Eldes ESIM264 Installation guide

Eldes ESIM264 Installation guide
ESIM264
GSM ALARM AND MANAGEMENT SYSTEM
INSTALLATION MANUAL
COMPLIES WITH EN 50131-1 GRADE 2, CLASS II REQUIREMENTS
Installation Manual v3.3
Valid for ESIM264 v7.15.00 and up
Safety instructions
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
• GSM alarm and management system ESIM264 (also referenced as “alarm system”, “system“ or “device”) has radio transceiver operating
in GSM 850/900/1800/1900 bands.
• DO NOT use the system where it can be interfere with other devices and cause any potential danger.
• DO NOT use the system with medical devices.
• DO NOT use the system in hazardous environment.
• DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
• DO NOT attempt to personally repair the system.
• System label is on the bottom side of the device.
GSM alarm system ESIM264 is a device mounted in limited access areas. Any system repairs must be done only by qualified,
safety aware personnel.
The system must be powered by main 16-24V 50 Hz ~1.5A max or 18-24V
1,5A max DC power supply which must be
approved by LST EN 60950-1 standard and be easily accessible nearby the device. When connecting the power supply to the
system, switching the pole terminals places does not have any affect.
Any additional devices linked to the system ESIM264 (computer, sensors, relays etc.) must be approved by LST EN 60950-1
standard.
The power supply can be connected to AC mains only inside installation room
with automatic 2-pole circuit breaker capable of disconnecting circuit in the
event of short circuit or over-current condition. Open circuit breaker must have
a gap between connections of more than 3mm (0.12in) and the disconnection
current 5A.
Phase
Null
PE
AC/DC
AC 230V
50 Hz/DC 24V
ESIM264
USB cable
Mains power and backup battery must be disconnected before any installation or tuning work starts. The system installation
or maintenance must not be done during stormy conditions
Backup battery must be connected via the connection which in the case of breaking would result in disconnection of one of
battery pole terminals. Special care must be taken when connecting positive and negative battery terminals. Switching the
pole terminals places is NOT allowed.
In order to avoid fire or explosion hazards the system must be used only with approved backup battery.
The device is fully turned off by disconnecting 2-pole switch off device of the mains power and disconnecting backup battery
connector.
Fuse F1 type – Slow Blown 3A. Replacement fuses have to be exactly the same as indicated by the manufacturer.
If you use I security class computer for setting the parameters it must be connected to earth.
2
EN
MANUAL ELDES ESIM264 V3.3
Contents
1.
GENERAL INFORMATION..........................................................................................................................................................6
1.1. Functionality.......................................................................................................................................................................................................6
1.2. Compatible Device Overview............................................................................................................................................................................6
1.3. Default Parameters and Ways of Parameter Configuration........................................................................................................................6
2.
Technical Specifications........................................................................................................................................................10
2.1. Electrical and Mechanical Characteristics....................................................................................................................................................10
2.2. Main Unit, LED and Connector Functionality...............................................................................................................................................11
2.3. Wiring Diagrams...............................................................................................................................................................................................12
3.
INSTALLATION........................................................................................................................................................................18
4. GENERAL OPERATIONAL DESCRIPTION ................................................................................................................................22
5.
CONFIGURATION METHODS...................................................................................................................................................23
5.1. SMS Text Messages .........................................................................................................................................................................................23
5.2. EKB2 LCD Keypad.............................................................................................................................................................................................23
5.3. EKB3 LED Keypad.............................................................................................................................................................................................23
5.4. ELDES Configuration Tool Software............................................................................................................................................................. 24
6.
PASSWORDS............................................................................................................................................................................25
7.
SYSTEM LANGUAGE............................................................................................................................................................... 26
8. USER PHONE NUMBERS.........................................................................................................................................................27
8.1. System Control from any Phone Number.................................................................................................................................................... 28
9.
DATE AND TIME...................................................................................................................................................................... 29
10. USER CODES........................................................................................................................................................................... 30
11. iBUTTON KEYS........................................................................................................................................................................32
11.1. Adding and Removing iButton Keys..............................................................................................................................................................32
12. ARMING AND DISARMING...................................................................................................................................................... 34
12.1. Free of Charge Phone Call.............................................................................................................................................................................. 34
12.2. SMS Text Message...........................................................................................................................................................................................35
12.3. EKB2 Keypad and User Code..........................................................................................................................................................................35
12.4. EKB3 Keypad and User Code......................................................................................................................................................................... 36
12.5. iButton Key........................................................................................................................................................................................................37
12.6. EWK1/EWK2 Wireless Keyfob........................................................................................................................................................................37
12.7. Arm-Disarm by Zone....................................................................................................................................................................................... 38
12.8. Disabling and Enabling Arm/Disarm Notifications.................................................................................................................................... 39
13. EXIT AND ENTRY DELAY.........................................................................................................................................................41
14. ZONES..................................................................................................................................................................................... 43
14.1. Zone Numbering.............................................................................................................................................................................................. 43
14.2. Zone Expansion............................................................................................................................................................................................... 43
14.3. 6-Zone Mode.................................................................................................................................................................................................... 43
14.4. ATZ (Advanced Technology Zone) Mode..................................................................................................................................................... 44
14.5. Zone Type Definitions.................................................................................................................................................................................... 45
14.6. Zone Attributes............................................................................................................................................................................................... 46
14.7. Bypassing and Activating Zones.................................................................................................................................................................. 48
14.8. Zone Names..................................................................................................................................................................................................... 49
14.9. Disabling and Enabling Zones....................................................................................................................................................................... 50
15. STAY MODE..............................................................................................................................................................................51
16. TAMPERS.................................................................................................................................................................................52
16.1. Tamper Names..................................................................................................................................................................................................52
17. ALARM INDICATIONS AND NOTIFICATIONS FOR USER..........................................................................................................53
17.1. Enabling and Disabling Alarm Notifications................................................................................................................................................ 54
18. PROGRAMMABLE (PGM) OUTPUTS........................................................................................................................................57
18.1. PGM Output Numbering..................................................................................................................................................................................57
18.2. PGM Output Expansion....................................................................................................................................................................................57
18.3. PGM Output Names......................................................................................................................................................................................... 58
18.4. Turning PGM Outputs ON and OFF................................................................................................................................................................ 58
18.5. PGM Output Control by Event and Scheduler............................................................................................................................................. 60
18.6. Wireless PGM Output Type Definitions.........................................................................................................................................................61
MANUAL ELDES ESIM264 V3.3
EN
3
Contents
19. WIRELESS DEVICES................................................................................................................................................................ 62
19.1. Pairing, Removing and Replacing Wireless Device.................................................................................................................................... 62
19.2. Wireless Device Information......................................................................................................................................................................... 63
19.3. Wireless Signal Status Monitoring............................................................................................................................................................... 64
19.4. Disabling and Enabling Siren if Wireless Signal is Lost............................................................................................................................. 64
19.5. EWT1 - Wireless Transmitter-Receiver........................................................................................................................................................ 65
19.6. EWF1 - Wireless Smoke Detector................................................................................................................................................................. 66
20. WIRED SIREN/BELL ............................................................................................................................................................... 68
20.1. Bell Squawk...................................................................................................................................................................................................... 69
20.2. Indication by EWS2 - Wireless Outdoor Siren Indicators.......................................................................................................................... 69
20.3. Indication by EWS3 - Wireless Indoor Siren Indicators.............................................................................................................................. 70
21. BACKUP BATTERY, MAINS POWER STATUS MONITORING AND MEMORY............................................................................71
21.1. Backup Battery Status Monitoring................................................................................................................................................................71
21.2. Mains Power Status Monitoring.....................................................................................................................................................................72
21.3. Memory..............................................................................................................................................................................................................73
22. GSM CONNECTION STATUS MONITORING ..............................................................................................................................74
23. PARTITIONS............................................................................................................................................................................74
23.1. Zone Partition...................................................................................................................................................................................................74
23.2. User Phone Number Partition........................................................................................................................................................................74
23.3. Keypad Partition and Keypad Partition Switch............................................................................................................................................75
23.4. User Code Partition........................................................................................................................................................................................ 76
23.5. iButton Key Partition...................................................................................................................................................................................... 76
23.6. EWK1/EWK2 Wireless Keyfob Partition....................................................................................................................................................... 76
24. TEMPERATURE SENSOR.........................................................................................................................................................77
24.1. Adding, Removing and Replacing Temperature Sensors..........................................................................................................................77
24.2. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS.........................................................................................77
25. REMOTE LISTENING AND 2-WAY VOICE COMMUNICATION....................................................................................................79
26. SYSTEM INFORMATION. INFO SMS........................................................................................................................................ 80
26.1. Periodic Info SMS............................................................................................................................................................................................. 80
27. SYSTEM NOTIFICATIONS....................................................................................................................................................... 82
27.1. SMSC (Short Message Service Center) Phone Number............................................................................................................................. 84
28. EVENT LOG............................................................................................................................................................................. 85
29. INDICATION OF SYSTEM FAULTS........................................................................................................................................... 86
30. MONITORING STATION........................................................................................................................................................... 87
30.1. Data Messages – Events................................................................................................................................................................................. 88
30.2. Communication................................................................................................................................................................................................ 92
31. WIRED DEVICES.................................................................................................................................................................... 102
31.1. RS485 Interface............................................................................................................................................................................................ 102
31.2. 1-Wire Interface.............................................................................................................................................................................................108
31.3. Modules Interface.........................................................................................................................................................................................108
32. REMOTE SYSTEM RESTART.................................................................................................................................................. 111
33. TECHNICAL SUPPORT ..........................................................................................................................................................112
33.1. Troubleshooting.............................................................................................................................................................................................112
33.2. Restoring Default Parameters.....................................................................................................................................................................112
33.3. Updating the Firmware via USB Cable Locally..........................................................................................................................................112
33.4. Updating Firmware via GPRS Connection Remotely............................................................................................................................... 113
33.5. Frequently Asked Questions....................................................................................................................................................................... 113
34. RELATED PRODUCTS............................................................................................................................................................115
4
EN
MANUAL ELDES ESIM264 V3.3
TERMS OF USE
The following terms and conditions govern use of the ESIM264 device and contains important information on limitations regarding the
product’s use and function, as well as information on the limitations of the manufacturer’s liability. Please carefully read these terms and
conditions. For more information on your product, please visit eldesalarms.com
TECHNICAL SUPPORT
In order to ensure continuous and proper operation of the ESIM264 device and uninterrupted service, it is the responsibility of the User to
make sure that: (i) the product is properly installed, and (ii) there is constant internet or GSM connection and electrical supply (low battery
must be replaced in time).
If you experience difficulty during the installation or subsequent use of the system, you may contact ELDES, UAB distributor or dealer in
your country/region. For more information see eldesalarms.com
WARRANTY PROCEDURES
Warranty and out of warranty service should be obtained by contacting the system integrator/dealer/retailer/e-tailer or distributor where
the customer purchased the product. When requesting for service, the proof of purchase and the product serial number must be provided.
The return of the defective product should be strictly through the original route of purchase, and the customers shall pack the product
appropriately to prevent the returned product from suffering in the transportation.
MANUFACTURER WARRANTY
ELDES provides a limited warranty for its products only to the person or entity that originally purchased the product from ELDES or its
authorized distributor or retailer and only in case of defective workmanship and materials under normal use of the system for a period of
twenty four (24) months from the date of shipment by the ELDES, UAB (Warranty Period). Warranty obligations do not cover expandable
materials (power elements and/or batteries), holders and enclosures. The warranty remains valid only if the system is used as intended,
following all guidelines outlined in this manual and in accordance with the operating conditions specified. The warranty is void if the system
has been exposed to mechanical impact, chemicals, high humidity, fluids, corrosive and hazardous environments or force majeure factors.
If a hardware defect arises and a valid claim is received within the Warranty Period, at its own discretion, ELDES, UAB will either (a) repair a
hardware defect at no charge, using new or refurbished replacement parts, or (b) exchange the product with a product that is new or which
has been manufactured from new or serviceable used parts and is at least functionally equivalent to the original product, or (c) refund the
purchase price of the product.
LIMITED LIABILITY
The buyer must agree that the system will reduce the risk theft, burglary or other dangers but does not provide guarantee against such
events. ELDES, UAB will not assume any responsibility regarding personal or property, or revenue loss while using the system. ELDES, UAB
is not affiliated with any of the Internet providers, therefore, it shall not responsible for the quality of Internet service.
ELDES, UAB shall also assume no liability due to direct or indirect damage or loss, as well as unreceived income when using the system, including cases, when the damages arise due to the above mentioned risks, when due to breakdown or malfunction the user is not informed
in a timely manner about a risk which has arisen. In any case, the liability of ELDES, UAB, as much as it is allowed by the laws in force, shall
not exceed the price of acquisition of the product.
CONSUMER PROTECTION LAWS
FOR CONSUMERS WHO ARE COVERED BY CONSUMER PROTECTION LAWS OR REGULATIONS IN THEIR COUNTRY OF PURCHASE OR, IF DIFFERENT, THEIR COUNTRY OF RESIDENCE, THE BENEFITS CONFERRED BY THIS WARRANTY ARE IN ADDITION TO ALL RIGHTS AND
REMEDIES CONVEYED BY SUCH CONSUMER PROTECTION LAWS AND REGULATIONS. This warranty grants upon you specific legal
rights, and you may also have other rights that vary by country, state or province.
DISPOSAL AND RECYCLING INFORMATION
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that the
product must not be disposed of together with household waste. To prevent possible harm to human health and/or the environment, the product must be disposed on in an approved and environmentally safe recycling process. For further information
on how to dispose of this product correctly, contact the system supplier, or the local authority responsible for waste disposal
in your area.
Content of Pack
1. ESIM264..................................................... qty. 1
2. Microphone.................................................qty.1
3. SMA antenna............................................. qty. 1
4. Buzzer......................................................... qty. 1
5. Back-up battery connection wire.......... qty. 1
6. User manual............................................... qty. 1
7. Resistors 5,6kΩ.........................................qty. 6
8. Resistors 3,3kΩ.........................................qty. 6
9. Plastic standoffs.......................................qty. 4
About Installation Manual
This document describes detailed installation and operation process of alarm system ESIM264. It is very important to read the installation
manual before starting to use the system.
Copyright © “ELDES UAB”, 2016. All rights reserved
It is strictly forbidden to copy and distribute the information contained in this document or to pass thereof to a third
party without an a priori written authorization obtained from ELDES, UAB. ELDES, UAB reserves the right to update
or modify this document and/or related products without an a priori warning. ELDES, UAB hereby declares that GSM
alarm and management system ESIM264 is in compliance with the essential requirements and other relevant provisions of the Directive 1999/5/EC. The declaration of conformity is available at eldesalarms.com.
MANUAL ELDES ESIM264 V3.3
EN
5
1. GENERAL INFORMATION
1.1. Functionality
ESIM264 – micro-controller based alarm system for houses, cottages, country homes, garages and other buildings, also capable of managing electrical appliances via cellular GSM/GPRS network. It can also be used as Intercom system.
Examples of using the system:
• Property security.
• Alarm switch.
• Thermostat, heating and air-conditioner control, temperature monitoring.
• Lighting, garden watering, water pump and other electrical equipment control via SMS text messages.
• Remote listening to what is happening in the secured area.
• Main 230V power status with SMS text message.
• Two-way intercom device via GSM network.
1.2. Compatible Device Overview
Wired Devices
Description
Device
EKB2
LCD keypad
4*
Max. Connectible Devices
EKB3
LED keypad
4*
EA1
EA2
EPGM1
EPGM8
Audio output module with 3,5mm jack
Audio amplifier module 1W 8Ω
16 zone and 2 PGM output expansion module
8 PGM output expansion module
1**
1**
1
1**
Device
EWD2
EWK1****
EWK2****
EWS2
EWS3
EWF1
Wireless Devices
Description
Wireless magnetic door contact/shock sensor/flood sensor
Wireless keyfob with 4 buttons
Wireless keyfob with 4 buttons
Wireless outdoor siren
Wireless indoor siren
Wireless smoke detector
Max. Connectible Devices
16***
5****
5****
16***
16***
16***
* - A mixed combination of EKB2 and EKB3 keypads is supported. The combination can consist of up to 4 keypads in total.
** - Only 1 of these modules can be connected at a time if the module slots are implemented in ESIM264 unit.
*** - A mixed combination of wireless devices is supported. The combination can consist of up to 16 wireless devices in total.
**** - A mixed combination of EWK1 and EWK2 keyfobs is supported. The combination can consist of up to 5 keyfobs in total.
1.3. Default Parameters and Ways of Parameter Configuration
Main Settings
Parameter
Default Value
Depends on firmware version according to user‘s location
SMS Password
0000
User Code 1
1111
User Code 2... 30
N/A
Administrator Password
1470
Duress Password
N/A
SGS Password
N/A
User 1... 5 Phone Number
N/A
Allow Control from Any Phone Number Disabled
Date and Time
N/A
Exit Delay - Partition 1... 4
15 seconds
Info SMS Scheduler
Frequency (days) – 1; Time - 11
SMS and EKB2 Menu Language
Zones
Configurable by:
SMS
EKB2 EKB3
Configuration
Tool











































Configurable by:
Parameter
Default Value
Zone Name
Z1 - Zone 1; Z2 - Zone 2; Z3 - Zone 3; Z4 - Zone 4; Z5 
Zone 5; Z6 - Zone 6
6
EN
SMS
EKB2 EKB3
Configuration
Tool

MANUAL ELDES ESIM264 V3.3
Zones
Parameter
Default Value
Entry Delay
On-Board Zone Delay
EPGM1 Zone Delay
On-board Z1 Zone Type
On-board Z2... Z12 Zone Type
Keypad Zone Type
EPGM1 Zone Type
Wireless Zone Type
Virtual Zone Type
ATZ Mode
6-Zone Mode: Zone Connection Type
ATZ Mode: Zone Connection Type
On-board Zone Status
Keypad Zone Status
EPGM1 Zone Status
Wireless Zone Status
Virtual Zone Status
Stay attribute for individual zone
Alarm Count to Bypass
Arm-Disarm by Zone
Force atrribute for individual zone
15 seconds
800 milliseconds
800 milliseconds
Delay
Instant
Instant
Instant
Depends on the connected wireless device
Interior Follower
Disabled
Type 1
Type 4
Enabled
Disabled
Enabled
Depends on the connected wireless device
Disabled
Disabled
0
N/A
Disabled
Tamper 1, Tamper 2, Tamper 3, Tamper 4, Tamper 5,
Tamper 6 etc.
Enabled
Tamper Name
Chime
PGM Outputs
Parameter
PGM Output Name
Default Value
C1 – Controll1, C2 – Controll2, C3 – Controll3, C4 – Controll4 etc.
Disabled
Disabled
Disabled
Enabled
Depends on the connected wireless device
Disabled
PGM Output Status
EPGM8 PGM Output Status
EPGM1 PGM Output Status
Wireless PGM Output Status
Wireless PGM Output Type
PGM Output Control by Event 1... 16
PGM Output Control by Event Management
Scheduler 1... 16
Disabled
Turn ON/OFF PGM Output by Timer
Using Module EPGM8 Mode
Disabled
SMS
EKB2 EKB3









































Configuration
Tool






















Configurable by:
SMS
EKB2 EKB3






Configuration
Tool



















Alarm Duration and Siren
Parameter
Default Value
Alarm Duration
EWS2 LED
Bell Squawk
Activate Siren if Wireless Device is Lost
1 minute
Disabled
Disabled
Disabled
MANUAL ELDES ESIM264 V3.3
Configurable by:

Configurable by:
SMS
EKB2 EKB3









Configuration
Tool




EN
7
Parameter
Call in Case of Alarm
Send Alarm SMS to All Users Simultaneously
Send Arm/Disarm SMS to User 1... 5
Send Arm/Disarm SMS to All Selected
Users Simultaneously
Alarm Notifications and Arm/Disarm Notifications
Configurable by:
Default Value
SMS EKB2 EKB3
Enabled
Disabled

Enabled
Disabled

Mains power Status
Parameter
Default Value
Mains power Loss Delay
Mains power Restore Delay
30 seconds
120 seconds
Default Value
Temperature Sensor MIN
Temperature Sensor MAX
Allow adding New iButton Keys
0 °C
0 °C
Disabled
Parameter
General Alarm
System Disarmed
System Armed
Mains Power Loss Event Enabled
Mains Power Restore Event Enabled
Low Battery
Periodical Info
Tamper Alarm Event
Battery Failed
System Started
Wireless Signal Loss
Temperature Fallen
Temperature Exceeded
System Shutdown
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Default Value
Partition 0 Name
Partition 1 Name
Keypad 1... 4 Partition
Keypad Partition Switch
User Code 1... 30 Partition
User 1... 5 Phone Number Partition
iButton 1... 5 Partition
Zone Partition
PART0
PART1
PART0
Disabled
PART0
PART0
PART0
PART0
8
EN






EKB2 EKB3


Configurable by:
SMS
EKB2 EKB3









Configurable by:
SMS




Partitions
Parameter




System Notifications
Parameter


Configurable by:
SMS
Peripheral Devices
Parameter

Configuration
Tool

EKB2 EKB3



























Configurable by:
SMS
EKB2 EKB3
















Configuration
Tool


Configuration
Tool



Configuration
Tool














Configuration
Tool








MANUAL ELDES ESIM264 V3.3
Monitoring Station
Parameter
Default Value
MS Mode
Data Messages
Account (Alarm System ID)
Monitoring Station Phone Number 1... 3
(Voice Calls/SMS)
Attempts (Voice Calls/SMS)
Monitoring Station Phone Number 1...
5 (CSD)
Attempts (CSD)
Server IP Address (GPRS)
DNS1 Server IP Address (GPRS)
DNS2 Server IP Address (GPRS)
Protocol (GPRS)
Server Port (GPRS)
Local Port (GPRS)
APN (GPRS)
User (GPRS)
Password (GPRS)
Profile (GPRS)
GPRS Attempts
Delay Between Attempts (GPRS)
Unit ID (GPRS)
Test Period (GPRS)
Communication - Primary
Communication - Backup 1... 4
Protocol over GPRS
Disabled
All Enabled
9999
SMS
EKB2 EKB3







Configuration
Tool



N/A



3



N/A



3
0.0.0.0
N/A
N/A
UDP
20000
N/A
N/A
N/A
N/A
Profile1
3
600 seconds
0000
180 seconds
N/A
N/A
EGR100






















































Additional Parameters
Parameter
Default Value
Event Log
Microphone Gain
Speaker Level
GSM Signal Loss Indication - Delay
GSM Signal Loss Indication - Activate
Output
Show ARMED Status in Keypad (EKB2)
Enabled
12
85
180 seconds
MANUAL ELDES ESIM264 V3.3
Configurable by:
Configurable by:
SMS
EKB2 EKB3




