Roger MCX2-BRD/MCX8-BRD Installation Guide

Add to my manuals
2 Pages

advertisement

Roger MCX2-BRD/MCX8-BRD Installation Guide | Manualzz

MCX2-BRD and MCX8-BRD Installation Manual 2020-10-05

Roger Access Control System

MCX2-BRD / MCX8-BRD Installation Manual

Firmware version: 2.0.24 and newer

Hardware version: 2.0

Document version: Rev. F

This document contains minimum information that is necessary for initial setup and installation of the device. The detailed description of configuration parameters and functionalities is specified in respective Operating Manual available at www.roger.pl

.

I

NTRODUCTION

The expander is designed to operate in RACS 5 system as peripheral device connected to RS485 bus of MC16 access controller. Factory new device is configured with default settings including ID=100 address. Before connecting to

MC16 controller, the device should be assigned with unoccupied address in range of 100-115. Programming of other parameters depends on the individual requirements and is not obligatory. Configuration of the expander with

RogerVDM requires RUD-1 interface.

C

ONFIGURATION WITH

R

OGER

VDM P

ROGRAM

Fig. 2 Connection of the expander to RUD-1 interface for firmware update

A

PPENDIX

Fig. 1 Connection of the expander to RUD-1 interface for configuration

Programming procedure with RogerVDM software:

1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to computer’s USB port.

2. Restart the device (press RESET button or switch power supply off and on).

3. Within 2-3 seconds place jumper on JP7 contacts (fig. 3 or fig. 4) and LED

PWR will pulsate quickly.

4. Start RogerVDM program, select MCX v2.x

device, v2.0

firmware version,

RS485 communication channel and serial port with RUD-1 interface.

5. Click Connect, the program will establish connection and will automatically display Configuration tab.

6. Enter unoccupied RS485 address in range of 100-115 and other settings according to requirements of specific installation.

7. Click Send to Device to update the configuration.

8. Optionally make a backup by clicking Send to File… and saving settings to file on disk.

9. Remove jumper from JP7 contacts and disconnect device from RUD-1 interface.

F

IRMWARE UPDATE

The update requires connection of expander to computer with RUD-1 interface

(fig. 2) and starting RogerVDM software. The latest firmware file is available at www.roger.pl

.

Firmware update procedure:

1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to computer’s USB port.

2. Place jumper on FDM contacts (fig. 3 or fig. 4).

3. Restart the device (press RESET button or switch power supply off and on).

4. Start RogerVDM program and in the top menu select Tools and then Update firmware .

5. In the opened window select device type, serial port with RUD-1 interface and path to firmware file (*.hex).

6. Click Update to start firmware upload with progress bar in the bottom.

7. When the update is finished, remove FDM jumper and restart the device.

Fig. 3 MCX2-BRD expander

Table 1. MCX2-BRD screw terminals

Screw terminal

+12V

Description

12VDC power supply

GND

A*

B*

IN1

Ground

RS485 bus, line A

RS485 bus, line B

IN1 input line

IN2

NC

COM

NO

IN2 input line

RELx relay output (NC)

RELx relay common terminal

RELx relay output (NO)

* In older versions of the MCX2-BRD expander, terminals A and B may be marked on the board respectively as IO1 and IO2.

Fig. 4 MCX8-BRD expander

Table 1. MCX8-BRD screw terminals

Screw terminal

+12V

Description

12VDC power supply

GND

A

B

NC

COM

Ground

RS485 bus, line A

RS485 bus, line B

RELx relay output (NC)

RELx relay common terminal

1/2

MCX2-BRD and MCX8-BRD Installation Manual 2020-10-05

NO

IN1..IN8

Current

(average)

Inputs

Certificates

RELx relay output (NO)

IN1..IN8 input line

Fig. 5 Connection of readers and expanders to MC16 access controller

Table 2. Specification

Supply voltage consumption

Nominal 12VDC, min./max. range 10-15VDC

30mA (when relays off)

Relay outputs

Distances

IP Code

Environmental class

(according to EN 50133-1)

Dimensions W x S x G

Weight

MCX2-BRD: Two (IN1, IN2)

MCX8-BRD: Eight (IN1..IN8) parametric inputs internally connected to the power supply plus (+12V) through a 15kΩ resistor, approx. 3.5V triggering level when configured as

NO or NC.

MCX2-BRD: Two relay outputs

REL1: 30VDC/1,5A

REL2: 30VDC/5A

MCX8-BRD: Eight relay outputs:

REL1..REL8: 30VDC/1.5A

Each with single NO/NC contacts.

Up to 1200 m between controller and expander

(RS485)

IP20

Class I, indoor general conditions, temperature:

+5°C to +40°C, relative humidity: 10 to 95% (no condensation)

MCX2-BRD:

MCX8-BRD:

80 x 54 x 20 mm

72 x 155 x 20 mm

MCX2-BRD:

MCX8-BRD:

CE

50g

115g

This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health. The user is obliged to deliver equipment to the designated collection points of electric and electronic waste. For detailed information on recycling, contact your local authorities, waste disposal company or point of purchase. Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment. Weight of the equipment is specified in the document.

Contact:

Roger Sp. z o. o. sp. k.

82-400 Sztum

Gościszewo 59

Tel.: +48 55 272 0132

Fax: +48 55 272 0133

Tech. support: +48 55 267 0126

E-mail: [email protected]

Web: www.roger.pl