Danfoss Start and stop of the SWRO Guide

Danfoss Start and stop of the SWRO Guide
Add to My manuals

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Danfoss Start and stop of the SWRO Guide | Manualzz

Design guide

iSave Energy Recovery Device

Start and stop of the SWRO with iSave hpp.danfoss.com

Design guide

Table of Contents

Start and stop of the SWRO with iSave unit

Prior to start-up..................................................................................................................................................................3

Starting up the system.....................................................................................................................................................3

Daily system shutdown....................................................................................................................................................4

More than one day system shutdown..........................................................................................................................5

2 180R9213 | 521B1164 | DKCFN.PI.003.F7.02 | 09.2017

Design guide Start and stop of the SWRO with iSave unit

Below procedures are general guidelines for the start-up and shut-down functions of SWROsystems with the Danfoss iSave Energy Recovery

Device.

Procedure details may differ depending on the system design.

The numbers marked in () refer to the diagram on page 5.

iSave can be both a single iSave and multiple iSaves in parallel.

General SWRO system understanding with

ISave

• Basically the permeate flow is the same as the

flow from the high-pressure pump.

• The HP concentrate flow into iSave HP-in and

HP seawater-out is determined by the rpm of

the iSave.

• The iSave (s) HP flow determines the recovery

rate (higher rpm on the iSave gives lower

recovery rate and vice versa).

• Flow on the low-pressure side of the iSave is

determined by feed pump and the pressure

control valve LP-out (15) (not by the rpm of

the iSave).

• The flow on the low-pressure side must be at

least the same as on the high-pressure side

of the iSave (LP in flow = HP in flow; this is

called balanced flow).

• Continuously operation:

• To minimize mixing, the flow on the

low-pressure side can be adjusted up to 10%

higher than the high-pressure flow with the

limitation that the flow rate at LP inlet may not

exceed 70 m³/h.

180R9213 | 521B1164 | DKCFN.PI.003.F7.02 | 09.2017

Prior to start-up

High quality water extends the service life of the whole system.

Both the APP pump and iSave are sensitive to hard particles.

Before connecting any APP pump or iSave to a piping system ALL pipes must be thorough flushed with high quality pre-filtered water or mechanical cleaned.

1. Install all filter cartridges in the system.

2. With the iSave(s) and APP pump(s) discon-

nected from the piping, the system must be flushed in order to remove possible impurities from the system (pipes, hoses, membranes etc.).

Flushing must run until the system can be ensured clean.

3. Connect the iSave(s) and APP pump(s) to the pipework. The iSave(s) and APP pump(s) are now ready for start-up.

Starting up the system

1. Make sure that all valves are set in normal operating positions.

2. Start the seawater supply pump (A).

3. Make sure all pipework is flushed with water.

Vent all air from the system through air valve

(8) and iSave unit (11). After venting, close valve (8).

At initial start-up also bleed the iSave(s) and

APP pump(s).

3

Design guide

4

Start and stop of the SWRO with iSave unit

4. Start the iSave(s).

In general: Only start the iSaves when the pressure ”HP in” (10) is below 20 barg/290 psig. Always start the iSave unit before the high-pressure pump is started.

There are in principle two ways to start multi ple iSaves:

- Slowly ramp up all the iSaves at the same

time.

- Slowly ramp up one by one.

Starting sequence - one by one: a) Start iSave #1.

b) After 5 sec. start iSave #2.

c) In a sequence of 5 sec. start the

remaining iSaves.

Comments:

- Ramp up time on iSaves is set between

10 –15 sec.

Starting sequence - Start all iSaves at the same time.

Comments:

- Ramp up time on iSaves is set between

10 –15 sec.

If the pressure (10) at ”HP in” drops below

3 barg/43.5 psig, the sound will change of the iSave. This is due to cavitation. ”HP in” pressure at 3 barg/43.5 psig is acceptable for less than 10 min. within a period of 6

hours.

If possible run the iSave at its min allowable speed to reduce cavitation.

“LP-out” pressure (14) is below 1 barg/

14.5 psig, adjust the flow by raising the

flow from the seawater supply pump (A).

3. If the “LP-in” flow (12) is too high, reduce

flow by closing the pressure control

valve (15) or the flow from the seawater

supply pump (A).

10. For iSave 50 and iSave 70:

Check the low pressure flow rates (12), and if required, adjust flow with valve (15) to achieve balanced flow to the iSave(s).

1. If the “LP-in” flow (12) is too low and the

“LP-in” pressure (21) is higher

than 2 barg/29 psig, increase flow and

decrease pressure by opening the

pressure control valve (15).

2. If the “LP-in” flow (12) is too low and the

“LP-in” pressure (21) is below 2 barg/

29 psig, adjust the flow by raising the

flow from the seawater supply pump

(A).

3. If the “LP-in” flow (12) is too high, reduce

flow by closing the pressure control

valve (15) or the flow from the seawater

supply pump (A).

Daily system shutdown

1. The system is running in normal operation and producing permeate flow.

2. Stop the high-pressure pump (4).

5. With a pressure control valve (15), adjust the back pressure of the “LP-out” to fulfill the minimum presure requested in the Data sheet. (May only be necessary at initial start

up).

6. An “over flush” of the iSave can be done to bleed any remaining air from the system.

Flush over a period of minimum 2 minutes.

7. Adjust the speed of the iSave unit to desired flow (rpm). The speed is controlled by a VFD.

3. Keep the iSave(s) (11) running until the

TDS in the high-pressure line is equal to the

TDS in the low-pressure line.

NB! If the pressure (10) at “HP in” drops below 3 barg/43.5 psig, the sound will change of the iSave. This is due to cavitation. “HP in” pressure at

3 barg/43.5 psig is acceptable for less than 10 minutes within a period of 6

hours.

If possible run the iSave at its minimum allowable speed to reduce cavitation.

8. Start the high-pressure pump(s) (4), and the system pressure (5) will rise until the permeate flow (17) almost equals the flow (2) from the high-pressure pump.

9. For iSave 21 and iSave 40:

Check the low pressure flow rates (12), and if required, adjust flow with valve (15) to achieve balanced flow to the iSave(s).

1. If the “LP-in” flow (12) is too low and the

“LP-out” pressure (14) is higher

than 1 barg/14.5 psig, increase flow and

decrease pressure by opening the

pressure control valve (15).

2. If the “LP-in” flow (12) is too low and the

4. Stop the iSave(s)(11).

5. Stop the seawater supply pump (A).

180R9213 | 521B1164 | DKCFN.PI.003.F7.02 | 09.2017

Design guide Start and stop of the SWRO with iSave unit

More than one day system shutdown

1. Run the “daily system shutdown” procedure.

2. Supply permeate water to the SWRO system

by using fresh water/permeate flush

connection..

3. When the pressure ”HP in” (10) is below 20

barg/ 290 psig start the iSave(s).

NB! If the pressure (10) in “HP in” drops

below 3 barg/43.5 psig, the sound will

change of the iSave. This is due to

cavitation. “HP in” pressure at 3 barg/43.5

psig is acceptable for less than 10 minutes

within a period of 6 hours.

If possible run the iSave at its minimum

allowable speed.

4. Start the APP pump(s) in a period of 5 sec. by

using normal ramp-up settings.

5. Stop the APP pump(s) after 5 sec.

6. Run the iSave(s) until the TDS in the high-

pressure line is equal to the TDS in the low-

pressure line.

7. Stop iSave(s) and permeate water supply.

VFD 22

A

Media filter

4 VFD 22

25

PI

B

Filter

3 micron nominel

PI

C

Filter

10 micron absolut

2

3

PI

PS

26

4

18

25

5

PI

PS

6

17

Fresh water permeate flush

PI

PS

21

24

*

12

1

LP in

26

HP out

11 iSave

HP in

18

HP out

11

HP in

7

Full flow cleaning/CIP

10

PI

9

8

Flowmeter

16

28

23

VFD

23

VFD

14

PI

13

PS

20 15 27

19

*

Second stage filter: If recommended housing design and cartridges are not used, a second stage filter is required

Drain

CIP

Permeate

180R9213 | 521B1164 | DKCFN.PI.003.F7.02 | 09.2017

5

Danfoss A/S

High Pressure Pumps

Nordborgvej 81

DK-6430 Nordborg

Denmark

© Danfoss | DCS (im) | 2017.09

1

80R9213 | 521B1164 | DKCFN.PI.003.F7.02

| 6

advertisement

Related manuals

Download PDF

advertisement