Climatemaster Tranquility® Compact High CapacityTC_L Series Horizontal 6 – 10 Ton (21.1 – 35.2 kW) Vertical 6 – 25 Ton (21.1 kW – 87.9 kW) Install Manual
Advertisement
Advertisement
Tranquility
®
Compact
High Capacity
(TC_L) Series
MODELS TC_LH072-120
TC_LV072-300
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0084N01
Revised: May 5, 2020
Table of Contents
Model Nomenclature
General Information
TC_LH Physical Data (includes unit w/WSE) 6
TC_LH072-120 Dimensional Data 7
3
4
TC_LH072-120 w/WSE Dimensional Data 8
TC_LV Physical Data (includes unit w/WSE) 9
TC_LV072-120 Dimensional Data 10
TC_LV072-120 w/WSE Dimensional Data 11
TC_LV160-240 Dimensional Data 12
TC_LV160-240 w/WSE Dimensional Data 13
TC_LV300 Dimensional Data 14
TC_LV300 w/WSE Dimensional Data 15
Horizontal Installation 16
TC_LH Field Conversion of Air Discharge 18
Vertical Installation 21
TC_LV Field Conversion of Air Discharge 22
TC_LV072-240 Field Conversion of Air Discharge 23
TC_LV300 Field Conversion of Air Discharge 26
TC_LV Field Conversion of Control Box 29
TC_LV Field Conversion of Water Connections 30
Vertical Condensate Installation
Piping Installation
Water-Loop Heat Pump Applications
Ground-Loop Heat Pump Applications
36
38
39
43
31
32
33
34
Ground-Water Heat Pump Applications
Water Quality Standards
Electrical - Line Voltage
Electrical - Power Wiring
Electrical - Power & Low Voltage Wiring
Electrical - Low Voltage Wiring
44
45
Electrical - Thermostat Wiring 46
Typical Wiring Diagram - TC_L Units with CXM 47
Typical Wiring Diagram - TC_L Units with MPC 48
Typical Wiring Diagram - TC_L Units with DXM 49
Typical Wiring Diagram - TC_L Units with LON 50
CXM Controls 51
52
54
55
DXM Controls
Safety Features
CXM and DXM Controls
Blower Adjustment
VFD Operation
Tensioning V-Belt Drives
Blower Sheave Information
TC_L072 Blower Performance 62
56
57
60
61
TC_L096 Blower Performance 63
TC_L120 Blower Performance 65
Blower Performance Data – TC_LV160 Standard Unit 67
Blower Performance Data – TC_LV192 Standard Unit 68
Blower Performance Data – TC_LV240 Standard Unit 69
Blower Performance Data – TC_LV300 Standard Unit 72
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Table of Contents, Cont’d.
Unit Starting and Operating Conditions
Piping System Cleaning and Flushing
Unit Starting and Operating Conditions
Unit Start-Up Procedure
Unit Operating Conditions
Start-Up Log Sheet
Preventive Maintenance
Circuit Diagram with Safety Devices
Functional Troubleshooting
Performance Troubleshooting
Functional Troubleshooting - I-P Units
Warranty (U.S. & Canada)
Revision History
78
79
80
81
73
74
75
76
82
83
84
85
88
2 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Model Nomenclature
1 2 3
TC H
4 5 6
0 9 6
7
A
8
H
9
C
MODEL TYPE
TC = TRANQUILITY ® COMPACT
COMMERCIAL HFC-410A
OPTION RANGE
4
F
G
D
3
E
H
2
B
C
1
A
CONFIGURATION
H = HORIZONTAL
V = VERTICAL
TCV
ONLY
{
UNIT SIZE
072
096
120
160
192
240
300
REVISION LEVEL
A = CURRENT REVISION
VOLTAGE
F = 460/60/3
H = 208/230/60/3 (FACTORY WIRED 208)
N = 575/60/3
ETL Approved
USA & Canada
{
CONTROLS
C = CXM
D = DXM
L = CXM w/LON
M = DXM w/LON
N = CXM w/MPC
P = DXM w/MPC
CABINET INSULATION / FILTER RAILS/FRAMES
TCV TCH
ULTRA QUIET
NO
1” FILTER
FRAMES
YES
NO
2” FILTER
FRAMES
YES
NO
4” FILTER
FRAMES
YES
NO
YES
YES
NO
YES
NO
YES
NO
NO
NO
NO
NO
YES
YES
YES
NO
NO
NO
NO
YES
NO
YES
NO
YES
NO
YES
1” FILTER
RAIL
YES
NO
NO
YES
NO
2” FILTER
RAIL
NO
NO
YES
NO
YES
YES
NO
NO
NO
YES
YES
NO
NO
YES
NO
10 11 12 13 14 15
3 A A L S S
S = STANDARD
A = DUAL POINT POWER
TCH
ONLY
TCV
ONLY
{
{
AIR FLOW OPTIONS
LB = LEFT RETURN/BACK DISCHARGE
LS = LEFT RETURN/STRAIGHT DISCHARGE
RB = RIGHT RETURN/BACK DISCHARGE
RS = RIGHT RETURN/STRAIGHT DISCHARGE
VS = LEFT RETURN S.S. DRAIN PAN/STRAIGHT DISCHARGE
WB = RIGHT RETURN S.S. DRAIN PAN/BACK DISCHARGE
WS = RIGHT RETURN S.S. DRAIN PAN/STRAIGHT DISCHARGE
BF = BACK RETURN/FRONT DISCHARGE
BT= BACK RETURN/TOP DISCHARGE
FB = FRONT RETURN/BACK DISCHARGE
FT = FRONT RETURN/TOP DISCHARGE
YF = BACK RETURN S.S. DRAIN PAN/FRONT DISCHARGE
YT = BACK RETURN S.S. DRAIN PAN/TOP DISCHARGE
ZB = FRONT RETURN S.S. DRAIN PAN/BACK DISCHARGE
ZT = FRONT RETURN S.S. DRAIN PAN/TOP DISCHARGE
HEAT EXCHANGER OPTIONS
CUPRO-NICKEL
WATER COIL
WATER SIDE
ECONOMIZER
OPTION
2
3
N
1
4
A
C
J
YES
NO
YES
NO
YES
N/A
N/A
N/A
N/A
YES
NO
YES
NO
NO
YES
NO
NO
YES
YES
NO
YES
NO
YES
NO
YES
NO
BLOWER DRIVE PACKAGE
A = STANDARD RPM & STANDARD MOTOR
B = LOW RPM & STANDARD MOTOR
C = HIGH RPM & STANDARD MOTOR
D = STANDARD RPM & LARGE MOTOR
E = HIGH RPM & LARGE MOTOR
F = VARIABLE FREQUENCE DRIVE*
*VFD Option comes with DXM2 controls c l i m a t e m a s t e r.c o m 3
4
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
General Information
Safety
Warnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any installation, service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury.
DANGER labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which, if not avoided, could result in minor or moderate injury or product or property damage.
NOTICE: Notification of installation, operation or maintenance information, which is important, but which is not hazard-related.
� WARNING!
�
WARNING!
The EarthPure ® Application and Service Manual should be read and understood before attempting to service refrigerant circuits with HFC-410A.
� WARNING!
�
WARNING!
To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.
� CAUTION!
�
CAUTION!
To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and filters can quickly become clogged with construction dirt and debris, which may cause system damage and void product warranty.
� WARNING!
�
WARNING! The installation of water-source heat pumps and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
� WARNING!
�
WARNING!
All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants.
If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
Inspection - Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Ensure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not filed within 15 days, the freight company can deny the claim without recourse.
Note: It is the responsibility of the purchaser to file all necessary claims with the carrier. Notify your equipment supplier of all damage within fifteen (15) days of shipment.
Storage - Equipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times.
Unit Protection - Cover units on the job site with either the original packaging or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing any of the system components. Remove any dirt or debris found in or on these components.
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Pre-Installation - Installation, Operation, and
Maintenance instructions are provided with each unit. Horizontal equipment is designed for installation above false ceiling or in a ceiling plenum. Other unit configurations are typically installed in a mechanical room.
The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Keep the cabinet covered with the original packaging until installation is complete and all plastering, painting, etc. is finished.
3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
5. Some airflow patterns and some control box locations are field convertible. Locate the conversion section of this IOM.
General Information, Cont’d.
� CAUTION!
�
CAUTION!
All three phase scroll compressors must have direction of rotation verified at start-up. Verification is achieved by checking compressor Amp draw. Amp draw will be substantially lower compared to nameplate values.
Additionally, reverse rotation results in an elevated sound level compared to correct rotation. Reverse rotation will result in compressor internal overload trip within several minutes.
Verify compressor type before proceeding.
� CAUTION!
�
CAUTION!
DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.).
Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life.
Always move and store units in an upright position. Tilting units on their sides may cause equipment damage.
� CAUTION! �
CAUTION!
CUT HAZARD - Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.
c l i m a t e m a s t e r.c o m 5
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LH Physical Data
Model
Compressor Quantity
Number of Circuits (Compressors)
Factory Charge HFC-410a (oz) [kg] per circuit
Blower Motor
Blower Motor Quantity
Standard Motor (hp) [kW]
* Large Motor (hp) [kW]
Blower
No. of Blowers
Blower Wheel Size D x W (in) [cm]
Water Connection Size
FPT (in) [mm]
Coax Volume
Volume (US Gallons) [liters]
Condensate Connection Size
072
60 [1.70]
1 [0.75]
2 [1.49]
Scroll
2
1
096
2 [1.49]
3 [2.24]
1
12 x 12 [30.48 x 30.48]
1-1/4" [31.8]
1.62 [6.13]
76 [2.15]
1.81 [6.85]
120
80 [2.27]
3 [2.24]
5 [3.73]
1-1/2" [38.1]
2.40 [9.08]
FPT (in) [mm]
Air Coil Data
3/4" [19.1]
Air Coil Dimensions H x W (in) [cm]
Air Coil Total Face Area (ft 2 ) [m 2 ]
Miscellaneous Data
Filter Standard - 1" [25.4mm] Throwaway
(qty) (in) [cm]
Weight - Operating (lbs) [kg]
Weight - Packaged (lbs) [kg]
20 x 54 [50.8 x 137.2]
7.5 [0.70]
20 x 64 [50.8 x 162.6]
8.9 [0.83]
(QTY.3) 16 x 20 [40.6 x 50.8]
(QTY.1) 20 x 20 [50.8 x 50.8]
586 [265.8] 644 [292.1] 698 [316.6]
626 [283.9]
* Unit with “F” Blower Drive Package is always Large Motor.
All units have grommet compressor mountings, and 1/2” & 1-3/4” electrical knockouts.
684 [310.3] 738 [334.8]
TC_LH072-120 Corner Weights
Weight - Operating (lbs) [kg]
Weight - Packaged (lbs) [kg]
Weight - Corner - Control box/
Compressor side (lbs) [kg]
Weight - Corner - Compressor side (lbs) [kg]
Weight - Corner - Blower side (lbs) [kg]
Weight - Corner - Air Coil side (lbs) [kg]
TC_LH072 TC_LH096 TC_LH120
586 [265.8] 644 [292.1] 698 [316.6]
626 [283.9] 684 [310.3] 738 [334.8]
235 [106.6] 254 [115.2] 271 [122.9]
101 [45.8]
180 [81.6]
70 [31.8]
120 [54.4]
190 [86.2]
80 [36.3]
137 [62.1]
200 [90.7]
90 [40.8]
Unit with WSE Option
TC_LH Series
Water Coil Dimensions (in) [cm]
Internal Water Coil Volume (Gal) [L]
Weight - Operating (lbs.) [Kg]
072
20 x 54 [50.8 x 137.2]
5.6 [21.6]
838 [380]
096 120
20 x 60 [50.8 x 152.4]
6.2 [23.5] 6.8 [25.7]
921 [418] 998 [453]
6 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LH072-120 Dimensional Data
CAP
[3.3cm] condensate
U
T
BSP
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 5 AND 6.
LEFT RETURN STRAIGHT DISCHARGE
A
BSP
Note 6
RIGHT RETURN STRAIGHT DISCHARGE
BSP
B
C
O
CAP
FRONT
PQR
1.0”
[2.54cm]
CBP
K
M
F
EAP
G E
D
LEGEND
CAP=Compressor Access Panel
CBP=Control Box Panel
BSP=Blower Service Panel
EAP=Expansion Valve Access panel
1=Water Outlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
2=Water Inlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
3=Condensate 3/4” FPT
4=High Voltage 1-1/8” [2.9cm] KO
5=Low Voltage 7/8” [2.2cm] KO
HANGER BRACKET DIMENSIONS
CONTROL BOX
1
EAP
Note 6
2 CAP
S V
LEFT RETURN END DISCHARGE
CBP
CAP
FRONT
EAP
CAP
CONTROL BOX
V
CAP
RIGHT RETURN END DISCHARGE
FRONT CAP
CBP
S
3
U
CAP
2
FRONT
1
SERVICE ACCESS
3’ (91 cm.)
Note 6
CBP
5
4
Model
A
Overall Cabinet
Depth
B
Width
C
Height
072-120 in.
36.3
92.2
84.9
215.6
21.6
54.9
D
14.0
35.6
Discharge Connections
Duct Flange
E F
Supply
Depth
17.0
43.2
Supply
Width
13.5
34.3
G
Supply
Height
7.8
19.8
Water Connections Electrical Knockouts
K L
15.0
1
Water
Outlet
8.3
38.1
21.1
M O P Q R
2
Water
Inlet
4.0
2.0 18.8 16.8 13.8
10.2
5.1 47.8 42.7 35.1
B
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 5 AND 6.
RIGHT RETURN STRAIGHT DISCHARGE LEFT RETURN STRAIGHT DISCHARGE
LEFT RETURN STRAIGHT DISCHARGE
A
A
BSP
Note 6
BSP
Note 6
B
DESCRIBED IN NOTES 5 AND 6.
C
C
S
Return
Depth
65.0
165.1
1
CAP
CAP
CAP
FRONT
O
CAP
PQR
FRONT
CBP
O
M
EAP
CBP
K
F
EAP
E
F D
D
1
EAP
2
1
G
G E EAP
2
LEGEND
LEGEND
CAP=Compressor Access Panel
CBP=Control Box Panel
BSP=Blower Service Panel
EAP=Expansion Valve Access panel
1=Water Outlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
2=Water Inlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
3=Condensate 3/4” FPT
4=High Voltage 1-1/8” [2.9cm] KO
5=Low Voltage 7/8” [2.2cm] KO
Note 6 Note 6
CAP
CAP
CAP
2
2
Return Air Connections
Using Return Air Opening
T U
1
Return
Height
SERVICE ACCESS
3’ (91 cm.)
Note 6
18.0
45.7
CBP
CBP
5
5
4
4
1.0
2.5
87”
[221cm]
4.3”
[10.8cm]
1.0”
[2.54cm]
1.0”
[2.54cm]
CONTROL BOX
PLAN VIEW
TOP
PLAN VIEW
TOP
CONTROL BOX
34.1”
[86.6cm]
34.1”
[86.6cm]
PLAN VIEW
TOP
PLAN VIEW
TOP
3
3
Note 5, 6
U
1.3” condensate
T
1.3”
[3.3cm] condensate
BSP
U
T
EAP
BSP
S
S
V
V
CONTROL BOX
CONTROL BOX
V
V
S
S
U
U
E
LEFT RETURN LEFT VIEW-
AIR COIL SIDE
LEFT RETURN END DISCHARGE
CBP
EAP
CAP
FRONT
CAP
FRONT
CAP
RIGHT RETURN RIGHT VIEW-
AIR COIL SIDE
1.3”
[3.3cm] condensate drain
[3.3cm]
RIGHT RETURN END DISCHARGE
FRONT
FRONT
CAP
CAP
EAP
EAP
CAP
CBP
CAP
CBP
D
V
18.9
48.0
-
NOTES:
All dimensions in table are inches (cm).
1. Service access is required for all removable panels and installer should take care to comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are available on either side (left or right) of the unit. Qty (2x) MPT Plugs are shipped loose in a plastic bag tied to the water leg in front of the unit. Installer must plug water inlet/outlet side not being
3. Condensate drain is 3/4" FPT and is located on cabinet end opposite the compressor.
3. Condensate drain is 3/4" FPT and is located on cabinet end opposite the compressor.
4. Electrical access is available on either side (left or right) of the front.
5. Electric box is on right side. It can be field converted to left side. Conversion should only be attempted by qualified service technician. If electric box relocated to opposite side, and water connected to opposite side, then this access is not required.
7. Overall cabinet width dimensions does not include filter rail and duct flange.
6. Units require 3’ (9.1 cm) clearance for water connections, CAP, CBP, EAP and BSP service access.
7. Overall cabinet width dimensions does not include filter rail and duct flange.
8. Units are shipped with air filter rails that are not suitable for supporting return air ductwork. An air filter frame with duct mounting collar is available as an accessory.
F E
BSP
BSP
D
F
G
-
NOTES:
All dimensions in table are inches (cm).
G
1. Service access is required for all removable panels and installer should take care to comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are available on either side (left or right) of the unit. Qty (2x) MPT Plugs are shipped loose in a plastic bag tied to the water leg in front of the unit. Installer must plug water inlet/outlet side not being connected to.
3. Condensate drain is 3/4" FPT and is located on cabinet end opposite the compressor.
4. Electrical access is available on either side (left or right) of the front.
5. Electric box is on right side. It can be field converted to left side. Conversion should only be attempted by qualified service technician. If electric box relocated to opposite side, and water connected to opposite side, then this access is not required.
6. Units require 3’ (9.1 cm) clearance for water connections, CAP, CBP, EAP and BSP service access.
7. Overall cabinet width dimensions does not include filter rail and duct flange.
8. Units are shipped with air filter rails that are not suitable for supporting return air ductwork. An air filter frame with duct mounting collar is available as an accessory. c l i m a t e m a s t e r.c o m 7
EAP
BSP
E
D
F
G
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LH072-120 w/WSE Dimensional Data
Model
072-120 in.
A
Overall Cabinet
B C
Width Depth Height
46.3
117.6
84.9
215.6
21.6
54.9
D
23.9
60.9
Discharge Connections
Duct Flange
E F G
Supply
Depth
17.0
43.2
Supply
Width
13.5
34.3
Supply
Height
7.8
19.8
Water Connections
K L M
15.0
38.1
1
Water
Outlet
18.3
46.4
2
Water
Inlet
4.0
10.2
O
Electrical Knockouts
P Q R
2.0
5.1
18.8
47.8
16.8
42.7
S
Return Air Connections
Using Return Air Opening
T U V
Return
Depth
13.8
54.0
35.1
137.2
Return
Height
18.4
45.7
1.0
2.5
29.4
74.7
Legend
BSP = Blower Service Panel
CAP = Compressor Access Panel
CBP = Control Box Panel
MSP = Motor Service Panel
ACP = Aquastat Controller Panel
EAP = Expansion Valve Access Panel
WSE = Waterside Economizer
CBP
Notes 5, 6
EAP
Notes 6, 9
87.00
[221 CM]
MSP BSP
Notes 6,7
15.00 (38.1)
Left Side View
Straight Discharge
Right Return
44.16
[112.18 CM]
C
L
M
F
R
O
N
T
V
B
O
A
1.00
[2.54 CM]
12.75
[32.39 CM]
Top View
Right Return Back Discharge
S
U
CAP, ACP
Notes 6, 8, 10
Front View
D E
K Right Side View
Notes:
1. Service access is required for all removable panels and installer
should take care to comply with all building codes allowing
adequate clearance for future field service.
2. Units are shipped with air filter rails that are not suitable for
supporting return air ductwork. An air filter frame with duct
mounting collar is available as an accessory.
3. Discharge flange and hanger brackets are factory installed.
4. Condensate drain is 3/4” FPT and is located on cabinet end
opposite the compressor.
5. Unit control box is on side opposite return air (not convertible)
6. Units require 3 feet (91cm) clearance for water connections,
CAP, CBP, EAP, MSP, ACP and BSP service panels.
R
Q
P
T
WSE
F
G
3/4” Drain
FPT
Back View
1.3 (3.3cm)
7. Blower service access is through back panel on straight discharge
units or through panel opposite air coil on back discharge units.
8. Factory supplied controller (aquastat) is inside unit completely wired.
To field adjust temperature setting, remove ACP panel and push button.
9. Expansion valve access panel is opposite return air side.
10. WSE coil air bleed access is through CAP.
Return
Air
Flow
8 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV Physical Data
Model
Compressor
Number of Circuits (Compressors)
Factory Charge HFC-410a - (oz)
[kg] per circuit
Blower Motor
Blower Motor Quantity
Standard Motor (hp) [kw]
072
60 [1.70]
096
76 [2.15]
120
80 [2.27]
Scroll
2
160
112 [3.18]
192
136 [3.86]
240
196 [5.56]
300
224 [6.35]
*Optional Large Motor (hp) [kw]
Blower
No. of Blowers
Blower Wheel Size D x W (in) [cm]
Water Connection Size
FPT (in) [mm]
1 [.75]
2 [1.49]
1
2 [1.49]
3 [2.24]
3 [2.23]
5 [3.73]
1
3 [2.24]
5 [3.73]
12 x 12 [30.48 x 30.48]
3 [2.24]
5 [3.73]
2
5 [3.73]
7.5 [5.59]
7.5 [5.60]
10 [7.46]
3
1-1/4" [31.8] 1-1/2" [38.1] 2" [50.8] 2-1/2" [63.5]
Coax Volume
Volume (US Gallons) [liters]
Condensate Connection Size
1.62 [6.13] 1.81 [6.85] 2.40 [9.08] 3.62 [13.70] 4.83 [18.28] 4.90 [18.55] 7.39 [27.98]
FPT (in) [mm]
Air Coil Data
Air Coil Dimensions H x W (in) [cm] 32 x 34 [81.28 x 86.36]
Air Coil Total Face Area (ft 2 ) [m 2 ] 7.6 [0.71]
Air Coil Tube Size (in) [cm]
Air Coil Fin Spacing (fpi)
[fins per cm]
Air Coil Number of Rows
Miscellaneous Data
Filter Standard - 1" [25.4mm]
Throwaway (qty) (in) [cm]
Weight - Operating (lbs) [kg] 586 [265.8]
3
36 x 36 [91.44 x 91.44]
9.0 [0.84]
(QTY.4) 20 x 20 [50.8 x 50.8]
14 [5.5]
1" [25.4]
3/8" [0.953]
2
36 x 76 [91.44 x 193.04]
19 [1.77]
3
(QTY.4) 20 x 25 [50.80 x 63.5]
(QTY.2) 20 x 30 [50.80 x 76.2]
644 [292.1] 698 [316.6] 1069 [484.9] 1164 [528.0] 1184 [537.1]
12 [4.72]
4
1297 [588.3]
Weight - Packaged (lbs) [kg] 626 [283.9]
*Unit with “F” Blower Drive Package is always Large Motor.
684 [310.3] 738 [334.8] 1149 [521.2] 1244 [564.3] 1264 [573.3] 1377 [624.6]
Unit with WSE Option
TC_LV Series
Water Coil Dimensions (in x cm)
Internal Water Coil Volume
(Gal) [L]
Weight - Operating (lbs.) [Kg]
072
32 x 34
[81.28 x 86.36]
5.9 [22.3]
762 [346]
096 120
35 x 36 [88.9 x 91.4]
6.6 [25]
837 [378]
7.2 [27.3]
907 [411]
160
13.3 [50.3]
1529 [694]
192
14.5 [54.9]
1665 [755]
240
35 x 76 [88.9 x 193]
23.9 [90.5]
1693 [768]
300
26.4 [99.9]
1855 [841] c l i m a t e m a s t e r.c o m 9
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV072-120 Dimensional Data
10
Model
072-120
Overall Cabinet
Discharge Connection
Duct Flange
A B C
Depth Width Height
D
Supply
Width
E
Supply
Depth
F K
1
Water
Inlet in.
29.0 41.0
69.8
17.5
14.8
11.9
22.0
Water Connections
L
2
Water
Outlet
7.3
M
3
Condensate
N O1
Electric Knockouts
O2 P Q R
Return Air Connections Using
Return Air Opening
S
Return
Depth
T
Return
Height
U V
14.5
21.3
8.0
15.0 11.3
1.0
1.5
36.3
29.4
30.6
2.7
cm.
73.7 104.1 177.2
44.5
37.5
30.2
55.9
18.4
36.8
54.0 20.3 38.1 28.6
2.5
3.8
96.2
74.7
77.8
6.9
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 7, 8, and 9
7.6
BSP
AIR OUT
UPA
F
BLOWER
ROTATION
BLOWER
ROTATION
RETURN AIR
2 NRP
(See Note 6)
BLOWER TO AIR COIL
RELATIONSHIP FOR
TOP DISCHARGE
072-120
CSP+CAP+MSP
Control
Box
Control
Box
1
4
4 5
CSP+CAP+MSP
3
K
L
M
REAR RETURN TOP DISCHARGE (RR/TD)
FRONT RETURN TOP DISCHARGE (FR/TD)
3
4
1
2
LEGEND
Water Inlet (See Note 2)
Water Outlet (See Note 2)
Condensate Drain (See Note 3)
5
High Voltage Access (See Note 4)
Low Voltage Access (See Note 4)
BSP - Blower Service Panel
CAP - Control Access Panel
CSP - Compressor Access Panel
MSP - Motor Service Panel
NRP - Non Removable Panel
UPA - Upper Pulley Access
Note 2
ALL CONFIGURATIONS
TCV072-096 TCV120
1-1/4” FPT
1-1/4” FPT
1-1/2” FPT
1-1/2” FPT
1” FPT
1-3/8” [3.49 CM]
7/8” [2.2 CM]
NOTES:
All dimensions in table are inches (cm)
1. While access to all removable panels may not be required, installer should take care to
comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are factory shipped on the left side. Union
allows field conversion to right side.
3. Condensate drain is available on either side (left or right) of unit. Drain hose and drain
connection will be tied inside the unit. Installer will untie the drain hose, form trap, and
connect to the condensate drain hole of installer’s choice.
4. Electrical access is available on either side (left or right) of unit and is also available in
the front on the left or right side of the unit.
5. Overall width - Add 3.12” (8cm) for 1“ (2.5cm) or 2” (5cm) Filter Frame; or 5.12” (13cm)
for 4” (10.2cm) and for front or rear supply add additional 1.06” (2.7cm) for supply
duct collar.
6. Overall cabinet height dimension does not include duct flange for top discharge
configuration.
7. Units require 3 feet(91 cm) clearance, CAP, CSP, MSP and BSP service access.
8. Side service access must be 2 feet (9.4cm) on any side that connections are made.
9. Filter removal is from right or left side of filter frame, allow 2 feet (9.4cm) access
for servicing.
1.7
F
D RETURN AIR
BSP
NRP
E
UPA
AIR OUT
1
BLOWER
ROTATION
BSP
AIR OUT
F
4
5
4
BSP+MSP
2
NRP
(See Notes 1 and 7)
RETURN AIR
2
NRP
BLOWER TO AIR COIL
RELATIONSHIP FOR
REAR OR FRONT
DISCHARGE 072-120
BLOWER
ROTATION
CSP
Control
Box
SIDE
SERVICE ACCESS
(See Note 8)
1
Control
Box
CSP+CAP+MSP
SERVICE ACCESS
3’ (91 CM)
FRONT AND BACK
(See Notes 1 and 7)
REAR RETURN FRONT DISCHARGE (RR/FD) FRONT RETURN REAR DISCHARGE (FR/RD)
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV072-120 w/WSE Dimensional Data
Model A
Overall Cabinet
B C
Discharge Connection
Duct Flange
D E F
072-120
Depth Width Height in.
39.5 41.0
69.8
Supply
Width
17.5
cm.
100.3 104.1 177.2
44.5
Supply
Depth
14.8
37.5
11.9
30.2
Water Connections
K
1
Water
Inlet
22.0
55.9
L
2
Water
Outlet
7.3
18.4
M
3
Condensate
14.5
36.8
N O1
Electric Knockouts
O2 P Q
21.3
8.0
15.0 11.3
54.0 20.3 38.1 28.6
1.0
2.5
R
1.5
3.8
Return Air Connections Using
Return Air Opening
S T U V
Return
Depth
36.3
96.2
Return
Height
29.4
30.6
2.7
74.7
77.8
6.9
B
BSP
Note 5
Top View
Rear Return Front Discharge
Legend
BSP = Blower Service Panel
CSP = Compressor Service Panel
CAP = Control Access Panel
MSP = Motor Service Panel
UPA = Upper Pulley Access
ACP = Aquastat Controller Panel
WSE = Waterside Economizer
UPA
Note 5
BSP
Note 5
7.72
Top View
Rear Return Top Discharge
F D
E
3.68
UPA
Note 5
BSP
Note 5
MSP
Note 2
C WSE Coil Air
Bleed Access
Note 2
Alternate
MSP
O2
P
CAP
CSP, ACP
Note 2
O1
Q
Front View
Rear Return Front Discharge
N
R
L
M
K
A
WSE
Right
Side
View
Return
Air
Flow
S
Back View
V
Rear Return Front Discharge
T
U
Notes:
1. While clear access to all removable panels may not be
required, installer should take care to comply with all building
codes and allow adequate clearance for future field service.
2. Units require 3 feet (91 cm) clearance for water connections,
WSE coil air bleed, CAP, CSP, BSP, ACP, UPA, and MSP.
3. Factory supplied controller (aquastat) is inside unit completely
wired. To field adjust temperature setting remove ACP panel and push button.
4. Condensate drain is internally trapped, externally vented.
5. For top discharge units, UPA is on top and BSP is on front. For front discharge
units, UPA is on front and BSP is on top. (allow 3 feet above unit for service). c l i m a t e m a s t e r.c o m 11
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV160-240 Dimensional Data
Overall Cabinet
A B C
Discharge Connection Duct
Flange
D E F G K
Water Connections
L M
Electrical Knockouts
N O1 O2 P Q R
Return Air Connections
Using Return Air Opening
S T U V
Model
160-
240 in.
Depth Width Height
29.0
82.0
69.8
cm.
73.7 208.3 177.2
Supply
Width
17.5
44.5
Supply
Depth
14.8
37.5
Supply
Width
17.9
Supply
Depth
11.5
45.4
29.3
Water
Inlet
26.1
66.3
Water
Outlet
3.1
7.9
Condensate
14.5
36.8
Return
Depth
25.8
8.0 15.0 11.3 1.0 1.5
77.0
65.5
20.3 38.1 28.6 2.5 3.8 195.6
Return
Height
35.8
31.7 2.6
90.8
80.5 6.7
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 7, 8, and 9
BLOWER
ROTATION
BLOWER
ROTATION
BLOWER TO AIR COIL
RELATIONSHIP FOR
TOP DISCHARGE
160-240 (See Note 6)
12
(See Note 5)
Note 2
REAR RETURN TOP DISCHARGE (RR/TD)
ALL CONFIGURATIONS
FRONT RETURN TOP DISCHARGE (FR/TD)
NOTES:
All dimensions in table are inches (cm)
1. While access to all removable panels may not be required, installer should take care
to comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are factory shipped on the left side. Union
allows field conversion to right side.
3. Condensate drain is available on either side (left or right) of unit. Drain hose and drain
connection will be tied inside the unit. Installer will untie the drain hose, form trap, and
connect to the condensate drain hole of installer’s choice.
4. Electrical access is available on either side (left or right) of unit and is also available in
the front on the left or right side of the unit.
5. Overall width - Add 3.12” (8cm) for 1“ (2.5cm) or 2” (5cm) Filter Frame; or 5.12” (13cm)
for 4” (10.2cm) and for front or rear supply add additional 1.06” (2.7cm) for supply
duct collar.
6. Overall cabinet height dimension does not include duct flange for top discharge
configuration.
7. Units require 3 feet(91 cm) clearance, CAP, CSP, MSP and BSP service access.
8. Side service access must be 2 feet (9.4cm) on any side that connections are made.
9. Filter removal is from right or left side of filter frame, allow 2 feet (9.4cm) access
for servicing.
BLOWER
ROTATION
BLOWER TO AIR COIL
RELATIONSHIP FOR
REAR OR FRONT
DISCHARGE 160-240
BLOWER
ROTATION
See Notes
1 and 7
SIDE SERVICE
ACCESS
(See Note 8)
REAR RETURN FRONT DISCHARGE (RR/FD)
SERVICE ACCESS
3’ (91 CM)
FRONT AND BACK
(See Notes 1 and 7)
FRONT RETURN REAR DISCHARGE (FR/RD)
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV160-240 w/WSE Dimensional Data
Overall Cabinet
A B C
Discharge Connection Duct
Flange
D E F G K
Water Connections
L M N
Electrical Knockouts
O1 O2 P Q R
Return Air Connections
Using Return Air Opening
S T U V
Model
160-
240
Depth Width in.
39.5
82.0
Height
69.8
cm.
100.3 208.3 177.2
Supply
Width
17.5
44.5
Supply
Depth
14.8
37.5
Supply
Width
17.9
45.4
Supply
Depth
11.5
29.3
Water
Inlet
26.1
66.3
Water
Outlet
3.1
7.9
Condensate
14.5
36.8
Return
Depth
25.8
8.0 15.0 11.3 1.0 1.5
77.0
65.5
20.3 38.1 28.6 2.5 3.8 195.6
Return
Height
35.8
31.7 2.6
90.8
80.5 6.7
F D G D
B
E
Top View
Rear Return Top Discharge
S V
UPA
Note 5
6.70
3.64
Legend
BSP = Blower Service Panel
CSP = Compressor Service Panel
CAP = Control Access Panel
MSP = Motor Service Panel
UPA = Upper Pulley Access
ACP = Aquastat Controller Panel
WSE = Waterside Economizer
BSP
Note 5
BSP
Note 5
Top View
Rear Return Front Discharge
A
BSP
Note 5
UPA
Note 5
MSP
Note 2
WSE
T
Back View
Rear Return Front Discharge
U
C
MSP
CSP
Note 2
Front View
MSP
CAP
CSP, ACP
Note 2
Rear Return Front Discharge
Q
N
O2
P
O1
L
R
M
K
Notes:
1. While clear access to all removable panels may not be
required, installer should take care to comply with all building
codes and allow adequate clearance for future field service.
2. Units require 3 feet (91 cm) clearance for water connections,
WSE coil air bleed, CAP, CSP, BSP, ACP, UPA, and MSP.
3. Factory supplied controller (aquastat) is inside unit completely
wired. To field adjust temperature setting remove ACP panel and push button.
4. Condensate drain is internally trapped, externally vented.
5. For top discharge units, UPA is on top and BSP is on front. For front discharge
units, UPA is on front and BSP is on top. (allow 3 feet above unit for service).
Right
Side
View c l i m a t e m a s t e r.c o m 13
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV300 Dimensional Data
A
Overall Cabinet
B C
Discharge Connection Duct
Flange
D E F G K
Water Connections
L M
Electrical Knockouts
N O1 O2 P Q R
Return Air Connections
Using Return Air Opening
S T U V
Model
300
Depth in.
29.0
Width
82.0
Height
69.8
Supply
Width
17.5
cm.
73.7
208.3 177.2
44.5
Supply
Depth
14.8
37.5
Supply
Width
6.3
16.0
Supply
Depth
8.6
Water
Inlet
25.7
Water
Outlet
3.1
Condensate
14.5
21.8
65.3
7.9
36.8
25.8
65.5
Return
Depth
8.0 15.0 11.3 1.0 1.5 77.0
Return
Height
35.8
31.7 2.6
20.3 38.1 28.6 2.5 3.8 195.6
90.9
80.5 6.7
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 7, 8, and 9
BSP
BLOWER
ROTATION
BLOWER TO AIR COIL
RELATIONSHIP FOR
TOP DISCHARGE
300
BLOWER
ROTATION
(See Note 6)
14
(See Note 5)
Note 2
ALL CONFIGURATIONS
REAR RETURN TOP DISCHARGE (RR/TD) FRONT RETURN TOP DISCHARGE (FR/TD)
NOTES:
All dimensions in table are inches (cm)
1. While access to all removable panels may not be required, installer should take care
to comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are factory shipped on the left side. Union
allows field conversion to right side.
3. Condensate drain is available on either side (left or right) of unit. Drain hose and drain
connection will be tied inside the unit. Installer will untie the drain hose, form trap, and
connect to the condensate drain hole of installer’s choice.
4. Electrical access is available on either side (left or right) of unit and is also available in
the front on the left or right side of the unit.
5. Overall width - Add 3.12” (8cm) for 1“ (2.5cm) or 2” (5cm) Filter Frame; or 5.12” (13cm)
for 4” (10.2cm) and for front or rear supply add additional 1.06” (2.7cm) for supply
duct collar.
6. Overall cabinet height dimension does not include duct flange for top discharge
configuration.
7. Units require 3 feet(91 cm) clearance, CAP, CSP, MSP and BSP service access.
8. Side service access must be 2 feet (9.4cm) on any side that connections are made.
9. Filter removal is from right or left side of filter frame, allow 2 feet (9.4cm) access
for servicing.
BLOWER
ROTATION
BLOWER TO AIR COIL
RELATIONSHIP FOR
REAR OR FRONT
DISCHARGE 300 ONLY
BLOWER
ROTATION
See Notes
1 and 7
SIDE SERVICE
ACCESS
(See Notes 8)
SERVICE ACCESS
3’ (91 CM)
FRONT AND BACK
(See Notes 1 and 7)
REAR RETURN FRONT DISCHARGE (RR/FD) FRONT RETURN REAR DISCHARGE (FR/RD)
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV300 w/WSE Dimensional Data
A
Overall Cabinet
B C
Discharge Connection Duct
Flange
D E F G K
Water Connections
L M
Electrical Knockouts
N O1 O2 P Q R
Return Air Connections
Using Return Air Opening
S T U V
Model
300
Depth in.
39.5
Width
82.0
Height
69.8
Supply
Width
17.5
cm.
100.3 208.3 177.2
44.5
Supply
Depth
14.8
37.5
Supply
Width
6.3
Supply
Depth
8.6
16.0
21.8
Water
Inlet
25.7
65.3
Water
Outlet
3.1
7.9
Condensate
Return
Depth
14.5
25.8
8.0 15.0 11.3 1.0 1.5 77.0
36.8
65.5
20.3 38.1 28.6 2.5 3.8 195.6
Return
Height
35.8
31.7 2.6
90.9
80.5 6.7
F D G D G D
E
6.40
Top View
Rear Return Top Discharge
Legend
BSP = Blower Service Panel
CSP = Compressor Service Panel
CAP = Control Access Panel
MSP = Motor Service Panel
ACP = Aquastat Controller Panel
WSE = Waterside Economizer
EAP = Expansion Valve Access Panel
B
BSP
Note 2
Top View
Rear Return Front Discharge
S V A
7.089
WSE
C
MSP, EAP
Note 2
CSP
Note 2
Front View
MSP
Note 2
CAP
CSP, ACP
Note 2
Q
Rear Return Front Discharge
T MSP
Note 2
Back View
Rear Return Front Discharge
U
N
O2
P
O1
R
L
M
K
Notes:
1. While clear access to all removable panels may not be
required, installer should take care to comply with all building
codes and allow adequate clearance for future field service.
2. Units require 3 feet (91 cm) clearance for water connections,
WSE coil air bleed, CAP, CSP, BSP, ACP, and MSP.
3. Factory supplied controller (aquastat) is inside unit completely
wired. To field adjust temperature setting remove ACP panel and push button.
4. Condensate drain is internally trapped, externally vented.
5. For top discharge units, BSP is on front. For front discharge units, BSP is on
top. (allow 3 feet above unit for service).
Right
Side
View c l i m a t e m a s t e r.c o m 15
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Horizontal Installation
Horizontal Unit Location Units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the ceiling. Horizontal units are typically installed above a false ceiling or in a ceiling plenum. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Consideration should be given to access for easy removal of the filter and access panels. Provide sufficient room to make water, electrical, and duct connection(s). Allow 3 feet (91 cm) clearance for servicing unit through all access panels.
Mounting Horizontal Units
Horizontal units have 4 hanger brackets partially attached at the factory, one at each corner. Enclosed within the unit there is a hanger kit hardware bag containing vibration isolation grommets, washers, screws and a hanger installation instruction page. One additional screw from the hardware bag must be added to each hanger bracket before unit installation.Tighten each screw to 75 in-lbs
(8.5 Nm). See Figure 1. Refer to the hanger installation instruction page contained in the hardware bag for details of final hanger bracket attachment and unit suspension.
See Figure 1a.
If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit.
Refer to Figure 3 for an illustration of a typical installation.
Refer to unit submittal data or engineering design guide for dimensional data.
Conform to the following guidelines when selecting unit location:
Use four (4) field supplied threaded rods and factory provided vibration isolators to suspend the unit. Safely lift the unit into position supporting the bottom of the unit. Ensure the top of the unit is not in contact with any external objects. Connect the top end of the 4 all-thread rods, slide rods through the brackets and grommet then assemble washers and double nuts at each rod. Ensure that the unit is approximately level and that the threaded rod extends past the nuts.
Pitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage.
1. Provide a hinged access door in concealed-spline or plaster ceilings. Provide removable ceiling tiles in T-bar or lay-in ceilings. Refer to horizontal unit dimensions for specific series and model in unit submittal data.
Size the access opening to accommodate the service technician during the removal or replacement of the compressor, control, or blower assembly. Provide access to hanger brackets, water valves and fittings.
Provide screwdriver clearance to access panels, discharge collars and all electrical connections.
2. DO NOT obstruct the space beneath the unit with piping, electrical cables and other items that prohibit future removal of components or the unit itself.
3. Use a manual portable jack/lift to lift and support the weight of the unit during installation and servicing.
Figure 1: Hanger Bracket
INSTALLED
AT FACTORY
ADD
BEFORE
HANGING
VIEW CONDENSATE END
BEFORE GROMMET AND HARDWARE
(Unit pictured for hanger bracket reference).
(Drain hardware may vary per unit model)
Figure 1a:
The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
ADD
BEFORE
HANGING
16
VIEW WATER CONNECTION END
FULLY ASSEMBLED
(Unit pictured for hanger bracket reference)
(Water hardware may vary per unit model)
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Horizontal Installation, Cont’d.
Figure 3: Typical Horizontal Unit Installation
CAP
F
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 5 AND 6.
U
CAP
FRONT
B
O
PQR
CBP
K
M
EAP
RIGHT RETURN STRAIGHT DISCHARGE
BSP
LEFT RETURN STRAIGHT DISCHARGE
Return Air
A
BSP BSP CBP
Note 6 Thermostat
Wiring
Supply Air
C
CBP
1
5
F
G E
D
EAP
2
CAP
4
Note 5, 6
Insulated supply duct with at least one 90 deg elbow to reduce air noise
LEGEND
CAP=Compressor Access Panel
CBP=Control Box Panel
BSP=Blower Service Panel
EAP=Expansion Valve Access panel
1=Water Outlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
2=Water Inlet 1-1/4” FPT (072-096) 1-1/2” FPT (120)
3=Condensate 3/4” FPT
4=High Voltage 1-1/8” [2.9cm] KO
5=Low Voltage 7/8” [2.2cm] KO
Note 6
LEFT RETURN STRAIGHT DISCHARGE
CAP
2 toward drain for drainage
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 5 AND 6.
SERVICE ACCESS
RIGHT RETURN STRAIGHT DISCHARGE
HANGER BRACKET DIMENSIONS
A
BSP BSP
EAP
Stainless steel braid hose with integral “J” swivel
Optional
Balancing Valve
CAP
Unit Hanger
CAP
Optional Low Pressure Drop Water
Control Valve
Note 6
Ball valve with optional integral P/T plug
Building
Loop
Water Out
Water In
CONTROL BOX
Unit
Power
T
S
CAP
V
CONTROL BOX
CAP
FRONT
LEFT RETURN END DISCHARGE
CBP
CAP
FRONT
V
B
CAP
O
PLAN VIEW
TOP
FRONT
F
G E
D
C
3
U
CBP
LEGEND
K
M
CAP=Compressor Access Panel
CBP=Control Box Panel
BSP=Blower Service Panel
EAP=Expansion Valve Access panel
AIR COIL SIDE
1.3” condensate drain
4=High Voltage 1-1/8” [2.9cm] KO
RIGHT RETURN END DISCHARGE
-
NOTES:
All dimensions in table are inches (cm).
1
CBP
1. Service access is required for all removable panels and installer should take care to comply with all building codes and
1
EAP
2 CAP
5 shipped loose in a plastic bag tied to the water leg in front of the unit. Installer must plug water inlet/outlet side not being connected to.
Note 5, 6
2 service technician. If electric box relocated to opposite side, and water connected to opposite side, then this access is not required.
6. Units require 3’ (9.1 cm) clearance for water connections, CAP, CBP, EAP and BSP service access.
Note 6
SERVICE ACCESS
8. Units are shipped with air filter rails that are not suitable for supporting return air ductwork. An air filter frame with duct
Note 6
EAP
CONTROL BOX
EAP
G
BSP
E
D U
CAP
T
PLAN VIEW
CBP
TOP
LEFT RETURN END DISCHARGE
CBP
CAP
FRONT
PLAN VIEW
TOP
BSP
RIGHT RETURN END DISCHARGE
FRONT CAP
3
Air Coil - To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of
S V
CONTROL BOX
V S dishwasher detergent and water is recommended for both sides of the coil. A thorough water rinse should follow. UV based anti-bacterial systems may damage coated air coils.
CAP
-
NOTES:
All dimensions in table are inches (cm).
Notice!
1. Service access is required for all removable panels and installer should take care to comply with all building codes and allow adequate clearance for future field service.
Installation Note - Ducted Return: Many horizontal WSHPs are installed in a return air ceiling plenum application (above ceiling). Vertical WSHPs are commonly installed in a mechanical room with free return
(e.g. louvered door). Therefore, filter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter frame. Canvas or flexible connectors should also be used to minimize
EAP
CAP
BSP
CBP BSP c l i m a t e m a s t e r.c o m 17
E
D
F
G
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LH Field Conversion of Air Discharge
� WARNING!
�
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation or conversion.
Overview Horizontal units can be field converted between straight (side) and back (end) discharge using the instructions below.
Note: It is not possible to field convert return air between left or right return models due to the necessity of refrigeration copper piping changes.
Preparation Field conversion must be completed on the ground. If the unit is already hung it should be taken down for the field conversion. Place in a well-lighted area.
Conversion should only be attempted by a qualified service technician.
Side to Back Discharge Conversion
1. Remove back panel and side access panel
2. Loosen 2 motor slide nuts, raise motor slide assembly and remove belt and motor sheave.
3. Remove blower sheave. Remove motor bolts and carefully remove motor.
4. Remove 2 motor clips and reattach to opposite side.
5. Unbolt (3 per side) complete housing assembly.
6. Rotate complete assembly into new position. Locate over mounting holes in base, reattach using 3 bolts per side.
7. Mount motor, motor sheave, blower sheave and belt.
Make sure wires are not pinched and not over sharp edges. Adjust motor downward to tighten belt. Raise or lower motor slide assembly with adjusting bolt and retighten 2 slide nuts. Check for correct tension (See
Tensioning V-Belt Drives page). Rewire motor (at contactor) for correct rotation. Spin blower wheel to ensure wheel is not obstructed.
8. Replace 2 panels.
Back to Side Discharge Conversion If the discharge is changed from back to side, use above instruction noting that illustrations will be reversed.
Left vs. Right Return It is not possible to field convert return air between left or right return models due to the
Step 1 the conversion process of side to back or back to side discharge for either right or left return configuration is the same. In some cases, it may be possible to rotate the entire unit 180 degrees if the return air connection needs to be on the opposite side. Note that rotating the unit will move the piping to the other end of the unit.
Step 3
Remove motor and blower
Figure 4: Left Return Side Discharge to Back - Steps 1-8
Step 1
Front
Return air
Step 3
Remove motor and blower
Step 2
Remove blower panel and access panel
Adjusting bolt - used to raise or lower motor slide
Remove 4 motor bolts
Loosen 2 motor slide nuts, raise slide assembly, remove
Step 4
Remove blower panel and access panel
Step 4
Move motor clips to other side on bracket
Step 7
Loosen 2 motor slide nuts, raise slide assembly, remove
Adjusting bolt - used to raise or lower motor slide
Remove 4 motor bolts
Move motor clips to other side on bracket
Motor motor, motor sheave, blower sheave and belt
Step 5
Remove (3x) per slide
1/4-20 UNC bolts
Step 6
Step 7
Remove (3x) per slide
1/4-20 UNC bolts
Step 6
Motor motor, motor sheave, blower sheave and belt
Step 8
Front
Step 8
Front
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Put blower panel and access panel back on
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Put blower panel and access panel back on
Step 3
Remove motor and blower
Step 1
Front
Return air
Adjusting bolt - used to raise or lower motor slide
Remove 4 motor bolts
Step 2
Remove blower panel and access panel
Step 4
Loosen 2 motor slide nuts, raise slide assembly, remove
Move motor clips to other side on bracket
Step 1
Front
Step 1
Front
Step 2
Step 2
Step 5
Step 5
Remove (3x) per slide
1/4-20 UNC bolts
Step 6
Remove (3x) per slide
1/4-20 UNC bolts
Step 6
Return air
Return air
Step 1
Front
Step 1
Front
Step 1
Front
Step 2
Step 3
Remove motor and blower
Step 3
Remove motor and blower
Step 2
Remove blower panel and access panel
Remove blower panel and access panel
Step 4
Step 5
Step 3
Return air
Return air
Remove motor and blower
Step 5
Adjusting bolt - used to raise or lower motor slide
Adjusting bolt - used to raise or lower motor slide
Remove 4 motor bolts
Remove 4
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Step 7
Tranquility ® Compact High Capacity (TC_L) Series and blower
R e v. : M a y 5 , 2 0 2 0
Return air Step 4
Remove blower panel and access panel
TC_LH Field Conversion of Air Discharge, Cont’d.
and access panel
Adjusting bolt - used to raise or
Remove (3x) per slide
1/4-20 UNC bolts
Move motor clips to other side on bracket
Remove 4 motor bolts
Loosen 2 motor slide nuts, raise slide assembly, remove
Step 6
Loosen 2 motor slide nuts, raise slide assembly, remove
Adjusting bolt - used to raise or lower motor slide
Adjusting bolt - used to raise or lower motor slide
Step 4
Remove blower panel and access panel
Remove 4 motor bolts Remove 4 motor bolts
Move motor clips to other side on bracket
Step 8
Front
Step 7
Loosen 2 motor slide nuts,
Step 7
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Motor motor, motor sheave, blower sheave and belt
Move motor clips to other side on bracket
Move motor clips to other side on bracket
Motor motor, motor sheave, blower sheave and belt
Put blower panel and access panel back on
Loosen 2 motor slide nuts, raise slide assembly, remove
Loosen 2 motor slide nuts, raise slide assembly, remove
Remove (3x) per slide
1/4-20 UNC bolts
Step 5
Remove (3x) per slide
1/4-20 UNC bolts
Step 6
Step 6
Step 7
Step 8
Front
Step 8
Front
Step 7
Step 7
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Motor motor, motor sheave, blower sheave and belt
Remove (3x) per slide
1/4-20 UNC bolts
Motor motor, motor sheave, blower sheave and belt
UNC bolts (3x) ea. side.
Step 6
Step 8
Front c l i m a t e m a s t e r.c o m
Put blower panel and access panel back on
Put blower panel and access panel back on
Motor motor, motor sheave, blower sheave and belt
19
Step 8
Front
Step 8
Front
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Put blower panel and access panel back on
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Rotate entire blower housing assembly to rest at back end of the unit. Locate housing holes and bolt down using previous 1/4-20
UNC bolts (3x) ea. side.
Put blower panel and access panel back on
Put blower panel and access panel back on
Motor motor, motor sheave, blower sheave and belt
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Horizontal Installation
Figure 5: Right Return Side Discharge to Back
RIGHT RETURN SIDE DISCHARGE
CBP
FRONT
RETURN AIR
RIGHT RETURN END DISCHARGE
FRONT
Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required.
Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT
IS INSTALLED IN THE DRAIN LINE, IT MUST BE
LOCATED AFTER THE TRAP IN THE DIRECTION OF
THE CONDENSATE FLOW.
Drain
CBP
Figure 6: Horizontal Condensate Connection
RETURN AIR
Drain
Horizontal Units Condensate Piping Pitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage. Ensure that unit pitch does not cause condensate leaks inside the cabinet.
Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection as shown in Figure 6. Design the depth of the trap (waterseal) based upon the amount of ESP capability of the blower (where 2 inches [51mm] of ESP capability requires
2 inches [51mm] of trap depth). As a general rule, 1-1/2 inch [38mm] trap depth is the minimum.
Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser.
Provide a means to flush or blow out the condensate line.
DO NOT install units with a common trap and/or vent.
2”
1.5”
1/8” Per
Foot
1.5”
* Some units include a painted drain connection.
Using a threaded pipe or similar device to clear any excess paint accumulated inside this fitting may ease final drain line installation.
� CAUTION!
�
CAUTION!
Ensure condensate line is pitched toward drain
1/8 inch per ft [11mm per m] of run.
DUCT SYSTEM INSTALLATION
Duct System Installation Proper duct sizing and design is critical to the performance of the unit. The duct system should be designed to allow adequate and even airflow through the unit during operation. Air flow through the unit MUST be at or above the minimum stated airflow for the unit to avoid equipment damage. Duct systems should be designed for quiet operation. Refer to Figure 3 for horizontal duct system details or Figure 8 for vertical duct system details. A flexible connector is recommended for both discharge and return air duct connections on metal duct systems to eliminate the transfer of vibration to the duct system. To maximize sound attenuation of the unit blower, the supply and return plenums should include internal fiberglass duct liner or be constructed from ductboard for the first few feet. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended, as the unit’s performance may be adversely affected.
At least one 90° elbow should be included in the supply duct to reduce air noise. If air noise or excessive air flow is a problem, the blower speed can be changed. For airflow charts, consult submittal data for the series and model of the specific unit.
20 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Vertical Installation
Figure 7: Typical Vertical Installation
Rear Return/Top Discharge shown
Refer to Dimensional Data pages for other arrangements & dimensions
Ductwork not shown.
Return Air
Return Air
Supply
Air
24 V Remote
Thermostat
Plug water in and out connections
Unions
Hoses
Optional Water
In
Supply
Water
Return
Water
Shutoff
To
Drain
(See Figure
10 for Vent)
Optional
Balancing
Valve
Water
Out
Condensate Internally
Trapped. Do not trap externally.
Pitch horizontal runs ¼” per foot.
Disconnect Box
Per NEC and
Local Codes
Vertical Location and Access
TC units are not designed for outdoor installation. Locate the unit in an indoor area that allows enough space for installation and for service personnel to perform typical maintenance or repairs. TC units are typically installed in a floor level closet or in a small mechanical room. Refer to
Figure 7 for an illustration of a typical installation. Install units with adequate clearance to allow maintenance and servicing. Conform to the following guidelines when selecting unit location:
• Provide adequate clearance for filter replacement and drain pan cleaning. DO NOT block filter access with piping, conduit or other materials. Refer to submittal drawing for Vertical Unit Dimensions.
• Provide access for fan and fan motor maintenance and for servicing of the compressor and coils without removal of the unit.
• Provide an unobstructed path to the unit within the closet or mechanical room to enable removal of the unit if necessary.
• Provide access to water valves and fittings, and screwdriver access to the unit side panels, discharge collar and all electrical connections
Duct System Design & Installation Guidelines
The following application guidelines must be used when installing TC units. Failure to follow these guidelines could result in unsatisfactory unit performance and/or premature failure of some unit components. ClimateMaster will not warrant, or accept responsibility for products which fail, have defects, damage or insufficient performance as a result of improper application.
• The duct system must be sized to handle the airflow quietly and must not exceed the maximum allowable External Static Pressure. To maximize sound attenuation metal supply and return ducts should include internal insulation or be of duct board construction for the first 10 feet or end of first full-sized elbow.
• Install a flexible connector in all supply and return air ducts close to the unit to inhibit sound transfer to the ducts.
• Do not install uninsulated duct in an unconditioned space. The unit performance will be adversely affected and damage from condensate can occur. c l i m a t e m a s t e r.c o m 21
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV Field Conversion of Air Discharge
� WARNING!
�
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation or conversion.
Overview Vertical units can be field converted between top and straight (side) and back (end) discharge using the instructions below.
Preparation Place in a well-lighted area. Conversion should only be attempted by qualified service technicians.
22 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV072-240 Field Conversion of Air Discharge
Figure 8: TC_LV072-120 and TC_LV160-240 Pictorally Shown
Top Discharge Steps to Convert to Straight Discharge
Step 1 - For TC_LV072-120 remove 3 panels.
For TC_LV160-240 remove 6 panels, middle dividers, and panel mounting brackets.
Figure 8 Continued on Following Page c l i m a t e m a s t e r.c o m 23
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV072-240 Field Conversion of Air Discharge, Cont’d.
Figure 8, Cont’d.: TC_LV072-120 and TC_LV160-240 Pictorally Shown Top
Discharge Steps to Convert to Straight Discharge
(2X) Bolts
24
Step 2 - Remove motor and then unscrew and remove motor mount assembly. Put motor mount assembly back in lower mount position.
Figure 8 Continued on Following Page
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
Upper Mount
Holes for Top
Discharge
Lower Mount
Holes for
Straight
Discharge
(2X) Bolts
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV072-240 Field Conversion of Air Discharge, Cont’d.
Figure 8 continued: TC_LV072-120 and TC_LV160-240 Pictorally Shown
Top Discharge Steps to Convert to Straight Discharge
Step 3 - Remove (4x) Blower Mount Bolts
Step 4 - Rotate blower assembly 90 degrees.
Reattach blower assembly to front of unit as shown. Put belt on and retighten.
Step 5 - Replace panels and misc from step1
(not shown).
Reverse steps to convert straight discharge to top discharge.
c l i m a t e m a s t e r.c o m 25
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV300 Field Conversion of Air Discharge
Figure 9: TC_LV300 Top Discharge Steps to Convert to Straight Discharge
26
Step 1 - Remove 5 panels, dividers, and panel mount brackets.
Figure 9 Continued on Following Page
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV300 Field Conversion of Air Discharge, Cont’d.
Figure 9, Cont’d.: TC_LV300 Top Discharge Steps to Convert to Straight Discharge
Note: Unlike the 160-240, the TC_LV300 only has 1 location for the motor mount assembly.
Do not remove.
Step 2 - Unattach and lift entire 3 blower sub assembly out of the unit.
Step 3 - Rotate blower assembly 180 degrees.
Remove blower sheave and put on opposite side.
Sheave End
Figure 9 Continued on Following Page c l i m a t e m a s t e r.c o m 27
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV300 Field Conversion of Air Discharge, Cont’d.
Figure 9, Cont’d.: TC_LV300 Top
Discharge Steps to Convert to
Straight Discharge
Step 7 - Replace brackets and 5 panels.
Reverse steps to convert straight discharge to top discharge.
28
Step 4 - Attach middle divider.
Step 6 - Reattach blower assembly to the front of the unit. Put belt on and retighten.
Step 5 - Rotate the blower assembly 90 degrees counter clockwise. The belly of the blowers should be facing upward.
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
� WARNING!
�
TC_LV300 Field Conversion of Control Box
Step 1 - Remove control box access panel and panel box will be relocated to.
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation or conversion.
Overview Vertical unit control box can be field converted from front to any other corner for 160-300 or opposite corner (water coil side) for 072-120.
Preparation Place in a well-lighted area. Conversion should only be attempted by a qualified service technician.
Figure 10: TC_LV160-240 Shown,
Typical All TC_LV Models
Note: Must provide 3 feet (or code requirement) service access for new control box location.
Original Control Box Location for Back Return Top Discharge
Step 2: Unattach all wires from components, remove the control box, tag wires. Pull wires out of box.
Step 3: Attach box to new location.
Step 4: Reroute wires. (Note: Keep wires away from hot lines and sharp edges).
Step 5: Reattach wires. (Note: Models with 2 compressors, rewire circuit 1 to same compressor. (I.E., compressor configuration does not change. Only location of control box changes.
Step 6: Check wiring is per wire diagram.
Step 7: Replace panels.
Step 1 - For TC_LV072-120 remove 3 panels.
For TC_LV160-240 remove 6 panels, middle dividers, and panel mounting brackets.
c l i m a t e m a s t e r.c o m 29
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_LV Field Conversion of Water Connections
� WARNING!
�
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation or conversion.
Overview All models the water connection can be field converted to opposite side. Connections can be both left, right, or 1 each side.
Preparation Field conversion must be completed on the ground. If the unit is already hung it should be taken down for the field conversion. Place in a well-lighted area. Conversion should only be attempted by a qualified service technician.
Side to Back Discharge Conversion
Step 1: Remove panels needed for access to water connections.
Step 2: Remove screws from side panels. Loosen (4x) screws in slots but do not remove.
Step 3: Both water in and out have a union centered in the middle of the unit. Undo both unions, rotate the water legs for opposite configuration retighten unions, reattach connection flanges to wrappers. Use slots to adjust and retighten screws in slots.
Step 4: Replace panels.
Step 5: Check wiring is per wire diagram.
Step 6: Replace panels
30 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Vertical Condensate Installation
Condensate Piping TC_LV - Remove KO on side that drain will be connected. Remove access panels. Inside of unit, untie and uncoil drain hose. Form trap in hose, make sure hose is not kinked or deformed. Connect plate assembly to side frame with 2 screws.
� WARNING!
�
WARNING! Ensure condensate line is pitched toward drain
1/4" per foot [10mm per 46cm] of run.
Outside of unit, connect 1” MPT fitting to plate assembly.
Run line to building drain. Horizontal runs must be pitched
¼” per foot (10 mm per 46 cm) toward drain. Do not trap externally.
Figure 11 illustrates a typical trap and vent used with
TC_LV series equipment.
Horizontal and Vertical Installations Drain main or riser must be sized for all units connected to it.
Pipe
Size
3/4” [19mm]
1” [25mm]
1-1/4” [32mm]
1-1/2” [38mm]
2” [51mm]
3” [76mm]
4” [102mm]
Connected Connected
Tons kW
<4
<6
<30
<50
<150
<300
<500
<14
<21
<105
<175
<527
<1055
<1758
Figure 11: TC_LV
*IPT
Trap Depth >1.5” [38mm]
Min 1.5”
[38mm]
* Make sure all connections are secure and water tight.
Copper by others
See size in table
1” IPT
2 Screws
All fittings and tubing outside of the unit are field supplied.
Each unit must be installed with its own individual line to the building main condensate drain line or riser. Provide a means to flush or blow out the condensate line. DO NOT install units with a common trap and or vent. Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN
LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE
DIRECTION OF THE CONDENSATE FLOW and opening
46” (117 cm) minimum from bottom of unit. (Vent per code)
1/4” per foot
After drain is connected to main and all drain connections are secure and water tight, pour 1 gallon of water into
Rev.: 10/11/04D
Condensate
Pan condensate pan. Water should drain out freely. Repair any leaks.
• On units with multiple fan outlets a “pair of pants” duct connection must be used for proper air balance and distribution and to prevent fan oscillation.
• Include at least one 90-degree turn in supply air ducts to reduce noise transmission.
• Existing ducts must be checked to ensure proper size and configuration prior to installation of any replacement unit. Also inspect for and repair all air leaks in existing ducts.
• Units may only be connected to a dedicated duct system. Consult the factory BEFORE connecting multiple units to a common duct system.
• Never connect a unit to a duct system with automatic or modulating dampers, VAV boxes, etc. in the supply air system. Never allow a situation where the total unit
CFM can drop below the minimum required for proper unit operation.
• Never connect a bypass damper from the supply air duct to the return air duct. Never allow the return air temperature to drop below the minimum allowable normal temperature for proper unit operation.
• Do not use TC units for 100% outdoor air treatment.
Do not add hot-gas-bypass to “convert” a unit for outdoor air treatment. Always use a dedicated outdoor air unit for outdoor air treatment.
• Do not exceed 10% of the total unit CFM with untreated outdoor air.
c l i m a t e m a s t e r.c o m 31
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Piping Installation
If the unit is connected to existing ductwork, a previous check should have been made to ensure that the ductwork has the capacity to handle the airflow required for the unit. If ducting is too small, as in the replacement of a heating only system, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as necessary.
Installation of Supply and Return Piping
Follow these piping guidelines:
1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.
2. Install shut-off / balancing valves and unions at each unit to permit unit removal for servicing.
3. Place strainers at the inlet of each system circulating pump.
4. Select the proper hose length to allow slack between connection points. Hoses may vary in length by +2% to -4% under pressure.
5. Refer to Table 1. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radius may cause the hose to collapse, which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.
Similar hoses can be obtained from alternate suppliers.
Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kinking during installation.
Refer to Figure 12 for an illustration of a typical supply/ return hose kit. Adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check regularly to avoid system failure and reduced service life.
� WARNING!
�
WARNING!
Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.
� CAUTION!
�
CAUTION!
Corrosive system water requires corrosion resistant fittings and hoses, and may require water treatment.
� CAUTION!
�
CAUTION!
Do not bend or kink supply lines or hoses.
� CAUTION!
�
CAUTION!
Piping must comply with all applicable codes.
Insulation is not required on loop water piping except where the piping runs through unheated areas, outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient conditions. Insulation is required if loop water temperature drops below the dew point (insulation is required for ground loop applications in most climates).
Pipe joint compound is not necessary when Teflon ® thread tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the external pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint.
Note: When antifreeze is used in the loop, ensure that it is compatible with the Teflon compound that is applied.
® tape or pipe joint
Table 1: Metal Hose Minimum Bend Radii
Hose Diameter Minimum Bend Radii
1/2" [12.7mm]
3/4" [19.1mm]
1" [25.4mm]
1-1/4" [31.8mm]
2-1/2" [6.4cm]
4" [10.2cm]
5-1/2" [14cm]
6-3/4" [17.1cm]
1-1/2" [38.1mm]
Rib Crimped
Length
(0.6m Length Standard)
8.5" [21.6cm]
Brass
Fitting
NOTICE! Do not allow hoses to rest against structural building components. Compressor vibration may be transmitted through the hoses to the structure, causing unnecessary noise complaints.
MPT
Maximum allowable torque for brass fittings is 30 ft-lbs
[41 N-m]. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.
Figure 12 : Supply/Return Hose Kit
Rib Crimped
Optional pressure-rated hose assemblies designed specifically for use with ClimateMaster units are available.
32
Length
(2 ft [0.6m] Length Standard)
MPT
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
Swivel
Brass
Fitting
MPT
Reborde Acanalado
Accesorio
Giratorio de Bronce
Accesorio de Bronce
MPT
Longitud
(Long. Estándar de 2 pies)
MPT
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Water-Loop Heat Pump Applications
Commercial Water Loop Applications - Commercial systems typically include a number of units connected to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system; therefore air elimination equipment is a major portion of the mechanical room plumbing. In piping systems expected to utilize water temperatures below 50°F [10°C], 1/2” (13mm) closed cell insulation is required on all piping surfaces to eliminate condensation (extended range units required).
Metal to plastic threaded joints should never be used due to their tendency to leak over time.
The piping system should be flushed to remove dirt, piping chips, and other foreign material prior to operation
(see “Piping System Cleaning and Flushing Procedures” in this manual). The flow rate is usually set between 2.25 and 3.5 gpm per ton [2.9 and 4.5 l/m per kW] of cooling capacity. ClimateMaster recommends 3 gpm per ton
[3.9 l/m per kW] for most applications of water loop heat pumps. To ensure proper maintenance and servicing, P/T ports are imperative for temperature and flow verification, as well as performance checks.
Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger. Do not over tighten connections and route piping so as not to interfere with service or maintenance access. Hose kits are available from ClimateMaster in different configurations as shown in
Figure 13 for connection between the unit and the piping system. Depending upon selection, hose kits may include shut off valves, P/T plugs for performance measurement, high pressure stainless steel braided hose, “Y” type strainer with blow down valve, and/or “J” type swivel connection. Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit.
Water loop heat pump (cooling tower/boiler) systems typically utilize a common loop, maintained between 60 -
90°F [16 - 32°C]. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.
Low Water Temperature Cutout Setting - CXM Control
When antifreeze is selected, the LT1 jumper (JW3) should be clipped to select the low temperature (antifreeze 10.0°F
[-12.2°C]) setpoint and avoid nuisance faults (see “Low
Water Temperature Cutout Selection” in this manual). Note:
Low water temperature operation requires extended range equipment.
HORIZONTAL INSTALLATION
BSP
Supply Air
EAP
Return Air
CAP
CBP
Thermostat
Wiring
Unit
Power
CAP
Insulated supply duct with at least one 90 deg elbow to reduce air noise
Unit Hanger
Optional
Balancing Valve
Water Out
Water In
Optional Low Pressure Drop Water
Control Valve
Building
Loop c l i m a t e m a s t e r.c o m 33
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Ground-Loop Heat Pump Applications
� CAUTION!
�
CAUTION!
The following instructions represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
� CAUTION!
�
CAUTION!
Ground loop applications require extended range equipment and optional refrigerant/water circuit insulation.
Pre-Installation Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.
Piping Installation The typical closed loop ground source system is shown in Figure 14. All earth loop piping materials should be limited to polyethylene fusion only for in-ground sections of the loop. Galvanized or steel fittings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fittings should be avoided due to their potential to leak in earth coupled applications. A flanged fitting should be substituted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat exchanger.
Earth loop temperatures can range between 25 and
110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to 3.23 l/m per kW] of cooling capacity is recommended in these applications.
Test individual horizontal loop circuits before backfilling.
Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled.
Flushing the Earth Loop Upon completion of system installation and testing, flush the system to remove all foreign objects and purge to remove all air.
Antifreeze In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area.
Low temperature protection should be maintained to
15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and low temperature protection should be at 15°F [-10°C].
Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes.
Calculate the total volume of fluid in the piping system.
Then use the percentage by volume shown in table 2 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity.
Low Water Temperature Cutout Setting - CXM Control
When antifreeze is selected, the LT1 jumper (JW3) should be clipped to select the low temperature (antifreeze 10.0°F
[-12.2°C]) setpoint and avoid nuisance faults (see “Low
Water Temperature Cutout Selection” in this manual). Note:
Low water temperature operation requires extended range equipment.
Table 2: Antifreeze Percentages by Volume
Type
Methanol
100% USP food grade Propylene Glycol
Ethanol*
* Must not be denatured with any petroleum based product
10°F [-12.2°C]
25%
38%
29%
Minimum Temperature for Low Temperature Protection
15°F [-9.4°C] 20°F [-6.7°C]
21%
25%
25%
16%
22%
20%
25°F [-3.9°C]
10%
15%
14%
34 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Ground-Loop Heat Pump Applications, Cont’d.
Figure 14: Typical Ground-Loop Application
HORIZONTAL INSTALLATION
Figure 3: Typical Horizontal Unit Installation
3/8" [10mm] threaded rods
(by others)
BSP
Return Air
Supply Air
CBP
Thermostat
Wiring
Unit
Power
EAP
CAP
CAP
Insulated supply duct with at least one 90 deg elbow to reduce air noise
Flexible Duct
Connector
Stainless steel braid hose with integral “J” swivel
Optional
Balancing Valve
Unit Hanger
Ball valve with optional integral P/T plug
Building
Loop
Water Out
Water In
Optional Low Pressure Drop Water
Control Valve c l i m a t e m a s t e r.c o m 35
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Ground-Water Heat Pump Applications
Open Loop - Ground Water Systems Typical open loop piping is shown in Figure 15. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid flushing of the heat exchanger. Shut off valves should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Supply and return water piping materials should be limited to copper, PE, or similar material. PVC or CPVC should never be used as they are incompatible with the POE oils used in HFC-410A products and piping system failure and property damage may result.
Water quantity should be plentiful and of good quality.
Water Quality Standards Table 3 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method.
If the pH <7.5 and the calcium hardness is less than
100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indecies should be calculated.
Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/open loop) and DHW (desuperheater); 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 3.
� WARNING!
�
WARNING!
Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.
Consult table 3 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult Table 3 for recommendations.
Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualified technician, as acid and special pumping equipment is required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid flushing. In some cases, the desuperheater option should not be recommended due to hard water conditions and additional maintenance required.
Expansion Tank and Pump Use a closed, bladdertype expansion tank to minimize mineral formation due to air exposure. The expansion tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.
Water Control Valve Note the placement of the water control valve in Figure 15. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off-cycle. Pilot operated slow closing valves are recommended to reduce water hammer.
If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Ensure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. This can overload smaller 40 or 50 VA transformers depending on the other controls in the circuit. A typical pilot operated solenoid valve draws approximately 15VA. Note the special wiring diagrams for slow closing valves (Figures 19 & 20).
36 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Ground-Water Heat Pump Applications, Cont’d.
Flow Regulation Flow regulation can be accomplished by two methods. One method of flow regulation involves simply adjusting the ball valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine flow rate from Tables
8a through 8e. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired flow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second method of flow control requires a flow control device mounted on the outlet of the water control valve. The device is typically a brass fitting with an orifice of rubber or plastic material that is designed to allow a specified flow rate. On occasion, flow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line. Slightly closing the valve will spread the pressure drop over both devices, lessening the velocity noise. NOTE: When EWT is below 50°F [10°C], 2 gpm per ton (2.6 l/m per kW) is required.
Water Coil Low Temperature Limit Setting For all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting-water) should be used to avoid freeze damage to the unit. See “Low Water Temperature Cutout Selection” in this manual for details on the low limit setting.
Figure 15: Typical Open Loop/Well Application
P/T Plugs
Flow
Regulator
Water
Control
Valve
Pressure
Tank
Water Out
Boiler
Drains
Optional
Filter
Shut-Off
Valve
Water In
c l i m a t e m a s t e r.c o m 37
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Water Quality Standards
Table 3: Water Quality Standards
Water Quality
Parameter
HX
Material
Closed
Recirculating
Open Loop and Recirculating Well
Scaling Potential - Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below pH/Calcium Hardness
Method
All
pH < 7.5 and Ca Hardness <100ppm
Index Limits for Probable Scaling Situations -
(Operation outside these limits is not recommended)
Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use.
A monitoring plan should be implemented.
Ryznar
Stability Index
All
6.0 - 7.5
If >7.5 minimize steel pipe use.
Langelier
Saturation Index
All
-0.5 to +0.5
If <-0.5 minimize steel pipe use. Based upon 66°C HWG and
Direct well, 29°C Indirect Well HX
Iron Fouling
Iron Fe 2+ (Ferrous)
(Bacterial Iron potential)
All
-
<0.2 ppm (Ferrous)
If Fe 2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
-
Iron Fouling All
<0.5 ppm of Oxygen
Above this level deposition will occur .
Corrosion Prevention
6 - 8.5
6 - 8.5
pH All
Monitor/treat as needed
-
Minimize steel pipe below 7 and no open tanks with pH <8
Hydrogen Sulfide (H
2
S)
All
<0.5 ppm
At H
2
S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.
Ammonia ion as hydroxide, chloride, nitrate and sulfate compounds All
-
<0.5 ppm
Maximum
Chloride Levels
Copper
Cupronickel
304 SS
316 SS
Titanium
-
-
-
-
-
Maximum Allowable at maximum water temperature.
10 ° C
<20ppm
<150 ppm
<400 ppm
<1000 ppm
>1000 ppm
24 ° C
NR
NR
<250 ppm
<550 ppm
>550 ppm
38 C
NR
NR
<150 ppm
< 375 ppm
>375 ppm
Erosion and Clogging
Particulate Size and
Erosion
All
<10 ppm of particles and a maximum velocity of 1.8 m/s
Filtered for maximum
841 micron [0.84 mm,
20 mesh] size.
<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,
20 mesh] size. Any particulate that is not removed can potentially clog components.
The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger and any other components damaged by a leak.
Notes:
• Closed Recirculating system is identified by a closed pressurized piping system.
• Recirculating open wells should observe the open recirculating design considerations.
• NR - Application not recommended.
• "-" No design Maximum.
38 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Line Voltage
Electrical – Line Voltage All field installed wiring, including electrical ground, must comply with the National
Electrical Code as well as all applicable local codes. Refer to the unit electrical data for fuse sizes. Consult wiring diagram for field connections that must be made by the installing (or electrical) contractor. All final electrical connections must be made with a length of flexible conduit to minimize vibration and sound transmission to the building.
General Line Voltage Wiring - Be sure the available power is the same voltage and phase shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Transformer All 208/230 voltage units are factory wired for 208 volt. If supply voltage is 230 volt, installer must rewire transformer. See wire diagram for connections.
� WARNING!
�
WARNING!
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
� CAUTION!
�
CAUTION!
Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Table 4a: Tranquility ® Compact (TC_L) Series Electrical Data - (Standard 60Hz Units)
Model #
Voltage
Code
H
Voltage
Min/Max
Voltage
208/230/60/3 197/254
Blower
Option
A, B, C
Compressor
QTY RLA LRA
2 10.4
73.0
Fan
Motor
FLA
3.2
Total
FLA/
Rated
Current
24.0
Min
Circuit
Amp
26.6
TC_L072
TC_L096
TC_L120
TC_LV160
H
H
N
N
F
H
F
N
H
F
F
N
N
F
F
H
H
N
F
N
H
F
N
208/230/60/3 197/254
460/60/3 414/506
460/60/3
575/60/3
575/60/3
414/506
518/633
518/633
208/230/60/3 197/254
208/230/60/3 197/254
460/60/3
460/60/3
575/60/3
414/506
414/506
518/633
575/60/3 518/633
208/230/60/3 197/254
208/230/60/3 197/254
460/60/3 414/506
460/60/3 414/506
575/60/3
575/60/3
518/633
518/633
208/230/60/3 197/254
208/230/60/3 197/254
460/60/3 414/506
460/60/3
575/60/3
575/60/3
414/506
518/633
518/633
10.4
73.0
5.8
38.0
5.8
3.8
3.8
38.0
36.5
36.5
13.7
83.1
13.7
83.1
6.2
6.2
4.8
41.0
41.0
33.0
4.8
33.0
15.6
110.0
15.6
110.0
7.8
52.0
7.8
52.0
5.8
5.8
38.9
38.9
23.2
164.0
23.2
164.0
11.2
75.0
11.2
75.0
7.9
54.0
7.9
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
3.2
5.2
8.5
13.8
4.1
3.2
8.5
13.8
4.1
6.5
6.5
3.2
5.2
6.0
8.5
2.9
4.1
2.4
6.0
1.6
2.9
1.2
2.4
14.8
16.8
54.9
60.2
26.5
12.8
39.7
45.0
19.7
22.1
33.4
35.9
15.3
16.5
12.0
26.8
13.2
14.5
8.8
10.0
28.9
19.0
21.0
16.3
18.3
60.7
66.0
29.3
14.0
43.6
48.9
21.7
24.1
36.8
39.3
16.9
18.1
13.2
29.4
14.7
16.0
9.8
11.0
31.7
21.0
23.0
All fuses Class RK-5
NOTE: All VFD Unit (Option F Motors) use E Motors in chart.
Table Continued on Following Page c l i m a t e m a s t e r.c o m
SCCR ka rms symetrical
SCCR
Volts
Maximum
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
5
5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
600
600
N/A
N/A
N/A
N/A
Max
Fuse/
HACR
15
50
60
25
30
50
50
20
20
15
20
15
15
35
35
20
40
25
30
20
20
80
80
40
39
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Line Voltage, Cont’d.
Table 4a, Cont’d.: Tranquility ® Compact (TC_L) Series Electrical Data - (Standard 60Hz Units)
Model #
Voltage
Code
H
Voltage
Min/Max
Voltage
208/230/60/3 197/254
Blower
Option
A, B, C
Compressor
QTY RLA LRA
2 25.0
164.0
Fan
Motor
FLA
8.5
Total
FLA/
Rated
Current
58.5
Min
Circuit
Amp
64.8
SCCR ka rms symetrical
5
SCCR
Volts
Maximum
600
TC_LV192
H
H
N
N
F
H
F
F
208/230/60/3 197/254
460/60/3 414/506
460/60/3 414/506
575/60/3
575/60/3
518/633
518/633
208/230/60/3 197/254
208/230/60/3 197/254
460/60/3 414/506
TC_LV240
N
H
F
N
H
460/60/3
575/60/3
414/506
518/633
575/60/3 518/633
208/230/60/3 197/254
208/230/60/3 197/254
TC_LV300
N
N
F
F
460/60/3
460/60/3
575/60/3
575/60/3
414/506
414/506
518/633
518/633
All fuses Class RK-5
NOTE: All VFD Unit (Option F Motors) use E Motors in chart.
D, E
A, B, C
D, E
A, B, C
E
A, B, C
E
A, B, C
E
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
D, E
A, B, C
25.0
164.0
12.2
100.0
12.2
100.0
9.0
9.0
78.0
78.0
30.1
225.0
30.1
225.0
16.7
114.0
16.7
114.0
12.2
80.0
12.2
80.0
48.1
245.0
48.1
245.0
18.6
125.0
18.6
125.0
14.7
100.0
14.7
100.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
47.5
32.7
35.5
129.2
134.2
51.8
54.4
41.1
43.3
70.1
31.6
34.0
23.5
25.5
81.5
88.7
44.1
43.3
29.6
32.4
117.2
122.2
47.1
49.7
37.4
39.6
63.8
28.5
30.9
21.2
23.2
74.0
81.2
39.9
9.9
12.5
8.0
10.2
9.9
5.2
8.0
21.0
26.0
13.8
4.1
6.5
3.2
5.2
13.8
21.0
6.5
5
5
N/A
N/A
N/A
N/A
N/A
5
5
5
N/A
N/A
N/A
N/A
5
5
N/A
600
600
N/A
N/A
N/A
N/A
N/A
600
600
600
N/A
N/A
N/A
N/A
600
600
N/A
Max
Fuse/
HACR
70
70
50
50
60
40
45
150
150
30
30
110
110
60
80
90
40
45
40 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Line Voltage, Cont’d.
Table 4b: Tranquility ® Compact (TC_L) Series Electrical Data - (Dual Point Power 60Hz Units)
TC_L072
TC_L096
TC_L120
F
F
H
H
N
F
N
H
F
N
N
N
F
F
H
H
H
Voltage
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254
460/60/3
460/60/3
575/60/3
575/60/3
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254 D, E
460/60/3 414/506 A, B, C
460/60/3
575/60/3
575/60/3
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254 D, E
460/60/3
460/60/3
575/60/3
Min/
Max
Voltage
414/506 A, B, C
414/506
518/633 A, B, C
518/633
414/506
518/633 A, B, C
518/633
414/506 A, B, C
414/506
Blower
Option
D, E
D, E
D, E
D, E
D, E
D, E
518/633 A, B, C
TC_LV160
H
F
N
H
F
575/60/3 518/633 D, E
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254 D, E
460/60/3 414/506 A, B, C
460/60/3 414/506 D, E
H
H
N
N
F
575/60/3
575/60/3
518/633 A, B, C
518/633 D, E
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254 D, E
460/60/3 414/506 A, B, C
TC_LV192
F
N
460/60/3
575/60/3
414/506 D, E
518/633 A, B, C
N 575/60/3 518/633 D, E
All fuses Class RK-5
Note: All VFD Units (Option F Fan Motors) use E motors.
QTY RLA LRA
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
10.4 73.0
10.4 73.0
5.8
38.0
5.8
38.0
3.8
36.5
3.8
36.5
13.7 83.1
13.7 83.1
6.2
41.0
6.2
41.0
4.8
33.0
4.8
33.0
15.6 110.0
31.2
15.6 110.0
31.2
7.8
52.0
7.8
52.0
5.8
38.9
15.6
15.6
11.6
27.4
12.4
12.4
9.6
9.6
5.8
38.9
23.2 164.0
46.4
23.2 164.0
46.4
11.2 75.0
11.2 75.0
7.9
54.0
7.9
54.0
25.0 164.0
25.0 164.0
12.2 100.0
24.4
12.2 100.0
24.4
9.0
78.0
9.0
78.0
11.6
11.6
7.6
7.6
27.4
Compressor Power Supply
Comp
FLA/
Rated
Current
20.8
Comp
MCA
23.4
SCCR kA rmas symetrical
N/A
SCCR
Volts
Maximum
N/A
20.8
23.4
N/A N/A
Emergency Power Supply
Comp
Max
Fuse/
HACR
30
Fan
FLA/
Rated
Current
3.2
Fan
MCA
4.0
SCCR kA rmas symetrical
N/A
SCCR
Volts
Maximum
N/A
13.1
13.1
8.6
8.6
30.8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
30
15
15
15
15
40
6.0
1.6
2.9
1.2
2.4
6.0
7.5
2.0
3.6
1.5
3.0
7.5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
11.6
22.4
22.4
15.8
15.8
50.0
50.0
18.0
18.0
30.8
14.0
14.0
10.8
10.8
35.1
35.1
17.6
17.6
13.1
13.1
52.2
52.2
25.2
25.2
17.8
17.8
56.3
56.3
27.5
27.5
20.3
20.3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
5
5
N/A
N/A
N/A
N/A
5
5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
600
600
N/A
N/A
N/A
N/A
600
600
N/A
N/A
N/A
N/A
40
20
20
15
15
50
50
25
25
15
15
70
70
35
35
25
25
80
80
35
35
25
25
8.5
2.9
4.1
2.4
3.2
8.5
13.8
4.1
6.5
3.2
5.2
8.5
13.8
4.1
6.5
3.2
5.2
8.5
13.8
4.1
6.5
3.2
5.2
10.6
3.6
5.1
3.0
4.0
10.6
17.3
5.1
8.1
4.0
6.5
10.6
17.3
5.1
8.1
4.0
6.5
10.6
17.3
5.1
8.1
4.0
6.5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15
15
15
30
15
15
15
30
15
15
15
15
15
15
30
15
15
15
15
15
15
15
15
15
15
15
15
15
Fan
Max
Fuse/
HACR
15
15
Table Continued on Following Page c l i m a t e m a s t e r.c o m 41
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Line Voltage, Cont’d.
Table 4b, Cont’d.: Tranquility ® Compact (TC_L) Series Electrical Data - (Dual Point Power 60Hz Units)
TC_LV240
TC_LV300
N
N
F
F
H
H
H
F
N
H
F
N
Voltage
Min/
Max
Voltage
208/230/60/3 197/254
Blower
Option
208/230/60/3 197/254 A, B, C
D, E
QTY RLA LRA
2
2
30.1 225.0
30.1 225.0
Compressor Power Supply
Comp
FLA/
Rated
Current
60.2
Comp
MCA
67.7
SCCR kA rmas symetrical
5
SCCR
Volts
Maximum
600
60.2
67.7
5 600
Comp
Max
Fuse/
HACR
90
Emergency Power Supply
Fan
FLA/
Rated
Current
Fan
MCA
13.8
17.3
SCCR kA rmas symetrical
N/A
SCCR
Volts
Maximum
N/A
90 21.0
26.3
N/A N/A
460/60/3
460/60/3
575/60/3
575/60/3
414/506 A, B, C
414/506 D, E
518/633 A, B, C
518/633 D, E
208/230/60/3 197/254 A, B, C
208/230/60/3 197/254
460/60/3
E
414/506 A, B, C
460/60/3
575/60/3
575/60/3
414/506 E
518/633 A, B, C
518/633 E
2
2
2
2
2
2
2
2
2
2
16.7 114.0
16.7 114.0
12.2 80.0
12.2 80.0
48.1 245.0
48.1 245.0
18.6 125.0
18.6 125.0
14.7 100.0
14.7 100.0
33.4
33.4
24.4
24.4
96.2
96.2
37.2
37.2
29.4
29.4
37.6
37.6
27.5
27.5
108.2
108.2
41.9
41.9
33.1
33.1
N/A
N/A
N/A
N/A
5
5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
600
600
N/A
N/A
N/A
N/A
50
50
35
35
150
150
60
60
45
45
6.5
9.9
5.2
8.0
8.1
12.4
6.5
10.0
21.0
26.3
26.0
32.5
9.9
12.4
12.5
15.6
8.0
10.0
10.2
12.8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15
20
15
15
45
Fan
Max
Fuse/
HACR
30
45
50
20
25
15
20
42 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Power Wiring
Figure 16: TC_LH072-120 Line Voltage Wiring � WARNING!
�
WARNING!
Disconnect electrical power source to prevent injury or death from electrical shock.
� CAUTION!
�
CAUTION!
Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Electrical – Line Voltage All field installed wiring, including electrical ground, must comply with the National
Electrical Code as well as all applicable local codes. Refer to the unit electrical data for fuse sizes. Consult wiring diagram for field connections that must be made by the installing (or electrical) contractor. All final electrical connections must be made with a length of flexible conduit to minimize vibration and sound transmission to the building.
General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the “L” side of the power block as shown in Figure 16. Consult electrical data tables for correct fuse size.
Transformer All 208/230 voltage units are factory wired for 208 volt. If supply voltage is 230 volt, installer must rewire transformer. See wire diagram for connections.
Power
Block c l i m a t e m a s t e r.c o m 43
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Power & Low Voltage Wiring
Thermostat Connections The thermostat should be wired directly to the CXM or DXM board. Figure 17 shows wiring for TC units. See “Electrical – Thermostat”
(Figure 21) for specific terminal connections. Review the appropriate AOM (Application, Operation and
Maintenance) manual for units with DDC controls.
Low Water Temperature Cutout Selection The CXM/
DXM control allows the field selection of low water (or water-antifreeze solution) temperature limit by clipping jumper JW3, which changes the sensing temperature associated with thermistor LT1. Note that the LT1 thermistor is located on the refrigerant line between the coaxial heat exchanger and expansion device (TXV or cap tube). Therefore, LT1 is sensing refrigerant temperature, not water temperature, which is a better indication of how water flow rate/temperature is affecting the refrigeration circuit.
The factory setting for LT1 is for systems using water
(30°F [-1.1°C] refrigerant temperature). In low water temperature (extended range) applications with antifreeze (most ground loops), jumper JW3 should be clipped as shown in Figure 18 to change the setting to
10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All
ClimateMaster units operating with entering water temperatures below 59°F [15°C] must include the optional water/refrigerant circuit insulation package to prevent internal condensation.
Figure 17: TC_LH072-120 Low Voltage Field Wiring
(CXM Shown) NOTE: For DXM, Y2 wiring at DXM1
CXM1 Low
Voltage
Connector
CXM2
Figure 18: LT1 Limit Setting
LT1
LT2
JW3-LT1 jumper should be clipped for low temperature operation
CXM PCB
Models with Waterside Economizer Controller is factory assembled. Factory settings are 45°F (7.2°C),
LT1
LT1
LT2
LT2 valve opens, closes at 55°F (12.8°C), and 5 minute short cycle delay. Settings are adjustable.
Accessory Connections A terminal paralleling the compressor contactor coil has been provided on the CXM/
DXM control. Terminal “A” is designed to control accessory devices, such as water valves. Note: This terminal should be used only with 24 Volt signals and not line voltage.
Terminal “A” is energized with the compressor contactor.
See the specific unit wiring diagram for details.
Low Voltage VA Ratings
Components In Unit
Typical Blower Contactor
Typical Reversing Valve Solenoid (2)
30A Compressor Contactor (2)
CXM board (2)
DXM board (2)
Units with CXM
Remaing VA for Accessories
Units with DXM
Remaing VA for Accessories
Standard transformer is 75VA.
VA
6 - 9
8 - 12
12 - 18
10 - 18
16 - 24
39 - 18
33 - 12
Figure 19 : Accessory Wiring
44 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
Figure 20: Optional Motorized Water Valve Wiring
1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
2
Switch
3
23B0040N01 for 072 and 096 or 23B0041N01 for 120 Valve
Electrical – Low Voltage Wiring
� CAUTION!
�
CAUTION! Many units are installed with a factory or field supplied manual or electric shut-off valve. DAMAGE WILL
OCCUR if shut-off valve is closed during unit operation. A high pressure switch must be installed on the heat pump side of any field provided shut-off valves and connected to the heat pump controls in series with the built-in refrigerant circuit high pressure switch to disable compressor operation if water pressure exceeds pressure switch setting. The field installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal flare connection as part number 39B0005N02.
Thermostat
Water Solenoid Valves An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water hammer. Figure 19 shows typical wiring for a 24VAC external solenoid valve. This wiring should only be used if valve fully opens in 15 second. Figure 20 illustrates a typical slow closing water control valve wiring for
Belimo valves. Slow closing valves take approximately
60 seconds to open (very little water will flow before
45 seconds). Once fully open, an end switch allows the compressor to be energized. Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25-35 VA through the “Y” signal of the thermostat.
Note: This valve can overheat the anticipator of an electromechanical thermostat. Therefore, only relay or triac based thermostats should be used.
c l i m a t e m a s t e r.c o m 45
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Electrical – Thermostat Wiring
Thermostat Installation The thermostat should be located on an interior wall in a larger room, away from supply duct drafts. DO NOT locate the thermostat in areas subject to sunlight, drafts or on external walls.
The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature measurement. Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate. Mark the position of the back plate mounting holes and drill holes with a 3/16” (5 mm) bit. Install supplied anchors and secure plate to the wall. Thermostat wire must be 18 AWG wire. Wire the appropriate thermostat as shown in Figure 20 to the low voltage terminal strip on the CXM or DXM control board. Practically any heat pump thermostat will work with ClimateMaster units, provided it has the correct number of heating and cooling stages.
Figure 21: Thermostat Connection
Connection to CXM Control
ATP32U03 Thermostat CXM1
Compressor-Stage 1 Y
CXM1
O
24Vac Hot
24Vac Com
G
R
C
G
R
24Vac Com C
Y1
Y2
O
Field Wiring
AL
Connection to DXM Control
O
G
R
C
AL
Y
O
G
R
C
AL
CXM2
Y
O
G
R
C
AL
CXM2
Y
O
G
R
C
AL
ATP32U03 Thermostat DXM1
Compressor-Stage 1
Connection to DXM Control
ATP32U03 Thermostat
Fan G
Compressor-Stage 2
24Vac Com C
Y1
Y2
O
G
R
Y2
O
G
R
C
AL1
DXM1
Y1
Y2
O
G
R
24Vac Com C C
AL AL1
COM 2
DXM2
Y COM 2
O
G
R
C
AL1
DXM2
Y
O
G
R
C
AL1
COM 2
46 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Typical Wiring Diagram – TC_L Units with CXM
c l i m a t e m a s t e r.c o m 47
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Typical Wiring Diagram – TC_L Units with MPC
48 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Typical Wiring Diagram – TC_L Units with DXM
c l i m a t e m a s t e r.c o m 49
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Typical Wiring Diagram – TC_L Units with LON
50 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
CXM Controls
CXM Control -
Application, Operation and Maintenance (AOM) manual
(part # 97B0003N12).
Field Selectable Inputs Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. At board, momentarily shorting the test terminals or externally, momentarily push test button
(See Fig 22), the CXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will flash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals or holding button for 3 seconds.
Retry Mode: If the control is attempting a retry of a fault, the status LED will slow flash (slow flash = one flash every 2 seconds) to indicate the control is in the process of retrying.
Field Configuration Options - configuration options, jumper wires should be clipped
ONLY when power is removed from the CXM control.
Water coil low temperature limit setting: Jumper 3 (JW3-
LT1 Low Temp) provides field selection of temperature limit setting for LT1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-LT2
Low Temp) provides field selection of temperature limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by the factory.
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides field selection of the alarm relay terminal AL2 to be jumpered to
24VAC or to be a dry contact (no connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry contact (no connection).
DIP Switches -
For detailed control information, see CXM
Note: In the following field
Note: In the following field configuration options, DIP switches should only be changed when power is removed from the CXM control.
DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage
2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.
On = Stage 1. Off = Stage 2
DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection for
DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.
Note: Some CXM controls only have a 2 position DIP switch package. If this is the case, this option can be selected by clipping the jumper which is in position 4 of
SW1.
Jumper not clipped = EH2 Normal. Jumper clipped = DDC
Output at EH2.
DIP switch 5: Factory Setting - Normal position is “On.”
Do not change selection unless instructed to do so by the factory.
Table 5a: LED And Alarm Relay Operations
Description of Operation
Normal Mode
LED
ON
Normal Mode w/UPS Warning
CXM is non-functional
Fault Retry
Lockout
Over/Under Voltage Shutdown
ON
OFF
Slow Flash
Fast Flash
Slow Flash
Test Mode - No Fault in Memory Flashing Code 1
Test Mode - HP Fault in Memory Flashing Code 2
Test Mode - LP Fault in Memory Flashing Code 3
Test Mode - LT1 Fault in Memory Flashing Code 4
Test Mode - LT2 Fault in Memory Flashing Code 5
Test Mode - CO Fault in Memory Flashing Code 6
Test Mode - Over/Under
Shutdown in Memory
Flashing Code 7
Test Mode - UPS in Memory Flashing Code 8
Test Mode - Swapped Thermistor Flashing Code 9
Alarm
Open
Cycle (Closed 5 seconds,
Open 25 seconds)
Open
Open
Closed
Open (Closed after 15
Minutes)
Cycling Code 1
Cycling Code 2
Cycling Code 3
Cycling Code 4
Cycling Code 5
Cycling Code 6
Cycling Code 7
Cycling Code 8
Cycling Code 9
- Slow Flash = 1 flash every 2 seconds
- Fast Flash = 2 flashes every 1 second
- Flash code 2 = 2 quick flashes, 10 second pause, 2 quick flashes, 10 second pause, etc.
- On pulse 1/3 second; off pulse 1/3 second
DIP switch 1: Unit Performance Sentinel Disable - provides field selection to disable the UPS feature.
On = Enabled. Off = Disabled.
� CAUTION!
�
CAUTION! Do not restart units without inspection and remedy of faulting condition. Equipment damage may occur. c l i m a t e m a s t e r.c o m 51
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
DXM Controls
DXM Control For detailed control information, see DXM
AOM (part #97B0003N13), Lon controller AOM (part
#97B0013N01) or MPC AOM (part # 97B0031N01).
Table 5b: DXM LED And Alarm Relay Operations
Normal mode
Normal mode with UPS
Status LED
(green)
On
On
Test LED
(yellow)
-
-
Fault LED
(red)
Off
Flashing Code 8
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-LT2
Low Temp) provides field selection of temperature limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant
Alarm Relay
Open
Cycle (closed 5 sec, open 25 sec) temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by Enertech technical services.
Not Clipped = 30°F [-1°C].
Clipped = 10°F [-12°C].
DXM is non-functional
Fault Retry
Lockout
Test Mode
Night Setback
ESD
Invalid T-stat Inputs
Off
Slow Flash
Fast Flash
-
Flashing Code 2
Flashing Code 3
Flashing Code 4
-
-
-
Off
-
-
On
Off
Flashing fault code
Flashing fault code
-
-
-
-
Open
Open
Closed
-
-
-
-
Alarm relay setting: Jumper 4 (JW4-AL2
Dry) provides field selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection).
Not Clipped = AL2 connected to R.
Clipped = AL2 dry contact (no connection).
HP Fault
LP Fault
LT1 Fault
LT2 Fault
CO Fault
Over/Under Voltages
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
Slow Flash
-
-
-
-
-
-
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
Flashing Code 7
- Slow Flash = 1 flash every 2 seconds
- Fast Flash = 2 flashes every 1 second
- Flash code 2 = 2 quick flashes, 10 second pause, 2 quick flashes, 10 second pause, etc.
- On pulse 1/3 second; off pulse 1/3 second
Open
Open
Open
Open
Open
Open (closed after 15 minutes)
Low pressure normally open: Jumper 1 (JW1-
LP norm open) provides field selection for low pressure input to be normally closed or normally open.
Not Clipped = LP normally closed.
Clipped = LP normally open.
DIP Switches - Note: In the following field configuration options, DIP switches should only be changed when power is removed from the DXM control.
Field Selectable Inputs Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the DXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will flash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.
Retry mode: the status LED will slow flash (slow flash = one flash every 2 seconds) to indicate the control is in the process of retrying.
If the control is attempting a retry of a fault,
Field Configuration Options -
Water coil low temperature limit setting: Jumper
3 (JW3-LT1 Low Temp) provides field selection of temperature limit setting for LT1 of 30°F or 10°F [-1°F or
-12°C] (refrigerant temperature).
Note: In the following field configuration options, jumper wires should be clipped
ONLY when power is removed from the DXM control.
DIP Package #1 (S1)
1.1
1.2
- DIP Package #1 has 8 switches and provides the following setup selections:
- Unit Performance Sentinel (UPS) disable: DIP Switch
1.1 provides field selection to disable the UPS feature.
On = Enabled. Off = Disabled.
- Compressor relay staging operation: DIP 1.2 provides selection of compressor relay staging operation.
The compressor relay can be selected to turn on with a stage 1 or stage 2 call from the thermostat. This is used with dual stage units (2 compressors where 2 DXM controls are being used) or with master/slave applications.
In master/slave applications, each compressor and fan will stage according to its appropriate DIP 1.2 setting. If set to stage 2, the compressor will have a 3 second on-delay before energizing during a Stage 2 demand. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.
On = Stage 1. Off = Stage 2.
1.3
- Thermostat type (heat pump or heat/cool): DIP 1.3 provides selection of thermostat type. Heat pump or heat/cool thermostats can be selected. When in heat/ cool mode, Y1 is the input call for cooling stage 1; Y2 is the input call for cooling stage 2; W1 is the input call for heating stage 1; and O/W2 is the input call for heating
52 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
DXM Controls, Cont’d.
stage 2. In heat pump mode, Y1 is the input call for compressor stage 1; Y2 is the input call for compressor stage 2; W1 is the input call for heating stage 3 or emergency heat; and O/W2 is the input call for reversing valve (heating or cooling, depending upon DIP 1.4).
On = Heat Pump. Off = Heat/Cool.
1.4
- Thermostat type (O/B): DIP 1.4 provides selection of thermostat type for reversing valve activation. Heat pump thermostats with “O” output (reversing valve energized for cooling) or “B” output (reversing valve energized for heating) can be selected with DIP 1.4.
On = HP stat with “O” output for cooling. Off = HP stat with “B” output for heating.
1.5
- Dehumidification mode: DIP 1.5 provides selection of normal or dehumidification fan mode. In dehumidification mode, the fan speed relay will remain off during cooling stage 2. In normal mode, the fan speed relay will turn on during cooling stage 2.
On = Normal fan mode. Off = Dehumidification mode.
1.6
- DDC output at EH2: DIP 1.6 provides selection for
DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.
1.7
- Boilerless operation: DIP 1.7 provides selection of boilerless operation. In boilerless mode, the compressor is only used for heating when LT1 is above the temperature specified by the setting of DIP 1.8. Below DIP 1.8 setting, the compressor is not used and the control goes into emergency heat mode, staging on EH1 and EH2 to provide heating.
On = normal. Off = Boilerless operation.
1.8
- Boilerless changeover temperature: DIP 1.8 provides selection of boilerless changeover temperature setpoint.
Note that the LT1 thermistor is sensing refrigerant temperature between the coaxial heat exchanger and the expansion device (TXV). Therefore, the 50°F [10°C] setting is not 50°F [10°C] water, but approximately 60°F
[16°C] EWT.
On = 50°F [10°C]. Off = 40°F [16°C].
DIP Package #2 (S2)
2.1
- DIP Package #2 has 8 switches and provides the following setup selections:
- Accessory1 relay personality: DIP 2.1 provides selection of ACC1 relay personality (relay operation/ characteristics). See table 5c for description of functionality.
2.2
- Accessory1 relay personality: DIP 2.2 provides selection of ACC 1 relay personality (relay operation/ characteristics). See table 5c for description of functionality.
2.3
- Accessory1 relay personality: DIP 2.3 provides selection of ACC 1 relay options. See table 5c for description of functionality.
2.4
- Accessory2 relay personality: DIP 2.4 provides selection of ACC 2 relay personality (relay operation/ characteristics). See table 5c for description of functionality.
2.5
- Accessory2 relay personality: DIP 2.5 provides selection of ACC 2 relay personality (relay operation/ characteristics). See table 5c for description of functionality.
2.6
- Accessory2 relay personality: DIP 2.6 provides selection of ACC 2 relay options. See table 5c for description of functionality.
2.7
- Auto dehumidification fan mode or high fan mode:
DIP 2.7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification mode, the fan speed relay will remain off during cooling stage 2
IF the H input is active. In high fan mode, the fan enable and fan speed relays will turn on when the H input is active.
On = Auto dehumidification mode. Off = High fan mode.
2.8
- Special factory selection: DIP 2.8 provides special factory selection. Normal position is “On”. Do not change selection unless instructed to do so by the factory.
Table 5c: Accessory DIP Switch Settings
DIP 2.1
On
Off
On
On
Off
Off
DIP 2.4
On
Off
On
On
DIP 2.2
On
On
Off
On
Off
On
DIP 2.5
On
On
Off
On
DIP 2.3
On
On
On
Off
Off
Off
DIP 2.6
On
On
On
Off
All other DIP combinations are invalid
ACC1 Relay Option
Cycle with fan
Digital NSB
Water Valve - slow opening
OAD
Reheat Option - Humidistat
Reheat Option - Dehumidistat
ACC2 Relay Option
Cycle with compressor
Digital NSB
Water Valve - slow opening
OAD c l i m a t e m a s t e r.c o m 53
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Safety Features
Safety Features – CXM/DXM Control
The safety features below are provided to protect the compressor, heat exchangers, wiring, and other components from damage caused by operation outside of design conditions.
Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor.
Note: The 5 minute anti-short cycle also occurs at power up.
Random start: The control features a random start upon power up of 5-80 seconds.
Fault Retry: In Fault Retry mode, the Status LED begins slowly flashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfied, the control will continue on as if no fault occurred.
If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed at the “fault” LED (DXM board) or by going into test mode (CXM board). Note:
LT1/LT2 faults are factory set at only one try.
Lockout: In lockout mode, the status LED will begin fast flashing. The compressor relay is turned off immediately.
Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset
(disconnecting power to the control) resets the control and erases fault memory.
Lockout with emergency heat: While in lockout mode, if W becomes active (CXM), emergency heat mode will occur. If DXM is configured for heat pump thermostat type (DIP 1.3), emergency heat will become active if O/
W2 is energized.
High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor).
High pressure lockout code = 2
Example: 2 quick flashes, 10 sec pause, 2 quick flashes,
10 sec. pause, etc.
Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during
“on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to
54 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s compressor power up it will be considered a low pressure
(loss of charge) fault. The low pressure switch input is bypassed for the initial 120 seconds of a compressor run cycle.
Low pressure lockout code = 3
Water coil low temperature (LT1): The LT1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT1 fault.
The LT1 input is bypassed for the initial 120 seconds of a compressor run cycle. LT1 is set at the factory for one try.
Therefore, the control will go into lockout mode once the
LT1 fault has occurred.
LT1 lockout code = 4
Air coil low temperature (LT2): The LT2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT2 fault.
The LT2 input is bypassed for the initial 60 seconds of a compressor run cycle. LT2 is set at the factory for one try.
Therefore, the control will go into lockout mode once the
LT2 fault has occurred.
LT2 lockout code = 5
Condensate overflow: The condensate overflow sensor must sense overflow level for 30 continuous seconds to be recognized as a CO fault. Condensate overflow will be monitored at all times.
CO lockout code = 6
Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 19VAC to 30VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the CXM/DXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close.
Over/under voltage shut down code = 7
Unit Performance Sentinel-UPS (patent pending): The
UPS feature indicates when the heat pump is operating inefficiently. A UPS condition exists when: a. In heating mode with compressor energized, LT2 is greater than 125°F [52°C] for 30 continuous seconds, or: b. In cooling mode with compressor energized, LT1 is greater than 125°F [52°C] for 30 continuous seconds, or: c. In cooling mode with compressor energized, LT2 is less than 40°F [4.5°C] for 30 continuous seconds.
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
CXM and DXM Controls
If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for
25 seconds, etc.
UPS warning code = 8
Swapped LT1/LT2 thermistors: During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout with code 9 after 30 seconds if: a. The compressor is on in the cooling mode and the LT1 sensor is colder than the LT2 sensor, or: b. The compressor is on in the heating mode and the LT2 sensor is colder than the LT1 sensor.
Swapped LT1/LT2 thermistor code = 9.
ESD (DXM only): The ESD (Emergency Shut Down) mode can be enabled from an external common signal to terminal ESD to shut down the unit. The green status light will flash code 3 when the unit is in ESD mode.
ESD mode = code 3 (green “status” LED)
CXM/DXM Control Start-up Operation
The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The first time after power-up that there is a call for compressor, the compressor will follow a 5 to
80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized. On all subsequent compressor calls, the random start delay is omitted.
Diagnostic Features
The LED on the CXM board advises the technician of the current status of the CXM control. The LED can display either the current CXM mode or the last fault in memory if in test mode. If there is no fault in memory, the LED will flash Code 1 (when in test mode).
The green status LED and red fault LED on the DXM board advise the technician of the current status of the
DXM control. The status LED will indicate the current mode that the DXM control is in. The fault LED will
ALWAYS flash a code representing the LAST fault in memory. If there is no fault in memory, the fault LED will flash Code 1. The yellow test LED will turn on when in test mode. CAUTION: Do not restart units without inspection and remedy of faulting condition. Damage may occur.
c l i m a t e m a s t e r.c o m 55
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Adjustment
� CAUTION!
�
CAUTION! Always disconnect all power supply(s) to unit prior to making belt or sheave adjustments. Inadvertently starting of the motor can cause damage to the equipment and personal injury.
Belt Tensioning An overly loose belt will, upon motor start, produce a slippage 'squeel' and cause premature belt failure and or intermittent airflow. An overly tight belt can cause premature motor or blower bearing failure.
Airflow and External Static Pressure
Selection Adjustment The TC_L Series is available with standard, low, and high static options. These options will substitute a different blower drive sheave for each static range. In addition certain static ranges (see blower tables) may require the optional large fan motor. Please specify static range and motor horsepower when ordering. See model nomenclature.
Belt Tensioning Procedure - TC_L
1. Remove belt from motor sheave
2. Lift motor assembly
3. Loosen the 5/16" hex nuts on the grommet motor adjustment bolts (2 per bolt). To increase the belt tension loosen the top hex nut. To decrease the belt tension loosen the bottom hex nut.
4. Turn the bolts by hand to the desired position then tighten the 5/16" hex nuts ( 2 per bolt).
5. Lower the motor assembly
6. Install the belt
7. The belt should be tensioned tensioning gauge method such as the Browning Belt Tensioner to set proper belt tension (See next page).
Sheave Adjustment The TC_L Series is supplied with variable sheave drive on the fan motor to adjust for differing airflows at various ESP conditions. Select an airflow requirement on the left side of the table, then move horizontally to right under the required ESP.
Note the sheave turns open, rpm and horsepower for that condition. Fully closed the sheave will produce the highest static capability (higher rpm). To adjust sheave position: loosen belt tension and remove belt, loosen set screw on variable sheave (on fan motor) and open sheave to desired position. Retighten set screw and replace belt and set belt tension as below.
Sheave and Pulley Alignment Verify belt is straight; misalignment will cause premature belt failure. Adjust sheave if needed.
Notes:
- Motor position should not need adjustment.
- Motor sheave position is at mid position of each sheave. Thus the motor sheave is typically 2.5 turns open on a 5 turn sheave.
Special Note for AHRI Testing
The Units should be adjusted as follows for rated airflow:
TCH/V072 - 2400cfm/2.5 turns and 0.57 in wg ESP
TCH/V096 - 3200cfm/3.0 turns and 0.62 in wg ESP
TCH/V120 - 4000cfm/3.0 turns and 0.59 in wg ESP
56 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
VFD Operation
VAV, Variable Air Volume Option, Motor Option F
If the unit has an option F motor, then it contains two items not found in the typical TC large units: a variable frequency drive (VFD) and a DXM2 control board. The second compressor will be controlled by a CXM board. The DXM2 board contains all of the special programing discussed below. The VFD receives a modulating signal from the
DXM2, 0-10VDC, and varies the output frequency directly proportionally to the input signal. With 60HZ current, a signal of 10 VDC will result in a 60HZ current to motor. If the signal is 5VDC, the the VFD output will be will be 30
HZ (50% fan speed).
VFD Blower Operation
If the DXM2 is configured for VFD blower operation, the
DXM2 will control an external VFD using a 0–10 VDC control signal on AO1, and will default to the LAT control mode.
NOTE: VFD output is 50% of last value during heating or cooling blower off delay times.
The actual operating range for the VFD when the blower should be active will be 2–10 VDC associated to the operating speed of 0–100%. When the VFD should be off, the output should be set to 0 VDC.
For each unit size, there will be a maximum and minimum operating speed that the VFD can be operated at for any mode, defined in table 7a.
The VFD blower may be operated in discrete speed or LAT control modes. If configured for discrete speed operation, the VFD speed will be operated using one of the three set operating speeds for each unit size, defined table 7a.
If configured for LAT operation, the VFD speed will be controlled by the DXM2 to achieve or maintain the selected target LAT value for the current operating mode.
4.6.5.1 Discrete Speed VFD Operation
When the DXM2 is configured for discrete speed VFD operation, the VFD speed will be set to the selected operating speed (A, B or C) for full load heating or cooling. Full load operation is defined as second stage or higher heating or cooling. The possible discrete operating speeds for each unit size are defined in table 7a.
When the DXM2 is configured for discrete speed VFD operation, the VFD operating speed may be increased or decreased by 10%, if the appropriate speed adjustment flag is set in the VFD configuration flags. If the increase and decrease flags are both set, there will be no adjustment from the normal value.
When operating in first stage heating or cooling, the
VFD speed will be set to the percentage of the selected full load operating speed (A, B or C, plus or minus adjustment) listed for each unit size as defined in table
7a.
4.6.5.2 LAT Control VFD Operation
When the DXM2 is configured for LAT control operation, the VFD speed will be controlled by the DXM2 to maintain the selected target LAT for heating or cooling operation.
When a compressor demand is recognized, the VFD output will be set to the most recent operating speed of the VFD in the current operating mode (heating or cooling). If there is no value stored from a previous heating or cooling cycle, the VFD speed will initially set at 75% or 8.0 VDC. After the VFD speed is initially set, the VFD control signal will not be adjusted until after
90 seconds of compressor operation, and then will be periodically checked and adjusted every 10 seconds if needed to maintain the LAT.
If the control switches from the heating mode to cooling, or cooling to heating without de-activating the compressor, the VFD control voltage will immediately switch to the last stored control voltage for the new operating mode, and then will not be adjusted for the first
90 seconds of operation in the new operating mode.
The VFD control voltage is increased or decreased incrementally based on the magnitude of the differential between the current LAT and the target LAT, using the following:
LAT differential
|Actual – Target|
∆T ≤ 1.0°F
1.0 < ∆T ≤ 2.0°F
2.0 < ∆T ≤ 3.0°F
3.0 < ∆T ≤ 5.0°F
∆T > 5.0°F
VFD adjust
(VDC)
0.0
0.1
0.2
0.3
0.4
c l i m a t e m a s t e r.c o m 57
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
VFD Operation, Cont’d.
The VFD control voltage is increased or decreased based on both the operating mode and the whether the current LAT is above or below the target LAT, using the following:
Operating mode
Heat
Cool
LAT differential
(Actual – Target)
Above
Below
Above
Below
VFD voltage adjustment
Increase
Decrease
Decrease
Increase
NOTE: Blower speed is directly proportional to VFD voltage
When the control stages from first to second stage operation, the output voltage signal will be immediately increased by 25% of the current value, not to exceed the maximum speed (voltage) for the selected heat pump family and size. The blower speed will not be adjusted further for 90 seconds after transition from first to second stage operation.
When making VFD speed adjustments for LAT control, the VFD speed should never go above the maximum speed (voltage) or below the minimum speed (voltage), for the selected heat pump family and size.
When the DXM2 is configured for LAT control operation, if auxiliary heat is active, either \for auxiliary or emergency heat, the VFD will operate using the discrete speed C for the selected heat pump family and size, until the auxiliary heat is no longer active, rather than using
LAT control.
4.6.5.3 Continuous Fan VFD Operation
When the DXM2 is configured for VFD blower operation, the continuous fan operating speed will be a selectable value. The default continuous fan operating speeds are shown in table 7a, along with the minimum and maximum operating speed values.
NOTE: In VFD operation (Blower Type = 128), the high speed fan relay (K2) is energized for high speed continuous fan, but the AO1 output voltage is unchanged.
58
Table 7a: VFD Control Valves
Unit
Series
TC_L
160
192
240
300
Unit
Size
072
096
120
144
Minimum
VFD Speed
3.7
3.8
4.2
4.0
4.1
4.4
4.2
5.0
Maximum
VFD Speed
10.0
10.0
10.0
8.8
10.0
10.0
10.0
10.0
VFD Fixed
Speed A
7.4
7.0
8.0
6.4
7.9
8.0
8.0
8.0
VFD Fixed
Speed B
6.2
6.0
7.0
7.2
6.4
7.0
7.0
8.0
VFD Fixed
Speed C
9.0
9.0
9.0
8.0
9.0
9.0
9.0
9.5
Part Load
Multiplier
71%
75%
70%
72%
76%
73%
70%
71%
Default Fan
Speed
5.2
5.0
6.0
6.4
5.4
6.0
6.0
7.0
Table 7b: Operating Temperatures
Unit Series
TC_L
Unit Size
072
096
120
144
160
192
240
300
Minimum
Heat LAT
85°
85°
85°
85°
85°
85°
85°
85°
Maximum
Heat LAT
125°
125°
125°
125°
125°
125°
125°
125°
Default
Heat LAT
105°
105°
105°
105°
105°
105°
105°
105°
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
Minimum
Cool LAT
45°
45°
45°
45°
45°
45°
45°
45°
Maximum
Cool LAT
65°
65°
65°
65°
65°
65°
65°
65°
Default
Cool LAT
55°
55°
55°
55°
55°
55°
55°
55°
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
VFD Operation, Cont’d.
DXM2 Specification:
Option: Enhanced solid state control system (DXM2)
This control system is a communicating controller, also features two stage control of cooling and two stage control of heating modes for exacting temperature and dehumidification purposes. This control system coupled with a multi-stage thermostat will better dehumidify room air by automatically running the heat pump’s fan at lower speed on the first stage of cooling thereby implementing low sensible heat ratio cooling. On the need for higher cooling performance the system will activate the second stage of cooling and automatically switch the fan to the higher fan speed setting. This system may be further enhanced with a humidistat. Units not having automatic low sensible heat ratio cooling will not be accepted; as an alternate a hot gas reheat coil may be provided with control system for automatic activation. This controller shall have sensors to monitor entering water, leaving water, supply air, and compressor discharge line temperatures.
Temperatures can be read by using service tool or communicating thermostat. Control shall have all of the above-mentioned features of the CXM control system along with the following expanded features: a. Removable thermostat connector.
b. Night setback control.
c. Random start on return from night setback.
d. Minimized reversing valve operation (Unit control logic shall only switch the reversing valve when cooling is demanded for the first time. The reversing valve shall be held in this position until the first call
for heating, ensuring quiet operation and increased valve life.).
e. Override temperature control with 2-hour timer for room occupant to override setback temperature at the thermostat.
f. Dry contact night setback output for digital night setback thermostats.
g. Ability to work with heat pump or heat/cool (Y, W) type thermostats.
h. Ability to work with heat pump thermostats using O or
B reversing valve control.
i. Emergency shutdown contacts.
j. Boilerless system heat control at low loop water temperature.
k. Ability to allow up to 3 units to be controlled by
one thermostat.
l. Relay to operate an external damper.
m. Ability to automatically change fan speed from multistage thermostat.
n. Relay to start system pump.
o. 75 VA control transformer.
Control transformer shall have load side short circuit and overload protection via a built in circuit breaker. Units not providing the 8 safety protections of anti-short cycle, low voltage, high voltage, high refrigerant pressure, low pressure (loss of charge), air coil low temperature cutout, water coil low temperature cut-out, and condensate overflow protection for both drain pans will not be accepted.
When DXM2 is connected to either ACDU service tool or ATC32U thermostat the installer/service technician can; check and set CFM; ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
c l i m a t e m a s t e r.c o m 59
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Tensioning V-Belt Drives
Figure 22: Tensioning V-Belt Drives
General Rules of Tensioning
1. Ideal tension is the lowest tension at which the belt will not slip under
peak load conditions.
2. Check tension frequently during the first 24-48 hours of operation.
3. Over tensioning shortens belt and bearing life.
4. Keep belts free from foreign material which may cause slip.
5. Make V-drive inspection on periodic basis. Tension when slipping.
Never apply belt dressing as this willl damage the belt and cause
early failure.
SMALL
“O” RING
LARGE
“O” RING
DEFLECTION =
BELT SPAN
BELT SPAN
64
FORCE
SCALE
Tension Measurement Procedure
1. Measure the belt span (see sketch).
2. Position bottom of the large “O” ring on the span scale at the measured belt span.
3. Set the small “O” ring on the deflection force scale to zero.
4. Place the tension checker squarely on one belt at the center of the belt span. Apply a force on the
plunger and perpendicular to the belt span until the bottom of the large “O” ring is even with the
top of the next belt or with the bottom of a straight edge laid across the sheaves.
5. Remove the tension checker and read the forct applied from the bottom of the small “O” ring on
the deflection force scale.
6. Compare the force you have applied with the values given in the table below. The force should be
between the minimum and maximum shown. The maximum value is shown for “New Belt” and
new belts should be tensioned at this value to allow for expected tension loss. Used belts should
be maintained at the minimum value as indicated in the table below.
NOTE: The ratio of deflection to belt span is 1:64.
Belt Deflection Force
Super Gripbelts and
Unnotched Gripbands
Gripnotch Belts and
Notched Gripbands
SPAN
SCALE
Cross
Section
A, AX
B, BX
Sheave
Range
7.6 - 9.1
9.6 - 12.2
12.7 - 17.8
8.6 - 10.7
11.2 - 14.2
14.7 - 21.8
RPM
Range
1000 - 2500
2501 - 4000
1000 - 2500
2501 - 4000
1000 - 2500
2501 - 4000
860- 2500
2501 - 4000
860- 2500
2501 - 4000
860- 2500
2501 - 4000
Used
Belt
16.458
12.454
20.016
16.902
24.019
20.906
-
-
23.574
20.016
28.022
26.688
New
Belt
24.464
18.682
30.246
25.354
35.584
31.136
-
-
35.139
29.802
41.811
39.587
Used
Belt
18.237
15.123
22.240
19.126
25.354
22.685
21.795
18.682
36.029
31.581
37.808
32.470
New
Belt
27.133
22.240
32.915
28.467
41.811
33.805
32.026
27.578
46.704
40.477
56.045
48.483
60 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Sheave Information
Table 8: TC_L Blower Sheave and Belt Information
Model
Configuration
Return/Supply
Component
72
96
120
160
192
240
300
Front or Back/ Top
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 2)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
Motor Sheave
Motor
Belt (Qty. 1)
Blower Sheave
1VP44 X 7/8"
3HP
BX42
BK77H
1VP44 X 7/8"
3HP
B41
BK90H
1VP60 X 1-1/8"
5HP
B45
2BK80H
2VP60 X 1-3/8"
7.5HP
BX55
A
BK67 X 1"
1VP34 X 7/8"
1HP
BX46
BK67 X 1"
1VP40 X 7/8"
2HP
BX46
BK67 X 1"
1VP44 X 7/8"
3HP
BX46
BK80H
1VP40 X 7/8"
3HP
B41
BK95H
1VP44 X 7/8"
3HP
B45
BK90H
1VP50 X 1-1/8"
5HP
B44
BK95H
1VP60 X 1-3/8"
7.5HP
BX57
B
BK85 X 1"
1VP34 X 7/8"
1HP
BX48
BK77 X 1"
1VP34 X 7/8"
2HP
BX47
BK67 X 1"
1VP34 X 7/8"
3HP
BX46
BK80H
Drive Package
C
BK67 X 1"
1VP44 X 7/8"
1HP
BX48
BK62 X 1"
1VP44 X 7/8"
2HP
BX46
BK67 X 1"
1VP50 X 7/8"
3HP
BX46
BK80H
D
BK67 X 1"
1VP34 X 7/8"
2HP
BX46
BK67 X 1"
1VP40 X 7/8"
E
BK67 X 1"
1VP44 X 7/8"
2HP
BX47
BK62 X 1"
1VP44 X 7/8"
3HP
BX46
3HP
BX46
BK67 X 1" BK67 X 1"
1VP44 X 1-1/8" 1VP50 X 1-1/8"
5HP
BX46
BK80H
5HP
BX47
BK80H
1VP50 X 7/8"
3HP
BX42
BK70H
1VP50 X 7/8"
3HP
B41
5HP
B41
5HP
B41
BK80H BK90H 2BK80H
1VP60 X 1-1/8" 1VP60 X 1-3/8" 2VP60 X 1-3/8"
5HP
B44
2BK80H
1VP44 X 1-1/8" 1VP50 X 1-1/8"
5HP 5HP
BX42
BK77H
BX42
BK70H
1VP44 X 1-1/8" 1VP50 X 1-1/8"
7.5HP
B44
7.5HP
BX42
2BK80H
2VP62 X 1-3/8"
7.5HP
BX55
N/A
2VP62 X 1-3/8"
10HP
BX55 c l i m a t e m a s t e r.c o m 61
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_L072 Blower Performance
All Data is Wet Coil
SCFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
ESP
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
0.00
0.10
0.20
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
0.28
0.32
0.35 0.39 0.42 0.45 0.48 0.52 0.56 0.60 0.64 0.69 0.72 0.76
B B B A A A A A A C C C C C
599 645 690 735 775 815 850 885 910 940 965 995 1015 1040
3 2 1 4 3.5
2.5
2 1.5
1 5 4.5
4 3.5
3
0.31
0.36
0.40 0.44 0.49 0.53 2.50 0.62 0.65 0.69 0.73 0.76 0.80 0.84
B B A A A A A A C C C C C C
RPM
Turns Open
BHP
Sheave/Mtr
604 655 695 740 780 820 855 890 920 950 980 1005 1030 1055
3 2 5 4 3 2.5
2 1.5
5.5
4.5
4 3.5
3 3
0.31
0.34
0.39
0.45 0.50 0.54 0.59 0.63 0.67 0.72 0.75 0.79 0.82 0.86 0.90
B B B A A A A A A C C C C C C
RPM
Turns Open
568
4.5
615 660 705 750 785 825 860 895 930 960 990 1015 1040 1065
2.5
1.5
4.5
3.5
3 2.5
1.5
1 5 4.5
4 3.5
3 2.5
BHP 0.33
0.38
0.42
0.46
0.50 0.54 0.59 0.65 0.70 0.74 0.78 0.81 0.85 0.89 0.94 0.98
Sheave/Mtr B B B A A A A A A A C C C C C C
RPM 531
Turns Open 4.5
BHP 0.37
Sheave/Mtr B
RPM 552
Turns Open 4
BHP 0.42
Sheave/Mtr B
RPM 573
583
3.5
630 670 715 755 795 835 875 905 940 970 1000 1025 1055 1080
2 5 4.5
3.5
2.5
2 1.5
1 5 4 4 3 2.5
2.5
0.40
0.45
0.49
0.55 0.60 0.65 0.70 0.75 0.79 0.83 0.87 0.92 0.96 1.00 1.04
B B A A A A A A C C C C C E E
599 645 685 730 770 810 850 885 915 950 980 1010 1040 1065 1090
3 2 5 4 3 2.5
2 1.5
5.5
4.5
4 3.5
3 2.5
2
0.47
0.51
0.56
0.60 0.65 0.70 0.75 0.80 0.84 0.89 0.94 1.00 1.05 1.10 1.16
B
620
B
660
A
705
A
745
A
785
A
820
A
860
A C C
895 925 960
C E E E E
990 1020 1050 1075 1105
Turns Open 3.5
BHP 0.48
2.5
0.52
1.5
0.57
4.5
0.61
4 3 2.5
1.5
1 5 4.5
4 3.5
3 2.5
2
0.66 0.72 0.78 0.83 0.87 0.92 0.97 1.02 1.07 1.13 1.19 1.25
Sheave/Mtr B
RPM 604
B
645
A
690
A
730
A
765
A
805
A
845
A
880
A C C E E E E E
910 945 975 1010 1035 1065 1095 1125
Turns Open 3
BHP 0.52
Sheave/Mtr B
RPM 620
2
B
660
5
0.57
0.61
0.66
0.72 0.78 0.83 0.89 0.94 1.00 1.03 1.08 1.14 1.20 1.25 1.31
A
700
4
A
740
3.5
2.5
A
780
A
815
2
A
850
1.5
A
885
1
C
5
E
4
E
3.5
E
3
E
2.5
E
2
E
1.5
E
920 950 985 1015 1045 1075 1100 1130
Turns Open 2.5
BHP 0.56
Sheave/Mtr B
RPM 635
Turns Open 2.5
BHP 0.61
Sheave/Mtr B
RPM 655
Turns Open 2
1.5
4.5
4 3 2.5
2 1.5
5.5
4.5
4 3.5
3 2.5
2 1.5
0.61
0.66
0.70
0.76 0.82 0.88 0.93 0.98 1.04 1.08 1.14 1.20 1.26 1.32 1.37
A
675
A
715
A
750
A
790
A
825
A
860
A
895
C E E E E E E E
925 960 990 1020 1050 1080 1110 1135
5 4.5
3.5
3 2 1.5
1 5 4.5
4 3.5
3 2.5
1.5
1.5
0.66
0.71
0.76
0.82 0.87 0.93 0.98 1.04 1.10 1.15 1.21 1.27 1.33 1.39 1.45
A
695
4.5
A
730
4
A
770
3.5
A
805
2.5
A
840
2
A
875
1.5
A
905
1
E E E E E E E E
940 970 1000 1030 1060 1090 1120 1145
5 4.5
3.5
3 2.5
2 1.5
1
BHP 0.66
0.72
0.77
0.83
0.88 0.93 0.99 1.05 1.11 1.16 1.22 1.30 1.37 1.44 1.51 1.57
Sheave/Mtr B A A A A A A D E E E E E E E E
RPM 670
Turns Open 1.5
710
4.5
750
3.5
785
3
815
2.5
850
1.5
885
1.5
915
1
950 980 1010 1040 1070 1100 1130 1155
4.5
4 3.5
3 2.5
2 1.5
1
BHP 0.71
0.77
0.82
0.87
0.93 0.98 1.04 1.10 1.16 1.22 1.30 1.36 1.43 1.50 1.57 1.63
Sheave/Mtr A A A A A A D E E E E E E E E E
RPM 685
Turns Open 5
725
4
765
3.5
795
3
830
2
860
1.5
895
1
925
5
955 985 1020 1045 1075 1105 1135 1160
4.5
4 3.5
3 2.5
1.5
1 1
BHP 0.79
0.84
0.90
0.95
1.01 1.07 1.13 1.19 1.25 1.31 1.38 1.46 1.52 1.59 1.66
Sheave/Mtr A A A A A D D E E E E E E E E
RPM 710
Turns Open 4.5
745
4
780
3
815
2.5
850
2
885
1
915
1
945
5
975 1005 1035 1065 1090 1120 1150
4 3.5
3 2.5
2 1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
62 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_L096 Blower Performance
All Data is Wet Coil
SCFM ESP
BHP
2400
Sheave/Mtr
RPM
2500
Turns Open
BHP
Sheave/Mtr
RPM
2600
2700
2800
0.00
0.10
0.20
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
0.45
0.50
0.54
0.59 0.63 0.69 0.74 0.80 0.85 0.90 0.94 0.99 1.04 1.10 1.16 1.22
B
578
B
625
B
665
B
705
B
745
A
785
A
820
A A A A A A A C C
860 895 925 960 990 1020 1050 1080 1110
5 4 3 2.5
1.5
5.5
5 4 3.5
3 2.5
2 1.5
1 4 3.5
0.50
0.55
0.59
0.64 0.69 0.75 0.81 0.88 0.92 0.97 1.01 1.06 1.12 1.17 1.23 1.29
B
599
B
645
B B A A A A A A A A A C C C
685 725 765 800 835 875 905 940 970 1005 1035 1060 1090 1120
Turns Open 4.5
BHP 0.55
3.5
0.60
2.5
0.65
2 6 5 4.5
4 3.5
3 2.5
2 1 4.5
3.5
3
0.69 0.75 0.80 0.86 0.92 0.97 1.02 1.08 1.13 1.19 1.25 1.30 1.36
Sheave/Mtr
RPM
B
625
B
665
B B A A A A A A A A A C C C
705 740 780 815 850 885 920 950 985 1015 1045 1075 1100 1130
Turns Open
BHP
Sheave/Mtr
RPM
4
0.60
B
645
3
0.65
B
685
2.5
0.70
B
725
1.5
760
5.5
795
5
830
4.5
865
3.5
3 2.5
2 1.5
1 4 3.5
3
0.75 0.80 0.86 0.91 0.97 1.02 1.08 1.14 1.20 1.26 1.32 1.38 1.44
A A A A A A A A A C C C C
900 930 960 995 1025 1055 1085 1115 1140
Turns Open 3.5
BHP 0.65
2.5
0.71
2
0.76
6 5.5
4.5
4 3.5
3 2.5
2 1.5
4.5
4 3.5
3
0.82 0.87 0.93 0.98 1.04 1.10 1.16 1.21 1.28 1.36 1.43 1.50 1.56
Sheave/Mtr
RPM
Turns Open
B
665
3
B
705
2.5
B
745
1.5
A
780
5.5
A
810
5
A
845
4.5
A
880
4
A
910 945 975 1005 1035 1065 1095 1125 1150
3
A
2.5
A
2
A
1.5
A
1
C
4
C
3.5
C
3
C
2.5
2900
3000
3100
3200
3300
3400
BHP
Sheave/Mtr
RPM 685
Turns Open 2.5
BHP
Sheave/Mtr
0.71
0.76
0.82
0.87 0.92 0.98 1.03 1.09 1.16 1.22 1.29 1.36 1.43 1.50 1.57 1.63
B B A A A A A A A A A A C C C C
720
2
760
6
795
5.5
825
5
860
4
890
3.5
920 955 985 1015 1045 1075 1105 1135 1160
3 2.5
2 1.5
1 4 3.5
3 2.5
0.78
0.84
0.89
0.95 1.00 1.06 1.12 1.18 1.24 1.30 1.37 1.43 1.50 1.58 1.64 1.71
B B A A A A A A A A A C C C C C
RPM 700
Turns Open 2.5
BHP
Sheave/Mtr
740
1.5
775
5.5
810
5
845
4.5
880
4
910
3.5
940 970 1000 1030 1055 1085 1115 1140 1170
2.5
2 1.5
1 4.5
3.5
3.5
3 2.5
0.85
0.91
0.96
1.02 1.08 1.14 1.22 1.29 1.36 1.44 1.50 1.57 1.63 1.70 1.76 1.82
B B A A A A A A A A A C C C C C
RPM
Turns Open
BHP
Sheave/Mtr
720
2
755
1
790
5.5
825
4.5
860
4
890
3.5
925
3
955 985 1015 1040 1070 1095 1125 1150 1175
2.5
2 1.5
1 4 3.5
3 2.5
2
0.93
1.00
1.07
1.14 1.20 1.26 1.32 1.38 1.44 1.51 1.57 1.64 1.70 1.78 1.85 1.92
B A A A A A A A A A C C C C C C
RPM 740
Turns Open 1.5
BHP
Sheave/Mtr
775
5.5
810
5
845
4.5
875
4
905
3.5
935
3
965 995 1025 1050 1080 1105 1135 1160 1185
2 1.5
1 4.5
4 3.5
3 2.5
2
1.01
1.08
1.14
1.21 1.28 1.33 1.39 1.45 1.51 1.58 1.64 1.72 1.78 1.84 1.93 2.00
B A A A A A A A A A C C C C C E
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
755
1
790
5.5
820
5
855
4
890
3.5
915
3
945
2.5
975 1005 1035 1060 1090 1115 1140 1170 1195
2 1.5
1 4 3.5
3 3 2.5
2
1.08
1.15
1.22
1.29 1.35 1.41 1.47 1.53 1.59 1.68 1.75 1.83 1.90 1.96 2.02 2.08
A A A A A A A A A A C C C C E E
765
6
800
5
835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200
4.5
4 3.5
3 2.5
2 1.5
1 4 3.5
3 2.5
2 2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large
Motor Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Table Continued on Following Page c l i m a t e m a s t e r.c o m 63
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_L096 Blower Performance, Cont’d.
Table Continued from Previous Page
All Data is Wet Coil
SCFM
3500
3600
3700
3800
3900
4000
ESP
BHP
Sheave/Mtr
0.00
0.10
0.20
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
1.16
1.23
1.29
1.36 1.42 1.48 1.54 1.60 1.66 1.73 1.79 1.85 1.92 2.01 2.09 2.17
A A A A A A A A A C C C C E E E
RPM 780
Turns Open 5.5
BHP
Sheave/Mtr
815
5
845
4.5
880
3.5
910
3
940
2.5
970 1000 1025 1055 1080 1105 1130 1160 1185 1210
2 1.5
1 4.5
4 3.5
3 2.5
2 1.5
1.24
1.30
1.37
1.44 1.51 1.58 1.65 1.72 1.78 1.86 1.92 1.98 2.06 2.13 2.21 2.29
A A A A A A A A A C C C E E E E
RPM 795
Turns Open 5.5
BHP
Sheave/Mtr
825
4.5
860
4
890
3.5
920
3
950
2.5
980 1010 1035 1065 1090 1115 1145 1165 1190 1215
2 1.5
1 4 3.5
3 2.5
2.5
2 1.5
1.34
1.40
1.46
1.53 1.61 1.68 1.75 1.82 1.90 1.97 2.06 2.13 2.21 2.28 2.36 2.44
A A A A A A A A C C E E E E E E
RPM
Turns Open
BHP
Sheave/Mtr
820
5
850
4.5
880
3.5
910
3
940
2.5
970 1000 1025 1055 1080 1110 1135 1160 1180 1205 1230
2 1.5
1 4.5
4 3.5
3 2.5
2 1.5
1.5
1.43
1.49
1.56
1.63 1.70 1.78 1.86 1.94 2.02 2.12 2.20 2.28 2.34 2.42 2.50 2.58
A A A A A A A A E E E E E E E E
RPM 840
Turns Open 4.5
BHP
Sheave/Mtr
RPM
1.58
A
865
870
4
1.64
A
890
900
3.5
1.71
A
930
3
A
960
2.5
A
990 1020 1045 1070 1100 1125 1150 1170 1195 1220 1245
2
A
1.5
D
1
D
4
E
3.5
E
3
E
2.5
E
2.5
E
2
E
1.5
1.78 1.85 1.93 2.01 2.09 2.19 2.27 2.35 2.41 2.49 2.57 2.65
E
920 950 980 1010 1035 1060 1090 1115 1140 1160 1185 1210 1235
1
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
4 4 3 2.5
2 1.5
1 1 4 3.5
3 2.5
2 1.5
1.5
1.68
1.75
1.83
1.92 2.00 2.08 2.16 2.26 2.34 2.42 2.50 2.56 2.64 2.72 2.80
A
885
4
A
910
3.5
A
940
2.5
A D D D E E E E E E E E
970 1000 1025 1050 1080 1105 1130 1155 1175 1200 1225 1250
2.5
2 1 1 4 3.5
3 2.5
2 2 1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
64 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_L120 Blower Performance
All Data is Wet Coil
SCFM
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
ESP
BHP
Sheave/Mtr
RPM
0.00
0.10
0.20
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
0.75
0.81
0.86
0.91 0.97 1.03 1.09 1.15 1.21 1.27 1.34 1.41 1.47 1.54 1.61 1.67
B
680
B
720
B
755
B
790
B
825
B
860
A
895
A A A A A A A A A
925 955 985 1015 1045 1070 1100 1130 1155
Turns Open 5
BHP 0.82
4
0.88
3.5
0.94
3 2.5
1.5
5.5
5 4.5
4 3.5
3 2.5
2 1.5
1
0.99 1.04 1.10 1.17 1.26 1.33 1.40 1.46 1.53 1.59 1.66 1.72 1.80
Sheave/Mtr
RPM
B
700
B
735
B
775
B
805
B
840
A
875
A
905
A A A A A A A A C
940 970 1000 1025 1055 1080 1110 1135 1165
Turns Open 4.5
BHP 0.90
4
0.96
3
1.03
2.5
2 6 5.5
4.5
4.5
3.5
3 3 2.5
2 1.5
4
1.10 1.17 1.23 1.29 1.35 1.41 1.47 1.55 1.61 1.68 1.74 1.81 1.89
Sheave/Mtr
RPM
B
720
B
755
B
790
B
825
B
860
A
890
A
920
A A A A A A A A C
950 980 1010 1040 1065 1095 1120 1145 1175
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
4
B
740
3.5
0.98
1.04
1.11
1.18 1.25 1.31 1.37 1.43 1.49 1.55 1.62 1.68 1.75 1.81 1.88 1.95
B
770
3
B
805
2
B
840
1.5
5.5
A
875
A
905
5
A
935
4.5
A
4
A
3.5
A
3
A
2.5
A
2
A
1.5
A
1
A
3.5
C
965 995 1020 1050 1075 1105 1130 1155 1180
4 3 2.5
2 6 5.5
5 4 4 3 2.5
2.5
2 1.5
1 3.5
1.06
1.13
1.19
1.26 1.33 1.38 1.44 1.50 1.56 1.65 1.72 1.80 1.87 1.94 2.00 2.06
B
755
B
790
B
820
B
855
A
890
A
915
A
945
A A A A A A A C C
975 1005 1035 1060 1090 1115 1140 1165 1190
Turns Open 3.5
BHP 1.14
3
1.21
2.5
1.27
1.5
6 5 4.5
4 3.5
3 2.5
2 1.5
1 4 3
1.34 1.40 1.46 1.52 1.58 1.65 1.71 1.77 1.84 1.90 1.98 2.06 2.14
Sheave/Mtr B B B A A A A A A A A A A A C C
RPM 770
Turns Open 3
BHP
Sheave/Mtr
1.23
B
805
2.5
1.29
B
835
2
1.36
B
870
6
900
5.5
930
5
960
4.5
990 1020 1045 1070 1100 1125 1150 1175 1200
3.5
3.5
3 2.5
2 1.5
1 3.5
3
1.42 1.50 1.57 1.64 1.71 1.77 1.84 1.90 1.96 2.05 2.13 2.21 2.27
A A A A A A A A A A C C C
RPM 790
Turns Open 3
BHP
Sheave/Mtr
1.32
B
820
2.5
1.38
B
855
1.5
1.44
A
885
6
915
5.5
945
4.5
975 1005 1030 1060 1085 1110 1140 1165 1190 1210
4 3.5
3 2.5
2 1.5
1.5
4 3.5
3
1.51 1.58 1.65 1.73 1.81 1.88 1.96 2.03 2.10 2.18 2.26 2.34 2.42
A A A A A A A A A A C C C
RPM 810
Turns Open 2.5
BHP
Sheave/Mtr
1.41
B
840
2
1.47
B
870
6
1.54
A
900
5.5
930
5
960
4.5
990 1020 1045 1075 1100 1125 1150 1175 1200 1225
4 3 3 2.5
2 1.5
1 3.5
3 2.5
1.61 1.68 1.75 1.82 1.91 1.99 2.07 2.17 2.25 2.31 2.39 2.47 2.55
A A A A A A A A A A C C C
RPM
Turns Open
BHP
Sheave/Mtr
830
2
860
1.5
890
5.5
920
5
950
4.5
980 1005 1035 1060 1085 1115 1140 1160 1185 1210 1235
4 3.5
3 2.5
2 1.5
1 1 3.5
3 2.5
1.54
1.60
1.67
1.74 1.82 1.89 1.96 2.04 2.14 2.22 2.30 2.38 2.46 2.52 2.60 2.68
B A A A A A A A A A A A C C C C
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
850
2
875
6
905 935 965 995 1020 1045 1075 1100 1125 1150 1175 1195 1220 1245
5.5
5 4.5
3.5
3 2.5
2.5
2 1.5
1 3.5
3 2.5
2
1.63
1.71
1.78
1.86 1.94 2.03 2.11 2.19 2.27 2.37 2.45 2.51 2.59 2.67 2.75 2.85
A A A A A A A A A A A A C C C C
865
6
895
5.5
920 950 980 1010 1035 1060 1085 1115 1140 1160 1185 1210 1235 1260
5 4.5
4 3.5
3 2.5
2 1.5
1 1 3.5
3 2.5
2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large
Motor Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Table Continued on Following Page c l i m a t e m a s t e r.c o m 65
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
TC_L120 Blower Performance, Cont’d.
Table Continued from Previous Page
All Data is Wet Coil
SCFM
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
ESP
BHP
0.00
0.10
0.20
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
1.73
1.81
1.90
1.97 2.05 2.12 2.20 2.27 2.34 2.42 2.52 2.62 2.70 2.80 2.90
Sheave/Mtr
RPM
BHP
A
885
Turns Open 6
1.87
A
915
5.5
1.94
A A A A A A A A A C C C C
945 970 1000 1025 1055 1080 1105 1130 1155 1180 1200 1225 1250
4.5
2.02
4 4 3 2.5
2 2 1.5
1 3.5
3 2.5
2.08 2.16 2.24 2.32 2.40 2.48 2.58 2.68 2.76 2.86 2.96
2
Sheave/Mtr
RPM
A
905
Turns Open 5.5
A
935
5
A
965
4.5
A
990 1020 1045 1070 1095 1120 1145 1170 1190 1215 1240
4
A
3.5
A
3
A
2.5
A
2
A
1.5
A
1
C
3.5
C
3.5
C
3
C
2.5
BHP
Sheave/Mtr
2.00
2.07
2.16
2.23 2.31 2.41 2.49 2.57 2.66 2.74 2.84 2.94 3.02 3.15
A A A A A A A A A C C C E E
RPM 930
Turns Open 5
955
4.5
985
4
1010 1035 1065 1090 1115 1140 1160 1185 1210 1230 1255
3.5
3 2.5
2 1.5
1.5
4 3.5
3 2.5
2
BHP
Sheave/Mtr
2.14
2.22
2.32
2.40 2.48 2.56 2.65 2.74 2.82 2.92 3.00 3.10 3.18
A A A A A A A A A C E E E
RPM 950
Turns Open 4.5
975
4
1005 1030 1055 1080 1110 1135 1155 1180 1200 1225 1245
3.5
3 3 2.5
2 1.5
1 4 3 3 2.5
BHP
Sheave/Mtr
2.30
2.38
2.46
2.54 2.62 2.72 2.80 2.88 3.00 3.08 3.16 3.26
A A A A A A A A D E E E
RPM 970
Turns Open 4.5
995
4
1020 1045 1070 1100 1125 1145 1170 1195 1215 1240
3.5
3 2.5
2 1.5
1.5
1 3.5
3 2.5
BHP
Sheave/Mtr
RPM
Turns Open
2.39
A
2.45
A
2.54
A
2.63 2.72 2.83 2.92 3.00 3.10 3.18 3.28 3.38
A A A A D D E E E
980 1000 1025 1050 1075 1105 1130 1150 1175 1195 1220 1245
4 3.5
3.5
3 2.5
2 1.5
1 1 3.5
3 2.5
BHP
Sheave/Mtr
2.46
2.52
2.62
2.72 2.82 2.92 3.02 3.12 3.22 3.32 3.40 3.50
A A A A A A D D E E E E
RPM 985 1005 1030 1055 1080 1105 1130 1155 1180 1205 1225 1250
Turns Open 4 3.5
3 2.5
2 1.5
1.5
1 4 3.5
2.5
2.5
BHP
Sheave/Mtr
2.57
2.64
2.74
2.84 2.94 3.04 3.14 3.24 3.32 3.42 3.52 3.60
A A A A A D D D E E E E
RPM 990 1010 1035 1060 1085 1110 1135 1160 1180 1205 1230 1250
Turns Open 4 3.5
3.
2.5
2 1.5
1 1 3.5
3 2.5
2
BHP
Sheave/Mtr
2.68
2.78
2.88
3.00 3.06 3.16 3.26 3.36 3.44 3.54 3.64 3.75
A A A D D D D E E E E E
RPM 995 1020 1045 1070 1090 1115 1140 1165 1185 1210 1235 1255
Turns Open 3.5
3 3 2.5
1.5
1.5
1 4 3.5
3 2.5
2
BHP
Sheave/Mtr
2.82
2.92
3.00
3.10 3.20 3.28 3.38 3.48 3.56 3.66 3.74
A A D D D D D E E E E
RPM 1005 1030 1050 1075 1100 1120 1145 1170 1190 1215 1235
Turns Open 3.5
3 2.5
2 1.5
1 1 3.5
3 2.5
2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
66 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV160 Standard Unit
All Data is Wet Coil
SCFM
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
0.69
0.78
0.86
0.95
1.02
1.11
1.21
1.32
1.41
1.50
1.57
1.64
1.72
1.80
B B B B A A A A A A A C C C
547 594 640 685 725 765 805 845 880 915 945 975 1005 1030
5.5
4 3 1.5
6 5 4 3.5
2.5
2 1 3.5
3 2.5
0.75
0.83
0.92
1.01
1.11
1.21
1.31
1.41
1.51
1.60
1.68
1.76
1.85
1.94
B B B B A A A A A A A C C C
563 609 655 695 735 775 815 855 890 925 955 985 1015 1045
5 3.5
2.5
1.5
5.5
5 4 3 2.5
1.5
1 3.5
2.5
2
0.75
0.85
0.95
1.03
1.11
1.19
1.30
1.40
1.50
1.60
1.70
1.78
1.89
2.00
2.10
B B B B B A A A A A A C C C C
526 573 625 665 705 745 785 825 860 895 930 960 995 1025 1050
6 4.5
3 2.5
1 5.5
4.5
3.5
3 2.5
1.5
4 3 2.5
2
0.83
0.94
1.03
1.12
1.20
1.30
1.40
1.53
1.63
1.73
1.82
1.92
2.00
2.12
2.22
B B B B A A A A A A A C C C C
542 594 640 680 720 760 795 835 870 905 935 970 1000 1030 1055
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 5.5
5.5
4 3 2 6 5 4.5
3.5
3 2 1 3.5
3 2 1.5
0.93
1.02
1.11
1.20
1.31
1.41
1.52
1.64
1.76
1.85
1.95
2.03
2.12
2.24
2.36
B B B B A A A A A A A C C C C
563 609 650 690 735 770 805 840 880 910 945 975 1005 1035 1065
5 3.5
2.5
1.5
5.5
5 4 3.5
2.5
2 1 3.5
3 2 1.5
0.93
1.02
1.10
1.20
1.29
1.39
1.50
1.61
1.72
1.83
1.94
2.06
2.15
2.26
2.38
2.50
B B B B B A A A A A A A C C C C
542 583 625 665 705 745 780 815 850 885 920 955 985 1015 1045 1075
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 4.5
4.5
3 2 1 5.5
4.5
4 3 2.5
1.5
1 3 2.5
2 1.5
1.03
1.10
1.19
1.29
1.39
1.50
1.59
1.70
1.80
1.92
2.03
2.16
2.26
2.38
2.50
2.62
B B B B B A A A A A A C C C C C
563 599 640 680 720 760 790 825 860 895 925 960 990 1020 1050 1080
5 4 3 2 1 5 4.5
3.5
3 2.5
1.5
4 3 2.5
1.5
1
1.12
1.19
1.28
1.39
1.50
1.61
1.72
1.84
1.93
2.06
2.17
2.29
2.40
2.54
2.69
2.83
B B B B A A A A A A A C C C C C
583 620 655 695 735 770 805 840 870 905 935 970 1000 1030 1060 1090
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
3.5
2.5
1.5
5.5
5 4 3.5
2.5
2 1.5
3.5
3 2 1.5
1
1.17
1.28
1.39
1.49
1.60
1.70
1.81
1.90
2.02
2.14
2.28
2.40
2.52
2.67
2.81
2.96
B B B B A A A A A A A C C C C C
588 630 670 710 750 780 815 845 880 910 945 975 1005 1035 1065 1095
4 3 2 1 5.5
4.5
4 3 2.5
2 1 3.5
2.5
2 1.5
1
1.25
1.40
1.51
1.61
1.73
1.84
1.94
2.05
2.18
2.30
2.42
2.54
2.67
2.79
2.94
3.08
B B B A A A A A A A A C C C C E
604 645 685 720 760 795 825 860 895 925 955 985 1015 1040 1070 1100
1 4
BHP
Sheave/Mtr
RPM
Turns Open 3.5
2.5
1.5
6 5 4.5
3.5
3 2 1.5
1 3 2.5
2 1.5
1.40
1.51
1.62
1.75
1.86
1.98
2.09
2.20
2.34
2.49
2.63
2.78
2.92
3.06
3.18
B B B A A A A A A A C C C E E
625 660 695 735 770 805 840 875 905 935 965 995 1025 1055 1080
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 2.5
2.5
1.5
5.5
5 4 3.5
2.5
2 1.5
4 3 2 1.5
1
1.55
1.68
1.79
1.90
2.04
2.18
2.32
2.44
2.56
2.68
2.80
2.92
3.07
3.19
3.33
B B B A A A A A A A C C E E E
640 680 715 750 785 820 855 885 915 945 975 1005 1035 1060 1090
3 2 1 5 4.5
3.5
3 2.5
1.5
1 3.5
2.5
2 1.5
1
1.73
1.84
1.94
2.06
2.20
2.34
2.46
2.58
2.70
2.82
2.94
3.07
3.19
3.34
3.46
B B A A A A A A A A C E E E E
665 700 730 765 800 835 865 895 925 955 985 1015 1040 1070 1095
1
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 1.5
1.5
5.5
5 4 3.5
3 2 1.5
1 3 2.5
2 1.5
1.87
1.98
2.08
2.20
2.34
2.48
2.62
2.74
2.86
2.96
3.08
3.24
3.38
3.55
B B A A A A A A A C E E E E
685 715 745 775 810 845 880 910 940 965 995 1025 1050 1080
2 1 5.5
4.5
4 3 2.5
2 1 4 3 2.5
2 1
2.03
2.13
2.22
2.36
2.50
2.62
2.76
2.88
3.00
3.12
3.22
3.37
3.49
3.61
B A A A A A A A D E E E E E
705 730 755 790 825 855 890 920 950 980 1005 1035 1060 1085
6 5 4.5
3.5
3 2.5
1.5
1 3.5
3 2 1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressure, contact your local representative.
Performance data does not include drive losses and is based on seal level conditions.
Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
c l i m a t e m a s t e r.c o m 67
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV192 Standard Unit
All Data is Wet Coil
SCFM
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
7400
7600
7800
8000
7000
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
ESP
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
0.00
A
835
A
865
4 3.5
2.70
2.85
A
850
A
885
4 3
2.88
3.02
A
870
D
900
3.5
3
3.07
3.22
D
890
D
920
3 2.5
3.34
3.49
A
760
A
795
5.5
5
2.02
2.16
A
780
A
815
5 4.5
2.18
2.32
A
795
A
830
5 4.5
2.36
2.50
A
815
A
850
4.5
4
2.54
2.66
B
680
B
720
4 2.5
1.40
1.51
B
700
B
740
3.5
2
1.52
1.63
B
720
A
760
3 6
1.67
1.78
B
740
A
775
2.5
5.5
1.83
1.94
0.10
0.20
0.98
1.07
B
615
B
660
5.5
4.5
1.07
1.18
B
635
B
680
5 4
1.18
1.28
B
660
B
700
4.5
3.5
1.29
1.39
D
905
D
935
3 2
3.58
3.75
D
925
2.5
D
955
1.5
3.22
D
880
3.5
3.41
D
895
3
2.76
A
840
4
2.94
A
860
4
2.40
A
800
5
2.58
A
820
4.5
2.06
A
765
5.5
2.22
A
780
5.5
1.70
B
720
3
1.88
B
745
2.5
1.41
B
680
4
1.56
B
700
3.5
1.19
B
640
5
1.30
B
660
4.5
0.99
B
594
6
1.09
B
620
5.5
A
755
A
790
6 5
1.62
1.74
A
775
A
810
5.5
5
1.73
1.84
A
790
A
825
5 4.5
1.89
2.00
A
810
A
845
5 4
2.06
2.17
0.30
0.40
1.16
1.24
B
700
B
740
3 2
1.27
1.37
B
720
A
760
2.5
5.5
1.36
1.48
B
735
A
775
2 5.5
1.48
1.59
A
830
A
865
4.5
3.5
2.28
2.42
A
845
A
880
4 3.5
2.46
2.58
A
865
A
895
3.5
3
2.62
2.74
A
880
A
910
3.5
2.5
2.80
2.92
A
900
A
930
3 2
2.99
3.14
A
915
D
945
3 2
3.16
3.31
A
825
A
860
4.5
3.5
1.85
1.95
A
845
A
875
4 3
1.95
2.06
A
860
A
890
3.5
3
2.12
2.24
A
880
A
910
3 2.5
2.30
2.44
0.50
0.60
1.34
1.47
A
775
A
815
5.5
4
1.49
1.60
A
795
A
830
5 3.5
1.59
1.70
A
810
A
845
4.5
3.5
1.70
1.80
A
895
A
925
3 2.5
2.54
2.66
A
910
A
940
2.5
2
2.70
2.82
A
925
A
955
2.5
1.5
2.86
3.00
A
940
2
3.04
D
960
1.5
3.28
D D E E E E E E E E
970 1000 1030 1055 1085 1110 1135 1160 1190 1215
1.5
3.14
D
985
1
3.42
0.70
0.80
1.59
1.69
A
855
A
890
3.5
3
1.73
1.82
A
870
A
900
3.5
3
1.82
1.93
A
880
A
915
3 2.5
1.92
2.03
A
895
A
925
3 2.5
2.08
2.18
A
910
A
940
2.5
2
2.18
2.32
A
920
A
955
2.5
1.5
2.36
2.48
A
940
2 1.5
2.58
2.73
A
955
1.5
2.78
1 5.5
2.60
2.74
5 4.5
2.89
3.01
4 3
3.15
3.30
3
3.42
A C C C E E E E
970 1000 1030 1060 1085 1115 1145 1170
A
985
1
2.90
A C E E E E E E E
970 1000 1030 1055 1085 1110 1140 1165 1190
1.5
6
2.94
3.07
5 4.5
3.19
3.34
4 3.5
3.46
3.60
3 2.5
3.74
3.88
2
4.02
A E E E E E E E E
985 1015 1040 1070 1095 1125 1150 1175 1200
1 5.5
3.10
3.27
1 5
3.27
3.39
E
1015
E
1040
5.5
5
3.54
3.66
0.90
1.00
1.78
1.87
A
920
C
1015
A
955
2.5
1.5
1.92
2.00
A
935
2
2.02
A
945
2
2.16
A
960
1.5
2.31
6 5
2.87
3.02
E
1045
5.5
5
3.04
3.16
5 4.5
3.41
3.58
1.10
1.20
1.96
2.06
1.30
1.40
2.18
2.30
1.50
2.42
A C C C C
985 1015 1045 1075 1105
1 5.5
2.10
2.22
4.5
4
3.14
3.28
E
1070
E
1100
4.5
4
3.31
3.43
4 3.5
3.72
3.85
5 4.5
2.32
2.44
3.5
3
3.40
3.54
E
1125
E
1155
3.5
3
3.58
3.72
3 2.5
3.97
4.11
4
2.56
A A C C C C
965 1000 1030 1055 1085 1115
1.5
2.14
A
980
1
2.26
A C C C C C
990 1020 1050 1080 1110 1140
1
2.42
A C C C C C E
975 1005 1035 1065 1095 1120 1150
1.5
5.5
2.44
2.57
5 4.5
2.72
2.86
4 3.5
3.00
3.15
3
3.27
A C C C E E E
985 1015 1045 1075 1105 1135 1160
4.5
4
3.54
3.66
E
1070
E
1095
4.5
4
3.81
3.93
1 5
2.24
2.36
C
1010
C
1040
5.5
5
2.38
2.50
5.5
5
2.57
2.71
3.5
3
3.78
3.96
E
1120
D
950
2
3.63
1
3.78
5.5
5
3.96
4.12
4.5
4
4.28
4.44
3.5
3
4.63
4.76
D
965
1.5
3.92
1
4.06
5.5
5
4.26
4.42
4.5
4
4.58
4.74
3.5
4.90
D E E E E E E
985 1010 1040 1065 1090 1115 1140
1 5.5
5 4.5
4 3.5
3
2.5
4.92
D E E E E E E E
995 1025 1050 1075 1100 1130 1150 1175
3 2.5
E
1150
3.5
3
4.06
4.22
4.5
4
2.48
2.60
C
1070
C
1100
4.5
4
2.62
2.74
4 3.5
2.86
2.98
2.5
2
4.12
4.28
E
1175
E
1200
2.5
2
4.38
4.54
3.5
2.72
C
1130
3.5
2.87
3
3.12
2.5
3.66
E
1180
2.5
3.86
2
4.23
2
4.44
E
1225
1.5
4.70
D E E E E E E E E E E
975 1005 1030 1055 1085 1110 1135 1160 1185 1210 1235
D
930
D
960
2.5
1.5
3.36
3.50
1.5
5.5
3.45
3.61
5 4.5
3.75
3.92
4 3.5
4.06
4.20
3 2.5
4.36
4.52
2.5
2
4.68
4.81
1.5
4.97
D E E E E E E E E E E
990 1020 1045 1075 1100 1125 1150 1175 1200 1220 1245
1.5
1.5
1 5.5
3.63
3.82
5 4.5
3.98
4.14
4 3.5
4.34
4.50
3 2.5
4.66
4.78
2
4.94
D E E E E E E E E E
980 1005 1035 1060 1085 1115 1140 1165 1185 1210
2 2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require fi eld selection.
For applications requiring higher static pressure, contact your local representative.
Performance data does not include drive losses and is based on seal level conditions.
68 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV240 Standard Unit
All Data is Wet Coil
SCFM ESP
BHP
6000
Sheave/Mtr
RPM
Turns
Open
6200
6400
BHP
Sheave/Mtr
RPM
Turns
Open
BHP
Sheave/Mtr
RPM
Turns
Open
BHP
0.00
0.10
0.20
1.82
B
0.30
1.78
B
775
5.5
0.40
1.89
B
810
4.5
0.50
2.00
B
845
4
0.60
2.12
A
880
6
0.70
2.24
A
910
5
0.80
2.36
A
940
4.5
0.90
2.48
A
970
3.5
1.00
2.60
A
1000 1030 1060 1085
3
1.10
2.74
A
2.5
1.20
2.89
A
1.5
1.30
3.01
A
1
1.40
3.15
C
1115
3.5
1.50
3.30
C
1145
3
755 790 825 860 895 925 955 985 1015 1040 1070 1095 1125 1150
6
2.00
B
775
5.5
1.93
B
5
2.14
B
810
4.5
2.04
B
4.5
2.26
B
840
4
2.15
B
3.5
2.40
B
875
3
2.30
A
5.5
2.52
A
905
5.5
2.44
A
5
2.64
A
935
4.5
2.58
A
4
2.76
A
965
4
2.73
A
3.5
2.88
A
995
3
2.87
A
2.5
3.02
A
2.5
2.99
A
2
3.14
A
2
3.14
A
1.5
3.28
A
1
3.26
C
4
3.40
C
1025 1050 1080 1105
4
3.40
C
3.5
3.56
C
1135
3
3.52
C
3
3.70
C
1160
2.5
6600
6800
Sheave/Mtr
RPM
Turns
Open
BHP
Sheave/Mtr
RPM
2.02
2.16
2.30
2.42
2.56
2.68
2.80
2.92
3.05
3.17
3.29
3.43
3.55
3.71
3.85
B
755
6
B
790
5.5
B
825
4.5
B
855
3.5
A
890
6
A
920
5
A
950
4
A
980
3.5
A
3
A
2
A
1.5
A
1010 1035 1060 1090
1
C
1115
3.5
C
1145
3
C
1170
2.5
2.18
2.32
2.46
2.58
2.70
2.84
2.94
3.06
3.21
3.35
3.52
3.66
3.82
3.94
4.06
B B B B A A A A A A A C C C C
770 805 840 870 900 935 960 990 1020 1045 1075 1100 1130 1155 1180
7000
7200
Turns
Open
BHP
Sheave/Mtr
RPM
Turns
Open
BHP
Sheave/Mtr
RPM
Turns
Open
5.5
5 4 3 5.5
4.5
4 3 2.5
2 1 4 3.5
2.5
2
2.22
2.34
2.48
2.62
2.74
2.86
2.98
3.10
3.22
3.34
3.49
3.61
3.73
3.90
4.06
4.22
B B B B A A A A A A A A C C C C
755
6
2.38
B
2.52
B
2.64
B
2.78
B
2.92
A
3.06
A
3.21
A
3.35
A
3.47
A
3.62
A
3.74
A
3.88
C
4.00
C
4.16
C
4.32
C
4.48
C
770 805 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200
5.5
785
5.5
5
820
4.5
4
855
3.5
3.5
885
6
5.5
915
5
4.5
945
4.5
4
975
3.5
3
1005 1030 1060 1085
3
2.5
2.5
2
1.5
1.5
1
4
1110
3.5
3.5
1140
3
3
1165
2.5
2
1190
2
1.5
BHP
Sheave/Mtr
2.56
2.68
2.82
2.95
3.09
3.24
3.38
3.53
3.67
3.84
3.98
4.12
4.26
4.42
4.58
4.74
B B B A A A A A A A A C C C C C
7400
RPM 790 820 855 885 915 945 975 1005 1030 1060 1085 1110 1135 1160 1185 1210
Turns
Open
5 4.5
3.5
6 5 4.5
3.5
3 2.5
1.5
1 3.5
3 2.5
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large
Motor Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
2 1.5
Table Continued on Following Page c l i m a t e m a s t e r.c o m 69
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV240 Standard Unit
Table Continued from Previous Page
All Data is Wet Coil
SCFM ESP
BHP
7600
Sheave/Mtr
RPM
Turns
Open
7800
8000
BHP
Sheave/Mtr
RPM
Turns
Open
BHP
Sheave/Mtr
RPM
0.00
2.74
B
810
4.5
2.98
B
830
4
0.10
2.86
B
840
4
3.13
B
860
3.5
0.20
2.98
B
870
3.5
3.25
A
885
6
0.30
3.12
A
900
5.5
3.39
A
915
5
0.40
3.26
A
930
4.5
3.54
A
945
4.5
0.50
3.41
A
960
4
3.68
A
975
3.5
0.60
3.55
A
990
3
3.83
A
3
0.70
3.70
A
1015 1045 1070 1095 1125
2.5
3.99
A
2.5
0.80
3.89
A
2
4.15
A
1.5
0.90
4.05
A
1.5
4.34
C
1005 1030 1055 1085
0
1.00
4.21
C
4
4.50
C
1110
3.5
1.10
4.40
C
3.5
4.66
C
1135
3
1.20
4.53
C
1145
3
4.82
C
1160
2.5
1.30
4.69
C
1170
2.5
4.95
C
5.11
E
5.27
E
1180 1205 1230
2
1.40
4.85
C
1.50
5.01
E
1195 1220
2
1.5
1.5
1
3.18
3.30
3.44
3.61
3.78
3.94
4.10
4.29
4.45
4.61
4.77
4.93
5.09
5.25
5.38
5.54
B B A A A A A A A C C C E E E E
850 875 900 930 960 990 1015 1045 1070 1095 1120 1145 1170 1195 1215 1240
8200
Turns
Open
BHP
Sheave/Mtr
RPM
7000
BHP
4 3.5
5.5
4.5
4 3.5
2.5
2 1.5
4 3.5
3 2.5
2 1.5
3.35
3.48
3.65
3.79
3.96
4.13
4.27
4.44
4.58
4.72
4.88
5.08
5.24
5.44
5.64
B A A A A A A A A C C E E E E
865 890 920 945 975 1005 1030 1060 1085 1110 1135 1160 1180 1205 1230
3.5
5.5
5 4.5
3.5
3 2.5
1.5
1 3.5
3 2.5
2 1.5
1
3.62
3.74
3.89
4.03
4.18
4.33
4.49
4.65
4.81
4.97
5.16
5.36
5.56
5.72
5.92
A A A A A A A A C C E E E E E
880 905 935 965 995 1020 1045 1070 1095 1120 1145 1170 1195 1215 1240
8400
Sheave/Mtr
RPM
Turns
Open
6 5.5
4.5
4 3 2.5
2 1.5
4 3.5
3 2.5
2 1.5
1
8600
BHP
Sheave/Mtr
RPM
Turns
Open
3.81
A
5.5
3.98
A
5
4.12
A
4
4.29
A
3.5
4.46
A
3
4.62
A
2
4.78
A
1.5
4.94
A
1
5.10
E
3.5
5.28
E
3
5.48
E
2.5
5.64
E
2
5.84
E
1.5
6.04
E
1.5
BHP
Sheave/Mtr
4.06
4.22
4.41
4.57
4.73
4.92
5.08
5.24
5.40
5.60
5.76
5.96
6.16
6.32
A A A A A A D E E E E E E E
8800
RPM 915 940 970 995 1020 1050 1075 1100 1125 1150 1170 1195 1220 1240
Turns
Open
5 4.5
3.5
3 2.5
1.5
1 4 3 3 2.5
2 1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large
Motor Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
6.20
E
895 925 950 980 1010 1035 1060 1085 1110 1135 1160 1180 1205 1230 1250
1
1
70
Table Continued on Following Page
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV240 Standard Unit
Table Continued from Previous Page
All Data is Wet Coil
SCFM ESP
BHP
Sheave/Mtr
9000
RPM
9200
Turns
Open
BHP
Sheave/Mtr
RPM
Turns
Open
BHP
0.00
4.38
A
935
4.5
4.65
A
955
4
0.10
4.54
A
960
4
4.76
A
975
3.5
0.20
4.70
A
985
3.5
4.90
A
3
0.30
4.86
A
1010 1035 1060 1085
3
5.08
D
2.5
0.40
5.02
D
2
5.26
D
1.5
0.50
5.18
D
1.5
5.44
D
1
0.60
5.34
D
1
5.62
E
1000 1025 1050 1075 1100
4
0.70
5.50
E
1110
3.5
5.80
E
1125
3.5
0.80
5.68
E
1135
3
6.00
E
1150
2.5
0.90
5.88
E
1160
2.5
6.16
E
1170
2.5
1.00
6.08
E
2
6.36
E
6.56
E
6.72
E
1195 1220 1240
2
1.10
6.24
E
1.5
1.5
1.20
6.44
E
1
1
1.30
6.60
E
1185 1205 1230 1250
1
9400
9600
Sheave/Mtr
RPM
Turns
Open
BHP
Sheave/Mtr
RPM
4.83
4.94
5.12
5.32
5.52
5.72
5.92
6.12
6.32
6.48
6.68
6.88
A
970
3.5
5.10
D
985
A
990
3.5
5.24
D
D
1015 1040 1065 1090
2.5
5.44
D
D
2
5.64
D
D
1.5
5.84
D
D
1
6.04
E
1005 1030 1055 1080 1105
E
1115
3.5
6.24
E
1130
E
1140
3
6.40
E
1150
E
1165
2.5
6.60
E
E
1185 1210 1235
2
6.80
E
E
1.5
6.96
E
E
1
7.16
E
1175 1200 1220 1245
Turns
Open
3.5
3 2 1.5
1 4 3.5
3 2.5
2 1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressure, contact your local representative. Performance data does not include drive losses and is based on seal level conditions.
Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
1.40
1.50
c l i m a t e m a s t e r.c o m 71
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Blower Performance Data – TC_LV300 Standard Unit
All Data is Wet Coil
SCFM ESP 0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
BHP 2.69
2.84
2.96
3.11
3.27
3.45
3.60
3.78
3.96
4.08
4.23
4.38
4.53
4.69
4.86
5.03
7500
7800
8100
8400
8700
9000
9300
9600
9900
10200
10500
10800
Sheave/Mtr
RPM
Turns Open
BHP
B
890
4.5
B
925
B
955
B A A A A A A A A A C C C
990 1020 1050 1075 1105 1135 1155 1180 1205 1230 1255 1275 1295
3.5
2.5
2 5.5
5 4.5
3.5
3 3 2 1.5
1 3.5
3 2.5
2.87
3.04
3.18
3.36
3.54
3.72
3.87
4.05
4.20
4.35
4.50
4.65
4.80
4.97
5.14
5.30
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 2.5
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open 5.5
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
Turns Open
BHP
Sheave/Mtr
RPM
7000
B
910
B
945
B A A A A A A A A A C C C C
975 1010 1040 1070 1095 1125 1150 1175 1200 1225 1250 1270 1290 1310
4 3 2 5.5
5 4.5
4 3 2.5
2.5
1.5
1 4 3 2.5
2.5
3.10
3.26
3.42
3.60
3.78
3.96
4.14
4.34
4.52
4.70
4.88
5.06
5.21
5.35
5.53
5.68
B
935
B
965
B A A A A A A A A C C C C C
995 1025 1055 1085 1115 1145 1170 1195 1220 1245 1265 1285 1310 1330
3.5
2.5
1.5
5.5
5 4 3.5
3 2.5
2 1.5
4 3.5
3 2.5
2
3.36
3.52
3.74
3.92
4.14
4.36
4.57
4.75
4.93
5.11
5.29
5.47
5.62
5.80
5.94
6.12
B
955
3
3.60
B
975
3.90
A
1000
6
4.34
A
1020
4.64
B
985
2
3.79
A
1005
6
4.12
A
1030
5.5
4.56
A
1050
5
4.85
A
1020
5.5
4.00
A
1035
5
4.30
A
4.5
4.74
A
1075
4.5
5.03
A
1045
5
4.22
A
1065
4.5
4.51
A
1055 1085
4
4.96
A
1105
3.5
5.25
A
1075
4.5
4.43
A
1095
4
4.73
A
1115
3.5
5.14
A
1130
3
5.46
A
1105
3.5
4.65
A
1125
3
4.91
A
1140
3
5.35
A
1160
2.5
5.67
A
1135
3
4.83
A
1150
3
5.09
A
1165
2.5
5.53
A
1185
2
5.88
A
1160
2.5
5.01
A
1175
2
5.30
A
1195
1.5
5.71
A
1210
1.5
6.13
A
1185
2
5.19
A
1200
1.5
5.48
A
1220
1
5.89
A
1235
1
6.34
A
1210
1.5
5.37
A
1225
1
5.66
C
1245
3.5
6.08
C
1260
3
6.52
A
1235
1
5.55
C
1250
3.5
5.89
C
1270
3
6.29
C
1285
3
6.66
C
1260
3.5
5.76
C
1275
3
6.08
C
1290
2.5
6.50
C
1310
2.5
6.84
2
7.02
1.5
7.16
A A A A A A A A C C C C C C
1040 1070 1095 1125 1150 1175 1200 1230 1255 1280 1300 1325 1350 1370
5 4.5
4 3.5
3 2 1.5
1 3.5
3 2.5
2 1.5
4.93
5.15
5.33
5.53
5.78
5.99
6.20
6.41
6.62
6.83
7.04
7.21
7.42
A A A A A A A C C C C C C
1060 1090 1115 1140 1170 1195 1220 1245 1270 1295 1320 1340 1365
1.5
4.5
4 3.5
3 2.5
1.5
1.5
3.5
3 2.5
2 2
5.36
5.57
5.77
5.95
6.17
6.35
6.53
6.74
6.94
7.18
7.42
7.61
A A A A A A C C C C C E
1085 1110 1135 1160 1190 1215 1240 1265 1285 1310 1335 1355
4 3.5
3 2.5
2 1.5
4 3 3 2.5
2 1.5
5.52
5.75
5.99
6.23
6.47
6.71
6.95
7.19
7.43
7.62
7.86
8.10
A A A A A A C C C E E E
1100 1130 1155 1180 1205 1230 1255 1280 1305 1325 1350 1375
1 4 3 2.5
2 1.5
1 3.5
3 2.5
2 1.5
6.00
6.24
6.48
6.72
6.96
7.20
7.39
7.63
7.87
8.11
8.30
A A A A A C C E E E E
1125 1150 1175 1200 1225 1250 1270 1295 1320 1345 1365
3.5
3 5 1.5
1 3.5
3.5
2.5
2 1.5
1.5
C
1280
3
5.97
C
1300
2.5
6.32
C
1315
2
6.67
C
1330
C
1305
2.5
6.14
C
1320
2
6.56
C
1340
1.5
6.88
C
1355
1
C
1325
2
6.35
C
1345
1.5
6.76
C
1360
1.5
7.05
C
1375
1
C
1350
1.5
6.56
C
1370
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressure, contact your local representative.
Performance data does not include drive losses and is based on seal level conditions.
Do not operate in black regions. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
72 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Unit Starting and Operating Conditions
Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Commissioning Conditions
Consult Table 9 for the particular model. Starting conditions vary depending upon model and are based upon the following notes:
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to ensure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table 8 for operating limits.
Notes:
1. Conditions in Table 9 are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.
2. Voltage utilization range complies with AHRI Standard
110.
Table 9a: Operating Limits
Operating Limits
Cooling
TC_LH/TC_LV
Heating
Air Limits
Min. ambient air, DB
Related ambient air, DB
Max. ambient air, DB
45°F [7°C]
80.6°F [27°C]
110°F [43°C]
Min. entering air, DW/WB 60/50°F [16/10°C]
Rated entering air, DB/WB 80.6/66.2°F [27/19°C]
Max. entering air, DB/WB
Water Limits
95/75°F [35/24°C]
Min. entering water
Normal entering water
Max. entering water
Normal Water Flow
30°F [-1°C]
50-110°F [10-43°C]
39°F [4°C]
68°F [20°C]
85°F [29°C]
50°F [10°C]
68°F [20°C]
80°F [27°C]
20°F [-6.7°C]
30-70°F [-1 to 21°C]
120°F [49°C] 90°F [32°C]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Table 9b: Commissioning Limits
Commissioning Limits
Cooling
TC_LH/TC_LV
Heating
Air Limits
Min. ambient air, DB
Related ambient air, DB
Max. ambient air, DB
45°F [7°C]
80.6°F [27°C]
110°F [43°C]
Min. entering air, DW/WB 50/45°F [10/7°C]
Rated entering air, DB/WB 80.6/66.2°F [27/19°C]
Max. entering air, DB/WB
Water Limits
110/83°F [43/28°C]
Min. entering water 30°F [-1°C]
Normal entering water
Max. entering water
Normal Water Flow
39°F [4°C]
68°F [20°C]
85°F [29°C]
40°F [4.5°C]
68°F [20°C]
80°F [27°C]
20°F [-6.7°C]
50-110°F [10-43°C] 30-70°F [-1 to 21°C]
120°F [49°C] 90°F [32°C]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW] c l i m a t e m a s t e r.c o m 73
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Piping System Cleaning and Flushing
Piping System Cleaning and Flushing
Cleaning and flushing the WLHP piping system is the single most important step to ensure proper start-up and continued efficient operation of the system.
DO NOT use “Stop Leak” or similar chemical agent in this system. Addition of chemicals of this type to the loop water will foul the heat exchanger and inhibit unit operation.
Follow the instructions below to properly clean and flush the system:
1. Ensure that electrical power to the unit is disconnected.
2. Install the system with the supply hose connected directly to the return riser valve. Use a single length of flexible hose.
3. Fill the system with water. DO NOT allow system to overflow. Bleed all air from the system. Pressurize and check the system for leaks and repair as appropriate.
Models with Waterside Economizer also manually open economizer valve and coil air vents (2) to bleed air from coil.
4. Verify that all strainers are in place (ClimateMaster recommends a strainer with a #20 stainless steel wire mesh). Start the pumps, and systematically check each vent to ensure that all air is bled from the system.
5. Verify that make-up water is available. Adjust makeup water as required to replace the air which was bled from the system. Check and adjust the water/air level in the expansion tank.
6. Set the boiler to raise the loop temperature to approximately 86°F [30°C]. Open a drain at the lowest point in the system. Adjust the make-up water replacement rate to equal the rate of bleed.
7. Refill the system and add trisodium phosphate in a proportion of approximately 150 gallons [1/2 kg per
750 l] of water (or other equivalent approved cleaning agent). Reset the boiler to raise the loop temperature to 100°F [38°C]. Circulate the solution for a minimum of 8 to 24 hours. At the end of this period, shut off the circulating pump and drain the solution. Repeat system cleaning if desired.
8. When the cleaning process is complete, remove the short-circuited hoses. Reconnect the hoses to the proper supply, and return the connections to each of the units. Refill the system and bleed off all air.
9. Test the system pH with litmus paper. The system water should be in the range of pH 6.0 - 8.5 (see table 3). Add chemicals, as appropriate to maintain neutral pH levels.
10. When the system is successfully cleaned, flushed, refilled and bled, check the main system panels, safety cutouts and alarms. Set the controls to properly maintain loop temperatures.
Note: The manufacturer strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any finishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system.
The manufacturer will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.
74 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Unit Starting and Operating Conditions
� WARNING!
�
WARNING!
Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.
BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT
� Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/ breakers are properly sized. Verify that low voltage wiring is complete.
� Unit control transformer: Ensure that transformer has the properly selected voltage tap. Commercial
380-420V units are factory wired for 380V operation unless specified otherwise.
� Balancing/shutoff valves: Ensure that all isolation valves are open (after system flushing - see System
Checkout) and water control valves are wired.
� Entering water and air: Ensure that entering water and air temperatures are within operating limits of
Table 9a.
� Low water temperature cutout: Verify that low water temperature cut-out on the CXM/DXM control is properly set.
� Unit blower wheel: Manually rotate blower wheel to verify free rotation and ensure that all blower wheels are secured to the blower motor shaft and centered in housing.
� Blower motor: Verify motor bolts are tight. DO NOT oil motors upon start-up. Fan motors are pre-oiled at the factory.
� Check shaft pillow blocks, sheave and pulley are tight
� Verify sheave has been set to turns in design requirement. Record turns on start up log sheet.
� Verify belt is straight and proper tension
� Condensate line: Verify that condensate line is open, trapped, vented and properly pitched toward drain.
� Water flow balancing: Record inlet and outlet water temperatures for each heat pump upon startup.
This check can eliminate nuisance trip outs and high velocity water flow that could erode heat exchangers.
� Unit air coil and filters: Ensure that filter is clean and accessible. Clean air coil of all manufacturing oils.
� Unit controls: Verify that CXM or DXM field selection options are properly set.
SYSTEM CHECKOUT
� System water temperature: Check water temperature for proper range and also verify heating and cooling setpoints for proper operation.
� System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fittings
(see table 3).
� System flushing: Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger, water valves and other components. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion.
� Cooling tower/boiler: Check equipment for proper
�
�
�
�
� setpoints and operation.
Standby pumps: Verify that the standby pump is properly installed and in operating condition.
System controls: Verify that system controls function and operate in the proper sequence.
Low water temperature cutout: Verify that low water temperature cut-out controls are provided for the outdoor portion of the loop. Otherwise, operating problems may occur.
System control center: Verify that the control center and alarm panel have appropriate setpoints and are operating as designed.
Miscellaneous: Note any questionable aspects of the installation.
� CAUTION!
�
CAUTION!
Verify that ALL water control valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
� CAUTION!
�
CAUTION!
To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.
NOTICE! Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise, and could cause component failure due to added vibration.
c l i m a t e m a s t e r.c o m 75
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Unit Start-Up Procedure
1. Turn the thermostat fan position to “ON”. Blower should start.
2. Balance air flow at registers.
3. Adjust all valves to their full open positions. Turn on the line power to all heat pumps.
4. Room temperature should be within the minimummaximum ranges of table 9a. During start-up checks, loop water temperature entering the heat pump should be between 60°F [16°C] and 95°F [35°C].
5. Two factors determine the operating limits of
ClimateMaster heat pumps, (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal level to ensure proper unit operation.
a. Adjust the unit thermostat to the warmest setting.
Place the thermostat mode switch in the “COOL” position. Slowly reduce thermostat setting until the compressor activates.
b. Check for cool air delivery at the unit grille within a few minutes after the unit has begun to operate.
c. Note: Units have a five minute time delay in the control circuit that can be eliminated on the CXM/
DXM control board as shown below in Figure 22.
See controls description for details.
d. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using the P/T plugs and comparing to table 10.
e. Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is filled to provide a water seal. Check the temperature of both entering and leaving water. If temperature is within range table, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to tables 11a through 11b. Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in table 10. Heat of rejection (HR) can be calculated and compared to submittal data capacity pages. The formula for HR for systems with water is as follows:
HR (Btuh) = TD x GPM x 500, where TD is the temperature difference between the entering and leaving water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to table 10. In S-I units, the formula is as follows:
HR (kW) = TD x l/s x 4.18.
f. Check air temperature drop across the air coil when compressor is operating. Air temperature drop should be between 15°F and 25°F [8°C and 14°C].
g. Turn thermostat to “OFF” position. A hissing noise indicates proper functioning of the reversing valve.
6. Allow five (5) minutes between tests for pressure to equalize before beginning heating test.
a. Adjust the thermostat to the lowest setting Place the thermostat mode switch in the “HEAT” position.
b. Slowly raise the thermostat to a higher temperature until the compressor activates.
c. Check for warm air delivery within a few minutes after the unit has begun to operate.
d. Refer to table 12. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to tables 11a through 11b.
Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in table 10. Heat of extraction (HE) can be calculated and compared to submittal data capacity pages.
The formula for HE for systems with water is as follows: HE (Btuh) = TD x GPM x 500, where TD is the temperature difference between the entering and leaving water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to table 10. e. In S-I units, Check air temperature rise across the air coil when compressor is operating. Air temperature rise should be between 20°F and 30°F [11°C and
17°C]. f. Check for vibration, noise, and water leaks.
7. If unit fails to operate, perform troubleshooting analysis
(see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to ensure proper diagnosis and repair of the equipment.
8. When testing is complete, set system to maintain desired comfort level.
9. BE CERTAIN TO FILL OUT AND FORWARD
ALL WARRANTY REGISTRATION PAPERS TO
CLIMATEMASTER.
Note: If performance during any mode appears abnormal, refer to the CXM/DXM section or troubleshooting section of this manual. To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended.
76 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
Figure 22: Test Mode Pins
LT1
LT2
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Short test pins together to enter
Test Mode and speed-up timing and delays for 20 minutes.
LT1
LT1
LT2
LT2
Unit Start-Up Procedure, Cont’d.
� WARNING!
�
WARNING!
When the disconnect switch is closed, high voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
� CAUTION!
�
CAUTION!
Verify that ALL water control valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.
UNIT OPERATING CONDITIONS
Table 10: TC_L Coax Water Pressure Drop
Model
U.S.
GPM
10 l/s
0.631
l/m
37.85
30°F [-1°C]
1.2 [8.3]
TC_L072 15
20
0.946
1.262
56.781
75.708
3.3 [22.8]
6.2 [42.7]
TC_L096
TC_L120
TC_LV160
TC_LV192
TC_LV240
TC_LV300
136.20
181.80
113.40
170.40
227.40
142.20
213.00
283.80
45.425
68.137
90.85
56.781
85.172
113.562
79.20
119.40
159.00
90.60
3.79
2.37
3.55
4.73
2.27
3.03
1.89
2.84
1.32
1.99
2.65
1.51
0.757
1.136
1.514
0.946
1.42
1.893
36.0
48.0
30.0
45.0
60.0
37.5
56.3
750.0
21.0
31.5
42.0
24.0
12
18
24
15
22.5
30
*Note: To convert kPa to millibars, multiply by 10.
2.1 [14.5]
5.3 [36.5]
9.3 [64.1]
4 [27.6]
8.6 [59.3]
14.5 [100.0]
7.6 [52.5]
14.3 [98.8]
22.3 [154.0]
10.1 [69.8]
18.6 [128.5]
28.7 [198.2]
8.3 [57.3]
15.5 [107.1]
24.4 [168.5]
11.6 [80.1]
21.3 [147.1]
32.9 [227.2]
Pressure Drop, psi [kPa]*
50°F [10°C] 70°F [21°C]
0.9 [6.2] 0.5 [3.4]
2.8 [19.1]
5.3 [36.5]
1.7 [11.7]
4.5 [31.0]
7.9 [54.5]
3.2 [22.1]
7.2 [49.6]
12.2 [83.4]
4.4 [30.3]
9.1 [62.9]
15.2 [105.0]
7.6 [52.5]
12.6 [87.0]
20.2 [139.5]
6.6 [45.6]
11.1 [76.7]
17.8 [122.9]
7.9 [54.6]
13.6 [93.9]
22.3 [154.0]
2.1 [14.5]
4.2 [29.0]
1.3 [9.0]
3.6 [24.8]
6.6 [45.5]
2.2 [15.2]
5.5 [37.9]
9.8 [67.6]
4.0 [27.6]
8.4 [58.02]
14.1 [97.4]
6.2 [42.8]
11.6 [80.1]
18.8 [129.9]
5.6 [38.7]
10.4 [71.8]
16.8 [116.0]
6.4 [44.2]
12.6 [87.0]
20.8 [143.6] c l i m a t e m a s t e r.c o m
90°F [32°C]
0.3 [2.1]
1.8 [12.4]
3.8 [26.2]
1.1 [7.6]
3.3 [22.8]
6.1 [42.1]
2 [13.8]
5.1 [35.2]
9.2 [63.4]
3.8 [26.3]
7.9 [54.6]
13 [89.8]
5.9 [40.8]
11.1 [76.7]
17.7 [122.3]
5.3 [36.6]
9.9 [68.4]
15.9 [109.8]
5.9 [40.8]
11.8 [81.5]
19.6 [135.4]
77
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Unit Operating Conditions
Operating Pressure/Temperature tables include the following notes:
• Airflow is at nominal (rated) conditions;
• Entering air is based upon 70°F [21°C] DB in heating and 80/67°F [27/19°C] in cooling;
• Subcooling is based upon head pressure at compressor service port;
• Cooling air and water values can vary greatly with changes in humidity level.
Table 11a: TC_L072-120 Series Typical Unit Operating Pressures and Temperatures (60Hz - I-P Units)
Cooling Heating
Entering
Water
Temp °F
20
Water
Flow
GPM/ton
1.5
2.25
3
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
30*
50
70
90
100
120
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
3
1.5
2.25
122 - 125
116 - 119
112 - 115
128 - 134
122 - 131
119 - 129
132 - 139
131 - 137
131 - 136
137 - 144
135 - 142
135 - 141
139 - 147
138 - 146
138 - 146
144 - 153
143 - 153
143 - 152
*Based on 15% Methanol antifreeze solution
197 - 204
177 - 184
168 - 173
240 - 252
219 - 233
209 - 224
311 - 329
287 - 306
275 - 294
400 - 420
373 - 395
359 - 383
448 - 471
420 - 445
405 - 432
549 - 583
525 - 557
511 - 543
13 - 16
17 - 19
19 - 21
11 - 14
12 - 17
13 - 18
9 - 12
10 - 13
10 - 13
8 - 10
9 - 11
9 - 12
8 - 9
8 - 10
8 - 10
7 - 8
7 - 8
8 - 9
15 - 20
15 - 18
14 - 18
13 - 16
12 - 16
11 - 15
12 - 15
10 - 12
9 - 11
13 - 16
10 - 12
9 - 11
13 - 16
11 - 13
10 - 11
15 - 17
12 - 14
11 - 13
20 - 24
13 - 16
10 - 12
20 - 22
13 - 15
10 - 11
19 - 21
13 - 14
9 -11
19 - 20
12 - 14
9 - 10
18 - 20
12 - 13
9 - 10
17 - 19
11 - 13
9 - 10
Air Temp
Drop °F
DB
22 - 23
21 - 22
21 - 22
21 - 22
21 - 22
21 - 22
20 - 21
20 - 21
20 - 21
19 - 20
19 - 20
19 - 20
18 - 19
18 - 19
18 - 19
17 - 18
17 - 18
17 - 18
Suction
Pressure
PSIG
60 - 63
67 - 71
71 - 75
74 - 76
97 - 102
104 - 108
107 - 122
130 - 135
139 - 144
145 - 149
164 - 169
175 - 178
179 - 187
Discharge
Pressure
PSIG
289 - 306
297 - 315
301 - 321
303 - 323
333 - 355
339 - 361
342 - 369
367 - 392
375 - 402
380 - 407
401 - 430
411 - 442
415 - 455
Superheat Subcooling
9 - 12
10 - 12
10 - 12
11 - 13
9 - 11
9 - 11
9 - 11
9 - 11
10 - 11
10 - 11
10 - 13
12 - 16
13 - 18
8 - 17
9 - 18
10 - 19
10 - 19
13 - 21
13 - 21
13 - 20
13 - 21
13 - 20
13 - 19
13 - 17
14 - 17
14 - 16
Water
Temp
Drop °F
3 - 4
8 - 9
6 - 7
4 - 5
11 - 12
8 - 9
6 - 7
14 - 16
10 - 12
8 - 9
18 - 20
12 - 14
9 - 11
Air Temp
Rise °F
DB
20 - 22
22 - 23
23 - 24
23 - 25
29 - 30
30 - 31
31 - 32
35 - 37
37 - 38
38 - 39
41 - 43
43 - 45
44 - 46
Table 11b: TC_LV160-300 Series Typical Unit Operating Pressures and Temperatures (60Hz - I-P Units)
Cooling Heating
Entering
Water
Temp ºF
Water
Flow
GPM/ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
20*
30*
50
70
90
1.5
2.25
3.0
1.5
2.25
3.0
1.5
2.25
3.0
1.5
2.25
3.0
1.5
2.25
3.0
118 - 121 166 - 197
109 - 119 154 - 167
104 - 117 153 - 166
127 - 135 232 - 247
122 - 133 215 - 228
121 - 131 206 - 218
130 - 139 304 - 317
128 - 139 284 - 295
127 - 138 272 - 284
136 - 145 404 - 420
134 - 143 381 - 406
133 - 142 369 - 392
100
120
1.5
2.25
3.0
1.5
2.25
3.0
137 - 146
135 - 145
134 - 144
141 - 152
140 - 151
139 - 149
434 - 445
407 - 425
395 - 413
537 - 553
512 - 531
500 - 517
*Based on 15% Methanol antifreeze solution
Superheat Subcooling
12 - 21
13 - 22
17 - 24
7 - 12
10 -16
11 - 17
6 - 11
6 - 11
6 - 12
4 - 10
5 - 11
6 - 12
4 - 9
5 - 9
5 - 10
4 - 9
5 - 9
5 - 9
5 - 12
6 - 16
4 - 13
4 - 12
4 -11
4 - 10
4 - 9
14 - 24
12 - 24
11 - 24
11 - 20
10 - 19
9 - 18
10 - 16
7 - 14
6 - 12
6 - 14
5 - 13
Water Temp
Rise ºF
9 - 24
9 - 24
10 - 21
10 - 21
8 - 19
8 - 19
Air Temp
Drop ºF
DB
17 - 23
17 - 23
17 - 23
17 - 21
17 - 21
16 - 20
Suction
Pressure
PSIG
54 - 76
59 - 66
64 - 70
66 - 73
85 - 96
97 - 104
99 - 108
121 - 131
132 - 140
137 - 149
158 - 168
173 - 182
175 -190
Discharge
Pressure
PSIG
280 - 302
285 - 309
289 - 316
292 - 320
315 - 342
323 - 355
325 - 357
354 - 387
363 - 398
374 - 418
386 - 428
400 - 441
405 - 445
Superheat Subcooling
5 - 18
5 - 13
5 - 17
5 - 17
7 - 12
7 - 12
7 - 12
8 - 13
8 - 13
8 - 18
10 - 16
10 - 17
11 - 17
8 - 20
10 - 21
10 - 16
9 - 15
11 - 25
12 - 25
13 - 25
11 - 26
12 - 27
13 - 28
6 - 22
6 - 22
6 - 22
Water
Temp
Drop ºF
3 - 6
4 - 10
5 - 13
7 - 17
9 - 21
Air Temp
Rise ºF
DB
18 - 23
19 - 23
24 - 31
31 - 39
37 - 45
Table 12: Water Temperature Change Through Heat Exchanger
Water Flow, gpm [l/m]
For Closed Loop: Ground Source or Closed
Loop Systems at 3 gpm per ton [3.2 l/m per kW]
For Open Loop: Ground Water
Systems at 1.5 gpm per ton
[1.6 l/m per kW]
Rise, Cooling
°F, [°C]
9 - 12
[5 - 6.7]
20 - 26
[11.1 - 14.4]
Drop, Heating
°F, [°C]
4 - 8
[2.2 - 4.4]
10 - 17
[5.6 - 9.4]
78 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Start-Up Log Sheet
Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record unit information, temperatures and pressures during start-up. Keep this form for future reference.
Job Name:
Model Number:
Unit Location in Building:
Date: Sales Order No:
Street Address:
Serial Number:
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
External Static:
Sheave Setting:
Temperatures: F or C
Pressures: PSIG or kPa
Turns Open
Return-Air Temperature
Supply-Air Temperature
Temperature Differential
Entering Fluid Temperature
Leaving Fluid Temperature
Temperature Differential
Water Coil Heat Exchanger
(Water Pressure IN)
Water Coil Heat Exchanger
(Water Pressure OUT)
Pressure Differential
Flow Rate GPM (l/s)
Compressor
Amps
Volts
Discharge Line Temperature
Motor
Amps
Volts
Cooling Mode
DB
DB
Allow unit to run 15 minutes in each mode before taking data.
Do not connect gauge lines
Antifreeze:
Type:
WB
WB
%
Heating Mode
DB
DB c l i m a t e m a s t e r.c o m 79
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Preventive Maintenance
Water Coil Maintenance -
(Direct ground water applications only)
If the system is installed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. Therefore, 1.5 gpm per ton [1.6 l/m per kW] is recommended as a minimum flow. Minimum flow rate for entering water temperatures below 50°F [10°C] is 2.0 gpm per ton [2.2 l/m per kW].
Condensate Drain - In areas where airborne bacteria may produce a “slimy” substance in the drain pan, it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem. The condensate pan may also need to be cleaned periodically to ensure indoor air quality. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect the drain twice a year to avoid the possibility of plugging and eventual overflow.
Compressor - Conduct annual amperage checks to ensure that amp draw is no more than 10% greater than indicated on the serial plate data.
Water Coil Maintenance -
(All other water loop applications)
Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treatment and mineral buildup through water use can also contribute to higher maintenance.
Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines.
Generally, the more water flowing through the unit, the less chance for scaling. However, flow rates over 3 gpm per ton (3.9 l/m per kW) can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.
Fan Motors - All units have lubricated fan motors. Fan motors should never be lubricated unless obvious, dry operation is suspected. Periodic maintenance oiling is not recommended, as it will result in dirt accumulating in the excess oil and cause eventual motor failure. Conduct annual dry operation check and amperage check to ensure amp draw is no more than 10% greater than indicated on serial plate data.
Belt - Check that the belt is tight. Retighten if needed.
Replace if it is split or cracked.
Air Coil - The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.
Refrigerant System To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Reference the operating charts for pressures and temperatures. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.
Filters - Filters must be clean to obtain maximum performance. Filters should be inspected every month under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Washable, high efficiency, electrostatic filters, when dirty, can exhibit a very high pressure drop for the fan motor and reduce air flow, resulting in poor performance. It is especially important to provide consistent washing of these filters (in the opposite direction of the normal air flow) once per month using a high pressure wash similar to those found at self-serve car washes.
80 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
AIR COIL
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
SYMBOL LEGEND
= TEMPERATURE SENSOR
= PRESSURE SWITCH
= REFRIGERANT FLOW COOLING MODE
= REFRIGERANT FLOW HEATING MODE
= REFRIGERANT FLOW EITHER MODE
= WATER FLOW
Circuit Diagram with Safety Devices
SOURCE
WATER
OUTLET
SOURCE
WATER
INLET
BALL VALVE BALL VALVE
(HOSES
RECOMMENDED)
STRAINER
(OPTIONAL)
LT2
THERMAL
EXPANSION VALVE
(BI-FLOW)
LT1
LIQUID LINE
FILTER DRIER
(BI-FLOW)
COMPONENTS MAY
BE INTERNAL
OR EXTERNAL
MOTORIZED
WATER VALVE
(OPTIONAL)
AUTO FLOW
REGULATOR
(OPTIONAL)
WATER HIGH PRESSURE SWITCHES (N.C.)
DISTRIBUTOR
(NUMBER OF
CIRCUITS VARY)
TXV
EQUALIZER
LINE
COAXIAL
WATER COIL
TXV
BULB
NOTES:
1. LT1 and LT2 sensors connect to CXM or DXM
2. Refrigerant high and low pressure switches
SUCTION
LINE connect to CXM or DXM
3. Water high pressure switches are wired in series with refrigerant high pressure switch.
REVERSING
VALVE
(COOLING MODE-
RV SOLENOID IS
ENERGIZED)
HIGH
PRESSURE
SWITCH
(N.C.)
DISCHARGE
LINE
REVERSING
VALVE
(HEATING MODE)
LOW
PRESSURE
SWITCH
(N.C.)
COMPRESSOR c l i m a t e m a s t e r.c o m 81
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Functional Troubleshooting
82
Fault
Main power problems
HP Fault
Code 2
High Pressure
LP/LOC Fault
Code 3
Low Pressure / Loss of Charge
LT1 Fault
Code 4
Water coil low temperature limit
LT2 Fault
Code 5
Air coil low temperature limit
Condensate Fault
Code 6
Over/Under
Voltage Code 7
(Auto resetting)
Unit Performance Sentinel
Code 8
Swapped Thermistor
Code 9
No Fault Code Shown
Unit Short Cycles
Only Fan Runs
Only Compressor Runs
Unit Doesn’t Operate in Cooling
X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
Htg Clg Possible Cause
X
X
X
X
X
X
X
X
X
X
X x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Green Status LED Off
Reduced or no water flow in cooling
Water Temperature out of range in cooling
Reduced or no air flow in heating
Air temperature out of range in heating
Overcharged with refrigerant
Bad HP Switch
Insufficient charge
Compressor pump down at start-up
Reduced or no water flow in heating
Inadequate antifreeze level
Improper temperature limit setting (30°F vs 10°F
[-1°C vs -2°C])
Water Temperature out of range
Bad thermistor
Reduced or no air flow in cooling
Air Temperature out of range
Improper temperature limit setting (30°F vs 10°F
[-1°C vs -12°C])
Bad thermistor
Blocked drain
Improper trap
Poor drainage
Moisture on sensor
Plugged air filter
Restricted Return Air Flow
Under Voltage
Over Voltage
Heating mode LT2>125°F [52°C]
Cooling Mode LT1>125°F [52°C] OR LT2< 40ºF
[4ºC])
LT1 and LT2 swapped
No compressor operation
Compressor overload
Control board
Dirty air filter
Unit in "test mode"
Unit selection
Compressor overload
Thermostat position
Unit locked out
Compressor Overload
Thermostat wiring
Thermostat wiring
Fan motor relay
Fan motor
Thermostat wiring
Reversing valve
Thermostat setup
Thermostat wiring
Thermostat wiring
Solution
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24VAC between R and C on CXM/DXM2
Check primary/secondary voltage on transformer.
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
Bring water temp within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table.
Bring return air temp within design parameters.
Check superheat/subcooling vs typical operating condition table.
Check switch continuity and operation. Replace.
Check for refrigerant leaks
Check charge and start-up water flow.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace..
Check water flow adjust to proper flow rate.
Check antifreeze density with hydrometer.
Clip JW3 jumper for antifreeze (10°F [-12°C]) use.
Bring water temp within design parameters.
Check temp and impedance correlation per chart
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high of external static. Check static vs blower table.
Too much cold vent air? Bring entering air temp within design parameters.
Normal airside applications will require 30°F [-1°C] only.
Check temp and impedance correlation per chart.
Check for blockage and clean drain.
Check trap dimensions and location ahead of vent.
Check for piping slope away from unit.
Check slope of unit toward outlet.
Poor venting. Check vent location.
Check for moisture shorting to air coil.
Replace air filter.
Find and eliminate restriction. Increase return duct and/or grille size.
Check power supply and 24VAC voltage before and during operation.
Check power supply wire size.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power supply voltage.
Check power supply voltage and 24VAC before and during operation.
Check 24VAC and unit transformer tap for correct power supply voltage.
Check for poor air flow or overcharged unit.
Check for poor water flow, or air flow.
Reverse position of thermistors
See "Only Fan Operates".
Check and replace if necessary.
Reset power and check operation.
Check and clean air filter.
Reset power or wait 20 minutes for auto exit.
Unit may be oversized for space. Check sizing for actual load of space.
Check and replace if necessary
Ensure thermostat set for heating or cooling operation.
Check for lockout codes. Reset power.
Check compressor overload. Replace if necessary.
Check thermostat wiring at heat pump. Jumper Y and R for compressor operation in test mode.
Check G wiring at heat pump. Jumper G and R for fan operation
Jumper G and R for fan operation. Check for Line voltage across BR contacts.
Check fan power enable relay operation (if present).
Check for line voltage at motor. Check capacitor.
Check thermostat wiring at heat pump. Jumper Y and R for compressor operation in test mode
Set for cooling demand and check 24VAC on RV coil and at CXM/DXM2 board.
If RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve.
Check for ‘O’ RV setup not ‘B’.
Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
Put thermostat in cooling mode. Check 24 VAC on O (check between C and O); check for
24 VAC on W (check between W and C). There should be voltage on O, but not on W. If voltage is present on W, thermostat may be bad or wired incorrectly.
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Performance Troubleshooting
Performance Troubleshooting Htg Clg Possible Cause
Insufficient capacity/ Not cooling or heating
High Head Pressure
X
X
X
X
X
X
X Dirty filter
Reduced or no air flow in heating
X Reduced or no air flow in cooling
X Leaky duct work
X Low refrigerant charge
X X Restricted metering device
X Defective reversing valve
X Thermostat improperly located
X Unit undersized
Solution
Replace or clean.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high of external static. Check static vs. blower table.
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high of external static. Check static vs. blower table.
Check supply and return air temperatures at the unit and at distant duct registers if significantly different, duct leaks are present.
Check superheat and subcooling per chart.
Check superheat and subcooling per chart. Replace.
Perform RV touch test.
Check location and for air drafts behind stat.
Recheck loads & sizing. Check sensible clg. load and heat pump capacity.
Perform scaling check and clean if necessary.
Check load, loop sizing, loop backfill, ground moisture.
X X Scaling in water heat exchanger
X X Inlet water too hot or too cold
X Reduced or no air flow in heating
X Reduced or no water flow in cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and air flow restrictions.
Too high of external static. Check static vs. blower table.
Check pump operation or valve operation/setting.
Check water flow. Adjust to proper flow rate.
X
X
X
X Inlet water too hot Check load, loop sizing, loop backfill, ground moisture.
Air temperature out of range in heating Bring return air temperature within design parameters.
X Scaling in water heat exchanger Perform scaling check and clean if necessary.
X Unit overcharged
X Non-condensables in system
X X Restricted metering device.
Check superheat and subcooling. Re-weigh in charge.
Vacuum system and re-weigh in charge.
X Reduced water flow in heating.
Check superheat and subcooling per chart. Replace.
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Low Suction Pressure
Low Discharge Air
Temperature in Heating
High humidity
X Water temperature out of range.
X Reduced air flow in cooling.
X Air temperature out of range
X X Insufficient charge
X
X
Too high of air flow
Poor performance
X Too high of air flow
X Unit oversized
Check water flow. Adjust to proper flow rate.
Bring water temperature within design parameters.
Check for dirty air filter and clean or replace.
Check fan motor operation and air flow restrictions.
Too high of external static. Check static vs. blower table.
Too much cold vent air? Bring entering air temperature within design parameters.
Check for refrigerant leaks.
Check fan motor speed selection and air flow chart.
See ‘Insufficient Capacity’
Check fan motor speed selection and airflow chart.
Recheck loads & sizing. Check sensible clg load and heat pump capacity.
c l i m a t e m a s t e r.c o m 83
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Functional Troubleshooting – I-P Units
C u s t o m e :r
Model #:
Complaint:
S e ir a l # :
Water-to-Air Units
L o o p T y p e : S t a tr u p D a t e :
A n it rf e e z e T y p e & % :
HEATING POSITION COOLING POSITION
OPERATING MODE: HEATING COOLING
10
AIR
COIL
REFRIG FLOW - HEATING
11
CONDENSER (HEATING)
EVAPORATOR (COOLING)
REFRIG FLOW - COOLING
REVERSING
VALVE
CONDENSER (COOLING)
EVAPORATOR (HEATING)
5 LT2:
HEATING
LIQUID
LINE
EXPANSION
VALVE
FILTER
DRIER
COAX
5 LT1:
COOLING
LIQUID
LINE
6
8
Source
7
9
2 1
SUCTION
3
COMPRESSOR
DISCHARGE
4
D e s c ir p it o n
Voltage
Compressor Amps
1
2
2a
2b
3
4
4a
4b
5
Suction Temp
Suction Press
Saturation Temp
Superheat
Discharge Temp
Discharge Press
Saturation Temp
Subcooling
Liquid Line Temp
6 Source Water In Tmp
9
9a
9b
10
7 Source Water Out Tmp
8 Source Water In Pres
11
Source Water Out Pres
Press Drop
Flow Rate
Return Air Temp
Supply Air Temp
Heating Cooling
Temp Diff. =
N o t e s
Heat of Extraction (Absorption) or Heat of Rejection:
HE or HR =
Fluid Factor: (for Btuh)
500 (Water); 485 (Antifreeze)
Fluid Factor: (for kW)
4.18 (Water); 4.05 (Antifreeze)
Flow Rate x Temp. Diff x Fluid Factor
Superheat = Suction temperature - suction saturation temp. = _________________ (deg F)
Subcooling = Discharge saturation temp. - liquid line temp. = _________________ (deg F)
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water flow and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a last resort.
84 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Warranty (U.S. & Canada)
c l i m a t e m a s t e r.c o m 85
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Notes:
86 C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Notes:
c l i m a t e m a s t e r.c o m 87
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility ® Compact High Capacity (TC_L) Series
R e v. : M a y 5 , 2 0 2 0
Revision History
Date:
5/5/20
3/17/20
09/09/19
07/25/17
06/19/17
11/28/16
10/6/16
06/22/16
04/15/16
4/5/16
02/10/15
06/13/14
09/30/13
11/09/12
04/26/12
02/09/12
10/07/11
08/09/11
07/08/11
01/03/11
Item:
ALL
ALL
Added Pages after Page 54
Page 40
Page 39
Page 9
Page 3
Page 16
All
Waterside Economizer
Page 12
Cover Picture
Text
Page 8
All
Page 13 & 34
Edit Text - Page 29
POE Oil Warning
TCV072-120 Dimensional Data
Water Quality Table
Condensate Drain Connection
All
Physical Data Table
Physical Data Table
Unit Maximum Working Water Pressure
All
Format - All Pages
Action:
Updated Table Headers
Updated Fonts
Inserted New VFD/VAV Fan Language
Updated TC_L Series Electrical Data Table
Updated TC_L Series Eletrical Data Table
Updated TC_LV Physical Data Table
New Decoder
Updated hanger mounting instructions
Update dimension tables
Added Waterside Economizer options and data
Text Update
Updated Unit Photo
Updated
Update Standard motor HP for 096
Update Air Filter Sizes and Electrical Tables
Change Text - Filter “rack” to “frame”
Water Quality table updated
Updated
Added
Updated
Updated
Updated
Added TCV sizes 160-300
Updated
Corrected TCV drain diameter
Updated to Reflect New Safeties
Added TCV072-120
Updated
88
*97B0084N01*
97B0084N01
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058 climatemaster.com
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
© ClimateMaster, Inc. 2009