- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Westinghouse
- JS6BF
- Installation guide
Westinghouse JS6BF Installation Instruction 20 Pages
advertisement
AIR CONDITIONER 16 SEER
User’s Manual / Installation Instructions
Two Stage R-410A Split System
Premium Model Shown
IMPORTANT
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor .
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
2
USER INFORMATION
Safety Information ........................................ 4
About the Air Conditioner ............................ 4
What are the Benefi ts of a Split
System?...................................................... 4
What are the Benefi ts of Two - Stage
Variable Speed Cooling? ............................ 4
Operating Instructions ................................. 4
Oper. the Indoor Blower Continuously ........ 5
Shutting the AC Off ..................................... 5
Warranty Information ................................... 5
System Maintenance .................................... 5
Before You Call a Technician ...................... 5
Troubleshooting ............................................ 5
INSTALLER INFORMATION
Safety Information ........................................ 6
Pressures Within the System ..................... 6
Labels, Tags, and Precautions .................... 6
High Pressure Switch ................................. 9
Comfort TM Diagnostic Module...........10
General Information ..................................... 7
Outdoor Unit Selection ............................... 7
Liquid and Suction Lines ............................ 7
Field Connections for Electrical Power
Supply......................................................... 7
Site Preparation ............................................ 7
Unpacking the Equipment .......................... 7
Inspect for Damage .................................... 7
Preferred Location of the Outdoor Unit ....... 7
Interpreting the Diagnostic LED’s .........10
Two - Speed Outdoor Fan Motor ..............11
Startup & Adjustments...............................11
Pre - Start Checklist .................................11
Functional Checkout ..................................11
Minimum Circuit Ampacity .......................... 7
Maximum Fuse / Circuit Breaker Size ........ 7
Installing the Indoor Unit ............................. 7
Installing the Outdoor Unit .......................... 7
Slab Mount ................................................ 7
Short Cycle Protection ..............................12
Roof Mount ................................................ 8
Connecting Refrigerant Tubing Between the Indoor and Outdoor Unit ....................... 8
Adjustment of Refrigerant Charge ............12
Charging R-410A Unit in AC Mode ..........13
Cooling Charging Charts ...........................13
Troubleshooting Tables ..............................16
Filter Drier Installation ................................ 8
Electrical Connections ................................. 8
Pre - Electrical Checklist............................. 8
Wiring Diagram / Schematic ....................... 8
Outdoor Unit Connections .......................... 9
Low Pressure Switch .................................. 9
3
USER INFORMATION
4
SAFETY INFORMATION
IMPORTANT:
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored.
WARNING
indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.
CAUTION
indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
What are the benefi ts of a split system?
Split systems are designed to work effi ciently for cooling in any climate. Split systems have two main components: the outdoor section (air conditioner or heat pump) and the indoor section
(matched air handler or coil). These two sections work together to provide top performance, maximum effi ciency, and comfort.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s
User Manual for detailed programming instructions.
For this type of equipment to function as intended, a two stage cooling / heating thermostat is required.
ABOUT THE AIR CONDITIONER
Your 16 SEER air conditioner has been carefully designed and engineered to give you outstanding energy effi ciency and years of trouble-free operation. This appliance uses only proven components, such as the Ultra-tech Copeland® scroll compressor, a leaders choice for effi ciency, durability, and longevity.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO.
See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE:
If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
What are the benefi ts of two stage; variable speed cooling?
• Two stage cooling products maintain a more consistent comfort level throughout your home. The AC always starts in fi rst stage and attempts to meet the cooling demand. When the temperature rises, the air conditioner or heat pump automatically adjusts itself and enters the second stage to meet increased cooling demands.
• A two stage, variable-speed unit runs for longer cycles and will remove up to six times more moisture than a conventional unit. The result is a more comfortable environment even at a higher thermostat setting.
• Since the fan operates slower during the low stage cooling demand, the fan motor produces less fan noise. The variable speed motor ramps up slowly, eliminating uncomfortable temperature swings. Since the unit runs at the stage needed based off demand, you never pay for energy that is not needed.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO.
See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE:
If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Fan
Mode
System
Mode
Temperature
Selector
Figure 1. Digital Thermostat
USER INFORMATION
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
SYSTEM MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
Shutting the Air Conditioner Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO (See Figure 1).
NOTE:
The system will not operate, regardless of the temperature selector setting.
Proper maintenance is most important to achieve the best performance from the appliance and should be performed by a qualifi ed service technician at least once a year. Follow the maintenance schedule and the instructions below for years of safe, trouble free operation.
WARRANTY INFORMATION
A warranty certificate with full details is included with the air conditioner. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the air conditioner.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
Regular Cleaning
• Clean or replace the indoor air fi lter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
• Check for obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the AC fails to operate, check the following:
• The thermostat is properly set. See Cooling
Operation for air conditioning or Heating
Operation for furnace or air handler (page 3).
• The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
5
6
INSTALLER INFORMATION
SAFETY INFORMATION
IMPORTANT:
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored.
WARNING
indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.
CAUTION
indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
These units are fully charged with
R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required.
If repairs make it necessary for evacuation and charging, it should only be attempted by qualifi ed, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation service personnel to service this type of equipment.
Under no circumstances should the homeowner attempt to install and/ or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
WARNING:
The safety information listed below must be followed during the installation, service, and operation of this unit.
Unqualified individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious per sonal injury or death.
WARNING:
I m p ro p e r i n s t a l l a t i o n , s e r v i c e , adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage.
Unless otherwise noted in these instructions, only factory authorized kits or accessories may be used with this product.
• The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
• This equipment contains liquid and gaseous refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
• All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National
Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
• Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment
(safety glasses, work gloves, fi re extinguisher, etc.) when performing brazing operations.
• Install this unit only in a location and position as specifi ed on page 6. This unit is designed only for outdoor installations and should be located with consideration of minimizing the length of the supply and return ducts.
Consideration should also be given to the accessibility of fuel, electric power, service access, noise, and shade.
• Follow all precautions in the literature, on tags, and on labels provided with the equipment.
Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment..
GENERAL INFORMATION
Split System units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations equipped with variable speed blowers.
SITE PREPARATION
Unpacking the Equipment
Remove the shipping carton and User’s Manual from the equipment. Take care not to damage the tubing connections when removing the carton.
This unit has been designed and tested for capacity and effi ciency in accordance with A.R.I.
Standards. This unit will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
Inspect for Damage
Inspect the equipment for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns.
Preferred Location of the Outdoor Unit
Survey the job site to determine the best location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.
Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.
Facility Prerequisites
Electrical power supplied to the unit must be adequate for proper operation of the equipment.
The system must be wired and provided with circuit protection in accordance with local building codes.
Outdoor Unit Selection
Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler. These units include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fi ttings.
Minimum Circuit Ampacity
Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
NOTE:
DO NOT USE ANY PORTION OF THE
CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully.
Maximum Fuse / Circuit Breaker Size
Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
INSTALLING THE INDOOR UNIT
The indoor unit (air handler, furnace, etc.) should be installed prior to the routing of refrigerant piping. Consult the Installation Instructions of the indoor unit for installation details.
Liquid and Suction Lines
Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply
All wiring must comply with current provisions of the “National Electrical Code” (ANSI/NFPA
70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
INSTALLING THE OUTDOOR UNIT
Slab Mount
The site selected for a slab mount installation requires a stable foundation and not subject to erosion. The slab should be level and anchored
(if necessary) prior to installation on the slab.
Cantilever Mount
The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.
7
Roof Mount
WARNING:
To avoid the risk of property damage, personal injury, or death, it is the installer’s responsibility to ensure that whatever means are used to move or lift the unit are safe and adequate:
Keep the unit in an upright position at all times.
The method of mounting should be designed so as not to overload roof structures or transmit noise to the interior of the structure. Refrigerant and electrical lines should be routed through suitably waterproofed openings to prevent water leaking into the structure.
CONNECTING REFRIGERANT TUBING
BETWEEN THE INDOOR & OUTDOOR UNIT
• The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet.
• If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
Filter Drier Installation
A fi lter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
Optional Equipment
Optional equipment such as liquid line solenoid valves, twinning kit, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
CAUTION:
This system uses R-410A refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.
General Information
After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.
ELECTRICAL CONNECTIONS
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
Pre-Electrical Checklist
Verify that the voltage, frequency and phase of the supply source are the same as those specifi ed on the unit rating plate.
Verify that the service provided by the utility is suffi cient to handle the additional load imposed by this equipment.
For minimum circuit ampacity and maximum overcurrent protection, see unit rating plate.
8 it is recommended that dry nitrogen be fl owing through the joints during brazing. This will prevent internal oxidation and scaling from occurring.
• Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing.
• Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
• Tubing should be kept clean of foreign debris during installation.
• Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
Wiring Diagram / Schematic
A wiring diagram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making any electrical connections to the outdoor unit.
Line Voltage
• Electrical power wiring must comply with the current provisions of the NEC (ANSI/NFPA
70) and with applicable local codes having jurisdiction.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate.
• Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
• Use only copper wire for the line voltage power supply to this unit (Table 1). Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit.
Use of rain tight conduit is recommended.
• See the unit wiring label for proper high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances.
• Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
• Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
200 150 100 50
Supply Circuit
Ampacity
2
2
3
2
1
4
4
6
4
3
8
6
6
4
4
4
3
3
3
2
10
8
8
6
6
6
4
4
4
3
14
12
10
10
8
8
6
6
6
4
15
20
25
30
35
40
45
50
55
60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
NOTE:
Jumper
W1 and W2 together for shorter staging time. See Table 2
Thermostat
G R W Y2 Y1
Outdoor Unit Connections
The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram / schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Y1
W2
W1
R
Y2
Control Circuit Wiring
The outdoor unit is designed to operate from a
24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
Thermostat Connections
Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. See Table 2 for proper wire gauge and their recommended lengths for typical thermostat connections. A typical residential installation with an air conditioner, thermostat, and air handler is shown in Figure 2.
Low-Pressure Switch
A low-pressure switch is factory installed and located internally on the suction line of the outdoor unit. The switch is designed to protect the compressor from a loss of charge by interrupting the thermostat inputs to the unit.
If the suction pressure falls below 5 psig, the switch will open and de-energize the outdoor unit. The switch will close again when the suction pressure increases above 20 psig.
NOTE:
When the switch opens and then closes, there is a 5 minute short cycling delay before the outdoor unit will energize. Under normal conditions the switch is closed.
G
R
O
Y/Y2
C
NOTE:
in AC applications, the O & Y connection must
be connected as shown.
C Y1
A/C OD Section
Figure 2. Typical 2-Stage Air Conditioner with Variable Speed Air Handler
Thermostat
Wire Gauge
24
22
20
18
Recommended T’STAT Wire
Length (Unit to T’STAT)
2-Wire
(Heating)
55
90
140
225
5-Wire
(Heating/Cooling)
25
45
70
110
Table 2. Thermostat Wire Gauge
High-Pressure Switch
A high-pressure switch is factory installed and located internally on the compressor discharge line of the outdoor unit. If the discharge pressure rises above 650 psig, the switch will open and de-energize the outdoor unit. The switch will close again after the discharge pressure decreases to
460 psig.
NOTE:
When the switch opens and then closes, there will be a 3 minute short cycling delay before the outdoor unit will energize. Under normal conditions the switch is closed.
9
Comfort Alert TM Diagnostics Module
The Comfort Alert
TM
diagnostics module is a breakthrough innovation for troubleshooting air conditioning system failures. The module installs easily in the electrical box of the outdoor unit near the compressor contactor. By monitoring and analyzing data from the Copeland scroll compressor and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A fl ashing LED indicator communicates the ALERT code and a diagnostic key is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem. See Figure 3.
NOTE:
This Comfort Alert TM module does not provide safety protection! This module is a monitoring device and cannot control or shut down other devices.
24 VAC Power Wiring
The Comfort Alert TM module requires a constant nominal 24 VAC power supply. The module cannot be powered by the
C
terminal on a defrost board or other control board without experiencing nuisance alerts.
NOTE:
The wiring to the module’s
R
&
C
terminals must be routed directly from the indoor unit or thermostat.
If the constant 24 VAC (
R
wire) is not present in the outdoor unit, use one of the spare wires in the thermostat cable to bring power to the module.
Connect the other end of the spare wire to
R
at the indoor unit or thermostat.
Thermostat Demand Wiring
The Comfor t Aler t
TM
module requires a thermostat demand signal to operate properly.
The thermostat demand signal input (labeled
Y
on the module), should always be connected to the compressor contactor coil.
NOTE:
When the coil is energized, the demand signal input is 24
VAC. When the coil is not energized, the demand signal input should be less than 0.5 VAC.
• Factory installed modules have different thermostat demand signal wiring. Always follow manufacturer wiring instructions when replacing the module.
• After the thermostat demand signal is connected, verify that 24 VAC across
Y
&
C
when demand is present.
Interpreting the Diagnostic LED’s
When an abnormal system condition occurs, the
Comfort Alert TM module displays the appropriate
ALERT and/or TRIP LED will fl ash a number of times consecutively, pause and then repeat the process. To identify a Flash Code number, count the number of consecutive fl ashes.
Each time the module powers up, the last ALERT
Flash Code that occurred prior to shut down is displayed for one minute. The module will continue to display the LED until the condition returns to normal or if 24 VAC power is removed from the module.
LED Description
NOTES:
• POWER LED (Green): indicates voltage is present at the module’s power connection.
• ALERT LED (Yellow): communicates an abnormal system condition through a unique fl ash code. The ALERT LED will fl ash consecutively, pause and then repeat the process. The number of consecutive fl ashes, referred to as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of these ALERT Flash Codes are listed in Table 4 (page 14).
• TRIP LED (Red): indicates a demand signal is received from the thermostat, but current to the compressor is not detected by the module. The TRIP LED typically indicates the compressor protector is open or may be missing supply power to the compressor.
POWER LED
(Green)
ALERT LED
(Yellow)
TRIP LED
(Red)
Diagnostics
Key
The scroll compressor’s
R
(run),
C
(common), and
S
(start) wires are routed through the holes in the Comfort Alert
TM
module marked
R
,
C,
and
S
.
NOTE:
The common wire does not need to be routed through the module for it to operate.
2-Speed Outdoor Fan Motor (Select Models)
If unit uses a 2-speed condenser fan motor, this motor will operate on low speed when in low cooling, and on high speed when in high cooling.
A relay within the control area switches the fan motor from low to high speed using the call for high cooling as the trigger.
Figure 3. Comfort Alert
TM
Diagnostics
Module
10
Optional Equipment
Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the
NEC (ANSI/NFPA 70), with applicable local codes having jurisdiction, and the installation instructions provided with the equipment.
Optional Equipment (low ambient control, hard start kits, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
FUNCTIONAL CHECKOUTS
CAUTION:
These units have a crankcase heater factory installed. Wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase.
Failure to comply may result in damage and could cause premature failure of the system.
Grounding
WARNING:
The unit must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or approved conduit when installed in accordance with national or local codes.
STARTUP AND ADJUSTMENTS
Pre-Start Checklist
The following check list should be observed prior to starting the unit.
Is the unit level? Unit should be level or slightly slanted toward the drain for proper condensate drainage.
Is the wiring correct according to the wiring diagram and electrical codes?
Inspect wiring for evidence of open, shorted, and/or improperly wired circuits.
Are all the wiring connections tight? Check the condenser fan to make sure it turns freely.
Is the overcurrent protection properly sized?
Is the thermostat wired correctly? Is it installed in a proper location?
Verify air fi lters are clean and in place prior to operating the equipment.
Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
Cooling
Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
Heating
If heating equipment (furnace, air handler) is provided with the system, lower the thermostat setpoint temperature to the lowest temperature setting and change the thermostat’s function mode to HEAT. The outdoor unit should stop running and the indoor blower will shut off after the preprogrammed delay. Increase the thermostat’s setpoint temperature to the maximum setting.
Verify the heating equipment and the indoor blower energize after a short period of time. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature.
Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
NOTE:
Other heating sources (electric furnace, fossil fuel furnace, air handler with electric heat options, etc.) that interface with the air conditioner should be functionally checked to verify system operation and compatibility. Refer to the installation instructions for this equipment and perform a functional checkout in accordance with the manufacturer’s instructions.
Thermostat
Set the thermostat’s system mode to OFF, the fan mode to AUTO, and adjust the temperature setpoint to its highest setting.
Outdoor Unit
Prior to applying electrical power to the outdoor unit, verify that the unit has been properly and securely grounded, and that power supply connections have been made at both the facility power interface and outdoor unit.
Indoor Blower
1. Turn the fan mode to ON. Verify that the indoor blower is operating and that airfl ow is not restricted.
2. Set the fan mode back to AUTO. Blower will operate at a decreased speed on continuous fan.
11
Short Cycle Protection
1. With the system operating in COOLING mode, record the setpoint temperature setting of the thermostat.
2. Gradually raise the setpoint temperature until the outdoor unit and indoor blower deenergize.
3. Immediately lower the setpoint temperature of the thermostat to its original setting and verify that the indoor blower is energized and that the outdoor unit remains de-energized.
4. After approximately 3 minutes, verify that the outdoor unit energizes and the temperature of the air supplied to the facility is cooler than ambient temperature.
not recommended and deviatons from rated airfl ows or non-listed equipment combinations may requiree modifi cations to the expansion devices and refrigerant charging procedures for proper and efi cient system operation.
Factory refrigerant levels are listed in Table 3
*4BF-
024KA
036KA
048KB
System Charge
R-410A oz.
150
170
278
Optional Equipment
A functional checkout should be performed in accordance with the checkout procedures supplied with the equipment.
060KB 260
Table 3. Split System
Air Conditioner Charge
ADJUSTMENT OF REFRIGERANT
CHARGE:
WARNING:
Split sytem air conditoners are shipped fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation/service personnel to service this type of equipment.
Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
Charging an R-410A unit in AC mode at outdoor temperatures above 65F.
1. With the system operating at steady-state, measure the liquid refrigerant pressure in psig at the service valve.
2. Measure the liquid refrigerant temperature in
Fahrenheit at the service valve.
3. For the temperature measured, determine the required liquid refrigerant pressure from the appropriate charging charts in Figures 4 - 7
(pages 13 - 14).
4. If the pressure measured in step 1 is greater than the required liquid refrigerant pressure determined in step 4, then there is too much charge in the system. Remove refrigerant and repeat steps 1 through 3 until the system is correctly charged.
5. If the pressure measured in step 1 is less than the required liquid refrigerant pressure determined in step 4, then there is too little charge in the system. Add refrigerant and repeat steps 1 through 3 until the system is correctly charged.
NOTES:
• The unit must be charged while both fi rst and second stages are operating.
• To achieve rated capacity and effi ciency the compressor must be exposed to refrigerant for at least 24 hours prior to running and then must be run for a minimum of 12 hours.
• The refrigerant charging charts (Figures 4 -
7, pages 13 - 14) are applicable to matched assemblies of our equipment and at listed airfl ows for the indoor coil. Assemblies of indoor coils and outdoor units not listed are
12
Cooling Charging Charts
*4BF-024KA Charging Chart
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70
Remove refrigerant when above curve
75 80 85 90 95
Add refrigerant when below curve
100 105 110 115 120 125 130 135
Liquid Temperature (F)
Figure 4. Charging Chart for 2 Ton Units
*4BF-036KA Charging Chart
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70 75 80 85 90 95 100 105 110 115 120 125 130 135
Liquid Temperature (F)
Figure 5. Charging Chart for 3 Ton Units
13
Cooling Charging Charts (continued)
*4BF-048KB Charging Chart
475
450
425
400
375
350
600
575
550
525
500
325
300
275
250
225
200
70
Remove refrigerant when above curve
75 80 85 90 95
Add refrigerant when below curve
100 105 110 115 120 125 130 135
Liquid Temperature (F)
Figure 6. Charging Chart for 4 Ton Units
14
*4BF-060KB Charging Chart
375
350
325
300
275
250
70
500
475
450
425
400
Remove refrigerant when above curve
75 80 85 90 95
Sa tur at ion
Lin e
Add no more than 0.5 lbs refrigerant when between curve and saturation line. If assistance is needed, call 1-800-4AC-HEAT
100 105
Liquid Temperature (F)
110 115 120 125
Figure 7. Charging Chart for 5 Ton Units
TROUBLESHOOTING
Status
LED
Green
“POWER”
Red “TRIP”
Yellow “ALERT”
Flash Code 1
Yellow “ALERT”
Flash Code 2
Status LED
Description
Status LED Troubleshooting Information
Module has power
Supply voltage is present at module terminals
Thermostat demand signal
Y is present, but compressor is not running
•
Compressor protector is open
•
Check for high head pressure
• Check compressor supply voltage
•
Outdoor unit power disconnect is open
•
Compressor circuit breaker or fuse(s) is open
• Broken wire or connector is not making contact
•
Low pressure switch open if present in system
•
Compressor contactor has failed open
Long Run Time
Compressor is running extremely long run cycles
•
Low refrigerant charge
•
Evaporator blower is not running
—
Check blower relay coil and contacts
—
Check blower motor capacitor
—
Check blower motor for failure or blockage
—
Check evaporator blower wiring and connectors
—
Check indoor blower control board
—
Check thermostat wiring for open circuit
• Evaporator coil is frozen
—
Check for low suction pressure
—
Check for excessively low thermostat setting
—
Check evaporator airfl ow (coil blockages or return airfi lter)
—
Check ductwork or registers for blockage
• Faulty metering device
—
Check TXV bulb installation (size, location and contact)
—
Check if TXV/fi xed orifi ce is stuck closed or defective
• Condenser coil is dirty
•
Liquid line restriction (fi lter drier blocked if present in system)
•
Thermostat is malfunctioning
—
Solenoid plug not connected
—
Y2 not wired at Comfort Alert
—
Check thermostat sub-base or wiring for short circuit
—
Check thermostat installation (location, level)
•
Comfort Alert failure
System
Pressure Trip
- Discharge or suction pressure out of limits or compressor overloaded
• High head pressure
—
Check high pressure switch if present in system
—
Check if system is overcharged with refrigerant
—
Check for non-condensable in system
•
Condenser coil poor air circulation (dirty, blocked, damaged)
• Condenser fan is not running
—
Check fan capacitor
—
Check fan wiring and connectors
—
Check fan motor for failure or blockage
•
Return air duct has substantial leakage
• If low pressure switch present in system, check Flash Code
1 information
Table 4. LED Diagnostics
15
16
TROUBLESHOOTING - CONTINUED
Status LED
Status LED
Description
Status LED Troubleshooting Information
Yellow “ALERT”
Flash Code 3
Yellow “ALERT”
Flash Code 4
Yellow “ALERT”
Flash Code 5
Short Cycling
Compressor is running only briefl y
Locked Rotor
Open Circuit
•
Thermostat demand signal is intermittent
•
Low line voltage (contact utility if voltage at disconnect is low)
•
Excessive liquid refrigerant in compressor
•
Compressor bearings are seized
• Run capacitor has failed
•
Low line voltage (contact utitlity if voltage at disconnect is low)
•
Check wiring connections
•
Excessive liquid refrigerant in compressor
• Compressor bearings are seized
•
Measure compressor oil level
•
Outdoor unit power disconnect is open
• Compressor circuit breaker or fuse(s) is open
•
Compressor contactor has failed open
—
Check compressor contactor wiring and connectors
—
Check for compressor contactor failure (burned, pitted or open)
—
Check wiring and connectors between supply and compressor
—
C heck for low pilot voltage at compressor contactor coil
—
High pressure switch is open and requires manual reset
•
Open circuit in compressor supply wiring or connections
• Unusually long compressor protector reset time due to extreme ambient temperature
• Compressor windings are damaged
—
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 6
Yellow “ALERT”
Flash Code 7
Open Start
Circuit
Current only in run circuit
Open run circuit
Current only in start circuit
•
Run capacitor has failed
•
Open circuit in compressor start wiring or connections
—
Check wiring and connectors between supply and the compressor
S
terminal
•
Compressor start winding is damaged
—
Check compressor motor winding resistance
•
Open circuit in compressor run wiring or connections
—
Check wiring and connectors between supply and the compressor
R
terminal
•
Compressor run winding is damaged
—
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 8
Welded
Contactor
Compressor always runs
•
•
Compressor contactor has failed closed
Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Voltage
Control circuit
< 17VAC
• Control circuit transformer is overloaded
•
Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
* Flash code number corresponds to a number of LED fl ashes, followed by a pause and then repeated. Trip and alert LED’s fl ashing at same time means control circuit voltage is too low for operation.
Table 4. LED Diagnostics - Continued
TROUBLESHOOTING - CONTINUED
Miswired Module Indication
Trip LED is on, but system and compressor check OK
Recommended Troubleshooting Action
Green LED is not on, module does not power up
• Determine if both
R
&
C
module terminals are connected.
• Verify voltage is present at module’s
R
&
C
terminals.
Green LED intermittent,
• Determine if
R
&
Y
terminals are wired in reverse.
module powers up only when
• Verify modules R and C terminals have a constant source.
compressor runs
• Verify
Y
terminal is connected to 24VAC at contactor coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Verify 24VAC is present across
Y
&
C
when thermostat demand signal is present. If not,
R
&
C
are reversed wired.
TRIP LED and ALERT LED fl ashing together
• Verify
R
and
C
terminals are supplied with 19 - 28VAC.
ALERT Flash CODE 3 displayed incorrectly (Compressor short cycling)
• Verify
Y
terminal is connected to 24VAC at contactor coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Verify the compressor run and start wires are routed
ALERT Flash Code 5, 6, or 7 through the module’s current sensing holes.
displayed incorrectly (Open • Verify the
Y
terminal is connected to 24VAC at contactor
Circuit, Open Start Circuit or
Open Run Circuit) coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
ALERT Flash Code 6 (Open
Start Circuit) displayed for
Code 7 (Open Run Circuit) or vice-versa
• Verify the compressor run and start wires are routed through the correct module sensing holes.
ALERT Flash Code 8 displayed incorrectly (Welded Contactor)
• Determine if module’s
Y
terminal is connected.
• Verify
Y
terminal is connected to 24VAC at contactor coil.
• Verify 24VAC is present across
Y
&
C
when thermostat demand signal is present. If not,
R
and
C
are reversed wired.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Review Thermostat Demand Wiring (page 10) for
Y
&
C
wiring.
Table 5. Module Wiring Troubleshooting
17
18
19
INSTALLER: PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS WITH
THE HOMEOWNER.
O’Fallon, MO
¢709129;¤
7091290
7091290
(Replaces 7090240)
Specifi cations and illustrations subject to change without notice or incurring obligations.
Printed in U.S.A. (11/09)
advertisement