- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- VOKERA
- UNICA i28
- Instructions
advertisement
Unica i28
-
i32
High efficiency combi boiler
Users Instructions
Installation &
Servicing
Instructions
G.C. NUMBER
Unica i28
47 364 14
Unica i32
47 364 15
THESE INSTRUCTIONS
TO BE RETAINED
BY USER
Vokèra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK.
Users instructions
1. THINGS YOU SHOULD KNOW ............................................1
1.1 GAS APPLIANCES ................................................................1
1.2 ELECTRICAL SUPPLY ..........................................................1
1.3 GUARANTEE REGISTRATION CARD ..................................1
1.4 APPLIANCE COMMISSIONING CHECKLIST (UK only) .......1
1.5 HOW DOES IT WORK? .........................................................1
1.6 DIMENSIONS.........................................................................1
1.7 CLEARANCES REQUIRED ...................................................1
1.8 FROST PROTECTION SYSTEM ...........................................1
1.9 APPLIANCE STATUS INDICATORS ......................................1
2. GETTING STARTED ..............................................................3
2.1 BEFORE SWITCHING ON .....................................................3
2.2 APPLIANCE CONTROLS .....................................................3
2.3 LIGHTING THE BOILER ........................................................3
2.4 ADJUSTING THE HEATING TEMPERATURE ......................3
2.5 ADJUSTING THE HOT WATER TEMPERATURE .................3
2.6 EXPLANATION OF FEATURES ............................................3
2.7 AUTOMATIC TEMPERATURE CONTROL ............................3
3. HOW TO... ..............................................................................4
3.1 HOW TO TOP-UP THE SYSTEM PRESSURE .....................4
3.2 HOW TO RESET THE APPLIANCE .......................................4
3.3 HOW TO SHUT DOWN THE SYSTEM
FOR SHORT PERIODS .........................................................4
3.4 HOW TO SHUT DOWN THE SYSTEM
FOR LONG PERIODS ..........................................................4
3.5 HOW TO CARE FOR THE APPLIANCE ...............................4
4. WHAT IF... ..............................................................................4
4.1 WHAT IF I SUSPECT A GAS LEAK .......................................4
4.2 WHAT IF I HAVE FREQUENTLY
TO TOP-UP THE SYSTEM ....................................................4
4.3 WHAT IF THE APPLIANCE IS DUE
ITS ANNUAL SERVICE .........................................................4
4.4 WHAT IF I NEED TO CALL AN ENGINEER...........................4
Installation and servicing instructions
SECTION 1 - DESIGN PRINCIPLES AND OPERATING SE-
QUENCE .......................................................................................6
1.1 PRINCIPLE COMPONENTS..................................................6
1.2 MODE OF OPERATION (at rest) ...........................................6
1.3 MODE OF OPERATION (Heating) .........................................6
1.4 MODE OF OPERATION (Hot water) ......................................6
1.5 SAFETY DEVICES .................................................................6
SECTION 2 - TECHNICAL DATA ....................................................7
2.1 CENTRAL HEATING ..............................................................7
2.2 DOMESTIC HOT WATER ......................................................7
2.3 GAS PRESSURES.................................................................7
2.4 EXPANSION VESSEL ............................................................7
2.5 DIMENSIONS.........................................................................7
2.6 CLEARANCES .......................................................................7
2.7 CONNECTIONS .....................................................................7
2.8 ELECTRICAL .........................................................................7
2.9 FLUE DETAILS (CONCENTRIC 60-100) ...............................7
2.9A FLUE DETAILS (CONCENTRIC 80-125) ...............................7
2.9B FLUE DETAILS (TWIN PIPES) ..............................................7
2.10 EFFICIENCY ..........................................................................7
2.11 EMISSIONS ...........................................................................7
2.12 PUMP DUTY ..........................................................................9
SECTION 3 - GENERAL REQUIREMENTS (UK) .........................10
3.1 RELATED DOCUMENTS .....................................................10
3.2 LOCATION OF APPLIANCE ................................................10
3.3 GAS SUPPLY .......................................................................10
3.4 FLUE SYSTEM ....................................................................10
3.5 AIR SUPPLY ........................................................................10
3.6 WATER CIRCULATION ........................................................10
3.7 ELECTRICAL SUPPLY ........................................................ 11
3.8 MOUNTING ON A COMBUSTIBLE SURFACE .................... 11
3.9 TIMBER FRAMED BUILDINGS ........................................... 11
3.10 INHIBITORS ......................................................................... 11
3.11 SHOWERS ........................................................................... 11
SECTION 3A - GENERAL REQUIREMENTS (EIRE) .................... 11
3A.1 RELATED DOCUMENTS ..................................................... 11
3A.2 LOCATION OF APPLIANCE ................................................ 11
3A.3 GAS SUPPLY .......................................................................12
3A.4 FLUE SYSTEM ....................................................................12
3A.5 AIR SUPPLY ........................................................................12
3A.6 WATER CIRCULATION ........................................................12
3A.7 ELECTRICAL SUPPLY ........................................................12
3A.8 MOUNTING ON A COMBUSTIBLE SURFACE ....................12
3A.9 TIMBER FRAMED BUILDINGS ...........................................12
3A.10 INHIBITORS .........................................................................12
3A.11 SHOWERS ...........................................................................12
3A.12 DECLARATION OF CONFORMITY .....................................12
SECTION 4 - INSTALLATION .......................................................13
4.1 DELIVERY ..........................................................................13
4.2 CONTENTS ..........................................................................13
4.3 UNPACKING ........................................................................13
4.4 PREPARATION FOR MOUNTING THE APPLIANCE ..........13
4.5 FITTING THE FLUE .............................................................14
4.6 CONNECTING THE GAS AND WATER ..............................18
4.7 ELECTRICAL CONNECTIONS ............................................18
SECTION 5 - COMMISSIONING ...................................................19
5.1 GAS SUPPLY INSTALLATION .............................................19
5.2 THE HEATING SYSTEM ......................................................19
5.3 FILL THE CONDENSATE TRAP ..........................................19
5.4 INITIAL FILLING OF THE SYSTEM .....................................19
5.5 INITIAL FLUSHING OF THE SYSTEM ................................19
5.6 PRE-OPERATION CHECKS ................................................19
5.7 INITIAL LIGHTING ...............................................................19
5.8 CHECKING GAS PRESSURE
AND COMBUSTION ANALYSIS ..........................................19
5.9 FINAL FLUSHING OF THE HEATING SYSTEM .................19
5.10 SETTING THE BOILER OPERATING TEMPERATURE ......19
5.11 SETTING THE SYSTEM DESIGN PRESSURE ..................19
5.12 REGULATING THE CENTRAL HEATING SYSTEM ............19
5.13 FINAL CHECKS ...................................................................20
5.14 INSTRUCTING THE USER ..................................................20
SECTION 6 - SERVICING INSTRUCTIONS ..................................20
6.1 GENERAL ............................................................................20
6.2 ROUTINE ANNUAL SERVICING .........................................20
6.3 REPLACEMENT OF COMPONENTS ..................................20
6.4 COMPONENT REMOVAL PROCEDURE ............................20
6.5 PUMP ASSEMBLY ..............................................................21
6.6 SAFETY VALVE ..................................................................21
6.7 LOWER AUTOMATIC AIR RELEASE VALVE .....................21
6.8 WATER PRESSURE SWITCH ............................................21
6.9 FLOW THERMISTOR .........................................................21
6.10 RETURN THERMISTOR .....................................................21
6.11 PRINTED CIRCUIT BOARD ...............................................21
6.12 GAS VALVE .........................................................................22
6.13 ELECTRODES & CONDENSE SENSOR ............................22
6.14 AIR PRESSURE SWITCH REMOVAL ................................22
6.15 FLUE FAN & MIXER ...........................................................22
6.16 BURNER .............................................................................22
6.17 MAIN HEAT EXCHANGER .................................................23
6.18 AUTOMATIC BY-PASS & DHW NON-RETURN VALVE .....23
6.19 EXPANSION VESSEL REMOVAL .......................................23
6.20 CONDENSE TRAP REMOVAL ...........................................23
6.21 FLUE COLLECTOR REMOVAL ..........................................24
SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING 25
7.1 CHECKING APPLIANCE OPERATION ...............................25
7.2 APPLIANCE MODES OF OPERATION ...............................25
7.3 CHECKING THE CO
2
AND
ADJUSTING THE GAS VALVE ............................................25
7.4 COMBUSTION ANALYSIS TEST .........................................26
7.5 CHECKING THE EXPANSION VESSEL ..............................26
7.6 EXTERNAL FAULTS ............................................................26
7.7 ELECTRICAL CHECKS .......................................................26
7.8 FAULT FINDING ...................................................................27
7.9 COMPONENT VALUES & CHARACTERISTICS .................27
7.10 ADJUSTMENTS ...................................................................28
7.11 ALARM RECORDS ..............................................................30
SECTION 8 - WIRING DIAGRAMS ...............................................31
8.1 EXTERNAL WIRING ............................................................31
8.2 TYPICAL CONTROL APPLICATIONS .................................31
8.3 OTHER DEVICES ................................................................31
SECTION 9 - LPG INSTRUCTIONS ..............................................33
9.1 RELATED DOCUMENTS .....................................................33
9.2 TECHNICAL DATA ...............................................................33
9.3 CONVERTING THE APPLIANCE GAS TYPE .....................33
9.4 GAS SUPPLY .......................................................................33
9.5 GAS SUPPLY INSTALLATION .............................................33
9.6 CHECKING THE CO
2
AND
ADJUSTING THE GAS VALVE ............................................33
Commissioning checklist ........................................................... 34
Benchmark .............................................................................. 35-38
Warranty Terms && Conditions .................................................. 39
USERS INSTRUCTIONS
INTRODUCTION
Dear Customer
Your Vokèra
Unica
boiler has been designed to meet and exceed the very latest standards in gas central heating technology, and if cared for, will give years of reliable use and efficiency. Please therefore take some time to read these instructions carefully.
Do’s and Don’t’s
-
Do
ensure that the system pressure is periodically checked
-
Do
ensure that the boiler should not be used by children or unassisted disabled people
-
Do
ensure that you know how to isolate the appliance in an emergency
-
Do
ensure that you are familiar with the appliance controls
-
Do
ensure that your installer has completed the appliance log book section
-
Do not
attempt to remove the appliance casing or gain internal access
-
Do not
hang clothes etc. over the appliance
-
Do not
forget to have the appliance serviced annually.
This booklet is an integral part of the appliance. It is therefore necessary to ensure that the booklet is handed to the person responsible for the property in which the appliance is located/installed. A replacement copy can be obtained from the Vokèra website - www.vokera.co.uk.
At the end of its life, the product should be not be disposed of as solid urban waste, but rather it should be handed over to a differentiated waste collection centre.
1. THINGS YOU SHOULD KNOW
1.1 GAS APPLIANCES
Gas Safety (Installation and Use) Regulation (UK).
In the interests of your safety and that of others it is a legal requirement that all gas appliances are installed and correctly maintained by a competent person and in accordance with the latest regulations.
1.2 ELECTRICAL SUPPLY
Please ensure that this appliance has been properly connected to the electrical supply by means of a double pole isolator or un-switched socket, and that the correct size of fuse (3 AMP) has been fitted.
Warning: this appliance must be earthed!
1.3 GUARANTEE REGISTRATION CARD
Please take the time to fill out your guarantee registration card.
The completed warranty card should be posted within 30 days of installation.
1.4 APPLIANCE COMMISSIONING CHECKLIST
(UK only)
A checklist section can be found at the rear of the appliance installation booklet. This important document must be completed during the installation/commissioning of your boiler. All
GAS SAFE registered installers carry a GAS SAFE ID card, and have a registration number. These details should be recorded in the Benchmark commissioning checklist section within the installation booklet. You can check your installers details by calling GAS SAFE direct on 08004085500. Failure to install and commission the appliance in accordance with the manufacturers instructions will invalidate the warranty.
This does not affect your statutory rights.
1.5 HOW DOES IT WORK?
Your
Unica
boiler supplies heated water to your radiators and trolled via a time clock and any thermostats that your installer may have fitted. The boiler will light when it receives a request from the time clock via any thermostat that may be installed, or whenever a hot water outlet (tap) is opened. Your
Unica
boiler lights electronically and does not have a pilot light.
In the unlikely event of a fault developing with your boiler, the supply of gas to the burner will be terminated automatically.
1.6 DIMENSIONS
Unica i28
HEIGHT 780 mm
WIDTH
DEPTH
400 mm
358 mm
Unica i32
780 mm
400 mm
358 mm
1.7 CLEARANCES REQUIRED
ABOVE
BELOW
150 mm
150 mm
LEFT SIDE 12 mm
RIGHT
SIDE
12 mm
FRONT 600 mm
1.8 FROST PROTECTION SYSTEM
The
Unica
is equipped with a built-in frost protection system, this enables the boiler to over-ride the time controls – even if switched off – and operate the burner and/or pump, should the temperature drop below 5
0
C for the main and for the DHW line. In particular the burner will be in ON status until the main temperature reaches 35°C for CH appliance and 55°C for
DHW appliance.
Please note that the frost protection system is designed to protect the appliance only, should frost protection be required for the heating system, additional controls may be required.
NOTE
The frost protection system is reliant on the appliance having a permanent electrical supply, and being in a non-fault condition.
1.9 APPLIANCE STATUS INDICATORS
Your boiler is equipped with a large LCD display that indicates the appliance operating status.
1
Fig. 1
PRESSURE GAUGE
DISPLAY LED
2
MODE SELECTOR SWITCH
HEATING TEMPERATURE SELECTOR
HOT WATER
TEMPERATURE
SELECTOR
HOT WATER TEMPERATURE SELECTOR
Move the selector clockwise to increase the hot water outlet temperature, or counter-clockwise to reduce the temperature
PRESSURE GAUGE
Ensure the system pressure is set correctly (minimum 0.5-bar)
MODE SELECTOR SWITCH/HEATING TEMPERATURE SELECTOR
Mode selector switch:
Hot water only
- Select this position if you want the boiler to supply hot water only (no heating)
Hot water temperature selector
: move the selector clockwise to increase the DHW outlet temperature, or counter-clockwise to reduce the temperature
(range: 37°C-60°C)
The display shows the temperature values.
DHW pre-heat function -
Turning the domestic hot water temperature adjustment knob to the symbol activates the pre-heating function. Bring the domestic hot water temperature adjustment knob back to the required position. The activation of this function is indicated on display with the
P
icon
ON. This function keeps the water in the domestic hot water exchanger hot, to reduce standby times when a request is made. The display shows the delivery temperature of the heating water or the domestic hot water, according to the current request. To deactivate the pre-heat function, rotate the domestic hot water temperature adjustment knob back to the symbol. Bring the domestic hot water temperature adjustment knob back to the required position. This function cannot be activated when the boiler is OFF: function selector to OFF position.
Heating & hot water
- Select this position when you want the boiler to respond to a heating and hot water request from the time-clock programmer
Heating temperature selector
: move the selector clockwise to increase the heating outlet temperature, or counter-clockwise to reduce the temperature
(range: 40°C-80°C for standard central heating).
The automatic temperature control function (SARA) is set within the blank bullet points.
The display shows the temperature values.
Boiler at OFF/standby
- Select this position when you want the boiler to be switched off for short periods (days) or if the boiler requires to be reset
The display shows “- -”.
Pressure gauge
shows the current pressure of your heating system, the gauge should be set between 1 and 1.5 BAR. When the appliance is operating the gauge may rise or fall slightly, this is quite normal. The minimum permissible level for the safe and efficient operation of the appliance is 0.5
BAR. Should the pressure fall below 0.5 BAR, the boiler may lockout.
correct pressure value
DIGITAL DISPLAY
Fig. 2
Symbol/Icon Description
Displayed when heating mode is active
Displayed when hot water mode is active
Displayed when frost protection function is active
Displayed when hot-water pre-heat function is enabled. Flashes when functioning
Displayed if an alarm or fault has been detected
Displayed when low system pressure has been detected
Displayed when an external sensor is connected to the boiler
Displayed if an ignition fault has been detected
2. GETTING STARTED
2.1 BEFORE SWITCHING ON
Before switching the appliance on, please familiarise yourself with:
- how to isolate the appliance from the gas, water, and electricity supplies;
- how to check and top-up – if necessary – the system water pressure;
- the time clock or programmer (if fitted);
- any external thermostats and their functions;
- the appliance controls.
2.2 APPLIANCE CONTROLS (see fig. 1)
The appliance controls are situated on the lower front of the appliance. The appliance controls include:
- pressure gauge;
- appliance mode selector;
- temperature selectors.
NOTE
The appliance frost protection is active in all the boiler modes.
The
temperature selectors
can be used to vary the temperature of the water that circulates around your radiators and the water that flows from your hot water taps. The temperature range is adjustable between 40 o
C and 80 o
C for the central heating, and between 37 o
C and 60 o
C for the hot water.
The display normally shows the current time.
Refer to the main appliance status table for fault indicator and boiler status.
The integral digital time clock is used to switch the heating on and off at pre-determined intervals.
2.3 LIGHTING THE BOILER
Ensure the gas and electrical supply to the boiler are turned on.
Turn the mode selector switch to the
ON
position. When there is a request for heating or hot water via the time clock or programmer, the boiler will begin an ignition sequence. When the appliance reaches the CH set temperature, the burner will go off for a minimum period of approximately 3 minutes.
When the programmer/time clock or external thermostats heating request has been satisfied, the appliance will switch off automatically.
2.4 ADJUSTING THE HEATING TEMPERATURE
Rotate the temperature selector – clockwise to increase, counterclockwise to decrease – to the desired temperature setting. The temperature can be set from a minimum of 40°C to a maximum of 80°C (if standard CH mode is selected).
2.5 ADJUSTING THE HOT WATER TEMPERA-
TURE
Rotate the temperature selector – clockwise to increase, counter-clockwise to decrease – to the desired temperature setting. The temperature can be set from a minimum of 37°C to a maximum of 60°C. If the temperature at the outlet is still not sufficiently hot enough, it may be necessary to reduce the flow of water at the hot water outlet (tap).
NOTE
If the appliance fails to ignite during the ignition sequence, it will enter a lockout condition. Should this occur, please allow a period of at least two minutes before re-setting the appliance.
2.6 EXPLANATION OF FEATURES
Although the Vokèra has been designed for simplicity of use, it utilises the latest in boiler technology, enabling a host of functions to be carried out simultaneously.
2.7 AUTOMATIC TEMPERATURE CONTROL
The automatic temperature control function (SARA), permits the boiler (when the heating temperature selector is set within the blank bullet points to automatically adjust (raise) the heating.
The activation and the disable of the function is visualized on the display if the heating temperature is selected between 55°
-65°C.
3
3. HOW TO...
3.1 HOW TO TOP-UP THE SYSTEM PRESSURE
(fig. 1-2)
The system pressure must be checked periodically to ensure the correct operation of the boiler. The needle on the gauge should be reading between 1 and 1.5 BAR when the boiler is in an off position and has cooled to room temperature. If the pressure requires ‘topping-up’ use the following instructions as a guide.
- Locate the filling valve connections (usually beneath the boiler, see fig. 3).
- Attach the filling loop to both connections.
- Open the filling valve slowly until you hear water entering the system.
- Close the filling valve when the pressure gauge (on the boiler) reads between 1 and 1.5 BAR (see fig. 1).
- Remove the filling loop from the connections.
3.2 HOW TO RESET THE APPLIANCE
When the fault code is displayed, the appliance will require to be reset manually. Before resetting the boiler, check what action is required to be taken, using the information on the fault code table on next page. Allow a period of two minutes to elapse before rotating the mode selector knob across the position (see fig. 1).
IMPORTANT
If the appliance requires to be reset frequently, it may be indicative of a fault, please contact your installer or Vokèra Customer
Services for further advice.
3.3 HOW TO SHUT DOWN THE SYSTEM FOR
SHORT PERIODS
The system and boiler can be shut down for short periods by simply turning the time clock to the off position. It is also advisable to turn off the main water supply to the house.
3.4 HOW TO SHUT DOWN THE SYSTEM FOR
LONG PERIODS
If the house is to be left unoccupied for any length of time – especially during the winter – the system should be thoroughly drained of all water. The gas, water, and electricity supply to the house should also be turned off. For more detailed advice contact your installer.
3.5 HOW TO CARE FOR THE APPLIANCE
To clean the outer casing use only a clean damp cloth. Do not use any scourers or abrasive cleaners.
control valve temporary connection
Fig. 3 control valve flow/return pipe double check valve supply pipe
FAULT CODES
ALARM CODE CAUSE
_St AUTOSTOP
_CL CALL FOR SERVICE
A01
A02
A03
A04
Ignition failure
Limit thermostat fault
Fan tacho signal fault - air pressure switch
Insufficient system water pressure
ACTION
Call Landlord
Call Landlord
Reset; ensure gas supply is turned on, if problem persists, call engineer.
Reset; ensure sufficient water pressure, if problem persists, call engineer
Reset; if problem persists, call engineer
Reset; ensure sufficient water pressure, if problem persists, call engineer
A06
DHW thermistor fault Reset; if problem persists, call engineer
A07
A08
Primary (flow) thermistor fault
Primary (Return) thermistor fault - low temperature system thermostat fault
Reset; if problem persists, call engineer
Reset; if problem persists, call engineer
Flue thermistor over temperature or flue thermistor counter fault Reset; if problem persists, call engineer
A09
A11
P
False flame
Preheating function active
P
blinking
Preheating function running
Temporary
None
None
4. WHAT IF...
4.1 WHAT IF I SUSPECT A GAS LEAK
If you suspect a gas leak, turn off the gas supply at the gas meter and contact your installer or local gas supplier. If you require further advice please contact your nearest Vokèra office.
4.2 WHAT IF I HAVE FREQUENTLY TO TOP-UP
THE SYSTEM
If the system regularly requires topping-up, it may be indicative of a leak. Please contact your installer and ask him to inspect the system.
4.3 WHAT IF THE APPLIANCE IS DUE ITS AN-
NUAL SERVICE
Advice for tenants only
Your landlord should arrange for servicing.
4
Advice for homeowners
Please contact Vokèra Customer Service
(0844 3910999 (UK) or 056 7755057 (ROI)
if you would prefer a Vokèra service engineer or agent to service your appliance. Alternatively your local GAS SAFE registered engineer may be able to service the appliance for you.
4.4 - WHAT IF I NEED TO CALL AN ENGINEER
If you think your boiler may have developed a fault, please contact your installer or Vokèra Customer Services
(0844 3910999 (UK) or 056 7755057 (ROI)
have all your details to hand including full address and postcode, relevant contact numbers, and your completed appliance log book.
6
5
8
7
4
3
15
14
13
10
9
12
11
INSTALLATION AND SERVICING INSTRUCTIONS
INTRODUCTION
All installers are asked to follow the Benchmark Scheme by adhering to the Code of Practise, which can be obtained from www.centralheating.co.uk.
Unica
comprises a range of high-efficiency combination The boilers with outputs to DHW of 28kW and 32kW respectively.
These appliances – by design – incorporate electronic ignition, circulating pump, expansion vessel, safety valve, pressure gauge and automatic by-pass.
Unica
range is produced as room sealed, category II2H3P The appliances, suitable for internal wall mounting applications only.
Each appliance is provided with a fan powered flue outlet with an annular co-axial combustion air intake that can be rotated
– horizontally – through 360 degrees for various horizontal or
Unica
can also be used with the vertical applications. The
Vokèra twin flue system.
The
Unica
is approved for use with C13 & C33 type flue applications. These appliances are designed for use with a sealed system only; consequently they are not intended for use on open vented systems. This booklet is an integral part of the appliance. It is therefore necessary to ensure that the booklet is handed to the person responsible for the property in which the appliance is located/installed. A replacement copy can be obtained from the Vokèra website - www.vokera.co.uk.
Unica
boiler complies with basic requirements of the following
Directives:
- Regulation (EU) 2016/426;
- Yield directive: Article 7(2) and Annex III of directive 92/42/
EEC;
- Electromagnetic compatibility directive 2014/30/EU;
- Low-voltage directive 2014/35/EU;
- Directive 2009/125/EC Ecodesign for energy-using appliances;
- Regulation (EU) 2017/1369 Energy labeling;
- Delegated Regulation (EU) No. 811/2013;
- Delegated Regulation (EU) No. 813/2013;
- Delegated Regulation (EU) No. 814/2013.
At the end of its life, the product should be not be disposed of as solid urban waste, but rather it should be handed over to a differentiated waste collection centre.
2
1
Fig. 4
16 17
R F G O I
18
29
30
31
26
27
28
32
24
25
22
23
19
20
21
33
General layout
1 Three porte valve actuator
2 Drain valve
3 Pressure switch
4 Safety valve
5 Pump
6 Bottom auto air vent (AAV)
7 Condense trap
8 Return thermistor (NTC)
9 Air pressure switch
10 Vacuum detection pipe
11 Degassing hose
12 Sensing Electrode
13 High limit thermostat
14 Flow thermistor (NTC)
15 Top AAV+De-aerator
16 Flue gas analysis test point
17 Flue outlet & air intake
18 Ignition transformer
19 Flues thermistor (NTC)
20 Spark Electrode
21 Burner
22 Main heat exchanger
23 Conveyor
24 Fan assembly
25 Mixer
26 Air intake pipe
27 Expansion vessel
28 Atmospheric connection tube
29 Domestic hot water sensor
30 Domestic hot water heat exchanger
31 Condense trap
32 Gas valve
33 DHW flow meter
R Heating return connection
F Heating flow connection
G Gas connection
O Hot water outlet
I Cold water inlet
5
SECTION 1 - DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
• A fully integrated electronic control board featuring electronic temperature control, anti-cycle control, pump over-run, selfdiagnostic fault indicator, full air/gas modulation
• Aluminium heat exchanger
• Electronic ignition with flame supervision
• Integral high-head pump
• Fan
• Expansion vessel
• Water pressure switch
• Flue sensor
• Pressure gauge
• Safety valve
1.2 MODE OF OPERATION (at rest)
When the appliance is at rest and there are no requests for heating or hot water, the following functions are active:
• frost-protection system – the frost-protection system protects the appliance against the risk of frost damage both for CH and DHW. For CH line, if the main temperature falls to 5°C, the appliance will function on minimum power until the temperature on main reaches 35°C.
Moreover if the DHW temperature falls to 5°C, the appliance will function on minimum power until the temperature on main reaches 55°C.
• anti-block function – the anti-block function enables the pump and divertor valve actuator to be energised for short periods, when the appliance has been inactive for more than 24-hours.
1.3 MODE OF OPERATION (Heating)
When there is a request for heat via the time clock and/or any external control, the pump and fan are started, the fan speed will modulate until the correct signal voltage is received at the control PCB. At this point an ignition sequence is enabled.
Ignition is sensed by the electronic circuit to ensure flame stability at the burner. Once successful ignition has been achieved, the electronic circuitry increases the gas rate to 75% for a period of
15 minutes. Thereafter, the boiler’s output will either be increase to maximum or modulate to suit the set requirement. When the appliance reaches the desired temperature the burner will shut down and the boiler will perform a three-minute anti-cycle
(timer delay).
When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appliance.
1.4 MODE OF OPERATION (Hot water)
When there is a request for DHW via a hot water outlet or tap, the pump and fan are started, the fan speed will modulate until the correct signal voltage is received at the control PCB. At this point an ignition sequence is enabled.
Ignition is sensed by the electronic circuit to ensure flame stability at the burner. Once successful ignition has been achieved, the electronic circuitry increases the gas rate to maximum or will modulate output to stabilise the temperature.
In the event of the appliance exceeding the desired temperature
(set point) the burner will shut down until the temperature drops.
When the request for DHW has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat within the appliance.
1.5 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by:
• a water pressure switch that monitors system water pressure and will de-activate the pump, fan, and burner should the system water pressure drop below the rated tolerance;
• fan speed sensor to ensure safe operation of the burner;
• a high limit thermostat that over-rides the temperature control circuit to prevent or interrupt the operation of the burner;
• flame sensor that will shut down the burner when no flame signal is detected;
• flue sensor;
• a safety valve which releases excess pressure from the primary circuit.
Expansion vessel
Pump
Fig. 5
Return temperature sensor
Diverter valve
Automatic by-pass
Safety valve
Bottom
AAV
Pressure switch
CH return
Drain valve
CH flow
DHW non return valve
DHW heat exchanger
Top AAV
Flow temperature sensor
Main heat exchanger
DHW temperature sensor
Flow regulator
DHW outlet
DHW inlet
DHW flow switch
6
Minimum heat output (kW) 60/80°C
Maximum heat output (kW) 30/50°C
Minimum heat output (kW) 30/50°C
Minimum working pressure
Maximum working pressure
Minimum flow rate
2.2 Domestic Hot Water
Heat input (kW)
Flow Rate: ΔT35°C
Maximum inlet pressure
Minimum inlet pressure
Minimum flow rate
2.3 Gas Pressures
Inlet pressure (G20)
Heating maximum gas rate (m
3
/hr)
DHW maximum gas rate (m
3
/hr)
Minimum gas rate (m
3
/hr)
Injector size (mm)
2.4 Expansion Vessel
Capacity
Maximum system volume
Pre-charge pressure
2.5 Dimensions
Height (mm)
Width (mm)
Depth (mm)
Dry weight (kg)
2.6 Clearances
Sides
Top
Bottom
Front
2.7 Connections
Flow & return
Gas
DHW hot & cold
Safety valve
Condense
2.8 Electrical
Power consumption - maximum heating power (Watts)
Power consumption maximum dhw power (Watts)
Pump power comsuption (1.000 l/h) (Watts)
Voltage (V/Hz)
Internal fuse
External fuse
2.9 Flue Details (concentric 60-100)
Maximum horizontal flue length (60/100mm)
Maximum vertical flue length (60/100mm)
2.9A Flue Details (concentric 80-125)
Maximum horizontal flue length (80/125mm)
Maximum vertical flue length (80/125mm)
2.9B Flue Details (twin pipes)
Maximum horizontal flue length (80mm/80mm)
Maximum vertical flue length (80mm/80mm)
2.10 Efficiency
SEDBUK (%) 2005
2.11 Emissions
CO2 @ maximum output (%)
CO2 @ minimum output (%)
CO @ maximum output (ppm)
CO @ minimum output (ppm)
Nox rating
SECTION 2 - TECHNICAL DATA
2.1 Central Heating
Heat input (kW)
Maximum heat output (kW) 60/80°C
G20
2.76
3.00
Unica i28
20.00
19.62
21.44
Unica i28
28.00
11.5
Unica i28
G31
3.95
4.20
2.12
2.96
0.30
4.70 flap side - 4.20 free side
G20
3.16
Unica i32
25.00
24.58
G31
4.45
26.70
4,74 3,44
0.25-0.45 bar
2.5 bar
300 l/h
Unica i32
32.00
13.1
6 bar
0,2 bar
2 l/min
Unica i32
20.0 mbar
2.64
3.38
0.34
4.30 flap side - 4.20 free side
Unica i28 Unica i32
8 litres
76 litres
1 bar
Unica i28 Unica i32
780
400
358
39
Unica i28
42
Unica i32
12mm
150mm from casing or 25mm above flue elbow (whichever is applicable)
150mm
600mm
Unica i28 Unica i32
22mm
15mm
15mm
15mm
21mm
Unica i28
68
86
Unica i32
82
103
39
230/50
3.15A T (for PCB) - 3.15A F (for connections block)
3A
Unica i28
7.80m
Unica i32
7.80m
8.80m
Unica i28
20m
25m
Unica i28
50m/50m
50m/50m
Unica i28
90.30
Unica i28
9.0
9.0
150
10 class 6
8.80m
Unica i32
20m
25m
Unica i32
50m/50m
50m/50m
Unica i32
90.39
Unica i32
9.0
9.0
150
5 class 6
7
Unica i28
Seasonal space heating energy efficiency class
Parameter
Rated heat output
Symbol Value
Prated
For boiler space heaters and boiler combination heaters: useful heat output
At rated heat output and hightemperature regime (*)
P4 19.6
At 30% of rated heat output and low-temperature regime (**)
Auxiliary electricity consumption
At full load
At part load
In Stand-by mode
P1 elmax elmin
PSB
20
6.6
29.0
12.6
5.6
A kW
Water heating energy efficiency class
Unit Parameter
Seasonal space heating energy efficiency
A
Symbol Value Unit
For boiler space heaters and boiler combination heaters:
kW
useful efficiency
At rated heat output and hightemperature regime (*)
At 30% of rated heat output and kW low-temperature regime (**)
Other parameters
W Stand-by heat loss
W Pilot flame energy consumption
W Annual energy consumption
Sound power level, indoors
Emissions of nitrogen oxides
ηs
η4
η1
Pstby
Pign
QHE
LWA
NOx
93
88.6
98.7
%
%
%
26.0
-
40
51
W
W
GJ dB
29 mg/kWh
For combination heaters:
Declared load profile
Daily electricity consumption
Annual electricity consumption
Qelec
AEC
XL Water heating energy efficiency
0.149
kWh Daily fuel consumption
33 kWh Annual fuel consumption
ηwh 85 %
Qfuel 22.827
kWh
AFC 17 GJ
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).
Unica i 32
Seasonal space heating energy efficiency class
Parameter
Rated heat output
Symbol Value
Prated
For boiler space heaters and boiler combination heaters: useful heat output
At rated heat output and hightemperature regime (*)
P4 24.6
At 30% of rated heat output and low-temperature regime (**)
Auxiliary electricity consumption
At full load
At part load
In Stand-by mode
P1 elmax elmin
PSB
25
8.2
43.0
16.8
5.6
A kW
Water heating energy efficiency class
Unit Parameter
Seasonal space heating energy efficiency
A
Symbol Value Unit
For boiler space heaters and boiler combination heaters:
kW
useful efficiency
At rated heat output and hightemperature regime (*)
At 30% of rated heat output and kW low-temperature regime (**)
Other parameters
W Stand-by heat loss
W Pilot flame energy consumption
W Annual energy consumption
Sound power level, indoors
Emissions of nitrogen oxides
ηs
η4
η1
Pstby
Pign
QHE
LWA
NOx
94
88.5
99.0
%
%
%
29.0
-
47
53
W
W
GJ dB
35 mg/kWh
For combination heaters:
Declared load profile
Daily electricity consumption
Annual electricity consumption
Qelec
AEC
XL Water heating energy efficiency
0.176
kWh Daily fuel consumption
39 kWh Annual fuel consumption
ηwh 84 %
Qfuel 23.137
kWh
AFC 18 GJ
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).
8
2.12 PUMP DUTY
Fig. 6 shows the flow-rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph, apply only the pressure loss of the system.
600
550
500
450
400
350
300
250
200
150
100
50
0
0 100 200 300 400
PWM area
500 600
Flow rate (l/h)
700 800 900 1000 1100 1200
Fig. 6
Fig. 7
Key Location
I
J
K
L
M
N
P
Q
A
B
C
D
E
F
G
H
R
S
T
V
W
Below an opening (window, air-brick, etc.)
Above an opening (window, air-brick, etc.)
To the side of an opening (window, air-brick, etc.)
Below gutter, drain-pipe, etc.
Below eaves
Below balcony, car-port roof, etc.
To the side of a soil/drain-pipe, etc.
From internal/external corner
Above ground, roof, or balcony level
From a surface or boundary facing the terminal
From a terminal facing a terminal
From an opening in the car-port into the building
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
From a structure to the side of the vertical terminal
From the top of the vertical terminal to the roof flashing
To the side of a boundary
To the side of an opening or window on a pitched roof
Below an opening or window on a pitched roof
From a vertical terminal to an adjacent opening (window, air-brick, etc.)
From a vertical terminal to an adjacent vertical terminal
Minimum distance
300 mm
300 mm
300 mm
25 mm
25 mm
25 mm
25 mm (60mm for 80/125 - 5” flue)
25 mm (60mm for 80/125 - 5” flue)
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
300 mm
As determined by the fixed collar of the vertical terminal
300 mm
600 mm
2000 mm
(call Vokera technical for advice)
300 mm (only if both terminals are the same height)
9
SECTION 3 - GENERAL REQUIREMENTS (UK)
This appliance must be installed by a competent person in accordance with the Gas Safety (Installation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the Gas Safety (Installation & Use)
Regulations, the local building regulations, the current I.E.E. wiring regulations, the bylaws of the local water authority, the
Building Standards (Scotland) Regulation and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant requirements of the local authority and the relevant recommendations of the following British Standard Codes of Practice.
ATTENTION
The use of PPE (Personal Protective Equipment) such as but not limited to gloves, mask, safety glasses, etc. is strongly recommended whenever carrying out the installation, repair, or maintenance of this appliance – please pay particular attention to:
• Sharp edges that may be encountered when:- handling or lifting the appliance, removing parts, etc. during installation and maintenance
• Airborne particles that may be released and/or disturbed when cleaning or removing components during maintenance
• Water treatment chemicals that could have been added to the system water may spill from the appliance and or components during maintenance
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3.4 FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 7). In cold and/or humid weather, water vapour will condense on leaving the terminal; the effect of such pluming must be considered. If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0.5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3.5 AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply. When installed in a cupboard or compartment, ventilation for cooling purposes is also not required.
Please refer to an appropriate Health and Safety document such as HSE L23 (UK) or S.I. 299 (Ireland), for more detailed advice on safe working practices and procedures.
3.6 WATER CIRCULATION
Detailed recommendations are given in BS 5449 Part 1 and
BS 6798. The following notes are for general guidance only.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations, and in Scotland, the electrical provisions of the Building Regulations, with respect to the installation of the appliance in a room or internal space containing a bath or shower. When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
3.6.1 PIPEWORK
It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular attention should be paid to pipes passing through ventilated areas such as under floors, loft space and void areas.
BS 5440 PART 1 FLUES
BS 5440 PART 2 FLUES & VENTILATION
BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS
BS 5546
BS 6798
BS 6891
INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
LOW PRESSURE INSTALLATION PIPES
BS 7074 PART 1 APPLICATION, SELECTION AND INSTALLATION OF EXPANSION VESSELS AND ANCILLARY
EQUIPMENT FOR SEALED WATER SYSTEMS
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance. Where the installation of the appliance will be in an unusual location special procedures may be necessary, BS
6798 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cupboard may be utilised provided that it is modified to suit. Details of essential features of compartment/cupboard design including airing cupboard installations are given in BS 6798. This appliance is not suitable for external installation.
3.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an external by-pass, however the design of the system should be such that it prevents boiler
‘cycling’.
3.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. The drain cocks must be manufactured in accordance with BS 2879.
3.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
3.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with BS 6891.
Pipe work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for tightness in accordance with BS6891.
3.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 8 litres of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.18).
10
3.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. directly from the mains supply, should be provided (see fig. 8). This method of filling complies with the current Water Supply (Water Fittings) Regulations 1999 and
Water Bylaws 2000 (Scotland). If an alternative location is preferred, it should be connected as detailed in fig. 8.
3.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least
5 metres above the boiler (see fig. 9).
The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
3.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar.
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch fused spur with a contact separation of at least 3,5mm (3° high-voltage category). The switch must only supply the appliance and its corresponding controls, i.e. time clock, room thermostat, etc. Alternatively an un-switched shuttered socket with a fused 3-pin plug both complying with
BS 1363 is acceptable.
3.8 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combustible material, there is no requirement for a sheet of fireproof material to protect the wall.
3.9 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers publication (IGE/UP/7) ‘Guide for Gas Installations in Timber
Frame Buildings’.
3.10 INHIBITORS
Vokèra recommend that an inhibitor - suitable for use with aluminium heat exchangers - is used to protect the boiler and system from the effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the manufacturers instructions*.
*Water treatment of the complete heating system - including the boiler - should be carried out in accordance with BS 7593 and the Domestic Water Treatment Association’s (DWTA) code of practice.
3.11 SHOWERS
If the appliance is intended for use with a shower, the shower must be thermostatically controlled and be suitable for use with a combination boiler.
control valve temporary connection control valve
Fig. 8 flow/return pipe
Automatic air-vent
Fig. 9 double check valve
Make-up vessel or tank
Non-return valve
Stopcock
Heating return supply pipe
SECTION 3A - GENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent person in accordance with and defined by, the Standard Specification
(Domestic Gas Installations) Declaration (I.S. 813).
ATTENTION
The use of PPE (Personal Protective Equipment) such as but not limited to gloves, mask, safety glasses, etc. is strongly recommended whenever carrying out the installation, repair, or maintenance of this appliance – please pay particular attention to:
• Sharp edges that may be encountered when:- handling or lifting the appliance, removing parts, etc. during installation and maintenance
• Airborne particles that may be released and/or disturbed when cleaning or removing components during maintenance
• Water treatment chemicals that could have been added to the system water may spill from the appliance and or components during maintenance
Please refer to an appropriate Health and Safety document such as HSE L23 (UK) or S.I. 299 (Ireland), for more detailed advice on safe working practices and procedures.
3A.1 RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant requirements of the local building regulations, the current ETCI National Rules for Electrical Installations and the bylaws of the local water undertaking.
It should be in accordance also with any relevant requirements of the local and/or district authority.
3A.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current ETCI National Rules for Electrical Installations, and
I.S. 813, Annex K.
When an appliance is installed in a room or internal space containing a bath or shower, the appliance or any control pertaining to it must not be within reach of a person using the bath or shower.
The location chosen for the appliance must permit the provision of a safe and satisfactory flue and termination. The location must also permit an adequate air supply for combustion purposes and an adequate space for servicing and air circulation around the appliance.
11
Where the installation of the appliance will be in an unusual location special procedures may be necessary, refer to I.S. 813 for detailed guidance on this aspect.
A compartment used to enclose the appliance must be designed and constructed specifically for this purpose. An existing compartment/cupboard may be utilised provided that it is modified to suit.
This appliance is not suitable for external installation.
3A.3 GAS SUPPLY
The gas meter – as supplied by the gas supplier – must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves. Installation pipes must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must be of adequate size. Pipes of a smaller size than the appliance gas inlet connection must not be used. The installation must be tested for tightness in accordance with I.S. 813.
If the gas supply serves more than one appliance, it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time.
3A.4 FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see I.S. 813).
In cold and/or humid weather, water vapour will condense on leaving the terminal; the effect of such pluming must be considered.
If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material.
The guard must be fitted centrally over the terminal. Refer to
I.S. 813, when the terminal is 0.5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves.
3A.5 AIR SUPPLY
The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation for cooling purposes is also not required.
3A.6 WATER CIRCULATION
Specific recommendations are given in I.S. 813. The following notes are for general guidance only.
3A.6.1 PIPEWORK
It is recommended that copper tubing be used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular attention should be paid to pipes passing through ventilated areas such as under floors, loft space and void areas.
3A.6.2 AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass, consequently there is no requirement for an external by-pass, however the design of the system should be such that it prevents boiler
‘cycling’.
3A.6.3 DRAIN COCKS
These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance.
3A.6.4 AIR RELEASE POINTS
These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system.
12
3A.6.5 EXPANSION VESSEL
The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. It can accept up to 8 litres of expansion from within the system, generally this is sufficient, however if the system has an unusually high water content, it may be necessary to provide additional expansion capacity (see 6.18).
3A.6.6 FILLING POINT
A method for initial filling of the system and replacing water lost during servicing etc. should be provided (see fig. 8). You should ensure this method of filling complies with the local water authority regulations.
3A.6.7 LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 9). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible.
3A.6.8 FREQUENT FILLING
Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar.
3A.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse. The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch fuse spur with a contact separation of at least 3,5 mm (3° high-voltage category). The switch must only supply the appliance and its corresponding controls, i.e. time clock, room thermostat, etc.
3A.8 MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of combustible material, there is no requirement for a sheet of fireproof material to protect the wall.
3A.9 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with I.S. 813 and local Building
Regulations.
The Institute of Gas Engineers publication (IGE/UP/7) ‘Guide for Gas Installations in Timber Frame Buildings’ gives specific advice on this type of installation.
3A.10 INHIBITORS
Vokèra recommend that an inhibitor - suitable for use with aluminium heat exchangers - is used to protect the boiler and system from the effects of corrosion and/or electrolytic action.
The inhibitor must be administered in strict accordance with the manufacturers instructions*.
*Water treatment of the complete heating system - including the boiler - should be carried out in accordance with I.S. 813 and the Domestic Water Treatment Association’s (DWTA) code of practice.
3A.11 SHOWERS
If the appliance is intended for use with a shower, the shower must be thermostatically controlled and be suitable for use with a combination boiler.
3A.12 DECLARATION OF CONFORMITY
A Declaration of Conformity (as defined in I.S. 813) must be provided on completion of the installation.
A copy of the declaration must be given to the responsible person and also to the gas supplier if required.
SECTION 4 - INSTALLATION
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
4.1 DELIVERY
Due to the weight of the appliance it may be necessary for two people to lift and attach the appliance to its mounting. The appliance is contained within a heavy-duty cardboard carton.
Lay the carton on the floor with the writing the correct way up.
4.2 CONTENTS
Contained within the carton is:
• the boiler
• the wall bracket
• carton template
• an accessories pack containing appliance service connections and washers
• the instruction pack containing the installation, servicing & user instructions, guarantee registration card and a 3-amp fuse.
4.3 UNPACKING
At the top of the carton pull both sides open – do not use a knife – unfold the rest of the carton from around the appliance, carefully remove all protective packaging from the appliance and lay the accessories etc. to one side. Protective gloves should be used to lift the appliance, the appliance back-frame should be used for lifting points.
Fig. 11
Fig. 12
The appliance should be mounted on a smooth, vertical, noncombustible surface, which must be capable of supporting the full weight of the appliance. Care should be exercised when determining the position of the appliance with respect to hidden obstructions such as pipes, cables, etc.
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wallmounting bracket (see fig. 10) and flue-hole (if applicable).
4.4.1 FITTING THE PRE-FIXING JIG
When the position of the appliance has been decided – using the template supplied – carefully mark the position of the wall mounting bracket/pre-fixing jig (see fig. 10) and flue-hole (if applicable). Once the pre-fixing jig is in place, the pipework can now be fitted. Fit the pipework to sit within the pre-formed guides of the fixing jig and to the required length for ether a standard wall or standoff bracket (see fig 10).
Once the pipes have been fitted, the jig can now be removed
(see fig 13).
Fig. 13
2
Fig. 10
4
2
4
2 2 2 2
4
4 4 4 without
rear spacer kit use position 2
with
rear spacer kit use position 4
Fig. 14
13
4.5 FITTING THE FLUE
The top flue outlet permits both horizontal and vertical flue applications to be considered, alternatively, the Vokèra twin flue system can be utilised if longer flue runs are required.
4.5.1 CONCENTRIC HORIZONTAL FLUE
(For concentric vertical flue, see 4.5.2).
(For twin flue applications, see 4.5.3).
The appliance can be used with either the Vokèra condensing
60/100mm concentric flue system or the optional 80/125mm concentric flue system.
NOTE
These instructions relate
only
to the Vokèra condensing
60/100mm concentric flue system. For specific details on the installation of the 80/125mm concentric flue system please refer to the instructions supplied. The appliance flue outlet elbow can be rotated through 360º on its vertical axis. In addition the flue may be extended from the outlet elbow in the horizontal plane
(see 2.9). A reduction must also be made to the maximum length
(see table below) when additional bends are used.
Reduction for additional bends
Bend Reduction in maximum flue length for each bend
45° bend 1.0 metre (60/100) - 1.0 metre (80/125)
90° bend 1.0 metre (60/100) - 1.0 metre (80/125)
Horizontal flue terminals and accessories
Part No.
Description
29450120 Horizontal flue kit
29450121 Telescopic flue kit
522
Plume management kit
29450123 90-degree bend
29450124 45-degree bends (pair)
29450125 500mm extension
29450126 1000mm extension
29450127 2000m extension
29450128 Telescopic extension
529 Wall bracket pack (5)
Length
900 mm
455/630 mm
1370 mm
N/A
N/A
500 mm
1000 mm
2000 mm
372/519 mm
208mm
Using the template provided, mark and drill a 125mm hole for the passage of the flue pipe. The hole should be drilled to ensure any condense fluid that forms, is allowed to drain back to the appliance (see fig. 12-14). The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, mount the appliance onto the bracket.
Fig. 15
Outer clamps
FITTING THE HORIZONTAL FLUE KIT
Carefully measure the distance from the centre of the appliance flue outlet to the edge of the finished outside wall (dimension
X). Add 65mm to dimension X to give you Dimension Y (see fig 16). Measure dimension Y from the terminal end of the concentric flue pipe and cut off the excess ensuring any burrs are removed. Pass the concentric flue pipe through the previously drilled hole. Fit the flue bend to the boiler flue outlet and insert the concentric flue pipe into the flue bend ensuring the correct seal is made.
Using the clamp, gasket, and screws supplied, secure the flue bend to the appliance flue spigot.
NOTE
Fit the internal (white) trim to the flue assembly prior to connecting the flue pipe to the bend.
You must ensure that the entire flue system is properly supported and connected. Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The exterior trim can now be fitted.
14
Terminal or extension
Attach the rear flue terminal to the appliance (using the previously retained screws) and fix the telescopic terminal to the correct length (wall thickness) ensuring that the terminal will protrude through the wall by the correct distance. At this point, lift the appliance and carefully insert the terminal into and through the wall, ensuring that the holes in the appliance back frame are aligned with the studs on the wall bracket.
Seal the top flue outlet of the boiler with the blanking plate provided with the rear flue kit (Fig. 19).
218
Fig. 16
EXTENDING THE FLUE
Connect the bend – supplied with the terminal kit – to the top of the boiler using clamp (supplied) see fig. 15. The additional bends & extensions have push-fit connections, care should be taken to ensure that the correct seal is made when assembling the flue system. Connect the required number of flue extensions or bends (up to the maximum equivalent flue length) to the flue terminal (see fig. 15-17).
The flue system should have a minimum of 1º; maximum of 3º rise from the boiler to outside, to ensure any condense fluid that forms, is allowed to drain back to the appliance.
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension. Remove any burrs, and check that all seals are located properly. You must ensure that the entire flue system is properly supported and connected. Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
Fig.18
Fig.19
Fig.20
Fig. 17
4.5.1.2 FITTING THE REAR FLUE (fi g. 18) (rear flue outlet only)
Using the template provided, mark and drill a 125mm hole for the passage of the flue pipe, see fig 12. The hole should be drilled LEVEL to ensure any condense fluid that forms, is allowed to drain back to the appliance. The fixing holes for the wall mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely. Once the bracket has been secured to the wall, remove the blanking plate from the rear of the boiler (Fig.20).
NOTE The inner 60mm pipe of the rear flue terminal mu
st be cut by 12mm at the point indicated (fig.18 pos. A).
Using the screws and washers provided, secure the appliance onto the wall bracket and tighten with a suitable spanner.
Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The exterior wall trim can now be fitted.
Part No.
Description
29450133 Rear flue terminal
Length
825 mm
15
4.5.2 CONCENTRIC VERTICAL FLUE
The appliance can be used with either the Vokèra condensing
60/100mm concentric flue system or the optional 80/125mm concentric flue system.
NOTE
These instructions relate
only
to the Vokèra condensing
60/100mm concentric flue system. For specific details on the installation of the 80/125mm concentric flue system please refer to the instructions supplied.
The vertical flue terminal can be connected directly to the appliance flue outlet. Alternatively, an extension or bend can be connected to the appliance flue outlet if desired, however if additional bends are fitted, a reduction must be made to the maximum flue length (see table below).
Bend Reduction in maximum flue length for each bend
45° bend 1.0 metre (60/100) - 1.0 metre (80/125)
90° bend 1.0 metre (60/100) - 1.0 metre (80/125)
Vertical flue terminal and accessories
Part No.
Description
29450120 Horizontal flue kit
29450122 Vertical flue terminal
531 Pitched roof flashing plate
532 Flat roof flashing plate
29450123 90-degree bend
29450124 45-degree bends (pair)
29450125 500mm extension
29450126 1000mm extension
29450127 2000m extension
29450128 Telescopic extension
529 Wall bracket pack (5)
Length
900 mm
1000 mm
N/A
N/A
N/A
N/A
500 mm
1000 mm
2000 mm
372/519 mm
208mm
Using the dimensions given in fig. 21 as a reference, mark and cut a 125mm hole in the ceiling and/or roof.
Fig. 21
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an ‘appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall, mount the appliance onto the bracket.
16
“X”
12/15/20HE = 202mm
25/30/35HE = 218mm
130mm
IMPORTANT
The vertical flue terminal is 1.0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
Connect the vertical flue assembly to the boiler flue spigot using the 100mm clip, gasket & screws (supplied), ensuring the correct seal is made. The flue support bracket (supplied with the vertical flue kit) can now be fitted.
If the vertical flue requires extension/s or additional bend/s, connect the required number of flue extensions or bends (up to the maximum equivalent flue length) between the boiler and vertical flue assembly (see fig. 17).
Ensure that any horizontal sections of the flue system have a minimum 1º; maximum 3º fall back to the boiler (1º = 17mm per 1000mm).
NOTE
When cutting an extension to the required length, you must ensure that the excess is cut from the plain end of the extension. Remove any burrs, and check that any seals are located properly.
You must ensure that the entire flue system is properly supported and connected.
4.5.3 TWIN FLUE SYSTEM
The Vokèra twin flue system enables greater flue distances to be achieved than that of a concentric flue system. It can be used for horizontal or vertical applications, however the twin flue system must be converted to the dedicated concentric flue kit for termination. It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions.
GUIDANCE NOTES ON TWIN FLUE INSTALLATION
• The flue must have a have a minimum 1º; maximum 3º (1º =
17mm per 1000mm) fall back to the appliance to allow any condensate that may form in the flue system to drain via the condensate drain. Consideration must also be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal.
• Ensure that the entire flue system is adequately supported, use at least one bracket for each extension.
• As the exhaust outlet pipe can reach very high temperatures it must be protected to prevent persons touching the hot surface.
• The condensate drain pipe must be connected in accordance with building regulations
Reduction for bends
Bend Reduction in maximum flue length for each bend
45° bend 1.0 metre
90° bend 1.0 metre
Twin flue accessories
Part No.
Description
0225805 Horizontal flue terminal
0225810 Vertical flue terminal
359 Twin adapter kit
531
532
Pitched roof flashing plate
Flat roof flashing plate
0225815 Condensate drain kit
0225820 0.25m extension (pair)
0225825 0.5m extension (pair)
0225830 1.0m extension (pair)
0225835 2.0m extension (pair)
0225840 45º bend (pair)
0225845 90º bend (pair)
0225850 Twin bracket (5)
0225855 Single bracket (5)
Length
1.0 metre
1.0 metre
N/A
N/A
N/A
N/A
250mm
500 mm
1000 mm
2000 mm
N/A
N/A
N/A
N/A
MOUNTING THE BOILER
The fixing holes for the wall-mounting bracket should now be drilled and plugged, an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely.
Once the bracket has been secured to the wall, mount the appliance onto the bracket.
INSTALLATION OF TWIN ADAPTOR KIT (fig. 22 & 23)
• Insert the exhaust connection manifold (A) onto the appliance flue outlet.
• Remove the blanking plate (located to the left of the appliance flue outlet) and – using the same screws – install the air inlet plate (B).
• Using the hole in the exhaust connection manifold as a guide, drill a 3mm hole in the appliance flue spigot and secure the exhaust manifold connection to the flue spigot using the screw provided (C).
• Using the two holes in the air inlet plate as a guide, drill a
3mm hole in each and secure the air inlet pipe/bend using the screws provided.
The twin flue pipes extensions and accessories can now be installed by pushing together (the plain end of each extension or bend should be pushed approximately 50mm into the female socket of the previous piece).
Fig. 22
B
A
C
NOTE
Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing. The interior and exterior trim can now be fitted.
VERTICAL TERMINATION (fig. 25)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
• The vertical terminal is supplied with a built-in converter box and cannot be shortened.
• A 130mm hole is required for the passage of the concentric terminal through the ceiling and/or roof.
Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes.
Fit the appropriate flashing plate to the roof and insert the vertical flue terminal through the flashing plate from the outside, ensuring that the collar on the flue terminal fits over the flashing.
Push-fit the twin flue pipes onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter.
If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
• Before cutting twin flue pipes ensure allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
• You must ensure that the entire flue system is properly supported and connected.
• Ensure that any horizontal sections of pipe have a fall of between 1 & 3º towards the appliance (1º =17mm per
1000mm).
1-deg = 17mm
Fig. 24
Fig. 23
HORIZONTAL TERMINATION (fig. 24)
The twin flue system must be converted to the dedicated concentric flue kit for termination.
• The horizontal terminal is supplied with a built-in converter box and cannot be shortened.
• A 130mm hole is required for the passage of the concentric terminal through the wall.
• The air inlet pipe must always be level with or below, that of the exhaust pipe.
Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes.
Mark and drill a level 130mm hole for the passage of the horizontal flue terminal. Insert the terminal assembly into the flue hole.
Push-fit the twin flue pipes onto the concentric to twin converter box ensuring that the exhaust pipe connects to the exhaust connection on the concentric to twin converter.
If necessary cut the plain ends (male) of the twin flue pipes to allow connection to the concentric to twin converter.
NOTE
Before cutting twin flue pipes ensure allowances have been made for connection onto the previous piece and onto the concentric to twin converter. The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter.
Fig. 25
17
4.6 CONNECTING THE GAS AND WATER
The appliance is supplied with an accessory pack that includes service valves. The service valves are of the compression type.
The accessory pack contains sealing washers’ etc, for use with the service valves. When connecting pipe work to the valves, tighten the compression end first then insert the sealing washers before tightening the valve to the appliance.
NOTE
It will be necessary to hold the valve with one spanner whilst tightening with another.
4.6.1 GAS (fig. 26)
The appliance is supplied with a 15mm service valve, connect a 15mm pipe to the inlet of the valve and tighten both nuts.
NOTE
It will be necessary to calculate the diameter of the gas supply pipe to ensure the appliance has an adequate supply of gas.
4.6.2 FLOW & RETURN (fig. 26)
The appliance is supplied with 22mm service valves for the flow and return connections, connect a 22mm pipe to the inlet of each valve and tighten both nuts.
NOTE
Depending on system requirements, it may necessary to increase the size of the flow & return pipe work after the service valve connections.
The appliance is supplied with a 15mm combined stopcock and double check-valve, connect a 15mm pipe to the inlet of the stopcock and tighten both nuts.
4.6.4 HOT WATER OUTLET (fig. 26)
The appliance is supplied with a 15mm outlet connection, connect a 15mm pipe to the outlet connection and tighten both nuts.
4.6.5 SAFETY VALVE (fig. 26)
Connect the safety valve connection pipe to the safety valve outlet and tighten. The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezing.
The discharge pipe must terminate in a position where any water
- possibly boiling - discharges safely without causing damage or injury, but is still visible.
4.6.6 CONDENSE PIPE
During normal operation the boiler produces condense which is collected in a trap located in the lower part of the boiler. A flexible pipe (condense outlet pipe) is connected to the outlet of the trap. The flexible pipe must be connected to a plastic waste pipe only. The plastic waste pipe must have a minimum of a 3º fall towards the drain. Any external run of pipe should be insulated to prevent the risk of freezing.
4.6.7 CONNECTING THE CONDENSATE OUTLET
Gently pull the condense outlet pipe down from its location inside the boiler until approximately 100mm protrudes from the underside of the boiler, care should be taken to ensure that the pipe connection to the trap remains secure. Connect a suitable plastic (not copper) pipe (no less than 21mm diameter) to the outlet pipe and ensure it discharges in accordance with local building regulations or other rules in force.
4.7 ELECTRICAL CONNECTIONS
The boiler is supplied with a 2-metre fly-lead. This lead can be used for connection to the electrical supply. Connect the fly-lead to a fused plug or fused isolator in the following way:
• brown wire to LIVE supply
• blue wire to NEUTRAL supply
• green/yellow to EARTH connection.
Insert the supplied 3-AMP fuse into the fused isolator or fused plug.
Should the fly-lead be unsuitable, refer to 4.7.3 for details on how to connect the electrical supply directly to the boiler.
The electrical supply must be as specified in section 3/3A.
A qualified electrician should connect the appliance to the electrical supply. If controls - external to the appliance - are required, a competent person must undertake the design of any external electrical circuits, please refer to section 8 for detailed instructions. ANY EXTERNAL CONTROL OR WIRING
MUST BE SERVED FROM THE SAME ISOLATOR AS THAT
OF THE APPLIANCE. The supply cable from the isolator to the appliance must be 3-core flexible sized 0.75mm to BS 6500 or equivalent. Wiring to the appliance must be rated for operation in contact with surfaces up to 90 ºC.
18
Fig. 26
C/H flow valve
Gas cock
Hot water outlet
Cold water inlet stopcock
Safety valve outlet
C/H return valve
4.7.1 CASING REMOVAL (fig. 27)
To gain internal access to the appliance you must first remove the casing, proceed as outlined below:
• locate and unscrew the 3-screws (A) that secure the outer
casing to the appliance lift the casing upward to disengage it from the top locating hooks and then remove
• store the casing and screws safely until required. Refit in the reverse order.
4.7.2 APPLIANCE TERMINAL BLOCK
The appliance terminal block is located on the rear of the control fascia. Remove the casing as described in 4.7.1. Gently pull the control panel forwards and down. Locate the terminal block cover (fig. 28).
NOTE
The appliance comes with a factory fitted link (‘TA’) to allow basic operation of the boiler via the mode selector switch.
If it is anticipated that external controls will be required please refer to the wiring diagrams in section 8 for more detailed information.
4.7.3 CONNECTING THE MAINS (230V) INPUT
Unhook and remove the terminal block cover (230V). Pass the cable through the cable anchorage point. Connect the supply cable wires (LIVE, NEUTRAL, & EARTH) to their corresponding terminals (L, N, & E) on the appliance – high voltage – terminal block. When connecting the EARTH wire, ensure that it’s left slightly longer that the others, this will prevent strain on the
EARTH wire should the cable become taut. Do not remove the link wire unless additional external controls are to be fitted (see section 8). The securing screw on the cable anchorage should now be tightened. This must be done before the terminal block cover is re-fitted in its position.
NOTE
It is the installer’s responsibility to ensure that the appliance is properly Earthed. Vokèra Ltd. cannot be held responsible for any damages or injuries caused as a result of incorrect Earth wiring.
Fig. 27
A
Fig. 28
SECTION 5 - COMMISSIONING
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
5.1 GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas meter, test for tightness and purge. Refer to BS 6891 (I.S. 813 in ROI) for specific instruction.
5.2 THE HEATING SYSTEM
The appliance contains components that may become damaged or rendered inoperable by oils and/or debris that are residual from the installation of the system, consequently it is essential that the system be flushed in accordance with the following instructions.
5.3 FILL THE CONDENSATE TRAP
The first time you turn the boiler on after a prolonged period of inactivity or for maintenance work, before using the appliance you must fill the siphon with water and make sure that the condensation is evacuated correctly.
Fill the condensation collection siphon pouring 1 litre of water into the boiler combustion-analysis outlet with the boiler off, and check that:
- the safety cut-off device is floating
- water is flowing correctly from the discharge pipe out of the boiler
- the condensate outlet connection line is watertight
If the condensate outlet circuit (siphon and pipes) is working correctly, the condensation level will not exceed the maximum.
Filling the siphon before using the appliance, and the use of a safety cut-off device inside the siphon, prevent exhaust gases from being released into the environment.
Repeat during standard and non-standard maintenance work.
MAX
5.4 INITIAL FILLING OF THE SYSTEM
Ensure both flow and return service valves are open, remove appliance casing as described in 4.7.1, identify the automatic air release valves (AAV) and loosen the dust cap/s by turning the cap anti-clockwise one full turn. Ensure all manual air release valves located on the heating system are closed. Connect the filling loop as shown in fig. 8, slowly proceed to fill the system by firstly opening the inlet valve connected to the flow pipe, and then turning the lever on the fill valve, to the open position. As water enters the system the pressure gauge will begin to rise.
Once the gauge has reached 1 BAR close both valves and begin venting all manual air release valves, starting at the lowest first.
It may be necessary to go back and top-up the pressure until the entire system has been filled. Inspect the system for water tightness, rectifying any leaks.
5.5 INITIAL FLUSHING OF THE SYSTEM
The whole of the heating system must be flushed both cold and hot as detailed in 5.8. Open all radiator or heating valves and the appliance flow & return service valve. Drain the boiler and system from the lowest points. Open the drain valve full bore to remove any installation debris from the boiler prior to lighting. Refill the boiler and heating system as described in 5.3.
5.6 PRE-OPERATION CHECKS
lowing checks must be carried out:
• ensure all gas service valves from the meter to the appliance are open and the supply pipe has been properly purged;
• ensure the proper electrical checks have been carried out,
(see 7.8) particularly continuity, polarity and resistance to earth;
• ensure the 3 AMP fuse – supplied with the appliance – has been fitted;
• ensure the system has been filled, vented and the pressure set to 1 BAR;
• ensure the flue system has been fitted properly and in accordance with the instructions;
• ensure all appliance service valves are open.
5.7 INITIAL LIGHTING
Ensure the electrical supply to the appliance is switched on.
Ensure any external controls are switched to an ‘ON’ position and are calling for heat. Move the selector switch to the ON position, the appliance will now operate as described in 1.2.
Should the appliance fail to ignite, refer to 5.6 and/or section 7
(mode of operation & fault finding).
The appliance is factory set so should require no additional adjustment once installed. However to satisfy the requirements of GSIUR 26/9 (I.S. 813 ROI), it will be necessary to gas rate the appliance using the gas meter that serves the appliance and carry out a combustion analysis check in accordance with
BS 7967 (UK) to ensure that correct combustion is occurring, see flow chart on page 38. Additionally, if the gas valve has been adjusted, replaced, or the appliance has been converted for use with another gas type, then it becomes necessary to carry out a combustion analysis check to ensure that correct combustion is occurring. If there are no means to carry out a combustion analysis check, then it will not be possible to complete the commissioning procedure.
Details on how to carry out the combustion analysis can be found in section 7.
IMPORTANT
It’s imperative that a sufficient dynamic – gas – pressure is maintained at all times. Should the dynamic gas pressure fall below an acceptable level, the appliance may malfunction or sustain damage.
5.9 FINAL FLUSHING OF THE HEATING SYSTEM
The system shall be flushed in accordance with BS 7593 (I.S.
813 ROI). Should a cleanser be used, it must be suitable for
Aluminium heat exchangers. It shall be from a reputable manufacturer and shall be administered in strict accordance with the manufacturers’ instructions and the DWTA code of practice.
NOTE
Chemicals used to cleanse the system and/or inhibit corrosion must be pH neutral, i.e. they should ensure that the level of the pH in the system water remains neutral. Premature failure of certain components can occur if the level of pH in the system water is out-with normal levels.
5.9.1 INHIBITORS
See Section 3 “General Requirements”.
5.10 SETTING THE FLOW OUTLET TEMPERATURE
The flow outlet temperature can be adjusted between 40 °C -
80 °C for standard CH system by using the Heating thermostat knob (see fig.1).
5.9.1 SETTING THE DHW OUTLET TEMPERATURE
The DHW outlet temperature can be adjusted between 37 °C
- 60 °C via the DHW thermostat knob (see fig.1).
5.11 SETTING THE SYSTEM DESIGN PRESSURE
The design pressure should be a minimum of 0.5 BAR and a maximum of 1.5 BAR. The actual reading should ideally be 1
BAR plus the equivalent height in metres (0.1 BAR = 1 metre) to the highest point in the system above the base of the appliance
(up to the maximum of 1.5 BAR total).
N.B.
The safety valve is set to lift at 3 BAR/30 metres/45 psig. To lower the system pressure to the required value, drain off some water from the appliance drain valve until the required figure registers on the pressure gauge (see fig. 1).
5.12 REGULATING THE CENTRAL HEATING
SYSTEM
Fully open all radiator and circuit valves and run the appliance for both heating and hot water until heated water is circulating.
If conditions are warm remove any thermostatic heads. Adjust radiator return valves and any branch circuit return valves until the individual return temperatures are correct and are approximately equal.
19
5.12.1 REGULATING THE DHW FLOW-RATE
The appliance is fitted with a flow rate restrictor that limits the maximum flow rate that can be drawn through the appliance.
The restrictor eliminates the need to manually adjust the DHW flow rate. However if it is felt necessary to further increase or decrease the available flow rate, spare restrictors are available from Vokèra spare parts.
The spare flow rate restrictors can be fitted to either increase or decrease the maximum flow rate.
5.12.2 FLOW-RATE RESTRICTOR
The boiler is supplied with the following flow restrictor.
9-litres
(Orange)
Spare
11-litres
(Beige)
Spare
Unica i28
10-litres
(Blue)
Fitted
Unica i32
12-litres
(Red)
Fitted
11-litres
(Beige)
Spare
13-litres
(Olive)
Spare
5.13 FINAL CHECKS
• ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS
VALVE ARE TIGHT AND CHECKED FOR TIGHTNESS.
• ENSURE THE APPLIANCE FLUE SYSTEM IS FITTED
CORRECTLY AND IS PROPERLY SECURED.
• ENSURE ALL PIPE WORK IS RE-CHECKED FOR TIGHTNESS.
• RE-FIT APPLIANCE CASING.
• COMPLETE BENCHMARK CHECKLIST.
FOR UK ONLY
Complete details of the boiler, controls, installation and commissioning in the Benchmark checklist at the back of this book. It is important that the Benchmark checklist is correctly completed and handed to the user. Failure to install and commission the appliance to the manufacturers instructions will invalidate the warranty.
5.14 INSTRUCTING THE USER
Hand over all documentation supplied with this appliance – including these instructions – and explain the importance of keeping them in a safe place. Explain to the user how to isolate the appliance from the gas, water and electricity supplies and the locations of all drain points. Show the user how to operate the appliance and any associated controls correctly. Show the user the location of the filling valve and how to top-up the system pressure correctly and show the location of all manual air release points. Explain to the user how to turn off the appliance for both long and short periods and advise on the necessary precautions to prevent frost damage.
Explain to the user that for continued safe and efficient operation, the appliance must be serviced annually by a competent person.
IMPORTANT
To validate the appliance warranty, it’s necessary to register the appliance details with us. The warranty can be registered in several ways:
• by completing the warranty registration card and posting to us using the envelope supplied
• online at: vokera.co.uk
• for UK residents by calling: 0870 607 0281.
• for ROI residents by calling: 056 6655057.
SECTION 6 - SERVICING INSTRUCTIONS
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
6.1 GENERAL
Once the appliance has been serviced, the benchmark Service
Record must be completed.
For UK only: It is important that the Benchmark Service Record is correctly completed and handed to the user. Failure to install and commission the appliance to the manufacturers instructions will invalidate the warranty.
To ensure the continued safe and efficient operation of the appliance, it is recommended that it is checked and serviced at regular intervals. To ensure correct and safe operation of the appliance, it is essential that any worn or failed component be replaced only with a
genuine Vokèra spare part
. It should be remembered that although certain generic components may look similar, they will be specific to an individual appliance or product range. Use of non-genuine Vokèra spare parts could invalidate your warranty and may pose a potential safety hazard. The frequency of servicing will depend upon the particular installation conditions, but in general, once per year should be sufficient. It is the law that any servicing work is carried out by competent person such as a Vokèra engineer, an approved service agent, British Gas, GAS SAFE registered personnel or other suitably qualified personnel. The following instructions apply to the appliance and its controls, but it should be remembered that the central heating and the domestic hot water systems would also require attention from time to time.
6.2 ROUTINE ANNUAL SERVICING
• Check the operation of the appliance and ensure it functions as described in section 7.
• Compare the performance of the appliance with its design specification. The cause of any noticeable deterioration should be identified and rectified without delay.
• Thoroughly inspect the appliance for signs of damage or deterioration especially the flue system and the electrical apparatus.
• Check and adjust – if necessary – all burner pressure settings
(see 7.4).
• Check and adjust – if necessary – the system design pressure (see 5.10).
• Carry out an analysis of the flue gases (see 7.3), and visually check the condition of the entire flue assembly.
• Compare the results with the appliance design specification.
Any deterioration in performance must be identified and rectified without delay.
• Check that the main heat exchanger is clean and free from any debris or obstruction.
• Check and clean – if necessary – the condense trap to ensure correct operation.
• Check that the atmospheric connection tube is clean and free from any debris or obstruction.
The flame side of the burner is made of state-of-the-art material.
Be particularly careful when handling, mounting or dismantling the burner and adjacent components (e.g. electrodes, insulation panelling etc.)
Avoid direct contact with any cleaning appliance (e.g. brushes, aspirators, blowers, etc.).
This component does not need any maintenance, please do not remove it from its housing, except where the O-ring may have to be replaced.
The manufacturer declines all responsibility in cases of damages due to failing to observe the above.
6.3 REPLACEMENT OF COMPONENTS
Although it is anticipated that this appliance will give years of reliable, trouble free service, the life span of components will be determined by factors such as operating conditions and usage.
Should the appliance develop a fault, the fault finding section will assist in determining which component is malfunctioning.
6.4 COMPONENT REMOVAL PROCEDURE
To remove a component, access to the interior of the appliance is essential. Isolate the appliance from the electrical supply and remove the fuse. And when necessary, close all service valves on the appliance, remove the appliance casing as described in
Fig. 29
20
section 4.7.1 and drain the water content from the appliance via the drain valve. Ensure some water absorbent cloths are available to catch any residual water that may drip from the appliance or removed component. Undertake a complete commissioning check as detailed in section 5, after replacing any component.
ALWAYS TEST FOR GAS TIGHTNESS IF ANY
GAS CARRYING COMPONENTS HAVE BEEN REMOVED
OR DISTURBED.
6.4.1 AIR BOX FRONT COVER REMOVAL (fig. 29)
Locate the 4 screws and remove air box front cover.
6.5 PUMP ASSEMBLY (fig. 30)
Carry out component removal procedure as described in 6.4.
Disconnect the flow pipe (B) from the combustion chamber connection, slacken the pipe (C) at the hydraulic assembly and swing/rotate clear of the pump assembly.
Remove the expansion pipe locking pin (D) from the top of the pump assembly and withdraw the flexible pipe. Locate and remove the pressure gauge securing pin (Dx) and disconnect the pressure gauge from the pump assembly. Disconnect the electrical wiring from the pump’s electrical connection point (E).
Locate and remove the 2 securing screws (A) at the rear of the pump assembly. Remove locking pin (F) from pump base and lift pump assembly clear of the hydraulic manifold. The pump assembly can now be removed from the appliance. Replace carefully in the reverse order.
6.6 SAFETY VALVE (fig. 31)
Carry out component removal procedure as described in 6.4.
Disconnect the outlet pipe
(I)
from the safety valve, remove safety valve locking pin
(L)
from the hydraulic manifold. Replace in the reverse order.
Fig. 30
Fig. 31
Carry out component removal procedure as described in 6.4.
Remove the expansion pipe locking pin
(D)
from the pump assembly and remove the expansion pipe. Locate and remove the AAV locking pin
(G)
from the pump assembly and remove the AAV assembly
(H)
. Replace in the reverse order.
6.7.1 TOP AUTOMATIC AIR RELEASE VALVE (fig. 32)
Carry out component removal procedure as described in 6.4.
Unclip and remove the air chamber front cover. Remove the
AAV locking pin (
M
) from the deaerator assembly and remove the AAV assembly (
N
). Replace in the reverse order.
6.8 WATER PRESSURE SWITCH (fig. 33)
Carry out component removal procedure as described in 6.4.
Locate and remove the locking pin
(O)
from the water pressure switch. Remove the wiring. Carefully withdraw the switch.
Replace in the reverse order.
6.9 FLOW THERMISTOR (fig. 4 - pos. 11)
Carry out component removal procedure as described in 6.4.
Unclip and remove the air chamber front cover. Unclip the flow thermistor from the flow outlet pipe. Disconnect thermistor electrical plug. Replace in the reverse order.
6.10 RETURN THERMISTOR (fig. 4 - pos. 8)
Carry out component removal procedure as described in 6.4.
Unclip the return thermistor from the return inlet pipe. Disconnect thermistor electrical plug. Replace in the reverse order.
6.11 PRINTED CIRCUIT BOARD (fig. 34)
Carry out component removal procedure as described in 6.4.
Pull the control fascia forward and lower it. Push the clips (
P
) which secure the PCB cover, remove cover, after carefully taking note of all wiring connections and jumper tag configuration.
Unhook and remove connection block (
Q
). Disconnect all wiring from the PCB, locate and remove the PCB securing screws, remove the required PCB. Replace in the reverse order ensuring that the position of the 2 control knobs are correctly aligned with the respective potentiometers on the PCB.
Ensure that the correct jumper tag configuration has been respected. It will be necessary to check the functioning of the
PCB is set for the correct boiler type/application.
Fig. 32
Fig. 33
Fig. 34
I
L
A B
D x
C
F
H D
G
E
P
N
M
O
Q
21
6.12 GAS VALVE (fig. 35)
Carry out component removal procedure as described in 6.4.
The gas valve must be changed as complete unit. Disconnect the electrical plug and leads from the gas valve, slacken and unscrew gas valve inlet and outlet connections.
Please note,
the sealing washers (
R
) must be discarded and replaced with new sealing washers. Locate and remove gas valve retaining screws
(T)
on the underside of the boiler if required, the gas valve can now be removed. Replace in the reverse order. Check and adjust burner pressure settings.
WARNING, A GAS TIGHTNESS CHECK MUST BE CAR-
RIED OUT.
Fig. 35
6.12.1 INJECTOR (fig. 36)
Carry out component removal procedure as described in 6.4
- Remove the mixer as described in 6.14.
- unscrew the screws fixing the plastic Venturi to the aluminium shell
- Loosen the plastic Venturi (
B1
) by levering from under the teeth (be careful not to force them) and press from the opposite side until it is completely extracted from the aluminium shell.
- Using a CH6 wrench remove the mixer assembly
- Clean plastic traces
- Substitute the mixer assembly with the two nozzles
- Reassemble the mixer with the flap in an horizontal position
- Replace in the reverse order.
- Check the number of fan speed
6.13 ELECTRODES & CONDENSE SENSOR
(fig. 37)
Carry out component removal procedure as described in 6.4.
Unclip and remove the air chamber front and RH side covers.
Disconnect the electrode leads and ancillary wiring from their respective connectors. Remove the retaining screws (W) for electrode and remove.
6.14 AIR PRESSURE SWITCH REMOVAL (fig. 38)
Carry out component removal procedure as described in 6.4.
Disconnect the air pressure switch wires.
Unscrew the 2 screws (
V
) and remove the bracket and pressure switch assembly
Refit the bracket and pressure switch assembly on the mixer and reconnect the air pressure switch wires.
Fig. 36
Fig. 37
6.15 FLUE FAN & MIXER (fig. 39-40)
Carry out component removal procedure as described in 6.4.
Remove the air pressure switch as described in 6.14.
Unclip and remove the air chamber front and the RH side covers. Slacken the gas pipe
(A1)
at the air box connection and swing/rotate away from the fan assembly. Locate and remove the sense electrode. To remove the mixer
(B1)
locate and remove the three screws
(C1)
. To remove the fan
(D1)
, disconnect the electrical connections attached to the fan, locate and remove the four screws
(E1)
. Gently ease the fan from its location. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.16 BURNER (fig. 39)
Carry out component removal procedure as described in 6.4.
Remove the air pressure switch as described in 6.14.
Unclip and remove the air chamber front and the RH side covers. Slacken the gas pipe (
A1
) at the air box connection and swing/rotate of the fan assembly. Locate and remove the 3 internal nuts (
F1
) which secure the fan assembly in position to the heat exchanger (
G1
). Disconnect the electrode leads and ancillary wiring from their respective connectors. Remove the retaining screws (fig. 36) for sensing electrode and remove.
Gently ease the fan assembly out of its location. Ensure the seal is in good condition, taking care to ensure it is placed correctly.
Replace in the reverse order.
Fig. 38
Fig. 39
22
B1
C1
T
R
V
U
Unica i28
Unica i32
G20 G31
4,70 flap side 3,40 flap side
4,20 free side 3,25 free side
4,30 flap side 3,40 flap side
4,20 free side 3,25 free side
V
A1
E1
D1
G1
W
V
F1
6.17 MAIN HEAT EXCHANGER (fig. 40)
Carry out component removal procedure as described in 6.4.
Remove the air pressure switch as described in 6.14.
Unclip and remove the three air chamber covers (front, LH, RH sides). Disconnect all the wiring connections. Fig. 36: Slacken the gas pipe (
L1
) at the air box connection and swing/rotate of the fan assembly. Remove fan and mixer as described in 6.14.
Locate and remove the 2-screws that secure the heat exchanger retaining clips and remove clips (
O1
). Pull the heat exchanger forward and disconnect it from the flue collector (
P1
). The heat exchanger can now be withdrawn from the appliance.
Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
P1
Carry out component removal procedure as described in 6.4.
Remove the locking pin (
Q1
) that secures the cover (
R1
) to the hydraulic manifold. Using a hooked piece of wire, carefully withdraw the by-pass cartridge (
S1
) and/or DHW non-return cartridge (
T1
). Ensure all seals are in good condition, taking care to ensure they are replaced correctly. Replace in the reverse order ensuring the cartridge is facing the correct way.
6.19 EXPANSION VESSEL
Should the removal and replacement of the expansion vessel be deemed impractical, an external expansion vessel may be fitted to the return pipe as close to the appliance as possible.
6.19.1 EXPANSION VESSEL REMOVAL
(with sufficient clearance above, fig. 42)
Carry out component removal procedure as described in 6.4.
Disconnect the flue from the appliance. Disconnect the expansion vessel from the flexible expansion pipe. Disconnect the flexible expansion pipe from the vessel. Unscrew the nut that secures the vessel to the lower frame. Locate and remove the
6 screws
(U1)
that secure the vessel top holding plate
(V1)
, remove the plate. The expansion vessel can now be removed.
Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.20 CONDENSE TRAP REMOVAL (fig. 43)
Carry out component removal procedure as described in 6.4.
Disconnect the 2 upper rubbers condense pipe
(W1)
. Remove the pin
(X1)
that secures the trap to the air box plate. Disconnect the lower rubber condense pipe from the condense trap.
Carefully remove the condense trap. Remove the 2 screws
(Y1) and clean the condense trap.
Replace the component taking care the longer pipe on the cover is positioned on the right side.
Disconnect the the locking pin (
Z1
) that secures the trap to the air condense pipe. Disconnect the lower rubber condense pipe from the condense trap. Carefully remove the condense trap. For cleaning unlock the upper and lower closing plug (
J1
).
Replace in the reverse order.
Fig. 40
Fig. 41
Fig. 42
V1
S1
L1
Q1
U1
O1
T1
R1
Fig. 43
W1
Y1
X1
Z1
J1
23
6.21 FLUE COLLECTOR REMOVAL (fig. 43)
Carry out component removal procedure as described in 6.16.
Locate and remove the screw (
A2
) that secures the flue gas analysis test point cover (
B2
). Remove the clip and the fumes thermostat (
C2
). Locate and remove the screws (
D2
) that secure the flue collector to the combustion chamber Gently pull forward and ease the flue collector from its location. Replace in the reverse order.
6.21.1 DHW FLOW RESTRICTOR (fig. 44)
Carry out the component removal procedure as described in
6.4.
Disconnect the cold water inlet pipe at the DHW flow switch
(
E2)
. Using a small screwdriver, gently ease the flow restrictor
(F2)
from its seating. Replace in the reverse order. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
6.21.2 DHW FLOW METER (fig. 44)
Carry out component removal procedure as described in 6.4.
Remove the locking pin
(G2)
. Disconnect and remove the cold water inlet pipe from the DHW flow switch & DHW heat exchanger. Disconnect the wiring to the DHW flow switch.
Slacken and unscrew the inlet connection
(E2)
. Unscrew the nut
(H2)
. Lift the DHW flow switch housing from its seating. If necessary remove the locking pin
(I2)
from the DHW flow switch.
Replace in the reverse order ensuring that the housing is firmly inserted onto its seating. Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
Fig. 43
6.21.3 VALVE ACTUATOR (fig. 45)
Carry out component removal procedure as described in 6.4.
Remove the locking pin
(L2)
that secures the actuator
(M2)
to the heating manifold. Disconnect the electrical plug from the actuator. Replace in the reverse order.
6.21.4 DHW THERMISTOR (fig. 45)
Carry out component removal procedure as described in 6.4.
Locate and remove the thermistor locking pin
(N2)
. Gently ease the thermistor assembly
(O2)
from the hydraulic manifold.
Replace in the reverse order.
6.21.5 DIVERTOR VALVE ASSEMBLY (fig. 46)
C arry out component removal procedure as described in 6.4.
Remove the valve actuator as described in 6.20. Gently prise the valve assembly from the manifold. Replace in the reverse order ensuring that the seating assembly is inserted properly.
Ensure all seals are in good condition, taking care to ensure they are replaced correctly.
Fig. 44
G2
B2
A2
C2
O2
N2
H2
D2
E2
F2
I2
Fig. 45
L2
M2
L2
Fig. 46
M2
24
SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
7.1 CHECKING APPLIANCE OPERATION
When carrying out any repairs or servicing to the appliance, the relevant commissioning procedure must be undertaken to ensure the continued safe operation of the appliance. Particular attention should be made to ensure gas tightness, water tightness and the electrical integrity of the appliance.
7.2 APPLIANCE MODES OF OPERATION
NOTE
There must be sufficient system water pressure (min. 0.5 bar) to ensure the water pressure switch is activated. If there is insufficient system pressure the pump and fan will be prevented from operating and the low-pressure fault code will be indicated.
7.2.1 SELECTOR SWITCH IN THE OFF/RESET POSITION
When the selector switch is in the OFF/RESET position, the following functions are active.
Active functions
:
• frost-protection system
• pump & actuator anti-block.
7.2.2 ON-BOARD FUNCTIONS
•
CO FUNCTION:
the CO function when activated, will allow the appliance to run at CH maximum, DHW maximum or minimum output whilst a combustion analysis check or a mechanical gas valve calibration is being carried out. Whilst the CO function is active, all other functions are disabled (minimum power operating period, anti-cycle, set-point, etc). Once enabled, the CO function will remain active for a 15-minute period, or until the function is manually deactivated
•
FROST-PROTECTION:
this function is only active when there are no requests for heating or HW. If the temperature drops below 5°C, the boiler will operate on minimum power until the temperature of the thermistors reaches 35°C for CH and 55°C for DHW. Thereafter the pump & fan will over-run for 30-seconds.
•
ANTI-CYCLE FUNCTION:
the anti-cycle function ensures the burner remains switched off for at least 3-minutes after the set-point hysterisis (set-point + 5-deg) for CH heat request.
•
PUMP ANTI-BLOCK FUNCTION:
when there has been no heating or HW request for 24-hours, the anti-block cycle is activated. The pump will be activated for a period of 30-seconds.
•
ACTUATOR ANTI-BLOCK FUNCTION:
when there has been no heating or HW request for 24-hours, the anti-block cycle is activated. The divertor valve actuator will motor briefly to the heating position, and then back to the DHW position. The pump will run briefly.
•
SARA function:
the SARA function permits the boiler (when the set-point is within the SARA range) to automatically adjust
(raise) the heating flow outlet temperature should the room thermostat contacts remain closed for more that 20-minutes.
•
DHW PRE-HEAT FUNCTION:
when the DHW pre-heat function is enabled, the appliance will light periodically to maintain the temperature of the DHW heat exchanger. When the
DHW thermistor and the primary thermistor fall below 35°C and 55°C respectively, the boiler will fire on minimum +25% power until the primary thermistor exceeds 55°C. Thereafter the pump will over-run for a period of 30-seconds.
7.2.3 HEATING MODE
With the selector switch in the heating & hot water position and any additional controls (time clock, programmer, room thermostat, etc.) calling for heat, the appliance will operate in the heating mode. The pump and fan will be activated via the flow temperature sensor. When the fan is sensed to be operating correctly (tacho signal), the ignition sequence commences. Ignition is sensed by the electronic circuit to ensure flame stability at the burner. Once successful ignition has been achieved, the electronic circuitry increases the gas rate to 75% for a period of 15 minutes.
The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor, consequently a high temperature at the flow sensor results in a lower fan speed. As the water temperature increases, the temperature sensors – located on the flow pipe of the boiler – reduce the fan speed via the electronic circuitry. Depending on the load, either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will increase relative to the output required. When the boiler has reached the set point
(+ hysterisis), the burner will switch off. The built-in anti-cycle device prevents the burner from re-lighting for approximately
3-minutes. When the temperature of the flow sensor falls below the set point (- hysterisis), the burner will re-light.
NOTE
If the spark/sensing electrode does not sense ignition the appliance will re-attempt ignition a further 4-times then go to lockout.
When the set-point has been reached (the position of the heating temperature selector) as measured at the primary thermistor, the appliance will begin the modulation phase whereby the fan and gas valve will continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-point by 5°C (hysterisis), the burner will shut down. A new ignition sequence will be enabled when the 3- minute anti-cycle has been performed and the temperature at the primary thermistor has dropped 5°C (hysterisis) below the set-point.
7.2.4 DHW MODE
With the selector switch in either the hot water only or heating
& hot water position, the appliance will operate in the hot water mode whenever a DHW outlet is opened. A flow rate exceeding
2-litres per minute will activate the DHW flow switch whereupon the pump and fan will be activated via the flow temperature sensor. When the fan is sensed to be operating correctly (tacho signal), the ignition sequence commences. Ignition is sensed by the electronic circuitry to ensure flame stability at the burner.
Once successful ignition has been achieved, the electronic circuit allows the gas rate to achieve the modulation value.
NOTE
When the request for heating and/or hot water has been satisfied, the appliance pump and fan may continue to circulate to dissipate any residual heat within the appliance.
ATTENTION
Gas type and appliance output
must be set
according to the specific appliance specification. Vokèra accepts no responsibility if the gas type is not correctly adjusted according to the respective appliance specification as detailed on the appliance data badge.
7.3 CHECKING THE CO
2
AND ADJUSTING THE
GAS VALVE
THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE
AID OF A PROPERLY CALIBRATED FLUE GAS ANALYSER.
Isolate the appliance from the electrical supply and remove the appliance casing as described in 4.7.1. Set the flue gas analyser to read CO
2
and insert the probe into the flue analysis test point
(fig. 42). Restore the electrical supply to the boiler and switch the boiler to the OFF mode.
Have access to the printed circuit board, locate and open the closing plug on the dash board (Q2), locate and press the CO button (see fig. 46 pos. SW1). Press the button the number of times according the function requirement as per 7.3.1.
Fig. 46
Q2 use the supplied screwdriver to push the
CO botton (SW1)
SW1
25
7.3.1 CO
2
FUNCTION SETTINGS
Locate the CO button (see 7.3).
Select the main selector switch in position .
CO
2
FUNCTIONS ACTION ON THE BUTTON DISPLAY
combustion analysis mode gas valve maximun setting press once = burner running at maximum heating press twice = burner running at maximum DHW
ACO
ACO gas valve minimum setting press three time = burner running at minimum
ACO
NOTE
1 - Any additional pressing of CO
2 - To restart the CO
3 - If the CO
2 button after the third time the burner switched between maximum DHW and minimum.
function it is necessary to pass throught the position with the main selector switch values do not correspond to the values in the technical data table, make further adjustments.
7.3.2 GAS VALVE MAXIMUM SETTING
Set the CO
2
button at maximum (see 7.3.1), once the maximum is obtained check that it corresponds with the appropriate CO
2
value (Maximum) for the respective appliance (see 2.11). If the CO
2
reading is correct, proceed to gas valve minimum setting (7.3.3).
However, if the CO
2
reading is incorrect, the maximum gas pressure must be adjusted as follows:
• using a 2.5mm Allen key, very slowly turn the maximum adjustment screw (see fig. 47) – clockwise to decrease, counter clockwise to increase – until the correct value is displayed on the CO
2
analyser (allow time for the analyser to stabilise).
7.3.3 GAS VALVE MINIMUM SETTING
Set the CO
2
button at minimum (see 7.3.1), once the minimum is obtained check that it corresponds with the appropriate CO
2
value (Minimum) for the respective appliance (see 2.11). If the
CO
2
reading is correct, proceed to completion (7.3.4).
However, if the CO
2
reading is incorrect, the minimum gas pressure must be adjusted as follows:
• locate the minimum adjustment screw (fig. 47), using a suitable screwdriver remove the protection plug
• using a 4mm Allen key, very slowly turn the minimum adjustment screw (see fig. 47) - clockwise to increase, counter clockwise to decrease - until the correct value is displayed on the CO
2
analyser (allow time for the analyser to stabilise).
7.3.4 COMPLETION
On completion of the combustion analysis check and/or any gas valve adjustment, refit the plug (fig. 44
Q2)
and move the mode selector throught position. Remove the test probe from the test point and refit the sealing screw/s and/or cap.
IMPORTANT
A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF ANY
GAS CARRYING COMPONENTS HAVE BEEN REMOVED,
REPLACED OR DISTURBED.
7.4 COMBUSTION ANALYSIS TEST
A combustion analysis check can easily be carried out on the appliance via the test points located on the top of the appliance (see 7.3).
• Insert the flue gas analyser probe into the flue gas test point
(see fig. 42).
• Operate the boiler in combustion analysis mode (see 7.3.1) and compare the values with those shown in section 2 (Nat.
Gas) or section 10 (LPG). If different adjust the gas valve according to 7.3.1, 7.3.2, & 7.3.3.
Note
Note: If a measured CO/CO
2
ratio of 0.004/1 or less AND a CO reading of less than 350ppm cannot be achieved, please contact Vokera technical for advice
Note:
When checking the air inlet test point, insert the probe no more than 25mm into the test point.
7.5 CHECKING THE EXPANSION VESSEL
Carry out the component removal procedure as described in
6.4. You must ensure that the boiler is completely drained of water. Using a suitable pressure gauge, remove dust cap on expansion vessel and check the charge pressure. The correct charge pressure should be 1.0 bar ± 0.1 bar. If the charge pressure is less, use a suitable pump to increase the charge.
26
Compensation pipe connection
Inlet gas pressure connection
Fig. 47
Maximum screw
Minimum screw
NOTE
You must ensure the drain valve is in the open position whilst re-charging takes place. Replace the dust cap and carry out the relevant commissioning procedure (section 5).
7.6 EXTERNAL FAULTS
Before carrying out any faultfinding or component replacement, ensure the fault is not attributable to any aspect of the installation.
7.6.1 INSTALLATION FAULTS
Symptom
No ignition
No hot water
No heating
Possible cause
Check wiring/check electrical supply
Check pipe-work
Check external controls
Fault
Fault code
Possible cause
Check gas supply, check flue system, check polarity
7.7 ELECTRICAL CHECKS
Any electrical checks must be carried out by a suitably qualified person.
7.7.1 EARTH CONTINUITY TEST
Isolate the appliance from the electrical supply, and using a suitable multi-meter carry out a resistance test. Connect test leads between an appliance earth point and the earth wire of the appliance supply cable. The resistance should be less than
1 OHM. If the resistance is greater than 1 OHM check all earth wires and connectors for continuity and integrity.
7.7.2 SHORT CIRCUIT CHECK
Isolate the appliance from the electrical supply, and using a suitable multi-meter, carry out a short circuit test between the
Live & Neutral connections at the appliance terminal strip.
Repeat above test on the Live & Earth connections at the appliance terminal strip.
NOTE
Should it be found that the fuse has failed but no fault is indicated, a detailed continuity check will be required to trace the fault. A visual inspection of components may also assist in locating the fault.
7.7.3 POLARITY CHECK
With the appliance connected to the electrical supply and using a suitable multimeter, carry out the following voltage tests:
• connect test leads between the Live & Neutral connections at the appliance terminal strip. The meter should read approximately
230V ac. If so proceed to next stage. If not, see 7.7.4.
• connect test leads between the Live & Earth connections at the appliance terminal strip. The meter should read approximately
230V ac. If so proceed to next stage. If not, see 7.7.4.
• connect test leads between the Neutral & Earth connections at the appliance terminal strip. The meter should read approximately 0 – 15Vac. If so polarity is correct. If not, see
7.7.4.
7.7.4 REVERSED POLARITY OR SUPPLY FAULT
Repeat the above tests at the appliance isolator, if testing reveals correct polarity and/or supply at the isolator, re-check wiring and connections between the isolator and the appliance.
If tests on the isolator also reveal reversed polarity or a supply fault, consult the local electricity supplier for advice.
ISTANCE TO EARTH CHECK
Isolate the appliance from the electrical supply, and using a suitable multi-meter carry out a resistance test. Connect test leads between the Live & Earth connections at the appliance terminal strip. If the meter reads other than infinity there is a fault that must be isolated, carry out a detailed continuity check to identify the location of the fault. These series of checks must be carried out before attempting any faultfinding procedures on the appliance. On completion of any task that required the disconnection and re-connection of any electrical wiring or component, these checks must be repeated.
7.8 FAULT FINDING
Before attempting any faultfinding, the electrical checks as detailed in 7.7 must be carried out. Isolate the appliance from the electrical supply. Disconnect any external controls from terminal plug (CN5 fig. 46), and insert a link-wire between the two wires at the ‘TA’ connections.
NOTE
Restore the electrical supply to the boiler and turn the selector switch to the on position. The boiler should now function as described in section 7. Should the boiler fail to respond, the internal fuses and connectors should be checked to ensure integrity and continuity.
7.9 COMPONENT VALUES & CHARACTERISTICS
COMPONENT
Fan
VALUE
230Vac
Pump
Valve actuator
Ignition transformer
Gas valve
Room thermostat connection
NTC thermistor (dry contact)
NTC thermistor (wet contact)
FUNCTION
Standard Heating temperature range (min – max °C)
DHW temperature range (min – max °C)
75% maximum CH time
Heating OFF hysterisis (°C)
Heating ON hysterisis (°C)
DHW OFF hysterisis (°C)
DHW ON hysterisis (°C)
Anti-cycle delay
Pump over-run
Low output (min. output + %)
CO function max temp. (°C)
CO re-light temp. (°C)
CO function time
Flow NTC max temp. (°C)
High limit thermostat (°C)
Flue NTC max temp. (°C)
Maximum differential (°C)
IGNITION CONTROL
Ignition attempts before L/O (lockout)
Re-ignition attempts after loss of flame signal
230Vac
230Vac
230Vac
230Vac
24Vdc
10Kohm
10Kohm
VALUE
40 - 80
37 - 60
15 min
SP + 5
SP – 5
SP + 5
SP + 4
3-min
30-sec
Min +25
90
78
15 min
90
105
125
35
VALUE
5
5
APPLIANCE STATUS AND FAULT CODES
When the boiler detects a temporary fault condition, the appropriate code is shown. If/when the fault is final, the pump will perform a 60-second post circulation and fault code will be displayed. See table on page. 28.
27
ALARM CODE CAUSE
A01
_St
_CL
A02
A03
A04
A06
AUTOSTOP
CALL FOR SERVICE
ALARM TYPE ACTION
Final Call Landlord
Temporary then final
Call Landlord
Final Reset, check appliance operation Ignition failure, flame not sensed, internal fault
Limit thermostat fault Final
Fan tacho signal fault, air pressure switch Final
Insufficient system water pressure
DHW thermistor fault
Final
Temporary
Reset, check appliance operation
Reset check appliance operation, check fan
Check/refill system pressure, reset, check appliance operation
Check DHW thermistor
A07
Primary (flow) thermistor fault Temporary
Primary (flow) thermistor over temperature Temporary then
Final
Temperature differential Final
Check primary thermistor, check wiring
Reset, check appliance operation
Reset, check appliance operation, check thermistors
Check return thermistor, check wiring
A08
Return thermistor fault, low temperature system thermostat fault
Return thermistor over temperature
Temperature differential inverted
Temporary
Temporary then
Final
Final
Reset, check appliance operation
A09
A11
Adj
ACO
Flue thermistor or flue thermistor counter fault
Flue thermistor over temperature
False flame
Calibration
Service operation
Temporary
Final
Temporary
Na
Na
Reset, check pump, ensure there is sufficient circulation around heating circuit/s
Check flue thermistor counter at power on, check flue thermistor, check wiring
Reset, check appliance operation
Check appliance power connection
None
None
Purge cycle mode active Na None
P
P
blinking
Preheating function active
Preheating function running
Flame ON
Na
Na
Na
None
None
None
Hours
- -
Stand-by
OFF
Na
Na
None
None
7.10 ADJUSTMENTS
The boiler has already been adjusted by the manufacturer during production. If the adjustments need to be made again, for example after extraordinary maintenance, replacement of the gas valve, or conversion from methane gas to LPG, observe the following procedures.
The adjustment of the maximum and minimum output, and of the maximum and minimum heating and of slow switch-on, must be made strictly in the sequence indicated, and only by qualified personnel only:
- disconnect the boiler from the power supply
- turn the heating water temperature selector to its maximum
- loosen the fixing screws (E) on the instrument panel
- lift then turn the instrument panel towards you
- loosen the fixing screws on the cover (F) to access the terminal board
- insert the jumpers JP1 and JP3
- power up the boiler
The display shows “ADJ” for approximately 4 seconds
Next change the following parameters:
1 - Domestic hot water/absolute maximum
2 - Minimum
3 - Heating maximum
4 - Soft light fan speed as follows:
- turn the heating water temperature selector to set the required value
28
- press the CO button and then skip to the calibration of the next parameter.
Live electrical parts (230 V AC).
The following icons light up on the monitor:
1. during domestic hot water/absolute maximum calibration
2. during minimum calibration
3. during heating maximum calibration
4.
P
during soft light fan speed calibration
End the procedure by removing jumpers JP1 and JP3 to store these set values in the memory.
THE function can be ended at any time without storing the set values in the memory and retaining the original values as follows:
- remove jumpers JP1 and JP3 before all 4 parameters have been set
- set the function selector to (OFF/RESET)
- cut the power supply
- waiting for 15 minutes after it is connected.
Calibration can be carried out without switch on the boiler.
By turning the heating selection knob, the monitor automatically shows the number of rotations, expressed in hundreds (e.g. 25 = 2,500 rpm).
GAS VALVE CALIBRATION
- Connect the boiler to the power supply
- Open the gas tap
- Set the function selector to (OFF/RESET) (monitor off)
- Remove the screws (E), remove the casing, remove the retaining screw below the control fascia then lower the fascia towards you (fig. 24)
- Loosen the fixing screws on the cover (F) to access the terminal board
- Press the CO button
Live electrical parts (230 V AC).
- Wait for burner ignition.
The display shows “ACO”. The boiler operates at maximum heat output.
The “combustion analysis” function remains active for a limited time (15 min); if a delivery temperature of 90°C is reached, the burner is switched off. It will be switched back on when this temperature drops below 78°C.
- Insert the analyser probe in the ports provided in the air distribution box, after removing the screws from the cover
- Press the “combustion analysis” button a second time to reach the number of rotations corresponding to the maximum domestic hot water output (table 1)
- Check the CO
2
value: (table 4) if the value does not match the value given in the table, use the gas valve maximum adjustment screw
- Press the “combustion analysis” button a third time to reach the number of rotations corresponding to the minimum output (table 2)
- Check the CO
2
value: (table 5) if the value does not match the value given in the table, use the gas valve minimum adjustment screw
- To exit the “combustion analysis” function, turn the control knob
- Remove the flue gas probe and refit the plug
- Close the instrument panel and refit the housing.
The “combustion analysis” function is automatically deactivated if the board triggers an alarm. In the event of a fault during the combustion analysis cycle, carry out the reset procedure.
table 1
MAXIMUM NUMBER OF
FAN ROTATIONS
METHANE
GAS (G20)
LIQUID GAS
(G31)
7.10.1 CHECKING THE FAN SPEED
Locate the CO button (see Fig 43).
Select the main selector switch to the ON position, press the
CO button once, the display will then scroll through the fan speeds along with the relevant icon.
7.10.2 THERMOREGULATION
To set the temperature regulation curve, locate potentiometer
(P3). By turning (P3), the curve is shown on the LCD display.
The user can adjust the temperature of the heating system indirectly by changing the required room temperature from between 15°C & 25°C, this will allow the PCB to recalculate the system temperature required, the default temperature for calculating the curve is 20°C.
The graph below can be used to determine the correct curve setting.
REFERENCE
TEMPERATURE 15 °C
90
80
70
60
50
40
30
20
ROOM TEMPERATURE CURVE OFFSET
10
30 25
25 ° C
20
20 °C
15
15 °C
10 5 0
REFERENCE
TEMPERATURE 20 °C
REFERENCE
TEMPERATURE 25 °C
-5 -10
External Temperature (°C)
-15 -20
Unica i 28 heating - DHW
Unica i 32 heating - DHW
45 - 61
51 - 62
45 - 61
49 - 60 rpm rpm
table 2
MINIMUM NUMBER OF
FAN ROTATIONS
Unica i 28 - i 32 table 3
SOFT LIGHT FAN
SPEED
Unica i 28
Unica i 32
METHANE
GAS (G20)
12
LIQUID GAS
(G31)
15 rpm
METHANE
GAS (G20)
37
37
LIQUID GAS
(G31)
37
37 rpm rpm
table 4
Max. CO
2
Unica i 28 - i 32 table 5
Min. CO
2
Unica i 28 - i 32
METHANE
GAS (G20)
9.0
LIQUID GAS
(G31)
10.0
%
METHANE
GAS (G20)
9.0
LIQUID GAS
(G31)
10.0
%
29
100
90
80
T80
70
60
50
T45
40
30
20
20 15 10 5 0 -5 -10 -15 -20
7.11 ALARM RECORDS
The “ALARM RECORDS” function starts automatically once the display has been on for 2 hours, or immediately by setting the
P1 parameter to 1.
The records include all the latest alarms, up to a maximum of 5 alarms, and they are displayed in sequence by pushing and releasing the P1 button on the display board. If the records are empty (P0=0) or if tracking the same is disabled (P1=0), the display function is not available.
Alarms are displayed in reverse order compared to the order in which they occurred: this means that the last alarm generated is the first to be displayed.
To delete the alarms records, simply set parameter P0 to 0.
NOTE:
To get to the P1 button the cover on the control panel must be removed and the display board must be identified
(see figure)
PROGRAMMING PARAMETERS
Functioning of the display can be personalised by programming three parameters:
When button P1 on the display is held down for at least 10 sec, the programming procedure is activated.
The three parameters, with their respective values, are shown in rotation on the display.
To edit a parameter value, simply push the P1 button again when the required parameter is displayed, and then hold it down until the value switches from 0 to 1 or vice-versa (approx. 2 sec).
The programming procedure is closed automatically after 5 minutes, or if there is an electrical power failure
P1
Parameter Default Description
P0 0 Deletion of alarms records
(0= records empty/1= records not empty)
P1 0 Immediate activation of alarm record management
(0= delayed records management activated/1= immediate records management activated)
P2 0 Do not change
30
SECTION 8 - WIRING DIAGRAMS
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
8.1 EXTERNAL WIRING
The appliance comes with a factory fitted (TA) link to allow basic operation of the boiler via the mode selector switch. If external controls are to be added to the system, they must be connected to the appliance as shown in the following diagrams. For advice on controls that are not featured in this book, please contact Vokera technical on 0844 391 0999.
8.1.1 EXTERNAL WIRING LIMITATIONS
Any external wiring must remain within the limits as detailed in the table below:
CONNECTION
External sensor
Room thermostat
OT+ connection
240V cables must be wired separately from 24V cables to avoid interference.
MAX LENGTH
30-metres
30-metres
30-metres
8.2 TYPICAL CONTROL APPLICATIONS
The appliance can be used with the following controls:
•
OT+ control (fig. 49), please contact Vokera technical for detailed instruction on specific OT+ controls.
Male connector is factory fitted to be used with OT+ control female connector.
•
• single-channel, voltage-free time clocks or programmable room thermostat (fig. 48). If using the factory fitted male/female connector, the pink wires connected to the terminal strip M6 must be moved over to the room thermostat socket position.
Vokera external sensor (fig. 50)
8.3 OTHER DEVICES
Contact the controls manufacturer and/or Vokera technical department should you require more specific information on the suitability of a particular control. Note if fitting other controls, we would suggest removing the factory fitted male connector wires for ease of installation. Further guidance on the recommended practice for the installation of external controls can be found in CHeSS – HC5/
HC6 (www.energyefficiency.gov.uk).
EXTERNAL
ALARM
IMPORTANT
230 V
• The boiler must always be supplied with a permanent
230V electrical supply.
• Always remove the link between TA & TA on the appliance high-voltage terminal strip whenever additional controls are connected to the appliance.
• Do not connect any controls or auxiliary equipment to the low-voltage terminal strip, other than that approved/
Fermale connector
Male connector
2 4
1
4 blue brown
ROOM
THERMOSTAT
(Voltage free contact inpunt)
230 V
N L
Fuse 3.15A F
M6
M3
F
M6
M6
OT+
EXTERNAL
SENSOR
ROOM
THERMOSTAT
(Voltage free contact inpunt)
-t°
ROOM
THERMOSTAT
(Voltage free contact inpunt)
M6
OT+
Fermale connector
OT+
Male connector
Fermale connector
4 4 3 3 2 2 1 1
Male connector
4 4 3 3 2 2 1 1
M3
M3
230 V
N L
F
230 V
N L
Fuse 3.15A F
Fuse 3.15A F
M2
Fig. 49
OPTIONAL DEVICE (24V) TERMINAL BLOCK
SENSOR
EXTERNAL
ALARM
ROOM
THERMOSTAT
(Voltage free contact inpunt)
M6
OT+
-t°
EXTERNAL
SENSOR
ROOM
THERMOSTAT
(Voltage free contact inpunt)
EXTERNAL
ALARM
OT+
-t°
M2
M6
F
ROOM
THERMOSTAT
(Voltage free contact inpunt)
Fig. 50
M2
External alarm
M6 E.S.
= external sensor
OT+
= opentherm + connection
ROOM
THERMOSTAT
(Voltage free contact inpunt)
31
ROOM
THERMOSTAT
(Voltage free contact inpunt)
2 4 1 blue brown
Fermale connector
Male connector
2 4
1
4
3 3
2 2 1 1 blue brown
Fermale connector
M6
Male connector
4 3 3 2 2 1 1
M3
ROOM
THERMOSTAT
(Voltage free contact inpunt)
M6
230 V
N L
Fuse 3.15A F
F
230 V
N L
Fuse 3.15A F
M6
M3
F
M6
FUNCTIONAL DIAGRAM
Fig. 51
Spark electrode brown blue yellow/green black red orange red orange black brown blue
2
1
12 brown blue brown blue blue brown
EXTERNAL ALARM white orange(-) violet (+) blue (out) red blue blue yellow yellow red red white white grey grey violet (+) blue (out) orange(-) white white red red
Heat
N
D.H.W.
blue black brown blue brown grey (-) blue (HS) red (+) pink (PWM)
1 1 2 2 3 3 4 4
EXTERNAL SENSOR pink pink black black black orange orange pink pink
CN15
CN7
32
SECTION 9 - LPG INSTRUCTIONS
NOTE
Please refer to Section 3, Para 3.1 and use the appropriate PPE when carrying out any of the actions or procedures contained within this section.
9.1 RELATED DOCUMENTS
BS 5440 PART 1&2 FLUES & VENTILATION REQUIREMENTS
BS 5449
BS 5482
BS 5546
BS 6798
PART 1 FORCED CIRCULATION HOT WATER SYSTEMS
PART 1 DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMANENT DWELLINGS
INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW
9.2 TECHNICAL DATA
Gas Pressures
Inlet pressure
Heating maximum gas rate (kg/hr)
DHW maximum gas rate (kg/hr)
Minimum gas rate (kg/hr)
Injector size
CO
2
@ maximum output (%)
CO
2
@ minimum output (%)
CO @ maximum output (ppm)
CO @ minimum output (ppm)
9.3 CONVERTING THE APPLIANCE GAS TYPE
To convert the appliance to another gas type it is necessary to change the injector and adjust the gas valve (CO
2
).
• To change the injector see 6.12.1.
• To adjust CO
2
values see 9.2.
9.4 GAS SUPPLY
The gas supply must be connected to the appliance by a competent LPG installer and must be of sufficient size to supply the appliance at its maximum output. An existing supply must be checked to ensure that it is of adequate size to deal with the maximum rated input of this and any other appliances that it serves.
9.5 GAS SUPPLY INSTALLATION
The entire installation including the meter must be purged and checked for gas tightness.
9.6 CHECKING THE CO
2
AND ADJUSTING THE
GAS VALVE
THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE
AID OF A PROPERLY CALIBRATED FLUE GAS ANALYSER.
Isolate the appliance from the electrical supply and remove the appliance casing as described in 4.7.1. Set the flue gas analyser to read CO
2
and insert the probe into the flue analysis test point
(fig. 40). Restore the electrical supply to the boiler and switch the boiler to the OFF mode.
Have access to the printed circuit board, locate and open the closing plug on the dash board (
L2
fig. 43), locate and press the CO button (see fig. 43 pos. SW1). The appliance will now operate in CO
2
mode for approximately 15-minutes.
9.6.2 GAS VALVE MAXIMUM SETTING
Set the CO button at maximum (see 9.6.1), once the maximum is obtained check that it corresponds with the appropriate CO
2 value (Maximum) for the respective appliance. If the CO
2 reading is correct, proceed to gas valve minimum setting (9.6.3).
9.6.1 CO
2
FUNCTION SETTINGS
Locate the CO button (see 7.3).
Select the main selector switch in position .
CO
2
FUNCTIONS
combustion analysis mode
ACTION ON THE BUTTON
press once = burner running at maximum heating
Unica i28
37.0 mbar
1.55
2.17
0.31
3.40 mm (flap side)
3.25 mm (free side)
10.0
10.0
190
20
Unica i32
37.0 mbar
1.94
2.48
0.35
3.40 mm (flap side)
3.25 mm (free side)
10.0
10.0
180
5
However, if the CO
2 reading is incorrect, the maximum gas pressure must be adjusted as follows:
• using a 2.5mm Allen key, very slowly turn the maximum adjustment screw (see fig. 47) – clockwise to decrease, counter clockwise to increase – until the correct value is displayed on the CO
2 analyser (allow time for the analyser to stabilise).
9.6.3 GAS VALVE MINIMUM SETTING
Set the CO button at minimum (see 9.6.1), once the minimum is obtained check that it corresponds with the appropriate CO
2 value (Minimum) for the respective appliance. If the CO
2 reading is correct, proceed to completion (9.6.4).
However, if the CO
2 reading is incorrect, the minimum gas pressure must be adjusted as follows:
• locate the minimum adjustment screw (fig. 47), using a suitable screwdriver remove the protection plug
• using a 4mm Allen key, very slowly turn the minimum adjustment screw (see fig. 47) - clockwise to increase, counter clockwise to decrease - until the correct value is displayed on the CO
2 analyser (allow time for the analyser to stabilise).
9 .6.4 COMPLETION
On completion of the combustion analysis check and/or any gas valve adjustment, refit the plug (
L2
j) and move the mode selector to the position. Remove the test probe from the test point and refit the sealing screw/s and/or cap.
IMPORTANT
A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF ANY
GAS CARRYING COMPONENTS HAVE BEEN REMOVED,
REPLACED OR DISTURBED.
ATTENTION
Gas type and appliance output
must be set
according to the specific appliance specification. Vokèra accepts no responsibility if the gas type is not correctly adjusted according to the respective appliance specification as detailed on the appliance data badge.
DISPLAY
ACO gas valve maximun setting press twice = burner running at maximum DHW
ACO gas valve minimum setting press three time = burner running at minimum
ACO
33
COMMISSIONING: CO AND COMBUSTION RATIO CHECK
BEFORE CO AND COMBUSTION RATIO CHECK
The installation instructions should have been followed, gas type verified and gas supply pressure/rate checked as required prior to commissioning.
As part of the installation process,
ESPECIALLY WHERE A
FLUE HAS BEEN FITTED BY PERSONS OTHER THAN THE
BOILER INSTALLER, visually check the integrity of the whole flue system to confirm that all components are correctly assembled, fixed and supported. Check that the maximum flue lengths have not been exceeded and all guidance has been followed (e.g. Technical Bulletin 008).
The flue gas analyser should be of the correct type, as specified by BS 7967.
Before use, the flue gas analyser should have been maintained and calibrated as specified by the manufacturer. The installer must have the relevant competence for use of the analyser.
Check and zero the analyser
IN FRESH AIR, as per analyser manufacturer’s instructions.
NOTE
The air/gas ratio valve is factory-set and must not be adjusted during commissioning unless this action is recommended, following contact with the Vokera technical help line. If any such adjustment is recommended and further checking of the boiler is required, the engineer must be competent to carry out this work and to use the flue gas analyser accordingly.
If the boiler requires conversion to operate with a different gas family (e.g., conversion from natural gas to LPG) separate guidance will be provided by the
Vokera technical help line and must be followed.
SET BOILER TO MAXIMUM RATE
In accordance with, section 7.3, set boiler to operate at maximum rate (full load condition). Allow sufficient time for combustion to stabilise. , insert analyser probe into air inlet sampling point.
Verify flue integrity
Analyser readings indicate that combustion products and inlet air are mixing.
Further investigation of the flue is therefore required.
Check that flue components are correctly assembled, fixed and supported as per boiler/flue instructions.
Check that flue and flue terminal are not obstructed.
N
O
Is O2 ≥20.6% and CO2 < 0.2%?
Is O2 ≥20.6% and CO2 < 0.2%?
NO
Turn off appliance and call Vokera’s technical helpline for advice.
The appliance must not be commissioned until problems are identified and resolved.
YES
YES
Check all seals around the appliance burner, internal flue seals, door and case seals. Rectify where necessary.
NO
CHECK CO AND
COMBUSTION RATIO
AT MAXIMUM RATE
With boiler still set at maximum rate, insert analyser probe into flue gas sampling point.
Allow readings to stabilise before di
Is CO less than
350ppm AND
CO/CO
2 ratio less than 0.004?
YES
Turn off appliance and call
Vokera’s technical helpline for advice.
The appliance must not be commissioned until problems are identified and resolved. If commissioning cannot be fully completed, the appliance must be disconnected from the gas supply in accordance with the GSIUR.
NOTE:
Check and record CO and combustion ratio at both maximum AND minimum rate before contacting the Vokera
NO
NO
Is CO less than 350ppm
AND
CO/CO
2 ratio less than
0.004?
YES
Is CO < 350ppm and CO/CO
2 ratio less than 0.004 ?
YES
CHECK CO AND COMBUSTION
RATIO AT MINIMUM RATE
With boiler set at minimum rate, insert analyser probe into flue gas sampling point. Allow readings to stabilise before recording.
SET BOILER TO
MINIMUM RATE
In accordance with section 7.3, set boiler to operate at minimum rate (to minimum load condition). Allow sufficient time for combustion to stabilise.
Boiler is operating satisfactorily
No further actions required.
Ensure test points are capped, boiler case is correctly replaced and all other commissioning procedures are completed.
Complete Benchmark Checklist, recording CO and combustion ratio readings as required.
34
Benchmark Commissioning &
Warranty Validation Service Record
It is a requirement that the boiler is installed and commissioned to the manufacturers’
To instigate the boiler warranty the boiler needs to be registered with the manufacturer within one month of the installation. The warranty rests with the end-user (consumer), and they should be made aware it is ultimately their responsibility to register with the manufacturer, within the allotted time period.
It is essential that the boiler is serviced in line with the manufacturers’ recommendations, at least annually. This must be carried out by a competent Gas
Safe registered engineer. The service details should be recorded on the Benchmark
Service and Interim Boiler Work Record and left with the householder. Failure to comply with the manufacturers’ servicing instructions and requirements will invalidate the warranty.
www.hhic.co.uk
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturers’ instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer’s statutory rights.
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
35
GAS BOILER SYSTEM COMMISSIONING CHECKLIST & WARRANTY VALIDATION RECORD
Address:
Boiler make and model:
Boiler serial number:
Commissioned by (PRINT NAME):
Company name:
Company email:
Gas Safe registration number:
Telephone number:
Company address:
Commissioning date:
Heating and hot water system complies with the appropriate Building Regulations? Yes
Time, temperature control and boiler interlock provided for central heating and hot water
Boiler Plus requirements (tick the appropriate box(s))
Boiler Plus option chosen for combination boiler in ENGLAND
Time and temperature control to hot water
Weather compensation
Load compensation
Cylinder thermostat and programmer/timer
Yes
Smart thermostat with automisation and optimisation
Flue Gas Heat Recovery
Combination boiler
Zone valves
Thermostatic radiator valves
Automatic bypass to system pre-existing pre-existing pre-existing pre-existing
Fitted
Fitted
Fitted
Fitted
Not required
Not required
Not required
Not required
Water quality
instructions Yes
What system cleaner was used?
What inhibitor was used?
pre-existing
CENTRAL HEATING MODE measure and record (as appropriate)
Gas rate (for combination boilers complete DHW mode gas rate)
Central heating output left at factory settings?
If no, what is the maximum central heating output selected?
Dynamic gas inlet pressure
Brand:
Brand:
Fitted m
3/ hr
Yes or
Product:
Product:
Not required
No ft
3
/hr kW mbar
°C
°C Central heating return temperature
System correctly balanced/rebalanced?
COMBINATION BOILERS ONLY
Is the installation in a hard water area (above 200ppm)?
Water scale reducer/softener pre-existing
Yes
Fitted
Yes
No
Not required
Brand: Product:
If yes- DHW expansion vessel
Pressure reducing valve
DOMESTIC HOT WATER MODE Measure and record
Gas rate
Dynamic gas inlet pressure at maximum rate
Cold water inlet temperature
Hot water has been checked at all outlets
CONDENSATE DISPOSAL pre-existing pre-existing m 3/ hr
Yes
Yes
Fitted
Fitted or
No
Not required
Not required ft 3 /hr mbar
°C
Temperature °C
The condensate drain has been installed in accordance with the manufacturers’ instructions and/or BS5546/BS6798
Point of termination Internal
Method of disposal
ALL INSTALLATIONS
Gravity
External (only where internal termination impractical)
Pumped
Yes
Record the following
At max rate:
At min rate (where possible)
CO ppm CO
2
% CO/CO
2
Ratio
CO ppm CO
2
% CO/CO
2
Ratio
instructions, and readings are correct?
Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer
The manufacturers’ literature, including Benchmark Checklist and Service Record, has been explained and left with the customer
Yes
Yes
Commissioning Engineer’s signature
Customer’s signature
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
36
SERVICE & INTERIM BOILER WORK RECORD
It is recommended that your boiler and heating system are regularly serviced and maintained, in line with manufacturers’ instructions, and that the appropriate service / interim work record is completed.
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name:
Telephone N o :
Company name:
Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name:
Telephone N o :
Company name:
Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments:
Signature:
yes n/a instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m
3
/h delete as appropriate
OR
Yes ft
3
/h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m
3
/h delete as appropriate
OR
Yes ft
3
/h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments:
Signature:
yes n/a instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
37
SERVICE & INTERIM BOILER WORK RECORD
It is recommended that your boiler and heating system are regularly serviced and maintained, in line with manufacturers’ instructions, and that the appropriate service / interim work record is completed.
Service provider
When completing a service record (as below), please ensure you have carried out the service as described in the manufacturers’ instructions. Always use the
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name:
Telephone N o :
Company name:
Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name:
Telephone N o :
Company name:
Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m 3 /h delete as appropriate
OR
Yes ft 3 /h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments:
Signature:
yes n/a instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m
3
/h delete as appropriate
OR
Yes ft
3
/h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
SERVICE/INTERIM WORK ON BOILER
delete as appropriate
Date:
Engineer name: Company name:
Telephone N o : Gas Safe registration N o :
Max rate CO ppm CO² % CO/CO²
Min rate CO ppm CO² % CO/CO² undertaken in accordance with manufacturers’ instructions, and readings are correct?”
Gas rate: m
3
/h delete as appropriate
OR
Yes ft
3
/h
No yes
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments:
Signature:
yes n/a instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. *
Comments: yes n/a
Signature:
instructions and BS 7593. It is only acceptable to not have undertaken this if the service engineers attendance visit was in between annual services to attend a non-water facing component.
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
38
Vokèra Warranty Terms and Conditions
Vokèra Ltd offer customers the comfort of a parts and labour warranty repair service subject to the following terms and conditions.
Vokèra Ltd only obligation under the guarantee shall be to repair or replace the faulty appliance at Vokèra Ltd discretion. This will be carried out where a fault arises from defects within the appliance, caused by either material or workmanship of the manufacturer.
1. The boiler must have been installed and commissioned within 12 months of manufacture by a registered Gas
Safe (RGII ROI) installer in accordance with the guidelines in the installation and servicing booklet provided with the boiler.
2. This guarantee does not protect malfunction or damage arising from incorrect installation, commissioning or maintenance procedures, as laid out in the installation handbook, inefficient flue system, poor or incorrect electricity, wrong gas supply or pressure, tampering by inexperienced persons and any other cause not directly due to manufacture.
3. Vokèra Ltd cannot accept responsibility for any costs arising from repair or maintenance carried out by any third party.
4. The “Benchmark” commissioning sheet must be completed by the installer and left with the boiler for reference purpose.
5. The warranty will commence from the date of installation. Without proof of purchase ie an invoice or completed
“Benchmark” commissioning sheet, the warranty will commence from the date of manufacture as detailed on the appliance data plate.
6. To qualify for the full term of warranty, the boiler must be serviced once annually by a Gas Safe Registered
Engineer (RGII ROI). Proof of annual service in accordance with the manufacturer’s instructions must be provided (e.g. Benchmark Service Record). If this condition is not met the period of warranty will extend to only 12 months from date of installation.
By registering your appliance, you will be helping us provide you with the best after sales service in the unlikely event that your boiler requires attention during the guarantee period.
Register online: www.vokera.co.uk (UK) or www.vokera.ie (ROI)
If the boiler suffers a mechanical or an electrical breakdown or you require an annual service, please contact our
Customer Care Centre on:
UK: 01274 866100
ROI: 056 7755057
Our normal working hours, excluding Bank holidays are:
8.15am - 5.00pm Monday to Friday
8.00am - 12.00pm Saturday (UK only)
We will arrange for an engineer or appointed agent, to inspect and repair, or where in our sole opinion repair is not economic, arrange to replace the boiler.
7. Health & Safety:
a. Engineers will only attend to boiler products where it is considered by the engineer that the installation does not pose a risk to health and safety.
b. A permanently fixed access ladder must service installations in lofts or attics. Adequate lighting and permanently fixed flooring must also be available.
c. Cupboard installations must provide minimum working clearances as detailed in the installation instructions.
Vokèra will not accept responsibility for the removal of cupboards, kitchen units or trims in order to gain access for repairs.
8. Warranty does not apply:
a. If the boiler is removed from its place of installation without our prior consent.
b. To any defect, damage or breakdown caused by inadequate servicing of the boiler or by deliberate action, accident, misuse or third party interference including modification or an attempted repair which does not fully comply with industry standards.
c. To any defect, damage or breakdown caused by the design, installation and maintenance of the central heating system.
39
d. To de-scaling or other work required as a result of hard water scale deposits or from damage caused by aggressive water or sludge resulting from corrosion. Indications that such work may be required include a noisy boiler, cold spots on radiators, sludge in pipes and poor circulation of the central heating system.
e. If the claim/contact procedure set out in section 6 is not adhered to.
f. To any other costs or expenses caused by or arising as a result of the breakdown of a Vokèra Boiler.
g. To any costs incurred during delays in fixing reported faults.
9. We reserve the right to a charge a callout fee where:
a. There is no completed “Benchmark” commissioning sheet or equivalent control document present.
b. There is incomplete or no service record(s) for each and every year the boiler has been installed.
c. A fault cannot be found.
d. The breakdown or fault has been caused by an event, which is excluded from the warranty – see section 8.
e. Failure to cancel an agreed appointment prior to our engineers visit.
f. The boiler is outside the period of warranty or the conditions of the warranty have not been met.
10. If we fit replacement parts or replace a boiler it will not extend the period of the warranty. All replaced parts or boilers will become the property of Vokèra Ltd.
11. The warranty applies only where a Vokèra boiler has been installed in a domestic dwelling in the United Kingdom,
Northern Ireland or Republic of Ireland, to provide heat and/or hot water to the central heating system.
12. Vokèra Ltd warranty is offered in addition to the rights provided to a consumer by law. Details of these rights can be obtained from a Trading Standards Authority or a Citizen Advice Bureaux.
Your Personal Details
Vokèra takes care of your personal details in order to protect your privacy. Below we detail how we use any data you provide us with and how we manage that data to protect it.
Personal data is collected by us confidentially and in accordance with data protection law regulations. Vokèra is registered as a data controller with the Information Commissioner’s Office.
Your personal data is only stored if you volunteer to provide it, for example, to request information, submit a service visit, or to register a product for purposes of warranties and surveys etc. Vokèra will only use your personal data to satisfy the request you have made, and will not disclose information to third parties without your prior consent.
Any personal data stored by Vokèra is protected to ensure unauthorised persons cannot access or disclose the data. Vokèra uses security measures to protect the data we collect, in order to prevent manipulation, loss and destruction. No user information provided is stored anywhere on the internet that can be accessed by the public.
Vokèra may like to inform you of products and services that you could be interested in, and request your opinion of our services. Participation is voluntary and you can request not to receive such communications at any time or request your details to be updated by emailing:
Contact Us:- Customer Care Centre
Tel: 01274 866100 (UK), 056 7755057 (ROI)
UK:
Vokèra Ltd, Customer Care, Stubs Beck Lane, West 26 Business Park, Whitehall Road, Cleckheaton, BD19 4TT
ROI:
Vokèra Ltd, Customer Care, West Court, Callen, Co Kilkenny, Ireland , R95 PW40
Email: [email protected] (UK), [email protected] (ROI)
Guarantor – Vokèra Ltd, Borderlake House, Unit 7 Riverside Ind Est, London Colney, Herts AL2 1HG
40
Registered address:
Vokèra Ltd
Borderlake House
Unit 7 Riverside Industrial Estate
London Colney
Herts AL2 1HG
www.vokera.co.uk
www.vokera.ie
Sales, General Enquires
T
0844 391 0999
F
0844 391 0998
Vokèra Ireland
West Court, Callan
Co Kilkenny
T
056 7755057
F
056 7755060
Vokèra Limited reserve the right to change specification without prior notice
Consumers statutory rights are not affected.
Company Reg No: 1047779
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 THINGS YOU SHOULD KNOW
- 3 1.1 GAS APPLIANCES
- 3 1.2 ELECTRICAL SUPPLY
- 3 1.3 GUARANTEE REGISTRATION CARD
- 3 1.4 APPLIANCE COMMISSIONING CHECKLIST (UK only)
- 3 1.5 HOW DOES IT WORK?
- 3 1.6 DIMENSIONS
- 3 1.7 CLEARANCES REQUIRED
- 3 1.8 FROST PROTECTION SYSTEM
- 3 1.9 APPLIANCE STATUS INDICATORS
- 5 GETTING STARTED
- 5 2.1 BEFORE SWITCHING ON
- 5 2.2 APPLIANCE CONTROLS
- 5 2.3 LIGHTING THE BOILER
- 5 2.4 ADJUSTING THE HEATING TEMPERATURE
- 5 2.5 ADJUSTING THE HOT WATER TEMPERATURE
- 5 2.6 EXPLANATION OF FEATURES
- 5 2.7 AUTOMATIC TEMPERATURE CONTROL
- 6 HOW TO
- 6 3.1 HOW TO TOP-UP THE SYSTEM PRESSURE
- 6 3.2 HOW TO RESET THE APPLIANCE
- 6 FOR SHORT PERIODS
- 6 FOR LONG PERIODS
- 6 3.5 HOW TO CARE FOR THE APPLIANCE
- 6 WHAT IF
- 6 4.1 WHAT IF I SUSPECT A GAS LEAK
- 6 TO TOP-UP THE SYSTEM
- 6 ITS ANNUAL SERVICE
- 6 4.4 WHAT IF I NEED TO CALL AN ENGINEER
- 8 QUENCE
- 8 1.1 PRINCIPLE COMPONENTS
- 8 1.2 MODE OF OPERATION (at rest)
- 8 1.3 MODE OF OPERATION (Heating)
- 8 1.4 MODE OF OPERATION (Hot water)
- 8 1.5 SAFETY DEVICES
- 9 SECTION 2 - TECHNICAL DATA
- 9 2.1 CENTRAL HEATING
- 9 2.2 DOMESTIC HOT WATER
- 9 2.3 GAS PRESSURES
- 9 2.4 EXPANSION VESSEL
- 9 2.5 DIMENSIONS
- 9 2.6 CLEARANCES
- 9 2.7 CONNECTIONS
- 9 2.8 ELECTRICAL
- 9 2.9 FLUE DETAILS (CONCENTRIC 60-100)
- 9 2.9A FLUE DETAILS (CONCENTRIC 80-125)
- 9 2.9B FLUE DETAILS (TWIN PIPES)
- 9 2.10 EFFICIENCY
- 9 2.11 EMISSIONS
- 11 2.12 PUMP DUTY
- 12 SECTION 3 - GENERAL REQUIREMENTS (UK)
- 12 3.1 RELATED DOCUMENTS
- 12 3.2 LOCATION OF APPLIANCE
- 12 3.3 GAS SUPPLY
- 12 3.4 FLUE SYSTEM
- 12 3.5 AIR SUPPLY
- 12 3.6 WATER CIRCULATION
- 13 3.7 ELECTRICAL SUPPLY
- 13 3.8 MOUNTING ON A COMBUSTIBLE SURFACE
- 13 3.9 TIMBER FRAMED BUILDINGS
- 13 3.10 INHIBITORS
- 13 3.11 SHOWERS
- 13 SECTION 3A - GENERAL REQUIREMENTS (EIRE)
- 13 3A.1 RELATED DOCUMENTS
- 13 3A.2 LOCATION OF APPLIANCE
- 14 3A.3 GAS SUPPLY
- 14 3A.4 FLUE SYSTEM
- 14 3A.5 AIR SUPPLY
- 14 3A.6 WATER CIRCULATION
- 14 3A.7 ELECTRICAL SUPPLY
- 14 3A.8 MOUNTING ON A COMBUSTIBLE SURFACE
- 14 3A.9 TIMBER FRAMED BUILDINGS
- 14 3A.10 INHIBITORS
- 14 3A.11 SHOWERS
- 14 3A.12 DECLARATION OF CONFORMITY
- 15 SECTION 4 - INSTALLATION
- 15 4.1 DELIVERY
- 15 4.2 CONTENTS
- 15 4.3 UNPACKING
- 15 4.4 PREPARATION FOR MOUNTING THE APPLIANCE
- 16 4.5 FITTING THE FLUE
- 20 4.6 CONNECTING THE GAS AND WATER
- 20 4.7 ELECTRICAL CONNECTIONS
- 21 SECTION 5 - COMMISSIONING
- 21 5.1 GAS SUPPLY INSTALLATION
- 21 5.2 THE HEATING SYSTEM
- 21 5.3 FILL THE CONDENSATE TRAP
- 21 5.4 INITIAL FILLING OF THE SYSTEM
- 21 5.5 INITIAL FLUSHING OF THE SYSTEM
- 21 5.6 PRE-OPERATION CHECKS
- 21 5.7 INITIAL LIGHTING
- 21 AND COMBUSTION ANALYSIS
- 21 5.9 FINAL FLUSHING OF THE HEATING SYSTEM
- 21 5.10 SETTING THE BOILER OPERATING TEMPERATURE
- 21 5.11 SETTING THE SYSTEM DESIGN PRESSURE
- 21 5.12 REGULATING THE CENTRAL HEATING SYSTEM
- 22 5.13 FINAL CHECKS
- 22 5.14 INSTRUCTING THE USER
- 22 SECTION 6 - SERVICING INSTRUCTIONS
- 22 6.1 GENERAL
- 22 6.2 ROUTINE ANNUAL SERVICING
- 22 6.3 REPLACEMENT OF COMPONENTS
- 22 6.4 COMPONENT REMOVAL PROCEDURE
- 23 6.5 PUMP ASSEMBLY
- 23 6.6 SAFETY VALVE
- 23 6.7 LOWER AUTOMATIC AIR RELEASE VALVE
- 23 6.8 WATER PRESSURE SWITCH
- 23 6.9 FLOW THERMISTOR
- 23 6.10 RETURN THERMISTOR
- 23 6.11 PRINTED CIRCUIT BOARD
- 24 6.12 GAS VALVE
- 24 6.13 ELECTRODES & CONDENSE SENSOR
- 24 6.14 AIR PRESSURE SWITCH REMOVAL
- 24 6.15 FLUE FAN & MIXER
- 24 6.16 BURNER
- 25 6.17 MAIN HEAT EXCHANGER
- 25 6.18 AUTOMATIC BY-PASS & DHW NON-RETURN VALVE
- 25 6.19 EXPANSION VESSEL REMOVAL
- 25 6.20 CONDENSE TRAP REMOVAL
- 26 6.21 FLUE COLLECTOR REMOVAL
- 27 7.1 CHECKING APPLIANCE OPERATION
- 27 7.2 APPLIANCE MODES OF OPERATION
- 27 ADJUSTING THE GAS VALVE
- 28 7.4 COMBUSTION ANALYSIS TEST
- 28 7.5 CHECKING THE EXPANSION VESSEL
- 28 7.6 EXTERNAL FAULTS
- 28 7.7 ELECTRICAL CHECKS
- 29 7.8 FAULT FINDING
- 29 7.9 COMPONENT VALUES & CHARACTERISTICS
- 30 7.10 ADJUSTMENTS
- 32 7.11 ALARM RECORDS
- 33 SECTION 8 - WIRING DIAGRAMS
- 33 8.1 EXTERNAL WIRING
- 33 8.2 TYPICAL CONTROL APPLICATIONS
- 33 8.3 OTHER DEVICES
- 35 SECTION 9 - LPG INSTRUCTIONS
- 35 9.1 RELATED DOCUMENTS
- 35 9.2 TECHNICAL DATA
- 35 9.3 CONVERTING THE APPLIANCE GAS TYPE
- 35 9.4 GAS SUPPLY
- 35 9.5 GAS SUPPLY INSTALLATION
- 35 ADJUSTING THE GAS VALVE
- 36 Commissioning checklist
- 37 Benchmark
- 41 Warranty Terms && Conditions