DKS 6500 Aug 2018 - later Manual

Add to my manuals
54 Pages

advertisement

DKS 6500 Aug 2018 - later Manual | Manualzz

Installation/Owner’s Manual

Use this manual for circuit board 4405-018 Revision A or higher.

Vehicular Swing Gate Operator

6500-065-P-10-20

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area.

UL 325 August 2018 Standard

THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE/DOOR SYSTEMS TECHNICIAN ONLY.

Visit

www.doorking.com/dealer-locator

to find a professional installing and servicing dealer in your area.

Date Installed:

Installer/Company Name:

Phone Number:

Circuit Board

Serial Number and Revision Letter:

Leave manual with owner : Property owner checklist in back of manual for new installation verification

Copyright 2020 DoorKing

®

, Inc. All rights reserved.

Conforms To UL STD 325

Certified To CSA STD C22.2 # 247

Copyright 2009 DoorKing, Inc. All rights reserved.

QUICK GUIDE: DIP-Switches

See page 22 for more information about DIP-switches.

The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.

Switch Function Setting

SW 1 (Top 8 Switches)

Description

1

Primary 6500

Changes Gate

Opening

Direction

Opens

Clockwise

ON OFF

Opens

Counter-Clockwise

2

Secondary 6500

Changes Gate

Opening

Direction

3

Exit Loop Port

Output

Full Open Input

OFF

4

Auto-Close

Timer

Reverses Gate

5

6

7 and 8

External Shadow

Loop Detector

Single Operator

Dual Operators

ON

OFF

ON

7-OFF 8-OFF

Circuit

Board

Relay

7-OFF

7-ON

7-ON

8-ON

8-OFF

8-ON

ON

OFF

ON

OFF

Same as above, for secondary 6500

ONLY

.

The output wired to terminal #4 becomes the output from the exit loop detector plugged into the EXIT Loop port.

Normal Setting.

Terminal #4 is a normal full open input.

Auto-close timer is OFF. Manual input required to close gate.

Normal Setting.

Auto-close timer is ON. Adjustable from 1-23 seconds.

Normal Setting.

Input to terminal #6 and reverse loop will stop and

reverse

gate to the full open position during the

close

cycle ONLY.

Input to terminal #6 becomes a SHADOW loop input. It is only active when the gate is fully opened. (Shadow loop setting when external loop detector is used)

Normal Setting.

Switch must be OFF for single operator.

Switch must be ON when primary/secondary (dual) gates are used.

Normal Setting.

Relay activates when gate is at open limit.

(Shadow loop setting when DoorKing Plug-In loop detector is used)

Relay activates when gate is not closed.

Relay activates when gate is opening and open.

Relay activates during opening and closing cycle.

See page 22 for ALL DIP-switch definitions and typical settings.

Switch

1

Function

Gate Overlap

2

3

4

2 Quick Guide - 1

Magnetic lock

Setting

SW 2 (Bottom 4 Switches)

Description

OFF

ON

OFF

ON

OFF

OFF

Primary and secondary operators start at the same time (Normal setting for single gate operator).

The

secondary

operator will start 1.5 sec. before primary operator during

open

cycle and the

primary

operator will start 1.5 sec. before the secondary operator during the

close

cycle (Normal setting for bi-parting gate operators).

Normal Setting.

Magnetic lock is not used.

Magnetic lock is used and connected to terminals 9 and 12. See page 27 for wiring.

Normal Setting.

Switch 3

MUST

be turned

OFF

for Model 6500 operator.

Normal Setting.

Switch 4

MUST

be turned

OFF

for Model 6500 operator.

6500-065-P-10-20

See pages 27 for terminal wiring.

QUICK GUIDE: Terminal Descriptions

Open LED

4-Pin Non-Removable Terminal

Close LED

Stop LED

3

4

1

2

Open N.O.

Close N.O.

Stop N.C.

Common

Notes:

• Use a standard

4-wire

3-button control station.

DoorKing’s

3-wire

3-button control station

cannot

be used.

3-Pin with

Jumper

• When using a 3-button control station

AND

a interlock device together, #3 terminal (N.C.) must be wired in series.

Jumper on

bottom

2 pins when using

4-pin terminal.

Jumper on

top

2 pins when

NOT

using

4-pin terminal.

• See page 27 for wiring.

1

2

3

4

1477-010

3 4

UL 325

Terminal

Pages 16,17,28-30

CE

G

G

OB 7

CB

OE

8

4

2

NC NO

Relay

Contacts

20

1

2

3

4

5

8

9

6

7

10

11

12

16

17

18

19

13

14

15

20

20-Pin Main Terminal

Low Voltage Common

Full Open

24 VAC - 250 mA max.

(See note below)

Full Open

Full Open

Standard Reverse

Gate Tracker Data

Gate Tracker Busy

24 VDC Mag Lock Power

Dry Relay Contact

Dry Relay Contact

Low Voltage Common

Low Voltage Common

Entrapment Alarm

Alarm Reset

Secondary Current Sensor

Motor

Motor

DANGER

HIGH VOLTAGE!

Circuit Board Power

Circuit Board Power

6

5

4

• lf SW 1,

switch 3

is

ON

, functions as a normal full open input (Normal setting).

• lf SW 1,

switch 3

is

OFF

, input to terminal #4 becomes the output from the

EXIT loop detector plugged into the EXIT loop port. (Used for specialized functions).

SW 1

• When gate is closed, input will open gate.

• When gate is open and auto close timer SW 1, switch 4 is turned

ON

, input will re-set and hold timer.

• When gate is open and auto close timer SW 1, switch 4 is turned

OFF

, input will close gate.

• When gate is closing, input will reverse gate.

SW 1

This input ONLY functions when gate is

fully opened

or in the

closing cycle

.

• When gate is closing: SW 1,

switch 5

is

OFF,

an input to terminal #6 will stop and

reverse

and the gate to the full open position.

Note:

If the auto-close timer is

ON

, when gate reaches the open position, timer

will not

close the gate. Another input command is needed to reset and close the gate (Normal

Setting).

SW 1

• SW 1,

switch 5 ON,

an input to terminal #6

(e.g.: external loop detector connected) becomes a

SHADOW loop input. It is only active when the gate is fully opened.

9

24-volt DC magnetic lock power is provided constantly except when the gate is

opening

or

open

(Normally

Closed function). 1 Amp Max.

16

10 11

Operation of the circuit board dry relay contact is dependent on setting of SW 1,

switches 7 and 8

.

Relay contacts

can be set for

Normally Open (NO) or

Normally Closed (NC)

NO

operation.

NC

SW 1

Contact rating is

1 amp maximum at 24-volts DC.

Relay

Not Available

when using DoorKing plug-In shadow loop detector.

For dual operator applications

ONLY.

Allows the secondary reversing sensor to monitor the current flow into the secondary operator. See page

25 for more information.

Terminal #3 Note:

Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat, causing intermittent problems.

6500-065-P-10-20

Quick Guide - 2 3

SPECIFICATIONS

Use this manual for the Model 6500 operators with circuit board 4405-018 Rev A or higher ONLY.

Class of Operation

Type of Gate

Inherent Entrapment Protection Device

Model 6500 - UL325 Class I, II, III, IV

Vehicular Swing Gates Only

Inherent Reverse Sensor System (Type A)

External Entrapment Protection Device Inputs

Connection inputs for Non-contact Sensor - Photo Sensor (Type B1)

(Monitored Inputs)

Connection input for Contact Sensor - Reversing Edge (Type B2)

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists.

The operator will not run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area.

Model #

6500-380

6500-381

Type

Operator

Primary

Secondary

Horsepower - Volts

1/2 HP - 115 VAC

1/2 HP - 115 VAC

Phase

1-Phase

1-Phase

6500-384

6500-385

Primary

Secondary

1 HP - 115 VAC

1 HP - 115 VAC

1-Phase

1-Phase

Note:

208/230/460/575 VAC input voltage can be connected to the operator by installing an “Optional” High Voltage Kit on the

PRIMARY

operator

ONLY

(P/N 2600-266).

Amp

5.4

5.4

9.7

9.7

Max Gate

Weight

700 Lbs.

700 Lbs.

Max Gate

Length

18 Ft.

18 Ft.

Cycles Per

Hour

60

60

Speed

90°

12-14 Sec

12-14 Sec

800 Lbs.

800 Lbs.

22 Ft.

22 Ft.

60

60

12-14 Sec

12-14 Sec

Type of wiring to be used on ALL external devices:

A)

Type

CL2

,

CL2P

,

CL2R

, or

CL2X

.

B)

Other cable with

equivalent

or

better

electrical, mechanical, and flammability ratings.

31

5 /

8

31”

28

3

/

8

18

3 /

8

” 23

1 /

4

4

DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.

6500-065-P-10-20

6500-065-P-10-20

TABLE OF CONTENTS

QUICK GUIDES

Quick Guide: DIP-Switches

Quick Guide: Terminal Descriptions

SPECIFICATIONS

Swing Gate Requirements

ASTM F2200 Standard for Gate Construction

Important Safety Instructions

Instructions regarding intended installation:

Important Notices

UL 325 Entrapment Protection

Glossary

SECTION 1 - INSTALLATION

1.1

1.4

1.5

1.6

1.7

1.8

1.9

Underground Conduit Requirements

SECTION 2 - AC POWER TO OPERATOR(S)

2.1

2.3 Bi-Parting Gates Wiring - Dual Gate Operators

SECTION 3 - ADJUSTMENTS

3.1

3.2

3.4

3.5

4405 Circuit Board Descriptions and Adjustments

DIP-Switch Settings for 4405 Circuit Board

Inherent Reverse Sensors Adjustment

Secondary Current Sensor Adjustment

SECTION 4 - WIRING

4.3

4.4

4.5

SECTION 5 - OPERATING INSTRUCTIONS

5.1 Power and Reset Switch

5.3

Overlapping Bi-Parting Gate Operator Positions

Securing Operator to Pad

Attach Gate Bracket

Determining Arm Lengths

Installation of Warning Signs

Entrapment Protection Installation

High Voltage Wire Run

Entrapment Protection Wiring

Dual Gates Multiple Photo Sensors Wiring Sample

Loop Detector Wiring

Manual Gate Operation

SECTION 6 - MAINTENANCE AND TROUBLESHOOTING

6.1 Maintenance

6.2 Troubleshooting

6.5 Gearbox Shaft Extension Replacement

Model 6500’s Wiring Diagrams

SECTION 7 - OWNER OF THE GATE OPERATOR

7.1

7.2

7.3

7.4

Alarm Sounding and Gate WILL NOT Operate

Manual Gate Operation

Gate Operators Monthly Checkup

New Installation Checklist for Installer and Property Owner

Printable Safety Page

Quick Guide - 1

Quick Guide - 2

Previous Page

2-3

4

4

4

5

6

7

8

9-12

13

8

8

14

14

15

15

16-17

18

20

21-22

23

24

25

26

18

18

19

20

26

27

28-29

30

31

32

32

33-34

34-35

36

36

37-38

39

40

41

42-44

45

45

46

47

48

49

1

Swing Gate Requirements

This operator is intended for installation only on gates used for vehicles.

Pedestrians must be supplied with a separate access opening. For pedestrian access in the vicinity of an automated vehicular gate, separate pedestrian access shall be provided or available. The pedestrian access shall be in a location such that a pedestrian shall not come in contact with a moving vehicular gate access gate during the entire path of travel of the vehicular gate. A pedestrian gate shall not be incorporated into an automated vehicular gate panel.

Closed Gates

2

A

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists.

The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH

ENTRAPMENT AREA.

Closed Gate

If distance is greater than

4 inches

, entrapment protection is

REQUIRED

for this area.

B If distance is

less than 16 inches

, entrapment protection is

REQUIRED

for this area.

A

B

Closed Gate

With the hinge mounted on the corner of the pilaster, eliminated and entrapment protection is

NOT required

for this area.

C If bottom of gate is

4” to 16”

above the ground at

any

part of the gate’s traveling path, entrapment protection is

REQUIRED

for this area.

Not Allowed

OK

C

4 inches to 16 inches

Gates shall have smooth bottom edges, with vertical bottom edged protrusions

NOT

exceeding

0.50 inches

.

6500-065-P-10-20

Swing Gate Requirements Continued

D

Monitored Non-contact

CLOSING Sensor (Type B1)

Minimizes the potential of the gate

closing

on vehicular or other traffic that loops cannot sense.

Monitored device helps protect against entrapment when needed. See page 13 for more information.

Reverse Loop

Minimizes the potential of the gate closing when a vehicle is present.

Number and placement of loops is dependent on the application.

Moving Gate Can Cause

Serious Injury or Death

KEEP CLEAR! Gate may move at any time without prior warning.

Do not let children operate the gate or play in the gate area.

This entrance is for vehicles only.

Pedestrians must use separate entrance.

E

Warning Signs

Permanently mounted and easily visible from either side of the gate.

E

D

E

6500-065-P-10-20

Shadow Loop

Provides a hold open command to the operator only if the gate is at the full open position.

Reverse Loop

Minimizes the potential of the gate closing when a vehicle is present.

Number and placement of loops is dependent on the application.

Automatic Exit Loop

(Optional) will provide an open command to the gate operator when a vehicle is exiting the property.

Separate

Pedestrian

Walkway

Located so pedestrians cannot come in contact with the vehicular gate.

G

F

F

Monitored Non-contact

OPENING Sensor (Type B1)

Minimizes the potential of the gate

opening

on vehicular or other traffic that loops cannot sense.

Monitored device helps protect against entrapment when needed. See page 13 for more information.

G

Monitored Contact

OPEN/CLOSE Sensor (Type B2)

Minimizes the potential of the gate striking vehicular or other traffic that loops cannot sense. Monitored device helps protect against entrapment when needed. Contact sensor may be necessary on bottom of gate. See previous page and page 17.

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists.

The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH ENTRAPMENT AREA.

3

4

ASTM F2200 Standard for Gate Construction

Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for Automated Vehicular Gate Construction.

For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; or www.astm.org.

Important Safety Instructions

WARNING - To reduce the risk of injury or death:

1.

READ AND FOLLOW ALL INSTRUCTIONS.

2.

Never let children operate or play with gate controls. Keep the remote control away from children.

3.

Always keep people and objects away from gate.

NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.

4.

Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors.

After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.

5.

Use the emergency release only when the gate is not moving.

6.

KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.

7.

The entrance is for vehicles only. Pedestrians must use separate entrance.

8.

SAVE THESE INSTRUCTIONS!

Instructions regarding intended installation:

• Install the gate operator only if:

1.

The operator is appropriate for the construction of the gate and the usage class of the gate.

2.

All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet (1.83 m) above the ground to

prevent a 2 ¼ inch (57.2 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence

that the gate covers in the open position.

3.

All exposed pinch points are eliminated or guarded.

4.

Guarding is supplied for exposed rollers.

• The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian

access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate

during the entire path of travel of the vehicular gate.

• The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to

reduce the risk of entrapment. Swinging gates should not open into public access areas.

• The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not over-tighten the operator

clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.

• For gate operators utilizing Type D protection:

1.

The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.

2.

A warning placard shall be placed adjacent to the controls.

3.

An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.

4.

No other activation device shall be connected.

• Controls intended for user activation must be located at least six feet (6’) away from any moving part of the gate and where the user is prevented from

reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls should have a security feature to prevent

• The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not cause the operator to start.

• A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.

• For gate operators utilizing a non-contact sensor:

1.

See the instructions on the placement of non-contact sensors for each type of application.

2.

Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving in the opening direction.

3.

One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the perimeter reachable by a moving

gate or barrier.

• For gate operators utilizing contact sensors:

1.

One or more contact sensors shall be located where the risk of entrapment or obstruction exist, such as at the leading edge, trailing edge, and

post mounted both inside and outside of a vehicular horizontal slide gate.

2.

One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.

3.

One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.

4.

A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not

subjected to mechanical damage.

5.

A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall

be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar

obstructions. A wireless contact sensor shall function under the intended end-use conditions.

6.

One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).

• Be sure you have instructed the owner of the gate operator about safe and proper operation and testing of the gate operator.

6500-065-P-10-20

Important Notices

Vehicular gate operator products provide convenience and security. However, gate operators must use high levels of force to move gates and most people underestimate the power of these systems and do not realize the potential hazards associated with an incorrectly designed or installed system.

These hazards may include:

• Pinch points

• Entrapment areas

Reach through hazards

• Absence of entrapment protection devices

• Improperly located access controls

• Absence of vehicle protection devices

• Absence of controlled pedestrian access

In addition to these potential hazards, automated vehicular gate systems must be installed in accordance with the UL 325 Safety Standard and the ASTM

F2200 Construction Standard. Most people are unaware of, or are not familiar with, these standards. If an automated vehicular gate system is not properly designed, installed, used and maintained, serious injuries or death can result. Be sure that the installer has instructed you on the proper operation of the gate and gate operator system.

Be sure that the installer has trained you on proper and safe operation of this gate operating system and about the basic functions of the required reversing systems associated with your gate operating system and how to test them (see section 7). These include reversing loops, inherent reversing system, electric edges, photoelectric cells, or other external devices.

• This Owner’s Manual is your property. Keep it in a safe place for future reference.

• Be sure that all access control devices are installed a minimum distance of 6 feet away from the gate and gate operator, or in such a way that a

person cannot touch the gate or gate operator while using the device. If access control devices are installed in violation of these restrictions,

immediately remove the gate operator from service and contact your installing dealer.

Opening device MUST be mounted a minimum of 6 feet from the gate and

NOT accessible through the gate!

6500-065-P-10-20

• Loops and loop detectors, photo-cells or other equivalent devices must be installed to prevent the gate from closing on vehicular traffic.

• The speed limit for vehicular traffic through the gate area is 5 MPH. Install speed bumps and signs to keep vehicular traffic from speeding

through the gate area. Failure to adhere to posted speed limits can result in damage to the gate, gate operator, and to the vehicle.

• Be sure that all persons who will use the gate system are familiar with the proper use of the gate and gate operator and are familiar with the

possible hazards associated with the gate system.

• Be sure that warning signs are permanently installed on both sides of the gate in an area where they are fully visible to traffic.

• It is your responsibility to periodically check all entrapment protection devices. If any of these devices are observed to function improperly,

remove the operator from service immediately and contact your installing or servicing dealer.

• Follow the recommended maintenance schedule.

• Do not allow children to play in the area of the operator or to play with any gate-operating device.

• To remove the gate operator from service, operate the gate to the full open position and then shut off power to the operator at the service panel.

5

UL 325 Entrapment Protection

UL 325 Classifications

Authorized

Personnel ONLY

Class I - Residential

Vehicular Gate Operator

A vehicular gate operator (or system) intended for use in garages or parking areas associated with a residence of one-to four single families.

Class III - Industrial/Limited Access

Vehicular Gate Operator

A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not accessible by or intended to service the general public.

Class II

- Commercial/General Access

Vehicular Gate Operator

A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotel, garages, retail store, or other buildings accessible by or servicing the general public.

Class IV - Restricted Access

Vehicular Gate Operator

A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

6

Gate Operator Category

Horizontal Slide, Vertical Lift, Vertical Pivot Swing, Vertical Barrier (Arm)

Entrapment Protection Types A, B1*, B2* or D A, B1*, B2*, C or D

Type A

- Inherent entrapment protection system.

Type B1

- Non-contact sensor (photoelectric sensor or the equivalent).

Type B2

- Contact sensor (edge device or equivalent).

Type C

- Inherent force limiting, inherent adjustable clutch or inherent pressure relief device.

Vertical Barrier Note:

Barrier gate operators (arm) that is not intended to move toward a rigid object closer than 16 inches (406 mm) are not required to be provided with a means of entrapment protection.

Type D

- Actuating device requiring constant pressure to maintain opening or closing motion of the gate.

*

B1 and B2 means of entrapment protection must be MONITORED.

6500-065-P-10-20

Glossary

GATE

- A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passage barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.

RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I

- A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or garage or parking area associated therewith.

COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II

- A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotels, garages, retail store, or other building servicing the general public.

INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III

- A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.

RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV

- A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM)

- An operator (or system) that controls a cantilever type device (or system), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow at entrances or exits to areas such as parking garages, lots or toll areas.

VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM)

- A vehicular gate operator (or system) that controls a gate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.

VEHICULAR SWING-GATE OPERATOR (OR SYSTEM)

- A vehicular gate operator (or system) that controls a gate which moves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.

SYSTEM

- In the context of these requirements, a system refers to a group of interacting devices intended to perform a common function.

WIRED CONTROL

- A control implemented in a form of fixed physical interconnections between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.

WIRELESS CONTROL

- A control implemented in means other than fixed physical interconnections (such as radio waves or infrared beams) between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.

INHERENT ENTRAPMENT PROTECTION SYSTEM

- A system, examples being a motor current or speed sensing system, which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part of the operator.

EXTERNAL ENTRAPMENT PROTECTION DEVICE

- A device, examples being an edge sensor, a photoelectric sensor, or similar entrapment protection device, which provides protection against entrapment when activated and is not incorporated as a permanent part of an operator.

ENTRAPMENT

- The condition when an object is caught or held in a position that increases the risk of injury.

6500-065-P-10-20

7

SECTION 1 - INSTALLATION

Prior to beginning the installation of the swing gate operator, we suggest that you become familiar with the instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation is performed in an efficient and professional manner compliant with UL 325 safety and ASTM F2200 construction standards.

The proper installation of the vehicular swing gate operator is an extremely important and integral part of the overall access control system.

Check all local building ordinances and building codes prior to installing this operator. Be sure your installation is in compliance with local codes.

1.1 Underground Conduit Requirements

Primary

Operator

Position

Secondary

Operator

Position

8

DoorKing’s Primary/Secondary Interconnection Cable (Dual Operator Application Only)

(Secondary Operator AC Power and Communication wires)

External Safety Devices, Controls and P.A.M.S. Wires (Low Voltage wire insulation)

Loop Lead-In Wires (Low Voltage wire insulation)

AC Input Power (High Voltage wire insulation)

Concrete Pad

Sweeps

• The conduit requirements are for a typical slide gate operator installation (the secondary operator is shown for those

applications where a secondary operator may be used).

The conduit requirements for your application may vary from

this depending on your specific needs.

Use only sweeps for conduit bends. Do not use 90° elbows as this will make wire pulls very

difficult and can cause damage to wire insulation. DoorKing recommends using 3/4-inch conduit.

Sweep

YES

Elbow

NO

External Entrapment Protection

is

REQUIRED

(photo sensor and/or reversing edge).

• Be sure that all conduits are installed in accordance with local codes.

Never

run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.

1.2 Concrete Pad

Operator and Conduit Location

Center Line

11”

12.5” to center

9”

7”

9”

Conduit

Area

21.5” to center of conduit area

31”

CAUTION

NEVER REMOVE HUB after manual release.

Concrete pad

MUST be level.

Note: Bevel the edges of concrete pad to eliminate water puddling under the operator.

7”

Conduit

Area

9”

3.75” 3.75”

Power, Reset Box

22” Concrete Pad Width

4” minimum

Underground depth of the concrete pad is determined by soil conditions and local building codes. Reinforced concrete recommended.

22”

Conduit

6500-065-P-10-20

1.3 Installation Layouts

48" Gate Attachment Point - Gates up to 22 Ft.

Closed Gate

48”

Arm Calculations

Drive Arm

67.94” / 2 = 33.97 (round number up) =

34 inches

34”

Drive Arm

67.94”

Connecting Arm

67.94” + 17.61” - 33.97” = 51.58 (round number down) =

51.5 inches

51.5”

Connecting Arm

Note: Maximum

usable connecting arm length is 58.5 inches.

90°

Note:

Arm length is measured from center hole to center hole.

“Actual” arm length will be longer.

Measured Length

Arm

Actual Length

17.61”

3”

15”

Hinge

Closed Gate

60”

28”

22”

Arms in Open Position

37” 6”

Connecting Arm

Arms in Closed Position

Drive Arm

6500-065-P-10-20

9

10

46" Gate Attachment Point - Gates up to 22 Ft.

Closed Gate

46”

90°

Arm Calculations

Drive Arm

67.88” / 2 = 33.94 (round number up) =

34 inches

34”

Drive Arm

67.88”

Connecting Arm

67.88” + 18.38” - 33.94” = 52.32 (round number down) =

52.25 inches

52.25”

Connecting Arm

Note: Maximum

usable connecting arm length is 58.5 inches.

Note:

Arm length is measured from center hole to center hole.

“Actual” arm length will be longer.

Measured Length

Arm

Actual Length

18.38”

3”

15”

Hinge

63”

28”

22”

Arms in Open Position

36” 6”

Closed Gate

Connecting Arm

Arms in Closed Position

Drive Arm

6500-065-P-10-20

36" Gate Attachment Point - Gates up to 14 Ft.

