GREE MULTIU24HP211 Ultra ENERGY STAR 2-Zone 25000 BTU 2 Ton Wi-Fi Ductless Mini Split Air Conditioner &Heat Pump w/ 25 ft. Install Kit 230V Installation Guide

GREE MULTIU24HP211 Ultra ENERGY STAR 2-Zone 25000 BTU 2 Ton Wi-Fi Ductless Mini Split Air Conditioner &Heat Pump w/ 25 ft. Install Kit 230V Installation Guide
Change for life
Installation & Owner's Manual
Original Instructions
Split Type Wall-mounted Air Conditioner
Model:
MULTIU18HP230V1DO
MULTIU24HP230V1DO
MULTIU36HP230V1DO
MULTIU42HP230V1DO
Thank you for choosing our product.
Please read this Owner’s Manual carefully before operation and
retain it for future reference.
If you have lost the Owner's Manual, please contact your local
distributor or visit www.greecomcomfort.com/resources for the
electronic version.
In line with the company’s policy of continual product improvement, the aesthetic and dimensional
characteristics, technical data and accessories of this appliance may be changed without notice.
INSTALLER
GENERAL
INFORMATION
CONTENTS
GENERAL INFORMATION
Conformity And Range
1
The Instructions Before Use
2
Name of Parts
3
Technical Data
5
Outdoor Unit Working Temperature Range
5
Electrical Connections
6
Installing The Outdoor Unit
10
Bleeding
10
Maintenance
11
Installation Dimension Diagram
11
Check After Installation
12
The products in this manual may be different from the ones you receive, due to different
models, some models have a display, some models do not. For the position and shape of the
display please refer to the your model.
This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety.
Children should be supervised to ensure that they do not play with the appliance.
Explanation of Symbols
DANGER
Indicates a hazardous situation that, if not avoided, will
result in death or serious injury.
WARNING
Indicates a hazardous situation that, if not avoided, could
result in death or serious injury.
CAUTION
Indicates a hazardous situation that, if not avoided, may
result in minor or moderate injury.
NOTICE
Indicates important but not hazard-related information,
used to indicate risk of property damage.
Indicates a hazard that would be assigned a signal word
WARNING or CAUTION.
Exception Clauses
Manufacturer will bear no responsibilities when personal injury or
property loss is caused by the following reasons.
1. Damage the product due to improper use or misuse of the product;
2. Altering, changing, servicing or using the product with other equipment without
abiding by the instruction manual of manufacturer.
3. Upon verification, the defect of product is directly caused by corrosive gas;
4. Upon verification, the defects are due to transportation damage.
5. Operating, repairing or servicing the unit without following the instruction manual
or related regulations.
6. Upon verification, the problem or dispute is caused by the quality specification or
performance of parts and components that produced by other manufacturers;
7. Damage caused by natural disasters, corrosive environments or force majeure.
CONFORMITY AND RANGE
GENERAL INFORMATION This appliance can be used by children aged from 8 years and above and persons
with reduced physical,sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without supervision.
Please read this owner's manual carefully before operating the unit and retain it for consultation.
Instructions for installation and use of this product are provided by the manufacturer.
Only use the air conditioner as instructed in this booklet. These instructions are not intended to
cover every possible condition and situation. As with any electrical household appliance, common sense
and caution are therefore always recommended for installation, operation and maintenance.
1
THE INSTRUCTIONS BEFORE USE
GENERAL INFORMATION
WARNING
★ If you smell something burning or
★ The power supply must be
★ Never cut off or damage power
★ All power wiring must comply
★ If you won't be using your unit for
★ Never damage electrical wiring or
Improper wiring can cause
electrical shock or fire.
Residual dust build up could
cause overheating or fire.
It could cause overheating or fire.
★ When cleaning, turn the unit off
★ Rated voltage of this air conditi-
★ Don't attempt to repair the air
see smoke, turn off the power supply
and contact an HVAC technician.
connected to a properly sized
circuit breaker. The unit will cycle
automatically according to your
settings. Do not frequently turn
your unit on or off, this may
interfere with its normal operation
and control wiring. If the power
and signal control wires are
damaged, have them replaced
by an HVAC technician.
If the abnormity still exists,the unit
may be damaged,and may cause
electric shock or fire.
with local, regional or national
electric codes.
and disconnect power supply at
the breaker.
Cut off power supply
extended periods, disconnect the
power supply.
oner 208/230V, 60Hz, The compressor will vibrate sharply if the
voltage is too low, resulting in
damage to the refrigeration
system.
Electrical components are easy
damaged if the voltage is too
high.
Not doing so may cause
electrical shock or damage.
★ Make sure the unit is safely
★ Don't step on or place anything
Improper installation may cause
damage to the unit or injure
someone
Serious injury or irreparable damage
could occur.
and securely installed.
on top of the outdoor unit.
2
use the electrical wire which is not
suited for this application.
conditioner yourself.
Improper repair could lead to an
electrical shock or fire, always
contacts an HVAC technician to
service or repair you unit.
★ Grounding: The unit must be
properly grounded. The ground
wire must be connected to the
appropriate grounding terminal
in the unit.
NAME OF PARTS
GENERAL INFORMATION
MULTIU18HP230V1DO
WARNING
If the supply wire is damaged, it must be replaced by the manufacturer or a licensed
HVAC technician or a similarly qualified person in order to avoid a hazard.
Be sure to disconnect the power supply before cleaning the air conditioner; to avoid an
electrical shock.
Wetting of air conditioner may cause the risk of electrical shock. Make sure not to wash
your air conditioner under any circumstance.
Volatile liquids such as thinner or gasoline will cause damage to the appearance of air
conditioner. (Only use soft dry cloth moist cloth clean the air conditioner cabinet).
Do not dispose this product as unsorted municipal waste. Dispose according to local
waste regulations.
The temperature of refrigerant circuit is high, please keep the interconnecting wire away
from the copper refrigerant lines.
1
OUTDOOR UNIT
No.
Description
1
Air outlet grille
2
Valve
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to
the appearance of the units that have been purchased.
2
MULTIU24HP230V1DO
WARNING
If the supply wire is damaged, it must be replaced by the manufacturer or a licensed HVAC technician or a
similarly qualified person in order to avoid a hazard.
Be sure to disconnect the power supply before cleaning the air conditioner; to avoid an electrical shock.
Wetting of air conditioner may cause the risk of electrical shock. Make sure not to wash your air conditioner
under any circumstance.
Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner. (Only use
soft dry cloth moist cloth clean the air conditioner cabinet).
Do not dispose this product as unsorted municipal waste. Dispose according to local waste regulations.
The temperature of refrigerant circuit is high, please keep the interconnecting wire away from the copper
refrigerant lines.
1
OUTDOOR UNIT
No.
Description
1
Air outlet grille
2
Valve
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to
the appearance of the units that have been purchased.
2
3
NAME OF PARTS
GENERAL INFORMATION
MULTIU36HP230V1DO MULTIU42HP230V1DO
WARNING
If the supply wire is damaged, it must be replaced by the manufacturer or a licensed
HVAC technician or a similarly qualified person in order to avoid a hazard.
Be sure to disconnect the power supply before cleaning the air conditioner; to avoid an
electrical shock.
Wetting of air conditioner may cause the risk of electrical shock. Make sure not to wash
your air conditioner under any circumstance.
Volatile liquids such as thinner or gasoline will cause damage to the appearance of air
conditioner. (Only use soft dry cloth moist cloth clean the air conditioner cabinet).
Do not dispose this product as unsorted municipal waste. Dispose according to local
waste regulations.
The temperature of refrigerant circuit is high, please keep the interconnecting wire away
from the copper refrigerant lines.
1
OUTDOOR UNIT
No.
Description
1
Air outlet grille
2
Valve
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to
the appearance of the units that have been purchased.
2
4
TECHNICAL DATA
GENERAL INFORMATION
MULTIU18HP230V1DO
MODE
Electrical data
Electricity supply
Fuse or circuit breaker
Minimum power wire section
208/230V,60Hz
35
5.3
A
mm 2
Size and clearance
L
P
H
L
920
mm
P
380
mm
H
790
mm
MULTIU24HP230V1DO
MODE
Electrical data
Electricity supply
Fuse or circuit breaker
Minimum power wire section
208/230V,60Hz
40
5.3
A
mm 2
Size and clearance
L
P
H
L
920
mm
P
380
mm
H
790
mm
MULTIU36HP230V1DO MULTIU42HP230V1DO
MODE
Electrical data
Electricity supply
Fuse or circuit breaker
Minimum power wire section
208/230V,60Hz
60
8.4
A
mm 2
Size and clearance
L
P
H
L
1016
mm
P
440
mm
H
1103
mm
OUTDOOR UNIT WORKING TEMPERATURE RANGE
Maximum cooling
Maximum heating
OutdoorsideDB/WB( °F / °C )
115°F(46°C)/75.2°F(24°C)/-
5
GENERAL INFORMATION
ELECTRICAL CONNECTIONS
INSTALLER
MULTIU18HP230V1DO
1. Remove the handle at the right side plate of the
outdoor unit (one screw).
An all-pole disconnect switch having a contact
separation of at least 3mm in all poles should be
connected to supply power wiring.
2. Remove the wire clamp, connect the power
connection wire to the appropriate terminal and
secure the connection. The wiring connections
must be consistent with the indoor unit terminal
connections. Wiring should match that of indoor
unit.
Wrong wire connections may cause malfunction of
some electric components. After fixing wire,
ensure that leads between connection to fixed
point have some space.
3. Secure power connection wire with a wire clamp.
The connection pipes and the connection wiring of
unit A, unit B, unit C and unit D must correspond
to each other respectively.
4. Ensure all wire is securely attached.
5. Install the handle.
Provide a circuit breaker with suitable capacity,
please note the following table. Circuit
breakers will prevent short-circuits and
overload. (Caution: do not use a fuse only for
circuit protection.
Air-conditioner
The appliance shall be installed in accordance
with national wiring regulations.
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.
Breaker capacity
35A
MULTIU18HP230V1DO
To unit B
To unit A
L1 L2
connecting
wire
Power wire
connecting
wire
To the power supply
POWER
L1 L2
black white green
(brown) (blue) (yellowgreen)
L1
L2
A
white
(blue)
B
green
black red
(yellow(brown)
green)
INDOOR UNIT A
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT B
6
ELECTRICAL CONNECTIONS
INSTALLER
MULTIU24HP230V1DO
1. Remove the handle at the right side plate of the
outdoor unit (one screw).
An all-pole disconnect switch having a contact
separation of at least 3mm in all poles should be
connected to supply power wiring.
2. Remove the wire clamp, connect the power
connection wire to the appropriate terminal and
secure the connection. The wiring connections
must be consistent with the indoor unit terminal
connections. Wiring should match that of indoor
unit.
Wrong wire connections may cause malfunction of
some electric components. After fixing wire, ensure
that leads between connection to fixed point have
some space.
3. Secure power connection wire with a wire clamp.
The connection pipes and the connection wiring of
unit A, unit B, unit C and unit D must correspond to
each other respectively.
4. Ensure all wire is securely attached.
5. Install the handle.
The appliance shall be installed in accordance with
national wiring regulations.
Provide a circuit breaker with suitable capacity,
please note the following table. Circuit
breakers will prevent short-circuits and
overload. (Caution: do not use a fuse only for
circuit protection.
Air-conditioner
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.
Breaker capacity
40A
MULTIU24HP230V1DO
To unit A
To unit B
To unit C
L1 L2
connecting
wire
Power wire
connecting
wire
connecting
wire
To the power supply
POWER
L1
black white green
(brown) (blue) (yellowgreen)
L1
A
B
C
L2
L2
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT A
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT B
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT C
7
ELECTRICAL CONNECTIONS
INSTALLER
MULTIU36HP230V1DO
1. Remove the handle at the right side plate of the
outdoor unit (one screw).
An all-pole disconnect switch having a contact
separation of at least 3mm in all poles should be
connected to supply power wiring.
2. Remove the wire clamp, connect the power
connection wire to the appropriate terminal and
secure the connection. The wiring connections
must be consistent with the indoor unit terminal
connections. Wiring should match that of indoor
unit.
Wrong wire connections may cause malfunction of
some electric components. After fixing wire,
ensure that leads between connection to fixed
point have some space.
3. Secure power connection wire with a wire clamp.
The connection pipes and the connection wiring
oft unit A, unit B, unit C and unit D must be
correspond to each other respectively.
4. Ensure all wire is securely attached.
5. Install the handle.
The appliance shall be installed in accordance
with national wiring regulations.
Provide a circuit breaker with suitable capacity,
please note the following table. Circuit
breakers will prevent short-circuits and
overload. (Caution: do not use a fuse only for
circuit protection.
Air-conditioner
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.
Breaker capacity
60A
MULTIU36HP230V1DO
To unit A
To unit B
To unit C
To unit D
L1 L2
connecting
wire
Power wire
connecting
wire
connecting
wire
connecting
wire
To the power supply
POWER
L1
black white green
(brown) (blue) (yellowgreen)
L1
A
B
C
D
L2
L2
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT A
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT B
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT C
8
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT D
ELECTRICAL CONNECTIONS
INSTALLER
MULTIU42HP230V1DO
1. Remove the handle at the right side plate of the
outdoor unit (one screw).
An all-pole disconnect switch having a contact
separation of at least 3mm in all poles should be
connected to supply power wiring.
2. Remove the wire clamp, connect the power
connection wire to the appropriate terminal and
secure the connection. The wiring connections
must be consistent with the indoor unit terminal
connections. Wiring should match that of indoor
unit.
Wrong wire connections may cause malfunction of
some electric components. After fixing wire, ensure
that leads between connection to fixed point have
some space.
3. Secure power connection wire with a wire clamp.
The connection pipes and the connection wiring of
unit A, unit B, unit C and unit D must correspond to
each other respectively.
4. Ensure all wire is securely attached.
5. Install the handle.
The appliance shall be installed in accordance with
national wiring regulations.
Provide a circuit breaker with suitable capacity,
please note the following table. Circuit
breakers will prevent short-circuits and
overload. (Caution: do not use a fuse only for
circuit protection.
Air-conditioner
Note: The above figures are only intended to be a simple
diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.
Breaker capacity
60A
MULTIU42HP230V1DO
To unit A
To unit B
To unit C
To unit D
To unit E
L1 L2
connecting
wire
Power wire
connecting
wire
connecting
wire
connecting
wire
connecting
wire
To the power supply
POWER
L1
black white green
(brown) (blue) (yellowgreen)
L1
A
B
C
D
E
L2
L2
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT A
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT B
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT C
9
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT D
white
(blue)
green
black red
(yellow(brown)
green)
INDOOR UNIT E
INSTALLING THE OUTDOOR UNIT
INSTALLER
Location
Caution: Installation Must be Performed in
Accordance with the NEC/CEC by Authorized
Personnel Only.
Install the drain fitting and the drain hose
(for model with heat pump only)
Use bolts to secure the unit to a flat, solid surface.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.
Do not install the outdoor unit in pits or air vents.
Installing the refrigerant lines
Use suitable refrigerant lines and equipment for
refrigerant R410A.
Models
(ft) 18Kx2 24Kx2 24Kx3 36Kx2 36Kx3
164
229 164 246
Max. connection pipe length 164
Max. connection pipe length
82
82
82
82
82
(Simple one indoor unit)
Condensation is produced and flows from the outdoor unit when the appliance is operating in the
heating mode. In order not to disturb neighbours
and to respect the environment,install a drain fitting
and a drain hose to channel the condensate water.
Install the drain fitting and rubber washer on the
outdoor unit chassis and connect a drain hose to it
as shown in the figure.
Models
(ft) 36Kx4 42Kx2 42Kx3 42Kx4 42Kx5
246
246 246 246
Max. connection pipe length 246
Max. connection pipe length
82
82
82
82
82
(Simple one indoor unit)
The refrigerant lines must not exceed the maximum
heights 33ft(18Kx2 &24Kx2 &24Kx3 &36x2 &36x3
&36x4& 42x2 &42x3 &42x4 &42x5).
Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches working in opposite directions.
BLEEDING
INSTALLER
Humid air left inside the refrigerant circuit can cause compressor malfunction. After having connected the indoor
and outdoor units, bleed the air and humidity from the
refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3way valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an
absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation, close the
low-pressure knob on the vacuum pump coupling.
Stop the vacuum pump.
(6) Open the 2-way valve by 1/4 turn and then close it
after 10 seconds. Check all the joints for leaks using
liquid soap or an electronic leak device.
(7) Turn the body of the 2-way and 3-way valves. Disconnect the vacuum pump hose.
(8) Replace and tighten all the caps on the valves.
Diameter (mm)
Vacuum pump
Vacuum pump
Twisting moment (ft lbs)
Φ6
11-14.75
Φ9.52
26-29.5
Φ16
42.3-48
Φ12
33.2-36.9
Φ19
51.6-55.3
Vacuum pump
(8) Secure
INDOOR
UNIT
Refrigerant fluid direction of fiow
18、
24 、
36、
42K unit need to be installed the indoor unit
2-way valve
3-way valve
(6) Open by 1/4 turn
(7)Turn to open fully
Service
inlet
(2)Turn
(8) Secure
conversion joint
10
(7)Turn to open fully
Valve cap
(2)Turn
(2)Turn
Valve cap
(8) Secure
Connect to the
indoor unit
MAINTENANCE
INSTALLER
Use suitable instruments for the refrigerant R410A.
Do not use any other refrigerant than R410A.
Do not use mineral oils to clean the unit.
INSTALLATION DIMENSION DIAGRAM
INSTALLER
The installation must be done by trained and licensed service personnel adhereing to the instructions
provideded in this manual.
Contact a licensed HVAC contractor for installation to avoid any issues that will void the warranty.
Any disconnecting and relocation of a unit must be done by a qualified licensed HVAC technician.
Ensure that the minimum spacing requirements (below) are adhered to.
MULTIU18HP230V1DO
MULTIU24HP230V1DO
20 in min
20 in min
12 in min
12 in min
12 in min
(Air inlet side)
79 in min
12 in min
(Air inlet side)
79 in min
(Air outlet side)
(Air outlet side)
20 in min
MULTIU36HP230V1DO
20 in min
MULTIU42HP230V1DO
20 in min
12 in min
79 in min
(Air outlet side)
12 in min
(Air inlet side)
20 in min
11
CHECK AFTER INSTALLATION
INSTALLER
Check Items
Problems Due to Improper Installation
Is the installation secure?
The unit may drop, vibrate or make noises
Has the gas leakage been checked?
May cause unsatisfactory cooling (heating)
problems
Is the thermal insulation of the unit
sufficient?
May cause condensation and water formation
Is the drainage sufficient?
May cause condensation and water formation
Does the power supply voltage match
the rated voltage specified on the
nameplate?
The unit may break down or the components
may burn out
Are the refrigerant lines and wiring
correctly installed?
The unit may break down or the components
may burn out
Has the unit been safely grounded?
Risk of electrical shock
Do the line sizes comply with
requirements?
The unit may break down or the components
may burn out
Are there any obstacles near the air
inlet and outlet of the indoor and outdoor units?
The unit may break down or the components
may burn out or not perform to specifications
Is the refrigerant charge correct for
the length of refrigerant lines installed
Check to see if more refrigerant needs to
be added.
12
U.S. CONTACT INFORMATION
TRADEWINDS, LLC
www.greecomfort.com/resources
E-mail: [email protected]
Contractor Support 888-850-7928 | Mon–Fri 8AM-5PM EDT
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070
Tel: (+86-756) 8522218
Fax: (+86-756) 8669426
E-mail: [email protected] www.gree.com
CAT NO: GREE_MULTIU_INSTALL & OWNERS_062819
66129932222
Was this manual useful for you? yes no
Thank you for your participation!