣﻮﺯ ﺍﻟﺨﻄﺄ ﻋﻦ ﻃﺮﻳﻖ ﺃﻧﻤﺎﻁ‬
‫ﺍﻟﻮﻣﻴﺾ‪ .‬ﺭﺍﺟﻊ ﺃﻧﻤﺎﻁ ﻭﻣﻴﺾ ﺍﻟﻤﺼﺒﺎﺡ ﻭﺭﻣﻮﺯ ﺍﻟﺨﻄﺄ ﻓﻲ ﺍﻟﺠﺪﻭﻝ ﺍﻟﺘﺎﻟﻲ‪.‬‬
‫‪) UTY-RNKYT / UTY-RNKG / UTY-RNKY‬ﺍﻟﻨﻮﻉ ﺛﻼﺛﻲ ﺍﻷﺳﻼﻙ(‬
‫ﺭﻣﺰ ﺍﻟﺨﻄﺄ‬
‫ﻣﺆﺷﺮﺍﺕ ﺍﻟﺨﻄﺄ‬
‫ﻣﺼﺒﺎﺡ‬
‫‪OPERATION‬‬
‫)ﺗﺸﻐﻴﻞ( )ﺃﺧﻀﺮ(‬
‫ﻣﺼﺒﺎﺡ ‪TIMER‬‬
‫)ﺍﻟﻤﺆﻗﺖ(‬
‫)ﺍﻟﺒﺮﺗﻘﺎﻟﻲ(‬
‫ﻣﺼﺒﺎﺡ‬
‫‪FILTER‬‬
‫)ﺍﻟﻤﺮﺷﺢ(‬
‫)ﺍﻷﺣﻤﺮ(‬
‫ﺭﻣﺰ ﺍﻟﺨﻄﺄ ﺑﻮﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫ﺍﻟﺴﻠﻜﻴﺔ‬
‫ﻣﺤﺘﻮﻳﺎﺕ ﺍﻟﺨﻄﺄ‬
‫‪) UTY-RNRGZ1 / UTY-RNRYZ1 / UTY-RNRG / UTY-RNRY‬ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ(‬
‫)‪(1‬‬
‫)‪(2‬‬
‫ﺧﻄﺄ ﺍﺗﺼﺎﻝ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‬
‫)‪(1‬‬
‫)‪(4‬‬
‫ﺧﻄﺄ ﺍﺗﺼﺎﻝ ﺍﻟﺸﺒﻜﺔ‬
‫)‪(1‬‬
‫)‪(6‬‬
‫ﺧﻄﺄ ﺍﺗﺼﺎﻝ ﺍﻟﻮﺣﺪﺓ ﺍﻟﻄﺮﻓﻴﺔ‬
‫)‪(2‬‬
‫)‪(6‬‬
‫ﺧﻄﺄ ﺇﻋﺪﺍﺩ ﻋﻨﻮﺍﻥ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)‪(2‬‬
‫)‪(9‬‬
‫ﺧﻄﺄ ﻓﻲ ﺭﻗﻢ ﻭﺣﺪﺓ ﺍﻻﺗﺼﺎﻝ ﻓﻲ ﻧﻈﺎﻡ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ‬
‫ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ‬
‫)‪(3‬‬
‫)‪(1‬‬
‫ﺇﻣﺪﺍﺩ ﻃﺎﻗﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻏﻴﺮ ﻋﺎﺩﻱ‬
‫)‪(3‬‬
‫)‪(2‬‬
‫ﺧﻄﺄ ﻟﻮﺣﺔ ﻛﻤﺒﻴﻮﺗﺮ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺍﻟﺮﺋﻴﺴﻴﺔ‬
‫)‪(3‬‬
‫)‪(10‬‬
‫ﺧﻄﺄ ﻓﻲ ﺩﺍﺋﺮﺓ ﺍﺗﺼﺎﻝ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ )ﻭﺣﺪﺓ‬
‫ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ ﺍﻟﺴﻠﻜﻴﺔ(‬
‫)‪(4‬‬
‫)‪(1‬‬
‫ﺧﻄﺄ ﻓﻲ ﺗﺮﻣﻮﺳﺘﺎﺕ ﺣﺮﺍﺭﺓ ﺍﻟﻐﺮﻓﺔ ﺑﺎﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)‪(4‬‬
