advertisement
▼
Scroll to page 2
of
30
® Turn to the Expertg Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Installer: Make sure the Owner's Manual and Service Instructions are left with the unit after installation, TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS ......................... 1 INTRODUCTION ................................... 2 RECEIVING AND INSTALLATION ................. 2-16 Check Equipment .................................. 2 Identify Unit .................................... 2 Inspect Shipment ................................. 2 Provide Unit Support ............................... 2 Roof Curb ...................................... 2 Slab Mount ..................................... 2 Ground Mount .................................. 2 Provide Clearances ................................. 2 Rig and Place Unit ................................. 2 Inspection ...................................... 2 Installation ...................................... 2 Select and Install Ductwork ........................... 5 Converting Horizontal Discharge Units to Downflow (Vertical) Discharge Units .......................... 7 Provide for Condensate Disposal ...................... 7 Install Electrical Connections ......................... 7 High-Voltage Connections ......................... 8 Routing Power Leads into Unit ...................... 8 Connecting Ground lead to Ground Lug ............... 8 Routing Control Power Wires (24-v) ................. 8 Easy Select _ . ................................... 9 50XZ Sequence of Operation ...................... 15 Special Procedures for 208-V Operation .............. 16 PRE-START-UP ................................... 16 START-UP ..................................... 16-19 50XZ Start-Up ................................... 16 Check for Refrigerant Leaks ......................... 17 Start-Up Adjustments ............................. 17 Check Cooling & Heating Operation ................. 17 Checking & Adjusting Refrigerant Charge ............ 18 Refrigerant Charge .............................. 18 No Charge ..................................... 18 Low Charge Cooling ............................. 18 To Use Cooling Charging Charts .................... 18 Indoor Airflow & Airflow Adjustments .............. 18 Defrost Control ................................... 19 Quiet Shift ..................................... 19 Defrost ....................................... 19 MAINTENANCE ................................ 20-25 Air Filter ........................................ 20 Indoor Blower and Motor ........................... 20 Outdoor Coil, Indoor Coil, & Condensate Drain Pan ...... 20 Outdoor Fan ..................................... 23 Electrical Controls and Wiring ....................... 23 Refrigerant Circuit ................................. 23 C99088 Fig. 1 - Unit 50XZ Indoor Airflow ................................... Metering Devices- TXV & AccuRater Piston .......... Pressure Switches ................................. Loss of Charge Switch ............................. High Pressure Switch .............................. Copeland Scroll compressor (Puron Refrigerant) ......... Refrigerant System ................................ Refrigerant .................................... Compressor Oil ................................. Servicing Systems on Roofs with Synthetic Materials .... Liquid Line Filter Drier ........................... Puron® (R-410A) Refrigerant Charging ............. System Information ................................ Loss of Charge Switch ............................ Check Defrost Thermostat ......................... TROUBLESHOOTING .............................. START-UP CHECKLIST ............................ TM SAFETY Improper installation 23 23 24 24 24 24 24 24 24 24 25 25 25 25 25 25 25 CONSIDERATIONS adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product Refer packaged with the kits or accessories to the individual when installing. instructions Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available. thoroughly and follow all warnings Read these or cautions instructions included in literature andattached to the current editions In Canada unit. Consult of the National refer to the current local building Electrical editions Code (NEC) codes, the NFPA of the Canadian 70. electrical Code CSA C22A. Recognize safety IMPORTANT: The gasketing for a watertight seal. Install roof curb. Improperly of the unit to the roof curb is critical gasketing applied material gasketing supplied with the also can result in air leaks and poor unit performance. information. This is the safety-alert symbol /_. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Curb should be level to within 1/4 in. (3 m) (See Fig. 6). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required. SLAB MOUNT Place the unit on a solid, level concrete pad that is a minimum except when required GROUND by local codes. MOUNT The unit may be installed either on a slab or placed directly ground if local codes permit. Place the unit prepared with gravel for condensate discharge. ELECTRICALSHOCK Failure to follow injury or death. HAZARD this warning could result in personal Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. of 4 in. (102 mm) thick with 2 in. (51 mm) above grade (See Fig. 7). The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab on on the level ground Step 3 -- Provide Clearances The required 3. Adequate minimum ventilation service clearances are shown in Fig. 2 and and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead under a partial overhang in. (1219 mm) above obstruction. The minimum clearance (such as a normal house overhang) is 48 the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm) IMPORTANT: Do not restrict outdoor airflow. An air restriction FIRE, EXPLOSION, CARBON MONOXIDE Failure to follow this injury, death or property ELECTRICAL POISONING warning damage. could SHOCK HAZARD result AND at either in personal A qualified installer or agency must use factory-authorized kits or accessories when modifying product. 50XZ heat pump is fully and designed for outdoor installation. (See Fig. 1) Standard units are shipped in a horizontal-discharge configuration for installation on a groundlevel slab. Standard units can be converted to downflow (vertical) discharge configurations RECEIVING for rooftop AND inlet or the fan discharge applications. The unit model number and serial number are stamped on the unit identification plate. Check this information against shipping Rigging many and reasons structures, handling due of this equipment to the installation can be hazardous location (roofs, qualified crane operators and install this equipment. and ground support Follow gloves. all applicable safety codes. Wear safety shoes and straps should be visually inspected for any damage, of wear, structural deformation, or cracks. Particular should be paid to excessive wear at hoist hooking points Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before Forward claim papers directly to transportation Manufacturer is not responsible for any damage incurred leave Step 2 -- Provide ROOF CURB Install accessory all parts in original removal. company. in transit. notify the To prevent packages until Unit Support roof curb in accordance staff and work INSPECTION Prior loss or damage, installation. for elevated etc.) Only trained, should handle INSPECT SHIPMENT against shipping list. Immediately distributor if any item is missing. units water Rig and Place Unit papers. all items equipment be When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply. INSTALLATION Step 1 -- Check Equipment IDENTIFY UNIT Check nearest may life. carpeting or other combustible materials. Slab-mounted should be at least 4 in. (102 mm) above the highest expected and runoff levels. Do not use unit if it has been under water. only this Step 4 -- self-contained outdoor-air to compressor Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on INTRODUCTION The the detrimental to initial use, and at monthly intervals, all rigging brackets evidence attention and load support areas. Brackets or straps showing any kind of wear in these areas must not be used and should be discarded. INSTALLATION 1. Remove unit from shipping carton. Leave top shipping skid on the unit as a spreader bar to prevent the rigging straps from damaging use a spreader the unit. If the wood skid is not available, bar of sufficient length to protect unit from damage. 2. Position with instructions with curb (See Fig. 5). Install insulation, cant strips, flashing. Ductwork must be attached to curb. shipped roofing, and the lifting bracket assembly unit. Be sure the strap does not twist. around the base of the 3OXZOR4 5460 861 [359] UNIT ELECTRICAL CHARACTERISTICS UNIT 208 230 I 60 WT UNIT KG IIAII 5 DO] Z 320 1451 940313702] 3683[145] 4064[160] 3 60 360 1633 991113902] 5588[220] 3874[153] 4470[176] 50XZO38 208/230 I 60, 2031230 3 60 403 1828 1041R[4102] 50801200] 3556[140] 4470[176] WEIGHT .... 2 CLEARANCES TO COMBUSTIBLE MATL. LBS/HG .... 3 .... 581263 34/243 731341 133/604 030 89/313 37/259 86/390 1481672 036 83/377 62/281 96/436 162/735 MILLIMETERS [IN] 355 6 [1400] 508 [2 00] 355 6 [14 O0] 127 [OBO] 9144 [3600] TOP OF UNIT ............................. DUCT SIDE OF UNIT ............................ SIDE OPPOSITE DUSTS ........................ BOTTOM OF UNIT ................................... ELECTRIC HEAT PANEL ................................ 4. 024 NEC. REQUIRED CLEARANCES MILLIMETERS [IN] BETWEEN UNITS, POWER ENTRY SIDE ................. I066 8 [42 00] UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ........ 9140 [3600] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY SIDE .................. 10668 [4200] REG_RED CLEARANCE FOR OPERATION AND SERVICING Y EVAP COIL ACCESS SIDE ..................... POWER ENTRY SIDE ............................ (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ........................................... SIDE OPPOSITE DUCTS .................................... DUCT PANEL .............................................. @ ml COIL OUTDOOR MMIIN Y 2031230 T INDOOR GRAVITY I 60, III It OF 2031230 CORNER ,t06 [16 CENTER 53XZO30 REO_RED 705 [878] HEIGHT LBS _MINIMUM MILLIMETERS [IN] 91_0 [36 OO] 91_0 [3600] 91_0 9140 3048 [3600] [3600] [12DO]+ DISTANCES:IF UNIT IS PLACED LESS THAN 3048 [1200] FROM WALL SYSTEM,THEN SYSTEM PERFORMANCE MAYBE COMPROMISED DIMENSIONS I IN [] ARE IN INCHES TOP VIEW I _7985 11939 [4700] [31 44] t FIELD ENTRY_ SERVICE FULL PORTS I LOUVER o, FULL LOUVER = _° ,_FULL A 222 LOUVER _ii° t [088] DIA HOLE CONTROL ENTRY_ N 4020 [1583] \ 5703 [2245] / t n I m _ 2762 [1087] 117 ! [463] [530] _COMPRESSOR, BLOWER, & ELECTRICAL o ° 1 [O2O] ACCESS ELECTRIC PANEL [1285] > RETURN DUCT OPENING _BO 871 [343] LEFT SIDE VIEW SUPPLY DUCT _ • X 13 427 [I 68] 8310 [3272] • FULL_O_ LOUVER.... OPENING Z , [285] _'-_-_ mm_ _ 5 [I 75] DIA POWER ENTRY KO HEAT 1222 [481] 88 [3 3 48] _ _5505 [2167] PaR6 [983] 2496 [985] 12263 [4828] FRONTVIEW RIGHT SIDE VIEW REAR VIEW 3DXZBDO22R /% UNIT ELECTRICAL CHARACTERISTICS UNIT WT LBS HG UNIT HEIGHT CENTER 208 230 I 60, 208/230 3 60 4Sa 206 10917[4298] 50XZO48 208 230 I 60, 208/230 3 60 479 217 11425[4_983 4953[1953 SOXZO6O 208 230 I 60, 208/230 3 60 499 226 1193 5334[21 III .... WEIGHT 2 REQUIRED CLEARANCES LBS/KG .... 3 .... 411 042 961436 591268 124/563 175/795 048 1021463 651295 131/595 1811822 000 107/486 70/318 136/617 186/844 MM/IN Y 50XZO42 CORNER OF GRAVITv "A" Z 4476[176] 3[4698] _572[180] 4476[1763 O] 5080[20 4572[1803 O] 4_20[17,6] TO COMBUSTIBLE MATL. MILLIMETERS [IN] 3556 [1400] 508 [200] 355 6 [14 003 127 [0 50] 9144 [3600] TOP OF UNIT ........................................ DUCT SIDE OF UNIT .............................. SIDE OPPOSITE DUCTS ....................... BOTTOM OF UNIT ........................... ELECTRIC HEAT _ANEL ..................................... [16 01] NEC. REQUIRED CLEARANCES. MILLIMETERS [IN] 10658 [4200] 9140 [3600] BETWEEN UNITS, POWER ENTRY SIDE ....................... UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ........ UNIT AND _LOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY SIDE ........... REQUIRED CLEARANCE 10668 MILLIMETERS [IN] 9140 [3600] 9140 [3000] EVAP COIL ACCESS SIDE .................................. °OWER ENTRY SlOE ........................................ (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP .................................. SIDE OPPOSITE DUCTS ...................... DUCT PANEL ............................ INDOOR [4200] FOR OPERATION AND SERVICING 9140 9140 3048 [3600] [3600] [1200]_ COIL _MINIMUM [_ OUTDOOR / Q DISTANCES:IF D COIL _VI UNIT IS SYSTEM,THEN PLACED LESS THAN 3048 [1200] FROM WALL SYSTEM PERFORMANCE MAYBE COMPROMISED DIMENSIONS IN [] ARE IN INCHES I TOP VIEW & 11939 [4700] 10906 [4294] FIELD r_ SERVICE FULL ENTRY_ FORTS i I / 230 E091] LOUVER FULL LOUVER .,_j _° 75] 445 [I T LOUVER m DIA HO POWER ENTRY_ t 5292 :2442] FULL 402 [15 t 0 83] SUPPLY DUCT RETURN DUCT • . OPENING 326 I [1284] 1177 [4 63] 427 • [168] DRAIN OUTLET 190 [075] NPT X 220 [088] DP _x COMPRESSOR, BLOWER, & ELECTRICAL _4 ELECTRIC HEAT ACCESS PANEL [1295] 11231 [4422] LEFT SIDE VIEW o> 2 2 I 12263 [4828] FRONT VIEW I [0 869 [342] IR20 [481] [088] OlA CONTROL ENTRY 16] .___J__ I [343] _3512 _ _B51 [1383] RIGHT SIDE VIEW --4. _3413 E1367] _872 HOLE 1 2 [1383] '_ REAR VIEW [ D rev 50XZSOO183 1 2 Y C00071 RIGGING WEIGHTS (SMALL CABINET) 024 Unit Rigging Weight RIGGING WEIGHTS (LARGE CABINET) 030 036 042 Ib kg Ib kg Ib kg Unit 331 150 371 168 414 188 Rigging Weight Fig. 4 - Rigging 3. Place each of the 4 metal holds in the composite strapping a. Open lever of tension c. Pull strapping into the rigging around bottom (ratchet type). through tension buckle perimeter as shown tension buckle field-supplied safety latch, lift lever, clevis or hook in Fig. When 8. Position lifting of sufficient brackets Failure to follow injury or death. strength to the unit's center of gravity. 9. Lift unit. When unit is directly the 2 safety straps. Lower 10. After the unit is placed ductwork 90 approximately 4 The design and installation of the duct system must be accordance with the standards of the NFPA for installation conditioning NFPA ductwork, consider openings the following: heaters warning could result in personal the unit and the conditioned cannot be and density falling installed, should 90 degree a grille be installed into the conditioned require space. If a then of to prevent space. Units with elbow in supply duct. 1. All units should have field-supplied filter rack installed in the return-air Recommended and ventilating 90B and/or filters side sizes for filters are shown or accessory of the unit. in Table 1. 2. Avoid abrupt duct size increases and reductions. change in duct size adversely affects air performance. IMPORTANT: unit Use to prevent ensure weather installed, flexible connectors transmission tight use fireproof and between of vibration. airtight canvas seal. (or similar ductwork Use suitable When heat Abrupt to heat is electric resistant and gaskets material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat Step 5 -- Select and Install Ductwork air strength from pad, in. (102 mm) down the tube sheet. The wire tie to be cut on the right is located approximately 6 in. (152 mm) down the tube sheet. type and return-air and return units, tools or parts could Install a 90 degree turn in the return elbow electric onto the roof curb. on the roof curb or mounting assembly must be cut. Remove the left panels and corner post to access wire ties. NFPA 90A or residence-type, ordinances. Heating, recommendations. over the roof curb, remove the equipment The wire tie to be cut on the left is located non-residence air grilles of HAZARD this between degree objects remove the top crating. On 50XZ060 units only, 2 wire ties fastened to the outdoor coils and reversing valve/accumulator and front louver INJURY For vertical supply drop into ductwork sufficient over Engineers) on the supply- and installing PERSONAL (See Fig. 9) directly designing and return Society To (See Fig. 9). point registers, (American and Air Conditioning and 7. Attach the 2 safety straps directly to the clevis or hook at the 4 rigging brackets. DO NOT attach the safety straps to the lifting brackets Refrigeration, supply-air ASHRAE unit taut. 5. Tighten the tension buckle until it is taut. Lifting must be secure in the rigging holds. hole in the lifting bracket. to The unit has duct flanges on the side of the unit. to lock strap in tension buckle. release strapping, squeeze pull webbing outward. 6. Attach Select and size ductwork, of 060 Weights according buckle through d. Snap lever down brackets unit base. 4. Thread lifting bracket unit as follows: b. Feed strapping 8. lifting 048 in of systems, local codes and resistant duct connector (610 mm) from electric (or sheet metal sleeve) 3. Size ductwork for cooling air quantity air quantity for proper electric heater Table below must extend 24-in. heater element. 2. Heater limit switches those recommended. may (cfm). The minimum operation is listed in trip at air quantities / / / base ,,,_crew'_._ / (NOTEA) _ *Gasketin;..._ _ I II1_11t Flashing field I supplied _ _n_il_ Roofcurb* II_i;llltJ \ _, field supplied Roof Curb for Small II ii l" Roofing matei'at \ /l_!i:llll _ Duct we rk field supplied c__tllt Cabinet Roof Curb for Note A:When unit mounting screw is used retainer bracket must also be used. Supply (BxC) Note Insulation(field supplied) j / Large Cabinet A:When unit mounting screw is used retainer bracket must also be used. opening \/ R/A S/A _ Gasket around \. duct / Insulated deck pan /2 \ Gasket around outer edge \ \\ \ C00076 UNIT SIZE 50XZ024-036 50XZ042-060 ODS CATALOG NUMBER A IN. (MM) B IN. (MM) CPRFCURB006A00 8 (203) 11 (279) 16-1/2 (419) 28-3/4 CPRFCURB007A00 14 (356) 11 (279) 16-1/2 (419) 28-3/4 17-3/8 17-3/8 (441) (441) CPRFCURB008A00 CPRFCURB009A00 8 (203) 14 (356) 16-3/16 16-3/16 NOTES: 1. Roof curb must be set up for unit being installed, 2. Seal strip must be applied, as required, to unit being installed. 5. Roof curb is made of 16-gauge steel, 6. Attach ductwork to curb (flanges of duct rest on curb). 7. Insulated panels: 1 -in. (25 mm) thick fiberglass 1 Ib (.45 kg) density. 8, When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl. Fig. 5 - Roof Curb Dimensions (411 ) (411) C IN. (MM) D IN. (MM) (730) (730) 40-1/4 (1022) 40-1/4 (1022) 2. Remove horizontal duct covers to access bottom return and supply knock out panels. 3. Use a screwdriver and hammer to remove the panels in the bottom of the unit base. NOTE: These panels are held in place with tabs similar to an electrical knockout. MAXIMUM ALLOWABLE DIFFERENCE in. (mm) B 4. Reinstall the horizontal duct covers (Fig. 11) to block off the horizontal air openings. A-B B-C ArC 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) NOTE: Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance. A07925 Fig. 6 - Unit Leveling IIIII OPEN'NGt /' [[[ I_l IIIII IIIII IIIII \ IIII 2" (50.8ram) ± EVAR COIL COND. COIL A07926 Fig. 7 - Slab Mounting Detail oo FEED C99067 Fig. 8 - Threading Belt 4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems. 5. Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices. CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE Provide for Condensate UNITS The 50XZ units dispose of condensate through a 3/4 in. NPT female fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit. If the installation requires draining the condensate water away from the unit, install a field-supplied 2 -in. trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field-supplied. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field-supplied 3/4-in. PVC or field-supplied 3/4-in. copper pipe at outlet end of the 2-in. (51 mm) trap. (See Fig. 12) Do not undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. (25 mm) every 10 ft (3 m) of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start-up. Step 7 -- UNIT Install Electrical COMPONENT 1. Make all electrical ANSI/NFPA governing connections C22.1 Canadian 3. Be sure operating HAZARD Failure to follow this warning could result in personal iniury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. 1. Open all electrical work. disconnects before starting any servace could result in damage connections in accordance Electrical Code Refer to unit wiring copper conductor field-supplied electrical NOT USE ALUMINUM SHOCK HAZARD to the unit with NEC 70 (latest edition) and local electrical codes such wiring. In Canada, all electrical must be in accordance with CSA standard local codes. only Connections DAMAGE Failure to follow this caution being installed. 2. Use ELECTRICAL Disposal NOTE: Ensure that condensate-water disposal methods comply with local codes, restrictions, and practices. Tolerances ill_ RETURN AIR IIIII IIII| III1! IIIII .... Step 6 -- Part 1 and applicable diagram. for connections disconnect WIRE. switch between and unit. DO that high-voltage power to unit is within voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within percent. Consult local power company for correction improper voltage and/or phase imbalance. 2 of 4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are in same conduit as high-voltage 5. Do not damage internal through any panel to mount etc. wires. components when electrical hardware, drilling conduit, DETAIL A SCALE 0.250 TIGHTEN STRAPPING SECURELY WITH TENSION BUCKLE INSTALL RIGGING SEE DETAIL SAFETY CLEVIS STRAPS TO AT 4 RIGGING BRACKETS PLACE RIGGING BRACKET ASSEMBLY IN 4 HAND HOLES AND INSTALL TIE DOWN STRAP AROUND PERIMETER OF UNIT AND THROUGH SPACE IN BRACKET ASSEMBLY A C99075 U NIT 50XZ A B in, 19.0 19.0 20.0 20.0 20.0 2t .0 024 030 036 042 048 060 in, 18.25 18.25 19.0 2t .25 2t .25 20.0 mm 482.6 482.6 508.0 508.0 508.0 533.4 Fig. 9 - Suggested Rigging ROUTING ELECTRICAL SHOCK could result in personal Run the high-voltage injury Association (latest edition) (in Canada, Canadian Code CSA C22.1) and local electrical codes. The unit must have separate 3-phase wires. service with a for wire sizing. The field-supplied disconnect may be mounted the high-voltage inlet hole (See Fig. 2 and 3). on the unit over If the unit has an electric heater, a second disconnect required. Consult the Installation, Start-Up, and Instructions connections. Operation provided with the accessory for may be Service electrical on improper may cause unit damage line voltage that could constitutes service affect warranty. abuse entry knockout on connect splice box (See Fig. 13 through 17). For leads to the black and yellow wires; for the leads GROUND to the black, LEAD and CONTROL POWER low-voltage hole provided The unit transformer supplies power LUG (24-V) unit control thermostat 24-v and blue lead to the chassis leads before leads through in unit into box. (See Fig. 2 and 3) Connect power leads as shown in Fig. 15. yellow, TO GROUND WIRES Form a drip-loop with the thermostat into the unit. Route the thermostat routing them grommeted, power splice leads to unit control for complete system including accessory electrical heater. An automatic-reset circuit breaker (See Fig. 17) is provided in the 24-v circuit; see the caution label on the transformer or Fig. 18. Transformer is factory wired for 230-v operation. If supply voltage is 208-v, rewire transformer primary as described in Special Procedures for 208-v Operation of unit UNIT Refer to Fig. 15 and 16. Connect the ground using the ground lug in the wiring splice box. ROUTING electrical units, CONNECTING Electrical field-supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) INTO leads through the power raceway to the line wiring singlephase units, connect CONNECTIONS a LEADS the power entry side panel. (See Fig. 2 and 3 for location and size) When the leads are inside the unit, run leads up the high-voltage The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA 70 American National Standards Institute/National Fire Protection HIGH-VOLTAGE POWER Use only copper wire between disconnect and unit. The highvoltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. HAZARD Failure to follow this warning or death. mm 463.6 463.6 482.6 539.8 539.8 508.0 section. Table UNIT SIZE NOMINAL CAPACITY (ton) SHIPPING WEIGHT (Ib) (kg) COMPRESSOR QUANTITY TYPE REFRIGERANT REFRIGERANT METERING DEVICE Rows... LOSS- OF- CHARGE/LOW- 0.038 (.89) (2) 0.038 (.97) (.97) 2...21 2...21 2...21 2...21 13.6 15.4 17.4 19.3 2700 22 2700 22 2800 22 2800 22 3300 22 3300 22 559 1/8 (825) 559 1/8 (825) 559 1/8 (825) 559 1/8 (825) 559 1/4 (1100) 559 1/4 (1100) 3...15 3...15 4...15 3...15 4...15 4...15 3.7 3.7 3.7 4.7 4.7 5.7 800 10x10 1000 10x10 11 O0 1 lx10 1400 1 lx10 1450 1 lx10 1750 1 lx10 254x254 1/2 254x254 1/2 279x254 3/4 279x254 3/4 279x254 3/4 279x254 1.0 (psig) 650_+15 420_+25 PRESSURE SWITCH (Liquid Line) (psig) Cutout RETURN-AIR (2) 13.5 6.1 TXV 0.042 (Left OD Coil) 0.052 (Right OD Coil) (1.07 Left OD Coil) (1.32 Right OD Coil) 12.0 Airflow (CFM) Size (in.) PRESSURE SWITCH Cutout Reset (Auto) (2) 11.5 5.2 TXV 0.038 (Left OD Coil) 0.046 (Right OD Coil) (.97 Left OD Coil) (1.17 Right OD Coil) 2...21 Fins/in. (mm) Motor (H P) HIGH- 0.035 5.0 TXV 50XZ080 5 551 250 12.3 face area (sq. ft.) INDOOR BLOWER Nominal (2) 4.4 TXV 50XZ048 4 531 241 2...21 face area (sq. ft.) OUTDOOR FAN Nominal Airflow (CFM) Diameter (in.) OUTDOOR COIL (mm) Motor HP (RPM) INDOOR COIL 50XZ042 3.5 508 230 1 SCROLL COMPRESSOR R- 410A Indoor-TXV Outdoor-Accurater 9.7 11.0 3.7 TXV (.89) Fins/in. 50XZ036 3 451 205 8.2 0.035 (mm) Data - Unit 50XZ 50XZ030 2.5 408 185 7.5 3.4 TXV Refrigerant (R-410A) Quantity (Ib) (kg) METERING DEVICE ID ORIFICE OD (in.) QTY Rows... I - Physical 50XZ024 2 388 167 20_+5 45_+10 Reset (Auto) FILTERS throwaway* (mm) (in.) 20x20x1 508x508x25 20x24x1 508x610x25 24x30x1 610x762x25 *Required filter sizes shown are based on the larger of the ARI (Air conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wc. Table UNIT-5OXZ AIRFLOW 2 - Minimum 024 750 Airflow for Reliable 030 1025 EASY SELECT - 50XZ EASY SELECT CONFIGURATION to configure a system. The operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used. a. AUX HEAT kW/CFM-SELECT HEATER RANGE FOR SIZE OF ELECTRIC HEATER INSTALLED must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked Operation with a range of heaters for which airflow (Cfm) 042 1400 (also marked), TAPS FOR 50XZ ECM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. The unit must be configured to Installer Heater 036 1250 TM Easy Select taps are used by the installer Electric 048 1710 is approved. For increased 060 1800 comfort, select the narrowest kW range matching the heater size, for example, 0-10 for 10-kW heater. This airflow must be greater than the minimum for CFM for electric heater application with the size system installed for safe and continuous operation. (See Tables 3, 4, 5, 6 & 7 for airflow delivery and n_ininmm CFM.) Note that airflow marked is the airflow which will be supplied in emergency conditioners source. heaters heat mode and heating mode on air when electric heat is the primary heating In heat pump are energized, heating mode when electric the ECM will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved indicated). (See Fig. 19, A as l INDOOR {?i;i:/_: THERMOSTAT RETURN FROM POWER _ SOURCE TOP COVER DISCONNECT PER NEC* *NEC - NATIONAL ELECTRICAL CODE C00063 Fig. 10 - Typical Installation o Duct Covers C00092 Fig. 11 - 50XZ 1" (25 mm) with Duct Covers On MIN. A08001 Fig. 12 - Condensate 10 Trap OPM FOR 042-060 UNITS ONLY COMP BEN YEL- CTD (TI.TR) COMPRESSOR DELAY CLOSES TSAT OPENS LAST DFROST T=30 CYCLE T:DO TzDO MAXIMUM L I o_ G AUTO BW r Y bN L 0 I_SUPL HEAT k SUPPL / E W HEAT FIELD-THERMOSTAT SEE NOTE_2 LEGEND FIELD RPLICR _TERMINA[ o TERMINAL SPLICE C>SPLICE --FACTORY - -- FIELD --- FIELD (MAR_ED) (UNMARKED} (MARKED) WIRING CONTROL W]RINO POWER ---- ACCRSSORY WIRING DO DRY _ERROST DEFROST DR EQUIP OEFROST RELAY EQUIPMENT FU GND,_ _S FUSE GROUND HIGH PRESSURE REATZR RELAY HEATER WIRING HTR OR OPTIONAL ICM --TO INDICATE COMMON POTENTIAL ONLY: NOT TO RRPRZSENT WIRING AHA C ADJUSTABLE HRAT ANTICIPATOR CONTACTOR CAP CO CCH COMP CTO CAPACITOR CIRCUIT BREAKER CRANKCASR HEAIRR COMPRESSOR MOTOR COMPRESSOR TIME DELAY OOARD IHERMOSTAI INTEGRATED MOTOR S_ITCH CONTROL IFM LPS OFM PL INDOOR FAN MOTOR LOW PRESSURE S_ITC_ ODTOOOR FAN MOTOR PLUG QT RVS QAUDRUPLE REVERSING _CO RlO_ BLOW FUSE THERMOSTAT - COOLING TIME DELAY RELAy THERMOSTAT - HEATING TRANSFORMER IDR TH TRAN TEfiMIRAL VALVE SOLENOID ORB BLU VIO BLK WRIT DIP SWITCHSETTINGS NOIES: I _ A,Y O_ T_E ORIGINAL _[RES _RNIS_[D ARE REPLACED. IT _ST DE REPLAC[O _IT_ TyPE _0 _EGREE C WIRE OR IT'S EQUIVALENT 2 SEE PRICE PAGES FOR IHERMOSTAI AND S_BBASES 3USE 75 DEGREE COPPER CONDUCTORS fOR FIELD INSTALLATION 4 REPLACE LOW VOLTAGE £_S[S WITH NO GREATER THAN 5 AMP FUSES 5REMOVE Jl WREN _SJNB TRER_IDI_TATIHU_IDISTAT A_D DERUMIDI_ICAIIO_ _ODE 6REMOVR JR WREN _SINB ELECTRIC HEAT STAGING ? TO BE WIRED IN ACCORDANCE W1TR NEC AND LOCAl CODES 8THlS FUSE IS MANUFACTURED BY LIIILZFUSE. PiN 251005 UNIT OUTDOOR SECTION COMPONENT ARRANGEMENT FAN (DEFAULT} SD MINUTES "IN--AN- - -- CONTROL SECTION SINGLE PT _ I :ONNECTION FOR ELECT HEAT FIELD _UNTING PANEL ABOVE INDOOR BLOWER 60 _]NUTES BOX AREA L DEFROST BOARD SEE FOR WIRING SCHEMATIC OPTIONS FOR TIME PE RIOO DEC ON DEFOOST DIET SHIFT" ON POSITION / BEATER SELECTABL[ BETWEEN DEFROST CYCLES (MINUTES} THE COMPRESSOR WILL SHUT OFF FOR 30 INITIATION ANO TERMINATION [N THE "O /GNB EQUIP SREEO_ Up JUMPERED FIELO IC_t_l _ COMPRESSOR _R_tPL'CL _4v POWER ENTRY " TEST PINS SPEED-UP OFF IUSE METAL OBJECT ) CYCLE DELAY R} SHORT FOR R+ DEC AND RELEASE FOR I) _OMENPARILY SHORT PINS ANO RELEAS 3} PERMANENT SHORT WILL BE IGNORED FORCED DEFROST E TO BYPASS DEFROST DEFROST DFT OPEN FT IS CLOSED WILL WILL TERMINATE TERMINATE IN 30 SZC IF NORMALLY IF O 50JZ500312 04B ODO A0848_ Fig. 13 - Wiring Schematics - 50XZ 11 Single Phase 4.0 SCHEMATIC FIELD 2081_0-340 DR _YEL -- POWER [OUIP_GND FOR 042-060 YEL BL_ UNITS ONLY OHM COUP FOR 042-060 UNITS ONLY GRR-YEL YEL _ CTB (T1,T2) CO,_PRESSOR BELAY BET Oft,Of2 [_ TEL PL4-4 " _ RVS CI CI CLOSES TSAT OPENS LAST BFROST f:3O CYCLE _4AXIMU_ f:GO T:90 T:120 BLK 32 A_ MANUAL R[SETL_ I I I 6RN_YEL GRN-YEL / BRN -- TO C BRN-- TO OB BRN-- ON G AUTO SW TO C TO TRANS 5 ire AMP TO ICM / Y TO SECI b, TO TRANS ' SUPPL H SUPL HEAT E TO HR SUPPL BEAT F IELD-THZRF4OSTAT SEE NOTE_2 TO HR TO C LEGEND FIELD SPLICE Q TERMINAL (MARK[Of 0 TERMINAL (UNMARKED} O SPL]CE C]o SPL ]DE (_ARKE B) --FACTORY WIRING -- --FIELD CONTROL _tIRINB --- FIELD POWER WIRING ---- ACCESSORY OR OPTIONAL WIRING TO I_DICA_E CO_ON POTENTIAL ONLY: NOT TO REPRESENT WIRING DB DEEROST BOARD OFT DEFROST DR EOUIP FU BND HPS HR HTR DEFROST RELAY EOUIP,_ENT FUSE GROUND HIG,_ PRESSURE SW]TCB HEATER RELAY HEATER ]OX INTEGRATED CONTROL MOTOR INDOOR FAN )40_OR LOW PRESSURE SWITCH O_TDOOR fAN _{OTOR PLUG [F,_ LPS or_ PL -- AHA ADJUSTABLE NEAT ANTIC IPA_OR AP ¢B CCFL COMP CTD CAPACITOR CIRCUIT BREAKER CRANKCASE HEATER COMPRESSOR MOTOR COMPRESSOR TI_[ DELAY THERMOSTAT OT RVS OA_DRUPLE TERMINAL REVERSII_G VALVE SOLENOID SLOW BLOWY FUSE THER&{OSTAT " COOLING TLME DELAY RELAY THERMOSTAT - HEATING TRANSFORWER fOR fH THAN ORB BLU vIO BLH WHT DIP SWITCH SETTINGS NOTES: fir ANY OF THE ORIGINAL IT MUST aE REPLACED iT'S EOUlVALENT 2SEE PRICE 3USE 75 4REPLAC[ 5 A_P PAGES DEGREE LO_ _USES COPPER VOLIAGE 5REHOVE _I WHE_ DEHUMIDIFICATION 6REHOVE J2 [OR WHEN _IR[S WITN TYPE I_[RNOSIAT CONDUCTORS fUSES _IlN g_NISH{D 90 ARE _EGREE AN_ FIEL_ FOR _0 C REPLAC[D_ WIRE GREATER USING MO_E THERg[DISIAIIH_HIOlSTAI _SING ELECIRIC UNIT CONPONENT ARRANGEMENT OR OUTDOOR SECTION S_8BASES FAN (DEFAULT) 30 MINUTES INSIALLAT[O_ HEAl 12o }4INUTES gO MINUTES k_p CONTROL 710 BE _IR[_ I_ ACCORDANCE B TNIS _SE IS MANUFACTURED 60 MINUTES THAN BOX AREA SIAGING WITH NED AND BY LITTLE_SE, LOCAL P/_ C00£S 2570_5 SINGLE _ .... J PT _ CONNECTION FOR ELECT }_EAT # FIELB SELECTABLE OPTIONS FOR TIRE PE RIOO BETWEEN DEFROST CYCLES (MINUTES) THE COMPRESSOR WILL SHUT OFF FOR 30 SEC ON DEFROST INITIATION POSITIO_ DEFROST BOARD / SEE BEATER MOUNTING PANEL ABOVE INDOOR BLOWER FOR WIRING SCHEMATIC _EOUIP GNB UP TERMINATION JB_PEREB _ FIELD TEST IN THE PINS SPEED-UP "0 DIET SBI_T" _4V POWER ENTRY CYCLE -060 RELEASE 21 SHORT FOR 3} PERMANENT S+ SEC AND RELEASE FOR SHORT WILL BE IBNOREB DEFROST BEFROST TERMINATE TERMINATE WILL WILL O_ (USE METAL OBJECT II _O_ENTARILY SHORT PINS AND COMPRESSOR OFF DELAY _ IZ_Z[%TL,C__ 0_2 AND SPEED_ IN 30 SEC IF NORMALLY IF D TO BYPASS FORCED DEFROST BET OPEN FT IS CLOSED 50XZ500242 3,0 AO8467 Fig. 14 - Wiring Schematics - 50XZ 12 Three Phase HIGH VOLTAGE POWER LEADS (SEE UNITWIRING LABEL) ( Io_ <[ -- - Lc. - -SSUPP _[ m = FIELD-SUPPLIED FUSED DISCONNECT GND CONTROL °- "LOWER BOX 'O' 2LK2_)O, --YE--L&YL GROG) LOW-VOLTAGE POWER LEADS(SEE UNIT WIRING LABEL) SPLICE $ $ O. RED,R± O, O BRN--(C).Z WH_LW2) b O G#A_2 b , O O.R_0£ '1:)' ,THERMOSTAT (TYPICAL) :£ 24 V Circuit Breaker BOX 24 Volt Com t LEGEND C99070 Field Control-Voltage Wiring Field High-Voltage Wiring Fig. 17 - Control Wiring Plate ....... A08472 Fig. 15 - High and Control Voltage Wiring Connections (3.) HP-EFF (Factory Selected for 50XZ)- Heat Pump Efficiency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton. d. AC/HP CFM ADJUST-SELECT NOMINAL, LOW, OR HIGH AIRFLOW The AC/HP CFM Adjust select is factory set to the High-Hi (NOM for 060) tap. The CFM Adjust selections NOM/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15 percent airflow over nominal unit size selected and LO provides 10 percent airflow below nominal unit size selected. CFM Adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal (See Fig. 19, D as indicated). e. ON/OFF DELAY-SELECT DESIRED TIME DELAY PROFILE Four motor operation delay profiles are provided to customize and enhance system operation (See Fig. 19, E as indicated). Selection options are: GROUND LUG :INSLPICE BOX) GROUND LEAD SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC 3-PHASE CONNECTIONS 4B:3 L1 L2 L3 NOTE: Use copper wire only. LEGEND NEC - National Electrical Code Field Wiring Splice Connections ¢q C99057 Fig. 16 - Line Power b. Connections AC/HP SIZE-SELECT SYSTEM SIZE INSTALLED The factory setting for air conditioner or heat pump size is the size which matches the model of packaged unit installed. Installer should verify air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes (See Fig. 19, B as indicated). SYSTEM TYPE-SELECT SYSTEM TYPE INSTALLED The type of system will be factory selected (see below for details): (1.) The standard 90 sec off delay (Factory Setting) at 100 percent airflow in cooling or heat pump heating mode. (2.) A 30 sec cooling delay with no airflow, 90 sec off delay at 100 percent airflow profile is used when it is desirable to allow system coils time to heat-up/cooldown in coniunction with the airflow in cooling or heat pump heating mode. (3.) A no delay option used for servicing unit or when a thermostat is utilized to perform delay functions. (1.) AC-Air conditioner (2.) HP-COMFORT-Heat Pump Comfort provides approximately 315 CFM per ton for higher normal heating air delivery temperature and provides approximately 350 CFM per ton cooling airflow for good humidity removal. (4.) ENH, enhanced selection, provides a 30 sec cooling on delay with no airflow, plus 150 sec at 70 percent airflow and no off delay for added comfort. This will minimize cold blow in heat pump operation and could enhance system efficiency. f. CONTINUOUS FAN--SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 13 (1.) LO speed-Factory mode airflow. setting, 50 percent (2.) MED speed-Move connector cooling mode airflow. (3.) HI speed-Move g. connector cooling to MED, TRANSFORMER CONTAINS A MANUAL RESET OVERCURRENT PROTECTOR 65 percent to HI, 100 percent IT WILL NOT AUTOMATICALLY cooling mode airflow (See Fig. 19, F as indicated). LOW-VOLTAGE CIRCUIT FUSING AND DISCONNECT SERVICING REFERENCE The low-voltage circuit is fused by a board-mounted 5-amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the marked with ground BASIC UNIT The following symbol. C99058 CONFIGURATION basic configuration of the indoor will provide ARI rated performance BASIC CONFIGURATION should rated ARI performance enhancements POWER PRIOR TO THIS COMPARTMENT MUST BE CLOSED EXCEPT WHEN SERVICING transformer is referenced to chassis ground through a printed circuit run at SECI connected to metal standoff h. RESET motor of the System. This be used when the is required, (1.) AUX HEAT kW/CFM-Select Label 9 PIN CONNECTOR or if system such as super dehumidify ICM PRINTED are not needed. CIRCUIT BOARD '_--_ the heater range for the size of electric heater installed no heater is installed). (2.) AC/HP SIZE-Factory selected size installed, please verify. (3.) SYSTEM TYPE-Factory unit 50XZ). Fig. 18 - Transformer (skip _ this step if SEO1_ i to match system selected HP-EFF (for (4.) AC/HP CFM ADJUST-Select HIGH for 042 & 048, NOM for 036 & 060, and LO for 024 & 030. (5.) ON/OFF DELAY-Select (6.) CONTINUOUS when thermostat 0/90 profile. FAN-Select desired fan speed is set to continuous fan. COMFORT OPTIONS-SUPER DEHUMIDIFY (See Quick Reference Guide) The Super Dehumidify option is possible when this unit is installed with a field supplied Thermidistat control (Super Dehumidify does not require an outdoor 24VAC temperature sensor). The following configuration is recommended for maximum cooling/dehumidifying comfort: This configuration will improve the comfort provided humidity by the air conditioning system if more removal is desired. While providing this 12 PIN CONNECTOR improved comfort, the system will operate efficiently, but not at the published HSPF or ARI SEER efficiency. The following system configuration is recommended for maximum (See heating and cooling/dehumidifying C01033 Fig. 19 - Detail comfort (9.) Fig. 19-21). (1.) AUX HEAT kW/CFM-Select the narrowest heater range to match size of electric heater installed (skip this step if no heater is installed). (2.) AC/HP Size-Factory selected installed, please verify. (3.) SYSTEM TYPE-Select HP-COMFORT air conditioner (4.) AC/HP (5.) ON/OFF CFM ADJUST-Select DELAY-Select (7.) DEHUMIDIFY activate. or AC (for provides the following reach wet coil operating b. A no blower TM (or capable comfort enhancements: conditions off delay eliminates in cooling. cold blow which may be associated with running the blower after shut down of the compressor and avoids reevaporation of fan speed fan. J1 jumper THERMIDISTAT Board airflow reducing the cold blow sensation at start up in heating and allowing the indoor coil to more quickly ENH profile. MODE-Remove Printed-Circuit a. A 30 sec blower on delay with 150 sec at 70 percent airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100 percent NOM (Lo for 060). (6.) CONTINUOUS FAN-Select desired when thermostat is set to continuous CONFIGURE This configuration system type system) of SPP zoning system)-Following its installation instructions for Super Dehumidify and Super Comfort Heat operation. to match system size (for heat pump system). GRY ==_ HEATER/MOTOR condensed operation. to c. Lower reduce (8.) LOW VOLTAGE CONNECTIONS-Make connections as shown in ELECTRICAL CONNECTIONS section. moisture cooling/dehumidifying airflow while the compressor is running to draft effects and increase heating air temperature and improved operation. 14 after humidity control during cooling ACCESSORY INSTALLATION a. ACCESSORY close its contacts. ELECTRIC Electric heaters per instructions may be installed with the 50XZ units supplied with electric heater package. See unit rating plate for factory-approved kits. b. AUXILIARY electric standard The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24-v. AIR CLEANER Sensor models are capable indoor system control 50XZ SEQUENCE (See Air Cleaner d. HUMIDIFIER/HUMIDISTAT when G thermostat Price Pages for Part air is present. are from the Thermidistat '_ HUM (See Fig. capacity d. COOLING TO HUMIDIFIER airflow. opens R to DH-The NOTE: The indoor capable of control WIRING unit delivers of the system. MODE-SUPER control providing is capable configuration DEHUMIDIFY (see quick reference guide) used, such as a Thermidistat, Super control must be configured instructions. Consult indoor J HUMIDIFIER cooling airflow which is approximately 80 percent of the nominal cooling airflow to increase the latent terminal. HUM 1F] (G) HUMIDITY unit delivers Thermidistat HUMIDISTAT HUM 2F] runs MODE-DEHUMIDIFICATION OPERATION 24-VAC Blower (1.) If indoor temperature is above temperature set point and humidity is above humidity set point, thermostat or Thermidistat closes circuits R to G, R to O, and R to Y/Y2 and humidistat or using a Thermidistat '_ Control, Zone Comfort Plus or Comfort Zone II, the 24-v. signal may be sourced (c) OPERATION MODE-LOW c. COOLING 19-21). Alternately, the 24-v. signal may be sourced from the W and C circuit board connections. When directly from zoning FAN to O-The HUMI and HUM2 to the low-voltage signal to a signal Thermidistat, (1.) If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R control of a humidifier through a standard humidistat (See Fig. 19-21). These terminals are energized with 24-v. OF b. COOLING CONNECTIONS Easy Select '_ Board terminals provided for direct connection of responding (thermostat, (1.) Thermostat closes circuit R to G-The at continuous fan airflow. are not always Number). The airflow sensor turns on electronic cleaner when the blower is operating. DEHUMIDIFY required. energized during blower operations, as described above. When using an electronic air cleaner with the unit, use Airflow SUPER These CONNECTIONS terminals To (See Fig. 19-21). AND a. CONTINUOUS and AUX2 close, the airflow operating modes are available, and to see control set up instructions. No special setup or wiring of unit is further information. The AUX1 the contacts control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these signal whenever the G terminal is energized (See Fig. 19). During Super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of the operating mode, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for humidistat f. DEHUMIDIFY CAPABILITIES heater TERMINALS c. ELECTRONIC When will return to 100 percent of selected cooling airflow. activate this mode, remove jumper J1 and wire in a HEATERS Dehumidify operation nmst be mode and as outlined in its installation control literature to determine if of providing Super Dehumidify inputs and for instruction. Ag5317 Fig. 20 - Humidifier Wiring (1.) If the indoor temperature is below the temperature set point and the humidity is above the humidity set point, the Thermidistat closes circuit R to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2. If circuit R to G is closed for 50XZ EASY SELECT[q BOARD TERMINAL[q BLOCK (24-v.), cooling R EMOVEJ requested value. If circuit R to G is open (0-v.) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal 1 J1 I I ''_] HUMIDISTAT .I of the system while minimizing JUMPER e. ELECTRIC e, Wiring DEHUMIDIFY HUMIDISTAT Latent capacities for De-Humidify CAPABILITY CONNECTION WITH Mode no on or off delays. for 50XZ f. HEAT PUMP HEATING (1.) Thermostat Y/Y2-The airflow. than average systems. If increased latent capacity is an application requirement, the circuit board provides connection terminals for use of a standard humidistat. The unit will MODE (1.) Thermostat R to W/WI contacts opening on increasing its airflow to approximately 80 falls to a level which causes the humidistat closes circuits R to G and R to unit delivers selected heat pump g. HEAT PUMP HEATING ELECTRIC HEAT WITH heating AUXILIARY closes circuits R to G, R to Y/Y2 and or W2 (and R to O in the case of defrost). In the event that electric heating is called for by the thermostat while the heat pump is also operating in percent of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity over cooling. MODE STANDARD for these units are better detect the humidistat humidity and reduce HEATING (1.) Thermostat closes circuit R to W/W1, or W2-The unit delivers the selected electric heat airflow. There are Ag5316 Fig. 21 - Humidistat the motor will deliver airflow at the full or cooling plus dehumidify mode to 15 either heating ordefrost modes, themotor will modify itsairflow output, if necessary, toprovide anairflow whichisdefined assafeforthe operation oftheelectric heater during heat pump operation. Thatairflow isthegreater oftheheat pump heating airflow andtheelectric heater only airflow. h.HEATING MODE-SUPER COMFORT HEAT OPERATION NOTE:Theindoor control used, such asaThermidistat, must be capable of providing Super Comfort Heatoperation modeand controlmustbe configured as outlined in its installation instructions. Thesystem must beinstalled withappropriate outdoor temperature sensor. Consult indoor control literature todetermine if control is capable andfor configuration instructions. Consult indoorcontrolinstructions andsensor instructions for sensor installation details. If theoutdoor temperature isintherange of12°Fto40°F(-11°C to4°C),theThermidistat closes circuitR toY/Y2andopens circuit R toG.If circuitRtoGisclosed (24-v.), themotor will deliver airflow atthefullheating requested value. If circuit RtoG isopen(0-v.)formaximum heating comfort, themotor delivers reduced airflowtomaximize thetemperature andminimize the drafteffect oftheheated airleaving theunit. SPECIAL PROCEDURES FOR 1. Be sure unit disconnect 2. Disconnect the transformer. 17,) 3. Connect terminal 208-V Use primary See unit wiring the yellow primary labeled 200-v. label. lead Checklist as follows 1. Remove from 3. Make the following a. Inspect broken ELECTRICAL Failure to follow this warning death or property damage. 1. Follow goggles recognized safety practices when checking or servicing remove sources leak compressor terminal cover are disconnected and tagged. is suspected around 5. Never attempt to repair soldered refrigerant system is under pressure. 6. Do not contains a. Shut off electrical tag. wear power 4. Verify the following cutter and remove the blade is correctly positioned b. Make sure that air filter(s) is in place. c. Make sure that condensate drain pan and trap are filled d. Make to ensure proper sure that drainage. on the 060 size, only the 2 wire ties fastened to the outdoor coils and reversing valve/accumulator have been removed. e. Make sure that all tools and miscellaneous have been removed. until mounted. bolts. loose parts Do not loosen has 2 Schrader-type ports, one low-side located on the suction line, and one Schrader fitting located on the compressor line. Be sure that caps on the ports are tight. 1/8" (3 ram) MAX BETWEEN MOTOR AND FAN HUB SHAFT A08474 Fig. 22 - Fan before box if while Blade Clearance Step 1 -- Start-Up CHECKING COOLING AND HEATING CONTROL OPERATION Start and check the unit for proper control operation as follows: (1.) Place room thermostat SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON System goggles MOTOR all and position selected to unit and install lockout component Be sure conditions: a. Make sure that outdoor-fan in fan orifice. and shuts down according to time delay on the Easy Select board (See Easy Select Section) when FAN MODE AUTO position. b. Relieve and reclaim all refrigerant from system using both high- and low-pressure ports. c. Cut component connecting tubing with tubing d. Carefully necessary. flame. see iniury, connection protective and d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. high-side discharge compressor use torch to remove any component. oil and refrigerant under pressure. To remove a component, proceed as follows: or protective system. 4. Relieve and recover all refrigerant from system touching or disturbing anything inside terminal refrigerant terminals. to, inspections: c. Inspect all field and factory-wiring connections. that connections are completed and tight. HAZARD and wear refrigerant WARNING, attached liquid-soap solution. If a refrigerant leak is detected, following Check for Refrigerant Leaks section. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 3. Do not electrical labels 5. Compressors are internally spring or remove compressor hold-down could result in personal and initial refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, or to the transformer SHOCK for for shipping and handling damages such as lines, loose parts, disconnected wires, etc. 6. Each unit system Schrader fitting EXPLOSION, unit b. Inspect for oil at all refrigerant tubing connections on unit base. Detecting oil generally indicates a PRE-START-UP FIRE, the on all DANGER, CAUTION, and INFORMATION shipped with, unit. (See Fig. 13 or 14 and lead (w110) prepare all access panels. with water 110) at the end of this book and 2. Read and follow instructions OPERATION (w supplied to inspect start-up: switch is open. yellow the Start-Up proceed switch is placed in (20 Thermostat: When the room temperature rises to a point that is slightly above the cooling control setting of the from unit. thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y, O unsweat remaining tubing stubs when Oil can ignite when exposed to torch and G.These thermostat 16 completed connect circuits contactor through the coil (C) (through unit wireY)andECMboard (through unitwireG) across the24-v.secondary oftransformer (TRAN). Thermidistat orThermostat andHumidistat: When theroom temperature rises toapointthatis slightly above thecooling control setting ofthe thermostat, thethermostat completes thecircuit between thermostat terminal Rtoterminals Y,O, DH,andG.These completed circuits through the thermostat connect contactor coil(C)(through unit wireY)andECMboard (though unitwireG) across the24-v.secondary oftransformer (TRANS). (3.)Place system switch orMODE control inHEAT position. Setcontrol above roomtemperature. Observe thatcompressor, outdoor fan,andindoor blower motors start. Observe thatheating cycle shuts downaccording totimedelay selected onthe Easy Select board (See Easy Select Section) when control setting issatisfied. (4.)When using anautomatic changeover room thermostat place bothSYSTEM orMODE control andFANmode switches inAUTO positions. Observe thatunitoperates inCooling mode when temperature control issetto"callforCooling" (below room temperature), andunitoperates in Heating mode when temperature control issetto "callforHeating" (above roomtemperature). NOTE:Once thecompressor hasstarted andthenhasstopped, it should notbestarted againuntil5 minutes have elapsed. The cooling cycle remains point that is slightly thermostat. At this between thermostat circuits de-energize condenser selected blower until point, the terminal motor stops. compressor temperature drops setting of the room control thermostat "breaks" R to terminals contactor and compressor the room the cooling coil motors C and ECM (See Easy Select The unit is in a "standby" for cooling" the board. from delay also applies the room condition, thermostat. to heat pump heating leaks and charge the unit as follows: remaining 2. Repair leak following NOTE: Install a bi-flow opened Leaks and low-pressure pressure and reclaim ports to relieve system refrigerant. accepted practices. filter drier whenever the system has been for repair. 3. Check system for leaks using an approved method. 4. Evacuate refrigerant system additional leaks are found. and reclaim refrigerant if no 5. Charge unit with R-410A refrigerant, using a volumetriccharging cylinder or accurate scale. Refer to unit rating plate for required Step 3 -- Start-Up Complete the required charge. Adjustments procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in Cooling mode when the outdoor temperature is below 40°F (4°C) (unless accessory low-ambient kit is installed). Do not rapid-cycle the compressor. Allow 5 rain. between "on" cycles to prevent compressor damage. CHECKING COOLING AND HEATING CONTROL OPERATION Start and check the unit for proper 1. Place room thermostat control SYSTEM operation switch as follows: or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down to within 60 sec (030-060 size) or 30 sec (024 size) when FAN MODE switch is placed in AUTO position. 2. Place system open Set control compressor, The Section) for Refrigerant 1. 1. Use both high- circuit Y and G. These Check Locate and repair refrigerant stop. After the time delay setting on the Easy Select board for the next "call minute "on" below Step 2 -- switch above outdoor Observe that heating is satisfied. , the or MODE control in HEAT position. room temperature. Observe fan, and indoor blower motors cycle shuts down when control that start. setting waiting The 5 mode. OUTDOORCOIL NNDOOR ¢ TXV COIL in Meterin( Position I-" r-q LCS 1-" Bypass Position LEGEND HPS - High Pressure Switch LCS - Loss of Charge _ f}-] _ _i}_Accuratet_Metering Arrow indicates Switch Device direction of flow D 0 C03011 Fig. 23 - Typical Heat Pump Operation, 17 Cooling Mode 3. When using an automatic changeover room thermostat, REFRIGERANT place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to "call for Cooling" (below room temperature), and unit operates in Heating mode when temperature control is set to "call for Heating" (above IMPORTANT: Three-phase, oriented. Unit 3-phase power the internal power nmst be scroll checked lead orientation. protector compressors to ensure backwards, discharge the difference pressures CHECKING within to correct between direction The 3-phase rotation. compressor When suction ADJUSTING and NOTE: Adjustment the unit is suspected charging label and pressures of the refrigerant of not having and the tables in Cooling is attached to the outside is suspect in Heating nameplate amount. physical charged the proper R-410A R-410A only. A refrigerant reclaim unless charge. The temperatures charging all refrigerant information CHARGE level and charge may be obtained from standard evacuating in the specified techniques. amount After of refrigerant COOLING Use Cooling Charging Chart (Fig. 26). Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging subcooling for the various gauge and temperature reading. Indoor air CFM range of the unit. TO USE Take label access door. If charge Use operating conditions. sensing devices are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the refrigerant is not required refer to system of the service mode, (This charge shown mode, with leak. the units to correct Accurate pressure REFRIGERANT CHARGE The refrigerant system is fully and is tested and factory sealed. for LOW 5 nfinutes, may be zero. AND CHARGE evacuating system, weigh (refer to system data plate). compressor off the compressor. leads to the unit must be reversed turning are proper If not corrected will shut NO Check room temperature). CHARGE The amount of refrigerant charge is listed on the unit nameplate and/or the physical data table. Refer to the Refrigeration Service Techniques Manual, Refrigerants Section. to the COOLING the liquid must be within CHARGING line temperature gauges. Refer to the chart temperature should be. problem the normal CHARTS and read the manifold to deternfine NOTE: If the refrigerant leak, refer to Check causing operating the what inaccurate for Refrigerant the pressure liquid line readings is a Leaks section. data table also.) IMPORTANT: When evaluating indicated adjustment to the specified very nfinimal. condition insufficient If a substantial the refrigerant charge, factory charge nmst always adjustment is indicated, an be INDOOR AIRFLOW AND AIRFLOW ADJUST- MENTS an abnormal exists somewhere in the cooling system, airflow across either coil or both coils. such as PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal or death and possible unit component damage. iniury The heating and cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For units with optional electric heat, the airflow must not be reduced below the levels stated in Table 2. OUTDOOR 9 COIL INDOOR COIL i .,.._ [ TXV in Bypass Position .--[ .--[ LCS 1 J .--[ Mete_ng Position LEGEND HPS - High Pressure Switch LCS - Loss of Charge Switch _ [iii_ Accurate¢:Meteting Device [] Arrow indicates direction of flow C03012 Fig. 24 - Typical Heat Pump Operation, 18 Heating Mode Tables 3 & 4 show both these tables to determine NOTE: Be sure and adjusted Airflow can be changed Select board. Motor) utilizes ID Blower and cooling by changing airflows. for the system Refer to being installed. The defrost control is a time/temperature control which includes a field-selectable time period (DIP switch 1 and 2 on the board) the set up pins on the Easy between defrost cycles of 30, 60, 90, or 120 minutes (factory set at 30 minutes). To initiate a forced defrost, two options are available depending on the status of the defrost thermostat. return-air grilles properly. state of the art ECM (Electronic If defrost thermostat is closed, speedup pins (J1) must be shorted by placing a flat head screw driver in between for 5 sec and Computated Motors. releasing, to observe a complete defrost cycle. When the Quiet Shift switch is selected, compressor will be turned off for two 30 Step 4 -- Defrost Control QUIET SHIFT Quiet Shift is a field-selectable defrost mode, which will eliminate occasional noise that could be heard at the start of defrost cycle and restarting of heating cycle. It is selected (on defrost board) in ON position. When Quiet Shift switch by placing is placed in ON position, DIP switch and a defrost If defrost is shorted (with a flat head screw driver) for 5 sec and released, a short defrost cycle will be observed (actual length is dependent off for 30 sec and then turn back on to complete defrost. At the start of heating after conclusion of defrost reversing valve will de-energize, compressor will turn off for another 30 sec, and the outdoor fan will stay off for 40 sec, before starting in the Heating mode. Table 3 - 50XZ Cooling 030 036 Table 4 - 50XZ Cooling CFM SIZE ADJUST EXTERNAL PIN SELECT STATIC 048 060 HEAT PUMP Heat Pump Effi ",iency and Cooling 600 0.005 700 0.007 0.007 .... 800 0.010 0.010 900 0.012 0.012 0.019 - and speedup pins are Quiet Shift position). When Quiet Shift switch is the length of defrost is 1 minute (30 sec period followed by 30 sec of defrost with sec. cycle will be observed. NOM PIN 0.0-0.39 HI PIN 0.4-0.69 0.7-1.0 0.0-0.39 0.4-0.69 0.7-1.0 885 805 730 99O 93O 855 715 695 645 795 775 745 79O 745 685 89O 85O 785 1105 1030 930 1255 1160 1050 89O 865 825 1010 98O 925 1020 965 895 1140 1105 995 1235 1175 1115 1400 1355 1280 99O 975 940 1125 1110 1085 1160 1080 1020 1305 1275 1220 Dry Coil ECM Airflow Cabinet NOM HI PIN PIN 0.1-1.0 0.1-1.0 1100 98O 99O 1260 1120 1135 1575 1400 1225 98O 1100 1400 1120 1260 1750 1400 1410 1125 1265 1610 1290 1450 2010 1610 1415 1575 1810 de iverequalairflow Table UNIT SIZE 024 030 036 042 048 060 position, 0.1-1.0 COMFORT pin selections is in open compressor operation). On return to heating operation, compressor will again turn off for an additional 30 sec and the outdoor fan for 40 sec. When the Quiet Shift is in OFF position, only a brief 30 LO PIN PRESSURE RANGE (in. wc) COOLING* COOLING DEHUMIDIFY HEAT PUMP COMFORT COOLING* COOLING DEHUMIDIFY HEAT PUMP COMFORT COOLING* COOLING DEHUMIDIFY 042 upon the selected in ON position, compressor off & Heating Large UNIT thermostat & Heating Dry Coil ECM Airflow Small Cabinet CFM ADJUST PIN LO PIN SELECT EXTERNAL STATIC PRESSURE RANGE 0.0-0.39 0.4-0.69 0.7-1.0 (in. wc) COOLING* 8OO 725 COOLING 715 67O DEHUMIDIFY HEAT PUMP 72O 66O COMFORT COOLING* 1010 92O 825 COOLING 89O 845 795 DEHUMIDIFY HEAT PUMP 945 850 765 COMFORT COOLING* 1110 1025 97O COOLING 99O 96O 910 DEHUMIDIFY HEAT PUMP 1035 975 910 COMFORT 7pEfficiency and Cooling pit selections de iver equal airflow 024 sec intervals during this complete defrost cycle, as explained previously. When Quiet Shift switch is in factory default OFF position, a normal and complete defrost cycle will be observed. 3 initiated, the following sequence of operation will occur. Reversing valve will energize, outdoor fan will turn off, compressor will turn UNIT SIZE DEFROST are open, that all supply-and free from obstructions, Unit 50XZ heating the airflow 1000 0.015 0.015 0.023 0.014 5 - ECM Wet Coil Pressure 1100 ...... 0.018 0.027 0.017 - STANDARD 1200 1300 0.021 0.032 0.020 0.027 0.024 0.037 0.024 0.032 19 Drop (in. wc) CFM (SCFM) 1400 1500 1600 1700 1800 1900 2000 2100 .... 0.047 0.031 0.041 0.029 0.035 0.046 0.032 0.039 0.052 0.036 0.043 0.057 0.040 0.063 0.045 0.068 0.049 0.053 0.042 0.027 0.036 If it is desirable to observe a complete defrost in warmer the defrost thermostat must be closed as follows. 1. Turn off power 2. Disconnect board. to outdoor outdoor 4. After unit. (See Fig. 27) Tape to prevent a few temperature should at approximately line or remainder from OF2 drop Heating below closing liquid point line of defrost 30 ° F) (- 1 ° C). defrost until defrost (27°C) thermostat coil temperature at liquid cycle time. MAINTENANCE continuing high performance, and to minimize the of premature equipment failure, periodic maintenance must be performed on this equipment. This heat pump unit should be inspected at least once each year by a qualified service person. To troubleshoot NOTE: about the availability for cleanliness each each for tightness cooling and controls season. Service for when Step 1 -- Air Filter Never operate the unit without a suitable air filter Always the filter with the in the return-air duct system. same dimensional for recommended size and type as originally filter sizes. replace installed. See Table 1 Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint. Step 2 -- Indoor Blower NOTE: All motors these motors. For clean motor longer and Motor are prelubricated. life, operating accumulated annually. OWNER: of a maintenance dirt Do not attempt economy, and grease and continuing from the blower to lubricate efficiency, wheel and Consult your local dealer contract. Failure to follow or death. INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal or death and unit component damage. perform any maintenance procedures recommended ELECTRICALSHOCK Failure to follow iniury or death: on this equipment, other than those in the Owner's Manual. HAZARD these warnings could result in personal 1. Turn off electrical power to the unit before performing maintenance or service on this unit. caution 3. Never place anything with the unit. OPERATION Failure to follow operation. when removing combustible panels any and parts. either on or in contact HAZARD this caution may result in improper HAZARD this warning could result in personal iniury Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel. iniury The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to UNIT connections operation ELECTRICALSHOCK 2. Use extreme wheel unit, refer to Table 8. TO EQUIPMENT PERSONAL and necessary. frost to accumulate mode, motor Clean when necessary. electrical proper on control 5. Turn off power to outdoor and reconnect fan motor lead to OF2 on control board after above forced defrost cycle. To ensure possibility season. grounding. allowing in 80°F of defrost blower cooling IMPORTANT: minutes thermostat (approximately NOTE: Unit will remain in reopens lead mode, 3. Inspect 4. Check fan motor 3. Restart unit in Heating on outdoor coil. weather, Step 3 -- Outdoor Coil, Indoor Condensate Drain Pan Coil, and Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year. The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base. Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a plumbers snake or similar probe device. Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing. The minimum maintenance requirements for this equipment are as follows: 1. Inspect air filter(s) each month. Clean or replace when necessary. 2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary. 20 Table FILTER SIZE 20X20Xl 508X508X25 20X24X1 508x610x25 24X30Xl 610x762x25 6 - Filter Table (in. wc) 1300 CFM 1400 1500 500 600 700 800 900 1000 1100 1200 0.07 0.08 0.10 0.12 0.13 0.14 0.15 0.09 0.10 0.11 0.13 0.14 0.15 0.15 0.07 0.08 0.09 0.10 Heat Pressure Drop 024-036 cfm 7 - Electric Small 500 0.00 0.00 0.00 0.00 0.00 600 0.00 0.00 0.00 0.00 0.00 700 0.00 0.00 0.00 0.00 0.02 800 0.00 0.00 0.00 0.02 0.04 1000 0.00 0.00 0.02 0.06 0.08 Heat Pressure Large 0100 0.00 0.00 Cabinet: 900 0.00 0.00 0.00 0.04 0.06 Electric 5kw 7.5 kw 10 kw Drop 0.05 Table 5kw 7.6 kw 10 kw 16 kw 20 kw Pressure Cabinet , _vv , vvv , _vv , _vv , _vv ,, 0.00 0.00 0.00 0.00 0.01 0.01 0.01 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.04 0.04 0.05 0.05 Balance Drop Table vv Point 1700 1800 1900 2000 2100 2200 2300 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 Table 11 O0 0.00 0.02 0.04 0.08 0.09 042-060 1600 1200 0.00 0.03 0.06 0.10 0.11 1300 0.02 0.05 0.07 0.12 0.13 1400 0.04 0.07 0.09 0.14 0.15 1500 0.06 0.08 0.10 0.16 0.17 1600 0.07 0.09 0.11 0.18 0.19 (in. wc) cfm , vvv , _vv _vvv _, 0.05 0.06 0.06 0.06 0.07 0.07 0.07 0.08 0.08 0.08 0.09 0.09 vv _vv _vvv 0.09 0.10 0.10 0.10 0.11 0.11 _w 0711 0.12 0.12 0.12 0.13 0.13 Worksheet 7O :_ iI 6O (D 8 o 50 o ,-- o3 ._ _ -d _ -o o o 2 060 048 4o 042 036 "-- so 030 5 _ 024 20 C3 10 0 -20 -10 0 10 Outdoor 20 Air 30 Temp 40 (Deg 50 6O F) C03008 Fig. 25 - 50XZ Balance Point 21 Worksheet _l Required Subcooting Outdoor Model oF Ambient (oC) Required Temperature Required 82 (28) 85 (29) 95 (35) 105 (41) (R-410A) Required Subcooling (°C) 10 15 20 25 (kPa) 3 6 8 11 14 56 51 46 41 1303 16 13 11 8 5 7(3.9) 196 63 58 53 48 43 1351 17 15 12 9 6 14.3(7.9) 203 66 61 56 51 46 1399 19 16 13 10 8 12.6(7) 210 68 63 58 53 48 1448 20 17 14 11 9 15,7(8.7) 14.8(8,2) 217 70 65 60 55 50 1496 21 18 15 13 10 14,5(8.1) 11.5(6,4) 224 72 67 62 57 52 1544 22 19 16 14 11 23t 74 59 64 59 54 1593 23 20 18 15 12 238 76 71 66 61 56 1641 24 21 19 16 13 245 77 72 67 62 57 1689 25 22 20 17 14 252 79 74 69 64 59 1737 26 23 21 18 15 27 25 22 19 16 17 9(5) 030 9.3(5.2) 8.8(4.9) 8.6 (4.8) 7.8(4.3) 036 17.6(9.8) 16.8(9.3) 16.5(9.2) 15.4(8.6) 042 12.8(7.1) 12.7(7.1) 12.7(7.1) 12.6(7) 048 17.5(9.7) 16.9(9.4) 16.6(9.2) 13.7(7.6) 13(7,2) 13(7.2) Charqinq 1- Measure 2- Measure the 8.6 (4.7) Procedure Discharge line Liquid pressure line by attaching temperature a gauge by attaching to the service a temperature port. sensing to it. 3- Insulate the temperature doesn'_affect the to the Outdoor required if the values. Extrapolate 6- Find the Pressure acro88 temperature Charge 50xz500174 for 8o that the Outdoor Ambient Subcooling Outdoor ambient Value in the the table Discharge Pressure a required if the table based temperature temperature Compre88or from in the on the model size and temperature. if the Pressure of the device reading. Ambient 5- Interpolate sensing lie8 beyond lie8 in between the table corresponding the table range. to the the measured line. reading to obtain the Liquid line Subcooling measured ] temperature i8 higher Pr_ssur_ 5 9.4 (5.2) 8- Add Subcooling 61 9.8(5.4) 7- Read a Specific 189 10.3(5.7) 060 the for (°F) Pr_sur_ (p_ 024 4- Refer Line Temperature Size 75 (24) device Liquid Subcooling than the table value, 260 81 76 71 66 61 1792 268 83 78 73 68 63 1848 29 26 23 20 276 85 80 75 70 65 1903 30 27 24 21 19 284 87 82 77 72 67 1958 31 28 25 22 20 292 89 84 79 74 69 2013 32 29 26 23 21 300 91 86 8t 76 71 2068 33 30 27 24 22 309 93 88 83 78 73 2130 34 31 28 26 23 318 95 90 85 80 75 2192 35 32 29 27 24 327 336 97 99 92 94 87 89 82 84 77 79 2254 36 33 31 28 25 2316 37 34 32 29 26 345 101 96 91 86 81 2378 38 35 33 30 27 354 103 98 93 88 83 2440 39 36 34 31 28 364 105 100 95 90 85 2509 40 38 35 32 29 374 107 102 97 92 87 2578 41 39 36 33 30 384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105 100 95 90 2716 44 41 38 35 32 404 112 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34 424 116 111 106 101 96 2923 47 44 41 38 35 434 118 113 108 103 98 2992 48 45 42 39 36 444 119 114 109 104 99 3061 48 46 43 40 37 454 121 116 111 106 101 3130 49 47 44 41 38 464 123 118 113 108 103 3199 50 48 45 42 39 474 124 119 114 109 104 3268 51 48 46 43 40 484 126 121 116 111 106 3337 52 49 47 44 41 494 127 122 117 112 107 3406 53 50 47 45 42 504 129 124 119 114 109 3475 54 51 48 46 43 514 131 126 121 116 111 3544 55 52 49 46 44 524 132 127 122 117 112 3612 56 53 50 47 45 534 134 129 124 119 114 3681 56 54 51 48 45 C03008 Fig. 26 - Cooling Charging Table-Subcooling 22 O 'n r_o --<>--<ED--- -CZ>- Quiet Shift Speedup Pins Defrost interval DI P switches A08020 Fig. 27 - Defrost Step 4 -- Outdoor Keep the condenser cycle Fan fan free from all obstructions 6 screws holding 2. Turn motor/grille expose 3. Inspect outdoor to ensure assembly grille and motor upside down for cracks position fan blade, shaft will be visible). 6. 6. Ensure that setscrew shaft when tightening. (See Fig. 22) engages and check the electrical the flat area on the motor Refrigerant and wiring annually. Be power to the unit. access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip and reassemble the connection properly and securely. are observed in has occurred, check proper electrical label when making these Circuit leak. or if low performance is suspected, leak-test all refrigerant tubing using an electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section. If no refrigerant leaks are found refer to Checking and Adjusting Step 7 -- and low performance is suspected, Refrigerant Charge section. Indoor Airflow airflow does not require is suspected. If a problem checking exists, be sure that all supplyand return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to and Wiring controls If discrepancies malfunction with the to the unit wiring The heating and/or cooling unless improper performance Controls sure to turn off the electrical Remove end (1/8 in. [3 mm] of grille. Step 5 -- Electrical Inspect and slide fan off blade so that the hub is 1/8 in. (3 mm) away from the motor operation. Refer If oil is detected or bends. 5. When proper Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant the fan blades loosen setscrew 7. Replace Step 6 -- to top on top cover to 4. If fan needs to be removed, motor shaft. motor instrumentation. checkouts. fan blade. replacing to ensure operating cycle, or if a suspected each electrical component proper cooling operation. Never place articles on top of the unit. Damage to unit may result. 1. Remove cover. Control the wire end After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling Indoor system Airflow airflow. Step 8 -Piston and Airflow Metering Adjustments Devices-TXV section to check the & Accurater This unit uses 2 types of metering devices. The outdoor metering device is a fixed orifice and is contained in the brass hex-body in the liquid line feeding the outdoor device is a TXV type device. 23 coils. The indoor metering Step 12 -- Copeland Refrigerant) Scroll Compressor The compressor used in this product is specifically operate with interchanged. Puron refrigerant EXPLOSION (R-410A) (Puron designed and to cannot be HAZARD Failure to follow this warning death or property damage. could result in personal injury, Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerant and oils. The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with an anti-rotational oggog7 Fig. 28 - Refrigerant Step 9 -- Pressure Circuit device device and an internal pressure relief port. The anti-rotational prevents the scroll from turning backwards and replaces the need for a cycle protector. device, designed to protect relief port has an operating Switches differential Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnom_ally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically systems. R-22 pressure for the Puron (R-410A) designed switches system. to operate with Puron (R-410A) must not be used as replacements is located suction pressures airflow across indoor by such drop at about 20 psig. If system should be closed. To check switch: 2. Disconnect 3. Apply ohm under meter leads these pressure, switches If switch must be removed, charge so that pressure without breaking protects low PROPERTY HAZARD on a pressure is above this, you switch. are remove against excessive have this device for COMPRESSOR The Copeland scroll compressor uses 3MAF oil is needed, use Uniqema RL32-3MAF. and recover read 0 psig. Never all system open system Switch is located condenser in the discharge coil pressure. line It opens and at 650 water readily. oils designed precautions SERVICING High THETIC pressure may be caused by a dirty outdoor coil, failed fan air recirculation. 1. Turn off all power 2. Disconnect to unit. leads on switch. 3. Apply ohm meter leads across continuity on a good switch. OIL switch. You should have POE oil. If additional If this oil is not POE oils can absorb 15 times as much water as other for HCFC and CFC refrigerants. Take all necessary to avoid exposure SYSTEMS of the oil to the atmosphere. ON ROOFS WITH SYN- MATERIALS POE (polyolester) compressor term damage to some synthetic To check switch: damage available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely hygroscopic, meaning it absorbs water readily. This oil is extremely hygroscopic, meaning it absorbs psig. motor, or outdoor INJURY could result in property that a problem with dry nitrogen. High-Pressure switch certain PERSONAL This system uses Puron (R-410A) refrigerant which has higher operating pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron. If you are unsure consult the equipment manufacturer. to refrigeration to remove OR switch You should attached are reasonably gauges vacuum HAZARD Failure to follow this warning or personal iniury or death. it is not advisable exists. high-pressure low etc. It opens pressure across unless The against of charge, switch. troubleshooting Step 11 -- as loss to unit. on a good Because system This step covers the refrigerant system of the 50XZ, including the compressor oil needed, servicing systems on roofs containing synthetic materials, the filter drier and refrigerant charging. leads on switch. continuity NOTE: line and protects events coil, dirty filters, 1. Turn off all power System Switch on the liquid caused pressure. Step 13 -- Refrigerant REFRIGERANT Step 10 -- Loss of Charge This switch The pressure relief port is a safety against extreme high pressure. The range between 550 and 625 psig lubricants are known to cause long roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure or reversing valve. 24 switch, metering device, coil, accumulator, Synthetic RoofPrecautionary 1. Cover extended polyethylene approximate roof CHECK DEFROST Procedure working area with an in, permeable (plastic) drip cloth or 10 X 10 fl (3 X 3 m) area. tarp. Cover cloth shop towel to absorb lubricant spills and prevent run-offs, and protect drop cloth from tears caused by tools or components. The defrost area in front 3. Place terry cloth of the unit service shop towel inside panel with unit immediately component(s) to be serviced and prevent lubricant through the louvered openings in the unit base. 4. Perform required LINE biflow FILTER filter under run-offs (-I°C drier of any oil contaminated material per OD stub tube approximately 3 in. (76 ram) long. (See The defrost thermostat should be located on stub tube. there is only 1 stub tube used with liquid header, and on it is the bottom circuit. thermostat signals heat pump that conditions are right for defrost or that conditions have changed to terminate defrost. It is a thermally actuated switch clamped to outdoor coil to sense its temperature. service. 5. Remove and dispose local codes. LIQUID a terry THERMOSTAT is a liquid header with a brass distributor and feeder tube into outdoor coil. At the end of I of the feeder tubes, there is a 3/8-in. Fig. 29). Note that most units 2. Cover The an There going Normal +/- 1.7°C) temperature range is closed and open at 80 ° + 5°F (27°C at 30 ° + 3°F +/- 2.8°C). NOTE: The defrost thermostat nmst be located on the liquid side of the outdoor coil on the bottom circuit and as close to the coil as possible. DRIER is specifically designed to operate FEEDERTUBE with Puron. Use only factory-authorized components. Filter drier nmst be replaced whenever the refrigerant system is opened. When STUB TUBE removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system. PURON (R-410A) REFRIGERANT CHARGING Refer to unit information plate and charging chart. Some R-410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to DEFROST THERMOSTAT flow from cylinder in upright position. For cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant C99029 Fig. 29 - Defrost into suction-line. Step 14 -- System Information LOSS OF CHARGE SWITCH The loss of charge switch circuit (low voltage). pressures are present NOTE: system Because under is a protective pressure, switches unless exists. must be removed, you charge so that pressure without breaking device wired vacuum gauges remove certain Never Refer to the Cooling and Heating for troubleshooting information. START-UP Use the Start-Up this device for that a problem and recover read 0 psig. low to refrigeration to remove are reasonably into control if abnormally are attached it is not advisable troubleshooting If switch TROUBLESHOOTING It shuts off" the compressor in the refrigeration circuit. these Thermostat all system open system with dry nitrogen. 25 Checklist. Troubleshooting CHECKLIST Chart (Table 8) PURON® • (R-410A) QUICK REFERENCE GUIDE Puron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron • Puron refrigerant cylinders are rose colored. • Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. • Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating • Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low-side retard. • Use hoses with 700 psig service pressure rating. • Leak detectors should be designed to detect HFC refrigerant. • Puron, as with other HFCs, is only compatible with POE oils. • Vacuum pumps will not remove moisture from oil. • Do not use liquid-line filter driers with rated working pressures less than 600 psig. • Do not leave Puron suction line filter driers in line longer than 72 hours. • Do not install a suction-line • POE oils absorb moisture rapidly. Do not expose oil to atmosphere. • POE oils may cause damage to certain plastics and roofing materials. • Wrap all filter driers and service valves with wet cloth when brazing. • • A factory approved liquid-line filter drier is required on every unit. Do NOT use an R-22 TXV. • If indoor unit is equipped with an R-22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV. • Never open system to atmosphere while it is under a vacuum. • When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter filter drier in liquid line. driers. Evacuate to 500 microns prior to recharging. • Do not vent Puron into the atmosphere. • Do not use capillary tube coils. • Observe all warnings, cautions, and bold text. • All indoor coils must be installed with a hard shutoff Puron TXV metering device. 26 9 PIN CONNECTOR -ECM PRINTED CIRCUIT BOARD C23 __ A_.._ 1. Configuration Taps (See Installation Instructions, for detailed description) A. HEAT RANGE - Set for gas heat size (EX:090 for unit048090---)D B. AC/HP SIZE - Set for size of outdoor unit (Cooling Size) C. SYSTEM TYPE - Select "AC" for Gas Package UnitsN D. AC/HP CFM ADJUST - Select "NOM" E. ON/OFF DELAY - Do not use "ENH" for this unit \_ C::3 EASYSELECT I€ _SEC1GAS HEAT vi_ _ _o _ SEC2 I C_M _ioo _o _ F. CONTINUOUS FAN - Select desired speed 2. Remove Jumper J1 to activate all dehumidify modes 3. Complete wiring and install outdoor temperature [B sensor according to Installation Instructions i _o AC/PPSIZE : C'-J_ O--_ _ I 8 i HP_ - FF ACiHP CFMADJUST E _f_/. _m_ _o 'OF ELA 90 o E÷ (__ DH m _ Wl _ G 1. Set "DIP Switches" - Set the dip switches Thermidistat Control Board) appropriately system being installed. Q' C 9 O 2. Thermidistat (See F___ yE__ LO[_ NED _ _/EL (back of [q for specific n _ AUX2 HUM2 Thermidistat Control Control Configurations installation Speed Instructions for detailed description)_ * Option 5 (Variable Indoor Motor) - Set to ON * Option * Option 7 (Super Dehumidify) - Set to ON 17 - Select Programmable or non-programmable 3. Set desired humidity level on fron of Thermidistat (50 to 55 % RH recommended). For dehumidification 0/7=__ = cooling, mode. in both "dhu" and "cool" must be displayed. J C01034 ECM ID Blower Motor-Quick 27 Reference Guide Table 8 - Troubleshooting SYMPTOM Chart CAUSE REMEDY Power failure Call power company Replace fuse or reset circuit breaker Fuse blown or circuit breaker tripped Compressor and condenser fan will not start. Defective contactor, transformer, or high-pressure, loss-of-charge or low-pressure switch Replace component Insufficient line voltage Determine Incorrect or faulty wiring Check wiring diagram and rewire correctly Lower thermostat setting below room temperature Thermostat setting too high Faulty wiring or loose connections cuit Compressor runs Three-phase will not start but condenser fan in compressor cir- Determine Defective run/start capacitor, overload, start relay Determine One leg of 3-phase Replace fuse or reset circuit breaker Determine cause power dead is rotating in the wrong direction overcharge or undercharge Defective compressor Compressor operates continuously Replace Locate restriction and remove motor or capacitor Restriction in refrigerant system Dirty air filter Unit undersized for load Thermostat set too low Replace filter Decrease load or increase Reset thermostat Low refrigerant Locate leak, repair, and recharge charge Refrigerant unit size Recover refrigerant, evacuate system, and recharge Clean coil or remove restriction Replace filter Clean coil overcharged or air short-cycling Low refrigerant charge Recover excess refrigerant Recover refrigerant, evacuate system, and recharge Determine cause and correct Check fo rleaks, repair, and recharge. Remove restriction Restriction in liquid tube High heat load Check for source and eliminate Refrigerant overcharged Dirty air filter Recover excess refrigerant Replace filter Low refrigerant charge Check for leaks, repair and recharge Remove source of restriction Metering device or low side restricted Suction pressure too low cause and correct Faulty condenser-fan Condenser air restricted Excessive suction pressure evacuate system, and reshown on rating plate Determine cause and replace Replace thermostat Air in system Head pressure too low Recover refrigerant, charge to capacities Determine Dirty condenser coil pressure 3-phase power leads to the unit. Shut down unit to allow pressures to equalize. Defective run/start capacitor, overload or start relay Defective thermostat Condenser coil dirty or restricted Dirty air filter head cause and replace Replace and determine cause Determine cause and correct Insufficient line voltage Blocked condenser Air in system Excessive cause Replace compressor Correct the direction of rotation by reversing the Scroll compressor Refrigerant Compressor cycles (other than normally satisfying thermostat). Check wiring and repair or replace Compressor motor burned out, seized, or internal overload open scroll compressor makes excessive noise, and there may be a low pressure differential. cause and correct Insufficient evaporator airflow Temperature too low in conditioned area Outdoor ambient below 55°F (12.7°C) Filter drier restricted 28 Increase air quantity Check filter-replace if necessary Reset thermostat Install low-ambient Replace filter kit START-UP (Remove I. Preliminary MODEL NO.: SERIAL NO.: CHECKLIST and Store in Job File) Information DATE: TECHNICIAN: II. PRE-START-UP () () () () () () () VERIFY III. START-UP (Insert check mark THAT ALL PACKING REMOVE ALL SHIPPING HOLD ELECTRICAL in box as each MATERIALS DOWN item is completed) HAVE BEEN REMOVED BOLTS AND BRACKETS CHECK ALL CONNECTIONS AND CHECK VERIFY THAT INDOOR (EVAPORATOR) AIR FILTER THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL, AND PROPELLER TERMINAL IN HOUSING/ORIFICE VOLTAGE COMPRESSOR AMPS INDOOR (EVAPORATOR) TEMPERATURES FAN AMPS OUTDOOR (CONDENSER) AIR TEMPERATURE RETURN-AIR TEMPERATURE DB COOLING SUPPLY HEAT PUMP ELECTRIC AIR SUPPLY HEAT DB WB DB WB AIR SUPPLY AIR PRESSURES REFRIGERANT SUCTION REFRIGERANT DISCHARGE VERIFY PSIG SUCTION CHARGE at suction ].Measured at liquid line leaving IV. SELECT EASY FULL UNIT MODEL CHARGING TEMPI CHARTS condenser. SETTINGS NUMBER: AVAILABLE HEAT SETTINGS ENTER AVAILABLE AIRFLOW PIN CONNECTION (0/0 or 0/90 for gas/electric HEAT AIR PIN CONNECTION SETTING SETTING PIN CONNECTION CONTINUOUS USING TEMP* inlet to compressor. ENTER ADJUST LINE PSIG DISCHARGE REFRIGERANT *Measured TYPE AND SETSCREW MAKE SURE THAT - (If Applicable) ON 060 SIZE PURON HEAT PUMP ONLY, THE TWO OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED SUPPLY SETTING models) FAN PIN CONNECTION SETTING EASY SELECT Heat Settings AC HI_ Size I AC I Norm I System [ Lo [ I I HP EFF Lo I Hi J ENH J Hi On/Off o/9o Type HP-Comfort AC/HP CFM Adjust Delay 3O/_O/O Med INSTRUCTIONS AND IN PLACE ELECTRICAL () UNIT FOR TIGHTNESS IS CLEAN FOR LOCATIONS FROM PER INSTALLATION 29 WIRE TIGHTNESS TIES FASTEN TO THE Copyright 2008 Carrier Corp. • Manufacturer reserves 7310 W. Morris St. • the right to change, Indianapolis, IN 46231 at any time, specification8 and design8 Printed in U.S.A. without Edition notice and without 3O Date: 09/08 obligations, Catalog No: 50XZ-05SI Replaces: 50XZ- 4Sl
advertisement