Configuration
Tool




N/A

Disabled

EN
9
2. TECHNICAL SPECIFICATIONS
2.1. Electrical and Mechanical Characteristics
Electrical and Mechanical Characteristics
Mains power
Current in standby without external sensors and keypad
Recommended backup battery voltage, capacity
Recommended backup battery type
Backup battery charge current
GSM modem frequency
Cable type for GSM/GPRS antenna connection
Number of zones on-board
Nominal zone resistance
Number of PGM outputs on-board
On-board PGM output circuit
Maximum commuting on-board PGM output values
BELL: Siren output when activated
BELL: Maximum cable length for siren connection
BELL: Cable type for siren connection
AUX: Auxiliary equipment power supply voltage
BELL+AUX: Maximum accumulative current of auxiliary equipment and
siren
AUX: Maximum cable length for auxiliary equipment connection
AUX: Cable type for auxiliary equipment connection
BUZ: Maximum current of mini buzzer
BUZ: Power supply voltage of buzzer
BUZ: Cable type for mini buzzer connection
Supported temperature sensor model
Maximum supported number of temperature sensors
DATA: Maximum cable length for 1-Wire communication
DATA: Cable type for 1-Wire communication
Supported iButton key model
Maximum supported number of iButton keys
Maximum supported number of keypads
Y/G: Maximum cable length for RS485 communication
Y/G: Cable type for RS485 communication
MIC: Maximum cable length for microphone connection
MIC: Cable type for microphone connection
Wireless band
Wireless communication range
Maximum supported number of wireless devices
Event log size
Maximum supported number of zones
Maximum supported number of pgm outputs
Cable type for zone and pgm output connection
Communications
Supported protocols
Dimensions
Operating temperature range
Humidity
10
EN
16-24V 50 Hz ~1.5A max / 18-24V
Up to 80mA
12V; 1,3-7 Ah
Lead-Acid
Up to 900mA
850/900/1800/1900MHz
Shielded
6 (ATZ mode: 12)
5,6kΩ (ATZ Mode: 5,6kΩ and 3,3kΩ)
4
1R
OUT
1,5A max
Open Collector Output.
Output is pulled to COM
when turned ON.
4 x Voltage – 30V; current – 500mA.
Connected to COM
Up to 100m (328.08ft)
Unshielded
13,8V DC
1A
Up to 100m (328.08ft)
Unshielded
150mA
5V DC
Unshielded
Maxim®/Dallas® DS18S20, DS18B20
1
Up to 30m (98.43ft)
Unshielded
Maxim®/Dallas® DS1990A
5
4 x EKB2 / EKB3
Up to 100m (328.08ft)
Unshielded
Up to 2m (6.56ft)
Unshielded
ISM868 /ISM 915
Up to 30m (98.43ft) in premises;
up to 150m (492.13ft) in open areas
16
500 events
44
44
Unshielded
SMS, Voice calls, GPRS network, RS485, CSD
Ademco Contact ID, EGR100, Kronos, Cortex SMS
140x100x18mm (5.51x3.94x0.71in)
-20...+55°C (-4... 131°F)
0-90% RH @ 0... +40°C
(0-90% RH @ 32... 104°F) (non-condensing)
MANUAL ELDES ESIM264 V3.3
2.2. Main Unit, LED and Connector Functionality
DEF
OPEN
SIM CARD
G SM
MO DE M
3A
Slots for EA1, EA2 or EPGM8 module
Slots for EWT1 wireless module
C4
C3
1
ANTENNA
SMA
PRG
EWT1
USB
FUSE
MODULES
EWT1
STATUS
PWR
Z6
Z5
Z4
Z3
Z2
Z1
C1
C2
NETWORK
Main Unit Functionality
GSM MODEM
GSM network 850/900/1800/1900MHz
modem
SIM CARD
SIM card slot / holder
DEF
Pins for restoring default settings
USB
Mini USB port
FUSE F1
3A fuse
GSM/GPRS antenna SMA type connector
ANTENNA
MODULES
AK U +
AK U -
NETWORK indication
AC /DC
AC /DC
AUX+
AUXBELL+
BELL-
CO M
G
Y
C2
C1
BU Z +
BU Z MIC +
M IC +5V
DAT A
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
LED Functionality
NETWORK GSM network signal strength and status
C2, C1
PGM output C1 and C2 status. Steady ON = turned ON; OFF
= turned OFF
Z1
Zone Z1 state (ATZ mode: Z1 and Z7). Steady ON = violated; OFF = restored.
Z2
Zone Z2 state (ATZ mode: Z2 and Z8). Steady ON = violated; OFF = restored.
Z3
Zone Z3 state (ATZ mode: Z3 and Z9). Steady ON = violated; OFF = restored.
Z4
Zone Z4 state ( ATZ mode: Z4 and Z10). Steady ON = violated; OFF = restored.
Z5
Zone Z5 state (ATZ mode: Z5 and Z11). Steady ON = violated; OFF = restored.
Z6
Zone Z6 state (ATZ mode: Z6 and Z12). Steady ON = violated; OFF = restored.
PWR
Power supply status. Steady ON = power supply OK; OFF
= no power.
STATUS
Micro-controller status. Flashing = micro-controller OK;
OFF = micro-controller fault.
Description
OFF
No GSM signal - SIM card
missing; PIN code enabled
on SIM card; GSM antenna
disconnected or faulty; GSM
operator’s fault; GSM signal
unavailable in the are
Flashing every 3 sec.
Poor GSM signal strength
Flashing every 1 sec.
Medium GSM signal
strength
Flashing several times per sec. Good GSM signal strength
Steady ON
Excellent GSM signal
strength
Connector Functionality
Z1 - Z6
Security zones
COM
Common terminal for all zones
DATA
1-Wire® interface for iButton® key and temperature sensor connection
+5V
Temperature sensor power supply contact (+5V)
MICMicrophone negative terminal
MIC+
Microphone positive terminal
BUZMini buzzer negative terminal
BUZ+
Mini buzzer positive terminal
C1 - C4
PGM outputs
Y
RS485 interface CLOCK terminal (yellow wire)
G
RS485 interface DATA terminal (green wire)
COM
Common return terminal
BELLSiren negative terminal
BELL+
Siren positive terminal
AUXNegative power supply terminal for auxiliary equipment
AUX+
Positive power supply terminal for auxiliary equipment
AC/DC
Mains power terminal
AKU-
Backup battery negative terminal
AKU+
Backup battery positive terminal
MANUAL ELDES ESIM264 V3.3
EN
11
2.3. Wiring Diagrams
2.3.1.General Wiring
2
AKU+
AKU-
Backup Battery
12V 1.3-7Ah
AC /DC
AC /DC
AUX+
AUXBELL+
BELLCO M
G
Y
C2
C1
BUZ+
BUZMIC +
MIC +5V
DATA
CO M
Z6
CO M
Z5
Z4
CO M
Z3
Z2
CO M
Z1
Metal cabinet
PE terminal
Fuse 500 mA
~16-24V
~230V 50Hz
Z6
Z5
Z4
Z3
Z2
Z1
BUZ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
MIC
SIREN/BELL
EPGM1
500mA max.
iButton®
key reader
Relay
module
EKB3
Temperature sensor
EKB2
2.3.2. Zone Connection Types
Type 1
Example of 4-wire smoke detector wiring
EOL 5.6K
COM
Z
EOL 5.6K
COM
Z
EOL 5.6K
COM
Z
3.3K
TAMPER
NC
5,6 kΩ
NO
AUX+
Z
C1
COM
Z1
3
COM
5.6K
NC
3.3K
NC
6-Zone mode: Normally open contact
with 5,6KΩ end-ofline resistor.
NC
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
NC
GND
COM
NO
+Vin
Type 2
Example of magnetic door contact wiring
Z
EOL 5.6K
COM
NC
6-Zone mode: Normally closed contact
with 5,6KΩ end-ofline resistor
Z
EOL 5.6K
COM
Z
3.3K
TAMPER
5,6 kΩ
OM
COM
Z1
4
5.6K
3.3K
NC
COM
NC
NC
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
NC
COM
NC
Magnet
NOTE: Based on the example given, in the event of an alarm, the smoke detector could be reset by turning OFF and ON the PGM output
C1. For more details, please refer to 18.4. Turning PGM Outputs ON and OFF.
NOTE: The system does NOT support 2-wire smoke detectors.
12
EN
MANUAL ELDES ESIM264 V3.3
Type 3
Example of motion detector wiring
Z
EOL 5.6K
Z
EOL 5.6K
NC
TAMPER
5.6K 3.3K
NC
NC
5,6 kΩ
COM
COM
3,3 kΩ
GND
NC
+Vin
TAMP
Type 4
NC
Example of magnetic door contact (Z1) and glass break sensor (Z7) wiring
AUX+
AUX-
6
COM
Z1
Z
EOL 5.6K
NC
3.3K
TAMPER
NC
ATZ mode: 5,6KΩ
end-of-line resistor
and normally closed
contact with 3,3KΩ
end-of-line resistor
and normally closed
contact
COM
5.6K 3.3K
3,3 kΩ
COM
5.6K
5,6 kΩ
Z
NC
NC
NC
COM
Magnet
Type 5
COM
GND
NC
+Vin
Example of motion detector (Z1) and magnetic door contact (Z7) wiring
AUX+
AUX-
7
COM
Z1
C
COM
5.6K
3.3K
6-Zone mode: Tamper
and 5,6KΩ end-of-line
resistor and 3,3KΩ
end-of-line
resistor
with normally closed
contact.
C
C
Z
NC
3K
M
COM
3.3K
TAMPER
M
AUX+
AUX-
COM
Z1
5
M
Z
EOL 5.6K
TAMPER
COM
5.6K 3.3K
NC
NC
ATZ mode: Tamper,
5,6KΩ
end-of-line
resistor, 5,6KΩ endof-line resistor with
normally
closed
contact and 3,3KΩ
end-of-line resistor
with normally closed
contact.
5,6 kΩ
5,6 kΩ
3,3 kΩ
NC
COM
Magnet
COM
NC
TAMP
GND
+Vin
See also 14.3. 6-Zone Mode and 14.4. ATZ (Advanced Technology Zone) Mode.
MANUAL ELDES ESIM264 V3.3
EN
13
2.3.3. Siren
BELL+
BELL-
8
RED +
BELL+
BELLCOM
9
Self-contained siren
1 Connect negative GND siren wire to COM terminal.
2 Controlling BELL siren wire must be connected
to BELL- terminal.
GND
SIREN/BELL
1A max.
1 Connect positive siren wire (red) to BELL+ terminal.
2 Connect negative siren wire (black) to BELLterminal.
BLACK SIREN/BELL
1A max.
Piezo siren
BELL
3 Connect positive +12V siren wire to BELL+ terminal.
+12V
See also 20. WIRED SIREN/BELL.
NOTE: BELL- is the commuted terminal intended for siren control.
14
EN
MANUAL ELDES ESIM264 V3.3
2.3.4.
iButton Key Reader and Buzzer
Supported iButton key model: Maxim/Dallas
DS1990A
BUZ+
BUZ-
COM
DATA
10
-
The iButton key reader can be installed with buzzer
or separately. The buzzer is intended for audio indication of exit/entry delay countdown providing
short beeps.
+ BUZZER
1 Connect iButton key reader terminal wires to
1-Wire interface: COM and DATA terminals respectively.
2 Connect buzzer‘s negative terminal wire to BUZand positive terminal wire to BUZ+.
iButton
key reader
DS1990A
NOTE: The installation of buzzer is not necessary if EKB2/EKB3 keypad is used.
ATENTION: The cable length for connection to 1-Wire interface can be up to 30m (98.43ft) max.
2.3.5.
Temperature Sensor and iButton Key Reader
Supported iButton key model: Maxim/Dallas DS1990A
Supported temperature sensor model: Maxim/Dallas DS18S20, DS18B20
1 Depending on the model, connect temperature sensor GND/black wire, DATA/yellow
wire, +5V/red wire terminals to 1-Wire interface: COM, DATA and +5V terminals respectively.
2 When connecting iButton key reader in parallel to temperature sensor, connect iButton
key rea­der terminal wires to COM and DATA
terminals respectively.
GND
+5V
DATA
white
brown
DATA +5V
red
Temperature
sensor
DS18S20
+5V
Temperature sensor
DS18S20
GND
black
yellow
DATA
GND
+5V
DATA
COM
+5V
DATA
COM
+5V
DATA
COM
11
iButton
key reader
DS1990A
Digital thermometer
with 3m (9.84ft) wire
Vinson DS18B20
ATENTION: The cable length for connection to 1-Wire interface can be up to 30m
(98.43ft) max.
2.3.6. Relay Finder 40.61.9.12 with Terminal Socket 95.85.3 to PGM Output
Example of relay wiring for negative PGM output control
AUX+
C1
12
1 Wire up relay A1 terminal to PGM output Cx and
A2 terminal to AUX+.
2 In addition, connect the switching diode to re­
lay‘s A2 and A1 terminals.
COIL
A1
A2
RELAY
NOTE: We highly recommend using switching
diode model 1N4148 or similar.
MANUAL ELDES ESIM264 V3.3
EN
15
Example of relay wiring for positive PGM output control
1 Wire up relay A1 terminal to PGM output‘s Cx
terminal and A2 terminal to AUX+ and one of
the relay‘s switch contacts: NC or NO.
2 In addition, connect the switching diode to re­
lay‘s A2 and A1 terminals.
AUX+
C1
13
COIL
A1
A2
RELAY
NOTE: We highly recommend using switching
diode model 1N4148 or similar.
2.3.7. RS485
Serial Wiring Method
ESIM264
a
EKB2/EKB3
b
EKB2/EKB3
c
EKB2/EKB3
d
EKB2/EKB3
e
Max. cable length: a+b+c+d+e = up to 100m (328.08ft)
EPGM1
NOTE: If necessary, the RS485 devices can be powered from an external 12-14V DC power supply instead of AUX+ and AUX- terminals
ATTENTION: The cable length must not exceed 100m (328.08ft) in total.
ATTENTION: When wiring more than 1 keypad, please ensure that the set address of each keypad is different.
NOTE: You may connect only 1 EKB2/EKB3 keypad or a mixed combination of EKB2 and EKB3 keypads. The combination can consist of
up to 4 keypads in total.
For more details on RS485 device installation, please refer to 32.1. RS485 Interface
16
EN
MANUAL ELDES ESIM264 V3.3
Parallel Wiring Method
ESIM264
Max. cable length: up to 100m (328.08ft)
EPGM1
EKB2/EKB3
EKB2/EKB3
EKB2/EKB3
EKB2/EKB3
NOTE: If necessary, the RS485 devices can be powered from an external 12-14V DC power supply instead of AUX+ and AUX- terminals
ATTENTION: The cable between ESIM264 and each RS485 device must be of the same length and can NOT exceed 100m (328.08ft).
ATTENTION: When wiring more than 1 keypad, please ensure that the set address of each keypad is different.
NOTE: You may connect only 1 EKB2/EKB3 keypad or a mixed combination of EKB2 and EKB3 keypads. The combination can consist of
up to 4 keypads in total.
For more details on RS485 device installation, please refer to 32.1. RS485 Interface
MANUAL ELDES ESIM264 V3.3
EN
17
3. INSTALLATION
• The system can be installed in a metal or non-flammable cabinet only. For a convenient installation, ME1 metal cabinet is highly recommended. The metal cabinet must always be grounded as well as ESIM264 system’s PCB by connecting one of the COM terminals to the
PE contact of the metal cabinet.
• For the connection of 230V transformer, use 3x0.75 mm2 (3x0.03in2) 1 thread double isolated cable. 230V power supply cables must
not be grouped with low voltage cable group.
• For the connection of auxiliary and BELL outputs, use 2x0.75 mm2 (2x0.03in2) 1 thread unshielded cable of up to 100m (328.08ft)
length.
• For the connection of zone/PGM output connectors, use 0.50 mm2 (0.02in2) 1 thread unshielded cable of up to 100m (328.08ft) length.
System Installation in ME1 Metal Cabinet
1.
ME1 metal cabinet components
14
to AC main power line
Null
blue
PE
Phase
brown
Fuse 1A
Transformer
(Primary voltage: 230V AC,
Secondary voltage: 17V
2,35A)
Tamper switch
to AC/DC terminals
of ESIM264 system
2.
Insert the plastic standoffs into the appropriate mounting points and fix the board of ESIM264 on the holders as indicated below.
15
mounting points
18
EN
MANUAL ELDES ESIM264 V3.3
16
7
3.
If EPGM1 module is to be installed, please install it in the first place and ESIM264 alarm system afterwards. EPGM1 must be mounted on
the shorter plastic standoffs, while ESIM264 – on the longer ones. The mounting points of EPGM1 module are indicated below.
17
mounting
points*
* The standard ME1 metal cabinet does NOT contain the mounting points intended for EPGM1 module mounting, therefore it will be necessary to drill out the mounting points by yourself.
MANUAL ELDES ESIM264 V3.3
EN
19
19
18
7
4. Wire up the accessories, such as keypads, zone and PGM output expansion modules, temperature sensor according to the wiring diagrams. Install the buzzer closer to iButton key reader in order to hear the exit delay countdown (see 2.3 Wiring Diagrams for more
details).
5.
Disable the PIN code of the SIM card by inserting it into a mobile phone and following the proper menu steps. Ensure that the addition
al services, such as voice mail, call forwarding, report on missed/busy calls are disabled on the SIM card. For more details on how
to disable these services, please contact your GSM operator.
6.
Once the PIN code is disabled, place the SIM card into the SIM CARD slot of the alarm system.
20
22
21
OPEN
24
23
OPEN
7.
Connect the GSM/GPRS and wireless antennas and follow the recommendations for the installation:
Never install in the
following locations:
25
GSM/
GPRS
and/or
wireless
antenna
• inside the metal cabinet
26
Recommended installation:
20cm (7.87in)
or more
• keep the distance of at least
20cm (0.66ft) or more.
• keep the distance of at least
20cm (7.87in) or more.
GSM/GPRS
antenna
Wireless
antenna
8. If one or more wireless devices are to be paired, follow the recommendations for the installation to achieve the strongest wireless signal:
20
EN
MANUAL ELDES ESIM264 V3.3
Never install in the
following locations:
27
0.5 m to 30 m
(1.64 to 98.43ft)
inside the building
• inside the metal cabinet
Wireless
device
Recommended installation:
28
• keep the distance of at least
20cm (7.87in) or more.
0.5 m to 150 m
(1.64 to 492.13ft)
in open areas
Wireless
device
Wireless
antenna
• face the front side of the
wireless device towards the
antenna
• keep the distance: 0,5 to 30m
(1.64 to 98.43ft) inside the
building, 0,5 to 150m (1.64 to
492.13ft) in open areas
For more details on how to install the wireless devices, please refer to RADIO SYSTEM INSTALLATION AND SIGNAL PENETRATION
manual located at eldesalarms.com
9. Power up the system.
10. The system starts up in less than a minute. Indicator STATUS should be flashing indicating successful micro-controller operation.
11. The illuminated indicator NETWORK indicates that the system successfully registered to GSM network. To find the strongest GSM signal, place the GSM/GPRS antenna and follow the indications provided by NETWORK indicator (see 2.3. Main Unit, LED and Connector
Functi­onality).
12. Change the default SMS password (see 6. PASSWORDS for more details).
13. Set the phone number for User 1 (see 8. USER PHONE NUMBERS for more details).
14. Set system date and time (see 9. DATE AND TIME for more details).
15. Once the system is fully configured, it is ready for use. However, if you fail to receive an SMS reply from the system, please check the
SMSC (Short Message Service Center) phone number. For more details regarding the SMS centre phone number, please refer to 27.1.
SMSC (Short Message Service Center) Phone Number.
ATTENTION: The system is NOT compatible with pure 3G SIM cards. Only 2G/GSM SIM cards and 3G SIM cards with 2G/GSM profile enabled
are supported. For more details, please contact your GSM operator.
NOTE: The installation of iButton key reader, EKB2/EKB3 keypad, EWK1/EWK2 wireless keyfob is not mandatory. However, it is recommended to have those devices installed as an emergency switch in case your mobile phone is switched off or missing.
NOTE: For maximum system reliability we recommend you do NOT use a Pay As You Go SIM card. Otherwise, in the event of insufficient
credit balance on the SIM card, the system would fail to make a phone call or send messages.
NOTE: We advise you to choose the same GSM SIM provider for your system as for your mobile phone. This will ensure the fastest, most
reliable SMS text message delivery service and phone call connection.
NOTE: Even though alarm system ESIM264 installation process is not too complicated, we still recommend to perform it by a person
with basic knowledge in electrical engineering and electronics to avoid any system damage.
MANUAL ELDES ESIM264 V3.3
EN
21
4. GENERAL OPERATIONAL DESCRIPTION
When the system is being armed, it will initiate the exit delay countdown intended for the user to leave the secured area. During the
countdown period the buzzer will emit short beeps and/or LED indicator will flash. By default, exit delay duration is 15 seconds. After the
countdown is complete, the system will become armed and lock the configuration by keypad possibility. In case the user does not leave the
secured area before the countdown is complete, the system will arm in Stay mode if at least 1 zone has Stay attribute enabled. By default,
if there is at least 1 violated zone or tamper, the user will not be able to arm the system until the violated zone or tamper is restored. In case
it is required to arm the alarm system despite the violated zone presence, the violated zone can be bypassed or Force attribute enabled.
After the system is armed and if a zone (depending on type) or tamper is violated, the system will cause an alarm lasting for 1 minute (by
default), During the alarm, the siren/bell will provide an alarm sound along with the buzzers of the keypads. By default, the system will also
makes a phone call and send an SMS text message containing the violated zone or tamper number to a listed user and indicate the violated
zone or tamper number on the keypad. If another zone or tamper is violated or the same one is restored and violated again during the alarm,
the system will act as mentioned previously, but will not extend the alarm time.
After the user enters the secured area, the system will initiate the entry delay countdown intended for system disarming. During the countdown period, the buzzer will emit a steady beep and/or LED indicator will light ON. By default, entry delay duration is 15 seconds. After the
user successfully performs the disarming process, the system will unlock the keypads. If the user does not disarm the system in time, the
alarm system will cause an instant alarm.
NOTE: The alarm will be caused even if a tamper is violated while the system is disarmed.
For more details, please refer to 12. ARMING AND DISARMING.
22
EN
MANUAL ELDES ESIM264 V3.3
5. CONFIGURATION METHODS
!!! In this installation manual the underscore character ”_” represents one space character. Every underscore character must
be replaced by a single space character. There must be no spaces or other unnecessary characters at the beginning and at
the end of the SMS text message.
5.1. SMS Text Messages
SMS
In order to configure and control the system by SMS text message, send the text command to the ESIM264 system phone
number from one of the listed user phone numbers. The structure of SMS text message consists of 4-digit SMS password
(the default SMS password is 0000 – four zeros), the parameter and value. For some parameters the value does not apply e. g.
STATUS. The variables are indicated in lower-case letters, while a valid parameter value range is indicated in
5.2. EKB2 LCD Keypad
EKB2
The system configuration and control by EKB2 keypad is carried out by navigating throughout the menu section list displayed
on LCD screen. To navigate in the menu path, touch ↓, ↑ keys to select the desired menu section and touch OK key to open the
selected section. To enter a required value, use 0... 9 keys and touch OK key for confirmation or cancel/go one menu section
back by touching ← key. The value can be typed in directly by touching 0... 9 keys while highlighting the desired menu section. EKB2 menu type is “circle”, therefore when the last section in the menu list is selected, you will be brought back to the
beginning of the list after touching the ↓ key. In this installation manual, the menu path is based on the EKB2 menu tree by
starting at home screen view (see 31.1.1.6. EKB2 Menu Tree ). The variables are provided in lower-case letters, while a valid
parameter value range is provided in brackets.
NOTE: Menu section CONFIGURATION is secured with administrator password. The default administrator password is 1470.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the menu section
CONFIGURATION is opened. The inactive EKB2 keypads will display
icon and CONFIGURATION MODE message.
NOTE: The keypad will automatically exit the menu section CONFIGURATION and return to home screen view if 1 minute after the last
key-touch expires.
5.3. EKB3 LED Keypad
EKB3
The system configuration and control by EKB3 keypad is carried out by activating the Configuration mode using the administrator password (by default – administrator password is 1470) and entering a valid configuration command using the number
keys 0
key for confirmation and * key to cancel the characters that are being entered. Alternatively, the user
9 ,
can wait for 10 seconds until the keypad buzzer will provide a long beep indicating that the entered characters have been
cancelled. When typing in the characters, the indication of each pressed key is provided by short beep of keypad buzzer and
red indicators when the number keys 0
,
and
keys as well.
9 are being pressed. Some commands require
The structure of a standard configuration command is a combination of digits. The commands, which do not require the Configuration mode being activated, are noted. The variables are provided in lower-case letters, while a valid parameter value
range is provided in brackets.
NOTE: If you were not willing to activate Configuration mode, but accidentally typed in the * as the first character, please press * key again
or wait for 10 seconds until the keypad buzzer will provide a long beep indicating that the typed in characters have been cancelled.
Activate/deactivate
Configuration mode
EKB3
Enter administrator password:
* aaaa #
Value: aaaa – 4-digit administrator password.
Example: *1470#
The following table provides a list of EKB3 indications, which are relevant during Configuration mode.
Indication
Indicator
flashing
Indicator
flashing
1 long beep
3 short beeps
Description
Configuration mode activated successfully.
Valid parameter entered and awaiting for valid value to be entered.
Non-existing command or invalid parameter value entered.
Command entered successfully.
NOTE: The system can be configured using only one keypad at a time. Other connected keypads will be inactive while the Configuration mode is activated.
NOTE: Configuration mode will automatically deactivate if 1 minute after the last key-stroke expires.
MANUAL ELDES ESIM264 V3.3
EN
23
5.4. ELDES Configuration Tool Software
Config
Tool
Software ELDES Configuration Tool is intended for ESIM264 alarm system configuration via USB port locally or via GPRS connection remotely. This software simplifies system configuration process by allowing to use a personal computer in the process.
Before starting to use ELDES Configuration Tool software, please read the user guide provided in the software’s HELP section.
ELDES Configuration Tool is freeware and can be downloaded from at: eldesalarms.com
5.4.1. Remote Connection
ATTENTION: The system will NOT send any data to monitoring station while configuring the system remotely via GPRS network. However,
during the configuration session, the data messages are queued up and transmitted to the monitoring station after the configuration session
is over.
ATTENTION: When the Configuration mode is activated by EKB3 keypad or menu section CONFIGURATION is opened by EKB2 keypad, remote system configuration will be disabled.
NOTE: The keypads will be inactive when the system is being configured remotely.
ELDES Configuration Tool software provides remote system configuration ability via Internet using one of the following methods:
• ELDES proxy server (recommended). The connection can be established on the system via GPRS network.
• Running TCP/IP server on ELDES Configuration Tool (advanced). The connection can be established on the system via GPRS network.
In order to start using the remote configuration feature, please run the step-by-step wizard and follow the steps provided in the start page
of ELDES Configuration Tool software. Please, note that it will be necessary to send an SMS text message to the system’s phone number
in order to initiate the remote connection. By following the steps you will be instructed on what text must be sent to the system’s phone
number in such case.
5.4.2. Ending the Remote Connection Session
Terminate the
connection
with server
After the system configuration is complete, use one of the following methods to end the configuration
process:
• Click Disconnect or Stop button and close ELDES Configuration Tool software.
•
The session will automatically expire in 20 minutes. Before the last 5 minutes, the software will offer
the user to extend the session for another 20 minutes.
•
Alternatively, the connection with the server can be terminated at any time by sending an SMS text
message.
SMS
SMS text message content:
ssss_ENDCONFIG
Value: ssss – 4-digit SMS password.
Example: 1111_ENDCONFIG
Once the session is expired or terminated, the system will reply with an SMS text message confirming the end of the session.
24
EN
MANUAL ELDES ESIM264 V3.3
6. PASSWORDS
For security reasons, the system uses the following types of passwords:
•
SMS password – 4-digit password used for system arming/disarming and configuration by SMS text messages. By default, SMS password is 0000, which MUST be changed!
•
Administrator password – 4-digit password used for Configuration mode activation by keypad and logging in to ELDES Configuration
Tool software. By default, Administrator password is 1470, which is highly recommended to change.
Set SMS password
SMS
EKB2
Set Administrator
password
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS
→ OK → SMS PASSWORD → OK → ssss → OK
Value: aaaa – 4-digit administrator password; ssss – 4-digit new SMS password; range –
[0001... 9999].
EKB3
Enter parameter 14 and new SMS password:
14 ssss #
Value: ssss – 4-digit new SMS password; range – [0001... 9999].
Example: 141111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → 1470 → OK → PRIMARY SETTINGS → OK → PASSWORDS
→ OK → ADMIN PASSWORD → OK → aaaa → OK
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
SMS text message content:
wwww_PSW_ssss
Value: wwww – 4-digit default SMS password; ssss – 4-digit new SMS password; range –
[0001... 9999].
Example: 0000_PSW_1111
Enter parameter 16 and new administrator password:
16 aaaa #
Value: aaaa – 4-digit new administrator password; range – [0000... 9999].
Example: 162538#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
25
7. SYSTEM LANGUAGE
The system comes equipped with 2 languages for communication with the user by SMS text messages and a single language for EKB2
keypad menu display. The default EKB2 menu language depends on ESIM264 firmware, which is based on the user’s location, while one of
languages for communication by SMS text messages is always English.
List of currently available system languages (firmwares):
• Czech
• English
• Estonian
• Finnish
• French
• Greek
• Hungarian
• Icelandic
• Italian
• Latvian
• Lithuanian
• Norwegian
• Portuguese
• Romanian
• Russian
• Slovak
• Spanish
• Swedish
To set a different SMS language, please refer to the following configuration methods.
Set SMS language
SMS
EKB2
SMS text message content:
ll
Value: ll - SMS language, range - [CZ - Czech, EN - English, EE - Estonian, FI - Finnish, GR Greek, HU - Hungarian, IC - Icelandic, IT - Italian, LV - Latvian, LT - Lithuanian, NO - Norwegian,
PT - Portuguese, RO - Romanian, RU - Russian, SK - Slovak, SP - Spanish, SW - Swedish].
Example: SK
Menu path:
OK → CONFIGURATION → OK → 1470 → OK → PRIMARY SETTINGS → OK → SMS LANGUAGE
→ OK → sms-lang → OK
Value: sms-lang – SMS language.
NOTE: To obtain a firmware that features a different SMS and EKB2 menu language, please contact your local dealer.
NOTE: To change the language once the system has already been configured, you need to reset the device to the default configuration. For
more details on how to do this, please refer to 35.2. Restoring Default Parameters.
26
EN
MANUAL ELDES ESIM264 V3.3
8. USER PHONE NUMBERS
The system supports up to 5 user phone numbers identified as User 1 through 5. When the phone number is set, the user will be able to
arm/disarm the system by SMS text messages and free of charge phone calls (see 12.1. Free of Charge Phone Call and 12.2. SMS Text
Message) as well as to configure the system by SMS text messages. User phone numbers are also used to receive alarm phone calls and
