Trane YHD180G3RHB302G Voyager™ 15 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Installation manual 41 Pages
Trane YHD180G3RHB302G Voyager™ 15 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Installation manual
Show HTML Add to My manuals41 Pages
Trane YHD180G3RHB302G is a powerful and efficient packaged rooftop air conditioner. It is designed for commercial and industrial applications, and it is capable of providing cooling, heating, and ventilation. The unit is equipped with a variety of features that make it easy to install, operate, and maintain.
With a cooling capacity of 18 tons and a heating capacity of 180,000 BTU/hr, the Trane YHD180G3RHB302G is well-suited for large spaces such as warehouses, factories, and retail stores. The unit is also equipped with a variety of features that make it energy-efficient, such as a variable-speed compressor and an economizer.
The Trane YHD180G3RHB302G is a versatile unit that can be used in a variety of applications. It is a reliable and durable unit that is built to last.
advertisement
Installation, Operation, and Maintenance
Packaged Rooftop Air Conditioners
Voyager™
–
Cooling, Gas/Electric
12.5 to 25 Tons, 60/50Hz
Model Number:
YS*150–301
YH*150-300
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
February 2017
RT-SVX26P-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTION s
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
• Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
© 2017 Ingersoll Rand RT-SVX26P-EN
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
• All Ingersoll Rand personnel must follow Ingersoll
Rand Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. All policies can be found on the BOS site . Where local regulations are more stringent than these policies, those regulations supersede these policies.
• Non-Ingersoll Rand personnel should always follow local regulations.
Introduction
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual.
Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
NOTICE:
Water Damage!
Non-factory penetrations through the base of this unit are not allowed. Any penetration in the base of the unit may affect the water tight integrity of the unit and lead to water leaks into the conditioned space. Failure to follow instructions could result in equipment and property damage.
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated Model Number Description, Unit Dimensions,
Unit Weight, and Start-Up sections.
Overview of Manual
Note:
One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems.
By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
RT-SVX26P-EN 3
4
Table of Contents
Model Number Description
. . . . . . . . . . . . . . . 5
General Information
. . . . . . . . . . . . . . . . . . . . . 7
Unit Description
. . . . . . . . . . . . . . . . . . . . . . . 7
System Input Devices & Functions
. . . . . . . 8
Sensors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Inspection
. . . . . . . . . . . . . . . . . . . . . . . 11
Storage
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Clearances
. . . . . . . . . . . . . . . . . . . . . . 11
Unit Dimensions
. . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Weights
. . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Rigging
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Foundation
. . . . . . . . . . . . . . . . . . . . . . . . . . 19
General Unit Requirements
. . . . . . . . . . . . 19
Main Unit Power
. . . . . . . . . . . . . . . . . . . . . 21
Space Temperature Averaging
. . . . . . . . . 25
Factory-Mounted Unit Options
. . . . . . . . . . . 30
Circuit Breaker (FIYUCB) & Unit Disconnect
(FIYUDC)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Powered and Unpowered Convenience
. . 31
Return Air Smoke Detector
. . . . . . . . . . . . . 32
Through the Base Gas Utility Option
. . . . 35
Air-Fi™ Wireless Communication Interface
(WCI)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pre Start
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Test Modes
. . . . . . . . . . . . . . . . . . . . . . . . . . 37
Verifying Proper Air Flow (Units with Belt
Drive Indoor Fan)
. . . . . . . . . . . . . . . . . . . . . 37
Start Up
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Economizer Start-Up
. . . . . . . . . . . . . . . . . . 38
Compressor Start-Up
. . . . . . . . . . . . . . . . . 38
Dehumidification Option
. . . . . . . . . . . . . . . 39
Heating Start-Up
. . . . . . . . . . . . . . . . . . . . . 39
Variable Air Volume Applications (Multi-zone,
Traditional VAV)
. . . . . . . . . . . . . . . . . . . . . . 39
Final System Set Up
. . . . . . . . . . . . . . . . . . 41
Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Fan Belt Adjustment—Belt Drive Units
. . 42
Monthly Maintenance
. . . . . . . . . . . . . . . . . 43
Final Process
. . . . . . . . . . . . . . . . . . . . . . . . . .44
Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . .45
ReliaTel Control
. . . . . . . . . . . . . . . . . . . . . . .45
System Status Checkout Procedure
. . . . . .45
Resetting Cooling and Heating Lockouts
. .47
Zone Temperature Sensor (ZTS) Service Indicator
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Zone Temperature Sensor (ZTS) Test
. . . .47
Programmable & Digital Zone Sensor Test
48
Wiring Diagrams
. . . . . . . . . . . . . . . . . . . . . . . .50
Warranty
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
RT-SVX26P-EN
Y
1
S
2
D
3
1
4
All products are identified by a multiple character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.
Digit 1 — Unit Type
Y = Packaged Gas/Electric
Digit 2 — Efficiency
S = Standard Efficiency
H = High Efficiency
Digit 3 — Airflow Configuration
D = Downflow
H = Horizontal
Digit 4, 5, 6 — Nominal Gross
Cooling Capacity (MBh)
150 = 12½ Tons, 60Hz
155 = 15 Tons, 50Hz
180 = 15 Tons, 60Hz
175 = 17½ Tons, 50Hz
210 = 17½ Tons, 60Hz DOE 2018
211 = 17½ Tons, 60Hz
200 = 20 Tons, 50Hz
240 = 20 Tons, 60Hz
250 = 25 Tons, 50Hz
300 = 25 Tons, 60Hz DOE 2018
301 = 25 Tons, 60Hz
Digit 7 — Major Design
Sequence
F = Microchannel Type Condenser
Coils
25
G = ASHRAE 90.1-2013 (Fan/
Compressor Staging)
13
or
Microchannel Type Evaporator &
Condenser Coils
Digit 8 — Voltage Selection
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
K = 380/60/3
D = 380-415/50/3
Digit 9 — Unit Controls
R = Reliatel
5
5
0
6
G
7
3
8
Digit 10 — Heating Capacity
H = Gas Heat - High
L = Gas Heat - Low
V = Gas Heat - SS Ht Ex - Modulating
X = Gas Heat - SS Ht Ex - Low
Z = Gas Heat - SS Ht Ex - High
Digit 11 — Minor Design
Sequence
Digit 12, 13 — Service Sequence
00 = None
01 = 18mm Microchannel Condenser
Coil
Note:
‘01’ only available on select models.
Digit 14 — Fresh Air Selection
0 = No Fresh Air
D = Econ Dry Bulb w/ Barometric
Relief
1
F = Econ Reference Enthaply w/
Barometric Relief
1
H = Econ Comparative Enthaply w/
Barometric Relief
1
K = Low Leak Econ w/ Barometric
Relief
1
M = Low Leak Econ Reference
Enthalpy w/ Barometric Relief
1
P = Low Leak Econ Comparative
Enthalpy w/ Barometric Relief
1
Digit 15 — Supply Fan/Drive
Type/Motor
0 = Standard Motor
1 = Oversized Motor
6
3 = High Efficiency Motor
6
6 = Single Zone Variable Air Volume
Standard Motor
7 = Multi-Speed Standard Motor
8 = Single Zone Variable Air Volume
Oversized Motor
9 = Multi-Speed Oversized Motor
A = Single Zone Variable Air Volume
Standard Motor w/ Shaft
Grounding Ring
B = Multi-Speed Standard Motor w/
Shaft Grounding Ring
C = Single Zone Variable Air Volume
Oversized Motor w/ Shaft
Grounding Ring
D = Multi-Speed Oversized Motor w/
Shaft Grounding Ring
E = VAV Supply Air Temperature
Control - Standard Motor
F = VAV Supply Air Temperature
Control - Oversized Motor
G = VAV Supply Air Temperature
Control - Standard Motor w/ Shaft
Grounding Ring
H = VAV Supply Air Temperature
Control - Oversized Motor w/
Shaft Grounding Ring
R
9
H
10
A
11
A
12
Digit 16 — Hinged Service Access /
Filters
0 = Standard Panels/Standard
Filters
22
A = Hinged Access/Standard Filters
22
B = Standard Panels/MERV 8 Filters
6
C = Hinged Access/MERV 8 Filters
6
D = Standard Panels/MERV 13 Filters
6
E = Hinged Access/MERV 13 Filters
6
Digit 17 — Condenser Coil
Protection
0 = Standard Coil
1 = Standard Coil With Hail Guard
4 = CompleteCoat™Condenser Coil
5 = CompleteCoat™Condenser Coil with Hail Guard
Digit 18 — Through The Base
Provisions
0 = No Through The Base Provisions
A = Through The Base Electric
12
B = Through The Base Gas
C = Through The Base Electric/Gas
12
D = Through The Base Access
Digit 19 — Disconnect Switch/
Circuit Breaker
11
0 = No Disconnect/circuit break
1 = Unit Mounted Non-Fused
Disconnect Switch
2 = Unit Mounted Circuit Breaker
Digit 20 — Convenience Outlet
Option
0 = Without Convenience Outlet
A = Unpowered Convenience Outlet
5
B = Powered Convenience Outlet
5
Digit 21 — Communications
Options
0 = Without Communications Options
1 = Trane Communications Interface
6 , 15
2 = Lontalk Communications
Interface
6
6 = Building Automation Control
Network Communications
Interface
7 = Air-Fi™ Wireless Communications
24
Digit 22 — Refrigeration System
Option
0 = Standard refrigeration system
B = Dehumidification (Hot Gas
Reheat)
4 , 13
Digit 23 — Refrigeration Controls
0 = Without Refrigeration Controls
1 = Frostat
9 , 18
Digit 24 — Smoke Detector
2 , 10
0 = Without Smoke Detector
A = Return Air Smoke Detector
B = Supply Air Smoke Detector
RT-SVX26P-EN 5
Model Number Description
C = Return/Supply Air Smoke
Detector
D = Plenum Smoke Detector
19
Digit 25 — System Monitoring
Controls
0 = No Monitoring Controls
1 = Clogged Filter Switch
9
2 = Fan Failure Switch
9
3 = Discharge Air Sensing
9
4 = Clogged Filter Switch and Fan
Failure switch
9
5 = Clogged Filter Switch and
Discharge Air Sensing
9
6 = Fan Failure Switch and Discharge
Air Sensing
9
7 = Clogged Filter Switch, Fan Failure
Switch and Discharge Air
Sensing
9
A = Condensate Drain Pan Overflow
Switch
B = Clogged Filter Switch and
Condensate Drain Pan Overflow
Switch
9
C = Fan Failure Switch and
Condensate Drain Pan Overflow
Switch
9
D = Discharge Air Sensing and
Condensate Drain Pan Overflow
Switch
9
E = Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
Overflow Switch
9
F = Clogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
9
G = Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
9
H = Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing and Condensate Drain Pan
Overflow Switch
9
Digit 26 - System Monitoring
Controls
0 = No Monitoring Controls
A = Demand Control Ventilation
(CO
2
)
17
B = FDD (Fault Detection and
Diagnostics)
C = FDD (Fault Detection Diagnostics)
& Demand Control Ventilation
(CO
2
)
17
Digit 27 - Unit Hardware
Enhancements
0 = No Enhancements
1 = Stainless Steel Drain Pan
Digit 28 - Short Circuit Current
Rating
0 = Standard SCCR
A = 65kA SCCR Option
20 , 21
Digit 31 - Advanced Unit
Controls
0 = Standard Unit Controls
1 = Human Interface
23
Note:
Most Factory Installed Options available for Downflow Air
Discharge units only. Please verify with ordering system for availability.
Model Number Notes
1.
Some field set up required.
2. Requires ReliaTel Options Module.
3. Requires Economizer.
4. All 22 nd
digit model numbers for reheat coil (B) require additional factory installed options: Frostat, and 2” pleated filters.
5. Must be ordered with Throughthe-Base Electrical option or
Horizontal-Side Access and either
Unit Mounted Disconnect or
Circuit Breaker.
6. Available factory installed on downflow AND horizontal units.
Verify with ordering system.
7.
Cannot be fused.
8. Must be factory installed when using Through-the-Base Options.
9. ReliaTel Options Module is required when ordering the following accessories: Clogged
Filter Switch, Fan Fail Switch,
Condensate Overflow Switch,
Discharge Air Sensing Kit, Frostat,
Ventilation Override, Smoke
Detector, Dehumidification and
Modulating Gas Heat Furnace.
10. Option cannot be ordered in conjunction with field installed economizer on downflow units.
Must be factory installed. The return air smoke detector may not fit up or work properly on the
Voyager units when used in conjunction with 3 rd
party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.
11. Unit mounted disconnect and circuit breakers are mutually exclusive of each other.
12. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker.
13. Available on high efficiency units only.
14. All Factory Installed Options are
Built-to-Order. Check order services for estimated production cycle.
15. TCI is for use with non-VariTrac systems and VariTrac systems.
16. For use with multi-speed and
SZVAV units only.
17. Demand Control Ventilation
Option includes wiring only. The
C0
2
sensor is a field-installed only option.
18. Frostat is standard on VAV, and high efficiency units.
19. Supply and/or return smoke detector may not be used with the plenum smoke detector.
20. Only available where MOP is above 60A.
21. 575 VAC option is 25kA.
22. Standard filters are not available with Low Leak Economizers.
23. Human Interface is standard with
FDD (Fault Detection Diagnostics).
24. Must be used with BACnet™ open protocol.
25. Apply to 50Hz units only.
6 RT-SVX26P-EN
General Information
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.
For major design sequence F units, the condenser coils are microchannel type aluminum coils.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module”
(RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network.
This module through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supply air temperature, and/or humidity conditions depending on the application.
The stages of capacity control for these units are achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling.
Economizer Control Actuator ReliaTel™
Control
The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO
2
setpoint, CO
2
, and ambient dry bulb/ enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of
±5 percent of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 in·lb of torque and is powered by 24 Vac.
RTCI—ReliaTel™ Trane Communication
Interface (Optional)
This module is used when the application calls for an ICS™ building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
RLCI—ReliaTel™ LonTalk Communication
Interface (Optional)
This module is used when the application calls for an ICS™ building management type control system that is LonTalk.
It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.
RBCI—ReliaTel BACnet™ Communication
Interface (Optional)
This module is used when the application calls for an open
BACnet protocol. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or as a kit to be field installed.
Follow the installation instructions that ships with each kit when field installation is necessary.
WCI—Trane Air-Fi™ Wireless
Communication Interface (Optional)
The Trane Air-Fi Communication Interface allows for wireless communication between system controls, unit controls, and wireless sensors for Trane control products that use BACnet protocol. The WCI replaces the need for communications wire in all system applications.
RTOM—ReliaTel™ Options Module
(Optional)
The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke detector. Refer to system input devices and functions for operation.
RTAM—ReliaTel™ Air Handler Module
(Standard with Traditional VAV)
RTAM receives information from the supply duct static pressure transducer. Attached to the module are the supply air heating potentiometer, supply air cooling setpoint potentiometer, supply pressure setpoint potentiometer, static pressure deadband potentiometer, morning warm-up setpoint potentiometer, reset setpoint potentiometer, and 5 DIP switches.
RT-SVX26P-EN 7
8
General Information
System Input Devices &
Functions
The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM.
The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules.
Refer to the unit’s electrical schematic for the specific module connections. The following controls are available from the factory for field installation.
Supply Fan Failure Input (Optional)
The Fan Failure Switch (FFS) can be connected to sense indoor fan operation. If air flow through the unit is not proven by the differential pressure switch connected to the
RTOM (factory set point 0.07“ w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash. The system will remain locked out until a reset is initiated either manually or through ICS.
Drain Pan Condensate Overflow Switch
(Optional)
This input incorporates the Condensate Overflow Switch
(COF) mounted on the drain pan and the ReliaTel Options
Module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit function until the overflow condition has cleared. The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes the unit to shutdown more than 2 times in a 3 day period, the unit will be locked-out of operation. A manual reset of the diagnostic system through the Zone Sensor or Building
Automation System (BAS) will be required. Cycling unit power will also clear the fault.
Clogged Filter Switch (Optional)
The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the
RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least
0.5” w.c.
The contacts will automatically open when the pressure differential across the filters decreases to approximately
0.4” w.c.
The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes. The system will continue to operate regardless of the status of the filter switch.
Please note that on units equipped with factory installed
MERV 13 filters, a clogged filter switch with different pressure settings will be installed. This switch will close when the differential pressure is approximately 0.8” w.c. and open when the differential falls to 0.7” w.c.
Compressor Disable (CPR1/2)
This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB.
If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.
If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor.
Phase Monitor
The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of
190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
Low Pressure Control ReliaTel Control
When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes.
If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICS™ if applicable, and a manual reset will be required to restart the compressor.
Discharge Line Thermostat ReliaTel
Control
The high pressure controls and discharge line thermostats are wired in series between the compressor outputs on the
RTRM and the compressor contactor coils. If the high pressure control switch or discharge line thermostat open, the RTRM senses a lack of current while calling for cooling and locks the compressor out. This is an auto reset lockout.
If the circuit is open three consecutive times when the contactor coil should be on, the RTRM sets a manual lockout for that compressor.
RT-SVX26P-EN
Power Exhaust Control (Optional)
The power exhaust fan is started whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on.
The setpoint panel is located in the return air section and is factory set at 25 percent.
Lead/Lag Control (Dual Circuit Only)
Lead/Lag is a selectable input located on the RTRM. The
RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the
RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor.
Evaporator Frost Control
This input incorporates the Frostat™ control (FOS) mounted in the indoor coil or on the suction line and can be activated by closing a field supplied contact installed in parallel with the FOS.
If this circuit is closed before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is closed for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the
FOS open.
Sensors
Note:
Zone sensor required for units configured for
Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.
Zone Sensor Module (ZSM)
(BAYSENS106*)
This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and
Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only.)
Zone Sensor Module (ZSM)
(BAYSENS108*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto). It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS075*.
Zone Sensor (BAYSENS110*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
RT-SVX26P-EN
General Information
Auto) with four system status LEDs. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor
BAYSENS075*.
Programmable Zone Sensor
(BAYSENS119*)
Programmable Night Setback: Auto or manual changeover with seven-day programming. Keyboard selection of Heat,
Cool, Fan, Auto, or On. All programmable sensors have
System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and one (1) Override program per day.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a
Trane Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, and remote temperature sensing (uncovered). Wiring procedures vary according to the particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections.
Remote Zone Sensor (BAYSENS075*)
This electronic sensor can be used with BAYSENS119*
Remote Panels. When this sensor is wired to a
BAYSENS119* Remote Panel, wiring must be 18 AWG
Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
Wireless Zone Sensor (BAYSENS050)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emergency Heat) and with On and
Auto fan settings. It is a manual or auto changeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and
Fahrenheit or Celsius temperature display. Included with the wireless zone sensor will be a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness.
9
General Information
High Temperature Sensor (BAYFRST003*)
This sensor connects to the RTRM Emergency Stop Input on the LTB and provides high limit “shutdown” of the unit.
The sensor is used to detect high temperatures due to fire in the air conditioning or ventilation ducts. The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors. The return air duct sensor
(X1310004001) is set to open at 135°F.
The supply air duct sensor (X1310004002) is set to open at
240°F. The control can be reset after the temperature has been lowered approximately 25°F below the cutout setpoint.
Thermostat (BAYSTAT150)
This thermostat is a multi-stage 3 heat/2 cool, autochangeover digital display thermostat. It is a programmable thermostat, and a 7-day programmable stat with night setback shall be available. In addition, it is wall mounted.
Thermostat (BAYSTAT151)
This thermostat is a single-stage 1 heat/1 cool, autochangeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat.
Thermostat (BAYSTAT155)
This thermostat is a multi-stage 3 heat/2 cool, auto changeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat, and it can be used for Economizer Operation.
Smoke Detector Sensor (Optional)
This sensor is only applicable on units equipped with a
RTOM. It provides high limit “shutdown” of the unit and requires a manual reset. The sensor is used to detect smoke due to fire in the air conditioning or ventilation ducts.
Notes:
•
The supply and return air smoke detectors are designed to shut off the unit if smoke is sensed in the supply air stream or return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detectors from performing it's design function.
•
Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.
•
Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature package for this unit.
In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air stream or return air stream, the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute.
Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables.
There are certain models, however, if operated at low airflow, will not develop an airflow velocity that falls within the required 500 to 4000 feet per minute range. For these models, the design airflow shall be greater than or equal to the minimum cfm specified in the table provided below.
Failure to follow these instructions will prevent the smoke detector from performing its design function.
Unit Model
Number
YHD180
Minimum Allowable Airflow with
Return Air Smoke Detector
5300 cfm
Wall Mounted Relative Humidity Sensor
(BAYSENS036*)
Field installed, wall mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option.
Humidity set points can be selected for relative humidity levels between 40 percent and 60 percent by adjusting the
DEHUMID setting on the ReliaTel Options Module; see
“RTOM—ReliaTel™ Options Module (Optional),” p. 7 .
Duct Mounted Relative Humidity Sensor
(BAYSENS037*)
Field installed, duct mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option.
Humidity set points can be selected for relative humidity levels between 40 percent and 60 percent by adjusting the
DEHUMID setting on the ReliaTel Options Module; see
“RTOM—ReliaTel™ Options Module (Optional),” p. 7 .
Human Interface - 5 Inch Color
Touchscreen (Optional)
The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features including:
10 RT-SVX26P-EN
• Data trending capabilities by means of time series graphs
• Historical alarm messages
• Real-time sensor measurements
• On board system setpoints
• USB port that enables the downloading of component runtime information as well as trended historical sensor data
• Customized reports
Unit Inspection
As soon as the unit arrives at the job site:
• Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
• Verify that the power supply complies with the unit nameplate specifications.
• Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
• Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
• If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
– Request an immediate joint inspection of the damage by the carrier and the consignee.
– Do not remove damaged material from the receiving location.
– Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
• Notify the appropriate sales representative before installing or repairing a damaged unit.
Precautionary Measures
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal
Protective Equipment (PPE) including gloves, eye protection, a NIOSH approved dust/mist respirator, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.
General Information
• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/mist respirator.
• Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
• Wash clothes separately from other clothing: rinse washer thoroughly.
• Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate
NIOSH approved respiration in these situations.
First Aid Measures
• Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
• Skin Contact - Wash affected areas gently with soap and warm water after handling.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:
• The unit is stored before it is installed; or,
• The unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes,
S/A and R/ A openings, and flue openings) from the ambient air until the unit is ready for start-up.
Note:
Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed under “Start Up,” p. 38 .
The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
Unit Clearances
Figure 1, p. 12 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.
RT-SVX26P-EN 11
Unit Dimensions
Figure 1.
Typical installation clearance for single and multiple unit applications
5' 8"
5' 0"
12 RT-SVX26P-EN
Figure 2.
Unit dimensional data for 12½ tons standard efficiency units
Unit Dimensions
DOWNFLOW CONDENSATE
DRAIN CONN 1”(25MM) NPT
1/2 NPT GAS CONNECTION
SERVICE GAUGE
PORT ACCESS
Note:
½ NPT Gas Connection
Figure 3.
Unit dimensional data for 12½ tons standard efficiency units
7/8”(22MM) DIA. HOLE
(UNIT CONTROL WIRE)
2”(51MM) DIA. HOLE
(UNIT POWER WIRE)
RT-SVX26P-EN 13
Unit Dimensions
Figure 4.
Horizontal duct dimensional data 12½ tons standard efficiency units
CLEARANCE 48”
1219 MM
CLEARANCE 60”
1524 MM
CLEARANCE 72”
1829 MM
FILTER ACCESS DOOR
HORIZONTAL UNITS
ONLY
SUPPLY
RETURN
HORIZONTAL
CONDENSATE
DRAIN CONNECTION
1.0 IN. NPT
CLEARANCE 38”
965 MM
CLEARANCE 18”
457 MM
Figure 5.
Unit dimensional data 15–25 tons standard efficiency & 12.5 tons high efficiency units
Note:
½ NPT Gas Connection
14 RT-SVX26P-EN
Figure 6.
Unit dimensional data 15–25 tons high efficiency units
Unit Dimensions
Note:
½ NPT Gas Connection
Figure 7.
Unit dimensional data 15–25 tons standard efficiency units, 12½–25 tons high efficiency units
RT-SVX26P-EN 15
Unit Dimensions
Figure 8.
Horizontal duct dimensional data 15–25 tons standard efficiency units, 12½–25 tons high efficiency units
16 RT-SVX26P-EN
Unit Weights
Table 1.
