Danfoss FVF Data Sheet | Manualzz
Data sheet
FVF strainer
Description
Strainer is installed to protect sensitive
equipment like meters, pumps, control valves
against danger caused by foreign particles and in
wide range of other applications.
Furthermore, strainer is available with a plug,
magnetic insert or ball valve. Combination with
ball valve allowing a quick and efficient cleaning.
FVF strainer is designed for heating, district
heating and cooling systems.
Strainer removes and retains foreign particles like
welding beads, swarf, sand, etc. carried along by
heating / cooling medium.
Ordering
Main data:
• DN 15-300
• PN 16/25
• Temperature:
- Circulation water / water with glycol:
−10 … 150 °C (PN 16), −20 … 150 °C (PN 25)
• Connections:
- flange (strainer) DIN EN 1092-2
- thread (ball valve)
Flange1) strainer FVF
Picture
DN
(mm)
kVS 2)
(m3/h)
Tmax
Code No.
Tmax
PN 16 with draining ball valve
Code No.
Tmax
PN 16
Code No.
PN 25
15
5.3
065B7726
065B7740
20
9.5
065B7727
065B7741
065B7770
065B7771
25
16.5
065B7728
065B7742
065B7772
065B7773
32
20
065B7729
065B7743
40
33
065B7730
065B7744
065B7774
50
54
065B7731
065B7745
065B7775
65
95
80
140
065B7732
150 oC 3)
065B7733
150 oC
065B7746
065B7747
150 oC
065B7776
065B7777
100
201
065B7734
065B7748
065B7778
125
350
065B7735
065B7749
065B7779
065B7780
150
542
065B7736
065B7750
200
870
065B7737
065B7751
065B7781
250
1.260
065B7738
065B7752
065B7782
300
1.735
065B7739
065B7753
065B7783
Flanges acc. to EN 1092-2 (PN 16 and PN 25 respectively)
2)
For strainers with normal screens
3)
To prevent scalds during draining the draining ball valve must be equipped with drain hose, that leads to drainage system
1)
Flange1) strainer FVF, I-pack
Picture
DN
(mm)
kVS 2)
(m3/h)
Tmax
Code No.
PN 16
065B7754
15
5.1
20
9.2
065B7755
25
15.1
065B7756
32
18.4
065B7757
40
30.6
065B7762
50
49
65
86.7
150 oC
065B7763
065B7764
80
133.6
065B7765
100
192.8
065B7766
125
326.4
065B7767
flanges acc. to EN 1092-2 (PN 16)
2)
for strainers with special screens
1)
© Danfoss | 2019.04
VD.BO.Y2.02 | 1
Data sheet
FVF strainer
Ordering (continuous)
Spare parts FVF-Screen
Picture
DN
(mm)
PN
(bar)
Spare parts FVF-Gasket
Code No.
Picture
(normal)
(fine)
15/20
065B7810
065B7824
25
065B7812
065B7826
32
065B7813
065B7827
40
065B7814
065B7828
50
065B7815
065B7829
65
065B7816
065B7830
80
16, 25
100
065B7817
065B7831
065B7818
065B7832
125
065B7819
065B7833
150
065B7820
065B7834
200
065B7821
065B7835
250
065B7822
065B7836
300
065B7823
065B7837
Accessories FVF-M magnetic insert
DN
(mm)
Picture
25
40
065B7792
50
065B7793
65
065B7794
80
065B7795
100
25/32
065B7887
40
065B7888
50
065B7889
65
065B7890
80
065B7891
100
065B7892
125
065B7893
150
065B7894
200
065B7895
250
065B7896
300
065B7897
Tmax
(°C)
10
(used for
FVF
DN 15 - 50)
065B7791
32
065B7886
DN
(mm)
Picture
065B7790
20
Code No.
15/20
Accessories FVF-B ball valve
Code No.
15
DN
(mm)
15
(used for
FVF
DN 65 - 300)
Code No.
065B7802
150
065B7801
065B7796
125
150
065B7797
200
065B7798
250
065B7799
300
065B7800
Technical data
Nominal diameter
DN
15
20
25
32
40
50
65
80
100
125
150
200
250
300
5.3
9.5
16.5
20
33
54
95
140
201
350
542
870
1260
1735
5.0
9.0
14.8
18
30
48
85
131
189
320
494
818
1184
1631
5.1
9.2
15.1
18.4
30.6
49
86.7
133.6
192.8
326.4
normal screen
4.8
8.6
14.9
18
29
49
86
127
183
316
489
809
1172
1613
fine screen
4.5
8.1
13.3
16
27
44
77
119
170
297
459
760
1101
1516
normal screen
kVS value
fine screen
special screen
kVS value
(with magnetic insert)
normal screen
Mesh size
fine screen
m3/h
mm
0.54
0.87
Number of meshes
fine screen
1.18
0.25
special screen
normal screen
-
0.40
n/cm2
150
-
64
25
625
special screen
280
Flow medium
-
Circulation water / glycolic water up to 50%
Nominal pressure
PN
16 or 25
Medium temperature
o
C
−10 ... 150 (PN 16), −20 ... 150 (PN 25)1)
Connection
Flanges acc. to DIN EN 1092-2 (PN 16 and PN 25 respectively)
Materials
Body (strainer)
PN 16
Grey cast iron EN-GJL-250 (GG-25)
PN 25
Ductile iron EN-GJS-400-18-LT (GGG 40.3)
Body (ball valve)
Dezincing free brass CuZn36Pb2As
Screen
Stainless steel, mat. No 1.4301
Gasket
1)
Graphite
Danfoss uses environmentally friendly paint that is resistant to a temperature of 150 C.
2 | VD.BO.Y2.02
o
© Danfoss | 2019.04
Data sheet
Pressure temperature
diagram
FVF strainer
PN
25
❶ EN-GJS-400-18-LT (GGG 40.3) PN 25
➋ EN-GJL-250 (GG 25) PN 16
❶
20
❷
15
10
Note: Danfoss uses environment
friendly paint which may crack at
temperatures above 150 °C.
0
120
140
160
180
200
220
240
260
280
300
320
340 350
o
C
Maximum allowed operating pressure as a function of medium temperature (according to EN 1092-2).
Flow diagram
Standard screen
Installation positions
Fine screen
The medium flow direction must correspond to
an arrow on the strainer body.
Strainers are to be installed in horizontal position
with mesh bonet directed downwards. Vertical
position is also allowed (be aware - when
medium flows upwards strainer retains all
foreign particles but is not able to collect them).
Sufficient space to pull out the mesh for
replacement and cleaning must be ensured.
© Danfoss | 2019.04
VD.BO.Y2.02 | 3
Data sheet
FVF strainer
Design
A
Body
Cover
Screen
Gasket
Screw
Nut
Plug screw
Magnet
Washer
Handle
Ball
Stem
A
With magnetic insert
Dimensions
With ball valve
L
H
DN
Ød
ØD
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
dk
DN
L
H
ØD
15
20
25
32
40
50
65
80
100
125
150
200
250
300
130
150
160
180
200
230
290
310
350
400
480
600
730
850
75
75
90
90
110
120
140
165
220
260
300
360
470
560
95
105
115
140
150
165
185
200
220
250
285
340
405
460
PN 16
Ød
dk
mm
14
65
14
75
14
85
19
100
19
110
19
125
19
145
19
160
19
180
19
210
23
240
23
295
28
355
28
410
ØD
PN 25
d
dk
Weight
(kg)
95
105
115
140
150
165
185
200
235
270
300
360
425
485
14
14
14
19
19
19
19
19
23
28
28
28
31
31
65
75
85
100
110
125
145
160
190
220
250
310
370
430
2.2
3.3
3.8
5.0
6.5
8.5
12.0
16.6
25.0
39.0
61.0
109
162
280
L1
10
15
L
L1
H
D
36
52
12.5
15.5
mm
47
60
43
50
DN
DN
H
Ball valve
L
D
Danfoss A/S
Heating Segment • heating.danfoss.com • +45 7488 2222 • E-Mail: [email protected]
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and all Danfoss logotypes are trademarks of Danfoss A/S. All rights reserved.
4 | VD.BO.Y2.02
© Danfoss | DHS-SRMT/SI | 2019.04
Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Download PDF

advertisement