SMS text messages from the system (see 17. ALARM INDICATIONS AND NOTIFICATIONS FOR USER).
By default, the system accepts incoming calls and SMS text messages from any phone number. Once a user phone number is listed, the
system ignores any incoming calls and SMS text messages from a non-listed phone number as well as it rejects the SMS text messages
containing wrong SMS password even from a listed user phone number (see 8.1. System Control from any Phone Number). To set User
1 phone number is mandatory, while the other 4 are optional. The supported phone number format is the following:
•
International (w/o plus) – The phone numbers must be entered starting with an international country code in the following format: [international code][area code][local number], example for UK: 4417091111111.
Set user phone
number
SMS
EKB2
EKB3
Config
Tool
View user phone
number
Delete user phone
number
MANUAL ELDES ESIM264 V3.3
SMS text message content:
ssss_NRup:ttteeellnnuumm
Value: ssss – 4-digit SMS password; up – user phone number slot, range – [1... 5]; ttteeelln­
nuumm – up to 15 digits user phone number.
Example: 1111_NR1:44170911XXXX1
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS SETTINGS
→ OK → USERS → OK → USER 1... 5 → OK → PHONE NUMBER → OK → ttteeellnnuumm → OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits user phone
number.
Enter parameter 17, user phone number slot and phone number:
17 up ttteeellnnuumm #
Value: up – user phone number slot, range – [01... 05]; ttteeellnnuumm – up to 15 digits user
phone number.
Example: 170144170911XXXX1#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_HELPNR
Value: ssss – 4-digit SMS password.
Example: 1111_HELPNR
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → PHONE NUMBER → PHONE NUMBER
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_NRup:DEL
Value: ssss – 4-digit SMS password; up – user phone number slot, range – [2... 5].
Example: 1111_NR2:DEL
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 2... 5 → OK → PHONE NUMBER → OK → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
27
ATTENTION: NEVER add a phone number of the device’s SIM card as a user phone number!
ATTENTION: Once User 1 phone number is set, it will be restricted to modify it only.
NOTE: Multiple user phone numbers can be set by a single SMS text message, Example: 1111_NR1:44170911XXXX1_
NR2:44170911XXXX2_ NR5:44170911XXXX3
NOTE: Multiple user phone numbers can be deleted by a single SMS text message, Example: 1111_NR2:DEL_NR3:DEL
8.1. System Control from any Phone Number
By default, once a user phone number is listed, the system ignores any incoming calls and SMS text messages from a non-listed phone
number as well as it rejects the SMS text messages containing wrong SMS password even from a listed user phone number. To permit/deny
system arming/disarming by phone call and SMS text message that contain a valid SMS password, configuration by SMS text message that
contain a valid SMS password from any phone number, please refer to the following configuration methods.
Enable system control
from any phone
number
Disable system
control from any
phone number
28
EN
SMS
SMS text message content:
ssss_STR:ON
Value: ssss – 4-digit SMS password.
Example: 1111_STR:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CTRL FROM ANY NUM → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 12 and parameter status value:
12 1 #
Example: 121#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_STR:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_STR:OFF
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CTRL FROM ANY NUM → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 12 and parameter status value:
12 0 #
Example: 120#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
9. DATE AND TIME
The system comes equipped with internal real-time clock (RTC) that keeps track of the current date and time. Once the system is up and
running, the user must set the correct date and time, otherwise the system will not operate properly. After shutting down and starting up
the system, the date and time must be set again.
Set date and time
SMS
EKB2
EKB3
Config
Tool
SMS text message content:
ssss_yyyy.mm.dd_hr:mn
Value: ssss – 4-digit SMS password; yyyy – year; mm – month, range – [01... 12]; dd – day,
range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Example: 1111_2015.03.16_14:33
Menu path:
a) OK → DATE/TIME SETTINGS → OK → yyyy-mm-dd hr:mn → OK
b) OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → DATE/TIME
SETTINGS → OK → yyyy-mm-dd hr:mn → OK
Value: aaaa – 4-digit administrator password; yyyy – year; mm – month, range – [01... 12];
dd – day, range – [01... 31]; hr – hours, range – [00... 23]; mn – minutes, range – [00... 59].
Enter parameter 66, date and time:
66 yyyy mm dd hr mn#
Value: yyyy – year; mm – month, range – [01... 12]; dd – day, range – [01... 31]; hr – hours,
range – [00... 23]; mn – minutes, range – [00... 59].
Example: 66201505291235#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: When the system is connected to the monitoring station via GPRS network connection, the date and time will be automatically
synchronized with the monitoring station upon the system startup.
MANUAL ELDES ESIM264 V3.3
EN
29
10. USER CODES
The system supports up to 30 numeric user codes, identified as User Code 1 through 30, allowing to carry out system arming/disarming by
the keypad. By default, User Code 1 is listed as 1111 and assigned to Partition 0. For more details regarding user code partition, please refer
to 23.4. User Code Partition.
Set user code
EKB2
EKB3
Delete user code
Replace user code
Menu path:
User code 1... 16: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (1-16) → OK → USER
PASSWORD 1... 16 → OK → PASSWORDS → OK → uuuu → OK
User code 17... 30: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (17-30) → OK → USER
PASSWORD 17... 30 → OK → PASSWORDS → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code, range – [0000...
9999].
Enter parameter 15, user code slot and user code:
15 us uuuu #
Value: us – user code slot, range – [01... 30]; uuuu – 4-digit user code; range – [0000... 9999].
Example: 15021111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → REMOVE PASSWORD → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code.
EKB3
Enter parameter 65 and user code:
65 uuuu #
Value: uuuu – 4-digit user code.
Example: 651111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
Config
Tool
Menu path:
User code 1... 16: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (1-16) → OK → USER
PASSWORD 1... 16 → OK → PASSWORD → OK → uuuu → OK
User code 17... 30: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (17-30) → OK → USER
PASSWORD 17... 30 → OK → PASSWORD → OK → uuuu → OK
Value: aaaa – 4-digit administrator password; uuuu – 4-digit user code, range – [0000...
9999].
Enter parameter 63, existing user code and new user code:
63 vvvv uuuu #
Value: vvvv – 4-digit existing user code; uuuu – 4-digit new user code, range – [0000...
9999].
Example: 6311113254#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system does not allow to set a duplicate password
30
EN
MANUAL ELDES ESIM264 V3.3
One of the user codes ranging from User Code 1 through 10 can be set as SGS (Security Guard Service) code, which is used as a checkpoint
by a security service guard upon his/her visit in the secured location. When used, a data message, containing a certain event code, will be
delivered to the monitoring station. However, NO system arming or disarming will be carried out after entering the SGS password.
Set SGS code
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → SGS PASSWORD → OK → N/A / us → OK
Value: aaaa – 4-digit administrator password; N/A – SGS code not in use; us – user code
slot, range – [1... 10].
EKB3
Enter parameter 74 and user code slot:
74 us #
Value: us – user code slot, range – [01... 10].
Example: 7403#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
The Duress code is used when system arming or disarming is demanded by force. When used, the system will arm/disarm as well as it will silently transmit an alert to the monitoring station. Only one of the user code ranging from User Code 1 through 10 can be set as Duress code.
Set Duress code
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → PASSWORDS →
OK → USER PASSWORDS → OK → DURESS PASSWORD → OK → N/A / us → OK
Value: aaaa – 4-digit administrator password; N/A – Duress password not in use; us – user
code slot, range – [1... 10].
EKB3
Enter parameter 73 and user code slot:
73 us #
Value: us – user code slot, range – [01... 10].
Example: 7309#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
31
11. iBUTTON KEYS
An iButton key is a unique 64-bit ID code containing chip enclosed in a stainless steel tab usually implemented in a small plastic holder.
ESIM264 system supports up to 5 iButton keys each holding a unique identity code (ID), which is used for system arming and disarming.
11.1. Adding and Removing iButton Keys
NOTE: iButton Key 1 can be added without Allow Adding New iButton Keys mode being enabled.
To add an iButton key to the system, do the following:
a) Disarm the system in all partitions (see 12. ARMING AND DISARMING).
b) Enable Allow Adding New iButton Keys mode.
c)
T ouch the key to the iButton key reader when the system is disarmed (see picture below).
29
d) The successfully added iButton key will be indicated by short beeps emitted by the system’s buzzer.
e) Add as many iButton keys as necessary – touch one key after another to the reader – until the number of 5 keys is reached.
Enable Allow Adding
New iButton Keys
mode
32
EN
SMS
SMS text message content:
ssss_IBPROG:ON
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → NEW IBUTTON →
OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 18 and parameter status value:
18 0 #
Example: 180#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
When adding of iButton keys is complete, please disable Allow Adding New iButton Keys mode.
Disable Allow Adding
New iButton Keys
mode
SMS
SMS text message content:
ssss_IBPROG:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_IBPROG:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → NEW IBUTTON →
OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 18 and parameter status value:
18 1 #
Example: 181#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To view the ID of the added iButton keys, please refer to the following configuration methods.
View iButton key ID
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → IBUTTON 1... 5 → OK
→ ID
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If the iButton key is lost or stolen, due to security reasons it is highly recommended to remove it from the system.
Remove individual
iButton key from the
system
Remove all iButton
keys from the system
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → IBUTTON 1... 5 → OK
→ REMOVE → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_RESETIB
Value: ssss – 4-digit SMS password.
Example: 1111_RESETIB
EN
33
12. ARMING AND DISARMING
The system features the following methods to carry out arming and disarming process:
•
Free of charge phone call.
•
SMS text message.
•
EKB2/EKB3 keypad and user code.
•
iButton key.
•
EWK1/EWK2 wireless keyfob.
•
Arm-Disarm by Zone.
•
EGR100 middle-ware.
The system arms/disarms the partitions that the listed user phone number, EKB2/EKB3 keypad and user code, iButton key, EWK1/EWK2 wireless keyfob or zone, set up for Arm-Disarm by Zone method, are assigned to. For example, if User 1 phone number is assigned to Partition 0,
the user will be able to arm/disarm Partition 0 by a single phone call to the system (see 23. PARTITIONS).
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message. For more details on SMS
text message regarding system arming/disarming and how to manage it, please refer to 12.9. Disabling and Enabling Arm/Disarm
Notifications.
The system will allow to arm the system if the following system faults are present (see 29. INDICATION OF SYSTEM FAULTS):
• Mains power is lost.
•
Low battery.
•
Battery failed.
•
Date/time not set.
•
GSM connection failed.
In case of violated zone/tamper presence when attempting to arm the system by free of charge phone call, SMS text message, iButton key
and Arm-Disarm by Zone method, the system will reply with SMS text message containing violated zone/tamper number. Due to security reasons it is highly recommended to restore the violated zone/tamper before arming the system. For more details on how to arm the
system regardless of the violated zone presence, please refer to 14.6. Zone Attributes and 14.7. Bypassing and Activating Zones.
Once a user phone number is listed, the system ignores any incoming calls and SMS text messages from a non-listed phone number as well
as it rejects the SMS text messages containing wrong SMS password even from a listed user phone number. For more details regarding
arming/disarming the system from a non-listed phone number, please refer to 8.1. System Control from any Phone Number.
12.1. Free of Charge Phone Call
To arm and disarm the system, dial the system‘s phone number from any of 5 available user phone numbers (see 8. USER
PHONE NUMBERS for user phone number management). The phone call is free charge as the system rejects it and carries out
arming/disarming procedure afterwards. When arming – the system rejects the phone call after 2 rings, when disarming – the
system rejects the phone call immediately. If there is more than one listed user dialling to the system at the same time, the
system will accept the incoming call from the user who was the first to dial while other user (-s) will be ignored.
The system will arm/disarm the partition corresponding to the one that the user phone number is assigned to. For more details on how to
set user phone number partition, please refer to 23.2. User Phone Number Partition.
30
CALL
User
34
EN
ESIM264
MANUAL ELDES ESIM264 V3.3
12.2. SMS Text Message
SMS
To arm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user
phone numbers (see 8. USER PHONE NUMBERS for user phone number management). When the SMS text message for arming is sent to the system’s phone number, the system will proceed as follows:
•
•
Non-partitioned system:
•
If ready (no violated zone/tamper), the system will arm.
•
If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number.
Partitioned system:
•
If all partitions are disarmed ready (no violated zone/tamper), the system will arm them.
•
If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and skip the unready one (-s). The system will then send an SMS text message, containing a list of violated
zones/tampers, to user phone number that the system arming was initiated from.
•
If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions
and skip the armed ones.
Arm the system
SMS text message content:
ssss_ARMp or ssss_ARMp,p
Value: ssss – 4-digit SMS password; p – partition number, range – [1 – Partition 0, 2 – Partition 1].
Example: 1111_ARM1
31
SMS
User
ESIM264
To disarm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user phone numbers:
Disarm the system
SMS text message content:
ssss_DISARMp or ssss_DISARMp,p
Value: ssss – 4-digit SMS password; p – partition number, range - [1 – Partition 0, 2 – Partition 1].
Example: 1111_DISARM1,2
32
SMS
User
ESIM264
Regardless of the partition a user phone number is assigned to, the user will be able arm/disarm by SMS text message method either Partition 0 , Partition 1 or both partitions simultaneously.
12.3. EKB2 Keypad and User Code
EKB2
READY message displayed in the home screen view by EKB2 keypad indicates that no violated zones and/or tampers are present, therefore the system can be armed. If the message is displayed as NOT READY, the user must restore all violated zones
and tampers before arming the system. Alternatively, the violated zones can be bypassed (see 14.7. Bypassing and Activating Zones), disabled (see 14.9. Disabling and Enabling Zones) or a Force attribute enabled (see 14.6. Zone Attributes).
To arm the system by EKB2 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad (see
10. USER CODES for user code management).
By default when a valid user code is entered, the system will initiate exit delay, the keypad’s buzzer will emit short beeps and
the keypad will display
icon next to the countdown timer. When the system is successfully armed, the keypad will display
icon for 5 seconds and switch to home screen view.
MANUAL ELDES ESIM264 V3.3
EN
35
Arm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu → OK
Value: uuuu – 4-digit user code.
Example: 1111 → OK
0
To cancel the system arming process, enter the user code again during exit delay countdown.
To disarm the system by EKB2 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad. When a valid
user code is entered, the keypad will display
icon for 3 seconds and switch to home screen view.
Disarm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu → OK
Value: uuuu – 4-digit user code.
Example: 1111 → OK
0
The system will arm/disarm the partition corresponding to the one that user code and the key­pad are assigned to. For example, if EKB2 keypad
and user code is assigned to Partition 1, the user will be able to arm/ disarm only Partition 1. For more details on how to set user code and
keypad partition, please refer to 23.4. User Code Partition and 23.3. Keypad Partition and Keypad Partition Switch respectively.
To arm/disarm a different partition than the keypad is assigned to, use keypad partition switch feature (by default – disabled) before arming/
disarming process. For more details on keypad partition switch and how to enable it, please refer to 23.3. Keypad Partition and Keypad
Partition Switch.
Use keypad partition
switch
Menu path:
P1 → [p] part-name → OK
Value: part-name – up to 15 characters partition name.
NOTE: If the user fails to enter a correct user code 10 times in a row, the system will block the keypad for 2 minutes and the keypad will
display KEYPAD BLOCKED message. While the keypad is blocked, the system prevents from entering any user code. The keypad will automatically unblock once the 2-minute time has expired and display KEYPAD UNBLOCKED message.
12.4. EKB3 Keypad and User Code
Illuminated indicator
on EKB3 keypad indicates that no violated zones and/or tampers are present, therefore the system can
be armed. If the indicator is not illuminated, the user must restore all violated zones and tampers before arming the system. Alternatively, the violated zones can be bypassed (see 14.7. Bypassing and Activating Zones), disabled (see 14.9. Disabling
and Enabling Zones) or a Force attribute enabled (see 14.6. Zone Attributes).
EKB3
To arm the system by EKB3 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad (see
10. USER CODES for user code management). By default, when a valid user code is entered, the system will initiate exit delay,
the keypad’s buzzer will emit short beeps and the indicator will light ON. When the system is successfully armed, the keypad’s
buzzer will silent down.
Arm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
0
To cancel the system arming process, enter the user code again during exit delay countdown.
To disarm the system by EKB3 keypad, enter any out of 30 available 4-digit user codes using the number keys on the keypad. When a valid
user code is entered, EKB3 keypad indicator will light OFF.
Disarm the system
1
2
3
4
5
6
7
8
9
Enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
0
The system will arm/disarm the partition corresponding to the one that user code and the key­pad are assigned to. For example, if EKB3
keypad and user code is assigned to Partition 0, the user will be able to arm/ disarm only Partition 0. For more details on how to set user
36
EN
MANUAL ELDES ESIM264 V3.3
code and keypad partition, please refer to 23.4. User Code Partition and 23.3. Keypad Partition and Keypad Partition Switch respectively.
To arm/disarm a different partition than the keypad is assigned to, use keypad partition switch feature (by default – disabled) to switch the
keypad to a different partition before arm­ing/disarming process. For more details on keypad partition switch and how to enable it, please
refer to 23.3. Keypad Partition and Keypad Partition Switch.
Use keypad partition
switch
Hold the [*] key, release it after 3 short beeps and enter partition number:
*p
Value: p – partition number, range – [0... 1]
Example: *1
NOTE: By default, User Code 1 is listed as 1111 and assigned to Partition 0.
12.5. iButton Key
To arm or disarm the system, touch the iButton key reader by any of 5 available iButton keys (see 11. iBUTTON KEYS for iBut­
ton key management). When the iButton is touched to the iButton key reader for arming, the system will proceed as follows:
• If ready (no violated zone/tamper), the system will initiate exit delay and arm.
• If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number. In such case the user must restore all violated zones and tampers before arming the system. Alternatively, the
violated zones can be bypassed (see 14.7. Bypassing and Activating Zones), disabled (see 14.9. Disabling and
Enabling Zones) or a Force attribute enabled (see 14.6. Zone Attributes).
33
The system will arm/disarm the partition corresponding to the one that the iButton key is assigned to. For more details on how
to set iButton key partition, please refer to 23.5. iButton Key Partition.
12.6. EWK1/EWK2 Wireless Keyfob
EWK1/
EWK2
To arm the system, press 1 of 4 keyfob buttons set to arm the system (by default, EWK1 –
EWK2 button is pressed for arming, the system will proceed as follows:
• If ready (no violated zone/tamper), the system will initiate exit delay and arm.
•
;EWK 2 -
). When EWK1/
If unready, the system will not arm. In such case the user must restore all violated zones and tampers before arming
the system. Alternatively, the violated zones can be bypassed (see 14.7. Bypassing and Activating Zones), disabled (see 14.9. Disabling and Enabling Zones) or a Force attribute enabled (see 14.6. Zone Attributes).
34
Arm the
system
34
Arm
the
system
To disarm the system, press 1 of 4 keyfob buttons set to disarm the system (by default, EWK1 -
MANUAL ELDES ESIM264 V3.3
; EWK2 -
).
EN
37
36
Disarm
the
system
37
Disarm
the
system
The system will arm/disarm the partition corresponding to the one that EWK1/EWK2 wireless keyfob is assigned to (see 23.6.
EWK1/ EWK2 Wireless Keyfob Partition). For example, if EWK1/EWK2 wireless keyfob is assigned to Partition 1, the user
will be able to arm/ disarm only Partition 1. To arm a different partition than the EWK1/EWK2 wireless keyfob is assigned to, pair
another EWK1/EWK2 keyfob with the system and assign it to a different partition.
For more details on how to manage EWK1/EWK2 keyfob buttons, please refer to ELDES Configuration Tool software‘s HELP
section.
12.7. Arm-Disarm by Zone
ARM/
DISARM
ZONE
The Arm-Disarm by Zone feature allows to use a zone for arming and disarming the alarm system when the zone is violated and
restored. The process is performed by providing a low-level pulse for more than 3 seconds into the specified zone. It means that
violating and restoring the zone leads to system arming and by repeating this action the system becomes disarmed. The system
will arm/disarm the partition (-s) that the zone is assigned to. This method can be set up for one on-board zone only.
Set zone for ArmDisarm by Zone
method
Disable Arm-Disarm by
Zone method
38
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → ZONE 1... 12 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 and on-board zone number:
34 nn #
Value: nn – on-board zone number, range – [01... 12].
Example: 3403#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → N/A → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 and parameter status value
34 00 #
Example: 3400#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
12.8. Disabling and Enabling Arm/Disarm Notifications
By default, when the system is successfully armed or disarmed, it replies with confirmation by SMS text message to:
•
user phone number, sharing the same partition as EKB2/EKB3 keypad and user code, iButton key, EWK1/EWK2 wireless keyfob or zone,
set up for Arm/Disarm by Zone method.
•
user phone number that the system arming/disarming by free of charge phone call was initiated from.
•
user phone number that the system arming/disarming by SMS text message was initiated from.
The confirmation SMS text message is sent to the user phone number regarding each partition separately and contains system status and
partition name.
To disable/enable this notification for individual user phone number, please refer to the following configuration methods.
Disable arm/disarm
notification for
individual user phone
number
Enable arm/disarm
notification for
individual user phone
number
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → SEND ARM/DARM SMS → OK →
DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 75, user phone number slot and parameter status value:
75 up 0 #
Value: up – user phone number slot, range – [01... 05].
Example: 75030#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → SEND ARM/DARM SMS → OK →
ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 75, user phone number slot and parameter status value:
75 up 1 #
Value: up– user phone number slot, range – [01... 05].
Example: 75041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the system sends SMS text message only to the first available user phone number when the system is successfully armed/
disarmed. If the system did not receive the SMS delivery report during 45 seconds, it will attempt to send the SMS text message to the next
listed user phone number. To ignore the SMS delivery report and allow/disallow the system to send the SMS text message to every listed
user phone number, please refer to the following configuration methods.
Enable arm/disarm
notification for all
listed user phone
numbers
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ARM/DARM ALL → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 22 and parameter status value:
22 1 #
Example: 221#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
39
Disable arm/disarm
notification for all
listed user phone
numbers
40
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ARM/DARM ALL → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 22 and parameter status value:
22 0 #
Example: 220#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
13. EXIT AND ENTRY DELAY
When arming, the system initiates the exit delay countdown (by default – 15 seconds) intended for the user to leave the secured area. The
exit delay is indicated by short beeps emitted by EKB2/EKB3 keypad buzzer and buzzer, connected to the alarm system. in addition, when
arming by EKB2 keypad,
icon will be displayed next to the countdown timer on keypad screen during exit delay.
•
in a non-partitioned system,
•
in a partitioned system, EKB2 keypad will display ARMING part-name message on the screen for 3 seconds and switch to partition
selection menu during exit delay.
icon will be displayed next to the countdown timer on EKB2 keypad screen during exit delay.
Exit delay is provided when arming the system by the following methods:
•
EKB2/EKB3 keypad and user code.
•
iButton key.
•
EWK1/EWK2 wireless keyfob.
•
Arm/Disarm by Zone.
To arm the system without exit delay, use one of the following system arming methods:
•
Free of charge phone call.
•
SMS text message.
•
EGR100 middle-ware.
Set exit delay
SMS
EKB2
SMS text message content:
ssss_EXITDELAY:ext
Value: ssss – 4-digit SMS password; ext – exit delay duration, range – [0... 600] seconds.
Example: 1111_EXITDELAY:20
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EXIT DELAY → OK
→ ext → OK
Value: aaaa – 4-digit administrator password;, ext – exit delay duration, range – [0... 600]
seconds.
EKB3
Enter parameter 72 and exit delay duration:
72 ext #
Value: ext – exit delay duration, range – [0... 600] seconds.
Example: 72259#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Alternatively, you can set exit delay value to 0 in order to arm the system without exit delay by any available method.
Once the exit delay has expired, the system initiates the entry delay countdown (by default – 15 seconds) if a Delay type zone is violated.
The countdown is indicated by short beeps emitted by keypad buzzer and by steady beep emitted by system’s buzzer. The indication is intended to advise the user that the system should be disarmed. Once the user presses/touches any key on the keypad during this delay, the
buzzer of the keypad will be silenced. If the system is disarmed before the entry delay expires, no alarm will be caused.
MANUAL ELDES ESIM264 V3.3
EN
41
Set entry delay for
Delay zone
SMS
EKB2
EKB3
Config
Tool
SMS text message content:
ssss_ENTRYDELAY:nn,eeeee or ssss_ENTRYDELAY:nn,eeeee;nn,eeeee;nn,eeeee;nn,eeeee
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 44], eeeee – entry delay
duration, range – [0... 65535] seconds.
Example: 1111_ENTRYDELAY:1,25;14,32;12,20
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK →
ONBOARD ZONES → OK → ZONE 1... 12 → OK → ENTRY DELAY → OK → eeeee → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → ENTRY DELAY → OK → eeeee → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → ENTRY DELAY → OK → eeeee → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → ENTRY DELAY → OK → eeeee → OK
Value: aaaa – 4-digit administrator password; eeeee – entry delay duration, range – [0...
65535] seconds.
Enter parameter 54, partition number and entry delay duration:
54 nn eeeee #
Value: nn – zone number, range – [01... 44], eeeee – entry delay duration, range – [0... 65535]
seconds
Example: 5403259#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
For more details on zone types, please refer to 14.5. Zone Type Definitions.
42
EN
MANUAL ELDES ESIM264 V3.3
14. ZONES
Detection devices such as motion detectors and door contacts are connected to the alarm system’s zone terminals. Once connected, the
associated zone’s parameters must be configured.
ESIM264 comes equipped with 6 on-board zones allowing to connect up to 6 detection devices. For more details regarding zone expansion,
please refer to 14.2. Zone Expansion.
ESIM264 zones are classified by 5 categories:
Description
Max. number of
zones per device
Max. number of
zones in total
On-board zones
Built-in wired zones of ESIM264 alarm system.
6/12*
6/12*
Keypad zones
Hardwired zones of EKB2/EKB3 keypad.
1
4
EPGM1 zones
Zones of EPGM1 - hardwired zone and PGM output expan- 16
sion module.
16
Wireless zones
Non-physical zones automatically created by connected 4**
wireless devices.
32***
Virtual zones
Non-physical zones intended for Panic button feature (alarm
activation upon pressing the button) on EWK1/EWK2 wireless keyfob. Virtual zones can be manually created using ELDES Configuration Tool software.
32****
Zone category
32****
* - 6-Zone mode is enabled by default. ATZ mode doubles the on-board zone number and increases it to 12 in total.
** - Depends on the connected wireless device.
*** - Available only if no keypad zones, EPGM1 zones and virtual zones are present.
**** - Available only if no keypad zones, EPGM1 zones and wireless zones are present.
14.1. Zone Numbering
The zone numbers ranging from Z1 through Z12 are permanently reserved for on-board zones even when ATZ mode is disabled. The
Z13-Z44 zone numbers are automatically assigned in the chronological order to the created virtual zones and the devices connected to the
system: keypads, wireless devices, EPGM1 modules.
14.2. Zone Expansion
For additional detection device connection, the number of zones can be expanded by:
•
enabling the ATZ (Advanced Technology zone) mode (see 14.4. ATZ (Advanced Technology Zone) Mode).
•
connecting EPGM1 hardwired zone and PGM output expansion module (for more details on technical specifications and installation,
please refer to the latest user manual of the device located at eldesalarms.com).
•
connecting keypads (see 31.1.1. EKB2 – LCD Keypad and 31.1.2. EKB3 – LED Keypad).
•
pairing wireless devices (see 19. WIRELESS DEVICES).
•
creating virtual zones (see ELDES Configuration Tool software’s Help section).
The maximum supported number of zones is 44.
14.3. 6-Zone Mode
By default, ESIM264 alarm system runs in the 6-Zone mode under zone connection Type 1 allowing to connect up to 6 detection devices of
NO (normally-open) type to the on-board zone terminals as indicated in the wiring diagram of Type 1. Once a different zone connection type
is set, the detection device wiring must be done according to the wiring diagram of the associated type.
Available zone connection types for the 6-Zone mode:
•
Type 1 – Parallel wiring of NO (normally-open) detection device with 5,6kΩ EOL (end-of-line) resistor.
•
Type 2 – Serial wiring of NC (normally-closed) detection device with 5,6kΩ EOL resistor.
•
Type 3 – Combination of serial and parallel wiring of tamper with 5,6kΩ EOL resistor and NC (normally-closed) detection device with
3,3kΩ EOL resistor.
MANUAL ELDES ESIM264 V3.3
EN
43
For zone wiring diagrams of the 6-Zone mode, please refer to 2.3.2. Zone Connection Types.
Set zone connection
type for 6-Zone mode
EKB2
EKB3
Config
Tool
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ZONE TYPE:6-ZONE M
→ OK → TYPE 1... 3 → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 39 and number of zone connection type:
39 1 # – Type 1
39 2 # – Type 2
39 3 # – Type 3
Example: 392#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system supports a mixed combination of Type 1 and Type 2 zone connection types simultaneously regardless of the type (Type 1
or Type 2) selected in the system’s configuration. This applies to on-board zones, keypad zones and EPGM1 zones. Example: On-board zone
Z1 and keypad zone is wired based on Type 1, while on-board zone Z3 and EPGM1 zone is wired based on Type 2.
NOTE: Type 3 is NOT supported by keypad zones.
NOTE: ATZ mode is NOT supported by keypad zones and EPGM1 zones. If ATZ mode is enabled, EPGM1 zones must be wired in accordance
with the last selected 6-Zone mode zone connection type before the ATZ mode has been enabled. The ATZ mode setting does NOT affect the
zone connection type of the keypad zones.
14.4. ATZ (Advanced Technology Zone) Mode
The ATZ mode is a software-based feature that doubles the number of on-board zones and enables two detection devices to be installed
per 1 zone terminal. Once this mode is enabled, the zone connection Type 4 is set automatically. The detection devices must be wired to the
on-board zone terminals as indicated in the wiring diagram of the associated zone connection type.
Available zone connection types for the ATZ mode:
•
Type 4 – Parallel wiring of 2 NC (normally-closed) detection devices with 5,6kΩ and 3,3kΩ EOL (end-of-line) resistors respectively.
5,6kΩ EOL resistor corresponds to zones ranging from Z1 through Z6, while 3,3kΩ EOL resistor corresponds to zones ranging from Z7
through Z12.
•
Type 5 – Combination of serial and parallel wiring of tamper with 5,6kΩ EOL resistor and 2 NC (normally-closed) detection devices with
5,6kΩ and 3,3kΩ EOL resistors respectively. 5,6kΩ EOL resistor corresponds to zones ranging from Z1 through Z6, while 3,3kΩ EOL
resistor corresponds to zones ranging from Z7 through Z12.
For zone wiring diagrams of the ATZ mode, please refer to 2.3.2. Zone Connection Types.
Enable ATZ mode
44
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ATZ MODE → OK →
ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 28 and parameter status value:
28 1 #
Example: 281#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
Disable ATZ mode
Set zone connection
type for ATZ mode
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ATZ MODE → OK →
DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 28 and parameter status value:
28 0 #
Example: 280#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ZONE TYPE:ATZ MODE →
OK → TYPE 4... 5 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 38 and number of zone connection type:
38 1 # – Type 4
38 2 # – Type 5
Example: 381#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Once enabled, the ATZ mode DOES NOT affect EPGM1 zones, nor keypad zones and applies to on-board zones only.
14.5. Zone Type Definitions
•
Interior Follower – The zone can be violated during exit and entry delay without causing an alarm. If the zone is violated before the
entry delay has begun, it will cause an instant alarm followed by single notification delivery even if the zone has been violated multiple
times or another Interior Follower-type zone has been violated while alarm period (by default - 1 minute) is in progress. Typically, this
zone is used for indoor protection devices, such as motion detectors, installed close to the exit/entry doors.
•
Instant – The alarm is instantly caused if this zone is violated when the system is armed or during entry delay. This zone type is usually
used for doors, windows, shock sensors or other zones.
•
24-Hour – When the system is either armed or disarmed, the zone will cause instant alarm if violated. Normally, this type of zone is
used for securing the areas that require constant supervisory.
•
Delay – This zone type can be violated during exit and entry delay without causing an alarm. If the zone is violated when the system
is armed, it will initiate entry delay countdown intended for the user to disarm the system. If the zone is left violated after the exit
delay expires, it will cause an instant alarm. Typically, this zone type is used for door contacts installed at designated exit/entry doors.
•
Fire – If this zone type is violated when the system is either armed or disarmed, the alarm will be instantly caused and the siren/bell
will emit pulsating sound. Once the alarm is caused by violating a Fire-type zone followed by turning OFF the alarm using any available
disarm method, the system will ignore the violations of any Fire-type zone (including the repeated violations of the said zone) caused
within a 1-minute time frame. Typically, this zone type is used for flame and smoke detectors.
•
Panic/Silent – This zone operates the same as 24-Hour zone type, but the system will not activate the siren/bell and keypad buzzer if
violated. Normally, this zone type used for panic alarm buttons.
Set zone type for
individual zone
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → TYPE → OK → INTERIOR FOLLOWER | INSTANT | 24HOUR | DELAY | FIRE | PANIC/SILENT → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES 1... 4 → OK → WLESS ZONE 1... 16 → OK → TYPE → OK → INTERIOR FOLLOWER |
INSTANT | 24-HOUR | DELAY | FIRE | PANIC/SILENT → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → TYPE → OK → INTERIOR FOLLOWER | INSTANT | 24HOUR | DELAY | FIRE | PANIC/SILENT → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → TYPE → OK → INTERIOR FOLLOWER | INSTANT | 24-HOUR |
DELAY | FIRE | PANIC/ SILENT → OK
Value: aaaa – 4-digit administrator password.
EN
45
EKB3
Config
Tool
Enter parameter 53, zone number and zone type number:
53 nn 1 # – Interior Follower
53 nn 2 # – Instant
53 nn 3 # –24-Hour
53 nn 4 # – Delay
53 nn 5 # – Fire
53 nn 6 # – Panic/Silent
Value: nn – zone number, range – [01... 44]
Example: 53125#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The system will NOT activate siren/bell and keypad buzzer only when Panic/Silent zone type is violated.
14.6. Zone Attributes
•
Stay – If this attribute is enabled, the zone, regardless of type, will not cause an alarm if violated when the system is Stay armed. For
more details on arming the system in the Stay mode, please refer to 15. STAY MODE.
•
Force – This attribute determines whether the system can be armed or not while a zone is violated. If a zone with the Force attribute
enabled is left violated until the exit delay expires, it will be ignored. Once the system is armed and the zone is restored, the violation
will not be ignored and the zone will operate according to the determined type. For more details on zone types, please refer to 14.5.
Zone Type Definitions.
•
Delay, ms – This attribute determines the zone sensitivity level by delay time (by default – 800 milliseconds). If a zone is left triggered
until the delay time expires, the zone is considered violated.
•
Delay becomes Instant in Stay mode – This attribute determines whether or not any Delay type zone will operate as Instant type
zone when the system is armed in the Stay mode. When the system is fully armed, the Delay type zone will operate normally. For more
details on Delay and Instant zone types, please refer to 14.5. Zone Type Definitions.
•
Chime – This feature is used to emit 3 short beeps from the keypad buzzer and display
icon on EKB2 keypad screen whenever any
Delay type zone is violated. Typically, the feature is used for designated exit/entry doors to indicate the opening of the doors.
•
Alarm count to bypass – This attribute determines a number of times the zone can be violated until it is automatically bypassed.
For more details on zone bypassing and how to activate a bypassed zone, please refer to 14.7. Bypassing and Activating Zones.
Enable Stay attribute
for individual zone
46
EN
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → STAY → OK → ENABLE → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → STAY → OK → ENABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD
ZONES → OK → KEYPAD 1... 4 ZONE → OK → STAY → OK → ENABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → STAY → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 56, zone number and parameter status value:
56 nn 1 #
Value: nn – zone number, range – [01... 44].
Example: 56041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
Disable Stay attribute
for individual zone
Enable Force attribute
for individual zone
Disable Force
attribute for
individual zone
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → STAY → OK → DISABLE → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → STAY → OK → DISABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD
ZONES → OK → KEYPAD 1... 4 ZONE → OK → STAY → OK → DISABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1
ZONES → OK → EPGM1 ZONE 1... 16 → OK → STAY → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 56, zone number and parameter status value:
56 nn 0 #
Value: nn – zone number, range – [01... 44].
Example: 56190#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → FORCE → OK → ENABLE → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → FORCE → OK → ENABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → FORCE → OK → ENABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → FORCE → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 82, zone number and parameter status value:
82 nn 1 #
Value: nn – zone number, range – [01... 44].
Example: 82061#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → FORCE → OK → DISABLE → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → FORCE → OK → DISABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD
ZONES → OK → KEYPAD 1... 4 ZONE → OK → FORCE → OK → DISABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → FORCE → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 82, zone number and parameter status value:
82 nn 0 #
Value: nn – zone number, range – [01... 44].
Example: 82110#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
47
Set Delay, ms atrribute
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Enable/disable Delay
becomes Instant in
Stay mode attribute
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Disable Chime
attribute
EKB2
Enable Chime attribute
Set Alarm count to
bypass attribute for
individual zone
Menu path:
OK → CONFIGURATION → OK →aaaa → OK → ZONES → OK → CHIME → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 32 and parameter status value:
32 0 #
Example: 320#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → CHIME → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 32 and parameter status value:
32 1 #
Example: 321#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
14.7. Bypassing and Activating Zones
NOTE for EKB3: The Configuration mode must remain deactivated before bypassing a violated zone or activating a bypassed zone.
Zone bypassing allows the user to deactivate a violated zone and arm the system without restoring the zone. If a bypassed zone is violated
or restored during exit/entry delay, or when then system is armed, it will be ignored. When a zone is bypassed, EKB3 keypad indi­cator will
light ON and EKB2 keypad will display BYP message in the home screen view.
Bypass individual
violated zone
EKB2
EKB3
48
EN
Menu path:
OK → BYPASS → OK → BYPASS LIST 1... 3 → OK → Z1-zone-name... Z44-zone-name → OK →
BYPASS → OK K
Value: zone-name - up to 24 characters zone name.
Press the key, enter zone number and user code:
nn uuuu #
Value: nn – zone number, range – [01... 44]; uuuu – 4-digit user code.
Example: 091111#
MANUAL ELDES ESIM264 V3.3
Bypass all violated
zones
EKB2
Menu path:
OK → BYPASS → OK → BYP VIOLATED ZONES → OK
The zone will remain bypassed until the system is disarmed. Once the system is disarmed, the corresponding zone state will be indicated on
the keypads (see 31.1.1. EKB2 – LCD Keypad and 31.1.2. EKB3 – LED Keypad) and Info SMS text message (see 26. SYSTEM INFORMATION. INFO SMS). Alternatively, the user can activate the bypassed zone by the following configuration methods.
Activate bypassed
zone
EKB2
EKB3
Menu path:
OK → BYPASS → OK → BYPASS LIST 1...3 → OK → Z1-zone-name... Z44-zone-name → OK →
UNBYPASS → OK
Value: zone-name - up to 24 characters zone name.
Press the key, enter zone number and user code:
nn uuuu #
Value: nn – zone number, range – [01... 44]; uuuu – 4-digit user code.
Example: 251111#
NOTE: Zones can only be bypassed and activated when the system is not armed.
14.8. Zone Names
Each zone has a name that can be customized by the user. Typically, the name specifies a device type connected to a determined zone
terminal, for Example: Kitchen doors opened. The zone names are used in SMS text messages that are sent to the user during alarm. the
By default, the zone names are: Z1 – Zone1, Z2 – Zone2, Z3 – Zone3, Z4 – Zone4 etc.
Set zone name
SMS
Config
Tool
View zone names
SMS
EKB2
Config
Tool
SMS text message content:
ssss_Znn:zone-name
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 44]; zone-name – up to
24 characters zone name.
Example: 1111_Z3:Door sensor triggered
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_STATUS
Value: ssss – 4-digit SMS password.
Example: 1111_STATUS
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → NAME
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → NAME
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → NAME
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → NAME
Value: aaaa – 4-digit administrator password.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Colon, semi-colon characters, parameter names and/or values, such as PSW, STATUS, ON, OFF etc. are NOT allowed in zone
names
NOTE: Multiple zone names can be set by a single SMS text message, Example: 1111_Z1:Kitchen doors opened;Z3:Movement in basement;Z4:Bedroom window opened
MANUAL ELDES ESIM264 V3.3
EN
49
14.9. Disabling and Enabling Zones
By default, all zones, except keypad and virtual zones, are enabled. To permanently disable/enable an individual zone, please refer to the
following configuration methods.
Disable zone
SMS
EKB2
Enable zone
EN
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → STATUS → OK → DISABLE → OK
Wireless zone: OK → CONFIGURATION → STATUS → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → STATUS → OK → DISABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → STATUS → DISABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → STATUS → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 52, zone number and parameter status value:
52 nn 0 #
Value: nn – zone number, range – [01... 44].
Example: 52360#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
EKB2
50
SMS text message content:
ssss_Znn:OFF
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 44].
Example: 1111_Z13:OFF
SMS text message content:
ssss_Znn:ON
Value: ssss – 4-digit SMS password; nn – zone number, range – [1... 44].
Example: 1111_Z6:ON
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → STATUS → OK → ENABLE → OK
Wireless zone: OK → CONFIGURATION → STATUS → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → STATUS → OK → DISABLE → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD ZONES
→ OK → KEYPAD 1... 4 ZONE → OK → STATUS → DISABLE → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
EPGM1 ZONE 1... 16 → OK → STATUS → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 52, zone number and parameter status value:
52 nn 1 #
Value: nn – zone number, range – [01... 44].
Example: 52151#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
15. STAY MODE
Stay mode allows the user to arm and disarm the alarm system without leaving the secured area. If the zones with Stay attribute enabled
are violated when the system is Stay armed, no alarm will be caused. Typically, this feature is used when arming the system at home before
going to bed.
The system can be Stay armed under the following conditions:
•
If a Delay-type zone is NOT violated during exit delay and a zone (-s) with Stay attribute enabled exists, the system will arm in Stay
mode. When arming the system in Stay mode under this condition, one of the available arming methods must be used that provide exit
delay. For more details on these methods, please refer to 13. EXIT AND ENTRY DELAY.
•
The system will instantly arm in Stay mode when using one of the following methods.
Arm the system in
Stay mode
EKB2
EKB3
Menu path:
P2 → uuuu → OK
Value: uuuu – 4-digit user code.
Press the key and enter user code:
uuuu
Value: uuuu – 4-digit user code.
Example: 1111
When the system is successfully armed in Stay mode, EKB2 keypad will display STAY message in the home screen view.
ATTENTION: System arming in Stay mode by the keypad must be carried out without Configuration mode being activated.
NOTE: The system can be armed in Stay mode, only if there is at least one zone with Stay attribute enabled.
NOTE: Stay mode is not supported by virtual zones.
For more details on how to enable Stay attribute for zone, please refer to 14.6. Zone Attributes.
MANUAL ELDES ESIM264 V3.3
EN
51
16. TAMPERS
The tamper circuit is a single closed loop such that a break in the loop at any point will cause a tamper alarm regardless of the system
status – armed or disarmed. During the tamper alarm, the system will activate the siren/bell and the keypad buzzer and send the SMS text
message to the listed user phone number. The system will cause tamper alarm under the following conditions:
•
If the enclosure of a detection device, siren/bell, metal cabinet or keypad is opened, the physical tamper switch will be triggered. By
default, indicated as Tamper x in the SMS text message (x = tamper number).
•
If the wireless signal is lost due to low signal level or low battery power on a certain wireless device (see 19.3. Wireless Signal Status
Monitoring).
By default, tamper alarm notification by SMS text message is enabled. To disable/enable tamper alarm notification, please refer to the
following configuration methods.
Disable tamper alarm
notification
Enable tamper alarm
notification
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → TAMPER EVENT → OK
→ DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, event number and parameter status value:
25 08 0 #
Example: 25080#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
Config
Tool
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → TAMPER EVENT → OK
→ ENABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 08 1 #
Example: 25081#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
For more details on how to view violated tamper, please refer to 17. ALARM INDICATIONS AND NOTIFICATIONS FOR USER
16.1. Tamper Names
Each tamper has a name that can be customized by the user. The tamper names are used in SMS text messages that are sent to the user
during the tamper alarm. By default, the tamper names are: Tamper 1, Tamper 2, Tamper 3, Tamper 4 etc. To set a different tamper name,
please refer to the following configuration methods.
Manage tamper name
52
EN
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
17. ALARM INDICATIONS AND NOTIFICATIONS FOR USER
When a zone, depending on zone type (see 14.5. Zone Type Definitions), or tamper is violated, the system will cause an alarm. By default, the alarm duration is 1 minute (see 20. SIREN/BELL regarding the alarm duration). During the alarm, the system will follow this
pattern:
1. The system activates the siren/bell and the keypad buzzer.
a) The siren/bell will emit pulsating sound if the violated zone is of Fire type, otherwise the sound will be steady.
b) The keypad buzzer will emit short beeps.
c) Depending on violated zone type, EKB2 keypad will display BURGLARY ALARM message followed by one of the alarm messages in the
home screen view:
•
ALARM.
•
FIRE ALARM.
•
24H ALARM.
d) During the tamper alarm, EKB2 keypad will display TAMPER ALARM message in the home screen view.
e) If one or more zones are violated, EKB3 will light ON the corresponding violated zone indicator (-s) ranging from 1 through 12. Indicator
will flash if one or more high-numbered zones are violated. If one or tampers are violated, indicator
will light ON. For more details
on viewing violated high-numbered zone and tamper numbers by EKB3 keypad, please refer to 29. INDICATION OF SYSTEM FAULTS.
2. The system attempts to send an SMS text message, containing the violated zone/tamper name (see 14.8. Zone Names on how to set
a zone name), to the first listed user phone number, sharing the same partition as the violated zone/tamper. The system will send SMS
text messages regarding each violated zone/tamper separately.
a) If the user phone number is unavailable and the system fails to receive the SMS delivery report during 45 seconds, it will attempt to
send the SMS text message to the next listed user phone number, assigned to the same partition as the previous one. The user phone
number may be unavailable due to the following reasons:
•
mobile phone was switched off.
•
was out of GSM signal coverage.
b) The system will continue sending the SMS text message to the next listed user phone numbers in the priority order until one is available. The system sends the SMS text message only once and will not return to the first user phone number if the last one was unavailable.
3. By default, the system attempts to ring the first user phone number, sharing the same partition as the violated zone/tamper. The system
will dial regarding each violated zone/tamper separately.
a) When the call is answered, the user will be able to listen on the mobile phone for approx. 30 seconds to what is happening in the area,
surrounding the alarm system. This feature will be available only if a microphone is connected to the system (see 25. REMOTE LISTENING AND 2-WAY VOICE COMMUNICATION).
b) The system will dial the next listed user phone number, assigned to the same partition, if the previous user was unavailable due to the
following reasons:
• mobile phone was switched off.
• mobile phone was out of GSM signal coverage.
• provided “busy” signal.
• user did not answer the call after several rings, predetermined by the GSM operator.
c)
The system will continue dialling the next listed user phone numbers in the priority order until one is available. The system dials only
once and will not return to the first user phone number if the last one was unavailable.
d) The system will not dial the next listed user phone number if the previous one was available, but rejected the phone call.
To silent the siren/bell as well as to cease system phone calls and SMS text message sending to the user phone numbers, please disarm the
system (see 12. ARMING AND DISARMING).
View violated zones
MANUAL ELDES ESIM264 V3.3
SMS
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
EKB2
Menu path:
OK → VIOLATED ZONES → OK → ZONE 1... 44
EKB3
Please, refer to illuminated zone indicators ranging from 1 through 12 on the keypad. The
flashing indicator
represents violated high-numbered zones (Z13-Z44). For more details
on violated high-numbered zone indication, please refer to 29. INDICATION OF SYS­TEM
FAULTS.
EN
53
View violated tampers
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
The system will automatically send an SMS text message, containing a violated tamper name,
to user phone number.
EKB2
Menu path:
OK → VIOLATED TAMPERS → OK → TAMPER 1... 44
EKB3
The illuminated indicator
represents system fault presence including violated tamper.
For more details on violated tamper indication, please refer to 29. INDICATION OF SYSTEM
FAULTS.
For more details on how to disable/enable SMS text messages and phone calls to the listed user phone number in case of alarm, please refer
to 17.1. Enabling and Disabling Alarm Notifications
ATTENTION: Phone calls to the listed user phone number in case of alarm are disabled by force when MS mode is enabled (see 30. MONITORING STATION).
NOTE: If one or more zones/tampers are violated during the alarm, the system will attempt to send as many SMS text message and dial the
user phone number as many times as the zone/tamper was violated. The capacity of the queue is 24 events maximum.
NOTE: If the system sent the SMS text message and/or dialled the user phone number after disarming the system, it means that the SMS
text message and/or phone call was queued up in the memory before the system was disarmed
17.1. Enabling and Disabling Alarm Notifications
By, default the system will ring the listed user phone numbers in case of alarm. To disable/enable this feature, please refer to the following
configuration methods.
Disable call in case of
alarm
Enable call in
case of alarm
54
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CALL IN CASE ALARM → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 30 and parameter status value:
30 1#
Example: 301#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → CALL IN CASE ALARM → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 30 and parameter status value:
30 0#
Example: 300#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
By, default the system will send SMS text message to the listed user phone numbers in case of alarm. To disable/enable this feature, please
refer to the following configuration methods.
Disable SMS text
message in case of
alarm
Enable SMS text
message in case of
alarm
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → ALARM EVENT → OK
→ DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, event number and parameter status value:
25 03 0 #
Example: 25010#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → ALARM EVENT → OK
→ ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, event number and parameter status value:
25 01 1 #
Example: 25011#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, the system sends SMS text message to the first available user in case of alarm. If the system did not receive the SMS delivery
report during 45 seconds, it will attempt to send the SMS text message to the next listed user phone number. To ignore the SMS delivery
report and allow/disallow the system to send the SMS text message to every listed user phone number, please refer to the following configuration methods
Enable SMS text
message to all listed
user phone numbers in
case of alarm
MANUAL ELDES ESIM264 V3.3
SMS
SMS text message content:
ssss_SMSALL:ON
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ALARM SMS ALL → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 21 and parameter status value:
21 1 #
Example: 211#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
55
Disable SMS text
message to all listed
user phone numbers in
case of alarm
SMS
SMS text message content:
ssss_SMSALL:OFF
Value: ssss – 4-digit SMS password
Example: 1111_SMSALL:OFF
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → SEND ALARM SMS ALL → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 21 and parameter status value:
21 0 #
Example: 210#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, tamper alarm notification by SMS text message is enabled. For more details on how to disable/enable tamper alarm notification,
please refer to 16. TAMPERS.
ATTENTION: Regardless of the Call in Case of Alarm parameter status, the system will NOT ring the listed user phone number if the system
is connected to the monitoring station (see 30. MONITORING STATION).
56
EN
MANUAL ELDES ESIM264 V3.3
18. PROGRAMMABLE (PGM) OUTPUTS
A PGM output is a programmable output that toggles to its set up state when a specific event has occurred in the system, the scheduled
weekday and time has come or if the user has initiated the PGM output state change manually. Normally, PGM outputs can be used to open/
close garage doors, activate lights, heating, watering and much more. When a PGM output turns ON, the system triggers any device or relay
connected to it.
ESIM264 comes equipped with four open-collector PGM outputs allowing to connect up to four devices or relays. For more details on PGM
output expanding, please refer to 18.2. PGM Output Expansion.
ESIM264 PGM outputs are classified by 4 categories:
PGM output category
Description
Max. number of PGM
outputs per device
Max. number of PGM
outputs in total
On-board PGM Outputs
Built-in wired PGM outputs of ESIM264 alarm system.
4
4
EPGM8 PGM Outputs
PGM outputs of EPGM8 - hardwired PGM output expan8
sion module.
8
EPGM1 PGM Outputs
PGM outputs of EPGM1 - hardwired zone and PGM output
2
expansion module.
4
Wireless PGM Outputs
Non-physical PGM outputs automatically created by con2*
nected wireless devices.
32**
* - Depends on the connected wireless device.
** - Available only if no EPGM1 PGM outputs are present.
For PGM output wiring diagram, please refer to 2.3.6. Relay Finder® 40.61.9.12 with Terminal Socket 95.85.3.
18.1. PGM Output Numbering
The PGM output numbers ranging from C1 through C12 are permanently reserved for on-board PGM outputs even if EPGM8 module mode is
disabled. The C13-C44 PGM output number are automatically assigned in the chronological order to the devices connected to the system:
EPGM1 modules and wireless devices.
18.2. PGM Output Expansion
For additional electrical appliance connection, the number of PGM outputs can be expanded by:
•
connecting EPGM8 hardwired PGM output expansion module. (see 18.2.1. EPGM8 Mode and 31.3.1. EPGM8 – Hardwired PGM
Output Expansion Module)
•
connecting EPGM1 hardwired zone and PGM output expansion module (see 31.1.3. EPGM1 – Hardwired Zone and PGM Output
Ex­pansion Module).
•
pairing the wireless devices (see 19. WIRELESS DEVICES).
The maximum supported PGM output number is 76.
18.2.1. EPGM8 Mode
EPGM8 is an expansion module, which expands the system with 8 additional hardwired PGM outputs. For more details on EPGM8 module
installation, please refer to 31.3.1. EPGM8 – Hardwired PGM Output Expansion Module.
Once the EPGM8 module is installed, the EPGM8 mode must be enabled.
Enable EPGM8 mode
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PGM OUTPUTS → OK → USING EPGM8 → OK
→ ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 33 and parameter status value:
33 1 #
Example: 331#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
57
Disable EPGM8 mode
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PGM OUTPUTS → OK → USING EPGM8 → OK
→ DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 33 and parameter status value:
33 0 #
Example: 330#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
18.3. PGM Output Names
Each PGM output has a name that can be customized by the user. Typically, the name specifies a device type connected to a determined
PGM output, e.g. Lights. The name can be used instead of PGM output number when controlling the PGM output by SMS text message. By
default, the PGM output names are: C1 – Controll1, C2 – Controll2, C3 – Controll3, C4 – Controll4 etc.
Set PGM output name
SMS
Config
Tool
View PGM output
names
SMS
SMS text message content:
ssss_Coo:out-name
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 44]; out-name –
up to 16 characters PGM output name.
Example: 1111_C2:Lights
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_STATUS
Value: ssss – 4-digit SMS password.
Example: 1111_STATUS
EKB2
Menu path:
On-board PGM output: OK → CONFIGURATION → OK → aaaa → OK → PGM OUTPUTS → OK
→ ONBOARD OUTPUTS → OK → OUTPUT 1... 12 → OK → NAME
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Space, colon, semi-colon characters, parameter names and/or values, such as PSW, STATUS, ON, OFF etc. are NOT allowed in
PGM output names.
18.4. Turning PGM Outputs ON and OFF
By default, all PGM outputs are turned OFF. To instantly turn ON/OFF an individual PGM output and set its state to ON/OFF when the system
starts-up, please refer to the following configuration methods.
Turn ON PGM output/
Set PGM output startup state as ON
SMS
EKB2
58
EN
SMS text message content:
ssss_Coo:ON or ssss_out-name:ON
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 44]; out-name –
up to 16 characters PGM output name.
Example: 1111_Lights:ON
Menu path:
On-board PGM output: OK → CONFIGURATION → OK → aaaa → OK → PGM OUTPUTS → OK
→ ONBOARD OUTPUTS → OK → OUTPUT 1... 12 → OK → STATUS → OK → ENABLED → OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM264 V3.3
Turn OFF PGM output/
Set PGM output startup state as OFF
EKB3
Enter parameter 61, PGM output number and parameter status value:
61 oo 1 #
Value: oo – PGM output number, range – [01... 44].
Example: 61031#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_Coo:OFF or ssss_out-name:OFF
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 76]; out-name –
up to 16 characters PGM output name.
Example: 1111_C2:OFF
EKB2
Menu path:
On-board PGM output: OK → CONFIGURATION → OK → aaaa → OK → PGM OUTPUTS → OK
→ ONBOARD OUTPUTS → OK → OUTPUT 1... 12 → OK → STATUS → OK → DISABLED → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 61, PGM output number and parameter status value:
61 oo 0 #
Value: oo – PGM output number, range – [01... 44].
Example: 61020#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To instantly turn ON an individual PGM output for a determined time period and automatically turn it OFF when the time period expires,
please refer to the following configuration method.
Turn ON PGM output
for time period
SMS
SMS text message content:
ssss_Coo:ON:hr.mm.sc or ssss_out-name:ON:hr.mn.sc
Value: ssss – 4-digit SMS password; oo – PGM output number, range – [1... 44]; out-name
– up to 16 characters PGM output name; hr – hours, range – [00... 23]; mn – minutes, range
– [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_C4:ON:10.15.35
To instantly turn OFF an individual PGM output for a determined time period and automatically turn it ON when the time period expires,
please refer to the following configuration method.
Turn OFF PGM output
for time period
SMS
SMS text message content:
ssss_Coo:OFF:00.00.sc or ssss_out-name:OFF:hr.mn.sc
Value: ssss – 4-digit SMS password;oo – PGM output number, range – [1... 44]; out-name
– up to 16 characters PGM output name; hr – hours, range – [00... 23]; mn – minutes, range
– [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_Lights:OFF:00.00.23
When the PGM output is turned ON or OFF, the system will send a confirmation by SMS text message to the user phone number that the
SMS text message was sent from.
NOTE FOR EKB2/EKB3/CONFIG TOOL USERS: Only the startup state of the PGM output can be changed using these configuration
methods
NOTE: PGM output can be turned ON for a determined time period only when it is in OFF state
NOTE: PGM output can be turned OFF for a determined time period only when it is in ON state
NOTE: Multiple PGM outputs can be turned ON/OFF by a single SMS text message, Example: 1111_C1:ON C2:OFF Pump:ON C4:ON:00.20.25
MANUAL ELDES ESIM264 V3.3
EN
59
18.5. PGM Output Control by Event and Scheduler
The PGM outputs can automatically operate when a specific event occurs in the system and/or when the scheduled weekday and time
comes.
PGM Output Actions
The automatic action of the determined PGM output can be set as follows:
•
Turn ON – Determines whether the PGM output is to be turned ON.
•
Turn OFF – Determines whether the PGM output is to be turned OFF.
•
Pulse – Determines whether the PGM output is to be turned ON for a set period of time in seconds.
System Events
The aforementioned PGM output action can be automatically carried out under the following events that have occurred in the system:
•
System armed – System is armed in a determined partition ranging from Partition 1 through 4 or any partition.
•
System disarmed – System is disarmed in a determined partition ranging from Partition 1 through 4 or any partition.
•
Alarm begins – Alarm begins in a determined partition ranging from Partition 1 through 4 or any partition.
•
Alarm stops – Alarm stops in a determined partition ranging from Partition 1 through 4 or any partition.
•
Temperature falls – Temperature falls below the set MIN value of a determined temperature sensor 1-8.
•
Temperature rises – Temperature rises above the set MAX value of a determined temperature sensor 1-8.
•
Zone violated – A determined zone ranging from Z1 through Z76 is violated.
•
Zone restored – A determined zone ranging from Z1 through Z76 is restored.
•
Scheduler starts – Operates based on Start Time of a selected scheduler 1-16.
•
Scheduler ends – Operates based on End Time of a selected scheduler 1-16.
The user can also set a custom text, which will be sent by SMS text message to user phone number when the automatic PGM output action
is carried out.
Schedulers
The system supports up to 16 schedulers that allow the PGM outputs to operate according to the day of the week and time. When the
scheduler, which includes the set weekday and time, is selected, the PGM output will operate according to it. Each scheduler includes the
following parameters:
•
Always – The scheduler is not in use.
•
At specified time – Determines whether weekday and time settings are enabled:
•
Start Time – Determines the point in time when the PGM output action can begin.
•
End Time – Determines the point in time when the PGM output action can complete.
•
On weekdays – Determines days in week when the PGM output action is valid.
Additional Conditions
Additional condition narrows down the chances for a determined automatic PGM output operation to be carried out. If this feature is enabled, the PGM output will become dependent on one more system event that must be occurred prior or must occur after the aforementioned system event. The PGM output will not operate until the chain of system events meets the set values:
•
System armed – System is armed in a determined partition ranging from 1 to 4 or any partition.
•
System disarmed – System is disarmed in a determined partition ranging from 1 to 4 or any partition.
•
Zone violated – A determined zone ranging from Z1 to 76 is violated.
•
Zone restored – A determined zone ranging from Z1 to Z76 is restored.
Example: PGM output C1 is set to be turned ON when zone Z6 is violated. The additional condition feature is enabled and set to allow this
action to be carried out only if system’s Partition 2 is disarmed. It means that the PGM output C1 will be turned ON when zone Z6 is violated,
but only if system’s Partition 2 is disarmed.
Manage PGM output
control by event and
scheduler
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: If the date and time are not set, the system will NOT be able to automatically control the PGM outputs. For more details on how
to set date and time, please refer to 9. DATE AND TIME.
NOTE: When both - a system event is determined and a scheduler is selected, the PGM output will operate only if the determined event has
occurred in the system during the scheduled time period.
NOTE: When PGM output action is selected as pulse, the PGM output will turn ON or turn ON for a set period of time based on the PGM output
state set up (ON or OFF) for system startup.
60
EN
MANUAL ELDES ESIM264 V3.3
18.6. Wireless PGM Output Type Definitions
•
Output – Operates as normal PGM output that can be controlled by the user or automatically by event and scheduler. Normally, this
type is used for any device or relay.
•
Siren – Operates as siren output that automatically activates during alarm. Typically, this type is used for bell/siren connected to EW1
wireless device.
Set output type for
individual wireless
PGM output
MANUAL ELDES ESIM264 V3.3
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
61
19. WIRELESS DEVICES
ESIM264 system can be equipped with a wireless transmitter-receiver module EWT1 (see 32.1. EWT1 - Wireless Transmitter-Receiver)
for system extension capabilities. The module allows the user to easily pair up to 16 ELDES-made wireless devices to the system. This
includes the following:
•
EWD2 - wireless magnetic door contact/shock sensor/flood sensor.
•
EWS3 – wireless indoor siren.
•
EWS2 – wireless outdoor siren.
•
EWK1 and EWK2 – wireless keyfob.
•
EWF1 - wireless smoke detector.
RADIO SYSTEM INSTALLATION AND SIGNAL PENETRATION manual and the latest user manual of the wireless device located at eldesalarms.com
The wireless devices can operate at a range of up to 30m (98.43ft) from the alarm system unit while inside the building and at up to 150m
(492.13ft) range in open areas. The wireless connection is two-way and operates in one of four available channels in ISM868 (EU version)
/ ISM915 (US version) non-licensed band.
The communication link between the wireless device and the alarm system is constantly supervised by a configurable self-test period,
known as Test Time. When the wireless device is switched ON, it will initiate the Test Time transmission to the system within its wireless
connection range. In order to optimize battery power saving of the wireless device, the Test Time periods vary by itself while the device
is switched ON, but still unpaired. When the alarm system is switched OFF or if the wireless device is unpaired or removed the Test Time
period of the wireless device is as follows (non-customizable):
• EWS2, EWS3, EWF1:
• First 360 attempts after the device startup (reset) - every 10 seconds.
• The rest of attempts - every 1 minute.
• EWD2:
• First 360 attempts after the device startup (reset) - every 10 seconds.
• The rest of attempts - every 2 minutes.
Once the wireless device is paired, it will attempt to exchange data with ESIM264 system. Due to battery saving reasons, all ELDES wireless
devices operate in sleep mode. The data exchange will occur instantly if the wireless device is triggered (zone alarm or tamper alarm) or
periodically when the wireless device wakes up to transmit the supervision signal, based on Test Time value, to the system as well as to ac­
cept the queued up command (if any) from the system. By increasing the Test Time period, EWS2/EWS3 siren response time will decrease.
Example: The alarm occurred at 09:15:25 and the system queued up the command for EWS3 siren to start sounding. By default, Test Time
value of EWS3 siren is 7 seconds, therefore EWS3 siren will sound at 09:15:32.
By default, the Test Time period is as follows (customizable):
• EWF1 EWD2: every 30 seconds.
• EWS2, EWS3: every 7 seconds.
To set a different Test Time value, please refer to the following configuration method.
Set Test Time
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Test Time affects the wireless device binding process due to the alarm system listening for the incoming data from the wireless
device. The system binds the wireless device only when the first data packet is received.
19.1. Pairing, Removing and Replacing Wireless Device
Wireless device management can be easily and conveniently carried out using the graphical interface of ELDES Configuration Tool software. If you intend to manage the wireless devices by SMS text massage, an 8-character wireless device ID code will be required in order to
pair the device with the system or to remove it from the system. The wireless ID code is printed on a label, which can be located on the inner
or outer side of the enclosure or on the printed circuit board (PCB) of the wireless device.
To pair a wireless device, please refer to the following configuration methods.
Pair wireless device
with the system
62
EN
SMS
SMS text message content:
ssss_SET:wless-id
Value: ssss – 4-digit SMS password; wless-id – 8-character wireless device ID code.
Example: 1111_SET:535185D
MANUAL ELDES ESIM264 V3.3
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE FOR EWK1/EWK2: When binding EWK1/EWK2 wireless keyfob, it is necessary to press several times any button on the device.
Once a wireless device is paired, it occupies one of 16 available wireless device slots and the system adds single or multiple wireless zones
and wireless PGM outputs depending on the wireless device model.
To remove a wireless device, please refer to the following configuration methods.
Remove wireless
device from the
system
SMS
Config
Tool
SMS text message content:
ssss_DEL:wless-id
Value: ssss – 4-digit SMS password; wless-id – 8-character wireless device ID code.
Example: 1111_DEL:535185D
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Once a wireless device is removed from the system, please restore its default parameters and remove the batteries from it.
To replace an existing wireless device with a new same model device, please refer to the following configuration methods
Replace wireless
device
SMS
SMS text message content:
ssss_REP:wless-id<oldwl-id
Value: ssss – 4-digit SMS password; wless-id – 8-character wireless device ID code of the new
device; oldwl-id - 8-character wireless device ID code of the old device.
Example: 1111_REP:535185D<41286652
When a wireless device is successfully replaced with a new one, the configuration of the old wireless device remains.
ATTENTION: In order to correctly remove the wireless device from the system, the user must remove the device using SMS text message
or ELDES Configuration Tool software and restore the parameters of the wireless device to default afterwards. If only one of these actions is
carried out, the wireless device and the system will attempt to exchange data to keep the wireless connection alive. This leads to fast battery
power drain on the battery-powered wireless device.
NOTE: If you are unable to pair a wireless device, please restore the wireless device’s parameters to default and try again. For more details
on how to restore the default parameters, please refer to the user manual provided along with the wireless device or visit eldesalarms.com to
download the latest user manual.
19.2. Wireless Device Information
Once a wireless device is paired, the user can view the following information of a determined wireless device:
•
Battery level (expressed in percentage).
•
Wireless signal strength (expressed in percentage).
•
Error rate (number of failed data transmission attempts in 10-minute period) - indicated only in EKB2 keypad menu.
•
Firmware version.
•
Test Time period (expressed in milliseconds) of a wireless device - indicated only in SMS text message reply.
To view the wireless device information, please refer to the following configuration methods.
View wireless device
information
MANUAL ELDES ESIM264 V3.3
SMS
SMS text message content:
ssss_RFINFO:wless-id or ssss_RFINFO:Znn
Value: wless-id – 8-character wireless device ID code; nn – wireless zone number, range
– [13... 44].
Example: 1111_RFINFO:535185D
EN
63
EKB2
Config
Tool
Menu path:
Battery level: OK → CONFIGURATION → OK → aaaa → OK → WIRELESS DEVICES → OK →
wless-dev wless-id → OK → BATTERY
Wireless signal: OK → CONFIGURATION → OK → aaaa → OK → WIRELESS DEVICES → OK →
wless-dev wless-id → OK → SIGNAL
Error rate: OK → CONFIGURATION → OK → aaaa → OK → WIRELESS DEVICES → OK → wlessdev wless-id → OK → ERROR RATE
Firmware version: OK → CONFIGURATION → OK → aaaa → OK → WIRELESS DEVICES → OK →
wless-dev wless-id → OK → FW RELEASE
Value: aaaa – 4-digit administrator password; wless-dev – wireless device model; wless-id
– 8-character wireless device ID code.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
The system supports up to 16 wireless devices. To view the number of unoccupied wireless device slots in the system, please refer to the
following configuration methods
View unoccupied
wireless device slots
SMS
Config
Tool
SMS text message content:
ssss_STATUS_FREE
Example: 1111_STATUS_FREE
This operation may be carried out from the PC using the ELDES Configuration Tool software.
19.3. Wireless Signal Status Monitoring
If the wireless signal is lost due to poor signal strength or low battery power on a certain wireless device and does not restore within 1-hour
period (EN 50131-1 Grade 2 requirement), the system will cause an alarm. This event is identified as Wireless Signal Loss. By default, in­
dicated as Tamper x * in the SMS text message (x = tamper number; * = wireless signal loss). The user will also be notified by SMS text
message as soon as the wireless signal is restored.
ELDES Configuration Tool software indicates a timer of the last Test Time signal delivered by a paired and unpaired wireless device. The
software will also warn you if the delivery of the Test Time signal is delayed for a time period 3 times longer than the Test Time period of a
paired wireless device. In case the Test Time signal delivery of an unpaired wireless device is delayed for more than 1,5 minute, a warning
will follow and the icon of such wireless device will be removed from the software’s interface in 10 seconds.
19.4. Disabling and Enabling Siren if Wireless Signal is Lost
If a wireless device loses its wireless signal for 1 hour or longer, the system will send notification by SMS text message to user phone number and activate the siren/bell. By default, the siren will not be activated when wireless signal is lost. To enable/disable this feature, please
refer to the following configuration methods.
Enable Siren if
Wireless Signal is Lost
Disable Siren if
Wireless Signal is Lost
64
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → SIREN SETTINGS
→OK → SRN IF WLESS LOSS → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 76 and parameter status value:
76 1 #
Example: 761#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → SIREN SETTINGS
→OK → SRN IF WLESS LOSS → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM264 V3.3
EKB3
Enter parameter 76 and parameter status value:
76 0 #
Example: 760#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
19.5. EWT1 - Wireless Transmitter-Receiver
Wireless transmitter-receiver EWT1 is an add-on module for ESIM264 system. It enables wireless transmission through alarm system ESIM264
and ELDES wireless devices, such as: wireless magnetic door contacts/shock sensors, wireless zone and PGM output expansion modules,
wireless indoor sirens, wireless outdoor sirens,, wireless smoke detectors and wireless keyfobs.
EWT1 enables ESIM264 alarm system to connect up to 16 wireless devices at a time. Maximum wireless connection range is 150m (492.13ft)
(in open areas).
19.5.1. Electrical and Mechanical Characteristics
Wireless band
ISM868/ISM915
Dimensions
68x38x18mm (2.72x1.50x0.71in)
Operating temperature range
-20...+55°C (-4... 131°F)
Wireless communication range
Up to 30m (98.43ft) in premises;
up to 150m (492.13ft) in open areas
Maximum number of wireless devices
16
19.5.2. Installation
40
ANTENNA SMA
LED
EWT1
ESIM264
1.
Disconnect ESIM264 alarm system mains power and backup battery.
2.
Insert EWT1 pins into appropriate ESIM264 slots.
3.
Mount the antenna to EWT1. It is not recommended to install the antenna inside the metal enclosure.
4. Power up ESIM264 system.
5.
EWT1 is ready to use with ESIM264 system.
MANUAL ELDES ESIM264 V3.3
EN
65
19.6. EWF1 - Wireless Smoke Detector
Main features:
• Photoelectric sensor for slow smouldering fires
• TEST button
• Non-radioactive technology for environmental friendly
• High and stable sensitivity
• Quick fix mounting plate for easy installation
• LED operation indicator
• Built-in speaker for audio alarm indication
• Auto-reset when smoke clears
For more details on EWF1 wireless smoke detector, please refer to the user manual of the device.
41
SIREN
FRONT SIDE
BACK SIDE
TEST button
D O N OT PA
I
NT
TAMPER
switch
RESET button
BATTERY
LED indicator
19.6.1. Interconnection
The interconnection feature automatically links all wireless smoke detectors that are paired with the alarm system. When any EWF1 detects smoke, it will sound the built-in siren and send the signal to the alarm system resulting in an instant alarm followed by built-in siren
sound caused by the rest of EWF1 wireless smoke detectors. EWF1 device that detected smoke will auto-reset when the smoke clears,
while the rest of EWF1 smoke detectors will continue to sound in accordance with the set time period (by default - 30 seconds).
By default, the interconnection feature is enabled and the siren alarm duration is 30 seconds. To manage these parameters, please refer
to the following configuration methods.
Disable
interconnection
Enable
interconnection
EKB2
EKB3
Enter parameter 50 and parameter status value:
50 0 #
Example: 500#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
66
EN
Menu path:
OK → iiii → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS → OK → EWF1 SIREN
INTERC. → OK → DISABLE → OK
Value: iiii – 4-digit installer code.
Menu path:
OK → iiii → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS → OK → EWF1 SIREN
INTERC. → OK → ENABLE → OK
Value: iiii – 4-digit installer code.
Enter parameter 29 and parameter status value:
50 1 #
Example: 501#
MANUAL ELDES ESIM264 V3.3
Config
Tool
Set EWF1 siren alarm
duration
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: The maximum supported EWF1 siren alarm duration is 255 seconds (4 mins. 15 secs.) even if the system‘s alarm duration value is longer.
NOTE: System‘s alarm duration has a higher priority against the EWF1 siren alarm duration, therefore EWF1 will sound as long as the
system‘s alarm duration set up, unless the set up value for EWF1 siren alarm duration is shorter.
For more details on EWF1 wireless smoke detector, please refer to the user manual of the device.
MANUAL ELDES ESIM264 V3.3
EN
67
20. WIRED SIREN/BELL
When the system is in alarm state, the siren/bell will sound until the set time (By default – 1 minute) expires or until the system is disarmed.
To set the alarm duration, please refer to the following configuration methods.
Set alarm duration
View alarm duration
SMS
SMS text message content:
ssss_SIREN:t
Value: ssss – 4-digit SMS password; t – alarm duration, range – [0... 5] minutes.
Example: 1111_SIREN:4
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → ALARM DURATION → OK → tt → OK
Value: aaaa – 4-digit administrator password; tt – alarm duration, range – [1... 10] minutes.
EKB3
Enter parameter 10 and alarm duration:
10 tt #
Value: tt – alarm duration, range – [00... 10] minutes.
Example: 1007#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SIREN
Value: ssss – 4-digit SMS password
Example: 1111_SIREN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → ALARM DURATION
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
For siren/bell wiring diagram, please refer to 2.3.3. Siren.
NOTE: 0 value disables the siren/bell.
NOTE: Due to battery power saving reasons, the wireless siren may sound for up 6 minutes max. regardless of the set system alarm
duration time, even if it is set longer than 6 minutes.
68
EN
MANUAL ELDES ESIM264 V3.3
20.1. Bell Squawk
If enabled, the siren/bell indicates the completed system arming and disarming process. After the system is successfully armed, the siren/
bell will emit 2 short beeps and 1 long beep after the system is disarmed. To enable/disable the Bell Squawk feature, please refer to the
following configuration methods.
Enable Bell Squawk
Disable Bell Squawk
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → BELL SQUAWK → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 29 and parameter status value:
29 1 #
Example: 291#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → BELL SQUAWK → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 29 and parameter status value:
29 0 #
Example: 290#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
20.2. Indication by EWS2 - Wireless Outdoor Siren Indicators
When enabled, the built-in LED indicators of EWS2 wireless outdoor siren will flash during the alarm. To enable/disable this feature, please
refer to the following configuration methods.
Enable EWS2 LED
indication
Disable EWS2 LED
indication
EKB2
EKB3
Enter parameter 88 and parameter status value:
88 1 #
Example: 881#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
MANUAL ELDES ESIM264 V3.3
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → EWS2 LED → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN SETTINGS
→ OK → EWS2 LED → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 88 and parameter status value:
88 0 #
Example: 880#
EN
69
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
20.3. Indication by EWS3 - Wireless Indoor Siren Indicators
When enabled, the built-in LED indicators of EWS3 wireless indoor siren will flash during the alarm. In the event of burglary, 24-hour or
tamper alarm, EWS3 will flash the blue LED indicators, while in case of a fire alarm, the device can flash the red LED indicator. To enable/
disable these features, please refer to the following configuration methods.
Enable EWS3 LED
indication
Disable EWS3 LED
indication
70
EN
EKB2
Menu path:
Burglary/24-hour/tamper alarm LED: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY
SETT INGS → OK → SIREN SETTINGS → OK → EWS3 ALARM → OK → ENABLE → OK
Fire alarm: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → SIREN
SETTINGS → OK → EWS3 FIRE LED → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 94/93 and parameter status value:
Burglary/24-hour/tamper alarm LED: 94 1 #
Fire alarm LED: 93 1 #
Example: 931#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EWS3
Menu path:
Burglary/24-hour/tamper alarm LED: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY
SETT INGS → OK → SIREN SETTINGS → OK → EWS3 ALARM → OK → DISABLE → OK
Fire alarm LED: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK →
SIREN SETTINGS → OK → EWS3 FIRE LED → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 94/93 and parameter status value:
Burglary/24-hour/tamper alarm LED: 94 0 #
Fire alarm LED: 93 0 #
Example: 940#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
21. BACKUP BATTERY, MAINS POWER STATUS MONITORING AND MEMORY
21.1. Backup Battery Status Monitoring
The system may come equipped with a backup battery maintaining power supply of the system when the mains power supply is temporally
lost. The implemented feature allows the system to perform a self-test on the backup battery and notify the listed user phone number by
SMS text message as well as to indicate system fault by the keypad (see 29. INDICATION OF SYSTEM FAULTS) if:
•
battery has failed and requires replacement – battery resistance is 2Ω or higher; self-tested every 24 hours.
•
battery power is running low – battery voltage is 10.5V or lower; constantly self-tested.
By default, all notifications regarding the backup battery status are enabled. To disable/enable a determined backup battery notification,
please refer to the following configuration methods.
Disable Battery Failed
notification
Enable Battery Failed
notification
Disable Low Battery
notification
Enable Low Battery
notification
MANUAL ELDES ESIM264 V3.3
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → BATTERY FAIL EVENT
→ OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 09 0 #
Example: 25090#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → BATTERY FAIL EVENT
→ OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 09 1 #
Example: 25091#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → LOW BATTERY EVENT
→ OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 06 0 #
Example: 25060#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → LOW BATTERY EVENT
→ OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EN
71
EKB3
Enter parameter 25, notification number and parameter status value:
25 061 #
Example: 25061#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
21.2. Mains Power Status Monitoring
If the household electricity is unstable in the system installation area, the system may temporally lose its power supply and continue operating on the backup battery power. The system supervises the mains power supply and notifies the listed user phone number by SMS text
message as well as indicates system fault condition on the keypad (see 29. INDICATION OF SYSTEM FAULTS) when the mains power
is lost. When the mains power restores, the system will notify the listed user phone number by SMS text message and the keypad will no
longer indicate system fault.
By default, system notification by SMS text message regarding mains power supply status is enabled. To disable/enable this notification,
please refer to the following configuration methods.
NOTE: In case of low back-up battery, the system will send the SMS text message to the user and transmit the data message to the monitoring station, but will NOT indicate a system fault on the keypad.
Disable mains power
loss notification
Enable mains power
loss notification
Disable mains power
restore notification
EKB2
EKB3
Enter parameter 25, notification number and parameter status value:
25 04 0 #
Example: 25040#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EN
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → MAIN PWR LOSS EV →
OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 04 1 #
Example: 25041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
72
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → MAIN PWR LOSS EV →
OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → MAIN PWR REST EV →
OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, notification number and parameter status value:
25 05 0 #
Example: 25050#
MANUAL ELDES ESIM264 V3.3
Config
Tool
Enable mains power
restore notification
EKB2
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → MAIN PWR REST EV →
OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 25, notification number and parameter status value:
25 05 1 #
Example: 25051#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, mains power loss and restore delay are 30 and 120 seconds respectively. To set a different mains power loss and restore delay
duration, please refer to the following configuration methods.
Set mains power
loss delay
Set mains power
restore delay
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → MAINS POWER
STATUS → OK → LOSS DELAY → OK → lllll → OK
Value: aaaa – 4-digit administrator password; lllll – mains power loss delay duration, range
- [0... 65535] seconds.
EKB3
Enter parameter 70 and loss delay duration:
70 lllll #
Value: lllll – mains power loss delay duration, range - [0... 65535] seconds.
Example: 7043#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → MAINS POWER
STATUS → OK → RESTORE DELAY → OK → rrrrr → OK
Value: aaaa – 4-digit administrator password; rrrrr – mains power restore delay duration,
range - [0... 65535] seconds.
EKB3
Enter parameter 71 and restore delay duration:
71 rrrrr #
Value: rrrrr – mains power restore delay duration, range - [0... 65535] seconds.
Example: 71150#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
21.3. Memory
The configuration settings and event log records are stored in a built-in EEPROM memory, therefore even if the system is fully shut down,
the configuration and event log remain. For more details regarding the event log, please refer to 28. EVENT LOG
MANUAL ELDES ESIM264 V3.3
EN
73
22. GSM CONNECTION STATUS MONITORING
The system supervises the GSM connection every 10 minutes. When the GSM connection loss is detected, the system indicator NETWORK
will light OFF and the system will attempt to restore the GSM connection. In case the system fails to restore the GSM connection within
a 3-min­ute period (by default), the keypad will indicate the system fault condition (see 29. INDICATION OF SYSTEM FAULTS) and the
system will continue the attempt to restore the GSM connection. In addition, the system may turn ON a determined PGM output to indicate
the GSM connection loss fault (by default - disabled).
Once the GSM connection is restore, the keypad will no longer indicate the system fault condition, while the specified PGM output will turn
OFF.
By default, the PGM output for GSM signal loss indication is not set. To set the PGM output and delay duration for GSM signal loss indication,
please refer to the following configuration method.
Manage GSM signal
loss indication by PGM
output
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
23. PARTITIONS
ESIM264 system comes equipped with a partitioning feature that can divide the alarm system into two independently controlled areas
identified as Partition 0 through 1, which are all supervised by one alarm system unit. Partitioning can be used in installations where shared
alarm system is more practical, such as a house and a garage or within a single multi-storey building. When partitioned, each system element, like zone, user phone number, keypad, user code, iButton key and wireless keyfob can be assigned to one of the partitions. The user
will then be able to arm/disarm the system partition that the zones and arm/disarm method are assigned to.
23.1. Zone Partition
Zone partition determines which system partition (-s) the zone will operate in.
Set zone partition
EKB2
Menu path:
On-board zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ONBOARD
ZONES → OK → ZONE 1... 12 → OK → PARTITION → OK → PARTITION0... 1 → OK
Wireless zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → WIRELESS
ZONES → OK → WLESS ZONE 1... 16 → OK → PARTITION → OK → PARTITION0... 1 → OK
Keypad zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → KEYPAD
ZONES → OK → KEYPAD 1... 4 ZONE → OK → PARTITION → OK → PARTITION0... 1 → OK
EPGM1 zone: OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → EPGM1 ZONES →
OK → EPGM1 ZONE 1... 16 → OK → PARTITION → OK → PARTITION0... 1 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 57, zone number and partition number:
57 nn p #
Value: nn – zone number, range – [01... 44]; p – partition number, range – [0... 1].
Example: 57031#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
23.2. User Phone Number Partition
User phone number partition determines which system partition (-s) can be armed/disarmed from a certain user phone number by dialing
system’s phone number.
Set user phone
number partition
EKB2
EKB3
74
EN
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → CALL/SMS
SETTINGS → OK → USERS → OK → USER 1... 5 → OK → PARTITION → OK→ PARTITION0... 1
→ OK
Value: aaaa – 4-digit administrator password.
Enter parameter 59, user phone number slot and partition number:
59 us p #
Value: nn – zone number, range – [01... 44]; p – partition number, range – [0... 1].
Example: 59030#
MANUAL ELDES ESIM264 V3.3
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
23.3. Keypad Partition and Keypad Partition Switch
Keypad partition determines which system partition the keypad will operate in. To identify which partition the keypad is operating in:
•
EKB2 – Refer to partition name (by default – PART0) indicated in home screen view.
•
EKB3 – Refer to the location of the illuminated indicator
represent Partition 0 and Partition 1 respectively.
on the keypad. The indicator will be illuminated under section A or B, which
The keypad must be assigned to the same partition as the user code (see 23.4. User Code Partition) in order to arm/disarm the system
by the keypad. For more details on system arming/disarming by the keypad, please refer to 12.3. EKB2 Keypad and User Code and 12.4.
EKB3 Keypad and User Code.
Set keypad partition
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → KEYPAD
PARTITION → OK → KEYPAD PARTITION → OK → KEYPAD 1... 4 → OK → PARTITION 0... 1 →
OK
Value: aaaa – 4-digit administrator password;
EKB3
Enter parameter 51, keypad slot and partition number:
51 kk p #
Value: kk – keypad slot, range – [01... 04];p – partition number, range – [0... 1];
Example: 51041#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Keypad partition switch allows to quickly change the keypad partition. When the keypad partition is changed and when 1 minute after the
last key-stroke/key-touch expires, the system will return to the assigned keypad partition. Typically, this feature is used for viewing arm/
disarm status and alarms of a different partition or when arming/disarming a different system partition by EKB2/EKB3 keypad than the
keypad is assigned to.
By default, keypad partition switch is disabled. To enable/disable this feature, please refer to the following configuration methods.
Enable keypad
partition switch
Disable keypad
partition switch
EKB2
EKB3
Enter parameter 77 and parameter status value:
77 1#
Example: 771#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
EKB3
MANUAL ELDES ESIM264 V3.3
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → KEYPAD
PARTITION → OK → PARTITION SWITCH → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → KEYPAD
PARTITION → OK → PARTITION SWITCH → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 77 and parameter status value:
77 0 #
Example: 770#
EN
75
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Keypad partition switch can only be used when the system is partitioned.
23.4. User Code Partition
User code partition determines which system partition can be armed/disarm using a certain user code. User code must be assigned to the
same partition as the keypad (see 23.3. Keypad Partition and Keypad Partition Switch) in order to arm/disarm the system by EKB2/
EKB3 keypad . For more details on system arming/disarming by the keypad, please refer to 12.3. EKB2 Keypad and User Code and 12.4.
EKB3 Keypad and User Code.
Set user code partition
EKB2
Menu path:
User code 1... 16: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (1-16) → OK → USER
PASSWORD 1... 16 → OK → PARTITION → OK → PARTITION0... 1 → OK
User code 17... 30: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS →
OK → PASSWORDS → OK → USER PASSWORDS → OK → USER PSW (17-30) → OK → USER
PASSWORD 17... 30 → OK → PARTITION → OK → PARTITION0... 1 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 87, user code and partition number:
87 uuuu p #
Value: uuuu – 4-digit user code; p – partition number, range – [0... 1].
Example: 8711110#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
23.5. iButton Key Partition
iButton key partition determines which system partition can be armed/disarmed using a certain key. iButton key must be assigned to the
partition (-s) that the user desires to arm. For more details on system arming/disarming by iButton key, please refer to 12.5. iButton Key.
Set iButton key
partition
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → IBUTTON KEYS → OK → IBUTTON 1... 5 → OK →
PARTITION → OK → PARTITION0... 1 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 60, iButton key slot and partition value:
60 ii p #
Value: ii – iButton key slot, range – [01... 05]; p – partition number, range – [0... 1].
Example: 60051#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
23.6. EWK1/EWK2 Wireless Keyfob Partition
EWK1/EWK2 wireless keyfob partition determines which system partition can be armed/disarmed using a certain EWK1/EWK2 wireless
keyfob. For more details on system arming/disarming by EWK1/EWK2 wireless keyfob, please refer to 12.6. EWK1/EWK2 Wireless Keyfob.
Set EWK1/EWK2
partition
76
EN
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
24. TEMPERATURE SENSOR
The system may be equipped with a temperature sensor intended for temperature measurement in the surrounding area. This feature
allows to monitor the temperature in real-time and receive a notification by SMS text message to the listed user phone number when the
set temperature boundaries are exceeded.
24.1. Adding, Removing and Replacing Temperature Sensors
To add a temperature sensor to the system, do the following:
a) Shutdown the system.
b) Wire up the temperature sensor to the 1-Wire interface terminals (see 2.3.5. Temperature Sensor and iButton Key Reader for
temperature sensor wiring diagram).
c)
Power up the system.
The real-time temperature value of the temperature sensor is included in the Info SMS text message (see 26. SYSTEM INFORMATION.
INFO SMS) as well as it is indicated in the home screen view of EKB2 keypad.
To view the real-time temperature value measured by the temperature sensor, please refer to the following configuration methods.
View real-time
temperature value
SMS
EKB2
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
Refer to home screen view on the keypad.
24.2. Setting Up MIN and MAX Temperature Boundaries. Temperature Info SMS
The system supports an SMS text message identified as the Temperature Info SMS, which is automatically delivered to the listed user
phone number if the specified minimum (MIN) or maximum (MAX) temperature boundary is exceeded.
To set the MIN and MAX temperature boundaries, please refer to the configuration methods.
Set MIN and MAX
temperature
boundaries
SMS
EKB2
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
SMS text message content:
ssss_TEMP:mnn:mxx
Value: ssss – 4-digit SMS password; mnn – MIN boundary, range – [-55... 125] C; mxx - MAX
boundary, range – [-55... 125] C.
Example: 1111_TEMP:-5:28
Menu path:
MIN: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MIN → OK → mnn → OK
MAX: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MAX → OK → mxx → OK
Value: aaaa – 4-digit administrator password; mnn – MIN boundary, range – [-55... 125] C;
mxx - MAX boundary, range – [-55... 125] C.
Keys P1 or P2 are used to enter minus character, e.g. -20.
Enter parameter 19 and temperature boundary value:
19 mnn mxx #
Value: mnn – MIN boundary, range – [-55... 125] C; mxx - MAX boundary, range – [-55... 125]
C. 00 value stands for minus character, e. g. 0020 = -20
Example: 19001532#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
77
View MIN and
MAX temperature
boundaries
SMS
EKB2
Config
Tool
SMS text message content:
ssss_TEMP
Value: ssss – 4-digit SMS password.
Example: 1111_TEMP
Menu path:
MIN: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MIN
MAX: OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK →
TEMPERATURE SENSOR → OK → TEMP. MAX
Value: aaaa – 4-digit administrator password.
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, Temperature Info SMS is enabled. To disable/enable it, please refer to the following configuration methods.
Disable Temperature
Info SMS
SMS
EKB2
EKB3
Config
Tool
Enable Temperature
Info SMS
EKB2
EKB3
Config
Tool
78
EN
SMS text message content:
ssss_TEMP:00:00
Value: ssss – 4-digit SMS password.
Example: 1111_TEMP:00:00
Menu path:
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → DISABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 14 0 # - Temperature fallen
25 15 0 # - Temperature exceeded
Example: 25140#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → ENABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 25, event number and parameter status value:
25 14 1 # - Temperature fallen
25 15 1 # - Temperature exceeded
Example: 25151#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
25. REMOTE LISTENING AND 2-WAY VOICE COMMUNICATION
ESIM264 comes equipped with a microphone that allows the user to listen on his mobile phone to what is happening in the secured area.
By installing one of the audio module EA2, the user will be able to have a 2-way voice communication (see 31.3.2. EA2 – Audio Output
Module with Amplifier). Remote listening and 2-way voice communication can op­erate under the following conditions:
•
The system makes a phone call to a listed user phone number in case of alarm and the user answers the call.
•
The user initiates remote listening by sending the SMS text message, the system makes a phone call to the user phone number that the
SMS text message was sent from and the user answers the call.
Initiate remote
listening
SMS
SMS text message content:
ssss_MIC
Value: ssss – 4-digit administrator password
Example: 1111_MIC
Set microphone gain
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → GSM AUDIO → OK
→ MICROPHONE GAIN → OK → mg → OK
Value: aaaa – 4-digit administrator password; mg – microphone gain, range – [0... 15].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → GSM AUDIO → OK
→ SPEAKER LEVEL → OK → sl → OK
Value: aaaa – 4-digit administrator password; sl – speaker level, range – [0... 85].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Set speaker level
ATTENTION: Phone calls to the listed user phone number in case of alarm are disabled by force when MS mode is enabled
(see 30. MONITORING STATION).
MANUAL ELDES ESIM264 V3.3
EN
79
26. SYSTEM INFORMATION. INFO SMS
The system supports an informational SMS text message identified as the Info SMS, which can be delivered upon request. Once requested,
the system will reply with Info SMS that provides the following:
•
System date and time.
•
System status: partition armed (ON)/disarmed (OFF).
•
GSM signal strength.
•
Mains power supply status.
•
Temperature of the area surrounding the temperature sensor (if any).
•
State of zones (OK/alarm).
•
Name and status (ON/OFF) of PGM outputs.
Request for system
information
SMS
Config
Tool
SMS text message content:
ssss_INFO
Value: ssss – 4-digit SMS password.
Example: 1111_INFO
This operation may be carried out from the PC using the ELDES Configuration Tool software.
26.1. Periodic Info SMS
By default, the system sends Info SMS to the listed user phone number periodically once a day at 11:00 (frequency – 1 day; time – 11). The
mini­mum period is every 1 hour (frequency – 0 days; time – 1). Typically, this feature is used to verify the power supply and online status
of the system.
To set a different frequency and time or disable periodic Info SMS, please refer to the following configuration methods.
Set periodic Info SMS
frequency and time
SMS
EKB2
EKB3
Config
Tool
Disable periodic Info
SMS
SMS
EKB2
80
EN
SMS text message content:
ssss_INFO:fff:it
Value: ssss – 4-digit SMS password; fff – frequency, range – [00... 99] days; it – time, range
– [01... 23].
Example: 1111_INFO:3.15
Menu path:
Frequency: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → FREQUENCY (DAYS) → fff → OK
Time: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → TIME → it → OK
Value: aaaa – 4-digit administrator password; fff – frequency, range – [00... 125] days; it –
time, range – [01... 23].
Enter parameter 11, time and frequency:
11it fff #
Value: it – time, range – [01... 23]; fff – frequency, range – [00... 125] days.
Example: 110412#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_INFO:00:00
Example: 1111_INFO:00.00
Menu path:
Frequency: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → FREQUENCY (DAYS) → 0 → OK
Time: OK → CONFIGURATION → OK → aaaa → PRIMARY SETTINGS → OK → INFO SMS
SCHEDULER → OK → TIME → 0 → OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM264 V3.3
EKB3
Enter parameter 11, time and frequency:
11 00 00 #
Example: 110000#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
ATTENTION: Unlike Info SMS upon request, periodic Info SMS text message does not included zone states, PGM output names and status.
MANUAL ELDES ESIM264 V3.3
EN
81
27. SYSTEM NOTIFICATIONS
In case of a certain event, the system attempts to send an SMS text message to the first listed user phone number only. If the user phone
number is unavailable and the system fails to receive the SMS delivery report during 45 seconds, it will attempt to send the SMS text message to the next listed user phone number, assigned to the same partition as the previous one. The user phone number may be unavailable
due to the following reasons:
•
mobile phone was switched off.
•
was out of GSM signal coverage.
The system will continue sending the SMS text message to the next listed user phone numbers in the priority order until one is available.
The system sends the SMS text message only once and will not return to the first user phone number if the last one was unavailable.
The following table provides the description of system notifications by SMS text message sent to the user phone number.
Seq. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Event
General alarm
System disarmed
System armed
Mains power loss
Mains power restore
Low battery
Periodical info
Tamper alarm
Battery failed
Description
SMS text message sent to the user in case of system alarm occurrence.
SMS text message sent to the user about disarmed system.
SMS text message sent to the user regarding armed system.
SMS text message sent to the user in case the mains power is lost.
SMS text message sent to the user in case the mains power supply is restored
SMS text message sent to the user in case the backup battery voltage is 10.5V or lower
Info SMS text message sent to the user periodically by the set values.
SMS text message sent to the user in case of tamper violation. Indicated as Tamper x.
SMS text message sent to the user in case the backup battery resistance is 2Ω or higher (battery
requires replacement).
System started
SMS text message sent to the user on system startup.
Wireless signal loss
SMS text message sent to the user in case the wireless signal is lost. Indicated as Tamper x *.
Temperature fallen
SMS text message sent to the user in case of temperature deviation by the set MIN value.
Temperature exceeded SMS text message sent to the user in case of temperature deviation by the set MAX value.
System shutdown
When the system is running on backup battery power, it sends the SMS text message to the user
before the backup battery power is fully depleted.
ATTENTION: The following methods provide the configuration of the master parameters, which override the notification parameters described in 12.9. Disabling and Enabling Arm/Disarm Notifications.
To disable/enable a certain system notification, please refer to the following configuration methods.
Disable system
notification
82
EN
EKB2
Menu path:
General alarm: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
ALARM EVENT → OK → DISABLE → OKK
System armed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
ARMED EVENT → OK → DISABLE → OK
System disarmed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
DISARMED EVENT → OK → DISABLE → OK
Mains power loss: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
MAIN PWR LOSS EV → OK → DISABLE → OK
Mains power restore: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
MAIN PWR REST EV → OK → DISABLE → OK
Low battery: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → LOW
BATTERY EVENT → OK → DISABLE → OK
Battery failed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
BATTERY FAIL EVENT → OK → DISABLE → OK
Periodical info: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
PERIODIC SMS EV → OK → DISABLE → OK
Tamper alarm: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TAMPER EVENT → OK → DISABLE → OK
System started: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
SYSTEM STARTED EV → OK → DISABLE → OK
Wireless signal loss: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
WLESS SIGN LOSS EV → OK → DISABLE → OK
System shutdown: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
SYSTEM SHUTDOWN EV → OK → DISABLE → OK
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → DISABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
MANUAL ELDES ESIM264 V3.3
EKB3
Config
Tool
Enable system
notification
MANUAL ELDES ESIM264 V3.3
EKB2
Enter parameter 25, event number and parameter status value:
25 01 0 # - General alarm
25 02 0 # - System armed
25 03 0 # - System disarmed
25 04 0 # - Mains power loss
25 05 0 # - Mains power restore
25 06 0 # - Low battery
25 07 0 # - Battery failed
25 08 0 # - Periodical info
25 10 0 # - Tamper alarm
25 11 0 # - System started
25 12 0 # - Wireless signal loss
25 13 0 # - System shutdown
25 14 0 # - Temperature fallen
25 15 0 # - Temperature exceeded
Example: 25040#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
General alarm: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
ALARM EVENT → OK → ENABLE → OKK
System armed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
ARMED EVENT → OK → ENABLE → OK
System disarmed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
DISARMED EVENT → OK → ENABLE → OK
Mains power loss: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
MAIN PWR LOSS EV → OK → ENABLE → OK
Mains power restore: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
MAIN PWR REST EV → OK → ENABLE → OK
Low battery: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK → LOW
BATTERY EVENT → OK → ENABLE → OK
Battery failed: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
BATTERY FAIL EVENT → OK → ENABLE → OK
Periodical info: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
PERIODIC SMS EV → OK → ENABLE → OK
Tamper alarm: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TAMPER EVENT → OK → ENABLE → OK
System started: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
SYSTEM STARTED EV → OK → ENABLE → OK
Wireless signal loss: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
WLESS SIGN LOSS EV → OK → ENABLE → OK
System shutdown: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
SYSTEM SHUTDOWN EV → OK → ENABLE → OK
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK →
TEMP LOW EVENT → OK → ENABLE → OK
Temperature exceeded: OK → CONFIGURATION → OK → aaaa → OK → SMS MESSAGES → OK
→ TEMP HIGH EVENT → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
EN
83
EKB3
Config
Tool
Enter parameter 25, event number and parameter status value:
25 01 1 # - General alarm
25 02 1 # - System armed
25 03 1 # - System disarmed
25 04 1 # - Mains power loss
25 05 1 # - Mains power restore
25 06 1 # - Low battery
25 07 1 # - Battery failed
25 08 1 # - Periodical info
25 10 1 # - Tamper alarm
25 11 1 # - System started
25 12 1 # - Wireless signal loss
25 13 1 # - System shutdown
25 14 1 # - Temperature fallen
25 15 1 # - Temperature exceeded
Example: 25061#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
27.1. SMSC (Short Message Service Center) Phone Number
An SMS center (SMSC) is a GSM network element, which routes SMS text messages to the destination user and stores the SMS text message
if the recipient is unavailable. Typically, the phone number of the SMS center is already stored in the SIM card provided by the GSM operator.
If the user fails to receive replies from the system, the SMS center phone number, provided by the GSM operator, must be set manually.
Set SMSC phone
number
SMS
SMS text message content:
ssss_SMS_+ttteeellnnuumm
Value: ssss – 4-digit SMS password; ttteeellnnuumm – up to 15 digits SMSC phone number.
Example: 1111_SMS_+4417031111111
ATTENTION: Before setting the SMSC phone number, please check the credit balance of the system’s SIM card. The system will fail to reply
if the credit balance is insufficient.
84
EN
MANUAL ELDES ESIM264 V3.3
28. EVENT LOG
This feature allows to chronologically register up to 500 timestamped records regarding the following system events:
•
System start.
•
System arming/disarming.
•
Zone violated/restored.
•
Tamper violated/restored.
•
Zone bypassing.
•
Wireless device management.
•
Temperature deviation by MIN and MAX boundaries.
•
System faults.
The event log is of LIFO (last in, first out) type that allows the system to automatically replace the oldest records with the the latest ones.
View event log
EKB2
Menu path:
OK → VIEW EVENT LOG → OK → uuuu → OK
Value: uuuu - 4-digit user code.
To export the event log to .log file or clear it, please refer to the following configuration method.
Export/clear event log
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, event log is enabled. To disable/enable this feature, please refer to the following configuration methods.
Disable event log
Enable event log
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EVENT LOG → OK
→ DISABLE → OK
EKB3
Enter parameter 36 and parameter status value:
36 0 #
Example: 360#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETTINGS → OK → EVENT LOG → OK
→ ENABLE → OK
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Enter parameter 36 and parameter status value:
36 1 #
Example: 361#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
85
29. INDICATION OF SYSTEM FAULTS
The system comes equipped with self-diagnostic feature allowing to indicate the presence of any system fault by the keypad.
Message TBL displayed in the home screen view indicates presence of system faults. In order to find out more on the particular system problem, please open menu section TROUBLES. The description on each system problem is indicated in the table
EKB2
below.
Menu path:
OK → TROUBLES
Name
VIOLATED TAMPER
BATTERY FAILED
Description
One or more tampers are violated
Backup battery requires replacement - backup
battery resistance is 2Ω or higher
Mains power supply is lost
Date/time not set
GSM connection is lost
MAIN PWR FAILURE
DATE/TIME NOT SET
GSM ERROR
1. Steady ON or flashing indicator
EKB3
Indication
Steady ON
Flashing
represents certain system faults. For more details, please refer to the following table below.
Description
One or more tampers are violated; other system faults (see below)
One or more high-numbered zones (Z13-Z76) are violated (see below)
2. In order to find out more on a certain system fault, please enter the following command.
Enter command:
#
View system faults
After this procedure the keypad will illuminate red indicators for 15 seconds. The description of each indication is provided in the
table below.
LED #
Description
1
2
3
4
5
One or more tampers are violated
Backup battery requires replacement - backup battery resistance is 2Ω or higher
Mains power supply is lost
Date/time not set
One or more high-numbered zones (Z13-Z44) are violated (see step #3)
6
GSM connection is lost
3. In order to find out the violated high-numbered zone, please enter the following command and refer to the table below.
View violated highnumbered zones
Enter command:
1
4. In order to find out which particular tamper is violated, please enter the following command. In case there is a combination of
flashing and illuminated red indicators on the keypad, please refer to the table below in order to find out the violated high-numbered tamper (Tamper 13 - 44).
Enter command:
2
View violated tampers
The following table provides the combinations of red indicators belonging to a certain indicator section (A or B) on the keypad.
The combination of the flashing red indicator in section A and illuminated (steady ON) red indicator in section B represents the
respective number of a violated high-numbered zone or tamper.
A (flashing)
LED #1
LED #2
LED #3
LED #4
LED #5
LED #6
86
EN
B (steady ON)
LED #7
LED #8
LED #9
LED #10
LED #11
LED #12
Z13
Z14
Z15
Z16
Z17
Z18
Z19
Z20
Z21
Z22
Z23
Z24
Z25
Z26
Z27
Z28
Z29
Z30
Z31
Z32
Z33
Z34
Z35
Z36
Z37
Z38
Z39
Z40
Z41
Z42
Z43
Z44
MANUAL ELDES ESIM264 V3.3
30. MONITORING STATION
The system can be configured to report events to the monitoring station by transmitting data messages to the monitoring station. The
system connects to the monitoring station when the MS (Monitoring Station) mode is enabled.
When using the MS mode, the data messages transmitted to the monitoring station (see 30.1. Data Messages - Events) will gain the
highest priority for the delivery, therefore based on the communication method (see 30.2. Communication), a constant and stable connection with the monitoring station must be ensured. In case of connection failure, the system will attempt to restore the connection
and if the monitoring is unavailable for a lengthy period of time, the system might consume a large amount of voice calls/data resulting in
additional charges applied by the GSM operator according to the cell phone service plan.
Enable MS mode
Disable MS mode
SMS
SMS text message content:
ssss_SCNSET:ON
Value: ssss – 4-digit SMS password.
Example: 1111_SCNSET:ON
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → MS MODE → OK →
ENABLE → OK
Value: aaaa – 4-digit administrator password
EKB3
Enter parameter 23 and parameter status value:
23 1 #
Example: 231#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SCNSET:OFF
Value: ssss – 4-digit SMS password.
Example: 1111_SCNSET:OFF
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → MS MODE → OK →
DISABLE → OK
Value: aaaa – 4-digit administrator password
EKB3
Enter parameter 23 and parameter status value:
23 0 #
Example: 230#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Account is a 4-digit number (By default – 9999) required to identify the alarm system unit by the monitoring station.
Set account
EKB2
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → ACCOUNT → OK → cccc
→ OK
Value: aaaa – 4-digit administrator password; cccc – 4-digit account number.
Enter parameter 27 and account number:
27 cccc #
Value: cccc – 4-digit account number.
Example: 278853#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
87
ATTENTION: The system will NOT send any data to the monitoring station while remote connection, remote firmware update or remote
listening/2-way voice communication is in progress. However, during the remote connection session or remote listening/2-way voice communication process, the data messages will be queued up and transmitted to the monitoring station after the remote connection session or
remote listening/2-way voice communication process is over, while during the remote firmware update process NO data will be queued up
and all data messages will be lost.
ATTENTION: Phone calls to the listed user phone number in case of alarm are disabled by force when MS mode is enabled.
NOTE: Additional charges may apply for voice calls/data traffic based on your cell phone service plan when using the MS mode.
30.1. Data Messages – Events
The configuration of data messages is based on Ademco Contact ID protocol. The data messages can either be transmitted to the monitoring station alone or with duplication by SMS text message to listed user phone number. For more details on system notifications by SMS text
message, please refer to 27. SYSTEM NOTIFICATIONS.
Seq. No.
Contact ID® Code
Event
Description
1
1110
Fire alarm
Transmitted in case a zone of Fire type is violated.
2
3110
Fire restore
Transmitted in case a zone of Fire type is restored.
3
3121
Armed by user (Duress code) Transmitted in case the system is armed by Duress code.
4
1121
Disarmed by user (Duress
code)
Transmitted in case the system is disarmed by Duress code.
5
1130
Burglary alarm
Transmitted in case a zone of Delay (if not disarmed before entry delay
countdown is completed), Interior Follower or Instant type is violated.
6
3130
Burglary restore
Transmitted in case a zone of Delay (if not disarmed before entry delay
countdown is completed), Interior Follower or Instant type is restored.
7
1133
24-Hour zone alarm
Transmitted in case of zone of 24-Hour type is violated.
8
3133
24-Hour zone restore
Transmitted in case of zone of 24-Hour type is restored.
9
1144
Tamper alarm
Transmitted in case the tamper is violated.
10
3144
Tamper restore
Transmitted in case the tamper is restored.
11
1146
Panic/Silent zone alarm
Transmitted in case of zone of Panic/Silent type is violated.
12
3146
Panic/Silent zone restore
Transmitted in case of zone of Panic/Silent type is restored.
13
1158
Temperature risen
Transmitted in case of the temperature has increased above the MAX set
value.
14
1159
Temperature fallen
Transmitted in case of temperature has decreased below the MIN set value.
15
1301
Mains power loss
Transmitted in case the mains power is lost.
16
3301
Mains power restore
Transmitted in case the mains power is restored.
17
1302
Low battery
Transmitted in case the backup battery voltage is 10.5V or lower / the
wireless sensor battery level runs below 5%.
18
1308
System shutdown
When the system is running on backup battery power, it transmits the data
message before the backup battery power is fully depleted.
19
1309
Battery failed
Transmitted in case the backup battery resistance is 2Ω or higher.
20
1358
GSM connection failed
Transmitted in case the GSM connection is lost.
21
1381
Wireless signal loss
Transmitted in case the connection with any wireless device is lost.
22
3381
Wireless signal restore
Transmitted in case the connection with any wireless device is restored.
23
1401
Disarmed by user
Transmitted in case the system is disarmed.
24
3401
Armed by user
Transmitted in case the system is armed.
25
1456
Disarmed in Stay mode
Transmitted in case the system is disarmed in Stay mode.
26
3456
Armed in Stay mode
Transmitted in case the system is armed in Stay mode.
27
3463
SGS code entered
Transmitted in case the SGS code is entered.
28
3602
Test event/Kronos ping
Transmitted for system online status verification purposes.
29
3626
Date/time not set
Transmitted in case system date and time is not set.
30
1900
System started
Transmitted on system startup.
88
EN
MANUAL ELDES ESIM264 V3.3
The following table refers to user codes included in arm/disarm data messages.
Type
User Phone Number 1
User Phone Number 2
User Phone Number 3
User Phone Number 4
User Phone Number 5
iButton 1
iButton 2
iButton 3
iButton 4
iButton 5
User Code 1
User Code 2 or Arm/Disarm by Zone
User Code 3
User Code 4
User Code 5
ID
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
User Code 6
User Code 7
User Code 8
User Code 9
User Code 10
User Code 11
User Code 12
User Code 13
User Code 14
User Code 15
User Code 16
User Code 17
User Code 18
User Code 19
User Code 20
User Code 21
User Code 22
User Code 23
User Code 24
User Code 25
User Code 26
User Code 27
User Code 28
User Code 29
User Code 30
Remote Code (EGR100)
KeyFob 1
KeyFob 2
KeyFob 3
KeyFob 4
KeyFob 5
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
85
86
87
88
89
MANUAL ELDES ESIM264 V3.3
EN
89
Disable data message
EKB2
EKB3
Config
Tool
90
EN
Menu path:
General alarm/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → ALARM/RESTORE EV → OK → DISABLE → OK
Mains power loss/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK
→ DATA MESSAGES → OK → MAINS POWER L/R EV → OK → DISABLE → OK
Armed by user: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → ARMED EVENT → OK → DISABLE → OK
Disarmed by user: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → DISARMED EVENT → OK → DISABLE → OK
Battery failed: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → BATTERY FAIL EVENT → OK → DISABLE → OK
Test event: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → TEST EVENT → OK → DISABLE → OK
System started: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → SYSTEM STARTED EV → OK → DISABLE → OK
Wireless signal loss/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS →
OK → DATA MESSAGES → OK → WLESS SIGN LOSS EV → OK → DISABLE → OK
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → TEMP LOW EVENT → OK → DISABLE → OK
Temperature risen: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → TEMP HIGH EVENT → OK → DISABLE → OK
System shutdown: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES 2 → OK → SYSTEM SHUTDOWN EV → OK → DISABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 24, event number and parameter status value:
24 01 0 # – General alarm/restore
24 02 0 # – Mains power loss/restore
24 03 0 # – Armed by user
24 04 0 # – Disarmed by user
24 05 0 # – Battery failed
24 06 0 # – Test event
24 07 0 # – System started
24 08 0 # – Wireless signal loss/restore
24 09 0 # – Temperature fallen
24 10 0 # – Temperature risen
24 13 0 # – System shutdown
Example: 24080#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
Enable data message
EKB2
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Menu path:
General alarm/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → ALARM/RESTORE EV → OK → ENABLE → OK
Mains power loss/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK
→ DATA MESSAGES → OK → MAINS POWER L/R EV → OK → ENABLE → OK
Armed by user: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → ARMED EVENT → OK → ENABLE → OK
Disarmed by user: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → DISARMED EVENT → OK → ENABLE → OK
Battery failed: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → BATTERY FAIL EVENT → OK → ENABLE → OK
Test event: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → TEST EVENT → OK → ENABLE → OK
System started: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DATA
MESSAGES → OK → SYSTEM STARTED EV → OK → ENABLE → OK
Wireless signal loss/restore: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS →
OK → DATA MESSAGES → OK → WLESS SIGN LOSS EV → OK → ENABLE → OK
Temperature fallen: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → TEMP LOW EVENT → OK → ENABLE → OK
Temperature risen: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → TEMP HIGH EVENT → OK → ENABLE → OK
System shutdown: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
DATA MESSAGES → OK → SYSTEM SHUTDOWN EV → OK → ENABLE → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 24, event number and parameter status value:
24 01 1 # – General alarm/restore
24 02 1 # – Mains power loss/restore
24 03 1 # – Armed by user
24 04 1 # – Disarmed by user
24 05 1 # – Battery failed
24 06 1 # – Test event
24 07 1 # – System started
24 08 1 # – Wireless signal loss/restore
24 09 1 # – Temperature fallen
24 10 1 # – Temperature risen
24 13 1 # – System shutdown
Example: 24031#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
91
30.2. Communication
The system supports the following communication methods and protocols:
• GPRS network – EGR100, Kronos protocol.
• Voice calls (GSM audio channel) – Ademco Contact ID protocol.
• RS485 data channel.
• CSD (Cricuit Switched Data).
• SMS – Cortex SMS format.
Any communication method can be set as primary or backup connection. The user can set up to 4 backup connections in any sequence order.
Initially, the system communicates via primary connection with the monitoring station. By default, if the initial attempt to transmit data is
unsuccessful, the system will make additional attempts until the data is successfully delivered. If all attempts are unsuccessful, the system
will follow this pattern:
a) The system switches to the backup connection that follows in the sequence (presumably - Backup 1).
b) The system then attempts to transmit data by the backup connection.
c)
If the initial attempt is unsuccessful, the system will make additional attempts until the data is successfully delivered.
d) If the system ends up with all unsuccessful attempts, it will switch to the next backup connection in the sequence (presumably - Back­
up 2) and will continue to operate as described in the previous steps. The connection is considered unsuccessful under the following
conditions:
• GPRS network – The system has not received the ACK data message from the monitoring station within 40 seconds.
• Voice calls:
• The system has not received the “handshake” signal from the monitoring station within 40 seconds.
• The system has not received the “kissoff” signal from the monitoring station within 5 attempts each lasting 1 second.
• CSD – The system has not received the ACK data message from the monitoring station within 35 seconds.
• SMS – The system has not received the SMS delivery report from the SMSC (Short Message Service Center) within 45 seconds.
e) If one of the attempts is successful, the system will transmit all queued up data messages by this connection.
f)
The system then returns to the primary connection and attempts to transmit the next data messages by primary connection.
g) If the system ends up with all unsuccessful attempts by all connections, it will wait until the Delay after last communication attempt
time (By default – 600 seconds) expires and will return to the primary connection afterwards.
h) If a new data message, except Test Event (ping), is generated during Delay after last communication attempt time, the system will
immediately attempt to transmit it to the monitoring station, regardless of Delay after last communication attempt being in progress.
92
EN
MANUAL ELDES ESIM264 V3.3
PRIMARY
Makes up to 3 or 5 attempts to transmit data
All attempts failed
Switches to BACKUP 1
Makes up to 3 or 5 attempts to transmit data
All attempts failed
One of the attempts is successful
Switches to BACKUP 2
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Switches to BACKUP 3
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Switches to BACKUP 4
Transmits all queued up data
Makes up to 3 or 5 attempts to transmit data
Returns to PRIMARY
All attempts failed
One of the attempts is successful
Waits for 600 seconds
Transmits all queued up data
Delay after last communication attempt
Returns to PRIMARY
Returns to PRIMARY
NOTE: The number of attempts, indicated in the diagram, are default and depends on the determined communication method.
MANUAL ELDES ESIM264 V3.3
EN
93
Set primary connection
EKB2
EKB3
Config
Tool
Set backup connection
1... 4
EKB2
EKB3
Menu path:
GPRS network: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
PRIMARY CONNECTION → OK → GPRS → OK
Voice calls: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → PRIMARY
CONNECTION → OK → VOICE CALLS → OK
RS485: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → PRIMARY
CONNECTION → OK → RS485 → OK
CSD: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → PRIMARY
CONNECTION → OK → CSD → OK
SMS: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → PRIMARY
CONNECTION → OK → SMS → OK
connection not in use: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
PRIMARY CONNECTION → OK → N/A → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 48 and communication method number:
48 0 # – GPRS network
48 1 # – Voice calls
48 2 # – RS485
48 3 # – CSD
48 4 # – SMS
Example: 484#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Menu path:
GPRS network: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
BACKUP CONNECTION1... 4 → OK → GPRS → OK
Voice calls: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → BACKUP
CONNECTION1... 4 → OK → VOICE CALLS → OK
RS485: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → BACKUP
CONNECTION1... 4 → OK → RS485 → OK
CSD: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
BACKUP CONNECTION1... 4 → OK → CSD → OK
SMS: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → BACKUP
CONNECTION1... 4 → OK → SMS → OK
connection not in use: OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK →
BACKUP CONNECTION1... 4 → OK → N/A → OK
Value: aaaa – 4-digit administrator password.
Enter parameter 83, backup connection slot number and communication method
number:
83 bb 0 # – GPRS network
83 bb 1 # – Voice calls
83 bb 2 # – RS485
83 bb 3 # – CSD
83 bb 4 # – SMS
83 bb 5 # – connection not in use
Value: bb – backup connection slot number, range – [01... 04].
Example: 83031#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
If all attempts by all set connections are unsuccessful, the system will wait until the delay time (By default – 600 seconds) expires and will
attempt to transmit data to the monitoring station again starting with the primary connection.
94
EN
MANUAL ELDES ESIM264 V3.3
Set delay after last
communication
attempt
EKB2
EKB3
Config
Tool
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → DELAY LAST ATTEMPT
→ OK → aaapp → OK
Value: aaaa – 4-digit administrator password; aaapp – duration of delay after last attempt,
range – [0... 65535] seconds.
Enter parameter 69 and duration of delay after last attempt:
69 aaapp #
Value: aaapp – duration of delay after last attempt, range – [0... 65535] seconds.
Example: 69200#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: 0 value disables delay after last communication attempt.
NOTE: The system is fully compatible with Kronos NET/Kronos LT monitoring station software for communication via GPRS network. When
using a different monitoring station software, EGR100 middleware is required. EGR100 is freeware and can be downloaded at eldesalarms.
com/en/download. Alternatively, you can use ESR100 digital receiver. For more details, please refer to eldesalarms.com
30.2.1. GPRS Network
The system supports data transmission to the monitoring station via IP-based networks by GPRS network. The supported data formats are the
following:
• EGR100
• Kronos
To set up the system for data transmission via GPRS network, please follow the basic configuration steps:
1.
Enable MS Mode parameter (see 30. MONITORING STATION).
2.
Set 4-digit Account number (see 30. MONITORING STATION).
3.
Set server IP address, which is a public IP address of ESR100 digital receiver or the machine running EGR100 or Kronos monitoring station
software.
4.
Set public server port, which is a port of ESR100 digital receiver or the machine running EGR100 or Kronos monitoring station software.
5.
Select TCP or UDP protocol. UDP is highly recommended for EGR100 data format.
6.
Select data format: EGR100 or Kronos.
7.
In case EGR100 is selected, set 4-digit Unit ID number. Unit ID number can be identical to Account number.
8.
Set up APN, user name and password provided by the GSM operator. De­pending on the GSM operator, only APN might be required to set
up.
For detailed step-by-step instructions on how to establish the communication between ESIM264 alarm system and EGR100 middleware, please
refer to the middle-ware’s HELP file.
Set server IP address
SMS
SMS text message content:
ssss_SETGPRS:IP:add.add.add.add
Value: ssss – 4-digit SMS password; add.add.add.add – server IP address.
Example: 1111_SETGPRS:IP:65.82.119.5
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → SERVER IP → OK →
add.add.add.add → OK
Value: aaaa – 4-digit administrator password; add.add.add.add – server IP address.
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Enter parameter 40 and server IP address:
40 add add add add #
Value: add add add add – server IP address.
Example: 40065082119005#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
95
Set server port
SMS
EKB2
EKB3
Set DNS1 server IP
address
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → DNS1 → OK → add.
add.add.add → OK
Value: aaaa – 4-digit administrator password; add.add.add.add – DNS1 server IP address.
Enter parameter 41 and DNS1 server IP address:
41 add add add add #
Value: add add add add – DNS1 server IP address.
Example: 41065082119001#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → DNS2 → OK → add.
add.add.add → OK
Value: aaaa – 4-digit administrator password; add.add.add.add – DNS2 server IP address.
Enter parameter 42 and DNS2 server IP address:
42 add add add add #
Value: add add add add – DNS2 server IP address.
Example: 41065082119002#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SETGPRS:PROTOCOL:ptc
Value: ssss – 4-digit SMS password; ptc – protocol, range – [TCP... UDP].
Example: 1111_SETGPRS:PROTOCOL:UDP
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → PROTOCOL → OK →
TCP | UDP → OK
Value: aaaa – 4-digit administrator password.
EKB3
EN
Value: pprrt – server port number, range – [1... 65535].
Example: 443365#
EKB2
Config
Tool
96
Enter parameter 44 and server port number:
44 pprrt #
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB3
Set protocol
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → SERVER PORT → OK
→ pprrt → OK
Value: aaaa – 4-digit administrator password; pprrt – server port number, range – [1...
65535].
Config
Tool
EKB3
Set DNS2 server IP
address
SMS text message content:
ssss_SETGPRS:PORT:pprrt
Value: ssss – 4-digit SMS password; pprrt – server port number, range – [1... 65535].
Example: 1111_SETGPRS:PORT:5521
Enter parameter 43 and protocol number:
43 0 # - TCP
43 1 # - UDP
Example: 431#
MANUAL ELDES ESIM264 V3.3
NOTE: Kronos NET/Kronos LT software communicates via TCP protocol, while EGR100 middle-ware v1.2 and up supports both – TCP and UDP
protocols. However, TCP protocol is NOT recommend to use with EGR100.
Set protocol
Set DNS1 server IP
address
Set DNS2 server IP
address
Set data format as
Kronos or EGR100
Set APN
MANUAL ELDES ESIM264 V3.3
SMS
SMS text message content:
ssss_SETGPRS:PROTOCOL:ptc
Value: ssss – 4-digit SMS password; ptc – protocol, range – [TCP... UDP].
Example: 1111_SETGPRS:PROTOCOL:UDP
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → PROTOCOL → OK →
TCP | UDP → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 43 and protocol number:
43 0 # - TCP
43 1 # - UDP
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → DNS1 → OK → add.
add.add. add → OK
Value: aaaa – 4-digit administrator password; add.add.add.add – DNS1 server IP address.
EKB3
Enter parameter 41 and DNS1 server IP address:
41 add add add add #
Value: add add add add – DNS1 server IP address.
Example: 41065082119001#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → GPRS SETTINGS → OK → DNS2 → OK → add.
add.add. add → OK
Value: aaaa – 4-digit administrator password; add.add.add.add – DNS2 server IP address.
EKB3
Enter parameter 42 and DNS2 server IP address:
42 add add add add #
Value: add add add add – DNS2 server IP address.
Example: 42065082119002#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS
SMS text message content:
ssss_SETGPRS:APN:acc-point-name
Value: ssss – 4-digit SMS password; acc-point-name – up to 31 character APN (Access Point
Name) provided by the GSM operator.
Example: 1111_SETGPRS:APN:internet
EN
97
Config
Tool
Set user name
SMS
Config
Tool
Set password
SMS
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS:USER:usr-name
Value: ssss – 4-digit SMS password; usr-name – up to 31 character user name provided by
the GSM operator.
Example: 1111_USER:mobileusr
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS:PSW:password
Value: ssss – 4-digit SMS password; password – up to 31 character password provided by
the GSM operator.
Example: 1111_SETGPRS:PSW:mobilepsw
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station via GPRS network method is unsuccessful, the system will make
up to 2 additional attempts. If all attempts are unsuccessful, the system will switch to next backup connection that follows in the sequence
and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
EKB3
Config
Tool
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → GPRS SETTINGS → OK
→ GPRS ATTEMPTS → OK → att → OK
Value: aaaa – 4-digit administrator password; att – number of attempts, range – [1... 255].
Enter parameter 68 and number of attempts:
68 att #
Value: att – number of attempts, range – [01... 255].
Example: 6809#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
To report the online status, the system periodically transmits (By default – every 180 seconds) Test Event data message (ping) to the
monitoring station via GPRS network.
Set test period
EKB2
EKB3
Config
Tool
98
EN
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → GPRS SETTINGS → OK
→ TEST PERIOD → OK → tteessttpp → OK
Value: aaaa – 4-digit administrator password; tteessttpp – test period, range – [0... 65535]
seconds.
Enter parameter 46 and number of attempts:
46 tteessttpp #
Value: tteessttpp – test period, range – [0... 65535] seconds.
Example: 46120#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
MANUAL ELDES ESIM264 V3.3
NOTE: 0 value disables test period.
Unit ID is a 4-digit number (By default – 0000) required to identify the alarm system unit by ESR100 digital receiver or EGR100 middle-ware.
It is MANDATORY to change the default Unit ID before using ESR100 or EGR100.
Set unit ID
EKB2
EKB3
Config
Tool
View GPRS network
settings
SMS
Config
Tool
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → GPRS SETTINGS → OK
→ UNIT ID → OK → unid → OK
Value: aaaa – 4-digit administartor password; unid – 4-digit unit ID number.
Enter parameter 47 and unit ID number:
47 unid #
Value: unid – 4-digit unit ID number.
Example: 472245#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
SMS text message content:
ssss_SETGPRS?
Example: 1111_SETGPRS?
This operation may be carried out from the PC using the ELDES Configuration Tool software.
NOTE: Kronos NET/Kronos LT software communicates via TCP protocol, while EGR100 middle-ware v1.2 and up supports both – TCP and UDP
protocols. However, TCP protocol is NOT recommend to use with EGR100.
ATTENTION: It is necessary to restart the system locally by powering down and powering up the system the system or remotely (see 32.
REMOTE SYSTEM RESTART) after changing the IP address or switching from TCP to UDP.
30.2.2. Voice Calls and SMS
The system supports up to 3 monitoring station phone numbers for communication with the alarm system by Voice Calls or SMS commu­
nication method. Tel. Number 1 is mandatory, the other two can be used as backup phone numbers and are not necessary. The supported
phone number format is the following:
• International (w/o plus) – The phone numbers must be entered starting with an international country code in the following format:
[international code][area code][local number], example for UK: 44170911XXXX1.
To set up the system for data transmission via Voice Calls or SMS, please follow the basic configuration steps:
1. Enable MS Mode parameter (see 30. MONITORING STATION).
2. Set 4-digit Account number (see 30. MONITORING STATION).
3. Set Tel. Number 1... 3.
Set monitoring station
phone number
EKB2
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → VOICE CALLS/SMS ST →
OK → TEL. NUMBER 1... 3 → OK → ttteeellnnuumm → OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits monitoring
station phone number.
Enter parameter 26, phone number slot and phone number:
26 ps ttteeellnnuumm #
Value: ps – phone number slot, range – [01... 03]; ttteeellnnuumm – up to 15 digits monitoring station phone number.
Example: 260144170911XXXX1#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
99
Delete monitoring
station phone number
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → VOICE CALLS/SMS ST →
OK → TEL. NUMBER 1... 3 → OK → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station’s Tel Number 1 via Voice Calls or SMS method is unsuccessful, the
system will make up to 4 additional attempts. After all unsuccessful attempts, the system will continue to communicate with the monitoring station by switching to the next phone number that follows in the sequence and making up to 4 additional attempts if the initial attempt is unsuccessful. If all attempts to all phone numbers are unsuccessful, the system will switch to next backup connection that follows
in the sequence and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → VOICE CALLS/SMS ST →
OK → ATTEMPTS → OK → at → OK
Value: aaaa – 4-digit administrator password; at – number of attempts, range – [1... 10].
EKB3
Enter parameter 37 and number of attempts:
37 at #
Value: at – number of attempts, range – [01... 10].
Example: 3706#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
Due to the individual configuration of each monitoring station, the system may fail to deliver the data message via Voice Calls communication method. In such cases it is recommended to adjust the microphone gain until the optimal value, leading to successful data message
delivery, is discovered.
Set microphone gain
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → PRIMARY SETT INGS → OK → GSM AUDIO → OK
→ MICROPHONE GAIN → OK → mg → OK
Value: aaaa – 4-digit administrator password; mg – microphone gain, range – [0... 15].
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
30.2.3. CSD
The system supports up to 5 monitoring station phone numbers for communication with the alarm system by CSD communication method.
Tel. Number 1 is mandatory, the other four can be used as backup phone numbers and are not necessary. The supported phone number
format is the following:
• International (w/o plus) – The phone numbers must be entered starting with an international country code in the following format:
[international code][area code][local number], example for UK: 44170911XXXX1.
To set up the system for data transmission via CSD, please follow the basic configuration steps:
1. Enable MS Mode parameter (see 30. MONITORING STATION).
2. Set 4-digit Account number (see 30. MONITORING STATION).
3. Set Tel. Number 1... 5.
Set monitoring station
phone number
100
EN
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → CSD SETTINGS → OK →
TEL. NUMBER 1... 5 → OK → ttteeellnnuumm → OK
Value: aaaa – 4-digit administrator password; ttteeellnnuumm – up to 15 digits monitoring
station phone number.
MANUAL ELDES ESIM264 V3.3
EKB3
Delete monitoring
station phone number
Enter parameter 85, number of entry and phone number:
85 ps ttteeellnnuumm #
Value: ps – phone number slot, range – [01... 05]; ttteeellnnuumm – up to 15 digits monitoring station phone number.
Example: 85014417091111111#
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → CSD SETTINGS → OK →
TEL. NUMBER 1... 5 → OK → OK
Value: aaaa – 4-digit administrator password.
Config
Tool
This operation may be carried out from the PC using the ELDES Configuration Tool software.
By default, if the initial attempt to transmit data to the monitoring station’s phone number via CSD method is unsuccessful, the system will
make up to 4 additional attempts. If all attempts are unsuccessful, the system will switch to next backup connection that follows in the
sequence and will attempt to transmit data until it is successfully delivered to the monitoring station.
Set attempts
EKB2
EKB3
Config
Tool
MANUAL ELDES ESIM264 V3.3
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → MS SETTINGS → OK → CSD SETTINGS → OK →
TEL. NUMBER 1... 5 → OK → OK
Value: aaaa – 4-digit administrator password; at – number of attempts, range – [1... 10].
Enter parameter 84 and number of attempts:
84 at #
Value: at – number of attempts, range – [01... 10].
Example: 8403#
This operation may be carried out from the PC using the ELDES Configuration Tool software.
EN
101
31. WIRED DEVICES
31.1. RS485 Interface
The system comes equipped with RS485 interface used for the communication with the following devices:
•
EKB2 - LCD keypad. Up to 4 units supported.
•
EKB3 - LED keypad. Up to 4 units supported.
•
EPGM1 - hardwired zone and PGM output expansion module. 1 unit supported.
The terminals of RS485 interface are Y (yellow wire) and G (green wire) terminals, which are data bus. The devices, connected to RS485
interface, must be powered from the AUX+ and AUX- terminals or by an external power supply.
For more details on RS485 device wiring, please refer to 3.2.7. RS485.
For more details on technical specifications and installation, please refer to the latest user manual of the device located at eldesalarms.com
31.1.1. EKB2 - LCD Keypad
Main features:
• Alarm system arming and disarming (see 12.3. EKB2 Keypad and User Code).
• Arming and disarming in Stay mode (see 15. STAY MODE).
• System parameter configuration (see 5. CONFIGURATION METHODS).
• PGM output control (see 18.4. Turning PGM Outputs ON and OFF).
• System information display (see 31.1.1.1. Icons and Messages).
• Keypad partition switch (see 23.3. Keypad Partition and Keypad Partition Switch).
• Audio indication by built-in buzzer.
• Wireless device information display (see 19.2. Wireless Device Information).
• Temperature display (see 31.1.1.1. Icons and Messages).
• Time display (see 31.1.1.1. Icons and Messages).
For more details on technical specifications and installation, please refer to the latest user manual of the device located at eldesalarms.com
102
EN
MANUAL ELDES ESIM264 V3.3
31.1.1.1. Icons and Messages
Temperature
43
GSM signal
strength
Digital
clock
20,20C
System
status
message
STAY
BYP
TBL
00:45
READY
GARAGE
One or more
violated
zones are
bypassed
One or
more
system
faults are
present
System
armed in Stay
mode
Custom
partition
name
Icon / Message
Home screen
view
Description
Chime - Delay zone violated when system
is disarmed.
Exit delay countdown initiated.
System is armed and menu is locked.
System is disarmed and menu is unlocked
Icon / Message
24H zone violated.
FIRE ALARM
Fire zone violated.
TAMPER ALARM
READY
NOT READY
ARMED
+ CONFIGURATION
MODE
BURGLARY ALARM
Configuration mode activated.
Delay, Instant or Follow zone violated
when system is armed.
MANUAL ELDES ESIM264 V3.3
Description
24 ALARM
Tamper violated
System is ready to be armed.
System is not ready to be armed – one or
more zones / tampers violated.
System is armed (optional feature).
STAY
Stay mode activated
BYP
System armed in Stay mode
TBL
One or more system faults are present
EN
103
31.1.1.2. Menu Tree
HOME SCREEN VIEW
P1
P2
[1] part-name...
[4] part-name
OK
ENTER STAY
uuuu
BYPASS
FAULTS
DATE/TIME SETTINGS
BYPASS LIST 2
VIEW EVENT LOG
UNBYPASS | BYPASS
Z13-zone-name...
Z44-zone-name
VIOLATED TAMPER | BATTERY FAILED | MAIN PWR FAILURE
| DATE/TIME NOT SET | GSM ERROR
BYPASS LIST 1
UNBYPASS | BYPASS
Z13-zone-name...
Z44-zone-name
TAMPER 1... 44
VIOLATED TAMPERS
BYP VIOLATED ZONES
Z1-zone-name...
Z12-zone-name
ZONE 1... 44
VIOLATED ZONES
yyyy-mm-dd hr:mn
uuuu
ENTER USER PSW
CONFIGURATION
BYPASS LIST 3
aaaa
PHONE NUMBER
ttteeellnnuumm
ENTER ADMIN PSW
PARTITION
UNBYPASS | BYPASS
PRIMARY SETTINGS
PARTITION0
| PARTITION1
SEND ARM/DARM SMS
CALL/SMS SETTINGS
USERS
WIRELESS DEVICES
wless-dev wless-id
BATTERY
DISABLE | ENABLE
USER 1... 5
SEND ARM/DARM ALL
DISABLE | ENABLE
SEND ALARM SMS ALL
DISABLE | ENABLE
CALL IN CASE ALARM
DISABLE | ENABLE
CTRL FROM ANY NUM
DISABLE | ENABLE
SIGNAL
PASSWORDS
ERROR RATE
SMS PASSWORD
FW RELEASE
IBUTTON KEYS
DISABLE | ENABLE
NEW IBUTTON
IBUTTON 1... 5
[0001... 9999]
ADMIN PASSWORD
[0000... 9999]
[0000... 9999]
USER PASSWORDS
PASSWORD
USER PASSWORD 1... 16
PARTITION
ID
PARTITION0 | PARTITION1
PARTITION
USER PASSWORD 17... 30
REMOVE
DURESS PASSWORD
SGS PASSWORD
PARTITION0 |
PARTITION1
PASSWORD
[0000... 9999]
PARTITION
PARTITION0 |
PARTITION1
N/A | 1... 10
N/A | 1... 10
REMOVE PASSWORD
[0000... 9999]
Continued in next page
104
EN
MANUAL ELDES ESIM264 V3.3
NAME
DISABLE |
ENABLE
seconds
ZONE 1... 12
STATUS
TYPE
[1... 65535]
ENTRY DELAY
WIRELESS ZONE 1... 16
ONBOARD ZONES
INTERIOR FOLLOWER | INSTANT | 24HOUR | DELAY | FIRE
| PANIC/SILENT
WIRELESS ZONES
NAME
DISABLE | ENABLE
INTERIOR FOLLOWER | INSTANT |
24-HOUR | DELAY | FIRE | PANIC/SILENT
[1... 65535]
ENTRY DELAY
STAY
SMS LANGUAGE
INFO SMS SCHEDULER
FREQUENCY (DAYS)
TIME
EVENT LOG
[-55... +125] 0C
TEMP. MAX
[-55... +125] 0C
seconds
PARTITION0 | PARTITION1
DISABLE | ENABLE
KEYPAD 1... 4 ZONE
[0... 600]
BELL SQUAWK
EWS2 LED
INTERIOR FOLLOWER | INSTANT |
24-HOUR | DELAY | FIRE | PANIC/SILENT
[1... 65535]
ENTRY DELAY
seconds
LOSS DELAY
[0... 65535]
PARTITION SWITCH
seconds
DISABLE | ENABLE
KEYPAD PARTITION
EPGM1 ZONES
NAME
KEYPAD 1... 4
PARTITION0
| PARTITION1
DISABLE | ENABLE
STATUS
INTERIOR FOLLOWER | INSTANT |
24-HOUR | DELAY | FIRE | PANIC/SILENT
[1... 65535]
ENTRY DELAY
seconds
GSM AUDIO
DISABLE | ENABLE
MICROPHONE GAIN
TAMPER NAME
PARTITION
FORCE
seconds
KEYPAD PARTITION
DISABLE | ENABLE
EPGM1 ZONE 1... 16
DISABLE | ENABLE
[0... 65535]
RESTORE DELAY
PARTITION0 | PARTITION1
DISABLE | ENABLE
DISABLE | ENABLE
MAIN POWER STATUS
DISABLE | ENABLE
PARTITION
minutes
DISABLE | ENABLE
EWF1 SIREN INTERC.
TAMPER NAME
STAY
[1... 10]
SRN IF WLESS LOSS
DISABLE | ENABLE
STATUS
TYPE
seconds
SIREN SETTINGS
ALARM DURATION
KEYPAD ZONES
NAME
FORCE
[0... 23]
DISABLE | ENABLE
TEMP. MIN
EXIT DELAY
STAY
[0... 99]
DISABLE | ENABLE
PARTITION
TYPE
yyyy-mm-dd hr:mn
DATE/TIME SETTINGS
TAMPER NAME
FORCE
ENGLISH | second-lang
TEMPERATURE SENSOR
STATUS
TYPE
PRIMARY SETTINGS
ZONES
CONFIGURATION
Continued from previous page
PARTITION0 | PARTITION1
SPEAKER LEVEL
[0... 15]
[0... 100]
DISABLE | ENABLE
Continued in next page
MANUAL ELDES ESIM264 V3.3
EN
105
ATZ MODE
CONFIGURATION
DISABLE | ENABLE
ZONES
Continued from previous page
MS SETTINGS
ACCOUNT
TYPE 1... 3
ZONE TYPE:6-ZONE M
TYPE 4... 5
ZONE TYPE:ATZ MODE
MS MODE
N/A / ZONE 1... 12
ARM/DISARM BY ZONE
DATA MESSAGES
DISABLE | ENABLE
DELAY LAST ATTEMPT
[1... 65535]
DISABLE | ENABLE
ALARM/RESTORE EV
DISABLE | ENABLE
CHIME
MAIN POWER L/R EV
PGM OUTPUTS
DISABLE | ENABLE
USING EPGM8
STATUS
DISARMED EVENT
BATTERY FAIL EVENT
DISABLE | ENABLE
TEST EVENT
OUTPUT 1... 12
DISABLE | ENABLE
ARMED EVENT
DISABLE | ENABLE
DISABLE | ENABLE
DISABLE | ENABLE
ONBOARD OUTPUTS
SYSTEM STARTED EV
DISABLE | ENABLE
DISABLE | ENABLE
WLESS SIGN LOSS EV
NAME
TEMP LOW EVENT
DISABLE | ENABLE
DISABLE | ENABLE
TEMP HIGH EVENT
wless-dev wless-id
BATTERY
SIGNAL
WIRELESS DEVICES
ERROR RATE
FW RELEASE
GPRS SETTINGS
[0.0.0.0]
SERVER IP
[0.0.0.0]
DNS1
APN
[0.0.0.0]
DNS2
USER
TCP | UDP
[1... 65535]
PROTOCOL
SERVER PORT
[1... 65535]
SYSTEM SHUTDOWN EV
DISABLE | ENABLE
DISABLE | ENABLE
VOICE CALLS/SMS ST
ATTEMPTS
LOCAL PORT
seconds
[1... 10]
TEL. NUMBER1
ttteeellnnuumm
15 digits
TEL. NUMBER2
ttteeellnnuumm
15 digits
TEL. NUMBER3
ttteeellnnuumm
15 digits
PASSWORD
PROFILE
Continued in next page
106
EN
MANUAL ELDES ESIM264 V3.3
MS SETTINGS
SMS MESSAGES
CONFIGURATION
Continued from previous page
CSD SETTINGS
[1... 10]
ATTEMPTS
DISABLE | ENABLE
ALARM EVENT
DISABLE | ENABLE
ARMED EVENT
TEL. NUMBER1
ttteeellnnuumm
15 digits
DISARMED EVENT
TEL. NUMBER2
ttteeellnnuumm
15 digits
TEL. NUMBER3
ttteeellnnuumm
15 digits
MAIN PWR REST EV
TEL. NUMBER4
ttteeellnnuumm
15 digits
PERIODIC SMS EV
TEL. NUMBER5
ttteeellnnuumm
15 digits
DISABLE | ENABLE
DISABLE | ENABLE
MAIN PWR LOSS EV
DISABLE | ENABLE
DISABLE | ENABLE
DISABLE | ENABLE
DISABLE | ENABLE
DISABLE | ENABLE
DISABLE | ENABLE
TAMPER EVENT
SYSTEM STARTED EV
GPRS SETTINGS
GPRS ATTEMPTS
[0... 255]
WLESS SIGN LOSS EV
SYSTEM SHUTDOWN EV
DISABLE | ENABLE
TEMP LOW EVENT
DISABLE | ENABLE
TEMP HIGH EVENT
UNIT ID
[0000... 9999]
TEST PERIOD
[0... 65535]
seconds
PRIMARY CONNECTION
GPRS | VOICE CALLS | RS485 | CSD | SMS | N/A
ENTER USER PSW
uuuu
RESET TO DEFAULT
BACKUP CONNECTION1
GPRS | VOICE CALLS | RS485 | CSD | SMS | N/A
BACKUP CONNECTION2
GPRS | VOICE CALLS | RS485 | CSD | SMS | N/A
BACKUP CONNECTION3
GPRS | VOICE CALLS | RS485 | CSD | SMS | N/A
BACKUP CONNECTION4
GPRS | VOICE CALLS | RS485 | CSD | SMS | N/A
MANUAL ELDES ESIM264 V3.3
EN
107
31.1.2. EKB3 - LED Keypad
Main features:
• Alarm system arming and disarming (see 12.4. EKB3 Keypad and User Code).
• Arming and disarming in Stay mode (see 15. STAY MODE).
• System parameter configuration (see 5. CONFIGURATION METHODS).
• PGM output control (see 18.4. Turning PGM Outputs ON and OFF).
• Visual indication by LED indicators (see 32.1.2.1. LED Functionality).
• Audio indication by built-in buzzer.
• Keypad partition switch (see 23.3. Keypad Partition and Keypad Partition Switch).
For more details on technical specifications and installation, please refer to the latest user manual of the device located at eldesalarms.com
31.1.2.1.
LED Functionality
INDICATION
(red)
(green)
System armed / exit delay in progress
Flashing
Configuration mode activated
Steady ON
System is ready – no violated zones and/or violated tampers exist
Steady ON
System faults exist
(orange) Flashing
(orange)
1-12
(red)
DESCRIPTION
Steady ON
Violated high-numbered zone
Steady ON
Violated zone bypassed
Steady ON
Zone violated / configuration command being typed in
31.1.2.2. Keys Functionality
DESCRIPTION
44 FRONT SIDE
1st character for STAY-arming
0
9
1st character for violated zone bypass and bypassed
zone activation
1
2
N/A
4
5
6
1st character for system fault list indication / 1st
character for violated high-numbered zone indication
/ 1st character for violated tamper indication
7
8
9
*
0
#
3
Command typing
1st character for Configuration mode activation
or deactivation / clear typed in characters / 1st
character for keypad partition switch (if enabled)
*
Typed in command confirmation
31.2. 1-Wire Interface
1-Wire interface is used for the system to communicate with an iButton key reader and a temperature sensor. 1-Wire interface COM and DATA
terminals are ground and data respectively. When connecting single or multiple temperature sensors, the +5V terminal must be used along.
For more details on 1-Wire device wiring, please refer to 2.3.4. iButton Key Reader and Buzzer and 2.3.5. Temperature Sensor and
iBut­ton Key Reader.
Main iButton features:
•
•
Up to 5 iButton keys per alarm system unit ESIM264;
Communication via 1-Wire interface.
31.3. Modules Interface
The system might be equipped with modules interface slots thus enabling to use one of the following devices at a time:
• EPGM8 - hardwired PGM output expansion module (for more details on technical specifications and installation, please refer to the
latest user manual of the device located at eldesalarms.com)
• EA1 - audio output module (see 31.2.1. EA1 - Audio Output Module)
• EA2 - audio output module with amplifier (see 31.2.2. EA2 - Audio Output Module with Amplifier)
108
EN
MANUAL ELDES ESIM264 V3.3
31.3.1. EA1 – Audio Output Module
EA1 audio output module enables a duplex audio connection for ESIM264 alarm system.
Main EA1 features:
•
Two-way voice conversation during a phone call;
•
Possibility to connect headphones or desktop speakers.
31.3.1.1. Technical Specifications
•
3,5 mm female jack
•
Dimensions: 41x40x24mm (1.61x1.57x0.95in)
31.3.1.2. Installation
1. Disconnect ESIM264 alarm system mains power and backup battery.
2. Insert EA1 pins into appropriate ESIM264 alarm system slots.
45
EA1
ESIM264
3. Connect headphones or desktop speakers to EA1 3,5 mm female jack.
46
EA1
4. Power up ESIM264 alarm system.
5. EA1 is ready for use with ESIM264 alarm system.
MANUAL ELDES ESIM264 V3.3
EN
109
31.3.2. EA2 – Audio Output Module with Amplifier
EA2 audio output module enables a duplex audio connection for ESIM264 alarm system.
Main EA2 features:
•
Two-way voice conversation during a phone call;
•
Possibility to connect a speaker.
31.3.2.1. Technical Specifications
• 1W 8Ω audio amplifier
• Dimensions: 35x33x12mm (1.38x1.30x0.47in)
31.3.2.2. Installation
1. Disconnect ESIM264 alarm system mains power and backup battery.
2. Insert EA2 pins into appropriate ESIM264 alarm system slots.
47
ESIM264
EA2
3. Connect a speaker to EA2 Speaker terminals.
48
EA2
4. Power up ESIM264 alarm system.
5. EA2 is ready for use with ESIM264 alarm system.
110
EN
MANUAL ELDES ESIM264 V3.3
32. REMOTE SYSTEM RESTART
In some critical situations, a system restart may be required. To remotely carry out system restart, please refer to the following configuration method.
Restart the system
MANUAL ELDES ESIM264 V3.3
SMS
SMS text message content:
ssss_RESET
Value: ssss – 4-digit SMS password.
Example: 1111_RESET
EN
111
33. TECHNICAL SUPPORT
33.1. Troubleshooting
Indication
Possible reason
Indicator STATUS is OFF
· No mains power
· Blown fuse
· Micro-controller is unable to initiate due to electrical mains noise or static discharge
Indicator PWR is OFF
· No mains power
Wiring done improperly
· Blown fuse
Indicator NETWORK is OFF
·
·
·
·
·
·
Missing SIM card
PIN code is enabled
SIM card is inactive
Disconnected antenna
GSM operator’s fault
GSM signal unavailable in the area
System is unable to send any SMS text messages
and/or does not ring
·
·
·
·
·
Insufficient SIM card credit balance
Incorrect SMS centre phone number
No GSM network signal
User phone number is not added (or control from any phone number is disabled)
SIM card changed before disconnecting mains power or backup battery
Received SMS text message “Wrong syntax”
· Incorrect SMS text message structure
· Extra space symbol could be left in SMS text message
Missing temperature indication in Info SMS text
message/EKB2 keypad
· Temperature sensor not connected
· Temperature sensor fault
· Cable length of the 1-Wire interface is exceeded (30 m 98.43ft) max.)
24H and/or Fire zones do not work
· Specified zone must be enabled by SMS, ELDES Configuration Tool, EKB2 or EKB3
keypad.
No sound during remote listening
· Microphone not connected
· Improper microphone connection
For product warranty repair service please , contact your local retail store where this product was purchased.
If your problem could not be fixed by the self-guide above, please contact your local distributor. More up to date information about your device
and other products can be found at the manufacturer’s website eldesalarms.com
33.2. Restoring Default Parameters
1.
2.
3.
4.
5.
6.
Disconnect the power supply and backup battery.
Short circuit (connect) DEF pins.
Power up the device for 7 seconds.
Power down the device.
Remove short circuit from DEF pins.
Parameters restored to default.
33.3. Updating the Firmware via USB Cable Locally
1.
Disconnect the power supply and backup battery.
2.
Short circuit (connect) DEF pins.
3.
Connect the device via USB cable to the PC.
4. Power up the device.
5.
The new window must pop-up where you will find the .bin file. Otherwise open My Computer and look for Boot Disk drive.
6.
Delete the .bin file found in the drive.
7.
Copy the new firmware .bin file to the very same window.
8. Power down the device.
9.
Unplug USB cable.
10. Remove short circuit from DEF pins.
11. Power up the device.
12. Firmware updated.
NOTE: It is strongly recommended to restore default parameters after the firmware update.
112
EN
MANUAL ELDES ESIM264 V3.3
33.4. Updating Firmware via GPRS Connection Remotely
ATTENTION: The system will NOT transmit any data to monitoring station while updating the firmware remotely via GPRS network. All
data messages will be lost and will NOT be transmitted to the monitoring station after the firmware upgrade process is over.
Before updating the firmware remotely via GPRS connection, make sure that:
• SIM card is inserted into SIM CARD slot of ESIM264 device (see 2.2. Main Unit, LED and Connector Functionality).
• Mobile internet service (GPRS) is enabled on the SIM card.
• Power supply is connected to ESIM264.
• Default SMS password is changed to a new 4-digit password (see 6. PASSWORDS).
• At least User 1 phone number is set up (see 8. USER PHONE NUMBERS).
• APN, user name and password are set up (see 30.2.1. GPRS Network).
Initiate FOTA
ESIM264 alarm system supports FOTA (firmware-over-the-air) feature. This allows to upgrade the firmware remotely via GPRS connection. Once the upgrade process is initiated, the system connects to the
specified FTP server address where the firmware file is hosted and begins downloading and re-flashing
the firmware. The firmware file must be located in a folder titled Firmware. In order to initiate the upgrade process please , send the following SMS message.
SMS
SMS text message content:
ssss_FOTA:ftp-server-ip,port,firmware-file-name.bin,user-name,password
Value: ssss - 4-digit SMS password; ftp-server-io - public IP address of FTP server where
ESIM264 firmware file is stored; port - port number of FTP server (usually - 21); firmwarefile-name.bin - name of the firmware file, allowed max. length - up to 31 character; username - user name of FTP server login, allowed max. length - up to 31 character; password
- password of FTP server login, allowed max. length - up to 31 character.
Example: 1111_FOTA:84.15.143.111,21,ESIM264fw bin,eldesuser,eldespassword
ATTENTION: Firmware filename MUST be renamed in lowercase format before using it.
ATTENTION: Comma and underscore character is NOT allowed to use in user name, password and firmware file name.
ATTENTION: “ELDES UAB” does not run a FTP server and does not host the firmware files online. Please, contact your local distributor to
request the latest firmware file.
NOTE: It is strongly recommended to restore default parameters after the firmware update.
33.5. Frequently Asked Questions
Question
Answer
Yes, ESIM264 device can fully operate without any SIM card inserted. In this case
Can ESIM264 operate as standalone device without SIM
you will not be able to configure and control the device by SMS and calls nor to
card inserted?
receive any SMS reports and calls.
Due to security reasons it is recommended to restore the violated zone (-s)
2. I am unable to arm the alarm system when one of the
before arming the alarm system. However, you can enable a Force attribute or
zones (some zones) is violated, although I was able to
use the Bypass feature in order to arm the alarm system despite the violated
perform disarming. Is there a way to arm the alarm syszone (-s) being present. Please, refer to 14.5. Zone Type Definitions and
tem while the zone is violated?
14.7. Bypassing and Activating Zones.
3. I have activated ATZ mode in ELDES Configuration Tool
It appears that your ELDES Configuration Tool software is outdated. Please,
software, but I am unable to set the connection Type 5.
download the latest ELDES Configuration Tool software version by visiting
Whenever I select Type 5 and press the “Write Settings”
eldesalarms.com/en/download.
button it switches back to Type 4. What’s wrong?
4. When ESIM264 fully powers down my configuration be- This might have happened due to the jumper left on DEF pins or it is a hardcomes lost and I have to re-configure the device again. ware failure. Please, remove the jumper if it is present on DEF pins or contact
What’s wrong?
your supplier for warranty service.
If the smoke detector is connected to one of the Esim264 PGM outputs you
5. I have a smoke detector connected to ESIM264 system.
can reset it by turning the PGM output OFF and then back ON. This can be
How do I reset the smoke detector when the “Fire” zone
performed by SMS, EKB2 keypad, EKB3 keypad and ELDES Configuration Tool
is violated?
software. Please, refer to 18.4. Turning PGM Outputs ON and OFF.
6. What happens if I switch backup battery pole terminals Switching backup battery pole terminals places is forbidden. Otherwise this
places?
will lead to blown fuse and ESIM264 alarm system will have to be repaired.
The SMS reports on tamper violation can be disabled by EKB2, EKB3 keypads
7. How do I disable SMS reports and calls in case of tamper or ELDES Configuration Tool software. For more details, please refer to 16.
violation when alarm system is disarmed?
TAMPERS or to the software’s HELP section. However, due to security reasons it is not recommended to disable this feature.
1.
MANUAL ELDES ESIM264 V3.3
EN
113
Question
Answer
8. Is any additional configuration necessary when conNo additional configuration is required in order to make EPGM1 module opernecting EPGM1 module after wiring is done according to
ational.
EPGM1 user manual?
No, the number of EPGM1 zones does not duplicate in ATZ mode as EPGM1
9. Does the number of EPGM1 zones duplicate when ATZ
module does not support ATZ mode. Only ESIM264 zones duplicate in ATZ
mode is activated in the system?
mode.
10. I connect the wired siren to ESIM264 and I hear a silent
sound alarm even when the alarm system is disarmed. Please, connect the resistor of 3,3 kΩ nominal to the BELL- / BELL+ contacts
In case of alarm system alarm the siren provides a loud This should solve the problem.
sound alarm as it should. Why?
11. I am using Windows operating system. The windows
Please, update ELDES Configuration Tool software by visiting eldesalarms.
of ELDES Configuration Tool are not fully displayed and
com/en/download and downloading the latest version.
some parts are like cut-off. What’s wrong?
12. The buzzer remains active when I disarm the alarm sys- The buzzer is intended for iButton indication only and it is not related to distem using the keypad. Why?
arming process by keypad.
This happens due to wireless connection loss. There might be several reasons:
1. ELDES wireless device is installed too close or too far from ESIM264
13. One of wireless devices connected to ESIM264 system
system.
sends a tamper alarm from time to time, although no
2. Interference of other electronic equipment.
tamper was violated. Why?
3. Physical interference (building walls, floors etc.)
4. Metal material interference.
This happens due to incorrect resistor connection. Please, refer to corre14. I have connected a wired magnetic door sensor, but I responding connection circuit according to the selected zone connection type
ceive tamper alarm instead of zone alarm. What’s wrong?
(Type 1 – 5). See 2.3.2 Zone Connection Types for more details.
By default, this notification is enabled. The system checks the backup battery
15. I disconnected the backup battery, but did not receive resistance once a day and sends an SMS report to User 1 on backup battery
any SMS report on this event. How do I enable SMS re- replacement if more than 2Ω resistance is detected. For more details, please
port on backup battery disconnection?
refer to 21. BACKUP BATTERY, MAINS POWER SUPPLY STATUS MONITORING AND MEMORY.
Every time an SMS text message is sent to the user, the system must “know” that
the message was successfully delivered. The only way to partly disable the SMS
16. When I check system SIM card credit balance I see a lot of
delivery report (for alarm notifications only) is to enable alarm SMS notifications
SMS delivery confirmation reports. How do I disable SMS
to all users. This is useful when having only User1 phone number set up, as in case
delivery confirmation ESIM264 system?
of alarm the system sends the alarm SMS text message to all listed users simultaneously, but does not require any SMS delivery report.
According to GSM standards 1 SMS text message may consist of up to 160
17. I have set zone names and/or PGM output names con- Latin alphabet/English characters maximum. If the message contains at
taining some Cyrillic and/or non-English characters. least one non-latin/non-English character, the length of SMS message beThe zone names and PGM output names do not fully fit comes at least half shorter, since those characters occupy more size of the
in the SMS message. What‘s wrong?
SMS text message than the Latin ones. It is recommended not to use any
non-Latin/ non-English characters in zone names and PGM output names.
18. The configuration of added wireless keyfob EWK1 to
ELDES Configuration Tool version is too old. Please, update it.
ESIM264 system is not visible in ELDES Configuration
Tool. What‘s wrong?
Microsoft .NET Framework v3.5 is not installed in Windows system. Please,
19. I am unable to run ELDES Configuration Tool - I receive
download this package from official Microsoft website free of charge and
error messages in Windows. Why?
install it to your Windows system.
20. Info SMS report comes with wrong date and time. How Please, set the correct system date and time using either ELDES Configura­
do I correct it?
tion Tool, EKB2, EKB3 keypad or SMS text message.
It appears that the device is unable to establish a communication with configuration / FTP server. Please, check the GPRS settings in ESIM264 config21. I receive an error message when attempting to config- uration (APN, user name, password), the location of the firmware .bin file
ure the device or update the firmware remotely. What’s (must be located in the FTP server folder titled Firmware) and the mobile
wrong?
internet feature presence on the SIM card used with ESIM264. If this does
not solve the problem, please contact your GSM operator (and ISP - for remote configuration problems) in order to request a list of blocked TCP ports.
22. I waited for at least 5 minutes, but did not receive any 1. Send the ssss_ENCONFIG SMS text message.
SMS message confirming that remote configuration via 2. In ELDES Configuration Tool software press Disconnect button and repeat
GPRS connection has stopped. What‘s wrong?
the steps from the beginning as described in 5.4.1. Remote Connection.
114
EN
MANUAL ELDES ESIM264 V3.3
34. RELATED PRODUCTS
EKB2 - LCD keypad
EKB3 - LED keypad
ME1 - metal cabinet
EPGM1 - hardwired zone and PGM
output expansion module
EPGM8 - hardwired PGM
output expansion module
EA1 - audio output module
MANUAL ELDES ESIM264 V3.3
EN
115
116
EN
EA2 - audio output module with amplifier
DS1990A-F5 - iButton key
DS18S20 - temperature sensor
ED1T - plastic enclosure with iButton key reader
and temperature sensor
EWS2 - wireless external siren
EWF1 – wireless smoke detector
EWK1 - wireless keyfob
ESR100 - digital receiver
MANUAL ELDES ESIM264 V3.3
EWD2 - wireless door contact/shock sensor
EWK2 - wireless keyfob
EWS3 - wireless indoor siren
Vinson DS18B20 - digital
thermometer with 3m (9.84ft) wire
MANUAL ELDES ESIM264 V3.3
EN
117
Made in the European Union
eldesalarms.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement