EtherCAT Communication Converter
COM-ML
[For SRZ]
Installation
Manual
IMR02E09-E3
All Rights Reserved, Copyright 2010, RKC INSTRUMENT INC.
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of the instrument, carefully read all the instructions in this manual.
Please place the manual in a convenient location for easy reference.
This manual describes the mounting, wiring and specifications only.
For detailed handling procedures and various function settings, refer to separate COM-ML [For SRZ] Instruction Manual (IMR02E11-E
The manual can be downloaded from the official RKC website: https://www.rkcinst.com/english/manual_load.htm
) .
Product check
COM-ML [For SRZ] Installation Manual (IMR02E09-E3) ..................................................... 1
COM-ML [For SRZ] Communication Data List (IMR02E10-E ) ......................................... 1
Joint connector cover (KSRZ-517A) ..................................................................................... 2
Power terminal cover (KSRZ-518A) ...................................................................................... 1
Safety precautions
To prevent injury to persons, damage to the instrument and the equipment, a suitable external protection device shall be required.
All wiring must be completed before power is turned on to prevent electric shock, fire or damage to the instrument and the equipment.
This instrument must be used in accordance with the specifications to prevent fire or damage to the instrument and the equipment.
This instrument is not intended for use in locations subject to flammable or explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or disassembled by other than factory-approved personnel. Malfunction may occur and warranty is void under these conditions.
This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy plant.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation.
Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
− If input/output or signal lines within the building are longer than 30 meters.
− If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock to operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or equipment.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
All wiring must be in accordance with local codes and regulations.
To prevent instrument damage as a result of failure, protect the power line and the input/output lines from high currents with a suitable overcurrent protection device with adequate breaking capacity such as a fuse, circuit breaker, etc.
A malfunction in this product may occasionally make control operations impossible or prevent alarm outputs, resulting in a possible hazard. Take appropriate measures in the end use to prevent hazards in the event of malfunction.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dissipation.
Do not connect wires to unused terminals as this will interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or discoloration may occur. Use a soft, dry cloth to remove stains from the instrument.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for explanation purpose.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty, expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
Various symbols are used on the equipment, they have the following meaning.
! : Caution (This symbol is used where the instruction manual needs to be consulted for the safety of operator and equipment.)
This symbol on the left side of the product denotes caution for electric shock and damages to the equipment. Read the following items before using this product.
- Safety precautions “WARNING”
- 3. MOUNTING “ WARNING ” and 4. WIRING “ WARNING ”
1. OUTLINE
The COM-ML is a EtherCAT gateway for RKC SRZ.
Multi-zone temperature control system can be easily achieved by connecting function modules
(Z-TIO-A/B and Z-DIO-A modules) of SRZ to COM-ML. The combination of COM-ML and function module of SRZ is called an SRZ unit.
EtherCAT
Host computer
RKC communication
Modbus
RS-485
RS-422A
SRZ unit
EtherCAT
Communication Converter
COM-ML
Z-TIO-A/B and Z-DIO-A modules
2. PARTS DESCRIPTION
Mainframe
Front view
Loader communication connector
Communication port
COM. PORT
FAIL/RUN
RX/TX
COM-ML
Indication lamp
FAIL/RUN
Indication lamp RX/TX
Host communication address setting switch
Left side view
DIP switch
EtherCAT connector
(Port1) [IN]
EtherCAT connector
(Port2) [OUT]
Indication lamp RUN
Indication lamp Link/Activity (Port1)
Indication lamp Link/Activity (Port2)
Indication lamp ERR
Indication lamp
FAIL/RUN
RX/TX
[Green or Red]
• When normal: Green lamp turns on (RUN)
• Self-diagnostic error (Recoverable fault): Green lamp flashing (FAIL)
• Self-diagnostic error (Major fault): Red lamp turns on (FAIL)
[Green] During host communication data send and receive: Green lamp turns on
RUN [Green or Red] • INIT or No power:
• ORERATIONAL:
• PRE-ORERATIONAL:
• SAFE-ORERATIONAL:
• EXCEPTION:
Link/Activity (Port1/Port2)
[Green]
Turns off
Green lamp turns on
Green lamp blinking
Green lamp single flashing *
Red lamp turns on
• No link or No power: Turns off
• Link sensed, activity detected: Green lamp flashing
• Link sensed, no activity: Green lamp turns on
ERR [Red] • No error or No power:
• Invalid configuration:
Turns off
Red lamp blinking
• Unsolicited state change: Red lamp single flashing *
• Application watchdog timeout: Red lamp double flashing *
• PDI watchdog timeout: Red lamp turns on
* Single flashing: Repeats ON (200 ms)/OFF (100 ms).
Double flashing: Repeats ON (200 ms)/OFF (200 ms)/ON (200 ms)/OFF (1000 ms).
Communication port (modular connector) and communication connector
COM. PORT Use to connecting the Operation panel or Host computer.
[RS-485 or RS-422A]
Loader communication connector
EtherCAT connector
(Port1) [IN]
EtherCAT connector
(Port2) [OUT]
Switch
Host communication address setting switch
Use to connecting the communication converter and personal computer when loader communication is performed.
Designed to connect EtherCAT with master instrument or slave instrument located near the master instrument.
Designed to connect EtherCAT with the next slave instrument.
Sets unit address for host communication.
DIP switch • Sets communication speed and communication protocol corresponding to host communication.
• Sets DIP switch setting validity/invalidity.
Base
Mounting holes (M3 screw)
Holes for screws to fix the base to a panel, etc.
Customer must provide the M3 screws.
Mounting bracket
Used to fix the COM-ML on
DIN rails.
1 2
3 4 5
Joint connector
Used to mechanically and electrically connect each function module.
Power supply terminals
These are terminals to supply power to the COM-ML and joined function modules.
Terminal 3, 4 and 5
These terminals cannot be used for the COM-ML.
(Usage is prohibited.)
3. MOUNTING
To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
3.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions.
(IEC 61010-1) [POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions:
• Allowable ambient temperature: − 10 to + 50 ° C
• Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX. W. C 29.3 g/m 3 dry air at 101.3 kPa)
• Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location:
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following conditions:
• Ensure at least 50 mm space on top and bottom of the instrument for maintenance and environmental reasons.
• Do not mount this instrument directly above the equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
• If the ambient temperature rises above 50 ° C, cool this instrument with a forced air fan, cooler, etc.
Cooled air should not blow directly on this instrument.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines:
Rotating machinery:
Separate at least 200 mm.
Separate as far as possible.
• For correct functioning mount this instrument in a horizontal position.
• Be sure the COM-ML and function modules are joined when using them.
Top
Bottom
(5) In case this instrument is connected to a supply by means of a permanent connection, a switch or circuit-breaker shall be included in the installation. This shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
3.2 Joining Each Module
Before joining the COM-ML and function modules, use the DIP switch to make the communication settings. For the setting procedure, refer to 5. HOST COMMUNICATION
SETTINGS (rear side).
The maximum number of function modules (Z-TIO-A/B, Z-DIO-A) described in the following can be joined per COM-ML. For details on joining function modules with the COM-ML, refer to the Z-TIO
INSTRUCTION MANUAL (IMS01T01-E ) .
• When joining function modules of the same type: Up to 16 modules
• When joining function modules of two or more different types: Up to 30 modules
(However, the maximum joinable number of function modules of the same type is 16.)
[Example] When the Z-TIO-A/B and Z-DIO-A modules are joined
SRZ unit
COM-ML
⋅⋅⋅⋅⋅⋅⋅⋅ ⋅⋅⋅⋅⋅⋅⋅⋅
3.3 Dimensions
76.9
16 Z-TIO-A/B modules 14 Z-DIO-A modules
Function modules: Up to 30 modules
4.7 30 6.7 (Unit: mm)
Space required between each instrument vertically
When the COM-ML is mounted on the panel, allow a minimum of 50 mm at the top and bottom of the COM-ML to attach the COM-ML to the mainframe.
Depth for communication cables mounting
Space for communication cables must be considered when installing
(Unit: mm)
Approx. 50
50 mm or more
Communication cable
Procedure for mounting or removing
The procedure for mounting or removing the COM-ML is the same as that of the function module
(Z-TIO-A/B or Z-DIO-A). Both DIN rail mounting and screw mounting are available.
For the mounting or removing, refer to the Z-TIO INSTRUCTION MANUAL (IMS01T01-E ) .
4. WIRING
To prevent electric shock or instrument failure, do not turn on the power until all the wiring is completed. Make sure that the wiring has been properly made before applying power to the instrument.
4.1 Wiring Cautions
• To avoid noise induction, keep communication signal wire away from instrument power line, load lines and power lines of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply input, supply power from a “SELV” circuit defined as IEC 60950-1.
• A suitable power supply should be considered in end-use equipment.
The power supply must be in compliance with a limited-energy circuits (maximum available current of 8 A).
• Select the power capacity which is appropriate for the total power consumption of all joined modules (including COM-ML) and the initial current surge when the power is turned on.
Power consumption (at maximum load): 120 mA max. (at 24 V DC)
Rush current: 12 A or less
• When connecting the wiring to the terminals on the base, use the specified solderless terminals. Only these specified solderless terminals can be used due to the insulation between the terminals.
Screw Size: Power supply terminals: M3
FG terminal
× 7 (with 5.8
M3 × 6
Recommended tightening torque: 0.4 N ・ m (4 kgf ・ cm)
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm 2
×
φ
5.8 square washer)
5.5 MAX
Specified solderless terminal:
Manufactured by J.S.T MFG CO., LTD.
Circular terminal with isolation V1.25
− MS3
(M3 screw, width 5.5 mm, hole diameter 3.2 mm)
• Make sure that during field wiring parts of conductors cannot come into contact with adjacent conductive parts.
φ
5.6 mm
3.2 MIN
9.0 mm
φ 5.0
4.2 Terminal Configuration
Lower part of the base
1 2
Power supply terminals
3 4 5
1 2
Supply the power to only one of the joined modules or COM-ML.
When power is supplied to any one of the joined modules or COM-ML, all of the joined modules and COM-ML will receive power.
+
24 V DC
−
Terminals 3, 4 and 5
(Usage is prohibited.)
4.3 Connection to EtherCAT
FAIL/RUN
RX/TX
C OM -ML
EtherCAT connector
RJ-45 pin number
8
1
5
6
7
8
1
2
3
4
Pin No. Signal name
Send data +
Send data −
Receive data +
Unused
Unused
Receive data −
Unused
Unused
Symbol
TX +
TX −
RX +
⎯
⎯
RX −
⎯
⎯
Connection Example
Can connect with the Ethernet cable which is marketed. The Ethernet cable must be provided by the customer.
Master instrument
Slave instrument 1 Slave instrument 2
Use IN port to connect with master instrument.
Ethernet cable
IN
Use OUT port to connect with slave instrument.
IN
OUT
Ethernet cable
Ethernet straight through cable and Ethernet crossover cable may be used.
The details of the EtherCAT are connected to the website of ETG (EtherCAT
Technology Group), and obtain necessary information.
URL: https://www.ethercat.org/
4.4 Connection to Host Computer
RS-422A
FAIL/RUN
RX/TX
COM-ML
Modular connector pin number
6
Pin No.
1
2
3
4
5
Signal name
Receive data
Receive data
Signal ground
Send data
Send data
Symbol
R (A)
R (B)
SG
T (B)
T (A)
6 Signal ground SG
1
RS-485
Communication port for Host computer or
Operation panel connection
COM. PORT
[RS-422A/RS-485]
Pin No.
1
2
Signal name
Send/receive data
Send/receive data
Symbol
T/R (A)
T/R (B)
3 Signal ground SG
4
5
Unused
Unused
⎯
⎯
SG 6 Signal ground
The six-pin type modular connector should be used for the connection to the COM-ML.
(Recommended manufacturer and model: Hirose Electric, TM4P-66P)
RS-422A
Up to 16 SRZ units can be connected to a host computer communication port.
COM-ML (COM. PORT)
RS-422A
Paired wire Host computer
( − )
R (A) 1 T (A)
( − )
( + )
R (B)
SG
2
3
4
R1
T (B)
SG
( + )
( + )
Host computer
T (B) R (A)
( − )
( − )
T (A) 5
R1
R (B)
( + )
SG 6
Shielded twisted pair wire
R1: Termination Resistor
(Host computer side)
If communication errors occur frequently due to the operation environment or the communication distance, connect termination resistors to the host computer side.
When the interface of host computer is RS-232C
Connect the RS-232C/RS-422A converter between the host computer and the COM-ML.
RS-232C/RS-422A converter
COM-A (RKC product)
W-BF-28* RS-232C
Connect to communication connector
D-sub 9-pin connector
Connect to
COM.PORT1 Connect to
COM.PORT2
SRZ unit
W-BF-02*
RS-422A
Connect to
COM.PORT
* Communication cable (RKC product) is sold separately.
W-BF-02 and W-BF-28 communication cable (RKC product) can be used as communication cable (sold separately). If noise is a factor, customer should use a twisted pair cable (not included) or something to that effect.
Recommended RS-232C/RS-422A converter: COM-A (RKC product)
For the COM-A, refer to the COM-A/COM-B Instruction Manual (IMSRM33-E ) .
When the host computer has a USB connector
Connect the USB communication converter between the host computer and the COM-ML.
Host computer Connect to USB port of a host computer
COM-ML (COM. PORT)
RS-422A
USB cable
(COM-K2 accessory)
( − )
R (A) 1 1 SG
( + )
( + )
( − )
R (B)
SG
T (B)
T (A)
2
3
4
5
2
3
4
5
T (A)
T (B)
R (A)
R (B)
Connect to
USB connector of COM-K2
The termination resistor is built into the COM-K2.
SG
6
USB communication converter COM-K2
Shielded twisted pair wire
(RKC product)
Paired wire
For the COM-K2, refer to the COM-K2 Instruction Manual .
RS-485
Up to 16 SRZ units can be connected to a host computer communication port.
COM-ML (COM. PORT)
RS-485
Host computer
( − )
T/R (A) 1 SG
( + )
T/R (B) 2 T/R (A)
( − )
SG 3 T/R (B)
R1
( + )
Unused 4
Paired
Unused 5 wire
SG 6
Shielded twisted pair wire
R1: Termination Resistor [Example: 120 Ω 1/2 W]
(Host computer side)
If communication errors occur frequently due to the operation environment or the communication distance, connect termination resistors to the host computer side.
When the interface of host computer is RS-232C
Connect the RS-232C/RS-485 converter between the host computer and the COM-ML.
RS-232C/RS-485 converter
Unused R(B)
R(A)
Orange
White
RS-485
Connect to
COM.PORT
SRZ unit
T/R (B)
T/R (A)
T(B)
T(A)
Black
Blue
Red
W-BF-01*
SG SG
Connect according to the label names as they are without crossing the wires.
RS-232C Host computer
* Communication cable (RKC product) is sold separately.
Connect to communication connector
Be sure to insulate the wires that are not used by covering them with insulating tape.
Recommended RS-232C/RS-485 converter:
CD485, CD485/V Data Link product, Inc. or equivalent.
W-BF-01 communication cable (RKC product) can be used as communication cable (sold separately). If noise is a factor, customer should use a twisted pair cable (not included) or something to that effect.
When the host computer has a USB connector
Connect the USB communication converter between the host computer and the COM-ML.
Host computer
Connect to USB port of a host computer
COM-ML (COM. PORT) RS-485
USB cable
(COM-K2 accessory )
( − )
T/R (A) 1
T/R (B) 2
1 SG
( + )
SG 3
4
2
3
T/R (A)
T/R (B)
Connect to
USB connector of COM-K2
Unused
SG
5
6
Shielded twisted pair wire
Paired wire
4
5
Unused
The termination resistor is built into the COM-K2.
USB communication converter COM-K2
(RKC product)
For the COM-K2, refer to the COM-K2 Instruction Manual .
Loader communication
Connect a USB communication converter between the host computer and the COM-ML.
Connect to loader communication connector of the COM-ML
USB communication converter
COM-K2 (RKC product)
Personal computer
USB cable
(COM-K2 accessory)
Connect to loader communication connector
The termination resistor is built into the COM-K2.
Loader communication cable
(W-BV-01) [Sold separately]
Connect to
USB connector
Connect to
USB port of a personal computer
The Loader port is only for parameter setup. Not used for data logging during operation.
During the loader communication, the COM-ML requires an external power source. The
COM-ML will not function on the USB power from a personal computer alone.
The module address for loader communication is fixed at “0.”
For the COM-K2, refer to the COM-K2 Instruction Manual .
5. HOST COMMUNICATION SETTINGS
5.1 Address Settings
Set the address for host communication. Use a small flat-blade screwdriver to configure the setting.
Set the address such that it is different to the other addresses on the same line.
Otherwise, problems or malfunction may result.
Host communication address setting switch
Setting range:
0 to F [0 to 15: decimal numbers]
Factory set value: 0
COM-ML
5.2 DIP Switch Settings
Use the DIP switch to set the speed and protocol of host communication, and DIP switch enable/disable.
DIP switch
Left side view
ON OFF
1 2 Host communication speed
OFF OFF
ON OFF
OFF ON
ON ON
4800 bps
9600 bps
19200 bps
38400 bps
Factory set value:
19200 bps
3
OFF
ON
Communication protocol/Data bit configuration
RKC communication
(Data 8-bit, without parity, Stop 1-bit)
Modbus
(Data 8-bit, without parity, Stop 1-bit)
Factory set value:
RKC communication
4 5 6 7
OFF OFF OFF OFF Fixed (Do not set this one)
8 DIP switch enable/disable
OFF Enable (enable the DIP switch settings)
ON
Disable (enable the host communication or loader communication settings)*
Factory set value:
Enabled
* The only host communication or loader communication settings that are enabled are the host communication speed and protocol and the data bit configuration.
When the communication protocol is set with the DIP switch, the data bit configuration is automatically set to “data 8-bit, without parity, stop 1-bit.” To change to another data bit configuration, set the configuration in host communication or loader communication.
If you wish to set the data bit configuration, host communication speed, and communication protocol in host communication or loader communication, first set DIP switch No. 8 to ON.
6. SPECIFICATIONS
EtherCAT communication
Physical layer: 100BASE-TX
User layer: EtherCAT
Correspondence protocol: CANopen over EtherCAT
Communication object:
Connector type:
Service data object (SDO), Process data object (PDO)
RJ-45 (2 ports)
Host communication
Interface:
Protocol:
Base on RS-422A, EIA standard
Base on RS-485, EIA standard
RKC communication (ANSI X3.28-1976 subcategories 2.5 and B1)
Modbus-RTU
4800 bps, 9600 bps, 19200 bps, 38400 bps Communication speed:
Maximum connections:
Termination resistor:
16 SRZ units per communication port of host computer
Externally connected
Loader communication
Connection method: Connection with a loader communication cable for our USB converter COM-K2 (sold separately).
Protocol:
Communication speed:
Maximum connections:
RKC communication (ANSI X3.28-1976 subcategories 2.5 and B1)
38400 bps
1 SRZ unit
General specifications
Power supply voltage: 24 V DC
Power supply voltage range: 21.6 V to 26.4 V DC
[Including power supply voltage variation]
Power consumption (at maximum load):
120 mA max. (24 V DC)
Rush current: 12 A or less
Allowable ambient temperature:
− 10 to + 50 ° C
Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX.W.C 29.3 g/m 3 dry air at 101.3 kPa)
Installation environment conditions:
Indoors use, Altitude up to 2000 m
Weight: Approx. 130 g
Standard
Safety standard: UL:
CE marking:
RCM: cUL:
LVD:
UL 61010-1
CAN/CSA-C22.2 No.61010-1
EN61010-1
POLLUTION DEGREE 2, Class II (Reinforced insulation)
EMC: EN61326-1
EN55011
7. MODEL CODE
CO M -M L- 3 * 02
(1) (2) (3)
(1) Ethernet communication type
3: EtherCAT
(2) Host communication interface (COM. PORT)
4: RS-422A 5: RS-485
(3) Corresponding to the RKC controller
02: SRZ
Other peripherals and accessories (Sold separately)
Communication cable [Modular ↔ Y-shaped terminal lugs] (W-BF-01 , : Cable length)
Communication cable [Modular ↔ Modular] (W-BF-02 , : Cable length)
Communication cable [Modular ↔ D-sub 9-pin] (W-BF-28 , : Cable length)
Communication converter COM-K2-1 (Optional: with loader communication cable)
End plate (DEP-01, Package of 2 plates)
EtherCAT ® is a registered trademark of Beckhoff Automation GmbH
Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the trademarks or registered trademarks of the respective companies.
The first edition: FEB. 2010 [IMQ00]
The third edition: JUL. 2019 [IMQ00]
Website: https://www.rkcinst.com/
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799)
E-mail: [email protected] ttp://www.rkcinst.com/ JUL. 2019
advertisement