Advertisement
Advertisement
SPEAKMAN COMPANY
SE-910 Installation, Maintenance & Operation Instructions
DESCRIPTION
Stay-open ball valve for eye and eye/face washes.
SPECIFICATIONS
VALVE: 1/2” NPT Female Brass, Chrome-Plated. Stay-Open Ball Valve.
INLET: 1/2” NPT Female.
OUTLET: 1/2” NPT Female.
SHIPPING WEIGHT: 1 lb. (.454 kg)
OPTIONS
◊
SSBV2
(1/2” Stainless Steel Valve)
INSTALLATION
Assemble unit in desired position. Connect a water supply to the unit (use pipe sealant on all joints) that is a 1/2” minimum uninterrupted source of potable water. Failure to use potable water can result in emergency units producing impure or contaminated water causing possible further injury.
OPERATION
The valve is activated by pushing the push handle back 90°. The unit will continue to discharge water until the push handle is manually pulled back to the off position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
MAINTENANCE
Should you need parts to repair this unit, please reference the parts listing below for correct part numbers. Before any maintenance is done be sure to shut the water supply off.
WARNING: Use only genuine Speakman parts when repairing or replacing components . To order parts call 1-800-537-2107.
SE-910 REPLACEMENT/REPAIR PARTS
1
PUSH DECAL
ITEM PART/GROUP # DESCRIPTION
1 SE-910 1/2” Ball Valve
FLOW DATA
2
FLOW PRESSURE PSI (BAR)
FLOW RATE GPM (LPM)
20 (1.38)
12 (46)
NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing pressure of 20 PSI and a maximum static pressure of 125 PSI. Note: All units meet existing
ANSI Z358.1 Standards and
OSHA Rules. Product improvements may cause specification and dimensional changes without notice.
06/06
92-1527 Rev-6