Fujitsu UTY-RVNUM Installation Manual
Fujitsu UTY-RVNUM wired remote controller offers precise temperature control and advanced features for your comfort. With its user-friendly interface and backlit display, you can easily adjust settings and monitor the status of your air conditioning system. The remote controller allows for group control, dual remote controller operation, and password protection for added convenience and security. Additionally, it provides valuable information such as error history and version details. Enjoy efficient and reliable climate control with the Fujitsu UTY-RVNUM remote controller.
विज्ञापन
विज्ञापन
REMOTE CONTROLLER (WIRED TYPE)
UTY-RVNUM
INSTALLATION MANUAL
For authorized service personnel only.
MANUEL D'INSTALLATION
Pour le personnel agréé uniquement.
MANUAL DE INSTALACIÓN
Sólo para personal de mantenimiento autorizado.
PART No. 9380222057-03
INSTALLATION MANUAL
PART No. 9380222057-03
REMOTE CONTROLLER (WIRED TYPE)
Contents
1. SAFETY PRECAUTIONS ........................................................................... 1
2. ACCESSORIES .......................................................................................... 2
3. ELECTRICAL REQUIREMENT .................................................................. 2
4. SELECTING AN INSTALLATION LOCATION
4.1. Dimensions ......................................................................................... 2
4.2. Name of parts ..................................................................................... 2
5. INSTALLING THE REMOTE CONTROLLER
5.1. Wiring .................................................................................................. 3
5.2. Connection of remote controller cable ................................................ 3
5.3. Installation ........................................................................................... 4
6. INSTALLATION METHODS
6.1. Group control ...................................................................................... 6
6.2. Dual remote controllers ....................................................................... 6
7. TURNING ON THE POWER ...................................................................... 6
8. INITIAL SETTING ....................................................................................... 6
9. SERVICE SCREEN SETTING
9.1. Test run ............................................................................................... 7
9.2. Function setting .................................................................................. 7
9.3. Error history ........................................................................................ 8
9.4. I.U. address veri fi cation ...................................................................... 8
9.5. Version ................................................................................................ 8
10. SETTING THE ROOM TEMPERATURE DETECTION LOCATION ......... 8
11. MANAGEMENT FUNCTION
11.1. Password setting ............................................................................... 9
11.2. Management setting ......................................................................... 9
12. OTHERS
12.1. Error code ....................................................................................... 10
1. SAFETY PRECAUTIONS
• The “SAFETY PRECAUTIONS” indicated in the manual contain important information pertaining to your safety. Be sure to observe them.
• For details of the operation methods, refer to the operating manual.
• Request the user to keep the manual on hand for future use, such as for relocating or repairing the unit.
• All products are manufactured to metric units and tolerances. United
States customary units are provided for reference only. In cases where exact dimensions and tolerances are required, always refer to metric units.
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING
For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
Do not turn on the power until all installation work is complete.
Perform electrical work by an authorized service personnel in accordance with the installation manual and the electrical wiring regulations or implementation regulations of the country. Improper electric work will cause electric shock or a fi re.
Perform installation work in accordance with the installation manual.
Request an authorized service personnel to perform installation work.
Do not install this unit by yourself. Improper installation will cause injury, electric shock, fi re, etc.
In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off the electrical breaker, and consult authorized service personnel.
WARNING
Do not install the unit in the following areas:
• Do not install the unit near a source of heat, steam, or fl ammable gas.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
• Area containing equipment that generates electromagnetic interference.
It will cause the control system to malfunction, preventing the unit from operating normally.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or fl ammable dust, or volatile in fl ammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a fi re.
• Install the unit in a well-ventilated place avoiding rains and direct sunlight.
Do not operate this unit when your hands are wet.
Touching the unit with wet hands will cause an electric shock.
If children may approach the unit, take preventive measures so that they cannot reach the unit.
CAUTION
When detecting the room temperature using the remote controller, please set up the remote controller according to the following conditions. If the remote controller is not well set, the correct room temperature will not be detected, and thus the abnormal conditions like “not cooled” or “not heated” will occur even if the air-conditioner is running normally.
• Locate where is not be affected by in fl ow of outside air such as caused by opening and closing a door.
• Locate where an average temperature for the room being air-conditioned will be sensed.
Temperature sensor
• Do not locate directly exposed to the outlet air from the air conditioner.
• Locate out of direct sunlight.
• Locate away from the in fl uence of other heat sources.
Do not touch the remote controller PC board and PC board parts directly with your hands.
Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables, transmission cables, and power supply cables of the indoor and outdoor units. It may cause erroneous operation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire.
Do not set the DIP switches, either on the air conditioner or the remote controller, in any way other than indicated in this manual or the manual that is supplied with the air conditioner. Doing so may result in an improper operation.
Do not touch the switches with sharp objects. Doing so will cause injury, trouble, or electric shock.
Do not expose this unit directly to water. Doing so will cause trouble, electric shock, or heating.
Do not set vessels containing a liquid on this unit. Doing so will cause heating, fi re, or electric shock.
Dispose of the packing materials safely. Tear and dispose of the plastic packing bags so that children cannot play with them. There is the danger of suffocation if children play with the original plastic bags.
En-1
2. ACCESSORIES
The following installation parts are supplied. Use them as required.
Name and Shape
Installation manual
Q’ty
This manual
Application
1
Operating manual Instruction book for operation
1
4. SELECTING AN INSTALLATION LOCATION
4.1. Dimensions
4-3/4 (120)
13/16 (21.3)
Remote controller cable
Connecting cable
Screw
(M4 × 16 mm)
Cable tie
Screw
(M4 × 14 mm)
For connecting the remote controller
1
1
For connecting the remote controller cable to the wall mounted type and the fl oor type indoor unit
For installing the remote controller
2
1
1
For remote controller and remote controller cable binding
For installing the remote controller cable to the indoor unit
1
For installing the remote controller cable to the indoor unit
1-3/16
(30)
1-5/16
(33.5)
7/8
(23)
3/8 (9)
3/16 (4.5)
Unit: in (mm)
Cable clamper
4.2. Name of parts
CAUTION
Press the button lightly with a fi nger. It may cause a failure if pressed with excessive force.
3. ELECTRICAL REQUIREMENT
When connecting the remote controller, use cable speci fi ed as follows:
Conductor size Type Remarks
Remote controller cable
0.33 mm 2
(22AWG)
Polar 3 core
Use sheathed
PVC cable
*We recommend that you purchase our service parts for the remote controller cable. Contact service personnel to purchase this.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(1) Display panel (with backlight)
(2) Screen switch button (Left)
(3) Menu button
(4) Cancel button
(5) Cursor button
(6) Screen switch button (Right)
(7) Power indicator
(8) On/Off button
(9) Enter button
-Note-
While the backlight is off by the automatic light off, the fi rst button operation does not work, and the backlight illuminates. (The On/Off button is excluded.)
While the backlight is set to [Off], it is effective from the fi rst button operation.
En-2
5. INSTALLING THE REMOTE CONTROLLER
5.1. Wiring
WARNING
Before starting installation work, turn off the power of the connection destination. Do not turn on the power again until installation is completed.
Otherwise, it will cause electric shock or fi re.
Use the accessories or speci fi ed connection cables.
Do not modify connection cables other than those speci fi ed, do not use extension cords, and do not use independent branch wiring. The allowable current will be exceeded and cause electric shock or fi re.
Install the connection cables securely to the terminal block. Con fi rm that external force is not applied to the wire. Use connection cables made of the speci fi ed wire. If intermediate connection or insertion fi xing are imperfect, it will cause electric shock, fi re, etc.
Do not connect functional earthing to a telephone functional earthing, water pipe, or conductor rod.
Always fasten the outside covering of the connection cable with the cable clamp. (If the insulator is chafed, electric leakage may occur.)
When performing cable wiring work, be sure that it does not touch the user. Doing so will cause injury or electric shock.
If any cable is damaged, do not repair or modify it yourself. Improper work will cause electric shock or fi re.
CAUTION
Do not parallel to the remote controller cables, indoor and outdoor connection cable, and power supply cables. It may cause erroneous operation.
When performing wiring work, be careful not to damage the cable or injure yourself. Also, connect the connectors securely. Loose connectors will cause trouble, heating, fi re, or electric shock.
Install the remote control cable 40 in (1 m) away from television and radio to avoid distorted images and noise.
Perform wiring so that water does not enter this unit along the external wiring. Always install a trap to the wiring or take other countermeasures.
Otherwise it will cause trouble or electric shock or fi re.
Con fi rm the name of each unit and name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual so that there is no incorrect wiring. Incorrect wiring will damage the electric parts and cause smoke and fi re.
When installing the connection cable near a source of electromagnetic waves, use shielded cable. Otherwise, a breakdown or malfunction could result.
5.2. Connection of remote controller cable
CAUTION
When connecting the remote controller cable to the wall mounted type and the fl oor type indoor unit, do not connect it to the outdoor unit or the indoor unit power terminal block. It may cause a failure.
There are 2 methods to connect the remote controller cable to the indoor unit. One is the connection using contained connecting cable and the other is the connection the remote controller cable is connected to the exclusive terminal block of the indoor unit.
Exclusive terminal block for remote controller connection method is different depending on each model. Modify the remote controller cable as per below description and connect it.
(For the details, refer to the installation manual of the indoor unit to be used.)
5.2.1 When connecting to the wall mounted type and the
fl
oor type connector
Connect the remote controller cable to the connecting cable and insert it to the connector.
Pattern 1
Connecting cable Indoor unit
Remote controller cable
Connector
PCB
Outdoor unit / power supply terminal block
Pattern 2
Connecting cable
Communication kit (option)
Indoor unit
PCB
Outdoor unit / power supply terminal block
Remote controller cable
Connector
Modify the cable as per below methods.
(1) Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. 1.
(2) Connect the remote controller cable and connecting cable as shown in
Fig. 2.
(3) Be sure to insulate the connection between the cables.
Fig. 1 Fig. 2
Connector
Wire
Remote controller cable
White
Red
Red
White
Black
Black
Insulated connection
Connecting cable
5.2.2 When connecting to the exclusive terminal block
Connect the end of remote controller cable directly to the exclusive terminal block.
M4 screw
3
2
1
Indoor unit side
Black
White
Red
Terminal block
Remote controller cable
Remote controller terminal block
Indoor unit
PCB
Outdoor unit / power supply terminal block
It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
En-3
5.3. Installation
WARNING
When installing this unit, make sure that there are no children nearby.
Otherwise, injury or electric shock could result.
CAUTION
Before opening the case of this unit, completely discharge static electricity charged on your body. Not doing so will cause trouble.
Do not touch the circuit board and circuit board parts directly with your hands. Otherwise, injury or electric shock could result.
Be careful so that the front case does not fall after the front case are removed. Otherwise, a damage of the front case could result.
To avoid incoming water or insects along the cable, always establish a trap and seal the wiring hole.
Overtighten of the screws may cause a distortion or a damage of the rear case.
Do not make any additional hole on the rear case to avoid a damage.
Do not use any other screws than the included ones. Using of other screws may cause a product malfunction or damage.
5.3.1 Installation space
• This product cannot be installed in wall.
• Recommendation installation height of the remote controller is 4.6ft. (1.4 m)
(from the fl oor surface to the bottom of the remote controller).
• Even when you install a remote controller to one of a switch box and the surface of a wall, secure the space shown in following fi gure. If spaces run short, it will become dif fi cult to remove a remote controller.
5.3.4 Installing the remote controller
A. When attaching to switch box:
(1) Seal the wiring hole of the remote controller cable.
(2) Put a remote controller cable through the hole of the rear case.
(3) Fix the rear case by securing it with attached screws (2 places).
Seal the wiring hole of the remote controller cable with putty.
Remote controller cable
Box
Trap
Rear case
Screws Trap
B. When attaching to the wall directly:
(1) Seal the wiring hole of the remote controller cable.
(2) Put a remote controller cable through the back hole of the rear case of the main body.
(3) Fix the rear case by securing it with attached screws (2 places).
Wall
Putty
Seal the wiring hole of the remote controller cable with putty.
2 (30) or more
2 (30) or more
2 (30) or more
Putty
Trap
Screws
Trap
Rear case
C. When routing the cable on-wall:
(1) Cut off the cable guide of the front case with using a knife or a nipper.
(2) Deburr the edge of the cable guide.
Cut off
9 (220) or more*
Unit: in (mm)
* Please secure enough space where a fl at screwdriver to take off a case can be inserted.
5.3.2 Processing of the remote controller cable
2-3/16 (55)
1-3/4 (45)
1-3/16 (30)
5/16
(8)
5/16
(8)
5/16 (8)
Unit: in (mm)
1. 12 V (Red)
2. Signal (White)
3. COM (Black)
5.3.3 Remove the front case
(1) Insert the fl at screwdriver and remove the front case and rear case by twisting it slightly.
Hooks (2 places) Rear case
Front case
(3) Fix the rear case by securing it with attached screws (2 places).
Remote controller cable
Epoxy putty
Screws
Rear case
Flat screwdriver
Front case
En-4
5.3.5 Connect the cable to the terminals
Terminal screw
Tightening torque
7.1 to 10.6 lbf•in (0.8 to 1.2N • m)
1. 12V (Red)
2. Signal (White)
3. COM (Black)
To avoid an excessive tension or pressure to the terminal block, fi x the remote controller cable with the cable tie properly.
Cable tie
Remote controller cable
GOOD
3/32 in.
(2 mm)
Hole for cable tie
PROHIBITED
DIP switch
No.
SW1
SW2
Switch state
OFF
Invalidity
ON
Validity
Detail
Memory backup setting
* Set to ON to use batteries for the memory backup.
If batteries are not used, the settings information stored in memory will be deleted if there is a power failure.
Dual remote controller setting
* Refer to “6.2. Dual remote controllers”.
( Factory setting)
5.3.7 Attach the front case
• Insert after adjusting upper part of front case.
• When insert the front case, do not pinch the cable.
Front case
GOOD
PROHIBITED
Click!
CAUTION
Be careful to avoid breaking the cable by over-tightening the cable tie.
When connecting the remote controller cables, do not over-tighten the screws.
5.3.6 Setting the DIP switch
CAUTION
Do not set the DIP switch of this unit except as speci fi ed in this installation manual or the operating manual supplied with the air conditioner. Please set DIP switch according to designation.
Use an insulated screwdriver to set the DIP switches.
Set SW1 on the DIP switch to ON to enable the memory backup of the settings information.
• Memory backup setting
If the SW1 is not set to ON, the settings information will be lost if there is a power failure.
* Registered information, such as that for the internal unit, is not erased even if the DIP switch is turned off.
DIP switch
ON
OFF 1 2
Front case (back side)
CAUTION
Insert the front case fi rmly. If improperly attached, it will cause the front case to fall off.
When routing the cable on top of the front case:
Seal the cable guide of the front case of the remote controller cable with an epoxy putty.
• Thickness of sheath of the remote controller cable should be thicker than 1/16 in. (1 mm) or more. Or insulate it with a cable cover thicker than 1/16 in. (1 mm) or more.
Cable cover
Epoxy putty
En-5
6. INSTALLATION METHODS
6.1. Group control
• A number of indoor units can be operated at the same time using a single remote controller.
• Some functions may become unusable, depending on the combination of the indoor units that are connected in a group.
(1) Wiring method (indoor unit to remote controller)
EXAMPLE: Single Type
Indoor unit 0 Indoor unit 1 Indoor unit 2 Indoor unit 3
1 2 3 1 2 3 1 2 3 1 2 3
7. TURNING ON THE POWER
CAUTION
Recheck the wiring. Incorrect wiring will cause trouble.
(1) Check the remote controller wiring and DIP switch settings.
(2) Install the front case.
(in 5. INSTALLING THE REMOTE CONTROLLER).
(3) Check the indoor and outdoor unit wiring and circuit board switch settings, and then turn on the indoor and outdoor units. After message
“Please wait” is displayed on the remote controller display, “Language” screen is displayed.
Please wait
Language
English
Español
Ɋɭɫɫɤɢɣ
Deutsch
Italiano
Português
OK:
Français
ǼȜȜȘȞȚțȐ
Türkçe
1 2 3
Remote controller cable
Remote controller
(2) Indoor unit address setting
Set each indoor unit address using the DIP switch of each indoor unit.
(Refer to the installation manual for the indoor unit.)
6.2. Dual remote controllers
• Field setting can be performed only on the primary unit.
• Assignment of primary unit and secondary unit is necessary. No assignment will cause an error.
• Depending on the model, some indoor units cannot be connected for dual remote controllers. (Dual remote controllers are available for the duct type, the cassette type and the ceiling type indoor unit.)
• Two separate remote controllers can be used to operate the indoor units.
• The timer and functions cannot be used on the secondary units. (For the details, refer to the operating manual.)
(1) Wiring method (indoor unit to remote controller)
Indoor unit
1 2 3
Remote controller cable
1 2 3
Primary unit
Remote controller
1 2 3
Secondary unit
(2) Remote controller DIP switch setting
Set the remote controller SW2 according to the following table.
Number of remote controllers
Primary unit
SW2
Secondary unit
SW2
1 (Normal)
2 (Dual)
OFF
OFF
–
ON
8. INITIAL SETTING
When “Language” screen is displayed, perform the initial setting as in the following procedure:
1
Select a language with the [Cursor button] on the “Language” screen displayed when the start-up is completed.
Language
English
Deutsch Français
Español
Ɋɭɫɫɤɢɣ
Italiano
Português
OK:
ǼȜȜȘȞȚțȐ
Türkçe
2
When con fi rmed by pressing the [Enter button], the “Temp. unit” screen is displayed.
Switch the unit for temperature “°C” or “°F” with [Cursor button (Up/
Down)].
When [Cancel button] is pressed, it returns to the “Language” screen.
Temp. unit
Temp. unit
°
F
OK:
Cancel:
3
(Temp. unit : Temperature unit)
When [Enter button] is pressed, the “Change display format” screen is displayed.
Set the display format of “Date format” and “Time format”.
Switch the setting item with [Cursor button (Left/Right)] and con fi rm with the [Cursor button (Up/Down)].
When [Cancel button] is pressed, it returns to the “Temp. unit” screen.
Change display format
Date format
Time format
Day/Month/Year 0:00-11:59AM/PM
Cancel: OK:
-Note-
Following display formats are available for setting.
Date format :
• Day/Month/Year
• Month/Day/Year
• Year/Month/Day
Time format:
• 0:00-23:59
• 0:00-11:59 AM/PM
• 12:00-11:59 AM/PM
When [Enter button] is pressed, the “Date” screen is displayed.
En-6
4
Set the “Day”, “Month”, and “Year”.
Switch the setting item with [Cursor button (Left/Right)], and adjust with [Cursor button (Up/Down)].
When [Cancel button] is pressed, it returns to the “Change display format” screen.
Date
Cancel:
Day
20
Monday
Month
08
OK:
Year
2012
When [Enter button] is pressed, the “Time” screen is displayed.
5
Set the “hour” and “min”.
Switch the setting item by [Cursor button (Left/Right)], and adjust with
[Cursor button (Up/Down)].
“Min” can be set quickly if the button is pressed continuously.
When [Cancel button] is pressed, it returns to the “Date” screen.
Time hour
10: min
00
AM
Cancel: OK:
6
When [Enter button] is pressed, the “Con fi rmation” screen is displayed.
When setting is completed, select “Yes” with [Cursor button (Left/
Right)], and press [Enter button].
When correcting a setting, set it again as it returns to the “Language” screen when “No” is selected and press [Enter button].
Initial setting will be ended. OK?
No Yes
9.1. Test run
• If the unit is operating, turn it off.
• Test run stops in 60 minutes.
When the [On/Off button] is pressed during the test run, the test run will be canceled.
• After completing the test run, wait enough until starting the operation.
1
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen.
If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor” screen.
Submenu
[ 1/2 ]
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Back:
Monitor
Setting:
Mo 10:00AM
Off
Off
2
Press the [Screen switch button (Left)] and [Screen switch button
(Right)] simultaneously for 5 seconds to switch to “Service” screen.
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back: Setting:
When you select [Test run] with the [Cursor button (Up/Down)] and press the
[Enter button], following con fi rmation screen is displayed.
To start the test run, select “Yes” with the [Cursor button (Left/Right)], and press the [Enter button].
In Set temp, test run is displayed.
Monitor
Mo 10:00AM
The test run will be performed. OK?
No Yes
►
Mode
Cool
Menu
Set temp.
Test run
Fan
High
9. SERVICE SCREEN SETTING
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen.
Press the [Screen switch button (Left)] and [Screen switch button (Right)] simultaneously for 5 seconds to switch to “Service” screen.
Submenu
[
1/2
]
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Back:
Monitor
Setting:
Mo 10:00AM
Off
Off
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back: Setting:
(R.C. Sensor control : Remote Controller sensor control)
(I.U.address veri fi cation : Indoor Unit address veri fi cation)
Service screen
Function name
Primary unit
Setting
Secondary unit
Test run
Function setting
Error history
I.U.address veri fi cation
Version
9.2. Function setting
This procedure changes the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. This procedure should be performed by authorized installation or service personnel only.
Perform the “Function setting” according to the installation conditions using the remote controller. (Refer to the indoor unit installation manual for details on the function numbers and setting values.)
Perform the setting during the operation is stopped.
1
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen.
If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor” screen.
Submenu
[
1/2
]
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Back:
Monitor
Setting:
Mo 10:00AM
Off
Off
2
Press the [Screen switch button (Left)] and [Screen switch button
(Right)] simultaneously for 5 seconds to switch to “Service” screen.
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back: Setting:
En-7
3
Select [Function setting] with pressing the [Cursor button (Up/Down)], and press the [Enter button].
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back: Setting:
4
Select [R.C. address] of the target indoor unit with pressing the [Cursor button (Up/Down)].
(R.C. Address : Remote Controller Address)
Function setting
Mo 10:00AM
R.C. Function Setting
address No. No.
00 00 00
Cancel: OK:
Version Error history
5
Select the [Function No.] with pressing the [Cursor button (Left/
Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)].
Function setting
Mo 10:00AM
R.C. Function Setting
address No. No.
00 00 00
Cancel: OK:
Version Error history
6
Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button
(Up/Down)],and press the [Enter button].
Function setting
Mo 10:00AM
R.C. Function Setting
address No. No.
00 00 00
Cancel: OK:
Version Error history
-Note-
“Service” screen or “Function setting” screen return to the “Submenu” screen if there is no button operation for 1 minute.
9.3. Error history
The error history can be displayed.
Select [Error history] with the [Cursor button (Up/Down)], and press the
[Enter button].
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back Setting:
Error history
[1/4 ] Mo 10:00AM
No. Date Time
Address Code
1 30/07/2012 9:00AM 00 Er 411
2 28/07/2012 8:00AM 00 Er J2u
3 13/07/2012 11:00AM 00 Er 156
4 08/07/2012 1:00PM 01 Er 141
Back:
Function set... I.U. address ...
9.5. Version
Software version of the remote controller can be displayed.
Select [Version] with the [Cursor button (Up/Down)], and press the [Enter button].
Version
Mo 10:00AM
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back Setting:
E031VXXPXXLXX
Back:
I.U. address ... Function set...
10. SETTING THE ROOM TEMPERATURE
DETECTION LOCATION
The detection location of the room temperature can be selected from the following 2 examples. Choose the detection location that is best for the installation location.
Refer to “9.2. Function setting”.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
When using this function, set “Room temperature sensor switching
(Function Number:42)” of “9.2. Function setting” to “Indoor unit(00)”.
A
Indoor unit
B. Indoor unit/remote controller setting (room temperature sensor selection)
The temperature sensor of the indoor unit and the remote controller is used to detect the room temperature.
When using this function, set “Room temperature sensor switching (Function Number:42)” of “9.2. Function setting” to “Both(01)”.
(1) Activate the sensor switching function as described in “Room temperature sensor switching (Function number: 42)”.
(2) Select either the temperature sensor on the indoor unit or the remote controller for detection. (For how to con fi gure the setting, refer to “5-5.
R.C. sensor control” in the operating manual.)
B
Indoor unit
9.4. I.U. address veri
fi
cation
The refrigerant address and the indoor unit address can be displayed.
Select [I.U. address veri fi cation] with the [Cursor button (Up/Down)], and press the [Enter button].
I.U. address verification
Mo 10:00AM Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back Setting:
R.C. Refrigerant Indoor Unit
address address address
00 00 00
Back : OK :
Error history Version
CAUTION
When selecting the “Remote controller setting”, if the detected temperature value between the temperature sensor of the indoor unit and the temperature sensor of the remote controller varies signi fi cantly, it is likely to return to the control status of temperature sensor of the indoor unit temporarily.
As the temperature sensor of remote controller detects the temperature near the wall, when there is a certain difference between the room temperature and the wall temperature, the sensor will not detect the room temperature correctly sometimes. Especially when the outer side of the wall on which the sensor is positioned is exposed to the open air, it is recommended to use the temperature sensor of the indoor unit to detect the room temperature when the indoor and outdoor temperature difference is signi fi cant.
The temperature sensor of the remote controller is not only used when there is a problem in the detection of the temperature sensor of the indoor unit.
En-8
1 ) Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
( ...Factory setting)
Setting Description
Indoor unit
Function No.
Setting No.
00
42
Both 01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller.
2 ) Setting record
Record the setting change in the following table.
Setting Description
Room temperature sensor switching
Setting No.
After completing the “Function setting”, be sure to turn off the power and turn it on again.
11. MANAGEMENT FUNCTION
Restricts the operations of following power-saving functions by non-authorized person, and helps more energy-ef fi cient operation of the system.
With the password control, only the administrator can get access to the function setting.
For the controlled functions, perform the setting change in “Management function” screen.
Settings Items:
Function
• Economy
• Set temp. auto return
• Set temp. range
Timer
• On timer
• Off timer
• Weekly timer
• Auto-off timer
(Set temp. auto return : Set temperature auto return)
(Set temp. range : Set temperature range)
For the details on each function, refer to “2-2. Setting items in Menu” in the operating manual.
11.1. Password setting
Preset value of password is “0000”
Change the password as necessary so that the setting change cannot be done by other than the administrator.
The changed password should be managed properly by the administrator.
A password (4-digit) required when setting up a Management function can be changed.
1
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen.
If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor” screen.
Submenu
[ 1/2 ]
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Back:
Monitor
Setting:
Mo 10:00AM
Off
Off
2
When [Initial] is selected in [Submenu] screen, “Initial” screen is displayed. Enter current password with the [Cursor button], and press the [Enter button].
Submenu
[
2/2
]
Mo 10:00AM
Key lock select Child lock
Initial
Management
Back: Setting:
Monitor
3
Cancel :
Select [Password setting (Management)] in the “Initial” screen, and press the [Enter button].
Initial
Mo 10:00AM
Language
Temp. unit
Password setting (Management)
English
°F
OK:
Back:
Filter sign
Setting:
Management
4
Enter current password.
With pressing the [Cursor button (Up/Down)], enter the number. When you press the [Cursor button (Right)], the cursor moves to next digit.
After you enter the 4 digits, press the [Enter button].
Password setting
Enter current password.
Mo 10:00AM
0 0 0 0
Cancel :
OK:
-Note-
When you forget a password, please push a [Menu button] and the
[Cancel button] at the same time for 3 seconds. Screen switches to
"Enter new password" screen.
5
Enter new password with same procedure in step 4.
Password setting
Enter new password.
Initial
Mo 10:00AM
Language
Temp. unit
Password setting (Management)
English
°F
0 0 0 0
Mo 10:00AM
Back:
Filter sign
Setting:
Management
11.2. Management setting
Management setting is a function that restricts the operation of some functions on this remote controller.
The functions to be restricted are set in this setting, but not in each functional setting.
Example: To restrict Economy setting to [ON]
Set to [ON] on all the other signal source except this remote controller.
1
When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen.
If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor” screen.
Submenu
[ 1/2 ]
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Back:
Monitor
Setting:
Mo 10:00AM
Off
Off
2
When [Management] is selected in [Submenu] screen, “Management” screen is displayed. Enter current password with the [Cursor button], and press the [Enter button].
Submenu
[ 2/2 ] Mo 10:00AM
Key lock select Child lock
Initial
Management
Management
Enter current password.
Mo 10:00AM
0 0 0 0
Back: Setting:
Monitor
Cancel :
Initial
OK:
Date and time
-Note-
If the entered password is not correct, message “Password is not correct” is displayed. Enter correct password.
En-9
3
When correct password is entered, “Management function” screen is displayed.
To select the function to be controlled by [Management], select [Edit] with pressing the [Cursor button (Up/Down)], and press the [Enter button].
“Management select” screen is displayed.
Management function
Edit
Back: Setting:
Mo 10:00AM
Management select
[
1/2
]
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Back: Setting:
Mo 10:00AM
-Note-
If the function you are selecting is restricted by [Management] function, following message is displayed in the operation guidance display. The message is displayed constantly during the management function is enabled.
Back:
XXXXXX
Restricted by the management function
XXXXXX
4
Select the target function with the [Cursor button (Up/Down)] and press the [Enter button]. Then the setting fi eld for the restriction setting is displayed.
Management select
[
1/2
]
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Back:
Setting:
Mo 10:00AM
Management select
[
1/2
]
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Cancel:
OK:
Mo 10:00AM
Select the setting with the [Cursor button (Up/Down)], and press the [Enter button].
Management select
[
1/2
]
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Cancel:
OK:
Mo 10:00AM
Management select
[
1/2
]
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Back:
Setting:
Mo 10:00AM
If there is another setting to be changed, you can continue the con fi guration.
Management select
[ 1/2 ] Mo 10:00AM
Economy
Set temp.auto return
Set temp.range
On timer
Off timer
Back: Setting:
To complete the setting, press the [Cancel button].
Functions marked check in “Management select” screen are listed in “Management function” screen.
Management function
Edit
Economy
Set temp. range
On timer
Mo 10:00AM
Off
Disable
Disable
Back: Setting:
5
In “Management function” screen, you can change the detailed setting on each function.
For how change the setting, refer to each function setting in
“3. FUNCTION SETTING” in the operating manual.
Management function
Edit
Economy
Set temp. range
On timer
Mo 10:00AM
Off
Disable
Disable
Back: Setting:
12. OTHERS
12.1. Error code
If an error occurs, the power indicator (green) blinks and the following display will be shown.
If “Error” is displayed, immediately stop the air conditioner operation, and consult authorized service personnel.
• When there is an error on this remote controller:
Error
Mo 10:00AM
Remote controller
Code : XXXXXX
Error code
Error code
Er 12.1
EE 1c
Contents
• Wired remote controller communication error
Er 15.4
EE 1d
• Incompatible indoor unit is connected
• Indoor unit date acquisition error
• Primary unit / Secondary unit setting error
Er CC.1
EE CC.1
• Remote controller sensor error
• When there is an error on the indoor unit:
Address number of the relevant indoor unit
Error code*
* The Error code (Er) contains a 2 digit number, a decimal point, followed by a 1 digit number.
Use the fi rst 2 digits to con fi rm the details of the error as speci fi ed in the
Installation manual of the indoor unit.
Ex) In case of “Er 51.2”
Er → “Indoor unit fan motor1 error”
Error display
OPERATION lamp
(green)
TIMER lamp
(orange)
ECO lamp
(green)
Wired remote controller
Error code
Mode DESCRIPTION
(5) (1) Indoor unit
Indoor unit fan motor1 error
En-10
डाउनलोड
विज्ञापन