‫)‪(2‬‬
‫ﺧﻄﺄ ﺗﺮﻣﻮﺳﺘﺎﺕ ﺣﺮﺍﺭﺓ ﺍﻟﻤﺒﺎﺩﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺑﺎﻟﻮﺣﺪﺓ‬
‫ﺍﻟﺪﺍﺧﻠﻴﺔ‬
‫)‪(5‬‬
‫)‪(1‬‬
‫ﺧﻄﺄ ﻓﻲ ﻣﻮﺗﻮﺭ ﻣﺮﻭﺣﺔ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ‪1‬‬
‫)‪(5‬‬
‫)‪(2‬‬
‫ﺧﻄﺄ ﻣﻠﻒ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ )ﺻﻤﺎﻡ ﺍﻟﺘﻮﺳﻌﺔ(‬
‫)‪(5‬‬
‫)‪(3‬‬
‫ﺗﺼﺮﻳﻒ ﻣﻴﺎﻩ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻏﻴﺮ ﻋﺎﺩﻱ‬
‫)‪(9‬‬
‫)‪(15‬‬
‫ﺧﻄﺄ ﻣﺘﻨﻮﻉ ﻓﻲ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ‬
‫)‪(13‬‬
‫)‪(1‬‬
‫ﺧﻄﺄ ﻭﺣﺪﺓ ‪RB‬‬
‫ﺍﻟﻤﺲ ]‪) [Next Page‬ﺍﻟﺼﻔﺤﺔ ﺍﻟﺘﺎﻟﻴﺔ( )ﺃﻭ ]‪[previous page‬‬
‫)ﺍﻟﺼﻔﺤﺔ ﺍﻟﺴﺎﺑﻘﺔ( ﻟﻠﺘﺒﺪﻳﻞ ﺇﻟﻰ ﻣﻌﻠﻮﻣﺎﺕ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﺍﻷﺧﺮﻯ‪.‬‬
‫ﺃﻳﻘﻮﻧﺔ ﺍﻟﺨﻄﺄ‬
‫ﺍﻟﻤﺲ ]‪) [Error Information‬ﻣﻌﻠﻮﻣﺎﺕ ﺍﻟﺨﻄﺄ(‪.‬‬
‫ﺍﻟﻤﺲ ]‪) [Status‬ﺍﻟﺤﺎﻟﺔ(‪.‬‬
‫ﺗﺘﻮﺍﻓﺮ ﺍﻷﻋﺪﺍﺩ ﻣﻦ ﺭﻗﻤﻴﻦ ﻣﻊ ﺭﻣﺰ‬
‫ﺍﻟﺨﻄﺄ ﻓﻲ ﺍﻟﺠﺪﻭﻝ ﺍﻟﺴﺎﺑﻖ‪.‬‬
‫ﻟﻤﺰﻳﺪ ﻣﻦ ﺍﻟﻤﻌﻠﻮﻣﺎﺕ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫‪) UTY-RLRG / UTY-RLRY‬ﺍﻟﻨﻮﻉ ﺛﻨﺎﺋﻲ ﺍﻷﺳﻼﻙ(‬
‫ﺃﻳﻘﻮﻧﺔ ﺍﻟﺨﻄﺄ‬
‫ﺭﻣﺰ ﺍﻟﺨﻄﺄ‬
‫ﻟﻤﺰﻳﺪ ﻣﻦ ﺍﻟﻤﻌﻠﻮﻣﺎﺕ‪ ،‬ﺭﺍﺟﻊ ﺩﻟﻴﻞ ﺗﺮﻛﻴﺐ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻋﻦ ﺑﻌﺪ‪.‬‬
‫ﻭﺿﻊ ﺍﻟﻌﺮﺽ‬
‫‪ 0.5 :‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ ‪ 0.5 /‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ‬
‫‪ 0.1 :‬ﺛﺎﻧﻴﺔ ﺗﺸﻐﻴﻞ ‪ 0.1 /‬ﺛﺎﻧﻴﺔ ﺇﻳﻘﺎﻑ‬
‫) ( ‪ :‬ﻋﺪﺩ ﺍﻟﻮﻣﻴﺾ‬
‫‪Ar-16‬‬
‫‪3/14/2016 4:32:15 PM‬‬
‫‪9371022451_IM_AR.indd 16‬‬