A.O. Smith R2VR-180E Signature 240-Volt 18-kW 1.6-GPM Tankless Electric Water Heater Use & care guide
Show HTML Add to My manuals36 Pages
A.O. Smith R2VR-180E is an electric tankless water heater that provides an endless supply of hot water without waiting. It is designed for residential use and can be installed indoors or outdoors. The R2VR-180E has a compact design and is easy to install. It is also energy-efficient and can save you money on your energy bills. With a flow rate of 1.8 gallons per minute, it is ideal for homes with up to 2 bathrooms.
advertisement
Installa on Instruc ons and Use & Care Guide
Electric Tankless
Water Heater
PLEASE DO NOT RETURN THIS UNIT TO THE
STORE.
Read this manual and the labels on the water heater before you install, operate, or service it. If you have di ffi aren’t sure you can safely and properly do any of this work yourself:
• Call our Technical Support Hotline:
We can help you with installation, operations, troubleshooting, or
maintenance. Before you call, write down the model and serial number from
the water heater’s data plate.
house and other property, and present risks including fi re, scalding, electric shock, and explosion, causing serious injury or death.
ENTER
°F
°C
ENTER
°F
°C
Table of Contents ..............................Page
IMPORTANT SAFETY INFORMATION ............................. 2
GENERAL INFORMATION ............................................... 5
INSTALLATION ............................................................... 11
OPERATION ................................................................... 15
TROUBLESHOOTING .................................................... 17
SERVICE ......................................................................... 22
WIRING DIAGRAMS ..................................................... 29
APPENDIX ...................................................................... 34
Keep this manual near the water heater for future reference whenever maintenance, adjustment or service is required.
Retain your original receipt as proof of purchase.
0618
100306524_2000558984 (REV. A)
IMPORTANT SAFETY INFORMATION
Read and follow all safety messages and instruc ons in this manual.
This is the safety alert symbol. It is used to alert you to poten al physical injury hazards. Obey all safety messages that follow this symbol to avoid possible property damage, serious injury or death. Do not remove any permanent instruc ons, labels, or the data plate from either the outside of the water heater or on the inside of the access panels. Keep this manual near the water heater.
Important informa on to keep...
Fill out this sec on and keep this manual for reference.
Date Purchased:
Model number:
Serial number:
DANGER
WARNING
CAUTION
NOTICE
DANGER indicates hazardous situa on that, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situa on that, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situa on that, if not avoided, could result in minor or moderate injury.
NOTICE indicates prac ces not related to physical injury.
Maintenance performed: Date:
2 • Electric Tankless Water Heater
T o reduce the risk of property damage, serious injury or death, read and follow the precau ons below, all labels on the water heater, and the safety messages and instruc ons throughout this manual.
General Requirements
• Install and properly ground the unit in accordance with local codes, or in the absence of local codes, with the current edition of the National Electrical Code:
ANSI/NFPA 70 in the USA or
CSA standard C22.1 Canadian
Electrical Code, Part 1 in Canada.
• Follow all applicable plumbing, heating, and air conditioning codes during installation.
RISKS DURING INSTALLATION
AND MAINTENANCE
WARNING
Electric Shock Risk
Contact with the electrical parts inside the water heater can result in severe injury or death from electrical shock:
• Disconnect power by opening the circuit breaker(s) before installing or servicing.
• SOME MODELS ARE CONNECTED
TO MORE THAN ONE BRANCH
CIRCUIT, AND MORE THAN ONE
DISCONNECT SWITCH MAY BE
REQUIRED TO DE ENERGIZE THE
EQUIPMENT. ALL BRANCH CIR
CUITS MUST BE DISCONNECTED
PRIOR TO SERVICE.
• Use a non-contact circuit tester to confirm that power is off before working on or near any electrical parts.
• Be sure the cover is reinstalled and secured after servicing to reduce the risk of fire and electric shock.
RISKS DURING OPERATION
WARNING
Scalding Risk
This water heater can make water hot enough to cause severe burns instantly, resulting in severe injury or death.
• Feel water before bathing or s howering.
• To reduce the risk of scalding, install Thermostatic Mixing
Valves (temperature limiting valves) at each point of use.
These valves automatically mix hot and cold water to limit the temperature at the tap. Mixing valves are available at your local hardware store or from your plumbing supplier. Follow the manufacturer’s instructions for installation and adjustment of the valves.
• For all models, the temperature set point is factory set to 120°F to reduce the risk of scalding.
Exception: single chamber (pointof-use) models are factory set to approximately 105°F.
• Higher temperatures increase the risk of scalding, but even at
120°F, hot water can scald. If you choose a higher temperature,
Thermostatic Mixing Valves located at each point of use are particularly important to help avoid scalding.
Temperature Time to Produce a
Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 1½ to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 1½ seconds
155°F (68°C) About 1 second
For information about changing the factory temperature setting, refer to
“Water Temperature Adjustment” on page 15.
Even if you set the water heater set point to a low se ng, higher temperatures may occur in certain circumstances:
• Water temperature will be hotter if someone adjusted the temperature set point to a higher setting.
• If the water supplied to the water heater is pre-heated (for example, by another water heater), the temperature of the water may be higher than the temperature set point.
• Problems with the UIM (user interface on two- or four-chamber models) or other malfunctions may result in higher than expected water temperatures.
To reduce the risk of unusually hot water reaching the fi xtures in the house, install Thermosta c Mixing Valves at each point of use.
If anyone in your home is at par cular risk of scalding (for example, the elderly, children, or people with disabili-
es) or if there is a local code or state law requiring a certain water temperature at the hot water tap, then these
Electric Tankless Water Heater • 3
precau ons are par cularly important.
According to a na onal standard, American Society of Sanitary Engineering
(ASSE 1070), and most local plumbing codes, the water heater’s temperature set point should not be used as the sole means to regulate water temperature and avoid scalds.
Properly adjusted Thermosta c Mixing
Valves installed at each point of use allow you to set the water heater’s set point to a higher se ng without increasing the risk of scalds. A higher temperature can help provide proper water temperatures for appliances such as dishwashers and washing machines. could cause a fire risk. If the water heater is subjected to flood conditions or has been submerged in water, the entire water heater must be replaced.
• Make electrical connections properly according to the instructions on page 13. Use a UL listed or CSA approved strain relief. Connect the ground wire to the ground lug. (The ground lug is identified by a green and white ground label inside the water heater.)
Water Contamination Risk
Do not use chemicals that could contaminate the potable water supply. Do not use piping that has been treated with chromates, boiler seal, or other chemicals.
WARNING
Fire Risk
To reduce the risk of a fire that could destroy your home and seriously injure or kill people:
• D o not store things that can burn easily such as paper or clothes next to the water heater.
• Be sure the water heater’s cover is in place. This cover keeps debris from entering and potentially being ignited, and helps keep any internal fires from spreading.
• Keep the water heater from becoming wet. Immediately shut the water heater off and have it inspected by a qualified person if you find that the wiring or control board have been exposed to water in any way
(e.g., leaks from plumbing or leaks from the water heater itself). Such leaks can damage property and
4 • Electric Tankless Water Heater
GENERAL INFORMATION
Introduction
• This manual provides information necessary for the installation, operation, and maintenance of the water heater.
• The model description is listed on the rating plate which is attached to the side panel of the water heater.
• Please read all installation instructions completely before installing this product.
• If you have any problems or questions regarding this equipment, consult the manufacturer or its local representative.
This appliance is an on-demand, electric tankless water heater. It is designed to efficiently supply endless hot water for your needs.
A built-in alarm is included. If water leaks inside your electric water heater, an alarm will sound to provide warning. Simply turn off power to the water heater at the circuit breakers, turn off the water supply, then correct the leak.
Your water heater also includes on-board self diagnostics. If the system produces an error code, see
“Troubleshooting” on one of the following pages:
• Point-of-use models: page 17.
• Two- or four-chamber models: page 19.
Component
Descriptions
Temperature and Pressure
Relief Valve
In most cases, you are not required to install a temperature and pressure relief valve (T&P valve). However, some local codes do require the installation of a T&P Valve. If a T&P valve must be installed, install it on the hot outlet pipe according to the valve manufacturer’s instructions and local code.
If you install a T&P valve, turn on the water supply to ensure that no water drips from it. Next, operate the valve manually two or three times to purge the trapped air from the top of the heater’s chamber, then close the valve. Verify that water has stopped flowing completely before connecting the discharge pipe to the valve.
NOTICE: If a temperature and pressure relief valve is installed, it must be piped by minimum 1 inch pipe to a suitable drain capable of discharging 10 GPM. A splash cover must be included to protect the area of attachment to the wall. The manufacturer will not be responsible for any water damage that may occur.
WARNING! Do not cap or plug the
T&P relief valve or discharge pipe.
Component Identification: Point-of-Use Models (RPV, CPV)
OUTLET INLET
Heating Element
(Behind inlet/outlet)
Thermistor* Connections
T-Aux Auxiliary thermistor
T-In Inlet thermistor
T-Out Outlet thermistor
T-Aux
T-In
T-Out
Outlet Thermistor *
(Connects to T-Out)
Auxiliary Thermistor *
(Connects to T-Aux)
Inlet Thermistor *
(Connects to T-In)
TERMINAL
BLOCK
POWER
SUPPLY
* Often referred to as a temperature sensor.
Continued on the next page...
Electric Tankless Water Heater • 5
Component Identification: Two-Chamber Models (R2V, C2V)
OUTLET INLET
HEATING ELEMENTS
NOTICE:
The user interface is described in Figure 7, page 16.
Intermediate
Thermistor *
(connects to
TH-1)
TH-1
TH-2
TH-IN
Thermistor* Connections
TH-IN Inlet thermistor
TH-1 Intermediate thermistor
TH-2 Outlet thermistor
Access Plate
(for draining)
L1
L2
* Often referred to as a temperature sensor.
Outlet Thermistor *
(connects to TH-2)
Inlet Thermistor *
(connects to TH-IN)
Component Identification: Four-Chamber Models (R4L, C4L, R4M, C4M)
OUTLET Intermediate
Thermistor *
(connects to
TH-2)
Element Element
Intermediate
Thermistor *
(connects to
TH-1)
Element Element
NOTICE:
The user interface is described in Figure 7, page 16.
INLET
TH-1
TH-2
TH-3
TH-4
TH-IN
Thermistor* Connections
TH-IN Inlet thermistor.
TH-1 Intermediate thermistor
TH-2 Intermediate thermistor
TH-3 Intermediate thermistor
TH-4 Outlet thermistor
* Often referred to as a temperature sensor.
Outlet Thermistor *
May be located on outlet elbow.
(connects to TH-4)
L1
L2
L1
L2
Access Plates
(for draining)
Intermediate Thermistor *
(connects to TH-3)
Inlet Thermistor *
(connects to TH-IN)
6 • Electric Tankless Water Heater
General Specifications
Models
Point-of-Use:
RPV, CPV
Two Chamber:
R2V, C2V
Four Chamber:
R4L, C4L, R4M, C4M
Wiring & Circuit Breaker
Requirements
Water Connections
Weight lbs. (kg)
Water Heater
Dimensions*
3/4” NPT
8 lbs. (3.6 kg)
See “Electrical Requirements” on page 8.
3/4” NPT
13 lbs. (5.9 kg)
3/4” NPT
20 lbs. (9 kg)
H 16-5/8” x W 6-1/2” x D 7-3/16”
(H 42.2cm x W 16.5cm x D 18.3 cm)
H 17-3/4” x W 11-1/2” x D 6-1/8”
(H 45.1 cm x W 29.2 cm x D 15.6 cm)
H 18-1/8” x W 17” x D 6-1/8”
(H 46 cm x W 43.2 cm x D 15.6 cm)
* Height dimension includes the distance from the bottom of the heater to the highest point of the inlet/outlet.
Width dimension includes the mounting tabs on the left-hand and right-hand sides (two- and four-chamber models).
NOTE:
• Check the rating plate to ensure this product matches your specifications.
• The manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
• The maximum working pressure is 150 psi. The water supply pressure should not exceed 80 psi. If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line.
• Maximum flow may require water pressure equal to or greater than 40 psi.
Electric Tankless Water Heater • 7
Electrical Requirements
• Follow these steps to determine the electrical requirements for your water heater:
1.) Find your model number on your water heater’s rating plate.
2.) Locate that model number in one of the tables listed below.
For example, if your model is RPVA-24-K5 , find *P**-24-K5 in the appropriate table.
Models within each table are sorted by Voltage first, then by Wattage per Element (KW) .
• Follow the requirements listed for your model.
□ Point-of-use models are listed below.
□ Two-chamber models: page 9.
□ Four-chamber models: page 10.
• Use copper conductors only.
Model
Point-of-Use Models
(For potable water heating only. Not for space heating.)
NOTICE: Models sorted by Voltage , then by Wattage per Element .
Recommended
Breaker Size
(Amps)
Voltage Number of
Elements
Wattage per Element
(KW)
Current per
Breaker
(Amps)
Recommended
Wire Size
(AWG)
*
25 120 1 2.4
20.00
10
30 120 1 3 25.00
10
Element Type
*P**-24-K5
*P**-30-K5
*P**-35-K5
*P**-40-X5
*P**-78-X5
*P**-35-E5
30
20
40
20
120
208
208
240 ‡
1
1
1
1
3.5
4
8
3.5
29.17
19.23
37.5
14.58
10
12
8
12
Single
Single
Single
Single
Single
Single
*P**-45-E5
*P**-55-E5
*P**-70-E5
*P**-80-E5
*P**-90-E5
20
25
30
40
40
240 ‡
240
‡
240
‡
240
‡
240
‡
240
‡
1
1
1
1
1
4.5
5.5
7
8
9
18.75
22.92
29.17
33.33
37.50
12
10
10
8
8
Single
Single
Single
Single
Single
*P**-120-E5 60 1 12 50 6
† Dual
*P**-30-Y5 15 277 1 3 10.83
14
* All wiring/conductors must be rated for 90°C or greater.
† Maximum recommended wire size is #6 cu AWG.
‡ This model may used with a 208 VAC supply. Use of 208 VAC may require different breaker and/or wire sizes.
Follow all code requirements.
Single
8 • Electric Tankless Water Heater
Model
Point-of-Use Models
(For potable water heating only. Not for space heating.)
NOTICE: Models sorted by Voltage , then by Wattage per Element .
Recommended
Breaker Size
(Amps)
Voltage Number of
Elements
Wattage per Element
(KW)
Current per
Breaker
(Amps)
Recommended
Wire Size *
(AWG)
20 277 1 4 14.44
12
Element Type
*P**-40-Y5
*P**-60-Y5 25 277 1 6 21.66
10
Single
Single
*P**-73-Y5 30 277 1 7.3
26.35
10 Single
*P**-90-Y5 40 277 1 9 32.49
8
* All wiring/conductors must be rated for 90°C or greater.
† Maximum recommended wire size is #6 cu AWG.
‡ This model may used with a 208 VAC supply. Use of 208 VAC may require different breaker and/or wire sizes.
Follow all code requirements.
Single
Model
Two-Chamber Models
(For potable water heating only. Not for space heating.)
NOTICE: Models sorted by Voltage , then by Wattage per Element .
Recommended
Breaker Size
(Amps)
Voltage Number of
Elements
Wattage per
Element (KW)
Current per
Breaker
(Amps)
Recommended
Wire Size *
(AWG)
Element
Type
208 2 7 33.65
8 Single
*2**-140-X5
40 amps each
(2 circuits)
*2**-120-E5
60 amps
*2**-140-E5
60 amps
*2**-160-E5
40 amps each
(2 circuits)
*2**-180-E5
40 amps each
(2 circuits)
240
240
240
240
2
2
2
2
6.1
7
8
9
50
58.34
33.33
37.5
6 †
6 †
8
8
Single
Single
Single
Single
* All wiring/conductors must be rated for 90°C or greater.
† Maximum recommended wire size is #6 cu AWG.
Electric Tankless Water Heater • 9
Model
*4**-280-X5
*4**-180-E5
*4**-220-E5
*4**-240-E5
*4**-280-E5
*4**-320-E5
Four-Chamber Models (Single Phase)
For potable water heating only. Not for space heating.
NOTICE: Models sorted by Voltage , then by Wattage per Element .
Recommended
Breaker Size
(Amps)
Voltage Number of
Elements
Wattage per
Element (KW)
Current per
Breaker
(Amps)
Recommended
Wire Size *
(AWG)
Element
Type
208 4 7 67.31
6
† Single 70 amps each
(2 cirucits)
40 amps each
(2 circuits)
50 amps each
(2 circuits)
60 amps each
(2 circuits)
60 amps each
(2 circuits)
70 amps each
(2 circuits)
240
240
240
240
240
4
4
4
4
4
4.5
5.5
6
7
8
37.50
45.83
50.00
58.33
66.67
8
6
6 †
6
†
6
†
Single
Single
Single
Single
Single
* All wiring/conductors must be rated for 90°C or greater.
† Maximum recommended wire size is #6 cu AWG.
10 • Electric Tankless Water Heater
INSTALLATION
Getting Started
electrical wires that will enter the heater from the side.
Clearances
See Figure 1 or Figure 2.
Top Clearance: A minimum of 12 inches (30.5 cm) is required for removal and maintenance of heating elements and to provide access for plumbing connections.
Bottom Clearance: At a minimum, maintain a bottom clearance of 8 inches (20.3 cm) for single chamber models or 15 inches (38.1 cm) for 2- or
4-chamber models. Do not store any items underneath the water heater.
Side Clearance: Allow an 8 inch (20.3 cm) minimum horizontal space for the heater. This horizontal clearance will allow for the removal of protective cover screws and provide access to
Figure 1.
Wall
Side View
Front Clearance:
15” + (38.1 cm +)
12”
(30.5 cm)
2-Chamber or
4-Chamber
Water Heater
Front Clearance: Maintain a minimum clearance of 8 inches (20.3 cm). In the absence of a door or removable access panel in front of the heater, allow a minimum of 15 inches (38.1 cm) front clearance. This will allow for cover removal and ease of service. See
Figure 1 or Figure 2.
Front
View
Wall or adjacent object
Install one
ƐƚĂŶĚŽīďƵŵƉĞƌĂƚ each corner.
;ϰƚŽƚĂů͖ƉƌŽǀŝĚĞĚ͘Ϳ
Figure 2.
Wall
Side View
8”
(20.3 cm)
12”
(30.5 cm)
Single
Chamber
Water Heater
Front
View
8”
(20.3 cm)
ENTER
°F
°C
8”
(20.3 cm)
Minimum Clearances
15”+
( 38.1 cm +)
8”
(20.3 cm)
Front Clearance:
15” + (38.1 cm +)
NOTICE: Point-of-use models may be mounted horizontally. See Figure 3, page 12.
Maintain 12” (30.5 cm) MIN. clearance at
8”+
(20.3 cm +) inlet/outlet.)
Minimum Clearances
Wall or adjacent object
Code Compliance
• Install and properly ground the unit in accordance with local codes, or in the absence of local codes, with the current edition of the National Electrical Code:
ANSI/NFPA 70 in the USA or
CSA standard C22.1 Canadian
Electrical Code, Part 1 in Canada.
• Follow all other applicable plumbing, heating, and air conditioning codes during installation.
• Your water heater is designed to be installed indoors only.
• Locate your water heater in a clean, dry area that is as close to the point of use as possible. Do not install it in a bath enclosure or shower stall.
• Your water heater and water lines must be protected from freezing.
Do not install your water heater where it may be subjected to freezing temperatures.
• Avoid locations that are prone to dampness, high humidity, moisture, or dust. Such locations include crawl space under a house or building, in the garage (in regions prone to high humidity) and in the attic (unless the attic has been converted to a living space).
• Locate your water heater where it will not be accessible to children.
WARNING! This water heater can make water hot enough to cause severe burns instantly, resulting in severe injury or death.
• Be sure that your water heater is accessible and that minimum
Electric Tankless Water Heater • 11
clearances are observed. Do not store any items underneath the water heater, and do not store flammable liquids or other flammable materials near the water heater. This is important for safety and future service. See
“Clearances” on page 11.
• Do not install your water heater underneath condensate lines.
• A drain pan, or other means of protection against water damage, is recommended to be installed under the water heater in case of leaks. In addition, you may install an active water leak detector with a shutoff valve which can turn off the water supply in the event of a leak. The manufacturer is not responsible for damage due to water leaks.
2 Mount Your
Water Heater
1. Unpack the heater from the shipping carton, but do not cut the shipping carton with a sharp instrument.
2. Stand the unit upright and remove the plastic wrap.
3. Remove the screws that secure the protective cover.
4. Remove the cover. If your water heater has a user interface display
(UIM) , unplug its ribbon cable from the control board in the water heater. (A UIM is shown in
Figure 7, page 16.)
NOTICE: Be sure to remember where to plug it back in later.
When the me comes to plug the connector back into the control board, it must be oriented correctly. We recommend marking the connector and board with a marker. You will then be able to align the marks later. See also
Figure 5, page 14.
5. If you have a point-of-use model, locate the four mounting holes in the back plate. (If you have a two- or four-chamber model, there are two mounting tabs on each side of your water heater.)
6. Two- or four-chamber water heaters only:
Apply one stando ff bumper to each corner on the back of the water heater. Stando ff s are provided. These stando ff s must be installed so the water heater can vent properly.
See Figure 1, page 11.
7. Determine the mounting location on the wall, then verify your clearances. (See “Clearances” on page 11.)
8. Position the unit against the wall.
Make sure that the unit is level.
NOTICE: Two-chamber and four-chamber models must be oriented with the inlet and outlet facing upward. However, point-of-use (POU) models may be oriented horizontally as described in Figure 3. To mount a POU water heater horizontally, follow the instructions on page
34.
9. Secure the water heater to the wall or other suitable structure with screws, bolts, or anchors as appropriate. Ensure that the mounting surface and fasteners will support the weight of the water heater. (You will reinstall the water heater’s protective cover later.)
Figure 3.
ĐĐĞƉƚĂďůĞŽƌŝĞŶƚĂƟŽŶƐĨŽƌ ŵŽƵŶƟŶŐĂƉŽŝŶƚͲŽĨͲƵƐĞ;WKhͿ water heater: sĞƌƟĐĂů
Horizontal
EKd/͗ ͻhƐĞŵŽƵŶƟŶŐďƌĂĐŬĞƚƐ;ƉƌŽǀŝĚĞĚͿ
ĨŽƌŚŽƌŝnjŽŶƚĂůŵŽƵŶƟŶŐ͘EŝƉƉůĞƐ ŵƵƐƚƉŽŝŶƚƚŽǁĂƌĚƚŚĞƌŝŐŚƚ͘ ͻdǁŽͲĐŚĂŵďĞƌĂŶĚĨŽƵƌͲĐŚĂŵďĞƌ ŵŽĚĞůƐŵƵƐƚďĞŽƌŝĞŶƚĞĚǁŝƚŚƚŚĞ
ŶŝƉƉůĞƐĨĂĐŝŶŐƵƉǁĂƌĚ;ǀĞƌƟĐĂůͿ͘
3
Connect the
Water Lines
NOTICE:
• DO NOT apply heat to the water lines, nipples, or any fitting on the water heater. Heat from soldering may damage the heat exchanger.
• Thread sealing tape (plumber’s tape) is the only sealer that may be used on the threads of the inlet and outlet fittings. DO
NOT use pipe dope or PVC/CPVC primer and glue on the threads of the inlet and outlet fittings.
Exposure to these compounds will damage the nipples, causing leaks.
• Use two wrenches when attaching the hot and cold water lines to
12 • Electric Tankless Water Heater
the heater. The second wrench must be used to hold the heater’s fittings securely because they are designed to turn freely.
• Flexible water supply hoses are recommended for your installation.
• Well water must be treated.
• Only potable water can be used with this water heater. Do not introduce pool or spa water, or any chemically treated water into the water heater.
• Do not connect to a saltregenerated water softener or a water supply of salt water.
• The warranty will not cover damage caused by water quality.
pressure: 50 to 60 psi. Higher pressures require a pressure reducing valve.
• Installations above the ceiling or in an attic require a bleed air separator.
• A properly-sized arrestor should be installed where water hammer exists.
NOTICE: Do not supply electrical power to your water heater yet. If you
Figure 4 .
Hot Cold do so at this point, you will damage your heating element(s).
1. Make sure that the water supply is turned off.
2. Connect the hot water line to the hot outlet of the water heater.
(Figure 4.)
3. Connect the cold water line to the cold inlet of the water heater.
(Figure 4.)
4. Open the valve on the main water line to supply water to the heater.
5. Open several hot water fixtures and allow water to run through the water heater for several minutes to purge air from the water lines.
6. Check for water leaks. Correct any that are found.
7. If you installed a T&P valve to meet local code requirements, operate it manually several times to allow any trapped air to escape.
NOTICE: Failure to purge air from the water lines can leave air pockets, causing damage to the heating elements when power is applied.
4 Install Electrical
Service
WARNING
Failure to observe these warnings could lead to an improper installation, and the risks include fire, electrical shock, and/or death:
• Installation must be performed by a qualified installer. The installer (licensed professional) is responsible for the correct installation of the water heater and for compliance with all national, state / provincial, and local codes.
• Refer to the electrical requirements and electrical schematic during installation and service.
• Turn off power service at the main circuit breaker(s) prior to installation. Working on an energized circuit can result in severe injury or death from electrical shock.
• Some models must be connected to more than one branch circuit, and more than one disconnect switch may be required to de-energize the equipment. All branch circuits must be disconnected during installa on or service.
• Install and properly ground the unit in accordance with local codes, or in the absence of local codes, with the current edition of the National Electrical Code:
ANSI/NFPA 70 in the USA or CSA standard C22.1 Canadian Electrical
Code, Part 1 in Canada.
NOTICE:
When using stranded wire, make sure that all strands are secure inside the terminal block. A loose strand can cause a short circuit and damage the circuit board.
1. Be sure the electrical power to the water heater is turned OFF at the circuit breaker panel (or remove the circuit’s fuses).
2. Using a non-contact circuit tester, check the wiring to make certain the power is OFF.
3. Check the water heater’s ra ng plate and ensure that the electrical service’s voltage, wiring size
Electric Tankless Water Heater • 13
(ampacity) and circuit breaker ra ng/type are correct for this water heater.
NOTICE: The electrical requirements for your model are listed in “Electrical Requirements” which starts on page 8.
4. Connect the electrical service as described in “Electrical
Requirements” (starting on page
8).
There is a wiring diagram label on the inside of your water heater’s protective cover. See also “Wiring
Diagrams” on page 29 of this manual.
5. Do the following:
□ Check all electrical connections to make sure that they are correct and secure.
□ Make sure that the supply voltage, wiring size (ampacity), circuit breaker rating and type are correct. (Refer to “Electrical
Requirements” which starts on page 8).
□ Label all breakers/connections to the water heater.
6. Ensure that all air has been purged from the water lines by opening several hot water fixtures near the water heater. Run water through the water heater until all air is purged from the lines.
7. Two- and four-chamber models only: Plug the connector end of the cover’s ribbon cable into the control board. See Figure 5.
(Plug it in where you see two rows of header pins close together, five pins in each row.) If necessary, refer to the “DISPLAY” callout in the wiring diagram for your model. (See “Wiring Diagrams” on page 29.)
If you marked the board and connector during earlier steps, align the marks when plugging the connector in.
NOTICE: The plug must be oriented correctly. If you plug it in backwards, it will not cause damage, but the display will not work.
If the display does not work a er you have completed installa on, follow these steps:
A.) Disconnect power at all branch circuits.
B.) Disconnect the plug.
C.) Rotate the plug 180 degrees, then plug it back in.
8. Reinstall the water heater’s cover.
WARNING! Be sure the cover is secured to reduce the risk of fi re and electric shock.
9. Turn on power to the water heater.
10. Verify proper operation.
Figure 5.
Ribbon Cable
Operating instructions are listed on page 15.
5
Test Water
Heater Operation
1. At nearby hot water faucets, turn water on medium-low.
□ You should hear a “click” as the heater’s relays engage.
□ You may hear a hissing or crackling noise from the heat exchanger after the unit begins to heat water. This is normal.
2. Check water at the fixtures to make sure that the water is being heated.
NOTICE:
Your water heater includes on-board self diagnos cs. If an error occurs, the system’s feedback will help you iden fy the issue. See “Troubleshoo ng” for more informa on (page 17 or 19).
Two- and four-chamber models only:
Red Band
“TX” Label
on Board
Ribbon Cable
Connector
Control Board
NOTICE:
When plugging the display
(User Interface Module) into the control board, orient it as shown in this graphic.
14 • Electric Tankless Water Heater
OPERATION
Water Temperature
Adjustment
WARNING
Scalding Risk
This water heater can make water hot enough to cause severe burns instantly, resulting in severe injury or death. Before a emp ng to adjust the temperature set point, read “RISKS DURING
OPERATION” on page 3. If the instruc ons are not clear, contact a quali fi ed service technician.
To adjust your temperature se ng, refer to one of the following procedures.
Point -of-use models only:
To adjust the temperature setting, turn the temperature adjustment knob as described below. This knob can be found at the top of the circuit board next to the plumbing connec-
ons. (Figure 6.)
The factory se ng is approximately
105°F (+/-1°F).
• To decrease the set temperature, turn the knob to the left (counter clockwise).
• To increase the set temperature, turn the knob to the right
(clockwise).
• Use a small flat blade screwdriver to turn the knob.
The water temperature set point can be adjusted within a range of 90°F
(32C) and 140°F (60 °C).
Two- or four-chamber models only:
The water temperature set point can be adjusted within a range of 90°F
(32C) and 140°F (60 °C).
To change the set temperature,
1. Press and release either the
UP or DOWN button (Figure 7, page 16). The display will blink and allow you to adjust the temperature set point.
2. Press and hold the UP or
DOWN button to scroll through the temperatures quickly.
Single presses will adjust the temperature setting one degree at a time.
3. Press the ENTER button to confirm.
Continued on the next page...
Figure 6.
POINT-OF-USE MODELS ONLY:
TEMPERATURE ADJUSTMENT KNOB ON INTERNAL CIRCUIT BOARD
PLUMBING CONNECTIONS
BEHIND CIRCUIT BOARD
TEMPERATURE ADJUSTMENT KNOB
• DECREASE SET TEMPERATURE:
TURN KNOB TOWARD LEFT
(COUNTER-CLOCKWISE )
• INCREASE SET TEMPERATURE:
TURN KNOB TOWARD RIGHT
(CLOCKWISE )
• USE A SMALL FLAT BLADE
SCREWDRIVER.
Electric Tankless Water Heater • 15
To toggle between Fahrenheit and
Celsius,
1. Press and hold the DOWN button for five seconds. See Figure 7.
2. The or °C LED will illuminate, and the 7-segment LED will display the temperature set point in the appropriate units.
hƉĂŶĚŽǁŶƵƩŽŶƐ
;ĂĚũƵƐƚƚŚĞƐĞƚƚĞŵƉĞƌĂƚƵƌĞͿ
En ƚĞƌďƵ on
;ƐĞƚͿ
Figure 7 .
Two and Four Chamber Models Only:
ENTER
°C dĞŵƉĞƌĂƚƵƌĞhŶŝƚƐ;
°F or °C
Ϳ
KŶĞǁŝůůďĞůŝƚŝĨƉŽǁĞƌƚŽƚŚĞ
ǁĂƚĞƌŚĞĂƚĞƌŝƐŽŶ͘ hƐĞƌ/ŶƚĞƌĨĂĐĞDŽĚƵůĞ;h/DͿ
16 • Electric Tankless Water Heater
TROUBLESHOOTING
Error Codes for Point-of-Use Models
If you have a two- or four-chamber model, see page 19.
WARNING
Electric Shock Risk
Contact with the electrical parts inside the water heater can result in severe injury or death from electrical shock:
• Disconnect power by opening the circuit breaker(s) or removing the fuses before installing or servicing.
• Some models are connected to more than one branch circuit, and more than one disconnect switch may be
required to de-energize the equipment. All branch circuits must be disconnected prior to service.
The LED on the circuit board will display a series of RED fl ashes, and each series of fl ashes represents one digit in the code. A er each sequence, the LED will fl ash GREEN . See the examples below. (Components are iden fi ed in Figure 8, page 18.)
NOTICE:
• There may be mul ple codes; verify all sequences.
• If you want to hear the fl ash code, press the mode bu on for two seconds. This will turn the audible beeper on. See Figure 8, page 18.
Examples from the Table Below:
Flash Code Sequence: 12/14 (Temperature Sensor Failure). The 12/14 code would be displayed like this:
1 2 / 1 4
1 red fl ash—pause—2 red fl ashes—pause—green fl ash—one red fl ash—pause—four red fl ashes—pause—green fl ash
Flash Code Sequence: 22 (Temperature Sensor Failure). The 22 code would be displayed like this:
2 2
2 red fl ashes—pause—two red fl ashes—pause—green fl ash
A er you iden fy the code, locate its descrip on and solu on in the table.
Flash Code
Sequence
12/14
22
13/16
14/16
12/13
11
Description
Temperature sensor failure
Temperature sensor shorted
Temperature sensor open
Disable switch open
17 High temperature shutdown
( This code will clear when the condi Ɵ on is corrected.)
Action / Solution
Turn o ff all power to the water heater.
Open a nearby hot water fi xture and allow water to run through the heater for about 5 minutes. Check the resistance of all temperature sensors (thermistors), then compare the readings. The failed sensor will be the one that has a resistance reading
(ohms) that is at least 10% to 15% di ff erent from all of the others.
Check wiring. Replace as necessary.
Check wiring. Replace as necessary.
Install the missing jumper(s) on the circuit board as shown in Figure 8, page 18. Both jumpers must be in place.
This code is triggered when the temperature of the water has exceeded the set point by more than 8°F. 1. Turn o ff all power to the water heater.
Open a nearby hot water fi xture and allow water to run through the heater for about 5 minutes. Check the resistance of the temperature sensors (thermistors). If one of the thermistors has a resistance that is much higher than the others, replace that thermistor. 2.
If the issue persists, the circuit board (control board) may need to be replaced.
Contact Technical Support.
Electric Tankless Water Heater • 17
Flash Code
Sequence
18
Description Action / Solution
21
23
22, 24, 25, 31,
32, 34, 35
Moisture detected
Level Detect
No temperature rise (water is not being heated su ffi
Data reading error
Shut o ff all power to the water heater. Check for water leaks. Correct any leaks found. Dry the control board completely before restoring power.
Ensure that the heater is fi lled with water and that there is no air trapped inside. Check the opera on of back fl ow preventer or check valve. If the heater is fi lled and there are no leaks, connect level detect spades on the circuit board to ground. If the code is accompanied by a clicking sound that is present when water is running, check the elements.
Check elements. Check temperature sensors. Check wiring and circuit breakers. Verify proper heater sizing. If necessary, reduce the unit temperature from maximum se ng and reduce fl ow rate with shut-o ff valve.
Reset the water heater. Turn o ff all circuit breakers to the heater for approx. 30 seconds. Turn on breakers. The LED should fl ash all green and the heater should produce hot water. If the code persists, reset the breakers again. If that does not work, test the temperature sensors. Replace the temperature sensors and/or circuit board as needed.
Figure 8 .
OPEN PINS (3) REQUIRED JUMPERS (2)
LED STATUS LAMP
INTERNAL CIRCUIT BOARD
PLUMBING CONNECTIONS
BEHIND CIRCUIT BOARD
TOP OF INTERNAL CIRCUIT BOARD
MODE BUTTON:
(PRESS FOR TWO
SECONDS TO TURN
AUDIBLE BEEPER
ON)
18 • Electric Tankless Water Heater
Error Codes for Two and Four Chamber Models
If you have a point-of-use model, see page 17.
WARNING
Electric Shock Risk
• Contact with the electrical parts inside the water heater can result in severe injury or death from electrical shock:
• Disconnect power by opening the circuit breaker(s) or removing the fuses before installing or servicing.
• Some models are connected to more than one branch circuit, and more than one disconnect switch may be
required to de-energize the equipment. All branch circuits must be disconnected prior to service.
Display
E02
E03
E04
E06
E10
E11
E12
E13
Description
Hardware determined that the heated water has exceeded the temperature limit.
Low water level in heater.
Action / Solution
Turn o ff power to the water heater. Contact Technical Support.
1. Turn off power to the water heater.
2. Turn on a nearby hot water faucet to flush air out of the water line.
3. When water runs uninterrupted from the hot water fixture, turn on power to the water heater.
Moisture/leak detected in heater. Turn o ff power and water supply to the water heater.
Contact Technical Support.
So ware determined that the water temperature is too high.
This error may appear when the unit is powered up. Turn on a hot water tap to run water through the water heater. The error should clear. If not, turn o ff the power to the water heater. Contact Technical Support.
Inlet temperature sensor is open.
Open thermistor.
2- and
4-Chamber models:
TH-1 open.
Point-of-use models:
T-Out open.
Open thermistor.
2-Chamber models:
Outlet thermistor open.
4-Chamber models:
TH-3 thermistor open.
1. Turn ff power to the water heater.
2. Check the connec ons of the thermistor in ques on.
3. Disconnect the thermistor, then reconnect it.
4. Turn on power to the water heater.
5. Does the error code reoccur? If yes, turn o ff power and replace the thermistor that is listed in the le -hand column. See “Thermistor
(Temperature Sensor) Replacement” on page 25.
4-Chamber models only:
TH-2 thermistor is open.
Continued on the next page...
Electric Tankless Water Heater • 19
E23
E24
E51
&
E52
Display
E14
E20
E21
E22
Description
4-Chamber models only:
Outlet thermistor open (TH-4).
Action / Solution
1. Turn power to the water heater.
2. Check the connec ons of the thermistor in ques on.
3. Disconnect the thermistor, then reconnect it.
4. Turn on power to the water heater.
5. Does the error code reoccur? If yes, turn o ff power and replace the thermistor that is listed in the le -hand column. See “Thermistor
(Temperature Sensor) Replacement” on page 25.
Inlet thermistor shorted.
Shorted thermistor.
2- and
4-Chamber models:
TH-1 shorted.
Point-of-use models:
T-Out shorted.
2-Chamber models:
TH-2 thermistor is shorted.
4-Chamber models:
TH-3 thermistor is shorted.
4-Chamber models only:
TH-2 thermistor is shorted.
4-Chamber models only:
TH-4 thermistor is shorted.
Replace the temperature sensor that is listed in the le -hand column.
See “Thermistor (Temperature Sensor) Replacement” on page 25.
Communica ons Failure. The user interface has lost connec on with the control board.
Turn o ff power to the water heater. Contact Technical Support.
20 • Electric Tankless Water Heater
General Troubleshooting
The following chart provides an overview of basic troubleshooting.
Symptom Possible Cause
Cold water used causes reverse flow through water heater.
Corrective Action
Install check valve on outlet.
Unit “clicks” periodically when no hot water is being used.
Hot water supply is warm, but it does not get hot.
Hot water supply is cold.
Hot water temperature fluctuates.
Unit has been in standby for an extended period with no hot water use.
Temperature set point too low.
Flow is too high.*
One of the main circuit breakers may be tripped. (For units with more than one branch circuit only.)
Failed heating element or temperature sensor.
Flow is too high.*
Replace element or sensor
(thermistor).
Reduce flow.
High temperature limit switch may be tripped.
Verify if limit switch is tripped. Reset if tripped.
The circuit breaker(s) may be tripped.
Check power panel. Reset breaker if tripped.
Failed heating element or temperature sensor.
Control board failure.
Flow is too high*
One of the main circuit breakers may be tripped. (For units with more than one branch circuit only.)
Failed heating element or temperature sensor.
NORMAL OPERATION. Unit will activate as needed to maintain a reference temperature to ensure quick start-up on next use.
Increase the temperature set point.
Reduce flow.
Check power panel. Reset breaker if tripped.
Replace element or sensor
(thermistor).
Contact Technical Support.
Reduce flow.
Check power panel. Reset breaker if tripped.
Replace element or sensor
(thermistor).
* If your water heater runs out of hot water too quickly, it may be too small for your needs. Consider replacing it with a larger model or adding additional heater(s) to meet flow demand. Please refer to the product specification sheet for proper flow rates based on incoming water temperature.
Electric Tankless Water Heater • 21
SERVICE
WARNING!
Electric Shock Risk
Servicing should be performed on this water heater only after it has been disconnected from the power supply circuit(s). Failure to do so can result in severe injury or death from electrical shock:
• Disconnect power by opening the circuit breaker or removing the fuses before installing or servicing.
• Some models are connected to more than one branch circuit, and more than one disconnect switch may be required to de-energize the equipment.
• All branch circuits must be disconnected prior to service.
• Use a non-contact circuit tester to confirm that power is off before working on or near any electrical parts.
• Replace the water heater’s cover after servicing to reduce the risk of fire and electric shock.
Element Removal and
Replacement
WARNING!
• Working on an energized circuit can result in severe injury or death from electrical shock. Turn power off.
• Some models are connected to more than one branch circuit.
Disconnect all branch circuits before servicing unit.
• Check wires with a non-contact circuit tester to make sure power is o ff . When you are fi nished, be sure all covers are secured to reduce the risk of fi re and electric shock.
NOTICE:
A built-in alarm is also included. If water leaks inside your electric water heater, an alarm will sound to provide warning. Simply turn off power to the water heater at the circuit breakers, turn off the water supply, then correct the leak.
Figure 9: Non-Contact circuit tester
If you are not comfortable replacing a hea ng element yourself, have this work done by a quali fi ed person. To replace the hea ng element, you’ll need the following tools and supplies:
• Phillips head screwdriver
• Adjustable wrench (for point-ofuse models)
• Pipe wrench or slip joint pliers (for point-of-use models only)
• 1-1/2 inch element wrench or adjustable wrench (for element removal; two- and four-chamber models)
• Bucket
• Rag
• Hair dryer or compressed air
1
Check your water heater’s data plate for the correct wattage and voltage. Verify that your new heating element has the correct wattage rating and is sized correctly for your water heater.
Figure 10: Heating elements
2
Figure 11: Installed heating
element
Con fi rm that power is o ff by checking the wires with a non-contact circuit tester.
3
4
Open a nearby hot water faucet and run the water until it is cool.
WARNING! To reduce the risk of scalding, be sure the water runs cool before you proceed.
Close the inlet valve to the water heater , but leave the hot water faucet open to relieve pressure.
Con Ɵ nued...
22 • Electric Tankless Water Heater
5
Remove the heater’s front cover, then place a bucket under the water heater to catch any water that spills.
NOTICE: If you have a two- or four-chamber model, you must unplug the cover’s ribbon cable from the control board.
When you plug it back in later, it must be oriented correctly.
(See Figure 5, page 14.)
We recommend marking the connector and board with a marker. You will then be able to align the marks.
• If you have a point-of-use water heater, go to step 6.
• If you have a two- or four-chamber water heater, go to step 7 on page
24.
6
Point-of-use water heaters only:
6.1
Remove the heater’s top plate:
A.) Remove both screws which secure the top plate to the water heater.
(See Figure 12.)
B.) Lift and remove the top plate.
Figure 12.
Top View of Point-of-Use Model
Figure 13.
Point-of-use models:
Grommet Orienta on
Outlet Inlet
Grommets
6.3. Remove the old element:
A.) Slide the inlet and outlet grommets upward to provide clearance. (Figure 13).
B.) Remove the screws that secure the red and black wires to the top of the heating element. (Use the
Phillips screwdriver. Save both screws for later use.)
C.) Disconnect the green ground wire from the heating element. (See
Figure 14.) It is secured with a spade connector. Pull it straight up from the element to slide it off the terminal.
Figure 1 4.
Element in point-of-use heater
Top Plate Screws
Retaining Nut
Ground wire (spade connector)
D.) Unscrew and remove the retaining nut that secures the heating element (See Figure 14).
Use an adjustable wrench. You may also purchase an element replacement kit which includes a thin-walled socket. Call Technical
Support for ordering information.
NOTICE: During the next step, protect the circuit board from dripping water!
E.) Lift the element out of the water heater. NOTICE: As you lift the element out of the opening, wrap it with a rag to keep water from dripping onto the circuit board.
F.) Remove the brass ground ring from the top of the element. (See
Figure 15: Brass ring and flag terminal.) Set it aside for later use.
Figure 15: Brass ring and flag terminal
Flag terminal
Brass ground ring
(point-of-use models)
6.4 Install the new element:
NOTICE: Ensure that there is an O-ring installed above the threads of the element. (See Figure 20, page 25.)
A.) Insert the new element into its water heater opening.
B.) Place the brass ground ring on top of the element. Make sure that the flag terminal is positioned so that the ground wire can be reconnected easily (Figure 16.)
Con Ɵ nued...
Electric Tankless Water Heater • 23
C.) Secure the element by installing and tightening the retaining nut (Figure
14, page 23). earlier.
Do not overtighten.
D.) Secure the red and black wires onto the top of the heating element. Use the two screws that you removed
E.) Reconnect the green ground wire to the element’s ground terminal
(flag terminal).
6.5 Reassemble the point-of-use water heater:
A.) Reposition both grommets as shown in Figure 17. Ensure that their flat surfaces press firmly against the top plate when you reinstall it.
Figure 16.
Brass ring on point-of-use models.
B.) Reinstall the top plate and secure it with the two screws that you removed earlier. (See Figure 12, page 23.)
C.) Go to step 8 on page 25.
Figure 17.
Point-of-use models:
Grommet Orienta on
Outlet
Flat
Inlet
Grommets
Flat surface presses against inside surface of housing. See above.
Place brass ground ring on top of element.
<ĞĞƉŇĂŐƚĞƌŵŝŶĂů accessible.
7
Two- or four-chamber water heaters only:
7.1 Drain the two- or four-chamber water heater:
A.) Remove all six screws that secure the access plate beneath the element (at the bottom of the water heater). See Figure 18.
B.) Remove the access plate and allow the water to drain into the bucket.
C.) Clean the access plate and both seals.
D.) Make sure that both seals are seated properly, then reinstall the access plate. (Use all six screws that you removed earlier.)
Figure 18.
Access Plates:
Two- or Four-Chamber models only ͻ dǁŽͲĐŚĂŵďĞƌŵŽĚĞůƐ͗ one access plate ͻ &ŽƵƌͲĐŚĂŵďĞƌŵŽĚĞůƐ͗ two access plates
ĐĐĞƐƐWůĂƚĞ;ďŽƩŽŵŽĨŚĞĂƚĞƌͿ
7.2 Remove the old element:
A.) Remove the screws that secure the red and black wires to the top of the heating element (Figure 19).
Use the Phillips screwdriver. Save both screws for later use.
B.) Remove the heating element with an element wrench.
C.) Lift the element out of the water heater. NOTICE: As you lift the element and O-ring out of the opening, wrap them with a rag to keep water from dripping onto the circuit board.
Figure 19.
Top view of element
(two- or four-chamber model)
D.)
24 • Electric Tankless Water Heater
7.3 Install the new element:
A.) Insert the new element into its water heater opening. Make sure that the O-ring is positioned properly. (See Figure 20.)
Figure 20.
O-ring
B.) Tighten the element with an element wrench until it is snug, then tighten for 1/4 turn more.
C.) Secure the red and black wires onto the top of the heating element. Use the two screws that you removed earlier. Proceed to step 8.
8
Turn on the WATER supply to the heater.
9
Turn on a nearby hot water faucet to fill the heater with water.
Continue until all air has been expelled from the heater and pipes. If a
T&P valve is installed, operate it manually several times to allow any trapped air to escape.
10
Check for water leaks. Correct any leaks that are found.
NOTICE: Do not restore power until the circuit board and components are completely dry. If water has dripped anywhere inside the heater (during element replacement or leak check), dry it with a hair dryer or compressed air. Be sure to dry behind the circuit board.
11
If there are no water leaks, complete these steps:
A.) Two- or four-chamber water heaters only: Take the connector end of the cover’s ribbon cable and plug it into the control board.
(Plug it in where you see two rows of header pins close together, five pins in each row.) If necessary, refer to the “DISPLAY” callout in the wiring diagram for your model. (See “Wiring Diagrams” on page 29.)
NOTICE: The plug must be oriented correctly. (The correct orienta on is shown in Figure 5, page 14.)
If you plug it in backwards, it will not cause damage, but the display will not work. If the display does not work a er you have completed installa on, 1.) disconnect power at all branch circuits, 2.) disconnect the plug, 3.) rotate it 180-degrees, then 4.) plug it back in.
B.) Reinstall the water heater’s cover.
WARNING! Be sure the cover is reinstalled and secured to reduce the risk of fire and electric shock.
C.) Restore power to the water heater.
D.) Run hot water from a faucet to make sure that the water heater is working as expected.
Thermistor
(Temperature Sensor)
Replacement
WARNING!
• Working on an energized circuit can result in severe injury or death from electrical shock. Turn power off.
• Some models are connected to more than one branch circuit. Continued on page 27.
Disconnect all branch circuits before servicing unit.
• Check wires with a non-contact circuit tester to make sure power is o ff . When you are fi nished, be sure all covers are secured to reduce the risk of fi re and electric shock.
If you are not comfortable replacing a thermistor yourself, have this work done by a quali fi ed person. To replace a thermistor, you’ll need the following tools/supplies:
• Phillips head screwdriver
• 1/2-inch open end wrench
• Bucket (for draining the heater)
• Siphon transfer pump & towels
1
2
Turn o ff power to the water heater.
Drain the water heater as described in the draining instructions (page 27).
3
Locate the thermistor (temperature sensor) that was iden fi ed by the error code.
Refer to the appropriate fi gure on page 26.
Figure 21.
4
Unplug the thermistor’s wires from the control board.
Electric Tankless Water Heater • 25
Figure 22.
Thermistor loca ons
(Point-of-use models)
OUTLET INLET
Thermistor* Connections
T-Aux Auxiliary thermistor
T-In Inlet thermistor
T-Out Outlet thermistor
T-Aux **
T-In **
T-Out
Outlet Thermistor *
(Connects to T-Out)
Auxiliary Thermistor *
(Connects to T-Aux)
Inlet Thermistor *
(Connects to T-In)
* Often referred to as a temperature sensor.
** If the inlet thermistor fails, there is no need to replace it.
Simply switch the
T-Aux and T-In plugs on the control board.
POWER
SUPPLY
TERMINAL
BLOCK
NOTICE:
Appearance of cap may vary.
Figure 23.
Thermistor loca ons
(Two-chamber models)
OUTLET
HEATING ELEMENTS
INLET
Intermediate
Thermistor *
(connects to
TH-1)
TH-1
TH-2
TH-IN
L1
L2
Figure 24.
Thermistor loca ons (Four-chamber models)
OUTLET Intermediate
Thermistor *
(connects to
TH-2)
Intermediate
Thermistor *
(connects to
TH-1)
INLET
TH-1
TH-2
TH-3
TH-4
TH-IN
L1
L2
L1
L2
Outlet Thermistor *
May be located on outlet elbow.
(connects to TH-4)
Intermediate Thermistor *
(connects to TH-3)
Thermistor* Connections
TH-IN Inlet thermistor.
TH-1 Intermediate thermistor
TH-2 Intermediate thermistor
TH-3 Intermediate thermistor
TH-4 Outlet thermistor
* Often referred to as a temperature sensor.
Inlet Thermistor *
(connects to TH-IN)
Outlet Thermistor *
(connects to TH-2)
Inlet Thermistor *
(connects to TH-IN)
Thermistor* Connections
TH-IN Inlet thermistor.
TH-1 Intermediate thermistor
TH-2 Outlet thermistor
* Often referred to as a temperature sensor.
26 • Electric Tankless Water Heater
5
Remove the thermistor by turning it counter-clockwise with a 1/2-inch open end wrench.
6
Install the new thermistor in the opening by turning it clockwise with a 1/2-inch open end wrench.
□ Make sure that the O-ring is in place before you install the thermistor.
□ Tighten the thermistor hand tight, then carefully tighten it with a wrench until it is seated. Do not overtighten.
7
Plug the thermistor’s wires into the control board. The proper loca on is shown in one of the fi gures on page 26.
8
Return the water heater to service. To do so, follow the instructions in “Returning the
Water Heater to Service,” page 28.
Draining the Water
Heater
WARNING!
• Working on an energized circuit can result in severe injury or death from electrical shock. Turn power off.
• Some models are connected to more than one branch circuit.
Disconnect all branch circuits before servicing unit.
• Check wires with a non-contact circuit tester to make sure power is o ff . When you are fi nished, be sure all covers are secured to reduce the risk of fi re and electric shock.
Draining the Water Heater
1
Con fi rm that power is o ff by checking the wires with a non-contact circuit tester.
2
3
Open a nearby hot water faucet and run the water until it is cool.
WARNING! Be sure the water runs cool before draining the water heater to reduce the risk of scalding.
Close the inlet valve to the water heater , but leave the hot water faucet open to relieve pressure.
4
Remove the heater’s cover, then place a bucket under the water heater to catch any water that spills.
NOTICE: If you have a two- or fourchamber model, you must unplug the cover’s ribbon cable from the control board. When you plug it back in later, it must be oriented correctly. We recommend marking the connector and board with a marker. You will then be able to align the marks. See also
Figure 5, page 14.
• If you have a point-of-use water heater, go to step 5.
• If you have a two- or four-chamber water heater, go to step 6.
5
Point-of-use water heaters only:
Drain the point-of-use water heater:
A.) Remove both screws which secure the top plate to the water heater.
(See Figure 25.)
Figure 25.
Top View of Point-of-Use Model
Top Plate Screws
B.) Lift and remove the top plate.
(Removing it will protect if from damage.)
C.) Cover the top of the water heater with heavy towels (to prevent water from dripping through the openings).
A er the towels are in place, disconnect the inlet and outlet water lines from the water heater.
D.) Remove the hea ng element as described in “Element Removal and
Replacement” (page 22).
E.) Insert a pump hose into the water heater’s chamber and pump all of the water out.
F.) Reinstall the hea ng element as described in “Element Removal and
Electric Tankless Water Heater • 27
Replacement” (page 22).
G.) Reinstall the inlet and outlet water lines to the water heater.
H.) Go to step 7.
6
Two- or four-chamber water heaters only:
Drain the two- or four-chamber water heater:
A.) Remove all six screws that secure the access plate beneath the element (at the bottom of the water heater). See Figure 26.
B.) Remove the access plate and allow the water to drain into the bucket.
C.) Clean the access plate and both seals.
D.) Make sure that both seals are seated properly, then reinstall the access plate. (Use all six screws that you removed earlier.)
E.) Repeat steps A through D for each access plate.
F.) Go to step 7.
Figure 26.
Access Plates:
Two- or Four-Chamber models only ͻ dǁŽͲĐŚĂŵďĞƌŵŽĚĞůƐ͗ one access plate ͻ &ŽƵƌͲĐŚĂŵďĞƌŵŽĚĞůƐ͗ two access plates
ĐĐĞƐƐWůĂƚĞ;ďŽƩŽŵŽĨŚĞĂƚĞƌͿ
Returning the Water Heater to
Service
When you are ready to return
7
the water heater to service, turn on the WATER supply to the heater.
8
Turn on a nearby hot water faucet to fill the heater with water.
Continue until all air has been expelled from the heater and pipes. If a
T&P valve is installed, operate it manually several times to allow any trapped air to escape.
9
Check for water leaks. Correct any leaks that are found.
NOTICE: Do not restore power until the circuit board and components are completely dry. If water has dripped anywhere inside the heater, dry it with a hair dryer or compressed air. Be sure to dry behind the circuit board.
10
If there are no water leaks, complete these steps:
A.) Two- or four-chamber models only: Take the connector end of the cover’s ribbon cable and plug it into the control board. (Plug it in where you see two rows of header pins close together, five pins in each row.) If necessary, refer to the “DISPLAY” callout in the wiring diagram for your model. (See “Wiring Diagrams” on page 29).
NOTICE: If you have a two- or fourchamber model, you must orient the plug as shown in Figure 5, page
14. If you plug it in backwards, it will not cause damage, but the display will not work. If the display does not work a er you have completed installa on, 1.) disconnect power at all branch circuits, 2.) disconnect the plug, 3.) rotate it 180-degrees, then 4.) plug it back in.
B.) Reinstall the water heater’s cover.
WARNING! Be sure the cover is reinstalled and secured to reduce the risk of fire and electric shock.
C.) Restore power to the water heater. Verify proper operation.
Replacement Parts
The following parts may be ordered through your retailer or local plumbing wholesaler:
• Thermistors
(temperature sensors)
When ordering replacement parts, please be ready to provide your water heater model and serial number.
28 • Electric Tankless Water Heater
WIRING DIAGRAMS
The wiring diagrams for various models are listed in this sec on. Locate the one that corresponds with your model.
NOTICE: The correct wiring diagram for your model can be found on the inside of your water heater’s cover.
The wiring diagrams are listed as follows:
• 1 Chamber, 1 Element, 120 VAC
(see below).
• 1 Chamber, 1 Element, 240/208
VAC (see below).
• 1 Chamber, 1 Dual Element,
240/208 VAC, p. 30.
• 1 Chamber, 1 Element, 277 VAC, p. 30.
• 2 Chamber, 2 Element, 240/208
VAC (other than 16kW, 18kW, or
14kW/208V), p. 31.
• 2 Chamber, 2 Element, 240/208
VAC (16 kW, 18kW and
14kW/208V only), p. 32.
Level
Detect
Moisture
Sense
TH-AUX
TH-IN
TH-OUT
1 Chamber, 1 Element, 120 VAC
GRN
Control
Board
3-Pin Conn.
RED
Relay 1
BLK
Relay 2
• 4 Chamber, 4 Element, 240/208
VAC, p. 33.
See also “Electrical Requirements” on page 8.
Element
Level
Detect
Moisture
Sense
TH-AUX
TH-IN
TH-OUT
1 Chamber, 1 Element, 240/208 VAC
GRN
Control
Board
3-Pin Conn.
RED
Relay 1
BLK
Relay 2
Element
Power
Supply
GRN
BLK
RED
GRN
Ground
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
BLK
RED
GRN
L1
N
GRND
Power
Supply
GRN
BLK
RED
GRN
Ground
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
BLK
RED
GRN
L1
L2
GRND
Electric Tankless Water Heater • 29
Level
Detect
Moisture
Sense
1 Chamber, 1 Dual Element, 240/208 VAC
GRN
Relay 1
RED
3-Pin Conn.
RED
Relay 2
BLK
Relay 1
RED
TH-AUX
TH-IN
BLK
RED
BLK Element
TH-OUT
Relay 2
BLK
Control Board
RED
BLK Element
Level
Detect
Moisture
Sense
TH-AUX
TH-IN
1 Chamber, 1 Element, 277 VAC
GRN
Control
Board
3-Pin Conn.
RED
Relay 1
BLK
TH-OUT
Relay 2
Power
Supply
GRN
BLK
RED
GRN
Ground
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
BLK
RED
GRN
L1
L2
GND
Element
Power
Supply
GRN
GRN
G
RN
BLK
RED
GRN
L1
L2
GRND
Ground
Transformer
Board
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
30 • Electric Tankless Water Heater
2 Chamber, 2 Element, 240/208 VAC
Moisture
Sense
Level
Detect
TH-1
TH-2
RED
BLK
Relay 2
BLK
BLK
Relay 3
BLK
RED
Relay 1
RED
RED
Relay 4
RED
TH-IN
Power
Supply
RED
BLK
RED
BLK
GRN
RED
BLK
L1
L2
Ground
Display
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
NOTICE: 16 kW and 18 kW two-chamber models DO NOT use this con fi gura on.
14kW, 208V models DO NOT use this con fi gura on.
For two circuit, two-chamber models, see page 32. Failure to observe this no ce can result in equipment malfunc on.
Electric Tankless Water Heater • 31
2 Chamber, 2 Element, 240/208 VAC
Used ONLY with the following two-chamber models:
• 14 kW at 208V
• 16 kW
• 18 kW
Moisture
Sense
Level
Detect
TH-1
TH-2
RED
BLK
Relay 2
BLK
BLK
Relay 3
BLK
RED
Relay 1
RED
Relay 4
RED
Power
Supply
RED
TH-IN
BLK
RED
BLK
GRN
RED
BLK
RED
BLK
L1
L2
L1
L2
CIRCUIT
BREAKER
A
CIRCUIT
BREAKER
B
Ground
Display
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
NOTICE: This wiring diagram applies to the following two-chamber models only: 16 kW, 18 kW, and
14 kW/208 V. If you have a two-chamber model that is rated other than 16 kW, 18 kW, or
14 kW/208V, refer to page 31. Failure to observe this no ce can result in equipment malfunc on.
32 • Electric Tankless Water Heater
4 Chamber, 4 Element, 240/208 VAC
Moisture
Sense
Level
Detect
TH-1
TH-2
TH-3
TH-4
TH-IN
RED
BLK
GRN
Ground
BLK
BLK
BLK
Relay 2
BLK
BLK
Relay 4
BLK
RED
Relay 1
RED
RED
Relay 3
RED
Relay 6
BLK RED
Relay 5
RED
Power
Supply
Relay 8
RED
Relay 7
RED
BLK
J7
RED
BLK
RED
BLK
L1
L2
L1
L2
CIRCUIT
BREAKER
A
CIRCUIT
BREAKER
B
Display
USE COPPER CONDUCTORS ONLY WHEN
CONNECTING TO ELECTRICAL SERVICE.
Electric Tankless Water Heater • 33
APPENDIX: HORIZONTAL MOUNTING OF POU MODELS
As stated on page 12, point-ofuse (POU) models may be mounted horizontally. Note the following:
• If a POU model is to be mounted horizontally, it must be mounted with brackets (provided). The nipples must face toward the right as shown in Figure 27.
• Two-chamber and four-chamber models cannot be mounted horizontally. They must be mounted vertically (nipples facing upward).
• This procedure is a supplement to
“Mount Your Water Heater,” page
12.
NOTICE: Read “Minimum Clearances”
(Figure 2, page 11) before you start.
Figure 27.
Horizontally-mounted POU water heater:
Figure 28.
Mount the brackets to the surface as shown.
See Figure 29 for fastener loca ons.
1
Complete the installa on steps on pages 11 and
12. Stop when you have completed step 7 on page 12.
2
Secure both brackets to the wall. (See Figure 28.) Use screws, bolts, or anchors as appropriate. NOTE: To drill pilot holes for the #10 screws that are provided, use a 7/64” drill bit.
Ensure that the mounting surface and fasteners will support the weight of the water heater.
Figure 29.
Pilot hole center distances:
Continued on the next page.
4.31 inches
(4 УШЕКŝŶĐŚĞƐ )
11.22 inches
(11 ХШЗЖŝŶĐŚĞƐ )
34 • Electric Tankless Water Heater
3
Set the water heater on the brackets, base plate down, and secure it with four sets of bolts and nuts. See Figure 30 and
Figure 31.
NOTICE: Ensure that the nipples face toward the right as shown in Figure
27, page 34.
4
Return to page 12 to complete the water heater installation.
Figure 30.
Internal water heater components are represented by hidden lines.
Water Heater
Components
Water Heater’s
Base Plate
Bolts (X4)
(Bolt heads face upward)
Figure 31.
Internal water heater components are represented by hidden lines.
Water Heater
Components
Brackets (X2)
Nuts (X4)
DŽƵŶƟŶŐ
Surface
DŽƵŶƟŶŐ
Surface
Electric Tankless Water Heater • 35
Copyright © 2018 A.O. Smith Corpora on. All rights reserved.
advertisement
Key Features
- Endless supply of hot water
- Compact design
- Easy to install
- Energy-efficient
- Flow rate of 1.8 gallons per minute
- Ideal for homes with up to 2 bathrooms
Related manuals
Frequently Answers and Questions
What is the flow rate of the A.O. Smith R2VR-180E?
How many bathrooms can the A.O. Smith R2VR-180E support?
Is the A.O. Smith R2VR-180E energy-efficient?
advertisement
Table of contents
- 2 IMPORTANT SAFETY INFORMATION
- 5 GENERAL INFORMATION
- 11 INSTALLATION
- 15 OPERATION
- 17 TROUBLESHOOTING
- 22 SERVICE
- 29 WIRING DIAGRAMS
- 34 APPENDIX