Schluter®-DITRA-HEAT Installation Handbook 2020
5,5 mm
Electric Floor Warming System
with Integrated Uncoupling Technology
Schluter®-DITRA-HEAT
Electric Floor Warming System with Integrated Uncoupling Technology
Ceramic and stone tiles are the ideal surface coverings because they are durable, easy to maintain, and hygienic. However two
common barriers to the selection of tile as a floor covering are concerns about cracking and the perception that tiles are cold.
Floor warming systems are a growing trend in tile applications, but none address concerns about cracking. A viable installation
system must address the magnified fluctuations in temperature that contribute to increased shear stresses between the substrate
and the tile covering. Schluter®-DITRA-HEAT integrates customizable, comfortable electric floor warming with the functions
associated with DITRA: uncoupling, waterproofing, vapor management and support to ensure a long lasting installation. DITRAHEAT is primarily intended to warm tile floors and make them more comfortable underfoot, but can contribute to space heating.
DITRA-HEAT is also suitable for applications with alternate floor coverings such as engineered wood, luxury vinyl, wood and
stone plastic composite, and laminate flooring.
DITRA-HEAT combines the flexibility of loose heating cables with the ease of installation of mat systems. Cables can be
placed wherever heat is desired, without creating height differences in the floor. Self-leveling compounds are not required to
encapsulate the cables, significantly reducing installation time and effort compared to uncoupling membranes over other electric
floor warming systems.
Uncoupling
Tile has been successfully installed for thousands of years by incorporating an uncoupling layer,
or forgiving shear interface, within the tile assembly. DITRA-HEAT provides uncoupling through
its geometric configuration, which allows for in-plane movement that effectively neutralizes the
differential movement stresses between the substrate and the tile, thus eliminating the major cause
of cracking and delaminating of the tiled surface.
Waterproofing
DITRA-HEAT provides reliable waterproofing. Its polypropylene composition protects the substrate
from moisture penetration, which is particularly important in today’s building environment where
most substrates are moisture sensitive.
Vapor Management
The free space on the underside of DITRA-HEAT provides a route for excess moisture and vapor
to escape from the substrate that could otherwise cause damage to the tile covering above.
Thus, DITRA-HEAT effectively manages moisture beneath the tile covering.
Support/Load Distribution
When placed on a solid foundation, columns or pillars can support tremendous loads. The
same physical principle applies to DITRA-HEAT installations. Column-like mortar structures are
formed in and between the studs on the surface of the matting. Loads are transferred from the
tile covering through these column-like mortar structures to the substrate. Since DITRA-HEAT is
virtually incompressible within the tile assembly, the advantages of uncoupling are achieved without
sacrificing point load distribution capabilities.
Legend
Essential
Significant
Helpful
Schluter®-Systems’ written installation instructions shall have
precedence over referenced industry standard guidelines and
installation procedures insofar as referenced information may contain
overlapping or conflicting requirements. Type, thickness, and format
of the ceramic or stone tile surface covering must be suitable for the
intended application.
CONTENTS
WOOD
4
6
7
7
Floors,
Floors,
Floors,
Floors,
Interior
Interior
Interior
Interior
–
–
–
–
16, 19.2, & 24-inch o.c. joist spacing
Natural Stone Tile
Existing Vinyl
Structural Plank Subfloor
CONCRETE
8 Floors, Interior – Ceramic or Stone Tile
GYPSUM
9 Floors, Interior – Ceramic or Stone Tile
SHOWER ASSEMBLY
10 Shower application
WATERPROOFING
12 Floors, Interior – Ceramic or Stone Tile
MOVEMENT JOINTS
13 Placement guidelines and descriptions
WOOD UNDERLAYMENT
ALTERNATIVE FLOOR COVERINGS
INSTALLATION
THIN-SET FACTS
HEATING CABLE SPECIFICATION
TESTING & CERTIFICATIONS
SOUND CONTROL
16 Installation guidelines
17 Floors, Interior - Engineered Wood, Vinyl, WPC, LVT/LVP,
SPC, and Laminate
19 Installation instructions
25 Discussion of thin-set mortar types to be used with
Schluter®-DITRA-HEAT
26 Schluter®-DITRA-HEAT-E-HK specification
27 Products evaluation
29 Discussion of sound control in conjunction with
ceramic & stone tile
DITRA-HEAT-DUO
CONCRETE SUBFLOORS
31 Solution to improve floor warming response time
32 Discussion on Schluter®-DITRA-HEAT installations over
concrete subfloors
208 V APPLICATIONS
SPACE HEATING
33 Discussion of heating cables in 208 V applications
34 Discussion on use of Schluter®-DITRA-HEAT for space
heating
NATURAL STONE
35 Discussion of natural stone and
single-layer wood subfloors
HEATING CABLE TESTS LOG
36
WARRANTY
40
Heating cables must be installed by a qualified person in accordance
with this handbook and with the National Electric Code (USA) or
Canadian Electric Code Part I (CAN) as applicable. All electrical
connections must be made by a qualified electrician, according to
the electrical and building codes effective in your region.
This installation handbook is subject to change without notice.
Please visit www.schluter.com for the latest version.
WOOD
Every substrate presents unique challenges
All wood materials, including OSB, plywood, and framing members, are subject to expansion, contraction, bending, and deflection as a
result of changes in moisture content and loading. Further, these deformations fluctuate over the life of the building structure.
The uncoupling function of DITRA-HEAT protects the ceramic or stone tile covering from the aforementioned deformations by neutralizing
the differential movement stresses between the wood structure and the tile, thus eliminating the major cause of cracking and delaminating
of the tiled surface. Therefore, DITRA-HEAT can replace a second layer of plywood in most applications.
Since wood structures are sensitive to moisture, the DITRA-HEAT membrane's waterproofing function adds an essential
element to the flooring assembly by providing simple, effective, and permanent moisture protection.
Wood continually absorbs and releases moisture. The free space beneath the DITRA-HEAT membrane allows the wood to
breathe and provides a route for any residual moisture in the wood substrate to escape.
Since DITRA-HEAT is virtually incompressible within the tile assembly, the advantages of uncoupling are achieved without
sacrificing point load distribution capabilities.
By addressing all of the challenges associated with today’s fast, lightweight construction methods, DITRA-HEAT provides a
durable installation system for ceramic and stone tile over wood substrates.
DITRA-HEAT combines the flexibility of loose heating cables with the ease of installation of mat systems. Cables can be placed wherever
heat is desired, without creating height differences in the floor. Self-leveling compounds are not required to encapsulate the cables,
significantly reducing installation time and effort compared to uncoupling membranes over other electric floor warming systems.
Floors, Interior - Ceramic or Porcelain Tile
DH-W16-T-20
Ceramic or porcelain tile
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter ALL-SET®,
Schluter FAST-SET®,
or modified thin-set mortar
Single layer of
plywood or OSB
Joists, I-joists, or
trusses
16" (406 mm) o.c. joist spacing, single layer OSB
or plywood subfloor
Areas of Application
over any even and structurally sound OSB or
plywood subfloor with 16" (406 mm) o.c. joist
spacing
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
for natural stone, see detail DH-W-S (page 6)
and natural stone discussion (page 35)
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 16" (406 mm) o.c.
minimum subfloor thickness – 19/32", 5/8"
nom. (16 mm) tongue-and-groove with 1/8"
(3 mm) gap between sheets.
Substrate Preparation
verify that subfloor panels are properly
fastened to framing members.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO.
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
4
WOOD — Floors, Interior - Ceramic or Porcelain Tile
Setting and Grouting Materials
modified thin-set mortar - ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT and DITRA-HEAT-DUO.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed
with KERDI-BAND using Schluter SET®,
Schluter ALL-SET®, Schluter FAST-SET®, or
unmodified thin-set mortar; see page 12.
DH-W19-T-20
Ceramic or porcelain tile
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter ALL-SET®,
Schluter FAST-SET®,
or modified thin-set mortar
Single layer of
plywood or OSB
Joists, I-joists, or
trusses
19.2" (488 mm) o.c. joist spacing, single layer OSB
or plywood subfloor
Areas of Application
over any even and structurally sound OSB or
plywood subfloor with 19.2" (488 mm) o.c.
joist spacing
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
for natural stone, see detail DH-W-S (page 6)
and natural stone discussion (page 35)
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 19.2" (488 mm) o.c.
minimum subfloor thickness – 23/32",
3/4" nom. (19 mm) tongue-and-groove with
1/8" (3 mm) gap between sheets.
Substrate Preparation
verify that subfloor panels are properly
fastened to framing members.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO.
DH-W24-T-20
Ceramic or porcelain tile
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter ALL-SET®,
Schluter FAST-SET®,
or modified thin-set mortar
Double layer of
plywood or OSB
Joists, I-joists, or
trusses
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
modified thin-set mortar - ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT and DITRA-HEAT-DUO.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND using Schluter SET®, Schluter
ALL-SET®, Schluter FAST-SET®, or unmodified
thin-set mortar; see page 12.
24" (610 mm) o.c. joist spacing, double layer OSB
or plywood subfloor
Areas of Application
over any even and structurally sound double
layer OSB or plywood floor
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 24" (610 mm) o.c.
double layer wood floor consisting of:
• minimum subfloor thickness – 23/32",
3/4" nom. (19 mm) tongue-and-groove
• minimum underlayment thickness –
11/32", 3/8" nom. (10 mm)
Substrate preparation
verify that subfloor panels are properly
fastened to framing members.
underlayment – minimum 11/32", 3/8" nom.
(10 mm)-thick Exposure 1, plugged-face
plywood or OSB with 1/8" (3 mm) gap
between sheets; see page 16 for
underlayment installation guidelines.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO.
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
modified thin-set mortar - ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT and DITRA-HEAT-DUO.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND using Schluter SET®, Schluter
ALL-SET®, Schluter FAST-SET®, or unmodified
thin-set mortar; see page 12.
WOOD — Floors, Interior - Ceramic or Porcelain Tile
5
Floors, Interior - Natural Stone Tile
DH-W-S-20
Natural stone tile
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter ALL-SET®,
Schluter FAST-SET®,
or modified thin-set mortar
Double layer of
plywood or OSB
Joists, I-joists, or
trusses
Double layer of OSB or Plywood subfloor
Areas of Application
over any even and structurally sound double
layer OSB or plywood floor
interior dry or wet areas
Limitations
requires double layer wood floor regardless
of joist spacing
minimum 2" x 2" (50 mm x 50 mm) tile
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 24" (610 mm) o.c.
double layer wood floor consisting of:
• minimum subfloor thickness – 23/32",
3/4" nom. (19 mm) tongue-and-groove
• minimum underlayment thickness –
11/32", 3/8" nom. (10 mm)
Substrate Preparation
verify that subfloor panels are properly
fastened to framing members.
underlayment – minimum 11/32", 3/8" nom.
(10 mm)-thick Exposure 1, plugged-face
plywood or OSB with 1/8" (3 mm) gap
between sheets; see page 16 for
underlayment installation guidelines.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO.
6
WOOD — Floors, Interior
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
modified thin-set mortar - ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
certain moisture-sensitive stones, e.g., green
marble, or resin-backed tiles may require
special setting materials. Consult stone
supplier and Schluter®-Systems for more
information.
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT and DITRA-HEAT-DUO.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND
using
Schluter
SET®,
Schluter ALL-SET®, Schluter FAST-SET®, or
unmodified thin-set mortar; see page 12.
Floors, Interior - Existing Vinyl Floors
DH-V-T-20
Tile or wood base
Areas of Application
over any even and structurally sound substrate
with existing vinyl flooring
interior dry or wet areas
Ceramic, porcelain
or stone tile
RONDEC
DILEX-EKE
Schluter SET®,
Schluter ALL-SET®,
Schluter FAST-SET®,
or unmodified
thin-set mortar
KERDI-BAND
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter FAST-SET
or fast-setting modified
thin-set mortar
®
Existing vinyl
Plywood or OSB
Joists, I-joists, or
trusses
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
cushioned vinyl unacceptable
perimeter bonded vinyl flooring unacceptable
multiple layers of vinyl unacceptable
Requirements
for wood substrates, subfloor/underlayment
configuration according to detail DH-W16-T,
DH-W19-T, DH-W24-T, or DH-W-S
Substrate Preparation
ensure that the structure beneath the vinyl is
sound and adequate
ensure that vinyl is well adhered
remove any wax and clean vinyl
for wood substrates, nail off floor with ring
shank flooring nails every 4" (102 mm) o.c. –
fasteners must pass through entire thickness
of assembly with minimal penetration into
joists
any leveling of the subfloor must be done prior
to installing DITRA-HEAT and DITRA-HEATDUO.
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
Fast-setting modified thin-set mortar - ANSI
A118.4 or ANSI A118.15
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
DH-SP-TS-20
Ceramic, porcelain
or stone tile
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter ALL-SET®,
Schluter FAST-SET®,
or modified thin-set mortar
Plywood or OSB
underlayment
Structural plank
subfloor
Joists
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
DITRA-HEAT and DITRA-HEAT-DUO are
adhered to the vinyl flooring using Schluter
FAST-SET® or fast-setting modified thin-set
mortar suitable for bonding to vinyl. As an
alternative, a suitable cement-based
embossing leveler or Schluter ALL-SET® or an
appropriate modified thin-set mortar can be
used to skim coat the vinyl to provide a
bonding surface. When skim coat is cured,
DITRA-HEAT and DITRA-HEAT-DUO are
adhered to the skim coat using Schluter SET®
or unmodified thin-set mortar. See page 25 for
discussion on latex-modified thin-set mortars
sandwiched between two impervious layers.
seaming DITRA-HEAT and DITRA-HEAT-DUO,
including floor/wall connections, with KERDIBAND may be appropriate in cases where a
break in the water line of an ice maker or
dishwasher can damage pre-existing moisturesensitive substrates and underlayments.
KERDI-BAND floor/wall connections are just as
easily concealed with wood base as with tile.
KERDI-BAND floor/wall connections in
dishwasher alcoves are parged with thin-set
mortar; see page 12.
vapor barrier on crawl space floors according
to regional building codes.
certain moisture-sensitive stones, e.g., green
marble, or resin-backed tiles may require
special setting materials. Consult stone supplier
and Schluter®-Systems for more information.
Floors, Interior - Structural Plank Subfloor
Areas of Application
over structural plank subfloors
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
Requirements
maximum spacing of joists is 24" (610 mm) o.c.
double layer wood floor consisting of:
• minimum structural plank subfloor
thickness – 3/4" (19 mm)
• minimum underlayment thickness –
15/32", 1/2" nom. (13 mm)
Substrate Preparation
verify that subfloor planks are properly
fastened to framing members.
underlayment – minimum 15/32", 1/2" nom.
(13 mm)-thick Exposure 1, plugged-face
plywood or OSB with 1/8" (3 mm) gap
between sheets; see page 16 for
underlayment installation guidelines.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO.
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
modified thin-set mortar - ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND using Schluter SET®, Schluter
ALL-SET®, Schlurer FAST-SET®, or unmodified
thin-set mortar; see page 12.
certain moisture-sensitive stones, e.g., green
marble, or resin-backed tiles may require
special setting materials. Consult stone
supplier and Schluter®-Systems for more
information.
WOOD — Floors, Interior
7
CONCRETE
Every substrate presents unique challenges
There are various challenges associated with the installation of hard surface coverings on concrete substrates.To begin, the coefficient of thermal
expansion of concrete is close to twice that of ceramic tile. Additionally, tile contractors are often expected to install tile over young concrete
(concrete cured less than 28 days). However, rigid surface coverings installed over young concrete are susceptible to damage as a result of
shrinkage during curing. Pre-stressed/post-tensioned concrete slabs are also commonplace in today’s construction environment. Although prestressing is used to help control deflections in concrete structures, these slabs are still subject to deformations caused by changes in moisture,
temperature, and loading. Many concrete slabs on or below grade are subject to moisture migration, which can be problematic. Furthermore,
these structures experience the same deformations as stated above.
The uncoupling function of DITRA-HEAT protects the ceramic or stone tile covering by neutralizing the differential movement
stresses between the concrete substrate and the tile, thus eliminating the major cause of cracking and delaminating of the tiled surface.
The DITRA-HEAT membrane’s waterproofing ability not only protects the substrate from harmful substances, it also slows the drying
of fresh concrete, which reduces the chances of cracking and curling of the slab.
The configuration of the DITRA-HEAT matting provides free space to accommodate vapor emissions from the concrete slab. This
allows the installation of DITRA-HEAT and the tile covering as soon as the slab can be walked upon. Vapor management is also
essential for slabs subject to moisture migration.
Since DITRA-HEAT is virtually incompressible within the tile assembly, the advantages of uncoupling are achieved without sacrificing
point load distribution capabilities.
By addressing all of the challenges associated with today’s fast construction methods, DITRA-HEAT provides a durable installation system for
ceramic and stone tile over concrete substrates.
DITRA-HEAT combines the flexibility of loose heating cables with the ease of installation of mat systems. Cables can be placed wherever heat is
desired, without creating height differences in the floor. Self-leveling compounds are not required to encapsulate the cables, significantly reducing
installation time and effort compared to uncoupling membranes over other electric floor warming systems. Concrete substrates can absorb heat
energy increasing the time it takes for floors to warm up, particularly when there is no insulation layer below the concrete. In some cases, floors
may never reach the desired temperature. DITRA-HEAT-DUO features an integrated thermal break to reduce sound transmission through floorceiling assemblies, reduce heat loss to concrete substrates, and improve floor warming response times.
Floors, Interior - Ceramic or Stone Tile
DH-C-TS-20
Concrete subfloor
Ceramic, porcelain
or stone tile
Schluter SET , Schluter ALL-SET ,
Schluter FAST-SET®, or unmodified
thin-set mortar
®
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter SET®,
Schluter ALL-SET®,
Schluter FAST-SET®,
or unmodified thin-set mortar
Concrete
®
Areas of Application
over any structurally sound and even concrete
subfloor
young concrete (concrete cured less than 28 days)
on or below grade concrete subject to moisture
migration
post-tensioned or pre-stressed concrete
cracked concrete
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
concrete slabs subject to moisture migration
must have all seams in DITRA-HEAT and
DITRA-HEAT-DUO sealed with KERDI-BAND
using unmodified thin-set mortar
any cracks in concrete subfloor must exhibit
in-plane movement only; thin-set tile assemblies,
including those incorporating DITRA-HEAT or
DITRA-HEAT-DUO, cannot accommodate
differential vertical displacement
Requirements
slab to be structurally sound
slab to be free of waxy or oily films and curing
compounds (when present, mechanical
scarifying is necessary)
the installation of DITRA-HEAT or DITRA-HEATDUO and tile can begin as soon as the slab can
be walked upon
slab to be free of standing water
sound control floors - Schluter perimeter
movement joints recommended to help limit
sound energy transfer
8
CONCRETE — Floors, Interior - Ceramic or Stone Tile
Substrate Preparation
any leveling of the subfloor must be done prior
to installing DITRA-HEAT and DITRA-HEATDUO
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints, including
perimeter joints, within the tiled surface. Movement
joints must be installed in accordance with industry
standards and norms; see page 13 of this
Handbook, TCNA EJ171, and TTMAC 301 MJ
Setting and Grouting Materials
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND using unmodified thin-set mortar;
see page 12.
certain moisture-sensitive stones, e.g., green
marble, or resin-backed tiles may require special
setting materials. Consult stone supplier and
Schluter®-Systems for more information
consider the use of DITRA-HEAT-DUO to
improve the response time of DITRA-HEAT in
applications over concrete. See page 31 for
more information.
GYPSUM
Every substrate presents unique challenges
Bonding ceramic or stone tiles directly to gypsum concrete substrates is generally considered questionable or not recommended. The
challenges associated with gypsum-based underlayments include the requirement of an extended drying period before installing tile and
continued sensitivity to the reintroduction of moisture throughout the life of the installation. In addition, since the coefficient of thermal
expansion of gypsum concrete is substantially greater than that of ceramic tile, shear stresses caused by temperature fluctuations can
result in delamination or cracking of the tile covering. This is particularly important when gypsum concrete is used as a thermal mass for
radiant heated floors. With the increasing popularity of radiant heated floors, which typically utilize gypsum concrete, tile installers need a
reliable installation system to address these issues.
The uncoupling function of DITRA-HEAT protects the ceramic or stone tile covering by neutralizing the differential movement
stresses between the gypsum concrete substrate and the tile, thus eliminating the major cause of cracking and delaminating
of the tiled surface.
The DITRA-HEAT membrane’s waterproofing function prevents the reintroduction of moisture to gypsum concrete
underlayments, which, if not prevented, could significantly compromise performance of the underlayment and lead to damage
of the tiled surface.
The configuration of the DITRA-HEAT matting provides free space to accommodate vapor emissions from the gypsum.
Since DITRA-HEAT is virtually incompressible within the tile assembly, the advantages of uncoupling are achieved without
sacrificing point load distribution capabilities.
By addressing all of the challenges associated with today’s fast, lightweight construction methods, DITRA-HEAT provides a durable
installation system for ceramic and stone tile over gypsum substrates.
DITRA-HEAT combines the flexibility of loose heating cables with the ease of installation of mat systems. Cables can be placed
wherever heat is desired, without creating height differences in the floor. Self-leveling compounds are not required to encapsulate the
cables, significantly reducing installation time and effort compared to uncoupling membranes over other electric floor warming systems.
DITRA-HEAT is useful even in applications where hydronic radiant-heating tubes are incorporated in gypsum concrete, as there may be
times when floor warming is desirable while radiant heating is not necessary.
Floors, Interior - Ceramic or Stone Tile
DH-G-TS-20
Gypsum concrete
Ceramic, porcelain
or stone tile
Schluter SET , Schluter ALL-SET ,
Schluter FAST-SET®, or unmodified
thin-set mortar
®
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Schluter SET®,
Schluter ALL-SET®,
Schluter FAST-SET®,
or unmodified thin-set mortar
Gypsum
concrete
®
Areas of Application
over gypsum concrete underlayment placed
over structurally sound wood or concrete
subfloors
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
DITRA-HEAT-DUO not recommended over
heated floors
Requirements
for wood substrates, subfloor/underlayment
configuration according to detail DH-W16-T,
DH-W-20-T, or DH-W24-T.
where radiant heat tubes are laid over the
subfloor, gypsum poured to a height that is
3/4" (19 mm) above the tops of the tubes is
required before installing DITRA-HEAT.
residual moisture in gypsum screed, 2.0%
(percentage by volume) or less before installing
DITRA-HEAT and DITRA-HEAT-DUO.
Substrate preparation
gypsum – follow manufacturer’s directions
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints, within the tiled
surface. Movement joints must be installed in
accordance with industry standards and
norms; see page 13 of this Handbook, TCNA
EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Installation Specifications
gypsum – follow manufacturer’s directions
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
since DITRA-HEAT and DITRA-HEAT-DUO
must bond to the gypsum concrete, follow
gypsum manufacturer’s directions regarding
primers and/or special surface preparation
before installing DITRA-HEAT and DITRAHEAT-DUO.
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed with
KERDI-BAND using Schluter SET®, Schluter
ALL-SET®, Schluter FAST-SET®, or unmodified
thin-set mortar; see page 12.
certain moisture-sensitive stones, e.g., green
marble, or resin-backed tiles may require
special setting materials. Consult stone
supplier and Schluter®-Systems for more
information.
vapor barrier on crawl space floors according
to regional building codes.
GYPSUM — Floors, Interior - Ceramic or Stone Tile
9
SHOWER ASSEMBLY
Showers – Ceramic or stone tile
Schluter®-DITRA-HEAT Shower Application
DH-SH-20
5
8
2
8
1
4
1
2
3
6
8
8
9
7
7
7
15
6
10a
11a
16
10b
3
11b
12
15
3
13
14
14
15
1
Ceramic or stone tile
9
Solid backing
2
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
10
Drain:
13
Schluter ®-SHOWERPROFILE-WSK/-WSL
Shower profile
3
Schluter ®-KERDI
waterproofing membrane
4
Schluter ®-KERDI-BOARD
waterproof building panel
5
Schluter ®-KERDI-BOARD-ZT/-ZS
washers and screws
6
Schluter ®-KERDI-BAND
waterproofing strips
7
Schluter ®-KERDI-KERECK-F
waterproofing corners
8
10
Schluter ®-KERDI-SEAL-PS/-MV
seals or Schluter ®-KERDI-FIX
sealant and bonding compound
SHOWER ASSEMBLY
Alternative (not shown):
a. Schluter ®-KERDI-DRAIN
b. Schluter ®-KERDI-LINE
• Schluter ®-SHOWERPROFILE-WS/-WSC
14
11
Base:
a. Schluter ®-KERDI-SHOWER-T/-TS/-TT
b. Schluter ®-KERDI-SHOWER-LT/-LTS
Alternative (not shown):
• Mortar bed
12
Schluter ®-KERDI-BOARD-SC
curb
Alternatives (not shown):
• Schluter®-KERDI-BOARD
waterproof building panel
• Built-up curb
Schluter ®-DITRA-HEAT or
Schluter ®-DITRA-HEAT-DUO
Electric floor warming and uncoupling
membrane
15
Wood or concrete subfloor
16
Schluter ®-DILEX profile (optional)
Bench (not shown, optional):
• Schluter ®-KERDI-BOARD-SB
• Schluter ®-KERDI-BOARD
Niche (not shown, optional):
• Schluter ®-KERDI-BOARD-SN
Showers – Ceramic or stone tile
Schluter®-DITRA-HEAT Shower Application
DH-SH-20
Areas of Application
2 studs from the edge of the KERDI-DRAIN flange.
Safety
Interior showers with or without curbless applications.
Interior intermittent use steam showers (e.g., residential applications). See detail
K-SSH in the Schluter®-Shower System Installation Handbook for more information.
Over wood or concrete subfloors.
Limitations
Certain glass tiles may not be compatible with bonded waterproof membranes and/
or may require special setting materials. Consult glass tile manufacturer and
Schluter®-Systems for more information.
Certain moisture sensitive stones, e.g., green marble, or resin-backed tiles may not
be appropriate for use in wet areas such as showers or may require special setting
materials. Consult stone supplier and Schluter®-Systems for more information.
Do not use sawn lumber curbs on concrete subfloors subject to moisture migration.
Requirements
Plywood, OSB, or concrete subfloor must be clean, even, and load bearing.
For wood substrates, subfloor/underlayment configuration according to detail
DH-W16-T, DH-W19-T, DH-W24-T, or DH-W-S.
For curbless applications: Recessing the floor of a bathroom must be done in a way
that preserves the structural integrity and safety of the construction. This may require
the services of a qualified design professional (e.g., architect, engineer, etc.).
Solid backing – gypsum wallboard, cementitious backer unit,
fiber-cement underlayment, fiber-reinforced water-resistant gypsum backerboard/
underlayment, coated glass mat water-resistant gypsum backerboard, Portland
cement mortar bed, concrete, or masonry.
Minimum KERDI-BOARD thickness – 1/2" (12.5 mm) for studs spaced at
16" (40.6 cm) o.c. and 3/4" (19 mm) for studs spaced at 24" (61.0 cm) o.c.
KERDI-BOARD shall be fastened to wood or metal framing with appropriate screws
(i.e., coarse thread wood screw for wood studs and self-tapping for metal studs) and
corresponding KERDI-BOARD-ZT washers. Screws must reach a depth of at least
3/4" (20 mm) in wood studs and 3/8" (10 mm) in metal studs. Maximum allowable
on-center fastener spacing is 12" (30 cm) for walls and 6" (15 cm) for ceilings.
KERDI or KERDI-BOARD shall be installed up to the height of the showerhead at
minimum.
Any protrusions through the KERDI or KERDI-BOARD (e.g., showerhead, mixing valve,
etc.) must be treated with KERDI-SEAL-PS/-MV seals, KERDI-FIX or suitable sealant.
Base – KERDI-SHOWER-T/-TS/-TT/-LT/-LTS or Portland cement mortar bed.
Ramp – KERDI-SHOWER-SR or Portland cement mortar bed.
Curb – KERDI-BOARD-SC, KERDI-BOARD, concrete, masonry block, or sawn
lumber sheathed with solid backing (see above).
Bench – KERDI-BOARD-SB, KERDI-BOARD, concrete, masonry block, or sawn
lumber sheathed with solid backing (see above).
All horizontal surfaces (e.g., benches, curbs, window sills, shelves, etc.) must be
sloped toward the shower drain.
KERDI-DRAIN/-LINE shall be properly supported. Additional thin-set mortar may be
needed to bed the KERDI-DRAIN for this detail.
KERDI-DRAIN/-LINE shall be connected to the waste line; use ABS cement for ABS
drains, PVC cement for PVC drains, a no-hub coupling for stainless steel drains with
no-hub outlets, and thread sealing compound or tape for stainless steel drains with
threaded outlets.
When using the stainless steel
KERDI-FIX to bond KERDI to the drain.
Note: Please refer to the Schluter®-Shower System
Installation Handbook for installation instructions and
warranty criteria for the Schluter®-Shower System.
KERDI-DRAIN
bonding
flange,
use
DITRA-HEAT heating cables must be installed in the DITRA-HEAT or DITRA-HEATDUO membrane. KERDI must be installed over the heating cables and DITRA-HEAT/DUO in the shower.
Due to the installation of the DITRA-HEAT membrane on top of the shower tray, it is
necessary to raise the height of the KERDI-DRAIN/LINE. Installation of DITRA-HEAT
membrane on the substrate under the detachable center section for KERDI-DRAIN or
under the KERDI-LINE channel body support will provide the proper height
adjustment.
When a curb is used, the heating cables must be installed over the curb in a 3/4" wide
x 1/4" deep routed section and encased in thin-set mortar. DO NOT install the
heating cable under the curb or go through the curb, as this could cause
damage to the heating cable and curb. After the heating cable is installed,
apply KERDI over the routed section of the KERDI-BOARD-SC curb or over
the entire built-up curb.
A dedicated heating cable is recommended in the shower area to allow for simple
disconnection without an impact on the bathroom floor heating in the event that the
shower heating cable is damaged. Multiple heating cables may be installed on a single
thermostat, up to the 15 amp limit.
Heating cables must be installed 3 studs from the edge of the KERDI-LINE flange and
Repairs to the DITRA-HEAT heating cable in the shower may not be approved. Verify
with the local inspector or authority having jurisdiction (AHJ). Flood testing the shower
is recommended before re-tiling.
Heating cable factory splice (i.e., cold lead splice) must not be installed in the shower
area.
Substrate Preparation
Verify that subfloor panels and solid backing are properly fastened to framing members.
Any leveling of the subfloor must be done prior to installing
KERDI-SHOWER-T/-TS/-TT/-LT/-LTS/-SR, KERDI-BOARD-SC/-SB, DITRA-HEAT,
and DITRA-HEAT-DUO membranes.
Solid Backing Materials
Gypsum wallboard – ASTM C1396/C1396M
Cementitious backer unit – ANSI A118.9 or ASTM C1325
Fiber-cement underlayment – ASTM C1288
Fiber-reinforced water-resistant gypsum
backerboard/underlayment – ASTM C1278
Coated glass mat water-resistant gypsum backerboard – ASTM C1178
Portland cement mortar – ANSI A108.1B
Concrete
Masonry
Setting and Grouting Materials
Unmodified thin-set mortar – ANSI A118.1
Grout – ANSI A118.3, A118.6, A118.7
Installation Specifications
Solid backing panels – follow manufacturer’s instructions
Portland cement mortar bed – ANSI A108.1B
Tile – ANSI A108.5
Grout – ANSI A108.6, A108.10
Other Considerations
Acceptance of electric floor warming in a shower and this detail must be verified by
the local inspector or authority having jurisdiction (AHJ).
KERDI is required on top of DITRA-HEAT installations in the shower. Schluter®Systems chooses to be conservative and to ensure everything is protected. Note:
DITRA-HEAT-E-HK heating cables are rated for wet applications per CAN/CSAC22.2 No.130-03. DITRA-HEAT membranes have been found to meet or exceed
the requirements of ANSI A118.10.
Curbless tiled showers rely on the slope of the floor to effectively contain water in the
immediate shower area and direct water to the drain. Given the wide range of
potential configurations, it isn’t possible to address them all in this Handbook.
For curbless applications: waterproofing must be installed in all areas subject to water
exposure.
Schluter®-SHOWERPROFILE-WS/-WSK system profiles can be used to form a
splashguard at the entrance of curbless showers.
Various building codes and other sources, such as the Americans with Disabilities Act,
include specific requirements for disabled access in public buildings and must be
consulted when applicable. Areas of interest may include degree of slope, clearance,
and supporting structures such as grab bars.
Shower grab bars must be anchored in the structure or solid blocking behind KERDIBOARD.
When KERDI-SHOWER-T/-TS/-TT/-LT/-LTS tray dimensions do not match the
dimensions of the shower compartment, the tray may be cut or extended with dry
pack mortar.
When KERDI or KERDI-BOARD and tile are installed on the ceiling, the solid backing
and fasteners must be able to support the load of the tile and setting and grouting
materials.
A water test is recommended before setting tile to verify a successful installation. Wait
24 hours minimum after the membrane installation is complete to allow for final set of
thin-set mortar and ensure waterproof performance at seams and connections. For
curbless showers a temporary dam (e.g., a 2x4 and silicone sealant, plastic sheeting
and sand, etc.) must be provided at the threshold to perform the water test.
Schluter®-Systems profiles may be used to finish and protect outside corners and
eliminate the use of sealant at inside corners.
Schluter®-SHOWERPROFILE-S/-R profiles eliminate the need for cutting wedges of
tile by covering the exposed wall area where the floor slopes to KERDI-LINE.
SHOWER ASSEMBLY
11
WATERPROOFING
Every substrate presents unique challenges
Today’s construction methods, which include the use of lightweight, moisture-sensitive materials, such as plywood, OSB, and gypsum
concrete, have made the installation of hard surface coverings particularly challenging. If wood or gypsum concrete substrates are exposed
to moisture, the tile covering above can be damaged as a result.
Typical areas that require waterproofing include tub surrounds and showers. However, there are other commonly tiled areas that may,
through unexpected circumstances, become exposed to significant amounts of water; for example, an overflowed toilet, or ruptured
dishwasher, icemaker, or washing machine lines, which can result in flooding.
Waterproofing these floors can save an owner from replacing the tile assembly and substructure in the event of a leak.
DITRA-HEAT and DITRA-HEAT-DUO installations can be made waterproof with minimal effort. Since the matting is made of waterproof
polypropylene, the only extra step necessary is to seal the seams and floor/wall connections. This is easily accomplished by applying
KERDI-BAND to these areas using Schluter SET®, Schluter ALL-SET®, Schluter FAST-SET®, or an unmodified thin-set mortar. The result is
a waterproof installation that will not suffer damage in the event of an unexpected water leak. KERDI-DRAIN or KERDI-LINE may be used
to provide drainage in DITRA-HEAT and DITRA-HEAT-DUO installations.
Floors, Interior - Ceramic or Stone Tile
DH-WP-20
Areas of Application
over any even and structurally sound
substrate where waterproofing is desired
Tile or wood base
Ceramic, porcelain
or stone tile
RONDEC
DILEX-EKE
Schluter SET®,
Schluter ALL-SET®,
Schluter FAST-SET®,
or unmodified
thin-set mortar
KERDI-BAND
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
Requirements
all seams in DITRA-HEAT and DITRA-HEATDUO matting and floor/wall transitions must
be sealed with KERDI-BAND using Schluter
SET®, Schluter ALL-SET®, Schluter FASTSET®, or unmodified thin-set mortar.
Note: KERDI-BAND must lap DITRA-HEAT
at seams and at floor/wall transitions by a
minimum of 2" (50 mm) in order to maintain
waterproof integrity
Thin-set mortar
per appropriate
detail
12
WATERPROOFING — Floors, Interior
Other Considerations
seaming DITRA-HEAT and DITRA-HEAT-DUO,
including floor/wall connections, with KERDIBAND may be appropriate in cases where a
break in the water line of an ice maker or
dishwasher can damage pre-existing moisturesensitive substrates and underlayments.
KERDI-BAND floor/wall connections are just as
easily concealed with wood base as with tile.
KERDI-BAND floor/wall connections in
dishwasher alcoves are parged with thin-set
mortar.
in some applications the vertical section of
the floor/wall transition will not accept a bond
to unmodified thin-set mortar. Connections
to such elements can be achieved using
KERDI-FIX or suitable trowel-applied
waterproofing materials, such as those that
require atmospheric moisture to cure (e.g.,
urethane sealant).
KERDI-DRAIN or KERDI-LINE may be used
to provide drainage in DITRA-HEAT and
DITRA-HEAT-DUO applications. DITRAHEAT and DITRA-HEAT-DUO are sealed to
the fleece-laminated KERDI-DRAIN bonding
flange with a section of KERDI membrane
using Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified thin-set
mortar. KERDI-FIX is used to seal the section
of KERDI to the stainless steel KERDI-DRAIN
bonding flange. DITRA-HEAT and DITRAHEAT-DUO are sealed to the KERDI
waterproofing collar on KERDI-LINE using
Schluter SET®, Schluter ALL-SET®, Schluter
FAST-SET®, or unmodified thin-set mortar.
MOVEMENT JOINTS
Every substrate presents unique challenges
DISCUSSION
Movement joints are an integral part of any tile assembly. The various components of a tile
assembly (tile, mortar, substrate, etc.) have unique physical characteristics that affect
their behavior. Specifically, these components will expand and contract at different
rates, according to each component’s intrinsic physical properties, with changes
in moisture, temperature, and loading (both dead and live loads). This differential
expansion/contraction of attached components results in internal stresses.
Furthermore, structures that restrain overall expansion of the tile field (walls, columns,
etc.) cause stress buildup within the system. If the aforementioned movements
are not accommodated through the use of movement joints in the tile field and at
restraining structures, the resulting stresses can cause cracking of the grout and tile
and delamination of the tile from the substrate. Thus, movement joints are an essential
component of any durable tile assembly.
SOLUTIONS
Movement joints must be incorporated within the tile field, at doorsills, and at transitions
to walls and other restraining structures to allow movement of the assembly and prevent
stresses that can damage the system. Schluter®-Systems’ prefabricated movement joint
profiles protect tile edges and prevent sound bridges and surface water penetration,
resulting in a permanent, maintenance-free installation. The family of Schluter®-DILEX
prefabricated movement profiles includes a variety of shapes, sizes, and materials to suit
different applications. Please see Schluter®-Systems’ Illustrated Price List and visit www.
schluter.com for more detailed information on DILEX movement profiles.
TECHNICAL NOTES
The Tile Council of North America (TCNA) and the Terrazzo, Tile, and Marble
Association of Canada (TTMAC) provide guidelines (EJ171 and 301MJ, respectively)
for the placement and construction of movement joints in and around the tile field.
Schluter®-Systems accepts these guidelines. However, given the increased use of larger
tiles, smaller grout joints, and lighter building materials, which are more susceptible to
movement, Schluter®-Systems recommends that movement joints within the tile field be
placed at more frequent intervals, as indicated below.
Guidelines for the placement of movement joints
Applications without heating cables: 16' - 20' (4.9 m - 6.1 m) in each direction
Applications with heating cables or exposed to direct sunlight or moisture:
12' - 16' (3.7 m - 4.9 m) in each direction
Place around the perimeter of any size floor and/or against all restraining surfaces
Fields should be as square as possible. The ratio between length and width should
not exceed 1:1.5.
MOVEMENT JOINTS
13
Typical movement joint applications
1 Schluter®-DILEX-EKE
Perimeter Joints
Perimeter joints are provided at the outer edges of any tile installation to accommodate
movements attributable to changes in moisture, temperature, and loading. See figures
1, 2, and 3.
If Schluter®-DILEX corner movement profiles will not be used, Schluter®-Systems
recommends the use of sill seal (a compressible polyethylene gasket used to seal the
gap between foundations and sill plates) as a quality control measure when providing
perimeter movement joints. The sill seal band is placed against perimeter structures
before any component of the tile assembly is installed, (e.g., DITRA-HEAT, DITRA-HEATDUO, additional underlayments including self-leveling materials, mortar beds, etc. See
figures 2 and 3). After the tile is installed and grouted, any excess sill seal material is cut
away, leaving a movement joint with uniform width that is void of any mortar, grout, or
other restraining materials that would render the joint ineffectual.
2 SILL SEAL BAND
Surface Joints
Surface joints must be placed within the tiled surface regardless of substrate conditions.
They provide for stress relief from movements in the tile field due to thermal and moisture
expansion/contraction and loading. See figure 4.
3 PERIMETER JOINT
Expansion Joints
Drywall
1/4-inch expansion
joint constructed with
sill seal band
Tile
Sealant
Thin-set
mortar
DITRA-HEAT
Subfloor
4 Schluter®-DILEX-BWS
Expansion joints permit both horizontal and vertical differential movements attributable
to thermal and moisture expansion/contraction by providing a complete separation
for the full depth of the slab to allow for free movement between adjoining parts of a
structure or abutting surfaces. They are typically placed at columns, walls, and any
other restraining surfaces. Expansion joints must be continued through the tile covering.
The DITRA-HEAT and DITRA-HEAT-DUO membranes are separated at expansion joints
and the joint is continued through the tile covering using DILEX movement joint profiles.
The DITRA-HEAT-E-HK heating cables must not cross expansion joints. When DITRAHEAT and DITRA-HEAT-DUO are used as waterproofing, the abutted sections must be
covered with KERDI-FLEX or KERDI-BAND.
Cold Joints
Cold (construction) joints occur where two successive placements of concrete meet.
True cold joints bond the new concrete to the old and do not allow movement. However,
it takes extra care to accomplish this, so they are usually designed to act as expansion
or control/contraction joints. Cold joints are treated in the same manner as expansion
joints. See above.
Control/Contraction Joints
Control/contraction joints are designed to induce controlled cracking caused by drying
and chemical shrinkage at preselected locations. They are typically formed by saw
cutting, tooling, or through the use of inserts. DITRA-HEAT and DITRA-HEAT-DUO are
not separated at control/contraction joints; however, surface movement joints must be
provided in the tile covering in accordance with the aforementioned guidelines. See
also Surface Joints.
Structural or Seismic Joints
Regarding structural and seismic expansion joints, please contact Schluter®-Systems at
1-800-472-4588 (USA) or 1-800-667-8746 (Canada) for proper installation guidelines.
14
MOVEMENT JOINTS
Note regarding residential applications
Due to the increased popularity of continuous tile installations (i.e., tile continuing from room to room on a given floor), movement joints
have become both increasingly important and increasingly difficult to provide. For instance, consider the residential installation shown in
Figure 5. It is almost certain that the homeowner will resist the idea of placing movement joints across any of the rooms shown in the figure,
despite TCNA, TTMAC, and Schluter®-Systems guidelines. However, the need for movement joints in this installation is undeniable, given the
extended size of the field. The question then becomes, “How does one provide the movement joints necessary to ensure a durable installation
without compromising the aesthetic qualities of the continuous tile field?”
The easiest way to accomplish this goal is to begin by providing movement joints at the perimeter of the installation. Perimeter joints are
absolutely necessary and do not interrupt the tile field. The next step would be to place movement joints at the thresholds between rooms or
where a tiled hallway meets a larger tiled room. These locations are relatively inconspicuous and the lines formed by the movement joints are
logical in that they reflect the natural perimeter of each room. Finally, determine if any other characteristics of the floor plan invite the placement
of additional movement joints. In this example, the intersection of the nook area and kitchen/family room may be a reasonable choice.
Figure 5
Nook
Kitchen
Family
Room
Study/Office
Living/Dining
Room
Master
Suite
Schluter®-Systems understands that the tile setter must take into account the needs of his or her client in determining the placement
of movement joints in a tile installation. For example, a client may not wish to interrupt a continuous tile field that spans multiple rooms.
However, as indicated by the orange lines above, there are ways to meet industry guidelines that will serve to provide the client with a
durable installation that remains aesthetically pleasing.
MOVEMENT JOINTS
15
WOOD UNDERLAYMENT
Plywood/OSB underlayment installation guidelines
DISCUSSION
In some applications referenced in this Handbook, adding a layer of plywood or OSB before installing DITRA-HEAT and
the ceramic or stone tile covering is required to reduce deflection and curvature of the sheathing between the joists.
INSTALLATION GUIDE
Place underlayment panels (Exposure 1, plugged-face plywood or OSB) with long dimension perpendicular to floor joists
such that the following conditions are met:
1. Abut all underlayment end joints at quarter points between joists.
Example: Abut underlayment panels on either side of the joist centerline at: 4" (102 mm) for 16" (406 mm) o.c. joists,
5" (127 mm) for 19.2" (488 mm) o.c. joists, or 6" (152 mm) for 24" (610 mm) o.c. joists (see figures 1 & 2).
Note: Underlayment end joints should be placed as far away from subfloor end joints as possible.
2. Underlayment to overlap edge joints of subfloor by 1/2 of the width of the subfloor panel (24" - 610 mm). At restraining
surfaces, overlap may be less than 24" (610 mm) when the subfloor panel is less than 48" (1.2 m)-wide (see figure 1).
3. Gap underlayment panels 1/8" (3 mm) on all ends and edges, and 1/4" (6 mm) at perimeter walls, cabinetry, or other
restraining surfaces.
Figures 1 & 2 – Typical Subfloor/Underlayment Detail (Not to Scale)
Figure 1
Figure 2
Plywood/OSB Type and Fastener Schedule Guidelines
Plywood/OSB
Grades
Exposure 1,
plugged-face
plywood or OSB
Plywood/OSB
Thickness - in (mm)
Maximum On-Center Fastener Spacing - in (mm)
Panel Edges
Field
3/8 (10)
4 (102)
6 (152)
1/2 (13)
4 (102)
6 (152)
Greater than 1/2 (13)
6 (152)
6 (152)
The following guidelines must be followed when fastening underlayment panels:
1. Use ring shank nails (no staples) or wood screws (no drywall screws).
2. Fasteners must pass through entire thickness of underlayment and subfloor panels with minimal penetration into
joists (see figure 2).
FINAL WORD
As stated previously, Schluter®-Systems requires that any underlayment panel must have a minimum thickness of 3/8"
(10 mm). When in doubt, increase underlayment thickness.
16
WOOD UNDERLAYMENT
ALTERNATIVE FLOOR COVERINGS
Engineered wood, vinyl, WPC/LVT/LVP, SPC tile/plank, and
laminate flooring over Schluter®-DITRA-HEAT
This section summarizes the requirements, limitations, and general installation guidelines for installing alternative floor coverings over
Schluter®-DITRA-HEAT and Schluter®-DITRA-HEAT-DUO membranes and Schluter®-DITRA-HEAT-E-HK heating cables. It also explains
the limitations of these flooring materials when used over a floor warming substrate compared to ceramic and stone tile. Please use this
section in conjunction with the Schluter®-DITRA-HEAT Installation Handbook to help ensure a successful installation. Table 1 below lists
the various types of alternative floor coverings tested.
The Schluter DITRA-HEAT system was designed for use with ceramic, porcelain, and stone tile coverings. It is important to note the
alternative flooring materials have heat conductivities which are on average 10 times lower than those for ceramic, porcelain and stone.
Also, not all brands and products that fall into the alternative floor coverings types listed in Table 1 are compatible with radiant floor warming.
It is essential to read the floor covering data sheet, or installation instructions, or to verify directly with the manufacturer that
the chosen floor covering is compatible with radiant floor warming and that the temperature limit is at minimum 85°F (29.5°C).
Table 1: Expected Flooring Surface Temperatures and Thickness Requirements for Self-Leveling Underlayment
Floor Covering
Self-Leveler Min. Thickness
Over DITRA-HEAT
Membrane Studs
Thickness
Type
(mm)
Expected
Average Surface
Temperature1, 2, 3
(in)
(mm)
(in)
(°F)
(°C)
SPC (Vinyl-Based LVT/LVP &
Non Vinyl-Based Tile & Plank)*
1/8 – 9/32
3–7
0.25
6
80.5 – 79
27 – 26
Vinyl/WPC/LVT/LVP
1/16 – 5/16
1.5 – 8
0.25
6
80 – 77
26.5 – 25
Engineered Wood
(Adhered)
3/8 – 9/16
5/8 – 3/4
10 – 15
16 – 19
0.25
0.31
6
8
77 – 76
75
25 – 24.5
24
Laminate & Engineered Wood
(Floating)4
9/32 – 19/32
7 – 15
0.25
6
77 – 76
25 – 24.5
Ceramic, Porcelain,
and Stone Tile
1/4 – 1/2
6 – 12.5
N/A
N/A
82
28
Notes
1. T
he temperature values reported above are based on laboratory testing; they can serve as estimates of performance in the field, but cannot predict project-specific results.
2. S
urface temperatures will vary with room temperature; those reported above are based on a thermostat set point of 82°F (28°C) and room temperature of 72°F (22°C).
3. S
urface temperature ranges are reported because results will vary based on floor covering thickness and installation method.
4. For floating laminate flooring and engineered wood, the foam pad or mat used was 3/32" (2.4 mm) in thickness. Expected flooring surface temperatures will be lower with
thicker foam pads or mats.
* Most SPC flooring materials withstand higher sub-floor temperatures than 85°F (29.5°C), please consult with manufacturer's data sheet or installation instructions to determine
how high your choice can be set.
REQUIREMENTS AND LIMITATIONS
Schluter®-DITRA-HEAT is suitable for applications with engineered wood, vinyl, wood plastic composite (WPC), luxury vinyl tiles (LVT),
luxury vinyl planks (LVP), stone plastic composite (SPC) tiles and planks, and laminate flooring, subject to the following requirements and
limitations:
erify with the floor covering manufacturer that the selected product is
V
suitable for radiant floor warming applications and that it can
withstand a temperature of 85°F (29.5°C) at minimum.
If floor covering to be used in a wet area, verify with the floor covering
manufacturer that the selected product is suitable.
The floor covering, including any foam/rubber pad or mat must not
exceed a thermal insulation value of R1 (Rsi of 0.18). All floor
coverings listed in Table 1 have a R-value below 1.
Carpets are generally not recommended, but if installed, they must not
exceed a R-value of 1, including any rubber pad or mat used.
Any floor covering adhesive must be recommended by the manufacturer,
suitable for use over a cementitious substrate, and compatible with
radiant floor warming.
A cementitious self-leveling underlayment is used to fill the
membrane and encapsulate the heating cables. Verify with the
underlayment manufacturer that it is suitable for the application. The
underlayment is applied to a level above the studs in the membrane as
specified in Table 1, according to the type and thickness of the floor
covering. The underlayment should be applied in a single pour.
Any floor leveling must be done prior to the DITRA-HEAT system
installation. Thicker than necessary, or uneven thickness of self-leveling
underlayment above the DITRA-HEAT system will affect performance.
he thermostat must be set at 82°F (28°C) or lower at all times.
T
This can be done manually or by selecting “Laminate Flooring” in the
“Floor Protection” section of the “Installer Settings” menu of any of the
Schluter®-DITRA-HEAT-E thermostats.
If the floor covering is SPC type, the thermostat set point could be set
higher, but verify the limit with the manufacturer's data sheet or installation
instructions.
Solid hardwood is not recommended in floor warming applications due
to its thickness and risk of damage caused by excessive drying of the
wood while exposed to heat.
ALTERNATIVE FLOOR COVERINGS
17
Alternative Floor Coverings
INSTALLATION
The following installation method has been developed and evaluated through a series of tests to ensure practicality and successful
results. This information below is meant to provide the highlights of a typical installation. Please refer to detail DH-AFC and the Schluter®DITRA-HEAT Installation Handbook for complete installation guidelines.
1. P
rovide perimeter joints at the outer edges of the installation to
accommodate movement due to changes in moisture, temperature, and
loading. Sill seal (a polyethylene foam gasket) is an effective quality control
measure to provide perimeter movement joints.
2. Install the DITRA-HEAT or DITRA-HEAT DUO membrane using thin-set
mortar.
3. Test the DITRA-HEAT heating cable(s) prior to installation.
4. Embed the heating cables between studs at continuously alternating
3-2 stud spacing.
5. Install the tip of each floor temperature sensor in the middle of a 2
stud cable spacing section, instead of a 3 stud cable spacing section.
6. Retest the heating cable(s) to verify no damage occurred during the
installation.
7. Fill the membrane and encapsulate the cables with a cementitious selfleveling underlayment. Apply the underlayment to a level according to
Table 1.
8. Once the self-leveling underlayment has set, retest the heating cable(s) to
verify no damage occurred during the installation.
9. A
llow the self-leveling underlayment to cure according to the underlayment
and floor covering manufacturers’ instructions prior to the installation of
the floor covering.
10. Install the floor covering according to the manufacturer’s instructions.
11. Install the DITRA-HEAT-E thermostat in the electrical junction box,
connecting it to the heating cable cold lead and to the electrical power
supply.
12. Start up the floor warming after any waiting period required by the selfleveling underlayment and floor covering manufacturers.
13. The thermostat must be set to “Laminate Flooring” in the “Floor
Protection” section, and to “Floor” in the “Sensor Application”
section, both in the “Installer Settings” menu. The set point
temperature of the thermostat must remain at 82°F (28°C) or below at
all times, unless the floor covering is a SPC type. If an SPC type, verify
with manufacturer's data sheet or installation instructions if the set point
temperature can be raised to a higher level.
Floors, Interior - Engineered Wood, Vinyl,
WPC, LVT/LVP, SPC, and Laminate
DH-AFC-20
Engineered Wood, Vinyl, WPC, LVT/LVP,
SPC, and Laminate
Floor covering adhesive
or foam underlayment,
if required, per manufacturer
Cementitious self-leveling
underlayment
DITRA-HEAT
or DITRA-HEAT-DUO
uncoupling membrane
and heating cables
Thin-set mortar
per appropriate
detail
Areas of Application
over any even and structurally sound
substrate
interior dry or wet areas (verify suitability of
floor covering material for wet areas)
Limitations
ITRA-HEAT-DUO not recommended over
D
hydronic heated floors
withstand temperature for floor covering:
85°F (29.5°C) or greater
maximum thermostat set point 82°F (28°C)
in service, unless floor covering is SPC type
and can withstand a higher temperature
maximum thermal insulation of floor
covering R1
moisture-sensitive floor coverings not
recommended for wet areas
Requirements
floor covering must be recommended for
the application by the manufacturer
DITRA-HEAT-E-HK heating cables spaced
at continuously alternating 3-2 stud pattern
floor temperature sensors must be placed
between heating cables spaced at 2 studs
minimum self-leveling underlayment
elevation over studs 1/4" (6 mm) or 5/16" (8
mm), as per Table 1
Substrate Preparation
in accordance with applicable DITRA-HEAT
Installation Handbook detail and floor
covering manufacturer’s directions
any leveling of the subfloor must be done
prior to installing DITRA-HEAT and DITRAHEAT-DUO
18
ALTERNATIVE FLOOR COVERINGS
Movement Joints
DITRA-HEAT and DITRA-HEAT-DUO do not
eliminate the need for movement joints,
including perimeter joints. Movement joints
must be installed in accordance with
industry standards and floor covering
manufacturer’s directions
Setting Materials
unmodified thin-set mortar – ANSI A118.1
modified thin-set mortar – ANSI A118.11
cementitious self-leveling underlayment –
recommended by SLU manufacturer
Installation Specifications
cementitious self-leveling underlayment –
ASTM F2873 and manufacturer’s directions
floor covering – follow manufacturer’s
directions
Other Considerations
alternative floor coverings have lower
thermal conductivity than ceramic and
stone tile and surface temperatures will be
lower in these applications at the same
thermostat set point; this effect is magnified
as the alternative floor covering thickness is
increased
where a waterproof floor is required, all
DITRA-HEAT and DITRA-HEAT-DUO seams
and floor/wall transitions must be sealed
with KERDI-BAND using Schluter SET®,
Schluter ALL-SET®, Schluter FAST-SET®, or
unmodified thin-set mortar; see DH-WP in
the DITRA-HEAT Installation Handbook
vapor barrier on crawl space floors
according to regional building codes
INSTALLATION
Schluter®-DITRA-HEAT membrane and heating cables
Planning
For access to the DITRA-HEAT Calculation Sheet and DITRA-HEAT Online Estimator, see www.schluter.com.
• Select DITRA-HEAT and DITRA-HEAT-DUO membrane according to the size of the area to be tiled.
• Select DITRA-HEAT-E-HK heating cable(s) according to the size of the area to be heated and the cable spacing in the DITRA-HEAT membranes (See table entitled HEATING CABLE
SPECIFICATION on page 26 for more details):
• Cable spaced at 3 studs apart is standard
• Cable may also be spaced at continuously alternating 3 stud - 2 stud intervals in isolated areas or over the entire floor. This practice may be desirable to increase heat output
(e.g., over uninsulated on or below grade concrete subfloors) or to consume more cable length in a given area (e.g., when using the standard 3 stud spacing doesn't allow the
selected cable to fit the floor area and respect minimum spacing requirements from walls, partitions, etc.)
• Cable spacing of 4 studs is not recommended, as it can produce inconsistent floor surface temperatures
• For alternative floor coverings (other than ceramic, porcelain and stone tiles) please refer to section entitled "Alternative Floor Coverings" on page 17 for details
• When measuring the area to be heated, be sure to measure accurately. The heating cable CANNOT be cut to fit. The allowable heated area is limited by the minimum required spacing
from fixed elements such as:
• Walls, partitions, and fixed cabinets = 2" (50 mm)
• Heat sources (baseboard heaters or other fixed heating devices, fireplaces, etc.) = 8" (200 mm)
• Forced air heating vents = 4" (100 mm)
• Centerline of toilet drains = 7" (180 mm)
• Drain pipe = 4" (100 mm). With a linear drain, the cable must be 4" (100 mm) from the actual drain pipe and a minimum of 1" (25 mm) from the channel body edges.
• It is helpful to plan the location of a buffer zone, as it is not possible to predict exactly where the heating cable will end. The buffer zone is an area where floor warming is not essential and
heating cable installation is not planned (e.g., behind a toilet or adjacent to a door opening). This area allows for placement of excess heating cable. Heating cables may also be installed 6"
(150 mm) from the wall to create a buffer zone.
• In the case where there is no space left in the buffer zone(s) and there is excess cable, a continuously alternating 3 stud and 2 stud spacing (i.e. 3-2-3-2) between cable runs may be used.
The following must be maintained:
• The minimum spacing from fixed elements mentioned above
• Do NOT install heating cable with a repeating 2 stud spacing or narrower spacing anywhere on the floor
• Not following the above limitations may cause cable overheating and cable malfunction
Note : The areas with 3-2-3 will be noticeably warmer in some cases and the installer should discuss the location of this with the homeowner.
• For more information on installing DITRA-HEAT-E-HK heating cables on 208 V circuits, please see page 33.
• Multiple DITRA-HEAT-E-HK heating cables can be connected and controlled by a single DITRA-HEAT-E thermostat, if the total current is less than 15 amps. The junction box must be sized
according to the electrical code effective in your region, and must consider the possible use of pigtails and the space occupied by the back part of the thermostat.
• Multiple DITRA-HEAT-E-HK heating cables over 15 amps cannot be connected to a single DITRA-HEAT-E thermostat. Additional DITRA-HEAT-E thermostats must be used, or a DITRAHEAT-E thermostat may be combined with the DITRA-HEAT-E-RR power modules.
Preparation
• The substrate must be clean, even, and load bearing. Any leveling of the subfloor must be done prior to installing DITRA-HEAT and DITRA-HEAT-DUO.
• For wood substrates, verify that panels are properly fastened. Tightly butted and/or tented plywood or OSB seams must be addressed prior to installing DITRA-HEAT and DITRA-HEAT-DUO.
If a plywood/OSB underlayment is to be installed, follow the Wood Underlayment guidelines on page 16.
• For vinyl substrates, ensure that the structure beneath is sound and adequate and that the vinyl is well adhered. Remove any wax and clean the surface. For vinyl over wood structures,
nail off floor with ring shank flooring nails every 4" (102 mm) o.c. - fasteners must pass through entire thickness of assembly with minimal penetration into joists.
• For concrete substrates, remove any waxy or oily films and curing compounds (if present) by mechanical scarification. When bonding DITRA-HEAT and DITRA-HEAT-DUO to particularly
dry, porous concrete, the slab should be moistened to saturate the concrete and help prevent premature drying or skinning of the bond coat. Excess or standing surface water must be
removed prior to installation.
• For gypsum substrates, residual moisture in gypsum screed must be 2.0% or less before installing DITRA-HEAT and DITRA-HEAT-DUO. Follow gypsum manufacturer’s directions for
additional substrate preparation.
Membrane
1
Using a thin-set mortar that is suitable for the substrate,
apply the thin-set mortar (mixed to a fairly fluid consistency,
but still able to hold a notch) using the DITRA-HEAT
trowel, or other 1/4" x 1/4" (6 mm x 6 mm) squarenotched trowel.
2
Apply DITRA-HEAT or DITRA-HEAT-DUO to the
floor, fleece side down. Solidly embed the matting
into the mortar using a float, screed trowel, or
DITRA-ROLLER, making sure to observe the open time of
the bonding mortar. If the mortar skins over prior to matting
installation, remove and reapply. Note: It may be helpful to
back roll the DITRA-HEAT matting before installation to help
the membrane to lay flat.
To bond the tile to the DITRA-HEAT, using a
1/4" x 3/8" (6 mm x 10 mm) square- or
U-notched trowel: Use one 50 lb (22.68 kg) bag
of mortar per 40 - 50 ft2 (3.7 - 4.6 m2).
DITRA-HEAT-DUO
Lift up a corner of the matting to check coverage. Proper
installation results in full contact between the fleece webbing
and the thin-set mortar. DITRA-HEAT-DUO fleece may not
pull up as much mortar from the floor as DITRA-HEAT when
lifted, but full contact can be achieved as shown. Note:
Coverage may vary with mortar consistency, angle at which
the trowel is held, substrate flatness, etc. If full coverage
is not achieved, remove and reapply, making sure to verify
proper mortar consistency and application.
ESTIMATED THIN-SET COVERAGE
To bond DITRA-HEAT and DITRA-HEAT-DUO
to the substrate, using the DITRA-HEAT
trowel, or other 1/4" x 1/4" (6 mm x 6 mm)
square-notched trowel:
Use one 50 lb. (22.68 kg) bag of mortar per
100 ft2 (9.3 m2).
DITRA-HEAT
3
When using the DITRA-ROLLER, place a weight (e.g., bags of
mortar/grout or box of tile) not to exceed 75 lbs on the DITRAROLLER shelf. Slowly move the roller from one end of the matting
to the other, slightly overlapping successive passes.
4
Abut end and side sections of adjacent sheets. Note: Aligning
the studs on the top of the matting during installation can help
make subsequent heating cable installation easier.
To bond the tile to the DITRA-HEAT, using a 1/2"
x 1/2" (13 mm x 13 mm) square- or U-notched
trowel: Use one 50 lb (22.68 kg) bag of mortar
per 30 - 40 ft2 (2.8 - 3.7 m2).
INSTALLATION
19
Heating Cables Installation
Warning Details
• Before installing and operating this product, the user and/or installer must read, understand and follow these instructions and keep them handy for future reference.
If you have a question, please contact Customer Service by phone 800-472-4588 (USA) or 800-667-8746 (Canada) or from our website at www.schluter.com.
• If these instructions are not followed, the warranty will be considered null and void and the manufacturer deems no further responsibility for this product.
• The following instructions must be adhered to in order to avoid personal injuries or property damages, including serious injuries and potentially fatal electric
shocks or fire.
• This product must be installed by a qualified person in accordance with this installation handbook and with the Canadian Electric Code Part I (Canada) or the
National Electric Code (U.S.) as applicable. All electric connections must be made by a qualified person, according to the electrical and building codes effective
in your region.
• De-energize all power circuits before installation and servicing.
• A dedicated circuit is recommended for each application, but a circuit supplying one or more fixed room heaters may be used, as long as its rating does not exceed 30 amperes,
that the total current from all branch circuits does not exceed 80% of the circuit breaker limit, and the branch circuit cable reaching the thermostat junction box is of the same
conductor size as the main circuit.
• A Class A (5 mA) ground fault circuit interrupter (GFCI) is required for each circuit. The DITRA-HEAT-E thermostats include a GFCI, thus a GFCI circuit breaker is not required when
using these thermostats.
• NEVER install a cable designed for a 120 V power source on a 240/208 V power source.
• The heating cable ground braid must be bonded to ground.
• For installations requiring a cold lead trim or splice, the electrical rating label shall be fixed to the cold lead and visible at the termination junction box. Removing the label will void
the warranty.
• Never CUT or modify the heating cable in any way. This would change the cable resistance, will cause damage to the cable, and could cause cable overheating.
• The type and thickness of floor covering materials used with this product must not exceed a thermal insulation “R” value of 1. Example “R” Values: Ceramic/Mosaic tile 0.25"
thick = R0.15, Natural stone 1" thick = R0.38-0.114, Porcelain Tile 0.25" thick = R0.024. Vinyl/LVT/LVP/WPC/SPC 0.25" thick = R0.4, Engineered Wood (glued) 0.5" thick = R0.25,
Engineered Wood (floating) 0.5" thick + 1/8" padding = R0.5, Laminate Flooring 0.38" thick + 1/8" padding = R0.62
• Heating cables shall not be altered in the field. If the installer or the user modifies the unit, he will be held responsible for any damage resulting from this modification, and the
warranty and the product certification will be void.
• Heating cables may not touch, cross over, or overlap one another or itself.
• The heating section of the cable and the factory splice (i.e., black plastic junction between the cold lead and gray heating cable) must be entirely installed under the floor covering,
and into a mortar or thin-set layer, as shown in the heating cable installation instructions. Do not install it in a wall, or anywhere else, as this may cause overheating and system failure.
• Threading the cold lead from the floor to the thermostat junction box needs to be done within an approved raceway or conduit. The conduit is required to begin at no greater than
2 inches (50 mm) from the floor. The opening in the horizontal stud at the base of the wall, which provides access for the cold lead to the inside of the wall, shall be covered by a
steel plate to protect the cold lead from any possible future damages from nails or screws.
• The temperature sensors need to be threaded either inside the same conduit as the cold lead, or in a separate conduit.
• Do not run the heating section of the heating cable set under or through a wall, partition, or through a floor.
• Do not install the heating cable on a wall (e.g., shower wall, inside of a built-in bathtub, etc.).
• In the USA, according to Rule 424.38 (A) of the National Electrical Code 2017, heating cables may extend beyond the room in which they originate. In previous editions of the
National Electrical Code (NEC), extending heating cables beyond the room was not permitted. Please verify with your local inspector to determine which edition of the NEC is being
enforced by the local Authority Having Jurisdiction (AHJ). Also, please verify approval of your cable layout prior to setting tile. Additionally, installations of heating cables in dressing
rooms or large walk-in closets are subject to approval by the local AHJ.
• In Canada, according to Rule 62-202 of the Canadian Electrical Code 2018, a thermostat or an applicable temperature control device is required for each enclosed area where a
heating cable is installed. As necessary, please verify your installation plan with local inspector to determine their interpretation of the rule, and whether or not your cable layout
is approved prior to setting tile.
• NEVER install the heating cable under vanities with no air space beneath, bathtub platforms, free standing bathtubs with no air space beneath, kitchen cabinets and islands,
appliances, or any other fixtures, or in small storage or clothing closets where there is or could have various items on the floor. Excessive heat will build up in these confined spaces
and may cause cable overheating.
• NEVER use the heating cable for any purpose other than for indoor floor warming as explained in this Handbook.
• Cable spacing shall be limited to a repeating 3 stud (3.6" or 9.1 cm) spacing, or a continuously alternating 3 stud (3.6" or 9.1 cm) and 2 stud (2.4" or 6.1 cm) spacing (i.e.: 3-23-2-3-2 and so on) between cable runs. A repeating 2 stud spacing or narrower spacing shall not be used as it may cause overheating and cable malfunction. A wider spacing
(e.g., 4 studs) may not provide sufficient power to warm the floor to the desired temperature, and may cause inconsistent floor surface temperatures. Exception: a continuous 2
stud spacing is recommended when connecting a 240 V heating cable to a 208 V power supply. See page 33 for more information.
• Minimum spacing from walls, partitions, and fixed cabinets is 2" (50 mm).
• Minimum spacing from other heat sources (baseboard heaters and other fixed heating devices, fireplaces, etc.) is 8" (200 mm).
• Minimum spacing from any forced air heating vents is 4" (100 mm).
• Minimum spacing from the centerline of toilet drain is 7" (180 mm).
• The minimum spacing from any drain pipe must be 4" (100 mm). With a linear drain, the cable must be 4" (100 mm) from the actual drain pipe and a minimum of 1" (25 mm) from
the channel body edges.
• The maximum allowable straight length of a single run of heating cable is 10 ft (3 m); the cable must be turned and go in the other direction, or form u-shaped "jog" at this point
as in Photo 5b on page 22. This is to take into account the expansion of the metallic hot conductors of the heating cable while heating.
• The minimum temperature at which the cable should be installed is 32° F (0° C).
• Avoid folding the heating cable on itself, a radius of curvature less than 1/16 inch (1.6 mm) could damage its sheath.
• The minimum installed bending radius of the heating cable is 0.5 inches (12.7 mm).
• NEVER energize the cable while it is on the spool. This would lead to overheating that could damage the cable.
Heating Cables Installation
• DITRA-HEAT is primarily intended to warm tile floors and make them more comfortable underfoot, but can contribute to space heating. See page 34 for space heating guidelines.
• It is helpful to plan the location of a buffer zone, as it is not possible to predict where the heating cable will end. The buffer zone is an area where heating is not essential and heating
cable installation is not planned (e.g., behind a toilet or adjacent to a door opening). This area allows for placement of excess heating cable. Heating cables may also be installed
6" (150 mm) from the wall to create a buffer zone.
• Mark the circuit breaker in the electrical panel that is connected to the DITRA-HEAT floor warming system using the identification sticker provided. Additional stickers provided may
be placed on the electrical panel door.
• Install the two thermostat floor temperature sensors within the tile assembly. Two floor temperature sensors are provided - one with the DITRA-HEAT thermostats and one with
the DITRA-HEAT-E-HK heating cables. Install the tip of each temperature sensor in the middle of the three stud spacing cable runs, no matter if the standard 3 stud cable spacing
or the continuously alternating 3-2 stud cable spacing option has been used. Connect only one to the thermostat and the other is a spare in case one is broken during overall
installation. The floor temperature sensors need to be threaded either inside the same conduit as the cold lead, or in a separate conduit.
• Heating cable testing is required while the heating cable is on the spool and at two subsequent steps during installation to ensure cable quality and for warranty purposes.
• If a break or damage is detected during the heating cable testing while the heating cable is on the spool, return the cable to the original place of purchase. Do not proceed with
heating cable installation into the DITRA-HEAT or DITRA-HEAT-DUO matting or with the tile covering installation.
20
INSTALLATION
i
To avoid damaging the DITRA-HEAT-E-HK heating cable spool due to handling, we recommend turning the box over to
remove the spool from the packaging box. Then pick up the spool from underneath the heating cable coil, but not by the
cardboard washers.
Heating Cable Tests
The following table outlines DITRA-HEAT system warranty coverage based on which heating cable tests are conducted, documented,
and submitted to Schluter. Please refer to the Heating Cable Tests Log on page 36 of this Handbook and Warranty on page 40 of this
Handbook for further information.
Tests Conducted
Term
Resolution
Test 1: Conductor Resistance
+
Test 2: Continuity between Conductor and Ground Braid
+
Test 3: Insulation Resistance
+
Test 4: Thermostat Floor Temperature Sensor
15 years
Assembly repair or replacement (labor & materials)
Test 1: Conductor Resistance
+
Test 2: Continuity between Conductor and Ground Braid
+
Test 4: Thermostat Floor Temperature Sensor
10 years
Assembly repair or replacement (labor & materials)
No Heating Cable Testing
Conducted
No heating cable warranty coverage; Only 10 year warranty
coverage on the DITRA-HEAT or DITRA-HEAT-DUO membrane.
Test 1: Conductor resistance (required)
In order to perform the resistance test, you must set your multimeter for resistance
measurement and take an ohms reading between the two power leads. If the ohms reading
taken on the two power leads varies significantly (10% or more) from the value printed on the
spool, it either means that the cable has been damaged, or that the measuring instrument is
not set properly, or that it is simply out of calibration. The ohms measurement must be recorded
in your heating cable tests log (page 36).
Test 2: Conductor and ground braid continuity (required)
The heating cable is protected by a ground braid. An electrical insulator prevents any contact
between the braid and the two conductors. To make sure there is no contact between the
braid and the two conductors, you must perform a continuity test. Using the continuity test
(buzzer logo) function of your multimeter, test your cable between the braid and one of the
two power leads. If there is no continuity (if the test is successful), the multimeter will display,
depending on the instrument used, either “OL ” for “over load” or “I” for “infinity”. Otherwise,
if the test fails, neither “OL ”, nor “I” will be displayed and a warning tone will be heard. The
test result must be recorded in your heating cable tests log (page 36).
Test 3: Insulation resistance (recommended)
This test is meant to detect very small breaks throughout the cable insulation. These breaks
often remain undetected during the continuity test since they are not necessarily short circuits
between the conductor and the ground braid. Even though they are small, these breaks
are likely to cause a current leakage to ground. Such a leakage is usually detected by the
mandatory ground-fault circuit interrupter “GFCI” (thermostat with integrated GFCI or panel
mount GFCI). When a current leakage is detected, the GFCI trips the circuit, thus disabling
the floor heating system. In order to perform the insulation resistance test, you must, using
a megohmmeter (Mohm logo), take an insulation measurement between the braid and one
of the two power leads. Make sure the megohmmeter range is set at 1000 V. The insulation
resistance measurement must be equal to or greater than 1 Gigaohms (1 Gigaohms = 1 G
ohms = 1000 M ohms = 1000 Mega ohms). The insulation resistance measurement must be
recorded in your heating cable tests log (page 36).
Test 4: DITRA-HEAT Thermostat Floor Temperature Sensor Test (required)
Test the floor temperature sensors using a multimeter to verify accuracy of the sensors. Set the
multimeter to the resistance setting (i.e., Ω or 20K Ω +/-2, as applicable) at room temperature
and take a reading between the sensor leads. The resistance will vary according to the
temperature (i.e., the colder the sensor, the higher the resistance). Compare values with the
table of expected values and record in the heating cable tests log on page 36.
INSTALLATION 21
Installation
Check to ensure the heating cable(s) purchased match the power supply (i.e., 120 V with 120 V or 240 V with 240 V, or 240 V with 208 V). Check to ensure you are
not exceeding the 15 amp limit of the thermostat. Compare the purchased cable area to the floor area to be heated. Important: The cable area purchased should be
as close to the heated area as possible, without going over. The heating cable CANNOT be trimmed or shortened to fit.
It is recommended that the installation of the DITRA-HEAT system is photographed (e.g., heating cable layout, floor temperature sensor placements, transition splice
location, end splice location, and wide view of the room) for reference with future renovation work and troubleshooting. The homeowner/end user should retain these
photos for their records.
1
4
Before the heating cable is removed from the spool,
conduct the first set of required tests and record values
in the heating cable tests log (page 36). If a break or
damage is detected during the tests, return the heating
cable to the original place of purchase.
Embed the heating cables between studs, at a spacing
determined in the Planning section on page 19.
A repeating 2 stud or narrower spacing shall not be used
as it may cause overheating and cable malfunction.
Exception: A two-stud spacing is used when connecting
a 240 V cable to a 208 V power supply. See page 33
for more information.
A wider spacing (e.g., 4 studs) will not provide sufficient
power to warm the floor to the desired temperature.
2
5
Thread the heating cable cold lead through a conduit
from the base of the wall to the thermostat electrical
box. Floor temperature sensors need to be threaded
through the same conduit containing the cold lead, or
within a separate conduit.
Thermostat to Power Module Connection
The signal wire used to connect the DITRA-HEAT-E
thermostats with DITRA-HEAT-E-RR power modules
must be 300 volt rated and does not need to be in a
conduit, if it has a proper flame rating (e.g., CM, CMG,
CMR, CMP, CL2, CL3, CL2R, CL3R, CL2P, CL3P, FT1,
FT4, or FT6).
Use care not to damage the cables during installation,
particularly before the cables are embedded in the
matting.
3
Mark where the cold/hot splice will be placed, cut the
DITRA-HEAT or DITRA-HEAT-DUO matting and subfloor
(if needed to accommodate the thickness of the splice),
and insert the splice. It may be necessary to temporarily
secure the splice to the floor with thin-set mortar or
adhesive (e.g., KERDI-FIX or hot glue).
Once the heating cable cold lead and remote sensors
are threaded to the thermostat electrical box, install a
metal protection plate at the base of the wall. This will
help prevent any damage from fasteners (e.g., nails,
screws, etc.) in the future.
The maximum allowable length of a single run is 10 ft (3 m); the
cable must be turned or a u-shaped "jog" created at this point
(see image above).
Notes:
• Make sure to leave space for inserting the floor temperature sensors.
• Heating cables may not touch, cross over, or overlap one another or itself.
• Minimum spacing from:
• Walls, partitions, and fixed cabinets is 2" (50 mm)
• Forced air heating vents is 4" (100 mm)
• Centerline of toilet drain is 7" (180 mm)
• Drain pipe is 4" (100 mm). For the linear drain, the cable must be 4" (100 mm) from the actual drain pipe and a minimum of 1" (25 mm) from the channel body edges.
• Other heating sources (baseboard heaters and other fixed heating devices, fireplaces, etc.) is 8" (200 mm)
6
Two sensors must be installed in the floor assembly. We recommend installing each of the thermostat sensors at a different
location on the floor, evenly spaced between two cable runs, and ideally towards the middle of the heating cable layout.
However, a minimum of 12" (305 mm) into the cable layout is recommended to obtain satisfactory temperature readings.
When continuously alternating 3-2 stud spacing is used, install the thermostat sensors in the middle of a 3 stud cable spacing
section when flooring material is ceramic, porcelain or stone tiles. When AFC's (see AFC section on page 17) are used, install
temperature sensors in the middle of a 2 stud cable spacing section. Mark the sensor location on the DITRA-HEAT and cut
the matting to recess the sensor. It is recommended to temporarily remove the heating cable from the area while cutting the
matting. It may be necessary to temporarily secure the sensor to the floor with thin-set mortar or adhesive (e.g., KERDI-FIX or
hot glue). Embed the sensor wire in the matting without overlapping or crossing the heating cable.
7
Once the heating cable and floor temperature
sensor installation is complete, retest and record
values in the heating cable tests log (page 36).
Extending the heating cable cold lead
The cold lead is made up of two 14 AWG conductors with a copper braided shield, that is used as the grounding conductor. The extension must be made with building wire that is suitable
for this application and complies with applicable building and electrical codes. The cold lead itself is not made of building wire and therefore cannot pass through studs unless run through a
conduit. Extension of the cold lead requires the addition of a “code compliant” junction box that must be accessible at all times. The maximum length for extending the cold lead is 75 ft (23 m).
Extending the floor temperature sensor
The floor temperature sensor can be extended using an 18 AWG, 2-wire cable. The sensor wire itself is not made of building wire and therefore cannot pass through studs unless run through
a conduit. We recommend twisting and soldering the wires and using electrical tape to insulate them. There is no maximum length that is recommended, however the longer the extension the
greater the possibility that the quality of the signal (and resulting temperature sensing) will be skewed. Regardless of the method used, the resulting splice must comply with applicable building
and electrical codes. A loose connection between the extension and the sensor will result in a false reading or an error code.
22
INSTALLATION
Waterproofing
The following steps are required for waterproofing only:
Note: While the heating cable is protected by the DITRA-HEAT and DITRA-HEAT-DUO matting, be careful when applying the mortar to not
damage the cable with the notched trowel.
joints, fill the matting with Schluter
1 At the
®
®
SET , Schluter ALL-SET , Schluter FASTSET®, or unmodified thin-set mortar,
approximately 8" (203 mm) wide, centered
over the joint.