Typical unit weights and point loading data (lb)
Unit Models
YS*150G
YH*150G
YH*150G
Reheat unit
YS*155F
YS*180G
YH*180G
YH*180G
Reheat unit
YSF175F
YS*210/211G
YH*210G
YH*210G
Reheat unit
YSF200F
YS*240G
YH*240G
YH*240G
Reheat unit
YSF250F
YS*300/301G
YH*300G
YH*300 Reheat unit
Net
Weights
1448
1971
2034
2004
1838
2222
2101
2053
1894
2186
2146
2115
1977
2257
2166
2100
2020
2291
2208
A
537
680
Corner Weights (lb)
B C
381
515
225
352
D
306
423
714
642
595
665
722
651
604
670
756
673
635
719
771
669
644
734
759
487
544
497
602
508
557
511
581
512
561
515
591
514
565
529
603
539
354
396
355
453
377
409
371
427
377
411
374
430
378
412
386
432
402
478
419
390
503
494
434
409
508
500
468
454
517
503
455
461
523
508
Table 2.
Typical unit weights and point loading data (kg)
Unit Models
YS*150G
YH*150G
YH*150G
Reheat unit
YS*155F
YS*180G
YH*180G
YH*180G
Reheat unit
YSF175F
YS*210/211G
YH*210G
YH*210G
Reheat unit
YSF200F
YS*240G
YH*240G
YH*240G
Reheat unit
YSF250F
YS*300/301G
YH*300G
YH*300
Reheat unit
Net
Weights
658
894
924
911
835
1010
955
933
861
994
975
961
899
1026
985
955
918
1041
1004
A
244
308
Corner Weights (kg)
B C
173
234
102
160
D
139
192
324
292
271
302
328
296
274
305
344
306
289
327
351
304
293
334
345
222
247
226
274
231
253
232
264
233
255
234
269
234
257
541
274
254
161
180
161
206
171
186
169
194
172
187
170
196
172
187
175
196
183
217
190
177
229
225
197
186
231
227
213
206
235
229
207
209
238
231
Figure 9.
Corner weights
RT-SVX26P-EN 17
Unit Weights
Rigging
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
7.
Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit.
Figure 10.
Rigging and center of gravity data
TOP CRATING
RIGGING
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.
Refer to Figure 10, p. 18 and Table 1, p. 17 and Table 2, p. 17 for typical unit operating weights rigging before proceeding.
1.
Remove the shipping crate from around the unit. Do not remove the crating from the top of the unit.
2. Rig the unit as shown in Figure 10, p. 18 . Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown.
3. Install a lifting bar, as shown in Figure 10, p. 18 , to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet.
NOTICE:
Unit Damage!
Unit damage will occur if fork lifting is attempted once the pallet has been removed.
4. Removal of the base pallet must be completed before unit can be set. Prior to lifting the unit, remove the 6 fork pockets from the base rails and 4 wood screws from the lifting lug corners. The unit will then separate from the pallet when lifted.
5. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
6. Lift the unit and position it into place.
CENTER OF GRAVITY
LENGTH
CENTER OF
GRAVITY WIDTH
18 RT-SVX26P-EN
Installation
Foundation
WARNING
Risk of Roof Collapsing!
Confirm with a structural engineer that the roof structure is strong enough to support the combined weight of the roofcurb and the unit. Refer to “Unit
Weights,” p. 17 for typical unit and curb weights. Failure to ensure proper structural roof support could cause the roof to collapse, which could result in death or serious injury and property damage.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
Note:
For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter.
If a Curb Accessory Kit is not used: a. The ductwork can be attached directly to the factory-provided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit.
b. For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
General Unit Requirements
NOTICE:
Water Damage!
Non-factory penetrations through the base of this unit are not allowed. Any penetration in the base of the unit may affect the water tight integrity of the unit and lead to water leaks into the conditioned space. Failure to follow instructions could result in equipment and property damage.
Horizontal Units
Notes:
•
For units with optional Condensate Overflow Switch
(COF), the switch will not work properly if unit is not level or slightly sloped toward switch.
•
To assure proper condensate flow during operation the unit and the curb must be level.
If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location with a “full perimeter” support structure or a slab foundation for support. Refer to Table 1, p. 17 and Table 2, p. 17 for the unit’s operating and point loading weights when constructing a footing foundation.
If anchoring is required, anchor the unit to the slab using hold down bolts or isolators. Isolators should be installed to minimize the transmission of vibrations into the building.
For rooftop applications, if anchoring is required, anchor the unit to the roof with hold-down bolts or isolators.
Check with a roofing contractor for proper waterproofing procedures.
Ductwork
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
When attaching the ductwork to the unit, provide a water- tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork.
RT-SVX26P-EN
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual.
• Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representative.
• Verify correct model, options and voltage from nameplate.
• Verify that the installation location of the unit will provide the required clearance for proper operation.
• Assemble and install the roof curb (if applicable). Refer to the latest edition of the curb installers guide that ships with each curb kit.
• Fabricate and install ductwork; secure ductwork to curb.
• Rigging the unit.
• Set the unit onto the curb; check for levelness.
• Ensure unit-to-curb seal is tight and without buckles or cracks.
• Install and connect a condensate drain line to the evaporator drain connection.
19
Installation
Factory Installed Economizer
• Ensure the standard economizer has been pulled out into the operating position. Refer to the economizer
Installation Instructions for proper setup.
Note:
Low Leak Economizers do not pull out. Refer to Low
Leak Economizers Installation Instructions for proper setup.
• Install all access panels.
Main Electrical Power Requirements
• Verify that the power supply complies with the unit nameplate specifications.
• 208VAC units are factory wired for 230VAC. Line side wiring on TNS1 and TNS3 will need to be moved from
230V terminal to 208V terminal. Factory powered convenience outlets also need to be configured. Please see Powered Convenience Outlet Powered Option
(FIYCOPO) section of this document.
• Inspect all control panel components; tighten any loose connections.
• Connect properly sized and protected power supply wiring to a field-supplied/ installed disconnect switch and to the main power terminal block (HTB1) in the unit control panel.
• Install proper grounding wires to an earth ground.
Note:
All field-installed wiring must comply with NEC and applicable local codes.
Electric Heat Requirements
• Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
• Inspect the heater junction box and control panel; tighten any loose connections.
• Check electric heat circuits for continuity.
• Low Voltage Wiring (AC and DC) Requirements
• Install the zone thermostat, with or without switching subbase.
• Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel.
Condensate Drain Configuration
An evaporator condensate drain connection is provided on each unit. Refer to “Unit Dimensions,” p. 12 for the appropriate drain location.
A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 11 .
A condensate drain line must be connected to the P-Trap.
Pitch the drain lines at least ½-inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible doubletrap condition which could result in condensate backup due to “air lock”.
Figure 11.
Condensate trap installation
Filter Installation
Each unit ships with 2-inch filters installed. The quantity of filters is determined by unit size. Access to the filters is obtained by removing the indoor fan access panel. If included, pull on filter removal tool to remove filters.
Refer to the unit Service Facts (shipped with each unit) for filter requirements.
Note:
Do not operate the unit without filters.
Field Installed Power Wiring
An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in “Unit
Dimensions,” p. 12 . To insure that the unit’s supply power wiring is properly sized and installed, follow the guidelines outlined below.
Note:
All field installed wiring must conform to NEC guidelines as well as state and Local codes.
Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power must be within 10 percent of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Note:
If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the
National Electrical Code (NEC latest edition).
20 RT-SVX26P-EN
Installation
Main Unit Power
Figure 12.
Through the base electrical option
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Standard Wiring
The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements.
Protection devices must be sized according to the electrical data on the nameplate.
• If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National
Electrical Code (NEC latest edition).
• Location of the applicable electrical service entrance is illustrated in “Unit Dimensions,” p. 12 . Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted nonfused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat terminal block. Refer to the customer connection diagram that shipped with the unit for specific termination points.
• Provide proper grounding for the unit in accordance with local and national codes.
Optional TBUE Wiring (Through the Base
Electrical Option)
• Location of the applicable electrical service is illustrated below. Refer to the customer connection diagram that is shipped with the unit for specific termination points. The termination points, depending on the customer option selected would be a factory mounted nonfused disconnect switch (UDC) or circuit breaker (UCB).
• Provide proper grounding for the unit in accordance with local and national codes.
Field Installed Control Wiring
An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure 17, p. 24 .
Note:
All field wiring must conform to NEC guidelines as well as state and local codes.
Control Power Transformer
The 24-volt control power transformers are to be used only with the accessories called out in this manual.
Transformers rated greater than 50 Vac are equipped with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it.
The transformer is located in the control panel. The circuit breaker is located on the left side of the transformer and can be reset by pressing in on the black reset button.
RT-SVX26P-EN 21
Installation
Controls using 24 Vac
Before installing any connecting wiring, refer to “Unit
Dimensions,” p. 12 for the electrical access locations provided on the unit and Table 3, p. 22 for AC conductor sizing guidelines.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
1.
Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three
(3) ohms/conductor for the length of the run.
Note:
Resistance in excess of 3 ohms per conductor could cause component failure due to insufficient
AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring.
4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
5. Route low voltage wiring per illustrations on the next page.
Table 3.
Electromechanical thermostat 24 Vac conductors with ReliaTel™
Distance from Unit to
Control
000–460 feet
000–140 m
461–732 feet
Recommended Wire Size
18 gauge
0.75 mm
2
16 gauge
Controls using DC Analog Input/Outputs
(Standard Low Voltage Multiconductor
Wire)
Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to “Unit Dimensions,” p. 12 for the electrical access locations provided on the unit.
1.
Table 4 lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a
DC analog input\output signal to the unit.
Note:
Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls.
2. Ensure that the wiring between controls and the unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires
Table 4.
Zone sensor module wiring
Distance from Unit to
Control
0–150 feet (0–45.7 m)
151–240 feet (46–73.1 m)
241–385 feet (73.5–117.3 m)
386–610 feet (117.7–185.9 m)
611–970 feet (186.2–295.7 m)
Recommended Wire Size
22 gauge (0.33 mm
2
)
20 gauge (0.50 mm
2
)
18 gauge (0.75 mm
2
)
16 gauge (1.3 mm
2
)
14 gauge ( 2.0 mm
2
)
Figure 13.
ReliaTel™ options module
Figure 14.
ReliaTel conventional thermostat field wiring diagram
RTRM
22 RT-SVX26P-EN
Figure 15.
ReliaTel relative humidity sensor
(dehumidification option)
Figure 16.
ReliaTel humidistat (dehumidification option)
Installation
RT-SVX26P-EN 23
Installation
Figure 17.
Typical field wiring diagrams for optional controls (ReliaTel only)
BAYSENS106*
BAYSENS075*
BAYSENS108*
BAYSENS075*
BAYSENS110*
BAYSENS073* BAYSENS074*
BAYSENS119*
BAYSENS075*
ASYSTAT669A
OPTIONAL REMOTE SENSOR
CONTROL BOX
24
RTRM
LTB
TEST 1 TEST 2
RT-SVX26P-EN
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four sensors are required to accomplish space temperature averaging.
Example #1 illustrates two series circuits with two sensors in each circuit wired in parallel. The square of any number of remote sensors required. Example #2 illustrates three sensors squared in a series/parallel circuit. Example #3 illustrates the circuit required for this senor. Table 5 lists the temperature versus resistance coefficient for all sensing.
Table 5.
Temperature vs. resistance
Degrees
°F
35
40
45
50
15
20
25
30
-20
-15
-10
-5
0
5
10
75
80
85
90
55
60
65
70
95
100
°C
-9.4
-6.7
-3.8
-1.1
1.7
4.4
7.2
10.0
-28.9
-26.1
-23.3
-20.6
-17.8
-15.0
-12.2
12.8
15.6
18.3
21.1
23.9
26.7
29.4
32.2
35.0
37.8
Nominal Resistance
(K-Ohms)
54.66
46.94
40.40
34.85
30.18
26.22
22.85
19.96
170.1
143.5
121.4
103.0
87.56
74.65
63.80
17.47
15.33
13.49
11.89
10.50
9.297
8.247
7.330
6.528
5.824
RT-SVX26P-EN
Installation
25
Installation
Table 6.
Space temperature averaging examples
26 RT-SVX26P-EN
Installation
Table 7.
Gas heater operating data
Heating Input Rate—Btu/h
(a)
135,000 205,000
Minimum Supply Gas Pressure Natural/
LP
Manifold Gas Pressure
(b)
3.5” w.c./ 8.0” w.c.
-0.2” w.c
Combustion Blower Suction Pressure (1
Stage) st
-2.1 to -3.1” w.c.
-0.8 to -1.2” w.c.
(With Gas Valve Closed) (2 nd
Stage) N/A -2.1 to -3.1” w.c.
Minimum Flame Sensing Current
(c)
5.0 Microamps D.C.
Normal Sensing Current Range
Flue Gas Temperature Rise Above
Ambient
Flue Gas Content - %CO
2
Natural LP
Minimum Supply Air Temperature Across
Heat Exchanger
8.0 to 16.0 Microamps D.C.
400°F to
500°F
350°F to
475°F
8.3 to 9.5 8.0 to 9.0
9.5 to 10.5
40°F
(a) For 50 Hertz applications, multiply rated Btu/h by 83 percent.
(b) Staged gas heat units have a negative pressure gas valve. Never adjust the staged gas pressure valve to a positive pressure.
(c) A voltage reading across pens (V+) & (V-) is equatable to the flame sensing current. One volt equals one micro amp.
Figure 19.
Typical unit gas train configuration
Table 8.
Piping
Length of
Pipe (ft)
Iron Pipe Size (IPS) Inches
½” Pipe ¾” Pipe 1” Pipe 1¼” Pipe 1½” Pipe
75 -
Note:
Capacity of Pipe of Different Diameters and Lengths in Cu. Ft. Per
Hr. with Pressure Drop of 0.3" and Specific Gravity of 0.60
Table 9.
Specific gravity multipliers
Specific Gravity Multipliers
0.50 1.10
0.55 1.04
0.60 1.00
0.65 0.96
Figure 18.
Schematic diagram for field gas piping to units
Use the following checklist in conjunction with the general checklist ( “General Unit Requirements,” p. 19 ) to ensure that the unit is properly installed and ready for operation.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Check all electrical connections for tightness and
“point of termination” accuracy.
• Verify that the condenser airflow will be unobstructed.
• Verify that the condenser fan and indoor blower turn freely without rubbing and are properly tightened on the shafts.
• Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions.
• Verify that a condensate trap is installed and the piping is properly sized and pitched.
• Verify that the correct size and number of filters are in place.
• Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit.
Voltage Imbalance
Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly.
Measure each leg (phase-to-phase) of the power supply.
RT-SVX26P-EN 27
Installation
Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit.
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail.
The maximum allowable voltage imbalance is 2 percent.
Measure and record the voltage between phases 1, 2, and
3 and calculate the amount of imbalance as follows:
% Voltage Imbalance =
100 X AV - VD
AV where;
AV (Average Voltage) =
Volt 1 + Volt 2 + Volt 3
3
• V1, V2, V3 = Line Voltage Readings
• VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
221 + 230 + 227
3
= 226 Avg.
• VD (reading farthest from average) = 221
• The percentage of Imbalance equals:
100 X 226 - 221
226
= 2.2%
The 2.2 percent imbalance in this example exceeds the maximum allowable imbalance of 2.0 percent. This much imbalance between phases can equal as much as a
20 percent current imbalance with a resulting increase in motor winding temperatures that will decrease motor life.
If the voltage imbalance is over 2 percent, notify the proper agencies to correct the voltage problem before operating this equipment.
Electrical Phasing (Three Phase Motors)
The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A, B, C.
Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45
Phase Sequence Indicator and following the steps below:
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Turn the field supplied disconnect switch that provides power to the main power terminal block or to the
“Line” side of the optional factory mounted disconnect switch to the “Off” position.
• Connect the phase sequence indicator leads to the terminal block or to the “Line” side of the optional factory mounted disconnect switch as follows;
Black (phase A) to L1
Red (phase B) to L2
Yellow (phase C) to L3
• Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
• Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires.
• Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator.
Compressor Crankcase Heaters
NOTICE:
Compressors Failure!
Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors are started. This will protect the compressors from premature failure.
Each compressor can be equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil
28 RT-SVX26P-EN
temperature during the “Off” cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
Before starting the unit in the “Cooling” mode, set the system switch to the “Off” position and turn the main power disconnect to the “On” position and allow the crankcase heater to operate a minimum of 8 hours.
Before closing the main power disconnect switch, insure that the “System”selection switch is in the “Off” position and the “Fan” selection switch is in the “Auto” position.
Close the main power disconnect switch and the unit mounted disconnect switch, if applicable.
ReliaTel Controls
Upon power initialization, the RTRM performs selfdiagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system.
The Liteport LED located on the RTRM module is turned
“On” within one second of power-up if internal operation is okay.
Use one of the following “Test” procedure to bypass some time delays and to start the unit at the control panel.
Each step of unit operation can be activated individually by temporarily shorting across the “Test” terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated.
The unit can be left in any “Test” step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch.
Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the
“System” control.
Three Stage Cooling
T/YH*150, 180, 210, and 240 models have the ability to utilize three stages of cooling when the unit is controlled by a zone sensor. To enable three stages of cooling, connect wires 36BY and 36BZ.
Important:
This is only intended for HIGH EFFICIENCY,
SHORT-ORIFICE UNITS. Disconnecting these wires will disable three-stage cooling.
4 Stages of Cooling (25 Tons)
25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set (similar to variable speed).
Installation
Modulating Gas Heat 2.5:1 Turndown
(Optional)
The set-up required for equipment ordered with modulating gas heat varies based on the control system utilized. Zone sensors, LonTalk, and Comm3/4 do not require additional set-up.
24 volt control systems (thermostats) require setting the desired leaving air temperature. The heat exchanger will modulate to maintain this temperature. Use the following procedure for set-up:
1.
Locate the RTOM
2. Locate the “Discharge Air SP” or “OA CFM SP”
3. Adjust the variable resistor to match the desired leaving temperature a. Range = 50°F–150°F i. Clockwise—Increase Temperature ii. Counterclockwise—Decrease Temperature
RT-SVX26P-EN 29
Factory-Mounted Unit Options
Circuit Breaker (FIYUCB) & Unit
Disconnect (FIYUDC)
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN
power conductors to the lugs provided. Connect the ground wire to the unit ground lug.
Note:
Wire size for the length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C.
4. Route low voltage (class II), control wiring through hole in base of unit but not through high voltage conduit. Feed control wiring through bushing provided on side panel and into the flexible conduit provided in the heat section of the unit ( Figure 20 ). Route wires through loose wire ties provided in unit as in Figure 20 .
5. Tighten the wire ties. Secure the excess wire bundle under the wire ties in the outdoor section. Do not leave excess wire in the electrical enclosure. Use the unit wiring diagram to make the low voltage connections.
Figure 20.
Main power entrance for units with factory mounted disconnect or circuit breaker
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Important:
All phases of this installation must comply with NATIONAL, STATE, and LOCAL
CODES. In addition to local codes, the installation must comply with National
Electric Code - ANSI/NFPA NO. 70 LATEST
REVISION.
1.
Field connections are made by first removing all access panels on the front of the unit. Unscrew the assembly around the outside of the disconnect switch or circuit breaker. This assembly is located between the evaporator and heat section of the unit ( Figure 20, p. 30 ).
For downflow configurations, the hole in the base section is for both high and low voltage power wiring on down flow units. Horizontal units will route through the front plate located directly under the circuit breaker or disconnect panel. The hole is sized for 1 1/2" conduit.
Horizontal units will use the front plate located directly under the circuit breaker panel.
2. If the conduit required for your application is larger, remove the termination plate and connect to the larger hole using field supplied reducing washers.
3. Route the power wires and ground conductor through conduit and into the bottom of the factory installed disconnect switch or circuit breaker. Connect the
30
Wire Ties
RT-SVX26P-EN
Factory-Mounted Unit Options
Powered and Unpowered
Convenience
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Powered Convenience Outlet Powered
Option (FIYCOPO)
When the powered convenience outlet option is installed, the unit will include a dedicated transformer located in the evaporator section of the unit. Additionally, a service receptacle disconnect switch will be provided on the side wall of the evaporator section. The service receptacle switch is shipped in the OFF position.
The powered outlet comes completely wired from the factory except for 208 volt applications.
1.
For 208 volt applications, disconnect and tape the blue
230 volt wire.
2. Then connect the brown 208 volt wire.
Figure 21. Wiring schematic 12½ through 25 ton options
RT-SVX26P-EN 31
Factory-Mounted Unit Options
Unpowered Convenience Outlet
Unpowered Option (FIYCOUP)
1.
When the unpowered convenience outlet option is installed, remove the receptacle.
2. The field wiring should be routed through the hole in the base for downflow applications or front panel for horizontal applications then through holes provided in the “J” box (bottom for EMT and top for flexible conduit).
3. Connect the three (3) wires to terminals inside outlet box.
Figure 22.
Power options
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN
A - Powered
B - Powered
Return Air Smoke Detector
Pre-Requisite
Note:
The following field installation instructions apply to downflow only. Horizontal return air smoke detectors require no field installation.
When a unit is ordered with a downflow economizer and a return air smoke detector as factory installed options, the return air smoke detector cannot be completely installed because the economizer, when it is in the shipping position, is occupying the space where the return air smoke detector is to be installed.
The partial assembly and set-up required for each factory installed economizer must be completed up to the point where the barometric relief hood is to be installed into the unit. Prior to this operation, go to Step 5 of this instruction and perform the operations described there. After this is completed, the economizer installation is to be completed in its entirety as outlined in the installation guide.
Smoke Detector Installation
Important:
The shipping screw that holds the barometric relief damper must be removed before proceeding with the smoke detector installation.
After completion of the economizer installation as outlined above, proceed with the installation of the return air smoke detector as follows:
32
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
1.
Remove the smoke detector assembly from its shipping position in the indoor fan compartment. This assembly is attached with three screws to the indoor fan board near the top of the unit.
2. Remove and discard the shipping bracket from the smoke detector assembly. This is the angled piece of sheet metal that secured the smoke detector assembly to the interior parts of the unit during shipment.
3. Place the end of the smoke detector 16 inch metal exhaust tube provided into the bottom hole in the back of the smoke detector. Line up the tab in the exhaust tube with one of the slots in the detector and insert the tube until the tube can be rotated. Rotate the tube 45 degrees to lock it in place.
Figure 23.
Brackets
RT-SVX26P-EN
Factory-Mounted Unit Options
Figure 24.
Return air smoke detector for downflow units
TWO PIECE HOOD
PLASTIC ELBOW
METAL INTAKE TUBE
SMOKE DETECTOR
COPPER TUBE
(FACTORY INSTALLED)
VINYL TUBES (7-3/4 INCHES LONG)
VINYL TUBES (2 INCHES LONG)
4. Slide one 2” piece of the vinyl tubing provided onto the short smoke detector inlet tube which protrudes out of the back side of the smoke detector. Push this piece of vinyl tubing onto the inlet tube until it contacts the end of the plastic extension on the backside of the smoke detector.
5. Slide the long piece of vinyl tubing provided onto one leg of the plastic barbed elbow provided. Slide the other end of this piece of vinyl tubing with the elbow attached approximately 1” onto the end of the copper sampling tube installed in the unit’s return air opening.
Position the leg of elbow without the vinyl tubing such that it points toward the front side of the unit (directly out of the unit toward the filter access panel).
6. Mount the smoke detector assembly into the unit.
Align the smoke detector (exhaust tube down) with the holes in the outer panel of the barometric relief hood and position the smoke detector flush on the panel.
Note:
On all units there is a hole with a plastic snap bushing located on the inner vertical side of the barometric relief hood that the long exhaust tube must pass through. Be sure that the exhaust tube is aligned with this hole before positioning the smoke detector flush on the outer panel of the barometric relief hood.
7.
Secure the smoke detector to the hood with two #10-16 x 3/4’ sheet metal screws provided.
Note:
In order to perform the last part of this operation, it will be necessary to remove the barometric relief
METAL EXHAUST TUBE
(16.34 INCHES LONG)
TUBES INSTALL FROM BOTTOM,
TOP DOES NOT NEED TO BE
REMOVED FROM SMOKE DETECTOR
filter, open the barometric relief damper, and reach inside through the barometric relief outlet to access and connect the copper exhaust elbow to the smoke detector exhaust tube.
8. Connect the leg of the plastic elbow without the vinyl tubing attached that was installed in Step 5 to the smoke detector inlet tube pushing it onto the piece of vinyl tubing attached to the inlet tube.
9. Refer to Figure 25, p. 34 for wire connections of return air smoke detector to the unit wiring harness.
10. This completes the installation of the return air smoke detector. If the unit’s air filter(s) and/or barometric relief filter were removed to ease installation of the smoke detector, they need to be replaced at this time.
Airflow & Sampling
Refer to the instructions provided below regarding unit airflow to assure that the return air smoke detector will function properly.
Important:
The return air smoke detector is designed to shut off the unit if smoke is sensed in the return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Observe the following instructions to assure the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detector from performing its design function.
RT-SVX26P-EN 33
Factory-Mounted Unit Options
In order for the return air smoke detector to properly sense smoke in the return air stream, the air velocity entering the unit must be between 500 and 4000 feet per minute. Most models of equipment covered by this instruction will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables.
Certain models, however, if operated at low airflow, will not develop an air velocity that falls within the required
500 to 4000 feet per minute range. For these models, the design airflow shall be greater than or equal to the minimum specified in Table 10 .
Table 10.
Minimum allowable airflow
Unit Model Number
YSD180, YHD180
Minimum Allowable
Airflow with Return Air
Smoke Detector
5300 CFM
Notes:
•
Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes and coil cleaning, is required.
•
Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature package for this unit.
Important:
Refer to the service literature provided for testing and other information about the smoke detector or if problems are encountered.
Figure 25.
Smoke detector wiring scheme
34 RT-SVX26P-EN
Factory-Mounted Unit Options
Through the Base Gas Utility
Option
This section contains the instructions for making field connections to the Through the Base Gas Utility Option.
For gas piping, supply, and manifold pressure information see the unit installation, operation, and maintenance guide.
Field Installed Connections
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN
WARNING
Outlet Pressure Check Required!
This unit uses a negative pressure gas valve. At startup, the outlet pressure should be checked and adjusted if required to a negative -0.2 inches of water column.
Never adjust the regulator to a positive pressure.
Failure to follow instructions could result in death or serious injury or equipment damage.
4. Place the assembly through the cabinet opening as shown in Figure 27 and make the union connection to the field piping and to the gas train. Refer to the unit
IOM for checkout procedures.
Table 11.
Piping hole dimension
Model
YS*150-300, YH*150-300
Dimension
1 3/16"
Figure 26.
Through the base opening
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Important:
All phases of this installation must comply with NATIONAL, STATE, and LOCAL
CODES. In absence of local codes, the installation must conform with American
National Standard-Z223.1a- National Fuel
Gas Code Latest Revision.
1.
Field connections are made by first removing the access panel for the heat section on the front of the unit, Figure 27 .
2. The gas piping assembly ships inside this section and includes the shut-off valve, a pressure tap for testing, and the necessary unions for field connection. For through the base access, remove the factory-provided cap from the base pan opening. See Figure 26 .
3. Route field piping through this hole to the dimension shown in Table 11 .
Figure 27.
Gas piping
RT-SVX26P-EN 35
Factory-Mounted Unit Options
Air-Fi™ Wireless Communication
Interface (WCI)
When installed, the Trane Air-Fi Wireless Communication
Interface is located in the evaporator section, near the return air ductwork. The exact mounting location is dependent on the airflow configuration, cabinet size, and fresh air selection. Refer to Figure 28 through Figure 32 .
Refer to BAS-SVX40*-EN for instructions and troubleshooting procedures.
Figure 28.
WCI mounting location - YSD150
Figure 30.
WCI mounting location - Y*D180-300
Air-Fi
Figure 31.
WCI mounting location - Y*H180-300
Air-Fi
Air-Fi
Figure 29.
WCI mounting location - YSH150
Air-Fi
Figure 32.
WCI mounting location - Y*D150-300 - with low leak economizer
36
Air-Fi
RT-SVX26P-EN
Pre Start
Test Modes
There are three methods in which the “Test” mode can be cycled at LTB-Test 1 and LTB-Test 2.
1.
Step Test Mode—This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds.
For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check.
2. Resistance Test Mode—This method can be used for start-up providing a decade box for variable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals. The unit will remain in the specific test mode for approximately one hour even though the resistance is left on the test terminals.
3. Auto Test Mode—This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every
30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied “System” control method.
For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 12 .
Table 12. Service test guide for component operation
TEST
STEP MODE Fan Econ
(a)
1
Fan On
Minimum
Position
Setpoint
0%
Comp
1
Comp Heat
2 1
Heat
2 Ohm
Off Off Off Off 2.2K
4
2
3
(c)
Minimum
Ventilation
Economizer
Test Open
Cool Stage
1
On
On
On
Cool Stage
2
Reheat
Selectable
Open
Minimum
Position
On Minimum
Off
Off
On
On
(b)
(b)
On
Off
Off
Off
On
(b)
Off
Off
Off
Off
Off
Off
Off
Off
3.3K
4.7K
6.8K
5
(c)
On Off Off 33K
6
7
(c)
(c)
Heat Stage
1
Heat Stage
2
On Minimum
On Minimum
Off
Off
Off On
Off On
Off
On
10K
15K
(a) The exhaust fan will turn on anytime the economizer damper position is equal
(b) The condenser fans will operate any time a compressor is “On.”
(c) Steps for optional accessories and non-applicable modes in unit will be skipped.
RT-SVX26P-EN
Verifying Proper Air Flow (Units with Belt Drive Indoor Fan)
Much of the systems performance and reliability is closely associated with, and dependent upon having the proper airflow supplied both to the space that is being conditioned and across the evaporator coil.
The indoor fan speed is changed by opening or closing the adjustable motor sheave.
Before starting the SERVICE TEST, set the minimum position setpoint for the economizer to 0% using the setpoint potentiometer located on the Economizer Control
(ECA), if applicable.
ReliaTel Control
Using the Service Test Guide in Table 12 , momentarily jump across the Test 1 and Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test.
Once the supply fan has started, check for proper rotation.
The direction of rotation is indicated by an arrow on the fan housing.
With the fan operating properly, determine the total system airflow (cfm):
1.
Measure the actual rpm.
2. Measure the amperage at the supply fan contactor and compare it with the full load amp (FLA) rating stamped on the motor nameplate.
a. Calculate the theoretical bhp:
Actual Motor Amps
Motor Nameplate Amps
X Motor HP b. Using the fan performance tables in the unit Service
Facts, plot the actual rpm ( Step 1 ) and the bhp ( Step
2a ) to obtain the operating cfm.
3. If the required cfm is too low, (external static pressure is high causing motor horsepower output to be below table value): a. Relieve supply and/or return duct static.
b. Change indoor fan speed and repeat Step 1 and
Step 2 .
4. To increase fan rpm, loosen the pulley adjustment set screw and turn sheave clockwise.
5. To decrease fan rpm, loosen the pulley adjustment set screw and turn sheave counterclockwise.
6. If the required cfm is too high, (external static pressure is low causing motor horsepower output to be above table value), change indoor fan speed and repeat Step
1 and Step 2 .
7.
To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).
37
Start Up
Economizer Start-Up
Using the Service Test Guide in Table 12, p. 37 , momentarily jump across the Test 1 and Test 2 terminals on LTB1 one-time to start the Minimum Ventilation Test.
1.
Set the minimum position setpoint for the economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the
Economizer Control (ECA).
The economizer will drive to its minimum position setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the
SERVICE TEST is initiated.
The Exhaust Fan will start anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.
2. Verify that the dampers stroked to the minimum position.
3. Momentarily jump across the Test 1 and Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started.
4. Verify that the dampers stroked to the full open position.
5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).
Compressor Start-Up
1.
Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts.
Using the Service Test Guide in Table 12, p. 37 , continue the Service Test start-up procedure for each compressor circuit.
Momentarily jump across the Test 1 and Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired startup component Test is started.
Scroll Compressors
a. Once each compressor has started, verify that the rotation is correct. If wired correctly the suction pressure should drop and the discharge pressure should rise. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed.
b. If the electrical phasing is correct, before condemning a compressor, interchange any two leads (at the compressor Terminal block) to check the internal phasing. Refer to the following
38 illustration for the compressor terminal/phase identification. Do not allow the compressor to operate backwards for more than 5 seconds.
Operation for a period of time longer than this will result in compressor damage. Copeland (Alliance) will experience failure also. If the compressor runs backward for an extended period, the motor winding can overheat and cause the motor winding thermostat to open.
Figure 33.
Compressor terminal box
Note:
The Copeland, SSA and SPA scroll compressors for
R-410A units use Trane OIL00094. The correct oil for
Trane CSHD is Trane OIL00079 or OIL00080.
Compressor types are listed in Table 13, p. 38 . The appropriate oil charge is listed in Table 14, p. 39 .
Table 13. Compressor types
Tonnage
YS*150
YH*150
YH*150 Reheat
YS*155
YS*180
YH*180
YH*180 Reheat
YS*175
YS*210
YS*211
YH*210
YH*210 Reheat
YS*200
YS*240
YH*240
YH*240 Reheat
YS*250
YS*300
YS*301
YH*300
C1
ZP83KCE
ZP91KCE
ZP67KCE
CSHD105
CSHD110
ZP104KCE
ZP83KCE
CSHD120
CSHD110
CSHD110
ZP122KCE
CSHD089
CSHD142
CSHD155
CSHD142K*0M
CSHD120
CSHD120
CSHD161
CSHD161
ZPT122K5E
C2
ZP42K5E
ZP38K5E
ZP67KCE
SPA050
ZP54K5E
ZP49K5E
ZP83KCE
SPA044
ZP54K5E
ZP54K5E
ZP54K5E
ZP83KCE
SSA083
ZP76KCE
ZP61KCE
CSHD120
CSHD120
ZP83KCE
ZP83KCE
ZP122KCE
RT-SVX26P-EN
Table 14. POE Oil recharge amount (fl. oz.)
Model
C1
25mm/18mm
C2
25mm/18mm
YS*150
YH*150
YH*150 Reheat
YS*155
YS*180
YH*180
YH*180 Reheat
YSH210, YS*175
YS*175
YS*210
YS*211
YH*210
YH*210 Reheat
YS*240/200
YH*240
56
56
56
112/182.4
112
81
56
112/182.4
112
112
112
81
102
112
112
38
38
56
62 (62)/96
38
38
56
38 (62)/96
38 (62)
38
38
38
56
56
38
YH*240 Reheat
YS*250
112
112
112
106
YS*300
YS*301
YH*300
112
112
76
(a)
56
56
81
(a) This is the total amount for both compressors (38oz per compressor).
2. After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the
Service Facts.
3. Check system subcooling. Follow the instruction listed on the subcooling charging curve in the Service Facts.
4. Repeat Step 1 through Step 3 for each refrigerant circuit.
5. To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up proc
6. edure. Remove electro mechanical test mode connections (if applicable).
Dehumidification Option
Momentarily jump across the Test 1 and Test 2 terminals of the LTB1 until the unit enters test mode 7. ( Table 12, p. 37 )
Once the unit is in the reheat test mode, verify that the three-way valve has shifted to the reheat position and that the supply temperature rises 10°F more than when in cooling mode stage 2. Monitor the suction pressure for 15 minutes. The suction pressure should remain within 5 psi of normal cooling operation.
RT-SVX26P-EN
Start Up
Heating Start-Up
Open the main disconnect switch to shut the unit off and to reset the RTRM.
Follow the Test Guide in Table 12, p. 37 to start the unit in the heating mode. ReliaTel Control Momentarily jump across the Test 1 and Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start-up component Test is started.
Note:
At initial start-up modulating gas heat exchangers can produce a resonance that will subside after the break-in period.
Variable Air Volume Applications
(Multi-zone, Traditional VAV)
Traditional VAV Standalone Operation
If a traditional VAV unit is required to operate without ICS,
BAS, or other “front end” controller, a jumper must be placed between J6-2 and J6-4 of the RTRM to allow local standalone control.
Supply Air Temperature Control -
Occupied Cooling and Heating
The RTRM is designed to maintain a selectable supply air temperature of 40ºF to 80ºF with a +/- 3.5ºF deadband. To reduce the risk of coil freezing, it is not recommended to set the supply air temperature below 50ºF. In cooling mode, if the supply air temperature is more than 3.5ºF warmer than the selected temperature, a stage of cooling will be turned ‘on’ (if available). Also, if the supply air temperature is more than 3.5ºF cooler than the selected temperature, a stage of cooling will be turned ‘off’. At very low airflow, the unit may cycle stages ‘on’ and ‘off’ to maintain an average discharge air temperature outside the
7 degrees deadband.
If the unit has modulating gas heat, it can be made to discharge heating with VAV control. This is done by placing a contact closure across the ‘Changeover Input’ on the RTAM. While in the mode, the unit will heat to the
Supply Air Heating Setpoint +/- 3.5ºF. During low loads, or low airflow conditions, the actual temperature swing of the discharge air will likely be greater.
The RTRM utilizes a proportional and integral control scheme with the integration occurring when the supply air temperature is outside the deadband. As long as the supply air temperature is within the setpoint deadband, the system is considered to be satisfied and no staging up or down will occur.
Supply Duct Static Pressure Control
The supply duct static pressure is measured by a transducer with a 0.25 to 2.125 Vdc proportional output which corresponds to an adjustable supply duct static
39
Start Up
pressure of 0.3" w.c. to 2.5" w.c. respectively with a deadband adjustment range from 0.2" w.c. to 1.0" w.c. The setpoint is adjustable on the RTAM Static Pressure
Setpoint potentiometer or through ICS.
Example:
Supply Duct Static Setpoint = 2.0" w.c.
(RTAM) deadband = 0.2" w.c. (RTAM)
Duct Static Control Range = 1.9" w.c. to 2.1" w.c.
Figure 34.
Supply duct static pressure control
VHR Relay Output
For standalone VAV unit operation, the VHR output should be wired to drive VAV boxes to maximum position during all heating modes and unoccupied periods. The VHR contacts are shown in the de-energized position and will switch (energize) during the above mentioned operating modes.
Figure 35.
VHR relay output
Table 15. Variable air volume mode operation
System Mode
Heat
Cool
Auto
DWU Active
DWU Off
DWU Active
DWU Off
Fan “Auto” Fan “On”
DWU
2
Off
4
VAV Cooling
1
DWU
2
VAV Heating
4
VAV Cooling
1
DWU or
Cooling
1,2,3,4
VAV Cooling
1
DWU or
Cooling
1,2,3,4
VAV Cooling or
Heating
1
Off
4
Off
4
Off
Notes:
1.
If Cooling is selected the supply fan will run continuously. If VAV
Heating is activated the supply fan will run continuously.
2.
If Daytime Warmup is Activated, the supply fan will run
continuously.
3.
Auto changeover between Cooling and Daytime
Warmup depends upon the DWU initiate setpoint.
4.
The fan will be Off any time the system selection switch
is “Off”.
To configure the proper potentiometer setpoints, connect a multi-meter across the customer connection header (J7) to the pins listed in Table 16 below.
Table 16. VAV setpoints
Resistance (Ohms) DC volts
240 0.97
280
320
360
410
450
1.09
1.21
1.32
1.45
1.55
Supply Air Cooling
Setpoint (J7-3,4)
Deg F
50.37
52.30
54.24
56.09
58.18
59.80
Resistance (Ohms) DC volts
Supply Air Pressure
Setpoint (J7-1,2)
“WC”
100
350
540
730
0.45
1.30
1.75
2.11
0.30
0.98
1.49
2.00
>900 >2.38
2.5
Note:
To reduce the risk of coil freezing, it is not recommended to set the supply air temperature setpoint below 50°F.
40 RT-SVX26P-EN
Figure 36.
RTAM module
1 2
IGV - OFF OFF
VFD - ON OFF
VAV w/o IGV
OFF ON
ON ON
3 4
No Reset OFF OFF
Return Air OFF ON
Zone Temp ON OFF
Outdoor Air ON ON
Supply Air Heating
Setpoint
Static pressure setpoint
5
DWU Disable OFF
DWU Enable ON
R64
Reset setpoint
R67
Static pressure deadband For remote deadband cut this jumper
R 75
Supply air cooling setpoint
Morning warmup setpoint
Reset amount
DIP switch
1 2
ON
12345
4 5
SW1
3
SW1
Supply Air (Static) Pressure S.P.
Supply Air Cooling Setpoint
Supply Air Reset Amount
Supply Air (Static) Pressure Deadband
Morning Warmup Setpoint
Supply Air Reset Setpoint
Supply Air Heating Setpoint
R69 R63
R68
1 2 3 4 5 6 7 8 9 10 11 12 13 14
R66
Remote setpoint terminal strip
Final System Set Up
After completing all of the pre-start and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its modes through all available stages of cooling and heating), perform these final checks before leaving the unit:
• Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.
• Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone
Temperature” settings for automatic operation are correct.
• Inspect the unit for misplaced tools, hardware, and debris.
• Verify that all exterior panels including the control panel doors and condenser grilles are secured in place.
• Close the main disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block or the unit mounted disconnect switch.
RT-SVX26P-EN
Start Up
41
advertisement
Key Features
- Cooling capacity of 18 tons
- Heating capacity of 180,000 BTU/hr
- Variable-speed compressor
- Economizer
- Easy to install, operate, and maintain
- Versatile and can be used in a variety of applications