MODEL ENC13 - NEMA 4 ENCLOSURES FOR CUB7
DESCRIPTION
This enclosure is designed for applications requiring a water resistant instrument enclosure. The enclosure is fabricated of polycarbonate and is designed to withstand NEMA 4X/IP65 wash-down applications. The enclosure must be drilled to accept conduit fittings or other types of wiring connectors.
The enclosure can be used free-standing, or it can be securely fastened to a mounting surface.
ENC13 DIMENSIONS In inches (mm)
ORDERING INFORMATION
MODEL NO DESCRIPTION
ENC13 Plastic Enclosure for CUB7 units
Bulletin No. ENC13-X
Drawing No. LP0781
Effective 03/09
PART NUMBER
ENC13000
ENC13 INSTALLATION
It is recommended to wire the unit before mounting it in the enclosure to ensure good electrical connections. The following steps outline the most common sequence for installing a unit.
1. Determine the location of the conduit fitting and drill the necessary hole.
Install the fitting and bring the wiring into the enclosure.
2. Slide the panel gasket over the rear of the unit to the back of the bezel .
3. Assemble nut fastener and mounting screw onto both sides of the mounting clip. The tip of the screw should not project from the hole in mounting clip.
4. Install the unit through the opening in the front of the lid until the bezel flange contacts the panel.
5. Slide the mounting clip over the rear of the unit until the mounting clip is against the inside of the enclosure. The mounting clip has latching features which engage into mating features on the unit’s housing.
Note: It is necessary to hold the unit in place when sliding the mounting clip into position.
6. Alternately tighten each screw to ensure uniform gasket pressure.
Visually inspect the front panel gasket. The gasket should be compressed to about 75 to 80% of its original thickness
(Recommended torque is 28 to 36 in-oz.). If not, gradually turn mounting screws to further compress the gasket.
7. If the gasket is not adequately compressed, and the mounting screws can no longer be turned, loosen the mounting screws and check that the mounting clip is latched as close as possible to the inside of enclosure. Repeat the procedure for tightening the screws.
8. Connect the necessary wires to the unit for the application desired.
9. Assemble the enclosure with the screws provided. Alternately tighten each screw to ensure uniform gasket pressure.
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683

Public link updated
The public link to your chat has been updated.
Advertisement