Leviton R07-LB115-DSR Smart Branch Circuit Breaker, AFCI/GFCI 1-Pole 15 Amp 120-Volt 10kA Interrupt Rating Installation instructions

Add to my manuals
2 Pages

advertisement

Leviton R07-LB115-DSR Smart Branch Circuit Breaker, AFCI/GFCI 1-Pole 15 Amp 120-Volt 10kA Interrupt Rating Installation instructions | Manualzz

INSTALLATION INSTRUCTIONS / DIRECTIVES

INSTRUCCIONES DE INSTALACIÓN

Nos.

LB1xx-DF, LB1xx-DS

IMPORTANT SAFETY INSTRUCTIONS

READ ALL INSTRUCTIONS BEFORE USING.

WARNING

• TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER

SUPPLYING THIS EQUIPMENT, AND CONFIRM POWER IS OFF, before installing, removing or servicing this equipment.

• The GFCI will not protect a person against a line to line shock hazard.

• This equipment MUST BE installed and serviced by an electrician.

• Replace all doors and covers before connecting power to this equipment.

• To be installed and/or used in accordance with electrical codes and regulations.

• To be used in permanently installed and listed enclosures only.

• Install only on a single phase 120/240 VAC grounded system in a residential application.

• Do not ground neutral on the load side of the AFCI/GFCI.

• DO NOT reverse-feed or back-wire. DO NOT perform a megger or a high voltage test with the breaker in place. Remove the breaker prior to high-pot testing of the circuit.

• To reduce false tripping, do not connect to swimming pool equipment installed prior to the adoption of the 1965 National

Electrical Code.

IMPORTANTES CONSIGNES DE SÉCURITÉ

LIRE TOUTES LES DIRECTIVES AVANT D’UTILISER.

AVERTISSEMENT

• POUR ÉVITER LES RISQUES D’INCENDIE, DE DÉCHARGE ÉLECTRIQUE

OU D’ÉLECTROCUTION, SECTIONNER LE COURANT QUI ALIMENTE LE ET

S’ASSURER QU’IL EST BIEN COUPÉ, avant de procéder à l’installation, à l’entretien ou au retrait de ce dernier.

• Le DDFT n’offre aucune protection aux personnes contre les risques de décharge ligne à ligne.

• L’installation et l’entretien DOIVENT ÊTRE faits par un électricien.

• Toutes les portes et tous les couvercles qui abritent le disjoncteur doivent

être fermés avant de le connecter à l’alimentation.

• Le doit être installé et utilisé conformément aux codes de l’électricité en vigueur.

• Le produit décrit aux présentes ne peut être installé que dans des boîtiers homologués, installés de manière permanente.

• Le produit décrit aux présentes ne peut être installé que dans un système résidentiel monophasé et mis à la terre de 120/240 V c.a.

• Ne pas mettre le neutre à la terre du côté charge du DDAA/DDFT.

• NE PAS inverser l’alimentation ou raccorder par l’arrière. Retirer le avant d’effectuer toute mesure de la résistance d’isolement (Megger) ou tout autre test à tension élevée sur le circuit.

• Pour réduire les déclenchements indésirables, ne pas raccorder le produit décrit aux présentes à un circuit alimentant de l’équipement de piscine installé avant l’adoption de l’édition de 1965 du National Electrical Code américain.

SAFETY INSTRUCTIONS

• Use this branch circuit AFCI/GFCI breaker with copper or copperclad wire only.

• DO NOT install this branch circuit AFCI/GFCI breaker on a circuit that powers life support equipment because if the AFCI/GFCI trips it will shut down the equipment.

CONSIGNES DE SÉCURITÉ

• N’utiliser le DDAA/DDFT qu’avec du fil de cuivre ou plaqué cuivre.

• NE PAS installer le DDAA/DDFT sur un circuit qui alimente de l’équipement de survie parce qu’en cas de déclenchement, ce circuit sera coupé.

MEDIDAS IMPORTANTES DE SEGURIDAD

LEA TODAS LAS INSTRUCCIONES ANTES DE USARLO.

ADVERTENCIAS

• PARA EVITAR FUEGO, DESCARGA ELÉCTRICA O MUERTE, ¡INTERRUMPA

EL PASO DE ENERGÍA mediante el interruptor de circuito o fusible y pruebe que la energía esté desconectada antes de instalar, sacarlo o hacer mantenimiento a este equipo!

• El ICFT no protegerá a la persona de una descarga eléctrica de línea a línea.

• Este equipo DEBE ser instalado y mantenido por un electricista.

• Reemplace todas las puertas y cubiertas antes de conectar la energía a este equipo.

• Para instalarse y/o usarse de acuerdo con los códigos eléctricos y normas apropiadas.

• Para ser usado sólo en cajas listadas e instaladas permanentemente.

• Instálelo en una aplicación residencial sólo en un sistema a tierra de una fase sencilla de 120/240VCA.

• No conecte el neutro a tierra en el lado de la carga del ICFA/ICFT.

• No invierta la alimentación o cableado posterior. No haga un megóhmetro o prueba de alto voltaje con el lugar del interruptor. Retire el interruptor antes de hacer una prueba de alta potencia en el circuito.

• Para reducir una activación no deseada, no conecte el interruptor de circuito a un equipo de una piscina instalada antes de la adopción del Código

Eléctrico Nacional (NEC) de 1965.

INSTRUCCIONES DE SEGURIDAD

• Use este interruptor de circuito derivado ICFA/ICFT sólo con cable de cobre o revestido de cobre.

• NO instale el interruptor de circuito derivado ICFA/ICFT en un circuito que da energía a un equipo para mantener la vida porque si el ICFA/

ICFT se dispara puede apagar el equipo.

FCC STATEMENT

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the

FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

• Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

• Consult the dealer or an experienced radio/TV technician for help.

IC STATEMENT

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions:

(1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.

DÉCLARATION DE LA FCC

Cet équipement a fait l’objet de tests et a été jugé conforme aux normes en matière de dispositifs numériques de classe B, en vertu de la partie 15 des règlements de la

FCC, et conforme aux normes en matière de brouillage (NMB) préjudiciable en vertu de la réglementation du ministère canadien des Communications. Ces normes ont

été élaborées dans le but d’assurer une protection raisonnable contre le brouillage préjudiciable quand l’équipement est utilisé en milieu résidentiel. Cet équipement génère, utilise et peut irradier de l’énergie haute fréquence; s’il n’est pas installé et utilisé conformément aux directives, il peut engendrer des perturbations susceptibles de brouiller les radiocommunications. Il est cependant impossible de garantir l’absence de telles perturbations dans une installation donnée. Si cet équipement est source de parasites au niveau des récepteurs radio ou des téléviseurs, ce qu’on peut déterminer en le mettant sous et hors tension, on recommande à l’utilisateur de rectifier la situation en adoptant une ou plusieurs des mesures suivantes :

• réorienter ou déplacer l’antenne réceptrice;

• augmenter la distance entre l’équipement et le récepteur;

• brancher l’équipement à une prise sur un circuit autre que celui où est branché le récepteur;

• consulter le détaillant ou un technicien expérimenté en matière de radios ou de téléviseurs.

DÉCLARATION IC

Le present appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisee aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, meme si le brouillage est susceptible d'en compromettre le fonctionnement.

DECLARACIÓN DE LA FCC

Este equipo ha sido probado y encontrado que cumple con los límites de un producto Digital Clase B, y cumple con el artículo

15 de las reglas FCC. Estos límites están diseñados para dar protección razonable contra interferencia dañina en instalaciones residenciales. Este equipo genera, usa y puede irradiar energía de radio frecuencia y si no se instala y usa de acuerdo con las instrucciones puede causar interferencia dañina a las comunicaciones de radio. Sin embargo, no hay garantía que no ocurra interferencia en una instalación particular. Si este equipo causa interferencia a la recepción de radio o televisión, la cual se puede determinar APAGANDO O ENCENDIENDO el equipo, el usuario puede tratar de corregir la interferencia con una o más de las siguientes medidas:

• Reoriente o reubique la antena de recepción.

• Aumente la separación entre el equipo y el receptor.

• Conecte el equipo en un contacto en un circuito diferente al del receptor.

• Para ayuda consulte con el vendedor o técnico con experiencia en radio/ televisión.

DECLARACIÓN DE IC

Este producto cumple con el estándar(es) RSS exento de licencia de la Industria de Canadá. La operación está sujeta a dos condiciones:

(1) Este producto no debe causar interferencia dañina, y (2) Este producto debe aceptar cualquier interferencia recibida, incluyendo interferencia que puede causar una operación no deseada.

Patents covering this product, if any, can be found on Leviton.com/ patents.

For Technical Assistance Call: 1-800-824-3005 (USA Only) or

1-800-405-5320 (Canada Only) www.leviton.com

Les brevets associés au produit décrit aux présentes, le cas

échéant, se trouvent à l’adresse leviton.com/patents.

Ligne d’Assistance Technique : 1-800-405-5320

(Canada seulement) www.leviton.com

Las patentes que cubren este producto, si las hay, pueden encontrarse en Leviton.com/patents.

Para Asistencia Técnica llame al: 1-800-824-3005

(Sólo en EE.UU.) www.leviton.com

SÓLO PARA MÉXICO

3.

4.

5.

POLÍTICA DE GARANTIA LIMITADA DEL PRODUCTO: Leviton S de RL de CV, Lago Tana No. 43, Col. Huichapan, Del. M. Hidalgo, Ciudad de México, CP 11290 México. Tel +52 (55) 5082-1040.

Garantiza este producto durante del tiempo de limitada del producto en todas sus partes y mano de obra contra cualquier defecto de fabricación y funcionamiento a partir de la fecha de entrega o instalación del producto bajo las siguientes CONDICIONES:

1.

2.

Para hacer efectiva esta garantía, no podrán exigirse mayores requisitos que la presentación de esta póliza junto con el producto en el lugar donde fue adquirido en cualquiera de los centros de servicio que se indican a continuación.

La empresa se compromete a reemplazar o cambiar el producto defectuoso sin ningún cargo para el consumidor, los gastos de transportación que se deriven de su cumplimiento serán cubiertos por: Leviton S de RL de CV.

El tiempo de reemplazo en ningún caso será mayor a 30 días contados a partir de la recepción del producto en cualquiera de los sitios en donde pueda hacerse efectiva la garantía.

Cuando se requiera hacer efectiva la garantía mediante el reemplazo del producto, esto se podrá llevar a cabo en: Leviton S de RL de CV.

Esta garantía no es válida en los siguientes casos: A) Cuando el producto ha sido utilizado en condiciones distintas a las normales. B) Cuando el producto no ha sido operado de acuerdo con el instructivo de uso en idioma español proporcionado. C) Cuando el producto ha sido alterado o reparado por personas no autorizadas por Leviton S de RL de CV.

6.

7.

El consumidor podrá solicitar que se haga efectiva la garantía ante la propia casa comercial donde adquirió el producto.

En caso de que la presente garantía se extraviara el consumidor puede recurrir a su proveedor para que se le expida otra póliza de garantía previa presentación de la nota de compra o factura respectiva.

DATOS DEL USUARIO

NOMBRE: _____________ DIRECCIÓN:_________

COL: _________________ C.P. ________________

CIUDAD: ___________________________________

ESTADO: ___________________________________

TELÉFONO: ________________________________

DATOS DE LA TIENDA O VENDEDOR

RAZÓN SOCIAL: ________ PRODUCTO: ________

MARCA: _______________ MODELO: __________

NO. DE SERIE: ______________________________

NO. DEL DISTRIBUIDOR:______________________

DIRECCIÓN: ________________________________

COL: _________________ C.P. ________________

CIUDAD: ___________________________________

ESTADO: ___________________________________

TELÉFONO: ________________________________

FECHA DE VENTA: ___________________________

FECHA DE ENTREGA O INSTALACIÓN: __________

© 2019 Leviton Mfg. Co., Inc.

INSTALLATION INSTRUCTIONS - ENGLISH

Dual-Function AFCI/GFCI Branch Circuit Breaker

INSTALLATION

WARNING: TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER

SUPPLYING THIS EQUIPMENT, AND CONFIRM POWER IS OFF, before installing, removing or servicing this equipment.

NOTE: DO NOT INSTALL AFCI, GFCI, AFCI/GFCI, OR GFPE CIRCUIT

BREAKERS ON CIRCUITS WITH SHARED NEUTRALS. FALSE TRIPS

WILL OCCUR

1.

Turn OFF all power to the panelboard by moving the handle of the main breaker to OFF position (see fig. 1) . NOTE: If installing the AFCI/GFCI breaker in a sub-panel turn power OFF from the breaker located in the main panel.

2.

Remove panel cover (if necessary) .

3.

Strip and connect the load power and load neutral conductors to appropriate terminal lugs (see fig. 1 and the Terminations table) . NOTE: The load neutral

MUST be connected to the load neutral terminal, NOT the main neutral terminal.

4.

Place handle of the AFCI/GFCI branch circuit breaker to the OFF position

(see fig. 2) . NOTE: The circuit breaker CAN NOT be switched to the ON position until the installation is complete and power is supplied to the unit.

NOTE: Leviton AFCI/GFCI branch circuit breakers contain a Reset Lockout feature that will prevent putting the breaker in the ON position if the

AFCI/GFCI cannot pass its internal test, indicating that it may not be able to provide protection in the event of a ground fault.

5.

Place AFCI/GFCI branch circuit breaker into the panel as shown (see fig. 4) .

6.

Install test instruction label and occupant’s test reminder card (supplied) .

7.

Replace all doors and covers before turning ON power to this equipment.

Fig. 1

C

B

A

Load Power

(Brass Terminal)

Load Neutral

(Silver Terminal)

ON OFF

Main Breaker

A

B

Fig. 2

Hooks

Guides

Fig. 3

Hooks

PK-A3202-10-02-2C

Handle

OFF

Handle

ON

Guides

TO ENABLE LB1xx-DS CIRCUIT BREAKER SMART FEATURES

USING THE My Leviton App, REFER TO THE SMART HUB (LDATA)

INSTRUCTIONS.

Fig. 4 Fig. 5 “GF” LED

Align guides

TESTING INSTRUCTIONS

WARNING: Test monthly to ensure continued protection.

1.

Turn power OFF or unplug all loads downstream of the AFCI/GFCI branch circuit breaker.

2.

Turn power to the panelboard ON by moving the main breaker to the ON position (see fig 1) . NOTE: If installed in a sub-panel restore power from the breaker located in the main panel.

3.

Place handle of the AFCI/GFCI branch circuit breaker to the OFF position

(see fig. 2) , then place the handle to the ON position (see fig. 3) .

4.

If the AFCI/GFCI branch circuit breaker can be put into the ON position, and the handle window is green, it is working properly.

5.

If the AFCI/GFCI branch circuit breaker handle cannot be put into the ON position, recheck wiring and installation, or contact an electrician to make the repairs.

HANDLE OPERATION AND LED DIAGNOSTICS

Each circuit breaker’s rocker handle window displays its operational status using an intuitive color scheme. In addition, LEDs indicate trip condition and are illuminated - even when the breaker is tripped - because the circuit breaker’s electronics are powered from the line side instead of the load side, an industry first

(see Handle operation and LED diagnostics table & fig. 5) .

Press

OR “AF” LED

“GF” LED

ON

Press until breaker snaps into place

Align hooks and guides

In the event that the circuit breaker trips move the handle to the OFF position and then to the ON position. If the circuit breaker will not reset or trips again turn OFF or unplug all loads downstream of the circuit breaker and try again. If the circuit breaker still will not reset contact an electrician to make repairs.

SAVE THESE INSTRUCTIONS

TERMINATIONS HANDLE OPERATION AND LED DIAGNOSTICS

Termination

Point

A (Brass)

B (Silver)

C

Branch

Wire

Load

Power

Load

Neutral

Wire Gauge

#4 AWG - #8 AWG

#10 AWG - #14 AWG

#4 AWG - #8 AWG

#10 AWG - #14 AWG

Ground #4 AWG - #6 AWG

#8 AWG

#10 AWG - #14 AWG

Strip Length

0.40 in.

0.40 in.

0.40 in.

0.40 in.

0.50 in.

0.50 in.

0.50 in.

Torque

45 in-lbs.

35 in-lbs.

45 in-lbs.

35 in-lbs.

35 in-lbs.

25 in-lbs.

20 in-lbs.

Handle Window “AF” LED

Green OFF

Red

Red

Red

Red

OFF

ON (solid)

OFF

ON (blinking)

OFF

Red

White

“GF” LED

OFF

OFF

OFF

ON (solid)

OFF

ON (blinking)

Device Status

ON

Overload or short-circuit trip

Series arc-fault trip

Ground fault trip

1 sec. delay -Parallel arc-fault trip

3 sec. delay -Neutral Miswired

ON (blinking) ON (blinking) 0.1 sec. delay -Electronics self-test failure

(breaker will be locked out and must be replaced)

OFF OFF Manual OFF

LIMITED PRODUCT WARRANTY

For Leviton’s limited product warranty, go to www.leviton.com

. For a printed copy of the warranty you may call 1-800-323-8920 .

PK-A3202-10-02-2C

DIRECTIVES - FRANÇAIS

Disjoncteur de dérivation à protection contre les arcs électriques et les fuites à la terre (DDAA/DDFT)

INSTALLATION

AVERTISSEMENT : POUR ÉVITER LES RISQUES D’INCENDIE, DE DÉCHARGE

ÉLECTRIQUE OU D’ÉLECTROCUTION, COUPER LE COURANT QUI ALIMENTE

CE DISPOSITIF ET S’ASSURER QU’IL LE SOIT avant de procéder à l’installation,

à l’entretien ou au retrait de ce dernier.

REMARQUE : NE PAS INSTALLER DE DDAA, DE DDFT, DE DDAA/DDFT NI DE

DPÉFT SUR DES CIRCUITS À NEUTRE PARTAGÉ. CELA POURRAIT PRODUIRE

DES DÉCLENCHEMENTS INTEMPESTIFS.

1.

Couper complètement le courant qui alimente le panneau de branchement en mettant la manette du disjoncteur principal à OFF (fig. 1) . REMARQUE : si le DDAA/DDFT doit être installé dans un sous-panneau, couper le courant à partir du disjoncteur qui se trouve sur le panneau principal.

2.

Retirer le couvercle du panneau (au besoin) .

3.

Dénuder les conducteurs de charge (neutre et alimentation) et les raccorder aux bornes appropriées (voir la figure 1 et le tableau RACCORDEMENTS) .

REMARQUE : le neutre de charge DOIT être raccordé à la borne de neutre de charge, et

NON à la borne de neutre principale.

4.

Mettre le levier du DDAA/DDFT à la position OFF (fig. 2) . REMARQUE : NE PAS mettre le disjoncteur à ON avant que l’installation soit terminée et que son alimentation ait été rétablie. REMARQUE : les DDAA/DDFT de dérivation de Leviton ont une fonction de verrouillage qui empêche de mettre leur levier à ON si leur mécanisme de vérification interne détecte la possibilité qu’ils ne puissent pas couper le courant en cas de fuites à la terre.

5.

Insérer le DDAA/DDFT dans le panneau de la manière illustrée (fig. 4) .

6.

Apposer l’étiquette de procédure de vérification et la carte de rappel à l’intention des occupants (toutes deux fournies) .

7.

Toutes les portes et tous les couvercles qui abritent le disjoncteur doivent être fermés avant de mettre ce dernier sous tension.

Fig. 1

ALLUMÉ ÉTEINT

Disjoncteur principal

C

B

A

Alimentation de charge

(borne laitonnée)

Neutre de charge

(borne argentée)

Fig. 4

A

B

Fig. 2

Crochets

Guides

Fig. 3

Crochets

Guides

Fig. 5

Levier à

ON

Témoin GF

Levier à

OFF

POUR ACTIVER LES FONCTIONS DES DISJONCTEURS LB1XX-DS VIA

L’APPLICATION MY LEVITON, ON PEUT SE REPORTER AUX DIRECTIVES

RELATIVES AU CONCENTRATEUR INTELLIGENT (LDATA).

Aligner les guides

PROCÉDURE DE VÉRIFICATION

AVERTISSEMENT : ce dispositif doit être testé tous les mois pour s’assurer qu’il offre toujours la protection voulue.

1.

Mettre toutes les charges en aval du DDAA/DDFT hors tension, ou les débrancher.

2.

Rétablir le courant qui alimente le panneau de branchement en mettant le disjoncteur principal à ON (fig. 1) . REMARQUE : si le DDAA/DDFT est installé dans un sous-panneau, rétablir le courant à partir du disjoncteur qui se trouve sur le panneau principal.

3.

Mettre le levier du DDAA/DDFT à la position OFF (fig. 2), puis à la position ON (fig. 3) .

4.

Si le levier du DDAA/DDFT peut être mis à la position ON, et si la fenêtre de ce levier est verte, le dispositif fonctionne bien.

5.

Si le levier du DDAA/DDFT ne peut pas être mis à la position ON, vérifier le câblage et l’installation, ou communiquer avec un électricien pour effectuer les réparations requises.

LEVIER ET TÉMOIN

Appuyer

OU Témoin AF

Témoin GF

ON

La fenêtre du levier du DDAA/DDFT affiche l’état du dispositif au moyen de couleurs

évocatrices. Des témoins s’allument en outre pour indiquer les déclenchements, et ce, même quand le courant a été coupé, parce que leurs circuits électroniques sont alimentés du côté ligne au lieu du côté charge, une première dans l’industrie (voir la figure 5 et le tableau FONCTIONNEMENT DU LEVIER ET DES TÉMOINS) .

Si le disjoncteur se déclenche, mettre le levier à OFF, puis encore à ON. S’il ne se réarme pas, ou s’il se déclenche à nouveau, débrancher ou mettre toutes les charges en aval hors tension, et essayer de nouveau. Si le disjoncteur ne se réarme toujours pas, communiquer avec un électricien pour effectuer les réparations requises.

Aligner les crochets et les guides

Appuyer jusqu’à enclenchement

CONSERVER LES PRÉSENTES DIRECTIVES

RACCORDEMENTS

A (laitonnée) Charge

Ligne

B (argentée) Charge

Neutre

C

Borne Fil Calibre

4 à 8 AWG

10 à 14 AWG

4 à 8 AWG

10 à 14 AWG

Terre 4 à 6 AWG

8 AWG

10 à 14 AWG

Longueur de dénudage

10,16 mm

10,16 mm

10,16 mm

10,16 mm

12,70 mm

12,70 mm

12,70 mm

Couple de serrage

45 po/lb

35 po/lb

45 po/lb

35 po/lb

35 po/lb

25 po/lb

20 po/lb

FONCTIONNEMENT DU LEVIER ET DES TÉMOINS

Fenêtre du levier Témoin AF (arcs) “GF” LED État

Verte Éteint Éteint Le dispositif est sous tension

Rouge

Rouge

Éteint

Allumé

Éteint

Éteint

Surcharge ou court-circuit

Amorçage d’arc sériel

Rouge

Rouge

Rouge

Éteint

Clignotant

Éteint

Clignotant

Allumé

Éteint

Clignotant

Fuite à la terre

Intervalles de 1 s = Amorçage d’arc parallèle

Intervalles de 3 s = Neutre mal raccordé

Clignotant Intervalles de 0,1 s = Échec de l’autovérification des composants électroniques (le disjoncteur ne peut être remis à ON et doit être remplacé)

Blanc Éteint Éteint Mise hors tension manuelle

GARANTIE LIMITÉE SUR LES PRODUITS

Pour consulter les garanties offertes par Leviton, on peut se rendre au www.leviton.com

. Pour en obtenir des versions imprimées, il suffit de composer le 1-800-323-8920 .

© 2019 Leviton Mfg. Co., Inc.

INSTRUCCIONES DE INSTALACIÓN - ESPAÑOL

Interruptor del circuito derivado ICFA/ICFT de doble función

INSTALACIÓN

Fig. 1 Fig. 2

ADVERTENCIA: PARA EVITAR FUEGO, DESCARGA ELÉCTRICA O MUERTE,

¡INTERRUMPA EL PASO DE ENERGÍA mediante el interruptor de circuito o fusible y pruebe que la energía esté desconectada antes de instalar, sacarlo o hacer mantenimiento!

APAGADO ENCENDIDO

Interruptor de circuitos principal

NOTA: NO USE INTERRUPTORES AUTOMÁTICOS DE CIRCUITOS DE TIPO ICFA,

ICFT, ICFA/ICFT O FTPE EN CIRCUITOS QUE COMPARTAN CONEXIÓN A NEUTRO.

PUEDEN OCURRIR ACTIVACIONES EN FALSO

1.

DESCONECTE la energía del tablero de alimentación moviendo la manija del interruptor de circuito principal a la posición de APAGADO (ver fig. 1) .

NOTA: Si está instalando un interruptor ICFA/ICFT en un sub-panel desconecte la energía en el interruptor ubicado en el panel principal

2.

Saque la cubierta del panel (si es necesario) .

3.

Pele y conecte los conductores de carga de energía y de neutro a las terminales apropiadas (ver figura 1 y cuadro de Terminaciones) . NOTA: El neutro de la carga se

DEBE conectar a la terminal neutra de la carga, NO a la terminal neutra principal.

4.

Coloque la manija del interruptor de circuito derivado ICFA/ICFT en la posición de APAGADO

(ver fig. 2) . NOTA: El la manija del interruptor de circuito NO SE PUEDE cambiar a la posición de ENCENDIDO hasta que la instalación esté terminada y que se esté suministrando energía a la unidad. NOTA: el interruptor de circuito derivado ICFA/ICFT de Leviton tienen un bloqueo de reinicio, que previene poner el interruptor en la posición de ENCENDIDO si el ICFA/ICFT no pasa su prueba interna, indicando que no es capaz de proporcionar protección en el caso de un falla a tierra.

5.

Coloque el interruptor de circuito derivado ICFA/ICFT en el panel como se muestra (ver fig. 4) .

6.

Instale la etiqueta de instrucciones de prueba y la tarjeta de recordatorio de prueba al ocupante

(suministradas) .

7.

Reemplace todas las puertas y cubiertas antes que el equipo tenga ENERGÍA.

C

B

A

Carga

(Terminal Latón)

Neutro de la

Carga

(Terminal plateado)

Fig. 4

A

B

Ganchos

Guías

Fig. 3

Ganchos

Guías

Fig. 5

Manija en

APAGADO

Manija en

ENCENDIDO

DEL “GF”

Alinee las guías PARA HABILITAR LAS CARACTERÍSTICAS SMART DEL INTERRUPTOR DE CIRCUITO

LB1xx-DS UTILIZANDO LA APLICACIÓN (App) My Leviton, CONSULTE LAS

INSTRUCCIONES DEL CONCENTRADOR SMART (LDATA).

INSTRUCCIONES DE PRUEBA

O DEL “AF” ENCENDIDO

ADVERTENCIA: Pruebe mensualmente para asegurar una protección continua.

1.

APAGUE o desconecte todas las cargas del circuito derivado del interruptor ICFA/ICFT.

2.

ENCIENDA la carga del tablero moviendo el interruptor principal a la posición de ENCENDIDO

(ver fig. 1) . NOTA: Si se instala en un sub-panel restablezca la energía en el interruptor ubicado en el panel principal.

3.

Ponga la manija del interruptor del circuito derivado ICFA/ICFT en la posición de APAGADO (ver fig. 2) , luego, ponga la manija en la posición de ENCENDIDO (ver fig. 3) .

4.

Si el interruptor del circuito derivado ICFA/ICFT se puede poner en la posición de ENCENDIDO y la ventana de la manija es verde, está funcionando perfectamente.

5.

Si la manija del interruptor del circuito derivado ICFA/ICFT no se puede poner en la posición de

ENCENDIDO, revise el cableado y la instalación, o póngase en contacto con un electricista para hacer la reparación.

OPERACIÓN DE LA MANIJA Y DIAGNÓSTICO DEL

Presione

DEL “GF”

Presione hasta que encaje en su sitio

Cada ventana de la manija de palanca del interruptor de circuito, muestra su estado operativo con un esquema intuitivo de color. Además, los DELs indican la condición de disparo y se iluminan - incluso cuando el interruptor se ha disparado - porque el interruptor de circuito de los electrónicos está alimentado del lado de la línea en lugar del lado de la carga, la primera del sector (ver operación de la manija y la tabla de diagnóstico DEL y fig. 5) .

Alinee los ganchos y guías

En el caso que el interruptor se dispare, mueva la manija a la posición de APAGADO y luego a la posición ENCENDIDO. Si el interruptor no reinicia o activa, APAGUE o desenchufe todas las cargas conectadas al interruptor de circuito y trate otra vez.

Si el interruptor de circuito no reinicia, contacte con un electricista para hacer las reparaciones.

GUARDE ESTAS INSTRUCCIONES

TERMINACIONES

OPERACIÓN DE LA MANIJA Y DIAGNÓSTICO DEL

Ventana de la manija

DEL “AF” DEL “GF” Estado de los dispositivos

Punto de

Terminación

Conductor del circuito derivado

Calibre del cable Medida de pelado

Presión Verde APAGADO APAGADO ENCENDIDO

Rojo

Rojo

APAGADO APAGADO

ENCENDIDO (fijo) APAGADO

Sobrecarga o disparo por cortocircuito

Disparo en serie por falla de arco

A (Latón) Carga #4 AWG - #8 AWG

#10 AWG - #14 AWG

0.40 in.

0.40 in.

45 in-lbs.

35 in-lbs.

Rojo APAGADO ENCENDIDO (fijo) Activación de falla a tierra

#4 AWG - #8 AWG

#10 AWG - #14 AWG

0.40 in.

0.40 in.

45 in-lbs.

35 in-lbs.

Rojo ENCENDIDO

(Parpadeando)

APAGADO Retraso de 1 seg. -activación de falla de arco en

B (Plateado) Neutro de

Carga

0.50 in.

0.50 in.

0.50 in.

35 in-lbs.

25 in-lbs.

20 in-lbs.

ENCENDIDO

(Parpadeando) paralelo Retraso de 3 seg. -Neutro mal cableado

C Tierra #4 AWG - #6 AWG

#8 AWG

#10 AWG - #14 AWG

Rojo

APAGADO

ENCENDIDO

(Parpadeando)

ENCENDIDO

(Parpadeando)

Retraso de 0.1 seg. -La autoprueba del dispositivo electrónico ha fallado (el interruptor automático se bloqueará y debe ser remplazado)

GARANTÍA LIMITADA DEL PRODUCTO

Blanco APAGADO APAGADO APAGADO manual

Para la garantía limitada del producto de Leviton, vaya a www.leviton.com

. Para obtener una copia impresa de la garantía le puede llamar al 1-800-323-8920 .

PK-A3202-10-02-2C

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement