Danfoss VLT® AutomationDrive FC302, 315-710 kW,E Guide
Advertisement
Advertisement
ENGINEERING TOMORROW
Design Guide
VLT® AutomationDrive FC 302
315–710 kW, Enclosure Size E
vlt-drives.danfoss.com
Contents Design Guide
Contents
1 Introduction
1.1 Purpose of the Design Guide
1.2 Additional Resources
1.3 Document and Software Version
1.4 Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualified Personnel
2.3 Safety Precautions
3 Approvals and Certifications
3.1 Regulatory/Compliance Approvals
3.2 Enclosure Protection Ratings
4 Product Overview
4.1 Enclosure Size by Power Rating
4.2 Overview of Enclosures, 380–500 V
4.3 Overview of Enclosures, 525–690 V
5 Product Features
5.1 Automated Operational Features
5.2 Custom Application Features
5.3 Dynamic Braking Overview
5.4 Mechanical Holding Brake Overview
5.5 Load Share Overview
5.6 Regen Overview
5.7 Back-channel Cooling Overview
6 Options and Accessories Overview
6.1 Fieldbus Devices
6.2 Functional Extensions
6.3 Motion Control and Relay Cards
6.4 Brake Resistors
6.5 Sine-wave Filters
6.6 dU/dt Filters
6.7 Common-mode Filters
6.8 Harmonic Filters
6.9 High-power Kits
7 Specifications
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
1
2
Contents VLT® AutomationDrive FC 302
7.1 Electrical Data, 380–500 V
7.2 Electrical Data, 525–690 V
7.3 Mains Supply
7.4 Motor Output and Motor Data
7.5 Ambient Conditions
7.6 Cable Specifications
7.7 Control Input/Output and Control Data
8 Exterior and Terminal Dimensions
8.1 E1h Exterior and Terminal Dimensions
8.2 E2h Exterior and Terminal Dimensions
8.3 E3h Exterior and Terminal Dimensions
8.4 E4h Exterior and Terminal Dimensions
9 Mechanical Installation Considerations
9.1 Storage
9.2 Lifting the Unit
9.3 Operating Environment
9.4 Mounting Configurations
9.5 Cooling
9.6 Derating
10 Electrical Installation Considerations
10.1 Safety Instructions
10.2 Wiring Schematic
10.3 Connections
10.4 Control Wiring and Terminals
10.5 Fuses and Circuit Breakers
10.6 Motor
10.7 Braking
10.8 Residual Current Devices (RCD) and Insulation Resistance Monitor (IRM)
10.9 Leakage Current
10.10 IT Mains
10.11 Efficiency
10.12 Acoustic Noise
10.13 dU/dt Conditions
10.14 Electromagnetic Compatibility (EMC) Overview
10.15 EMC-compliant Installation
10.16 Harmonics Overview
11 Basic Operating Principles of a Drive
11.1 Description of Operation
Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Contents Design Guide
11.2 Drive Controls
12 Application Examples
12.1 Programming a Closed-loop Drive System
12.2 Wiring Configurations for Automatic Motor Adaptation (AMA)
12.3 Wiring Configurations for Analog Speed Reference
12.4 Wiring Configurations for Start/Stop
12.5 Wiring Configuration for an External Alarm Reset
12.6 Wiring Configuration for Speed Reference Using a Manual Potentiometer
12.7 Wiring Configuration for Speed Up/Speed Down
12.8 Wiring Configuration for RS485 Network Connection
12.9 Wiring Configuration for a Motor Thermistor
12.10 Wiring Configuration for a Relay Set-up with Smart Logic Control
12.11 Wiring Configuration for Mechanical Brake Control
12.12 Configuring the Encoder
12.13 Wire Configuration for Torque and Stop Limit
13 How to Order a Drive
13.1 Drive Configurator
13.2 Ordering Numbers for Options and Accessories
13.3 Ordering Numbers for Filters and Brake Resistors
13.4 Spare Parts
14 Appendix
14.1 Abbreviations and Symbols
14.2 Definitions
Index
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
3
Introduction VLT® AutomationDrive FC 302
1 1
1 Introduction
1.1 Purpose of the Design Guide
This design guide is intended for:
•
Project and systems engineers.
•
Design consultants.
•
Application and product specialists.
The design guide provides technical information to understand the capabilities of the drive for integration into motor control and monitoring systems.
VLT ® is a registered trademark.
1.2 Additional Resources
Other resources are available to understand advanced drive operation, programming, and directives compliance.
•
The Operating Guide provides detailed information for the installation and start up of the drive.
•
The Programming Guide provides greater detail on how to work with parameters and includes many application examples.
•
The VLT ® Safe Torque Off Operating Guide describes how to use Danfoss drives in functional safety applications. This manual is supplied with the drive when the safe torque off option is present.
•
The VLT ® Brake Resistor Design Guide describes how to select the optimal brake resistor.
•
Optional equipment is available that can change some of the information described in these publications. Be sure to see the instructions supplied with the options, for specific requirements.
Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/ technical-documentation/ for listings.
1.3 Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
shows the document version and the corresponding software version.
Edition
MG38C1xx
Remarks
Initial release
Table 1.1 Document and Software Version
Software version
7.51
1.4 Conventions
•
Numbered lists indicate procedures.
•
Bullet lists indicate other information and description of illustrations.
•
Italicized text indicates:
Cross-reference.
Link.
Footnote.
Parameter name, parameter group name, parameter option.
•
All dimensions in drawings are in mm (in).
•
An asterisk (*) indicates a default setting of a parameter.
4 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Safety Design Guide
2 Safety
2.1 Safety Symbols
The following symbols are used in this guide:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualified Personnel
Only qualified personnel are allowed to install or operate this equipment.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the personnel must be familiar with the instructions and safety measures described in this manual.
2.3 Safety Precautions
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains input, DC supply, load sharing, or permanent motors.
Failure to use qualified personnel to install, start up, and maintain the drive can result in death or serious injury.
•
Only qualified personnel must install, start up, and maintain the drive.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait 40 minutes after power has been removed before performing service or repair work can result in death or serious injury.
1.
2.
3.
4.
5.
Stop the motor.
Disconnect AC mains and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
Disconnect or lock motor.
Wait 40 minutes for the capacitors to discharge fully.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
• Ensure the correct grounding of the equipment by a certified electrical installer.
NOTICE
MAINS SHIELD SAFETY OPTION
A mains shield option is available for enclosures with a protection rating of IP21/IP 54 (Type 1/Type 12). The mains shield is a cover installed inside the enclosure to protect against the accidental touch of the power terminals, according to BGV A2, VBG 4.
2 2
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
5
Safety VLT® AutomationDrive FC 302
2 2
2.3.1 ADN-compliant Installation
To prevent spark formation in accordance with the
European Agreement concerning International Carriage of
Dangerous Goods by Inland Waterways (ADN), precautions must be taken for drives with protection rating of IP00
(Chassis), IP20 (Chassis), IP21 (Type 1) or IP54 (Type 12).
•
Do not install a mains switch.
•
Ensure that parameter 14-50 RFI Filter is set to
[1] On .
•
Remove all relay plugs marked RELAY . See
•
Check which relay options are installed, if any.
The only allowed relay option is VLT ® Extended
Relay Card MCB 113.
6
1, 2 Relay plugs
Illustration 2.1 Location of Relay Plugs
1
2
Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Approvals and Certification...
Design Guide
3 Approvals and Certifications
This section provides a brief description of the various approvals and certifications that are found on Danfoss drives. Not all approvals are found on all drives.
3.1 Regulatory/Compliance Approvals
NOTICE
IMPOSED LIMITATIONS ON THE OUTPUT
FREQUENCY
From software version 6.72 onwards, the output frequency of the drive is limited to 590 Hz due to export control regulations. Software versions 6.xx also limit the maximum output frequency to 590 Hz, but these versions cannot be flashed, that is, neither downgraded nor upgraded.
3.1.1.1 CE Mark
The CE mark (Communauté Européenne) indicates that the product manufacturer conforms to all applicable EU directives. The EU directives applicable to the design and manufacture of drives are listed in
.
NOTICE
The CE mark does not regulate the quality of the product. Technical specifications cannot be deduced from the CE mark.
EU Directive
Low Voltage Directive
EMC Directive
Machinery Directive 1)
ErP Directive
ATEX Directive
RoHS Directive
Version
2014/35/EU
2014/30/EU
2014/32/EU
2009/125/EC
2014/34/EU
2002/95/EC
Table 3.1 EU Directives Applicable to Drives
1) Machinery Directive conformance is only required for drives with an integrated safety function.
NOTICE
Drives with an integrated safety function, such as Safe
Torque Off (STO), must comply with the machinery directive.
Declarations of conformity are available on request.
Low Voltage Directive
Drives must be CE-labeled in accordance with the Low
Voltage Directive of January 1, 2014. The Low Voltage
Directive applies to all electrical equipment in the 50–
1000 V AC and the 75–1500 V DC voltage ranges.
The aim of the directive is to ensure personal safety and avoid property damage when operating electrical equipment that is installed, maintained, and used as intended.
EMC Directive
The purpose of the EMC (electromagnetic compatibility)
Directive is to reduce electromagnetic interference and enhance immunity of electrical equipment and installations. The basic protection requirement of the EMC
Directive is that devices that generate electromagnetic interference (EMI), or whose operation can be affected by
EMI, must be designed to limit the generation of electromagnetic interference. The devices must have a suitable degree of immunity to EMI when properly installed, maintained, and used as intended.
Electrical equipment devices used alone or as part of a system must bear the CE mark. Systems do not require the
CE mark, but must comply with the basic protection requirements of the EMC Directive.
Machinery Directive
The aim of the Machinery Directive is to ensure personal safety and avoid property damage to mechanical equipment used in its intended application. The Machinery
Directive applies to a machine consisting of an aggregate of interconnected components or devices of which at least
1 is capable of mechanical movement.
Drives with an integrated safety function must comply with the Machinery Directive. Drives without a safety function do not fall under the Machinery Directive. If a drive is integrated into a machinery system, Danfoss can provide information on safety aspects relating to the drive.
When drives are used in machines with at least 1 moving part, the machine manufacturer must provide a declaration stating compliance with all relevant statutes and safety measures.
3.1.1.2 ErP Directive
The ErP Directive is the European Ecodesign Directive for energy-related products, including drives. The aim of the directive is to increase energy efficiency and the level of protection of the environment, while increasing the security of the energy supply. Environmental impact of energy-related products includes energy consumption throughout the entire product life cycle.
3 3
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
7
Approvals and Certification...
VLT® AutomationDrive FC 302
3 3
3.1.1.3 UL Listing
The Underwriters Laboratory (UL) mark certifies the safety of products and their environmental claims based on standardized testing. Drives of voltage T7 (525–690 V) are
UL-certified for only 525–600 V. The drive complies with UL
61800-5-1 thermal memory retention requirements. For more information, refer to
3.1.1.4 CSA/cUL
The CSA/cUL approval is for AC drives of voltage rated at
600 V or lower. The standard ensures that, when the drive is installed according to the provided operating/installation guide, the equipment meets the UL standards for electrical and thermal safety. This mark certifies that the product performs to all required engineering specifications and testing. A certificate of compliance is provided on request.
3.1.1.5 EAC
The EurAsian Conformity (EAC) mark indicates that the product conforms to all requirements and technical regulations applicable to the product per the EurAsian
Customs Union, which is composed of the member states of the EurAsian Economic Union.
The EAC logo must be both on the product label and on the packaging label. All products used within the EAC area, must be bought at Danfoss inside the EAC area.
3.1.1.6 UKrSEPRO
UKrSEPRO certificate ensures quality and safety of both products and services, in addition to manufacturing stability according to Ukrainian regulatory standards. The
UkrSepro certificate is a required document to clear customs for any products coming into and out of the territory of Ukraine.
3.1.1.7 TUV
TUV SUD is a European safety organization which certifies the functional safety of the drive in accordance to EN/IEC
61800-5-2. The TUV SUD both tests products and monitors their production to ensure that companies stay compliant with their regulations.
3.1.1.8 RCM
The Regulatory Compliance Mark (RCM) indicates compliance with telecommunications and EMC/radiocommunications equipment per the Australian
Communications and Media Authorities EMC labeling notice. RCM is now a single compliance mark covering both the A-Tick and the C-Tick compliance marks. RCM compliance is required for placing electrical and electronic devices on the market in Australia and New Zealand.
3.1.1.9 Marine
Marine applications - ships and oil/gas platforms - must be certified by 1 of more marine certification societies in order to receive a regulatory license and insurance. Danfoss VLT ®
AutomationDrive series drives are certified by up to 12 different marine classification societies.
To view or print marine approvals and certificates, go to the download area at http://drives.danfoss.com/industries/ marine-and-offshore/marine-type-approvals/#/ .
3.1.2 Export Control Regulations
Drives can be subject to regional and/or national export control regulations.
An ECCN number is used to classify all drives that are subject to export control regulations.
The ECCN number is provided in the documents accompanying the drive.
In case of re-export, it is the responsibility of the exporter to ensure compliance with the relevant export control regulations.
8 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Approvals and Certification...
Design Guide
3.2 Enclosure Protection Ratings
The VLT ® drive series are available in various enclosure protection to accommodate the needs of the application. Enclosure protection ratings are provided based on 2 international standards:
•
UL type validates that the enclosures meet NEMA (National Electrical Manufacturers Association) standards. The construction and testing requirements for enclosures are provided in NEMA Standards Publication 250-2003 and UL
50, Eleventh Edition.
•
IP (Ingress Protection) ratings outlined by IEC (International Electrotechnical Commission) in the rest of the world.
Standard Danfoss VLT ® drive series are available in various enclosure protections to meet the requirements of IP00 (Chassis),
IP20 (Protected chassis) or IP21 (UL Type 1), or IP54 (UL Type 12). In this manual, UL Type is written as Type. For example,
IP21/Type 1.
UL type standard
Type 1 – Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed units and to provide a degree of protection against falling dirt.
Type 12 – General-purpose enclosures are intended for use indoors to protect the enclosed units against the following:
•
Fibers
•
Lint
•
Dust and dirt
•
Light splashing
•
Seepage
•
Dripping and external condensation of noncorrosive liquids
There can be no holes through the enclosure and no conduit knockouts or conduit openings, except when used with oilresistant gaskets to mount oil-tight or dust-tight mechanisms. Doors are also provided with oil-resistant gaskets. In addition, enclosures for combination controllers have hinged doors, which swing horizontally and require a tool to open.
IP Standard
provides a cross-reference between the 2 standards.
demonstrates how to read the IP number and then defines the levels of protection. The drives meet the requirements of both.
NEMA and UL
Chassis
Protected chassis
Type 1
Type 12
IP
IP00
IP20
IP21
IP54
Table 3.2 NEMA and IP Number Cross-reference
3 3
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
9
Approvals and Certification...
VLT® AutomationDrive FC 302
3 3
–
–
–
–
–
–
–
–
–
5
6
3
4
1
2
1 st digit
0
Table 3.3 IP Number Breakdown
6
7
8
4
5
2
3
0
1
–
–
–
–
–
–
2 nd digit
–
Level of protection
No protection.
Protected to 50 mm (2.0 in). No hands would be able to get into the enclosure.
Protected to 12.5 mm (0.5 in). No fingers would be able to get into the enclosure.
Protected to 2.5 mm (0.1 in). No tools would be able to get into the enclosure.
Protected to 1.0 mm (0.04 in). No wires would be able to get into the enclosure.
Protected against dust – limited entry
Protected totally against dust
No protection
Protected from vertical dripping water
Protected from dripping water at 15° angle
Protected from water at 60° angle
Protected from splashing water
Protected from water jets
Protected from strong water jets
Protected from temporary immersion
Protected from permanent immersion
10 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Overview Design Guide
4 Product Overview
4.1 Enclosure Size by Power Rating
kW 1)
315
355
400
450
500
Hp 1)
450
500
550
600
650
Available enclosures
E1h/E3h
E1h/E3h
E1h/E3h
E2h/E4h
E2h/E4h
Table 4.1 Enclosure Power Ratings, 380–500 V
1) All power ratings are taken at high overload (150% current for
60 s). Output is measured at 400 V (kW) and 460 V (hp).
kW 1)
355
400
500
560
630
710
Hp 1)
400
400
500
600
650
750
Available enclosures
E1h/E3h
E1h/E3h
E1h/E3h
E1h/E3h
E2h/E4h
E2h/E4h
Table 4.2 Enclosure Power Ratings, 525–690 V
1) All power ratings are taken at high overload (150% current for
60 s). Output is measured at 690 V (kW) and 575 V (hp).
4.2 Overview of Enclosures, 380–500 V
E1h Enclosure size
Power rating 1)
Output at 400 V (kW)
Output at 460 V (hp)
Protection rating
IP
UL type
Hardware options 3)
Stainless steel back channel
Mains shielding
Space heater
RFI filter (Class A1)
Safe torque off
No LCP
Graphical LCP
Fuses
Heat sink access
Brake chopper
Regen terminals
Load share terminals
Fuses + load share
Disconnect
Circuit breakers
Contactors
24 V DC supply (SMPS, 5 A)
Dimensions
Height, mm (in)
Width, mm (in)
Depth, mm (in)
Weight, kg (lb)
315–400
450–550
IP21/54
Type 1/12
2043 (80.4)
602 (23.7)
513 (20.2)
295 (650)
O
S
O
O
O
O
O
O
S
O
–
–
–
O
–
O
–
E2h
450–500
600–650
IP21/54
Type 1/12
O
S
O
O
O
O
O
O
S
O
–
–
–
O
–
O
–
E3h
315–400
450–550
IP20 2)
Chassis
O
O
O
O
–
O
O
–
S
O
–
–
O
–
–
O
O
E4h
450–500
600–650
IP20 2)
Chassis
2043 (80.4)
698 (27.5)
513 (20.2)
318 (700)
1578 (62.1)
506 (19.9)
482 (19.0)
272 (600)
1578 (62.1)
604 (23.9)
482 (19.0)
295 (650)
Table 4.3 E1h–E4h Drives, 380–500 V
1) All power ratings are taken at high overload (150% current for 60 s).
2) If the enclosure is configured with load share or regen terminals, then the protection rating is IP00, otherwise the protection rating is IP20.
3) S = standard, O = optional, and a dash indicates that the option is unavailable.
O
O
O
O
–
O
O
–
S
O
–
–
O
–
–
O
O
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
11
4 4
Product Overview VLT® AutomationDrive FC 302
4 4
4.3 Overview of Enclosures, 525–690 V
E1h Enclosure size
Power rating 1)
Output at 690 V (kW)
Output at 575 V (hp)
Protection rating
IP
UL type
Hardware options 3)
Stainless steel back channel
Mains shielding
Space heater
RFI filter (Class A1)
Safe torque off
No LCP
Graphical LCP
Fuses
Heat sink access
Brake chopper
Regen terminals
Load share terminals
Fuses + load share
Disconnect
Circuit breakers
Contactors
24 V DC supply (SMPS, 5 A)
Dimensions
Height, mm (in)
Width, mm (in)
Depth, mm (in)
Weight, kg (lb)
355–560
400–600
IP21/54
Type 1/12
2043 (80.4)
602 (23.7)
513 (20.2)
295 (650)
O
–
O
O
–
O
O
S
S
O
O
–
O
O
–
–
–
E2h
630–710
650–950
IP21/54
Type 1/12
O
–
O
O
–
O
O
S
S
O
O
–
O
O
–
–
–
E3h
355–560
400–600
IP20 2)
Chassis
O
O
O
O
O
–
O
O
S
O
–
–
O
–
–
–
–
E4h
630–710
650–950
IP20 2)
Chassis
2043 (80.4)
698 (27.5)
513 (20.2)
318 (700)
1578 (62.1)
506 (19.9)
482 (19.0)
272 (600)
1578 (62.1)
604 (23.9)
482 (19.0)
295 (650)
Table 4.4 E1h–E4h Drives, 525–690 V
1) All power ratings are taken at high overload (150% current for 60 s).
2) If the enclosure is configured with load share or regen terminals, then the protection rating is IP00, otherwise the protection rating is IP20.
3) S = standard, O = optional, and a dash indicates that the option is unavailable.
O
O
O
O
O
–
O
O
S
O
–
–
O
–
–
–
–
12 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
5 Product Features
5.1 Automated Operational Features
Automated operational features are active when the drive is operating. Most of them require no programming or setup. The drive has a range of built-in protection functions to protect itself and the motor when it runs.
For details of any set-up required, in particular motor parameters, refer to the programming guide .
5.1.1 Short-circuit Protection
Motor (phase-to-phase)
The drive is protected against short circuits on the motor side by current measurement in each of the 3 motor phases. A short circuit between 2 output phases causes an overcurrent in the inverter. The inverter is turned off when the short circuit current exceeds the permitted value
( Alarm 16, Trip Lock ).
Mains side
A drive that works correctly limits the current it can draw from the supply. Still, it is recommended to use fuses and/or circuit breakers on the supply side as protection if there is component break-down inside the drive (first fault). Mains side fuses are mandatory for UL compliance.
NOTICE
To ensure compliance with IEC 60364 for CE or NEC 2009 for UL, it is mandatory to use fuses and/or circuit breakers.
Brake resistor
The drive is protected from a short circuit in the brake resistor.
Load sharing
To protect the DC bus against short circuits and the drives from overload, install DC fuses in series with the load sharing terminals of all connected units.
5.1.2 Overvoltage Protection
Motor-generated overvoltage
The voltage in the DC link is increased when the motor acts as a generator. This situation occurs in following cases:
•
The load rotates the motor at constant output frequency from the drive, that is, the load generates energy.
•
During deceleration (ramp-down) if the inertia moment is high, the friction is low, and the rampdown time is too short for the energy to be dissipated as a loss throughout the drive system.
•
Incorrect slip compensation setting causing higher DC-link voltage.
•
Back EMF from PM motor operation. If coasted at high RPM, the PM motor back EMF can potentially exceed the maximum voltage tolerance of the drive and cause damage. To help prevent this situation, the value of parameter 4-19 Max Output Frequency is automatically limited based on an internal calculation based on the value of parameter 1-40 Back EMF at
1000 RPM , parameter 1-25 Motor Nominal Speed and parameter 1-39 Motor Poles .
NOTICE
To avoid motor overspeeds (for example, due to excessive windmilling effects), equip the drive with a brake resistor.
The overvoltage can be handled either using a brake function ( parameter 2-10 Brake Function ) and/or using overvoltage control ( parameter 2-17 Over-voltage Control ).
Brake functions
Connect a brake resistor for dissipation of surplus brake energy. Connecting a brake resistor allows a higher DC-link voltage during braking.
AC brake is an alternative to improving braking without using a brake resistor. This function controls an overmagnetization of the motor when the motor is acting as a generator. Increasing the electrical losses in the motor allows the OVC function to increase the braking torque without exceeding the overvoltage limit.
NOTICE
AC brake is not as effective as dynamic braking with a resistor.
Overvoltage control (OVC)
By automatically extending the ramp-down time, OVC reduces the risk of the drive tripping due to an overvoltage on the DC-link.
NOTICE
OVC can be activated for a PM motor with all control core, PM VVC + , Flux OL, and Flux CL for PM Motors.
NOTICE
Do not enable OVC in hoisting applications.
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
13
Product Features VLT® AutomationDrive FC 302
5 5
5.1.3 Missing Motor Phase Detection
The missing motor phase function ( parameter 4-58 Missing
Motor Phase Function ) is enabled by default to avoid motor damage if a motor phase is missing. The default setting is
1000 ms, but it can be adjusted for faster detection.
5.1.4 Supply Voltage Imbalance Detection
Operation under severe supply voltage imbalance reduces the lifetime of the motor and drive. If the motor is operated continuously near nominal load, conditions are considered severe. The default setting trips the drive if there is supply voltage imbalance
( parameter 14-12 Response to Mains Imbalance ).
5.1.5 Switching on the Output
Adding a switch to the output between the motor and the drive is allowed, however fault messages can appear.
Danfoss does not recommend using this feature for 525–
690 V drives connected to an IT mains network.
5.1.6 Overload Protection
Torque limit
The torque limit feature protects the motor against overload, independent of the speed. Torque limit is controlled in parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode . The time before the torque limit warning trips is controlled in parameter 14-25 Trip Delay at Torque Limit .
Current limit
The current limit is controlled in parameter 4-18 Current
Limit , and the time before the drive trips is controlled in parameter 14-24 Trip Delay at Current Limit .
Speed limit
Mininum speed limit: Parameter 4-11 Motor Speed Low Limit
[RPM] or parameter 4-12 Motor Speed Low Limit [Hz] limit the minimum operating speed range of the drive.
Maximum speed limit: Parameter 4-13 Motor Speed High
Limit [RPM] or parameter 4-19 Max Output Frequency limit the maximum output speed the drive can provide.
Electronic thermal relay (ETR)
ETR is an electronic feature that simulates a bimetal relay based on internal measurements. The characteristic is shown in
.
Voltage limit
The inverter turns off to protect the transistors and the DC link capacitors when a certain hard-coded voltage level is reached.
Overtemperature
The drive has built-in temperature sensors and reacts immediately to critical values via hard-coded limits.
5.1.7 Locked Rotor Protection
There can be situations when the rotor is locked due to excessive load or other factors. The locked rotor cannot produce enough cooling, which in turn can overheat the motor winding. The drive is able to detect the locked rotor situation with open-loop PM flux control and PM VVC + control ( parameter 30-22 Locked Rotor Protection ).
5.1.8 Automatic Derating
The drive constantly checks for the following critical levels:
•
High temperature on the control card or heat sink.
•
High motor load.
•
High DC-link voltage.
•
Low motor speed.
As a response to a critical level, the drive adjusts the switching frequency. For high internal temperatures and low motor speed, the drives can also force the PWM pattern to SFAVM.
NOTICE
The automatic derating is different when parameter 14-55 Output Filter is set to [2] Sine-Wave Filter
Fixed .
5.1.9 Automatic Energy Optimization
Automatic energy optimization (AEO) directs the drive to monitor the load on the motor continuously and adjust the output voltage to maximize efficiency. Under light load, the voltage is reduced and the motor current is minimized. The motor benefits from:
•
Increased efficiency.
•
Reduced heating.
•
Quieter operation.
There is no need to select a V/Hz curve because the drive automatically adjusts motor voltage.
5.1.10 Automatic Switching Frequency
Modulation
The drive generates short electrical pulses to form an AC wave pattern. The switching frequency is the rate of these pulses. A low switching frequency (slow pulsing rate) causes audible noise in the motor, making a higher switching frequency preferable. A high switching frequency, however, generates heat in the drive that can limit the amount of current available to the motor.
14 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
Automatic switching frequency modulation regulates these conditions automatically to provide the highest switching frequency without overheating the drive. By providing a regulated high switching frequency, it quiets motor operating noise at slow speeds, when audible noise control is critical, and produces full output power to the motor when required.
5.1.11 Automatic Derating for High
Switching Frequency
The drive is designed for continuous, full-load operation at switching frequencies between 1.5 kHz–2 kHz for 380–500
V, and 1 kHz–1.5 kHz for 525–690V. The frequency range depends on power size and voltage rating. A switching frequency exceeding the maximum allowed range generates increased heat in the drive and requires the output current to be derated.
An automatic feature of the drive is load-dependent switching frequency control. This feature allows the motor to benefit from as high a switching frequency as the load allows.
5.1.12 Power Fluctuation Performance
The drive withstands mains fluctuations such as:
•
Transients.
•
Momentary drop-outs.
•
Short voltage drops.
•
Surges.
The drive automatically compensates for input voltages
± 10% from the nominal to provide full rated motor voltage and torque. With auto restart selected, the drive automatically powers up after a voltage trip. With flying start, the drive synchronizes to motor rotation before start.
5.1.13 Resonance Damping
Resonance damping eliminates the high-frequency motor resonance noise. Automatic or manually selected frequency damping is available.
5.1.14 Temperature-controlled Fans
Sensors in the drive regulate the operation of the internal cooling fans. Often, the cooling fans do not run during low load operation, or when in sleep mode or standby. These sensors reduce noise, increase efficiency, and extend the operating life of the fan.
5.1.15 EMC Compliance
Electromagnetic interference (EMI) and radio frequency interference (RFI) are disturbances that can affect an electrical circuit due to electromagnetic induction or radiation from an external source. The drive is designed to comply with the EMC product standard for drives IEC
61800-3 and the European standard EN 55011. Motor cables must be shielded and properly terminated to comply with the emission levels in EN 55011. For more information regarding EMC performance, see
chapter 10.14.1 EMC Test Results .
5.1.16 Galvanic Isolation of Control
Terminals
All control terminals and output relay terminals are galvanically isolated from mains power, which completely protects the controller circuitry from the input current. The output relay terminals require their own grounding. This isolation meets the stringent protective extra-low voltage
(PELV) requirements for isolation.
The components that make up the galvanic isolation are:
•
Supply, including signal isolation.
•
Gatedrive for the IGBTs, trigger transformers, and optocouplers.
•
The output current Hall effect transducers.
5.2 Custom Application Features
Custom application functions are the most common features programmed in the drive for enhanced system performance. They require minimum programming or setup. See the programming guide for instructions on activating these functions.
5.2.1 Automatic Motor Adaptation
Automatic motor adaptation (AMA) is an automated test procedure used to measure the electrical characteristics of the motor. AMA provides an accurate electronic model of the motor, allowing the drive to calculate optimal performance and efficiency. Running the AMA procedure also maximizes the automatic energy optimization feature of the drive. AMA is performed without the motor rotating and without uncoupling the load from the motor.
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
15
Product Features VLT® AutomationDrive FC 302
5 5
5.2.2 Built-in PID Controller
The built-in proportional, integral, derivative (PID) controller eliminates the need for auxiliary control devices.
The PID controller maintains constant control of closed loop systems where regulated pressure, flow, temperature, or other system requirements must be maintained.
The drive can use 2 feedback signals from 2 different devices, allowing the system to be regulated with different feedback requirements. The drive makes control decisions by comparing the 2 signals to optimize system performance.
5.2.3 Motor Thermal Protection
Motor thermal protection can be provided via:
•
Direct temperature sensing using a
PTC- or KTY sensor in the motor windings and connected on a standard
AI or DI.
PT100 or PT1000 in the motor windings and motor bearings, connected on VLT ®
Sensor Input Card MCB 114.
PTC Thermistor input on VLT ® PTC
Thermistor Card MCB 112 (ATEX approved).
•
Mechanical thermal switch (Klixon type) on a DI.
•
Built-in electronic thermal relay (ETR).
ETR calculates motor temperature by measuring current, frequency, and operating time. The drive shows the thermal load on the motor in percentage and can issue a warning at a programmable overload setpoint.
Programmable options at the overload allow the drive to stop the motor, reduce output, or ignore the condition.
Even at low speeds, the drive meets I2t Class 20 electronic motor overload standards.
16 t [s]
2000
1000
600
500
400
300
200
100
60
50
40
30
20
10
1.0
1.2
1.4
1.6
1.8
Illustration 5.1 ETR Characteristics
2.0
fOUT = 1 x f M,N(par. 1-23) fOUT = 2 x f M,N fOUT = 0.2 x f M,N
I
MN
I
M
(par. 1-24)
The X-axis shows the ratio between I motor
and I motor nominal. The Y-axis shows the time in seconds before the
ETR cuts off and trips the drive. The curves show the characteristic nominal speed, at twice the nominal speed and at 0.2 x the nominal speed.
At lower speed, the ETR cuts off at lower heat due to less cooling of the motor. In that way, the motor is protected from being overheated even at low speed. The ETR feature calculates the motor temperature based on actual current and speed. The calculated temperature is visible as a readout parameter in parameter 16-18 Motor Thermal .
A special version of the ETR is also available for EX-e motors in ATEX areas. This function makes it possible to enter a specific curve to protect the Ex-e motor. See the pogramming guide for set-up instructions.
5.2.4 Motor Thermal Protection for Ex-e
Motors
The drive is equipped with an ATEX ETR thermal monitoring function for operation of Ex-e motors according to EN-60079-7. When combined with an ATEX approved
PTC monitoring device such as the VLT ® MCB 112 PTC option or an external device, the installation does not require an individual approval from an approbated organization.
The ATEX ETR thermal monitoring function enables use of an Ex-e motor instead of a more expensive, larger, and heavier Ex-d motor. The function ensures that the drive limits motor current to prevent overheating.
Requirements related to the Ex-e motor
•
Ensure that the Ex-e motor is approved for operation in hazardous zones (ATEX zone 1/21,
ATEX zone 2/22) with drives. The motor must be certified for the specific hazardous zone.
•
Install the Ex-e motor in zone 1/21 or 2/22 of the hazardous zone, according to motor approval.
Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
NOTICE
Install the drive outside the hazardous zone.
•
Ensure that the Ex-e motor is equipped with an
ATEX-approved motor overload protection device.
This device monitors the temperature in the motor windings. If there is a critical temperature level or a malfunction, the device switches off the motor.
The VLT ® PTC Thermistor MCB 112 option provides ATEX-approved monitoring of motor temperature. It is a prerequisite that the drive is equipped with 3–6 PTC thermistors in series according to DIN 44081 or 44082.
Alternatively, an external ATEX-approved
PTC protection device can be used.
•
Sine-wave filter is required when
Long cables (voltage peaks) or increased mains voltage produce voltages exceeding the maximum allowable voltage at motor terminals.
Minimum switching frequency of the drive does not meet the requirement stated by the motor manufacturer. The minimum switching frequency of the drive is shown as the default value in parameter 14-01 Switching Frequency .
Compatibility of motor and drive
For motors certified according to EN-60079-7, a data list including limits and rules is supplied by the motor manufacturer as a data sheet, or on the motor nameplate.
During planning, installation, commissioning, operation, and service, follow the limits and rules supplied by the manufacturer for:
•
Minimum switching frequency.
•
Maximum current.
•
Minimum motor frequency.
•
Maximum motor frequency.
shows where the requirements are indicated on the motor nameplate.
3
4
1
2
СЄ 1180 xЗ
CONVERTER SUPPLY
VALID FOR 380 - 415V FWP 50Hz
3 ~ Motor
MIN. SWITCHING FREQ. FOR PWM CONV. 3kHz l = 1.5XI
M,N
t
OL
= 10s t
COOL
= 10min
MIN. FREQ. 5Hz MAX. FREQ. 85 Hz
Ex-e ll T3 f [Hz]
PTC
Ix/I
M,N
PWM-CONTROL
5 15
0.4
0.8
°C DIN 44081/-82
25
1.0
50
1.0
85
0.95
1 Minimum switching frequency
2 Maximum current
3 Minimum motor frequency
4 Maximum motor frequency
Illustration 5.2 Motor Nameplate showing Drive Requirements
When matching drive and motor, Danfoss specifies the following extra requirements to ensure adequate motor thermal protection:
•
Do not exceed the maximum allowed ratio between drive size and motor size. The typical value is I
VLT, n
≤ 2x I m,n
•
Consider all voltage drops from drive to motor. If the motor runs with lower voltage than listed in the U/f characteristics, current can increase, triggering an alarm.
For further information, see the application example in
chapter 12 Application Examples .
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
17
Product Features VLT® AutomationDrive FC 302
5 5
5.2.5 Mains Drop-out
During a mains drop-out, the drive keeps running until the
DC-link voltage drops below the minimum stop level. The minimum stop level is typically 15% below the lowest rated supply voltage. The mains voltage before the dropout and the motor load determines how long it takes for the drive to coast.
The drive can be configured ( parameter 14-10 Mains Failure ) to different types of behavior during mains drop-out:
•
Trip Lock once the DC link is exhausted.
•
Coast with flying start whenever mains return
( parameter 1-73 Flying Start ).
•
Kinetic back-up.
•
Controlled ramp down.
Flying start
This selection makes it possible to catch a motor that is spinning freely due to a mains drop-out. This option is relevant for centrifuges and fans.
Kinetic back-up
This selection ensures that the drive runs as long as there is energy in the system. For short mains drop-out, the operation is restored after mains return, without bringing the application to a stop or losing control at any time.
Several variants of kinetic back-up can be selected.
Configure the behavior of the drive at mains drop-out, in parameter 14-10 Mains Failure and parameter 1-73 Flying
Start .
5.2.6 Automatic Restart
The drive can be programmed to restart the motor automatically after a minor trip, such as momentary power loss or fluctuation. This feature eliminates the need for manual resetting, and enhances automated operation for remotely controlled systems. The number of restart attempts and the duration between attempts can be limited.
5.2.7 Full Torque at Reduced Speed
The drive follows a variable V/Hz curve to provide full motor torque even at reduced speeds. Full output torque can coincide with the maximum designed operating speed of the motor. This drive differs from variable torque drives and constant torque drives. Variable torque drives provide reduced motor torque at low speed. Constant torque drives provide excess voltage, heat, and motor noise at less than full speed.
5.2.8 Frequency Bypass
In some applications, the system can have operational speeds that create a mechanical resonance. This mechanical resonance can generate excessive noise and possibly damage mechanical components in the system.
The drive has 4 programmable bypass-frequency bandwidths. The bandwidths allow the motor to step over speeds that induce system resonance.
5.2.9 Motor Preheat
To preheat a motor in a cold or damp environment, a small amount of DC current can be trickled continuously into the motor to protect it from condensation and cold starts. This function can eliminate the need for a space heater.
5.2.10 Programmable Set-ups
The drive has 4 set-ups that can be independently programmed. Using multi-setup, it is possible to switch between independently programmed functions activated by digital inputs or a serial command. Independent set-ups are used, for example, to change references, or for day/ night or summer/winter operation, or to control multiple motors. The LCP shows the active set-up.
Set-up data can be copied from drive to drive by downloading the information from the removable LCP.
5.2.11 Smart Logic Control (SLC)
Smart logic control (SLC) is a sequence of user-defined actions (see parameter 13-52 SL Controller Action [x]) executed by the SLC when the associated user-defined event (see parameter 13-51 SL Controller Event [x]) is evaluated as TRUE by the SLC.
The condition for an event can be a particular status, or that the output from a logic rule or a comparator operand becomes TRUE. The condition leads to an associated action as shown in
.
18 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
Par. 13-51
SL Controller Event
Running
Warning
Torque limit
Digital input X 30/2
. . .
Par. 13-43
Logic Rule Operator 2
. . .
. . .
Par. 13-11
Comparator Operator
=
TRUE longer than..
. . .
. . .
Illustration 5.3 SLC Event and Action
Par. 13-52
SL Controller Action
Coast
Start timer
Set Do X low
Select set-up 2
. . .
Events and actions are each numbered and linked in pairs
(states), which means that when event [0] is fulfilled
(attains the value TRUE), action [0] is executed. After the 1 st action is executed, the conditions of the next event are evaluated. If this event is evaluated as true, then the corresponding action is executed. Only 1 event is evaluated at any time. If an event is evaluated as false, nothing happens in the SLC during the current scan interval and no other events are evaluated. When the SLC starts, it only evaluates event [0] during each scan interval.
Only when event [0] is evaluated as true, the SLC executes action [0] and starts evaluating the next event. It is possible to program 1–20 events and actions.
When the last event/action has been executed, the sequence starts over again from event [0]/action [0].
shows an example with 4 event/actions:
Start event P13-01
13-51.0
13-52.0
13-51.1
13-52.1
Stop event P13-02
State 4
13-51.3
13-52.3
State 3
13-52.2
Stop event P13-02
Illustration 5.4 Order of Execution when 4 Events/Actions are
Programmed
Comparators
Comparators are used for comparing continuous variables
(output frequency, output current, analog input, and so on) to fixed preset values.
Par. 13-11
Comparator Operator
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
=
TRUE longer than.
. . .
. . .
Illustration 5.5 Comparators
Logic rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from timers, comparators, digital inputs, status bits, and events using the logical operators AND, OR, and NOT.
Par. 13-43
Logic Rule Operator 2
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-41
Logic Rule Operator 1
. . .
. . .
. . .
. . .
Par. 13-44
Logic Rule Boolean 3
Illustration 5.6 Logic Rules
5.2.12 Safe Torque Off
The Safe Torque Off (STO) function is used to stop the drive in emergency stop situations. The FC 302 drive can use the STO function with asynchronous, synchronous, and permanent magnet motors.
For more information about Safe Torque Off, including installation and commissioning, refer to the Safe Torque Off
Operating Guide .
Liability conditions
The customer is responsible for ensuring that personnel know how to install and operate the safe torque off function by:
•
Reading and understanding the safety regulations concerning health, safety, and accident prevention.
•
Understanding the generic and safety guidelines provided in the Safe Torque Off Operating Guide .
•
Having a good knowledge of the generic and safety standards for the specific application.
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
19
Product Features VLT® AutomationDrive FC 302
5 5
5.3 Dynamic Braking Overview
Dynamic braking slows the motor using 1 of the following methods:
•
AC brake
The brake energy is distributed in the motor by changing the loss conditions in the motor
( parameter 2-10 Brake Function = [2]). The AC brake function cannot be used in applications with high cycling frequency since this situation overheats the motor.
•
DC brake
An overmodulated DC current added to the AC current works as an eddy current brake
( parameter 2-02 DC Braking Time ≠ 0 s ).
•
Resistor brake
A brake IGBT keeps the overvoltage under a certain threshold by directing the brake energy from the motor to the connected brake resistor
( parameter 2-10 Brake Function = [1]). For more information on selecting a brake resistor, see VLT ®
Brake Resistor MCE 101 Design Guide .
For drives equipped with the brake option, a brake IGBT along with terminals 81(R-) and 82(R+) are included for connecting an external brake resistor.
The function of the brake IGBT is to limit the voltage in the
DC link whenever the maximum voltage limit is exceeded.
It limits the voltage by switching the externally mounted resistor across the DC bus to remove excess DC voltage present on the bus capacitors.
External brake resistor placement has the advantages of selecting the resistor based on application need, dissipating the energy outside of the control panel, and protecting the drive from overheating if the brake resistor is overloaded.
The brake IGBT gate signal originates on the control card and is delivered to the brake IGBT via the power card and gatedrive card. Also, the power and control cards monitor the brake IGBT for a short circuit. The power card also monitors the brake resistor for overloads.
20 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
5.4 Mechanical Holding Brake Overview
A mechanical holding brake is an external piece of equipment mounted directly on the motor shaft that performs static braking. Static braking is when a brake is used to clamp down on the motor after the load has been stopped. A holding brake is either controlled by a PLC or directly by a digital output from the drive.
NOTICE
A drive cannot provide a safe control of a mechanical brake. A redundancy circuitry for the brake control must be included in the installation.
5.4.1 Mechanical Brake Using Open Loop Control
For hoisting applications, typically it is necessary to control an electro-magnetic brake. A relay output (relay 1 or relay 2) or a programmed digital output (terminal 27 or 29) is required. Normally, this output must be closed for as long as the drive is unable to hold the motor. In parameter 5-40 Function Relay (array parameter), parameter 5-30 Terminal 27 Digital Output , or parameter 5-31 Terminal 29 Digital Output , select [32] mechanical brake control for applications with an electro-magnetic brake.
When [32] mechanical brake control is selected, the mechanical brake relay remains closed during start until the output current is above the level selected in parameter 2-20 Release Brake Current . During stop, the mechanical brake closes when the speed is below the level selected in parameter 2-21 Activate Brake Speed [RPM] . If the drive is brought into an alarm condition, such as an overvoltage situation, the mechanical brake immediately cuts in. The mechanical brake also cuts in during safe torque off.
Consider the following when using the electro-magnetic brake:
•
Use any relay output or digital output (terminal 27 or 29). If necessary, use a contactor.
•
Ensure that the output is switched off as long as the drive is unable to rotate the motor. Examples include the load being too heavy or the motor not being mounted.
•
Before connecting the mechanical brake, select [32] Mechanical brake control in parameter group 5-4* Relays (or in parameter group 5-3* Digital Outputs ).
•
The brake is released when the motor current exceeds the preset value in parameter 2-20 Release Brake Current .
•
The brake is engaged when the output frequency is less than the frequency set in parameter 2-21 Activate Brake
Speed [RPM] or parameter 2-22 Activate Brake Speed [Hz] and only if the drive carries out a stop command.
NOTICE
For vertical lifting or hoisting applications, ensure that the load can be stopped if there is an emergency or a malfunction. If the drive is in alarm mode or in an overvoltage situation, the mechanical brake cuts in.
For hoisting applications, make sure that the torque limits in parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode are set lower than the current limit in parameter 4-18 Current Limit . It is also recommended to set parameter 14-25 Trip Delay at Torque Limit to 0, parameter 14-26 Trip Delay at Inverter Fault to 0, and parameter 14-10 Mains Failure to [3] Coasting .
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
21
Product Features VLT® AutomationDrive FC 302
5 5
Start term.18
Par 1-71
Start delay time
1=on
0=off
Shaft speed
Par 1-74
Start speed
Output current
Pre-magnetizing current or
DC hold current
Par 2-23
Brake delay time
Par 1-76 Start current/
Par 2-00 DC hold current
Reaction time EMK brake
Relay 01
Mechanical brake locked
Mechanical brake free on off
Illustration 5.7 Mechanical Brake Control in Open Loop
Par 2-20
Release brake current
Par 2-21
Activate brake speed
Time
5.4.2 Mechanical Brake Using Closed Loop Control
The VLT ® AutomationDrive features a mechanical brake control designed for hoisting applications and supports the following functions:
•
2 channels for mechanical brake feedback, offering protection against unintended behavior resulting from a broken cable.
•
Monitoring the mechanical brake feedback throughout the complete cycle. Monitoring helps protect the mechanical brake - especially if more drives are connected to the same shaft.
•
No ramp up until feedback confirms that mechanical brake is open.
•
Improved load control at stop.
•
The transition when motor takes over the load from the brake can be configured.
Parameter 1-72 Start Function [6] Hoist Mech. Brake Rel activates the hoist mechanical brake. The main difference compared to the regular mechanical brake control is that the hoist mechanical brake function has direct control over the brake relay.
Instead of setting a current to release the brake, the torque applied against the closed brake before release is defined.
Because the torque is defined directly, the set-up is more straightforward for hoisting applications.
22 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
The hoist mechanical brake strategy is based on the following 3-step sequence, where motor control and brake release are synchronized to obtain the smoothest possible brake release.
1.
2.
3.
Pre-magnetize the motor.
To ensure that there is a hold on the motor and to verify that it is mounted correctly, the motor is first premagnetized.
Apply torque against the closed brake.
When the load is held by the mechanical brake, its size cannot be determined, only its direction. The moment the brake opens, the motor must take over the load. To facilitate the takeover, a user-defined torque
( parameter 2-26 Torque Ref ) is applied in the hoisting direction. This process is used to initialize the speed controller that finally takes over the load. To reduce wear on the gearbox due to backlash, the torque is ramped up.
Release the brake.
When the torque reaches the value set in parameter 2-26 Torque Ref , the brake is released. The value set in parameter 2-25 Brake Release Time determines the delay before the load is released. To react as quickly as possible on the load-step that follows after brake release, the speed-PID control can be boosted by increasing the proportional gain.
5 5
Motor
Speed Torque Ramp
Up Time p. 2-27
Torque Ref. p. 2-26
Brake Release
Time p. 2-25
Ramp 1 Up
P. 3-41
W22
Active
Torque
Ref.
Brake
Relay
High
Low
Contact no.1
E.g. DI32 [70] Mech. Brake Feedback
Mech Brake
Feedback
High
Low
Contact no.2
OPTIONAL
E.g. DI33 [71] Mech. Brake Feedback
Mech Brake
Position
Open
Closed
Gain Boost. p. 2-28
Gain Boost or
Postion Control
Illustration 5.8 Brake Release Sequence for Hoist Mechanical Brake Control
A22
Active
Ramp 1 Down
P. 3-42
Stop Delay
P. 2-24
Activate Brake
Delay
P. 2-23
Torque Ramp
Down Time
p. 2-29
A22
Active W22
Active
Parameter 2-26 Torque Ref to parameter 2-33 Speed PID Start Lowpass Filter Time are only available for the hoist mechanical brake control (FLUX with motor feedback). Parameter 2-30 Position P Start Proportional Gain to parameter 2-33 Speed PID Start
Lowpass Filter Time can be set up for smooth transition change from speed control to position control during parameter 2-25 Brake Release Time - the time when the load is transferred from the mechanical brake to the drive.
Parameter 2-30 Position P Start Proportional Gain to parameter 2-33 Speed PID Start Lowpass Filter Time are activated when parameter 2-28 Gain Boost Factor is set to 0. See
for more information.
NOTICE
For an example of advanced mechanical brake control for hoisting applications, see
chapter 12 Application Examples .
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
23
Product Features VLT® AutomationDrive FC 302
5 5
5.5 Load Share Overview
Load share is a feature that allows the connection of DC circuits of several drives, creating a multiple-drive system to run 1 mechanical load. Load share provides the following benefits:
Energy savings
A motor running in regenerative mode can supply drives that are running in motoring mode.
Reduced need for spare parts
Usually, only 1 brake resistor is needed for the entire drive system instead of 1 brake resistor for per drive.
Power back-up
If there is mains failure, all linked drives can be supplied through the DC link from a back-up. The application can continue running or go though a controlled shutdown process.
Preconditions
The following preconditions must be met before load sharing is considered:
•
The drive must be equipped with load sharing terminals.
•
Product series must be the same. Only VLT ® AutomationDrive drives used with other VLT ® AutomationDrive drives.
•
Drives must be placed physically close to one another to allow the wiring between them to be no longer than 25 m (82 ft).
•
Drives must have the same voltage rating.
•
When adding a brake resistor in a load sharing configuration, all drives must be equipped with a brake chopper.
•
Fuses must be added to load share terminals.
For a diagram of a load share application in which best practices are applied, see
DC connecting point for additional drives in the load sharing application
2x aR-1000 A 2x aR-1500 A
315 kW
FC 302
500 kW
FC 302
3x 1.2%
3x Class L-800 A
91
92
93
82 81
96
97
98
M
380 V
Common mains disconnect switch
Illustration 5.9 Diagram of a Load Share Application Where Best Practices are Applied
91
92
93
82 81
3x 1.2%
96
97
98
3x Class L-1200 A
M
Mains connecting point for additional drives in the load sharing application
24 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Product Features Design Guide
Load sharing
Units with the built-in load sharing option contain terminals (+) 89 DC and (–) 88 DC. Within the drive, these terminals connect to the DC bus in front of the DC-link reactor and bus capacitors.
The load sharing terminals can connect in 2 different configurations.
•
Terminals tie the DC-bus circuits of multiple drives together. This configuration allows a unit that is in a regenerative mode to share its excess bus voltage with another unit that is running a motor. Load sharing in this manner can reduce the need for external dynamic brake resistors, while also saving energy. The number of units that can be connected in this way is infinite, as long as each unit has the same voltage rating. In addition, depending on the size and number of units, it may be necessary to install DC reactors and DC fuses in the DC-link connections, and AC reactors on the mains. Attempting such a configuration requires specific considerations.
•
The drive is powered exclusively from a DC source. This configuration requires:
A DC source.
A means to soft charge the DC bus at power-up.
5.6 Regen Overview
Regen typically occurs in applications with continuous braking such as cranes/hoists, downhill conveyors, and centrifuges where energy is pulled out of a decelerated motor.
The excess energy is removed from the drive using 1 of the following options:
•
Brake chopper allows the excess energy to be dissipated in the form of heat within the brake resistor coils.
•
Regen terminals allow a 3 rd party regen unit to be connected to the drive, allowing the excess energy to be returned to the power grid.
Returning excess energy back to the power grid is the most efficient use of regenerated energy in applications using continuous braking.
5 5
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
25
Product Features VLT® AutomationDrive FC 302
5 5
5.7 Back-channel Cooling Overview
A unique back-channel duct passes cooling air over the heat sinks with minimal air passing through the electronics area.
There is an IP54/Type 12 seal between the back-channel cooling duct and the electronics area of the VLT ® drive. This backchannel cooling allows 90% of the heat losses to be exhausted directly outside the enclosure. This design improves reliability and prolongs component life by dramatically reducing interior temperatures and contamination of the electronic components.
shows the standard airflow configuration for an E1h–E4h drive.
Different back-channel cooling kits are available to redirect the airflow based on individual needs.
shows 2 optional airflow configurations for an E1h–E4h drive.
225 mm (8.9 in)
225 mm (8.9 in)
Illustration 5.10 Standard Airflow Configuration for E1h/E2h (Left) and E3h/E4h (Right)
225 mm (8.9 in)
225 mm (8.9 in)
26
Illustration 5.11 Optional Airflow Configuration Through the Back Wall for E1h/E2h (Left) and E3h/E4h (Right)
Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Options and Accessories Ove...
Design Guide
6 Options and Accessories Overview
6.1 Fieldbus Devices
This section describes the fieldbus devices that are available with the VLT ® AutomationDrive series. Using a fieldbus device reduces system cost, delivers faster and more efficient communication, and provides an easier user interface. For ordering numbers, refer to
chapter 13.2 Ordering Numbers for Options and Accessories
.
6.1.1 VLT
®
PROFIBUS DP V1 MCA 101
The MCA 101 provides:
•
Wide compatibility, a high level of availability, support for all major PLC vendors, and compatibility with future versions.
•
Fast, efficient communication, transparent installation, advanced diagnosis, and parameterization and auto-configuration of process data via GSD file.
•
Acyclic parameterization using PROFIBUS DP-V1,
PROFdrive, or Danfoss FC profile state machines.
6.1.2 VLT
®
DeviceNet MCA 104
The MCA 104 provides:
•
Support of the ODVA AC drive profile supported via I/O instance 20/70 and 21/71 secures compatibility to existing systems.
•
Benefits from ODVA’s strong conformance testing policies that ensure products are interoperable.
6.1.3 VLT
®
CAN Open MCA 105
The MCA 105 option provides:
•
Standardized handling.
•
Interoperability.
•
Low cost.
This option is fully equipped with both high-priority access to control the drive (PDO communication) and to access all parameters through acyclic data (SDO communication).
For interoperability, the option uses the DSP 402 AC drive profile.
6.1.4 VLT
®
PROFIBUS Converter MCA 113
The MCA 113 option is a special version of the PROFIBUS options that emulates the VLT ® 3000 commands in the
VLT ® VLT ® AutomationDrive.
The VLT ® 3000 can be replaced by the VLT ®
AutomationDrive, or an existing system can be expanded without costly change of the PLC program. For upgrade to a different fieldbus, the installed converter can be removed and replaced with a new option. The MCA 113 option secures the investment without losing flexibility.
6.1.5 VLT
®
PROFIBUS Converter MCA 114
The MCA 114 option is a special version of the PROFIBUS options that emulates the VLT ® 5000 commands in the
VLT ® VLT ® AutomationDrive. This option supports DP-V1.
The VLT ® 5000 can be replaced by the VLT ®
AutomationDrive, or an existing system can be expanded without costly change of the PLC program. For upgrade to a different fieldbus, the installed converter can be removed and replaced with a new option. The MCA 114 option secures the investment without losing flexibility.
6.1.6 VLT
®
PROFINET MCA 120
The MCA 120 option combines the highest performance with the highest degree of openness. The option is designed so that many of the features from the VLT ®
PROFIBUS MCA 101 can be reused, minimizing user effort to migrate PROFINET and securing the investment in a PLC program.
