CASH VALVE TYPE E-55
CRYOGENIC PRESSURE REDUCING VALVE OR PRESSURE BUILD-UP REGULATOR INSTALLATION INSTRUCTIONS
Before installation, these instructions must be carefully read and understood.
DESCRIPTION
GENERAL INSTALLATION INSTRUCTIONS
OPERATING INSTRUCTIONS
The Type E-55 pressure reducing and
regulating valve for cryogenic service is
specifically designed for use in the pressure
build-up circuit and maintains a relatively
constant pressure differential across the valve
even during high flow rates.
Type E-55 regulators should be installed in the
horizontal position with the spring chamber
upright. For other installation requirements,
consult the factory. For ease of operation and
maintenance, it is suggested that manual
shut-off valves be installed upstream and
downstream from the valve. Before installing
the valve, the piping and valve should be
thoroughly flushed out to remove any foreign
material. Install the valve with the inlet pipe
fitted to the inlet connection identified on the
valve body. Use a compatible sealant on the
male pipe threads and do not over tighten the
valve connections.
Adjusting the Delivery Pressure:
The regulator’s delivery pressure setting is
adjusted by turning the adjusting screw (1) at
the top of the spring chamber after loosening
the adjusting screw lock nut (2). To increase
the delivery pressure, turn the adjusting
screw clockwise (into the spring chamber).
To decrease the delivery pressure, turn the
adjusting screw counter-clockwise (out of the
spring chamber). Tighten the adjusting screw
lock nut after the adjustment has been made.
The Type E-55 pressure reducing valve is also
available for final-line gas service. For specific
information, consult the factory.
SPECIFICATION DATA
Service: Liquid or gas
Sizes: 1¼”, 1½” and 2”
Connections: Threaded internal inlet and outlet
(available with NPT or BSP threads)
Body: Bronze
Temperature Rating: 150°F to -320°F
(65°C to -195.5°C)
Maximum Initial Pressure: 400 psi (27.6 bar)
Capacity:
For specific capacity information, consult
the factory.
CONSTRUCTION
See component description for materials of
construction.
All parts are commercially cleaned for
cryogenic service.
MAINTENANCE INSTRUCTIONS
CAUTION
Before attempting to replace any spare parts, be
sure to shut off all pressure connections to the
valve. With the valve closed, however, system
pressure could still be locked between the
shut-off valve and the inlet and/or outlet sides of
the regulator. Before proceeding with any valve
service, be certain to relieve the pressure from
BOTH sides of the regulator.
Refer to the Type E-55 regulator section view for
parts identification.
It is not necessary to remove the valve from the
line for servicing.
Emerson.com/FinalControl
© 2018 Emerson. All rights reserved.
VCIOM-10778-EN 19/01
CASH VALVE TYPE E-55
CRYOGENIC PRESSURE REDUCING VALVE OR PRESSURE BUILD-UP REGULATOR INSTALLATION INSTRUCTIONS
No.
Component Description
Construction
1
Adjusting Screw
SST
2
Lock Nut
SST
3
Spring Chamber
Bronze
4
Spring Button
Brass
5
Pressure Spring
SST
6
Name Plate
Aluminum
7
Drive Screw
SST
8
Screw
SST
9
O-ring
Teflon
10
Diaphragm Sub
10a
Nut
SST
10b
Washer
SST
10c
Pressure Plate
Brass
10d
Diaphragm
SST
10e
O-ring
Teflon
10f
Pusher Post
Brass
11
Seat Ring
SST
12
Seat Disc
Teflon
13
Piston
Brass
14
Screen
Monel
15
Body
Bronze
16
Gasket
Teflon
17
Gasket
Teflon
18
Bottom Plug
Bronze
19
Screen
Monel
FIGURE 1
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Cash Valve is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions,
Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by
our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without
notice.
Emerson.com/FinalControl
2
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement