OUTPUT MODULES
SPECIFICATIONS & TYPICAL CONNECTIONS:
INSTALLING OUTPUT MODULES
To install an output module into the controller, remove the bezel assembly from the case (see Removing Bezel Assembly in the appropriate instruction manual).
Locate the correct output module socket (OP1, AL1, or AL2/OP2, see figure below or label on outside of case) and plug the output module into the socket. No re-programming is required. If changing an output module type, be sure the appropriate output interface wiring changes are made. Re-install the bezel assembly when complete.
Relay :
Type : Form-C
Rating : 5 Amps @ 120/240 VAC or 28 VDC (resistive load ), 1/8 HP @
120 VAC (inductive load).
Life Expectancy : 100,000 cycles at maximum load rating. (Decreasing load and/or increasing cycle time, increases life expectancy).
Logic/SSR Drive : Can drive multiple SSR Power Units.
Type : Non-isolated switched DC, 12 VDC typical.
Drive : 45 mA max. (3 VDC min.)
Note: Reference the “Output Modules” section for the various output configurations.
Triac :
Type : Isolated, Zero Crossing Detection
Rating :
Voltage : 120/240 VAC
Max. Load Current: 1 Amp @ 35 ° C
0.75 Amp @ 50 ° C
Min. Load Current : 10 mA max.
Offstate Leakage Current : 7mA max. @ 60 Hz
Operating Frequency : 20 to 500 Hz
Protection : Internal Transient Snubber, Fused
Red Lion Controls
20 Willow Springs Circle
York PA 17402
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls BV
Basicweg 11b
NL - 3821 BR Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls AP
31, Kaki Bukit Road 3,
#06-04/05 TechLink
Singapore 417818
Tel +65 6744-6613
Fax +65 6743-3360
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project