•
Same PPO types as the VLT ® PROFIBUS DP V1
MCA 101 for easy migration to PROFINET.
•
Built-in web server for remote diagnosis and reading out of basic drive parameters.
•
Supports MRP.
•
Supports DP-V1. Diagnostic allows easy, fast, and standardized handling of warning and fault information into the PLC, improving bandwidth in the system.
•
Supports PROFIsafe when combined with VLT ®
Safety Option MCB 152.
•
Implementation in accordance with Conformance
Class B.
6 6
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
27
Options and Accessories Ove...
VLT® AutomationDrive FC 302
6 6
6.1.7 VLT
®
EtherNet/IP MCA 121
Ethernet is the future standard for communication at the factory floor. The VLT ® EtherNet/IP MCA 121 option is based on the newest technology available for industrial use and handles even the most demanding requirements.
EtherNet/IP™ extends standard commercial Ethernet to the
Common Industrial Protocol (CIP™) – the same upper-layer protocol and object model found in DeviceNet.
MCA 121 offers advanced features such as:
•
Built-in, high-performance switch enabling linetopology, which eliminates the need for external switches.
•
DLR Ring (from October 2015).
•
Advanced switch and diagnosis functions.
•
Built-in web server.
•
E-mail client for service notification.
•
Unicast and Multicast communication.
6.1.8 VLT
®
Modbus TCP MCA 122
The MCA 122 option connects to Modbus TCP-based networks. It handles connection intervals down to 5 ms in both directions, positioning it among the fastest performing Modbus TCP devices in the market. For master redundancy, it features hot swapping between 2 masters.
Other features include:
•
Built-in web-server for remote diagnosis and reading out basic drive parameters.
•
Email notification that can be configured to send an email message to 1 or more recipients when certain alarms or warnings occur, or when they are cleared.
•
Dual master PLC connection for redundancy.
6.1.9 VLT
®
POWERLINK MCA 123
The MCA 123 option represents the 2 nd generation of fieldbus. The high bit rate of industrial Ethernet can now be used to make the full power of IT technologies used in the automation world available for the factory world.
This fieldbus option provides high performance, real-time, and time synchronization features. Due to its CANopenbased communication models, network management, and device description model, it offers a fast communication network and the following features:
•
Dynamic motion control applications.
•
Material handling.
•
Synchronization and positioning applications.
6.1.10 VLT
®
EtherCAT MCA 124
The MCA 124 option offers connectivity to EtherCAT® based networks via the EtherCAT Protocol.
The option handles the EtherCAT line communication in full speed, and connection towards the drive with an interval down to 4 ms in both directions, allowing the MCA
124 to participate in networks ranging from low performance up to servo applications.
•
EoE Ethernet over EtherCAT support.
•
HTTP (hypertext transfer protocol) for diagnosis via built-in web server.
•
CoE (CAN over Ethernet) for access to drive parameters.
•
SMTP (simple mail transfer protocol) for e-mail notification.
•
TCP/IP for easy access to drive configuration data from MCT 10.
6.2 Functional Extensions
This section describes the functional extension options that are available with the VLT ® AutomationDrive series. For ordering numbers, refer to
chapter 13.2 Ordering Numbers for Options and Accessories
.
6.2.1 VLT
®
General Purpose I/O Module
MCB 101
The MCB 101 option offers an extended number of control inputs and outputs:
•
3 digital inputs 0–24 V: Logic 0 < 5 V; Logic 1 >
10 V.
•
2 analog inputs 0–10 V: Resolution 10 bits plus sign.
•
2 digital outputs NPN/PNP push-pull.
•
1 analog output 0/4–20 mA.
•
Spring-loaded connection.
28 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Options and Accessories Ove...
Design Guide
6.2.2 VLT
®
Encoder Input MCB 102
The MCB 102 option offers the possibility to connect various types of incremental and absolute encoders. The connected encoder can be used for closed-loop speed control and closed-loop flux motor control. The following encoder types are supported:
•
5 V TTL (RS 422)
•
1VPP SinCos
•
SSI
•
HIPERFACE
•
EnDat
6.2.3 VLT
®
Resolver Option MCB 103
The MCB 103 option enables connection of a resolver to provide speed feedback from the motor.
•
Primary voltage: 2–8 V rms
•
Primary frequency: 2.0–15 kHz
•
Primary maximum current: 50 mA rms
•
Secondary input voltage: 4 V rms
•
Spring-loaded connection
6.2.4 VLT
®
Relay Card MCB 105
The MCB 105 option extends relay functions with 3 more relay outputs.
•
Protects control cable connection.
•
Spring-loaded control wire connection.
Maximum switch rate (rated load/minimum load)
6 minutes -1 /20 s -1
Maximum terminal load
AC-1 resistive load: 240 V AC, 2 A
6.2.5 VLT
®
Safe PLC Interface Option
MCB 108
The MCB 108 option provides a safety input based on a single-pole 24 V DC input. For most applications, this input provides a way to implement safety in a cost-effective way.
For applications that work with more advanced products like Safety PLC and light curtains, the fail-safe PLC interface enables the connection of a 2-wire safety link. The PLC
Interface allows the fail-safe PLC to interrupt on the plus or the minus link without interfering with the sense signal of the fail-safe PLC.
6.2.6 VLT
®
PTC Thermistor Card MCB 112
The MCB 112 option provides extra motor monitoring compared to the built-in ETR function and thermistor terminal.
•
Protects the motor from overheating.
•
ATEX-approved for use with Ex-d and Ex-e motors
(EX-e only FC 302).
•
Uses Safe Torque Off function, which is approved in accordance with SIL 2 IEC 61508.
6.2.7 VLT
®
Sensor Input Option MCB 114
The MCB 114 option protects the motor from being overheated by monitoring the temperature of motor bearings and windings.
•
3 self-detecting sensor inputs for 2 or 3-wire
PT100/PT1000 sensors.
•
1 extra analog input 4–20 mA.
6.2.8 VLT
®
Safety Option MCB 150 and
MCB 151
MCB 150 and MCB 151 options expand the safe torque off functions, which are integrated in a standard VLT ®
AutomationDrive. Use the Safe Stop 1 (SS1) function to perform a controlled stop before removing torque. Use the
Safety-Limited Speed (SLS) function to monitor whether a specified speed is exceeded.
These options can be used up to PL d according to ISO
13849-1 and SIL 2 according to IEC 61508.
•
Extra standards-compliant safety functions.
•
Replacement of external safety equipment.
•
Reduced space requirements.
•
2 safe programmable inputs.
•
1 safe output (for T37).
•
Easier machine certification.
•
Drive can be powered continuously.
•
Safe LCP copy.
•
Dynamic commissioning report.
•
TTL (MCB 150) or HTL (MCB 151) encoder as speed feedback.
6 6
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
29
Options and Accessories Ove...
VLT® AutomationDrive FC 302
6 6
6.2.9 VLT
®
Safety Option MCB 152
The MCB 152 option activates safe torque off via the
PROFIsafe fieldbus with VLT ® PROFINET MCA 120 fieldbus option. It improves flexibility by connecting safety devices within a plant.
The safety functions of the MCB 152 are implemented according to EN IEC 61800-5-2. The MCB 152 supports
PROFIsafe functionality to activate integrated safety functions of the VLT ® AutomationDrive from any PROFIsafe host, up to Safety Integrity Level SIL 2 according to EN IEC
61508 and EN IEC 62061, and Performance Level PL d,
Category 3 according to EN ISO 13849-1.
•
PROFIsafe device (with MCA 120).
•
Replacement of external safety equipment.
•
2 safe programmable inputs.
•
Safe LCP copy.
•
Dynamic commissioning report.
6.3 Motion Control and Relay Cards
This section describes the motion control and relay card options that are available with the VLT ® AutomationDrive series. For ordering numbers, refer to
Numbers for Options and Accessories .
6.3.1 VLT
®
Motion Control Option MCO 305
The MCO 305 option is an integrated programmable motion controller that adds extra functionality for VLT ®
VLT ® AutomationDrive.
The MCO 305 option offers easy-to-use motion functions combined with programmability – an ideal solution for positioning and synchronizing applications.
•
Synchronization (electronic shaft), positioning, and electronic cam control.
•
2 separate interfaces supporting both incremental and absolute encoders.
•
1 encoder output (virtual master function).
•
10 digital inputs.
•
8 digital outputs.
•
Supports CANopen motion bus, encoders, and I/O modules.
•
Sends and receives data via fieldbus interface
(requires fieldbus option).
•
PC software tools for debugging and commissioning: program and cam editor.
•
Structured programming language with both cyclic and event-driven execution.
6.3.2 VLT
®
Synchronizing Controller
MCO 350
The MCO 350 option for VLT ® AutomationDrive expands the functional properties of the AC drive in synchronizing applications, and replaces traditional mechanical solutions.
•
Speed synchronizing.
•
Position (angle) synchronizing with or without marker correction.
•
On-line adjustable gear ratio.
•
On-line adjustable position (angle) offset.
•
Encoder output with virtual master function for synchronization of multiple followers.
•
Control via I/Os or fieldbus.
•
Home function.
•
Configuration and readout of status and data via the LCP.
6.3.3 VLT
®
Positioning Controller MCO 351
The MCO 351 option offers a host of user-friendly benefits for positioning applications in many industries.
•
Relative positioning.
•
Absolute positioning.
•
Touch-probe positioning.
•
End-limit handling (software and hardware).
•
Control via I/Os or fieldbus.
•
Mechanical brake handling (programmable hold delay).
•
Error handling.
•
Jog speed/manual operation.
•
Marker-related positioning.
•
Home function.
•
Configuration and readout of status and data via the LCP.
30 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Options and Accessories Ove...
Design Guide
6.3.4 VLT
®
Extended Relay Card MCB 113
The MCB 113 option adds inputs/outputs for increased flexibility.
•
7 digital inputs.
•
2 analog outputs.
•
4 SPDT relays.
•
Meets NAMUR recommendations.
•
Galvanic isolation capability.
6.4 Brake Resistors
In applications where the motor is used as a brake, energy is generated in the motor and sent back into the drive. If the energy cannot be transported back to the motor, it increases the voltage in the drive DC line. In applications with frequent braking and/or high inertia loads, this increase can lead to an overvoltage trip in the drive and, finally, a shutdown. Brake resistors are used to dissipate the excess energy resulting from the regenerative braking.
The resistor is selected based on its ohmic value, its power dissipation rate, and its physical size. Danfoss offers a wide variety of different resistors that are specially designed to
Danfoss drives. For ordering numbers and more information on how to dimension brake resistors, refer to the VLT ® Brake Resistor MCE 101 Design Guide .
6.5 Sine-wave Filters
When a drive controls a motor, resonance noise is heard from the motor. This noise, which is the result of the motor design, occurs every time an inverter switch in the drive is activated. The frequency of the resonance noise thus corresponds to the switching frequency of the drive.
Danfoss supplies a sine-wave filter to dampen the acoustic motor noise. The filter reduces the ramp-up time of the voltage, the peak load voltage (U
PEAK
), and the ripple current ( Δ I) to the motor, which means that current and voltage become almost sinusoidal. The acoustic motor noise is reduced to a minimum.
The ripple current in the sine-wave filter coils also causes some noise. Solve the problem by integrating the filter in a cabinet or enclosure.
For ordering numbers and more information on sine-wave filters, refer to the Output Filters Design Guide .
6.6 dU/dt Filters
Danfoss supplies dU/dt filters which are differential mode, low-pass filters that reduce motor terminal phase-to-phase peak voltages and reduce the rise time to a level that lowers the stress on the insulation at the motor windings.
This is a typical issue with set-ups using short motor cables.
Compared to sine-wave filters, the dU/dt filters have a cutoff frequency above the switching frequency.
For ordering numbers and more information on dU/dt filters, refer to the Output Filters Design Guide .
6.7 Common-mode Filters
High-frequency common-mode cores (HF-CM cores) reduce electromagnetic interference and eliminate bearing damage by electrical discharge. They are special nanocrystalline magnetic cores that have superior filtering performance compared to regular ferrite cores. The HF-CM core acts like a common-mode inductor between phases and ground.
Installed around the 3 motor phases (U, V, W), the common mode filters reduce high-frequency commonmode currents. As a result, high-frequency electromagnetic interference from the motor cable is reduced.
For ordering numbers refer to the Output Filters Design
Guide .
6.8 Harmonic Filters
The VLT ® Advanced Harmonic Filters AHF 005 & AHF 010 should not be compared with traditional harmonic trap filters. The Danfoss harmonic filters have been specially designed to match the Danfoss drives.
By connecting the AHF 005 or AHF 010 in front of a
Danfoss drive, the total harmonic current distortion generated back to the mains is reduced to 5% and 10%.
For ordering numbers and more information on how to dimension brake resistors, refer to the VLT
®
Advanced
Harmonic Filters AHF 005/AHF 010 Design Guide .
6.9 High-power Kits
High-power kits, such as back-wall cooling, space heater, mains shield, are available for these enclosures. See
chapter 13.2 Ordering Numbers for Options and Accessories
for a brief description and ordering numbers for all available kits.
6 6
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
31
Specifications VLT® AutomationDrive FC 302
7 Specifications
7 7
7.1 Electrical Data, 380–500 V
VLT ® AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s, normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 500 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload)
(at 400 V) [A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload)
(at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 500 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Maximum number and size of cables per phase (E1h)
Mains and motor without brake [mm 2 (AWG)] 1)
Mains and motor with brake [mm 2 (AWG)] 1)
Brake or regen [mm 2 (AWG)] 1)
Maximum number and size of cables per phase (E3h)
Mains and motor [mm 2 (AWG)] 1)
Brake [mm 2 (AWG)] 1)
Load share or regen [mm 2 (AWG)] 1)
Maximum external mains fuses [A] 2)
Estimated power loss at 400 V [W] 3), 4)
Estimated power loss at 460 V [W] 3), 4)
Efficiency 4)
Output frequency [Hz]
Heat sink overtemperature trip [ ° C ( ° F)]
Control card overtemperature trip [ ° C ( ° F)]
Power card overtemperature trip [ ° C ( ° F)]
Fan power card overtemperature trip [ ° C ( ° F)]
Active in-rush card overtemperature trip
[ ° C ( ° F)]
HO
600
900
540
810
416
430
468
578
520
N315
NO
315
450
355
E1h/E3h
355
500
400
658
724
590
649
456
470
511
634
569
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6178
5322
6928
5910
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
Table 7.1 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x380–500 V AC
HO
658
987
590
885
456
470
511
355
500
400
E1h/E3h
400
600
500
634
569
N355
NO
718
653
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6851
5846
8036
6933
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
745
820
678
746
516
540
587
HO
N400
NO
695
1043
678
1017
482
540
587
400
550
500
E1h/E3h
450
600
530
800
880
730
803
554
582
632
670
653
771
704
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
7297
7240
8783
7969
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
32 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Specifications Design Guide
VLT ® AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s, normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 500 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload)
(at 400 V) [A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload)
(at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA
(at 500 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Maximum number and size of cables per phase (E2h)
Mains and motor without brake [mm 2 (AWG)] 1)
Mains and motor with brake [mm 2 (AWG)] 1)
Brake or regen [mm 2 (AWG)] 1)
Maximum number and size of cables per phase (E4h)
Mains and motor [mm 2 (AWG)] 1)
Brake [mm 2 (AWG)] 1)
Load share or regen [mm 2 (AWG)] 1)
Maximum external mains fuses [A] 2)
Estimated power loss at 400 V [W] 3), 4)
Estimated power loss at 460 V [W] 3), 4)
Efficiency 4)
Output frequency [Hz]
Heat sink overtemperature trip [ ° C ( ° F)]
Control card overtemperature trip [ ° C ( ° F)]
Power card overtemperature trip [ ° C ( ° F)]
Fan power card overtemperature trip [ ° C ( ° F)]
Active in-rush card overtemperature trip [ ° C ( ° F)]
HO
450
600
530
800
1200
730
1095
554
582
632
771
704
N450
E2h/E4h
NO
500
650
560
880
968
780
858
610
621
675
848
752
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
8352
7182
1200
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
9473
7809
HO
500
650
560
880
1320
780
1170
610
621
675
848
752
N500
E2h/E4h
NO
560
750
630
990
1089
890
979
686
709
771
954
858
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
9449
7771
1200
0.98
0–590
100 (212)
80 (176)
85 (185)
85 (185)
85 (185)
11102
9236
Table 7.2 Electrical Data for Enclosures E2h/E4h, Mains Supply 3x380–500 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
3) Typical power loss is at normal conditions and expected to be within ± 15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
4) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
7 7
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
33
Specifications VLT® AutomationDrive FC 302
7 7
7.2 Electrical Data, 525–690 V
VLT ® AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s, normal overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload)
(at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum number and size of cables per phase (E1h)
Mains and motor without brake [mm 2 (AWG)] 1)
Mains and motor with brake [mm 2 (AWG)] 1)
Brake or regen [mm 2 (AWG)] 1)
Maximum number and size of cables per phase (E3h)
Mains and motor [mm 2 (AWG)] 1)
Brake [mm 2 (AWG)] 1)
Load share or regen [mm 2 (AWG)] 1)
Maximum external mains fuses [A] 2)
Estimated power loss at 600 V [W] 3)4)
Estimated power loss at 690 V [W] 3)4)
Efficiency 4)
Output frequency [Hz]
Heat sink overtemperature trip [ ° C ( ° F)]
Control card overtemperature trip [ ° C ( ° F)]
Power card overtemperature trip [ ° C ( ° F)]
Fan power card overtemperature trip [ ° C ( ° F)]
Active in-rush card overtemperature trip
[ ° C ( ° F)]
HO
395
593
380
570
376
378
454
381
366
366
N355
NO
315
400
355
E1h/E3h
355
450
450
470
517
450
495
448
448
538
453
434
434
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
4989 6062
4920 5939
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
Table 7.3 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x525–690 V AC
HO
429
644
410
615
409
408
490
355
400
400
E1h/E3h
400
500
500
413
395
395
N400
NO
504
482
482
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
5419 6879
5332
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
6715
85 (185)
523
575
500
550
498
498
598
HO
N500
NO
523
785
500
750
498
498
598
400
500
500
E1h/E3h
450
600
560
596
656
570
627
568
568
681
504
482
482
574
549
549
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6833 8076
6678
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
7852
85 (185)
34 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Specifications Design Guide
VLT ® AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s, normal overload=110% current during 60 s)
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload)
(at 575/690 V) [A]
Continuous kVA (at 550 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum number and size of cables per phase (E2h)
Mains and motor without brake [mm 2 (AWG)] 1)
Mains and motor with brake [mm 2 (AWG)] 1)
Brake or regen [mm 2 (AWG)] 1)
Maximum number and size of cables per phase (E4h)
Mains and motor [mm 2 (AWG)] 1)
Brake [mm 2 (AWG)] 1)
Load share or regen [mm 2 (AWG)] 1)
Maximum external mains fuses [A] 2)
Estimated power loss at 600 V [W] 3)4)
Estimated power loss at 690 V [W] 3)4)
Efficiency 4)
Output frequency [Hz]
Heat sink overtemperature trip [ ° C ( ° F)]
Control card overtemperature trip [ ° C ( ° F)]
Power card overtemperature trip [ ° C ( ° F)]
Fan power card overtemperature trip [ ° C ( ° F)]
Active in-rush card overtemperature trip
[ ° C ( ° F)]
HO
450
600
560
596
894
570
855
568
568
681
574
549
549
N560
E1h/E3h
NO
500
650
630
630
693
630
693
600
627
753
607
607
607
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
8069
7848
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
9208
8921
HO
500
650
630
659
989
630
945
628
627
753
635
607
607
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
8543
8363
N630
E2h/E4h
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
NO
560
750
710
763
839
730
803
727
727
872
735
704
704
10346
10066
HO
560
750
710
763
1145
730
1095
727
727
872
735
704
704
N710
E2h/E4h
NO
670
950
800
857
819
819
6x240 (6x500 mcm)
5x240 (5x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
10319
10060
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
12723
12321
Table 7.4 Electrical Data for Enclosures E1h–E4h, Mains Supply 3x525–690 V AC
1) American Wire Gauge.
2) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
3) Typical power loss is at normal conditions and expected to be within ± 15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
4) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
889
978
850
935
847
847
1016
7 7
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
35
Specifications VLT® AutomationDrive FC 302
7 7
7.3 Mains Supply
Mains supply (L1, L2, L3)
Supply voltage 380–500 V ±10%, 525–690 V ±10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cos Φ) near unity
Switching on input supply L1, L2, L3 (power ups)
Environment according to EN60664-1
50/60 Hz ±5%
3.0% of rated supply voltage 1)
≥0.9 nominal at rated load
(>0.98)
Maximum 1 time/2 minute
Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 480/600 V.
1) Calculations based on UL/IEC61800-3.
7.4 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
1) Dependent on voltage and power.
Torque characteristics
Starting torque (constant torque)
Overload torque (constant torque)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
0–100% of supply voltage
0–590 Hz 1)
Unlimited
0.01–3600 s
Maximum 150% for 60 s 1)2)
Maximum 150% for 60 s 1)2)
7.5 Ambient Conditions
Environment
E1h/E2h enclosure
E3h/E4h enclosure
Vibration test (standard/ruggedized)
Relative humidity
Aggressive environment (IEC 60068-2-43) H
2
S test
Aggressive gases (IEC 60721-3-3)
Test method according to IEC 60068-2-43
Ambient temperature (at SFAVM switching mode)
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
- with derating
- with full output power of typical EFF2 motors (up to 90% output current)
- at full continuous FC output current
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
IP21/Type 1, IP54/Type 12
IP20/Chassis
Class Kd
Class 3C3
H2S (10 days)
Maximum 55 °
0.7 g/1.0 g
C (131 ° F) 1)
Maximum 50 ° C (122 ° F) 1)
Maximum 45 ° C (113 ° F) 1)
0 ° C (32 ° F)
10 ° C (50 ° F)
-25 to +65/70 ° C (13 to 149/158 ° F)
1000 m (3281 ft)
3000 m (9842 ft)
1) For more information on derating, see chapter 9.6 Derating.
EMC standards, Emission EN 61800-3
36 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Specifications Design Guide
EMC standards, Immunity
Energy efficiency class 1)
1) Determined according to EN 50598-2 at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
7.6 Cable Specifications
Cable lengths and cross-sections for control cables 1)
Maximum motor cable length, shielded/armored
Maximum motor cable length, unshielded/unarmored
Maximum cross-section to motor, mains, load sharing, and brake
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
1) For power cables, see electrical data in chapter 7 Specifications.
EN 61800-3
IE2
150 m (492 ft)
300 m (984 ft)
See
1.5 mm 2 /16 AWG (2x0.75 mm 2 )
1 mm 2 /18 AWG
0.5 mm 2 /20 AWG
0.25 mm 2 /23 AWG
7.7 Control Input/Output and Control Data
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic 1 NPN
Maximum voltage on input
Input resistance, R i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as outputs.
4 (6)
18, 19, 27 1) , 29 1) , 32, 33
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
Approximately 4 k Ω
Analog inputs
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
Maximum voltage
Current mode
Current level
Input resistance, R
Maximum current i i
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
2
53, 54
Voltage or current
Switches A53 and A54
Switch A53/A54=(U)
-10 V to +10 V (scaleable)
Approximately 10 k Ω
± 20 V
Switch A53/A54=(I)
0/4 to 20 mA (scaleable)
Approximately 200 Ω
30 mA
10 bit (+ sign)
Maximum error 0.5% of full scale
100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
7 7
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
37
Specifications VLT® AutomationDrive FC 302
PELV isolation
+24 V
18
Control
37
Functional isolation
RS485
Illustration 7.1 PELV Isolation
High voltage
Mains
Motor
DC-bus
7 7
Pulse inputs
Programmable pulse inputs
Terminal number pulse
Maximum frequency at terminal 29, 33 (push-pull driven)
Maximum frequency at terminal 29, 33 (open collector)
Minimum frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R i
Pulse input accuracy (0.1–1 kHz)
2
29, 33
110 kHz
5 kHz
4 Hz
See Digital Inputs in
chapter 7.7 Control Input/Output and Control Data
28 V DC
Approximately 4 k Ω
Maximum error: 0.1% of full scale
Analog output
Number of programmable analog outputs
Terminal number
Current range at analog output
Maximum resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
1
42
0/4–20 mA
500 Ω
Maximum error: 0.8% of full scale
8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication
Terminal number
Terminal number 61
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
2
27, 29 1)
0–24 V
40 mA
1 k Ω
10 nF
0 Hz
32 kHz
Maximum error: 0.1% of full scale
12 bit
38 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Specifications Design Guide
Control card, 24 V DC output
Terminal number
Maximum load
12, 13
200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.
Relay outputs
Programmable relay outputs
Maximum cross-section to relay terminals
Minimum cross-section to relay terminals
Length of stripped wire
Relay 01 terminal number
Maximum terminal load (AC-1) 1) on 1–2 (NO) (Resistive load) 2)3)
Maximum terminal load (AC-15) 1) on 1–2 (NO) (Inductive load @ cos φ 0.4)
Maximum terminal load (DC-1) 1) on 1–2 (NO) (Resistive load)
Maximum terminal load (DC-13) 1) on 1–2 (NO) (Inductive load)
Maximum terminal load (AC-1) 1) on 1–3 (NC) (Resistive load)
Maximum terminal load (AC-15) 1) on 1–3 (NC) (Inductive load @ cos φ 0.4)
Maximum terminal load (DC-1) 1) on 1–3 (NC) (Resistive load)
Maximum terminal load (DC-13) 1) on 1–3 (NC) (Inductive load)
Minimum terminal load on 1–3 (NC), 1–2 (NO)
Environment according to EN 60664-1
Relay 02 terminal number
Maximum terminal load (AC-1) 1) on 4–5 (NO) (Resistive load) 2)3)
Maximum terminal load (AC-15) 1) on 4–5 (NO) (Inductive load @ cos φ 0.4)
Maximum terminal load (DC-1) 1) on 4–5 (NO) (Resistive load)
Maximum terminal load (DC-13) 1) on 4–5 (NO) (Inductive load)
Maximum terminal load (AC-1) 1) on 4–6 (NC) (Resistive load)
Maximum terminal load (AC-15) 1) on 4–6 (NC) (Inductive load @ cos φ 0.4)
Maximum terminal load (DC-1) 1) on 4–6 (NC) (Resistive load)
Maximum terminal load (DC-13) 1) on 4–6 (NC) (Inductive load)
Minimum terminal load on 4–6 (NC), 4–5 (NO)
Environment according to EN 60664-1
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
1) IEC 60947 part 4 and 5.
2) Overvoltage Category II.
3) UL applications 300 V AC 2 A.
2
2.5 mm 2 (12 AWG)
0.2 mm 2 (30 AWG)
8 mm (0.3 in)
1–3 (break), 1–2 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
4–6 (break), 4–5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 2 mA
Overvoltage category III/pollution degree 2
Control card, +10 V DC output
Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–1000 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed accuracy (open loop)
All control characteristics are based on a 4-pole asynchronous motor.
10.5 V ±
50
0.5 V
25 mA
± 0.003 Hz
≤ 2 ms
1:100 of synchronous speed
30–4000 RPM: Maximum error of ± 8 RPM
7 7
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
39
7 7
Specifications VLT® AutomationDrive FC 302
Control card performance
Scan interval 5 ms
Control card, USB serial communication
USB standard
USB plug
1.1 (full speed)
USB type B device plug
NOTICE
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB connector on the drive or an isolated USB cable/converter.
40 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
8 Exterior and Terminal Dimensions
8.1 E1h Exterior and Terminal Dimensions
8.1.1 E1h Exterior Dimensions
22 (0.8)
3X 13 (0.5)
2043
(80.4)
2002
(78.8)
1553
(61.1)
1393
(54.9)
912
(35.9)
393 (15.5)
602 (23.7)
Illustration 8.1 Front View of E1h
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
41
8 8
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
2X 20 (0.8)
2X 101 (4.0)
2X 9 (0.7)
8 8
1
1 Knockout panel
Illustration 8.2 Side View of E1h
2X
280 (11.0)
513
(20.2)
567
(22.3)
2X
35 (1.4)
2X
190 (7.5)
2X
125 (4.9)
42 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
96 (3.8)
206
(8.1)
412 (16.2)
18 (0.7)
168 (6.6)
154 (6.1)
1
168 (6.6)
1800 (70.9)
1209 (47.6)
601 (23.7)
4X 73 (2.8)
69 (2.7)
1 Heat sink access panel (optional)
Illustration 8.3 Back View of E1h
4X 457 (18.0)
464 (18.3)
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
43
8 8
8 8
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
750 (29.5)
558
(22.0)
75
A
22 (0.8)
137
(5.4)
412 (16.2)
560 (22.0)
184
(7.3)
424
(16.7)
17 (0.7)
A
14 (0.6)
11 (0.4)
1
293 (11.5)
173 (6.8)
22 (0.8) 560 (22.0)
1 Gland plate
Illustration 8.4 Door Clearance and Gland Plate Dimensions for E1h
44 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
8.1.2 E1h Terminal Dimensions
Design Guide
1
6X 613 (24.1)
515 (20.3)
485 (19.1)
200 (7.9)
0 (0.0)
1
2
Mains terminals
Brake or regen terminals
Illustration 8.5 E1h Terminal Dimensions (Front View)
3
4
Motor terminals
Ground terminals, M10 nut
721 (28.4)
2
3
4
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
45
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
649 (25.5) 649 (25.5)
8 8
0 (0.0) 0 (0.0)
5X 14 (0.5)
44 (1.8)
0 (0.0)
36 (1.4)
Illustration 8.6 E1h Terminal Dimensions (Side Views)
A
A
46 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
8.2 E2h Exterior and Terminal Dimensions
8.2.1 E2h Exterior Dimensions
97
(3.8)
3X 13 (0.5)
2043
(80.4)
2002
(78.8)
1553
(61.1)
1393
(54.9)
912
(35.9)
394
(15.5)
698
(27.5)
Illustration 8.7 Front View of E2h
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
47
8 8
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
2X 20 (0.8)
2X 101 (4.0)
2X 9 (0.7)
8 8
1
1 Knockout panel
Illustration 8.8 Side View of E2h
2X
280 (11.0)
513
(20.2)
567
(22.3)
2X
125 (4.9)
2X
35 (1.4)
2X
190 (7.5)
48 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
96 (3.8) 254
(10.0)
508 (20.0)
18 (0.7)
168 (6.6)
154 (6.1)
1
1209 (47.6)
168 (6.6)
1800 (70.9)
601 (23.7)
4X 121 (4.8)
69 (2.7)
1 Heat sink access panel (optional)
Illustration 8.9 Back View of E2h
4X 457 (18.0)
560 (22.0)
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
49
8 8
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
871 (34.3)
653
(25.7)
75
A
22 (0.8)
137
(5.4)
508 (20.0)
656 (25.8)
184
(7.3)
424
(16.7)
17 (0.7)
A
14 (0.6)
11 (0.4)
1
293 (11.5)
173 (6.8)
22 (0.8) 656 (25.8)
1 Gland plate
Illustration 8.10 Door Clearance and Gland Plate Dimensions for E2h
50 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
8.2.2 E2h Terminal Dimensions
Design Guide
1
6X 613 (24.1)
515 (20.3)
485 (19.1)
200 (7.9)
0 (0.0)
1
2
Mains terminals
Brake or regen terminals
Illustration 8.11 E2h Terminal Dimensions (Front View)
3
4
Motor terminals
Ground terminals, M10 nut
721 (28.4)
2
3
4
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
51
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
649 (25.5) 649 (25.5)
8 8
0 (0.0) 0 (0.0)
5X 14 (0.5)
44 (1.8)
0 (0.0)
36 (1.4)
Illustration 8.12 E2h Terminal Dimensions (Side Views)
A
A
52 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
8.3 E3h Exterior and Terminal Dimensions
8.3.1 E3h Exterior Dimensions
3X 13 (0.5)
1578
(62.1)
1537
(60.5)
1348
(53.1)
Illustration 8.13 Front View of E3h
30
(1.2)
506
(19.9)
10 (0.4)
A
13 (0.5)
A
15 (0.6)
10 (0.4)
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
53
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
2X 20 (0.8)
2X 101 (4.0)
2X 19 (0.7)
8 8
Illustration 8.14 Side View of E3h
2X 21 (0.8)
482 (19.0)
2X 18 (0.7)
54 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
48 (1.9)
206
(8.1)
412
(16.2)
18 (0.7)
168 (6.6)
154 (6.1)
1
744 (29.3)
39 (1.5)
22 (0.9)
1 Heat sink access panel (optional)
Illustration 8.15 Back View of E3h
215 (8.5)
430 (16.9)
4X 457 (18.0)
464 (18.3)
168 (6.6)
136 (5.4)
1335 (52.5)
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
55
8 8
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
262
(10.3)
1
2
8 8
19 (0.7) 2X 219 (8.6)
2X 220
(8.6)
160
(6.3)
1
2
3
RFI shield termination (standard with RFI option)
Cable/EMC clamp
Gland plate
Illustration 8.16 RFI Shield Termination and Gland Plate Dimensions for E3h
56 Danfoss A/S © 05/2017 All rights reserved.
294
(11.6)
163
(6.4)
3
MG38C102
Exterior and Terminal Dimen...
8.3.2 E3h Terminal Dimensions
Design Guide
1
6X 148 (5.8)
90 (3.5)
50 (2.0)
0 (0.0)
1
2
Mains terminals
Brake or regen terminals
Illustration 8.17 E3h Terminal Dimensions (Front View)
3
4
Motor terminals
Ground terminals, M8 and M10 nuts
256 (10.1)
2
33 (1.3)
3
4
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
57
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
184
(7.2)
184
(7.2)
0 (0.0)
8 8
5X 14 (0.5)
44 (1.8)
0 (0.0)
36 (1.4)
Illustration 8.18 E3h Mains, Motor, and Ground Terminal Dimensions (Side Views)
A
0 (0.0)
A
58 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
2X 125 (4.9)
0 (0.0)
A
20 (0.8)
0 (0.0)
35(1.4)
Illustration 8.19 E3h Load Share/Regen Terminal Dimensions
A
8X 14 (0.5)
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
59
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
8.4 E4h Exterior and Terminal Dimensions
8.4.1 E4h Exterior Dimensions
3X 13 (0.5)
8 8
1578
(62.1)
1537
(60.5)
1348
(53.1)
30
(1.2)
Illustration 8.20 Front View of E4h
604
(23.8)
A
10 (0.4)
13 (0.5)
A
15 (0.6)
10 (0.4)
60 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
2X 20 (0.8)
2X 101 (4.0)
2X 19 (0.7)
Illustration 8.21 Side View of E4h
2X 21 (0.8)
482 (19.0)
2X 18 (0.7)
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
61
8 8
Exterior and Terminal Dimen...
48 (1.9)
VLT® AutomationDrive FC 302
254
(10.0)
508
(20.1)
18 (0.7)
168 (6.6)
154 (6.1)
1335 (52.5)
8 8
1
744 (29.3)
39 (1.5)
4X 74 (2.9)
22 (0.9)
1 Heat sink access panel (optional)
Illustration 8.22 Back View of E4h
263 (10.4)
4X 457 (18.0)
526 (20.7)
560 (22.0)
168 (6.6)
136 (5.4)
62 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
262
(10.3)
1
2
19 (0.7) 2X 268 (10.6)
2X 220
(8.6)
160
(6.3)
1
2
3
RFI shield termination (standard with RFI option)
Cable/EMC clamp
Gland plate
Illustration 8.23 RFI Shield Termination and Gland Plate Dimensions for E4h
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
294
(11.6)
163
(6.4)
8 8
3
63
Exterior and Terminal Dimen...
8.4.2 E4h Terminal Dimensions
VLT® AutomationDrive FC 302
8 8
1
6X 148 (5.8)
90 (3.5)
50 (2.0)
0 (0.0)
1
2
Mains terminals
Brake or regen terminals
Illustration 8.24 E4h Terminal Dimensions (Front View)
3
4
Motor terminals
Ground terminals, M8 and M10 nuts
256 (10.1)
2
3
33 (1.3)
4
64 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Exterior and Terminal Dimen...
Design Guide
184
(7.2)
184
(7.2)
0 (0.0)
5X 14 (0.5)
44 (1.8)
0 (0.0)
36 (1.4)
Illustration 8.25 E4h Mains, Motor, and Ground Terminal Dimensions (Side Views)
A
0 (0.0)
8 8
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
65
Exterior and Terminal Dimen...
VLT® AutomationDrive FC 302
2X 125 (4.9)
0 (0.0)
8 8
20 (0.8)
0 (0.0)
35(1.4)
Illustration 8.26 E4h Load Share/Regen Terminal Dimensions
A
8X 14 (0.5)
A
66 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Mechanical Installation Con...
Design Guide
9 Mechanical Installation Considerations
9.1 Storage
Store the drive in a dry location. Keep the equipment sealed in its packaging until installation. Refer to
chapter 7.5 Ambient Conditions
for recommended ambient temperature.
Periodic forming (capacitor charging) is not necessary during storage unless storage exceeds 12 months.
9.2 Lifting the Unit
Always lift the drive using the dedicated lifting eyes. To avoid bending the lifting holes, use a bar.
WARNING
RISK OF INJURY OR DEATH
Follow local safety regulations for lifting heavy weights.
Failure to follow recommendations and local safety regulations can result in death or serious injury.
• Ensure that the lifting equipment is in proper working condition.
•
See
for the weight of the different enclosure sizes.
•
Maximum diameter for bar: 20 mm (0.8 in).
•
The angle from the top of the drive to the lifting cable: 60 ° or greater.
Illustration 9.1 Recommended Lifting Method
9.3 Operating Environment
In environments with airborne liquids, particles, or corrosive gases, ensure that the IP/Type rating of the equipment matches the installation environment. For specifications regarding ambient conditions, see
chapter 7.5 Ambient Conditions .
NOTICE
CONDENSATION
Moisture can condense on the electronic components and cause short circuits. Avoid installation in areas subject to frost. Install an optional space heater when the drive is colder than the ambient air. Operating in standby mode reduces the risk of condensation as long as the power dissipation keeps the circuitry free of moisture.
NOTICE
EXTREME AMBIENT CONDITIONS
Hot or cold temperatures compromise unit performance and longevity.
•
Do not operate in environments where the ambient temperature exceeds 55 ° C (131 ° F).
•
The drive can operate at temperatures down to
-10 ° C (14 ° F). However, proper operation at rated load is only guaranteed at 0 ° C (32 ° F) or higher.
•
If temperature exceeds ambient temperature limits, extra air conditioning of the cabinet or installation site is required.
9.3.1 Gases
Aggressive gases, such as hydrogen sulphide, chlorine, or ammonia can damage the electrical and mechanical components. The unit uses conformal-coated circuit boards to reduce the effects of aggressive gases. For conformalcoating class specifications and ratings, see
chapter 7.5 Ambient Conditions .
9.3.2 Dust
When installing the drive in dusty environments, pay attention to the following:
Periodic maintenance
When dust accumulates on electronic components, it acts as a layer of insulation. This layer reduces the cooling capacity of the components, and the components become
9 9
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
67
Mechanical Installation Con...
VLT® AutomationDrive FC 302
9 9 warmer. The hotter environment decreases the life of the electronic components.
Keep the heat sink and fans free from dust build-up. For more service and maintenance information, refer to the operating guide.
Cooling fans
Fans provide airflow to cool the drive. When fans are exposed to dusty environments, the dust can damage the fan bearings and cause premature fan failure. Also, dust can accumulate on fan blades causing an imbalance which prevents the fans from properly cooling the unit.
9.3.3 Potentially Explosive Atmospheres
WARNING
EXPLOSIVE ATMOSPHERE
Do not install the drive in a potentially explosive atmosphere. Install the unit in a cabinet outside of this area. Failure to follow this guideline increases risk of death or serious injury.
Systems operated in potentially explosive atmospheres must fulfill special conditions. EU Directive 94/9/EC
(ATEX 95) classifies the operation of electronic devices in potentially explosive atmospheres.
•
Class d specifies that if a spark occurs, it is contained in a protected area.
•
Class e prohibits any occurrence of a spark.
Motors with class d protection
Does not require approval. Special wiring and containment are required.
Motors with class e protection
When combined with an ATEX approved PTC monitoring device like the VLT ® PTC Thermistor Card MCB 112, installation does not need an individual approval from an approbated organization.
Motors with class d/e protection
The motor itself has an e ignition protection class, while the motor cabling and connection environment is in compliance with the d classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output.
When using a drive in a potentially explosive atmosphere, use the following:
•
Motors with ignition protection class d or e.
•
PTC temperature sensor to monitor the motor temperature.
•
Short motor cables.
•
Sine-wave output filters when shielded motor cables are not used.
NOTICE
MOTOR THERMISTOR SENSOR MONITORING
VLT ® AutomationDrive units with the VLT ® PTC
Thermistor Card MCB 112 option are PTB-certified for potentially explosive atmospheres.
9.4 Mounting Configurations
lists the available mounting configurations for each enclosure. For specific wall mount or pedestal mount installation instructions, see the operating guide . See also
chapter 8 Exterior and Terminal Dimensions
.
NOTICE
Improper mounting can result in overheating and reduced performance.
Mounting
Pedestal
Wall
E1h
X
–
E2h
X
–
E3h
–
X
E4h
–
X
Table 9.1 Mounting Configurations for Enclosures E1h–E4h
Mounting considerations:
•
Locate the unit as near to the motor as possible.
See
chapter 7.6 Cable Specifications
for the maximum motor cable length.
•
Ensure unit stability by mounting the unit to a solid surface.
•
Enclosures E3h and E4h can be mounted:
Vertically on the backplate of the panel
(typical installation).
Vertically upside down on the backplate of the panel.
1)
Horizontally on its back, mounted on the backplate of the panel.
1)
Horizontally on its side, mounted on floor of the panel.
1)
•
Ensure that the strength of the mounting location supports the unit weight.
•
Ensure that there is enough space around the unit for proper cooling. Refer to
chapter 5.7 Backchannel Cooling Overview .
•
Ensure enough access to open the door.
•
Ensure cable entry from the bottom.
1) For non-typical installation, contact the factory .
68 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Mechanical Installation Con...
Design Guide
9.5 Cooling
NOTICE
Improper mounting can result in overheating and reduced performance. For proper mounting, refer to chapter 9.4.1 Mounting Configurations .
•
Ensure that top and bottom clearance for air cooling is provided. Clearance requirement:
225 mm (9 in).
•
Provide sufficient airflow flow rate. See
.
•
Consider derating for temperatures starting between 45 ° C (113 ° F) and 50 ° C (122 ° F) and elevation 1000 m (3300 ft) above sea level. See
for detailed information on derating.
The drive utilizes a back-channel cooling concept that removes heat sink cooling air. The heat sink cooling air carries approximately 90% of the heat out of the back channel of the drive. Redirect the back-channel air from the panel or room by using:
•
Duct cooling
Back-channel cooling kits are available to direct the heat sink cooling air out of the panel when
IP20/Chassis drives are installed in Rittal enclosures. Use of these kits reduce the heat in the panel and smaller door fans can be specified.
•
Back-wall cooling
Installing top and base covers to the unit allows the back-channel cooling air to be ventilated out of the room.
NOTICE
For E3h and E4h enclosures (IP20/Chassis), at least 1 door fan is required on the enclosure to remove the heat not contained in the back-channel of the drive. It also removes any additional losses generated by other components inside the drive. To select the appropriate fan size, calculate the total required airflow.
Secure the necessary airflow over the heat sink.
E1h
E2h
E3h
E4h
Frame Door fan/top fan
[m 3 /hr (cfm)]
510 (300)
552 (325)
595 (350)
629 (370)
Table 9.2 Airflow Rate
Heat sink fan
[m 3 /hr (cfm)]
994 (585)
1053–1206 (620–710)
994 (585)
1053–1206 (620–710)
9.6 Derating
Derating is used to reduce output current in certain situations, which prevents the drive from generating excessive heat within the enclosure. Consider derating when any of the following conditions are present:
•
Low-speed operation.
•
Low air pressure (operating at high altitudes).
•
High ambient temperature.
•
High switching frequency.
•
Long motor cables.
•
Cables with a large cross-section.
If these conditions are present, Danfoss recommends stepping up 1 power size.
9.6.1 Derating for Low-Speed Operation
When a motor is connected to a drive, it is necessary to check that the cooling of the motor is adequate. The level of cooling required depends on the load on the motor, the operating speed, and the length of time.
Constant torque applications
A problem can occur at low RPM values in constant torque applications. In a constant torque application, a motor can overheat at low speeds because less cooling air is being provided by the fan within the motor.
If the motor is run continuously at an RPM value lower than half of the rated value, the motor must be supplied with extra air cooling. If extra air cooling cannot be provided, a motor designed for low RPM/constant torque applications can be used instead.
Variable (quadratic) torque applications
Extra cooling or derating of the motor is not required in variable torque applications where the torque is proportional to the square of the speed, and the power is proportional to the cube of the speed. Centrifugal pumps and fans are common variable torque applications.
9 9
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
69
Mechanical Installation Con...
VLT® AutomationDrive FC 302
9.6.2 Derating for Altitude
The cooling capability of air is decreased at lower air pressure.
No derating is necessary at or below 1000 m (3281 ft). Above 1000 m (3281 ft), the ambient temperature (T
AMB
) or maximum output current (I
MAX
) should be derated. Refer to
Max.I
out
(%) at T
AMB, MAX
100%
96%
92%
T
AMB, MAX at 100% I out
HO NO
0 K -5 K
-3 K
-6 K
-8 K
-11 K
1 km 2 km 3 km Altitude (km)
Illustration 9.2 Derating of Output Current Based on Altitude at T
AMB
,
MAX
9 9
shows that at 41.7 ° C (107 ° F), 100% of the rated output current is available. At 45 ° C (113 ° F) (T
AMB
, MAX-3
K), 91% of the rated output current is available.
9.6.3 Derating for Ambient Temperature and Switching Frequency
NOTICE
FACTORY DERATING
Danfoss drives are already derated for operational temperature (55 ° C (131 ° F) T
AMB,MAX
and 50 ° C (122 ° F) T
AMB,AVG
).
Use the graphs in
to
to determine if the output current must be derated based on switching frequency and ambient temperature. When referring to the graphs, I out
indicates the percentage of rated output current, and fsw indicates the switching frequency.
70 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Mechanical Installation Con...
Design Guide
Enclosure Switching pattern
60 AVM E1h–E4h
N315 to N500
380–500 V
110
100
90
80
70
60
0
SFAVM
110
100
90
80
70
60
0
1
1
High overload HO, 150%
2 3 4 fsw [kHz]
2 fsw [kHz]
3
5 6
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
7
4
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
5
110
100
90
80
70
60
50
0
Normal overload NO, 110%
110
100
90
80
70
60
50
0 1 2 3 fsw [kHz]
4 5 6
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
50 ˚C (131 ˚F)
7
1 2 fsw [kHz]
3 4
40 ˚C (104 ˚F)
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
5
Table 9.3 Derating Tables for Drives Rated 380–500 V
Enclosure Switching pattern
60 AVM E1h–E4h
N355 to N710
525–690 V
SFAVM
High overload HO, 150%
110
100
90
80
70
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
60
0.0
0.5
1.0
1.5
2.0
2.5
3.0
fsw [kHz]
3.5
4.0
4.5
5.0
5.5
110
100
90
80
70
60
0.0
0.5
1.0
1.5
2.0
fsw [kHz]
2.5
3.0
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
3.5
4.0
Normal overload NO, 110%
110
100
90
80
70
60
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
50
0.0
0.5
1.0
1.5
2.0
2.5
3.0 3.5
fsw [kHz]
4.0
4.5
5.0
5.5
110
100
90
80
70
60
50
0.0
0.5
1.0
1.5
2.0
fsw [kHz]
2.5
3.0
40 ˚C (104 ˚F)
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
3.5
4.0
Table 9.4 Derating Tables for Drives Rated 525–690 V
9 9
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
71
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 Electrical Installation Considerations
10 10
10.1 Safety Instructions
See
for general safety instructions.
WARNING
INDUCED VOLTAGE
Induced voltage from output motor cables from different drives that are run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result in death or serious injury.
•
Run output motor cables separately or use shielded cables.
•
Simultaneously lock out all the drives.
WARNING
SHOCK HAZARD
The drive can cause a DC current in the ground conductor and thus result in death or serious injury.
•
When a residual current-operated protective device (RCD) is used for protection against electrical shock, only an RCD of Type B is allowed on the supply side.
Failure to follow the recommendation means that the
RCD cannot provide the intended protection.
Overcurrent protection
•
Extra protective equipment such as short-circuit protection or motor thermal protection between drive and motor is required for applications with multiple motors.
•
Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer must provide them.
See maximum fuse ratings in
chapter 10.5 Fuses and Circuit Breakers
.
Wire type and ratings
•
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
•
Power connection wire recommendation:
Minimum 75 ° C (167 ° F) rated copper wire.
See
chapter 7.6 Cable Specifications
for recommended wire sizes and types.
CAUTION
PROPERTY DAMAGE!
Protection against motor overload is not included in the default setting. To add this function, set parameter 1-90 Motor Thermal Protection to [ETR trip] or
[ETR warning] . For the North American market, the ETR function provides class 20 motor overload protection in accordance with NEC. Failure to set parameter 1-90 Motor
Thermal Protection to [ETR trip] or [ETR warning] means that motor overload protection is not provided and, if the motor overheats, property damage can occur.
72 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
10.2 Wiring Schematic
Design Guide
230 V AC
50/60 Hz
TB5
R1 Space heater (optional) power input
Load share
(optional)
+10 V DC
-10 V DC - +10 V DC
0/4-20 mA
-10 V DC - +10 V DC
0/4-20 mA
91 (L1)
92 (L2)
93 (L3)
95 PE
88 (-)
89 (+)
50 (+10 V OUT)
A53 U-I (S201)
53 (A IN)
A54 U-I (S202)
54 (A IN)
ON=0-20 mA
OFF=0-10 V
Switch mode power supply
10 V DC
+ +
24 V DC
200 mA
-
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN/OUT)
24V
0V
P 5-00
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
(U) 96
(V) 97
(W) 98
(PE) 99
Regen +
(R+) 82
(R-) 81
Regen - 83
Relay1
03
02
Relay2
01
06
05
04
(COM A OUT) 39
(A OUT) 42
S801/Bus Term.
OFF-ON
ON=Terminated
OFF=Open
1
5V 2
29 (D IN/OUT)
24V
24 V (NPN)
0 V (PNP)
32 (D IN)
33 (D IN)
0V
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
RS485 interface
S801
0V
(P RS485) 68
(N RS485) 69
(COM RS485) 61
37 (D IN) 1)
Brake resistor
(optional)
Regen (optional)
240 V AC, 2A
400 V AC, 2A
240 V AC, 2A
400 V AC, 2A
Analog output
0/4-20 mA
Motor
Brake temperature
(NC)
RS485
(PNP) = Source
(NPN) = Sink
Illustration 10.1 Basic Wiring Schematic
A=Analog, D=Digital
1) Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the Safe Torque Off
Operating Guide.
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
73
Electrical Installation Con...
VLT® AutomationDrive FC 302
10.3 Connections
10.3.1 Power Connections
NOTICE
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. UL applications require 75 ° C (167 ° F) copper conductors. Non-UL applications can use 75 ° C
(167 ° F) and 90 ° C (194 ° F) copper conductors.
The power cable connections are located as shown in
. See
for correct dimensioning of motor cable cross-section and length.
For protection of the drive, use the recommended fuses unless the unit has built-in fuses. Recommended fuses are listed in
chapter 10.5 Fuses and Circuit Breakers
. Ensure that proper fusing complies with local regulations.
The connection of mains is fitted to the mains switch if included.
10 10 3 Phase power input
91 (L1)
92 (L2)
93 (L3)
95 PE
Illustration 10.2 Power Cable Connections
NOTICE
The motor cable must be shielded/armored. If an unshielded/unarmored cable is used, some EMC requirements are not complied with. Use a shielded/ armored motor cable to comply with EMC emission specifications. For more information, see
chapter 10.15 EMC-compliant Installation
.
Shielding of cables
Avoid installation with twisted shield ends (pigtails). They spoil the shielding effect at higher frequencies. If it is necessary to break the shield to install a motor isolator or contactor, continue the shield at the lowest possible HF impedance.
Connect the motor cable shield to both the decoupling plate of the drive and the metal housing of the motor.
Make the shield connections with the largest possible surface area (cable clamp) by using the installation devices within the drive.
Cable length and cross-section
The drive has been EMC tested with a given length of cable. Keep the motor cable as short as possible to reduce the noise level and leakage currents.
Switching frequency
When drives are used together with sine-wave filters to reduce the acoustic noise from a motor, the switching frequency must be set according to the instructions in parameter 14-01 Switching Frequency .
Terminal 96 97 98 99
– U V W PE 1) Motor voltage 0–100% of mains voltage. 3 wires out of motor.
– U1 V1 W1
W2 U2 V2
PE 1)
Delta-connected.
6 wires out of motor.
– U1 V1 W1 PE 1) Star-connected U2, V2, W2
U2, V2, and W2 to be interconnected separately.
Table 10.1 Motor Cable Connection
1) Protected ground connection
NOTICE
In motors without phase insulation, paper, or other insulation reinforcement suitable for operation with voltage supply, use a sine-wave filter on the output of the drive.
Motor
U
2
U
1
V
2
V
1
W
2
W
1
Motor
U
2
U
1
V
1
V
2
W
1
W
2
FC
96 97 98
FC
96 97 98
Illustration 10.3 Motor Cable Connection
10.3.2 DC Bus Connection
The DC bus terminal is used for DC back-up, with the DC link being supplied from an external source.
Terminal
88, 89
Function
DC Bus
Table 10.2 DC Bus Terminals
74 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
10.3.3 Load Sharing
Load sharing links together the DC intermediate circuits of several drives. For an overview, see
The load sharing feature requires extra equipment and safety considerations. Consult Danfoss for ordering and installation recommendations.
Terminal
88, 89
Function
Load sharing
Table 10.3 Load Sharing Terminals
The connection cable must be shielded and the maximum length from the drive to the DC bar is limited to 25 m
(82 ft).
10.3.4 Brake Cable
The connection cable to the brake resistor must be shielded and the maximum length from the drive to the
DC bar is limited to 25 m (82 ft).
•
Use cable clamps to connect the shield to the conductive backplate on the drive and to the metal cabinet of the brake resistor.
•
Size the brake cable cross-section to match the brake torque.
Terminal
81, 82
Function
Brake resistor terminals
Table 10.4 Brake Resistor Terminals
See the VLT ® Brake Resistor MCE 101 Design Guide for more details.
NOTICE
If a short circuit in the brake IGBT occurs, prevent power dissipation in the brake resistor by using a mains switch or contactor to disconnect the mains from the drive.
Only the drive should control the contactor.
10.4 Control Wiring and Terminals
10.4.1 Control Cable Routing
Tie down and route all control wires as shown in
. Remember to connect the shields in a
proper way to ensure optimum electrical immunity.
•
Isolate control wiring from high-power cables.
•
When the drive is connected to a thermistor, ensure that the thermistor control wiring is shielded and reinforced/double insulated. A 24 V
DC supply voltage is recommended.
Fieldbus connection
Connections are made to the relevant options on the control card. See the relevant fieldbus instruction. The cable must be tied down and routed along with other control wires inside the unit. See
.
10 10
MG38C102
Illustration 10.4 Control Card Wiring Path
Danfoss A/S © 05/2017 All rights reserved.
75
10 10
Electrical Installation Con...
VLT® AutomationDrive FC 302
10.4.2 Control Terminals
shows the removable drive connectors.
Terminal functions and default settings are summarized in
–
.
Illustration 10.5 Control Terminal Locations
1
61 68 69 39 42 50 53 54 55
3
Terminal
61
68 (+)
69 (-)
01, 02, 03
Serial communication terminals
Parameter Default setting
Description
– – Integrated RC-filter for cable shield. ONLY for connecting the shield in case of EMC problems.
Parameter group 8-3* FC
Port Settings
Parameter group 8-3* FC
Port Settings
–
–
RS485 interface. A switch (BUS TER.) is provided on the control card for bus termination resistance. See the
VLT ® AutomationDrive
FC 300 90–1200 kW
Design Guide .
Parameter 5-40
Function Relay
[0]
04, 05, 06 Parameter 5-40
Function Relay
[1]
Relays
[0] No operation
[0] No operation
Form C relay output.
For AC or DC voltage and resistive or inductive loads.
Table 10.5 Serial Communication Terminal Descriptions
2
12 13 18 19 27 29 32 33 20 37
1
2
3
Serial communication terminals
Digital input/output terminals
Analog input/output terminals
Illustration 10.6 Terminal Numbers Located on the Connectors
76 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
Terminal
12, 13
18
19
32
33
27
29
20
37
Digital input/output terminals
Parameter Default setting
Description
– +24 V DC 24 V DC supply voltage for digital inputs and external transducers.
Maximum output current 200 mA for all
24 V loads.
[8] Start Digital inputs.
Parameter 5-10
Terminal 18
Digital Input
Parameter 5-11
Terminal 19
Digital Input
[10]
Reversing
[0] No operation
Parameter 5-14
Terminal 32
Digital Input
Parameter 5-15
Terminal 33
Digital Input
Parameter 5-12
Terminal 27
Digital Input
Parameter 5-13
Terminal 29
Digital Input
–
[0] No operation
[2] Coast inverse
[14] JOG
–
For digital input or output. Default setting is input.
– STO
Common for digital inputs and 0 V potential for 24 V supply.
When not using the optional STO feature, a jumper wire is required between terminal 12 (or 13) and terminal 37. This set-up allows the drive to operate with factory default programming values.
Table 10.6 Digital Input/Output Terminal Descriptions
Terminal
39
42
50
53
54
55
Analog input/output terminals
Parameter Default setting
Description
– – Common for analog output.
Parameter 6-50
Terminal 42
Output
–
[0] No operation
Programmable analog output. 0–20 mA or
4–20 mA at a maximum of 500 Ω .
+10 V DC 10 V DC analog supply voltage for potentiometer or thermistor. 15 mA maximum.
Parameter group 6-1*
Analog Input 1
Parameter group 6-2*
Analog Input 2
–
Reference Analog input. For voltage or current.
Feedback
Switches A53 and
A54 select mA or V.
– Common for analog input.
Table 10.7 Analog Input/Output Terminal Descriptions
Relay terminals:
RELAY 1 RELAY 2
01 02 03 04 05 06
Illustration 10.7 Relay 1 and Relay 2 Terminals
10 10
•
Relay 1 and relay 2. The location of the outputs depends on the drive configuration. See the operating guide .
•
Terminals on built-in optional equipment. See the instructions provided with the equipment option.
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
77
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
10.5 Fuses and Circuit Breakers
Fuses ensure that possible damage to the drive is limited to damages inside the unit. To ensure compliance with EN 50178, use identical Bussmann fuses as replacements. Refer to
.
NOTICE
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Input voltage (V)
380–500
525–690
Table 10.8 Fuse Options
Bussmann ordering number
170M7309
170M7342
The fuses listed in
are suitable for use on a circuit capable of delivering 100000 A rms
(symmetrical), depending on the drive voltage rating. With the proper fusing, the drive short circuit current rating (SCCR) is 100000 A rms
. E1h and E2h drives are supplied with internal drive fusing to meet the 100 kA SCCR and to comply with UL 61800-5-1 enclosed drive requirements. E3h and E4h drives must be fitted with Type aR fuses to meet the 100 kA SCCR.
NOTICE
DISCONNECT SWITCH
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet the 100 kA SCCR for the drive. If a circuit breaker is used, the SCCR rating is 42 kA. The input voltage and power rating of the drive determines the specific Class L fuse. The input voltage and power rating is found on the product nameplate. For more information regarding the nameplate, see the operating guide .
Input voltage (V)
380–500
380–500
525–690
525–690
Power rating (kW)
315–400
450–500
355–560
630–710
Short circuit rating (A)
42000
100000
42000
100000
40000
100000
42000
100000
Required protection
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
10.6 Motor
10.6.1 Motor Cable
All types of 3-phase asynchronous standard motors can be used with a drive unit. The motor must be connected to the following terminals:
•
U/T1/96
•
V/T2/97
•
W/T3/98
•
Ground to terminal 99
Factory setting is for clockwise rotation with the drive output connected as follows:
78 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Terminal
96
97
98
99
Function
Mains U/T1
V/T2
W/T3
Ground
Table 10.9 Motor Cable Terminals
Motor
U
2
V
2
W
2
U
1
V
1
W
1
FC
96 97 98
Motor
U
2
U
1
V
2
V
1
W
2
W
1
Design Guide
FC
96 97 98
Illustration 10.8 Changing Motor Rotation
•
Terminal U/T1/96 connected to U-phase
•
Terminal V/T2/97 connected to V-phase
•
Terminal W/T3/98 connected to W-phase
The direction of rotation can be changed by switching 2 phases in the motor cable, or by changing the setting of parameter 4-10 Motor Speed Direction .
Motor rotation check can be performed using parameter 1-28 Motor Rotation Check and following the configuration shown in
10.6.2 Motor Thermal Protection
The electronic thermal relay in the drive has received ULapproval for single motor overload protection, when parameter 1-90 Motor Thermal Protection is set for ETR Trip and parameter 1-24 Motor Current is set to the rated motor current (see the motor nameplate).
For motor thermal protection, it is also possible to use the
VLT ® PTC Thermistor Card MCB 112 option. This card provides ATEX certification to protect motors in explosion hazardous areas Zone 1/21 and Zone 2/22. When parameter 1-90 Motor Thermal Protection , set to [20] ATEX
ETR , is combined with the use of MCB 112, it is possible to control an Ex-e motor in explosion hazardous areas.
Consult the programming guide for details on how to set up the drive for safe operation of Ex-e motors.
10.6.3 Parallel Connection of Motors
The drive can control several parallel-connected motors.
For different configurations of parallel-connected motors, see
When using parallel motor connection, observe the following points:
•
Run applications with parallel motors in U/F mode (volts per hertz).
•
VVC + mode can be used in some applications.
•
Total current consumption of motors must not exceed the rated output current I
INV
for the drive.
•
Problems can occur at start and at low RPM if motor sizes are widely different because the relatively high ohmic resistance in the stator of a small motor demands a higher voltage at start and at low RPM.
•
The electronic thermal relay (ETR) of the drive cannot be used as motor overload protection.
Provide further motor overload protection by including thermistors in each motor winding or individual thermal relays.
•
When motors are connected in parallel, parameter 1-02 Flux Motor Feedback Source cannot be used, and parameter 1-01 Motor Control
Principle must be set to [0] U/f .
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
79
Electrical Installation Con...
VLT® AutomationDrive FC 302 a d
10 10 b e c f
A Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B Be aware of the maximum motor cable length specified in
chapter 7.6 Cable Specifications
.
C The total motor cable length specified in
chapter 7.6 Cable Specifications
is valid as long as the parallel cables are kept short less than 10 m (32 ft) each.
D Consider voltage drop across the motor cables.
E Consider voltage drop across the motor cables.
F
The total motor cable length specified in chapter 7.6 Cable Specifications
is valid as long as the parallel cables are kept less than 10 m
(32 ft) each.
Illustration 10.9 Different Parallel Connections of Motors
80 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
10.6.4 Motor Insulation
For motor cable lengths that are less than or equal to the maximum cable length listed in
chapter 7.6 Cable Specifications
, use the motor insulation ratings shown in
. If a motor has lower insulation rating, Danfoss recommends using a dU/dt or sine-wave filter.
Nominal mains voltage
U
N
≤ 420 V
420 V<U
500 V<U
600 V<U
N
N
N
≤ 500 V
≤ 600 V
≤ 690 V
Motor insulation
Standard U
LL
=1300 V
Reinforced U
LL
=1600 V
Reinforced U
LL
=1800 V
Reinforced U
LL
=2000 V
Table 10.10 Motor Insulation Ratings
10.6.5 Motor Bearing Currents
To eliminate circulating bearing currents in all motors installed with VLT ® AutomationDrive, install NDE (non-drive end) insulated bearings. To minimize DE (drive end) bearing and shaft currents, ensure proper grounding of the drive, motor, driven machine, and motor to the driven machine.
Standard mitigation strategies:
•
Use an insulated bearing.
•
Follow proper installation procedures.
Ensure that the motor and load motor are aligned.
-
-
-
-
Follow the EMC Installation guideline.
Reinforce the PE so the high frequency impedance is lower in the PE than the input power leads.
Provide a good high frequency connection between the motor and the drive. Use a shielded cable that has a
360 ° connection in the motor and the drive.
Ensure that the impedance from the drive to building ground is lower than the grounding impedance of the machine. This procedure can be difficult for pumps.
Make a direct ground connection between the motor and load motor.
•
Lower the IGBT switching frequency.
•
Modify the inverter waveform, 60 ° AVM vs.
SFAVM.
•
Install a shaft grounding system or use an isolating coupling.
•
Apply conductive lubrication.
•
Use minimum speed settings if possible.
•
Try to ensure that the mains voltage is balanced to ground. This procedure can be difficult for IT,
TT, TN-CS, or grounded leg systems.
•
Use a dU/dt or sine-wave filter.
10.7 Braking
10.7.1 Brake Resistor Selection
To handle the higher demands of resistor braking, a brake resistor is necessary. The brake resistor absorbs the energy instead of the drive. For more information, see the VLT ®
Brake Resistor MCE 101 Design Guide .
If the amount of kinetic energy transferred to the resistor in each braking period is not known, the average power can be calculated based on the cycle time and braking time (intermittent duty cycle). The resistor intermittent duty cycle indicates the duty cycle at which the resistor is active.
shows a typical braking cycle.
Motor suppliers often use S5 when stating the allowed load, which is an expression of intermittent duty cycle. The intermittent duty cycle for the resistor is calculated as follows:
Duty cycle=t b
/T
T=cycle time in s t b
is the braking time in s (of the cycle time)
10 10
Load
Speed ta tc
T tb to ta tc tb to ta
Time
Illustration 10.10 Typical Braking Cycle
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
81
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
Nominal braking
[45 ° C
(113 ° F)]
Overload braking
[45 ° C
(113 ° F)]
Nominal braking
[25 ° C
(77 ° F)]
Overload braking
[25 ° C
(77 ° F)]
Power size (high overload)
N315 N355 N400 N450 N500
600 600 600 600 600 Cycle time
(s)
Current (%) 100
Braking time (s)
70
240 240
62
240
56
240
80
240
Cycle time
(s)
300
Current (%) 136
300
92
300
81
300
72
300
107
30 30 30 Braking time (s)
Cycle time
(s)
30
600
30
600
Current (%) 100
Braking time (s)
92
240 240
Cycle time
(s)
300 300
Current (%) 136 113
Braking time (s)
30 10
600
81
240
300
100
10
600
89
240
300
72
30
600
80
240
300
107
30
Table 10.11 Braking Capability, 380–500 V
Nominal braking
[45 ° C
(113 ° F)]
Overload braking
[45 ° C
(113 ° F)]
Nominal braking
[25 ° C
(77 ° F)]
Overload braking
[25 ° C
(77 ° F)]
Cycle time (s)
Current
(%)
Braking time (s)
Cycle time (s)
Current
(%)
Braking time (s)
Cycle time (s)
Current
(%)
Braking time (s)
Cycle time (s)
Current
(%)
Braking time (s)
Power size (high overload)
N355 N400 N500 N560 N630 N710
600 600 600 600 600 600
89
240
300
113
30
600
89
240
300
113
30
79
240
300
100
30
600
79
240
300
100
30
63
240
300
80
30
600
63
240
300
80
30
63
240
300
80
30
600
63
240
300
80
30
71
240
300
94
30
600
71
240
300
94
30
63
240
300
84
30
60
63
240
300
84
30
Table 10.12 Braking Capability, 525–690 V
Danfoss offers brake resistors with duty cycle of 5%, 10%, and 40%. If a 10% duty cycle is applied, the brake resistors are able to absorb brake power for 10% of the cycle time.
The remaining 90% of the cycle time is used to dissipate excess heat.
NOTICE
Make sure that the resistor is designed to handle the required braking time.
The maximum allowed load on the brake resistor is stated as a peak power at a given intermittent duty cycle. The brake resistance is calculated as shown:
R br
Ω =
U 2 dc
P peak where
P peak
=P motor xM br
[%]xη motor xη
VLT
[W]
As can be seen, the brake resistance depends on the DClink voltage (U dc
).
Size
380–500 V 1)
525–690 V
Brake active
810 V
1084 V
Warning before cut out
828 V
1109 V
Cut out
(trip)
855 V
1130 V
Table 10.13 FC 302 Brake Limits
1) Power size dependent
NOTICE
Check that the brake resistor can handle a voltage of
410 V, 820 V, 850 V, 975 V, or 1130 V. Danfossbrake resistors are rated for use on all Danfoss drives.
Danfoss recommends the brake resistance R rec
. This calculation guarantees that the drive is able to brake at the highest braking torque (M br(%)
) of 150%. The formula can be written as:
R rec
Ω =
P motor
x M
U
2 dc
x 100 br ( % )
xη
VLT
x η motor
η motor
is typically at 0.90
η
VLT
is typically at 0.98
For 200 V, 480 V, 500 V, and 600 V drives, R rec
at 160% braking torque is written as:
200V : R rec
= 107780 motor
Ω
500V : R rec P motor
Ω
600V : R rec P motor
Ω
690V : R rec P motor
Ω
82 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
NOTICE
The resistor brake circuit resistance selected should not be higher than what is recommended by Danfoss. Enclosure sizes E1h–E4h contain 1 brake chopper.
NOTICE
If a short circuit occurs in the brake transistor, power dissipation in the brake resistor is prevented only by using a mains switch or contactor to disconnect the mains from the drive, or a contact in the brake circuit. Uninterrupted power dissipation in the brake resistor can cause overheating, damage, or a fire.
WARNING
FIRE HAZARD
Brake resistors get hot while/after braking, and must be placed in a secure environment to avoid fire risk.
10.7.2 Control with Brake Function
A relay/digital can be used to protect the brake resistor against overloading or overheating by generating a fault in the drive. If the brake IGBT is overloaded or overheated, the relay/digital signal from the brake to the drive turns off the brake
IGBT. This relay/digital signal does not protect against a short circuit in the brake IGBT. Danfoss recommends a means to disconnect the brake if a short circuit occurs in the brake IGBT.
In addition, the brake makes it possible to read out the momentary power and the average power for the latest 120 s. The brake can monitor the power energizing and make sure that it does not exceed the limit selected in parameter 2-12 Brake
Power Limit (kW) . Parameter 2-13 Brake Power Monitoring selects what function occurs when the power transmitted to the brake resistor exceeds the limit set in parameter 2-12 Brake Power Limit (kW) .
NOTICE
Monitoring the brake power is not a safety function; a thermal switch connected to an external contactor is required for that purpose. The brake resistor circuit is not ground leakage protected.
Overvoltage control (OVC) can be selected as an alternative brake function in parameter 2-17 Over-voltage Control . This function is active for all units and ensures that if the DC-link voltage increases, the output frequency also increases to limit the voltage from the DC link, which avoids a trip.
NOTICE
OVC cannot be activated when running a PM motor, while parameter 1-10 Motor Construction is set to [1] PM nonsalient SPM .
10.8 Residual Current Devices (RCD) and Insulation Resistance Monitor (IRM)
Use RCD relays, multiple protective grounding, or grounding as extra protection, provided they comply with local safety regulations.
If a ground fault appears, a DC current can develop in the faulty current. If RCD relays are used, local regulations must be observed. Relays must be suitable for protection of 3-phase equipment with a bridge rectifier and for a brief discharge on power-up. See
for more details.
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
83
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
10.9 Leakage Current
Follow national and local codes regarding protective grounding of equipment where leakage current exceeds
3.5 mA.
Drive technology implies high-frequency switching at high power. This high-frequency switching generates a leakage current in the ground connection.
The ground leakage current is made up of several contributions and depends on various system configurations, including:
•
RFI filtering.
•
Motor cable length.
•
Motor cable screening.
•
Drive power.
Leakage current a
Leakage current
THDv=0%
THDv=5%
Illustration 10.12 Line Distortion Influences Leakage Current b
Motor cable length
Illustration 10.11 Motor cable length and power size influence on leakage current. Power size a > power size b.
The leakage current also depends on the line distortion.
If the leakage current exceeds 3.5 mA, compliance with
EN/IEC61800-5-1 (power drive system product standard) requires special care.
Reinforce grounding with the following protective earth connection requirements:
•
Ground wire (terminal 95) of at least 10 mm 2 (8
AWG) cross-section.
•
2 separate ground wires both complying with the dimensioning rules.
See EN/IEC61800-5-1 and EN 50178 for further information.
Using RCDs
Where residual current devices (RCDs), also known as ground leakage circuit breakers, are used, comply with the following:
•
Use RCDs of type B only as they can detect AC and DC currents.
•
Use RCDs with a delay to prevent faults due to transient ground currents.
•
Dimension RCDs according to the system configuration and environmental considerations.
The leakage current includes several frequencies originating from both the mains frequency and the switching frequency. Whether the switching frequency is detected depends on the type of RCD used.
84 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
Leakage current
RCD with low f cut-
RCD with high f cut-
Mains
50 Hz 150 Hz
3rd harmonics f sw
Cable
Frequency
Illustration 10.13 Main Contributions to Leakage Current
The amount of leakage current detected by the RCD depends on the cut-off frequency of the RCD.
Leakage current [mA]
100 Hz
2 kHz
100 kHz
Illustration 10.14 Influence of the RCD Cut-off Frequency on
Leakage Current
Filter to [ON]. Refer also to the Application Note, VLT on IT
Mains, MN50P . It is important to use isolation monitors that are rated for use together with power electronics (IEC
61557-8).
Danfoss does not recommend using an output contactor for 525–690 V drives connected to an IT mains network.
10.11 Efficiency
Efficiency of the drive (η
VLT
)
The load on the drive has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency f
M,N
, whether the motor supplies 100% of the rated shaft torque or only 75%, in case of part loads.
The efficiency of the drive does not change even if other
U/f characteristics are selected. However, the U/f characteristics influence the efficiency of the motor.
The efficiency declines slightly when the switching frequency is set to a value of above 5 kHz. The efficiency is slightly reduced when the mains voltage is 480 V, or if the motor cable is longer than 30 m (98 ft.).
Drive efficiency calculation
Calculate the efficiency of the drive at different speeds and loads based on
. The factor in this graph must be multiplied with the specific efficiency factor listed in the specification tables in
and
chapter 7.2 Electrical Data, 525–690 V .
1.01
1.0
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0% 50% 100%
% Speed
150% 200%
100% load 75% load 50% load 25% load
Illustration 10.15 Typical Efficiency Curves
10 10
10.10 IT Mains
Mains Supply Isolated from Ground
If the drive is supplied from an isolated mains source (IT mains, floating delta, or grounded delta) or TT/TN-S mains with grounded leg, the RFI switch is recommended to be turned off via parameter 14-50 RFI Filter on the drive and parameter 14-50 RFI Filter on the filter. For more detail, see
IEC 364-3. In the off position, the filter capacitors between the chassis and the DC link are cut off to avoid damage to the DC link and to reduce the ground capacity currents, according to IEC 61800-3.
If optimum EMC performance is needed, or parallel motors are connected, or the motor cable length is above 25 m
(82 ft), Danfoss recommends setting parameter 14-50 RFI
Example: Assume a 160 kW, 380–480 V AC drive at 25% load at 50% speed.
shows 0.97 - rated efficiency for a 160 kW drive is 0.98. The actual efficiency is then: 0.97x 0.98=0.95.
Efficiency of the motor (η
MOTOR)
The efficiency of a motor connected to the drive depends on magnetizing level. In general, the efficiency is as good as with mains operation. The efficiency of the motor depends on the type of motor.
In the range of 75–100% of the rated torque, the efficiency of the motor is practically constant, both when the drive controls it and when it runs directly on the mains.
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
85
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
In small motors, the influence from the U/f characteristic on efficiency is marginal. However, in motors from 11 kW
(14.75 hp) and up, the advantages are significant.
Typically the switching frequency does not affect the efficiency of small motors. Motors from 11 kW (14.75 hp) and up have their efficiency improved (1–2%) because the shape of the motor current sine-wave is almost perfect at high switching frequency.
Efficiency of the System ( η
SYSTEM
)
To calculate system efficiency, the efficiency of the drive
(η
VLT
) is multiplied by the efficiency of the motor ( η
MOTOR
):
η
SYSTEM
= η
VLT
x η
MOTOR
10.12 Acoustic Noise
The acoustic noise from the drive comes from 3 sources:
•
DC intermediate circuit coils.
•
Internal fans.
•
RFI filter choke.
lists the typical acoustic noise values measured at a distance of 1 m (9 ft) from the unit.
E1h–E4h
Enclosure size
Table 10.14 Acoustic Noise dBA at full fan speed
80
Test results performed according to ISO 3744 for audible noise magnitude in a controlled environment. Noise tone has been quantified for engineering data record of hardware performance per ISO 1996-2 Annex D.
A new fan control algorithm for E1h-E4h enlosure sizes helps improve audible noise performance by allowing the operator to select different fan operation modes based on specific conditions. For more information, see parameter 30-50 Heat Sink Fan Mode .
10.13 dU/dt Conditions
NOTICE
To avoid the premature aging of motors that are not designed to be used with drives, such as those motors without phase insulation paper or other insulation reinforcement, Danfoss strongly recommends a dU/dt filter or a sine-wave filter fitted on the output of the drive. For further information about dU/dt and sine-wave filters, see the Output Filters Design Guide .
When a transistor in the inverter bridge switches, the voltage across the motor increases by a dU/dt ratio depending on:
•
The motor cable (type, cross-section, length shielded or unshielded).
•
Inductance.
The natural induction causes an overshoot U
PEAK
in the motor voltage before it stabilizes itself at a level depending on the voltage in the intermediate circuit. The rise time and the peak voltage U
PEAK affect the service life of the motor. In particular, motors without phase coil insulation are affected if the peak voltage is too high.
Motor cable length affects the rise time and peak voltage.
For example, if the motor cable is short (a few meters), the rise time and peak voltage are lower. If the motor cable is long (100 m (328 ft)), the rise time and peak voltage are higher.
Peak voltage on the motor terminals is caused by the switching of the IGBTs. The drive complies with the demands of IEC 60034-25 regarding motors designed to be controlled by drives. The drive also complies with IEC
60034-17 regarding Norm motors controlled by drives.
High-power range
The power sizes in the following tables at the appropriate mains voltages comply with the requirements of IEC
60034-17 regarding normal motors controlled by drives,
IEC 60034-25 regarding motors designed to be controlled by drives, and NEMA MG 1-1998 Part 31.4.4.2 for inverter fed motors. The power sizes in the following tables do not comply with NEMA MG 1-1998 Part 30.2.2.8 for general purpose motors.
86 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
380–500 V
Power size [kW (hp)]
315–400 (450–550)
450–500 (600–650)
Cable [m (ft)]
5 (16)
30 (98)
150 (492)
300 (984)
5 (16)
30 (98)
150 (492)
300 (984)
Mains voltage
[V]
460
460
460
460
460
460
460
460
Rise time [
0.23
0.72
0.46
1.84
0.42
0.57
0.63
2.21
µ s] Peak voltage [V]
1038
1061
1142
1244
1042
1200
1110
1175
Table 10.15 NEMA dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
315–400 (450–550)
450–500 (600–650)
Cable [m (ft)]
5 (16)
30 (98)
150 (492)
300 (984)
5 (16)
30 (98)
150 (492)
300 (984)
Mains voltage
[V]
460
460
460
460
460
460
460
460
Rise time [
0.33
1.27
0.84
2.25
0.53
1.22
0.90
2.29
µ s] Peak voltage [V]
1038
1061
1142
1244
1042
1200
1110
1175
Table 10.16 IEC dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
315–400 (450–550)
450–500 (600–650)
Cable [m (ft)]
5 (16)
30 (98)
150 (492)
5 (16)
30 (98)
150 (492)
Mains voltage
[V]
460
460
460
460
460
460
Rise time [
0.17
–
0.41
0.17
–
0.22
µ s] Peak voltage [V]
1017
–
1268
1042
–
1233
Table 10.17 NEMA dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V
Power size [kW (hp)]
315–400 (450–550)
450–500 (600–650)
Cable [m (ft)]
5 (16)
30 (98)
150 (492)
5 (16)
30 (98)
150 (492)
Mains voltage
[V]
460
460
460
460
460
460
Rise time [
0.26
–
0.70
0.27
–
0.52
µ s] Peak voltage [V]
1017
–
1268
1042
–
1233
Table 10.18 IEC dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–500 V dU/dt [V/ µ s]
2372
644
1160
283
1295
820
844
239 dU/dt [V/ µ s]
2556
668
1094
443
1569
1436
993
411 dU/dt [V/ µ s]
3176
–
1311
3126
–
2356 dU/dt [V/ µ s]
3128
–
1448
3132
–
1897
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
87
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
525–690 V
Power size [kW (hp)]
355–560 (400–600)
630–710 (650–750)
Cable [m (ft)]
30 (98)
50 (164)
5 (16)
20 (65)
50 (164)
Mains voltage
[V]
690
690
690
690
690
Rise time [
0.37
0.86
0.25
0.33
0.82
µ s] Peak voltage [V]
1625
2030
1212
1525
2040
Table 10.19 IEC dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 525–690 V
Power size [kW (hp)]
355–560 (400–600)
630–710 (650–750)
Cable [m (ft)]
5 (16)
48 (157)
150 (492)
5 (16)
48 (157)
150 (492)
Mains voltage
[V]
690
690
690
690
690
690
Rise time [ µ s]
0.23
0.38
0.94
0.26
0.46
0.94
Peak voltage [V]
1450
1637
1762
1262
1625
1710
Table 10.20 IEC dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 525–690 V
NOTICE
TEST RESULTS
NEMA does not provide dU/dt results for 690 V.
dU/dt [V/ µ s]
3494
1895
3850
3712
1996 dU/dt [V/ µ s]
5217
3400
1502
3894
2826
1455
10.14 Electromagnetic Compatibility (EMC) Overview
Electrical devices both generate interference and are affected by interference from other generated sources. The electromagnetic compatibility (EMC) of these effects depends on the power and the harmonic characteristics of the devices.
Uncontrolled interaction between electrical devices in a system can degrade compatibility and impair reliable operation.
Interference takes the form of the following:
•
Electrostatic discharges
•
Rapid voltage fluctuations
•
High-frequency interference
Electrical interference is most commonly found at frequencies in the range 150 kHz to 30 MHz. Airborne interference from the drive system in the range 30 MHz to 1 GHz is generated from the inverter, motor cable, and the motor.
Capacitive currents in the motor cable, coupled with a high dU/dt from the motor voltage, generate leakage currents. See
. Shielded motor cables have higher capacitance between the phase wires and the shield, and again
between the shield and ground. This added cable capacitance, along with other parasitic capacitance and motor inductance, changes the electromagnetic emission signature produced by the unit. The change in electromagnetic emission signature occurs mainly in emissions less than 5 MHz. Most of the leakage current (I1) is carried back to the unit through the PE (I3), leaving only a small electromagnetic field (I4) from the shielded motor cable. The shield reduces the radiated interference but increases the low-frequency interference on the mains.
88 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
z z z z
PE
L3
PE
L1
L2
Design Guide
C
S U
V
W
I
2
I
3
C
S
I
4
I
1
C
S
1
2
C
S
I
4
C
S
C
S
3 4 5 6
1 Ground wire
2 Shield
3 AC mains supply
4 Drive
5 Shielded motor cable
6 Motor
Illustration 10.16 Electric Model Showing Possible Leakage Currents
Cs Possible shunt parasitic capacitance paths (varies with different installations)
I1 Common-mode leakage current
I2 Shielded motor cable
I3 Safety ground (fourth conductor in motor cables
I4 Unintended common-mode current
– –
10.14.1 EMC Test Results
The following test results have been obtained using a drive (with options if relevant), a shielded control cable, a control box with potentiometer, a motor, and motor shielded cable.
RFI filter type
Standards and requirements
EN 55011
EN/IEC 61800-3
H2
FC 302 90–800 kW 380–500 V
90–1200 kW 525–
690 V
No
No
H4
FC 302 90–800 kW 380–500 V No
90–315 kW 525–690 V No
Table 10.21 EMC Test Results (Emission and Immunity) and light industries
Conducted emission
Class B
Housing, trades
Class A group 1
Industrial environment
Class A group
2
Industrial environment
Category C1
First environment
Home and office
Category C2
First environment
Home and office
Category C3
Second environment
Industrial
Radiated emission
Class B
Housing, trades
Class A group 1
Industrial and light industries environment
Category C1
First environment
Home and office
Category C2
First environment
Home and office
No
No
150 m (492 ft)
150 m (492 ft)
150 m (492 ft)
150 m (492 ft)
30 m (98 ft) 150 m (492 ft)
No
No
No
No
No
No
Yes
No
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
89
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
WARNING
This type of power drive system is not intended to be used on a low-voltage public network that supplies domestic premises. Radio frequency interference is expected if used on such a network, and supplementary mitigation measures may be required.
10.14.2 Emission Requirements
According to the EMC product standard for adjustable speed drives EN/IEC 61800-3:2004, the EMC requirements depend on the environment in which the drive is installed. These environments along with the mains voltage supply requirements are defined in
The drives comply with EMC requirements described in IEC/EN 61800-3 (2004)+AM1 (2011), category C3, for equipment having greater than 100 A per-phase current draw, installed in the second environment. Compliance testing is performed with a 150 m (492 ft) shielded motor cable.
Category
(EN 61800-3)
Definition Conducted emission (EN 55011)
C1
C2
C3
C4
First environment (home and office) with a supply voltage less than 1000 V
First environment (home and office) with a supply voltage less than 1000 V, which is not plug-in or movable and where a professional is intended to be used to install or commission the system.
Second environment (industrial) with a supply voltage lower than 1000 V
Second environment with the following:
•
Supply voltage equal to or above 1000 V
•
Rated current equal to or above 400 A
•
Intended for use in complex systems
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan must be made.
Table 10.22 Emission Requirements
When the generic emission standards are used, the drives are required to comply with
Environment Generic Standard
First environment
(home and office)
Second environment
(industrial environment)
EN/IEC 61000-6-3 Emission standard for residential, commercial, and light industrial environments.
EN/IEC 61000-6-4 Emission standard for industrial environments.
Table 10.23 Generic Emission Standard Limits
Conducted emission requirement according to EN 55011 limits
Class B
Class A Group 1
90 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
10.14.3 Immunity Requirements
The immunity requirements for drives depend on the installation environment. The requirements for the industrial environment are higher than the requirements for the home and office environment. All Danfoss drives comply with the requirements for both the industrial and the home/office environment.
To document immunity against burst transient, the following immunity tests have been performed on a drive (with options if relevant), a shielded control cable, and a control box with potentiometer, motor cable, and motor. The tests were performed in accordance with the following basic standards. For more details, see
•
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human beings.
•
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the effects of radar, radio communication equipment, and mobile communications equipment.
•
EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor, relay, or similar devices.
•
EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about by lightning strikes near installations.
•
EN 61000-4-6 (IEC 61000-4-6): RF common mode: Simulation of the effect from radio-transmission equipment joined by connection cables.
Basic standard
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
Relay wires
Application and Fieldbus options
LCP cable
External 24 V DC
Burst
IEC 61000-4-4
B
4 kV CM
4 kV CM
4 kV CM
4 kV CM
2 kV CM
2 kV CM
2 kV CM
2 kV CM
Surge
IEC 61000-4-5
B
2 kV/2 Ω DM
4 kV/12 Ω CM
4 kV/2
4 kV/2 Ω 1)
4 kV/2 Ω 1)
2 kV/2 Ω
2 kV/2
Ω
Ω
2 kV/2 Ω
2 kV/2 Ω
1)
1)
1)
1)
1)
ESD
IEC
61000-4-2
B
–
–
–
–
–
–
–
–
2 kV CM
2 V CM
2 kV/2 Ω 1)
0.5 kV/2 Ω DM
1 kV/12 Ω CM
–
–
–
Enclosure – 8 kV AD
6 kV CD
Table 10.24 EMC Immunity Form, Voltage Range: 380–500 V, 525–600 V, 525–690 V
1) Injection on cable shield
AD: air discharge; CD: contact discharge; CM: common mode; DM: differential mode
Radiated electromagnetic Field
IEC 61000-4-3
A
–
–
–
–
–
–
–
–
–
–
10 V/m
RF common mode voltage
IEC 61000-4-6
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
–
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
91
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
10.14.4 EMC Compatibility
NOTICE
OPERATOR RESPONSIBILITY
According to the EN 61800–3 standard for variable-speed drive systems, the operator is responsible for ensuring
EMC compliance. Manufacturers can offer solutions for operation conforming to the standard. Operators are responsible for applying these solutions, and for paying the associated costs.
There are 2 options for ensuring electromagnetic compatibility.
•
Eliminate or minimize interference at the source of emitted interference.
•
Increase the immunity to interference in devices affected by its reception.
RFI filters
The goal is to obtain systems that operate stably without radio frequency interference between components. To achieve a high level of immunity, use drives with highquality RFI filters.
NOTICE
RADIO INTERFERENCE
In a domestic environment, this product can cause radio interference in which case supplementary mitigation measures are required.
PELV and galvanic isolation compliance
All E1h–E4h drives control and relay terminals comply with
PELV (excluding grounded Delta leg above 400 V).
Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creepage/clearance distances. These requirements are described in the EN 61800–5–1 standard.
Electrical isolation is provided as shown (see
). The components described comply with
both PELV and the galvanic isolation requirements.
8
7 6 4 3
1
M
5 2
1 Current transducers
2 Galvanic isolation for the RS485 standard bus interface
3 Gatedrive for the IGBTs
4 Supply (SMPS) including signal isolation of V DC, indicating the intermediate current voltage
5 Galvanic isolation for the 24 V back-up option
6 Opto-coupler, brake module (optional)
7 Internal inrush, RFI, and temperature measurement circuits
8 Customer relays
Illustration 10.17 Galvanic Isolation
10.15 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in the operating guide . For an example of proper EMC installation, see
NOTICE
TWISTED SHIELD ENDS (PIGTAILS)
Twisted shield ends increase the shield impedance at higher frequencies, which reduces the shield effect and increases the leakage current. Avoid twisted shield ends by using integrated shield clamps.
•
For use with relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current loops.
•
Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate through the mounting screws to the drive chassis.
•
Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit.
92 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
NOTICE
SHIELDED CABLES
If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency (RF) emission levels.
•
Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system.
•
Avoid placing cables with a sensitive signal level alongside motor and brake cables.
•
For communication and command/control lines, follow the particular communication protocol standards. For example, USB must use shielded cables, but RS485/ethernet can use shielded UTP or unshielded UTP cables.
•
Ensure that all control terminal connections are
PELV.
NOTICE
EMC INTERFERENCE
Use shielded cables for motor and control wiring, and separate cables for mains input, motor wiring, and control wiring. Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance. Minimum 200 mm (7.9 in) clearance between mains input, motor, and control cables are required.
NOTICE
INSTALLATION AT HIGH ALTITUDE
There is a risk for overvoltage. Isolation between components and critical parts could be insufficient, and not comply with PELV requirements. Reduce the risk for overvoltage by using external protective devices or galvanic isolation.
For installations above 2000 m (6500 ft) altitude, contact
Danfoss regarding PELV compliance.
NOTICE
PELV COMPLIANCE
Prevent electric shock by using protective extra low voltage (PELV) electrical supply and complying with local and national PELV regulations.
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
93
10 10
Electrical Installation Con...
VLT® AutomationDrive FC 302
6
7
1
90
10 10
2
3
4
5
L1
L2
L3
PE
4
4
PE u v w
18
3
4
1
2
7
8
5
6
9
PLC
Minimum 16 mm 2 (6 AWG) equalizing cable
Control cables
Minimum 200 mm (7.9 in) between control cables, motor cables, and mains cables.
Mains supply
Bare (unpainted) surface
Star washers
Brake cable (shielded)
Motor cable (shielded)
Illustration 10.18 Example of Proper EMC Installation
10 Mains cable (unshielded)
11 Output contactor, and so on
12 Cable insulation stripped
13 Common ground busbar. Follow local and national requirements for cabinet grounding.
14 Brake resistor
15 Metal box
16 Connection to motor
17 Motor
18 EMC cable gland
94 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
13
14
15
16
17
10
11
8
9
12
Electrical Installation Con...
Design Guide
10.16 Harmonics Overview
Non-linear loads such as found with drives do not draw current uniformly from the power line. This non-sinusoidal current has components which are multiples of the basic current frequency. These components are referred to as harmonics. It is important to control the total harmonic distortion on the mains supply. Although the harmonic currents do not directly affect electrical energy consumption, they generate heat in wiring and transformers that can affect other devices on the same power line.
10.16.1 Harmonic Analysis
Since harmonics increase heat losses, it is important to design systems with harmonics in mind to prevent overloading the transformer, inductors, and wiring. When necessary, perform an analysis of the system harmonics to determine equipment effects.
A non-sinusoidal current is transformed with a Fourier series analysis into sine-wave currents at different frequencies, that is, different harmonic currents I
N
with
50 Hz or 60 Hz as the basic frequency.
Abbreviation f
1
I
1
U
1
I n
U n n
Description
Basic frequency (50 Hz or 60 Hz)
Current at the basic frequency
Voltage at the basic frequency
Current at the n th harmonic frequency
Voltage at the n th harmonic frequency
Harmonic order
Table 10.25 Harmonics-related Abbreviations
Current
Frequency
Basic current (I
1
)
I
1
50 Hz
I
5
Harmonic current (I
250 Hz
I
7
350 Hz
Table 10.26 Basic Currents and Harmonic Currents n
)
I
11
550 Hz
Current
Input current
I
Harmonic current
RMS
1.0
I
1
0.9
I
5
0.5
I
7
0.2
I
11-49
<0.1
Table 10.27 Harmonic Currents Compared to the RMS Input
Current
The voltage distortion on the mains supply voltage depends on the size of the harmonic currents multiplied by the mains impedance for the frequency in question. The total voltage distortion (THDi) is calculated based on the individual voltage harmonics using this formula:
10.16.2 Effect of Harmonics in a Power
Distribution System
In
, a transformer is connected on the primary side to a point of common coupling PCC1, on the medium voltage supply. The transformer has an impedance
Z xfr
and feeds several loads. The point of common coupling where all loads are connected is PCC2. Each load connects through cables that have an impedance Z
1
, Z
2
, Z
3
.
PCC
MV
LV
Z xfr
Z
#
Point of common coupling
Medium voltage
Low voltage
Transformer impedance
Modeling resistance and inductance in the wiring
Illustration 10.19 Small Distribution System
Harmonic currents drawn by non-linear loads cause distortion of the voltage because of the voltage drop on the impedances of the distribution system. Higher impedances result in higher levels of voltage distortion.
Current distortion relates to apparatus performance and it relates to the individual load. Voltage distortion relates to system performance. It is not possible to determine the voltage distortion in the PCC knowing only the harmonic performance of the load. To predict the distortion in the
PCC, the configuration of the distribution system and relevant impedances must be known.
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
95
Electrical Installation Con...
VLT® AutomationDrive FC 302
10 10
A commonly used term for describing the impedance of a grid is the short circuit ratio R sce
, where R sce
is defined as the ratio between the short circuit apparent power of the supply at the PCC (S sc
) and the rated apparent power of the load.
(S equ
).
R sce
=
S
S sc equ where S sc
2
= U supply
and S equ
= U × I equ
Negative effects of harmonics
•
Harmonic currents contribute to system losses (in cabling and transformer).
•
Harmonic voltage distortion causes disturbance to other loads and increases losses in other loads.
10.16.3 IEC Harmonic Standards
In most of Europe, the basis for the objective assessment of the quality of mains power is the Electromagnetic Compatibility of Devices Act (EMVG). Compliance with these regulations ensures that all devices and networks connected to electrical distribution systems fulfill their intended purpose without generating problems.
Standard
EN 61000-2-2, EN 61000-2-4, EN 50160
EN 61000-3-2, 61000-3-12
EN 50178
Definition
Define the mains voltage limits required for public and industrial power grids.
Regulate mains interference generated by connected devices in lower current products.
Monitors electronic equipment for use in power installations.
Table 10.28 EN Design Standards for Mains Power Quality
There are 2 European standards that address harmonics in the frequency range from 0 Hz to 9 kHz:
EN 61000–2–2 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signaling in Public Low-Voltage
Power Supply Systems
The EN 61000–2–2 standard states the requirements for compatibility levels for PCC (point of common coupling) of lowvoltage AC systems on a public supply network. Limits are specified only for harmonic voltage and total harmonic distortion of the voltage. EN 61000–2–2 does not define limits for harmonic currents. In situations where the total harmonic distortion
THD(V)=8%, PCC limits are identical to those limits specified in the EN 61000–2–4 Class 2.
EN 61000–2–4 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signaling in Industrial Plants)
The EN 61000–2–4 standard states the requirements for compatibility levels in industrial and private networks. The standard further defines the following 3 classes of electromagnetic environments:
•
Class 1 relates to compatibility levels that are less than the public supply network, which affects equipment sensitive to disturbances (lab equipment, some automation equipment, and certain protection devices).
•
Class 2 relates to compatibility levels that are equal to the public supply network. The class applies to PCCs on the public supply network and to IPCs (internal points of coupling) on industrial or other private supply networks. Any equipment designed for operation on a public supply network is allowed in this class.
•
Class 3 relates to compatibility levels greater than the public supply network. This class applies only to IPCs in industrial environments. Use this class where the following equipment is found:
-
-
-
Large drives.
Welding machines.
Large motors starting frequently.
Loads that change quickly.
Typically, a class cannot be defined ahead of time without considering the intended equipment and processes to be used in the environment. VLT ® high-power drives observe the limits of Class 3 under typical supply system conditions (R
SC
>10 or
Vk
Line
<10%).
96 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Electrical Installation Con...
Design Guide
Harmonic order (h)
5
7
11
13
17
17 ˂ h≤49
Table 10.29 Compatibility Levels for Harmonics
Class 1 (V h
%)
3
3
3
3
2
2.27 x (17/h) – 0.27
Class 2 (V
6
5
3.5
3
2 h
%)
2.27 x (17/h) – 0.27
THDv
Class 1
5%
Class 2
8%
Table 10.30 Compatibility Levels for the Total Harmonic Voltage Distortion THDv
10.16.4 Harmonic Compliance
Danfoss drives comply with the following standards:
•
IEC61000-2-4
•
IEC61000-3-4
•
G5/4
10.16.5 Harmonic Mitigation
In cases where extra harmonic suppression is required, Danfoss offers the following mitigation equipment:
•
VLT ® 12-pulse drives
•
VLT ® AHF filters
•
VLT ® Low Harmonic Drives
•
VLT ® Active Filters
Class 3 (V h
%)
8
7
5
4.5
4
4.5 x (17/h) – 0.5
Class 3
10%
Selecting the right solution depends on several factors:
•
The grid (background distortion, mains unbalance, resonance, and type of supply (transformer/generator).
•
Application (load profile, number of loads, and load size).
•
Local/national requirements/regulations (such as IEEE 519, IEC, and G5/4).
•
Total cost of ownership (initial cost, efficiency, and maintenance).
10.16.6 Harmonic Calculation
Use the free Danfoss MCT 31 calculation software to determine the degree of voltage pollution on the grid and needed precaution. The VLT ® Harmonic Calculation MCT 31 is available at www.danfoss.com
.
10 10
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
97
Basic Operating Principles ...
VLT® AutomationDrive FC 302
11 Basic Operating Principles of a Drive
11 11
This chapter provides an overview of the primary assemblies and circuitry of a Danfoss drive. It describes the internal electrical and signal processing functions. A description of the internal control structure is also included.
11.1 Description of Operation
A drive is an electronic controller that supplies a regulated amount of AC power to a 3-phase inductive motor. By supplying variable frequency and voltage to the motor, the drive varies the motor speed or maintains a constant speed as the load on the motor changes. Also, the drive can stop and start a motor without the mechanical stress associated with a line start.
In its basic form, the drive can be divided into the following 4 main areas:
Rectifier
The rectifier consists of SCRs or diodes that convert 3phase AC voltage to pulsating DC voltage.
DC link (DC bus)
The DC-link consists of inductors and capacitor banks that stabilize the pulsating DC voltage.
Inverter
The inverter uses IGBTs to convert the DC voltage to variable voltage and variable frequency AC.
Control
The control area consists of software that runs the hardware to produce the variable voltage that controls and regulates the AC motor.
1 2 3
11.2 Drive Controls
The following processes are used to control and regulate the motor:
•
User input/reference.
•
Feedback handling.
•
User-defined control structure.
Open loop/closed-loop mode.
Motor control (speed, torque, or process).
•
Control algorithms (VVC + , flux sensorless, flux with motor feedback, and internal current control
VVC + ).
11.2.1 User Inputs/References
The drive uses an input source (also called reference) to control and regulate the motor. The drive receives this input either
•
Manually via the LCP. This method is referred to as local [Hand On].
•
Remotely via analog/digital inputs and various serial interfaces (RS485, USB, or an optional fieldbus). This method is referred to as remote
[Auto On] and is the default input setting.
Active reference
The term active reference refers to the active input source.
The active reference is configured in parameter 3-13 Reference Site . See
and
For more information, see the programming guide .
L1
L2
L3
T1
T2
T3
1
2
3
Rectifier (SCR/diodes)
DC link (DC bus)
Inverter (IGBTs)
Illustration 11.1 Internal Processing
98 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Basic Operating Principles ...
Design Guide
Remote reference
Local reference
(Auto On)
(Hand On)
Remote
Linked to hand/auto
Local
Reference
LCP keys:
(Hand On), (Off), and (Auto On)
P 3-13 Reference Site
Illustration 11.2 Selecting Active Reference
LCP Keys
[Hand On]
[Hand On] ⇒ (Off)
[Auto On]
[Auto On] ⇒ (Off)
All keys
All keys
Parameter 3-13 Reference
Site
Linked to hand/auto
Linked to hand/auto
Linked to hand/auto
Linked to hand/auto
Local
Remote
Active
Reference
Local
Local
Remote
Remote
Local
Remote
Table 11.1 Local and Remote Reference Configurations
11.2.2 Remote Handling of References
Remote handling of reference applies to both open-loop and closed-loop operation. See
.
Up to 8 internal preset references can be programmed into the drive. The active internal preset reference can be selected externally through digital control inputs or through the serial communications bus.
External references can also be supplied to the drive, most commonly through an analog control input. All reference sources and the bus reference are added to produce the total external reference. The active reference can be selected from the following:
•
External reference
•
Preset reference
•
Setpoint
•
Sum of the external reference, preset reference, and setpoint
The active reference can be scaled. The scaled reference is calculated as follows:
Where X is the external reference, the preset reference, or the sum of these references, and Y is parameter 3-14 Preset
Relative Reference in [%].
If Y, parameter 3-14 Preset Relative Reference , is set to 0%, the scaling does not affect the reference.
11 11
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
99
Basic Operating Principles ...
VLT® AutomationDrive FC 302
P 3-14
Preset relative ref.
Input command:
Preset ref. bit0, bit1, bit2
[4]
[5]
[6]
[7]
[0]
[1]
[2]
[3]
No function
Analog inputs
Frequency inputs
Ext. closed loop outputs
DigiPot
Input command:
Freeze ref.
P 3-04
Ref. function
Y
X
Relative
X+X*Y
/100
±200%
±200% on
±200% off
Input command:
Ref. Preset
±100%
& increase/ decrease ref.
max ref.
%
% min ref.
P 1-00
Configuration mode
Open loop
Scale to
RPM,Hz or %
Scale to
Closed loop unit
Closed loop
Remote ref.
11 11
No function
Analog inputs
Frequency inputs
Ext. closed loop outputs
DigiPot
No function
Analog inputs
Frequency inputs
Ext. closed loop outputs
DigiPot
Bus reference
Illustration 11.3 Remote Handling of Reference
External reference in %
Setpoint
Closed loop
±200%
From Feedback Handling
Ref. in %
Increase
0/1
DigiPot
Digipot ref.
±200%
Clear
0/1
100 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Basic Operating Principles ...
Design Guide
11.2.3 Feedback Handling
Feedback handling can be configured to work with applications requiring advanced control, such as multiple setpoints and multiple types of feedback. See
. Three types of control are common:
Single zone (single setpoint)
This control type is a basic feedback configuration. Setpoint 1 is added to any other reference (if any) and the feedback signal is selected.
Multi-zone (single setpoint)
This control type uses 2 or 3 feedback sensors but only 1 setpoint. The feedback can be added, subtracted, or averaged. In addition, the maximum or minimum value can be used. Setpoint 1 is used exclusively in this configuration.
Multi-zone (setpoint/feedback)
The setpoint/feedback pair with the largest difference controls the speed of the drive. The maximum value attempts to keep all zones at or below their respective setpoints, while the minimum value attempts to keep all zones at or above their respective setpoints.
Example
A 2-zone, 2-setpoint application. Zone 1 setpoint is 15 bar, and the feedback is 5.5 bar. Zone 2 setpoint is 4.4 bar, and the feedback is 4.6 bar. If maximum is selected, the zone 2 setpoint and feedback are sent to the PID controller, since it has the smaller difference (feedback is higher than setpoint, resulting in a negative difference). If minimum is selected, the zone 1 setpoint and feedback is sent to the PID controller, since it has the larger difference (feedback is lower than setpoint, resulting in a positive difference).
0%
Setpoint to
Reference
Handling
Setpoint 1
P 20-21
Setpoint 2
P 20-22
Setpoint 3
P 20-23
Multi setpoint min.
Multi setpoint max.
0%
0%
11 11
Feedback
Feedback 1 Source
P 20-00
Feedback 2 Source
P 20-03
Feedback 3 Source
P 20-06
Feedback conv.
P 20-01
Feedback conv.
P 20-04
Feedback conv.
P 20-07
Feedback 1
Feedback 2
Feedback 3
Feedback 1 only
Feedback 2 only
Feedback 3 only
Sum (1+2+3)
Difference (1-2)
Average (1+2+3)
Minimum (1|2|3)
Maximum (1|2|3)
0%
Feedback Function
P 20-20
Illustration 11.4 Block Diagram of Feedback Signal Processing
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
101
Basic Operating Principles ...
VLT® AutomationDrive FC 302
Feedback conversion
In some applications, it is useful to convert the feedback signal. One example is using a pressure signal to provide flow feedback. Since the square root of pressure is proportional to flow, the square root of the pressure signal yields a value proportional to the flow, see
.
Reference signal
Reference
PID
Desired flow
FB conversion
FB P
Flow
Flow
P
FB signal
P
Illustration 11.5 Feedback Conversion
11 11
11.2.4 Control Structure Overview
The control structure is a software process that controls the motor based on user-defined references (for example, RPM) and whether feedback is used/not used (closed loop/open loop). The operator defines the control in parameter 1-00 Configuration Mode .
The control structures are as follows:
Open-loop control structure
•
Speed (RPM)
•
Torque (Nm)
Closed-loop control structure
•
Speed (RPM)
•
Torque (Nm)
•
Process (user-defined units, for example, feet, lpm, psi, %, bar)
102 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Basic Operating Principles ...
Design Guide
11.2.5 Open-loop Control Structure
In open-loop mode, the drive uses 1 or more references (local or remote) to control the speed or torque of the motor. There are 2 types of open-loop control:
•
Speed control. No feedback from the motor.
•
Torque control. Used in VVC + mode. The function is used in mechanically robust applications, but its accuracy is limited. Open loop torque function works only in 1 speed direction. The torque is calculated based on current measurement within the drive. See
chapter 12 Application Examples
.
In the configuration shown in
, the drive operates in open-loop mode. It receives input from either the LCP
(hand-on mode) or via a remote signal (auto-on mode). The signal (speed reference) is received and conditioned with the following:
•
Programmed minimum and maximum motor speed limits (in RPM and Hz).
•
Ramp-up and ramp-down times.
•
Motor rotation direction.
The reference is then passed on to control the motor.
Reference handling
Remote reference
P 4-13
Motor speed high limit [RPM]
P 4-14
Motor speed high limit [Hz]
Auto mode
Hand mode
Remote
Linked to hand/auto
Local
Reference
Local reference scaled to
RPM or Hz
P 4-11
Motor speed low limit [RPM]
LCP Hand on, off and auto on keys
P 3-13
Reference site
P 4-12
Motor speed low limit [Hz]
Illustration 11.6 Block Diagram of an Open-loop Control Structure
P 3-4* Ramp 1
P 3-5* Ramp 2
Ramp
100%
0%
100%
-100%
To motor control
P 4-10
Motor speed direction
11 11
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
103
Basic Operating Principles ...
VLT® AutomationDrive FC 302
11 11
11.2.6 Closed-loop Control Structure
In closed-loop mode, the drive uses 1 or more references (local or remote) and feedback sensors to control the motor. The drive receives a feedback signal from a sensor in the system. It then compares this feedback to a setpoint reference value and determines if there is any discrepancy between these 2 signals. The drive then adjusts the speed of the motor to correct the discrepancy.
For example, consider a pump application in which the speed of the pump is controlled so that the static pressure in a pipe is constant (see
). The drive receives a feedback signal from a sensor in the system. It compares this feedback
to a setpoint reference value and determines the discrepancy if any, between these 2 signals. It then adjusts the speed of the motor to compensate for the discrepancy.
The static pressure setpoint is the reference signal to the drive. A static pressure sensor measures the actual static pressure in the pipe and provides this information to the drive as a feedback signal. If the feedback signal exceeds the setpoint reference, the drive ramps down to reduce the pressure. Similarly, if the pipe pressure is lower than the setpoint reference, the drive ramps up to increase the pump pressure.
There are 3 types of closed-loop control:
•
Speed control. This type of control requires a speed PID feedback for an input. A properly optimized speed closedloop control has higher accuracy than a speed open-loop control. The speed control selects which input to use as speed PID feedback in parameter 7-00 Speed PID Feedback Source .
•
Torque control. Used in flux mode with encoder feedback, this control offers superior performance in all 4 quadrants and at all motor speeds.
The torque control function is used in applications where the torque on the motor output shaft is controlling the application as tension control. Torque control is selected in parameter 1-00 Configuration Mode , either in [4] VVC+ open loop or [2] Flux control closed loop with motor speed feedback . Torque setting is done by setting an analog, digital, or bus-controlled reference. The maximum speed limit factor is set in parameter 4-21 Speed Limit Factor
Source . When running torque control, it is recommended to make a full AMA procedure since the correct motor data is essential for optimal performance.
•
Process control. Used to control application parameters that can be measured by different sensors (pressure, temperature, and flow) and be affected by the connected motor through a pump or fan.
100%
0%
Ref.
Handling
(Illustration)
+
_
Feedback
Handling
(Illustration)
*[-1]
P 20-81
PID Normal/Inverse
Control
Illustration 11.7 Block Diagram of Closed-loop Controller
PID
100%
-100%
P 4-10
Motor speed direction
Scale to speed
To motor control
Programmable features
While the default values for the drive in closed loop often provide satisfactory performance, system control can often be optimized by tuning the PID parameters. Auto tuning is provided for this optimization.
•
Inverse regulation - motor speed increases when a feedback signal is high.
•
Start-up frequency - lets the system quickly reach an operating status before the PID controller takes over.
•
Built-in lowpass filter - reduces feedback signal noise.
104 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Basic Operating Principles ...
Design Guide
11.2.7 Control Processing
See Active/Inactive Parameters in Different Drive Control Modes in the programming guide for an overview of which control configuration is available for your application, depending on selection of AC motor or PM non-salient motor.
11.2.7.1 Control Structure in VVC
+
Ref.
P 1-00
Config. mode
P 4-13
Motor speed high limit (RPM)
P 4-14
Motor speed high limit (Hz)
High P 3-**
P 1-00
Config. mode
Ramp
Motor controller
P 4-19
Max. output freq.
+f max.
-f max.
+
_
Process
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
Low
P 4-11
Motor speed low limit (RPM)
P 4-12
Motor speed low limit (Hz)
+
_
P 7-0*
Speed
PID
P 7-00 Speed PID feedback source
Illustration 11.8 Control Structure in VVC + Open Loop and Closed-loop Configurations
Motor controller
P 4-19
Max. output freq.
+f max.
-f max.
In
, the resulting reference from the reference handling system is received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output of the motor control is then limited by the maximum frequency limit.
Parameter 1-01 Motor Control Principle is set to [1] VVC + and parameter 1-00 Configuration Mode is set to [0] Speed open loop .
If parameter 1-00 Configuration Mode is set to [1] Speed closed loop , the resulting reference is passed from the ramp limitation and speed limitation into a speed PID control. The speed PID control parameters are located in parameter group
7-0* Speed PID Ctrl . The resulting reference from the speed PID control is sent to the motor control limited by the frequency limit.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of, for example, speed or pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb and 7-3* Process PID Ctrl .
11 11
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
105
Basic Operating Principles ...
VLT® AutomationDrive FC 302
11.2.7.2 Control Structure in Flux Sensorless
P 1-00
Config. mode
Ref.
+
_
Process
PID
P 4-13 Motor speed high limit [RPM]
P 4-14 Motor speed high limit [Hz]
High P 3-**
Ramp
+
_
Low
P 4-11 Motor speed low limit [RPM]
P 4-12 Motor speed low limit [Hz]
P 7-0*
Speed
PID
Motor controller
P 4-19
Max. output freq.
+f max.
-f max.
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
Illustration 11.9 Control Structure in Flux Sensorless Open Loop and Closed-loop Configurations
11 11
In
, the resulting reference from the reference handling system is fed through the ramp and speed limitations as determined by the parameter settings indicated.
Parameter 1-01 Motor Control Principle is set to [2] Flux Sensorless and parameter 1-00 Configuration Mode is set to [0] Speed open loop . An estimated speed feedback is generated to the speed PID to control the output frequency. The speed PID must be set with its P, I, and D parameters ( parameter group 7-0* Speed PID control ).
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of that is, speed or pressure in the controlled application. The process PID parameters are found in parameter groups 7-2* Process Ctrl.
Feedb and 7-3* Process PID Ctrl .
106 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Basic Operating Principles ...
Design Guide
11.2.7.3 Control Structure in Flux with Motor Feedback
P 1-00
Config. mode
Torque
P 4-13 Motor speed high limit (RPM)
P 4-14 Motor speed high limit (Hz)
High P 3-**
Ref.
+
P 7-2*
Process
PID
Ramp
+
_ _
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
Low
P 4-11 Motor speed low limit (RPM)
P 4-12 Motor speed low limit (Hz)
P 7-00
PID source
Illustration 11.10 Control Structure in Flux with Motor Feedback Configuration
P 7-0*
Speed
PID
P 1-00
Config. mode
Motor controller
P 4-19
Max. output freq.
+f max.
-f max.
In
, the motor control in this configuration relies on a feedback signal from an encoder or resolver mounted directly on the motor (set in parameter 1-02 Flux Motor Feedback Source ). The resulting reference can be used as input for the speed PID control, or directly as a torque reference.
Parameter 1-01 Motor Control Principle is set to [3] Flux w motor feedb and parameter 1-00 Configuration Mode is set to [1]
Speed closed loop . The speed PID control parameters are in parameter group 7-0* Speed PID Control
Torque control can only be selected in the Flux with motor feedback ( parameter 1-01 Motor Control Principle ) configuration.
When this mode has been selected, the reference uses the Nm unit. It requires no torque feedback, since the actual torque is calculated based on the current measurement of the drive.
Process PID control can be used for closed-loop control of speed or pressure in the controlled application. The process PID parameters are located in parameter groups 7-2* Process Ctrl. Feedb and 7-3* Process PID Ctrl .
11.2.7.4 Internal Current Control in VVC
+
Mode
When the motor current/torque exceed the torque limits set in parameter 4-16 Torque Limit Motor Mode , parameter 4-17 Torque Limit Generator Mode , and parameter 4-18 Current Limit , the integral current limit control is activated.
When the drive is at the current limit during motor operation or regenerative operation, it tries to get below the preset torque limits as quickly as possible without losing control of the motor.
11 11
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
107
Application Examples VLT® AutomationDrive FC 302
12 Application Examples
12 12
The examples in this section are intended as a quick reference for common applications.
•
Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional Settings ).
•
Parameters associated with the terminals and their settings are shown next to the drawings.
•
Where switch settings for analog terminals A53 or
A54 are required, these settings are also shown.
•
For STO, a jumper wire may be required between terminal 12 and terminal 37 when using factory default programming values.
12.1 Programming a Closed-loop Drive
System
A closed-loop drive system usually consists of the following:
•
Motor
•
Drive
•
Encoder as feedback system
•
Mechanical brake
•
Brake resistor for dynamic braking
•
Transmission
•
Gear box
•
Load
Applications demanding mechanical brake control typically need a brake resistor.
Brake resistor
Transmission
Encoder
Motor
Mechanical brake
Gearbox
Load
Illustration 12.1 Basic Set-up for FC 302 Closed-loop Speed
Control
108 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Application Examples Design Guide
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
12.2 Wiring Configurations for Automatic
Motor Adaptation (AMA)
Parameters
Function Setting
Parameter 1-29
Automatic Motor
[1] Enable complete AMA
Adaptation
(AMA)
Parameter 5-12 T erminal 27
Digital Input
*=Default value
[2]* Coast inverse
Notes/comments: Set parameter group 1-2* Motor
Data according to motor nameplate.
+10 V
A IN
A IN
COM
A OUT
COM
20
27
29
32
12
13
18
19
33
37
50
53
54
55
42
39
Table 12.1 Wiring Configuration for AMA with T27 Connected
+10 V
A IN
A IN
COM
A OUT
COM
D IN
D IN
D IN
D IN
D IN
+24 V
FC
+24 V
D IN
D IN
COM
12
13
18
19
20
27
29
32
33
37
55
42
39
50
53
54
Parameters
Function Setting
Parameter 1-29
Automatic Motor
[1] Enable complete AMA
Adaptation
(AMA)
Parameter 5-12 T erminal 27
Digital Input
*=Default value
[0] No operation
Notes/comments: Set parameter group 1-2* Motor
Data according to motor nameplate.
Table 12.2 Wiring Configuration for AMA without
T27 Connected
+10 V
A IN
A IN
COM
A OUT
COM
U - I
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
12.3 Wiring Configurations for Analog
Speed Reference
55
42
39
50
53
54
20
27
29
32
12
13
18
19
33
37
+
-
-10 - +10V
Parameters
Function Setting
Parameter 6-10 T erminal 53 Low
0.07 V*
Voltage
10 V* Parameter 6-11 T erminal 53 High
Voltage
Parameter 6-14 T erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
1500 RPM
A53
+10 V
A IN
A IN
COM
A OUT
COM
+24 V
FC
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
20
27
29
32
12
13
18
19
33
37
50
53
54
55
42
39
Table 12.3 Wiring Configuration for Analog Speed Reference
(Voltage)
+
-
4 - 20mA
Parameters
Function Setting
Parameter 6-12 T erminal 53 Low
4 mA*
Current
20 mA* Parameter 6-13 T erminal 53 High
Current
Parameter 6-14 T erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T erminal 53 High
Ref./Feedb. Value
*=Default value
Notes/comments:
1500 RPM
U - I
A53
Table 12.4 Wiring Configuration for Analog Speed Reference
(Current)
12 12
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
109
Application Examples VLT® AutomationDrive FC 302
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
12.4 Wiring Configurations for Start/Stop
+10
A IN
A IN
COM
A OUT
COM
12
27
29
32
13
18
19
20
33
37
50
53
54
55
42
39
Parameters
Function Setting
Parameter 5-10 T erminal 18
[8] Start*
Digital Input
Parameter 5-12 T erminal 27
Digital Input
Parameter 5-19 T erminal 37 Safe
Stop
[0] No operation
[1] Safe
Torque Off
Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No operation , a jumper wire to terminal 27 is not needed.
+10 V
A IN
A IN
COM
A OUT
COM
D IN
D IN
D IN
D IN
D IN
+24 V
+24 V
D IN
D IN
COM
FC
27
29
32
33
37
12
13
18
19
20
50
53
54
55
42
39
Parameters
Function Setting
Parameter 5-10 T erminal 18
Digital Input
[9] Latched
Start
Parameter 5-12 T erminal 27
Digital Input
[6] Stop
Inverse
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No operation , a jumper wire to terminal 27 is not needed.
Table 12.5 Wiring Configuration for Start/Stop Command with
Safe Torque Off
Speed
Table 12.6 Wiring Configuration for Pulse Start/Stop
Speed
12 12
Start/Stop (18)
Illustration 12.2 Start/Stop with Safe Torque Off
Latched Start (18)
Stop Inverse (27)
Illustration 12.3 Latched Start/Stop Inverse
110 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Application Examples
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
FC
19
20
27
29
12
13
18
32
33
+10 V
A IN
A IN
COM
A OUT
COM
55
42
39
50
53
54
Design Guide
Parameters
Function Setting
Parameter 5-10 T erminal 18
[8] Start
Digital Input
Parameter 5-11 T erminal 19
Digital Input
[10]
Reversing*
Parameter 5-12 T erminal 27
Digital Input
Parameter 5-14 T erminal 32
Digital Input
Parameter 5-15 T erminal 33
Digital Input
Parameter 3-10 P reset Reference
[0] No operation
[16] Preset ref bit 0
[17] Preset ref bit 1
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
*=Default value
Notes/comments:
25%
50%
75%
100%
12.5 Wiring Configuration for an External
Alarm Reset
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
20
27
29
32
12
13
18
19
33
37
Parameters
Function Setting
Parameter 5-11 T erminal 19
[1] Reset
Digital Input
*=Default value
Notes/comments:
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
Table 12.7 Wiring Configuration for Start/Stop with Reversing and 4 Preset Speeds
Table 12.8 Wiring Configuration for an External Alarm Reset
12 12
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
111
12 12
Application Examples
12.6 Wiring Configuration for Speed
Reference Using a Manual
Potentiometer
+10 V
A IN
A IN
COM
A OUT
COM
+24 V
FC
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
50
53
54
55
42
39
20
27
29
32
12
13
18
19
33
37
Parameters
Function Setting
0.07 V* Parameter 6-10 T erminal 53 Low
Voltage
10 V* Parameter 6-11 T erminal 53 High
Voltage
Parameter 6-14 T erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T erminal 53 High
≈ 5kΩ
Ref./Feedb. Value
*=Default value
Notes/comments:
1500 RPM
U - I
A53
Table 12.9 Wiring Configuration for Speed Reference
(Using a Manual Potentiometer)
VLT® AutomationDrive FC 302
12.7 Wiring Configuration for Speed Up/
Speed Down
+10 V
A IN
A IN
COM
A OUT
COM
+24 V
FC
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
20
27
29
32
33
37
12
13
18
19
50
53
54
55
42
39
Parameters
Function Setting
Parameter 5-10 T erminal 18
[8] Start*
Digital Input
Parameter 5-12 T erminal 27
Digital Input
Parameter 5-13 T erminal 29
Digital Input
[19] Freeze
Reference
[21] Speed Up
Parameter 5-14 T erminal 32
Digital Input
*=Default value
Notes/comments:
[22] Speed
Down
Table 12.10 Wiring Configuration for Speed Up/Speed Down
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 12.4 Speed Up/Speed Down
112 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Application Examples Design Guide
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
12.8 Wiring Configuration for RS485
Network Connection
19
20
27
29
12
13
18
32
33
37
Parameters
Function Setting
Parameter 8-30
Protocol
FC*
1* Parameter 8-31
Address
Parameter 8-32
Baud Rate
*=Default value
9600*
Notes/comments:
Select protocol, address, and baud rate in the parameters.
+10 V
A IN
A IN
COM
A OUT
COM
55
42
39
50
53
54
04
05
06
61
68
69
01
02
03
+
-
RS-485
Table 12.11 Wiring Configuration for RS485 Network Connection
12 12
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
113
Application Examples VLT® AutomationDrive FC 302
12 12
+10 V
A IN
A IN
COM
A OUT
COM
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
VLT
20
27
29
32
33
12
13
18
19
37
50
53
54
55
42
39
U - I
A53
12.9 Wiring Configuration for a Motor
Thermistor
NOTICE
Thermistors must use reinforced or double insulation to meet PELV insulation requirements.
Parameters
Function Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor trip
Parameter 1-93 T hermistor Source
*=Default value
[1] analog input 53
Notes/comments:
If only a warning is wanted, set parameter 1-90 Motor Thermal
Protection to [1] Thermistor warning .
Table 12.12 Wiring Configuration for a Motor Thermistor
12.10 Wiring Configuration for a Relay Setup with Smart Logic Control
+10 V
A IN
A IN
COM
A OUT
COM
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
50
53
54
55
42
39
20
27
29
32
12
13
18
19
33
37
01
02
03
04
05
06
Parameters
Function Setting
Parameter 4-30
Motor Feedback
[1] Warning
Loss Function
100 RPM Parameter 4-31
Motor Feedback
Speed Error
Parameter 4-32
Motor Feedback
Loss Timeout
5 s
Parameter 7-00 S peed PID
Feedback Source
Parameter 17-11
Resolution (PPR)
[2] MCB 102
1024*
[1] On Parameter 13-00
SL Controller
Mode
Parameter 13-01
Start Event
Parameter 13-02
Stop Event
Parameter 13-10
Comparator
Operand
Parameter 13-11
Comparator
Operator
[19] Warning
[44] Reset key
[21] Warning no.
[1] ≈ (equal)*
Parameter 13-12
Comparator
Value
Parameter 13-51
SL Controller
Event
90
[22]
Comparator 0
Parameter 13-52
SL Controller
Action
Parameter 5-40 F unction Relay
*=Default value
[32] Set digital out A low
[80] SL digital output A
Notes/comments:
If the limit in the feedback monitor is exceeded, warning 90,
Feedback Mon.
is issued. The SLC monitors warning 90, Feedback
Mon.
and if the warning becomes true, relay 1 is triggered.
External equipment may require service. If the feedback error goes below the limit again within 5 s, the drive continues and the warning disappears. Reset relay 1 by pressing [Reset] on the
LCP.
Table 12.13 Wiring Configuration for a Relay Set-up with
Smart Logic Control
114 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Application Examples Design Guide
+24 V
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
FC
12.11 Wiring Configuration for Mechanical
Brake Control
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
20
27
29
32
12
13
18
19
33
37
01
02
03
04
05
06
Parameters
Function Setting
Parameter 5-40 F unction Relay
[32] Mech.
brake ctrl.
[8] Start* Parameter 5-10 T erminal 18
Digital Input
[11] Start reversing
Parameter 5-11 T erminal 19
Digital Input
Parameter 1-71 S tart Delay
Parameter 1-72 S tart Function
0.2
[5] VVC+/
FLUX
Clockwise
Parameter 1-76 S tart Current
Parameter 2-20
Release Brake
Current
Im,n
App.
dependent
Parameter 2-21
Activate Brake
Speed [RPM]
*=Default value
Notes/comments:
Half of nominal slip of the motor
Table 12.14 Wiring Configuration for Mechanical Brake Control
1-76
Current
Speed
1-71
Start (18)
Start reversing (19)
2-21 1-71
Relay output
Open
Closed
Illustration 12.5 Mechanical Brake Control
2-21
Time
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
115
12 12
Application Examples VLT® AutomationDrive FC 302
12 12
A
B
12.12 Configuring the Encoder
Before setting up the encoder, the basic wire configuration for a closed-loop speed control system is shown in
.
12 13 18 19 27 29 32 33 20 37
24 V or 10–30 V encoder
Illustration 12.6 Encoder Connection to the Drive
CW
The direction of the encoder, identified by looking into the shaft end, is determined by which order the pulses enter the drive.
•
Clockwise (CW) direction means channel A is 90 electrical degrees before channel B.
•
Counterclockwise (CCW) direction means channel
B is 90 electrical degrees before A.
12.13 Wire Configuration for Torque and
Stop Limit
In applications with an external electro-mechanical brake, such as hoisting applications, it is possible to stop the drive via a standard stop command and simultaneously activate the external electro-mechanical brake.
shows the programming of these drive connections.
If a stop command is active via terminal 18 and the drive is not at the torque limit, the motor ramps down to 0 Hz.
If the drive is at the torque limit and a stop command is activated, the system activates terminal 29 output
(programmed to [27] Torque limit & stop ). The signal to terminal 27 changes from logic 1 to logic 0 and the motor starts to coast. This process ensures that the hoist stops even if the drive itself cannot handle the required torque, for example due to excessive overload.
To program the stop and torque limit, connect to the following terminals:
Start/stop via terminal 18
( Parameter 5-10 Terminal 18 Digital Input [8] Start ).
Quick stop via terminal 27
( Parameter 5-12 Terminal 27 Digital Input [2] Coasting Stop,
Inverse ).
Terminal 29 output
( Parameter 5-02 Terminal 29 Mode [1] Terminal 29 Mode
Output parameter 5-31 Terminal 29 Digital Output [27] Torque limit & stop ).
Relay output [0] (Relay 1)
( Parameter 5-40 Function Relay [32] Mechanical Brake
Control ).
CCW
A
B
Illustration 12.7 24 V incremental encoder. Maximum cable length 5 m (16 ft).
116 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Application Examples Design Guide
12 13 18 19 27 29 32 33 20 37
External
24 V DC
+
Start
-
I max
0.1 Amp
P 5-40 [0] [32]
Mechanical brake connection
Illustration 12.8 Wire Configuration for Torque and Stop Limit
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
117
12 12
How to Order a Drive VLT® AutomationDrive FC 302
13 How to Order a Drive
13.1 Drive Configurator
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
F C T
21 22
X
23
X
24
S
25 26 27
X X X
28 29
X A
30 31
B
32 33
C
34 35 36 37 38 39
D
13 13
Table 13.1 Type Code String
Product groups 1–3
Drive series
Generation code
Power rating
Phases
Mains Voltage
Enclosure
Enclosure type
Enclosure class
Control supply voltage
Hardware configuration
RFI filter/Low Harmonic Drive/12pulse
Brake
Display (LCP)
Coating PCB
Mains option
Adaptation A
Adaptation B
Software release
Software language
A option
B options
C0 options, MCO
C1 options
C option software
D options
24–27
28
29–30
35
31–32
33–34
36–37
38–39
23
21
22
20
18
19
13–15
16–23
16–17
4–6
7
8–10
11
12
Table 13.2 Type Code Example for Ordering a Drive
Configure the correct drive for the proper application by using the internet-based drive configurator. The drive configurator is found on the global internet site: www.danfoss.com/drives . The configurator creates a type code string and an 8-digit sales number, which can be delivered to the local sales office. It is also possible to build a project list with several products and send it to a
Danfoss sales representative.
An example of a type code string is:
FC-302N355T5E20H4BGCXXXSXXXXA0BXCXXXXD0
The meaning of the characters in the string is defined in
. In the example above, a PROFIBUS DP-V1 and a
24 V back-up option is built-in.
Drives are delivered automatically with a language package relevant to the region from which they are ordered. Four regional language packages cover the following languages:
Language package 1
English, German, French, Danish, Dutch, Spanish, Swedish,
Italian, and Finnish.
Language package 2
English, German, Chinese, Korean, Japanese, Thai,
Traditional Chinese, and Bahasa Indonesian.
Language package 3
English, German, Slovenian, Bulgarian, Serbian, Romanian,
Hungarian, Czech, and Russian.
Language package 4
English, German, Spanish, English US, Greek, Brazilian
Portuguese, Turkish, and Polish.
To order drives with a different language package, contact the local Danfoss sales office.
118 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
How to Order a Drive Design Guide
Description
Product group
Drive series
Power rating
Phases
Mains voltage
Enclosure
RFI filter
Brake
Display
Coating PCB
Mains option
Hardware, adaptation A
Hardware, adaptation B
Software release
Position
1–3
4–6
8–10
11
11–12
13–15
16–17
18
19
20
21
22
23
24–28
Possible option
FC-
302: FC 302
N315: 315 kW (450 hp)
N355: 355 kW (500 hp)
N400: 400 kW (550 hp)
N450: 450 kW (600 hp)
N500: 500 kW (650 hp)
N560: 560 kW (750 hp)
N630: 630 kW (900 hp)
N710: 710 kW (1000 hp)
Three phases (T)
T5: 380–500 V AC
T7: 525–690 V AC
E00: IP00/Chassis (only enclosures E3h/E4h with top regen/loadshare)
E20: IP20/Chassis
E21: IP21/Type 1
E54: IP54/Type 12
E2M: IP21/Type 1 + mains shield
E5M: IP54/Type 12 + mains shield
H21: IP21/Type 1 + space heater
H54: IP54/Type 12 + space heater
C20: IP20/Type 1 + stainless steel back channel
C21: IP21/Type 1 + stainless steel back channel
C54: IP54/Type 12 + stainless steel back channel
C2M: IP21/Type 1 + mains shield + stainless steel back channel
C5M: IP54/Type 12 + mains shield + stainless steel back channel
C2H: IP21/Type 1 + space heater + stainless steel back channel
C5H: IP54/Type 12 + space heater + stainless steel back channel
H2: RFI filter, class A2 (C3)
H4: RFI filter, class A1 (C2)
X: No brake chopper
B: Brake chopper mounted
T: Safe torque off (STO)
U: Brake chopper + safe torque off
R: Regen terminals
S: Brake chopper + regen terminals (only enclosures E3h/E4h)
X: No LCP
G: Graphical LCP (LCP-102)
J: No LCP + USB through the door
L: Graphical LCP + USB through the door
C: Coated PCB
R: Coated PCB 3C3 + ruggedized
X: No mains option
3: Mains disconnect + fuses
7: Fuses
A: Fuses + load share terminals (only enclosures E3h/E4h)
D: Load share terminals (only enclosures E3h/E4h)
X: No option
X: No option
Q: Heat sink access
SXXX: Latest release - standard software
S067: Integrated motion control software
X: Standard language pack Software language 28
Table 13.3 Ordering Type Code for Enclosures E1h–E4h
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
119
13 13
How to Order a Drive VLT® AutomationDrive FC 302
13 13
Description
A option
B options
C0/ E0 options
C1 options/ A/B in C option adapter
C option software/E1 options
D options
Position Possible option
29–30 AX: No A option
A0: VLT ® PROFIBUS DP V1 MCA 101
A4: VLT ® DeviceNet MCA 104
A6: VLT ® CANopen MCA 105
A8: VLT ® EtherCAT MCA 124
AT: VLT ® PROFIBUS Converter MCA 113
AU: VLT ® PROFIBUS Converter MCA 114
AL: VLT ® PROFINET MCA 120
AN: VLT ® EtherNet/IP MCA 121
AQ: VLT ® POWERLINK MCA 122
AY: VLT ® Modbus TCP MCA 123
31–32 BX: No option
B2: VLT ® PTC Thermistor Card MCB 112
B4: VLT ® Sensor Input Option MCB 114
B6: VLT ® Safety Option MCB 150
B7: VLT ® Safety Option MCB 151
B8: VLT ® Safety Option MCB 152
BK: VLT ® General Purpose I/O Module MCB 101
BP: VLT ® Relay Card MCB 105
BR: VLT ® Encoder Input MCB 102
BU: VLT ® Resolver Option MCB 103
BY: VLT ® Extended Cascade Controller MCO101
BZ: MCB 108 Safe PLC I/O MCB 108
33–34
35
36–37
CX: No option
C4: VLT ® Motion Control Option MCO 305
X: No option
R: VLT ® Extended Relay Card MCB 113
XX: No software option
10: VLT ® Synchronizing Controller MCO-350
11: VLT ® Position Controller MCO-351
38–39 DX: No option
D0: VLT ® 24 V DC Supply MCB-107
Table 13.4 Type Code Ordering Options for Enclosures E1h–E4h
120 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
How to Order a Drive Design Guide
13.2 Ordering Numbers for Options and Accessories
Type
Miscellaneous hardware
PROFIBUS top entry
USB in the door
Ground bar
Description
Top entry for enclosure protection rating IP54.
USB extension cord kit to allow access to the drive controls via laptop computer without opening the drive.
More grounding points for E1h and E2h drives.
Mains shield, E1h
Mains shield, E2h
Terminal blocks
Shielding (cover) mounted in front of the power terminals to protect from accidental contact.
Shielding (cover) mounted in front of the power terminals to protect from accidental contact.
Screw terminal blocks for replacing spring loaded terminals.
(1 pc 10 pin 1 pc 6 pin and 1 pc 3-pin connectors)
Back-channel cooling kits
In bottom/out top, E3h
In bottom/out top, E3h
In bottom/out top, E4h
In back/out back, E1h
In back/out back, E2h
In back/out back, E3h
In back/out back, E4h
In bottom/out back, E3h
In bottom/out back, E3h
Allows the cooling air to be directed in through the bottom and out through the top of the drive. This kit used only for enclosure E3h with
600 mm (21.6 in) base plate.
Allows the cooling air to be directed in through the bottom and out through the top of the drive. This kit used only for enclosure E3h with
800 mm (31.5 in) base plate.
Allows the cooling air to be directed in through the bottom and out through the top of the drive. This kit used only for enclosure E4h with
800 mm (31.5 in) base plate.
Allows the cooling air to be directed in and out through the back of the drive. This kit used only for enclosures E1h.
Allows the cooling air to be directed in and out through the back of the drive. This kit used only for enclosures E2h.
Allows the cooling air to be directed in and out through the back of the drive. This kit used only for enclosures E3h.
Allows the cooling air to be directed in and out through the back of the drive. This kit used only for enclosures E4h.
Allows the cooling air to be directed in through the bottom and out through the back of the drive. This kit used only for enclosure E3h with 600 mm (21.6 in) base plate.
Allows the cooling air to be directed in through the bottom and out through the back of the drive. This kit used only for enclosure E3h with 800 mm (31.5 in) base plate.
In bottom/out back, E4h
In back/out top, E3h
In back/out top, E4h
Allows the cooling air to be directed in through the bottom and out through the back of the drive. This kit used only for enclosure E4h with 800 mm (31.5 in) base plate.
Allows the cooling air to be directed in through the back and out through the top of the drive. This kit used only for enclosures E3h.
Allows the cooling air to be directed in through the back and out through the top of the drive. This kit used only for enclosures E4h.
LCP
LCP 101
LCP 102
LCP cable
LCP kit, IP21
Numerical local control panel (NLCP).
Graphical Local control panel (GLCP).
Separate LCP cable, 3 m (9 feet).
Panel mounting kit including graphical LCP, fasteners, 3 m (9 feet) cable and gasket.
Panel mounting kit including numerical LCP, fasteners and gasket.
LCP kit, IP21
LCP kit, IP21 Panel mounting kit for all LCPs including fasteners, 3 m (9 feet) cable and gasket.
Options for slot A (Fieldbus Devices)
Ordering number
176F1742
130B1156
176F6609
176F6619
176F6620
130B1116
176F6606
176F6607
176F6608
176F6617
176F6618
176F6610
176F6611
176F6612
176F6613
176F6614
176F6615
176F6616
130B1124
130B1107
175Z0929
130B1113
130B1114
130B1117
Uncoated Coated
13 13
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
121
How to Order a Drive VLT® AutomationDrive FC 302
13 13
MCA 101
MCA 104
MCA 105
MCA 113
MCA 114
MCA 120
MCA 121
PROFIBUS option DP V0/V1.
DeviceNet option.
CANopen.
PROFIBUS VLT 3000 protocol converter.
PROFIBUS VLT 5000 protocol converter.
PROFINET option.
EtherNet/IP option.
MCA 122
MCA 123
Modbus TCP option.
Powerlink option.
MCA 124 EtherCAT option.
Options for slot B (Functional Extensions)
MCB 101 General-purpose input output option.
MCB 102
MCB 103
MCB 105
MCB 108
MCB 112
MCB 114
MCB 150
MCB 151
Encoder option.
Resolver option.
Relay option.
Safety PLC interface (DC/DC converter).
ATEX PTC thermistor card.
PT100 sensor input.
Safety option (TTL encoder).
Safety option (HTL encoder).
MCB 152 Safety option (PROFIsafe functionality).
Options for slot C (motion control and relay cards)
MCO 305
MCO 350
Programmable motion controller.
Synchronizing controller.
MCO 351
MCB 113
Option for slot D
MCB 107
External options
EtherNet/IP
Positioning controller.
Extended relay card.
24 V DC backup.
Ethernet master.
130B1100
130B1102
130B1103
–
–
130B1135
130B1119
130B1196
130B1489
130B5546
130B1125
130B1115
130B1127
130B1110
130B1120
–
130B1172
–
–
–
130B1134
130B1152
130B1153
130B1164
Uncoated
130B1108
130B1200
130B1202
130B1205
130B1245
130B1246
130B1235
130B1219
130B1296
130B1490
130B5646
130B1212
130B1203
130B1227
130B1210
130B1220
130B1137
130B1272
130B3280
130B3290
130B9860
130B1234
130B1252
120B1253
130B1264
Coated
130B1208
175N2584
Table 13.5 Options and Accessories
Type
PC software
MCT 10
MCT 10
MCT 10
MCT 10
MCT 10
MCT 10
MCT 10
Description
MCT 10 Set-up Software - 1 user.
MCT 10 Set-up Software - 5 users.
MCT 10 Set-up Software - 10 users.
MCT 10 Set-up Software - 25 users.
MCT 10 Set-up Software - 50 users.
MCT 10 Set-up Software - 100 users.
MCT 10 Set-up Software - unlimited users.
Ordering number
130B1000
130B1001
130B1002
130B1003
130B1004
130B1005
130B1006
Table 13.6 Software Options
Options can be ordered as factory built-in options. For information on fieldbus and application option compatibility with older software versions, contact the Danfoss supplier.
122 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
How to Order a Drive Design Guide
13.3 Ordering Numbers for Filters and Brake Resistors
Refer to the following design guides for dimensioning specifications and ordering numbers for filters and brake resistors:
•
VLT ® Brake Resistor MCE 101 Design Guide .
•
VLT ® Advanced Harmonic Filters AHF 005/AHF 010 Design Guide .
•
Output Filters Design Guide .
13.4 Spare Parts
Consult the VLT shop or the Drive Configurator ( www.danfoss.com/drives ) for the spare parts that are available for your application.
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
123
13 13
Appendix VLT® AutomationDrive FC 302
14 Appendix
14 14 kHz
LCP lsb m mA
Hz
I
INV
I
LIM
I
M,N
I
VLT,MAX
I
VLT,N
CE
CM
CT
DC
DI
DM
D-TYPE
EMC
EMF
ETR
° F f
JOG f
M f
MAX
14.1 Abbreviations and Symbols
60 ° AVM
A
AC
AD
AEO
AI
AIC
AMA
AWG
° C
CB
CD
CDM f
MIN f
M,N
FC
Hiperface ®
HO hp
HTL
60 ° asynchronous vector modulation
Ampere/AMP
Alternating current
Air discharge
Automatic energy optimization
Analog input
Ampere interrupting current
Automatic motor adaptation
American wire gauge
Degrees Celsius
Circuit breaker
Constant discharge
Complete drive module: The drive, feeding section, and auxiliaries
European conformity (European safety standards)
Common mode
Constant torque
Direct current
Digital input
Differential mode
Drive dependent
Electromagnetic compatibility
Electromotive force
Electronic thermal relay
Degrees Fahrenheit
Motor frequency when jog function is activated
Motor frequency
Maximum output frequency that the drive applies on its output
Minimum motor frequency from the drive
Nominal motor frequency
Frequency converter (drive)
Hiperface ® is a registered trademark by Stegmann
High overload
Horse power
HTL encoder (10–30 V) pulses - High-voltage transistor logic
Hertz
Rated inverter output current
Current limit
Nominal motor current
Maximum output current
Rated output current supplied by the drive
Kilohertz
Local control panel
Least significant bit
Meter
Milliampere
MCM
MCT mH mm ms msb
η
VLT
PCB
PCD
PDS
PELV
P m nF
NLCP
Nm
NO n s
Online/
Offline
Parameters
P br,cont.
Mille circular mil
Motion control tool
Inductance in milli Henry
Millimeter
Millisecond
Most significant bit
Efficiency of the drive defined as ratio between power output and power input
Capacitance in nano Farad
Numerical local control panel
Newton meter
Normal overload
Synchronous motor speed
Changes to online parameters are activated immediately after the data value is changed
P
M,N
PM motor
Rated power of the brake resistor (average power during continuous braking)
Printed circuit board
Process data
Power drive system: CDM and a motor
Protective extra low voltage
Drive nominal output power as high overload
(HO)
Nominal motor power
Permanent magnet motor
Process PID PID (proportional integrated differential) regulator that maintains the speed, pressure, temperature, and so on
R br,nom
Nominal resistor value that ensures a brake power on the motor shaft of 150/160% for 1 minute
RCD
Regen
R min
Residual current device
Regenerative terminals
Minimum allowed brake resistor value by the drive
RMS
RPM
R rec s
SCCR
SFAVM
Root average square
Revolutions per minute
Recommended brake resistor resistance of
Danfoss brake resistors
Second
Short-circuit current rating
Stator flux-oriented asynchronous vector modulation
STW
SMPS
THD
T
LIM
TTL
Status word
Switch mode power supply
Total harmonic distortion
Torque limit
TTL encoder (5 V) pulses - transistor logic
U
M,N
UL
Nominal motor voltage
Underwriters Laboratories (US organization for the safety certification)
124 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Appendix Design Guide
V
VT
VVC +
Volts
Variable torque
Voltage vector control plus
Table 14.1 Abbreviations and Symbols
14.2 Definitions
Brake resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative brake power increases the DC-link voltage and a brake chopper ensures that the power is transmitted to the brake resistor.
Break-away torque n s
Torque
Pull-out
Illustration 14.1 Break-away Torque Chart
RPM
Coast
The motor shaft is in free mode. No torque on the motor.
CT characteristics
Constant torque characteristics used for all applications such as conveyor belts, displacement pumps, and cranes.
Initializing
If initializing is carried out ( parameter 14-22 Operation
Mode ), the drive returns to the default setting.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an off-load period. The operation can be either periodic duty or nonperiodic duty.
Power factor
The true power factor (lambda) takes all the harmonics into consideration and is always smaller than the power factor (cos phi) that only considers the 1 st harmonics of current and voltage.
Uλ x Iλ x cosϕ
Uλ x Iλ
Cos phi is also known as displacement power factor.
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
Both lambda and cos phi are stated for Danfoss VLT ® drives in
The power factor indicates to which extent the drive imposes a load on the mains supply.
The lower the power factor, the higher the I
RMS
for the same kW performance.
In addition, a high-power factor indicates that the harmonic currents are low.
All Danfoss drives have built-in DC coils in the DC link to have a high-power factor and reduce the THD on the main supply.
Pulse input/incremental encoder
An external digital sensor used for feedback information of motor speed and direction. Encoders are used for highspeed accuracy feedback and in high dynamic applications.
Set-up
Save parameter settings in 4 set-ups. Change between the
4 parameter set-ups and edit 1 set-up while another set-up is active.
Slip compensation
The drive compensates for the motor slip by giving the frequency a supplement that follows the measured motor load, keeping the motor speed almost constant.
Smart logic Control (SLC)
The SLC is a sequence of user-defined actions executed when the associated user-defined events are evaluated as true by the SLC. ( Parameter group 13-** Smart Logic ).
FC Standard bus
Includes RS485 bus with FC protocol or MC protocol. See parameter 8-30 Protocol .
Thermistor
A temperature-dependent resistor placed where the temperature is to be monitored (drive or motor).
Trip
A state entered in fault situations, such as when the drive is subject to an overtemperature or when it protects the motor, process, or mechanism. Restart is prevented until the cause of the fault has disappeared and the trip state is canceled. Cancel the trip state by either:
•
Activating reset.
•
Programming the drive to reset automatically.
Do not use trip for personal safety.
Trip lock
A state entered in fault situations when the drive is protecting itself and requires physical intervention. A locked trip can only be canceled by cutting off mains, removing the cause of the fault, and reconnecting the drive. Restart is prevented until the trip state is canceled by activating reset.
VT characteristics
Variable torque characteristics for pumps and fans.
14 14
125
Index VLT® AutomationDrive FC 302
Index
A
Abbreviations...................................................................................... 125
AC brake................................................................................................... 20
Acoustic noise........................................................................................ 86
Active reference.................................................................................... 98
Airflow
Configurations.................................................................................. 26
Rates..................................................................................................... 69
Alarm reset........................................................................................... 111
Altitude..................................................................................................... 70
AMA
Wiring configuration.................................................................... 109
Ambient conditions
Overview............................................................................................. 67
Specifications.................................................................................... 36
Analog
Input specifications......................................................................... 37
Input/output descriptions and default settings................... 77
Output specifications..................................................................... 38
Wiring configuration for speed reference............................ 109
Analog speed reference wiring configuration........................ 109
ATEX monitoring............................................................................ 16, 68
Auto on..................................................................................................... 98
Automatic energy optimization...................................................... 14
Automatic motor adaptation........................................................... 15
Automatic switching frequency modulation............................. 14
B
Back-channel cooling................................................................... 26, 69
Brake resistor
Definition.......................................................................................... 125
Design guide........................................................................................ 4
Formula for rated power............................................................. 124
Ordering............................................................................................ 123
Overview............................................................................................. 31
Selecting............................................................................................. 81
Terminals............................................................................................. 75
Wiring schematic............................................................................. 73
Braking
Capability chart................................................................................ 82
Control with brake function......................................................... 83
Dynamic braking.............................................................................. 20
Electro-magnetic brake................................................................. 21
Electro-mechanical brake........................................................... 116
Limits.................................................................................................... 82
Mechanical holding brake............................................................ 21
Static braking.................................................................................... 21
Use as an alternative brake function......................................... 83
Wiring configuration for mechanical brake......................... 115
Break-away torque............................................................................. 125
C
Cables
Brake..................................................................................................... 75
Cable type and ratings................................................................... 72
Motor cables...................................................................................... 78
Opening............................................................................................... 41
Power connections.......................................................................... 74
Routing................................................................................................ 75
Shielded............................................................................................... 93
Shielding............................................................................................. 74
Specifications............................................................................. 32, 37
Calculations
Brake resistance................................................................................ 82
Braking torque.................................................................................. 83
Harmonic software.......................................................................... 97
Resistor duty cycle........................................................................... 81
Scaled reference............................................................................... 99
Short-circuit ratio............................................................................. 96
THDi...................................................................................................... 95
CANOpen................................................................................................. 27
Capacitor storage................................................................................. 67
CE mark....................................................................................................... 7
Circuit breaker......................................................................... 13, 78, 84
Closed loop....................................................................... 102, 104, 108
Commercial environment................................................................. 90
Common-mode filter.......................................................................... 31
Compliance
Directives............................................................................................... 7
With ADN............................................................................................... 6
Condensation......................................................................................... 67
Conducted emission........................................................................... 89
Control
Characteristics................................................................................... 39
Description of operation............................................................... 98
Structures......................................................................................... 102
Types of............................................................................................. 104
Control card
RS485 specifications....................................................................... 38
Specifications.................................................................................... 40
Control terminals.................................................................................. 76
Controller................................................................................................. 30
Conventions.............................................................................................. 4
Cooling
Dust warning..................................................................................... 67
Overview of back-channel cooling............................................ 26
Requirements.................................................................................... 69
CSA/cUL approval................................................................................... 8
126 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Index Design Guide
Current
Distortion............................................................................................ 95
Formula for current limit............................................................. 124
Fundamental current...................................................................... 95
Harmonic current............................................................................. 95
Internal current control............................................................... 107
Leakage current................................................................................ 84
Mitigating motor.............................................................................. 81
Rated output current................................................................... 124
Transient ground.............................................................................. 84
D
DC brake.................................................................................................. 20
DC bus
Description of operation............................................................... 98
Terminals............................................................................................. 74
Derating.............................................................................. 14, 15, 36, 69
DeviceNet...................................................................................... 27, 122
Digital
Input specifications......................................................................... 37
Input/output descriptions and default settings................... 77
Output specifications..................................................................... 38
Dimensions
E1h exterior........................................................................................ 41
E1h terminal....................................................................................... 45
E2h exterior........................................................................................ 47
E2h terminal....................................................................................... 51
E3h exterior........................................................................................ 53
E3h terminal....................................................................................... 57
E4h exterior........................................................................................ 60
E4h terminal....................................................................................... 64
Product series overview................................................................ 11
Discharge time......................................................................................... 5
Disconnect.............................................................................................. 78
Door clearance...................................................................................... 41
Drive
Clearance requirements................................................................ 69
Configurator.................................................................................... 118
Dimensions of product series...................................................... 11
Power ratings..................................................................................... 11
DU/dt........................................................................................................ 86
Duct cooling........................................................................................... 69
Duty cycle
Calculation.......................................................................................... 81
Definition.......................................................................................... 125
E
EAC mark.................................................................................................... 8
Efficiency
Calculation.......................................................................................... 85
Formula for drive efficiency....................................................... 124
Specifications.................................................................................... 32
Using AMA.......................................................................................... 15
Electromagnetic interference.......................................................... 15
Electro-mechanical brake............................................................... 116
Electronic thermal overload............................................................. 16
Electronic thermal relay (ETR).......................................................... 72
EMC
Compatibility..................................................................................... 92
Directive................................................................................................. 7
General aspects................................................................................ 88
Installation.......................................................................................... 94
Interference........................................................................................ 93
Test results.......................................................................................... 89
Emission requirements....................................................................... 90
Enclosure protection............................................................................. 9
Encoder
Configuration.................................................................................. 116
Definition.......................................................................................... 125
Determining encoder direction............................................... 116
VLT® Encoder Input MCB 102....................................................... 29
Energy efficiency class........................................................................ 36
Environment.................................................................................... 36, 67
ErP directive.............................................................................................. 7
EtherCAT.................................................................................................. 28
EtherNet/IP.............................................................................................. 28
Explosive atmosphere......................................................................... 68
Export control regulations................................................................... 8
Extended relay card............................................................................. 31
Exterior dimensions
E1h......................................................................................................... 41
E2h......................................................................................................... 47
E3h......................................................................................................... 53
E4h......................................................................................................... 60
External alarm reset wiring configuration................................ 111
F
Fans
Required airflow............................................................................... 69
Temperature-controlled fans....................................................... 15
Feedback
Conversion....................................................................................... 102
Handling........................................................................................... 101
Signal................................................................................................. 104
Fieldbus............................................................................................. 27, 75
Filters
Common-mode filter...................................................................... 31
DU/dt filter.......................................................................................... 31
Harmonic filter.................................................................................. 31
Ordering............................................................................................ 123
RFI filter................................................................................................ 92
Sine-wave filter.......................................................................... 31, 74
Flux
Control structure in flux sensorless......................................... 106
Control structure in flux with motor feedback................... 107
Flying start................................................................................ 14, 15, 18
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
127
Index VLT® AutomationDrive FC 302
Formula
Current limit.................................................................................... 124
Drive efficiency............................................................................... 124
Output current............................................................................... 124
Rated power of the brake resistor........................................... 124
Fourier series analysis......................................................................... 95
Frequency bypass................................................................................. 18
Fuses
For use with power connections................................................ 74
Overcurrent protection.................................................................. 72
Recommendation for mains supply.......................................... 13
Specifications.................................................................................... 78
G
Galvanic isolation................................................................... 15, 38, 92
Gases......................................................................................................... 67
General purpose I/O module........................................................... 28
Gland plate.............................................................................................. 41
Grounding........................................................................................ 15, 84
H
Hand on.................................................................................................... 98
Harmonics
Definition of power factor.......................................................... 125
EN standards...................................................................................... 96
Filter...................................................................................................... 31
IEC standards..................................................................................... 96
Mitigation........................................................................................... 97
Overview............................................................................................. 95
Heat sink
Access panel...................................................................................... 43
Cleaning.............................................................................................. 68
Required airflow............................................................................... 69
Heater
Usage.................................................................................................... 67
Wiring schematic............................................................................. 73
High voltage............................................................................................. 5
High-altitude installation................................................................... 93
Hoisting............................................................................................. 21, 22
Humidity.................................................................................................. 67
I
Immunity requirements..................................................................... 91
Input specifications............................................................................. 37
Installation
Electrical.............................................................................................. 72
Qualified personnel........................................................................... 5
Requirements.................................................................................... 68
Insulation................................................................................................. 81
Inverter..................................................................................................... 98
IP rating...................................................................................................... 9
IT mains.................................................................................................... 85
K
Kinetic back-up...................................................................................... 18
Kits............................................................................................................. 31
Knockout panel..................................................................................... 42
L
Language packages.......................................................................... 118
Leakage current................................................................................ 5, 84
Lifting................................................................................................. 21, 67 see also Hoisting
Load share
Overview............................................................................................. 24
Short-circuit protection................................................................. 13
Terminals...................................................................................... 25, 75
Warning.................................................................................................. 5
Wiring schematic............................................................................. 73
Low voltage
Directive................................................................................................. 7
Public network.................................................................................. 90
Low-speed operation.......................................................................... 69
M
Machinery directive............................................................................... 7
Mains
Drop-out............................................................................................. 18
Fluctuations....................................................................................... 15
Shield...................................................................................................... 5
Specifications.................................................................................... 36
Supply specifications...................................................................... 36
Maintenance.......................................................................................... 68
Marine certification................................................................................ 8
Mechanical brake
Using closed-loop control............................................................. 22
Using open-loop control............................................................... 21
Wiring configuration.................................................................... 115
Modbus.................................................................................................... 28
Modulation.................................................................................... 14, 124
Motion control option........................................................................ 30
128 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Index Design Guide
Motor
Break-away torque definition.................................................... 125
Cables..................................................................................... 74, 78, 84
Class protection................................................................................ 68
Ex-e................................................................................................. 16, 29
Feedback.......................................................................................... 107
Full torque.......................................................................................... 18
Insulation............................................................................................ 81
Leakage current................................................................................ 84
Missing phase detection............................................................... 14
Mitigating bearing currents......................................................... 81
Nameplate.......................................................................................... 17
Output specifications..................................................................... 36
Parallel connection.......................................................................... 79
Rotation............................................................................................... 79
Thermal protection.................................................................. 16, 79
Thermistor wiring configuration.............................................. 114
Wiring schematic............................................................................. 73
Mounting configurations.................................................................. 68
N
NEMA protection rating........................................................................ 9
O
Open loop................................................................................... 102, 103
Operating guide...................................................................................... 4
Options
Enclosure availability...................................................................... 11
Fieldbus............................................................................................... 27
Functional extensions.................................................................... 28
Motion control.................................................................................. 30
Ordering......................................................................... 119, 120, 122
Relay cards.......................................................................................... 30
Ordering................................................................................................ 118
Output
Contactor..................................................................................... 85, 94
Specifications.................................................................................... 38
Switch................................................................................................... 14
Overcurrent protection...................................................................... 72
Overload
Electronic thermal overload......................................................... 16
Issue with harmonics...................................................................... 95
Limits.................................................................................................... 14
Overtemperature............................................................................... 125
Overvoltage
Alternative brake function............................................................ 83
Braking................................................................................................. 31
Protection........................................................................................... 13
P
PELV............................................................................................. 15, 38, 92
Periodic forming................................................................................... 67
PID controller...................................................................... 16, 101, 105
Pigtails...................................................................................................... 92
Point of common coupling............................................................... 95
Positioning controller.......................................................................... 30
Potentiometer.............................................................................. 77, 112
Power
Connections....................................................................................... 74
Factor................................................................................................. 125
Losses................................................................................................... 32
Ratings.......................................................................................... 11, 32
POWERLINK............................................................................................. 28
Preheat..................................................................................................... 18
Process control.................................................................................... 104
PROFIBUS....................................................................................... 27, 122
PROFINET................................................................................................. 27
Programming guide............................................................................... 4
Protection
Brake function................................................................................... 13
Enclosure rating................................................................................ 11
Motor thermal................................................................................... 16
Overcurrent........................................................................................ 72
Overload.............................................................................................. 14
Overvoltage....................................................................................... 13
Short circuit........................................................................................ 13
Supply voltage imbalance............................................................ 14
PTC thermistor card............................................................................. 29
Pulse
Input specifications......................................................................... 38
Wiring configuration for start/stop......................................... 110
Q
Qualified personnel................................................................................ 5
R
Radiated emission................................................................................ 89
Radio frequency interference.......................................................... 15
RCM mark................................................................................................... 8
Rectifier.................................................................................................... 98
Reference
Active reference................................................................................ 98
Remote handling of........................................................................ 99
Remote reference............................................................................. 99
Speed input..................................................................................... 109
Regen
Availability.......................................................................................... 11
Overview............................................................................................. 25
Terminals............................................................................................. 45
Relay
ADN-compliant installation............................................................ 6
Card....................................................................................................... 30
Extended relay card option.......................................................... 31
Option.................................................................................................. 29
Specifications.................................................................................... 39
Terminals............................................................................................. 77
Remote reference................................................................................. 99
Residential environment.................................................................... 90
Residual current device............................................................... 83, 84
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
129
Index VLT® AutomationDrive FC 302
Resistor brake......................................................................................... 20
Resolver option..................................................................................... 29
Resonance damping............................................................................ 15
Restart....................................................................................................... 18
RFI
Filter...................................................................................................... 92
Location of E3h shield termination........................................... 56
Location of E4h shield termination........................................... 63
Using switch with IT mains........................................................... 85
Rise time.................................................................................................. 86
Rotor.......................................................................................................... 14
RS485
FC standard bus............................................................................. 125
Terminals............................................................................................. 76
Wiring configuration.................................................................... 113
Wiring schematic............................................................................. 73
S
Safe PLC interface option.................................................................. 29
Safe Torque Off
Design guide........................................................................................ 4
Machinery directive compliance.................................................. 7
Overview............................................................................................. 19
Terminal location............................................................................. 77
Wiring configuration.................................................................... 110
Wiring schematic............................................................................. 73
Safety
Instructions.................................................................................... 5, 72
Options................................................................................................ 29
Scaled reference.................................................................................... 99
Sensor input option............................................................................. 29
Serial communication......................................................................... 76
Shielding
Cables................................................................................................... 74
Mains....................................................................................................... 5
RFI termination................................................................................. 56
Twisted ends...................................................................................... 92
Short circuit
Braking.......................................................................................... 20, 83
Definition.......................................................................................... 125
Ratio calculation............................................................................... 96
SCCR rating......................................................................................... 78
Short-circuit protection................................................................. 13
Sine-wave filter............................................................................... 31, 74
Slip compensation............................................................................. 125
Smart logic control
Overview............................................................................................. 18
Wiring configuration.................................................................... 114
Software versions............................................................................... 122
Spare parts............................................................................................ 123
Speed
Control............................................................................................... 104
PID feedback................................................................................... 104
Wiring configuration for speed reference............................ 112
Wiring configuration for speed up/down............................. 112
Start/stop wiring configuration.......................................... 110, 111
STO............................................................................................................... 4 see also Safe Torque Off
Storage..................................................................................................... 67
Switches
A53 and A54................................................................................ 37, 77
Disconnect.......................................................................................... 78
Switching frequency
Derating........................................................................................ 14, 70
Power connections.......................................................................... 74
Sine-wave filter.......................................................................... 31, 74
Use with RCDs................................................................................... 84
Synchronizing controller.................................................................... 30
T
Temperature.................................................................................... 67, 70
Terminal dimensions
E1h......................................................................................................... 45
E2h......................................................................................................... 51
E3h......................................................................................................... 57
E4h......................................................................................................... 64
Terminals
Analog input/output...................................................................... 77
Brake resistor..................................................................................... 75
Control descriptions and default settings.............................. 76
Digital input/output........................................................................ 77
Load share.......................................................................................... 75
Relay terminals.................................................................................. 77
RS485.................................................................................................... 76
Serial communication.................................................................... 76
Terminal 37......................................................................................... 77
Thermistor
Cable routing..................................................................................... 75
Definition.......................................................................................... 125
Terminal location............................................................................. 77
Wiring configuration.................................................................... 114
Torque
Characteristic..................................................................................... 36
Control............................................................................................... 104
Wiring configuration for torque and stop limit.................. 116
Transducer............................................................................................... 77
Transformer............................................................................................ 95
Trip
Definition.......................................................................................... 125
Points for 380–500 V drives.......................................................... 32
Points for 525–690 V drives.......................................................... 34
TUV certificate.......................................................................................... 8
Type code.............................................................................................. 118
U
UKrSEPRO certificate.............................................................................. 8
UL
Enclosure protection rating............................................................ 9
Listing mark.......................................................................................... 8
USB specifications................................................................................ 40
130 Danfoss A/S © 05/2017 All rights reserved.
MG38C102
Index Design Guide
User input................................................................................................ 98
V
Voltage imbalance............................................................................... 14
VVC+.............................................................................................. 105, 107
W
Warnings............................................................................................. 5, 72
Wires.......................................................................................................... 72 see also Cables
Wiring schematic.................................................................................. 73
MG38C102 Danfoss A/S © 05/2017 All rights reserved.
131
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten vlt-drives.danfoss.com
130R0797 MG38C102 *MG38C102* 05/2017

Download
Advertisement