- Home
- Domestic appliances
- Floor care
- Vacuum cleaners
- AirVac
- AVP24000
- Installation instructions
- 2 Pages
AirVac AVP24000 Installation Instructions
AirVac AVP24000 is a powerful central vacuum system designed for large homes up to 12,000 square feet. It boasts a 240 VAC operating voltage and a 7 AMP current draw, providing significant suction power. This system is equipped with a dedicated 15 AMP circuit breaker and offers a maximum duct length of 500 feet, making it suitable for multi-level homes with extensive ductwork.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
INTAKE
(LEFT OR
RIGHT)
PRINTER’S INSTRUCTIONS:
INSTR,INSTL,AIRVAC; LINEAR P/N: 226529 B; INK: BLACK; MATERIAL: 20# MEAD BOND; SIZE: 11.000” x 17.000”; FOLDING: 1‑FOLD VERTICAL, 1‑FOLD HORIZONTAL, FINISH 8.500” X 5.500” WITH LOGO SHOWING; SCALE: 1‑1; SIDE 1 OF 2
CENTRAL VACUUM MODELS
AVP3000, AVP7500, AVP12000, AVP24000
AVR3000, AVR7500, AVR12000, AVR24000
INSTALLATION INSTRUCTIONS
For Platinum and Red Series AirVac Units
(for Household Use Only)
IMPORTANT SAFETY NOTES
Please read the instructions carefully! Through many years of continuous use ‑‑ and through quality tests that are ongoing at our factory ‑‑ AirVac central vacuums, attachments and accessories have built a remarkable record for cleaning effectiveness and safety. However, there are potential hazards that could occur if the system is not installed and operated correctly and safely. READ ALL INSTRUCTIONS BEFORE USING THIS APPLIANCE.
THE FOLLOWING FORMATS ARE USED FOR SAFETY NOTES IN THESE INSTRUCTIONS.
CAUTION
This type of warning note is used to indicate the possibility of damage to the vacuum power unit or vacuum duct system.
WARNING
This type of warning note is used to indicate possible fire or electrical shock hazards that may cause serious injuries or death.
BALANCED, THE
DOOR WILL STAY AT A
HALFWAY POSITION
IMPORTANT SAFETY INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY:
1 NEVER OPERATE THE SYSTEM ON WET
SURFACES OR TO PICK UP LIQUIDS.
2 DO NOT USE THE SYSTEM TO VACUUM UP
FLAMMABLE OR COMBUSTIBLE LIQUIDS
SUCH AS GASOLINE or use in areas where they may be present.
3 Connect the power unit to a properly grounded
AC outlet only on a dedicated branch circuit.
7 Do not vacuum up anything that is burning or smoking, such as cigarettes, matches, or hot ashes.
8 Do not use without the dust bag (Platinum Series only) and filters in place.
9 Keep hair, loose clothing, fingers, and all parts of the body away from openings and moving parts.
4 Current‑carrying vacuum hose contains electrical wires. DO NOT USE THE HOSE IF IT IS
DAMAGED, CUT, OR PUNCTURED. Avoid vacuuming up sharp objects with the hose.
10 Do not put any object into any of the wall inlet valves or vacuum auxiliary air inlet. Do not use the system with any vacuum opening blocked; keep all ducting free of dust, lint, hair, or anything that may reduce the air flow.
5 The AirVac system is not a toy. NEVER LET 11 Turn off all controls before unplugging the power
CHILDREN OPERATE, OR PLAY WITH THE
AIRVAC SYSTEM.
IF PROPERLY
6 Use only as described in the Owner’s Manual and
DOOR WILL STAY AT A
HALFWAY POSITION only with the manufacturer’s recommended attachments.
unit.
12 Use extra care when cleaning stairs to prevent a fall.
SAVE THESE INSTRUCTIONS.
ARCHITECT’S SPECIFICATIONS
FOR LEFTWARD EXHAUST
30"
MINIMUM
WALL STUD
DRYWALL
EXHAUST
INTAKE AND
EXHAUST
FROM BOTTOM
OF MOUNTING
BRACKET
EXHAUST
(LEFT, RIGHT OR VERTICAL)
DEPTH DIMENSIONS
(TOP VIEW)
1-1/4"
1-3/4"
16"
AC POWER
OUTLET MUST BE
WITHIN 5 FEET OF
POWER UNIT TOP
HEIGHT DIMENSIONS
(SIDE VIEW)
40" TO
FLOOR
SPECIFICATIONS
CAUTION
All circuit breakers must be SEPARATE and DEDICATED as with any other major appliance. The electrical outlets
MUST match the plug WITHOUT USE OF ADAPTERS
120 VAC
NEMA 5-15R
240 VAC
NEMA 6-15R
“TYPE 1” “TYPE 2”
RECEPTACLE
TYPES
AIRVAC
MODEL
OPERATING
VOLTAGE
OPERATING
CURRENT
AVR3000
AVR7500
AVR12000
AVR24000
AVP3000
AVP7500
AVP12000
AVP24000
120 VAC
120 VAC
120 VAC
240 VAC
120 VAC
120 VAC
120 VAC
240 VAC
13.5 AMPS
13.5 AMPS
13.5 AMPS
7 AMPS
13.5 AMPS
13.5 AMPS
13.5 AMPS
7 AMPS
POWER UNIT SPECIFICATIONS
HOUSE
CIRCUIT
BREAKER
SIZE
20 AMP
20 AMP
20 AMP
15 AMP
20 AMP
20 AMP
20 AMP
15 AMP
RECEPTACLE
TYPE
HOME
SQUARE
FOOTAGE
TYPE 1
TYPE 1
TYPE 1
TYPE 2
TYPE 1
TYPE 1
TYPE 1
TYPE 2
3000
7500
12000
12000
3000
7500
12000
12000
MAXIMUM
DUCT
LENGTH
150 FEET
200 FEET
DEBRIS
CAPACITY
6 GALLONS
6 GALLONS
AIR
WATTS
537 PEAK
551 PEAK
350 FEET
500 FEET
6 GALLONS
6 GALLONS
570 PEAK
627 PEAK
150 FEET 5.2 GALLONS 537 PEAK
200 FEET 5.2 GALLONS 551 PEAK
350 FEET 5.2 GALLONS 570 PEAK
500 FEET 5.2 GALLONS 627 PEAK
WATER
LIFT
123”
131”
127”
137”
123”
131”
127”
137”
AIR
FLOW
118 CFM
118 CFM
122 CFM
124 CFM
118 CFM
118 CFM
122 CFM
124 CFM
TYPICAL VACUUM SYSTEM INSTALLATION
VM112
VM103 VM106
LOW
VOLTAGE
WIRES
VM102
LO
W
VO
LTA
GE WIRES
VM103 VM106
VM106
VM104
LOW VOLTAGE WIRES
WALL VALVE
BRACKET
VM241
VM104
WALL VALVE
BRACKET
VM241
LOW
VOLTAGE
WIRES
WALL VALVE
BRACKET
VM241
VM109
DOUBLE-FLANGED
WALL TEE
WALL VALVE
BRACKET
VM241
INTAKE
VM103
VM101
WALL VALVE
BRACKET
VM241
VM103
AIRVAC
POWER
UNIT
VM103
DO NOT CEMENT
THIS JOINT!
VM195 WALL INLET VALVES
TRIM OUT THE VM241 WALL
INLET VALVE BRACKETS
8-3/4"
7-1/2"
VM195 WALL INLET
VALVE (BACK VIEW)
1 New Construction Vacuum Duct and Wall Inlet Valve Installation
Valve Brackets for Wall Inlet Valves
1 Locate the first valve bracket at a point the farthest distance from the power unit. From this location, select additional valve locations. Each location should allow vacuuming in all corners of the room with a 30’ hose. Remember walls and furniture can shorten the distance serviced by a valve in some areas, so be sure to locate inlets with furniture and walls in mind.
TYPICAL WALL INLET VALVE LOCATIONS
MAIN VACUUM TUBE
2 Nail the valve brackets to the wall studs 12” to 15” above the floor, usually the same distance from the floor as electrical wall outlets. Alternate wall valve bracket configurations are possible.
Vacuum Duct System
1 After the valve brackets are nailed in place, drill a
2‑9/16” diameter hole in the header plate directly above each valve bracket. Cement a RISER tube from the valve bracket, extending the tube through the hole in the header plate for each valve.
2 Starting from the farthest valve bracket, lay tubing (cut‑ to‑length) on top of ceiling joist and work toward the power unit location. All sweep fittings must curve
in the direction of air flow. Connect all risers from valve brackets to the main duct line using only 90°
Sweep Tee Fittings (VM106) or 90° Sweep Fittings
(VM103). Cement all duct connections at the time
of installation. There cannot be any air leaks in the duct systems. Testing of vacuum integrity with wall inlet valves installed is highly recommended. Vacuum leaks will affect system performance.
VALVE BRACKET INSTALLATION
RISER
TUBE
STUD
VIEW FROM
INSIDE OF
WALL
DUCT SYSTEM INSTALLATION
FARTHEST WALL INLET
VALVE LOCATION
DRYWALL
SWEEP
TEE
POWER
UNIT
VALVE
BRACKET
TUBING STRAP
CEILING
JOIST
➤ NOTE: The use of nail guards (VM118) and plaster guards (VM196) are highly recommended to protect the wall valve brackets and vacuum duct system during construction.
90˚ ELBOW
BE SURE ALL
SWEEP TEE FITTINGS
CURVE IN THE DIRECTION
OF THE AIR FLOW
VALVE
BRACKET
MAIN VACUUM
TUBE TO
POWER UNIT
RISER
TUBE
Low Voltage Vacuum Control Wiring
CAUTION
All wiring installation must conform to local electrical codes. Wiring in the ground (soil) must be in conduit. All wiring installation must have a good, solid mechanical connection.
Protect all connections and/or splices against short circuits using wire nuts.
PLATE
CONTROL WIRE ROUTING
MAIN VACUUM
TUBE
STUD
1 Low voltage 18‑gauge, 2‑conductor cable connects all inlet valves to the power unit. When a hose is inserted into the wall inlet valve, the switch in the hose activates the power unit automatically; turning the switch off or removing the hose stops the power unit. Low voltage cable follows the same route as the vacuum duct system. Route the 2‑conductor cable from each valve bracket, up the risers to the main duct line.
2 Splice each additional riser cable to the main duct cable using wire nuts. All connections will be in PARALLEL.
3 Secure the wiring to the horizontal main line ducts with tape or quick clips (VM450), but DO NOT TAPE THE
CABLE TO THE RISERS. Secure the loose cable end at each valve bracket, allowing 6” of extra cable for each inlet valve connection and 18” of extra cable at the power unit location.
ROUTE 2-CONDUCTOR WIRE
FROM EACH VALVE BRACKET
UP TO THE MAIN VACUUM TUBE
CABLE THAT LEADS TO THE
POWER UNIT LOCATION
CONTROL WIRE SPLICING
VM450
QUICK
CLIP
LOW
VOLTAGE
WIRES
MAIN VACUUM
TUBE CABLE
AIRVAC
POWER UNIT
LOCATION
WIRE
NUTS
SPLICE WIRES
IN PARALLEL
Wall Inlet Valve Trim-out
1 When the installation is ready for trim‑out, connect the wires from a wall inlet valve to the cable that descends from the riser at the valve bracket.
2 Slide the wall inlet valve into the fitting on the valve bracket.
CAUTION
DO NOT CEMENT WALL INLET VALVES TO THE
VALVE BRACKET FITTING! Occasionally, wall inlet valves require replacement due to leaky gaskets or other damage. If the wall inlet valve is cemented to the valve bracket fitting, the wall inlet valve cannot be replaced.
DO NOT TAPE
CABLE TO RISER!
WALL INLET VALVE TRIM-OUT
FROM VALVE
BRACKET
CONNECT CONTROL
WIRES TO WALL
INLET VALVE
VM450
QUICK
CLIP
3 Secure the wall inlet valve to the valve bracket with the two wall plate screws.
4 Repeat steps for each wall inlet valve location.
ATTACH WALL INLET
VALVE TO VALVE
BRACKET WITH
TWO SCREWS
DO NOT CEMENT
THIS CONNECTION!
2 Existing Construction Vacuum Duct Installation Techniques
Overhead Vacuum Duct Installation
Two people are normally required to perform overhead vacuum duct installations. Power unit installation requirements are the same as in new construction. Wall inlet valves should be limited to interior walls. Exterior walls contain insulation and are not normally accessible from inside the roof to drill holes for the vacuum duct.
1 After marking a wall valve location, check inside the roof area to see if a hole can be drilled in the header plate for the tubing. BEFORE DRILLING,
CHECK FOR ELECTRICAL WIRING. If there are no obstructions, drill a 2‑9/16” diameter hole in the header
OVERHEAD RISER INSTALLATION
LOWER RISER
TUBE DOWN
FROM ATTIC
RISER TUBE plate. It is possible that you will hit a fire block about halfway down the wall. If this is the case, you must use an extension drill and drill through the fire block. Make sure the drill is straight up and down or you might drill through the side of the wall!
2 After holes are drilled, lower tubing and the low‑voltage control wire from inside the roof to the wall valve.
Seldom is the roof high enough to use a single length of tubing. As the tube is dropped down the wall to the valve location, several short lengths of tubing should be cemented together with a straight coupling (VM102).
1“ DIAMETER
WALL INLET VALVE
INSPECTION HOLE
BECAUSE OF LOW
ATTIC CLEARANCE
USE VM102 COUPLINGS
TO CONNECT SEVERAL
SHORT LENGHTS OF
TUBING
3 At the wall valve location, drill a 1” diameter hole in the wall. Using a flashlight from the attic, check for hole alignment. Then cut a rectangular hole 2‑½” horizontal and 3‑½” vertically from the center of the 1” diameter hole. This hole will allow an adapter (VM107) to make contact with tubing inside the wall. CEMENT THE
ADAPTER TO THE TUBING.
ALIGNING THE WALL ADAPTER FITTING
CUT HOLE 2-1/2” WIDE BY
3-1/2” HIGH TO SLIP VM107
ADAPTER INSIDE WALL
4 Secure the adapter to the mounting bracket (VM142) with screws. After the mounting bracket is attached to the adapter, the completed assembly inside the wall is ready for the inlet valve (VM195).
5 Connect the low‑voltage control wires and slide the inlet valve into the fitting on the valve bracket.
DO
NOT CEMENT THE INLET VALVE TO THE WALL
BRACKET FITTING. Tighten the valve against the wall with screws to the mounting bracket.
VM107
ADAPTER
ALIGN WITH
FINGER WHILE
CEMENTING THE
FITTING TO THE
RISER TUBE
LOW VOLTAGE
CONTROL WIRE
(DO NOT TAPE TO RISER!)
PRINTER’S INSTRUCTIONS:
INSTR,INSTL,AIRVAC; LINEAR P/N: 226529 B; INK: BLACK; MATERIAL: 20# MEAD BOND; SIZE: 11.000” x 17.000”; FOLDING: 1‑FOLD VERTICAL, 1‑FOLD HORIZONTAL, FINISH 8.500” X 5.500” WITH LOGO SHOWING; SCALE: 1‑1; SIDE 2 OF 2
Overhead Vacuum Duct Installation (continued)
6 Secure the inlet valve to the valve bracket with the two wall plate screws.
7 Repeat steps for each wall inlet valve location.
Under the Floor Installation
In homes with a pier and beam foundation or basement, either the overhead or an under the floor installation can be made. Sometimes under the floor installation is easier in an existing home, especially if the roof has a low pitch and clearances in the attic adds to the installation problem.
Under the floor installation also eliminates encountering fire blocks in the wall. Shorter risers are also utilized, eliminating the longer tube drop from the attic.
1 Vacuum tubing should be secured to floor joist with perforated nailing strips or tube straps.
2 Generally, follow the overhead installation steps, but from below the floor, to install each wall inlet valve.
Alternate Vacuum Duct Riser Installation
An effective technique highly suitable for many types of construction with adequate working room inside the attic is to make drops to the wall inlet valves through the ceiling, then route the tube through the wall at inlet level for the inlet valve on the opposite side of the wall. If this method is used, the drop from the inside of the attic for the riser can be made in the corner of a closet, utility room, etc. where the tubing is not visible or not objectionable to the Homeowner. On occasion this might be the only alternative for placing an inlet valve in a desired location.
UNDER FLOOR INSTALLATION
INSTALL
VALVE BRACKET
12" TO 15" ABOVE
FLOOR LEVEL
PLATE
FLOOR
THE TUBING DROP
CAN BE INSIDE A CLOSET
THEN THROUGH THE
WALL TO THE WALL
VALVE INSIDE THE ROOM
VM106
SWEEP TEE
FLOOR
JOIST
ALTERNATE DUCT RISER INSTALLATION
TO WALL VALVE
ON OTHER SIDE
OF THE WALL
FLOW
MAIN VACUUM TUBE
STUD
HOLE IN
CEILING
RISER AND
CONTROL
WIRE
3 Power Unit Installation
Power Unit Unpacking and Pre-assembly
This AirVac power unit is packaged disassembled in a nested configuration which reduces the size of the shipping carton and allows for much smaller shelf space requirements than previous AirVac models. The power unit must be assembled during installation.
1 Carefully remove the nested vacuum from the box.
2 Separate each of the nested parts and place them gently on the floor.
3 Refer to the parts identification figure below to familiarize yourself with each of the parts.
VACUUM PARTS IDENTIFICATION
EXHAUST MUFFLER
EXHAUST ELBOW FLEXIBLE HOSE
INLET PLUG HOSE
CLAMPS
VACUUM BODY
MOUNTING
BRACKET
LAG
SCREWS
CAUTION
Do not mount the motor head onto the vacuum body until AFTER the vacuum body is hung on the mounting bracket. Placing the motor head on the vacuum body before mounting causes the unit to be top heavy and may tip the vacuum over, causing damage to the vacuum.
DUST CONE
(PLATINUM SERIES ONLY) DEBRIS BUCKET
EXHAUST ELBOW & DUST CONE INSTALLATION
ATTACH THE EXHAUST
ELBOW TO THE MOTOR
HEAD WITH #4 SCREW
4 Connect the 90° steel exhaust elbow to the motor head. The exhaust elbow can point to the left, right or vertical depending on the installation requirements.
Secure the exhaust elbow to the motor head flange with the #4 self‑tapping screw.
5 PLATINUM SERIES ONLY: Install the dust cone inside the bottom end of the vacuum body as shown in the figure. Be sure the cone snaps against the large ridge in the vacuum body. DO NOT PUSH DUST CONE PAST
THE LARGE RIDGE!
6 PLATINUM SERIES ONLY: Install the slide‑gate collar dust bag into the debris bucket. BE SURE TO FULLY
EXPAND THE BAG WITH YOUR HAND TO FILL THE
BUCKET.
Power Unit Mounting
1 Determine the mounting location for the power unit. Be sure clearance dimensions are followed. The power supply cord length is 5 feet. An AC power outlet of the proper type on a dedicated circuit breaker must be available within 5 feet so the power supply cord can be directly plugged into the electrical outlet. DO NOT USE
AN EXTENSION CORD.
2 Use a stud finder to locate a wall stud for attaching the mounting bracket. Mark the stud location.
3 Attach the mounting bracket to the wall, centered on the marked stud, with the bottom edge 40" above the floor, using the two 1/4" x 2" lag screws and a 7/16" socket.
4 Carefully hang the vacuum body by sliding the body’s mounting tab into the mounting bracket slot.
5 Fit the motor head onto the vacuum body with the controls facing forward latching the two locking snaps.
6 Hang the debris bucket on the two bucket slide latches.
Swing the two slide latch handles up to lock the debris bucket into place.
7 Slide the exhaust muffler onto the exhaust elbow.
Optional Exhaust Tubing
The vacuum’s exhaust can be piped away from the power unit if desired or required. The exhaust tubing must vent to the outside of the house, NOT INTO THE
ATTIC. A louvered exhaust vent cap (VM136) is available to terminate the exhaust tubing. Steel tubing is also available for the exhaust tubing and may be required by local building codes.
CAUTION
In order to avoid motor failure resulting from excessive back pressure, DO NOT install more than 30 feet of exhaust tubing and DO NOT install any bends in the exhaust tubing closer than 18" from the exhaust muffler.
1 Install any optional exhaust tubing following the guidance above.
2 Connect the optional exhaust tubing to the muffler.
SLIDE-GATE COLLAR BAG
(PLATINUM SERIES ONLY)
DO NOT PRESS
CONE PAST THE
LARGE RIDGE
EXHAUST ELBOW
CAN POINT TO
LEFT, RIGHT OR VERTICAL
MOTOR HEAD
TIP DUST CONE
INTO VACUUM BODY
BOTTOM END
PRESS DUST CONE
IN UNTIL THE FOUR
TABS SNAP AGAINST
THE LARGE RIDGE
DUST BAG INSTALLATION (PLATINUM SERIES ONLY)
EXPAND THE DUST
BAG BEFORE PLACING
IT INTO THE DEBRIS BUCKET
PLACE THE BAG INTO THE
DEBRIS BUCKET AND
EXPAND THE BAG AGAINST
THE DEBRIS BUCKET SIDES
SCREW TO
WALL STUD
SLIDE-GATE COLLAR BAG
BOTTOM
EDGE 40"
ABOVE
FLOOR
SNAP MOTOR HEAD
ONTO VACUUM BODY
RETAINING
SNAP
OPTIONAL EXHAUST TUBING
PLACE BAG'S
SLIDE-GATE
HERE
HANGING THE MOUNTING BRACKET & MOUNTING THE VACUUM BODY
ATTACH MOUNTING BRACKET
TO WALL WITH TWO LAG SCREWS
INSTALLING THE MOTOR HEAD AND DEBRIS BUCKET
HANG DEBRIS
BUCKET ON BUCKET
SLIDE LATCHES
18" MINIMUM FROM
THE MUFFLER BEFORE
ANY BENDS IN THE
EXHAUST TUBING
BUCKET
SLIDE
LATCH
EXHAUST TUBING
MUST VENT OUTSIDE
OF THE HOUSE
VM136
LOUVERED
EXHAUST
VENT CAP
HANG VACUUM BODY ON
MOUNTING BRACKET
SWING THE TWO
BUCKET SLIDE
LATCHES UP
OUTSIDE
WALL
Vacuum Intake Connection
Depending on the requirements of the installation, the main vacuum duct line can be connected to the left or right side intake port of the power unit.
1 Cut a 4" piece of duct tubing.
2 Slide the tubing piece into the left or right power unit intake port. DO NOT CEMENT TUBING.
3 Slide a hose clamp onto the flexible hose. Slide the flexible hose onto the tubing piece. Tighten the hose clamp.
4 Slide another hose clamp onto the flexible hose.
Connect the flexible hose to the drop from the main vacuum duct system line. Tighten the hose clamp.
5 The unused power unit intake port MUST be sealed, slide the inlet plug onto the unused intake port.
VACUUM INTAKE CONNECTION
VACUUM
INTAKE PORT
HOSE
CLAMPS
FLEXIBLE
HOSE
THE UNUSED
INTAKE PORT
MUST BE SEALED!
MAIN
VACUUM
TUBE
INSERT THE INLET
PLUG ONTO THE
UNUSED VACUUM
INTAKE PORT
4 Power Unit Electrical
Low Voltage Control Wire Connection
1 Strip back the insulation about 1/2" from the two‑ conductor low voltage control wire cable at the power unit.
2 Using a small screwdriver or other object, press down on one of the wire locks on the control wire connector
(top rear of motor head) while inserting the wire into the connector hole. Release the wire lock while holding the wire in. Repeat with the other wire and the other hole. Polarity is not important, either wire can be connected to either hole.
Grounding Instructions
LOW VOLTAGE CONTROL WIRE CONNECTION
LOW VOLTAGE
CONTROL WIRE
CONNECTOR
LOW VOLTAGE
CONTROL WIRE
FROM WALL VALVES
PUSH EACH WIRE
LOCK DOWN WHILE
INSERTING THE WIRE
INTO THE CONECTOR
HOLE
This appliance must be grounded. If it should malfunction or breakdown, grounding provides a path of least resistance for electrical current to reduce the risk of electrical shock. This appliance is equipped with a cord having an equipment‑grounding conductor and grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
WARNING CAUTION
Improper connection of the equipment-grounding conductor can result in risk of electric shock.
Check with a qualified electrician or service person if you are in doubt as to whether the outlet is properly grounded. Do not modify the plug provided with the appliance - if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
All circuit breakers must be SEPARATE and
DEDICATED as with any other major appliance.
The electrical outlets MUST match the plug
WITHOUT THE USE OF ADAPTERS. DO NOT USE
AN EXTENSION CORD.
AC POWER CONNECTION
Power Connection
1 BE SURE THE UNIT’S POWER SWITCH IS OFF.
Plug the line cord into the AC receptacle.
2 Verify that power is available to the vacuum by switching the unit’s power on then off.
BE SURE THE POWER
SWITCH IS OFF
PLUG THE POWER UNIT
INTO A GROUNDED
AC OUTLET THAT IS
WIRED TO A DEDICATED
CIRCUIT BREAKER
DO NOT USE AN
EXTENSION CORD
OR AN AC ADAPTER!
System Testing
The AirVac central vacuum system should be tested for good suction throughout the system. Use a vacuum gauge
(VM181) at each wall inlet valve location to measure the vacuum suction.
5 Troubleshooting
NOTE: NO USER SERVICEABLE PARTS INSIDE, DO NOT LUBRICATE MOTOR.
IF THE MOTOR FAILS TO OPERATE
1 Be sure the power unit is plugged into a working AC outlet.
2 Push breaker reset button on the power unit.
3 Check the panel circuit breaker that connects the power unit.
AFTER CHANGING OF THE BAG (PLATINUM SERIES ONLY)
1 Push down the RESET button for 7 seconds to reset the bag indicator.
IN CASE OF LOW VACUUM POWER
1 Be sure that the inlet plug is inserted into the unused power unit intake port.
2 Check that all wall valves are closed.
3 Check that all gaskets on wall valves are sealed.
4 Check to see if debris bucket or bag (Platinum Series only) needs emptying.
5 Check for obstructions in the hose, tools, or vacuum lines.
6 Check for any ruptures or breaks in the vacuum duct system.
If you are unable to resolve the operational problems, please contact AirVac technical support at (800) 421‑1587.
6 Limited Warranty
Linear LLC warrants AirVac Platinum Series power units to be free of defects for
10 years, and AirVac Red Series power units to be free of defects for 5 years.
The warranty period begins from either (1) the date of “first user” purchase of this product or (2) the first close of escrow date on a residence in which this new product was originally installed. This warranty extends to the original user of the product and to each subsequent owner of the product during the term of this warranty. Linear LLC will repair or replace, at its option, parts and materials at no charge. Parts supplied under this warranty may be new or rebuilt at the option of Linear LLC.
If, during the limited warranty period, it appears as though this product contains a defect which is covered by this limited warranty, call our toll free service number before dismantling the product (1-800-421-1587). Remember to attain a Return Product Authorization number (RPA) before returning any product to Linear LLC. Send this product freight pre-paid and insured
to our service center for warranty repair. You will be advised on shipping instructions when you call the toll free service number. Linear LLC will return the repaired product freight pre‑paid within the U.S.A. The installing dealer or distributor may assist you, at your choice and expense, with returning product for repair. Please include a brief description of the problem and a dated proof‑ of‑purchase receipt with any product that is returned for warranty repair. ANY
PRODUCT RETURNED WITHOUT A RETURN PRODUCT AUTHORIZATION
NUMBER WILL BE REFUSED.
THIS LIMITED WARRANTY IS IN LIEU OF ANY OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR
OTHERWISE, AND OF ANY OTHER OBLIGATIONS OR LIABILITY ON THE
SELLER’S PART. THIS LIMITED WARRANTY DOES NOT COVER DAMAGE
CAUSED BY ACTS OF GOD, IMPROPER INSTALLATION, NORMAL
SYSTEM WEAR AND TEAR AS DEFINED BY THE MANUFACTURER, THE
VIOLATION OF APPLICABLE BUILDING OR ELECTRICAL CODES, OR
THE USE OF NON-AIRVAC WIRE, CABLE, OR WALL HOUSINGS. THIS
LIMITED WARRANTY APPLIES ONLY TO PRODUCTS INSTALLED IN A
PRIVATE RESIDENCE.
UNDER NO CIRCUMSTANCES SHALL THE SELLER BE LIABLE FOR
CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES ARISING IN
CONNECTION WITH USE, OR INABILITY TO USE THIS PRODUCT. IN
NO EVENT SHALL SELLER’S LIABILITY, FOR BREACH OF WARRANTY,
BREACH OF CONTRACT, NEGLIGENCE, OR STRICT LIABILITY, EXCEED
THE COST OF THE PRODUCT COVERED HEREBY. NO PERSON
IS AUTHORIZED TO ASSUME FOR US ANY OTHER LIABILITY IN
CONNECTION WITH THE SALE OF THIS PRODUCT.
Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or exclusion may not apply to you.
This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Copyright © 2010 Linear LLC
www.purelypowerful.com
Manufactured by:
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340 www.linearcorp.com
226529 B
advertisement
Key Features
- 240 VAC, 7 AMP
- 12,000 sq ft
- 500 ft duct length
- 6 gal debris capacity
- 124 CFM air flow
- Type 2 receptacle
- Dedicated 15 AMP breaker