Midmark Classic Series Installation guide

Midmark Classic Series Installation guide
Components:
Water Filter / Bypass System Installation
3/4” - 77002146, 1” - 77002147
1 1/4” - 77002148, 1 1/2” - 77002149
Bypass Assy .......
Filter Cartridge ....
O-ring ..................
Filter Bowl ...........
Bowl Wrench ......
Bracket Kit ...........
1
1
1
1
1
1
Requirements / Restrictions:
Install Water Filter / Bypass System according to local electrical and plumbing codes.
Installer provides union connecting fittings.
Change Filter Cartridge every 6 months.
Protect from freezing. Don’t use torch near plastic housing.
Do NOT Install: • On hot water lines.
• On line pressures above 100 PSI.
• Near direct sunlight or heat producing equipment.
Intended Use:
To provide safe water supply shut-off from dental operatory.
Step 1: Locate a convenient water and electrical
supply line run for Filter/Bypass installation.
Close-off main water supply.
Step 2: Install mounting bracket to wall.
Mounting Bracket Kit
Installer Supplies Union Fitting to Water Line
Step 3:
Install Filter/Bypass to bracket and water line.
Note: Direction of water flow through solenoid
must be maintained during installation.
Step 4: Install and secure union
connectors at both ends.
Filter Cartridge
O-Ring
Water Filter . Bypass Systems
Pipe Size Max. Dimensions
Model
(MPT) GPM
H x W x D)
7002146
3/4"
6 19" x 15" x 5.5"
7002147
1"
30 23" x 21" x 7.5"
77002148 1 1/4"
40 23" x 23" x 7.5"
77002149 1 1/2"
40 25" x 23" x 7.5"
Step 5: Install o-ring and filter cartridge into filter bowl.
AA198800
© Midmark Corporation 2007
1
10552900
Rev. D
Specs: 120 VAC
1 amp
60 Hz
RD
BL
WH
BK
WH
GN
RD
RD
Use Wrench Provided
GN
Step 6: Install bowl.
From Power
Source
Note: Do not over tighten.
To Valve
Step 7: Plug relay control box to 120 volt power source to energize electrical solenoid.
Step 9: Unplug relay control box from outlet.
Note: Where state or local codes do not permit the use of a power
supply cord, the product may be converted to fixed wiring as follows...
A) Remove manufacture power cord.
B) Connect green wire to bottom connection on ground stud.
C) Connect common wires to L1 and L2.
Step 8: Open main water valve and check for leaks.
AA198900
© Midmark Corporation 2007
2
Note
OPTIONAL
Control Panel
Water Switch
Control Panel provides a remote means of controlling
dental equipment from inside the office area.
Blue
115 Volt
Line Cord
Relay Control
Box
Control Panel Reference Cross Wiring
Wire
Brand
Light
White
Red
A
B (Light)
C
Midmark
Blue
White
Red
Air Techniques
Yellow
Brown
Orange
DentalEz
Black
Brown
Yellow
Matrx
Red
Blue
White
Apollo
Blue
White
Red
Step 10: Connect low voltage wires to control panel water switch.
Plug relay control box into 115 volt outlet.
Step 11: Set mode.
Bypass Mode
Operational Mode
AA19900
© Midmark Corporation 2007
3
LIMITED WARRANTY
SCOPE OF WARRANTY
Midmark Corporation (“Midmark”) warrants to the original purchaser its Air and Vacuum accessories (except for components not warranted under “Exclusions”)
manufactured by Midmark to be free from defects in material and workmanship under normal use and service. Midmark’s obligation under this warranty is limited to the
repair or replacement, at Midmark’s option, of the parts or the accessories the defects of which are reported to Midmark within the applicable warranty period and
which, upon examination by Midmark, prove to be defective.
APPLICABLE WARRANTY PERIOD
The applicable warranty period, measured from the date of installation for the original user, shall be:
• Midmark Air and Vacuum Accessories: 90 Days
EXCLUSIONS
This warranty does not cover and Midmark shall not be liable for the following: (1) repairs and replacements because of misuse, abuse, negligence, alteration,
accident, freight damage, or tampering; (2) products which are not installed, used, and properly cleaned as required in the Midmark “Installation” manual and/or
“Maintenance guide” for this applicable product; (3) products considered to be of a consumable nature; (4) accessories or parts not manufactured by Midmark; (5)
charges by anyone for adjustments, repairs, replacement parts, installation, or other work performed upon or in connection with such products which is not expressly
authorized in writing in advance by Midmark.
EXCLUSIVE REMEDY
Midmark’s only obligation under this warranty is the repair or replacement of defective parts. Midmark shall not be liable for any direct, special, indirect, incidental,
exemplary, or consequential damages or delay, including, but not limited to, damages for loss of profits or loss of use.
NO AUTHORIZATION
No person or firm is authorized to create for Midmark any other obligation or liability in connection with the products.
THIS WARRANTY IS MIDMARK’S ONLY WARRANTY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. MIDMARK MAKES NO IMPLIED WARRANTIES OF
ANY KIND INCLUDING ANY WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. THIS WARRANTY IS LIMITED TO THE REPAIR OR
REPLACEMENT OF DEFECTIVE PARTS.
Midmark Corporation
145 Mid County Drive
Orchard Park, New York 14127
Customer Service Phone: 1-800-643-6275
Technical Service Phone: 1-888-279-1260
Fax: 1-877-725-6495
www.midmark.com
© Midmark Corporation 2007
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement