Instructions AM-PBU 25

Description

AM-PBU 25 is a standby power supply for AME 55 and AME 85 actuators. It will drive the actuators to open or closed position during a power failure. The AM-PBU 25 can power one AMV(E) 85/86 or two AMV(E) 55/56 actuators.

Installation

1. Connect the VMS25 to the actuator(s) as shown.

Connect NC1 or NC2 to terminal 3 on an actuator to drive the valve stem down during power failure or to terminal 2 to drive the valve stem up during a power failure.

2. Connect AM-PBU 25 to 24 volts ac power.

3. Connect the red wire to the battery positive (+) and the black wire to the battery negative (-).

Note: Connect the 24 volt power to the AM-PBU 25 before connecting the battery. Connecting the battery fi rst causes the AM-PBU 25 to go into the power failure mode.

���������

�� ��� ��� ��� ��� ��� ���� ��� ���� ��� ��� ���� ��� ���

������

�����������

�� �� ��� ��� �� �

���������

������

�� �� ��� ��� �� �

���������

������

� �

��������������

� �

7369082-0 SIBC 06 / 04 VI.AE.P1.02

L

LN

BT

24 Vac power

System neutral

Battery Test

RC

TG

C1

Remote Control

Test Ground

Common, Output 1

NC1 Normally Closed, Output 1

NC2 Normally Open, Output 1

AC

C2

24 Vac output

Common, Output 2

NC2 Normally Closed, Output 2

NO2 Normally Open, Output 2

1 (2)

Testing the AM-PBU 25 and the battery

The jumper between LN & RC can be replaced by a connection to a

Building Management System (BMS), a controller or a manual switch. When the contact opens, the mains power is disconnected and the AM-PBU 25 goes through a cycle, running on battery power. This feature can be used for remote control of the valve or for testing of the battery.

Connecting terminals TG (-) and BT (+) to a BAS or volt meter and taking a reading just after an exercise cycle, gives a good indication of battery condition. At the end of the cycle (6.5 minutes), the battery should not be below 10 V.

When the connection between LN & RC is restored the AM-PBU 25 will charge the battery with 13 - 14 volts dc wich can be verifi ed on terminals

TG & BT.

AM-PBU 25

�� ��� ��� ��� ��� ��� ���� ��� ���� ��� ��� ���� ��� ���

������

�� �� �� �� ��

����������������

����������������

��������

�����������

AM-PBU 25

�� ��� ��� ��� ��� ��� ���� ��� ���� ��� ��� ���� ��� ���

�� �� ��� ��� �� �

���������

������

�� �� ��� ��� �� �

���������

������

���������������������������������

����������������������

�����������

��������������

� �

AM-PBU 25

�� ��� ��� ��� ��� ��� ���� ��� ���� ��� ��� ���� ��� ���

������

������

��������

���

����������

�����������

�� �� ��� ��� �� �

���������

������

� �

��������������

AM-PBU 25

2(2)