4 At all wall junctions, apply KERDI-BAND as
described in steps 1-3, centered where the
wall and floor meet. In some applications
the vertical section of the floor/wall transition
will not accept a bond to unmodified
thin-set mortar. Connections to such
elements can be achieved using KERDI-FIX
sealant and bonding compound or suitable
trowel-applied waterproofing materials, such
as those that require atmospheric moisture
to cure (e.g., urethane sealant).
2 Comb
additional
Schluter
SET ®,
Schluter ALL-SET®, Schluter FASTSET®, or unmodified thin-set mortar
over the joint using a 1/4" x 3/16"
(6 mm x 5 mm) V-notched trowel or the
KERDI-TROWEL, which features a 1/8" x
1/8" (3 mm x 3 mm) square-notched design.
3 Apply 5" (127 mm)-wide KERDI-BAND,
centered over the joint. Using the flat side
of the trowel, firmly press the banding into
the mortar to ensure 100% coverage and to
remove excess mortar and air pockets.
Note: KERDI-BAND must lap DITRA-HEAT and DITRA-HEAT-DUO at seams and at floor/wall
transitions by a minimum of 2" (50 mm) in order to maintain waterproof integrity.
INSTALLATION 23
Tiles
Note: While the heating cable is protected by the DITRA-HEAT and DITRA-HEAT-DUO matting, be careful when applying the mortar to not
damage the cable with the notched trowel.
1 Tile can be installed over DITRA-HEAT and
DITRA-HEAT-DUO immediately; no need to
wait for the mortar to cure. Fill the matting
with Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified thin-set
mortar and comb additional mortar over the
matting using a trowel that is appropriate for
the size of the tile.
2 Solidly embed the tiles in the setting material,
making sure to observe the open time of the
bonding mortar. If the mortar skins over prior
to tile installation, remove and reapply.
3 Periodically remove and check a tile to
ensure that full coverage is being attained.
Note: Coverage may vary with mortar consistency, angle at which the trowel is held, substrate flatness, etc. If full coverage is not achieved, remove
and reapply, making sure to verify proper mortar consistency and application. For large-format tiles, e.g., 12" x 12" (305 mm x 305 mm) and larger,
back-buttering the tiles with a skim coat of thin-set mortar is a useful way to help ensure proper coverage. The skim coat can fill in the concave area on
the back of the tile (ceramic tiles are not perfectly flat) and improve contact with the mortar combed on the substrate.
ESTIMATED THIN-SET COVERAGE
To bond DITRA-HEAT and DITRA-HEAT-DUO to the substrate, using the DITRA-HEAT trowel,
or other 1/4" x 1/4" (6 mm x 6 mm) square-notched trowel:
Use one 50 lb. (22.68 kg) bag of mortar per 100 ft2 (9.3 m2).
To bond the tile to the DITRA-HEAT, using a 1/4" x 3/8" (6 mm x 10 mm) square- or U-notched trowel:
Use one 50 lb (22.68 kg) bag of mortar per 40 - 50 ft2 (3.7 - 4.6 m2).
To bond the tile to the DITRA-HEAT, using a 1/2" x 1/2" (13 mm x 13 mm) square- or U-notched trowel:
Use one 50 lb (22.68 kg) bag of mortar per 30 - 40 ft2 (2.8 - 3.7 m2).
4 Once the tile installation is complete, retest
the heating cable and record values in the
heating cable tests log (page 36).
Allow the assembly to cure for 7 days after
grouting before putting the floor warming
into service.
Operating Tips
• Do not place furniture or mats over the floor temperature sensor. They can act as insulation and raise the floor temperature reading at the thermostat.
This may cause the heating to turn off before the remainder of the floor reaches the desired temperature.
• Area rugs are not recommended over the DITRA-HEAT system, but if used, they shall have an insulating R-value not greater than 1 (Rsi not greater than
0.18). The area rugs shall not be located on top of where the floor temperature sensor is placed, as it will otherwise reduce the heat efficiency.
• Futons, mattresses, floor-level furniture, pillows, etc. must not be placed directly onto the heated floor. Placement of items directly onto the heated floor
will prevent heat diffusion (i.e., air circulation) and could result in damage.
24
INSTALLATION
THIN-SET FACTS
Discussion of thin-set mortars and Schluter®-DITRA-HEAT installations
Schluter®-Systems offers thin-set mortars designed for use with Schluter® membranes and boards. All Schluter®-Systems’ thin-set mortars,
including the Schluter ALL-SET® and Schluter FAST-SET® modified varieties, can be used to set tile over Schluter®-DITRA, DITRA-HEAT,
KERDI, KERDI-BOARD non absorptive substrates. If Schluter® thin-set mortars are not used, we require unmodified thin-set mortar when
setting ceramic or porcelain tile over DITRA-HEAT.
QUESTION: Can ceramic tile, including porcelain tile, be set on DITRA-HEAT with unmodified thin-set mortar?
ANSWER: YES. In fact, we recommend it. Here’s why:
Portland cement-based unmodified thin-set mortars are dependent on the presence of moisture for hydration in order to gain strength. Since
DITRA-HEAT is impervious, it does not deprive the mortar of its moisture. This allows the cement to properly hydrate, resulting in a strong,
dense bond coat. In fact, after the mortar has reached final set (usually within 24 hours), unmodified thin-set mortars achieve higher strengths
when cured in continually moist conditions.
QUESTION: Can ceramic tile, including porcelain tile, be set on DITRA-HEAT with latex-modified thin-set mortar?
ANSWER: In general, we DON'T recommend it. Here’s why:
Latex-modified mortars must dry for the polymers to coalesce and form a hard film in order to gain strength. When sandwiched between two
impervious materials such as DITRA-HEAT and ceramic tile, including porcelain tile, drying takes place very slowly through the open joints in
the tile covering. [According to the TCNA Handbook for Ceramic, Glass, and Stone Tile Installation, this drying period can fluctuate from 14
days to over 60 days, depending on the geographic location, the climatic conditions, etc.]. Therefore, extended cure times could be required
before grouting if using modified thin-set mortars between DITRA-HEAT and ceramic tile, including porcelain tile. If extended cure times were
not observed, the results could be unpredictable.
QUESTION: Can Schluter ALL-SET® and Schluter FAST-SET® modified thin-set mortars be used to set tile over Schluter boards
and membranes?
ANSWER: Yes.
All Schluter® thin-set mortars, including the Schluter ALL-SET® and Schluter FAST-SET® modified varieties can be used to set tile over DITRA,
DITRA-HEAT, KERDI, KERDI-BOARD, etc. non absorptive substrates.
QUESTION: How is this possible?
ANSWER: The key is predictability.
Schluter Systems’ modified thin-set mortars have been specifically formulated to set and gain strength in a timeframe that fits typical
installation practice, even when sandwiched between Schluter® membranes or boards and porcelain tile. The proportions of cement, waterretention agents, polymers, and other components in the mixtures were balanced to ensure that extended dry times are not required. This
was validated through both laboratory and practical testing. Now, the installer can select from either unmodified or modified thin-set mortar
to install tiles within our systems according to his or her preference.
QUESTION: Why did Schluter Systems change its position on thin-set mortar?
ANSWER: We haven’t changed our position on thin-set mortar use within our systems.
Developing our own setting materials has given us the ability to guarantee consistently positive results. And since we control the formulas,
we can be sure no changes will be made that have a negative impact on setting times and strength gain in these environments.
QUESTION: Does this mean I can use other manufacturers’ modified thin-set mortars to install tile over Schluter boards and
membranes?
ANSWER: No.
Our position on thin-set mortar use within our systems in general has not changed. We have no control over the formulation of other
manufacturers’ products and therefore cannot guarantee consistently positive results with their modified thin-set mortars.
QUESTION: Can I still use other manufacturers’ unmodified thin-set mortars to install tile over Schluter boards and membranes?
ANSWER: Yes.
We still warrant the use of unmodified thin-set mortar meeting ANSI A118.1 to install tile within our systems because we have confidence in
the performance of this product category. This is based on the science of cement hydration and years of positive testing and field experience.
Please note, if Schluter® thin-set mortars are used with Schluter membranes an extended system warranty is available.
ADDITIONAL NOTES
Pre-mixed thin-set mortars and mastics are not suitable for use in conjuction with DITRA-HEAT and DITRA-HEAT-DUO.
Remember, the type of mortar used to apply DITRA-HEAT depends on the type of substrate. The mortar must bond to the substrate and
mechanically anchor the fleece on the underside of the DITRA-HEAT. For example, bonding DITRA-HEAT to wood requires latex-modified thinset mortar. When bonding DITRA-HEAT to particularly dry, porous concrete with unmodified thin-set mortar, the slab should be moistened to
saturate the concrete and help prevent premature drying of the mortar. Excess or standing surface water must be removed prior to installation.
Additionally, all mortars (modified and unmodified) have an acceptable temperature range that must be observed during application and curing.
THIN-SET FACTS
25
HEATING CABLE SPECIFICATION
Schluter®-DITRA-HEAT-E-HK
DITRA-HEAT-E-HK are twisted pair heating cables designed for integration with the DITRA-HEAT and DITRA-HEAT-DUO uncoupling
membranes in interior floor warming applications.
Item No.
Heating Cable (120 V)
DHE HK 120 11
DHE HK 120 16
DHE HK 120 21
DHE HK 120 27
DHE HK 120 32
DHE HK 120 38
DHE HK 120 43
DHE HK 120 51
DHE HK 120 64
DHE HK 120 73
DHE HK 120 83
DHE HK 120 92
DHE HK 120 102
DHE HK 120 113
DHE HK 120 134
Heating Cable (240 V)
DHE HK 240 11
DHE HK 240 16
DHE HK 240 21
DHE HK 240 27
DHE HK 240 32
DHE HK 240 38
DHE HK 240 43
DHE HK 240 53
DHE
DHE
DHE
DHE
DHE
DHE
DHE
DHE
DHE
DHE
HK
HK
HK
HK
HK
HK
HK
HK
HK
HK
240
240
240
240
240
240
240
240
240
240
64
75
85
103
129
145
167
183
204
225
Heating Cable
Length
Area Covered per Cable Spacing
Regular 3 Stud
(m2)
(ft2)
Alternating 3-2 Stud
(ft2)
(m2)
Total
Power
Avg. Power per Unit Area per Cable Spacing
Regular 3 Stud
Current
Alternating 3-2 Stud
(W)
(Watts/ft2)
(Watts/m2)
(Watts/ft2)
(Watts/m2)
(Amps)
0.8
1.2
1.7
2.1
2.5
2.9
3.3
4.0
5.0
5.6
6.5
7.1
7.9
8.7
10.4
135
203
270
338
405
475
540
650
815
920
1055
1160
1290
1425
1700
12.6
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
136
136
136
136
136
136
136
136
136
136
136
136
136
136
136
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
164
164
164
164
164
164
164
164
164
164
164
164
164
164
164
1.1
1.7
2.3
2.8
3.4
4.0
4.5
5.4
6.8
7.7
8.8
9.7
10.7
11.9
14.2
8.9
13.4
17.8
22.2
26.7
31.3
35.5
44.4
0.8
1.2
1.7
2.1
2.5
2.9
3.3
4.1
135
203
270
338
405
475
540
675
12.6
12.6
12.7
12.7
12.7
12.7
12.7
12.7
136
136
136
136
136
136
136
136
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
164
164
164
164
164
164
164
164
0.6
0.8
1.1
1.4
1.7
2.0
2.3
2.8
53.3
62.6
71.1
85.6
107.3
121.1
138.9
152.7
169.9
187.7
5.0
5.8
6.6
7.9
10.0
11.3
12.9
14.2
15.8
17.4
810
950
1080
1300
1630
1840
2110
2320
2580
2850
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
136
136
136
136
136
136
136
136
136
136
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
164
164
164
164
164
164
164
164
164
164
3.4
4.0
4.5
5.4
6.8
7.7
8.8
9.7
10.7
11.9
(ft)
(m)
35.3
52.9
70.5
88.2
105.8
124.1
141.1
169.8
212.9
240.2
275.5
303.0
336.9
372.2
444.0
10.8
16.1
21.5
26.9
32.2
37.8
43.0
51.8
64.9
73.2
84.0
92.4
102.7
113.4
135.3
10.7
16.0
21.3
26.7
32.0
37.5
42.7
51.4
64.4
72.7
83.3
91.7
101.9
112.6
134.3
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.8
6.0
6.8
7.7
8.5
9.5
10.5
12.5
8.9
13.3
17.8
22.2
26.7
31.3
35.6
42.8
53.7
60.6
69.4
76.4
84.9
93.8
111.9
35.3
53.1
70.6
88.2
105.8
124.1
141.0
176.3
10.8
16.2
21.5
26.9
32.2
37.8
43.0
53.7
10.7
16.1
21.4
26.7
32.0
37.5
42.6
53.3
1.0
1.5
2.0
2.5
3.0
3.5
4.0
5.0
211.6
248.2
282.1
339.4
425.8
480.5
551.0
605.9
673.8
744.4
64.5
75.7
86.0
103.4
129.8
146.5
167.9
184.7
205.4
226.9
64.0
75.1
85.3
102.7
128.8
145.3
166.7
183.3
203.8
225.2
5.9
7.0
7.9
9.5
12.0
13.5
15.5
17.0
18.9
20.9
Each heating cable includes a floor temperature sensor compatible with the DITRA-HEAT-E thermostats and features an approximately
7 ft (2.1 m) long cold lead.
26
HEATING CABLE SPECIFICATION
TESTING & CERTIFICATIONS
Product Evaluation
Schluter®-Systems is committed to providing reliable installation systems for ceramic and stone tile. As part of this commitment, we have
invested considerable resources in testing our products and obtaining certifications where applicable to provide our customers and local
code officials with relevant data that supports the efficacy of our systems. All the testing referenced below was performed by independent
laboratories.
Uncoupling and Support/Load Distribution
The method used to establish the overall performance of a tile assembly under loading is the ASTM C627 “Standard Test Method for Evaluating
Ceramic Floor Tile Installation Systems Using the Robinson Type Floor Tester.” The assembly is tested in cycles using a loaded, revolving carriage.
Load, wheel hardness, and number of revolutions vary with each cycle. Once a specified level of damage is exceeded, the test is stopped. The
TCNA Handbook for Ceramic, Glass, and Stone Tile Installation assigns performance levels to an assembly based on the number of cycles
successfully completed. The ratings include residential, light, moderate, heavy, and extra heavy, in order of improving performance.
Report Number
Substrate
Joist Spacing
Tile
Rating
TCNA-415-13
OSB
TCNA-415-13
OSB
19.2" o.c.
12" x 12" porcelain
Extra Heavy
24" o.c.
12" x 12" carrara marble
Light
TTMAC-UFT09-2013
Concrete
N/A
12" x 12" porcelain
Moderate
TCNA-415-13
Concrete
N/A
2" x 2" porcelain
Light
Schluter®-DITRA-HEAT
Schluter®-DITRA-HEAT-DUO
TCNA-455-15 (1)
Concrete
N/A
12" x 12" porcelain
Light
TCNA-455-15 (2)
Concrete
N/A
2" x 2" porcelain
Residential
TNCA-455-15 (3)
Concrete
N/A
12" x 12" marble
Light
TCNA-455-15 (4)
Plywood
19.2" o.c.
12" x 12" porcelain
Light
Assembly Notes:
1. All plywood and OSB subfloors were 23/32" (3/4" nom.) -thick; 11/32" (3/8" nom.) -thick OSB underlayment added for carrara marble test
2. Modified thin-set mortar (ANSI A118.11) to bond membrane to plywood and OSB
3. Unmodified thin-set mortar (ANSI A118.1) to bond membrane to concrete
4. Unmodified thin-set mortar (ANSI A118.1) to bond tile to membrane
5. High Performance Cement Grout (ANSI A118.7)
The test results above demonstrate that DITRA-HEAT performs extremely well under load while at the same time providing flexibility within the shear plane.
DITRA-HEAT-DUO was found to be suitable for residential and light commercial traffic, depending on the substrate and tile chosen.
Waterproofing
DITRA-HEAT and DITRA-HEAT-DUO provide reliable waterproofing in interior applications. The products have been found to meet or exceed the
requirements of the American National Standard Specifications for Load Bearing, Bonded, Waterproof Membranes for Thin-set Ceramic Tile and
Stone Installation A118.10.
Sound Control
DITRA-HEAT-DUO reduces impact sound transmission through floor-ceiling assemblies and supports the covering to ensure a lasting installation.
No.
Report
Test
Floor
Ceiling
Results
Schluter®-DITRA-HEAT-DUO
1
NGC 7017176
ASTM E2179
8" Concrete
N/A
ΔIIC = 20
2
IN17-007
ASTM E492
8" Concrete
N/A
IIC = 50
3
IN18_001
ASTM E492
8" Concrete
9" wire suspended ceiling with gypsum board
IIC = 67
4
IN17_059
ASTM E492
6" Concrete
RSIC-1 clips with gypsum board
IIC = 60
*All assemblies featured 12" x 12" porcelain tile over DITRA-HEAT-DUO installed with cement based thin-set mortars and grouts
DITRA-HEAT-DUO has been found to meet or exceed the requirements of the American National Specifications for Bonded Sound Reduction
Membranes for Thin-Set Ceramic Tile Installation A118.13.
TESTING & CERTIFICATIONS
27
Vapor Management
The free space under the DITRA-HEAT and DITRA-HEAT-DUO mattings allow the substrate to breathe, while the material composition provides for
a very low water vapor permeance, which prevents any significant vapor intrusion in the tile assembly from below.
Product
Schluter -DITRA-HEAT
Test Method
®
Schluter®-DITRA-HEAT-DUO
ASTM E96*
Performance
0.21 perms
0.48 perms
*Using the water method at 73ºF (23ºC) and 50% RH
The result is the DITRA-HEAT and DITRA-HEAT-DUO effectively manage vapor and prevent damage to the tile covering as a result.
Certifications
Heating Cables
The DITRA-HEAT-E-HK heating cables sets are certified or listed to the following standards and usage:
• CAN/CSA-C22.2 No. 130-03 "Requirements for Electrical Resistance Heating Cables and Heating Device Sets" under usage markings
GXW for general use (G) with a wet rating (W), but specifically (X) for floor embedded indoor floor warming applications.
For products bearing the cCSAus certification mark:
• UL 1673 "Electric Space Heating Cables" for installation in poured masonry floors within enclosed structures.
For products bearing the cULus certification mark:
• UL 1683 "Outline of investigation for Electric Heating Products For Installation Under Floor Coverings"
Thermostat
DITRA-HEAT-E-WiFi thermostat WiFi radio chip authorized by the FCC (USA) and IC (Canada) under the following numbers:
FCC ID.................AZY-HF-LPT200
IC ID....................12243A-HFLPT2001
The DITRA-HEAT-E-RT/-R/-WiFi digital thermostats are UL listed according to the following standards:
• UL 60730-1 “Automatic Electrical Controls for Household and Similar Use – Part 1: General Requirements”
• UL 60730-2-9 “Automatic Electrical Controls for Household and Similar Use – Part 2-9: Particular Requirements for Temperature Sensing
Controls”
• CSA E60730-1:13 “Automatic Electrical Controls for Household and Similar Use – Part 1: General Requirements”
• CSA E60730-2-9 “Automatic Electrical Controls for Household and Similar Use – Part 2-9: Particular Requirements for Temperature
Sensing Controls”
• UL 943 4th ed. “Ground-Fault Circuit Interrupters”
• CSA C22.2 No. 144.1-06 “Ground-Fault Circuit Interrupters”
Membrane
DITRA-HEAT:
• ICC-ES Report No. ESR-2467
• ICC-ES PMG Report No. PMG-1204
• U.S. Pat. No. 8,950,141, and U.S. DES. PAT. No. D706459
Canada D Schluter Systems L.P. and other patents pending
DITRA-HEAT-DUO:
• ICC-ES Report No. ESR-2467
• ICC-ES PMG Report No. PMG-1204
• Patent pending
Certifications and listings may be accessed
via our website at www.schluter.com
Green Building
DITRA-HEAT and DITRA-HEAT-DUO have been evaluated according to the "Standard Method for the Testing and Evaluation of Volatile Organic
Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1" for California Specification 01350 and found to comply
with the VOC requirements. California Specification 01350 is referenced by various green building standards and rating systems.
28
TESTING & CERTIFICATIONS
SOUND CONTROL
Discussion of sound control in conjunction with ceramic &
stone tile
Controlling sound transmission through floor/ceiling assemblies in multi-story construction can present challenges to architects and
design professionals, particularly when hard surface coverings, including ceramic and stone tiles, are used. This is because sound control
materials tend to be compressible and may not provide adequate support for the tile layer in thin-set applications. However, there are
practical methods that allow for the use of tile and stone while providing sound transmission control.
Sound transmission evaluation and requirements
Impact sound transmission through floor-ceiling assemblies is most commonly measured in the laboratory according to test method
ASTM E492. The measured data is used to calculate a single-number rating per ASTM E989 called impact insulation class (IIC). The
contribution of a flooring assembly to the IIC of an assembly with a concrete slab subfloor can be determined using the ASTM E2179 test
method. The test method yields a rating called ΔIIC (delta IIC), and measures the performance of the combination of all elements above
the concrete. ΔIIC values are useful tools to compare the performance of different flooring assemblies over a concrete slab. However,
full assembly testing can be used as the basis for designing floor-ceiling assemblies to meet impact sound control requirements. For
example, the International Building Code (IBC) requires a minimum IIC of 50 and the International Residential Code (IRC) a minimum IIC of
45. Condominium or homeowners associations may have their own requirements, which are typically higher than code minimums.
DITRA-HEAT-DUO
Schluter®-DITRA-HEAT integrates electric floor warming with the functions associated with DITRA: uncoupling, waterproofing, vapor
management and load support. Schluter®-DITRA-HEAT-DUO integrates two additional benefits: reducing impact sound transmission
through floor-ceiling assemblies and providing faster warm-up times. While sound control materials tend to be compressible, DITRA-HEATDUO supports the covering to ensure a lasting installation. This versatility makes the system an ideal solution for ceramic and stone tile
floor installations in many applications, such as multi-story residential construction, hotel guest rooms, and many more.
SOUND CONTROL
29
Test Results
Test results of assemblies with DITRA-HEAT-DUO and porcelain tile over concrete are listed in the table below. DITRA-HEAT-DUO with
porcelain tile received a rating of ΔIIC 20, a significant contribution to sound rated floor-ceiling designs. To further improve IIC ratings, sound
rated ceilings can be installed below the subfloor. Wood construction sound tests are in progress.
No.
Report
Test
Floor
Ceiling
Results
Schluter -DITRA-HEAT-DUO
®
1
NGC 7016078
ASTM E2179
8" Concrete
N/A
ΔIIC = 20
2
IN17-007
ASTM E492
8" Concrete
N/A
IIC = 50
3
IN18_001
ASTM E492
8" Concrete
9" wire suspended ceiling with gypsum board
IIC = 67
4
IN17_059
ASTM E492
6" Concrete
RSIC-1 clips with gypsum board
IIC = 60
No.
Report
Floor-Ceiling Sketch
Schluter -DITRA-HEAT-DUO
®
1
2
3
4
Tile and underlayment
• 8" concrete slab
• No ceiling
Concrete slab
8.625"
Floor-ceiling thickness = 8.625"
• 8" concrete slab
• 9" wire-suspended ceiling
with cold rolled steel and 7/8"
furring channel
• R-11 unfaced fiberglass batt
insulation
• 5/8" gypsum board
• 6" concrete slab
• RSIC-1 clips with 7/8" furring
channel
• R-11 unfaced fiberglass batt
insulation
• 5/8" gypsum board
Tile and underlayment
8.625"
Concrete slab
Steel Wire
9"
Floor-ceiling thickness = 17.625"
Gypsum Board
Furring
Channel
Tile and underlayment
6.625"
Concrete slab
1.625"
Floor-ceiling thickness = 8.25"
RSIC-1 Clips
Gypsum Board
*All assemblies featured 12" x 12" porcelain tile over DITRA-HEAT-DUO installed with cement based thin-set mortars and grouts
Installation Considerations
In laboratory testing, sound energy transmission is directed through the test specimen only, with negligible transfer through other paths.
The values provide an accurate picture of the sound control characteristics of the test specimen itself. However, floor/ceiling assemblies
may not perform as expected in the field if they are not isolated from adjacent walls to prevent sound energy transfer. Thus, perimeter joints
are not only necessary to accommodate expansion of the tile assembly, but to also prevent “flanking” sound transfer. Schluter®-Systems
provides a range of prefabricated movement joint profiles that can be used for these purposes.
DH-C-TS
Ceramic, porcelain
or stone tile
Schluter SET®, Schluter ALL-SET®, Schluter
FAST-SET®, or unmodified
thin-set mortar
DITRA-HEAT or DITRA-HEAT-DUO
uncoupling membrane and heating cables
Schluter SET®, Schluter ALL-SET®,
Schluter FAST-SET®, or unmodified
thin-set mortar
Concrete
30
SOUND CONTROL
DITRA-HEAT-DUO
Solution to improve floor warming response time
The challenge of concrete substrates
Concrete substrates can absorb enough heat energy to significantly increase the time it takes for floors to warm up, particularly when there
is no insulation layer below the concrete. In some cases, floors may never reach the desired temperature. There are solutions suggested
by other heating cable manufacturers to address this challenge, such as installing the heating cables at closer spacing for increased
energy output or installing a thermal break prior to heating cable installation to reduce heat loss into the substrate.1 However, both of these
solutions increase material and labor costs.
A one-step solution
Schluter®-DITRA-HEAT-DUO offers the same functions as the Schluter®-DITRA-HEAT membrane, but also features an integrated thermal
break in the form of a thicker bonding fleece. The thermal break reduces the initial rates of heat loss to the substrate, and improves the
floor warming response time during temperature ramp-ups. Since an effective thermal break can be created with a relatively low R-value,
the DITRA-HEAT-DUO membrane is only 5/16" (8 mm)-thick, compared to DITRA-HEAT at 1/4" (5.5 mm)-thick.
Thermal resistance
The DITRA-HEAT-DUO thermal break was tested according to the ASTM C518 “Standard Test Method for Steady-State Thermal
Transmission Properties by Means of the Heat Flow Meter Apparatus” and determined to have an R-value of 0.35. This value may seem
low, but it is sufficient to improve the system warm up time. If improving overall energy efficiency is desired, and the floor warming system
is to be used for extended periods of time (i.e more than early morning and/or evenings) increased thermal resistance may be required.
Floor warming performance
In laboratory testing, when heating the floor from 68°F (20°C) to 78°F (25°C), DITRA-HEAT-DUO reduced floor warming response time by
approximately 80% (90 minutes) compared to DITRA-HEAT over a concrete substrate.
Wood substrates act as insulators and typically do not pose the same challenges as concrete substrates. In the same laboratory testing,
when heating the floor from 68°F (20°C) to 78°F (25°C), DITRA-HEAT-DUO only reduced floor warming response time by approximately
20% (5 minutes) compared to DITRA-HEAT over a plywood substrate.
Figure 1 - DITRA-HEAT-DUO Performance over Concrete
Figure 2 - DITRA-HEAT-DUO Performance over Wood
85.0
93.0
83.0
88.0
79.0
77.0
73.0
73.0
DITRA-HEAT
DITRA-HEAT-DUO
71.0
Temperature (ºF)
Temperature (ºF)
81.0
83.0
78.0
DITRA-HEAT
DITRA-HEAT-DUO
73.0
69.0
67.0
68.0
0
10 20 30
40 50
60
70
80 90 100 110 120
0
10
20
30
Time (minutes)
40
50
60
70
80
90 100 110 120
Time (minutes)
Schluter®-DITRA-HEAT-E-HK heating cables were spaced at three studs in all of the above tests.
Results above are based upon laboratory testing. Actual results may vary depending on various factors, including concrete substrate
thickness, concrete substrate temperature, room temperature, heat losses, etc.
DITRA-HEAT-DUO
31
CONCRETE SUBFLOORS
Discussion on Schluter®-DITRA-HEAT installations over
concrete subfloors
Concrete substrates absorb more heat energy than wood substrates. As such, the time required for an electric floor warming system, such
as Schluter®-DITRA-HEAT, to bring a tile covering to the desired temperature will be longer for applications over concrete than for applications
over plywood/OSB. The warm up time will vary depending on many factors, including concrete thickness, temperature, location, and
insulation. Therefore Schluter Systems cannot predict or guarantee the temperature increase over time as follows:
Elevated Concrete
Elevated concrete substrates, as found in multi-story residential construction, hotels, etc. will typically be located over another occupied
space that is at or near room temperature. For these applications, the DITRA-HEAT-DUO membrane with integrated thermal break is an
excellent means to reduce the warm up time and will typically produce satisfactory results.
Concrete on or Below Grade
Concrete substrates placed on or below grade, as in basements or first floors of single-family dwellings, have the potential to absorb even
more heat energy than elevated concrete substrates and further extend the warm up time. This effect is exacerbated if there is no insulation
provided below the concrete on ground.
If the concrete on grade is sufficiently insulated, the DITRA-HEAT-DUO membrane with integrated thermal break can reduce the warm
up time and satisfactory results will typically be achieved. If the concrete is not insulated, the DITRA-HEAT-DUO thermal break is likely
not sufficient to reduce the warm up time to a satisfactory value. In fact, it is possible that the heat loss to the concrete is such that the
tile covering will not reach the desired temperature. For these applications, it is likely that providing insulation on top of the concrete will
be required to produce satisfactory floor warming performance. If providing insulation on top of the concrete is not possible, the use of
the continuously alternating 3-2 stud heating cable spacing is recommended. This alternating cable spacing will provide a 20% increase
in heat output compared to the 3 stud spacing and a similar reduction in warm up time, over and above the reduction obtained with the
DITRA-HEAT-DUO membrane, depending on your particular application or installation. Please contact a design professional (e.g., HVAC
contractor, engineer or architect) and Schluter Systems to discuss such projects during the planning stage.
32
CONCRETE SUBFLOORS
208 V APPLICATIONS
Discussion of Schluter®-DITRA-HEAT-E-HK Heating Cables in
208 V Applications
Schluter®-DITRA-HEAT offers complete flexibility when creating warm floors in any application. Schluter®-DITRA-HEAT-E-HK heating cables
are designed for use with common 120 V and 240 V power sources. 208 V power sources are used in some cases to handle larger loads
(e.g., HVAC equipment, motors, etc.) or to improve energy efficiency.
Schluter®-Systems recommends using the DITRA-HEAT-E-HK 240 V heating cables when a 208 V power source is present. However, this
will reduce the heating power by 25% to 9.5 W/ft2 at the standard 3-stud cable spacing, which may not be sufficient power to warm the
floor in these applications. To offset the effect of the lower voltage, we recommend installing the heating cable at a 2-stud spacing in these
applications. This results in an increased heating power of 14.2 W/ft2, which will ensure adequate performance.
The heating cable will cover 33% less area when spaced at 2 studs compared to 3 studs. Therefore, a longer heating cable must be selected
to cover a given area in these applications. Coverage for each 240 V heating cable spaced at 2 studs can be found in the table below.
DITRA-HEAT-E-HK 240 V Heating Cables in 208 V Applications at 2 Stud Spacing
Item No.
Length (ft - m)
Area (ft2 - m2)
Power (W)
Average Power
(W/ft2 - W/m2)
Current (A)
DHE HK 240 11
35.3 – 10.8
7.1 – 0.7
101
14.2 - 152.8
0.5
DHE HK 240 16
53.1 – 16.2
10.7 – 1.0
152
14.2 - 152.8
0.7
DHE HK 240 21
70.5 – 21.5
14.2 – 1.3
203
14.2 - 152.8
1.0
DHE HK 240 27
88.2 – 26.9
17.8 – 1.7
254
14.2 - 152.8
1.2
DHE HK 240 32
105.8 – 32.2
21.3 – 2.0
304
14.2 - 152.8
1.5
DHE HK 240 38
124.1 – 37.8
25.0 – 2.3
356
14.2 - 152.8
1.7
DHE HK 240 43
141 – 43.0
28.4 – 2.6
405
14.2 - 152.8
1.9
DHE HK 240 53
176.3 – 53.7
35.5 – 3.3
506
14.2 - 152.8
2.4
DHE HK 240 64
211.6 – 64.5
42.7 – 4.0
608
14.2 - 152.8
2.9
DHE HK 240 75
248.2 – 75.7
50.0 – 4.7
713
14.2 - 152.8
3.4
DHE HK 240 85
282.1 – 86.0
56.9 – 5.3
810
14.2 - 152.8
3.9
DHE HK 240 103
339.4 – 103.4
68.4 – 6.4
975
14.2 - 152.8
4.7
DHE HK 240 129
425.8 – 129.8
85.8 – 8.0
1223
14.2 - 152.8
5.9
DHE HK 240 145
480.5 – 146.5
96.9 – 9.0
1380
14.2 - 152.8
6.6
DHE HK 240 167
551 – 167.9
111.1 – 10.3
1583
14.2 - 152.8
7.6
DHE HK 240 183
605.9 – 184.7
122.1 – 11.4
1740
14.2 - 152.8
8.4
DHE HK 240 204
673.8 – 205.4
135.8 – 12.6
1935
14.2 - 152.8
9.3
DHE HK 240 225
744.4 – 226.9
150.1 – 13.9
2138
14.2 - 152.8
10.3
We recommend consulting with a qualified electrician for design and installation of your DITRA-HEAT system on a 208 V power source. Keep
in mind during design of the system that the DITRA-HEAT-E thermostats have an electrical current limit of 15 A.
208 V APPLICATIONS
33
SPACE HEATING
Discussion on use of Schluter®-DITRA-HEAT for space heating
Schluter®-DITRA-HEAT is intended to warm tile floors and make them more comfortable underfoot but can also contribute to space heating. Floor warming is
a type of radiant heating that provides heat differently than from a forced air heating system, or from a baseboard heater or wall convector. As the tile covering
warms up, it will radiate heat to the surrounding objects in the room, which can increase the comfort level of the occupants.
What determines comfort?
Ambient temperature alone does not determine human comfort. This is already clear when one considers the outdoor environment. For example, meteorologists
will report the impacts of wind on perceived temperature in cold weather or humidity on perceived temperature in hot weather. We’ve all experienced the effect
of sun exposure in regard to perceived temperature as well. Sitting in the shade will feel cooler than sitting in the sun, despite the ambient temperature being
the same. This phenomenon applies to the interior environment as well.
How does radiant heating contribute to comfort?
In the interior environment, occupant comfort is primarily based on air temperature and the temperature of surrounding surfaces. Warmer surfaces, such as a
floor that incorporates heating elements, emit heat in the form of infrared radiation. This radiant heat does not directly warm the air, but warms the surrounding
objects and occupants, similar to the sun. Increases in air temperature result indirectly from convective heat from the warm objects. The temperature effect
on the occupant is referred to as the “mean radiant temperature”. “Operative temperature” is the average of air temperature and mean radiant temperature
and is what most directly determines the comfort of the occupant. Therefore, when radiant heating is present, occupants can feel the same level of comfort
at lower air temperatures.
Can I rely on DITRA-HEAT as the only heating source in my bathroom, kitchen, or living space?
In some cases the answer is yes. However, the amount of heat required to achieve a comfortable room depends on many variables that affect ambient
temperature and mean radiant temperature, including but not limited to the following.
•
•
•
•
•
Starting temperature and target temperature
Outdoor temperature and desired indoor temperature
Heat loss through walls, windows, and doors according to size and R-value of the components
Size of room and height of the ceiling
Total heated surface area
All of these variables must be considered to calculate the required heat output of the system and determine if it can meet the needs of the owner. Schluter
Systems does not perform heating load calculations as a service and can’t make a final recommendation on the owner’s heating system requirements. It is
recommended that an HVAC professional be consulted to perform such an analysis and design. However, Schluter Systems offers the following information
to aid in the process and support the successful use of the DITRA-HEAT system.
The following notes are based on information gathered from articles and design guidebooks published by ASHRAE and other professional heating and cooling
associations. They are intended to help support successful use of the DITRA-HEAT system to enhance or provide space heating comfort. They do not
represent all variables or best practices that the heating professional must consider.
1.
2.
3.
4.
5.
6.
Operative temperature is what most directly determines the comfort of the occupant.
Since radiant heat contributes to approximately 55% of the total heat, the operative temperature is calculated as the average of air temperature
and mean radiant temperature.
Total heat output of the floor warming system to the space is proportional to the temperature differential between the floor surface and the
operative temperature.
The ideal operative temperature for occupants is typically between 68°F to 75°F (20°C to 24°C), depending on the level of activity.
The air temperature will typically be controlled at approximately 2°F to 3°F (1°C to 1.5°C) lower when the floor warming system is in use at
optimum conditions.
The recommended floor surface temperature is 84°F (29°C) or lower for comfort.
The heat output from the DITRA-HEAT system can be calculated using the recognized equation from various major heating and cooling engineering
associations. This equation takes into account the contribution from radiant heat and convective heat.
Q = 8.92ΔT1.1, where Q is in units of W/m2 and ΔT is in units of °C
ΔT*
Total heat Output
ΔT*
Total heat Output
°F
(W/ft )
(Btu/hr/ft )
°C
(W/m2)
(Btu/hr/m2)
2
0.9
3.2
1
8.9
30.4
2
2
4
2.0
6.8
2
19.1
65.2
6
3.1
10.6
3
29.9
101
8
4.3
14.6
4
41.0
140
10
5.5
18.6
5
52.4
179
12
6.7
22.8
6
64.0
218
14
7.9
27.0
7
75.9
259
16
9.2
31.3
8
87.9
300
18
10.4
35.6
9
100
341
20
11.7
40.0
10
112
383
*ΔT = Temperature Differential between Floor Surface and Operative Temperature
For example, in a typical situation where the floor surface temperature is 82°F and the operative temperature is 72°F, the differential is 10°F, so the total heat
output from the floor surface is 5.5 W/ft2 or 18.6 Btu/hr/ft2.
34
SPACE HEATING
NATURAL STONE
Discussion of natural stone and single-layer wood subfloors
Natural stone is a product of nature with a wide variety of colors, patterns, and textures that come together to distinguish it as one of the
premiere surface coverings available on the market. Some of stone’s characteristics, which add to its beauty and uniqueness, are veins,
fissures, starts, and dry-seams. While these characteristics enhance its aesthetic appeal, they’re also indicators that point to the inherent
variability of the flexural strength of natural stone, which can have detrimental effects on serviceability. This variability is underscored by
examining the range of typical flexural (bending) strengths of ceramic tile compared to the range of strength for some common natural stones.
Schluter®-Systems contracted the Tile Council of North America (TCNA) to perform flexural strength testing on various commercially available
ceramic tiles and dimension stones guided by the ASTM C880 Standard Test Method for Flexural Strength of Dimension Stone. Five samples
of each tile and stone were tested, with the minimum recorded values displayed in the figure below. We have chosen to show only minimum
values since these represent the weakest samples, which would be most prone to cracking in service over a bending substrate.
6000
Minimum Recorded Flexural Strength (psi)
5236
5000
4485
4241
4000
3000
2490
2438
2000
1856
1488
1000
539
0
Porcelain A
Ceramic B
Porcelain B
Granite
Ceramic A
White Carrara
Slate
Crema Marfil
337
Travertine
It is clear from the figure that the minimum recorded flexural strengths of these dimension stones tend to be significantly less than those
of the ceramic tiles. In some cases, the differences are dramatic. For example, the minimum recorded flexural strength of the weakest
travertine sample (337 psi) was only 14% of the minimum flexural strength of the weakest ceramic sample (2438 psi). In other words, the
weakest ceramic sample was more than 7 times as strong as the weakest travertine sample. As another example, the minimum recorded
flexural strength of the weakest porcelain sample is more than 12 times as strong as the minimum recorded flexural strength of the weakest
travertine sample.
Q. Why does Schluter®-Systems recommend a double-layer wood floor for installing natural stone over DITRA-HEAT and DITRA-HEATDUO?
A. There are three principle reasons: 1) As illustrated above, the fact that most stone products have a minimum flexural strength that
is substantially lower than what is typical for ceramic tile; 2) Stones are products of nature and complex heterogeneous materials with
naturally occurring regions of discontinuity, such as veins and fissures. Such features can be weaker than the surrounding stone fabric and
act as “stress risers,” concentrating bending stresses within the region of discontinuity; and 3) When wood floor assemblies are subjected
to forces such as loading – both live and dead loads – they produce flexural stresses in the surface covering which can cause weak and
brittle materials to break or crack.
Engineering mechanics as well as field observations show that the location of maximum flexural stresses in the floor assembly is directly
over the floor joists and at seams in the subfloor panels. Therefore, we recommend double-layer wood floors when installing natural stone
in order to increase the stiffness of the sheathing assembly and position underlayment seams away from the joists to minimize flexural
stresses in the stone covering directly above the joists and at seams. Refer to page 16 for underlayment installation guidelines. For more
information on the development of these guidelines, please refer to the article titled “Position of Underlayment to Prevent Cracked Tile and
Grout” on our website at https://www.schluter.com/schluter-us/en_US/articles.
NATURAL STONE
35
HEATING CABLE TESTS LOG
Validation for warranty coverage
Each heating cable is subject to factory quality control. However, damage to the cables may happen after the product leaves the factory. In order to ensure
that the cable quality remains unchanged throughout the installation process and for warranty purposes, tests must be conducted while the cable is still on the
spool and during two specific subsequent steps. Measurements must be recorded in the table below and compared to initial measurements taken when the
cable was on the spool in order to enable you to detect any changes related to the electrical property of the cable. Any installation-related cable damages are
not covered by the warranty. See page 21 in this DITRA-HEAT Installation Handbook for complete heating cable testing instructions.
The DITRA-HEAT system has warranty coverage up to a period of fifteen (15) years. In order to receive warranty coverage,
the owner must complete and submit the warranty registration card and completed heating cable tests log to Schluter Systems online at
https://www.schluter.com/schluter-us/en-US/registerwarranty or via mail at the address provided heaeafter within fourteen (14) day of installation. It is an
installation requirement that the heating cable tests log be completed by the installer at the time of installation with a copy submitted to Schluter Systems; it is
recommended that the owner retain the original logs. The heating cable tests log must include results for the following tests: “Test 1: Conductor Resistance,”
“Test 2: Conductor and Ground Braid Continuity,” “Test 3: Insulation Resistance,” and “Test 4: Thermostat Floor Temperature Sensors Test.” Failure to
conduct these tests and submit the heating cable tests log will reduce or may void coverage under this Limited Warranty.
In the event the heating cable tests log only includes the results for “Test 1: Conductor Resistance,” “Test 2: Conductor and Ground Braid Continuity,”
and “Test 4: Thermostat Floor Temperature Sensors Test,” but does not include results for “Test 3: Insulation Resistance,” the applicable warranty term
shall be ten (10) years from the date of purchase. If the heating cable tests log does not include test results for “Test 1: Conductor Resistance,” “Test 2:
Conductor and Ground Braid Continuity,” and “Test 4: Thermostat Floor Temperature Sensors Test,” such installation does not qualify for coverage under
this Limited Warranty.
Completion of warranty registration qualifies customers for the system warranty, in which Schluter®-Systems shall a) reinstall or replace the failed portion
of the floor covering assembly or b) pay an amount not to exceed the original square foot cost of the installation of the floor covering assembly verified to
be defective.
The owner must retain a copy of this heating cable tests log for warranty purposes.
Heating Cable Tests Log
Location/Homeowner: _____________________________________________
Date of installation: ___________________________
Certified electrician: _______________________________________________
Date put into service*: __________________________
Identification
Factory Value
Before Installation
After Cable Installation
Test 1: Conductor Resistance Test
Readings must fall within 10% of the factory value printed on the silver heating cable identification tag.
Test 2: Conductor and Ground Braid Continuity Test
Infinity (I) or
Overload (OL)
Test 3: Insulation Resistance Test
Equal to or
greater than
1 Gigaohms**
Test 4: Thermostat Floor Temperature Sensor Test
Temperature
Resistance
ºC
ºF
Kohms
10
50
18.1
15
59
14.8
20
68
12.1
25
77
10.0
30
86
8.3
* Allow the assembly to cure for 7 days after grouting before putting the floor warming into service.
**1 Gigaohms = 1 G ohms = 1000 M ohms = 1000 Mega ohms
36
HEATING CABLE TESTS LOG
After Tile Installation
Notes :
NOTES
37
Notes :
38
NOTES
Notes :
NOTES
39
WARRANTIES
Schluter ®-DITRA-HEAT System 15-Year Limited Warranty
LIMITED WARRANTY COVERAGE: Subject to the conditions and limitations as stated in this Schluter®-DITRA-HEAT System 15-Year Limited Warranty (the “Limited Warranty”),
Schluter Systems warrants that its Schluter®-DITRA-HEAT System (defined hereafter) will be free from manufacturing defects and will perform as described in the Schluter®-DITRA-HEAT
Installation Handbook and Schluter®-DITRA-HEAT Technical Data Sheet (collectively, the “Written Materials”1) for a period of fifteen (15) years from the date of purchase when installed and
used in accordance with the terms and conditions of the Written Materials and industry standard guidelines that are not in conflict with the Written Materials in effect at the time of installation.
In order to receive coverage under this Limited Warranty, the Owner (defined hereafter) must complete and submit the warranty registration card and completed heating cable tests log
to Schluter Systems online at https://www.schluter.com/schluter-us/en_US/registerwarranty or via mail at the address provided hereafter within fourteen (14) days of installation. It is an
installation requirement that the heating cable tests log be completed by the installer at the time of installation with a copy submitted to Schluter Systems; it is recommended that the Owner
retain the original logs. The heating cable tests log must include results for the following tests: “Test 1: Conductor Resistance,” “Test 2: Conductor and Ground Braid Continuity,” “Test 3:
Insulation Resistance,” and “Test 4: Thermostat Floor Temperature Sensor Test.” Failure to conduct these tests and submit the heating cable tests log will reduce or may void
coverage under this Limited Warranty.
In the event the heating cable tests log only includes results for “Test 1: Conductor Resistance,” “Test 2: Conductor and Ground Braid Continuity,” and “Test 4: Thermostat Floor Temperature
Sensor Test,” but does not include results for “Test 3: Insulation Resistance,” the applicable warranty term shall be ten (10) years from the date of purchase. If the heating cable tests log does
not include test results for “Test 1: Conductor Resistance,” “Test 2: Conductor and Ground Braid Continuity,” and “Test 4: Thermostat Floor Temperature Sensor Test,” such installation does
not qualify for coverage under this Limited Warranty; such installation may instead receive warranty coverage under the Schluter®-DITRA-HEAT and Schluter®-DITRA-HEAT-DUO Uncoupling
Membrane 10-Year Limited Warranty.
For the purposes of this Limited Warranty, a “DITRA-HEAT System” is defined as Schluter®-DITRA-HEAT or Schluter-DITRA-HEAT-DUO uncoupling membrane and Schluter®-DITRAHEAT-E-HK heating cables; “Owner” is defined as the original end user of the property in which the DITRA-HEAT System is installed; and “Floor Covering Assembly” is defined to include
the DITRA-HEAT System, non-reusable flooring surfaces, and applicable setting and grouting materials.
This Limited Warranty is only applicable to installations in the United States of America and Canada. Schluter Systems is not responsible or liable under any circumstances for determining
the suitability of a DITRA-HEAT System for the Owner’s intended purpose. It is the responsibility of the Owner to consult with an experienced and professional installer to ensure the suitability
of a DITRA-HEAT System, subfloor/substrate and all building materials in the installation and that the Written Materials are followed properly.
RESOLUTION: If a DITRA-HEAT System is installed and used in accordance with the terms and conditions as described hereinabove and such DITRA-HEAT System is proven defective
within the applicable warranty term, the Owner’s exclusive remedy and the sole obligation of Schluter Systems, at its election, shall be to (a) reinstall or replace the failed portion of the Floor
Covering Assembly or (b) pay an amount not to exceed the original square foot cost of the installation of the Floor Covering Assembly verified to be defective. Due to conditions beyond the
control of Schluter Systems (e.g., color and shade availability, discontinuation, normal wear and tear), Schluter Systems cannot guarantee or warrant an exact match to the specific tile, stone,
or other flooring materials used in the original installation. In such event, substantially similar materials may be substituted. This Limited Warranty does not cover the cost of disconnection
or installation.
EXCLUSIONS FROM COVERAGE: This Limited Warranty excludes and in no event shall Schluter Systems have any liability for any indirect, special, incidental, punitive, exemplary, or
consequential damages, including lost profits, arising out of or otherwise connected to the failure of DITRA-HEAT System, regardless of any strict liability or active or passive negligence of
Schluter Systems, and regardless of legal theory, whether in contract, tort, extra-contractual or other. This Limited Warranty further excludes any loss or damage arising out of or otherwise
connected to: acts of war, terrorism, fire, explosion, natural disaster, acts of God, any failure to comply with the Written Materials, inadequate subfloor/substrate, improper preparation or
other failure of subfloor/substrate, faulty or negligent penetration of a DITRA-HEAT System or subfloor/substrate, intentional acts of destruction, structural failure, misuse of or failure to
maintain a DITRA-HEAT System, normal wear and tear, scratches, dents, corrosion or discoloration (whether caused by excessive heat, chemical cleaning products, abrasive agents or
otherwise), efflorescence and shading which are a natural occurrence with cementitious materials and are not considered a defective condition for the purposes of this Limited Warranty,
variations of texture, color or shade from those on product samples, packaging materials or other marketing materials, or other causes unrelated to a DITRA-HEAT System (e.g. floor covering
failure, excess point loading, overvoltage). This Limited Warranty excludes exterior applications and applications utilizing glass tile or other non-approved floor coverings, unless specifically
approved in writing on a case by case basis by the Schluter Systems Technical Services Director. Schluter® DITRA-HEAT™-E thermostats are specifically excluded from coverage under this
Limited Warranty; warranty coverage for Schluter® DITRA-HEAT™-E thermostats are limited and subject to the Schluter-DITRA-HEAT Thermostat 3-Year Limited Warranty. Any substitution
of a non-Schluter Systems product for a Schluter Systems component in a DITRA-HEAT System voids this Limited Warranty.
This Limited Warranty is conditioned and will be considered null and void and Schluter Systems will have the right to refuse any claims if: (a) a DITRA-HEAT System has been improperly
stored or installed, (b) any component comprising a DITRA-HEAT System has been altered or otherwise modified in any way, (c) a DITRA-HEAT System is subject to abusive or abnormal
use, lack of maintenance, or used in a manner other than that for which the DITRA-HEAT System was designed or in any way contrary to the Written Materials, (d) the nameplate numbers
(electrical rating label) are not accessible, readable or recognizable or have been removed from the applicable heating cables or other components, if applicable, or (e) the Owner fails to
return a copy of the completed heating cable tests log with the warranty registration card.
DISCLAIMER: There are no warranties beyond this expressed warranty as stated herein. To the extent permitted by law, all other warranties, representations or conditions, expressed or
implied, are hereby disclaimed and excluded, including but not limited to the implied warranties of MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE (as limited to
such purposes as described in the Written Materials) or arising from a course of dealing, usage of trade or otherwise by law. ANY IMPLIED WARRANTIES ARISING BY OPERATION OF
LAW ARE LIMITED IN DURATION TO THE TERM OF THIS LIMITED WARRANTY. NO REPRESENTATION, PROMISE, AFFIRMATION OR STATEMENT BY ANY EMPLOYEE OR AGENT OF
SCHLUTER SYSTEMS WILL BE ENFORCEABLE AGAINST SCHLUTER SYSTEMS UNLESS IT IS SPECIFICALLY INCLUDED IN THIS LIMITED WARRANTY OR AUTHORIZED IN WRITING
BY THE SCHLUTER SYSTEMS TECHNICAL SERVICES DIRECTOR. This Limited Warranty is given in lieu of any other warranty, whether expressed or implied. The remedies contained
herein are the only remedies available for breach of this Limited Warranty. Schluter Systems excludes and in no event shall have any liability for any indirect, special, incidental, punitive,
exemplary, or consequential damages, including lost profits, arising out of or otherwise connected to failure of a DITRA-HEAT System. This Limited Warranty extends only to the Owner and
is not transferable or assignable unless authorized by written agreement and signed by the Schluter Systems Technical Services Director or otherwise prohibited by specific state or provincial
law. This Limited Warranty gives you specific legal rights; some states and provinces do not allow disclaimers or other restrictions of implied warranties; some of the above disclaimers may
not apply to you. No changes or modifications of any terms or conditions of this Limited Warranty are permitted unless duly authorized in writing by the Schluter Systems
Technical Services Director. This Limited Warranty shall supersede and replace any and all prior oral or written warranties, agreements, or other representations made by or on behalf
of Schluter Systems relative to a DITRA-HEAT System or the application of a DITRA-HEAT System and shall apply to any installation occurring on or after March 13, 2019. If the Schluter®DITRA-HEAT or Schluter®-DITRA-HEAT-DUO uncoupling membrane are used in conjunction with other Schluter products, a different Schluter warranty may apply. For the most current
information and materials regarding Schluter Systems warranties and programs, please visit https://www.schluter.com/schluter-us/en_US/downloadfiles.
MAKING A CLAIM: To make a claim under this Limited Warranty, the Owner must provide Schluter Systems with written notice within thirty (30) days of any alleged defect in a DITRA-HEAT
System covered by this Limited Warranty, together with date and proof of purchase of such DITRA-HEAT System and/or all of its components and name and address of all installers and all
invoices related to the original installation, failing which this Limited Warranty shall have no legal effect . Schluter Systems reserves the right at its election and as a condition of this Limited
Warranty to inspect the alleged failed and/or defective DITRA-HEAT System.
All U.S. Claims shall be sent to: Schluter Systems L.P.
Attn: Warranty Claims Dept.
194 Pleasant Ridge Road
Plattsburgh, NY 12901-5841 All Canadian Claims shall be sent to:
Schluter Systems (Canada), Inc.
Attn: Warranty Claims Dept.
21100 chemin Ste-Marie
Ste-Anne-de-Bellevue, QC H9X 3Y8
If there are any conflicting terms between any Written Materials, the most recently updated document shall be deemed to control.
This Limited Warranty is limited to sales of DITRA-HEAT Systems made in and intended for use in the United States and Canada. For the purposes of this Limited Warranty, Schluter Systems L.P. shall offer warranty coverage to Owners located in the
United States, and Schluter Systems (Canada) Inc. shall offer warranty coverage to Owners located in Canada.
3
In the event that Owner fails to provide such required invoices relating to the original installation, Schluter Systems shall pay Owner an amount equal to the average, reasonable costs of a comparable installation. If the parties fail to agree on such amount,
such dispute shall promptly, and in the first instance, be submitted: (a) if a U.S. claim, to arbitration in Clinton County, New York, in accordance with the rules of the American Arbitration Association, or (b) if a Canadian claim, in the Province of Quebec,
Canada, in accordance with the ADRIC Arbitration Rules. Any outcome of such arbitration proceeding shall be final and binding upon the parties hereto.
1
2
40
WARRANTIES
Schluter ®-DITRA-HEAT and Schluter ®-DITRA-HEAT-DUO 10-Year Limited Warranty
LIMITED WARRANTY COVERAGE: Subject to the conditions and limitations as stated in this Schluter®-DITRA-HEAT and Schluter-DITRA-HEAT-DUO
Uncoupling Membrane 10-Year Limited Warranty (the “Limited Warranty”), Schluter Systems warrants that its Schluter®-DITRA-HEAT and Schluter-DITRA-HEATDUO uncoupling membranes (the “Products”) will be free from manufacturing defects and will perform as described in the Schluter®-DITRA-HEAT Installation Handbook
and Schluter®-DITRA-HEAT Technical Data Sheet (collectively, the “Written Materials”1) for a period of ten (10) years from the date of purchase when installed and used
in accordance with the terms and conditions of the Written Materials and industry standard guidelines that are not in conflict with the Written Materials in effect at the
time of installation.
For the purposes of this Limited Warranty, “Owner” is defined as the original end user of the property in which the Products are installed; and “Floor Covering
Assembly” is defined to include the Products, non-reusable flooring surfaces, and applicable setting and grouting materials.
This Limited Warranty is only applicable to installations in the United States of America and Canada. Schluter Systems is not responsible or liable under any circumstances
for determining the suitability of the Products for the Owner’s intended purpose. It is the responsibility of the Owner to consult with an experienced and professional installer
to ensure the suitability of the Products, subfloor/substrate and all building materials in the installation and that the Written Materials are followed properly.
RESOLUTION: If the Products are installed and used in accordance with the terms and conditions as described hereinabove and such Products are proven defective
within the applicable warranty term, the Owner’s exclusive remedy and the sole obligation of Schluter Systems, at its election, shall be to (a) reinstall or replace the failed
portion of the Floor Covering Assembly or (b) pay an amount not to exceed the original square foot cost of the installation of the Floor Covering Assembly verified to be
defective. Due to conditions beyond the control of Schluter Systems (e.g., color and shade availability, discontinuation, normal wear and tear), Schluter Systems cannot
guarantee or warrant an exact match to the specific tile, stone, or other flooring materials used in the original installation. In such event, substantially similar materials may
be substituted. This Limited Warranty does not cover the cost of disconnection or installation.
EXCLUSIONS FROM COVERAGE: This Limited Warranty excludes and in no event shall Schluter Systems have any liability for any indirect, special, incidental, punitive,
exemplary, or consequential damages, including lost profits, arising out of or otherwise connected to the failure of the Products, regardless of any strict liability or active or
passive negligence of Schluter Systems, and regardless of legal theory, whether in contract, tort, extra-contractual or other. This Limited Warranty further excludes any loss
or damage arising out of or otherwise connected to: acts of war, terrorism, fire, explosion, natural disaster, acts of God, any failure to comply with the Written Materials,
inadequate subfloor/substrate, improper preparation or other failure of subfloor/substrate, faulty or negligent penetration of the Products or subfloor/substrate, intentional
acts of destruction, structural failure, misuse of or failure to maintain the Products, normal wear and tear, scratches, dents, corrosion or discoloration (whether caused
by excessive heat, chemical cleaning products, abrasive agents or otherwise), efflorescence and shading which are a natural occurrence with cementitious materials
and are not considered a defective condition for the purposes of this Limited Warranty, variations of texture, color or shade from those on product samples, packaging
materials or other marketing materials, or other causes unrelated to the Products (e.g. floor covering failure, excess point loading, overvoltage). This Limited Warranty
excludes exterior applications and applications utilizing glass tile or other non-approved floor coverings, unless specifically approved in writing on a case by case basis by
the Schluter Systems Technical Services Director.
This Limited Warranty is conditioned and will be considered null and void and Schluter Systems will have the right to refuse any claims if: (a) the Products have been
improperly stored or installed, (b) the Products are subject to abusive or abnormal use, lack of maintenance, or used in a manner other than that for which the Products
were designed or in any way contrary to the Written Materials , or (c) any non-Schluter heating cable is installed with Schluter®-DITRA-HEAT or Schluter®-DITRA-HEATDUO uncoupling membrane.
DISCLAIMER: There are no warranties beyond this expressed warranty as stated herein. To the extent permitted by law, all other warranties, representations or
conditions, expressed or implied, are hereby disclaimed and excluded, including but not limited to the implied warranties of MERCHANTABILITY or FITNESS FOR A
PARTICULAR PURPOSE (as limited to such purposes as described in the Written Materials) or arising from a course of dealing, usage of trade or otherwise by law.
ANY IMPLIED WARRANTIES ARISING BY OPERATION OF LAW ARE LIMITED IN DURATION TO THE TERM OF THIS LIMITED WARRANTY. NO REPRESENTATION,
PROMISE, AFFIRMATION OR STATEMENT BY ANY EMPLOYEE OR AGENT OF SCHLUTER SYSTEMS WILL BE ENFORCEABLE AGAINST SCHLUTER SYSTEMS
UNLESS IT IS SPECIFICALLY INCLUDED IN THIS LIMITED WARRANTY OR AUTHORIZED IN WRITING BY THE SCHLUTER SYSTEMS TECHNICAL SERVICES
DIRECTOR. This Limited Warranty is given in lieu of any other warranty, whether expressed or implied. The remedies contained herein are the only remedies available for
breach of this Limited Warranty. Schluter Systems excludes and in no event shall have any liability for any indirect, special, incidental, punitive, exemplary, or consequential
damages, including lost profits, arising out of or otherwise connected to failure of a DITRA-HEAT System. This Limited Warranty extends only to the Owner and is not
transferable or assignable unless authorized by written agreement and signed by the Schluter Systems Technical Services Director or otherwise prohibited by specific
state or provincial law. This Limited Warranty gives you specific legal rights; some states and provinces do not allow disclaimers or other restrictions of implied warranties;
some of the above disclaimers may not apply to you. No changes or modifications of any terms or conditions of this Limited Warranty are permitted unless
duly authorized in writing by the Schluter Systems Technical Services Director. This Limited Warranty shall supersede and replace any and all prior oral or written
warranties, agreements, or other representations made by or on behalf of Schluter Systems relative to the Products or the application of the Products and shall apply to
any installation occurring on or after March 13, 2019. If the Schluter®-DITRA-HEAT or Schluter®-DITRA-HEAT-DUO uncoupling membrane are used in conjunction with
other Schluter products, a different Schluter warranty may apply. For the most current information and materials regarding Schluter Systems warranties and programs,
please visit https://www.schluter.com/schluter-us/en_US/downloadfiles.
MAKING A CLAIM: To make a claim under this Limited Warranty, the Owner must provide Schluter Systems2 with written notice within thirty (30) days of any alleged
defect in the Products covered by this Limited Warranty, together with date and proof of purchase of such Products and/or all of its components and name and address
of all installers and all invoices related to the original installation, failing which this Limited Warranty shall have no legal effect3. Schluter Systems reserves the right at its
election and as a condition of this Limited Warranty to inspect the alleged failed and/or defective Products.
All U.S. Claims shall be sent to:
All Canadian Claims shall be sent to:
Schluter Systems L.P.
Attn: Warranty Claims Dept.
194 Pleasant Ridge Road
Plattsburgh, NY 12901
Schluter Systems (Canada), Inc.
Attn: Warranty Claims Dept.
21100 chemin Ste-Marie
Ste-Anne-de-Bellevue, QC H9X 3Y8
If there are any conflicting terms between any Written Materials, the most recently updated document shall be deemed to control.
This Limited Warranty is limited to sales of the Products made in and intended for use in the United States and Canada. For the purposes of this Limited Warranty,
Schluter Systems L.P. shall offer warranty coverage to Owners located in the United States, and Schluter Systems (Canada) Inc. shall offer warranty coverage to Owners
located in Canada.
3
In the event that Owner fails to provide such required invoices relating to the original installation, Schluter Systems shall pay Owner an amount equal to the average,
reasonable costs of a comparable installation. If the parties fail to agree on such amount, such dispute shall promptly, and in the first instance, be submitted: (a) if a U.S.
claim, to arbitration in Clinton County, New York, in accordance with the rules of the American Arbitration Association, or (b) if a Canadian claim, in the Province of Quebec,
Canada, in accordance with the ADRIC Arbitration Rules. Any outcome of such arbitration proceeding shall be final and binding upon the parties hereto.
1
2
WARRANTIES
41
Schluter®-DITRA-HEAT Thermostat 3-Year Limited Warranty
LIMITED WARRANTY COVERAGE: Subject to the conditions and limitations as stated in this Schluter®-DITRA-HEAT Thermostat 3-Year Limited Warranty (the
“Limited Warranty”), Schluter Systems warrants that its Programmable Wi-Fi Thermostat (DHE RT 104/BW), Touchscreen Programmable Thermostat (DHE RT 102/
BW), Non-Programmable Thermostat (DHE RT 103/BW), and Power Module (DHE RR 1/BW) (hereafter collectively referred to as the “Products”) will be free from
manufacturing defects and will perform as described in the applicable Schluter®-DITRA-HEAT Thermostat User Guide and/or Quick Start Guide (collectively, the “Written
Materials”1) for a period of three (3) years from the date of purchase when installed and used in accordance with the terms and conditions of the Written Materials and
industry standard guidelines that are not in conflict with the Written Materials in effect at the time of installation.
For the purposes of this Limited Warranty, “Owner” is defined as the original end user of the property in which the Products are installed.
This Limited Warranty is only applicable to installations in the United States of America and Canada. Schluter Systems is not responsible or liable under any circumstances
for determining the suitability of the Products for the Owner’s intended purpose. It is the responsibility of the Owner to consult with an experienced and professional installer
to ensure the suitability of the Products, subfloor/substrate and all building materials in the installation and that the Written Materials are followed properly.
RESOLUTION: If the Products are installed and used in accordance with the terms and conditions as described hereinabove and such Products are proven defective
within the applicable warranty term, the Owner’s exclusive remedy and the sole obligation of Schluter Systems, at its election, shall be to repair or replace the Products,
and does not cover the cost of disconnection, transport, and installation.
EXCLUSIONS FROM COVERAGE: This Limited Warranty excludes and in no event shall Schluter Systems have any liability for any indirect, special, incidental, punitive,
exemplary, or consequential damages, including lost profits, arising out of or otherwise connected to the failure of the Products, regardless of any strict liability or active or
passive negligence of Schluter Systems, and regardless of legal theory, whether in contract, tort, extra-contractual or other. This Limited Warranty further excludes any loss
or damage arising out of or otherwise connected to: acts of war, terrorism, fire, explosion, natural disaster, acts of God, any failure to comply with the Written Materials,
inadequate subfloor/substrate, improper preparation or other failure of subfloor/substrate, faulty or negligent penetration of the Products or subfloor/substrate, intentional
acts of destruction, structural failure, misuse of or failure to maintain the Products, normal wear and tear, scratches, dents, corrosion or discoloration (whether caused by
excessive heat, chemical cleaning products, abrasive agents or otherwise), efflorescence and shading which are a natural occurrence with cementitious materials and are
not considered a defective condition for the purposes of this Limited Warranty, variations of texture, color or shade from those on product samples, packaging materials
or other marketing materials, or other causes unrelated to the Products (e.g. excess point loading, overvoltage). This Limited Warranty excludes exterior applications,
unless specifically approved in writing on a case by case basis by the Schluter Systems Technical Services Director.
This Limited Warranty is conditioned and will be considered null and void and Schluter Systems will have the right to refuse any claims if: (a) the Products have been
improperly stored or installed, (b) any component comprising a Schluter® DITRA-HEAT System has been altered or otherwise modified in any way, or (c) the Products
are subject to abusive or abnormal use, lack of maintenance, or used in a manner other than that for which the Products were designed or in any way contrary to the
Written Materials
DISCLAIMER: There are no warranties beyond this expressed warranty as stated herein. To the extent permitted by law, all other warranties, representations or
conditions, expressed or implied, are hereby disclaimed and excluded, including but not limited to the implied warranties of MERCHANTABILITY or FITNESS FOR A
PARTICULAR PURPOSE (as limited to such purposes as described in the Written Materials) or arising from a course of dealing, usage of trade or otherwise by law.
ANY IMPLIED WARRANTIES ARISING BY OPERATION OF LAW ARE LIMITED IN DURATION TO THE TERM OF THIS LIMITED WARRANTY. NO REPRESENTATION,
PROMISE, AFFIRMATION OR STATEMENT BY ANY EMPLOYEE OR AGENT OF SCHLUTER SYSTEMS WILL BE ENFORCEABLE AGAINST SCHLUTER SYSTEMS
UNLESS IT IS SPECIFICALLY INCLUDED IN THIS LIMITED WARRANTY OR AUTHORIZED IN WRITING BY THE SCHLUTER SYSTEMS TECHNICAL SERVICES
DIRECTOR. This Limited Warranty is given in lieu of any other warranty, whether expressed or implied. The remedies contained herein are the only remedies available for
breach of this Limited Warranty. Schluter Systems excludes and in no event shall have any liability for any indirect, special, incidental, punitive, exemplary, or consequential
damages, including lost profits, arising out of or otherwise connected to failure of a DITRA-HEAT System. This Limited Warranty extends only to the Owner and is not
transferable or assignable unless authorized by written agreement and signed by the Schluter Systems Technical Services Director or otherwise prohibited by specific
state or provincial law. This Limited Warranty gives you specific legal rights; some states and provinces do not allow disclaimers or other restrictions of implied warranties;
some of the above disclaimers may not apply to you. No changes or modifications of any terms or conditions of this Limited Warranty are permitted unless
duly authorized in writing by the Schluter Systems Technical Services Director. This Limited Warranty shall supersede and replace any and all prior oral or written
warranties, agreements, or other representations made by or on behalf of Schluter Systems relative to the Products or the application of the Products and shall apply to
any installation occurring on or after August 1, 2017. For the most current information and materials regarding Schluter Systems warranties and programs, please visit
https://www.schluter.com/schluter-us/en_US/downloadfiles.
MAKING A CLAIM: To make a claim under this Limited Warranty, the Owner must provide Schluter Systems with written notice within thirty (30) days of any alleged
defect in the Products covered by this Limited Warranty, together with date and proof of purchase of such Products and/or all of its components and name and address
of all installers and all invoices related to the original installation, failing which this Limited Warranty shall have no legal effect. Schluter Systems reserves the right at its
election and as a condition of this Limited Warranty to inspect the alleged failed and/or defective Products.
All U.S. Claims shall be sent to:
Schluter Systems L.P.
Attn: Warranty Claims Dept.
194 Pleasant Ridge Road
Plattsburgh, NY 12901
1
2
All Canadian Claims shall be sent to:
Schluter Systems (Canada), Inc.
Attn: Warranty Claims Dept.
21100 chemin Ste-Marie
Ste-Anne-de-Bellevue, QC H9X 3Y8
If there are any conflicting terms between any Written Materials, the most recently updated document shall be deemed to control.
This Limited Warranty is limited to sales of the Products made in and intended for use in the United States and Canada. For the purposes of this Limited Warranty,
Schluter Systems L.P. shall offer warranty coverage to Owners located in the United States, and Schluter Systems (Canada) Inc. shall offer warranty coverage to Owners
located in Canada.
42
WARRANTIES
Schluter®-Systems Lifetime Thin-Set System Extended Limited Warranty
LIMITED WARRANTY COVERAGE: Subject to the conditions and limitations as stated in this Lifetime Thin-Set System Extended Limited Warranty (the
“Limited Warranty”), Schluter Systems warrants that a Thin-Set System (defined hereafter) will be free from manufacturing defects and will perform as described in
the applicable installation handbook(s) and/or technical data sheet(s) (collectively, the “Written Materials1” ) for the lifetime (defined hereafter) of such Thin-Set System
when installed in a Residential or Commercial application (defined hereafter) and used in accordance with the terms and conditions of the Written Materials and industry
standard guidelines that are not in conflict with the Written Materials in effect at the time of installation. In order to extend warranty coverage for Schluter® DITRA® or
DITRA®-XL uncoupling membranes, Schluter®-Shower System, Schluter® KERDI® or KERDI®-DS waterproofing membranes, or Schluter® DITRA-HEAT™ or Schluter®
DITRA-HEAT-DUO™ uncoupling membrane to lifetime coverage under this Lifetime Thin-Set System Extended Limited Warranty, Owner must complete and submit the
Thin-Set System Registration to Schluter Systems, available at www.schluter.com, or submit proof of purchase and installation information (including installation date,
installer’s name and address) to Schluter Systems at the address provided hereafter within ninety (90) days of installation. Note: Please retain Schluter® Thin-set Mortar
Lot/Batch Number(s) for Lifetime Warranty Registration. These numbers are required for completion of the warranty registration process.
For the purposes of this Limited Warranty, a “Thin-Set System” is defined as Schluter® DITRA® or DITRA®-XL uncoupling membranes, Schluter®-Shower System,
Schluter®-KERDI®-BOARD within a Schluter®-Shower System, Schluter® KERDI® or KERDI®-DS waterproofing membranes, or Schluter® DITRA-HEAT™ or Schluter®
DITRA-HEAT-DUO™ uncoupling membrane installed with Schluter SET®, Schluter ALL-SET®, or Schluter FAST-SET® thin-set mortar; “Owner” is defined as the original
end user of the property in which a Thin-Set System is installed; “Lifetime” is defined as that period of time that the original Thin-Set System installation remains
unchanged and under the ownership of the Owner; “Residential” applications are defined to include Thin-Set System installations in single family detached residential
dwellings; and “Commercial” applications are defined to include Thin-Set System installations in multi-family residential dwellings (e.g., apartments, condominiums,
cooperatives, and timeshares). Thin-Set System installations in public places, commercial establishments and other applications may be afforded lifetime coverage
under this Limited Warranty on a case by case basis as determined by the Schluter Systems Technical Services Director.
This Limited Warranty is only applicable to installations in the United States of America and Canada. Schluter Systems is not responsible or liable under any
circumstances for determining the suitability of a Thin-Set System for the Owner’s intended purpose. It is the responsibility of the Owner to consult with an experienced
and professional installer to ensure the suitability of a Thin-Set System, subfloor/substrate and all building materials in the installation and that the Written Materials are
followed properly.
RESOLUTION: If a Thin-Set System is installed and used in accordance with the terms and conditions as described hereinabove and such Thin-Set System is proven
defective within the applicable warranty term, the Owner’s exclusive remedy and the sole obligation of Schluter Systems, at its election, shall be to (a) reinstall or
replace the failed portion of the Thin-Set System or (b) pay an amount not to exceed the original square foot cost of the installation of the Thin-Set System verified to
be defective. Due to conditions beyond the control of Schluter Systems (e.g., color and shade availability, discontinuation, normal wear and tear), Schluter Systems
cannot guarantee or warrant an exact match to the specific tile, stone, or other flooring materials used in the original installation. In such event, substantially similar
materials may be substituted.
EXCLUSIONS FROM COVERAGE: This Limited Warranty excludes and in no event shall Schluter Systems have any liability for any indirect, special, incidental,
punitive, exemplary, or consequential damages, including lost profits, arising out of or otherwise connected to the failure of a Thin-Set System, regardless of any strict
liability or active or passive negligence of Schluter Systems, and regardless of legal theory, whether in contract, tort, extra-contractual or other. This Limited Warranty
further excludes any loss or damage arising out of or otherwise connected to: acts of war, terrorism, fire, explosion, natural disaster, acts of God, any failure to comply
with the Written Materials, inadequate subfloor/substrate, improper preparation or other failure of subfloor/substrate, faulty or negligent penetration of a Thin-Set
System or subfloor/substrate, intentional acts of destruction, structural failure, misuse of or failure to maintain a Thin-Set System, normal wear and tear, scratches,
dents, corrosion or discoloration (whether caused by excessive heat, chemical cleaning products, abrasive agents or otherwise), efflorescence and shading which are
a natural occurrence with cementitious materials and are not considered a defective condition for the purposes of this Limited Warranty, variations of texture, color or
shade from those on product samples, packaging materials or other marketing materials, or other causes unrelated to a Thin-Set System (e.g. surface covering failure,
excess point loading, overvoltage). This Limited Warranty excludes exterior, submerged and steam room applications and further excludes applications using glass tile,
moisture sensitive stone, or other non-approved surface coverings, unless specifically approved in writing on a case by case basis by the Schluter Systems Technical
Services Director. Schluter® DITRA-HEAT™-E-HK heating cables and Schluter® DITRA-HEAT™-E thermostats are specifically excluded from coverage under this
Limited Warranty. Any substitution of a non-Schluter Systems product for a Schluter Systems component in a Thin-Set System voids this Limited Warranty.
DISCLAIMER: There are no warranties beyond this expressed warranty as stated herein. To the extent permitted by law, all other warranties, representations or
conditions, expressed or implied, are hereby disclaimed and excluded, including but not limited to the implied warranties of MERCHANTABILITY or FITNESS FOR A
PARTICULAR PURPOSE (as limited to such purposes as described in the Written Materials) or arising from a course of dealing, usage of trade or otherwise by law.
ANY IMPLIED WARRANTIES ARISING BY OPERATION OF LAW ARE LIMITED IN DURATION TO THE TERM OF THIS LIMITED WARRANTY. NO REPRESENTATION,
PROMISE, AFFIRMATION OR STATEMENT BY ANY EMPLOYEE OR AGENT OF SCHLUTER SYSTEMS WILL BE ENFORCEABLE AGAINST SCHLUTER SYSTEMS
UNLESS IT IS SPECIFICALLY INCLUDED IN THIS LIMITED WARRANTY OR AUTHORIZED IN WRITING BY THE SCHLUTER SYSTEMS TECHNICAL SERVICES
DIRECTOR. This Limited Warranty is given in lieu of any other warranty, whether expressed or implied. The remedies contained herein are the only remedies available
for breach of this Limited Warranty. Schluter Systems excludes and in no event shall have any liability for any indirect, special, incidental, punitive, exemplary, or
consequential damages, including lost profits, arising out of or otherwise connected to failure of a Thin-Set System. This Limited Warranty extends only to the Owner
and is not transferable or assignable unless authorized by written agreement and signed by the Schluter Systems Technical Services Director or otherwise prohibited
by specific state or provincial law. This Limited Warranty gives you specific legal rights; some states and provinces do not allow disclaimers or other restrictions of
implied warranties; some of the above disclaimers may not apply to you. No changes or modifications of any terms or conditions of this Limited Warranty are
permitted unless duly authorized in writing by the Schluter Systems Technical Services Director. This Limited Warranty shall supersede and replace any and
all prior oral or written warranties, agreements, or other representations made by or on behalf of Schluter Systems relative to a Thin-Set System or the application of a
Thin-Set System and shall apply to any installation occurring on or after March 13, 2019. For the most current information and materials regarding Schluter Systems
warranties and programs, please visit https://www.schluter.com/schluter-us/en_US/downloadfiles.
MAKING A CLAIM: To make a claim under this Limited Warranty, the Owner must provide Schluter Systems with written notice within thirty (30) days of any alleged
defect in a Thin-Set System covered by this Limited Warranty, together with date and proof of purchase of such Thin-Set System and/or all of its components and name
and address of all installers and all invoices related to the original installation, failing which this Limited Warranty shall have no legal effect . Schluter Systems reserves
the right at its election and as a condition of this Limited Warranty to inspect the alleged failed and/or defective Thin-Set System.
All U.S. Claims shall be sent to: Schluter Systems L.P.
Attn: Warranty Claims Dept.
194 Pleasant Ridge Road
Plattsburgh, NY 12901-5841 All Canadian Claims shall be sent to:
Schluter Systems (Canada), Inc.
Attn: Warranty Claims Dept.
21100 chemin Ste-Marie
Ste-Anne-de-Bellevue, QC H9X 3Y8
If there are any conflicting terms between any Written Materials, the most recently updated document shall be deemed to control.
In the event that Owner fails to provide such required invoices relating to the original installation, Schluter Systems shall pay Owner an amount equal to the average, reasonable costs of a comparable
installation. If the parties fail to agree on such amount, such dispute shall promptly, and in the first instance, be submitted: (a) if a U.S. claim, to arbitration in Clinton County, New York, in accordance with the
rules of the American Arbitration Association, or (b) if a Canadian claim, in the Province of Quebec, Canada, in accordance with the ADRIC Arbitration Rules. Any outcome of such arbitration proceeding shall be
final and binding upon the parties hereto.
1
2
WARRANTIES
43
=
Labor and materials are covered
when Schluter® heating cables are
installed with DITRA-HEAT.
See complete warranty on page 40.
554508
12/2019
© 2019 Schluter Systems L.P.
+
System warranty!
Schluter Systems L.P. • 194 Pleasant Ridge Road, Plattsburgh, NY 12901-5841 • Tel.: 800-472-4588 • Fax: 800-477-9783
Schluter Systems (Canada) Inc. • 21100 chemin Ste-Marie, Ste-Anne-de-Bellevue, QC H9X 3Y8 • Tel.: 800-667-8746 • Fax: 877-667-2410
www.schluter.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement