Samsung AR9500T Wall-mount AC con Fast Cooling Installation guide

Samsung AR9500T Wall-mount AC con Fast Cooling Installation guide
Air conditioner
Installation manual
AR**TVCA*** / AR**TVFC*** / AR**TVFY***/ AR**TVFZ***/
AR**TVEA*** / AR**TSEA*** / AR**TSFZ***
•• Thank you for purchasing this Samsung air conditioner.
•• Before operating this unit, please read this installation manual carefully and retain it for
future reference.

Contents
Safety Information
3
Safety Information
3
Installation
4
Preparation
4
Step 1.1 Viewing the typical installation
Step 1.2 Choosing the installation location
Step 1.3 Unpacking
Step 1.4 Preparing materials and tools
4
5
8
9
Indoor Unit Installation
11
Step 2.1 Attaching the mounting bracket to the wall
Step 2.2 Drilling the wall penetration
Step 2.3 Connecting the refrigerant pipes
Step 2.4 Connecting the power and communication cables
Step 2.5 Optional: Extending the power cable
Step 2.6 Connecting the drain hose
Step 2.7 Taping the pipes, cables, and drain hose
11
11
12
13
14
16
17
Outdoor Unit Installation
18
Step 3.1 Mounting the outdoor unit
Step 3.2 Connecting the cables and the pipes
18
19
Installation Inspection and Testing
21
Step 4.1 Performing a drain leak test
Step 4.2 Performing the gas leak tests
Step 4.3 Evacuating the system
Step 4.4 Adding refrigerant (if needed)
Step 4.5 Preparing the system for commissioning
Step 4.6 Commissioning the unit
Step 4.7 Performing final checks and trial operation
21
21
22
23
23
23
24
2 English
Safety Information
WARNING: Read This Manual
•• Read and follow all safety information and instructions
before installation, use, or maintenance of this
appliance. Incorrect installation, use, or maintenance
of this appliance can result in death, serious injury, or
property damage. Keep these instructions with this
appliance. This manual is subject to change. For the
latest version,
visit www.samsung.com.
WARNING
The installation and testing of this appliance must be
performed by a qualified technician.
•• The instructions in this manual are not intended as a
substitute for proper training or adequate experience in
the safe installation of the appliance.
Always install the air conditioner in compliance with current
local, state, and federal safety standards.
To make you aware of safety messages and highlighted
information, we use the following notices and notes
throughout this manual:
WARNING
Hazards or unsafe practices that may result in severe personal
injury or death.
CAUTION
Hazards or unsafe practices that may result in minor personal
injury or property damage.
IMPORTANT
Information of special interest
NOTE
Supplementary information that may be useful
The user and installer guides
should be read carefully.
The user and installer guides
should be read carefully.
•• The air conditioner should be used only for the
applications for which it has been designed: the indoor
unit is not suitable to be installed in areas used for
laundry.
Installation of the product
•• Our units must be installed in compliance with the
spaces indicated in the installation manual to ensure
either accessibility from both sides or ability to perform
routine maintenance and repairs. The units’ components
must be accessible and that can be disassembled in
conditions of complete safety either for people or things.
For this reason, where it is not observed as indicated
into the Installation Manual, the cost necessary to reach
and repair the unit (in safety, as required by current
regulations in force) with slings, trucks, scaffolding or
any other means of elevation won’t be considered inwarranty and will be charged to end user.
Power supply line, fuse, or circuit breaker
•• Be sure not to perform power cable modification,
extension wiring, and multiple wire connection.
‐‐
It may cause electric shock or fire due to poor
connection, poor insulation, or current limit
override.
‐‐
When extension wiring is required due to power
line damage, refer to "Step 2-5 Optional: Extending
the power cable" in the installation manual.
English 3
Safety Information
General information
Notices and notes
Preparation
Step 1.1 Viewing the typical installation
A typical installation will be similar to the one shown below.
Evaporator/fancoil (indoor)
Maximum pipe height
Refrigerant lines,
electric, and drain
Make at least one round to
reduce noise and vibration.
Maximum pipe length
Compressor/
condenser
(outdoor)
The actual units may look different from
the images depicted here.
(Unit : m)
Model
Pipe length
Installation
Minimum
Maximum
Standard for factory charge
Maximum
3
15
5
8
3
30
5
15
3
15
7.5 (For Panama : 5)
8
3
30
7.5 (For Panama : 5)
15
**09*******
**12*******
**18*******
**24*******
**09********AP
**12********AP
**18********AP
**24********AP
Outdoor Unit
Outer wall
Indoor Unit
Cut insulation to have
rainwater drained
4 English
Pipe height
Make a U-trap (A) on the pipe (which is connected to
the indoor unit) at outer wall and cut the bottom part of
the insulation (about 10 mm) to prevent rainwater from
CAUTION getting inside through the insulation.
CAUTION
Step 1.2 Choosing the installation location
WARNING
•• Verify that a dedicated circuit breaker and a disconnect
switch of the appropriate sizes for the air conditioner
are preinstalled and available for use.
•• Verify that the voltage and frequency of the power
supply comply with the rated voltage as defined on the
unit name plate.
•• Verify that a suitable grounding connection is available.
•• Do not install this appliance in an environment
containing hazardous substances or close to equipment
that releases open flames.
•• Do not install this appliance near a heater or flammable
material.
CAUTION
•• The manufacturer shall not be responsible for damage
occurring as a result of the wrong voltage being
applied to this air conditioner.
•• The indoor and outdoor units must be installed in
compliance with minimum clearances to ensure that
both units are accessible from both sides and can be
maintained or repaired. Insufficient clearance may
reduce product performance, generate excessive noise,
and reduce the life of some unit components.
Indoor unit location requirements
WARNING
•• Do not install the unit in a humid, oily, or dusty location
or in a location exposed to direct sunlight, water, or rain.
•• Make sure that the wall can support the unit weight.
Examine the area that the customer wants to be air
conditioned. Consider the following:
•• What wall location will meet minimum clearances and
provide optimal product performance?
•• Will the wall provide adequate support for the unit
weight (wall with stud construction or concrete)? If
applicable, where are the studs?
•• Where will you place the wall penetration for
routing the piping bundle (consisting of power and
communication cables, refrigerant pipes, and the drain
hose) through the wall to the outdoor unit? Will the
hole intersect any plumbing or wires in the wall?
•• Is the location as close as possible to where the outdoor
unit will be installed, to minimize the length of piping
and cables?
•• Will the condensate drain inside the room, through the
wall penetration to the outdoor unit, or be connected to
a condensate pump?
NOTE
IMPORTANT
Minimum clearances for the indoor unit
To determine where to locate the indoor and outdoor units,
you must survey the entire site and consider many variables.
The goal is to select locations that comply with all safety
precautions while also minimizing the total effort involved.
Ceiling
100 mm
125 mm
Wall
125 mm
English 5
Installation
•• Any changes or modifications to the installation
described in this manual that are not expressly
approved by the manufacturer could void the
manufacturer’s warranty.
•• This manual covers a typical gravity‑drain installation
where the drain hose is routed to the outdoor unit
through a hole in the wall.
Preparation
Outdoor unit location requirements
Installation Guide at the seashore
Examine the area where the outdoor unit could be located.
Consider the following:
Make sure to follow below guides when installing at the
seashore.
•• What location will meet minimum clearances and
provide optimal product performance?
1
•• Is there an existing level and hard foundation, such as
a concrete pad, that will support the unit weight and
produce minimal vibration? Installation on uneven
ground may result in abnormal vibrations, noise, or
problems with the unit.
Do not install the product in a place where it is directly
exposed to sea water and sea breeze.
‐‐
Make sure to install the product behind a structure
(such as building) that can block see breeze.
‐‐
Even when it is inevitable to install the product in
seashore, make sure that product is not directly
exposed to sea breeze by installing a protection wall.
•• Does the unit need to be mounted on the wall?
2
•• Where are the dedicated circuit breaker and disconnect
switch located? How will you connect them to the unit?
Consider that the salinity particles clinging to the external
panels should be sufficiently washed out.
3
Because the residual water at the bottom of the outdoor
unit significantly promotes corrosion, make sure that the
slope does not disturb drainage.
•• How will you route the piping bundle from the indoor
unit? Is the location as close as possible to where the
indoor unit will be installed, to minimize the length of
piping and cables?
‐‐
Keep the floor level so that rain does not accumulate.
‐‐
Be careful not to block the drain hole due to foreign
substance.
•• Will the unit be sheltered from the wind? In a
high‑wind area, you may need to build a protective
fence around the unit.
4
•• Where will the condensate drain?
When product is installed in seashore, periodically clean it
with water to remove attached salinity.
5
Make sure to install the product in a place that provides
smooth water drainage. Especially, ensure that the base
part has good drainage.
6
If the product is damaged during the installation or
maintenance, make sure to repair it.
7
Check the condition of the product periodically.
WARNING
•• The drain location must allow condensate to drain
properly and prevent ice from forming on the unit in
winter. If a block of ice falls from the unit, it may result
in death, serious injury, or property damage. Improper
or inadequate draining may result in water overflowing
and property damage.
Installation
CAUTION
•• Do not connect the drain hose to existing waste pipes
as odors may arise.
Installation on an exterior wall
If the outdoor unit must be installed on an exterior wall, you
will need an L‑bracket to support the unit. This bracket is not
included with the unit.
WARNING
•• The wall must be capable of supporting the weight
of both the L‑bracket and the outdoor unit. If the unit
falls, it may result in crushing, electric shock, fire, or
explosion that could cause death, severe personal
injury, or property damage.
6 English
8
‐‐
Check the installation site every 3 months and
perform anti-corrosion treatment such as R-Pro
supplied by SAMSUNG (Code : MOK-220SA) or
commercial water repellent grease and wax, etc.,
based on the product condition.
‐‐
When the product is to be shut down for a long
period of time, such as off-peak hours, take
appropriate measures like covering the product.
If the product installed within 500m of seashore, special
anti-corrosion treatment is required.
※ Please contact your local SAMSUNG representative for
further details.
Outdoor
unit
Examples for installing one outdoor unit:
Outdoor
unit
Unit: mm
300
Sea breeze
2000
1500
Outdoor
unit
Sea breeze
300
1500
Sea
Sea
300
1500
Sea breeze
600
300
Outdoor
unit
Protection wall
500
150
Outdoor unit
Sea
•• Protection wall should be constructed with a solid
material that can block the sea breeze and the height
and width of the wall should be 1.5 times larger than
the size of the outdoor unit. (You must secure more
than 700 mm of space between the protection wall and
the outdoor unit for air circulation.)
Minimum clearances for the outdoor unit
Installation
Legends:
Wall
300
Minimum clearance in mm
600
Air flow direction
Top view
Side view
English 7
Preparation
Examples for installing multiple outdoor units:
Unit: mm
1500
600
3000
3000
200
Step 1.3 Unpacking
Upon receipt, inspect the product to verify that it has not been
damaged during transport. If the product appears damaged,
do not install it and immediately report the damage to your
local Samsung distributor.
Packing material must be disposed of in accordance with local
regulations.
300
Unpacking the indoor unit
1500
600
1500
600
At the selected indoor unit location:
300
300
600
Open the indoor unit package.
2
Remove the left and right cushions.
3
Carefully remove the unit from the package.
4
Place the unit on a flat surface where it will be protected
from possible damage.
Unpacking the outdoor unit
300
600
500
Installation
8 English
600
500
300
1
At the selected outdoor unit location:
1
Remove the package.
2
Remove the top cushion.
3
Carefully remove the unit from the bottom cushion.
4
Place the unit on a flat surface where it will be protected
from possible damage.
Step 1.4 Preparing materials and tools
Materials in the indoor unit package
Make sure that the indoor unit package contains the following
materials:
Optional accessories
Insulated assembly pipe,
Ø 6.35 mm (1)
Insulated assembly pipe,
Ø 9.52 mm (1)
**09*******
**12*******
Mounting bracket (1)
**09*******
**12*******
Mounting bracket (1)
**18*******
**24*******
Insulated assembly pipe,
Ø 12.70 mm (1)
**18*******
Insulated assembly pipe,
Ø 15.88 mm (1)
**24*******
Remote control (1)
Remote control battery (2)
Pipe clamp B (3)
Pipe clamp A (3)
General information (1)
Quick guide (1)
Drain Hose, 2 m long (1)
Foam Insulation (1)
Vinyl tape (2)
PE T3 foam tube
insulation (1)
Putty 100 g (1)
M4 x 25 tapped screw (6)
Cement nail (6)
3-wire Power Cable (1)
3-wire Assembly Cable (1)
2-wire Assembly Cable (1)
Installation manual (1)
Materials in the outdoor unit package
Rubber foot (4)
Drain plug (1)
*****S*****
English 9
Installation
Make sure that the outdoor unit package contains the
following materials:
Preparation
NOTE
•• A flare nut is attached to the end of each refrigerant
pipe coming from the evaporator. Use these flare nuts
when connecting the pipes.
Materials supplied by the installer
Make sure you have all other materials required for the
selected installation method and location.
IMPORTANT
Tools
Make sure you have the required tools available.
General tools
•• Vacuum pump
(Backward flowing prevention)
•• Manifold gauge
•• Stud finder
•• Torque wrench
•• Pipe cutter
•• No mounting hardware, tubing, cables, and other
materials listed below are included with the appliance.
•• Reamer
The required materials will vary, but may include the following:
•• Spirit level
•• 1.8 m electrical whip for connecting the power from the
installed disconnect switch to the outdoor unit
•• Screwdriver
•• Spanner
•• UV-resistant vinyl line set tape for the exposed line set
•• Drill
•• Lines-set cover and fittings, if used
•• L-wrench
•• Miscellaneous pipe hangers
•• Measuring tape
•• Miscellaneous screws and anchors for hanging pipe
hangers, the line-set cover, the indoor unit mounting
bracket, and so on.
Tools for test operation
•• Electrical ring connectors for connecting all power and
communication wiring
•• Resistance meter
•• Electrical tape
•• Refrigerant R-410A if additional refrigerant is required
due to line-set length
Installation
•• Closed cell foam tape insulation (roll)
•• Outdoor unit risers or L-brackets for wall installation
•• Silicone caulking for sealing the wall penetration
•• Rags
10 English
•• Pipe bender
•• Thermometer
•• Electroscope
Indoor Unit Installation
Step 2.1 Attaching the mounting bracket
to the wall
1
Hold the mounting bracket against the wall at the
selected installation position (Step 1.2 on page 5),
making sure that the screw holes align with the center of
the studs in the wall. If the screw locations do not align
with the studs, use wall anchors.
Step 2.2 Drilling the wall penetration
1
Determine the position of the hole through which the
piping bundle (consisting of power and communication
cables, refrigerant pipes, and the drain hose) will pass.
Consider the following:
‐‐
The hole inner diameter must be 65 mm.
‐‐
The recommended hole location is behind the unit
so that the hole and the piping bundle will not
be visible in the room. The minimum distances
between the hole and the mounting bracket are:
CAUTION
•• The recommended best practice is to attach the
mounting bracket directly to the studs in the wall. If
you did not find a suitable location with studs (in Step
1.2 on page 5), or if the wall is concrete, you must
use wall anchors of a suitable type and weight capacity,
and install them according to the manufacturer’s
instructions. Failure to do so may cause the material
surrounding the joints to crumble over time and the
screws to be loosened and stripped. This may result
in the unit falling from the wall, which could cause
physical injury or equipment damage.
2
Using a level, make sure that the mounting bracket is
level, then mark the location of the screw holes on the
wall.
3
If using wall anchors, install them at the screw hole
positions, following the manufacturer’s instructions.
4
Using six field-supplied mounting screws and anchors (if
applicable), attach the bracket to the wall.
Center of indoor unit (B)
Center of indoor unit (A)
a
b
Model
**09*******
**12*******
**18*******
**24*******
a
b
c
A
165
305
416
A
150
305
650.5
If the hole cannot be positioned behind the unit,
find a position as close to the unit as possible. The
piping bundle that exits the unit and extends to the
hole will need to be attached to the wall and will be
visible inside the room.
‐‐
In relation to the bracket shown above, the unit
is shipped with the drain hose connection on the
right, the drain hose exits the unit on the left, and
the refrigerant pipes are bent to exit on the left.
Thus, positioning the hole to the left requires the
least effort. If you position the hole to the right
or below the unit, you will need to move the drain
hose connection to the left and bend the pipes so
that the hose and pipes exit to the right or bottom.
See the figure in step 3 on page 12.
English 11
Installation
‐‐
Level
Screw Location x 4ea
c
Possible positions for hole behind unit
Indoor Unit Installation
2
Use a standard 65 mm hole saw to drill one hole at the
selected location, at a 15° downward angle so that the
drain hose will drain properly.
•• The smaller‑diameter pipe is for the high‑pressure,
two‑phase refrigerant.
•• The larger‑diameter pipe is for the low‑pressure
refrigerant vapor.
Wall
Drain hose
Indoor unit
3
Two short refrigerant pipes are already attached to the air
conditioner:
Based on the hole location, determine where the piping
bundle (drain hose, refrigerant pipes, and cables) will exit
the unit.
Left
Right
<Front view>
<Side view>
bottom
Rear right or left
NOTE
Installation
•• The left, right, or bottom exit will only be used if the
hole is not positioned behind the unit.
Step 2.3 Connecting the refrigerant pipes
Connect indoor and outdoor units with field-supplied copper
pipes by means of flare connections. Use insulated seamless
refrigeration grade pipe only, (Cu DHP type according to
ISO1337), degreased and deoxidized, suitable for operating
pressures of at least 4200 kPa and for burst pressure of at
least 20700 kPa. Under no circumstances must sanitary type
copper pipe be used.
IMPORTANT
•• When installing the unit, always connect the
refrigerant pipes first, followed by the electrical cables.
For disassembly, always disassemble the electric cables
before the refrigerant pipes.
12 English
Drain hose
Refrigerant Connection hose
pipes
(assembly pipe)
In Step 2.2, step 3 you determined the exit position for the
piping bundle. The unit has three knockouts available for the
left, right, and bottom exits. When the bundle exits directly
from the rear, none of the knockouts are used.
1
If the pipes will exit directly from the rear, skip to step 3.
Otherwise, cut out the appropriate knockout piece (left,
right, or bottom).
2
Use a razor knife to clean the cut edges (flashing).
3
The left exit is the only position that does not require
bending the pipes. For other positions, bend the pipes so
that they will exit in the selected exit position.
‐‐
The bending radius should be greater than 100 mm.
‐‐
Bend the smaller pipe gradually to prevent kinking.
The larger pipe has a preinstalled spring bender to
prevent kinking.
‐‐
Make sure that the pipes do not protrude from the
back of the unit in a way that will make it difficult to
attach the unit to the mounting bracket.
‐‐
For right and bottom exits, pull the pipes out through
the selected knockout opening. For left exits, the
piping connections will be made in the service space
behind the indoor unit (under the cover panel).
NOTE
•• If you are using the right rear exit, the pipes should
be long enough to extend through the wall without
needing to connect the line set first. It may be easier
to connect the line set outside of the building, after
you have bundled the pipes and cables and passed the
bundle through the wall. In this case, do not connect
the line set now. Instead, complete Step 2.4 through
Step 2.7, then go outside and connect the line set as
described below.
4
Slowly remove the protective caps on the refrigerant pipe
connections to relieve the nitrogen holding charge.
5
Connect the line set to each pipe.
Step 2.4 Connecting the power and
communication cables
Flare nut
Indoor outlet pipe
6
Hand-tighten the flare nuts to make sure that they do not
become stripped.
Liquid service port
<High pressure>
7
Connecting pipe
Gas service port
<Low pressure>
Torque the flare connections to the following values:
Outer diameter (mm)
Torque (N·m)
ø 6.35
14–18
ø 9.52
34–42
ø 12.70
49–61
ø 15.88
68–82
WARNING
•• Do not modify the power cable in any way. Doing so may
cause electric shock or fire due to poor connection, poor
insulation, or current limit override. Make sure to comply
with the technical standards of electrical installations
and the wiring regulations in the local area.
•• This appliance must be properly grounded. Do not
ground the appliance to a gas pipe, plastic water pipe,
or telephone line. Failure to comply may result in
electric shock, fire, and explosion.
1
Connect each wire to its corresponding terminal number.
Model
Power cable
(Outdoor unit)
Outdoor-to-indoor
power cable
Communication
cable
Type GL
**09*******
**12*******
**18*******
**24*******
3G X 2.5 mm²,
H07RN-F
3G X 1.0 mm²,
H07RN-F
2 X 0.75 mm²,
H05RN-F
16A
3G X 2.5 mm²,
H07RN-F
3G X 1.0 mm²,
H07RN-F
2 X 0.75 mm²,
H05RN-F
20A
CAUTION
8
Do not box in or cover the pipe connections. Make sure
that the connections are accessible for testing later in the
installation process and for future servicing.
9
Tape over the end of the pipes so that debris will not enter
the piping when it is passed through the wall. The pipes
will be insulated later in the installation process.
Installation
•• Tighten the flare nuts only to the specified torque. If
a flare nut is overtightened, the flare face may crack,
causing refrigerant leakage.
Control box
Before
connecting
After
connecting
Correct
Upside
down
Damaged
Non-circular
Correct
(Front
view)
Correct
(Side view)
Upside
down
Non-fitted
<Circular terminal>
English 13
Indoor Unit Installation
CAUTION
•• Connect the wires firmly so that wires cannot be pulled
out. Loose wires can cause the connection to overheat.
Step 2.5 Optional: Extending the power
cable
1
Prepare the following tools.
Each circular terminal must match the size of its
corresponding screw in the terminal block.
CAUTION
•• For the terminal block wiring, use a wire with a
ring terminal socket only. Regular wires without a
ring terminal socket may become a hazard as the
connections may loosen during operation.
2
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5 (HxOD)
Insulation tape
Width 19 mm
Contraction tube
(mm)
70xØ8.0 (LxOD)
Tighten the terminal block screw.
2
1(L) 2(N)
F1 F2
Shape
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
•• Peel off 20 mm of cable shields from the preinstalled tube.
CAUTION
3
In Step 2.2, step 3 you determined the exit position for the
piping bundle. If using the left, right, or bottom exits, pass
the cables through the selected knockout.
NOTE
Installation
•• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC: 60245 IEC66/
CENELEC: H07RN-F, IEC: 60245 IEC57 CENELEC:
H05RN-F, IEC: 60227 IEC53: H05VV-F)
•• For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
•• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
•• If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance (reduction of passing current)
and consequently may result in a fire.
(Unit: mm)
Power cable
•• Power & Communication cable shall not exceed 30 m.
20
20
180
20
14 English
60
120
60
20
180
120
20
20
Pre-installed
tube for the
power cable
3
Insert both sides of core wire of the power cable into the
connection sleeve.
6
Apply heat to the contraction tube to contract it.
Method 1
•• Method 1: Push the core wire into the sleeve from
both sides.
Contraction tube
•• Method 2: Twist the wire cores together and push it
into the sleeve.
Method 1
Connection sleeve
4
Method 2
7
Connection sleeve
Method 2
Contraction tube
After tube contraction work is completed, wrap it with the
insulation tape to finish.
Three or more layers of insulation are required.
Method 1
Using a crimping tool, compress the two points and flip
it over and compress another two points in the same
location.
Insulation tape
Method 2
Insulation tape
•• The compression dimension should be 8.0.
Compression
dimension
•• After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
CAUTION
•• Make sure that the connection parts are not exposed
to outside.
•• Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials
that have the same level of withstand voltage with
the power cable. (Comply with the local regulations on
extensions.)
Method 2
Compress it 4 times
WARNING
Compress it 4 times
5 mm
5
5 mm
‐‐
Incomplete wire connections can cause electric
shock or a fire.
Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Method 1
Method 2
Insulation tape
40 mm
Insulation tape
35 mm
English 15
Installation
•• In case of extending the electric wire, please DO NOT use
a round-shaped Pressing socket.
Indoor Unit Installation
Step 2.6 Connecting the drain hose
1
In Step 2.2, step 3 you determined the exit position for the
piping bundle. If using the right, bottom, or right rear exit,
change the drain hose connection from the right to the
left so that the drain hose will lie along the inside of the
unit and exit to the right.
CAUTION
•• If the diameter of the connection hose is smaller than
the product’s drain hose, leakage may occur.
Drain hose (A)
Extension drain hose (B)
Drain pan outlet
Rubber cap
40~45 mm
40~45mm
(A)
(B)
CAUTION
•• Be careful not to puncture the plug with the
screwdriver when installing it.
2
Drain hose
Extension drain hose
If using the left, right, or bottom exit, pass the drain hose
through the selected knockout.
20 mm or more
Foam insulation
Vinyl tape
Drain hose Refrigerant pipes
(assembly pipe)
Installation
3
Connection hose
Connect a 15.88 mm ID extension drain hose to the main
drain hose.
16 English
4
Do not box in or cover the drain hose connection. It must
be accessible for testing later in the installation process
and for future servicing.
5
If the drain hose is routed inside the room, insulate the
hose so that dripping condensation does not damage the
furniture or floors.
Step 2.7 Taping the pipes, cables, and
drain hose
1
Wrap foam insulation around the refrigerant pipes, up
to the connection points. The connections must remain
accessible for testing later in the installation process.
Either leave slits in the insulation or do not cover the
connections.
Insulation
Refrigerant pipes
Test parts for the
indoor unit
2
Make a piping bundle by using vinyl tape to wrap together
the refrigerant pipes, power cable, communication cable,
and drain hose, up to the connection points. Connection
points must remain accessible for testing later in the
installation process.
Installation
Mounting bracket
Refrigerant pipes
(assembly pipe)
Vinyl tape
Power and communication
cables (assembly cable)
Drain hose
English 17
Outdoor Unit Installation
Step 3.1 Mounting the outdoor unit
3
Level the unit, then use anchor bolts to secure it at the
four mounting points.
To promote proper condensate draining, the recommended
installation of the outdoor unit is elevated above the ground
on a mounting bracket attached to a concrete pad.
4
For installations in locations that require seismic or
hurricane tie downs, comply with local codes.
5
If the selected location is exposed to strong winds, install
a protective fence around the unit so that the fan can
operate correctly.
In areas where snowfall occurs, the unit must be mounted
above the snow line to allow for proper heating. Snow cannot
be allowed to collect on top of the unit. For promoting natural
drainage in a heavy snow fall area:
On a wall
•• Make space more 80 mm between the bottom of the
outdoor unit and the ground for installation. (Ensure
that the drained water runs off correctly and safely.)
•• Allow enough separation distance between the product
and the ground.
Snow-proof
hood
WARNING
•• The unit must be properly secured to the wall. If the
unit falls, it may result in crushing, electric shock, fire,
or explosion that could cause death, severe personal
injury, or property damage.
1
Estimated
snow fall
80 mm
At the selected installation location (Step 1.1 on page
4), attach the L‑bracket to the wall as follows:
‐‐
Install the bracket as close to the wall as possible.
‐‐
Insert rubber isolators between the bracket and
the wall to minimize sound and vibration to the
structure. Do not fully compress the isolators.
Ground
On the ground
1
Place the outdoor unit in the selected installation location
(Step 1.1 on page 4), ensuring proper clearances and with
the arrow on top of the unit pointing away from the wall.
2
Clip the rubber feet to the tabs to minimize sound and
vibration to the structure.
Y
Installation
X
Soft rubber designed to cut off residual vibration from
outdoor unit to rack (not supplied with product)
Soft rubber designed to cut off vibration from
rack to wall (not supplied with product)
Rubber leg
Model
**09TSFZ***
**09/12TV*****
**09/12TSEA***
**12TSFZ***
**18TVFY***
**18TVFCA**
**18**FZ***
**18TVCA***
**18TVFCB**
**18**EA***
**24*******
18 English
X
436
(Unit: mm)
Y
265
‐‐
Make sure that the bracket is level.
‐‐
Use suitable bolts/washers and lock washers.
507
292
2
Place the outdoor unit on the bracket, ensuring proper
clearances and with the arrow on top of the unit pointing
away from the wall.
602
310
3
Clip the rubber feet to the tabs to minimize sound and
vibration to the structure.
4
660
340
Level the unit, then use anchor bolts to secure it at the
four mounting points.
5
For installations in locations that require seismic or
hurricane tie downs, comply with local codes.
Step 3.2 Connecting the cables and the
pipes
1
Route the piping bundle to the outdoor unit.
2
Use piping clamps to fasten the piping bundle to the
foundation or wall.
3
Cut the refrigerant pipes to the length needed to reach
the pipe connections (located behind the cover panel; see
the figure in step 7).
6
Remove the cover panel on the unit.
7
Remove the service valve caps.
Pipe cutter
Pipe
90°
Oblique
Rough
Burr
4
Remove any burrs, positioning the pipe face down to
make sure that the burrs do not get into the pipe.
5
Assemble the flare connections on the cut pipe ends.
D
90°±2°
Installation
A
45°±2°
L
R 0.4 to 0.8
Pipe
Flare
D
(Unit: mm)
Outer diameter
(D)
Depth (A)
Flare dimension (L)
ø 6.35
1.3
8.7–9.1
ø 9.52
1.8
12.8–13.2
ø 12.70
2.0
16.2–16.6
ø 15.88
2.2
19.3–19.7
English 19
Outdoor Unit Installation
8
Connect the pipes to the service valve with the flare nuts.
Hand-tighten the nuts to prevent stripping.
9
Torque the flare connections to the values in Step 2.3, step
7 on page 13.
10 Connect the power cables and secure with a cable clamp.
L
N
F1
Outdoor-to-indoor power cable
(three wires)
Power cable
(three wires)
F2
Communication cable
(two wires)
11 Connect the outdoor unit power supply cable to the
preinstalled disconnect switch.
12 Leave the cover panel off for testing later in the
installation process.
Installation
20 English
Installation Inspection and Testing
Step 4.1 Performing a drain leak test
Step 4.2 Performing the gas leak tests
1
1
Pour water into the drain pan.
Before inspecting the leakage, use a torque wrench to
close the cap for the stop valve. (Comply with a tightening
torque for each size of the diameter, and tighten the cap
firmly to prevent any leakage.)
Tightening torque for body cap (Refer to the table)
Spindle
Charging core
CAUTION
R-22: Thread of the screw - 7/16-2OUNF
R-410A/R-32 : Thread of the screw -1/2-2OUNF
•• Make sure that the water does not overflow onto the
electrical connection.
2
Tightening torque for charging port cap (Refer to the table)
Check for leaks at the drain connection under the cover
panel.
Tightening torque
<Front view>
3
Make sure that the hose is draining properly at the
outdoor unit.
Outer diameter (mm)
Body cap
(N•m)
ø 6.35
20 to 25
ø 9.52
20 to 25
ø 12.70
25 to 30
ø 15.88
30 to 35
Over ø 19.05
35 to 40
Charging port
cap (N•m)
10 to 12
( 1 N•m = 10 kgf•cm )
Insert inert gas into the pipes connected to indoor and
outdoor units.
3
Test leakage on the connection parts of the indoor and
outdoor units with soap lather or liquid.
Test parts for the
indoor unit
Test parts for the
indoor unit
English 21
Installation
2
Installation Inspection and Testing
Step 4.3 Evacuating the system
CAUTION
•• Because the system does not have filter driers, you
must perform this triple evacuation procedure to
remove all noncondensables and moisture from the
system before charging. Failure to do so will result in
reduced performance and shorter equipment life.
The time required to perform each evacuation will depend on
the capacity (CFM) of the vacuum pump used.
1
Install a micron vacuum gauge to the larger liquid/vapor
line’s service port on the branch of a tee.
2
Install the red high‑side hose of an R-410A gauge
manifold set to the smaller liquid/vapor line’s service port
on the run of the tee.
3
Attach a vacuum pump to the common hose of the
manifold set.
4
To ensure optimal performance, verify that the vacuum
pump’s oil has been changed recently.
5
With the service port closed and the manifold gauge
open, start the vacuum pump and make sure that the
vacuum level drops below 4000 microns (as read on the
micron gauge). If it is difficult to achieve a proper vacuum,
a leak in the hoses is likely. Repair the leak(s) and/ or
check performance of vacuum pump, then repeat this
step.
Installation
6
Open the service port to connect the system to the
manifold.
7
Evacuate until 4000 microns is achieved, for at least 10
minutes.
8
Close the gauge manifold valve, shut off the vacuum
pump, and remove the common hose.
9
Connect the hose to the nitrogen pressure regulator and
bleed the hose by opening the end of the common hose
closest to the manifold.
10 Open the high-pressure manifold valve and slowly bring
the system pressure to atmosphere (50 kPa).
11 Close the manifold and nitrogen cylinder and remove the
common hose.
22 English
12 Reconnect the common hose to the vacuum pump.
Repeat steps 6 through 12, alternating between breaking
the vacuum with dry nitrogen and evacuating, until
system evacuation has occurred three times, to the
following vacuum levels:
Evacution
Microns
First
4000
Second
2000
Third
500
13 After evacuating to at least 500 microns for the third
time, close the gauge manifold valve and wait 10 minutes,
making sure that the vacuum level in the system does not
decrease. If it does, a small leak is likely. Repair the leak
and repeat the evacuation process.
3
Valve
4
15 minutes
Vacuum
Pump
(Backward owing prevention)
Liquid service port <Low pressure>
5
Liquid service port <High pressure>
Step 4.4 Adding refrigerant (if needed)
The outdoor unit is charged with sufficient R-410A refrigerant
to support up to a 5 m line set. For lengths greater than 5 m,
you must add 15g of refrigerant per meter of additional
length, after the lines are evacuated.
1
Calculate the additional refrigerant required:
Additional grams of R-410A = (Total line set meter − 5)
× 15
2
Connect the common hose of the manifold gauge set to
the inverted R-410A refrigerant cylinder.
3
Place the refrigerant cylinder on a scale set to measure
grams.
4
Open the valve on the tank.
5
At the manifold connection, bleed the refrigerant to
remove any air that may be present in the common hose.
6
Open the gauge manifold and charge the system with the
amount of refrigerant calculated in step 1.
7
Close the gauge manifold valve, close the valve on the
refrigerant tank, and remove the common hose.
Step 4.5 Preparing the system for
commissioning
1
Wrap the remaining refrigerant pipe lengths and
connection points with foam insulation.
2
Wrap the unwrapped portions of the piping bundle with
vinyl tape.
3
With the manifold gauge set still installed, open the
isolation valves on the outdoor unit to connect the
outdoor unit to the line set and indoor unit.
4
Remove the manifold set and vacuum gage.
Step 4.6 Commissioning the unit
The unit is commissioned using the Smart Install feature.
Smart Install can be started only with the remote control.
While Smart Install is running, you cannot operate the remote
control.
1
Make sure that the air conditioner is in standby status
(powered up with the controller in off mode).
2
Install batteries in the remote control.
3
Hold down the
(Power),
(Mode), and
(SET)
buttons on the remote control simultaneously for 4
seconds.
4
Wait until Smart Install succeeds or fails (approximately 7
to 13 minutes).
‐‐
While Smart Install is running:
Display
Installation
Type
Indoor unit indicator
The progress is displayed as a
number between 0 and 99 on
the indoor unit display.
‐‐
When Smart Install succeeds: Smart Install ends
with a ringing sound, and the air conditioner
returns to standby status.
‐‐
When Smart Install fails: An error message is
displayed on the indoor unit display, and Smart
Install ends. To correct the problem, see the error
table on page 24.
English 23
Installation Inspection and Testing
Error indicator
Error
Display
,
Measures for the installer to take
Communication error between
indoor and outdoor units
•• Check the cables between the indoor and outdoor units.
See if the power cable or communication cable is crossed.
Error on indoor temperature sensor
•• Make sure that the indoor temperature sensor is properly
connected.
Error on indoor heat exchanger
•• Make sure that the evaporator temperature sensor is
properly connected.
Error on indoor fan motor
•• Make sure that the evaporator motor is properly
connected to the board.
•• Check for a foreign substance inside the unit that may be
preventing the blower wheel from turning.
,
,
EEPROM/Option error
•• Reset the option codes.
•• Make sure that the service valves are completely open.
Refrigerant flow blocking error
•• Check for any blockage in the refrigerant pipe that
connects the indoor and outdoor units.
•• Check for refrigerant leaks.
Lack of refrigerant (for inverter
models only)
Installation
Step 4.7 Performing final checks and
trial operation
•• Make sure a sufficient amount of refrigerant has been
added for a pipe that is longer than 7.5 m.
•• Check for refrigerant leaks between the valve and pipe
connection.
1
WARNING
Stop the unit, disconnect the power, and contact Samsung
technical support if any of the following occurs:
•• The unit produces a burning smell or smoke.
•• The power cable is hot or damaged.
•• The unit is very noisy.
•• Any foreign substance, such as water, has entered the
appliance.
•• The appliance becomes flooded.
24 English
2
Check the following:
‐‐
Strength of the installation site
‐‐
Tightness of pipe connection to detect gas leak
‐‐
Electric wiring connection
‐‐
Heat-resistant insulation of the pipe
‐‐
Drainage
‐‐
Grounding conductor connection
‐‐
Correct operation (Take the following steps.)
Press the
(Power) button on the remote control to
check the following:
‐‐
The indicator on the indoor unit lights up.
‐‐
The airflow blade opens and the fan gears up for
operation.
3
Press the
(Mode) button to select Cool or Heat mode.
Then take the following sub-steps:
‐‐
In Cool mode, use the Temperature button to set
the set temperature to 16 °C.
‐‐
In Heat mode, use the Temperature button to set
the set temperature to 30 °C.
‐‐
Check whether, approximately 3 to 5 minutes later,
the outdoor unit starts, and a cool air blows out.
‐‐
After 12 minutes of stationary condition, check the
indoor unit air treatment.
4
Press the
(Air swing) button to check whether the
airflow blades work properly.
5
Press the
(Power) button to stop the trial operation.
CAUTION
•• Compressor damage may occur if the compressor is run
at a negative suction pressure.
1
1 minute
Gas service port
<Low pressure>
Liquid service port
<High pressure>
Pumping down for removing the product
Pump-down is an operation intended to collect all the system
refrigerant in the outdoor unit. This operation must be carried
out before disconnecting the refrigerant tubing in order to
avoid refrigerant loss to the atmosphere.
WARNING
•• After installing the product, be sure to perform leak
tests on the piping connections. After pumping down
refrigerant to inspect or relocate the outdoor unit,
be sure to stop the compressor and then remove the
connected pipes.
‐‐
2
Off
1
Hold down the
(Power) button on the indoor unit for
5 seconds. Beep sounds immediately to indicate that the
product is ready for pump down procedure.
2
Let the compressor run for more than 5 minutes.
3
Release the valve caps on High and Low pressure side.
4
Use L-wrench to close the valve on the high pressure side.
5
After approximately 1 minute, close the valve on the low
pressure side.
6
Stop operation of the air conditioner by pressing the
(Power) button on the indoor unit or remote control.
7
Disconnect the pipes.
Installation
Do not operate the compressor while a valve is
open due to refrigerant leakage from a pipe or an
unconnected or incorrectly connected pipe. Failure
to do so may cause air to flow into the compressor
and too a high pressure to develop inside the
refrigerant circuit, leading to an explosion or
product malfunction.
English 25
Installation
26 English
Installation
English 27
DB68-08808A-00
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF