Vacon 10 Machinery User Guide
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Table of contents
Document code: DPD00288B3
Edited: 20.01.2011
1. Safety
1.1 Warnings
1.2 Safety instructions
1.3 Earthing and earth fault protection
1.4 Before running the motor
2. Receipt of delivery
2.1 Type designation code
2.2 Storage
2.3 Maintenance
2.4 Warranty
2.5 Manufacturer’s declaration of conformity
3. Installation
3.1 Mechanical installation
3.1.1 Vacon 10 dimensions
3.1.2 Cooling
3.1.3 EMC levels
3.1.4 Changing the EMC protection class from C2 or C3 to
C4 for IT networks
3.2 Cabling and connections
3.2.1 Power cabling
3.2.2 Control cabling
3.2.3 Cable and fuse specifications
3.2.4 General cabling rules
3.2.5 Stripping lengths of motor and mains cables
3.2.6 Cable installation and the UL standards
3.2.7 Cable and motor insulation checks
4. Commissioning
4.1 Commissioning steps of Vacon 10
5. Fault tracing
6. Vacon 10 Application Interface
6.1 Introduction
6.2 Control I/O
8
8
8
9
10
11
6
7
8
4
4
6
11
12
13
13
18
21
22
22
22
23
14
15
15
16
23
25
28
28
30
7. Control panel
7.1 General
7.2 Display
7.3 Keypad
7.4 Navigation on the Vacon 10 control panel
7.4.1 Main menu
7.4.2 Reference menu
7.4.3 Monitoring menu
7.4.4 Parameter menu
7.4.5 Fault history menu
8. STANDARD application parameters
8.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
8.2 Motor settings (Control panel: Menu PAR -> P1)
8.3 Start/stop setup (Control panel: Menu PAR -> P2)
8.4 Frequency references (Control panel: Menu PAR -> P3)
38
39
40
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4) 45
8.6 Digital inputs (Control panel: Menu PAR -> P5) 45
8.7 Analogue inputs (Control panel: Menu PAR -> P6)
8.8 Digital and analogue outputs (Panel: Menu PAR -> P7)
46
47
41
43
44
44
34
34
35
36
32
32
32
33
8.9 Protections (Control panel: Menu PAR -> P9)
8.10 Fault autoreset parameters (Panel: Menu PAR -> P10)
48
49
8.11 PI control parameters (Control panel: Menu PAR -> P12) 50
8.12 Easy usage menu (Control panel: Menu PAR -> P0) 51
8.13 System parameters
9. Parameter descriptions
9.1 Motor settings (Control panel: Menu PAR -> P1)
9.2 Start/Stop setup (Control panel: Menu PAR -> P2)
51
53
53
58
9.3 Frequency references (Control panel: Menu PAR -> P3)
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
9.5 Digital inputs (Control panel: Menu PAR -> P5)
9.6 Analoque inputs (Control panel: Menu PAR -> P6)
9.7 Digital and analoque outputs (Panel: Menu PAR -> P7)
9.8 Motor thermal protection (parameters 9.7 - 9.10)
69
70
9.9 Fault autoreset parameters (Panel: Menu PAR -> P10) 75
9.10 PI control parameters (Control panel: Menu PAR -> P12) 76
62
63
67
68
9.11 Easy usage menu (Control panel: Menu PAR -> P9)
9.11.1 Termination resistor
9.11.2 Modbus address area
9.11.3 Modbus process data
79
79
79
80
10. Technical data
10.1 Vacon 10 technical data
10.2 Power ratings
10.2.1 Vacon 10 - Mains voltage 115 V
10.2.2 Vacon 10 - Mains voltage 208 - 240 V
10.2.3 Vacon 10 - Mains voltage 380 - 480 V
10.2.4 Vacon 10 - Mains voltage 575 V
10.3 Brake resistors
82
82
84
84
84
85
86
86
safety vacon
•
4
1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY
OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully:
= Dangerous voltage
Risk of death or severe injury
= General warning
Risk of damage to the product or connected appliances
1.1 Warnings
The components of the power unit of the frequency converter are live when Vacon 10 is connected to mains. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals -/+ are live when Vacon 10 is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the relay output terminals may have a dangerous control voltage present even when Vacon 10 is disconnected from mains.
The earth leakage current of Vacon 10 frequency converters exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
If the frequency converter is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
If Vacon 10 is disconnected from mains while running the motor, it remains live if the motor is energized by the process.
In this case the motor functions as a generator feeding energy to the frequency converter.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
1
5
• vacon safety
After disconnecting the frequency converter from the mains, wait until the fan stops and the indicators on the display go out. Wait 5 more minutes before doing any work on Vacon 10 connections.
The motor can start automatically after a fault situation, if the autoreset function has been activated
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
safety
1.2 Safety instructions
vacon
•
6
The Vacon 10 frequency converter has been designed for fixed installations only.
Do not perform any measurements when the frequency converter is connected to the mains.
Do not perform any voltage withstand tests on any part of
Vacon 10. The product safety is fully tested at factory.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the frequency converter.
Do not open the cover of Vacon 10. Static voltage discharge from your fingers may damage the components. Opening the cover may also damage the device. If the cover of Vacon 10 is opened, warranty becomes void.
1.3 Earthing and earth fault protection
The Vacon 10 frequency converter
must always
be earthed with an earthing conductor connected to the earthing terminal. See figure below:
•
The earth fault protection inside the frequency converter protects only the converter itself against earth faults.
•
If fault current protective switches are used they must be tested with the drive with earth fault currents that are possible to arise in fault situations.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
1
7
• vacon
1.4 Before running the motor
Checklist:
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor shaft rotation direction make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
safety
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of delivery vacon
•
8
2. RECEIPT OF DELIVERY
After unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
2.1 Type designation code
Vacon 0010 - 1L - 0001 - 4 Machinery +SMO1 +EMC2
Changes to default setup:
+SM01 = API RS-485 -> API Full
+EMC2 = EMC C4 -> EMC C2
Version
Voltage rating
1 = 115 Vac
2 = 208–240Vac
4 = 380–480Vac
6 = 575 Vac
Current rating
Input phase
Product range:
Figure 2.1: Vacon 10 type designation code
2.2 Storage
If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable:
Storing temperature-40…+70°C
Relative humidity < 95%, no condensation
2.3 Maintenance
In normal operating conditions, Vacon 10 frequency converters are maintenancefree.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
2
9
• vacon receipt of delivery
2.4 Warranty
Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications. Neither can the manufacturer be held responsible for consequential damages.
The Manufacturer's time of warranty is 18 months from the delivery or 12 months from the commissioning whichever expires first (General Conditions NL92/Orgalime
S92).
The local distributor may grant a warranty time different from the above. This warranty time shall be specified in the distributor's sales and warranty terms. Vacon assumes no responsibility for any other warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
receipt of delivery
2.5 Manufacturer’s declaration of conformity
vacon
•
10
EU DECLARATION OF CONFORMITY
We
Manufacturer's name:
Manufacturer's address:
Vacon Oyj
P.O.Box 25
Runsorintie 7
FIN-65381 Vaasa
Finland hereby declare that the product
Product name:
Vacon 10 Frequency Converter
Model designation:
Vacon 10 1L 0001 1…to 1L 0005 1
Vacon 10 1L 0001 2…to 1L 0009 2
Vacon 10 3L 0001 2…to 3L 0011 2
Vacon 10 3L 0001 4...to 3L 0012 4
Vacon 10 3L 0002 6…to 1L 0011 6 has been designed and manufactured in accordance with the following standards:
Safety:
EN 61800-5-1 (2003)
EMC:
EN 61800-3 (2004) and conforms to the relevant safety provisions of the Low Voltage
Directive
2006/95/EC and EMC Directive 2004/108/EC.
It is ensured through internal measures and quality control that the product conforms at all times to the requirements of the current Directive and the relevant standards.
In Vaasa, 6th of May, 2008
Vesa Laisi
President
2
24-hour support +358 (0)40 837 1150 • Email: [email protected]
2
11
• vacon installation
3. INSTALLATION
3.1 Mechanical installation
There are two possible ways to mount Vacon 10 in the wall; either screw or DIN-rail mounting. The mounting dimensions are given on the back of the drive and on the following page.
MI1
=M 4
MI2-3
=M 5
Figure 3.2: Screw mounting
1 2
3
Figure 3.3: DIN-rail mounting
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation
3.1.1 Vacon 10 dimensions
W2
W3
D2
vacon
•
12
H1 H2 H3
W1
Figure 3.4: Vacon 10 dimensions, MI1-MI3
D1
Type H1 H2 H3 W1 W2
MI1 160.1
147 137,3 65,5 37,8
MI2 195 183 170 90
MI3 254,3 244 229,3 100
Table 3.1: Vacon 10 dimensions in millimetres
62,5
75
W3
4,5
5,5
5,5
D1
98,5
101,5
108,5
D2
7
7
7
24-hour support (0)201 212 575 • Email: [email protected]
3
3
13
• vacon installation
3.1.2 Cooling
Forced air flow cooling is used in all Vacon 10 drives.
Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below:
Type Dimensions (mm)
A B
MI1
MI2
100
100
50
50
MI3 100 50
Table 3.2: Dimensions required for cooling
A
Type
Cooling air required (m
3
/h)
MI1 10
MI2 10
MI3
Table 3.3: Required cooling air
30
B
NOTE!
See the mounting dimensions on the back of the drive.
Leave
free space
for cooling above
(100 mm)
, below
(50 mm)
, and on the sides
(10 mm)
of Vacon 10! (Side-to-side installation allowed only if the ambient temperature is below 40°C)
.
3.1.3 EMC levels
EN61800-3 defines the division of frequency converters into five classes according to the level of electromagnetic disturbances emitted, the requirements of a power system network and the installation environment (see below). The EMC class of each product is defined in the type designation code.
Category C1:
Frequency converters of this class comply with the requirements of category C1 of the product standard EN 61800-3 (2004). Category C1 ensures the best EMC characteristics and it includes converters the rated voltage of which is less than 1000V and which are intended for use in the 1st environment. NOTE: The requirements of class C are fulfilled only as far as the conducted emissions are concerned.
Category C2:
Frequency converters of this class comply with the requirements of category C2 of the product standard EN 61800-3 (2004). Category C2 includes converters in fixed installations and the rated voltage of which is less than 1000V. The class C2 frequency converters can be used both in the 1st and the 2nd environment.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon
•
14
Category C3:
Frequency converters of this class comply with the requirements of category C3 of the product standard EN 61800-3 (2004). Category C3 includes converters the rated voltage of which is less than 1000V and which are intended for use in the second environment only.
Category C4:
The drives of this class do not provide EMC emission protection. These kinds of drives are mounted in enclosures.
Category C4 for IT networks:
Frequency converters of this class fulfil the product standard EN 61800-3 (2004) if intended to be used in IT systems. In IT systems, the networks are isolated from earth, or connected to earth through high impedance to achieve a low leakage current. NOTE: if converters are used with other supplies, no
EMC requirements are complied with.
Environments in product standard EN 61800-3 (2004)
First environment:
Environment that includes domestic premises. It also includes establishments directly connected without intermediate transformers to a low-voltage power supply network which supplies buildings used for domestic purposes.
NOTE: houses, apartments, commercial premises or offices in a residential building are examples of first environment locations.
Second environment:
Environment that includes all establishments other than those directly connected to a low-voltage power supply network which supplies buildings used for domestic purposes.
NOTE: industrial areas, technical areas of any building fed from a dedicated transformer are examples of second environment locations.
3.1.4 Changing the EMC protection class from C2 or C3 to C4 for IT networks
The EMC protection class of Vacon 10 frequency converters can be changed from class C2 or C3 to class C4 for IT networks by
removing the EMC-capacitor disconnecting screw
, see figure below.
Note!
Do not attempt to change the EMC level back to class C2 or C3. Even if the procedure above is reversed, the frequency converter will no longer fulfil the EMC requirements of class C2/C3!
24-hour support (0)201 212 575 • Email: [email protected]
3
15
• vacon
3.2 Cabling and connections
3.2.1 Power cabling
Note!
Tightening torque for power cables is 0.5 - 0.6 Nm
3~ (230V, 400V)
1~ (230V)
Motor out
installation
3
Strip the plastic cable coating for 360 ° earthing
Strip the plastic cable coating for
360 ° earthing
MOTOR
MAINS
Figure 3.5: Vacon 10 power connections, MI1
3~ (230V, 400V) External brake resistor
3~
(230, 400V)
1~ (230V) 1~ (115V)
L1 L2/N L3
Motor out
R+ RU/T1 V/T2 W/T3
MAINS
BRAKE
RESISTOR
MOTOR
Figure 3.6: Vacon 10 power connections, MI2 - MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation
3.2.2 Control cabling
vacon
•
16
Attach the support
AFTER installing the power cables
Attach this plate
BEFORE installing the power cables
Figure 3.7: Mount the PE- plate and API cable support
24-hour support (0)201 212 575 • Email: [email protected]
3
17
• vacon installation
Figure 3.8: Open the lid
3
Control cable tightening torque: 0.4 Nm
Strip the plastic cable coating for
360 ° earthing
Figure 3.9: Install the control cables. See Chapter 6.3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon
•
18
3.2.3 Cable and fuse specifications
Use cables with heat resistance of at least +70 C. The cables and the fuses must be dimensioned according to the tables below. Installation of cables according to UL
regulations is presented in Chapter 3.2.6.
The fuses function also as cable overload protection.
These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. In any other case, ask the factory for more information.
EMC category
Mains cable types
cat. C2
1
cat. C3
1
cat. C4
1
Motor cable types 3 2 1
Control cable types 4 4 4
Table 3.4: Cable types required to meet standards. EMC categories are
Cable type Description
1
2
3
Power cable intended for fixed installation and the specific mains voltage. Shielded cable not required.
(NKCABLES/MCMK or similar recommended)
Power cable equipped with concentric protection wire and intended for the specific mains voltage.
(NKCABLES /MCMK or similar recommended).
Power cable equipped with compact low-impedance shield and intended for the specific mains voltage.
(NKCABLES /MCCMK, SAB/ÖZCUY-J or similar recommended).
*360º earthing of both motor and FC connection required to meet the standard
4
Screened cable equipped with compact low-impedance shield
(NKCABLES /Jamak, SAB/ÖZCuY-O or similar).
Table 3.5: Cable type descriptions
24-hour support (0)201 212 575 • Email: [email protected]
3
3
19
• vacon installation
Terminal cable size (min/max)
Frame Type
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Main terminal
[mm
2
]
MI2 0001-0004 20 2*2.5+2.5
3*1.5+1.5
1.5-4
MI3 0005 20 2*2.5+2.5
3*1.5+1.5
1.5-4
Table 3.6: Cable and fuse sizes for Vacon 10, 115V, 1~
Earth terminal
[mm
2
]
Control terminal
[mm
2
]
Relay terminal
[mm
2
]
1.5-4
1.5-4
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
Frame Type
Terminal cable size (min/max)
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Main terminal
[mm
2
]
Earth terminal
[mm
2
]
Control terminal
[mm
2
]
Relay terminal
[mm
2
]
MI1 0001-0004 10
MI2 0005-0007 20
MI3 0009 32
208 - 240V, 1~
2*1.5+1.5
3*1.5+1.5
2*2.5+2.5
3*1.5+1.5
2*6+6 3*1.5+1.5
208 - 240V, 3~
1.5-4
1.5-4
1.5-6
1.5-4
1.5-4
1.5-6
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
MI1 0001-0003 6
MI2 0004-0007 10
3*1.5+1.5
3*1.5+1.5
3*1.5+1.5
3*1.5+1.5
1.5-4
1.5-4
1.5-4
1.5-4
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
MI3 0011 20 3*2.5+2.5
3*2.5+2.5
1.5-6 1.5-6 0.5-1.5
0.5-1.5
Table 3.7: Cable and fuse sizes for Vacon 10, 208 - 240V, 1~ and 3~
Terminal cable size (min/max)
Frame Type
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Main terminal
[mm
2
]
Earth terminal
[mm
2
]
Control terminal
[mm
2
]
Relay terminal
[mm
2
]
MI1 0001-0003 6 3*1.5+1.5
3*1.5+1.5
1.5-4 1.5-4
MI2 0004-0006 10 3*1.5+1.5
3*1.5+1.5
1.5-4 1.5-4
MI3 0008-0012 20 3*2.5+2.5
3*2.5+2.5
1.5-6 1.5-6
Table 3.8: Cable and fuse sizes for Vacon 10, 380 - 480V, 3~
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon
•
20
Terminal cable size (min/max)
Frame Type
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Main terminal
[mm
2
]
MI3 0002-0004 6 3*1.5+1.5
3*1.5+1.5
1.5-4
MI3 0005-0006 10 3*1.5+1.5
3*1.5+1.5
1.5-4
MI3 0009 20 3*2.5+2.5
3*2.5+2.5
1.5-6
Table 3.9: Cable and fuse sizes for Vacon 10, 575V
Earth terminal
[mm
2
]
Control terminal
[mm
2
]
Relay terminal
[mm
2
]
1.5-4
1.5-4
1.5-6
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
Note!
To fulfil standard EN61800-5-1, the protective conductor should be
at least
10mm
2
Cu or 16mm
2
Al
. Another possibility is to use an additional protective conductor of at least the same size as the original one.
24-hour support (0)201 212 575 • Email: [email protected]
3
21
• vacon installation
3.2.4 General cabling rules
1
Before starting the installation, check that none of the components of the frequency converter is live.
2
Place the motor cables sufficiently far from other cables:
•
Avoid
placing the motor cables in long
parallel lines
with other cables
• If the motor cable runs in parallel with other cables, the
minimum distance
between the motor cable and other cables is
0,3 m
.
• The given distance also applies between the motor cables and signal cables of other systems.
• The
maximum length
of the motor cables is
30 m
• The
motor cables
should cross other cables at an angle of
90 degrees
.
3
If cable insulation checks are needed, see Chapter 3.2.7.
4
Connecting the cables:
• Strip the motor and mains cables as advised in Figure 3.10.
• Connect the mains, motor and control cables into their respective
terminals, see Figures 3.5 - 3.9.
• Note the tightening torques of
power cables and control cables
• For information on cable installation according to UL regulations
• Make sure that the control cable wires do not come in contact with the electronic components of the unit
• If an
external brake resistor
(option) is used, connect its cable to the appropriate terminal.
•
Check the connection
of the earth cable to the motor and the frequency converter terminals marked with
• Connect the
separate shield of the motor cable to the earth plate
of the frequency converter, motor and the supply centre
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation
3.2.5 Stripping lengths of motor and mains cables
Earth conductor
8 mm 8 mm
vacon
•
22
35 mm
20 mm
Figure 3.10: Stripping of cables
Note!
Strip also the plastic cover of the cables for 360 degree earthing. See Figures
3.2.6 Cable installation and the UL standards
To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a minimum heat-resistance of +60/75 C must be used.
3.2.7 Cable and motor insulation checks
These checks can be performed as follows if motor or cable insulations are suspected to be faulty.
1. Motor cable insulation checks
Disconnect the motor cable from terminals U/T1, V/T2 and W/T3 of the frequency converter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1MOhm.
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2/N and L3 of the frequency converter and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor.The insulation resistance must be >1MOhm.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed
1000 V. The insulation resistance must be >1MOhm.
24-hour support (0)201 212 575 • Email: [email protected]
3
4
23
• vacon commissioning
4. COMMISSIONING
Before commissioning, note the warnings and instructions listed in
Chapter 1!
4.1 Commissioning steps of Vacon 10
1
Read carefully the safety instructions in Chapter 1 and follow them.
2
After the installation, make sure that:
• both the frequency converter and the motor are grounded
• the mains and motor cables comply with the requirements given in Chapter 3.2.3
• the control cables are located as far as possible from the power cables (see Chapter , step 2) and the shields of the shielded cables are connected to protective earth
3
Check the quality and quantity of cooling air (Chapter 3.1.2)
4
Check that all Start/Stop switches connected to the I/O terminals are in
Stop
-position.
5
Connect the frequency converter to mains
Note: The following steps are valid if you have API Full or API Limited Application Interface in your Vacon 10.
6
Set the parameters of group 1 according to the requirements of your application. At least the following parameters should be set:
• motor nominal voltage (par. 1.1)
• motor nominal frequency (par. 1.2)
• motor nominal speed (par. 1.3)
• motor nominal current (par. 1.4)
You will find the values needed for the parameters on the motor rating plate
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
commissioning vacon
•
24
Perform test run
without motor
. Perform either Test A or Test B:
7
10
A)
Control from the I/O terminals:
• Turn the Start/Stop switch to ON position.
• Change the frequency reference (potentiometer)
• Check in the Monitoring Menu that the value of Output frequency changes according to the change of frequency reference.
• Turn the Start/Stop switch to OFF position
B)
Control from the keypad:
• Select the keypad as the control place with par 2.5
. You can also move to keypad control by pressing the navigation wheel for 5 seconds.
• Push the Start button on the keypad
• Check in the Monitoring Menu that the value of Output frequency changes according to the change of frequency reference
• Push the Stop button on the keypad
8
Run the no-load tests without the motor being connected to the process, if possible. If this is not possible, secure the safety of each test prior to running it. Inform your co-workers of the tests.
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of the frequency converter.
• See to that all Start/Stop switches are in Stop positions.
• Switch the mains ON
• Repeat test 7A or 7B
9
Perform an identification run (see par. 1.18), especially if the application requires a high startup torque or a high torque with low speed.
Connect the motor to the process (if the no-load test was run without the motor being connected)
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
24-hour support (0)201 212 575 • Email: [email protected]
4
6
25
• vacon fault tracing
5. FAULT TRACING
Note:
The fault codes listed in this chapter are visible if the Application Interface has a display, like e.g. in API FULL or API LIMITED or if a personal computer has been connected to the drive
When a fault is detected by the frequency converter control electronics, the drive is stopped and the symbol F together with the ordinal number of the fault and the fault code appear on the display in the following format, e.g:
F1 02
Fault code(02=overvoltage)
Fault ordinal number (F1=latest fault)
The fault can be reset by pressing the Stop button on the control keypad or via the I/
O terminal or fieldbus. The faults with time labels are stored in the Fault history menu which can be browsed. The different fault codes, their causes and correcting actions are presented in the table below.
Fault code
1
2
Fault name
Overcurrent
Overvoltage
3
Earth fault
Table 5.10: Fault codes
Possible cause Correcting actions
Frequency converter has detected too high a current
(>4*I
N
) in the motor cable:
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
The DC-link voltage has exceeded the internal safety limit:
• too short a deceleration time
• high overvoltage spikes in mains
Check loading.
Check motor size.
Check cables.
Increase the deceleration time (P.4.3)
Current measurement has detected extra leakage current at start:
• insulation failure in cables or motor
Check motor cables and motor
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
fault tracing vacon
•
26
Fault code
Fault name Possible cause Correcting actions
8
9
11
13
14
15
16
17
System fault
Undervoltage
Output phase supervision
Frequency converter undertemperature
Frequency converter overtemperature
Motor stalled
Motor overtemperature
Motor underload
• component failure
• faulty operation
Reset the fault and restart.
Should the fault re-occur, contact the distributor near to you
NOTE!
If fault F8 occurs, find out the subcode of the fault from the Fault
History menu under M
(minutes)!
The DC-link voltage has gone below the internal safety limit:
• most probable cause: too low a supply voltage
• frequency converter internal fault
• Power outages
In case of temporary supply voltage break reset the fault and restart the frequency converter.
Check the supply voltage.
If it is adequate, an internal failure has occurred.
Contact the distributor near to you
Current measurement has detected that there is no current in one motor phase
Check motor cable and motor
Heat sink temperature is under -
10 C
Check the ambient temperature
Heat sink is overheated.
Motor stall protection has tripped
Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded
Motor underload protection has tripped
Check that the cooling air flow is not blocked.
Check the ambient temperature.
Make sure that the switching frequency is not too high in relation to ambient temperature and motor load.
Check that the motor is able to rotate freely
Decrease the motor load.
If no motor overload exists, check the temperature model parameters.
Check motor and load, e.g. for broken belts or dry pumps
Table 5.10: Fault codes
24-hour support +358 (0)40 837 1150 • Email: [email protected]
6
6
27
• vacon fault tracing
Fault code
Fault name Possible cause Correcting actions
22
25
27
34
35
41
50
51
53
57
EEPROM checksum fault
Microcontroller watchdog fault
Back EMF protection
Internal bus communication
Application fault
IGBT Overtemperature
Analogue input I in
<
4mA (selected signal range 4 to 20 mA)
External fault
Fieldbus fault
Idenfication fault
Parameter save fault
• faulty operation
• component failure
Contact the distributor near to you
• faulty operation
• component failure
Reset the fault and restart.
Should the fault re-occur, contact the distributor near to you.
Drive has detected that the magnetized motor is running in start situation
• A rotating PM-motor
Make sure that there is no rotating PM-motor when the start command is given.
Ambient interference or defective hardware
Application is not working properly
Overtemperature alarm is issued when the IGBT switch temperature exceeds 110 °C
Should the fault re-occur, contact the distributor near to you.
Contact the distributor near to you
Check loading.
Check motor size.
Make identification run.
Current at the analogue input is
< 4mA
• control cable is broken or loose
• signal source has failed
Digital input fault. Digital input has been programmed as external fault input and this input is active.
Check the current loop circuitry
The data connection between the fieldbus Master and the fieldbus of the drive broken
Check installation.
If installation is correct contact the nearest Vacon distributor.
Identification run has failed.
Run command was removed before completion of identification run.
Motor is not connected to frequency converter.
There is load on motor shaft
Table 5.10: Fault codes
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 api vacon
•
28
6. VACON 10 APPLICATION INTERFACE
6.1 Introduction
There are three versions of Application Interfaces (API) available for the Vacon 10 drive:
API Full API Limited
6 Digital inputs
2 Analogue inputs
1 Analogue output
1 Digital output
2 Relay outputs
RS-485 Interface
3 Digital inputs
1 Analogue input
1 Relay output
RS-485 Interface
Table 6.1: Available Application Interfaces
API RS-485 (Modbus
RTU)
1 Digital input
1 Relay output
RS-485 Interface
This section provides you with a description of the I/O-signals for these versions and instructions for using the Vacon 10 general purpose application.
The frequency reference can be selected from the analogue inputs, fieldbus, preset speeds or keypad.
Basic properties:
• Digital inputs DI1…DI6 are freely programmable. The user can assign a single input to many functions
• Digital-, relay- and analogue outputs are freely programmable
• Analogue input 1 can be programmed as current or voltage input in API Limited version
Special features in all API versions:
• Programmable Start/Stop and Reverse signal logic
• Reference scaling.
• Programmable start and stop functions
• DC-brake at start and stop
• Programmable U/f curve
• Adjustable switching frequency
• Autoreset function after fault
• Protections and supervisions (all fully programmable; off, alarm, fault):
24-hour support +358 (0)40 837 1150 • Email: [email protected]
6
29
• vacon vacon 10 api
• Current signal input fault
• External fault
• Undervoltage fault
• Earth fault
• Motor thermal, stall and underload protection
• Fieldbus communication
Special features in API Full and API Limited:
• 8 preset speeds
• Analogue input range selection, signal scaling and filtering
• PI-controller
6
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 api vacon
•
30
6.2 Control I/O
Reference mA
Potentiometer:1~ 10K +/- 5%
Terminal Signal
API FULL
Factory preset
1 +10Vre Ref. voltage out
2 AI1 Analog signal in 1 Freq. reference P)
Description
Maximum load 10 mA
0 - +10 V Ri = 200 k
Ω
(min)
3 GND
6
7
8
9
10 DI3
A A
B B
4
5
24Vout
GND
DI1
DI2
AI2
GND
13 GND
14 DI4
15 DI5
16 DI6
18 AO
20 DO
22 RO 13
23 RO 14
24 RO 22
25 RO 21
26 RO 24
I/O signal ground
24V output for DI's ±
20
%, max. load 50 mA
I/O signal ground
Digital input 1
Start forward
P)
Digital input 2
Digital input 3
Start reverse
P)
Preset speed B0
P)
RS485 signal A
RS485 signal B
FB Communication Positive
FB Communication Negative
Analog signal in 2
PI actual value
P)
0(4) - 20 mA, Ri = 200
Ω
I/O signal ground
I/O signal ground
Digital input 4
Digital input 5
Preset speed B1
P)
0 - +30 V Ri = 12 k
Fault reset
P)
(min)
Digital input 6
Disable PI contr.
P)
Output frequency
P)
0(4) - 20 mA, RL = 500
Ω
Digital signal out
Active = READY
P) Open collector, max. load 48V/50mA
Relay out 1 Active = RUN
P)
Relay out 2 Active = FAULT P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
Table 6.2: Vacon 10 General purpose application default I/O configuration and connections for API FULL version
P) = Programmable function, see parameter lists and descriptions, chapters 8 and
9.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
6
6
31
• vacon vacon 10 api
API LIMITED
Terminal Signal
1 +10Vre Ref. voltage out
2 AI1
Factory preset
Analog signal in 1
Freq. reference
P)
Can be changed to
0(4)mA - 20mA current input with the dip switch (see ch. 9.12.1)
3 GND I/O signal ground
6 24Vout 24V output for DI's
Description
Maximum load 10 mA
0 - +10 V Ri = 200 k
Ω
±
20
%, max. load 50 mA
7 GND
8 DI1
I/O signal ground
Digital input 1
Start forward
P)
9 DI2 Digital input 2
Start reverse P)
10 DI3 Digital input 3
Preset speed B0
P)
A A
B B
RS485 signal A
RS485 signal B
FB Communication Positive
FB Communication Negative
24 RO 22
25 RO 21
Relay out 2 ACTIVE (Relay opened) = FAULT
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
Table 6.3: Vacon 10 General purpose application default I/O configuration and connections for API LIMITED version
P) = Programmable function, parameter lists and descriptions, chapters
8 and 9.
Terminal
3 GND
Signal
I/O signal ground
6 24Vout 24V output for DI's
API RS-485
Factory preset Description
±
20
%, max. load 50 mA
7 GND
8 DI1
I/O signal ground
Digital input 1
A A
B B
RS485 signal A
RS485 signal B
FB Communication Positive
FB Communication Negative
24 RO 22
25 RO 21
Relay out 2 ACTIVE (Relay opened) = FAULT
P)
Max. switching load:
250Vac/2A or 250Vdc/
0,4A
Table 6.4: Vacon 10 General purpose application default I/O configuration and connections for API RS-485 version
P) = Programmable function, parameter lists and descriptions, chapters
8 and 9.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon
•
32
7. CONTROL PANEL
7.1 General
The Vacon 10 API Full and API Limited versions have similar control panels. The panel is integrated to the drive consisting of corresponding application card and an overlay on the drive cover with status display and button clarifications.
The Control panel consists of an LCD display with backlight and a keypad including
a navigation wheel, a green START button and a red STOP button (see Figure 7.11).
7.2 Display
The display includes 14-segment and 7-segment blocks, arrowheads and clear text unit symbols. The arrowheads, when visible, indicate some information about the drive, which is printed in clear text on the overlay (numbers 1…14 in the figure below). The arrowheads are grouped in 3 groups with the following meanings and Eng-
lish overlay texts (see Figure 7.11):
Group 1 - 5; Drive status
1= Drive is ready to start (READY)
2= Drive is running (RUN)
3= Drive has stopped (STOP)
4= Alarm condition is active (ALARM)
5= Drive has stopped due to a fault (FAULT)
Group 6 - 10; Control selections
6= Motor is rotating forward (FWD)
7= Motor is rotating reverse (REV)
8= I/O terminal block is the selected control place (I/O)
9= Keypad is the selected control place (KEYPAD)
10= Fieldbus is the selected control place (BUS)
Group 11 - 14; Navigation main menu
11= Reference main menu (REF)
12= Monitoring main menu (MON)
13= Parameter main menu (PAR)
14= Fault history main menu (FLT)
24-hour support +358 (0)40 837 1150 • Email: [email protected]
7
33
• vacon control panel
1 2
3 4
5
11
12
13
14
Navigation wheel
Stop button
6 7
8
9 10
Start button
7
Figure 7.11: Vacon 10 Control panel
7.3 Keypad
The keypad section of the control panel consists of a navigation wheel and START
and STOP buttons (see Figure 7.11). The navigation wheel is used for navigating on
the panel display, but it also works as a reference potentiometer when KEYPAD has been selected as the control place of the drive. The wheel has two separate functions;
- rotating the wheel e.g. for changing parameter value (12 steps / round)
- pressing the wheel e.g. for accepting the new value.
The drive stops always, regardless of the selected control place, by pressing the keypad STOP button. The drive starts by pressing the keypad START button, but only if the selected control place is KEYPAD.
NOTE!
You can quickly change the active control place from remote (I/O or fieldbus) to local (keypad) by pressing the navigation wheel for about 5 seconds!
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon
•
34
7.4 Navigation on the Vacon 10 control panel
This chapter provides you with information on navigating the menus on Vacon 10 and editing the values of the parameters.
7.4.1 Main menu
The menu structure of Vacon 10 control software consists of a main menu and several submenus. Navigation in the main menu is shown below:
REFERENCE
MENU
Displays the keypad reference value regardless of the selected control place.
REF
MON
PAR
FLT
READY RUN
FWD REV
STOP ALARM FAULT
Hz
I/O KEYPAD BUS
PUSH
REF
READY RUN
MON
PAR
FLT
FWD REV
STOP ALARM FAULT
Hz
I/O KEYPAD BUS
ROTATE
MONITORING
MENU
In this menu you can browse the monitoring values.
REF
MON
READY RUN STOP ALARM FAULT
PAR
FLT
FWD REV I/O KEYPAD BUS
PUSH
REF
MON
READY RUN STOP ALARM FAULT
PAR
FLT
FWD REV I/O KEYPAD BUS
ROTATE
PARAMETER
MENU
In this menu you can browse and edit the parameters.
READY RUN STOP ALARM FAULT
REF
MON
PAR
FLT
FWD REV I/O KEYPAD BUS
REF
MON
PUSH
PAR
FLT
READY RUN
FWD REV
STOP ALARM FAULT
I/O KEYPAD BUS
ROTATE
READY RUN
FAULT HISTORY
MENU
Here you will be able to browse through the faults occurred.
REF
MON
PAR
FLT
FWD REV
STOP ALARM FAULT
I/O KEYPAD BUS
PUSH
REF
MON
READY RUN
PAR
FLT
STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
Figure 7.12: The main menu of Vacon 10
24-hour support +358 (0)40 837 1150 • Email: [email protected]
7
35
• vacon
7.4.2 Reference menu
REF
READY RUN
MON
PAR
FLT
FWD REV
STOP ALARM FAULT
Hz
I/O KEYPAD BUS
control panel
Push to enter edit mode
Change value
Push to confirm
Figure 7.13: Reference menu display
Move to the reference menu with the navigation wheel (see Figure 7.12). The refe-
rence value can be changed with the navigation wheel as shown in Figure 7.13. The
reference value follows the rotation continuously (= without separate new value acceptance) .
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel
7.4.3 Monitoring menu
Alternates in the display
REF
READY RUN
MON
PAR
FLT
STOP ALARM FAULT
Hz
FWD REV I/O KEYPAD BUS
vacon
•
36
Browse
M1.1 - M1.20
Figure 7.14: Monitoring menu display
Monitoring values mean actual values of measured signals as well as statuses of some control settings. They are visible in API Full and Limited display, but they can-
not be edited. The monitoring values are listed in Table 7.15.
Pushing the navigation wheel once in this menu takes the user to the next level,
where the monitoring value, e.g. M1.11 and value are visible (see Figure 7.12). The
monitoring values can be browsed by rolling the navigation wheel clockwise, as
24-hour support +358 (0)40 837 1150 • Email: [email protected]
7
7
37
• vacon control panel
Code
M1.1
M1.2
M1.3
M1.4
M1.5
M1.6
M1.15
M1.16
M1.18
M1.19
Monitoring signal
Output frequency
Frequency reference
Motor shaft speed
Motor current
Motor torque
Motor power
M1.7
M1.8
Motor voltage
DC-link voltage
M1.9
Unit temperature
M1.10
Motor temperature
M1.11
Analogue input 1
M1.12
Analogue input 2
M1.13
Analogue output
M1.14
DI1, DI2, DI3
DI4, DI5, DI6
RO1, (also RO2, DO in
API FULL)
M1.17
PI setpoint
PI feedback
PI error value
Unit
Hz
Hz rpm
A
%
%
%
%
%
V
V
°C
%
%
%
%
M1.20
PI Output %
Table 7.15: Vacon 10 monitoring signals
ID Description
2
3
1
25
6
7
8
Frequency to the motor
4
5
Calculated motor speed
Measured motor current
Calculated actual/nominal torque of the motor
Calculated actual/nominal power of the motor
Motor voltage
Measured DC-link voltage
Heat sink temperature
Calculated motor temperature
13 AI1 value
14 AI2 value
ONLY IN API FULL!
26 AO1
ONLY IN API FULL!
15 Digital input statuses
16
Digital input statuses
ONLY IN API FULL!
17 Relay/digital output statuses
20
21
22
23
In percent of the maximum process reference
In percent of the maximum actual value
In percent of the maximum error value
In percent of the maximum output value
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon
•
38
7.4.4 Parameter menu
In Parameter menu only the Quick setup parameter list is shown by default. By giving the value 0 to the parameter 13.1, it is possible to open other advanced parameter groups. The parameter lists and descriptions can be found in chapters 8 and 9.
The following figure shows the parameter menu view:
Alternates in the display
REF
MON
READY RUN
PAR
FLT
FWD REV
STOP ALARM FAULT
Hz
I/O KEYPAD BUS
Browse
P1.1 ->
Push to enter edit mode
Figure 7.15: Parameter menu
Change value
Push to confirm
24-hour support +358 (0)40 837 1150 • Email: [email protected]
7
7
39
• vacon
7.4.5 Fault history menu
REF
READY RUN
MON
PAR
FLT
FWD REV
STOP ALARM FAULT
I/O KEYPAD BUS
Push control panel
REF
READY RUN
MON
PAR
FLT
FWD REV
STOP ALARM FAULT
I/O KEYPAD BUS
Browse faults 1-9
REF
MON
PAR
READY RUN
FLT
STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
Push
REF
MON
PAR
READY RUN
FLT
STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
Browse for days (D), hours (H) and minutes (M)
Figure 7.16: Fault history menu
In Fault history menu you can browse through 9 latest faults (see Figure 7.16). If a
fault is active, the relevant fault number (e.g. F1 02) alternates in the display with main menu. When you browse between the faults, the fault codes of active faults are blinking. The active faults can be reset by pressing the STOP button for 1 time. If the fault cannot be reset, the blinking continues. It is possible to navigate in the menu structure also when there are active faults present, but the display returns automatically to the fault menu if buttons or navigation wheel are not pressed or navigation is not rotated. The operating date, hour and minute values at the fault instant are shown in the value menu (operating hours = displayed reading).
Note! The whole fault history can be cleared by pressing STOP button for 5 sec time when the drive is stopped and Fault history menu is selected in the display.
See Chapter 5 for fault descriptions
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon
•
40
8. STANDARD APPLICATION PARAMETERS
On the next pages you can find the lists of parameters within the respective parameter groups. The parameter descriptions are given in Chapter 9.
NOTE: Parameters can only be changed when drive is in stop mode!
Explanations:
Code:
Location indication on the keypad; Shows the operator the present
Monitoring value number or Parameter number
Parameter:
Name of monitoring value or parameter
Min:
Max:
Unit:
Unit of parameter value; given if available
Default:
Factory value
ID:
Minimum value of parameter
Maximum value of parameter i
ID number of the parameter (used with fieldbus control)
More information on this parameter available in chapter 9: ‘Parameter descriptions’ click on the parameter name.
NOTE: This manual is for Vacon 10 standard application only. If you are using a special application, please download the appropriate user manual on http://www.vacon.com -> Support & Downloads.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
41
• vacon parameters
8.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
i i i i i i i i i i
Code
P1.1
P1.2
P1.3
P1.4
P1.5
P1.7
P1.15
P2.1
P2.2
P2.3
P3.1
P3.2
P3.3
P3.4
P3.5
P3.6
P3.7
Parameter
Motor nominal voltage
Motor nominal frequency
Motor nominal speed
Motor nominal current
Motor cos Ï•
Current limit
Torque boost
Remote control place
Start function
Stop function
Min frequency
Max frequency
I/O reference
Preset speed 0
Preset speed 1
Preset speed 2
Preset speed 3
Min Max Unit Default ID
180 690 V
230
400
575
110
30 320
0,2 x
I
Nunit
2,0 x
I
Nunit
Hz
300 20000 rpm
0,30 1,00
A
50,00
1440
I
Nunit
Note
Check rating plate on the motor
111
112
113
120
Check rating plate on the motor
Default applies for a 4pole motor.
Check rating plate on the motor
Check rating plate on the motor
I
0,2 x
Nunit
2 x
I
Nunit
0
1
1
2
0
0
1
1
0,00 P3.2
P3.1
320
0 4
0,00 P3.2
0,00 P3.2
0,00 P3.2
0,00 P3.2
P4.2
Acceleration time 0,1 3000
A
Hz
Hz
Hz
Hz
Hz
Hz s
0,85
1,5 x
I
Nunit
0
1
0
0
0,00
50,00
3
5,00
10,00
15,00
20,00
1,0
107
109
0
= Not used
1
= Used
172
1
= I/O terminal
2
= Fieldbus
(one selection removed)
505
0
= Ramp
1
= Flying start
506
0
= Coasting
1
= Ramp
101
102
117
0
= Preset Speeds (0-7)
1
= Keypad Reference
2
= Fieldbus Reference
3
= AI1
(API FULL &
LIMITED)
124
105
106
126
103
4
= AI2
(API FULL)
Activated by digital inputs
Activated by digital inputs
Activated by digital inputs
Activated by digital inputs
Acceleration time from 0
Hz to maximum frequency
Table 8.1: Quick setup parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon
•
42
Code
P6.5
AI2 Signal range
(API Full only)
P10.4
Fault autoreset
P13.1
Parameter
P6.1
AI1 Signal range
Parameter conceal
Min Max Unit Default ID
P4.3
Deceleration time 0,1 3000
0
2
0
0
3
3
1
1 s 1,0
0
3
0
1
Note
104
379
Deceleration time from maximum frequency to 0
Hz.
API FULL and LIMITED:
0
= Voltage 0…10 V
1
= Voltage 2…10 V
API LIMITED ONLY:
2
= Current 0…20 mA
3
= Current 4…20 mA
NOTE:
When using API
LIMITED, select the voltage/current range also with the dip switch
390
2
= Current 0…20 mA
3
= Current 4…20 mA
731
0
= Not used
1
= Used
115
0
= All parameters visible
1
= Only quick setup parameter group visible
Table 8.1: Quick setup parameters
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
43
• vacon parameters
8.2 Motor settings (Control panel: Menu PAR -> P1)
Code
P1.1
P1.2
P1.3
P1.4
P1.5
Parameter
Motor nominal voltage
Motor nominal frequency
Motor nominal speed
Motor nominal current
Motor cos Ï•
Min Max Unit Default ID
180 690 V
230
400
575
Note
110 Check rating plate on the motor
30 320 Hz 50,00
300 20000 rpm 1440
111
Check rating plate on the motor
112
Default applies for a 4-pole motor.
0,2 x
I
Nunit
I
2,0 x
Nunit
0,30 1,00
A
I
Nunit
0,85
113
Check rating plate on the motor
120
Check rating plate on the motor i i i
P1.7
P1.8
Current limit
Motor control mode
P1.9
U/f ratio selection
0,2 x
I
Nunit
2 x
I
Nunit
0
0
1
2
A
1,5 x
I
Nunit
0
0
107
600
108
0
= Frequency control
1
= Speed control
0
= Linear
1
= Squared
2
= Programmable i i i i i i
P1.10
P1.11
P1.12
P1.13
P1.14
P1.15
Field weakening point
Voltage at field weakening point
U/f curve midpoint frequency
U/f curve midpoint voltage
Output voltage at zero frequency
30,00
10,00
0,00
0,00
0,00
320
200
P1.10
P1.11
40,00
Torque boost 0 1
Hz
%
Hz
%
%
50,00
100,00
50,00
100,00
0,00
0
602
603
% of Nominal voltage of the motor
604
605
606
109
% of Nominal voltage of the motor
% of Nominal voltage of the motor
0
= Not used
1
= Used i i
P1.16
P1.17
Switching frequency
Brake chopper i
P1.18
Motor identification
Table 8.2: Motor settings
1,5
0
0
16,0 kHz 6,0 601
2 0 504
0
=Disabled
1
=Used in Run state
2
=Used in Run and Stop state
Only in API FULL & LIMITED
1 0 631
1
=Identification without run after start command
NOTE!
These parameters are shown, when
P13.1 = 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon
•
44
8.3 Start/stop setup (Control panel: Menu PAR -> P2)
i i i i i
Code
P2.1
P2.2
Start function
P2.3
Stop function
P2.4
Parameter
Remote control place
Start/Stop logic
P2.5
Local/remote
Min
1
0
0
0
0
Max
2
1
1
3
1
Unit Default
1
0
0
0
ID
172
505
506
300
211
Note
1
= I/O terminal
2
= Fieldbus
(keypad control is activated with par. 2.5)
0
= Ramp
1
= Flying start
0
= Coasting
1
= Ramp
Start signal 1 Start signal 2
(Default DI1) (Default DI2)
0
Start Fwd Start reverse
1
Start Reverse
2
Start Pulse Stop Pulse
3
Start Fwd Start Rv
REAF REAF
0
= Remote
1
= Keypad
Table 8.3: Start/stop setup
8.4 Frequency references (Control panel: Menu PAR -> P3)
i i i i i i i i i
Code
P3.1
P3.2
P3.3
Parameter
I/O reference
Min Max Unit Default ID
Min frequency 0,00 P3.2
Max frequency P3.1
320
0 4
P3.4
Preset speed 0 0,00 P3.2
P3.5
Preset speed 1 0,00 P3.2
P3.6
Preset speed 2 0,00 P3.2
P3.7
Preset speed 3 0,00 P3.2
P3.8
Preset speed 4 0,00 P3.2
P3.9
Preset speed 5 0,00 P3.2
P3.10
Preset speed 6 0,00 P3.2
P3.11
Preset speed 7 0,00 P3.2
Table 8.4: Frequency references
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
0,00
50,00
3
5,00
10,00
15,00
20,00
25,00
30,00
40,00
50,00
Note
101
102
0
= Preset Speeds (0-7)
1
= Keypad Reference
2
= Fieldbus Reference
117
3
= AI1
(API FULL &
LIMITED)
4
= AI2
(API FULL)
124 Activated by digital inputs
105 Activated by digital inputs
106 Activated by digital inputs
126 Activated by digital inputs
127 Activated by digital inputs
128 Activated by digital inputs
129 Activated by digital inputs
130 Activated by digital inputs
NOTE!
These parameters are shown, when
P13.1 = 0.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
45
• vacon parameters
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
i i i i i i
Code Parameter Min Max
P4.1
P4.2
Ramp shape
Acceleration time
P4.3
Deceleration time
0,0
0,1
0,1
0.2 x
I
Nunit
10,0
3000
3000
2 x
I
Nunit
P4.4
DC braking current
P4.5
P4.6
P4.7
DC braking time at start
Frequency to start
DC braking during ramp stop
DC braking time at stop
0,00 600.00
0,10 10,00
0,00 600.00
i P4.8
Flux brake 0 3 i
P4.9
Flux braking current
Ramp shape 2
0 7,4
P4.10
0,0 10,0
P4.11
Acceleration time 2 0,1 3000
P4.12
Deceleration time 2 0,1 3000
Table 8.5: Motor control parameters
Unit Default ID
s s s
0,0
1,0
1,0
Note
500
0
= Linear
>0
= S-curve ramp time
103
104
A s
Varies 507
0 516
0
= DC brake is off at start
Hz s
A s s s
1,50
0
0,0
1,0
1,0
515
508
520
0
= DC brake is off at stop
0
= Off 2 = Chopper
1
= On 3 = Full mode
519
501
0
= Linear
>0
= S-curve ramp time
502
503 i
8.6 Digital inputs (Control panel: Menu PAR -> P5)
Code Parameter Min Max
P5.1
Start signal 1 0
P5.2
P5.3
Start signal 2
Reverse
P5.4
Ext. fault Close
Table 8.6: Digital inputs
0
0
0
6
6
6
6
Unit Default ID
1
2
0
0
Note
403
0
= Not used
1
= DI1
2
= DI2
Only in API FULL
& LIMITED
3
= DI3
4
= DI4
Only in API FULL
5
= DI5
6
= DI6
404 As parameter 5.1
412 As parameter 5.1
405 As parameter 5.1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon
•
46 i
Code Parameter
P5.5
Ext. fault Open
P5.6
P5.7
Fault reset
Run enable
P5.8
Preset speed B0
P5.9
Preset speed B1
P5.10 Preset speed B2
P5.11
Disable PI
Min
0
0
0
0
0
0
0
P5.12
Force to I/O 0 i
P5.13
Ramp time select
Table 8.6: Digital inputs
0
Max
6
6
6
6
6
6
6
1 (FULL &
LIMITED
6 (RS485)
Unit Default ID
3
4
0
6
0
5
0
Note
406 As parameter 5.1
414 As parameter 5.1
407 As parameter 5.1
419 As parameter 5.1
420 As parameter 5.1
421 As parameter 5.1
1020 As parameter 5.1
0 409 As parameter 5.1
6 0 408 As parameter 5.1
8.7 Analogue inputs (Control panel: Menu PAR -> P6)
i i i i i i
Code Parameter
P6.1
AI1 Signal range
Min Max Unit Default ID
Only in API FULL & LIMITED
0 3
P6.2
AI1 filter time 0,0 10,0
P6.3
AI1 Custom min -100,0 100,0 s
%
0
0,1
0,0
P6.4
AI1 Custom max -100,0 100,0 % 100,0
Only in API FULL
Note
379
API FULL and LIMITED:
0
= Voltage 0…10 V
1
= Voltage 2…10 V
API LIMITED ONLY:
2
= Current 0…20 mA
3
= Current 4…20 mA
NOTE:
When using API
LIMITED, select the voltage/current range also with the dip switch
378 0 = no filtering
380 0,0 = no min scaling
381 100,0 = no max scaling
P6.5
AI2 signal range 2 3
P6.6
AI2 filter time 0,0 10,0
P6.7
AI2 Custom min -100,0 100,0
P6.8
AI2 Custom max -100,0 100,0
Table 8.7: Analoque inputs
s
%
%
3
0,1
0,0
100,0
390
2
= Current 0…20 mA
3
= Current 4…20 mA
389 0 = no filtering
391 0,0 = no min scaling
392 100,0 = no max scaling
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
47
• vacon parameters
8.8 Digital and analogue outputs (Control panel: Menu PAR -> P7)
i i i
Code
P7.1
P7.2
P7.3
P7.4
P7.5
Parameter
Relay output 1 content
Relay output 2 content
Digital output 1 content
Analogue output function
Analogue output minimum
Min Max Unit Default ID
Only in API FULL
0 11 2
Selections
313
0
= Not used
1
= Ready
2
= Run
3
= Fault
4
= Fault Inverted
5
= Alarm
6
= Reversed
7
= At Speed
8
= Motor Regulator
Active
9
= FBControlWord.B13
10
= FBControlWord.B14
11
= FBControlWord.B15
In all API versions
0 11
Only in API FULL
3 314
As parameter 7.1
0
0
0
11
4
1
1
1
1
Only in API Limited
P7.6
Relay 2 invert 0 1
Table 8.8: Digital and analogue outputs
0
312
As parameter 7.1
307
310
0
= Not in use
1
= Output freq. (0-f max
)
2
= Output current (0-
I nMotor
)
3
= Torque (0-Nominal torque)
4
= PI controller output
0
= 0 mA
1
= 4 mA
489
1
= Relay 2 inverted
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon
•
48 i i i i i i
8.9 Protections (Control panel: Menu PAR -> P9)
Code
P9.1
P9.2
P9.3
P9.4
P9.5
P9.7
Parameter
Response to 4mA reference fault
Response to undervoltage fault
Earth fault protection
Stall protection
Underload protection
Thermal protection of the motor
Min Max Unit Default ID
1
1
1
1
1
1
2
2
2
2
2
2
1
2
2
1
1
2
Note
700
727
703
709
713
704
0
= No response
1
= Alarm
2
= Fault, stop acc. to
P2.3
1
= Alarm
2
= Fault, stop acc. to
P2.3
1
= Alarm
2
= Fault, stop acc. to
P2.3
0
= No response
1
= Alarm
2
= Fault, stop acc. to
P2.3
0
= No response
1
= Alarm
2
= Fault, stop acc. to
P2.3
0
= No response
1
= Alarm
2
= Fault, stop acc. to
P2.3
P9.8
P9.9
Motor ambient temperature
Motor cooling factor at zero speed
P9.10
Motor thermal time constant
P9.11
Motor Phase
Supervision
Table 8.9: Protections
-20 100
0,0 150,0
1
0
200
2
°C
% min unit
40
40,0
45
2
705
706
707
702 Description
NOTE!
These parameters are shown, when
P13.1 = 0.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
49
• vacon parameters
8.10 Fault autoreset parameters (Control panel: Menu PAR -> P10 )
i
Code
P10.1
P10.2
P10.3
Parameter
Wait time
Trial time
Start function
P10.4
Fault autoreset
Min
0,10
0,00
0
0
Max
10,00
90,00
(FULL &
LIMITED)
60,00
(RS485)
2
1
Unit Default
s s
0,50
0
0
ID
717
30,00 718
719
731
Note
Delay before automatic restart after a fault has disappeared
Defines the time before the frequency converter tries to automatically restart the motor after the fault has disappeared
0
= Ramp
1
= Flying start
2
= According to P4.2
Affects only to start after autoreset!
0
= Disabled
1
= Enabled
Table 8.10: Fault autoreset parameters
NOTE!
These parameters are shown, when
P13.1 = 0.
8
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon
•
50 i i i i i
8.11 PI control parameters (Control panel: Menu PAR -> P12)
Code Parameter
P12.1
PI activation
P12.2
PI controller gain
P12.3
PI controller Itime
P12.4
Keypad PI reference
Min Max Unit Default ID
0
0,0
2
1000 %
0
100,0
Note
163
0
= Not used
1
= PI for motor control
2
= PI for external use
(Only in API FULL)
118
0,00 320,0 s 10,00 119
0,0 100,0 % 0,0
P12.5
Setpoint source
P12.6
Feedback source
P12.7
P12.8
Feedback minimum
Feedback maximum
P12.9
Error value inversion
0
0
0,0
0,0
0
3
2
100,0
100,0
1
%
%
0
2
0,0
100,0
0
167
332
0
= Keypad PI reference,
P12.4
1
= Fieldbus
2
= AI1
Only in API FULL &
LIMITED
334
3
= AI2
Only in API FULL
0
= Fieldbus
1
= AI1
Only in API FULL &
LIMITED
2
= AI2
Only in API FULL
336 0 = No minimum scaling
337
340
100,0 = No maximum scaling
0
=No inversion (Feedback<Setpoint->Increase PI
Output)
1
=Inverted (Feedback<Setpoint->Decrease PI Output)
Table 8.11: PI control parameters
NOTE!
These parameters are shown, when
P13.1 = 0.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
51
• vacon parameters
8.12 Easy usage menu (Control panel: Menu PAR -> P0)
i
Code
P13.1
P13.2
Parameter
Parameter conceal
Drive setup
Min Max Unit Default ID
0
0
1
3
1
0
Note
115
540
0
= All parameters visible
1
= Only quick setup parameter group visible
0 =
Basic
1 =
Pump drive
2 =
Fan drive
3 =
Conveyor drive (HP)
NOTE!
Visible only duriing Startup wizard
Table 8.12: Easy usage menu parameters
8.13 System parameters
Code Parameter Min Max Default ID
Software information (MENU PAR -> S1)
Note
S1.1
S1.2
S1.3
S1.4
S1.5
S1.6
S1.7
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
API system SW
API system SW version
Power SW ID
Power SW version
Application SW ID
Application SW revision
System load i
2314
835
2315
834
837
838
839
RS485 information
(MENU PAR -> S2)
Communication status
Fieldbus protocol
Slave address
Baud rate
Number of stop bits
Parity type
S2.7
Communication time-out
0
1
0
0
0
0
1
255
5
1
0
255
1
0
0
1
5
0
808
Format:
xx.yyy
xx
= 0 - 64 (Number of error messages)
yyy
= 0 - 999 (Number of correct messages)
809
0 =
FB disabled
1
= Modbus
810
811
0
=300,
1
=600,
2
=1200,
3
=2400,
4
=4800,
5
=9600,
812
0
=1,
1
=2
813
0
= None (locked)
814
0
= Not used,
1
= 1 second,
2
=
2 seconds, etc.
Table 8.13: System parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon
•
52
Code
S2.8
Parameter Min Max Default ID Note
Reset communication status
0 1 0 815
1
= Resets par. S2.1
Total counters
(MENU PAR -> S3)
S3.1
S3.2
S3.3
S4.1
S4.2
S4.3
MWh counter
Power on days
Power on hours
Display contrast
Default page
827
828
829
User settings
(MENU PAR -> S4)
Restore factory defaults
0
0
0
15
20
1
15
0
0
830 Adjusts the display contrast
2318
831
Defines which monitoring page (1.1. - 1.20) is shown after startup.
0
= Not used
1
= Restores factory defaults for all parameters
Table 8.13: System parameters
24-hour support +358 (0)40 837 1150 • Email: [email protected]
8
9
53
• vacon parameter descriptions
9. PARAMETER DESCRIPTIONS
On the next pages you can find the descriptions of certain parameters. The descriptions have been arranged according to parameter group and number.
9.1 Motor settings (Control panel: Menu PAR -> P1)
1.7
C
URRENT LIMIT
This parameter determines the maximum motor current from the frequency converter. To avoid motor overload, set this parameter according to the rated current of the motor. The current limit is equal to the rated converter current
(I n
) by default.
1.8
M
OTOR CONTROL MODE
With this parameter the user can select the motor control mode. The selections are:
0 = Frequency control:
Drive frequency reference is set to output frequency without slip compensation. Motor actual speed is finally defined by motor load.
1 = Speed control:
Drive frequency reference is set to motor speed reference. The motor speed remains the same regardless of motor load. Slip is compensated.
1.9
U/
F RATIO SELECTION
There are three selections for this parameter:
0 = Linear:
The voltage of the motor changes linearly with the frequency in the constant flux area from 0 Hz to the field weakening point where the field weakening point voltage is supplied to the motor. Linear U/f ratio
should be used in constant torque applications. See Figure 9.1.
This default setting should be used if there is no special need for another setting.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
54
1 = Squared:
The voltage of the motor changes following a squared curve form with the frequency in the area from 0 Hz to the field weakening point where the field weakening point voltage is also supplied to the motor. The motor runs under magnetised below the field weakening point and produces less torque, power losses and electromechaniqal noise.
Squared U/f ratio can be used in applications where torque demand of the load is proportional to the square of the speed, e.g in centrifugal fans and pumps
U[V]
Un par.1.11
Default: Nominal voltage of the motor
Field weakening point
Linear par. 1.14
Squared
Default: Nominal frequency of the motor f[Hz] par.1.10
Figure 9.1: Linear and squared change of motor voltage
2 = Programmable U/f curve:
The U/f curve can be programmed with three different points. Programmable U/f curve can be used if the other settings do not satisfy the needs of the application
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
55
• vacon
U[V]
Un
Par 1.11
Default: Nominal voltage of the motor
parameter descriptions
Field weakening point
Par. 1.13
(Def. 50%)
Par. 1.14
(Def. 0.0%)
Par. 1.12
(Def. 10%)
Figure 9.2: Programmable U/f curve
Default: Nominal frequency of the motor
f[Hz]
Par. 1.10
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
56
1.10 F
IELD WEAKENING POINT
The field weakening point is the output frequency at which the output voltage reaches the value set with par. 1.11.
1.11 V
OLTAGE AT FIELD WEAKENING POINT
Above the frequency at the field weakening point, the output voltage remains at the value set with this parameter. Below the frequency at the field weakening point, the output voltage depends on the setting of the U/f curve parame-
ters. See parameters 1.9 - 1.14 and Figures 9.1 and 9.2.
When the parameters 1.1 and 1.2 (nominal voltage and nominal frequency of the motor) are set, the parameters 1.10 and 1.11 are automatically given the corresponding values. If you need different values for the field weakening point and the voltage, change these parameters after setting the parameters
1.1 and 1.2.
1.12 U/
F CURVE
,
MIDDLE POINT FREQUENCY
If the programmable U/f curve has been selected with the parameter 1.9, this
parameter defines the middle point frequency of the curve. See Figure 9.2.
1.13 U/
F CURVE
,
MIDDLE POINT VOLTAGE
If the programmable U/f curve has been selected with the parameter 1.9, this
parameter defines the middle point voltage of the curve. See Figure 9.2.
1.14 O
UTPUT VOLTAGE AT ZERO FREQUENCY
This parameter defines the zero frequency voltage of the curve. See Figures
1.15 T
ORQUE BOOST
When this parameter has been activated, the voltage to the motor changes automatically with high load torque which makes the motor produce sufficient torque to start and run at low frequencies. The voltage increase depends on the motor type and power. Automatic torque boost can be used in applications with high load torque, e.g. in conveyors.
0 =
Disabled
1 =
Enabled
Note:
In high torque - low speed applications - it is likely that the motor will overheat. If the motor has to run a prolonged time under these conditions, special attention must be paid to cooling the motor. Use external cooling for the motor if the temperature tends to rise too high.
Note:
The best performance can be reached by running motor identification,
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
57
• vacon parameter descriptions
1.16 S
WITCHING FREQUENCY
Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the capacity of the frequency converter unit.
Switching frequency for Vacon 10: 1.5…16 kHz.
1.17 B
RAKE CHOPPER
Note!
An internal brake chopper is installed in three phase supply MI2 and MI3 size drives
0 =
No brake chopper used
1 =
Brake chopper used in Run state
2 =
Used in Run and Stop state
When the frequency converter is decelerating the motor, the energy stored to the inertia of the motor and the load are fed into an external brake resistor, if the brake chopper has been activated. This enables the frequency converter to decelerate the load with a torque equal to that of acceleration (provided that the correct brake resistor has been selected). See separate Brake resistor installation manual.
1.18 M
OTOR IDENTIFICATION
0 =
No action
1 =
ID no run
When ID no run is selected, the drive will perform an ID-run when it is started from selected control place. Drive has to be started within 20 seconds, otherwise identification is aborted.
The drive does not rotate the motor during ID no run. When ID run is ready the drive is stopped. Drive will start normally, when the next start command is given.
The ID run improves the torque calculations and the automatic torque boost function. It will also result in a better slip compensation in speed control
(more accurate RPM).
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
58
9.2 Start/Stop setup (Control panel: Menu PAR -> P2)
2.1
R
EMOTE CONTROL PLACE
With this parameter, the user can select the active control place. The selections are:
1 =
I/O terminal (frequency reference can be selected with P3.3)
2 =
Fieldbus
The priority order of selecting the control place is
1. Navigation wheel
2. Forced from I/O terminal
3. Par. 2.1
Note:
Local/Remote control mode can be toggled by pressing the navigation wheel for 5 seconds. P2.1 will have no effect in local mode.
Local =
Keypad is the control place
Remote =
P2.1 defines the control place
2.2
S
TART FUNCTION
The user can select two start functions for Vacon 10 with this parameter:
0 = Ramp start
The frequency converter starts from 0 Hz and accelerates to the set frequency reference within the set acceleration time (See detailed description: ID103). (Load inertia, torque or starting friction may cause prolonged acceleration times).
1 = Flying start
With this function the drive identifies the speed of the motor and starts to the corresponding frequency immediately.
Use this mode if the motor is rotating when the start command is given. With the flying start, it is possible to ride through short mains voltage interruptions
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
59
• vacon parameter descriptions
2.3 S
TOP FUNCTION
Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency converter after the Stop command.
1 = Ramp stop
After the Stop command, the speed of the motor is decelerated according to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external braking resistor for to be able to decelerate the motor in acceptable time.
2.4
S
TART
/
STOP LOGIC
With this parameter the user can select the start/stop logic.
0 =
DI 1 = Start forward
DI 2 = Start reverse (
API FULL & LIMITED
)
FWD
Output frequency
Stop function
(par. 2.3)
= coasting t
REV
DI1
DI2
1
Figure 9.3: Start/Stop logic, selection 0
2 3
1 The first selected direction has the highest priority.
2 When the DIN1 contact opens the direction of rotation starts the change.
3 If Start forward (DI1) and Start reverse (DI2) signals are active simultaneously the
Start forward signal (DI1) has priority
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions
1 =
DI1 = Start
DI2 = Reverse (
API FULL & LIMITED
)
FWD Output frequency
Stop function
(par. 2.3)
= coasting vacon
•
60
REV
DI1
DI2
Figure 9.4: Start/Stop logic, selection 1
2 =
DI1 = Start pulse
DI2 = Stop pulse (
API FULL & LIMITED
)
Output frequency
Stop function
(Par. 2.3)
= coasting
If Start and Stop pulses are simultaneous the Stop pulse overrides the Start pulse t
REV
DI1
Start t
Figure 9.5: Start/Stop logic, selection 2
3
= DI1 = Start forward, rising edge after fault
DI2 = Start reverse, rising edge after fault
(API FULL & LIMITED
)
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
61
• vacon parameter descriptions
2.5
L
OCAL
/
REMOTE
This parameter defines whether the control place of the drive is remote (I/O or FieldBus) or Keypad. Keypad can also be selected as control place by pressing the navigation wheel for 5 seconds.
The priority order of selecting control place is
1. Navigation wheel
2. Forced from I/O
3. Parameter 2.1
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions
9.3 Frequency references (Control panel: Menu PAR -> P3)
vacon
•
62
Defines the selected frequency reference source when the drive is controlled from the I/O terminal.
0 =
Preset speed 0 - 7
1 =
Keypad reference
2 =
Reference from Fieldbus (FBSpeedReference)
API FULL & LIMITED:
3 =
AI1 reference (terminals 2 and 3, e.g. potentiometer)
API FULL:
4 =
AI2 reference (terminal 4 and 5, e.g. transducer)
3.4 - 3.11 P
RESET SPEEDS
0 - 7
These parameters can be used to determine frequency references that are applied when appropriate combinations of digital inputs are activated. Preset speeds can be activated from digital inputs despite of the active control place.
Parameter values are automatically limited between the minimum and maximum frequencies. (par. 3.1, 3.2).
Speed Preset speed B2
If P3.3 = 0,
Preset speed 0
Preset speed 1
Preset speed 2
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7 x x x x
Table 9.1: Preset speeds 0 - 7
Preset speed B1 x x x x
Preset speed B0 x x x x
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
63
• vacon parameter descriptions
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
4.1
R
AMP SHAPE
4.10 R
AMP SHAPE
2
The start and end of the acceleration and deceleration ramp can be smoothed with this parameter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped acceleration/deceleration. The acceleration and deceleration times are determined with parameters 4.2 and 4.3.
[Hz]
P4.2, 4.3
P4.1
P4.1
[t]
Figure 9.6: S-shaped acceleration/deceleration
4.2 A
CCELERATION TIME
4.3
D
ECELERATION TIME
4.11 A
CCELERATION TIME
2
4.12 D
ECELERATION TIME
2
These limits correspond to the time required for the output frequency to accelerate from the zero frequency to the set maximum frequency, or to decelerate from the set maximum frequency to zero frequency.
The user can set two different acceleration/deceleration time sets for one application. The active set can be selected with the selected digital input (par.
5.13)
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
64
4.5
D
C BRAKING TIME AT START
DC-brake is activated when the start command is given. This parameter defines the time of the DC-braking. After the brake is released, the output frequency increases according to the set start function by par. 2.2.
DC-braking current
Output frequency
Par 4.4
t
Par 4.5
RUN
STOP
Figure 9.7: DC braking time at start
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
65
• vacon parameter descriptions
4.6
F
REQUENCY TO START DC BRAKING DURING RAMP STOP
The output frequency at which the DC-braking is applied. See Figure 9.9.
4.7
DC
BRAKING TIME AT STOP
0 =
DC brake is not in use
>0 =
DC brake is in use and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
fn fout
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the frequency converter.
With the DC injection, the motor can be electrically stopped in the shortest possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the frequency is greater, or equal to the nominal frequency of the motor, the set value of parameter 4.7 determines the braking time. For example, when the frequency is 10% of the nominal, the braking time is 10% of the set value of parameter 4.7.
fout fn
Output frequency
Motor speed
DC-braking ON t = 1 x par. 4.7
t
0,1 x fn
Output frequency
Motor speed
DC-braking ON t = 0,1 x par. 4.7
t
RUN
STOP
RUN
STOP
Figure 9.8: DC-braking time when Stop mode = Coasting
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
66
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the set deceleration parameters, if the inertia of of the motor and load allows that, to the speed defined with parameter 4.6, where the DC-braking starts.
The braking time is defined with parameter 4.7. See Figure 9.9.
fout
Motor speed
Output frequency
DC-braking
Par. 4.6
t = par. 4.7
t
RUN
STOP
Figure 9.9: DC-braking time when Stop mode = Ramp
4.8
F
LUX BRAKE
Instead of DC braking, flux braking is a useful form of braking with motors of max. 15kW.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.
Activation mode
0 = Off
1 = On
2 = Chopper
3 = Full mode
Description
Not used
Normal mode. Activates flux bracking during deceleration regardless of load.
Emulates the behavior of a braking chopper by activating flux bracking based on DC-link voltage. Minimizes the heating up of the motor in applications with frequent speed changes.
Activates flux bracking both during deceleration and on generative shock loads at constant speed.Offers the highest performance in demanding applications.
Note
: Flux braking converts the energy into heat at the motor, and should be used intermittently to avoid motor damage.
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
67
• vacon parameter descriptions
9.5 Digital inputs (Control panel: Menu PAR -> P5)
These parameters are programmed using the FTT-method (Function To Terminal), where you have a fixed input or output that you define a certain function for. You can also define more than one function to a digital input, e.g. Start signal 1 and Preset Speed B1 to DI1.
The selections for these parameters are:
0 =
Not used
1 =
DI1
2 =
DI2 (
API FULL & LIMITED
)
3 =
DI3 (
API FULL & LIMITED
)
4 =
DI4 (
API FULL
)
5 =
DI5 (
API FULL
)
6 =
DI6 (
API FULL
)
5.1
S
TART SIGNAL
1
5.2
S
TART SIGNAL
2
5.3
R
EVERSE
5.4
E
XTERNAL FAULT
(
CLOSE
)
5.5
E
XTERNAL FAULT
(
OPEN
)
5.6
F
AULT RESET
5.7
R
UN ENABLE
5.8
P
RESET SPEED
B0
5.9
P
RESET SPEED
B1
5.10 P
RESET SPEED
B2
5.11 D
ISABLE
PI
5.12 F
ORCE TO
I/0
The priority order of selecting control place is
5.13 R
AMP TIME SELECTION
Contact open: Acceleration/Deceleration time 1 selected
Contact closed: Acceleration/Deceleration time 2 selected
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
68
9.6 Analoque inputs (Control panel: Menu PAR -> P6)
6.2
AI1
SIGNAL FILTER TIME
(
ONLY IN API FULL
&
LIMITED
)
6.6
AI2
SIGNAL FILTER TIME
(
ONLY IN API FULL
)
This parameter, given a value greater than 0, activates the function that filters out disturbances from the incoming analogue signal.
Long filtering time makes the regulation response
%
Unfiltered signal
100%
Filtered signal
63% t [s]
Par. 6.2
Par. 6.6
Figure 9.10: AI1 and AI2 signal filtering
6.3
AI1 C
USTOM SETTING MINIMUM
6.4
AI1 C
USTOM SETTING MAXIMUM
6.7
AI2 C
USTOM SETTING MINIMUM
6.8
AI2 C
USTOM SETTING MAXIMUM
These parameters set the analogue input signal for any input signal span from
-100 to 100%.
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
69
• vacon parameter descriptions
9.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
7.1
R
ELAY OUTPUT
1
FUNCTION
(
ONLY IN API FULL
)
7.2
R
ELAY OUTPUT
2
FUNCTION
7.3
D
IGITAL OUTPUT
1
FUNCTION
(
ONLY IN API FULL
)
0 =
1 =
2 =
7 =
Not used
Ready
Run
Setting
3 =
Fault
4 =
Fault inverted
5 =
Alarm
6 =
Reversed
At speed
8 =
Motor regulator activated
9 =
FBControlWord.B13
10 =
FBControlWord.B14
11 =
FBControlWord.B15
Signal content
Not in operation
The frequency converter is ready to operate
The frequency converter operates (motor is running, or DC-braking)
A fault trip has occurred
A fault trip has not occurred
An alarm has occurred
The reverse command has been selected, output frequency to the motor is negative.
The output frequency has reached the set reference
One of the limit regulators (e.g. current limit, voltage limit) is activated
Modbus control word bit 13
Modbus control word bit 14
Modbus control word bit 15
Table 9.2: Output signals via RO1, RO2 and DO1
7.4
A
NALOGUE OUTPUT FUNCTION
0 =
Full scale
1 =
0 - Max. frequency
2 =
0 - Nominal current
3 =
0 - Nominal torque
4 =
PID controller output, 0-100%
7.5
A
NALOGUE OUTPUT MINIMUM
0 =
0-20 mA, 0-10V
1 =
4-20 mA, 2-10V
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
70
9.8 Motor thermal protection (parameters 9.7 - 9.10)
The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current I
T
specifies the load current above which the motor is overloaded. This current limit is a function of the output frequency.
CAUTION! The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill
9.4
S
TALL PROTECTION
0 =
No response
1 =
Alarm
2 =
Fault, stop according to P2.3
The motor stall protection protects the motor from short time overload situations such as one caused by a stalled shaft. The stall current is I nMotor
*1.3, stall time 15 seconds and stall frequency limit 25Hz . If the current is higher than the limit and output frequency is lower than the limit, the stall state is true and the drive reacts according to this parameter. There is actually no real indication of the shaft rotation.
I
Stall area
Inmotor *1.3
Figure 9.11: Stall characteristics
25Hz f
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
71
• vacon parameter descriptions
9.5
U
NDERLOAD PROTECTION
0 =
No response
1 =
Alarm
2 =
Fault, stop according to P2.3
The purpose of the motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or a dry pump.
The underload protection time limit is 20 seconds, which is the maximum time allowed for an underload state to exist before causing a trip according to this parameter.
Torque
Underload curve at nominal freq. = 50%
Underload curve at zero freq. = 10%
5 Hz
Figure 9.12: Underload protection
Underload area
Field weakening point, P1.11
f
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
72
9.7
T
HERMAL PROTECTION OF THE MOTOR
0 =
No response
1 =
Alarm
Fault, stop mode after fault according to parameter
If tripping is selected the drive will stop and activate the fault stage, if the temperature of the motor becomes too high. Deactivating the protection, i.e. setting parameter to 0, will reset the thermal model of the motor to 0%.
9.8
M
OTOR AMBIENT TEMPERATURE
When the motor ambient temperature must be taken into consideration, it is recommended to set a value for this parameter. The value can be set between
-20 and 100 degrees Celsius.
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
73
• vacon parameter descriptions
9.9 M
OTOR COOLING FACTOR AT ZERO SPEED
The cooling power can be set between 0-150.0% x cooling power at nominal
Pcooling
100%
Overload area
I
T par.9.9=40%
0 f n f
Figure 9.13: Motor cooling power
9.10 M
OTOR THERMAL TIME CONSTANT
This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the bigger the time constant. The time constant is the time within which the calculated thermal model has reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between different motor manufacturers.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2xt6. If the drive is in stop state the time constant is internally increased to three times the set parameter value.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
74
Motor temperature
Trip area
105%
Motor current
I/I
T
Fault/warning activation point, if selected with par. 9.7
Time constant T*)
Motor temperature
Q = (I/IT)
2 x (1-e-t/T)
*)
Changes by motor size and
adjusted with parameter 9.10
Time
Figure 9.14: Motor temperature calculation
9.11 M
OTOR
P
HASE
S
UPERVISION
Motor phase supervision of the motor ensures that the motor phases have an approximately equalcurrent.
Settings for P9.11, range 0-2:
Activation mode Description
1 Warning
2 Fault,stop mode after fault according to ID506(P2.3 Stop function)
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
75
• vacon parameter descriptions
9.9 Fault autoreset parameters (Control panel: Menu PAR -> P10)
10.2 A
UTO RESET
,
TRIAL TIME
The Automatic restart function restarts the frequency converter when the faults have disappeared and the waiting time has elapsed.
The time count starts from the first autoreset. If the number of faults occurring during the trial time exceeds three, the fault state becomes active. Otherwise the fault is cleared after the trial time has elapsed and the next fault
starts the trial time count again. See Figure 9.15.
If a single fault remains during the trial time, a fault state is true.
Wait time par.10.1
Wait time par.10.1
Wait time par.10.1
Fault trigger
Motor stop signal
Restart 1 Restart 2
Motor start signal
Supervision
Trial time par.10.2
Fault active
RESET/
Fault reset
Autoreset function: (Trials = 3)
Figure 9.15: Automatic restart
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
76
9.10 PI control parameters (Control panel: Menu PAR -> P12)
12.1 PI A
CTIVATION
0 =
Not used
1 =
PI for motor control
2 =
PI for external use
(Only in API Full!)
12.2 PI
GAIN
This parameter defines the gain of the PI controller. If the value of the parameter is set to 100% a change of 10% in the error value causes the controller output to change by 10%.
12.3 PI
CONTROLLER
I-
TIME
This parameter defines the integration time of the PI controller. If this parameter is set to 1,00 second the controller output is changed by a value corresponding to the output caused from the gain every second. (Gain*Error)/s.
12.7 F
EEDBACK MINIMUM
12.8 F
EEDBACK MAXIMUM
This parameter sets the minimum and maximum scaling points for feedback value.
Controller feedback (%) par. 12.8
par. 12.7
0V
0mA
Custom min par. 6.3/6.7
Custom max par.6.4/6.8
10V
20mA
Analoque input with custom min and max scaling (%)
Figure 9.16: Feedback minimum and maximum
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
77
• vacon parameter descriptions
9.11 Easy usage menu (Control panel: Menu PAR -> P9)
13.2 D
RIVE SETUP
With this parameter you can easily set up your drive for four different applications.
Note!
This parameter is only visible when the Startup Wizard is active. The startup wizard will start in first power-up. It can also be started as follows.
See the figures below.
NOTE! Running the startup wizard will always return all parameter settings to their factory defaults!
Alternates in the display
REF
MON
READY RUN
PA R
FLT
STOP ALARM FAULT
REF
MON
READY RUN
PAR
FLT
STOP ALARM FAULT
rp m
REF
MON
READY RUN
PAR
FLT
STOP ALARM FAULT
1 Press STOP for 5 seconds in main menu
2
Push to enter edit mode
3
Select motor nominal speed and push to confirm.
4
PERFORM THE SAME
PROCEDURE FOR PAR. 1.4,
MOTOR NOMINAL CURRENT
Figure 9.17: Startup wizard
5
PERFORM DRIVE SETUP,
PAR. 13.2, SEE NEXT PAGE
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
78
REF
MON
READY RUN STOP A LARM FAULT
PAR
FLT
REF
MON
PAR
FLT
READY RUN STOP ALARM FAULT
REF
MON
PAR
FLT
READY R UN STOP ALARM FAULT
1 Startup wizard shows par 13.2
number.
2 Push to enter edit mode.
3
Select between
0 - 3, see below!
0
1
2
Selections:
= Basic
= Pump drive
= Fan drive
P1.1 P1.2
V
V
V
*
*
*
P1.7
P1.15
50/
Hz
50/ 60
Hz
50/
Hz
60
60
I
1,1 x
I
NMOT
1,1 x
NMOT
1,1 x
I
NMOT
0=
Not used
0=
Not used
0=
Not used
P2.1
I/O
I/O
I/O
P2.2 P2.3
P3.1
P3.2
0=
0=
Ramp Coast.
0
Hz
50/
60
Hz
0=
Ramp
1=
Ramp
20
Hz
0=
Ramp
0=
Coast.
20
Hz
50/ 60
Hz
50/
60
Hz
3
= Conveyor drive
V
*
50/
60
Hz
1,5 x
I
NMOT
1=
Used
I/O
*Same as drive voltage, except in 115V drives this value is 230V
Parameters affected:
P1.1 Motor Un (V)
P1.2 Motor fn (H z)
P1.7 Current limit (A)
P1.15 Torque boost
P2.1 Control place
P2.2 Start function
0=
0=
Ramp Coast.
0
Hz
50/
60
Hz
P2.3 Stop function
P3.1 Min frequency
P3.2 Max frequency
P3.3 I/O reference
P4.2 Acc. time (s)
P4.3 Dec time (s)
P3.3
0=
Ai1
0-10V
0=
Ai1
0-10V
0=
Ai1
0-10V
0=
Ai1
0-10V
P4.2 P4.3
3 s
5 s
20 s
1 s
3 s
5 s
20 s
1 s
REF
MON
READY RUN
PAR
FLT
STOP ALARM FAULT
Figure 9.18: Drive setup
4 Push to confirm drive setup
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
79
• vacon parameter descriptions
9.12 Modbus RTU
Vacon 10 has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with the RS-485 standard.
The built-in Modbus connection of Vacon 10 supports the following function codes:
Function code
03
04
06
Function name Address Broadcast messages
Read Holding Registers All ID numbers No
Read Input Registers All ID numbers No
Preset Single Registers All ID numbers Yes
9.12.1 Termination resistor
The RS-485 bus is terminated with termination resistors of 120 ohms in both ends.
Vacon 10 has a built-in termination resistor which is switched off as a default (presented below). The termination resistor can be switched on and off with the right hand dip switch located above IO-terminals in the front of the drive (see below).
AI2 GND GND DI4 DI5 DI6 AO DO
4 5 13 14 15 16 18 20
1 2 3 6 7 8 9 10
+10V AI1 GND 24V GND DI1 DI2 DI3
ON mA
V
OFF
RO1 RO1
22 23
A B
120
+
-
25
RO2
26
24
RO2 RO2
= A PI R S-4 85
= API LIMITED
9.12.2 Modbus address area
The Modbus interface of Vacon 10 uses the ID numbers of the application parameters as addresses. The ID numbers can be found in the parameter tables in chapter 8.
When several parameters/monitoring values are read at a time, they must be consecutive. 11 addresses can be read and the addresses can be parameters or monitoring values.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon
•
80
9.12.3 Modbus process data
Process data is an address area for fieldbus control. Fieldbus control is active when the value of parameter 2.1 (Control place) is 3 (=fieldbus). The contents of the process data has been determined in the application. The following tables present the process data contents in the General Purpose Application.
Table 9.3: Output process data:
ID
2101
2102
2103
2104
2105
2106
2107
2108
2109
2110
2111
Modbus register Name
32101, 42101
32102, 42102
32103, 42103
32104, 42104
32105, 42105
32106, 42106
32107, 42107
Scale
FB Status Word -
FB General Status Word -
FB Actual Speed
Motor freq.
0,01
0,01
Motor speed
Motor current
Motor torque
1
0,01
0,1
32108, 42108
32109, 42109
32110, 42110
32111, 42111
Motor power
Motor voltage
DC voltage
Active fault
0,1
0,1
1
-
Type
Binary coded
Binary coded
%
+/- Hz
+/- Rpm
A
+/- % (of nominal)
+/- % (of nominal)
V
V
Fault code
Table 9.4: Input process data:
ID
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
Modbus register Name
32001, 42001 FB Control Word
32002, 42002
32003, 42003
32004, 42004
32005, 42005
32006, 42006
32007, 42007
32008, 42008
32009, 42009
32010, 42010
32011, 42011
FB General Control Word
FB Speed Reference
PI Control Reference
PI Actual value
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Scale
0,01
0,01
0,01
-
-
-
-
-
-
Type
Binary coded
Binary coded
%
%
%
24-hour support +358 (0) 201 212 575 • Email: [email protected]
9
9
81
• vacon parameter descriptions
Status word (output process data)
Information about the status of the device and messages is indicated in the Status word. The Status word is composed of 16 bits the meanings of which are described in the table below:
Bit
B0, RDY
B1, RUN
B2, DIR
B3, FLT
B4, W
B5, AREF
B6, Z
B7, F
B8 - B15
Value = 0
Drive not ready
Stop
Clockwise
No fault
No alarm
-
-
Ramping
-
Description
Value = 1
Drive ready
Run
Counter-clockwise
Fault active
Alarm active
Speed reference reached
Drive is running at zero speed
Flux ready
-
Actual speed (output process data)
This is actual speed of the frequency converter. The scaling is -10000...10000. The value is scaled in percentage of the frequency area between set minimum and maximum frequency.
Control word (input process data)
The three first bits of the control word are used to control the frequency converter.
By using control word it is possible to control the operation of the drive. The meaning of the bits of control word are explained in the table below:
Bit
B0, RUN
B1, DIR
B2, RST
Value = 0
Description
Value = 1
Stop
Clockwise
Run
Counter-clockwise
Rising edge of this bit will reset active fault
Speed reference (input process data)
This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0...10000. The value is scaled in percentage of the frequency area between the set minimum and maximum frequencies.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
technical data vacon
•
82
10. TECHNICAL DATA
10.1 Vacon 10 technical data
Mains connection
Input frequency
Line current THD
Connection to mains
Supply network
Networks
Motor connection
Input voltage U in
Short circuit current
Output voltage
Output current
115V, -15%...+10% 1~
208…240V, -15%...+10% 1~
208…240V, -15%...+10% 3~
380 - 480V, -15%...+10% 3~
575V, -15%...+10% 3~
45…66 Hz
> 120%
Once per minute or less (normal case)
Vacon 10 (400V) cannot be used with corner grounded networks
Maximum short circuit current has to be < 50kA
0 - U in
Continuous rated current I
N
at ambient temperature max.
+50ºC (depends on the unit size), overload 1.5 x I
N
1min/10min
max.
Control characteristics
Starting current / torque Current 2 x I
N
for 2 secs in every 20 sec period. Torque depends on motor
Output frequency 0…320 Hz
Frequency resolution
Control method
Switching frequency
Frequency reference
0,01 Hz
Frequency Control U/f
Open Loop Sensorless Vector Control
1,5...16 kHz; Factory default 6 kHz
Resolution 0.01 Hz
Field weakening point
Acceleration time
Deceleration time
Braking torque
30…320 Hz
0.1…3000 sec
0.1…3000 sec
100%*T
N
with brake option (only in 3~ drives sizes MI2 and
MI3 ) 30%*T
N
without brake option
Table 10.1: Vacon 10 technical data
24-hour support +358 (0)40 837 1150 • Email: [email protected]
10
83
• vacon technical data
Ambient conditions
EMC
Standards
Ambient operating temperature
Storage temperature
Relative humidity
-10°C (no frost)…+40/50°C (depends on the unit size): rated loadability I
N
-40°C…+70°C
0…95% RH, non-condensing, non-corrosive, no dripping water
Air quality:
- chemical vapours
- mech. particles
Altitude
Vibration:
EN60068-2-6
Shock
IEC 68-2-27
Enclosure class
Pollution degree
Immunity
Emissions
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000m. 1% derating for each 100m above 1000m; max. 2000m
3...150 Hz
Displacement amplitude 1(peak) mm at 3...15.8 Hz Max acceleration amplitude 1 G at 15.8...150 Hz
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
IP20
PD2
Complies with EN50082-1, -2, EN61800-3
115V: Complies with EMC category C4
230V : Complies with EMC category C2; With an internal
RFI filter
400V: Complies with EMC category C2; With an internal
RFI filter
575V: Complies with EMC category C4
All: No EMC emission protection (Vacon level N): Without
RFI filter
For EMC: EN61800-3,
For safety: UL508C, EN61800-5
Certificates and manufacturer’s declarations of conformity
Table 10.1: Vacon 10 technical data
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see unit nameplate for more detailed approvals)
10
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
technical data vacon
•
84
10.2 Power ratings
10.2.1 Vacon 10 - Mains voltage 115 V
Mains voltage 115 V, 50/60 Hz, 1~ series
Frequency converter type
0001
0002
Rated loadability
100% contin. current I
N
[ A ]
1,7
2,4
150% overload current [ A ]
2,6
3,6
0003
0004
2,8
3,7
4,2
5,6
0005 4,8 7,2
Table 10.2:Vacon 10 power ratings, 115 V
Motor shaft power
P
[ HP ]
0.33
0.5
0.75
1
1.5
Nominal input current
[ A ]
9,2
11,6
12,4
15
16,5
Mecha nical size
MI2
MI2
MI2
MI2
MI3
Weight
(kg)
0,70
0,70
0,70
0,70
0,99
10.2.2 Vacon 10 - Mains voltage 208 - 240 V
Mains voltage 208-240 V, 50/60 Hz, 1~ series
Frequency converter type
0001
0002
0003
Rated loadability
100% contin. current I
N
[ A ]
1,7
2,4
2,8
150% overload current [ A ]
2,6
3,6
4,2
Motor shaft power
P
[ kW ]
0,25
0,37
0,55
0004
0005
3,7
4,8
0007 7,0
0009 9,6
5,6
7,2
10,5
14,4
0,75
1,1
1,5
2,2
Table 10.3: Vacon 10 power ratings, 208 - 240 V, 1~
Nominal input current
[ A ]
4,2
5,7
6,6
8,3
11,2
14,1
22,1
Mechanical size
MI1
MI1
MI1
MI2
MI2
MI2
MI3
Weight
(kg)
0,55
0,55
0,55
0,70
0,70
0,70
0,99
24-hour support +358 (0)40 837 1150 • Email: [email protected]
10
85
• vacon technical data
Mains voltage 208-240 V, 50/60 Hz, 3~ series
Frequency converter type
0001
0002
0003
Rated loadability
100% contin. current I
N
[ A ]
1,7
2,4
2,8
150% overload current [ A ]
2,6
3,6
4,2
Motor shaft power
P
[ kW ]
0,25
0,37
0,55
0004
0005
0007
0011
3,7
4,8
7,0
11
5,6
7,2
10,5
16,5
0,75
1,1
1,5
2,2
Table 10.4: Vacon 10 power ratings, 208 - 240 V, 3~
Nominal input current
[ A ]
2,7
3,5
3,8
4,3
6,8
8,4
13,4
Mechanical size
MI1
MI1
MI1
MI2
MI2
MI2
MI3
Weight
(kg)
0,55
0,55
0,55
0,70
0,70
0,70
0,99
10.2.3 Vacon 10 - Mains voltage 380 - 480 V
Mains voltage 380-480 V, 50/60 Hz, 3~ series
Rated loadability
150% overload current
[ A ]
Motor shaft power
Freguency converter type
0001
0002
0003
0004
0005
0006
0008
0009
100% continuous current
I
N
[ A ]
1,3
1,9
2,4
3,3
4,3
5,6
7,6
9,0
2,0
2,9
3,6
5,0
6,5
8,4
11,4
13,5
380-480V supply
P[ kW ]
0,37
0,55
0,75
1,1
1,5
2,2
3,0
4,0
0012 12,0 18,0 5,5
Table 10.5: Vacon 10 power ratings, 380 - 480 V
Nominal input current
[ A ]
2,2
2,8
3,2
4,0
5,6
7,3
9,6
11,5
14,9
Mechanical size
Weight
(kg)
MI1 0,55
MI1 0,55
MI1
MI2
0,55
0,70
MI2
MI2
MI3
MI3
MI3
0,70
0,70
0,99
0,99
0,99
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
10
technical data vacon
•
86
10.2.4 Vacon 10 - Mains voltage 575 V
Mains voltage 575 V, 50/60 Hz, 3~ series
Rated loadability
Frequency converter type
0002
0003
100% contin. current I
N
[ A ]
1,7
2,7
150% overload current [ A ]
2,6
4,2
0004
0006
0009
0011
3,9
6,1
9
11
5,9
9,2
13,5
16,5
Table 10.6: Vacon 10 power ratings, 575 V
Motor shaft power
P
[ HP ]
1
2
3
5
7,5
10
Nominal input current
Mechanical size
[ A ]
2
3,6
5
7,6
10,4
14,1
MI3
MI3
MI3
MI3
MI3
MI3
Weight
(kg)
0,99
0,99
0,99
0,99
0,99
0,99
Note 1:
The input currents are calculated values with 100 kVA line transformer supply.
Note 2:
The mechanical dimensions of the units are given in Chapter 3.1.1.
10.3 Brake resistors
Vacon 10 type
MI2 380-480V
MI3 380-480V
MI2 204-240V, 3~
MI3 204-240V, 3~
MI3 575V
Minimum braking resistance
75 Ohm
54 Ohm
35 Ohm
26 Ohm
Resistor type code (from Vacon NX family)
Light duty Heavy duty Resistance
-
BRR 0022 LD 5 BRR 0022 HD 5 63 Ohm
BRR 0022 LD 5 BRR 0022 HD 5 63 Ohm
BRR 0022 LD 5 BRR 0022 HD 5 63 Ohm
Contact the manufacturer for data!
Note!
Only 3-phase MI2 and MI3 drives are equipped with brake chopper.
For further information on brake resistors, please download Vacon NX Brake Resistor Manual (UD00971C) on http://www.vacon.com/Support & Downloads
24-hour support +358 (0)40 837 1150 • Email: [email protected]
10
advertisement