Victron Energy Phoenix Inverter 3000VA 120V Datasheet

Add to my manuals
2 Pages

advertisement

Victron Energy Phoenix Inverter 3000VA 120V Datasheet | Manualzz

Phoenix Inverters 3 kVA

(120V/60Hz)

Phoenix Inverter

24/3000 www.victronenergy.com

SinusMax - Superior engineering

Developed for professional duty, the Phoenix range of inverters is suitable for the widest range of applications.

The design criteria have been to produce a true sine wave inverter with optimised efficiency but without compromise in performance. Employing hybrid HF technology, the result is a top quality product with compact dimensions, light in weight and capable of supplying power, problem free, to any load.

Extra start-up power

A unique feature of the SinusMax technology is very high start-up power. Conventional high frequency technology does not offer such extreme performance. Phoenix inverters, however, are well suited to power up difficult loads such as refrigeration compressors, electric motors and similar appliances.

Virtually unlimited power thanks to parallel 3-phase and split phase operation capability

Up to 6 units inverters can operate in parallel to achieve higher power output. Six 24/3000 units, for example, will provide 15 kW / 18 kVA output power. Operation in 3-phase or split phase configuration is also possible.

To transfer the load to another AC source: the automatic transfer switch

If an automatic transfer switch is required we recommend using the MultiPlus inverter/charger instead. The switch is included in these products and the charger function of the MultiPlus can be disabled. Computers and other electronic equipment will continue to operate without disruption because the MultiPlus features a very short switchover time (less than 20 milliseconds).

Communications interface

These larger Phoenix inverter models come with a VE.Bus port. All you need to connect to your PC is our MK3-

USB VE.Bus to USB interface (see under accessories). Together with our VictronConnect or VEConfigure software, which can be downloaded free of charge from our website, parameters of the inverters can be customized. This includes output voltage and frequency, over and under voltage settings and programming the relay. This relay can for example be used to signal several alarm conditions, or to start a generator. The inverters can also be connected to a GX device (eg Cerbo GX) for monitoring and control.

New applications of high power inverters

The possibilities of paralleled high power inverters are truly amazing. For ideas, examples and battery capacity calculations please refer to our book ‘Energy Unlimited’ (available free of charge from Victron Energy and downloadable from www.victronenergy.com

).

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands

General phone: +31 (0)36 535 97 00 | E-mail: [email protected] www.victronenergy.com

Phoenix Inverter

Parallel,3-phase and split-phase operation

Input voltage range (V DC)

Output

Cont. output power at 25 º C / 77 º F (VA) (2)

Cont. output power at 25 º C / 77 º F (W)

Cont. output power at 40 º C / 104 º F (W)

Cont. output power at 65 º C / 150 º F (W)

Peak power (W)

Max. efficiency (%)

Zero load power (W)

Zero load power in AES mode (W)

Zero load power in Search mode (W)

Programmable relay (3)

Protection (4)

VE.Bus communication port

Remote on-off

Common Characteristics

Common Characteristics

Battery-connection

120 V AC-connection

Weight

Dimensions (hxwxd)

Safety

Emission Immunity

1) Can be adjusted to 60 Hz and to 240 V

2) Non-linear load, crest factor 3:1

3) Programmable relay that can a.o. be set for

general alarm, DC under voltage or genset

start/stop function.

AC rating: 120 V/4A

DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC

Phoenix Inverter Control

This panel can also be used on a MultiPlus inverter/charger when an automatic transfer switch but no charger function is desired.

The brightness of the LEDs is automatically reduced during night time.

12/3000 24/3000

3000

2400

2200

1700

6000

93

20

15

8

9.5 – 17V

Yes

INVERTER

19 – 33V

Output voltage: 120 VAC ± 2% Frequency: 60 Hz ± 0.1% (1)

3000

94

20

15

10

2400

2200

1700

6000

GENERAL

Yes a - g

For parallel and three phase operation, remote monitoring and system integration

Yes

Operating temperature range: -40 to +65ºC (-40 - 150°F)

Humidity (non-condensing): max 95%

ENCLOSURE

Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21

2+2 M8 bolts

Screw terminals

18 kg 38 lbs

362x258x218 mm 14.3x10.2x8.6 inch

STANDARDS

EN 60335-1

EN 55014-1 / EN 55014-2

4) Protection key:

a) output short circuit

b) overload

c) battery voltage too high

d) battery voltage too low

e) temperature too high

f) 120 V AC on inverter output

g) input voltage ripple too high

Computer controlled operation and monitoring

Several interfaces are available:

Color Control GX

Provides monitor and control. Locally, and also remotely on the VRM Portal.

MK3-USB VE.Bus to USB interface

Connects to a USB port (see ‘A guide to

VEConfigure’)

VE.Bus to NMEA 2000 interface

Connects the device to a NMEA2000 marine electronics network. See the NMEA2000 & MFD integration guide

BMV Battery Monitor

The BMV Battery Monitor features an advanced microprocessor control system combined with high resolution measuring systems for battery voltage and charge / discharge current. Besides this, the software includes complex calculation algorithms, like

Peukert’s formula, to exactly determine the state of charge of the battery. The BMV selectively displays battery voltage, current, consumed Ah or time to go. The monitor also stores a host of data regarding performance and use of the battery.

Several models available (see battery monitor documentation).

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands

General phone: +31 (0)36 535 97 00 | E-mail: [email protected] www.victronenergy.com