Danfoss Filter driers, with their solid core technology, excel in removing moisture and acid from liquid lines in refrigeration, A/C systems, and refrigerated containers. Choose the DN filter for systems using HCFC refrigerants or the DU filter for HFC refrigerants. Both models offer effective filtering down to 20 µm and can be installed in any position with the arrow indicating flow direction. Their robust solid core withstands pressure surges and vibrations without releasing dust into the system, ensuring reliable performance.
advertisement
Data sheet
Introduction
Features
Approvals
Technical data
ã Danfoss A/S, 12 - 1999
Filter driers with solid core, type DN and DU
DN and DU filter driers with solid core are for use in liquid lines in refrigeration and freezing systems, A/C systems and refrigerated containers.
DN filters have a solid core composed of
Molecular Sieves and activated aluminium oxide.
This makes the DN filter suitable in applications where moisture and acid must be absorbed. DN is the correct choice for systems using HCFC refrigerants, but can also be used for HFC refrigerants.
DU filters have a solid insert with 100%
Molecular Sieves, which are recommended for refrigerating systems using HFC refrigerants, R
134a, R 404a, etc.
DU filters have been specially designed for refrigerating and A/C systems where high water adsorption is required. DU filters do not contain aluminium oxide and can therefore be used with all types of compressors. They are therefore particularly suitable for systems using polyolester with additives.
DN and DU
DN
·
Refrigerants
R 22, R 134a and R 404A, R 507 etc.
·
Compatible with CFC and refrigerant blends containing R 124a, R 125, R 134a, R143a,
R 152a, R 218, R 23 and R 32.
·
Solid core consisting of:
3Å molecular sieves and activated aluminium oxide for acid adsorption.
DN and DU filter driers
·
Removes moisture in the refrigeration system quickly and effectively
·
Optimized, uniform grain size in the solid core
·
Insignificant pressure drop
·
Can be installed in any position provided the arrow is in flow direction.
·
Effective filtering down to 20 µm
·
Solid core
High vibration resistance eliminates the risk of dust formation from desiccant wear.
S
A
UL file no. SA 6398
CSA certificate, no. 51840
DU
·
Refrigerants
HFC refrigerants. R 134a, R 404a, R 407C,
R 507, R410A, etc.
·
100% 3Å Molecular Sieves
Quick moisture adsorption in refrigeration system lessens the risk of acid formation.
Not harmful to additives in polyolester oil.
·
High water adsorption capacity
Very low moisture content left in the refrigeration system. Because of their long life, these filter driers are environmentally friendly and economical in use.
·
Robust solid core withstands pressure surge and vibration without releasing dust into the refrigeration system.
·
DN/DU 032s, DN/DU 032.5s and DN/DU 033s specially prepared for use in units with capillary tube expansion.
·
Helium leak detection
All DN and DU filter driers are leak tested before being painted.
·
Surface finish, powder coating
High corrosion resistance. Can be used in all environments - from plant rooms to ships’ refrigeration systems.
Pressure standard
HP-marked in accordance with German directive
TRB 521/522 on pressure vessels.
