Eldes ESIM264 User manual

Eldes ESIM264 User manual
ESIM264
GSM ALARM AND MANAGEMENT SYSTEM
USER MANUAL
COMPLIES WITH EN 50131-1 GRADE 2, CLASS II REQUIREMENTS
User Manual v2.4
Valid for ESIM264 v7.15.00 and up
GSM alarm system ESIM264 is a device mounted in limited access areas. Any system repairs must be done only by qualified,
safety aware personnel.
The system must be powered by main 16-24V 50 Hz ~1.5A max or 18-24V
1,5A max DC power supply which must be
approved by LST EN 60950-1 standard and be easily accessible nearby the device. When connecting the power supply to the
system, switching the pole terminals places does not have any affect.
Any additional devices linked to the system ESIM264 (computer, sensors, relays etc.) must be approved by LST EN 60950-1
standard.
The power supply can be connected to AC mains only inside installation room
with automatic 2-pole circuit breaker capable of disconnecting circuit in the
event of short circuit or over-current condition. Open circuit breaker must have
a gap between connections of more than 3mm (0.12in) and the disconnection
current 5A.
Phase
Null
PE
AC/DC
AC 230V
50 Hz/DC 24V
ESIM264
USB cable
Mains power and backup battery must be disconnected before any installation or tuning work starts. The system installation
or maintenance must not be done during stormy conditions
Backup battery must be connected via the connection which in the case of breaking would result in disconnection of one of
battery pole terminals. Special care must be taken when connecting positive and negative battery terminals. Switching the
pole terminals places is NOT allowed.
In order to avoid fire or explosion hazards the system must be used only with approved backup battery.
The device is fully turned off by disconnecting 2-pole switch off device of the mains power and disconnecting backup battery
connector.
Fuse F1 type – Slow Blown 3A. Replacement fuses have to be exactly the same as indicated by the manufacturer.
If you use I security class computer for setting the parameters it must be connected to earth.
2
EN
ESIM264 USER MANUAL V2.4
Contents
1.
GENERAL INFORMATION..........................................................................................................................................................4
1.1. EKB2 - LCD Keypad............................................................................................................................................................................................. 5
1.2. EKB3 - LED Keypad.............................................................................................................................................................................................6
1.3. Partitions.............................................................................................................................................................................................................6
2.
GENERAL OPERATIONAL DESCRIPTION ..................................................................................................................................6
3.
BASIC CONFIGURATION AND USE.............................................................................................................................................7
3.1. SMS Text Messages ........................................................................................................................................................................................... 7
3.2. Password.............................................................................................................................................................................................................8
3.3. System language................................................................................................................................................................................................8
3.4. User phone numbers.........................................................................................................................................................................................9
3.5. Date and time....................................................................................................................................................................................................11
3.6. User codes.........................................................................................................................................................................................................11
3.7. iButton Keys......................................................................................................................................................................................................13
4. ARMING AND DISARMING.......................................................................................................................................................15
4.1. Free of Charge Phone Call...............................................................................................................................................................................16
4.2. SMS Text Message...........................................................................................................................................................................................16
4.3. EKB2 Keypad and User Code..........................................................................................................................................................................17
4.4. EKB3 Keypad and User Code..........................................................................................................................................................................17
4.5. iButton Key........................................................................................................................................................................................................18
4.6. EWK1/EWK2 Wireless Keyfob........................................................................................................................................................................18
4.7. Arm-Disarm by Zone........................................................................................................................................................................................19
4.8. Disabling and Enabling Arm/Disarm Notifications.....................................................................................................................................19
4.9. Exit and Entry Delay.........................................................................................................................................................................................21
4.10. Bypassing and activating zones....................................................................................................................................................................22
4.11. Stay Mode..........................................................................................................................................................................................................23
4.12. Tampers.............................................................................................................................................................................................................23
4.13. Alarm indications and notifications for user............................................................................................................................................... 24
4.14. Enabling and Disabling Alarm Notifications................................................................................................................................................ 26
4.15. Programmable (PGM) outputs.......................................................................................................................................................................27
5.
WIRELESS DEVICES................................................................................................................................................................ 28
5.1. Pairing, Removing and Replacing Wireless Device.................................................................................................................................... 28
5.2. Wireless Device Information......................................................................................................................................................................... 28
5.3. Electrical and Mechanical Characteristics................................................................................................................................................... 28
6.
BACKUP BATTERY, MAINS POWER STATUS MONITORING AND MEMORY........................................................................... 29
6.1. Backup Battery Status Monitoring............................................................................................................................................................... 29
6.2. Mains Power Status Monitoring.................................................................................................................................................................... 29
7.
TEMPERATURE SENSOR........................................................................................................................................................ 29
7.1. Adding, Removing and Replacing Temperature Sensors......................................................................................................................... 29
7.2. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS........................................................................................ 30
8. SYSTEM INFORMATION. INFO SMS.........................................................................................................................................32
8.1. Periodic Info SMS..............................................................................................................................................................................................32
9.
EVENT LOG..............................................................................................................................................................................33
10. INDICATION OF SYSTEM FAULTS........................................................................................................................................... 34
11. CONTROLLING ELECTRICAL APPLIANCES..............................................................................................................................35
12. IF THE ALARM SYSTEM IS CONNECTED TO A MONITORING STATION................................................................................... 36
13. TECHNICAL SPECIFICATIONS..................................................................................................................................................37
13.1. Electrical & Mechanical Characteristics........................................................................................................................................................37
13.2. Main unit, LED and Connector functionality............................................................................................................................................... 38
13.3. Wiring Diagrams.............................................................................................................................................................................................. 39
14. ADDITIONAL INFORMATION...................................................................................................................................................41
ESIM264 USER MANUAL V2.4
EN
3
CONTENTS OF PACK
Element
Quantity
1. ESIM264.............................................................1
2. Microphone........................................................1
3. SMA antenna.....................................................1
4. Buzzer.................................................................1
5. Back-up battery connection wire..................1
6. User manual.......................................................1
7. Resistors 5,6kΩ................................................ 6
8. Resistors 3,3kΩ................................................ 6
9. Plastic standoffs.............................................. 4
1. GENERAL INFORMATION
Functionality
ESIM264 – micro-controller based alarm system for houses, cottages, country homes, garages and other buildings, also capable of managing electrical appliances via cellular GSM/GPRS network. It can also be used as Intercom system.
Examples of using the system:
•
•
•
•
•
•
•
Property security.
Alarm switch.
Thermostat, heating and air-conditioner control, temperature monitoring.
Lighting, garden watering, water pump and other electrical equipment control via SMS text messages.
Remote listening to what is happening in the secured area.
Main 230V power status with SMS text message.
Two-way intercom device via GSM network.
Short Description of Main Definitions
The following table provides the explanation of main definitions which are met in this user manual.
Definition
Description
System; alarm system
ESIM264 device
SMS
Short Message Service text
Keyboard
Device with a set keys allowing to configure & control the system, view violated zones & system troubles
EKB2
Model of LCD keyboard
EKB3
Model of LED keyboard
EWK1
Wireless keyfob model
EWK2
Wireless keyfob model
User phone number; User 1... 5
Phone number of the user allowed to control the system
System phone number
Phone number of the SIM card inserted in ESIM264 device
User password
4-digit combination intended for system arming/disarming using a keyboard
iButton® key
Small metal tab containing a unique ID code intended for system arming/disarming
Zone
Alarm system input for wired and wireless sensor connection
PGM output
Alarm system output for connection of electrical appliances (heating, lighting, gates etc.)
Partition
Section dividing one alarm system into two independent parts software-wise
4
EN
ESIM264 USER MANUAL V2.4
1.1. EKB2 - LCD Keypad
Main features:
• Alarm system arming and disarming
• Keypad partition switch
• Arming and disarming in Stay mode
• Audio indication by built-in buzzer.
• System parameter configuration
• Wireless device information display
• PGM output control
• Temperature display
• System information display
• Time display
For more details on technical specifications and installation, please refer to the latest installation manual of the device located at
eldesalarms.com
Icons and Messages
Temperature
1
GSM signal
strength
Digital
clock
20,2 C
0
System
status
message
STAY
BYP
TBL
00:45
READY
GARAGE
One or more
violated
zones are
bypassed
One or
more
system
faults are
present
System
armed in Stay
mode
Custom
partition
name
Icon / Message
Home screen
view
Description
Chime - Delay zone violated when system
is disarmed.
Exit delay countdown initiated.
System is armed and menu is locked.
System is disarmed and menu is unlocked
Icon / Message
24H zone violated.
FIRE ALARM
Fire zone violated.
TAMPER ALARM
READY
NOT READY
ARMED
+ CONFIGURATION
MODE
BURGLARY ALARM
Configuration mode activated.
Delay, Instant or Follow zone violated
when system is armed.
ESIM264 USER MANUAL V2.4
Description
24 ALARM
Tamper violated
System is ready to be armed.
System is not ready to be armed – one or
more zones / tampers violated.
System is armed (optional feature).
STAY
Stay mode activated
BYP
System armed in Stay mode
TBL
One or more system faults are present
EN
5
1.2. EKB3 - LED Keypad
Main features:
• Alarm system arming and disarming.
• Arming and disarming in Stay mode
• System parameter configuration
• PGM output control
• Visual indication by LED indicators
• Audio indication by built-in buzzer.
• Keypad partition switch
For more details on technical specifications and installation, please refer to the latest installation manual of the device located at
eldesalarms.com
LED Functionality
INDICATION
(red)
(green)
System armed / exit delay in progress
Flashing
Configuration mode activated
Steady ON
System is ready – no violated zones and/or violated tampers exist
Steady ON
System faults exist
(orange) Flashing
(orange)
1-12
(red)
DESCRIPTION
Steady ON
Violated high-numbered zone
Steady ON
Violated zone bypassed
Steady ON
Zone violated / configuration command being typed in
Keys Functionality
DESCRIPTION
2 FRONT SIDE
1st character for STAY-arming
0
9
1st character for violated zone bypass and bypassed
zone activation
1
2
3
N/A
4
5
6
1st character for system fault list indication / 1st
character for violated high-numbered zone indication
/ 1st character for violated tamper indication
7
8
9
*
0
#
Command typing
1st character for Configuration mode activation
or deactivation / clear typed in characters / 1st
character for keypad partition switch (if enabled)
*
Typed in command confirmation
1.3. Partitions
ESIM264 system comes equipped with a partitioning feature that can divide the alarm system into two independently controlled areas
identified as Partition 0 through 1, which are all supervised by one alarm system unit. Partitioning can be used in installations where shared
alarm system is more practical, such as a house and a garage or within a single multi-storey building. When partitioned, each system element, like zone, user phone number, keypad, user code, iButton key and wireless keyfob can be assigned to one of the partitions. The user
will then be able to arm/disarm the system partition that the zones and arm/disarm method are assigned to.
2. GENERAL OPERATIONAL DESCRIPTION
When the system is being armed, it will initiate the exit delay countdown intended for the user to leave the secured area. During the
countdown period the buzzer will emit short beeps and/or LED indicator will flash. By default, exit delay duration is 15 seconds. After the
countdown is complete, the system will become armed and lock the configuration by keypad possibility. In case the user does not leave the
secured area before the countdown is complete, the system will arm in Stay mode if at least 1 zone has Stay attribute enabled. By default,
if there is at least 1 violated zone or tamper, the user will not be able to arm the system until the violated zone or tamper is restored. In case
it is required to arm the alarm system despite the violated zone presence, the violated zone can be bypassed or Force attribute enabled.
After the system is armed and if a zone (depending on type) or tamper is violated, the system will cause an alarm lasting for 1 minute (by
default), During the alarm, the siren/bell will provide an alarm sound along with the buzzers of the keypads. By default, the system will also
makes a phone call and send an SMS text message containing the violated zone or tamper number to a listed user and indicate the violated
zone or tamper number on the keypad. If another zone or tamper is violated or the same one is restored and violated again during the alarm,
the system will act as mentioned previously, but will not extend the alarm time.
6
EN
ESIM264 USER MANUAL V2.4
After the user enters the secured area, the system will initiate the entry delay countdown intended for system disarming. During the countdown period, the buzzer will emit a steady beep and/or LED indicator will light ON. By default, entry delay duration is 15 seconds. After the
user successfully performs the disarming process, the system will unlock the keypads. If the user does not disarm the system in time, the
alarm system will cause an instant alarm.
NOTE: The alarm will be caused even if a tamper is violated while the system is disarmed.
For more details, please refer to 4. ARMING AND DISARMING and 4.9. Exit and Entry Delay.
3. BASIC CONFIGURATION AND USE
!!! In this installation manual the underscore character ”_” represents one space character. Every underscore character must
be replaced by a single space character. There must be no spaces or other unnecessary characters at the beginning and at
the end of the SMS text message.
3.1. SMS Text Messages
In order to configure and control the system by SMS text message, send the text command to the ESIM264 system phone
number from one of the listed user phone numbers. The structure of SMS text message consists of 4-digit SMS password
(the default SMS password is 0000 – four zeros), the parameter and value. For some parameters the value does not apply e. g.
STATUS. The variables are indicated in lower-case letters, while a valid parameter value range is indicated in brackets.
3.1.1. EKB2 LCD Keypad
SMS
EKB2
The system configuration and control by EKB2 keypad is carried out by navigating throughout the menu section list displayed
on LCD screen. To navigate in the menu path, touch ↓, ↑ keys to select the desired menu section and touch OK key to open the
selected section. To enter a required value, use 0... 9 keys and touch OK key for confirmation or cancel/go one menu section
back by touching ← key. The value can be typed in directly by touching 0... 9 keys while highlighting the desired menu section. EKB2 menu type is “circle”, therefore when the last section in the menu list is selected, you will be brought back to the
beginning of the list after touching the ↓ key. In this installation manual, the menu path is based on the EKB2 menu tree by
starting at home screen view. The variables are provided in lower-case letters, while a valid parameter value range is provided
in brackets.
NOTE: Menu section CONFIGURATION is secured with administrator password. The default administrator password is 1470.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the menu section
CONFIGURATION is opened. The inactive EKB2 keypads will display
icon and CONFIGURATION MODE message.
NOTE: The keypad will automatically exit the menu section CONFIGURATION and return to home screen view if 1 minute after the last
key-touch expires.
3.1.2.EKB3 LED Keypad
EKB3
The system configuration and control by EKB3 keypad is carried out by activating the Configuration mode using the administrator password (by default – administrator password is 1470) and entering a valid configuration command using the number
keys 0
key for confirmation and * key to cancel the characters that are being entered. Alternatively, the user
9 ,
can wait for 10 seconds until the keypad buzzer will provide a long beep indicating that the entered characters have been
cancelled. When typing in the characters, the indication of each pressed key is provided by short beep of keypad buzzer and
red indicators when the number keys 0
,
and
keys as well.
9 are being pressed. Some commands require
The structure of a standard configuration command is a combination of digits. The commands, which do not require the Configuration mode being activated, are noted. The variables are provided in lower-case letters, while a valid parameter value
range is provided in brackets.
NOTE: If you were not willing to activate Configuration mode, but accidentally typed in the * as the first character, please press * key again
or wait for 10 seconds until the keypad buzzer will provide a long beep indicating that the typed in characters have been cancelled.
Activate/deactivate
Configuration mode
EKB3
Enter administrator password:
* aaaa #
Value: aaaa – 4-digit administrator password.
Example: *1470#
The following table provides a list of EKB3 indications, which are relevant during Configuration mode.
Indication
Indicator
flashing
Indicator
flashing
1 long beep
3 short beeps
Description
Configuration mode activated successfully.
Valid parameter entered and awaiting for valid value to be entered.
Non-existing command or invalid parameter value entered.
Command entered successfully.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the Configuration mode is activated.
NOTE: Configuration mode will automatically deactivate if 1 minute after the last key-stroke expires.
ESIM264 USER MANUAL V2.4
EN
7
3.1.3.ELDES Configuration Tool Software
Config
Tool
Software ELDES Configuration Tool is intended for ESIM264 alarm system configuration via USB port locally or via GPRS connection remotely. This software simplifies system configuration process by allowing to use a personal computer in the process.
Before starting to use ELDES Configuration Tool software, please read the user guide provided in the software’s HELP section.
ELDES Configuration Tool is freeware and can be downloaded from at: www.eldes.lt
3.2. Password
For security reasons, the system uses the following types of passwords:
•
SMS password – 4-digit password used for system arming/disarming and configuration by SMS text messages. By default, SMS password is 0000, which MUST be changed!
•
Administrator password – 4-digit password used for Configuration mode activation by keypad and logging in to ELDES Configuration
Tool software. By default, Administrator password is 1470, which is highly recommended to change.
Set SMS password
SMS
EKB2
Set Administrator
password
SMS text message content:
wwww_PSW_ssss
Value: wwww – 4-digit default SMS password; ssss – 4-digit new SMS password; range –
[0001... 9999].
Example: 0000_PSW_1111
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS
→ OK → SMS PASSWORD → OK → ssss → OK
Value: aaaa – 4-digit administrator password; ssss – 4-digit new SMS password; range –
[0001... 9999].
EKB3
Enter parameter 14 and new SMS password:
14 ssss #
Value: ssss – 4-digit new SMS password; range – [0001... 9999].
Example: 141111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → 1470 → OK → PRIMARY SETTINGS → OK → PASSWORDS
→ OK → ADMIN PASSWORD → OK → aaaa → OK
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
EKB3
Config
Tool
Enter parameter 16 and new administrator password:
16 aaaa #
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
Example: 162538#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
3.3. System language
The system comes equipped with 2 languages for communication with the user by SMS text messages and a single language for EKB2
keypad menu display. The default EKB2 menu language depends on ESIM264 firmware, which is based on the user’s location, while one of
languages for communication by SMS text messages is always English.
List of currently available system languages (firmwares):
• Czech
• English
• Estonian
• Finnish
• French
• Greek
• Hungarian
• Icelandic
• Italian
• Latvian
• Lithuanian
• Norwegian
• Portuguese
• Romanian
• Russian
• Slovak
• Spanish
• Swedish
To set a different SMS language, please refer to the following configuration methods.
8
EN
ESIM264 USER MANUAL V2.4
Set SMS language
SMS
EKB2
SMS text message content:
ll
Value: ll - SMS language, range - [CZ - Czech, EN - English, EE - Estonian, FI - Finnish, GR Greek, HU - Hungarian, IC - Icelandic, IT - Italian, LV - Latvian, LT - Lithuanian, NO - Norwegian,
PT - Portuguese, RO - Romanian, RU - Russian, SK - Slovak, SP - Spanish, SW - Swedish].
Example: SK
Menu path:
OK → CONFIGURATION → OK → 1470 → OK → PRIMARY SETTINGS → OK → SMS LANGUAGE
→ OK → sms-lang → OK
Value: sms-lang – SMS language.
NOTE: To obtain a firmware that features a different SMS and EKB2 menu language, please contact your local dealer.
3.4. User phone numbers
The system supports up to 5 user phone numbers identified as User 1 through 5. When the phone number is set, the user will be able to
arm/disarm the system by SMS text messages and free of charge phone calls (see 4.1. Free of Charge Phone Call and 4.2. SMS Text
Message) as well as to configure the system by SMS text messages. User phone numbers are also used to receive alarm phone calls and
SMS text messages from the system (see 4.13. Alarm Indications and Notifications for User).
By default, the system accepts incoming calls and SMS text messages from any phone number. Once a user phone number is listed, the
system ignores any incoming calls and SMS text messages from a non-listed phone number as well as it rejects the SMS text messages
containing wrong SMS password even from a listed user phone number (see 3.4.1 System Control from any Phone Number). To set
User 1 phone number is mandatory, while the other 4 are optional. The supported phone number format is the following:
•
International (w/o plus) – The phone numbers must be entered starting with an international country code in the following format: [international code][area code][local number], example for UK: 4417091111111.
Set user phone
number
SMS
EKB2
EKB3
Config
Tool
View user phone
number
ESIM264 USER MANUAL V2.4
SMS text message content:
ssss_NRup:ttteeellnnuumm
Value: ssss – 4-digit SMS password; up – user phone number slot, range – [1... 5]; ttteeelln­
nuumm – up to 15 digits user phone number.
Example: 1111_NR1:44170911XXXX1
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS SETTINGS
→ OK → USERS → OK → USER 1... 5 → OK → PHONE NUMBER → OK → ttteeellnnuumm → OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits user phone
number.
Enter parameter 17, user phone number slot and phone number:
17 up ttteeellnnuumm #
Value: up – user phone number slot, range – [01... 05]; ttteeellnnuumm – up to 15 digits user
phone number.
Example: 170144170911XXXX1#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_HELPNR
Value: ssss – 4-digit SMS password.
Example: 1111_HELPNR
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → PHONE NUMBER → PHONE NUMBER
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
9
Delete user phone
number
SMS
SMS text message content:
ssss_NRup:DEL
Value: ssss – 4-digit SMS password; up – user phone number slot, range – [2... 5].
Example: 1111_NR2:DEL
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 2... 5 → OK → PHONE NUMBER → OK → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: NEVER add a phone number of the device’s SIM card as a user phone number!
ATTENTION: Once User 1 phone number is set, it will be restricted to modify it only.
NOTE: Multiple user phone numbers can be set by a single SMS text message, Example: 1111_NR1:44170911XXXX1_
NR2:44170911XXXX2_ NR5:44170911XXXX3
NOTE: Multiple user phone numbers can be deleted by a single SMS text message, Example: 1111_NR2:DEL_NR3:DEL
3.4.1. System Control from any Phone Number
By default, once a user phone number is listed, the system ignores any incoming calls and SMS text messages from a non-listed phone
number as well as it rejects the SMS text messages containing wrong SMS password even from a listed user phone number. To permit/deny
system arming/disarming by phone call and SMS text message that contain a valid SMS password, configuration by SMS text message that
contain a valid SMS password from any phone number, please refer to the following configuration methods.
Enable system control
from any phone
number
Disable system
control from any
phone number
10
EN
SMS
SMS text message content:
ssss_STR:ON
Value: ssss – 4-digit SMS password.
Example: 1111_STR:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CTRL FROM ANY NUM → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 12 and parameter status value:
12 1 #
Example: 121#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_STR:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_STR:OFF
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CTRL FROM ANY NUM → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 12 and parameter status value:
12 0 #
Example: 120#
ESIM264 USER MANUAL V2.4
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
3.5. Date and time
The system comes equipped with internal real-time clock (RTC) that keeps track of the current date and time. Once the system is up and
running, the user must set the correct date and time, otherwise the system will not operate properly. After shutting down and starting up
the system, the date and time must be set again.
Set date and time
SMS
EKB2
EKB3
Config
Tool
SMS text message content:
ssss_yyyy.mm.dd_hr:mn
Value: ssss – 4-digit SMS password; yyyy – year; mm – month, range – [01... 12]; dd – day,
range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Example: 1111_2015.03.16_14:33
Menu path:
a) OK → DATE/TIME SETTINGS → OK → yyyy-mm-dd hr:mn → OK
b) OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → DATE/TIME
SETTINGS → OK → yyyy-mm-dd hr:mn → OK
Value: aaaa – 4-digit administrator password; yyyy – year; mm – month, range – [01... 12];
dd – day, range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Enter parameter 66, date and time:
66 yyyy mm dd hr mn#
Value: yyyy – year; mm – month, range – [01... 12]; dd – day, range – [01... 31]; hr – hours,
range – [00... 23]; mn – minutes, range – [00... 59].
Example: 66201505291235#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: When the system is connected to the monitoring station via GPRS network connection, the date and time will be automatically
synchronized with the monitoring station upon the system startup.
3.6. User codes
The system supports up to 30 numeric user codes, identified as User Code 1 through 30, allowing to carry out system arming/disarming by
the keypad. By default, User Code 1 is listed as 1111 and assigned to Partition 0.
Set user code
EKB2
EKB3
Config
Tool
ESIM264 USER MANUAL V2.4
Menu path:
User code 1... 16: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (1-16) → OK → USER
PASSWORD 1... 16 → OK → PASSWORDS → OK → uuuu → OK
User code 17... 30: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (17-30) → OK → USER
PASSWORD 17... 30 → OK → PASSWORDS → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code, range – [0000...
9999].
Enter parameter 15, user code slot and user code:
15 us uuuu #
Value: us – user code slot, range – [01... 30]; uuuu – 4-digit user code; range – [0000... 9999].
Example: 15021111#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
11
Delete user code
Replace user code
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → REMOVE PASSWORD → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code.
EKB3
Enter parameter 65 and user code:
65 uuuu #
Value: uuuu – 4-digit user code.
Example: 651111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
Config
Tool
Menu path:
User code 1... 16: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (1-16) → OK → USER
PASSWORD 1... 16 → OK → PASSWORD → OK → uuuu → OK
User code 17... 30: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (17-30) → OK → USER
PASSWORD 17... 30 → OK → PASSWORD → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code, range – [0000...
9999].
Enter parameter 63, existing user code and new user code:
63 vvvv uuuu #
Value: vvvv – 4-digit existing user code; uuuu – 4-digit new user code, range – [0000...
9999].
Example: 6311113254#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system does not allow to set a duplicate password
One of the user codes ranging from User Code 1 through 10 can be set as SGS (Security Guard Service) code, which is used as a checkpoint
by a security service guard upon his/her visit in the secured location. When used, a data message, containing a certain event code, will be
delivered to the monitoring station. However, NO system arming or disarming will be carried out after entering the SGS password.
Set SGS code
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → SGS PASSWORD → OK → N/A / us → OK
Value: aaaa – 4-digit administrator password; N/A – SGS code not in use; us – user code
slot, range – [1... 10].
EKB3
Enter parameter 74 and user code slot:
74 us #
Value: us – user code slot, range – [01... 10].
Example: 7403#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
The Duress code is used when system arming or disarming is demanded by force. When used, the system will arm/disarm as well as it will silently transmit an alert to the monitoring station. Only one of the user code ranging from User Code 1 through 10 can be set as Duress code.
12
EN
ESIM264 USER MANUAL V2.4
Set Duress code
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → DURESS PASSWORD → OK → N/A / us → OK
Value: aaaa – 4-digit administrator password; N/A – Duress password not in use; us – user
code slot, range – [1... 10].
EKB3
Enter parameter 73 and user code slot:
73 us #
Value: us – user code slot, range – [01... 10].
Example: 7309#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
3.7. iButton Keys
An iButton key is a unique 64-bit ID code containing chip enclosed in a stainless steel tab usually implemented in a small plastic holder.
ESIM264 system supports up to 5 iButton keys each holding a unique identity code (ID), which is used for system arming and disarming.
3.7.1. Adding and Removing iButton Keys
NOTE: iButton Key 1 can be added without Allow Adding New iButton Keys mode being enabled.
To add an iButton key to the system, do the following:
a) Disarm the system in all partitions (see 4. ARMING AND DISARMING).
b) Enable Allow Adding New iButton Keys mode.
c)
T ouch the key to the iButton key reader when the system is disarmed (see picture below).
3
d) The successfully added iButton key will be indicated by short beeps emitted by the system’s buzzer.
e) Add as many iButton keys as necessary – touch one key after another to the reader – until the number of 5 keys is reached.
Enable Allow Adding
New iButton Keys
mode
ESIM264 USER MANUAL V2.4
SMS
SMS text message content:
ssss_IBPROG:ON
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → NEW IBUTTON →
OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 18 and parameter status value:
18 0 #
Example: 180#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
13
When adding of iButton keys is complete, please disable Allow Adding New iButton Keys mode.
Disable Allow Adding
New iButton Keys
mode
SMS
SMS text message content:
ssss_IBPROG:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → NEW IBUTTON →
OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 18 and parameter status value:
18 1 #
Example: 181#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To view the ID of the added iButton keys, please refer to the following configuration methods.
View iButton key ID
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → IBUTTON 1... 5 → OK
→ ID
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If the iButton key is lost or stolen, due to security reasons it is highly recommended to remove it from the system.
Remove individual
iButton key from the
system
Remove all iButton
keys from the system
14
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → IBUTTON 1... 5 → OK
→ REMOVE → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_RESETIB
Value: ssss – 4-digit SMS password.
Example: 1111_RESETIB
ESIM264 USER MANUAL V2.4
4. ARMING AND DISARMING
Before arming the system it is necessary to close all doors and windows in the secured area and move yourself away from the motion
detection field.
Move away from
motion detection
field
Close all
windows
Close all
doors
Close all
doors
4
The system features the following methods to carry out arming and disarming process:
•
Free of charge phone call.
•
SMS text message.
•
EKB2/EKB3 keypad and user code.
•
iButton key.
•
EWK1/EWK2 wireless keyfob.
•
Arm-Disarm by Zone.
•
EGR100 middle-ware.
The system arms/disarms the partitions that the listed user phone number, EKB2/EKB3 keypad and user code, iButton key, EWK1 wireless
keyfob or zone, set up for Arm-Disarm by Zone method, are assigned to. For example, if User 1 phone number is assigned to Partition 0, the
user will be able to arm/disarm Partition 0 by a single phone call to the system (see 1.3. Partitions).
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message. For more details on
SMS text message regarding system arming/disarming and how to manage it, please refer to 4.8. Disabling and Enabling Arm/Disarm
Notifications.
The system will allow to arm the system if the following system faults are present (see 10. INDICATION OF SYSTEM FAULTS):
• Mains power is lost.
•
Low battery.
•
Battery failed.
•
Date/time not set.
•
GSM connection failed.
In case of violated zone/tamper presence when attempting to arm the system by free of charge phone call, SMS text message, iButton key
and Arm-Disarm by Zone method, the system will reply with SMS text message containing violated zone/tamper number. Due to security
reasons it is highly recommended to restore the violated zone/tamper before arming the system. For more details on how to arm the system regardless of the violated zone presence, please refer to 4.10. Bypassing and Activating Zones.
Once a user phone number is listed, the system ignores any incoming calls and SMS text messages from a non-listed phone number as well
as it rejects the SMS text messages containing wrong SMS password even from a listed user phone number. For more details regarding
arming/disarming the system from a non-listed phone number, please refer to 3.4.1 System Control from any Phone Number.
ESIM264 USER MANUAL V2.4
EN
15
4.1. Free of Charge Phone Call
To arm and disarm the system, dial the system‘s phone number from any of 5 available user phone numbers (see 3.4. User
phone numbers for user phone number management). The phone call is free charge as the system rejects it and carries out
arming/disarming procedure afterwards. When arming – the system rejects the phone call after 2 rings, when disarming – the
system rejects the phone call immediately. If there is more than one listed user dialling to the system at the same time, the
system will accept the incoming call from the user who was the first to dial while other user (-s) will be ignored.
The system will arm/disarm the partition corresponding to the one that the user phone number is assigned to.
5
CALL
User
ESIM264
4.2. SMS Text Message
To arm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user
phone numbers (see 3.4. User phone numbers for user phone number management). When the SMS text message for arming
is sent to the system’s phone number, the system will proceed as follows:
SMS
•
•
Non-partitioned system:
•
If ready (no violated zone/tamper), the system will arm.
•
If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number.
Partitioned system:
•
If all partitions are disarmed ready (no violated zone/tamper), the system will arm them.
•
If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and skip the unready one (-s). The system will then send an SMS text message, containing a list of violated
zones/tampers, to user phone number that the system arming was initiated from.
•
If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions
and skip the armed ones.
Arm the system
SMS text message content:
ssss_ARMp or ssss_ARMp,p
Value: ssss – 4-digit SMS password; p – partition number, range – [1 – Partition 0, 2 – Partition 1].
Example: 1111_ARM1
6
SMS
User
ESIM264
To disarm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user phone numbers:
Disarm the system
SMS text message content:
ssss_DISARMp or ssss_DISARMp,p
Value: ssss – 4-digit SMS password; p – partition number, range - [1 – Partition 0, 2 – Partition 1].
Example: 1111_DISARM1,2
7
SMS
User
16
EN
ESIM264
ESIM264 USER MANUAL V2.4
Regardless of the partition a user phone number is assigned to, the user will be able arm/disarm by SMS text message method either Partition 0, Partition 1 or both partitions simultaneously.
4.3. EKB2 Keypad and User Code
EKB2
READY message displayed in the home screen view by EKB2 keypad indicates that no violated zones and/or tampers are
present, therefore the system can be armed. If the message is displayed as NOT READY, the user must restore all violated
zones and tampers before arming the system. Alternatively, the violated zones can be bypassed (see 4.10. Bypassing and
Activating Zones), disabled or a Force attribute enabled.
To arm the system by EKB2 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad (see
3.9. User codes for user code management).
By default when a valid user code is entered, the system will initiate exit delay, the keypad’s buzzer will emit short beeps and
the keypad will display
icon next to the countdown timer. When the system is successfully armed, the keypad will display
icon for 5 seconds and switch to home screen view.
Arm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu → OK
Value: uuuu – 4-digit user code.
Example: 1111 → OK
0
To cancel the system arming process, enter the user code again during exit delay countdown.
To disarm the system by EKB2 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad. When a valid
user code is entered, the keypad will display
icon for 3 seconds and switch to home screen view.
Disarm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu → OK
Value: uuuu – 4-digit user code.
Example: 1111 → OK
0
The system will arm/disarm the partition corresponding to the one that user code and the key­pad are assigned to. For example, if EKB2 keypad
and user code is assigned to Partition 1, the user will be able to arm/ disarm only Partition 1.
To arm/disarm a different partition than the keypad is assigned to, use keypad partition switch feature (by default – disabled) before arming/
disarming process.
Use keypad partition
switch
Menu path:
P1 → [p] part-name → OK
Value: part-name – up to 15 characters partition name.
NOTE: If the user fails to enter a correct user code 10 times in a row, the system will block the keypad for 2 minutes and the keypad will
display KEYPAD BLOCKED message. While the keypad is blocked, the system prevents from entering any user code. The keypad will automatically unblock once the 2-minute time has expired and display KEYPAD UNBLOCKED message.
4.4. EKB3 Keypad and User Code
EKB3
Illuminated indicator
on EKB3 keypad indicates that no violated zones and/or tampers are present, therefore the system can
be armed. If the indicator is not illuminated, the user must restore all violated zones and tampers before arming the system.
Alternatively, the violated zones can be bypassed (see 4.10. Bypassing and Activating Zones), disabled or a Force attribute
enabled..
To arm the system by EKB3 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad (see
3.9. User codes for user code management). By default, when a valid user code is entered, the system will initiate exit delay,
the keypad’s buzzer will emit short beeps and the indicator will light ON. When the system is successfully armed, the keypad’s
buzzer will silent down.
Arm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
0
To cancel the system arming process, enter the user code again during exit delay countdown.
ESIM264 USER MANUAL V2.4
EN
17
To disarm the system by EKB3 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad. When a valid
user code is entered, EKB3 keypad indicator will light OFF.
Disarm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
0
The system will arm/disarm the partition corresponding to the one that user code and the key­pad are assigned to. For example, if EKB3
keypad and user code is assigned to Partition 0, the user will be able to arm/ disarm only Partition 0.
To arm/disarm a different partition than the keypad is assigned to, use keypad partition switch feature (by default – disabled) to switch the
keypad to a different partition before arm­ing/disarming process.
Use keypad partition
switch
Hold the [*] key, release it after 3 short beeps and enter partition number:
*p
Value: p – partition number, range – [0... 1]
Example: *1
NOTE: By default, User Code 1 is listed as 1111 and assigned to Partition 0.
4.5. iButton Key
To arm or disarm the system, touch the iButton key reader by any of 5 available iButton keys. When the iButton is touched to
the iButton key reader for arming, the system will proceed as follows:
• If ready (no violated zone/tamper), the system will initiate exit delay and arm.
• If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number. In such case the user must restore all violated zones and tampers before arming the system. Alternatively, the
violated zones can be bypassed (see 4.10. Bypassing and Activating Zones), disabled or a Force attribute enabled.
8
The system will arm/disarm the partition corresponding to the one that the iButton key is assigned to.
4.6. EWK1/EWK2 Wireless Keyfob
EWK1/
EWK2
To arm the system, press 1 of 4 keyfob buttons set to arm the system (by default, EWK1 –
EWK2 button is pressed for arming, the system will proceed as follows:
• If ready (no violated zone/tamper), the system will initiate exit delay and arm.
•
Arm the
system
10
Arm
the
system
To disarm the system, press 1 of 4 keyfob buttons set to disarm the system (by default, EWK1 EN
). When EWK1/
If unready, the system will not arm. In such case the user must restore all violated zones and tampers before arming
the system. Alternatively, the violated zones can be bypassed (see 4.10. Bypassing and Activating Zones), disabled or a Force attribute enabled.
9
18
;EWK 2 -
; EWK2 -
).
ESIM264 USER MANUAL V2.4
11
Disarm
the
system
12
Disarm
the
system
The system will arm/disarm the partition corresponding to the one that EWK1/EWK2 wireless keyfob is assigned to. For example, if EWK1/EWK2 wireless keyfob is assigned to Partition 1, the user will be able to arm/ disarm only Partition 1. To arm a
different partition than the EWK1/EWK2 wireless keyfob is assigned to, pair another EWK1/EWK2 keyfob with the system and
assign it to a different partition.
For more details on how to manage EWK1/EWK2 keyfob buttons, please refer to ELDES Configuration Tool software‘s HELP
section.
4.7. Arm-Disarm by Zone
ARM/
DISARM
ZONE
The Arm-Disarm by Zone feature allows to use a zone for arming and disarming the alarm system when the zone is violated and
restored. The process is performed by providing a low-level pulse for more than 3 seconds into the specified zone. It means that
violating and restoring the zone leads to system arming and by repeating this action the system becomes disarmed. The system
will arm/disarm the partition (-s) that the zone is assigned to. This method can be set up for one on-board zone only.
Set zone for ArmDisarm by Zone
method
Disable Arm-Disarm by
Zone method
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → ZONE 1... 12 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 and on-board zone number:
34 nn #
Value: nn – on-board zone number, range – [01... 12].
Example: 3403#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → N/A → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 and parameter status value
34 00 #
Example: 3400#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
4.8. Disabling and Enabling Arm/Disarm Notifications
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message to:
•
user phone number, sharing the same partition as EKB2/EKB3 keypad and user code, iButton key, EWK1/EWK2 wireless keyfob or zone,
set up for Arm/Disarm by Zone method.
•
user phone number that the system arming/disarming by free of charge phone call was initiated from.
•
user phone number that the system arming/disarming by SMS text message was initiated from.
The confirmation SMS text message is sent to the user phone number regarding each partition separately and contains system status and
partition name.
ESIM264 USER MANUAL V2.4
EN
19
To disable/enable this notification for individual user phone number, please refer to the following configuration methods.
Disable arm/disarm
notification for
individual user phone
number
Enable arm/disarm
notification for
individual user phone
number
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → SEND ARM/DARM SMS → OK →
DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 75, user phone number slot and parameter status value:
75 up 0 #
Value: up – user phone number slot, range – [01... 05].
Example: 75030#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → SEND ARM/DARM SMS → OK →
ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 75, user phone number slot and parameter status value:
75 up 1 #
Value: up– user phone number slot, range – [01... 05].
Example: 75041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the system sends SMS text message only to the first available user phone number when the system is successfully armed/
disarmed. If the system did not receive the SMS delivery report during 45 seconds, it will attempt to send the SMS text message to the next
listed user phone number. To ignore the SMS delivery report and allow/disallow the system to send the SMS text message to every listed
user phone number, please refer to the following configuration methods.
Enable arm/disarm
notification for all
listed user phone
numbers
Disable arm/disarm
notification for all
listed user phone
numbers
EKB2
EKB3
Enter parameter 22 and parameter status value:
22 1 #
Example: 221#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
20
EN
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ARM/DARM ALL → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ARM/DARM ALL → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 22 and parameter status value:
22 0 #
Example: 220#
ESIM264 USER MANUAL V2.4
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
4.9. Exit and Entry Delay
When arming, the system initiates the exit delay countdown (by default – 15 seconds) intended for the user to leave the secured area. The
exit delay is indicated by short beeps emitted by EKB2/EKB3 keypad buzzer and buzzer, connected to the alarm system. in addition, when
arming by EKB2 keypad,
icon will be displayed next to the countdown timer on keypad screen during exit delay.
•
in a non-partitioned system,
•
in a partitioned system, EKB2 keypad will display ARMING part-name message on the screen for 3 seconds and switch to partition
selection menu during exit delay.
icon will be displayed next to the countdown timer on EKB2 keypad screen during exit delay.
Exit delay is provided when arming the system by the following methods:
•
EKB2/EKB3 keypad and user code.
•
iButton key.
•
EWK1/EWK2 wireless keyfob.
•
Arm/Disarm by Zone.
To arm the system without exit delay, use one of the following system arming methods:
•
Free of charge phone call.
•
SMS text message.
•
EGR100 middle-ware.
Set exit delay
SMS
EKB2
SMS text message content:
ssss_EXITDELAY:ext
Value: ssss – 4-digit SMS password; ext – exit delay duration, range – [0... 600] seconds.
Example: 1111_EXITDELAY:20
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EXIT DELAY → OK
→ ext → OK
Value: aaaa – 4-digit administrator password;, ext – exit delay duration, range – [0... 600]
seconds.
EKB3
Enter parameter 72 and exit delay duration:
72 ext #
Value: ext – exit delay duration, range – [0... 600] seconds.
Example: 72259#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Alternatively, you can set exit delay value to 0 in order to arm the system without exit delay by any available method.
Once the exit delay has expired, the system initiates the entry delay countdown (by default – 15 seconds) if a Delay type zone is violated.
The countdown is indicated by short beeps emitted by keypad buzzer and by steady beep emitted by system’s buzzer. The indication is intended to advise the user that the system should be disarmed. Once the user presses/touches any key on the keypad during this delay, the
buzzer of the keypad will be silenced. If the system is disarmed before the entry delay expires, no alarm will be caused.
ESIM264 USER MANUAL V2.4
EN
21
Set entry delay for
Delay zone
SMS
EKB2
EKB3
Config
Tool
SMS text message content:
ssss_ENTRYDELAY:nn,eeeee or ssss_ENTRYDELAY:nn,eeeee;nn,eeeee;nn,eeeee;nn,eeeee
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 44], eeeee – entry delay
duration, range – [0... 65535] seconds.
Example: 1111_ENTRYDELAY:1,25;14,32;12,20
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK →
ONBOARD ZONES → OK → ZONE 1... 12 → OK → ENTRY DELAY → OK → eeeee → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → ENTRY DELAY → OK → eeeee → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → ENTRY DELAY → OK → eeeee → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → ENTRY DELAY → OK → eeeee → OK
Value: aaaa – 4-digit administrator password; eeeee – entry delay duration, range – [0...
65535] seconds.
Enter parameter 54, partition number and entry delay duration:
54 nn eeeee #
Value: nn – zone number, range – [01... 44], eeeee – entry delay duration, range – [0... 65535]
seconds
Example: 5403259#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
4.10. Bypassing and activating zones
NOTE for EKB3: The Configuration mode must remain deactivated before bypassing a violated zone or activating a bypassed zone.
Zone bypassing allows the user to deactivate a violated zone and arm the system without restoring the zone. If a bypassed zone is violated
or restored during exit/entry delay, or when then system is armed, it will be ignored. When a zone is bypassed, EKB3 keypad indi­cator BYPS
will light ON and EKB2 keypad will display BYP message in the home screen view.
Bypass individual
violated zone
EKB2
EKB3
Bypass all violated
zones
EKB2
Menu path:
OK → BYPASS → OK → BYPASS LIST 1... 3 → OK → Z1-zone-name... Z44-zone-name → OK →
BYPASS → OK K
Value: zone-name - up to 24 characters zone name.
Press the key, enter zone number and user code:
nn uuuu #
Value: nn – zone number, range – [01... 44]; uuuu – 4-digit user code.
Example: 091111#
Menu path:
OK → BYPASS → OK → BYP VIOLATED ZONES → OK
The zone will stay bypassed until the system is disarmed. Once the system is disarmed, the corresponding zone state will be indicated on
the keypads (see 1.1. EKB2 – LCD Keypad and 1.2. EKB3 – LED Keypad) and Info SMS text message (see 8. SYSTEM INFORMATION.
INFO SMS). Alternatively, the user can activate the bypassed zone by the following configuration methods.
Activate bypassed
zone
22
EN
EKB2
Menu path:
OK → BYPASS → OK → BYPASS LIST 1...3 → OK → Z1-zone-name... Z44-zone-name → OK →
UNBYPASS → OK
Value: zone-name - up to 24 characters zone name.
ESIM264 USER MANUAL V2.4
EKB3
Press the key, enter zone number and user code:
nn uuuu #
Value: nn – zone number, range – [01... 44]; uuuu – 4-digit user code.
Example: 251111#
NOTE: Zones can only be bypassed and activated when the system is not armed.
4.11. Stay Mode
Stay mode allows the user to arm and disarm the alarm system without leaving the secured area. If the zones with Stay attribute enabled
are violated when the system is Stay armed, no alarm will be caused. Typically, this feature is used when arming the system at home before
going to bed.
The system can be Stay armed under the following conditions:
•
If a Delay-type zone is NOT violated during exit delay and a zone (-s) with Stay attribute enabled exists, the system will arm in Stay
mode. When arming the system in Stay mode under this condition, one of the available arming methods must be used that provide exit
delay. For more details on these methods, please refer to 4.9. Exit and entry delay.
•
The system will instantly arm in Stay mode when using one of the following methods.
Arm the system in
Stay mode
EKB2
EKB3
Menu path:
P2 → uuuu → OK
Value: uuuu – 4-digit user code.
Press the key and enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
When the system is successfully armed in Stay mode, EKB2 keypad will display STAY message in the home screen view.
ATTENTION: System arming in Stay mode by the keypad must be carried out without Configuration mode being activated.
NOTE: The system can be armed in Stay mode, only if there is at least one zone with Stay attribute enabled.
NOTE: Stay mode is not supported by virtual zones.
4.12. Tampers
The tamper circuit is a single closed loop such that a break in the loop at any point will cause a tamper alarm regardless of the system
status – armed or disarmed. During the tamper alarm, the system will activate the siren/bell and the keypad buzzer and send the SMS text
message to the listed user phone number. The system will cause tamper alarm under the following conditions:
•
If the enclosure of a detection device, siren/bell, metal cabinet or keypad is opened, the physical tamper switch will be triggered. By
default, indicated as Tamper x in the SMS text message (x = tamper number).
•
If the wireless signal is lost due to low signal level or low battery power on a certain wireless device.
By default, tamper alarm notification by SMS text message is enabled. To disable/enable tamper alarm notification, please refer to the
following configuration methods.
Disable tamper alarm
notification
EKB2
EKB3
ESIM264 USER MANUAL V2.4
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → TAMPER EVENT → OK
→ DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 08 0 #
Example: 25080#
EN
23
Config
Tool
Enable tamper alarm
notification
EKB2
EKB3
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → TAMPER EVENT → OK
→ ENABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 08 1 #
Example: 25081#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
For more details on how to view violated tamper, please refer to 4.13. Alarm indications and notifications for user.
4.12.1. Tamper Names
Each tamper has a name that can be customized by the user. The tamper names are used in SMS text messages that are sent to the user
during the tamper alarm. By default, the tamper names are: Tamper 1, Tamper 2, Tamper 3, Tamper 4 etc. To set a different tamper name,
please refer to the following configuration methods.
Manage tamper name
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
4.13. Alarm indications and notifications for user.
When a zone, depending on zone type (see 14.5. Zone Type Definitions), or tamper is violated, the system will cause an alarm. By default, the alarm duration is 1 minute (see 20. SIREN/BELL regarding the alarm duration). During the alarm, the system will follow this
pattern:
1. The system activates the siren/bell and the keypad buzzer.
a) The siren/bell will emit pulsating sound if the violated zone is of Fire type, otherwise the sound will be steady.
b) The keypad buzzer will emit short beeps.
c) Depending on violated zone type, EKB2 keypad will display BURGLARY ALARM message followed by one of the alarm messages in the
home screen view:
•
ALARM.
•
FIRE ALARM.
•
24H ALARM.
d) During the tamper alarm, EKB2 keypad will display TAMPER ALARM message in the home screen view.
e) If one or more zones are violated, EKB3 will light ON the corresponding violated zone indicator (-s) ranging from 1 through 12. Indicator
will flash if one or more high-numbered zones are violated. If one or tampers are violated, indicator
will light ON. For more
details on viewing violated high-numbered zone and tamper numbers by EKB3 keypad, please refer to 10. INDICATION OF SYSTEM
FAULTS.
2. The system attempts to send an SMS text message, containing the violated zone/tamper name, to the first listed user phone number,
sharing the same partition as the violated zone/tamper. The system will send SMS text messages regarding each violated zone/tamper
separately.
a) If the user phone number is unavailable and the system fails to receive the SMS delivery report during 45 seconds, it will attempt to
send the SMS text message to the next listed user phone number, assigned to the same partition as the previous one. The user phone
number may be unavailable due to the following reasons:
•
mobile phone was switched off.
•
was out of GSM signal coverage.
b) The system will continue sending the SMS text message to the next listed user phone numbers in the priority order until one is available. The system sends the SMS text message only once and will not return to the first user phone number if the last one was unavaila-
24
EN
ESIM264 USER MANUAL V2.4
ble.
3. By default, the system attempts to ring the first user phone number, sharing the same partition as the violated zone/tamper. The system
will dial regarding each violated zone/tamper separately.
a) When the call is answered, the user will be able to listen on the mobile phone for approx. 30 seconds to what is happening in the area,
surrounding the alarm system. This feature will be available only if a microphone is connected to the system (see REMOTE LISTENING
AND 2-WAY VOICE COMMUNICATION).
b) The system will dial the next listed user phone number, assigned to the same partition, if the previous user was unavailable due to the
following reasons:
• mobile phone was switched off.
• mobile phone was out of GSM signal coverage.
• provided “busy” signal.
• user did not answer the call after several rings, predetermined by the GSM operator.
c)
The system will continue dialling the next listed user phone numbers in the priority order until one is available. The system dials only
once and will not return to the first user phone number if the last one was unavailable.
d) The system will not dial the next listed user phone number if the previous one was available, but rejected the phone call.
To silent the siren/bell as well as to cease system phone calls and SMS text message sending to the user phone numbers, please disarm the
system (see 4. ARMING AND DISARMING).
View violated zones
View violated tampers
SMS
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
EKB2
Menu path:
OK → VIOLATED ZONES → OK → ZONE 1... 44
EKB3
Please, refer to illuminated zone indicators ranging from 1 through 12 on the keypad. The
flashing indicator
represents violated high-numbered zones (Z13-Z44). For more details
on violated high-numbered zone indication, please refer to 10. INDICATION OF SYS­TEM
FAULTS.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
The system will automatically send an SMS text message, containing a violated tamper name,
to user phone number.
EKB2
Menu path:
OK → VIOLATED TAMPERS → OK → TAMPER 1... 44
EKB3
The illuminated indicator
represents system fault presence including violated tamper.
For more details on violated tamper indication, please refer to 10. INDICATION OF SYSTEM
FAULTS.
For more details on how to disable/enable SMS text messages and phone calls to the listed user phone number in case of alarm, please refer
to 4.13. Enabling and Disabling Alarm Notifications
ATTENTION: Phone calls to the listed user phone number in case of alarm are disabled by force when MS mode is enabled.
NOTE: If one or more zones/tampers are violated during the alarm, the system will attempt to send as many SMS text message and dial the
user phone number as many times as the zone/tamper was violated. The capacity of the queue is 24 events maximum.
NOTE: If the system sent the SMS text message and/or dialled the user phone number after disarming the system, it means that the SMS
text message and/or phone call was queued up in the memory before the system was disarmed
ESIM264 USER MANUAL V2.4
EN
25
4.14. Enabling and Disabling Alarm Notifications
By, default the system will ring the listed user phone numbers in case of alarm. To disable/enable this feature, please refer to the following
configuration methods.
Disable call in case of
alarm
Enable call in
case of alarm
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CALL IN CASE ALARM → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 30 and parameter status value:
30 1#
Example: 301#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CALL IN CASE ALARM → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 30 and parameter status value:
30 0#
Example: 300#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By, default the system will send SMS text message to the listed user phone numbers in case of alarm. To disable/enable this feature, please
refer to the following configuration methods.
Disable SMS text
message in case of
alarm
Enable SMS text
message in case of
alarm
26
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → ALARM EVENT → OK
→ DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, event number and parameter status value:
25 03 0 #
Example: 25010#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → ALARM EVENT → OK
→ ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, event number and parameter status value:
25 01 1 #
Example: 25011#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ESIM264 USER MANUAL V2.4
By default, the system sends SMS text message to the first available user in case of alarm. If the system did not receive the SMS delivery
report during 45 seconds, it will attempt to send the SMS text message to the next listed user phone number. To ignore the SMS delivery
report and allow/disallow the system to send the SMS text message to every listed user phone number, please refer to the following configuration methods
Enable SMS text
message to all listed
user phone numbers in
case of alarm
Disable SMS text
message to all listed
user phone numbers in
case of alarm
SMS
SMS text message content:
ssss_SMSALL:ON
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ALARM SMS ALL → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 21 and parameter status value:
21 1 #
Example: 211#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SMSALL:OFF
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:OFF
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ALARM SMS ALL → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 21 and parameter status value:
21 0 #
Example: 210#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, tamper alarm notification by SMS text message is enabled. For more details on how to disable/enable tamper alarm notification,
please refer to 4.12. Tampers.
ATTENTION: Regardless of the Call in Case of Alarm parameter status, the system will NOT ring the listed user phone number if the system
is connected to the monitoring station.
4.15. Programmable (PGM) outputs
A PGM output is a programmable output that toggles to its set up state when a specific event has occurred in the system, the scheduled
weekday and time has come or if the user has initiated the PGM output state change manually. Normally, PGM outputs can be used to open/
close garage doors, activate lights, heating, watering and much more. When a PGM output turns ON, the system triggers any device or relay
connected to it.
ESIM264 comes equipped with four open-collector PGM outputs allowing to connect up to four devices or relays. For more details on PGM
output, please refer to ESIM264 installation manual at eldesalarms.com
ESIM264 USER MANUAL V2.4
EN
27
5. WIRELESS DEVICES
ESIM264 system can be equipped with a wireless transmitter-receiver module EWT1 for system extension capabilities. The module allows
the user to easily pair up to 16 ELDES-made wireless devices to the system. This includes the following:
• EWD2 - wireless magnetic door contact/shock sensor/flood sensor.
• EWS3 – wireless indoor siren.
• EWS2 – wireless outdoor siren.
• EWK1 and EWK2 – wireless keyfob.
• EWF1 - wireless smoke detector.
RADIO SYSTEM INSTALLATION AND SIGNAL PENETRATION manual and the latest user manual of the wireless device located at
eldesalarms.com
The wireless devices can operate at a range of up to 30m (98.43ft) from the alarm system unit while inside the building and at up to 150m
(492.13ft) range in open areas. The wireless connection is two-way and operates in one of four available channels in ISM868 (EU version)
/ ISM915 (US version) non-licensed band.
The communication link between the wireless device and the alarm system is constantly supervised by a configurable self-test period,
known as Test Time. When the wireless device is switched ON, it will initiate the Test Time transmission to the system within its wireless
connection range. In order to optimize battery power saving of the wireless device, the Test Time periods vary by itself while the device
is switched ON, but still unpaired. When the alarm system is switched OFF or if the wireless device is unpaired or removed the Test Time
period of the wireless device is as follows (non-customizable):
• EWS2, EWS3, EWF1:
• First 360 attempts after the device startup (reset) - every 10 seconds.
• The rest of attempts - every 1 minute.
• EWD2:
• First 360 attempts after the device startup (reset) - every 10 seconds.
• The rest of attempts - every 2 minutes.
Once the wireless device is paired, it will attempt to exchange data with ESIM264 system. Due to battery saving reasons, all ELDES wireless
devices operate in sleep mode. The data exchange will occur instantly if the wireless device is triggered (zone alarm or tamper alarm) or
periodically when the wireless device wakes up to transmit the supervision signal, based on Test Time value, to the system as well as to ac­
cept the queued up command (if any) from the system. By increasing the Test Time period, EWS2/EWS3 siren response time will decrease.
Example: The alarm occurred at 09:15:25 and the system queued up the command for EWS3 siren to start sounding. By default, Test Time
value of EWS3 siren is 7 seconds, therefore EWS3 siren will sound at 09:15:32.
By default, the Test Time period is as follows (customizable):
• EWF1 EWD2: every 30 seconds.
• EWS2, EWS3: every 7 seconds.
5.1. Pairing, Removing and Replacing Wireless Device
Wireless device management can be easily and conveniently carried out using the graphical interface of ELDES Configuration Tool software. If you intend to manage the wireless devices by SMS text massage, an 8-character wireless device ID code will be required in order to
pair the device with the system or to remove it from the system. The wireless ID code is printed on a label, which can be located on the inner
or outer side of the enclosure or on the printed circuit board (PCB) of the wireless device.
Once a wireless device is paired, it occupies one of 16 available wireless device slots and the system adds single or multiple wireless zones
and wireless PGM outputs depending on the wireless device model.
NOTE: If you are unable to pair a wireless device, please restore the wireless device’s parameters to default and try again. For more details
on how to restore the default parameters, please refer to the user manual provided along with the wireless device or visit eldesalarms.com
to download the latest user manual.
5.2. Wireless Device Information
Once a wireless device is paired, the user can view the following information of a determined wireless device:
•
Battery level (expressed in percentage).
•
Wireless signal strength (expressed in percentage).
•
Error rate (number of failed data transmission attempts in 10-minute period) - indicated only in EKB2 keypad menu.
•
Firmware version.
•
Test Time period (expressed in milliseconds) of a wireless device - indicated only in SMS text message reply.
5.3. Electrical and Mechanical Characteristics
Wireless band
ISM868/ISM915
Dimensions
68x38x18mm (2.72x1.50x0.71in)
Operating temperature range
-20...+55°C (-4... 131°F)
Wireless communication range
Up to 30m (98.43ft) in premises; up to 150m (492.13ft) in open areas
Maximum number of wireless devices
16
28
EN
ESIM264 USER MANUAL V2.4
6. BACKUP BATTERY, MAINS POWER STATUS MONITORING AND MEMORY
6.1. Backup Battery Status Monitoring
The system may come equipped with a backup battery maintaining power supply of the system when the mains power supply is temporally
lost. The implemented feature allows the system to perform a self-test on the backup battery and notify the listed user phone number by
SMS text message as well as to indicate system fault by the keypad (see 10. INDICATION OF SYSTEM FAULTS) if:
•
battery has failed and requires replacement – battery resistance is 2Ω or higher; self-tested every 24 hours.
•
battery power is running low – battery voltage is 10.5V or lower; constantly self-tested.
6.2. Mains Power Status Monitoring
If the household electricity is unstable in the system installation area, the system may temporally lose its power supply and continue operating on the backup battery power. The system supervises the mains power supply and notifies the listed user phone number by SMS text
message as well as indicates system fault condition on the keypad (see 10. INDICATION OF SYSTEM FAULTS) when the mains power
is lost. When the mains power restores, the system will notify the listed user phone number by SMS text message and the keypad will no
longer indicate system fault.
NOTE: In case of low back-up battery, the system will send the SMS text message to the user and transmit the data message to the monitoring station, but will NOT indicate a system fault on the keypad.
Memory
The configuration settings and event log records are stored in a built-in EEPROM memory, therefore even if the system is fully shut down,
the configuration and event log remain. For more details regarding the event log, please refer to 9. EVENT LOG
7. TEMPERATURE SENSOR
The system may be equipped with a temperature sensor intended for temperature measurement in the surrounding area. This feature
allows to monitor the temperature in real-time and receive a notification by SMS text message to the listed user phone number when the
set temperature boundaries are exceeded.
7.1. Adding, Removing and Replacing Temperature Sensors
To add a temperature sensor to the system, do the following:
a) Shutdown the system.
b) Wire up the temperature sensor to the 1-Wire interface terminals.
c)
Power up the system.
The real-time temperature value of the temperature sensor is included in the Info SMS text message (see 8. SYSTEM INFORMATION.
INFO SMS) as well as it is indicated in the home screen view of EKB2 keypad.
To view the real-time temperature value measured by the temperature sensor, please refer to the following configuration methods.
View real-time
temperature value
SMS
EKB2
ESIM264 USER MANUAL V2.4
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
Refer to home screen view on the keypad.
EN
29
7.2. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS
The system supports an SMS text message identified as the Temperature Info SMS, which is automatically delivered to the listed user
phone number if the specified minimum (MIN) or maximum (MAX) temperature boundary is exceeded.
To set the MIN and MAX temperature boundaries, please refer to the configuration methods.
Set MIN and MAX
temperature
boundaries
SMS
EKB2
EKB3
Config
Tool
View MIN and
MAX temperature
boundaries
SMS
EKB2
Config
Tool
SMS text message content:
ssss_TEMP:mnn:mxx
Value: ssss – 4-digit SMS password; mnn – MIN boundary, range – [-55... 125] C; mxx - MAX
boundary, range – [-55... 125] C.
Example: 1111_TEMP:-5:28
Menu path:
MIN: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MIN → OK → mnn → OK
MAX: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MAX → OK → mxx → OK
Value: aaaa – 4-digit administrator password; mnn – MIN boundary, range – [-55... 125] C;
mxx - MAX boundary, range – [-55... 125] C.
Keys P1 or P2 are used to enter minus character, e.g. -20.
Enter parameter 19 and temperature boundary value:
19 mnn mxx #
Value: mnn – MIN boundary, range – [-55... 125] C; mxx - MAX boundary, range – [-55... 125]
C. 00 value stands for minus character, e. g. 0020 = -20
Example: 19001532#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_TEMP
Value: ssss – 4-digit SMS password.
Example: 1111_TEMP
Menu path:
MIN: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MIN
MAX: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MAX
Value: aaaa – 4-digit administrator password.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, Temperature Info SMS is enabled. To disable/enable it, please refer to the following configuration methods.
Disable Temperature
Info SMS
SMS
EKB2
30
EN
SMS text message content:
ssss_TEMP:00:00
Value: ssss – 4-digit SMS password.
Example: 1111_TEMP:00:00
Menu path:
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → DISABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
ESIM264 USER MANUAL V2.4
EKB3
Config
Tool
Enable Temperature
Info SMS
EKB2
EKB3
Config
Tool
ESIM264 USER MANUAL V2.4
Enter parameter 25, event number and parameter status value:
25 14 0 # - Temperature fallen
25 15 0 # - Temperature exceeded
Example: 25140#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → ENABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 14 1 # - Temperature fallen
25 15 1 # - Temperature exceeded
Example: 25151#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
31
8. SYSTEM INFORMATION. INFO SMS
The system supports an informational SMS text message identified as the Info SMS, which can be delivered upon request. Once requested,
the system will reply with Info SMS that provides the following:
• System date and time.
• System status: partition armed (ON)/disarmed (OFF).
• GSM signal strength.
• Mains power supply status.
• Temperature of the area surrounding the temperature sensor (if any).
• State of zones (OK/alarm).
• Name and status (ON/OFF) of PGM outputs.
Request for system
information
SMS
Config
Tool
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
This operation may be carried out from the PC using the ELDES Configuration Tool software.
8.1. Periodic Info SMS
By default, the system sends Info SMS to the listed user phone number periodically once a day at 11:00 (frequency – 1 day; time – 11). The
mini­mum period is every 1 hour (frequency – 0 days; time – 1). Typically, this feature is used to verify the power supply and online status
of the system.
To set a different frequency and time or disable periodic Info SMS, please refer to the following configuration methods.
Set periodic Info SMS
frequency and time
SMS
EKB2
EKB3
Config
Tool
Disable periodic Info
SMS
SMS
EKB2
32
EN
SMS text message content:
ssss_INFO:fff:it
Value: ssss – 4-digit SMS password; fff – frequency, range – [00... 99] days; it – time, range
– [01... 23].
Example: 1111_INFO:3.15
Menu path:
Frequency: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → FREQUENCY (DAYS) → fff → OK
Time: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → TIME → it → OK
Value: aaaa – 4-digit administrator password; fff – frequency, range – [00... 125] days; it –
time, range – [01... 23].
Enter parameter 11, time and frequency:
11it fff #
Value: it – time, range – [01... 23]; fff – frequency, range – [00... 125] days.
Example: 110412#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_INFO:00:00
Example: 1111_INFO:00.00
Menu path:
Frequency: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → FREQUENCY (DAYS) → 0 → OK
Time: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → TIME → 0 → OK
Value: aaaa – 4-digit administrator password.
ESIM264 USER MANUAL V2.4
EKB3
Enter parameter 11, time and frequency:
11 00 00 #
Example: 110000#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Unlike Info SMS upon request, periodic Info SMS text message does not included zone states, PGM output names and status.
9. EVENT LOG
This feature allows to chronologically register up to 500 timestamped records regarding the following system events:
•
System start.
•
System arming/disarming.
•
Zone violated/restored.
•
Tamper violated/restored.
•
Zone bypassing.
•
Wireless device management.
•
Temperature deviation by MIN and MAX boundaries.
•
System faults.
The event log is of LIFO (last in, first out) type that allows the system to automatically replace the oldest records with the the latest ones.
View event log
EKB2
Menu path:
OK → VIEW EVENT LOG → OK → uuuu → OK
Value: uuuu - 4-digit user code.
To export the event log to .log file or clear it, please refer to the following configuration method.
Export/clear event log
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, event log is enabled. To disable/enable this feature, please refer to the following configuration methods.
Disable event log
Enable event log
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EVENT LOG → OK
→ DISABLE → OK
EKB3
Enter parameter 36 and parameter status value:
36 0 #
Example: 360#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EVENT LOG → OK
→ ENABLE → OK
EKB3
Config
Tool
ESIM264 USER MANUAL V2.4
Enter parameter 36 and parameter status value:
36 1 #
Example: 361#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
33
10. INDICATION OF SYSTEM FAULTS
The system comes equipped with self-diagnostic feature allowing to indicate the presence of any system fault by the keypad.
Message TBL displayed in the home screen view indicates presence of system faults. In order to find out more on the particular system problem, please open menu section TROUBLES. The description on each system problem is indicated in the table
EKB2
below.
Menu path:
OK → TROUBLES
Name
VIOLATED TAMPER
BATTERY FAILED
Description
One or more tampers are violated
Backup battery requires replacement - backup
battery resistance is 2Ω or higher
Mains power supply is lost
Date/time not set
GSM connection is lost
MAIN PWR FAILURE
DATE/TIME NOT SET
GSM ERROR
1. Steady ON or flashing indicator
EKB3
Indication
Steady ON
Flashing
represents certain system faults. For more details, please refer to the following table below.
Description
One or more tampers are violated; other system faults (see below)
One or more high-numbered zones (Z13-Z76) are violated (see below)
2. In order to find out more on a certain system fault, please enter the following command.
Enter command:
#
View system faults
After this procedure the keypad will illuminate red indicators for 15 seconds. The description of each indication is provided in the
table below.
LED #
Description
1
2
3
4
5
One or more tampers are violated
Backup battery requires replacement - backup battery resistance is 2Ω or higher
Mains power supply is lost
Date/time not set
One or more high-numbered zones (Z13-Z44) are violated (see step #3)
6
GSM connection is lost
3. In order to find out the violated high-numbered zone, please enter the following command and refer to the table below.
View violated highnumbered zones
Enter command:
1
4. In order to find out which particular tamper is violated, please enter the following command. In case there is a combination of
flashing and illuminated red indicators on the keypad, please refer to the table below in order to find out the violated high-numbered tamper (Tamper 13 - 44).
Enter command:
2
View violated tampers
The following table provides the combinations of red indicators belonging to a certain indicator section (A or B) on the keypad.
The combination of the flashing red indicator in section A and illuminated (steady ON) red indicator in section B represents the
respective number of a violated high-numbered zone or tamper.
A (flashing)
LED #1
LED #2
LED #3
LED #4
LED #5
LED #6
34
EN
B (steady ON)
LED #7
LED #8
LED #9
LED #10
LED #11
LED #12
Z13
Z14
Z15
Z16
Z17
Z18
Z19
Z20
Z21
Z22
Z23
Z24
Z25
Z26
Z27
Z28
Z29
Z30
Z31
Z32
Z33
Z34
Z35
Z36
Z37
Z38
Z39
Z40
Z41
Z42
Z43
Z44
ESIM264 USER MANUAL V2.4
11. CONTROLLING ELECTRICAL APPLIANCES
Your system features 4 or more PGM outputs intended for connection and control of various electrical appliances. This provides a possibility to
control garage gates, turn on and off your house heating, lighting, cooling system, reset smoke sensors to restored state etc. The PGM outputs
must be configured by your installer before using them.
Turning ON/OFF the Electrical Appliances Instantly
1.
SMS
In order to turn ON a specified PGM output, send the following SMS text message to the system’s phone number from any
out of 10 listed user phone numbers:
SMS text message content:
ssss_Coo:ON or ssss_out-name:ON
Value: ssss - 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name – PGM output name.
Example: 1111_Pump:ON
2.
In order to turn OFF a specified PGM output, send the following SMS text message to the system‘s phone number from any
out of 10 listed user phone numbers:
SMS text message content:
ssss_Coo:OFF or ssss_out-name:OFF
Value: ssss - 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name – PGM output name.
Example: 1111_C2:OFF
3.
The system will reply with confirmation by SMS text message to the user phone number that sent the SMS text message.
13
SMS
SMS
User
ESIM264
Turning ON/OFF the Electrical Appliances for a Determined Time Period
1.
EKB2
In order to instantly turn ON a specified PGM output and keep it in this state for a determined time period, send the following SMS message to the system’s phone number from any out of 5 preset user phone numbers:
SMS text message content:
XXXX_Cn:ON:hr.mn:sc or XXXX_OutputName:ON:hr.mn:sc
Value: Cn – PGM output number, range – [C1... C44]; hr – hours, range – [00... 23], mn – minutes, range – [00... 59];
sc – seconds, range – [00... 59].
Example: 1111_Pump:ON:12:30:15
2.
In order to instantly turn OFF a specified PGM output and keep it in this state for a determined time period, send the following
SMS message to the system’s phone number from any out of 10 preset user phone numbers:
SMS text message content:
XXXX_Cn:OFF:hr.mn:sc or XXXX_OutputName:OFF:hr.mn:sc
Value: Cn – PGM output number, range – [C1... C44]; hr – hours, range – [00... 23], mn – minutes, range – [00... 59];
sc – seconds, range – [00... 59].
Example: 1111_C3:OFF:13.25:56
3. The system will reply with confirmation by SMS text message to the user phone number who sent the SMS message..
14
SMS
User
ESIM264 USER MANUAL V2.4
SMS
ESIM264
EN
35
12. IF THE ALARM SYSTEM IS CONNECTED TO A MONITORING STATION
The following system features may be disabled by your alarm system installer if the system is con­nected to a monitoring station:
36
•
Confirmation by SMS text message when arming, disarming and turning off the alarm by phone call, SMS text message, EKB2/EKB3
keypad, iButton key, EWK1/EWK2 wireless keyfob.
•
Alarm indication by phone call.
•
Alarm indication by SMS text message.
•
Violated zone/tamper name indication by SMS text message.
•
Temperature indication by SMS text message.
•
Periodical system information by SMS text message.
•
Any fault indication by SMS text message and keypad.
•
Any other SMS text message generated by the system.
EN
ESIM264 USER MANUAL V2.4
13. TECHNICAL SPECIFICATIONS
13.1. Electrical & Mechanical Characteristics
Electrical and Mechanical Characteristics
Mains power
Current in standby without external sensors and keypad
Recommended backup battery voltage, capacity
Recommended backup battery type
Backup battery charge current
GSM modem frequency
Cable type for GSM/GPRS antenna connection
Number of zones on-board
Nominal zone resistance
Number of PGM outputs on-board
On-board PGM output circuit
Maximum commuting on-board PGM output values
BELL: Siren output when activated
BELL: Maximum cable length for siren connection
BELL: Cable type for siren connection
AUX: Auxiliary equipment power supply voltage
BELL+AUX: Maximum accumulative current of auxiliary equipment and
siren
AUX: Maximum cable length for auxiliary equipment connection
AUX: Cable type for auxiliary equipment connection
BUZ: Maximum current of mini buzzer
BUZ: Power supply voltage of buzzer
BUZ: Cable type for mini buzzer connection
Supported temperature sensor model
Maximum supported number of temperature sensors
DATA: Maximum cable length for 1-Wire communication
DATA: Cable type for 1-Wire communication
Supported iButton key model
Maximum supported number of iButton keys
Maximum supported number of keypads
Y/G: Maximum cable length for RS485 communication
Y/G: Cable type for RS485 communication
MIC: Maximum cable length for microphone connection
MIC: Cable type for microphone connection
Wireless band
Wireless communication range
Maximum supported number of wireless devices
Event log size
Maximum supported number of zones
Maximum supported number of pgm outputs
Cable type for zone and pgm output connection
Communications
Supported protocols
Dimensions
Operating temperature range
Humidity
ESIM264 USER MANUAL V2.4
16-24V 50 Hz ~1.5A max / 18-24V
Up to 80mA
12V; 1,3-7 Ah
Lead-Acid
Up to 900mA
850/900/1800/1900MHz
Shielded
6 (ATZ mode: 12)
5,6kΩ (ATZ Mode: 5,6kΩ and 3,3kΩ)
4
1R
OUT
1,5A max
Open Collector Output.
Output is pulled to COM
when turned ON.
4 x Voltage – 30V; current – 500mA.
Connected to COM
Up to 100m (328.08ft)
Unshielded
13,8V DC
1A
Up to 100m (328.08ft)
Unshielded
150mA
5V DC
Unshielded
Maxim®/Dallas® DS18S20, DS18B20
1
Up to 30m (98.43ft)
Unshielded
Maxim®/Dallas® DS1990A
5
4 x EKB2 / EKB3
Up to 100m (328.08ft)
Unshielded
Up to 2m (6.56ft)
Unshielded
ISM868 /ISM 915
Up to 30m (98.43ft) in premises;
up to 150m (492.13ft) in open areas
16
500 events
44
44
Unshielded
SMS, Voice calls, GPRS network, RS485, CSD
Ademco Contact ID, EGR100, Kronos, Cortex SMS
140x100x18mm (5.51x3.94x0.71in)
-20...+55°C (-4... 131°F)
0-90% RH @ 0... +40°C
(0-90% RH @ 32... 104°F) (non-condensing)
EN
37
13.2. Main unit, LED and Connector functionality
STATUS
PWR
Z6
Z5
Z4
Z3
Z2
Z1
C1
C2
NETWORK
Slots for EA1, EA2 or EPGM8 module
Slots for EWT1 wireless module
DEF
OPEN
SIM CARD
G SM
MO DE M
3A
MODULES
EWT1
C4
C3
15
ANTENNA
SMA
PRG
EWT1
USB
FUSE
Main Unit Functionality
GSM MODEM
GSM network 850/900/1800/1900MHz
modem
SIM CARD
SIM card slot / holder
DEF
Pins for restoring default settings
USB
Mini USB port
FUSE F1
3A fuse
GSM/GPRS antenna SMA type connector
ANTENNA
MODULES
AK U +
AK U -
NETWORK indication
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
LED Functionality
NETWORK GSM network signal strength and status
C2, C1
PGM output C1 and C2 status. Steady ON = turned
ON; OFF = turned OFF
Z1
Zone Z1 state (ATZ mode: Z1 and Z7). Steady ON =
violated; OFF = restored.
Z2
Zone Z2 state (ATZ mode: Z2 and Z8). Steady ON =
violated; OFF = restored.
Z3
Zone Z3 state (ATZ mode: Z3 and Z9). Steady ON =
violated; OFF = restored.
Z4
Zone Z4 state ( ATZ mode: Z4 and Z10). Steady ON =
violated; OFF = restored.
Z5
Zone Z5 state (ATZ mode: Z5 and Z11). Steady ON =
violated; OFF = restored.
Z6
Zone Z6 state (ATZ mode: Z6 and Z12). Steady ON =
violated; OFF = restored.
PWR
Power supply status. Steady ON = power supply OK;
OFF = no power.
STATUS
Micro-controller status. Flashing = micro-controller
OK; OFF = micro-controller fault.
Description
OFF
No GSM signal - SIM card
missing; PIN code enabled
on SIM card; GSM antenna
disconnected or faulty; GSM
operator’s fault; GSM signal
unavailable in the are
Flashing every 3 sec.
Poor GSM signal strength
Flashing every 1 sec.
Medium GSM signal
strength
Flashing several times per sec. Good GSM signal strength
Steady ON
Excellent GSM signal
strength
Connector Functionality
Z1 - Z6
Security zones
COM
Common terminal for all zones
DATA
1-Wire® interface for iButton® key and temperature sensor connection
+5V
Temperature sensor power supply contact (+5V)
MICMicrophone negative terminal
MIC+
Microphone positive terminal
BUZMini buzzer negative terminal
BUZ+
Mini buzzer positive terminal
C1 - C4
PGM outputs
Y
RS485 interface CLOCK terminal (yellow wire)
G
RS485 interface DATA terminal (green wire)
COM
Common return terminal
BELLSiren negative terminal
BELL+
Siren positive terminal
AUXNegative power supply terminal for auxiliary equipment
AUX+
Positive power supply terminal for auxiliary equipment
AC/DC
Mains power terminal
AKU-
Backup battery negative terminal
AKU+
Backup battery positive terminal
38
EN
ESIM264 USER MANUAL V2.4
General Wiring
16
AKU+
AKU-
Backup Battery
12V 1.3-7Ah
AC /DC
AC /DC
AUX+
AUXBELL+
BELLCO M
G
Y
C2
C1
BUZ+
BUZMIC +
MIC +5V
DATA
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
Metal cabinet
PE terminal
Fuse 500 mA
~16-24V
Z6
Z5
Z4
Z3
Z2
Z1
~230V 50Hz
BUZ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
MIC
SIREN/BELL
EPGM1
500mA max.
iButton®
key reader
Relay
module
1
2
3
4
5
6
7
8
9
*
0
#
EKB3
Temperature sensor
EKB2
Zone Connection Types
Type 1
Example of 4-wire smoke detector wiring
EOL 5.6K
COM
Z
C1
Z
EOL 5.6K
COM
Z
EOL 5.6K
TAMPER
NC
COM
Z
3.3K
5,6 kΩ
NO
AUX+
17
COM
Z1
COM
5.6K
NC
3.3K
NC
6-Zone mode: Normally open contact
with 5,6KΩ end-ofline resistor.
NC
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
NC
GND
COM
NO
+Vin
Type 2
Example of magnetic door contact wiring
18
COM
Z1
Z
EOL 5.6K
COM
NC
6-Zone mode: Normally closed contact
with 5,6KΩ end-ofline resistor
Z
EOL 5.6K
COM
Z
3.3K
TAMPER
5,6 kΩ
OM
13.3. Wiring Diagrams
5.6K
3.3K
NC
COM
NC
NC
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
NC
COM
NC
Magnet
NOTE: The system does NOT support 2-wire smoke detectors.
ESIM264 USER MANUAL V2.4
EN
39
Type 3
Example of motion detector wiring
EOL 5.6K
TAMPER
Z
COM
5.6K
6-Zone mode: Tamper
and 5,6KΩ end-of-line
resistor and 3,3KΩ
end-of-line
resistor
with normally closed
contact.
Z
EOL 5.6K
NC
3.3K
NC
TAMPER
NC
NC
5,6 kΩ
COM
5.6K 3.3K
COM
Type 4
GND
NC
+Vin
Example of magnetic door contact (Z1) and glass break sensor (Z7) wiring
3.3K
C
NC
ATZ mode: 5,6KΩ
end-of-line resistor
and normally closed
contact with 3,3KΩ
end-of-line resistor
and normally closed
contact
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
3,3 kΩ
NC
5,6 kΩ
COM
5.6K
AUX+
AUX-
Z
COM
Z1
20
K
NC
3,3 kΩ
TAMP
M
NC
NC
COM
Magnet
Type 5
COM
NC
EN
+Vin
5.6K 3.3K
NC
ATZ mode: Tamper,
5,6KΩ
end-of-line
resistor, 5,6KΩ endof-line resistor with
normally
closed
contact and 3,3KΩ
end-of-line resistor
with normally closed
contact.
40
NC
AUX+
AUX-
TAMPER
GND
COM
Z1
Z
EOL 5.6K
C
COM
Example of motion detector (Z1) and magnetic door contact (Z7) wiring
21
M
C
COM
3.3K
AUX+
AUX-
Z
COM
Z1
19
M
5,6 kΩ
5,6 kΩ
3,3 kΩ
NC
COM
Magnet
COM
NC
TAMP
GND
+Vin
ESIM264 USER MANUAL V2.4
14. ADDITIONAL INFORMATION
TERMS OF USE
The following terms and conditions govern use of the ESIM264 device and contains important information on limitations regarding the
product’s use and function, as well as information on the limitations of the manufacturer’s liability. Please carefully read these terms and
conditions. For more information on your product, please visit eldesalarms.com
TECHNICAL SUPPORT
In order to ensure continuous and proper operation of the ESIM264 device and uninterrupted service, it is the responsibility of the User to
make sure that: (I) the product is properly installed, and (II) there is constant internet or GSM connection and electrical supply (low battery
must be replaced in time). If you experience difficulty during the installation or subsequent use of the system, you may contact ELDES, UAB
distributor or dealer in your country/region. For more information see eldesalarms.com
WARRANTY PROCEDURES
Warranty and out of warranty service should be obtained by contacting the system integrator/dealer/retailer/e-tailer or distributor where
the customer purchased the product. When requesting for service, the proof of purchase and the product serial number must be provided.
The return of the defective product should be strictly through the original route of purchase, and the customers shall pack the product
appropriately to prevent the returned product from suffering in the transportation.
MANUFACTURER WARRANTY
ELDES provides a limited warranty for its products only to the person or entity that originally purchased the product from ELDES or its
authorized distributor or retailer and only in case of defective workmanship and materials under normal use of the system for a period of
twenty four (24) months from the date of shipment by the ELDES, UAB (Warranty Period). Warranty obligations do not cover expandable
materials (power elements and/or batteries), holders and enclosures. The warranty remains valid only if the system is used as intended,
following all guidelines outlined in this manual and in accordance with the operating conditions specified. The warranty is void if the system
has been exposed to mechanical impact, chemicals, high humidity, fluids, corrosive and hazardous environments or force majeure factors.
If a hardware defect arises and a valid claim is received within the Warranty Period, at its own discretion, ELDES, UAB will either (a) repair a
hardware defect at no charge, using new or refurbished replacement parts, or (b) exchange the product with a product that is new or which
has been manufactured from new or serviceable used parts and is at least functionally equivalent to the original product, or (c) refund the
purchase price of the product.
LIMITED LIABILITY
The buyer must agree that the system will reduce the risk theft, burglary or other dangers but does not provide guarantee against such
events. ELDES, UAB will not assume any responsibility regarding personal or property, or revenue loss while using the system. ELDES, UAB
is not affiliated with any of the Internet providers, therefore, it shall not responsible for the quality of Internet service.
ELDES, UAB shall also assume no liability due to direct or indirect damage or loss, as well as unreceived income when using the system, including cases, when the damages arise due to the above mentioned risks, when due to breakdown or malfunction the user is not informed
in a timely manner about a risk which has arisen. In any case, the liability of ELDES, UAB, as much as it is allowed by the laws in force, shall
not exceed the price of acquisition of the product.
CONSUMER PROTECTION LAWS
FOR CONSUMERS WHO ARE COVERED BY CONSUMER PROTECTION LAWS OR REGULATIONS IN THEIR COUNTRY OF PURCHASE OR, IF DIFFERENT, THEIR COUNTRY OF RESIDENCE, THE BENEFITS CONFERRED BY THIS WARRANTY ARE IN ADDITION TO ALL RIGHTS AND
REMEDIES CONVEYED BY SUCH CONSUMER PROTECTION LAWS AND REGULATIONS. This warranty grants upon you specific legal
rights, and you may also have other rights that vary by country, state or province.
About User Manual
This document describes basic configuration and usage of alarm system ESIM264. It is very impor­tant to read the user manual before starting
to use the system.
Safety instructions
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
• GSM alarm and management system ESIM264 (also referenced as “alarm system”, “system“ or “device”) has radio transceiver operating
in GSM 850/900/1800/1900 bands.
• DO NOT use the system where it can be interfere with other devices and cause any potential danger.
• DO NOT use the system with medical devices.
• DO NOT use the system in hazardous environment.
• DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
• DO NOT attempt to personally repair the system.
• System label is on the bottom side of the device.
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that the
product must not be disposed of together with household waste. To prevent possible harm to human health and/or the environment, the product must be disposed on in an approved and environmentally safe recycling process. For further information
on how to dispose of this product correctly, contact the system supplier, or the local authority responsible for waste disposal
in your area.
Copyright © ELDES, UAB, 2016. All rights reserved
It is strictly forbidden to copy and distribute the information contained in this document or to pass thereof to a third
party without an a priori written authorization obtained from ELDES, UAB. ELDES, UAB reserves the right to update
or modify this document and/or related products without an a priori warning. ELDES, UAB hereby declares that GSM
alarm and management system ESIM264 is in compliance with the essential requirements and other relevant provisions of the Directive 1999/5/EC. The declaration of conformity is available at eldesalarms.com
ESIM264 USER MANUAL V2.4
EN
41
Made in the European Union
eldesalarms.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement