ELPRO 915U-TCADP Thermocouple Adapter Configuration Guide
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Installation & Configuration Guide
Thermocouple Adapter for 915U-2
Configuration
On the “I/O Configuration” web page select:
Select Thermocouple type from the drop down list. Options are Type T, Type J, Type K.
Select the Polarity from the drop down list (Normal or
Reversed)
Set Thermocouple Error Value to a value the integer registers (30003 and/or 30004) will go to during fail *
Press “Save and Activate Changes” button.
Thermocouple Range @ Tamb (+10- +40)
* Error Value is set in register 30003 when the thermocouple is open circuit.
* Error Value is set in register 30003 and 30004 when the thermocouple adaptor is not fitted
Thermocouple Range @ Tamb (-40- +60)
Type Normal Reverse
Type T - 25°C to + 365°C - 200°C to + 70°C
Type K - 25°C to + 455°C - 200°C to + 70°C
Type J - 10°C to + 345°C - 210°C to + 60°C
Type
Type T
Type K
Type J
Normal Reverse
0°C to + 330°C - 200°C to + 5°C
0°C to + 410°C - 200°C to + 5°C
15°C to + 300°C - 210°C to + 10°C
PWR
RF
232
485
915U-TCADP
Dip Switches
Installation
915U-TCADP board plugs into the bottom 6 terminals on the 915U-2 terminal strip.
A separate 14 way terminal strip is provided to allow connection to the remaining terminals.
Address locations
38005 = 32 bit Floating Point temperature value
38007 = 32 bit Floating Point Cold Junction value
30003 = Scaled 16 bit Analog value
30004 = Scaled 16 bit Cold Junction value
Connections
Caution:
ESD Sensitive pins. Use ESD handling precautions.
Thermocouple input terminals must be within +/- 5V of the
915U-2 „GND‟ terminal
Analog Input Scale Examples
For normal Polarity setting Zero and Span to 0 and 100 respectively will scale the register to read the temperature as an integer value, e.g. 148.25 °C will read 14825 or 26.51 °C will read 2651
For normal Polarity, setting Zero and Span to 15019 and 682.6667 respectively will scale the register so that a temperature of -10 to
50°C will give a scaled range of 8192 to 49152
For Reverse Polarity, setting Zero and Span to 30948 and 455.106 respectively will scale the register so that a temperature of -50 to
40°C will give a scaled range of 8192 to 49152
Revision 1.6 - Oct 2011
Thermocouple Adapter
-Ve
If „Thermocouple
Polarity‟ selection is reversed
Thermocouple wires must be swapped, e.g. (red) to TC+ &
(blue) to TC-
TC-
Constantan
(red)
+Ve
N/C
N/C
COM
(+24V)
TC+
Copper (blue)
Normal Type “T”
Thermocouple
All Dip Switches must be set to the OFF position.
ELPRO
915U-2
Elpro inst_915U_TC_Adapter_1-6.vsd