Surface and volume
Filter
DN/DU 03
DN/DU 05
DN/DU 08
DN/DU 16
DN/DU 30
DN 46
DN 60
Max. working pressure
PB
35 bar
35 bar
35 bar
35 bar
35 bar
35 bar
35 bar
Temperature range
– 40 to 70°C
Solid core surface
[cm 2 ]
60
75
10
175
330
505
660
Solid core volume
[cm 3 ]
50
65
100
225
480
705
960
Filter drier volume
[l]
0.10
0.12
0.17
0.38
0.67
1.05
1.34
DN acid capacity
[g]
0.71
0.87
1.36
3.12
6.40
9.52
12.80
RD.6A.G3.02
1
Data sheet
Capacity
Filter driers with solid core, type DN and DU
Drying and liquid capacity
Drying capacity in kg refrigerant
1
)
Type
DN 303
DN 304
DN 305
DN 306
DN 307
DN 464
DN 465
DN 466
DN 467
DN 607
DN 032
DN 032.5
DN 033
DN 052
DN 053
DN 082
DN 083
DN 084
DN 162
DN 163
DN 164
DN 165
DN 166
24°C
R 22
52°C
5.0
5.0
5.0
6.0
6.0
9.5
9.5
9.5
9.0
9.0
9.0
21.5
20.0
21.5
20.0
21.5
20.0
21.5
20.0
21.5
20.0
4.5
4.5
4.5
5.5
5.5
44.0
41.0
44.0
41.0
44.0
41.0
44.0
41.0
44.0
41.0
66.0
61.0
66.0
61.0
66.0
61.0
66.0
61.0
89.0
82.0
R 134a/R 507
24°C 52°C
R 404A
24°C 52°C
R 407C/R 410A
24°C 52°C
5.5
5.0
5.5
5.0
5.5
5.0
6.5
6.0
6.5
6.0
10.0
9.5
10.0
9.5
10.0
9.5
23.5
22.0
23.5
22.0
23.5
22.0
23.5
22.0
23.5
22.0
8.5
8.5
8.5
10.5
10.5
16.0
16.0
16.0
8.5
10.0
8.5
10.0
8.5
10.0
8.5
8.5
8.5
36.5
20.0
22.5
19.5
36.5
20.0
22.5
19.5
36.5
20.0
36.5
20.0
36.5
20.0
22.5
22.5
22.5
19.5
19.5
19.5
47.0
44.0
47.0
44.0
47.0
44.0
47.0
44.0
47.0
44.0
70.0
66.0
70.0
66.0
70.0
66.0
70.0
66.0
76.5
76.5
76.5
76.5
76.5
112.0
112.0
112.0
112.0
41.0
41.0
41.0
41.0
41.0
61.0
61.0
61.0
61.0
93.5
89.5
150.0
82.0
4.5
4.5
4.5
5.5
5.5
5.0
5.0
5.0
6.5
6.5
4.0
4.0
4.0
5.5
5.5
46.5
39.5
46.5
39.5
46.5
39.5
46.5
39.5
46.5
93.0
39.5
69.0
59.0
69.0
59.0
69.0
59.0
69.0
59.0
79.0
R 22
7.0
15.0
19.0
7.5
19.0
7.5
21.0
28.5
7.5
23.5
32.5
47.0
44.0
23.0
33.5
49.0
67.5
65.0
29.0
40.0
45.5
50.0
47.0
Liquid capacity in kW
2
)
DN
R 134a R 404A
R 507
4.5
10.0
12.5
5.0
14.0
5.0
14.0
19.5
5.0
15.5
21.5
30.0
29.0
15.0
22.0
32.5
44.5
43.0
19.5
27.0
33.0
35.0
31.0
6.5
13.0
17.0
7.0
17.5
7.0
19.0
26.0
7.0
21.5
29.5
42.5
40.0
21.0
30.5
44.5
61.5
59.0
26.5
36.5
42.0
47.0
43.0
R 407C
R 410A
7.0
15.0
19.0
7.5
19.0
7.5
21.0
28.5
7.5
23.5
32.5
47.0
44.0
23.0
33.5
49.0
67.5
65.0
29.0
40.0
45.5
50.0
47.0
DU 032
DU 032.5
DU 033
DU 052
DU 053
DU 082
DU 083
DU 084
DU 162
DU 163
DU 164
DU 165
DU 303
DU 304
DU 305
DU 306
DU 307
Drying and liquid capacity
Type
Drying capacity in kg refrigerant 1 )
R 134a/R 507 R 404A R 407C/R 410A
24 ° C 52 ° C 24 ° C 52 ° C 24 ° C 52 ° C
7.0
7.0
7.0
8.5
8.5
6.5
6.5
6.5
8.0
8.0
11.0
11.0
11.0
13.0
13.0
12.5
12.0
20.0
12.5
12.0
20.0
12.5
12.0
20.0
27.0
25.5
43.5
27.0
25.5
43.5
27.0
25.5
43.5
27.0
25.5
43.5
57.0
54.0
92.5
57.0
54.0
92.5
57.0
54.0
92.5
57.0
54.0
92.5
57.0
54.0
92.5
6.0
6.0
6.0
7.5
7.5
11.5
11.5
11.5
24.0
51.0
51.0
51.0
51.0
51.0
6.5
6.5
6.5
8.0
8.0
12.5
12.5
12.5
27.0
24.0
27.0
23.0
24.0
27.0
23.0
24.0
27.0
23.0
57.0
57.0
57.0
57.0
57.0
6.0
6.0
6.0
7.0
7.0
11.0
11.0
11.0
23.0
48.5
48.5
48.5
48.5
48.5
R 134a
6.5
13.0
17.0
7.0
17.5
7.0
19.0
26.0
7.0
21.5
29.5
42.5
21.0
30.5
44.5
61.5
59.0
Liquid capacity in kW 2 )
R 404A
R 507
4.5
10.0
12.5
5.0
14.0
5.0
14.0
19.5
5.0
15.5
21.5
30.0
15.0
22.0
32.5
44.5
43.0
DU
R 407C
R 410A
1
) Drying capacity is based on following moisture content in the refrigerant before and after drying:
R 22:
R 134a:
From 1050 ppm W to 60 ppm W in accordance with ARI 710-86.
From 1050 ppm W to 75 ppm W. If drying of refrigerant to 50 ppm W is required, this can be achieved with a 15% reduction of the stated capacities.
R 404A, R 407C og R 507: From 1020 ppm W to 30 ppm W.
2
R 410A: From 1050 ppm W to 60 ppm W.
) Given in accordance with ARI 710-86 for t e
=
-
15
°
C, t c
= 30
°
C and
D p = 0,07 bar.
7.0
15.0
19.0
7.5
19.0
7.5
21.0
28.5
7.5
23.5
32.5
47.0
23.0
33.5
49.0
67.5
65.0
2 RD.6A.G3.02
ã Danfoss A/S, 12 - 1999
Data sheet
Selection
Example
Type designation
Filter driers with solid core, type DN and DU
DN and DU are selected on the basis of:
1. Refrigerant and oil (see table).
2. The quantity of refrigerant in the system.
3. The refrigerant capacity of the system.
The refrigerant quantity is used to determine the amount of desiccant necessary to dry the refrigerant and oil.
The refrigerant capacity is used to determine the necessary pressure connection size.
Type selection is made considering the application
Refrigerant
Oil
HFC
HCFC
CFC
Mineral or AB
Pure POE, PAG or PVE
POE or PAG, with additives
DN
Can be used
Recommended
Can be used
Recommended
Can be used
Not recommended 2 )
DU
Recommended
Can be used
Not recommended
Can be used
Recommended
Recommended
1
1 ) For CFC systems, DN filter driers are recommended. In these systems, circumstances may require the use of a filter drier with acid adsorbing properties.
2 ) Use of filter driers containing activated alumina are not recommended in systems with oils containing additives.
)
1. Amount of charge:
7 kg R 22 at t l
= 24°C
To dry 7 kg R 22 from 1050 to 60 ppm moisture, a DN 08 is necessary.
2. Cooling capacity:
Q e
= 27 kW
To obtain a mass flow corresponding to 27 kW cooling effect with a DN 08 filter drier, a 12 mm connection must be chosen.
Larger connections can be chosen in accordance with the liquid line dimension.
3. Result
A DN 084 or DN 084s can be used.
If the initial moisture content is very small or a planned change of the filter drier is considered, a smaller filter drier size can be chosen.
Type
DN 082
DN 083
DN 084
24°C
9.5
9.5
9.5
R 22
52°C
9.0
9.0
9.0
Drying capacity in kg refrigerant
R 134a/R 507 R 404A
24°C
10.0
10.0
10.0
52°C
9.5
9.5
9.5
24°C
16.0
16.0
16.0
52°C
8.5
8.5
8.5
R407C/R 410A
24°C
10.0
10.0
10.0
52°C
8.5
8.5
8.5
Liquid capacity in kW
R 22 R 134a R 404A R 407C
R 507 R410A
7.5
21.0
28.5
7.0
19.0
26.0
5.0
14.0
19.5
7.5
21.0
28.5
Example: DN 053s
Filter drier
Solid core
N = Core with 80% Molecular Sieves and 20% activated aluminium oxide
U = Core with 100% Molecular Sieves
Filter size
Filter volume in cubic inches
Connection
Filter connection in eights of an inch
Connection type s = solder blank = flare
D N 05 3 s
ã Danfoss A/S, 12 - 1999
RD.6A.G3.02
3
Data sheet Filter driers with solid core, type DN and DU
Ordering
Type
DN 032
DN 033
DN 052
DN 053
DN 082
DN 083
DN 084
DN 162
DN 163
DN 164
DN 165
DN 166
DN 303
DN 304
DN 305
DN 306
DN 464
DN 465
DN 466
Connection in.
Code no.
Flare
Connection mm
Code no.
1 /
4
3 /
8
1 /
2
5 /
8
3 /
4
1 /
4
3 /
8
1 /
2
5 /
8
3 /
4
3 /
8
1 /
4
3 /
8
1 /
4
3 /
8
1 /
2
1 /
2
5 /
8
3 /
4
DU 032
DU 033
DU 052
DU 053
DU 082
DU 083
DU 084
DU 162
DU 163
DU 164
DU 165
DU 303
DU 304
DU 305
DU 306
1 /
4
3 /
8
3 /
8
1 /
2
5 /
8
3 /
4
1 /
4
3 /
8
1 /
2
5 /
8
1 /
4
3 /
8
1 /
4
3 /
8
1 /
2
023U3552
023U3553
023U3556
023U3557
023U3560
023U3561
023U3562
023U3564
023U3565
023U3566
023U3567
023U3569
023U3570
023U3571
023U3572
1 ) With mesh gauze for capillary tube systems
023U4034
023U4035
023U4036
023U4037
023U4038
023U4039
023U4040
023U4041
023U4042
023U4043
023U4044
023U4045
023U4046
023U4047
023U4048
023U4049
023U4084
023U4085
023U4086
6
10
12
16
18
6
10
12
16
18
10
6
10
6
10
12
12
16
18
6
10
10
12
16
18
6
10
12
16
6
10
6
10
12
023U3552
023U3553
023U3556
023U3557
023U3560
023U3561
023U3562
023U3564
023U3565
023U3566
023U3567
023U3569
023U3570
023U3571
023U3572
023U4034
023U4035
023U4036
023U4037
023U4038
023U4039
023U4040
023U4041
023U4042
023U4043
023U4044
023U4045
023U4046
023U4047
023U4048
023U4049
023U4084
023U4085
023U4086
DN 032s 1 )
DN 032.5s
1 )
DN 033s 1 )
DN 052s
DN 053s
DN 082s
DN 083s
DN 084s
DN 162s
DN 163s
DN 164s
DN 165s
DN 166s
DN 303s
DN 304s
DN 305s
DN 306s
DN 307s
DN 464s
DN 467s
DN 607s
Type
DU 032s 1 )
DU 032.5s
1 )
DU 033s 1 )
DU 052s
DU 053s
DU 082s
DU 083s
DU 084s
DU 162s
DU 163s
DU 164s
DU 165s
DU 303s
DU 304s
DU 305s
DU 306s
DU 307s
Connection in.
ODF solder
Code no.
Connection mm
Code no.
7 /
8
7 /
8
1 /
4
5 /
16
3 /
8
3 /
8
1 /
2
5 /
8
3 /
4
7 /
8
1 /
4
3 /
8
1 /
2
5 /
8
1 /
4
3 /
8
1 /
4
3 /
8
1 /
2
3 /
8
1 /
2
5 /
8
3 /
4
7 /
8
1 /
4
3 /
8
1 /
2
5 /
8
3 /
4
1 /
4
5 /
16
3 /
8
1 /
4
3 /
8
1 /
4
3 /
8
1 /
2
023U4001
023U4002
023U4004
023U4006
023U4008
023U4012
023U4014
023U4016
023U4020
023U4022
023U4024
023U4025
023U4026
023U4028
023U4030
023U4031
023U4033
023U4032
023U4093
023U4097
023U3501
023U3502
023U3504
023U3509
023U3511
023U3516
023U3518
023U3520
023U3523
023U3525
023U3527
023U3528
023U3533
023U3535
023U3536
023U3538
023U3539
6
8
10
6
10
6
10
12
6
10
12
16
10
12
16
18
22
18
22
22
6
8
10
10
12
16
19
22
6
10
12
16
6
10
6
10
12
023U4093
023U4097
DU
023U3500
023U3502
023U3503
023U3508
023U3510
023U3515
023U3517
023U3519
023U3522
023U3524
023U3526
023U3528
023U3532
023U3534
023U3536
023U3538
023U3539
DN
023U4000
023U4002
023U4003
023U4005
023U4007
023U4011
023U4013
023U4015
023U4019
023U4021
023U4023
023U4025
023U4027
023U4029
023U4031
023U4073
023U4032
023U4099
4 RD.6A.G3.02
ã Danfoss A/S, 12 - 1999
Data sheet
Construction
Function
1. Inlet
2. Spring
3. Solid core
4. Polyester mat
6. Corrugated, perforated plate
7. Outlet
8. Plastic union nut
9. Capsule
Dimensions and weights
Filter driers with solid core, type DN and DU
The relatively large diameter of the filter drier means that through-flow liquid velocity is suitably low and pressure drop slight.
Powder formation is eliminated since the solid core grains cannot move against each other.
Flare connection
Type
DN / DU 032
DN / DU 033
DN / DU 052
DN / DU 053
DN / DU 082
DN / DU 083
DN / DU 084
DN / DU 162
DN / DU 163
DN / DU 164
DN / DU 165
DN / DU 166
DN / DU 303
DN / DU 304
DN / DU 305
DN / DU 306
DN / DU 464
DN / DU 465
DN / DU 466
L
1 mm
105
118
114
154
167
175
184
127
140
153
161
182
243
251
260
258
341
350
348
D mm
52
52
52
74
74
74
74
74
74
74
52
52
52
52
74
74
74
74
74
Weight kg
0.22
0.25
0.24
0.27
0.38
0.41
0.46
0.71
0.74
0.79
0.84
0.91
0.99
1.04
1.08
1.15
1.70
1.74
1.84
DN / DU 032s
DN / DU 032.5s
DN / DU 033s
DN / DU 052s
DN / DU 053s
DN / DU 082s
DN / DU 083s
DN / DU 084s
DN / DU 162s
DN / DU 163s
DN / DU 164s
DN / DU 165s
DN / DU 166s
DN / DU 303s
DN / DU 304s
DN / DU 305s
DN / DU 306s
DN / DU 307s
DN / DU 467s
DN / DU 607s
Solder connection ODF
Type
L
2 mm
93
96
99
160
164
224
228
236
240
246
336
411
138
142
148
152
102
108
128
134
Weight kg
0.20
0.21
0.21
0.74
0.75
0.96
1.01
1.02
1.03
1.04
1.65
1.95
0.21
0.22
0.36
0.37
0.39
0.67
0.68
0.73
D mm
52
52
52
74
74
74
74
74
74
74
74
74
52
74
74
74
52
52
52
52
ã Danfoss A/S, 12 - 1999
RD.6A.G3.02
5
Data sheet Filter driers with solid core, type DN and DU
6 RD.6A.G3.02
ã Danfoss A/S, 12 - 1999
Data sheet Filter driers with solid core, type DN and DU
ã Danfoss A/S, 12 - 1999
RD.6A.G3.02
7
Data sheet Filter driers with solid core, type DN and DU
8 RD.6A.G3.02
ã Danfoss A/S, 12 - 1999
advertisement