BERKELEY
®
Cable Selection
Stainless steel, 4" submersible motors
TWO DIFFERENT CABLE SIZES CAN BE USED
The example below is for reference. Depending on the installation, any number of combinations may be used, as long as the total percentage length of the two cables used does not exceed 100%. This is to ensure that adequate voltage will be supplied to the motor.
EXAMPLE:
1 HP,
230 Volt, 3W,
1 PH Motor
In a replacement installation, the well already has 210 feet of buried #12 cable between the service entrance and the well head. The question is: What size cable is required in the well with a 1 HP, 230 Volt, 1 PH, 3W motor setting at 310 feet?
1. According to the table, #12 cable is large enough for the 1 HP motor so the percent of the maximum allowable cable used by the 210-foot run is 210 ÷ 359 = 58.5%, since 359 feet is the total allowable.
2. With 58.5% of the total allowable cable already used between the service entrance and the well head, only
41.5% is left for the well. Therefore, the 310 feet needed in the well can only utilize 41.5% of the total feet allowed in the table.
3. From the table, 41.5% of the 573 feet for #10 cable equals only 238 feet, so a larger size is needed. For #8,
41.5% of 908 feet = 377 feet. As a result, #8 can be used for the 310 feet in the well.
CAUTION Use of wire size smaller than listed will void warranty.
MOTOR LEAD LENGTHS: PENTEK ® 2-WIRE PSC MOTORS
60 HZ MOTOR RATING
VOLTS HP
115 1/2
1/2
230
3/4
1
14
107
457
342
267
12
171
726
545
425
10
273
1158
869
678
8
60C AND 75C INSULATION – AWG COPPER WIRE SIZE
6 4 3 2 1 1/0
432
1835
672
2855
1071
4551
1346
5721
1700
7225
2142
9102
2703
11489
1376
1074
2141
1671
3413
2664
2080
4291
3349
2615
5419
4229
3303
6826
5328
4161
8617
6725
5252
2/0
3411
10871
8485
6626
3/0
4305
10711
8365 1-1/2 209 332 530 839 1305
MOTOR LEAD LENGTHS: PENTEK 3-WIRE MOTORS
CSIR CONTROL BOXES
60 HZ MOTOR RATING
VOLTS HP
115 1/2
1/2
230 3/4
1
CSCR CONTROL BOXES
14
94
348
277
231
12
150
553
441
367
10
240
883
704
585
8
60C AND 75C INSULATION – AWG COPPER WIRE SIZE
6 4 3 2 1 1/0
380
1398
591
2175
942
3467
1184
4359
1495
5505
1883
6935
2377
8753
1115
927
1734
1442
2765
2299
3476
2891
4390
3651
5530
4599
6981
5805
2/0
2999
8807
7324
3/0
3786
60 HZ MOTOR RATING
VOLTS HP
1/2
3/4
230
1
1-1/2
2
3
5
14
438
359
296
199
180
133
12
697
571
471
317
286
211
10
1112
912
751
505
456
337
206
8
60C AND 75C INSULATION – AWG COPPER WIRE SIZE
6 4 3 2 1 1/0
1761
1444
2740
2246
4369
3581
5492
4502
6936
5685
8738
7162
11029
9040
2/0
11406
1190
801
1852
1246
2952
1986
3711
2496
4686
3153
5904
3972
7452
5013
9402
6325
722
534
326
1123
830
507
1790
1324
809
2251
1664
1017
2843
2102
1284
3581
2648
1618
4520
3342
2042
5703
4217
2577
3/0
5323
3253
4/0
5424
4/0
4770
4/0
All lengths in feet.
NOTE: Based on service factor amps, 30C ambient and 5% voltage drop.
(1) This table is based on copper wire. If aluminum wire is used it must be two sizes larger.
Example: When the table calls for #12 copper wire you would use #10 aluminum wire.
(2) Cables #14 to 4/0 are AWG sizes.
CB6342WS
BERKELEY
®
Cable Selection
Stainless steel, 4" submersible motors
7.5
0.5
0.75
1
1.5
1.5
2
3
5
2
3
5
7.5
0.5
0.75
1
7.5
10
1.5
2
3
5
7.5
1.5
2
3
5
MOTOR LEAD LENGTHS: PENTEK ® 3-PHASE MOTORS
60 HZ MOTOR RATING 60C AND 75C INSULATION – AWG COPPER WIRE SIZE
VOLTS HP 14 12 10 8 6 4 3 2 1 1/0
0.5
3/4
1
629
468
386
1000
745
614
1595
1188
979
2526
1881
1551
3931
2927
2414 3848 4837
200
230
460
575
5367
4025
3220
2368
1964
1519
947
596
468
3870
3049
2454
1324
1006
3374
2531
2024
1489
1234
955
595
375
294
2433
1917
1543
832
633
73
844
633
516
383
316
251
290
237
183
109
461
376
292
173
117
1342
1006
821
610
503
399
186
2140
1605
1310
973
735
600
465
276
3777
3132
2423
1511
951
747
6173
4864
3915
2112
1605
803
636
367
1271
1007
581
385
8561
6420 10168
5136 8135
5981
4960
3837
2393
1506
1182
7703
6200
3345
2542
1163
951
737
438
295
3389
2542
2075
1541
7718
5971
3723
2344
1840
1810
1479
1147
681
459
5274
3956
3229
2397
1978
1567
904
599
5205
3956
2886
2358
1828
1086
3628
2965
2298
1365
3744
2902
1724
1161 731 919
8408 10570
6306
5148
3822
7927
6471
4804
10011
8172
6067
3153
2497
1441
955
3964
3140
1812
1201
5006
3965
2288
1517
5935
3737
2933
4698
3687
5933
4656
4717
3656
2172
1462
7643
6306
4995
2883
1911
7474
5866
5954
4614
2741
1846
2/0
3458
2329
3/0
4366
2940
4/0
5500
3704
9648
7960 10042
6305 7954 10042 12651
3639
2412
4591
3043
5795
3842
7301
4840
All lengths in feet.
NOTE: Based on service factor amps, 30C ambient and 5% voltage drop.
(1) This table is based on copper wire. If aluminum wire is used it must be two sizes larger. Example: When the table calls for
#12 copper wire you would use #10 aluminum wire.
(2) The portion of the total cable that is between the service entrance and a 3-phase motor starter should not exceed 25% of the total maximum length to assure reliable starter operation.
(3) Cables #14 to 4/0 are AWG sizes.
©2017 Pentair plc. All Rights Reserved.
US: 293 WRIGHT STREET, DELAVAN, WI 53115 WWW.BERKELEYPUMPS.COM PH: 888-782-7483 ORDERS FAX: 800-426-9446
CANADA: 490 PINEBUSH ROAD, UNIT 4, CAMBRIDGE, ONTARIO N1T 0A5 PH: 800-363-7867 ORDERS FAX: 888-606-5484
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
CB6342WS (12/18/17)