Closed Gate

36”

90°

Arm Calculations

Drive Arm

50.99” / 2 = 25.495 (round number up) =

25.5 inches

25.5”

Drive Arm

50.99”

Connecting Arm

50.99” + 17.56” - 25.495” = 43.055 (round number down) =

43 inches

43”

Connecting Arm

Note: Maximum

usable connecting arm length is 58.5 inches.

17.56”

3”

Note:

Arm length is measured from center hole to center hole.

“Actual” arm length will be longer.

Measured Length

Arm

Actual Length

15”

Hinge

47.75”

22”

Arms in Open Position

31.5” 6”

28”

Closed Gate

Connecting Arm

Arms in Closed Position

Drive Arm

6500-065-P-10-20

11

12

28" Gate Attachment Point - Gates up to 8 Ft.

Closed Gate

28”

15”

Hinge

90°

Arm Calculations

Drive Arm

39.7” / 2 = 19.85 (round number down) =

19.75 inches

19.75”

Drive Arm

39.7”

Connecting Arm

39.7” + 17.26” - 19.85” = 37.11 (round number down) =

37 inches

37”

Connecting Arm

Note: Maximum

usable connecting arm length is 58.5 inches.

17.26”

3”

Note:

Arm length is measured from center hole to center hole.

“Actual” arm length will be longer.

Measured Length

Arm

Actual Length

39.25”

22”

Arms in Open Position

27.5” 6”

28”

Closed Gate

Connecting Arm

Arms in Closed Position

Drive Arm

6500-065-P-10-20

1.4 Overlapping Bi-Parting Gate Operator Positions

When installing overlapping gates (using a maglock to secure gates in the center or architectural overlapping design etc.), certain considerations must be taken into account or gates will

NOT

operate correctly.

The

SECONDARY

operator

OPENS

1.5 secs

BEFORE

the

primary

operator (SW2, switch 1 -

ON

) to allow the secondary operator’s gate to stay clear of the gate overlap. It is

VERY

important to install the

SECONDARY

operator on the gate that opens

FIRST

according to

YOUR

specific gate layout or gates will

NOT

operate correctly.

Overlap

This gate

MUST

open first in this example.

Interconnection Cable

See page 19.

Primary

Operator

Position

Gates Opening Inside

IMPORTANT

All loop detector, safety and access control devices are wired to the

PRIMARY operator

.

AC power is also wired to the

primary operator ONLY.

Secondary

Operator

Position

IMPORTANT

The

SECONDARY

operator

MUST

be installed on the gate that opens

FIRST

.

IMPORTANT

The distance

EACH

gate travels while cycling

MUST

be set the same (Limit sensors settings), otherwise the 1.5 second time delay may

NOT

allow the primary operator’s gate

with the overlap

to

CLOSE BEFORE

the secondary operator’s gate.

6500-065-P-10-20

13

14

1.5 Securing Operator to Pad

Permanently attach the operator to the concrete pad using six (6) 3/8” x 3” sleeve anchors (not supplied).

3/8

Sleeve Anchor

(Not supplied)

IMPORTANT:

Center mounted sleeve anchors are

REQUIRED

to prevent chassis from flexing during operation.

1.6 Attach Gate Bracket

A Release hub with release tool.

DO NOT REMOVE HUB!

B

Bolt crank arm to operator.

C

Slide elbow assembly on crank arm.

D

Bolt control arm to gate bracket.

E

Slide control arm into elbow assembly.

KEEP ARM ASSEMBLY LEVEL

.

F

Bolt gate bracket to gate.

D

Gate

Bracket

Arm assembly and gate bracket

MUST

be level for gate to function correctly.

F

Gate Bracket

D

E

Elbow

Assembly

Control Arm

B

A

C

Crank Arm

CAUTION

DO NOT REMOVE HUB!

31”

Control Arm

6500-065-P-10-20

1.7 Determining Arm Lengths

Slide elbow assembly back and fourth, manually opening and closing gate until satisfied with the gate’s 90° open and fully closed positions.

Mark and cut off excess arms. Secure arms to elbow assembly with 6 allen screws. Tighten hub and replace release tool. Install safety covers.

excess excess

1.8 Installation of Warning Signs

This DoorKing Swing Gate Operator is shipped with two warning signs. The purpose of the warning sign is to alert uninformed persons, and to remind persons familiar with the gate system, that a possible hazard exists so that appropriate action can be taken to avoid the hazard or to reduce exposure to the hazard. See page 3 for suggested mounting positions of signs.

Permanently install the supplied warning signs in locations so

that the signs are visible by persons on both sides of the gate.

• Use appropriate hardware such as wood or sheet metal screws

(not supplied) to install the warning signs.

6500-065-P-10-20

1 5

16

1.9 Entrapment Protection Installation

External Entrapment Protection Devices:

In addition to the inherent reversing sensor system, this operator has a UL 325 terminal for the connection of

photo sensors

-Type B1 and/or

reversing edges

-Type B2 entrapment protection required by UL 325 standards. Install these devices where the risk of entrapment or a safety hazard exists, examples of which are shown below and next page. Installations can vary.

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will NOT run without one or more monitored type B1 or B2 external entrapment protection devices installed in EACH entrapment area.

Close

Beam

5” or less

Typical UL Photo Sensor mounting height and distance away from gate.

Open Beam

Open Beam

UL sensor mounted just above top of operator

21”

Typical

27.5”

Max

Monitored OPEN Photo Sensor

Wall

See page 28 for UL 325 terminal wiring for a monitored photo sensor.

Wall

Monitored CLOSE Photo Sensor

Opening Gate

If the distance between an entrapment or obstruction exists less than 16” from the open gate, then entrapment protection is

REQUIRED

for this area.

Close Beam

Entrapment protection is

RECOMMENDED

for this area.

Closing Gate

Open Beam

6500-065-P-10-20

1.9 Continued

A monitored reversing edge (Type B2) or a monitored photo sensor (Type B1, see previous page)

MUST

be installed in

EACH

entrapment area or operator

WILL NOT

function.

Monitored Edge

Transmitter

OPTIONAL wireless transmitter can be used.

Receiver

MUST

monitor for the presence of the transmitter.

Monitored

Reversing

Edge

Typical Monitored Reversing Edge mounted on end of gate.

Note:

If bottom edge of gate is less than 4” or greater that 16” above the ground, then

NO

reversing edge is required on bottom of gate.

Mointored Reversing Edge Note:

Input can be wired to be active in

BOTH

directions of travel.

Reversing Edge

Potential

Entrapment

Area

Entrapment protection is

RECOMMENDED

for this area.

See page 29 for UL 325 terminal wiring for a monitored reversing edge.

If the distance between an entrapment or obstruction exists less than 16” from the open gate, then entrapment protection is

REQUIRED

for this area.

2-Wire

End-of-Line

Edge

Monitored Edge

Transmitter

OPTIONAL wireless transmitter can be used.

Receiver

MUST

monitor for the presence of the transmitter.

Typical Wireless Reversing

Edges mounted on bottom and end of gate when needed.

If the bottom of gate is greater than 4” but less than 16” above the ground

at any point in its arc of travel

, entrapment protection is

REQUIRED

for this area.

4-Wire In-Line Edge

Reversing Edges are wired in series

2-Wire End-of-Line Edge

Greater than 4” but less than 16”

6500-065-P-10-20

17

SECTION 2 - AC POWER TO OPERATOR(S)

Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.

Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements.

THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!

2.1 High Voltage Wire Run

The distance shown in the chart is measured in Feet from the operator to the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. The wire run calculations are based on a power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.

This table illustrates the high voltage AC power wire size and distance limitations for a single operator.

Model

Type

6500 1/2 HP

6500 1 HP

Voltage

Required

115

115

Amps

Required

5.4

9.7

12 AWG

180

100

Wire Size / Max Distance in Feet

10 AWG 8 AWG

290

162

485

270

6 AWG

725

405

Reduce the wire distance in half for a primary/secondary dual gate operator application

Never

run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.

“Optional” High Voltage Kit Installation Note:

When installing a high voltage kit for 208/230/460/575 VAC input power, refer to the

“high voltage AC power wire size and distance limitations”

table on the instruction sheet with the high voltage kit (P/N 2600-266) for AC power wire run limitations.

“Optional” Heater Installation Note:

When installing a heater, refer to the

“high voltage AC power wire size and distance limitations”

table on the instruction sheet with the heater kit for AC power wire run limitations.

1 8

2.2 High Voltage Terminal Connection

N

N

EN

OPEN OPE

OPE OP

115 VAC

AC Power Terminal

Chassis

Ground

CL

OS

CLOS

E

White - Neutral

Black - 115 VAC Hot

Green - Chassis Ground

Neu Hot

• Route incoming high voltage power through conduit and into the operator as shown.

High Voltage

AC Power Wire

• Be sure wiring is installed in accordance with local codes. Be sure to color code all wiring.

DANGER

HIGH VOLTAGE!

PU

SH TO

tec

O

PE

hn ici

RA

TE

e o an

us nly

High Voltage

AC Power Wire

AC POWER

ON

• It is recommended that a surge suppressor be installed on the high voltage power lines to help protect the operator and circuit board from surges and power fluctuations.

High

Voltage

Conduit

External Power

Disconnect

Switch

Note:

A

separate

power disconnect switch may be needed in your area. Check local building codes before installation.

OFF

• Secondary operator in a dual operator application gets AC power through the

8-wire interconnection cable that connects the 2 operators together. See next page.

DO NOT cycle the operator without the OPEN and CLOSE limit sensors in their specific open and close positions.

The limit sensors or the AC power switch are the only ways to STOP the operator once an open cycle has started. This could cause damage to the gate and/or operator if the gate opens too far!

EXTERNAL ENTRAPMENT PROTECTION MUST be connected or the gate operator WILL NOT function.

6500-065-P-10-20

2

1

2

3

4

4

1477-010

5

6

OB 7

CB

OE

8

CE

G

G

NC NO

20

8

9

6

7

10

11

12

13

14

1

2

3

4

5

15

16

17

18

19

20

2.2 Bi-Parting Gates Wiring - Dual Gate Operators

Connect the Primary/Secondary operators together with DoorKing’s interconnection cable as shown (Different lengths sold separately P/N 2600-75x). High voltage power and low voltage communications are supplied to the secondary operator by

DoorKing’s UL approved cable that is run in a single conduit. Two conduits (High voltage and low voltage) will need to be provided to the secondary operator when NOT using DoorKing’s UL listed, wet environment interconnection cable.

Primary Operator Control Board (4405)

• All loop detector, safety and access control devices

are wired to the primary operator.

Interconnection Cable Wiring

Primary Operator

(Red) Motor 1 High

(Blue) Motor 2 High

SW 1, switches 1 and 2 will be

opposite

each other.

Switch 6

MUST

be

ON

, see page 21.

(White) Neutral 3 High

(Purple) 24VAC 4 Low

(Yellow) Limit 5 Low

(Brown) Spare 6 Low

(Orange) Limit 7 Low

(Gray) COM 8 Low

Secondary Operator Terminal

• Secondary operator contains

NO control board.

1 2 3 4 5 6 7 8

Secondary Operator

Motor 1 High (Red)

Motor 2 High (Blue)

Neutral 3 High (White)

24VAC 4 Low (Purple)

Limit 5 Low (Yellow)

Spare 6 Low (Brown)

Limit 7 Low (Orange)

COM 8 Low (Gray)

Operator

Chassis

Ground

Conduit

CL

OS

E

N

EN

EN EN

OPE OP OP OP

1 2 3 4 5 6 7 8

Primary Operator

8-Pin

Secondary

Chassis

Ground

Interface

Terminal

et Environment)

OS

CLOSE

E

OSE

N N

EN

OPE OPE OP OPEN

Conduit

Primar

Secondary

Operator

SH

TO O

PE

use

on tec hn an ici

RAT

AC power conduit to primary operator only.

AC Power

Primary

Operator

y y/secondar

Primar inter connection cable in underground conduit.

If optional heaters are to be installed on the operators, run two power wires through the interconnection cable conduit to power the secondary operator’s heater. Refer to the instruction sheet with the heater kit for more information.

19

6500-065-P-10-20

20

SECTION 3 - ADJUSTMENTS

The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is complete.

Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then turned back on for the new setting to take effect.

3.1 4405 Circuit Board Descriptions and Adjustments

DIP-Switches

Set the DIP-switches on the circuit board to the desired setting. See switch-settings on next

2 pages.

SW 1

Single

Channel

See page 29.

9410

9409

Dual

Channel

Inherent

SW 2

Reverse Sensors

Adjust reversing sensitivity for the open

AND

close direction of the PRIMARY (single) and

SECONDARY (dual) operators,

See page 24.

Secondary Primary

Fire Dept Open

Connect ONLY emergency access controls accessible by authorized personnel (e.g., fire, police, EMS). Upon activation, alarm will sound and the operator will go into a hard shutdown after reaching the open limit. Operator must be reset to resume normal operation. See pages 27,

33-34.

Auto-Close Timer

Auto-close timer

(when turned on)

SW 1, switch 4.

SW 1

Time Delay:

Adjust from 1 sec (full counter-clockwise) to approx 23 sec

(full clockwise).

1 23

Limit

Sensors

Plug P2

Plugs

MUST

be plugged in.

P2

EXIT

LOOP

Limit

LEDs

See page

23

Power LED

POWER

Loop LEDs

REVERSE

LOOP

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

4405-018

2

3

4

1

2

1477-010

4

5

6

OB

7

CB

8

OE

CE

G

G

NC NO

20

1

2

3

4

5

9

10

11

12

6

7

8

13

14

15

16

17

18

19

20

Secondary

Interface

Terminal Plug

Primary Current Sensor

Uses a sensing coil with a given number of wire turns through it to monitor the current flow of the primary operator motor.

Factory Set:

1/2 HP Motor - 2 Turns

1 HP Motor - 1 Turn

How LEDs Function

Illuminated

LEDs

Indicates that low voltage power is being applied to the circuit board.

Input LEDs

should be OFF and will only illuminate when the input is activated.

Limit LEDs

will only illuminate when the respective limit sensor has been activated.

Loop LEDs

will only illuminate when a reverse, shadow or exit loop is activated

(Vehicle passing over a loop).

4-Pin

Non-Removable

Terminal

See pages 26 and 27.

6-Pin UL 325

Removable

Terminal and

4 DIP-Switches

See pages 16,17, 28-30.

Dry Relay Contact

N.O.

Terminals 10-11

N.C.

can be set for

Normally Open

(NO) or Normally

Closed (NC) operation by placing the relay shorting bar on the N.O. or

N.C. pins respectively.

(Standard shadow loop function, NO)

Secondary Current Sensor

Uses a sensing coil with a given number of wire turns through it to monitor the current flow of the secondary gate operator motor.

Factory Set:

1/2 HP Motor - 2 Turns

1 HP Motor - 1 Turn

See page 25.

6500-065-P-10-20

3.2 DIP-Switch Settings for 4405 Circuit Board

The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.

Switch Function Setting

SW 1 (Top 8 Switches)

Description

1

Primary 6500

Changes Gate

Opening

Direction

Opens

Clockwise

ON OFF

Opens

Counter-Clockwise

2

Secondary 6500

Changes Gate

Opening

Direction

3

Exit Loop Port

Output

Full Open Input

OFF

4

Auto-Close

Timer

Reverses Gate

5

6

7 and 8

External Shadow

Loop Detector

Single Operator

Dual Operators

ON

OFF

ON

7-OFF 8-OFF

Circuit

Board

Relay

7-OFF

7-ON

7-ON

8-ON

8-OFF

8-ON

ON

OFF

ON

OFF

Same as above, for secondary 6500

ONLY

.

The output wired to terminal #4 becomes the output from the exit loop detector plugged into the EXIT Loop port.

Normal Setting.

Terminal #4 is a normal full open input.

Auto-close timer is OFF. Manual input required to close gate.

Normal Setting.

Auto-close timer is ON. Adjustable from 1-23 seconds.

Normal Setting.

Input to terminal #6 and reverse loop will stop and

reverse

gate to the full open position during the

close

cycle ONLY.

Input to terminal #6 becomes a SHADOW loop input. It is only active when the gate is fully opened. (Shadow loop setting when external loop detector is used)

Normal Setting.

Switch must be OFF for single operator.

Switch must be ON when primary/secondary (dual) gates are used.

Normal Setting.

Relay activates when gate is at open limit.

(Shadow loop setting when DoorKing Plug-In loop detector is used)

Relay activates when gate is not closed.

Relay activates when gate is opening and open.

Relay activates during opening and closing cycle.

See next page for switch definitions and typical settings.

Switch

1

Function

Gate Overlap

2

3

4

6500-065-P-10-20

Magnetic lock

Setting

SW 2 (Bottom 4 Switches)

Description

OFF

ON

OFF

ON

OFF

OFF

Primary and secondary operators start at the same time (Normal setting for single gate operator).

The

secondary

operator will start 1.5 sec. before primary operator during

open

cycle and the

primary

operator will start 1.5 sec. before the secondary operator during the

close

cycle (Normal setting for bi-parting gate operators).

Normal Setting.

Magnetic lock is not used.

Magnetic lock is used and connected to terminals 9 and 12. See page 27 for wiring.

Normal Setting.

Switch 3

MUST

be turned

OFF

for Model 6500 operator.

Normal Setting.

Switch 4

MUST

be turned

OFF

for Model 6500 operator.

21

3.2 Continued

Switch Definitions

SW 1 (Top 8 Switches)

Typical

Settings

Switch 1

Must OPEN

the primary operator’s gate upon initial AC power up and open command. If the

FIRST

open command begins to close the gate, turn AC power off and reverse this switch.

Switch 2

Must OPEN

the secondary operator’s gate upon initial AC power up and open command. If the

FIRST

open command begins to close the gate, turn AC power off and reverse this switch. This switch will be set the opposite of switch 1 (e.g. If switch 1 is OFF, then switch 2 will be ON).

Switch 3

Determines that a device wired to terminal #4 is a normal full open command

OR

terminal #4 becomes the output from the exit loop detector that is plugged into the EXIT Loop port in the circuit board (Used for specialized functions).

Switch 4

Turns the auto-close timer on or off. Maximum time that the close timer can be set for is approximately 23 seconds.

Switch 5

OFF

setting is Standard Reverse for a

CLOSING

gate. An input to terminal #6 (e.g.: Normally Open-N.O. photo beam,

NOT

entrapment protection) gets obstructed

AND/OR

reverse loops will stop and

reverse

the gate back to the full open position. If the auto-close timer is ON, when gate reaches the open position, timer

will not

close the gate. Another input command is needed to reset and close the gate.

ON

setting allows an input to terminal #6 (e.g.: external loop detector only) to become a SHADOW loop input. It is only active when the gate is in the fully opened position.

Switch 6

Sets up the circuit board for a single gate operator or primary / secondary (dual) gate operators.

Switches 7-8

These work in conjunction with each other and determine when the relay on the board will be activated. This relay can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the gate is full open.

This relay is not available for these uses if it is being used for the DoorKing Plug-In shadow loop function.

SW 2 (Bottom 4 Switches)

Typical

Settings

22

Switch 1 When the gate overlap is

OFF

, the gate operator(s) will start the open and close cycles at the

same time

. This is the normal setting for a

single

gate operator.

Turning the gate overlap

ON

when using dual gate operators will cause the secondary operator to start the

open

cycle 1.5 seconds

before

the primary operator. The primary operator will start the

close

cycle 1.5 seconds

before

the secondary operator.

Switch 2 If a magnetic lock is not used with the gate operator, leave this switch in the OFF position. Turn this switch ON if a magnetic lock is used and connected to terminals 9 and 12. This applies magnetic lock power and logic to these terminals (NC).

Switch 3 MUST be turned OFF for the Model 6500.

Switch 4 MUST be turned OFF for the Model 6500.

6500-065-P-10-20

3.3 Limit Sensors

Magnetic Sensor

Activator

The hub

must not slip

during operation. Tighten nut to stop any slipping.

Magnetic

Close

Limit Sensor

Loosen set screw to rotate the limit sensor.

Tighten screw when finished.

CL

OS

CLOSE

E

E

N

N

HUB

OPE

OPE

OPEN

OPEN

Important Limit Sensor Adjustment Note:

It is very important

NOT

to cycle the gate operator before the limit sensors are in the correct position or it could cause damage to the gate and operator.

ONLY

turn

ON AC power

. Manually release the gate operator hub with the release tool (See page 35). Physically move the gate to the desired open position. Loosen the set screw on the

OPEN

limit sensor and slowly slide it under the magnetic sensor activator until the

OPEN

limit Sensor LED lights up on the circuit board. Tighten the set screw and repeat this process for the close gate position.

Secure the hub with the release tool and cycle the operator a few times and readjust if necessary.

Magnetic Open

Limit Sensor

CAUTION

DO NOT REMOVE HUB!

Magnetic sensor activator must be directly above the limit sensor to activate it.

Close

Note:

If P2 plug is not connected to the circuit board and AC power is turned on, alarm will sound and operator will NOT function.

Limit Sensor LEDs

P8 P2

P2

Open

Limit

Sensors

Plug

EXIT

Primary

Limit

Sensors

Secondary

Limit

Sensors

PRIMARY Operator DIP Switch OPENING Direction

Switch 1

“OFF”

Switch 1

“ON”

SW 1

Operator Opens

Counter-clockwise

SW 1

Operator Opens

Clockwise

SECONDARY Operator DIP Switch OPENING Direction

Switch 2

“OFF”

Switch 2

“ON”

EXIT

LOOP

P2

REVERSE

LOOP

POWER

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

4405-018

2

1

2

3

4

1477-010

4

5

6

CE

G

G

OB

7

CB

OE

8

NC NO

20

1

2

3

4

5

6

7

10

11

12

8

9

13

14

15

16

17

18

19

20

SW 1

Operator Opens

Counter-clockwise

6500-065-P-10-20

SW 1

Operator Opens

Clockwise

Dual Gate Operators Note:

SW 1, switch 2 will be set the opposite of SW 1, switch 1 (e.g. If switch 1 is OFF, then switch 2 will be ON).

23

3.4 Inherent Reverse Sensors Adjustment

This vehicular gate operator is equipped with an inherent adjustable reversing sensor (Type A) used as entrapment protection according to UL 325 standards.

The gate will reverse direction after “physically” encountering an obstruction in either the opening or closing gate cycle

.

If the Auto-Close Timer (DIP-switch SW 1, switch 4) is ON and the gate physically encounters an obstruction during the

CLOSING

cycle, it will reverse to the open position and

HOLD

the gate at this position (Soft shutdown condition). Another input command is needed before the gate will reset and close again.

For the reverse sensors to function correctly,

THE HUB MUST NOT SLIP

when the gate encounters an obstruction. The gate must be properly installed and work freely in both directions. A good set of roller bearing hinges is essential for proper swing gate operation.

For the reverse system to function correctly, the gate must be properly installed and work freely in both directions and

the limit sensors must be properly adjusted BEFORE adjusting the reverse sensors

. The ideal adjustment will allow the operator to move the gate through its entire travel cycle without reversing, but will reverse upon contact with an obstruction with no more than 40 Lbs of force. This force can be measured with a gate scale.

CAUTION: Keep pedestrians and vehicles clear of the gate while adjusting and testing sensors!

Note: “

Push to Operate

” button will use the

Auto-Close timer if turned ON (SW 1, switch 4

ON

).

1 Press the “

Push to Operate

” button to

OPEN

the gate.

O OPERA

TE

2 While gate is opening, slowly rotate the primary reverse sensor clockwise until the LED lights up and the gate reverses direction. Rotate the primary reverse sensor back counter-clockwise approximately 1/8 turn to decrease the sensitivity (LED will turn off).

Note: The LED will light up during the first seconds of gate travel.

Wait until it turns off before adjusting the reverse sensor.

Note: The LED will turn on briefly when AC power is turned on.

Primary

Max Min

LED

Sensitivity

3 Press the “

Push to Operate

” button and

CLOSE

the gate.

Make sure the gate closes completely. If it reverses and opens (LED will turn on), rotate the primary reverse sensor counter-clockwise a little more to decrease the

O OPERA

TE

reverse sensitivity (LED will turn off).

Cycle the gate a few times to be sure that it cycles completely in both directions, adjusting the primary sensor as necessary.

Safety Note:

The LED will remain ON after a cycling gate gets obstructed during normal operation to indicate that the reverse sensor has been tripped.

Always check the gate area for possible obstructions before putting operator back in service.

Dual Operators:

Adjust reverse sensors for each operator when dual operators have been installed.

Secondary

Note:

If the minimum or maximum reverse sensor sensitivity adjustment is reached and the

Secondary Operator

will not reverse properly, the Secondary

Operator Current Sensor’s wire turns will have to be altered.

See 3.5 Secondary Current Sensor Adjustment on the next page.

Primary

24

Test the operator reversing sensitivity:

Place an immobile object along the gate path, allowing the gate to strike it while in the

open

and

close

cycles. The gate must reverse direction after striking the object. If it does not, increase the reverse sensitivity and repeat this testing until the correct sensitivity has been achieved in

BOTH

directions. The operator will assume a soft shutdown (Hold the auto-close timer) after striking and reversing the gate which will require pressing the “

Push to Operate

” button to cycle the operator again.

6500-065-P-10-20

3.5 Secondary Current Sensor Adjustment

(Dual Gates ONLY)

The

PRIMARY

gate operator’s “secondary reversing sensor” uses a secondary current sensing device (Located only in the primary operator) to detect any obstructions “physically” encountered in the SECONDARY gate path when using dual gates.

The secondary current sensor uses a sensing coil with a given number of turns through it to monitor the current flow into the secondary operator. Each time the wire passes through the coil, it is considered a turn. The number of turns through the sensing coil is dependant on the operating voltage of the operator and the weight of the gate. In general, light weight gates may require additional turns of wire through the secondary current sensor, while heavier gates may require less turns.

CAUTION –

HIGH VOLTAGE:

Be sure power is turned OFF before changing the number of wire turns to the secondary current sensor. When you are setting the secondary reverse sensor (section 3.4 on the previous page) and reach the

MAXIMUM sensitivity

position on the reverse sensor without activating the secondary operator reversing function, add an additional turn of wire through the secondary current sensor. If you set the secondary reverse sensor to the

MINIMUM sensitivity

position and the gate will not cycle completely, reduce the number of turns through the secondary current sensor.

Sample Turns

Primary Operator

CL

OS

CLOSE

E

E

N

N

OPEN

OPEN

OPE

OPE

DANGER

HIGH VOLTAGE!

1

1 Turn

To AC power terminal.

Typical Number of Turns for

Secondary Current Sensor

Secondary Operator Model Turns

115 - 1/2 HP - Single Phase

115 - 1 HP - Single Phase

2

1

Secondary

Current

Sensor located

only

in

primary

operator.

PU SH

O

TO

tec hn

PER

us ici an

AT

E

e o nly

1 2

2 Turns

To AC power terminal.

Secondary

Operator

Reverse

Primary

Operator

AC Power

Shadow y inter connection cable

Primar y/secondar

Reverse

6500-065-P-10-20

2 5

26

SECTION 4 - WIRING

4.1 Main Terminal Description

Open LED

Close LED

Stop LED

4-Pin Non-Removable Terminal

3

4

1

2

Open N.O.

Close N.O.

Stop N.C.

Common

Notes:

• Use a standard

4-wire

3-button control station.

DoorKing’s

3-wire

3-button control station

cannot

be used.

3-Pin with

Jumper

• When using a 3-button control station

AND

a interlock device together, #3 terminal (N.C.) must be wired in series.

Jumper on

bottom

2 pins when using

4-pin terminal.

Jumper on

top

2 pins when

NOT

using

4-pin terminal.

• See next page for wiring.

4

• lf SW 1,

switch 3

is

ON

, functions as a normal full open input (Normal setting).

• lf SW 1,

switch 3

is

OFF

, input to terminal #4 becomes the output from the

EXIT loop detector plugged into the EXIT loop port. (Used for specialized functions).

SW 1

• When gate is closed, input will open gate.

• When gate is open and auto close timer SW 1, switch 4 is turned

ON

, input will re-set and hold timer.

• When gate is open and auto close timer SW 1, switch 4 is turned

OFF

, input will close gate.

• When gate is closing, input will reverse gate.

SW 1

1

2

3

4

1477-010

UL 325

Terminal

Pages 16,17,28-30

5

OB

7

CB

OE

8

CE

G

G

4

2

NC NO

Relay

Contacts

20

1

2

3

4

5

10

11

8

9

6

7

15

16

17

18

19

20

12

13

14

20-Pin Main Terminal

Low Voltage Common

Full Open

24 VAC - 250 mA max.

(See note below)

Full Open

Full Open

Standard Reverse

Gate Tracker Data

Gate Tracker Busy

24 VDC Mag Lock Power

Dry Relay Contact

Dry Relay Contact

Low Voltage Common

Low Voltage Common

Entrapment Alarm

Alarm Reset

Secondary Current Sensor

Motor

Motor

DANGER

HIGH VOLTAGE!

Circuit Board Power

Circuit Board Power

Terminal #3 Note:

Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat, causing intermittent problems.

6

5

16

9

This input ONLY functions when gate is

fully opened

or in the

closing cycle

.

• When gate is closing: SW 1,

switch 5

is

OFF,

an input to terminal #6 will stop and

reverse

and the gate to the full open position.

Note:

If the auto-close timer is

ON

, when gate reaches the open position, timer

will not

close the gate. Another input command is needed to reset and close the gate (Normal

Setting).

SW 1

• SW 1,

switch 5 ON,

an input to terminal #6

(e.g.: external loop detector connected) becomes a

SHADOW loop input. It is only active when the gate is fully opened.

10 11

24-volt DC magnetic lock power is provided constantly except when the gate is

opening

or

open

(Normally

Closed function). 1 Amp Max.

Operation of the circuit board dry relay contact is dependent on setting of SW 1,

switches 7 and 8

.

Relay contacts

can be set for

Normally Open (NO) or

Normally Closed (NC) operation.

NC

NO

SW 1

Contact rating is

1 amp maximum at 24-volts DC.

Relay

Not Available

when using DoorKing plug-In shadow loop detector.

For dual operator applications

ONLY.

Allows the secondary reversing sensor to monitor the current flow into the secondary operator. See page

25 for more information.

6500-065-P-10-20

4.2 Control Wiring

Power is limited to 250 mA

24 Volt

Relay

Com

Fire Dept Open

Gate will

ONLY OPEN

when this device is activated by authorized personnel ONLY (fire, police, EMS) and operator has power. Alarm will sound during entire open cycle. Operator will then go into a hard shutdown once fully opened. Operator

MUST

be reset to function normally again. This device

MUST

be mounted in the line-of-site of gate so authorized personnel can monitor gate movement.

3-Pin Remote

Terminal

Activation Note:

Activation of this device will

OPEN

gate regardless of the status of the open direction monitored external entrapment protection device(s). If gate is opening, and the operator’s

inherent

entrapment protection system detects an obstruction, the operator will reverse approx. 2 inches and

4-Pin Non-Removable Terminal go into a hard shutdown.

Operator reset button

MUST

be pushed to function again

OR

cycle operator’s power.

3-Pin With

Jumper

3-Button Control Station

Use a standard

4-wire

3-button control station. DoorKing’s

3-wire

3-button control station

CANNOT be used.

Normally Closed Interlock Switch

Operator Cycling

N.C.

Com

N.O.

Lock Engaged

Place jumper on bottom

2 pins when using 4-pin terminal.

#1 Open N.O.

#2 Close N.O.

#3 Stop N.C.

OPEN

CLOS

E

STOP

Note:

When using 3-button control station

AND

interlock switch together,

#3 terminal

(N.C.) must be wired in series.

Operator Stopped

N.C.

N.O.

Com

Lock Disengaged

#4 Com

Supplied

Wire Harness

To #3 Stop N.C.

To #4 Com

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

UL 325 Terminal

See next page.

4405-018

Com

1

Radio

Open

2

2

24VAC

3

1

2

3

4

1477-010

4

Safety

Open

4

Access

Device

Open

5

OB

CB

7

OE

8

CE

G

G

5

6

Std

Reverse

6

Gate

Tracker

7

Gate

Tracker

24VDC

8

9

10

NC NO

11

Com

12

20

Com

13

14

15

16

17

18

19

20

Terminal #3 Note:

Exceeding 250 mA of power from this terminal may cause the circuit board transformer to overheat, causing intermittent problems.

#5 Normally Open

#9 Normally Close

Type of wiring to be used on ALL external devices:

A)

Type

CL2

,

CL2P

,

CL2R

, or

CL2X

.

B)

Other cable with

equivalent

or

better

electrical, mechanical, and flammability ratings.

24 Volt

1 amp max.

Quad Box

Shown

Magnetic Lock

Power (24-Volt DC) and logic output. Power is shut off .5 sec. prior to gate starting and remains off while gate is opening and in the open position.

SW 2, switch 2

ON

.

SW 2

Stand-Alone

Keypad

Stand-Alone

Card Reader

Gate Tracker

-

DoorKing Access Control System (Model 1833,

1835, 1837 or 1838) tracker system can be connected. This system can keep track of gate operator cycle count, shorted inputs, loop detector problems, any forced entry attempts, if the gate has struck anything during the open or close cycle, power interruptions, etc. For more detailed information refer to the

Tracker Installation and Wiring Manual, DoorKing P/N 2358-065.

CL

OS

CLOSE

E E

N

N

OPE OPE OPEN OPEN

PU SH

TO O

tec hn an ici

TE

PE RA

us e o nly

(2) Two 115 VAC

Convenience Outlets on Primary Operator ONLY

#5 - Access Control

Devices

Telephone

Entry

Stand-Alone

Key Switch

3-Wire

Radio

Receiver

Important:

Controls intended for user activation must be located at least six (6) feet away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls.

Emergency access controls only accessible by authorized personnel (e.g., fire, police,

EMS) may be placed at any location in the line-of-sight of the gate.

Note: All stand-alone and telephone entry devices must use a separate power source.

6500-065-P-10-20

27

4.3 Entrapment Protection Wiring

External Entrapment Protection Devices:

In addition to the inherent reversing sensor system, this operator has a UL 325 terminal for the connection of

photo sensors

-Type B1 and/or

reversing edges

-Type B2 entrapment protection required by UL 325 standards. Install these devices where the risk of entrapment or a safety hazard exists. Installations can vary.

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will NOT run without one or more monitored type B1 or B2 external entrapment protection devices installed in EACH entrapment area.

EXIT

LOOP

P2

REVERSE

LOOP

POWER

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

4405-018

2

3

4

1

2

1477-010

4

5

6

CE

G

G

OB

7

CB

OE

8

NC NO

20

1

4

5

6

7

8

2

3

9

10

11

12

16

17

18

19

20

13

14

15

UL 325 DIP-Switches

ON

DIP-switches

MUST

be turned

ON

for each device wired to terminal.

1 2 3 4

6-Pin UL 325 Terminal

Connect

ONLY MONITORED

Devices

1

4

5

2

3

6

OB OPEN Beam (Switch 1)

CB CLOSE Beam (Switch 2)

OE OPEN Edge (Switch 3)

G

G

CE CLOSE Edge (Switch 4)

Ground (Common)

Ground (Common)

Sensor LEDs Note:

LED ON:

Connected device has been activated.

LED remains off during normal operation.

LED Flashing:

Connected device is in fault.

Wiring to device is bad.

Mointored Device Note:

Only 1 monitored Device can be connected to each input. An

OPTIONAL

Expansion

Kit (sold separately) will allow connection for additional devices.

Type of wiring to be used on ALL external devices:

A)

Type

CL2

,

CL2P

,

CL2R

, or

CL2X

.

B)

Other cable with

equivalent

or

better

electrical, mechanical, and flammability ratings.

Monitored CLOSE Photo Sensor

CLOSE Beam

Entrapment protection is

RECOMMENDED

for this area.

CL

OS

E

E

E

E

N N

OPEN OPEN OPE OPE

PUS

TO

H

O

PE

tec hn an ici

us e o nly

(2) Two 115 VAC

Convenience Outlets on Primary Operator ONLY.

UL 325 DIP-Switches

ON

DIP-switches 1 & 2

MUST

be turned

ON

.

1 2 3 4

OB OPEN Beam

CB

CLOSE Beam

OE

CE

G

G

Ground (Common)

Ground (Common)

UL 325 Terminal

Note:

Only 1 monitored device can be connected to each input.

An

OPTIONAL

Expansion Kit

(sold separately) will allow connection for additional devices.

2 8

IMPORTANT:

Monitored Photo and

Edge sensors must be end-of-line resistive types. See specific manufacturer's wiring manual for more information.

If the distance between an entrapment or obstruction exists less than 16” from the open gate, then entrapment protection is

REQUIRED

for this area.

OPEN Beam

Monitored OPEN Photo Sensor

6500-065-P-10-20

29

4.3 Entrapment Protection Wiring Continued

EXIT

LOOP

P2

REVERSE

LOOP

POWER

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

2

1

2

3

4

1477-010

4

5

6

CE

G

G

OB

7

CB

OE

8

NC NO

24 VAC

Main Terminal

#3 Note:

Exceeding the mA of power from this terminal may cause the circuit board transformer to overheat, causing intermittent problems.

Type of wiring to be used on ALL external devices:

A)

Type

CL2

,

CL2P

,

CL2R

, or

CL2X

.

B)

Other cable with

equivalent

or

better

electrical, mechanical, and flammability ratings.

WIRELESS

Multiple Reversing Edge Configuration

Monitored Edge

Transmitter

2-Wire

End-of-Line Edge

4-Wire

In-Line Edge

4-Wire

In-Line Edge

20

4405-018

Main Terminal

HARDWIRED

Multiple Reversing Edge Configuration

DIP-switches

MUST

be turned

ON

for each device wired to terminal.

1477-010

LED Notes:

LED OFF: appropriate device is connected.

SW1 ON

1 2 3 4

LED ON: device has been activated.

Flashing LED:

Device NOT connected.

Not appropriate device.

1

4

5

2

3

6

OB

CB

OE

CE

G

G

3-Sided Edge

Note:

When using

3-Sided

Edge

active in

BOTH

directions of gate travel - jumper terminals

3 & 4 together and turn on switches 3 & 4.

4-Wire

In-Line Edge

2-Wire

End-of-Line Edge

4-Wire

In-Line Edge

Wiring to Operator

Hardwiring arranged so that the communication between the sensor and the gate operator is

NOT

subjected to mechanical damage.

4-Wire

In-Line

Edge

Wiring Multiple Reversing Edges

(Add as many “4-wire” In-Line edges as needed)

Reversing Edges are wired in series

4-Wire

In-Line

Edge

2-Wire

End-of-Line

Edge

Receiver MUST monitor for the presence of the transmitter.

Wireless Note:

Refer to the instruction sheet that comes with the receiver/transmitter for more specific wiring and mounting instructions.

RB-G-K10

CHECK

GND ANT

See manufacturer’s manual to “PROG” wireless edges.

Gate Link

PROG

MR

R1

R2

ON DIP

1 2 3 4

R3 ATEST

Power

Com

To Wireless Edge Transmitter

OR

UL 325 Terminals 3 & 6

Black to Black. White to White.

Monitored OPEN/CLOSE Reversing Edge

Entrapment protection is

RECOMMENDED

for this area.

Potential

Entrapment

Area

To Com

To Open/Close Edge

+ -

CS1 C1 BS1 CS2 C2 BS2 NO3 C3 Com ATEST

Sold Separately

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will not run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area.

OPEN/CLOSE

2-Wire End-of-Line Edge

If the distance between an entrapment or obstruction exists less than 16” from the open gate, then entrapment protection is

REQUIRED

for this area.

IMPORTANT:

Monitored

Photo and Edge sensors must be end-of-line resistive types. See specific manufacturer's wiring manual for more information.

6500-065-P-10-20

4.4 Dual Gates Multiple Photo Sensors Wiring Sample

Retro-Reflective Photocell

Wall

Open

Beam

(Monitored)

Close

Beam

(Monitored)

IMPORTANT:

Monitored Photo and

Edge sensors must be end-of-line resistive types. See specific manufacturer's wiring manual for more information.

A If the distance between an

entrapment or obstruction

exists less than 16” from the

OPEN

gate, then entrapment protection is

REQUIRED

for this area.

Wall

Open

Beam

(Monitored)

A

A

Retro-Reflective

Photocell

MIM-62 Back

See manufacturer’s manual to “LEARN” open photocells.

Retro-Reflective

Photocell

Power

Power

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will not run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area.

Use a 24 VDC power transformer

(not supplied) or (U.L. listed equivalent) to power the MIM-62.

(P/N 1812-136)

Set 3 to

“B Output”

PWR (+)

PWR (-)

INPUT (-)

INPUT (+)

COM

P/N.C.

10K

COM

P/N.C.

10K

POWER

OUT A

OUT B

Set to

“P” Pulse

P2

POWER

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

2

1

2

3

4

1477-010

4

5

6

CE

G

G

OB 7

CB

OE

8

NC NO

REVERSE

LOOP

24 VDC

COM

P/N.C.

10K

COM

P/N.C.

10K

POWER

IMPORTANT:

All inputs

must

use power from MIM-62.

75 mA maximum per channel.

Output B (P/N.C.)

IN3

Output A

(P/N.C.)

IN1

and

IN2

20

4405-018

LED Notes:

LED OFF: appropriate device is connected.

SW1 ON

1 2 3 4

UL 325 Terminal

1477-010

Set 1 & 2 “ON”

LED ON: device has been activated.

Flashing LED:

Device NOT connected.

Not appropriate device.

1

2

3

4

5

6

OB

CB

OE

CE

G

G

Open Beam

Close Beam

MIM-62 Front

Power 24VDC

UL 325 DIP-Switches

DIP-switches

MUST

be turned

ON

for each device wired to terminal.

ONLY connect monitored devices.

6500-065-P-10-20

Power

30

4.5 Loop Detector Wiring

To help protect the operator from accidentally closing on vehicles in the gate’s path, DoorKing highly recommends that loops and loop detectors be installed. Loops are laid underneath, cut into asphalt or concrete driveways or buried beneath gravel and earth driveways. A loop detection system will sense a vehicle like a metal detector and send a signal to the gate operator preventing the gate from automatically opening or closing on a vehicle when it is in the gate’s path. DoorKing recommends that a licensed installer perform this work.

Reverse

• Loop detector wiring is shown for DoorKing

plug-in loop detectors. If other loop detectors are

used, refer to the installation instructions supplied

with those detectors for wiring instructions.

• If other detectors are used, use a separate power

supply to power these detectors.

• Loop layout shown is for a typical swing gate

application with two-way traffic, or one-way exit

DoorKing offers a free “

Loop and

Loop-Detectors Information

Manual

” PDF located at

DoorKing’s web site for more information. www.doorking.com

Shadow

ference.

Automatic Exit Loop

Automatically opens the gate for exiting vehicles without having to use a transmitter or keypad. The exit loop can be placed a minimum of 4 feet away from the reverse loop or far enough away from the gate so the gate has started opening or even completely opened by the time you drive up to it (Free exit).

Automatic exit loop lead in wires are twisted approx. 6 twists per foot.

LOOP 1

Shadow Loop

will

ONLY HOLD

the main gates in the

Full Open Position

when a vehicle is on the shadow loop. However, it

WILL NOT stop or reverse

the main gates once they start to close.

Shadow loop lead in wires are twisted approx. 6 twists per foot.

LOOP 2

Reverse Loops

are placed on each side of the gate to prevent the gate from closing on a vehicle in the gate’s path. They will stop or reverse the cycling of the gate while a vehicle is in or near the gate’s pathway.

Reverse loop lead in wires are twisted approx. 6 twists per foot and are wired in series.

LOOP 1

Reverse

ference.

Automatic Exit

DoorKing Plug-In

Single Channel

Loop Detector

9410

DoorKing Plug-In

Dual Channel

Loop Detector

9409

Jumper Note:

SW 1, switch 5

OFF.

EXIT

LOOP

P2

REVERSE

LOOP

Exit Loop Port

POWER

FIRE

Shadow Loop Note:

Circuit board relay

SW1 ON

1 2 3 4

MUST

be used and set to

N.O.

NC

REV SENSE

SECONDARY

REV SENSE

PRIMARY

Reverse Loop Port

Relay Note:

SW 1, switches 7

1

and 8 must be

OFF

.

2

4405-018

2

1

2

3

4

1477-010

4

5

6

6

7

OB

7 8

CB

OE

8

9

CE

NC

G

Relay

G

Relay

10

11

12

3

4

5

13

14

15

20

16

17

18

19

20

SW 1

Com

N.O.

6500-065-P-10-20

31

32

SECTION 5 - OPERATING INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS

WARNING

-

To reduce the risk of injury or death:

1. READ AND FOLLOW ALL INSTRUCTIONS.

2. Never let children operate or play with gate controls. Keep the remote control away from children.

3. Always keep people and objects away from gate.

NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE

.

4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.

5. Use the emergency release only when the gate is not moving and power has been shut-off.

6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate

hardware.

7. The entrance is for vehicles only. Pedestrians must use separate entrance.

8. .

5.1 Power and Reset Switch

Unlock the power switch cover and open to access the MAIN POWER and the operator RESET switch.

AC

POWER

Reset Switch

- Used to turn off the entrapment alarm and to reset the operator after a hard shutdown has occurred.

Alarm Siren

AC Power Switch

- Powers the operator

ON (toggle up) or OFF (toggle down).

OFF

6500-065-P-10-20

5.2 Shutdown Conditions

Under various entrapment conditions the operator will assume either a

soft

or

hard (alarm)

shutdown. To determine what type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.

Soft Shutdown

This occurs in various situations where the inherent or entrapment protection devices have been activated. In a soft shutdown condition, the operator

will not

respond to any input that was present when the entrapment protection device sensed an obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.

Example 1

- A time clock keys the gate open in the morning and an entrapment protection device senses

an obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent

system, the gate will reverse and run back to the closed position. The time clock input is still present, but

the gate will not re-open.

NOTE: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a soft shutdown condition.

Example 2

- If the gate is closing and an entrapment protection device is activated, the gate will either stop

or reverse and run back to the open position, depending upon if the secondary or inherent device was

activated. The automatic close timer will not close the gate.

Example 3

- Vehicle arrives at open loop and gate runs towards the open position. The inherent entrapment

protection is activated. The gate reverses and runs back to the closed position. If the vehicle is still present

at the open loop a soft shutdown condition does not occur. The loop input provides an immediate reset of

the operator and the gate will again run to the open position.

Resetting a Soft Shutdown

In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor (photo sensor) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell clears, the operator will return to normal operation.

When the operator is in a soft shutdown, activation of any "intended input" will reset the operator. An "intended input" includes any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.

6500-065-P-10-20

Hard Shutdown (Alarm Activated)

A hard shutdown condition occurs when the inherent entrapment protection system has sensed

TWO

consecutive obstructions before the gate reaches the full open or closed position.

Example

- The gate is closing and the inherent entrapment protection system senses an obstruction and

causes the gate to reverse direction. As the gate begins to run in the open direction, a second obstruction

is sensed prior to the gate reaching the full open position. Once the second obstruction has been sensed,

the operator will stop, the audio alarm will be activated and all standard inputs are shut down (including

open commands, safety commands, loop inputs, etc.).

The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed.

• After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard

shutdown condition and the reset switch must be activated to reset the operator and silence the alarm.

Continued on the next page

33

Resetting a Hard Shutdown

When the operator is in a hard shutdown condition (audio alarm activated or audio alarm “chirps” every 5 seconds), the only way to reset the gate operator and return it to normal operation is to activate the alarm reset input

(auxiliary terminals 2 and 3). An alarm-reset switch can be mounted external of the gate operator provided that it is installed in the line of sight of the gate and gate operator.

• Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any

obstructions along its path that could have activated the inherent entrapment sensing system. Inspect

the gate and gate hardware.

NOTE: DoorKing operators have a built-in alarm reset push button mounted on the operator above the power

ON-OFF toggle switch. Activating this button will return the gate operator to normal operation,

but will not activate the gate operator.

Once the gate has been reset, an open or close command is needed to start the gate operator. Most activating commands will cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of the automatic exit loop. Activation of a close command will run the gate to the closed position.

34

5.3 Manual Gate Operation

This operator is equipped with a manual release system that will allow the gate to be pushed open in the event of a power outage or equipment failure.

NEVER

remove the hub from the operator after manually releasing it.

This gate operator CAN NOT be manually forced open in the event of a power failure without FIRST manually releasing the gate!

(See next page)

Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.

Emergency Vehicle Access Conditions

The automatic vehicular gate system must be designed to allow access to emergency vehicles under different operating conditions.

1. During normal powered operation,

emergency vehicles access the gate by use of the

Emergency Vehicle

Access Device

installed on your gate system. The type of device that is used in your community is dependent on your city codes. These devices may include (but are not limited to) Fire Department lock boxes, Click-2-

Enter radio receivers, strobe light sensors, siren sensors, etc.

2. In the event of a primary (AC) power failure

, the system must have a release system to allow the gate to be

Manually Operated

(See next page).

6500-065-P-10-20

Manual Release

A Unlock the cover and rotate sliding door.

Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.

B Remove release tool and place where shown.

6500-065-P-10-20

CAUTION

DO NOT REMOVE HUB!

C Release hub.

Gate can now be manually operated.

3 5

SECTION 6 - MAINTENANCE AND TROUBLESHOOTING

Inspection and service of this gate operator by a qualified technician should be performed anytime a malfunction is observed or suspected. High cycle usage may require more frequent service checks.

6.1 Maintenance

When servicing the gate operator, always check any external reversing devices (loops, photo eyes, etc.) for proper operation. If external reversing devices cannot be made operable, do not place this operator in service until the malfunction can be identified and corrected.

Always check the entrapment protection devices (external and internal) when performing any maintenance. If any of these devices cannot be made operable, remove this operator from service until the cause of the malfunction is identified and corrected. Keeping this operator in service when any entrapment protection devices are malfunctioning creates a hazard for persons which can result in serious injury or death should they become entrapped in the gate.

When servicing this gate operator, always turn power

OFF!!

If gearbox requires oil, use only Mobil SYNTHETIC SHC-629 Oil. Do not completely fill gearbox with oil. Gearbox should be half full only. Do not exceed this level.

36

Operator

Component

Warning Signs

Alarm

Arms

Drive Belt

Fire Dept.

Gate

Inherent Reverse System

Loop(s)

Manual Release

External Reverse Device

Complete System

Maintenance

Check that warning signs are on BOTH sides of the gate area.

Activate the inherent reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate. Press the reset button to silence the alarm.

Monthly Interval

6 12 1

Check set screws and nuts. Check bushings for wear.

Check for alignment, tightness and wear.

Check emergency vehicle access device for proper operation.

Inspect for damage. Check gate hinges for wear and grease if necessary.

Check that the gate reverses on contact with an object in both the opening and closing cycles. See page 47.

Adjust the reversing sensor if necessary.

Check vehicular reverse and shadow loops for proper operation.

Check manual release for proper operation. See page 46.

Check external reverse device(s) stop or reverse the gate when activated. See page 47.

Complete check of gate and gate operating system.

6500-065-P-10-20

6.2 Troubleshooting

Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of resistance is necessary to properly check the integrity of the ground loops. When a malfunction occurs, isolate the problem to one of three areas: 1) the operator, 2) the loop system, 3) the keying devices.

Use caution when checking high voltage areas: terminals 17 through 20, the motor capacitor and the motor.

1

. Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is activated. If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one at a time until the LED goes OFF.

2

. Check any external entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to stop or to hold open.

3

. A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is present over the loop. The LEDs next to the loop detector ports on the operator circuit board will light only when the loop has detected an object above it. If the LEDs stays on after the object has gone, then the loop detector has malfunctioned. Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to your loop detector instruction sheet and to the DoorKing Loop and Loop Detector Information Manual.

4

. Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying device fails to open the gate, momentarily jumper across terminals 1 and 2 (or 1 and 5) on the gate operator circuit board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.

5

. Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will cause the operator to malfunction. Refer to the wire size chart in section 2.1 page 18.

Operator will not run.

Power LED is OFF.

• Check that power to the operator is turned ON.

• Transformer may be overheated. Turn power off and allow board to cool for several minutes then retest.

Check for low 115 VAC power and low voltage shorts.

• Check for 115 VAC at terminals 19 and 20. If voltage measures OK, check the terminal strip or replace the

Operator will not run.

Power LED is ON.

• Insure that a minimum of one (1) external entrapment protection device is connected in

EACH

entrapment

area and the inputs are connected and enabled (UL 325 DIP-switches are turned ON).

• Push test button or momentarily jumper terminal 1 to terminal 2 (or 1 to 5). If the input LED does not come

ON, check the terminal strip or replace the circuit board. If LED does come ON, proceed to next steps.

Check Motor:

Remove circuit board. With power ON, momentarily jumper terminal 19 to terminal 18 with a 14 AWG

insulated jumper wire. CAUTION – HIGH VOLTAGE. The motor should run.

With power ON, momentarily jumper terminal 19 to terminal 17 with a 14 AWG insulated jumper wire.

CAUTION – HIGH VOLTAGE. The motor should run in the opposite direction of the above step.

If the motor runs in both steps above, replace the control board. If the motor does not run, or runs in

only one direction, problem can be a bad motor, motor capacitor, wire connections from the control

board to the motor or a bad control board.

Secondary operator motor will not run.

• Check that SW-1, switch 6 is ON.

• Remove circuit board. Momentarily jumper terminal 19 to the primary/secondary connection terminal block

terminal 1, then to terminal 2 with a 14 AWG insulated jumper wire. CAUTION – HIGH VOLTAGE.

The secondary motor should run one way, then the other way as power is applied to each terminal.

• If the secondary motor runs in both directions, replace the control board. If secondary motor does not run, or

runs in only one direction, problem can be in the wiring from the primary to secondary operator,

bad secondary motor or motor capacitor.

6500-065-P-10-20

37

Operator will not run, entrapment protection input(s) LED is ON.

• The entrapment protection device has a fault or the wiring to it is shorted.

3 8

Operator will not run, entrapment protection input(s) LED is

Blinking.

• The entrapment protection device is not connected or the wiring to it is open.

Gate will not reverse when an obstruction is encountered.

Gate opens a short distance, then stops and reverses.

Gate opens but will not close.

Gate closes but will not open.

• Check ERD setting.

Make sure operator hub does not slip when gate encounters an obstruction.

• Check the reversing sensitivity.

• Disconnect gate from the gate operator and check that the gate swings freely without any binding.

• Continue troubleshooting or replace the circuit board.

• Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.

• Check the secondary safety devices. Any activated will hold the gate open and indicates a problem with the

• Check the loop detectors. Any activated can hold the gate open and indicates a problem with the loop detector

or ground loop.

• Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns to normal

operation.

• If automatic close is desired, be sure SW-1, switch 4 is ON.

• Check motor as described on previous page.

• Operator may be in a “soft shutdown.” Check input LEDs. If any are ON, momentarily disconnect, then

re-connect the wire going to the respective terminal. Operator should open.

• Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back ON.

Activate a keying device. Operator should run in the open direction. If operator runs in the close direction,

turn power OFF and change direction switch SW-1, switches 1 and/or 2. Go to above section if operator now

opens but will not close.

• Be sure that the respective LED on the control board lights when the keying device connected to the respective

terminal is activated. If LED does not light, momentarily place a jumper wire from terminal 1 to the input

terminal being checked. If LED lights and gate opens, problem is with the keying device. If LED does not light,

replace control board.

• Check motor as described on previous page.

Gate starts to close, then reverses to open.

• Check that the reverse sensitivity is properly adjusted.

• Disconnect the gate from the operator and check that the gate operates freely without any binding.

• Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.

• If a shadow loop is used, check for proper wiring. A mis-wired shadow loop detector will cause the gate to

reverse.

• Continue troubleshooting or replace the circuit board.

Gate closes and then re-opens.

• Check for any input or loop detector LEDs that are ON.

• Check that operator is running in the proper direction (see “Gate closes but will not open” above).

Alarm sounds for 5 minutes and then beeps once every 5 seconds. Operator will not run.

• Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to normal

operation.

Operator has intermittent functionality problems that vary.

• The main terminal #3 250 mA power has been exceeded. Check total amp draw of connected device(s).

6500-065-P-10-20

6.3 Built-in Diagnostics

This gate operator is designed with built-in diagnostics that will alert you to potential or existing problems that the microprocessor has detected. Specific fault conditions are checked and the operator will signal that a fault exist through the built-in alarm.

Constant tone is heard when power is applied:

This indicates that the limit switch wire harness is not connected to the circuit board. In this condition, the operator will not run and the tone will continue until the fault is corrected. Check to be sure that the limit switch plug is properly inserted into P2.

Constant tone is heard:

This indicates that the operator is in a hard shutdown condition. The tone will continue to sound for five minutes, and then will beep once every five seconds. The operator-reset button must be pressed or power must be removed and then reapplied to return the operator to normal operation.

Short tone is heard every five seconds:

This indicates that the operator has been in a hard shutdown condition in excess of five minutes. This will continue until the operator-reset button is pressed or until power is removed from the operator.

Operator runs for 1 second and stops, two short tones are heard:

This indicates that there may be a fault with the current sensor circuit. Check that the black current sensor wire has been passed through the hole in the current sensor donut with the correct number of loops (1/2 HP motor - 2 loops, 1 HP motor - 1 loop).

6500-065-P-10-20

39

40

6.4 Accessory Items

UL 325 Monitored Entrapment Protection Devices available for the model 6500 swing gate operator.

Type B2 Contact Sensors (Reversing Edge)

DoorKing 8080 Series Sensing Edges

Miller Edge Sensing Edges - all models with a T2 (resistive) termination.

Miller Edge wireless monitored transmitter/receiver kit model RB-G-K10

ASO GMBH Sentir GF Series sensing edges

Type B1 Non-contact Sensors (Photo Cell)

DoorKing Model 8080-057 Retro-Reflective Photocell

Miller Edge Reflective-Guard Model RG

Miller Edge Prime-Guard Model PG

EMX Industries Model IRB-MON

EMX Industries Model IRB-RET

Omron Model E3K-R10K4

Seco-Larm Model E-936-S45RRGQ

Seco-Larm Model E-960-D90GQ

Monitored Expansion Kit

Miller Edge Multi-Input Module Model MIM-62

Accessory items available for the model 6500 swing gate operator.

Plug-In Loop Detector

- Detectors plug directly into ports on circuit board simplifying wiring.

Single channel detector - P/N 9410-010

Dual channel detector - P/N 9409-010

Single channel detector with aux relay - P/N 9411-010

Single channel low power draw detector - P/N 9416-010

Dual channel low power draw detector - P/N 9415-010

External Loop Detector

Reno A&E 12/24 VDC or 24 VAC - 9402-045

Reno A&E 120 VAC - 9402-047

Carlo Gavazzi 24 VAC/VDC - 9402-044

Diablo 10-30 VAC/VDC low power draw - 9402-050

Magnetic Lock

- Magnetic Gate Lock Kit provides an excellent means to secure swing gates and is a fail-safe device allowing emergency vehicle access upon power outage.

P/N 1216-080 and P/N 1216-081

115 VAC Heater and Fan Assembly

- Cold weather climates where temperatures drop below 40°F (4°C). P/N 6500-480

Interconnection Cable

- Interconnect wire cable contains all the necessary wires to interconnect primary / secondary operators.

Cable length 30 feet. P/N 2600-755

Cable length 40 feet. P/N 2600-756

Cable length 50 feet. P/N 2600-757

High Voltage Kit

- Alter the input AC voltage on a 115 VAC 6500 to 208, 230, 460 or 575 VAC. P/N 2600-266

Time Clock

- 7 day time clock can be used to automatically open gate at pre-set time and days. Compact clock fits inside the operator.

P/N 2600-791 - 7 day clock

Torsion Rods

- Torsion rod assembly is used on uphill swing gates for counter balance.

Hinges

- Heavy-duty ball bearing hinges provide easy swing gate operation.

P/N 1200-009, P/N 1200-019, P/N 1200-039.

Surge Devices

- High and low voltage surge suppressors help prevent circuit board failure caused by lightning strikes and power surges.

P/N 1879-010 - High Voltage

P/N 1878-010 - Low Voltage

Speed Bumps

- Prefabricated six-foot speed bump reduces traffic speed through gate system. P/N 1610-150

6500-065-P-10-20

6.5 Gearbox Shaft Extension Replacement

Crank Arm Only

P/N 6500-255

Control Arm Only

P/N 2600-714

Elbow Assy ONLY

P/N 2600-720

Complete Arm Kit

P/N 6500-430

Crank Arm

Magnet

Assy

P/N 6500-420

Limit Sensor Assemblies

Loosen set screws on plastic limit assemblies to remove them.

Note:

Close Limit Sensor must be reinstalled on

TOP

of Open Limit Sensor.

CL

OS

CLOSE

E

E

Close

Hub Assembly

Remove the

TWO

bolts to remove hub assembly from hub extension shaft.

Brass Bushings

P/N 6500-145

Hub Extension Shaft Assembly

P/N 6500-162

Snap Ring Channel

Limit Sensors

P/N 6600-035 - 2x

N

N

EN

OPEN

OPE

OPE

OP

Open

MUST

be installed as shown.

Set Screw

Limit Sensor

Assembly

N

N

OPE

OPE

OPEN

OPEN

Reversible

Limit Sensors Collar

P/N 6500-118

Remove the

FOUR

bolts to remove collar.

Carbon Steel Washers

P/N 2620-076 - 2x

P/N 2630-007

Snap Ring

Removing snap ring will release hub extension shaft.

Gearbox

P/N 2600-719

PU

SH

O

TO

hn tec ici an

RA

PE

TE

e o

us nly

6500-065-P-10-20

41

42

Model 6500 1/2 HP 115 VAC

Magnetic

Close

Sensor

Yellow

Gray

Gray

Gray

Orange

Magnetic

Open

Sensor

Remote

Terminal

White

Brown

Orange

EXIT

LOOP

P2

REVERSE

LOOP

POWER

Orange

Yellow

White Loops

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

4405-018

2

1

2

3

4

1477-010

4

5

6

OB

7

CB

OE

8

CE

G

G

NC NO

1

2

3

4

5

6

7

8

9

10

11

12

16

17

18

19

13

14

15

20

Push to Operate

Power

Brown

Ground

Neutral

Power

NEU HOT

115 VAC

Chassis

Ground

115 VAC

Convenience Open

Outlets

AC Power

Secondary

Current

Sensor

Red

50uf Capacitor

Blue

1/2 HP

Blue

White

Red

Alarm

Red

Yellow

White

Reset

Ground

Secondary Interface Terminal

6500-065-P-10-20

Model 6500 1 HP 115 VAC

Magnetic

Close

Sensor

Yellow

Gray

Gray

Gray

Orange

Magnetic

Open

Sensor

Remote

Terminal

White

Brown

Orange

EXIT

LOOP

P2

REVERSE

LOOP

POWER

Orange

Yellow

White Loops

FIRE

TIME

DELAY

REV SENSE

SECONDARY

REV SENSE

PRIMARY

SW1 ON

1 2 3 4

4405-018

2

3

4

1

2

1477-010

4

5

6

OB

7

CB

OE

8

CE

G

G

NC NO

1

2

3

4

5

6

7

8

9

10

11

12

16

17

18

19

13

14

15

20

Push to Operate

Power

Brown

Ground

Neutral

Power

NEU HOT

115 VAC

Chassis

Ground

115 VAC

Convenience Open

Outlets

AC Power

6500-065-P-10-20

Secondary

Current

Sensor

Red

Blue

White

1 HP

Alarm

Red

Yellow

White

Reset

Ground

Secondary Interface Terminal

43

44

Model 6500 1/2 HP Secondary Operator

Ground

1/2 HP

Red

50uf Capacitor

Blue

Magnetic

Close

Sensor

Red

Blue

White

CL

OS

CLOSE

E E

N N

OPEN

OPEN OPE

OPE

Magnetic

Open

Sensor

Secondary Operator Configuration

NO circuit Board

NO 115 VAC convenience outlets

Model 6500 1 HP Secondary Operator

1 HP

Magnetic

Close

Sensor

Red

Blue

White

Ground

Magnetic

Open

Sensor

6500-065-P-10-20

SECTION 7 - OWNER OF THE GATE OPERATOR

7.1 Alarm Sounding and Gate WILL NOT Operate

A KEY has been supplied that will unlock the power switch cover on this gate operator.

Note:

The

owner

of the gate operator is responsible for the

KEY

availability.

When alarm is sounding . .

ALWAYS CHECK GATE AREA FOR ANY OBSTRUCTIONS FIRST.

If the cause of the alarm cannot be corrected, shut-off power and

DO NOT

place this operator back into service until the malfunction can be identified and

CORRECTED

.

IMPORTANT: Putting this gate operator back into service without

CORRECTING the cause of the alarm could result in serious injury or DEATH!

Power

Switch

Cover

RESET BUTTON

AC

POWER

UNLOCK

the power switch cover with

KEY

and press

RESET BUTTON

.

This will reset the gate operator and allow normal gate operation again.

OFF

Gate Operator is in a Hard Shutdown Condition when Alarm is Sounding

This occurs when:

1. The inherent entrapment protection system (Type A) gets activated TWO consecutive times before the gate completes

the open or close cycle.

2. The reversing edge contact sensor (Type B2) gets activated and reverses but before the gate completes the reverse

cycle the inherent entrapment protection system (Type A) gets activated.

The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed.

6500-065-P-10-20

Please read

SECTION 5 - OPERATING INSTRUCTIONS

for more information about operating this gate operator.

4 5

7.2 Manual Gate Operation

Caution:

NEVER attempt to manually operate the gate until you have VERIFIED that power to the gate operator has been

SHUT-OFF!

A KEY has been supplied that will unlock the cover and power switch cover on this gate operator.

Note:

The

owner

of the gate operator is responsible for the

KEY

availability.

A Unlock the cover and rotate sliding door.

Power

Switch

Cover

B Remove release tool and place where shown.

C Release hub.

Gate can now be manually operated.

CAUTION

DO NOT REMOVE HUB!

46

Please read

SECTION 5 - OPERATING INSTRUCTIONS

for more information about operating this gate operator.

6500-065-P-10-20

7.3 Gate Operator’s Monthly Checkup

Caution:

Make SURE gate area is clear BEFORE testing the gate operator!

DO NOT

repair or adjust gate systems yourself. Contact a trained gate systems technician with any questions or to make any repairs or adjustments. If you feel uncomfortable performing any of these inspections or testing, a qualified service technician will perform the visual inspections and testing for you.

You can find a trained service technician at DoorKing’s “Dealer Locator” at www.doorking.com

Visual Inspection

Visually inspect the rollers, fasteners, brackets and other gate hardware for proper alignment, proper tightness, and signs of damage, breakage, looseness, rust or wear. Moving parts should be lubricated and should not be squeaking.

Visually inspect wiring for fraying or exposure. If a malfunction is found, contact a trained service technician to make adjustments or repairs.

Test Built-In Reversing Sensor

Begin with the gate in the fully

OPEN

position. Stand just outside the path of the gate and close the gate (typically auto-timer will time-out and close gate automatically). As the gate is

closing

, firmly press a solid object against the end of the gate frame in the direction opposing the travel of the gate. The gate should

stop

within 2 sec. and

reverse

to the

OPEN

position.

Another input command is needed before the gate will reset and close again. Repeat this test while

opening

the gate. Start from the fully

CLOSED

position. While

opening

, gate should

stop

and

reverse

to the

CLOSE

position. If gate does

NOT

respond like it should in

either

direction of gate travel, contact a trained service technician to make adjustments or repairs.

Test Photo Sensors

If the gate has a photo sensing device protecting the path of a

closing gate

, perform the following test. Begin with the gate in the fully

OPEN

position. Stand just outside the path of the gate and close the gate (typically auto-timer will time-out and close gate automatically). Pass an object across the path of the closing photo sensing beam. The gate should

stop

within 2 sec. and

reverse

to the

OPEN

position. Typically the auto-timer times out and gate closes again.

If the gate has a photo sensing device protecting the path of a

opening gate

, start from the fully

CLOSED

position.

OPEN

gate. Pass an object across the path of the opening photo sensing beam. The gate should

stop,

the gate will resume opening when the beam is clear. If gate does

NOT

respond like it should in

either

direction of gate travel, contact a trained service technician to make adjustments or repairs.

Test Reversing Edges

If the gate has a reversing edge(s) protecting the path of a

closing gate

, perform the following test. Begin with the gate in the fully

OPEN

position. Stand just outside the path of the gate and close the gate. As the gate is closing, firmly press a solid object against the reversing edge in the direction opposing the travel of the gate. The gate should

stop

within 2 sec. and

reverse

to the

OPEN

position (typically auto-timer will time-out and close gate automatically). If the gate encounters

another

obstruction before it is closed, the gate will

stop

and reverse to the

OPEN

position

again

. A input command is needed before the gate will reset and close again, auto-timer will

NOT

close gate (Typically, press your remote button for input command).

If the gate has a reversing edge(s) protecting the path of a

opening gate

, starting from the fully

CLOSED

position.

Stand just outside the path of the gate and open the gate.

OPEN

gate. As the gate is opening, firmly press a solid object against the reversing edge in the direction opposing the travel of the gate. gate should

stop

and

reverse

to the

CLOSE

position. If gate does

NOT

respond like it should in

either

direction of gate travel, contact a trained service technician to make adjustments or repairs.

Note:

This gate operator uses high levels of force to move the gate and most people underestimate the power of these systems and do not realize the potential hazards associated with this system if

NOT

maintained properly.

Scheduled maintenance visits are offered by most qualified service technicians to MAINTAIN your gate operator system.

6500-065-P-10-20

47

7.4 New Installation Checklist for Installer and Property Owner

Instructions:

Check the space next to each item (“

”) to indicate that it has been addressed by installer

AND

property owner.

If it is not applicable, enter N/A. Please note that the checklist is intended to be a summary of many

important

automated vehicular gate aspects,

But may not inclusively identify all potential hazards of every specific gate system installation.

Each item listed and checked has been examined by the Installer and is CLEARLY understood by the Property Owner.

4 8

Installer

Property

Owner

Description

The operator is installed on a gate used for vehicles only.

Verify that separate pedestrian access is provided or available, and the access is such that pedestrians cannot come in contact with the moving vehicular access gate during its entire length of travel.

Gate/Hardware:

Insure that there is a means to prevent the gate from falling over in the event of a roller or hinge failure. Insure the gate has physical limit stops and that gravity will not initiate motion of the gate. Insure that all rollers are guarded or covered to eliminate the possibility of a finger being inserted between the roller and gate.

Slide Gate:

Insure that the maximum opening in the gate and in that portion of the adjacent fence that the gate covers when the gate is in the open position is such that a 2 ¼" sphere cannot pass through the openings up to 72 inches above the ground or to the top of the gate, whichever is less. If the gate and adjacent fence do not meet this requirement, wire mesh (or other means) must be added to meet this requirement before placing the gate system in operation.

Insure that any gaps between the slide gate and stationary posts/pilasters is less than 2 1/4" and that these areas are protected with an entrapment protection device.

The gate operator system is in compliance with the

entrapment protection requirements of UL 325.

Identify all potential entrapment zones and ensure they are protected. Potential pinch areas have been guarded so as to be inaccessible OR have a contact (reverse edge) and/or non-contact (photocell) obstruction sensing devices installed.

Verify that the system has in place external entrapment protection, independent from the inherent entrapment protection. Edge sensors or photocells are typical, other means are possible. For more information see your

specific

installation/owners manual for entrapment protection installation and locations.

The installer has properly adjusted the

inherent entrapment protection feature

on the gate operator, and has tested the gate to make sure that the gate stops and reverses a short distance upon striking an immovable object.

Check that placement of

user operational controls

are six (6) or more feet away from the gate. If any operational control is closer than six (6) feet to the gate,

DO NOT

place the automated vehicular gate into service.

Warning signs

have been installed so that they are visible from each side of the gate - whether the gate is open or closed.

The installer has instructed the property owner in the

proper use of the gate operator

and has reviewed the operational functions, obstruction-sensing devices, alarm, and reset as outlined in

your specific

installation/owners manual.

The installer has instructed the property owner in the proper use of the operator's

manual release feature

as outlined in

your specific

installation/owners manual.

The installer has

reviewed all safety instructions with the property owner

, including the need to never let children operate or play with gate controls, to keep the remote control away from children, and to always keep people and objects away from the gate.

The installer has explained to the property owner that a

regular maintenance schedule

for both the gate and the gate operator is recommended, including regular testing of entrapment protection as outlined in the manufacturer's instructions.

The installer has left the installation/owners manual with the property owner for future reference.

6500-065-P-10-20

6500-065-P-10-20

RESET

Cover

Switch

Power

Cover

Switch

Power

49

Installation/Owner’s Manual

Use this manual for circuit board 4405-018 Revision A or higher.

Vehicular Swing Gate Operator

6500-065-P-10-20

Entrapment Protection must be provided for the gate system where the risk of entrapment or obstruction exists. The operator will NOT run without one or more monitored type B1 or B2 entrapment protection devices in EACH entrapment area.

UL 325 August 2018 Standard

5 0

THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE/DOOR SYSTEMS TECHNICIAN ONLY.

Visit

www.doorking.com/dealer-locator

to find a professional installing and servicing dealer in your area.

www.doorking.com

DoorKing, Inc.

120 S. Glasgow Avenue

Inglewood, California 90301

U.S.A.

Phone: 310-645-0023

Fax: 310-641-1586

Copyright 2009 DoorKing, Inc. All rights reserved.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement