Generac 50kW RD05034GDAL Standby Generator Manual

Add to My manuals
2 Pages

advertisement

Generac 50kW RD05034GDAL Standby Generator Manual | Manualzz

B

4

REMOVE PANEL TO

ALLOW TANK VENTS

TO TERMINATE OUTSIDE

OF THE GENERATOR

ENCLOSURE (CHECK LOCAL

AND STATE CODE FOR

APPLICABILITY)

173 [6.8]

618 [24.3]

INTERNAL DIVIDER PANEL

SEPARATES FUEL TANK VENTILATION

DUCT FROM THE ENGINE,

ALTERNATOR AND EXHAUST SYSTEM

RADIATOR/EXHAUST

DISCHARGE AIR

(BOTH SIDES)

998 [39.3]

CENTER OF GRAVITY

SEE NOTE 5

AIR INTAKE

(BOTH SIDES)

LIFT-OFF DOOR PROVIDES ACCESS TO:

FUEL FILL, FUEL LEVEL GAUGE,

NORMAL VENT, INNER TANK

EMERGENCY VENT, OUTER TANK

EMERGENCY VENT, OPTIONAL

90% ALARM ASSEMBLY,

OPTIONAL 5 GALLON SPILL

BOX

TOP VIEW

RADIATOR/EXHAUST

DISCHARGE AIR

758 [29.8]

DOOR TYP

3

SERVICE ITEM

OIL FILL CAP

OIL DIP STICK

3.4L

RIGHT SIDE

RIGHT SIDE

OIL FILTER

OIL DRAIN HOSE

RIGHT SIDE

RIGHT SIDE

RADIATOR DRAIN HOSE LEFT SIDE

AIR CLEANER ELEMENT RIGHT SIDE

MUFFLER

FAN BELT

BATTERY

FRONT

EITHER SIDE

LEFT SIDE

REFERENCE OWNERS MANUAL FOR PERIODIC

REPLACEMENT PART LISTINGS.

SH 1/2 REV A WINDCHILL VERSION A.1

WEIGHT DATA WITH EMPTY BASETANK

(SEE NOTE 5)

GENERATOR AS SHOWN (STEEL ENCL)

WITH WOODEN SHIPPING SKID

997 [2197]

1042 [2297]

1

NOTES:

1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718

(107") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT

FOR CONCRETE PAD GUIDELINES

2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE

AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT

APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,

STATE AND LOCAL CODES.

3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:

- SEE SPECIFICATION SHEET OR OWNERS MANUAL

- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF

GENERATOR

4. REMOVE THE REAR TANK AND REAR ENCLOSRE COVER PANEL TO ACCESS

THE STUB-UP AREAS AS FOLLOWS:

- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION

NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.

- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES

5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.

6. ENGINE SERVICE CONNECTIONS

OIL DRAIN: 3/8" NPT

EXHAUST OUTLET: 2" O.D.

7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND

RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.

8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H2O.

9. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.

10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5

(USE STANDARD SAE TORQUE SPECS)

VICE ACTION LATCH,

ONE PER DOOR, LIFT-OFF

DOORS ON FRONT, RIGHT, AND LEFT SIDES

LIFTING PROVISIONS (4 PLACES)

SEE NOTES 5, 9, AND CENTER

OF GRAVITY DIMENSIONS

REAR ENCLOSURE COVER

PANEL

SEE NOTE 4

CIRCUIT BREAKER

SEE NOTE 3

CUSTOMER ACCESS

ASSEMBLY, CONTROL PANEL

ACCESS, BATTERY CHARGER

LOCATED WITHIN

SEE NOTE 4

1449

[57.0]

OVERALL

HEIGHT

A

OPEN PUNCHED LOUVERS TYPICAL

ON BOTH SIDES OF

FUEL TANK VENTILATION

DUCT TO PROVIDE ADEQUATE

CROSS-FLOW OF AIR VENTILATION

DRAWING CREATED FROM PRO/ENGINEER

3D FILE. ECO MODIFICATION TO BE

APPLIED TO SOLID MODEL ONLY.

FUEL TANK

VENTILATION DUCT

EXHAUST MUFFLER ENCLOSED WITHIN

GENERATOR ENCLOSURE

LEFT SIDE VIEW

REAR TANK COVER

SEE NOTE 4

4 3

B

343

[13.5]

182

[7.2] 888 [35.0]

OVERALL WIDTH

1625 [64.0]

2424 [95.4] OVERALL LENGTH

REAR VIEW RIGHT SIDE VIEW

TITLE

INSTALL CPL PROT D3.4L EXT

GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING

WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR

ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT

THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.

c GENERAC POWER SYSTEMS 2013

2

ELECTRONICALLY APPROVED

INSIDE WINDCHILL

ISSUE DATE:

SIZE

B

SCALE

CAGE NO DWG NO

0.050 WT-KG

0K6968

SEE ABOVE SHEET

1

REV

A

1 of 2

A

4 3

A

110 [4.3] TYP

DRAWING CREATED FROM PRO/ENGINEER

3D FILE. ECO MODIFICATION TO BE

APPLIED TO SOLID MODEL ONLY.

690 [27.2] TYP

1216 [47.9] TYP

1769 [69.6] TYP

2322 [91.4] TYP

SH 2/2 REV A WINDCHILL VERSION A.1

B

101 [4.0]

OUTER TANK EMERGENCY VENT

(2" NPT FEMALE)

FUEL LEVEL

GAUGE/SENDER

660 [26.0]

351 [13.8]

FUEL FILL

INNER TANK NORMAL VENT

(2" NPT FEMALE)

INNER TANK EMERGENCY VENT

(2" NPT FEMALE)

(2" NPT FEMALE)

CUSTOMER OPTION

(2" FEMALE NPT)

OUTER TANK LEAK DETECTOR

2226 [87.6]

FUEL RETURN FUEL SUPPLY

121 [4.8]

196 [7.7]

STUB-UP

AREA

38

[1.5]

HIGH AND LOW VOLTAGE

STUB-UP AREA

CIRCUIT BREAKER,

NEUTRAL AND CUSTOMER

CONNECTION OPENING

786 [30.9]

STUB-UP

AREA

125

[4.9]

51

[2.0]

4 3

1

FUEL TANK

TOTAL CAPACITY

USABLE CAPACITY

233 [61]

209 [55]

CAPACITY: LITER [GALLONS]

DIMENSIONS: MM [INCH]

THIS TANK IS LISTED TO UL142 AND ULC/ORD C142.18

B

REMOVABLE

STUB-UP COVER

394 [15.5]

16.7 [.66] MOUNTING HOLES

(10 PLACES)

19

[.7]

851 [33.5] TYP

888 [35.0]

TITLE

INSTALL CPL PROT D3.4L EXT

GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING

WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR

ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT

THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.

c GENERAC POWER SYSTEMS 2013

2

ELECTRONICALLY APPROVED

INSIDE WINDCHILL

ISSUE DATE:

SIZE

B

SCALE

CAGE NO DWG NO

0.075 WT-KG

0K6968

SEE ABOVE SHEET

1

REV

A

2 of 2

A

advertisement

Key Features

  • 50kW of power
  • Can run essential appliances and equipment
  • Digital control panel
  • Automatic voltage regulation
  • Low-oil shutdown sensor

Related manuals

Frequently Answers and Questions

What is the fuel tank capacity?
125 [4.9]
What is the overall height?
1449 [57.0]
What is the overall width?
888 [35.0]
What is the overall length?
2424 [95.4]