Trane CenTraVac CVHE, CenTraVac CVHG Assembly/Disassembly Manual

Trane CenTraVac CVHE, CenTraVac CVHG Assembly/Disassembly Manual

Trane CenTraVac CVHE is a water-cooled chiller designed for commercial and industrial applications, offering high efficiency, reliability, and precise temperature control. Its advanced features and capabilities make it an ideal choice for various cooling needs, including data centers, hospitals, and manufacturing facilities.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Trane CenTraVac CVHE Assembly/Disassembly Manual | Manualzz
Disassembly and Reassembly Units
Water-Cooled CenTraVac™ Chillers
50 Hz Models: CDHG, CVHE, CVHG
60 Hz Models: CDHF, CVHE, CVHF
X39640718110
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
January 2019
CVHE-SVN04M-EN
Introduction
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTION
NOTICE
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs and HCFCs such as
saturated or unsaturated HFCs and HCFCs.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or
serious injury.
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION
hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and
grounding as described in NEC and your local/
state/national electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being
undertaken could result in death or serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual
and on the tags, stickers, and labels, as well as the
instructions below:
•
Before installing/servicing this unit,
technicians MUST put on all PPE required for
the work being undertaken (Examples; cut
resistant gloves/sleeves, butyl gloves, safety
glasses, hard hat/bump cap, fall protection,
electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety
Data Sheets (MSDS)/Safety Data Sheets
(SDS) and OSHA guidelines for proper PPE.
•
When working with or around hazardous
chemicals, ALWAYS refer to the appropriate
MSDS/SDS and OSHA/GHS (Global
Harmonized System of Classification and
Labelling of Chemicals) guidelines for
information on allowable personal exposure
levels, proper respiratory protection and
handling instructions.
•
If there is a risk of energized electrical
contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA
70E, or other country-specific requirements
for arc flash protection, PRIOR to servicing
the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING
WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE
ELECTRICAL METERS AND EQUIPMENT ARE
PROPERLY RATED FOR INTENDED
VOLTAGE.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices
are important to the environment, our customers, and
the air conditioning industry. All technicians who
handle refrigerants must be certified according to local
rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
©2019 Ingersoll Rand
CVHE-SVN04M-EN
Introduction
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in
death or serious injury.
•
•
All Ingersoll Rand personnel must follow
Ingersoll Rand Environmental, Health and
Safety (EHS) policies when performing work
such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. All
policies can be found on the BOS site. Where
local regulations are more stringent than
these policies, those regulations supersede
these policies.
Non-Ingersoll Rand personnel should always
follow local regulations.
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY.
Contractor must provide a two-week startup
notification to Trane (or an agent of Trane specifically
authorized to perform startup).
Additional Requirements for Units Requiring
Disassembly and Reassembly
When a new chiller is shipped and received from our
Trane manufacturing location and, for any reason, it
requires disassembly or partial disassembly, and
reassembly— which could include but is not limited to
the evaporator, condenser, control panel, compressor/
motor, economizer, purge, factory-mounted starter or
any other components originally attached to the fully
assembled unit— compliance with the following is
required to preserve the factory warranty:
•
Trane, or an agent of Trane specifically authorized
to perform start-up and warranty of Trane®
products, will perform or have direct on-site
technical supervision of the disassembly and
reassembly work.
•
The installing contractor must notify Trane—or an
agent of Trane specifically authorized to perform
startup and warranty of Trane® products—two
weeks in advance of the scheduled disassembly
work to coordinate the disassembly and
reassembly work.
•
Start-up must be performed by Trane or an agent of
Trane specifically authorized to perform startup and
warranty of Trane® products.
Copyright
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
•
Update to Figure 1, p. 10
•
Update to Figure 2, p. 11
Factory Warranty Information
Compliance with the following is required to preserve
the factory warranty:
Trane, or an agent of Trane specifically authorized to
perform start-up and warranty of Trane® products, will
provide qualified personnel and standard hand tools to
perform the disassembly and reassembly work at a
location specified by the contractor. The contractor
shall provide the rigging equipment such as chain falls,
gantries, cranes, forklifts, etc. necessary for the
disassembly and reassembly work and the required
qualified personnel to operate the necessary rigging
equipment.
All Unit Installations
CVHE-SVN04M-EN
3
General Information
WARNING
Refrigerant May Be Under Positive
Pressure!
Failure to follow instructions below could result in
an explosion which could result in death or
serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
NOTICE
Equipment Damage!
Mixing refrigerants or oils could result in
equipment damage including bearing damage,
introduction of acids into the chiller, or continuous
purge pump-out in high-head/high ambient
applications.
CenTraVac chillers are manufactured with
different refrigerant/oil systems: 1) chillers using
R-123 refrigerant and OIL00022 compressor oil,
and 2) chillers using R-514A refrigerant and
OIL00334/OIL00335 compressor oil.
Verify proper refrigerant and oil for your chiller
and do NOT mix refrigerants or oils!
Contractor Responsibilities
WARNING
Heavy Objects!
Failure to follow instructions below could result in
component dropping which could result in death
or serious injury, and equipment or property-only
damage.
Loads can shift and become off-center during
shipping. Ensure that components are centered
before lifting and always test lift each component
to verify center of gravity using lifting equipment
rated for the task. Only experienced riggers should
perform unit disassembly/reassembly.
•
Handle/lift and rig equipment
•
Protect all internal components from exposure to
elements, which could contaminate or corrode
chiller components
•
Chiller reassembly
•
Replace all gaskets with new gaskets or O-rings and
sealing compound; the contractor should assist a
qualified Trane Technician with this responsibility
NOTICE
Compressor Damage!
POE oil is hygroscopic – it absorbs water
directly from the air. This water is nearly
impossible to remove from the compressor oil
and can result in compressor failures.
To prevent POE oil from absorbing water, the
system should not remain open for longer than
necessary. When open, dry nitrogen should
flow through the piping. Only new oil
containers should be used for service and
maintenance. Always use the smallest
container size required for the job
requirements. Always leave the oil container
tightly sealed until time of use. Do not reuse oil
that has been opened.
This Installation, Operation, and Maintenance manual
applies to CenTraVac™ chillers with two different
refrigerant and oil systems:
•
R-123 and OIL00022
•
R-514A and OIL00334/OIL00335
I m p o r t a n t : Verify proper refrigerant and oil for your
chiller before proceeding!
The information and procedures in this document are
to facilitate unit disassembly for clearance and access
reasons during the installation process.
The understanding is that the chiller has what is
referred to as the “compressor doweling option” or
“separable shell option” (which includes compressor
doweling). Compressor doweling sets up the
compressor for removal. The separable shell option
includes a bolt together design between the evaporator
and condenser and allows the shells to be separated in
the field.
I m p o r t a n t : These procedures do NOT apply to units
that have been installed and electrical
supply wiring has been completed.
4
•
Change the compressor oil; the contractor should
assist a qualified Trane Technician with this
responsibility
•
Evacuate the chiller under 1000 microns; the
contractor should assist a qualified Trane
Technician with this responsibility
•
Recharge the chiller with dry nitrogen to 5 psig; the
contractor should assist a qualified Trane
Technician with this responsibility
•
Replace and/or repair insulation
•
Reconnect electrical connections
•
Spot paint the chiller if necessary
CVHE-SVN04M-EN
General Information
Metric Conversions
Device Descriptions
English
Metric
Device
Description
ft·lb x 1.3558
Newton·meter
CPTF
lb x 0.4536
kg
Optional control power transformer (INDP
units only)
in x 25.4000
mm
FRCL
Optional free cooling
HGBP
Optional hot gas bypass
INDP
Optional industrial control package
SMP
Optional supplemental motor protection
(INDP units only)
UAFD
Unit-mounted Adaptive Frequency™ drive
UATR
USID
Unit-mounted medium-voltage auto
transformer
Unit-mounted medium-voltage primary
reactor
Unit-mounted medium-voltage across-theline starter
Unit-mounted low-voltage solid state starter
USTR
Unit-mounted low-voltage wye-delta starter
UPIR
UXL
CVHE-SVN04M-EN
5
Dimensions and Weights
Dimensions
Single Compressor Chillers: Models
CVHE, CVHF, and CVHG
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
Table 1. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers
Model
CVHE
NTON
Shell Size
Comp
Size
A
B
C
D
E
F
G
H
J
K
L
M
190–270
032
320
66.7
53.1
N/A
N/A
84.9
49.2
49.7
70.8
45.5
53.1
37.9
34.5
230–320
050
320
75.4
53.6
N/A
N/A
73.4
49.2
52.4
77.1
45.5
52.5
43.9
38.7
N/A
87.8
51.7
54.4
77.1
45.5
52.5
42.3
38.7
87.8
51.7
58.6
93.8
45.5
62.2
63.5
44.3
300–420
050
500
73.7
52.7
N/A
360–500
080
500
93.5
77.1
101.3
42.0
300–450
050/080
500
84.1
66.0
90.4
42.0
87.8
51.7
58.6
82.7
46.0
54.9
49.32
41.3
050
480
75.4
52.7
N/A
N/A
78.3
51.3
54.4
77.1
45.5
52.5
43.9
38.7
350–570
620–870
650–910
CVHF
1070–1300
1470–1720
6
050/080
480
84.1
64.6
90.4
42.0
78.3
51.3
59.1
82.7
46.0
54.9
49.32
41.3
080
480
93.5
75.7
101.3
42.0
78.3
51.3
59.1
93.8
45.5
62.2
63.5
44.3
080
870
93.5
75.0
101.3
42.0
81.2
59.7
73.2
93.8
45.5
63.9
63.5
44.3
080/142
870
101.3
79.4
107.5
(a)
81.3
59.7
73.2
102.0
45.5
67.9
63.59
46.0
142
870
98.1
80.4
121.9
(a)
81.2
59.7
73.2
110.9
46.9
65.4
62.5
50.5
080
910
93.5(b)
76.5
101.3
42.0
81.2
54.6
66.7
93.8
45.5
63.9
63.5
44.3
080/142
910
101.3
79.4
107.5
(a)
81.3
54.6
66.7
102.0
45.5
64.6
63.59
46.0
142
910
98.1
83.0
111.0
(a)
81.2
54.6
66.7
105.5
46.9
69.8
62.5
46.0
080/142
1300
102.2
80.5
107.5
(a)
80.5
59.1
72.4
102.0
45.5
65.7
63.59
46.0
142
1300
120.9
80.4
121.9
(a)
80.2
54.6
72.6
110.9
46.9
64.2
76.5
50.5
142/210
1300
106.0
88.2
109.7
(a)
80.5
59.1
72.4
105.4
46.9
73.1
62.5
52.4
210
1300
106.5
94.5
116.0
(a)
80.2
59.7
72.6
116.4
50.5
84.5
68.2
50.5
250
1300
120.9
98.6
121.9
(a)
80.2
59.7
72.6
116.4
54.5
84.5
76.7
56.6
142/210
1720
106.0
86.5
109.7
(a)
93.8
63.1
75.6
105.4
46.9
73.1
62.5
52.4
91.2
63.1
75.6
110.9
50.5
78.2
68.2
50.5
91.2
63.1
75.6
116.4
54.5
84.4
76.7
56.6
210
1720
106.5
92.8
116.0
(a)
250
1720
120.9
96.9
121.9
(a)
CVHE-SVN04M-EN
Dimensions and Weights
Table 1. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers (continued)
Model
NTON
480–565
670–780
Shell Size
Comp
Size
A
B
050
565
75.4
52.6
080
565
93.5
74.6
050/080
565
82.6(c)
63.4
080
780
93.5
080/142
780
101.3
C
D
E
F
G
H
J
K
L
M
N/A
N/A
93.8
53.0
57.5
77.1
45.5
52.5
43.9
38.7
101.3
42.0
94.3
53.0
62.8
93.8
45.5
62.2
63.5
44.3
90.2
42.0
94.5
52.9
62.8
82.7
46.0
57.6
49.32
40.0
76.5
101.3
42.0
94.0
54.3
66.6
93.8
45.5
63.9
63.5
44.3
79.4
107.5
(a)
91.9
54.3
66.6
102.0
45.5
66.8
63.59
46.0
142
780
98.1
83.0
111.0
(a)
94.0
54.3
66.6
105.5
46.9
69.8
62.5
46.0
080/142
920
102.2
82.0
107.5
(a)
90.9
54.6
68.7
102.0
45.5
64.3
63.59
46.0
CVHG
142
920
98.1
84.0
111.0
(a)
93.2
54.3
68.0
105.5
46.9
69.8
62.5
46.0
142/210
920
106.0
89.7
109.7
(a)
93.3
54.6
68.7
105.4
46.9
76.2
62.5
52.4
210
920
106.5
96.0
116.0
(a)
93.2
54.3
68.0
110.9
50.5
81.5
68.2
50.5
920–1067
080/142
1100
102.2
80.5
107.5
(a)
93.2
59.1
72.4
102.0
45.5
65.7
63.59
46.0
142
1100
98.8
80.4
107.4
(a)
93.2
59.7
71.8
101.9
46.9
62.0
62.3
46.0
142/210
1100
106.0
88.2
109.7
(a)
93.2
59.1
72.4
105.4
46.9
76.2
62.5
52.4
210
1100
106.5
94.5
116.0
(a)
93.2
59.7
72.6
110.9
50.5
78.2
68.2
50.5
1100
Note: All dimensions are in inches (±0.5 inch).
(a)
(b)
(c)
Does not extend beyond the condenser tube unit.
Add 1 in. to overall width for compressor.
Add 0.4 in. to overall width for compressor.
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
CVHE-SVN04M-EN
7
Dimensions and Weights
Table 2. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers
Model
CVHE
NTON
Shell Size
Exp
Std
Comp
Size
N
Long
Short
R
S
T
U
V
X
P
W
190–270
032
320
60.1
71.4
81.9
29.7
17.0
26.5
68.6
93.9
47.0
47.0
N/A
230–320
050
320
64.6
71.4
81.9
29.7
17.0
23.4
80.5
98.4
63.4
54.9
N/A
300–420
050
500
62.8
71.4
81.9
29.8
17.3
26.5
80.5
98.7
63.4
54.9
N/A
360–500
080
500
79.0
71.4
81.9
29.8
17.3
26.5
97.1
114.9
80.8
80.8
66.3
300–450
050/080
500
68.1
71.8
82.3
29.0
16.3
26.5
90.1
103.8
N/A
N/A
N/A
050
480
64.3
71.4
81.9
29.0
16.3
26.5
80.5
100.0
60.7
54.9
N/A
350–570
050/080
480
68.1
71.8
82.3
29.0
16.3
26.5
90.1
103.7
N/A
N/A
N/A
080
480
79.0
71.4
81.9
29.0
16.3
26.5
97.1
114.9
75.0
75.0
66.3
080
870
75.7
71.4
81.9
30.5
17.8
29.0
97.1
117.1
82.4
82.4
63.9
080/142
870
79.0
71.3
81.8
N/A
18.5
29.0
120.9
121.6
N/A
N/A
72.7
142
870
93.8
72.8
83.3
30.5
17.8
29.0
117.4
121.5
82.4
82.4
72.7
080
910
75.7
71.4
81.9
30.5
17.8
29.0
97.1
114.9
82.4
82.4
63.9
620–870
650–910
CVHF
1070–1300
1470–1720
480–565
670–780
080/142
910
79.0
71.3
81.8
N/A
18.5
29.0
120.9
117.8
N/A
N/A
72.7
142
910
82.1
72.8
83.3
30.5
17.8
29.0
115.4
121.3
84.4
84.4
72.7
080/142
1300
80.5
71.3
81.8
N/A
18.6
36.8
121.8
121.6
N/A
N/A
72.7
142
1300
93.8
72.8
83.3
N/A
21.1
36.8
117.4
121.5
78.1
78.1
72.7
142/210
1300
87.7
72.8
83.3
N/A
21.1
36.8
126.9
129.0
N/A
N/A
72.7
21.1
36.8
124.7
135.2
87.2
87.2
82.4
18.6
36.8
137.2
139.4
N/A
N/A
82.7
210
1300
93.8
76.4
86.9
N/A
250
1300
97.9
80.4
90.9
N/A
142/210
1720
86.5
72.8
83.3
N/A
25.8
36.8
126.9
130.9
N/A
N/A
72.7
210
1720
92.6
76.4
86.9
N/A
25.8
33.3
124.7
137.2
92.9
92.9
76.4
250
1720
96.8
80.4
90.9
N/A
23.3
33.3
137.2
141.4
N/A
N/A
82.7
050
565
66.4
71.4
81.9
32.4
19.9
26.5
80.5
103.0
63.4
54.9
N/A
080
565
68.4
71.8
82.3
32.4
19.9
29.0
91.4
104.7
N/A
N/A
N/A
050/080
565
79.2
71.4
81.9
33.6
21.2
29.0
98.1
115.8
81.7
81.7
N/A
080
780
75.7
71.4
81.9
33.5
21.1
32.8
98.1
114.7
82.4
82.4
N/A
N/A
72.7
84.4
N/A
080/142
780
79.0
71.3
81.8
N/A
18.5
32.8
120.9
117.6
N/A
142
780
82.1
72.8
83.3
27.8
17.8
32.8
115.4
121.2
84.4
080/142
920
80.5
71.3
81.8
N/A
18.6
36.8
121.8
119.4
N/A
N/A
72.7
142
920
82.1
72.8
83.3
28.0
18.0
36.8
115.4
121.2
84.4
84.4
N/A
CVHG
920–1067
142/210
920
87.7
72.8
83.3
N/A
21.3
36.8
126.9
126.7
N/A
N/A
72.7
210
920
93.8
76.4
86.9
33.7
21.3
36.8
124.7
132.8
92.9
92.9
N/A
080/142
1100
80.5
71.3
81.8
N/A
18.6
36.8
121.8
121.6
N/A
N/A
72.7
142
1100
80.1
72.8
83.3
28.0
18.0
36.8
117.4
121.5
78.1
78.1
72.7
142/210
1100
87.7
72.8
83.3
N/A
21.3
36.8
126.9
129.0
N/A
N/A
72.7
210
1100
93.8
76.4
86.9
33.7
21.3
36.8
124.7
135.2
87.2
87.2
82.4
1100
Note: All dimensions are in inches (±0.5 inch).
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
8
CVHE-SVN04M-EN
Dimensions and Weights
Table 3. Dimensional data for CVHE, CVHF and CVHG CenTraVac chillers
Model
NTON
Shell Size
Comp
Size
UATR
UPIR
UXL
USID
USTR
Y1
CVHE
UATR
UPIR
UXL
USID
USTR
Y2
AFDE UAFD
405–608A
Y1
900–1210A
Y2
AD
Y1
Y2
AD
N/A
N/A
N/A
190–270
032
320
79.8
N/A
49.1
N/A
94.9
64.2
N/A
230–320
050
320
94.1
N/A
57.5
N/A
101.2
64.6
N/A
N/A
N/A
N/A
300–420
050
500
92.5
N/A
55.9
N/A
101.2
64.6
N/A
N/A
N/A
N/A
360–500
080
500
(a)
(a)
(a)
(a)
110.6
77.0
N/A
N/A
N/A
N/A
300–450
050/080
500
(a)
(a)
(a)
(a)
111.5
70.63
N/A
N/A
N/A
N/A
050
480
92.7
N/A
56.1
N/A
101.2
64.6
N/A
N/A
N/A
N/A
050/080
480
(a)
(a)
(a)
(a)
111.5
70.63
N/A
N/A
N/A
N/A
080
480
(a)
(a)
(a)
(a)
110.6
77.0
N/A
N/A
N/A
N/A
080
125.8
92.2
7.0
133.3
99.8
4.8
350–570
620–870
650–910
CVHF
870
(a)
(a)
(a)
(a)
080/142
870
(a)
(a)
(a)
(a)
140.0
81.75
N/A
147.0
88.8
5.8
142
870
(a)
(a)
(a)
(a)
139.9
77.5
N/A
144.0
91.0
4.6
080
910
(a)
(a)
(a)
(a)
119.3
85.7
N/A
126.8
93.3
4.8
080/142
910
(a)
(a)
(a)
(a)
132.7
75.33
N/A
146.2
88.8
5.8
142
910
(a)
(a)
(a)
(a)
130.4
77.5
N/A
144.0
91.0
4.6
080/142
1300
(a)
(a)
(a)
(a)
140.0
81.75
N/A
147.0
88.8
6.3
(a)
(a)
(a)
N/A
146.0
91.0
4.6
1300
(a)
139.9
77.5
142/210
1300
(a)
(a)
(a)
(a)
147.9
83.6
3.5
154.9
90.6
5.6
210
1300
(a)
(a)
(a)
(a)
N/A
N/A
N/A
152.4
95.9
3.9
250
1300
140.7
(b)
80.2
(a)
N/A
N/A
N/A
160.0
99.5
3.1
142/210
1720
(a)
(a)
(a)
(a)
N/A
N/A
N/A
155.0
90.7
5.6
210
1720
(a)
(a)
(a)
(a)
N/A
N/A
N/A
152.4
95.9
3.9
250
1720
140.7
(a)
80.2
(a)
N/A
N/A
N/A
160.0
99.5
3.1
050
565
93.3
N/A
56.6
N/A
N/A
N/A
N/A
N/A
N/A
N/A
080
565
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
050/080
565
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
080
780
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
080/142
780
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
142
780
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
080/142
920
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
142
920
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
142/210
920
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
(a)
(a)
(a)
142
1070–1300
1470–1720
480–565
670–780
CVHG
920–1067
920
(a)
N/A
N/A
N/A
N/A
N/A
N/A
080/142
1100
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
142
1100
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
142/210
1100
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
210
1100
(a)
(a)
(a)
(a)
N/A
N/A
N/A
N/A
N/A
N/A
210
1100
Notes:
1.
2.
(a)
(b)
Refer to Table 5, p. 13.
All dimensions are in inches (±0.5 inch).
When indicated, see Note 1 (above).
Does not extend beyond the main unit control panel.
See Table 1, p. 6 through for dimensional data
regarding the following figure.
CVHE-SVN04M-EN
9
Dimensions and Weights
Figure 1. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers
UATR, UPIR, UXL OR SMP
Y1
USID, USTR, OR UACD
Y1
Y3 MOTOR TERMINAL BOX (NOT SHOWN)
OPTIONAL USID OR USTR
SEE UNIT SUBMITTALS FOR DIMENSIONS
COMPRESSOR MAX WIDTH
OPTIONAL UATR, UPIR, UXL OR SMP
SEE UNIT SUBMITTALS FOR DIMENSIONS
G
OPTIONAL UAFD
SEE UNIT SUBMITTALS FOR DIMENSIONS
SEE NOTE 4
MAIN UNIT CONTROL PANEL
COMPRESSOR
PURGE
CVHE
320
FRCL
PURGE
UAFD DISCONNECT SWITCH TO
ENCLOSURE DOOR LATCHES
V
1.6 405–608A UAFD
1.0 900–1210A UAFD
2.5 318A & 530–636A UAFD
CONDENSER
H
EVAPORATOR
ECONOMIZER
2
AB
AD
MAIN UNIT CONTROL PANEL
4 1.00
2
5
U
UAFD
Y1
Notes:
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A
UAFD are welded on and non-removable. See Table 5, p. 13 for applicable dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer AdaptiView™ display mounting arm in stowed position.
WHEN CONDENSER IS WIDEST
5
A
MAIN CONTROL PANEL
PURGE
OPTIONAL CPTR
MOTOR
SUPPORT
CPTR
LIFTING1.3
LUG
CONDENSER
P
EVAPORATOR
N
SMALLEST
MOTOR
B
X
K
5.7
3.0
J
Z
AA
A
WHEN OIL TANK IS WIDEST
5
CVHF-080 UNIT SHOWN (COOLING ONLY) WITH COMPRESSOR AND ECONOMIZER REMOVED
10
OIL FILTER
CVHE-SVN04M-EN
Dimensions and Weights
See Table 1, p. 6 through for dimensional data for the
following figure.
Figure 2. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers (CVHF-080 shown)
LARGEST MOTOR
MOTOR
REMOVAL SPACE
E
DIMENSIONS: 40.0 W X 26.2 D X 27.0 H
WEIGHT: 1200 LBS MAX
R
MOTOR
S
OPTIONAL
UATR OR UPIR
REDUCED VOLTAGE
ENCLOSURE
T
MAX OD
LARGEST
MOTOR
F
COMPRESSOR
.100
MAIN UNIT
CONTROL PANEL
OPTIONAL
CPTR
C
CVHF-080 UNIT SHOWN (COOLING ONLY)
SHORT SHELL
LONG SHELL
Notes:
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A
UAFD are welded on and non-removable. See Table 5, p. 13 for application dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer Adaptiview™ display mounting arm in stowed position.
WHEN CONDENSER IS WIDEST
M
UATR, UPIR, UXL OR SMP
Y2
SUPPORTS FOR OPTIONAL UNIT MOUNTED UATR
OR UPIR REDUCED VOLTAGE ENCLOSURE
(ENCLOSURE NOT SHOWN)
OPTIONAL USID OR USTR
SEE UNIT SUBMITTALS FOR DIMENSIONS
USID, USTR, OR UACD
Y2
MAIN UNIT CONTROL PANEL
OPTIONAL FRCL CONNECTION
5
L
OPTIONAL UATR, UPIR, UXL OR SMP
SEE UNIT SUBMITTALS FOR DIMENSIONS
OPTIONAL UAFD
SEE UNIT SUBMITTALS FOR DIMENSIONS
PURGE
MAIN UNIT CONTROL PANEL
MOTOR SUPPORT
CONDENSER
UAFD DISCONNECT SWITCH TO
ENCLOSURE DOOR LATCHES
1.6 405-608A UAFD
1.0 900-1210A UAFD
2.5 339A & 539-677A UAFD
W
EVAPORATOR
2
AD
AC
M
WHEN OIL TANK IS WIDEST
2
UAFD
Y2
OIL FILTER
CVHE-SVN04M-EN
11
Dimensions and Weights
Table 4. Motor terminal boxes for CVHE, CVHF, and
CVHG CenTraVac chillers
Low Voltage
Shell
Size
Comp
Size
Motor
Size
Std
INDP
Medium Voltage
Std
Y3
032
320
Table 4. Motor terminal boxes for CVHE, CVHF, and
CVHG CenTraVac chillers (continued)
Low Voltage
Shell
Size
INDP
Comp
Size
360
(a)
N/A
N/A
N/A
400
(a)
N/A
N/A
N/A
440E
N/A
N/A
78.1
N/A
360
(a)
N/A
N/A
N/A
780
910
920
870
1100
1300
870
1300
12
(a)
5000
118.5
118.8
5800
(a)
(a)
120.3
120.6
440E
(a)
(a)
(a)
(a)
5000
(a)
(a)
120.5
120.8
5800
(a)
(a)
122.3
122.6
440E
(a)
N/A
128.2
N/A
N/A
400
N/A
N/A
N/A
440E
(a)
N/A
87.9
N/A
400
(a)
N/A
N/A
N/A
5000
(a)
N/A
129.7
N/A
440E
(a)
N/A
87.7
N/A
5800
(a)
N/A
131.5
N/A
400
(a)
N/A
N/A
N/A
440E
(a)
(a)
128.2
128.3
440E
(a)
N/A
88.5
N/A
5000
(a)
(a)
129.7
129.8
400
(a)
(a)
N/A
N/A
5800
(a)
(a)
131.5
131.6
440E
(a)
(a)
(a)
(a)
6200
N/A
N/A
137.1
N/A
400
(a)
N/A
N/A
N/A
6800
N/A
N/A
137.1
N/A
440E
(a)
N/A
100.8
N/A
5000
(a)
(a)
(a)
(a)
5000
(a)
N/A
102.3
N/A
440E
(a)
N/A
106.9
N/A
5000
(a)
N/A
108.4
N/A
5800
100.2
N/A
110.2
N/A
440E
(a)
(a)
105.9
106.1
5000
(a)
(a)
107.4
107.6
400
(a)
N/A
N/A
N/A
440E
(a)
N/A
97.2
N/A
400
(a)
N/A
N/A
N/A
440E
(a)
N/A
97.2
N/A
400
(a)
N/A
N/A
N/A
440E
(a)
N/A
100.9
N/A
5000
92.4
N/A
102.4
N/A
440E
(a)
N/A
(a)
N/A
5000
(a)
N/A
(a)
N/A
5800
(a)
N/A
122.6
N/A
440E
(a)
(a)
(a)
(a)
5000
(a)
(a)
(a)
121.08
440E
(a)
N/A
(a)
N/A
5000
(a)
N/A
(a)
N/A
5800
(a)
N/A
123.4
N/A
440E
(a)
(a)
(a)
(a)
5000
(a)
(a)
(a)
(a)
5800
(a)
(a)
123.4
123.7
920
1100
1300
142/210
1300
1720
1720
920
1100
210
1300
1720
1300
5800
131.6
131.7
131.6
131.7
5800L
131.6
131.7
131.6
131.7
440E
(a)
N/A
(a)
N/A
5000
(a)
N/A
(a)
N/A
5800
(a)
N/A
127.8
N/A
440E
(a)
(a)
(a)
(a)
5000
(a)
(a)
(a)
(a)
5800
(a)
(a)
127.8
128.1
5000
(a)
(a)
(a)
(a)
5800
(a)
(a)
127.8
128.1
5800L
(a)
(a)
127.8
128.1
440E
(a)
(a)
(a)
(a)
5000
(a)
(a)
(a)
(a)
5800
(a)
(a)
(a)
(a)
5000
(a)
(a)
(a)
(a)
5800
(a)
(a)
(a)
(a)
5800L
(a)
(a)
(a)
(a)
250
1720
910
920
1100
(a)
(a)
N/A
500
080/142
(a)
(a)
N/A
480
780
(a)
(a)
080
565
440E
(a)
565
050/080
INDP
Y3
400
500
870
910
Std
142
050
780
INDP
Medium Voltage
Y3
480
565
Std
Y3
320
480
500
Motor
Size
Note: All dimensions are in inches (±0.5 inch).
(a)
Does not extend beyond the main unit control panel.
CVHE-SVN04M-EN
Dimensions and Weights
Table 5. Unit mounted starters for CVHE, CVHF, and CVHG CenTraVac chillers
USID, USTR
Shell Size
Comp Size
UATR, UPIR, UXL, SMP
USID, USTR
UATR, UPIR, UXL, SMP
Motor Size
Y1
Y2
400
103.3
N/A
69.7
N/A
440E
(a)
100.7
(a)
67.1
400
103.3
N/A
69.7
N/A
440E
(a)
100.7
(a)
67.1
400
103.7
N/A
70.1
N/A
440E
(a)
102.0
(a)
68.4
5000
96.8
103.5
63.2
69.9
480
500
565
080
780
440E
101.3
108.0
67.8
74.4
5000
102.8
108.7
69.3
75.1
5800
104.6
111.3
71.0
77.7
440E
107.8
114.5
74.3
80.9
5000
109.3
116.0
75.8
82.4
870
440E
101.3
108.0
67.8
74.4
5000
102.8
109.5
69.3
75.9
910
400
92.4
N/A
51.59
N/A
440E
94.9
101.6
54.09
60.85
400
92.4
N/A
51.59
N/A
480
050/080
500
440E
94.9
101.6
54.09
60.85
440E
96.2
103.0
54.09
60.85
5000
97.7
104.3
55.59
62.19
440E
(a)
121.2
(a)
63.89
5000
(a)
122.9
(a)
65.54
5800
(a)
124.5
(a)
67.19
440E
(a)
122.2
(a)
63.96
5000
(a)
123.7
(a)
65.46
5800
(a)
125.5
(a)
67.26
440E
(a)
119.1
(a)
66.2
5000
(a)
120.6
(a)
67.7
5800
(a)
122.4
(a)
69.5
440E
(a)
121.1
(a)
66.2
5000
(a)
122.6
(a)
67.7
5800
(a)
124.4
(a)
69.5
440E
(a)
133.6
(a)
69.3
5000
(a)
135.0
(a)
70.7
5800
127.0
136.9
62.6
72.6
565
780, 910
780
080/142
870, 920, 1100, 1300
780, 910, 920
142
870, 1100, 1300
920, 1100, 1300
142/210
1720
CVHE-SVN04M-EN
5000
131.2
141.1
66.8
76.8
5800
127.0
136.9
62.6
72.6
5800L
127.0
136.9
62.6
72.6
13
Dimensions and Weights
Table 5. Unit mounted starters for CVHE, CVHF, and CVHG CenTraVac chillers (continued)
USID, USTR
Shell Size
Comp Size
UATR, UPIR, UXL, SMP
USID, USTR
UATR, UPIR, UXL, SMP
Motor Size
Y1
920, 1100, 1300
Y2
440E
(a)
126.6
(a)
70.1
5000
(a)
128.1
(a)
71.6
5800
(a)
129.9
(a)
73.4
210
5000
127.4
134.1
70.9
77.6
5800
(a)
129.9
(a)
73.4
5800L
(a)
129.9
(a)
73.4
1720
Note: All dimensions are in inches (±0.5 inch).
(a)
Does not extend beyond the main unit control panel.
Duplex Chillers: Models CDHF and CDHG
Table 6. Dimensional data for CDHF and CDHG CenTraVac chillers
Model
CDHF
CDHG
CDHF
NTON
1500–2000
(2-Comp)
2170 & 2550
(2-Comp)
1250–1750
(2-Comp)
2250
(2-Comp)
2250
(2-Comp)
3000
(2-Comp)
3500
(2-Comp)
Shell
Size
A
B
C
D
E
F
G
H
J
K
L
M
N
2100
107.4
-0.2
108.2
66.6
78.5
54.3
116.0
110.9
50.2
81.0
68.9
50.5
94.2
2500
120.9
0.5
121.6
73.2
81.8
59.7
120.6
116.4
54.5
87.6
76.9
56.8
97.8
2100
107.4
-0.2
108.2
66.6
95.0
54.3
116.0
110.9
50.2
81.3
68.9
50.5
94.2
2100
110.5
2.7
111.3
73.2
94.2
59.7
116.0
110.9
50.5
74.7
71.9
52.4
93.8
2500
120.9
0.5
121.6
73.2
94.2
59.7
120.6
116.4
54.5
79.7
76.9
56.8
94.6
250M
120.9
0.5
121.6
76.3
92.3
63.1
120.6
116.4
54.5
84.3
76.9
56.8
96.8
250X
120.9
0.5
121.6
76.3
92.3
63.1
120.6
116.4
54.5
84.3
76.9
56.8
96.8
Table 7. Dimensional data for CDHF and CDHG CenTraVac chillers
Model
CDHF
CDHG
CDHF
14
NTON
1500–2000
(2-Comp)
2170 & 2550
(2-Comp)
1250–1750
(2-Comp)
2250
(2-Comp)
2250
(2-Comp)
3000
(2-Comp)
3500
(2-Comp)
Shell
Size
P
2100
86.9
51.3
45.0
28.5
124.7
2500
90.9
57.5
46.0
36.8
2100
86.9
51.3
45.0
2100
86.9
53.2
2500
90.6
250M
250X
R
S
T
U
V
AFD 900–
1210A
UAFD Low Mount Control Panel
W
X
Z
AA
BB
CC
DD
EE
132.8
152.4
24.3
135.5
118.2
10.6
119.0
9.2
79.7
137.2
139.3
160.0
20.2
147.2
130.9
10.5
131.6
135.
86.9
32.4
124.7
132.8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
46.0
36.8
127.7
135.4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
57.5
46.0
36.8
137.2
139.3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
90.9
57.5
37.0
33.3
137.2
141.3
160.0
20.2
147.2
130.9
10.5
131.6
13.5
86.9
90.9
57.5
37.0
33.3
137.2
141.3
160.0
20.2
147.2
130.9
10.5
131.6
13.5
86.9
CVHE-SVN04M-EN
Dimensions and Weights
Table 8. Motor terminal boxes and unit mounted starters for CDHF and CDHG CenTraVac chillers
Shell Size
Comp Size
Motor Size
Y1 USTR, USID
Y2 UATR, UPIR, UXL
440E
9.7
11.4
Y3 LV Motor Terminal Box Y3 MV Motor Terminal Box
-10.2
-0.2
091
5000
9.7
12.9
-8.7
1.3
440E
9.7
11.4
-10.2
-0.2
5000
9.7
12.9
-8.7
1.3
440E
6.8
11.8
-13.1
-3.1
5000
6.8
11.8
-11.6
-1.6
5800
6.8
11.8
-9.8
0.2
440E
3.6
0.5
-21.1
-11.1
5000
3.6
2.0
-19.6
-9.6
5800
3.6
3.8
-17.8
-7.8
440E
3.6
5.5
-21.1
-11.1
5000
3.6
7.0
-19.6
-9.6
078
2100
092
1100
130
2500
092
110
250M
250X
147
172
5800
3.6
8.8
-17.8
-7.8
5000
3.6
1.9
-13.6
-13.6
5800
3.6
3.7
-7.9
-7.9
5800L
3.6
3.7
-7.9
-7.9
5000
3.6
1.9
-13.6
-13.6
5800
3.6
3.7
-7.9
-7.9
5800L
3.6
3.7
-7.9
-7.9
Data for the following figure is found in Table 6, p. 14
and Table 7, p. 14.
CVHE-SVN04M-EN
15
Dimensions and Weights
Figure 3. Assembly for CDHF and CDHG CenTraVac chillers (CDHF shown)
U
MAIN UNIT CONTROL PANEL
OPTIONAL UNIT-MOUNTED
REDUCED-VOLTAGE STARTERS
Y2 (UATR, UPIR, & UXL STARTERS)
Y3 (MOTOR TERMINAL BOX, NOT SHOWN)
D
Y1 (USTR & USID STARTERS)
COMPRESSOR
AFD
CONTROL PANEL
PURGE
1.0 (90D–1210A AFD)
AFD DISCONNECT SWITCH TO
ENCLOSURE DOOR LATCHES
V
G
H
CONDENSER
EVAPORATOR
K
ECONOMIZER
CONTROL PANEL
AFD LOCATION ONLY
X
Z
W
NOTES:
ADD 1.5” FOR DISTANCE TO TRACER ADAPTIVIEW ™ DISPLAY MOUNTING ARM IN STOWED POSITION.
ADD 2.2” FOR DISTANCE TO TRACER ADAPTIVIEW DISPLAY MOUNTING ARM IN STOWED POSITION (AFD UNITS).
BRACKETS ARE WELDED TO EVAPORATOR ON 900–1210A AFD. SUPPORTS CAN BE UNBOLTED FROM BRACKETS.
SUPPORTS FOR THE
OPTIONAL UNIT-MOUNTED
REDUCED-VOLTAGE STARTER
(AUTOTRANSFORMER OR
PRIMARY REACTOR) ENCLOSURE
(ENCLOSURE NOT SHOWN)
R
M
PURGE
L
MAIN UNIT
CONTROL PANEL
CONTROL PANEL
CONDENSER
EVAPORATOR
B
BB
EE
CONTROL PANEL
AFD LOCATION ONLY
SHELL SEPARATION DIMENSIONS (INCHES)
Data for the following figure is found in Table 6, p. 14
and Table 7, p. 14.
16
CVHE-SVN04M-EN
Dimensions and Weights
Figure 4. Assembly for CDHF and CDHG CenTraVac chillers (CDHF shown)
OPTIONAL
UNIT-MOUNTED
MEDIUM (REDUCED)
VOLTAGE
AUTOTRANSFORMER
OR PRIMARY
REACTOR STARTER
ENCLOSURE IS
40.0 X 26.2 X 27.0
MAX. WEIGHT IS
1200 LB EACH
E
MOTOR
REMOVAL
SPACE
LARGEST MOTOR
S
MOTOR
MOTOR
ØT
MAX OD
LARGEST MOTOR
F
CDHF UNIT SHOWN (COOLING ONLY)
CHILLER DIMENSIONS (INCHES)
NOTES:
ADD 1.5” FOR DISTANCE TO TRACER ADAPTIVIEW ™ DISPLAY MOUNTING ARM IN STOWED POSITION.
ADD 2.2” FOR DISTANCE TO TRACER ADAPTIVIEW DISPLAY MOUNTING ARM IN STOWED POSITION (AFD UNITS)
BRACKETS ARE WELDED TO EVAPORATOR ON 900–1210A AFD. SUPPORTS CAN BE UNBOLTED FROM BRACKETS.
C
MAIN UNIT CONTROL PANEL
A
MAIN UNIT CONTROL PANEL
PURGE
PURGE
MOTOR
SUPPORT
CONTROL PANEL
CONTROL PANEL
SUPPORTS FOR
OPTIONAL
UNIT-MOUNTED
REDUCED-VOLTAGE
STARTERS
N
P
EVAPORATOR
CONDENSER
EVAPORATOR
CONDENSER
J
DD
CC
CHILLER DIMENSIONS (INCHES)
W/REDUCED-VOLTAGE STARTER OPTION
CVHE-SVN04M-EN
CONTROL PANEL
AFD LOCATION
ONLY
AA
CONTROL PANEL
AFD LOCATION ONLY
RIGHT-HAND VIEW (INCHES)
17
Dimensions and Weights
Weights
Single Compressor and Duplex Chillers: Models CVHE, CVHF, CVHG CDHF, and CDHG
Table 9. Compressor and motor weights
Compressor and Motor
Weight
Motor Weight
Model
CPKW(a)
NTON
Volts
Hz
lb
kg
lb
kg
190–270
242
6600
50
2558
1160
7294
3308
230–320
287
4160
60
2530
1147
7266
3295
300–420
379
6600
50
2767
1255
8185
3712
360–500
453
6600
60
3385
1535
8803
3992
350–485
453
6600
60
3385
1535
8013
3634
350–570
588
480
60
2803
1271
7431
3370
620–870
957
2300
60
3862
1751
9900
4490
650–910
957
2300
60
3862
1751
9900
4490
1060–1280
1228
4160
60
4559
2067
10597
4806
1070–1300
1228
4160
60
4559
2067
10714
4859
1470–1720
1340
2400
60
5196
2356
13932
6319
480–565
489
6600
50
3794
1720
10000
4535
CVHE
CVHF
CVHG
CDHF(b)
670–780
621
6600
50
4685
2125
11311
5130
920–1067
621
6600
50
4685
2125
12151
5511
1500–2000
745
460
60
3460
1569
9498
4308
2100–2500
1062
460
60
4296
1948
10334
4687
3500
1340
2400
60
5196
2356
13911
6309
1250–1750
621
6600
50
4685
2125
11311
5130
2150
621
6600
50
4685
2125
12151
5511
CDHG(b)
Note: All weights are nominal and ±10%.
(a)
(b)
Heaviest motor used; does not include the weight of the suction elbow.
For Duplex™ chillers, weights shown are for individual components; multiply by two for total component weights (for Duplex chillers only).
Table 10.
Component weights
Suction Elbow
Purge
Control Panel
lb
kg
119
54
050
119
080
119
050
080
Model
Evap Shell Size
CVHE
032
CVHE
CVHG
CVHF
(a)
Oil Tank
lb
kg
140
64
54
140
54
140
119
54
119
54
Economizer
without Free
Cooling
Economizer
with Free
Cooling
lb
kg
lb
kg
lb
kg
lb
kg
350
159
279
127
404
183
564
256
64
350
159
280
127
635
288
885
401
64
350
159
519
235
976
443
1296
588
140
64
350
159
280
127
420
191
670
304
140
64
350
159
519
135
735
333
1055
479
142/210/250
119
54
140
64
350
159
722
327
878
398
1348
611
CVHG
142/210
119
54
140
64
350
159
722
327
1433
650
1903
863
CDHF(b)
210/250D/250M/250X
119
54
140
64
350
159
683
310
878
398
1348
611
CDHG
210/250
119
54
140
64
350
159
1350
612
1433
650
1903
863
Note: All weights are nominal and ±10%.
(a)
(b)
18
Suction elbow weights include flanges and assume largest compressor available for that size.
For Duplex chillers, weights shown are for individual components; multiply by two for total component weights (for Duplex chillers only)
CVHE-SVN04M-EN
Dimensions and Weights
Table 11.
Evaporator and condenser bundle weights
Evaporator
Model
Shell Size
Bundle
Size(a)
032S
320
Shell(b)
Condenser
Waterbox(c)
Shell(d)
Waterbox(c)
lb
kg
lb
kg
lb
kg
lb
kg
2778
1260
653
296
2458
1115
644
292
CVHE
CVHE
CVHF
CVHG
CDHF
CDHG
032L
320
3483
1579
653
296
3006
1363
644
292
050S
700
4897
2221
1061
481
3526(e)
1599
1328
602
050L
700
5984
2714
1061
481
4436(e)
2012
1328
602
080S
1400
7884
3283
2490
1129
5280
2394
2565
1164
080L
1400
9653
4066
2490
1129
6776
3073
2565
1164
142M
1420
11036
5005
3701
1679
N/A
N/A
5330
2418
142L
1420
11938
5414
3701
1679
10995
4987
5330
2418
142E
1420
12921
5860
3701
1679
N/A
N/A
5330
2418
210L
2100
14755
6692
6403
2904
14154
6420
7319
3320
250
2500
20068
9102
8343
3784
17200
7801
9144
4148
210D
2100
22437
10177
8382(f)
3802(f)
22635
10267
8928(f)
4050(f)
250D
2500
24610
11162
10954(f)
4969(f)
25853
11726
11442(g)
5190(f)
4969(f)
29817
13524
11442(f)
5190(f)
4969(f)
33486
15188
11442(f)
5190(f)
250M
2500
28679
13008
10954(f)
250X
2500
31902
14470
10954(f)
Note: All weights are nominal and ±10%.
(a)
(b)
(c)
(d)
(e)
(f)
Bundle weights are for the maximum bundle size for chiller family with TECU.035 tubes.
Evaporator shell weight includes: Evaporator + Control Panel + Legs; waterbox weight is NOT included.
Based on two-pass marine, 300 lb (136 kg); includes supply and return.
Condenser shell weight includes: Condenser + Oil Tank + Purge + Legs; waterbox weight is NOT included.
Condenser bundle is a 500.
Based on 1-pass marine, 300 lb (136 kg); includes supply and return.
Table 12.
Unit-mounted starters/Adaptive Frequency™
™ drives
lb
kg
Wye Delta
557
252
Solid State
557
252
Low Voltage (less than 600 volts)
405 amp
1680
762
608 amp
1680
762
900 amp
3000
1360
1210 amp
3000
1360
Adaptive Frequency Drive (less than 600 volts)
Medium Voltage (2300–6600 volts)
Across the line
557
252
Primary Reactor
1586
719
Autotransformer
1639
743
Note: All weights are nominal and ±10%.
CVHE-SVN04M-EN
19
Disassembly
Remove Nitrogen Charge
WARNING
Refrigerant May Be Under Positive
Pressure!
Failure to follow instructions below could result in
an explosion which could result in death or
serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
Introduction
The disassembly and reassembly procedures described
in this manual should be performed only on chillers
that have been ordered with this shell option. The
process is to be initiated by experienced service
technicians. Contact your local Trane Service office for
assistance if required.
This section discusses a typical disassembly process.
Proper lifting techniques vary based on mechanical
room layout.
•
It is the responsibility of the person(s) performing
the work to be properly trained in the safe practice
of rigging, lifting, securing, and fastening the
components involved.
•
It is the responsibility of the person(s) providing
and using the rigging and lifting devices to inspect
these devices to ensure they are free from defect
and are rated to meet or exceed the published
weights.
•
Always use rigging and lifting devices in
accordance with the applicable instructions for such
devices.
NOTICE
Equipment Damage!
Mixing refrigerants or oils could result in
equipment damage including bearing damage,
introduction of acids into the chiller, or continuous
purge pump-out in high-head/high ambient
applications.
CenTraVac chillers are manufactured with
different refrigerant/oil systems: 1) chillers using
R-123 refrigerant and OIL00022 compressor oil,
and 2) chillers using R-514A refrigerant and
OIL00334/OIL00335 compressor oil.
Verify proper refrigerant and oil for your chiller
and do NOT mix refrigerants or oils!
This Installation Guide applies to CenTraVac™ chillers
with two different refrigerant and oil systems:
•
R-123 and OIL00022
•
R-514A and OIL00334/OIL00335
I m p o r t a n t : Verify proper refrigerant and oil for your
chiller before proceeding!
N o t e : This manual applies to model CDHF, CDHG,
CVHE, CVHF, and CenTraVac chillers.
I m p o r t a n t : Remove the nitrogen charge from the
chiller vessel before starting any
disassembly procedures.
N o t e : Additional gaskets and O-rings are shipped with
the chiller when compressor doweling and/or
separable shells are selected.
WARNING
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or
serious injury, and equipment or property-only
damage.
Ensure that all the lifting equipment used is
properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks,
and shackles used to lift the unit must be capable
of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
NOTICE
Equipment Damage!
I m p o r t a n t : New units that have been factory run-tested
contain residual refrigerant; vent discharge
outdoors.
Failure to remove the strain relief with the sensor
could result in equipment damage.
Do NOT attempt to pull sensor bulb through the
strain relief; always remove the entire strain relief
with the sensor.
Check to make sure there is a positive pressure holding
charge.
Wiring Disassembly
N o t e : New units ship with a 5 psig (34.5 kPag) dry
nitrogen holding charge at nominal 72°F (22°C).
Before separating shells, remove the purge, the
compressor, and the various unit mounted sensors
(frame LLIDs) as indicated. If possible, the best method
20
CVHE-SVN04M-EN
Disassembly
is to remove the sensor and carefully coil the wire after
labeling the device and its location to aid in
reinstallation. All sensors connect to the buss wiring
with a universal plug. This allows easy disconnection
and reconnection of the sensors.
Reassemble the purge unit in reverse order when the
process is complete.
Figure 5. Example purge unit
Purge Unit Removal
WARNING
Refrigerant May Be Under Positive
Pressure!
Failure to follow instructions below could result in
an explosion which could result in death or
serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
Figure 6. Purge unit detail
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
For additional information regarding the safe
discharge of capacitors, see PROD-SVB06*-EN.
N o t e : Purge unit may appear slightly different than
example shown here.
To remove the purge assembly from the top of the
condenser:
1. Isolate the purge unit from the condenser shell by
closing the vapor and liquid line valves.
2. Disconnect and mark all piping and wiring attached
to the purge unit. Sand all paint off at points and
use a tubing cutter where cuts are to be made. See
Figure 5, p. 21, and Figure 6, p. 21.
3. Remove the fasteners connecting the purge unit
base to its mounting bracket.
4. Two people will be needed to lift purge unit clear of
the chiller. Refer to Table 10, p. 18 for purge unit
weight. Store the purge unit in a clean dry area.
CVHE-SVN04M-EN
21
Disassembly
Compressor Motor Assembly
Removal
Figure 9. Compressor doweling on condenser
discharge flange (these are standard on all CenTraVac
chillers)
NOTICE
Compressor Damage!
Failure to follow instructions below could cause
the internal components to shift which could
result in serious compressor damage upon
starting the unit.
The compressor motor assembly must not be
removed from the chiller unless special doweling
has been installed at the factory. Doweling must
be installed to prevent the interstage casings from
shifting. If the compressor/motor assembly is
lifted without doweling installed, the internal
alignment may shift. It would then be necessary to
disassemble and then reassemble the compressor
making sure that all internal clearances and
specifications are proper. If doweling is not
factory installed, and it is necessary to install
doweling, contact the local Trane Service
Company. The compressor discharge flange and
mounting foot are also doweled at the factory to
provide proper alignment during reassembly.
Figure 7, p. 22 through Figure 10, p. 22 show factoryinstalled compressor doweling. If components are not
factory doweled, doweling must be installed before
proceeding. Contact the local Trane Service Company.
Figure 7. Compressor dowelings on casings
1. Disconnect the inlet vane linkage.
a. Disconnect the rod end bearings connecting the
inlet vane operator levers to the guide vane
links as in Figure 10, p. 22 and Figure 11, p. 23.
Leave the rod end bearing connecting the guide
vane links to the main drive levers attached.
N o t e : Do not rotate the rod end bearings on the
shaft as this will alter the inlet guide vane
operations and compressor performance.
b. Remove the cotter pin securing the vane
operator stud to the vane drive and slide the
stud out of the main drive. See Figure 12, p. 23.
c. Remove the hex head bolts securing the vane
drive support assemblies to the compressor
castings and remove the main drive and inlet
vane levers from the compressor as a unit. See
Figure 12, p. 23.
d. Remove the hex head bolts securing the vane
drive support assemblies to the compressor
castings and remove the main drive and inlet
vane levers from the compressor as a unit. See
Figure 12, p. 23.
Figure 10.
Vane actuator level on suction cover
Figure 8. Compressor doweling on evaporator foot
(these are standard on all CenTraVac™
™ chillers)
22
CVHE-SVN04M-EN
Disassembly
Figure 11.
Vane actuator level on interstage
reassembling the chiller. Cap open lines to prevent
entry of foreign material.
N o t e : Cover all open connections to avoid
prolonged exposure of oil to humid air.
Remove oil if a chiller is kept in a
disassembled condition for an extended time.
Figure 12.
Figure 13.
vent lines
Lubrication system supply, drain, and
Figure 14.
Lubrication system motor cooling lines
Vane actuator operator mechanism
WARNING
Refrigerant May Be Under Positive
Pressure!
Failure to follow instructions below could
result in an explosion which could result in
death or serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
2. Disconnect all external vent lines, motor cooling
supply and drain lines, and oil supply and drain
lines which are connected to the compressor and
compressor motor. Sand all paint off the points
where cuts are to be made. Use a tubing cutter to
ensure that cuts are smooth and square. Figure 13,
p. 23 and Figure 14, p. 23 illustrate these lines.
Couplings will be used to reconnect the lines when
CVHE-SVN04M-EN
3. Remove the control panel if necessary. Also,
disconnect and remove the unit mounted starter, if
so equipped. See “Control Panel Removal,” p. 27
for instructions.
23
Disassembly
Figure 15. Lifting clevis on the suction elbow
lifting tab (three-piece elbow style)
4. Remove the economizer vent pipe flange bolts at
the compressor connection. See “Economizer
Removal,” p. 25 for instructions.
WARNING
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or
serious injury, and equipment or property-only
damage.
Ensure that all the lifting equipment used is
properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks,
and shackles used to lift the unit must be capable
of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
5. Only Trane Service Agencies have access to the
certified lifting plates to allow safe compressor/
motor assembly removal. Before removing the
compressor/motor assembly, consult with a rigging
specialist. Employ rigging specialist procedures
when removing the compressor motor/assembly.
WARNING
Improper Unit Lift!
Using the elbow lifting tab to lift chiller could
result in chiller dropping which could result in
death, serious injury, or equipment damage.
•
•
Do NOT lift chiller using elbow lifting tab.
Elbow lifting tab and approved clevis are
used ONLY when removing elbow from
chiller.
Do not lift chiller utilizing waterbox lifting
lug. Waterbox lifting lug is to be used only
for removing waterbox from chiller.
6. Remove the suction elbow.
There are two styles of suction elbows, a 90° elbow
and a three-piece elbow, that can be found in the
disassembly process.
N o t e : Apply oil on steel compressor internal parts
for rust prevention. Only a thin layer of oil is
necessary. Avoid over applying. Use POE
break-in oil.
a. Use a sling to support the 90° elbow style
suction elbow. Apply slight lifting pressure.
b. Three-piece suction elbows have a lifting tab.
You will need a lifting clevis to remove the
elbow. A Crosby screw pin shackle, model S209, stock number 1018482 with a 5/8-in. pin is
acceptable as shown in Figure 15, p. 24.
24
c. Remove the bolts from the control mounting
bracket on the back of the control panel.
d. Remove the suction elbow bolts at the
compressor and evaporator connections..
e. Lift the suction elbow from the chiller being
careful to avoid damage to flange surfaces.
f.
Install protective covers on the evaporator and
compressor connections. Plastic secured with
duct tape makes an adequate cover if no heavy
objects are set on the openings.
7. Support the compressor/motor assembly as
indicated by the rigging specialist (see Step 5). Do
not lift the assembly; instead support the assembly
to prevent it from slipping as the compressor foot
and discharge connection flange bolts are removed.
NOTICE
Equipment Damage!
Failure to follow instructions below could result in
equipment damage.
The cast iron foot of the compressor and the
discharge flange of the volute can be broken easily
if rough handling of the compressor/motor
assembly is allowed. Take great care to prevent
this breakage when removing the compressor/
motor assembly and setting it down, or when
moving it laterally on the floor (e.g., on rollers,
etc). Take extra care to gently sit the compressor/
motor assembly down and avoid letting it swing or
drop into an obstruction while lifting or moving it.
CVHE-SVN04M-EN
Disassembly
NOTICE
Figure 16.
Motor support detail
Equipment Damage!
Properly support the compressor casting foot to
avoid prevent breakage and equipment damage.
N o t e : Plan ahead where the compressor will be
secured. Build a suitable plant form to support
the assembly before the lift. Gently set
compressor onto prefabricated pre-formatted
support. Use care not to damage the cast
compressor foot (see foot in Figure 8, p. 22).
Similarly, avoid damage to the discharge volute
flange (see discharge flange in Figure 9, p. 22).
8. Remove the compressor/motor assembly. Remove
the locating dowel pins from the compressor foot
and discharge flange connections as shown in
Figure 8, p. 22 and Figure 9, p. 22. To remove the
dowel pin, first remove the nut on the dowel pin,
place a bushing on the pin, and then reinstall the
nut. As the nut is tightened, the dowel pin should
pull out of its hole; at this point, remove the
compressor/motor assembly.
Compressor Motor Mount
Disassembly
If additional vertical clearance is required, the height of
the compressor motor mount can be reduced. Use the
following procedure:
1. Before cutting off the motor mount, first fabricate a
1/4-inch steel backing plate.
a. Cut the backing plate to shape and clamp it to
the motor mount.
b. Drill four 1/4-inch holes through the motor
mount and the backing plate as shown in Figure
16, p. 25. These holes with bolts or roll pins
installed will be used to align the components
during reassembly.
Compressor Motor
1/4-inch Steel
Backing Plate
Cut Here
Alignment
Bolt Holes
Economizer Removal
WARNING
Refrigerant May Be Under Positive
Pressure!
Failure to follow instructions below could result in
an explosion which could result in death or
serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
WARNING
c. Remove the backing plate.
2. Using an oxyacetylene torch, cut the mount as
shown in Figure 16, p. 25.
During reassembly, use the backing plate with bolts or
roll pins to locate the pieces properly. After the pieces
are located, Trane recommends welding the mount and
backing plate in place.
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or
serious injury, and equipment or property-only
damage.
Ensure that all the lifting equipment used is
properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks,
and shackles used to lift the unit must be capable
of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
1. Support the weight of the economizer with a
movable floor jack. Do not lift the economizer;
simply support it. Economizer weights are provided
in Table 10, p. 18; also see submittal. It is
CVHE-SVN04M-EN
25
Disassembly
recommended that larger size economizers be lifted
using overhead rigging.
economizer may tend to rotate off the jack towards
the chiller. Be prepared to offset the rotation.
2. If the unit has insulation, remove the insulation and
loosen the bolts on the condenser liquid line flange.
See Figure 17. Do not remove the bolts at this time.
Cut the motor cooling drain line(s) if present and
cut entering and leaving 5/8 inch OD copper oil
cooler lines. Refer to Figure 17, p. 26.
9. Remove the economizer orifice plates and mark
them so they are reinstalled in their original
position. The orifice with the greatest number of
holes is to be located between the economizer and
the evaporator. The orifice with fewer holes is to be
located between the condenser and economizer.
Figure 17.
10. Move the economizer away from the chiller and set
it on a pallet. Cover all openings to prevent the
entry of foreign material into the economizer,
condenser and compressor.
Condenser liquid line flange
11. Use the reverse order to reassemble the
economizer on the chiller. Be sure to install new
gaskets at the appropriate joints.
12. Torque all bolts to specifications. Consult with your
Trane service group for specific torques for your
economizer design.
Tracer AdaptiView Display Arm
Removal
WARNING
Hazardous Voltage w/Capacitors!
NOTICE
Angle Valves Damage!
Rigging, handling, and placing chiller components
on uneven surfaces can cause damage to angle
valves.
Remove angle valves to avoid breakage during
handling if it is necessary to remove the
economizer.
N o t e : Take care to avoid damage to angle valves
during handling and transfer of economizer.
3. Loosen the bolts on the evaporator liquid line
flange. This connection is near the bottom of the
evaporator. See Figure 17, p. 26. Do not remove the
bolts at this time.
4. Economizers are connected to the condenser shell
via a bolted flange. See Figure 22, p. 29. Remove
the bolts at this flanged connection.
5. Loosen the economizer vent pipe bolts that secure
the vent pipes to the compressor interstage
castings (unless the compressor has already been
removed to gain vertical clearance.)
6. Secure economizer with appropriate rigging.
7. Remove the bolts from the condenser and
evaporator liquid line connection flanges. Adjust
the floor jack as necessary to support the weight of
the economizer.
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
For additional information regarding the safe
discharge of capacitors, see PROD-SVB06*-EN.
Use the following steps to remove the Tracer
AdaptiView™ display arm if additional clearance is
required.
1. Cut tie wraps holding wires inside of control arm
and remove wires from arm.
2. Remove 3-3/8-in. bolts from the angle bracket
attached to the control panel mounting bracket.
3. Use the reverse order to re-attach the arm to the
control panel mounting bracket.
8. Remove the economizer vent pipe flange bolts to
loosen the economizer. When the bolts are free,
back the economizer away from the chiller. The
26
CVHE-SVN04M-EN
Disassembly
Control Panel Removal
Unit-mounted Starter Removal
WARNING
Additional horizontal and vertical clearances may be
obtained by removing the unit-mounted starter on
chillers so equipped. See Figure 19, p. 27 and Figure
20, p. 27.
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
For additional information regarding the safe
discharge of capacitors, see PROD-SVB06*-EN.
N o t e : Unless otherwise stated, lift only vertically on
starter-provided devices. Refer to all starterrelated manuals prior to lifting. If needed, use a
spreader bar to avoid angles in chains and
reduce required lifting height clearance.
Figure 19.
Unit-mounted starter
Figure 20.
Starter mounting bracket
Use the following steps to remove the control panel if
additional horizontal clearance is required.
1. Mark and disconnect incoming wiring to the control
panel.
2. Remove the bolts from the bottom of the panel
which secure the panel to the lower mounting
bracket.
3. Loosen the bolts on the back of the panel which
secure the panel to the top (suction elbow)
mounting bracket. See Figure 18, p. 27.
Figure 18.
Control panel mounting bracket
4. Two people will be needed to lift the panel clear of
the chiller. Refer to Table 10, p. 18 for control panel
weight. Steady the panel as the top retaining bolts
are removed. Then lift the panel clear. Store the
panel in a clean dry area.
The following procedure assumes the chiller is new
and has never been installed and therefore there is no
electrical power connected to the chiller. If there is
power to the unit, follow proper lockout/tagout
procedures, and any other applicable safety
regulations regarding electric power.
5. Use the reverse order to reassemble the control
panel.
CVHE-SVN04M-EN
27
Disassembly
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
For additional information regarding the safe
discharge of capacitors, see PROD-SVB06*-EN.
1. Mark and disconnect the power wiring at the
compressor motor terminal lugs inside the starter
panel.
2. Mark and disconnect control wiring entering the
starter panel.
3. Remove the bolts securing the bottom of the starter
to the brackets on the evaporator.
4. To move the starter panel away from the chiller, it is
recommended that a fork truck be used. Position
the truck so that it is ready to take up the weight of
the starter panel. The panel is top-heavy and must
be adequately secured before moving. Refer to
Table 12, p. 19 for starter weights.
WARNING
Heavy Objects!
Placing, assembling, and/or suspending more than
one module/subassembly at a time could result in
death, serious injury, or equipment damage.
Always place, assemble, and suspend modules/
subassemblies one at a time.
5. Loosen the bolts which hold the starter to the flange
on the motor. Steady the starter panel as the
retaining bolts are removed because the panel will
tip forward. See Figure 19, p. 27.
Condenser/Evaporator
Disassembly
After the compressor assembly has been removed on
separable shell units, the condenser and evaporator
shells can be taken apart at flanged connections to
reduce the horizontal clearance required for the chiller
installation.
WARNING
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or
serious injury, and equipment or property-only
damage.
Ensure that all the lifting equipment used is
properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks,
and shackles used to lift the unit must be capable
of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
NOTICE
Condenser Legs Damage!
Failure to follow instructions below could result in
condenser legs damage.
Condenser legs are designed for vertical support
only! Additional bracing is required if it is
necessary to move the condenser horizontally.
Contact your local Trane Service agency for
assistance.
N o t e : Brace condenser legs to prevent flexing. Do not
move the condenser horizontally without bracing
legs.
1. Ensure that condenser and evaporator shells are
securely supported on level ground. If not, shim
under the bases.
2. Support the condenser with rigging using the lifting
holes on the tube sheets. See Figure 21, p. 29. Do
not lift the shell, simply support it to avoid slipping
as the bolts are removed from the connecting
flange.
6. Support the weight of the starter panel with the fork
truck and carefully remove the starter panel from
the chiller. Store the panel in a clean dry area free of
any corrosive agents. When ready, reassemble the
panel on the chiller in reverse order.
28
CVHE-SVN04M-EN
Disassembly
Figure 21.
Separable shell unit (end view)
Disassembly of Chillers with
Options
Heat Recovery
Use the following steps when disassembling chillers
with auxiliary or heat recovery condenser shells to
reduce the vertical clearance required for the chiller
installation.
WARNING
Refrigerant May Be Under Positive
Pressure!
3. Remove the bolts from the flanges connecting the
evaporator tube sheet and condenser shell support
(see Figure 22, p. 29). Then remove the bolts from
the flanges connecting the shells.
N o t e : Some small shell combinations do not have
flanged connections between shells.
4. Remove the two dowel pins located in the flange on
each end of the shell tube sheet connections and lift
the condenser clear of the evaporator.
5. Reassemble the evaporator and condenser shells in
the reverse order.
6. Torque all bolts to specifications listed in Table 13,
p. 32.
Figure 22.
Separable shell unit (flange connection)
Failure to follow instructions below could result in
an explosion which could result in death or
serious injury or equipment damage.
System contains refrigerant and may be under
positive pressure; system may also contain oil.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or nonapproved refrigerant additives.
WARNING
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or
serious injury, and equipment or property-only
damage.
Ensure that all the lifting equipment used is
properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks,
and shackles used to lift the unit must be capable
of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same
length. Adjust as necessary for even unit lift.
1. Support the auxiliary or heat recovery condenser
with rigging using the lifting holes on the tube
sheets. Do not lift the shell; simply support it to
avoid slipping as the bolts are removed from the
connecting flanges.
2. Remove the bolts from the flanges on the
interconnecting piping and flanges connecting the
auxiliary heat recovery condenser and condenser
tube sheets.
3. Remove the bolts from the flanges on the
interconnecting piping and the flanges connecting
the shells.
4. Lift the condenser clear of the unit.
5. Reassemble the condenser in the reverse order.
Install new gaskets at the appropriate joints.
6. Torque all bolts to torque specifications listed in
Table 13, p. 32.
CVHE-SVN04M-EN
29
Disassembly
7. Remove and coil up sensors.
Free Cooling
connecting flanges. (Typical rigging for lifting the
suction elbow can be seen in Figure 15, p. 24.
2. Remove the bolts from the flanges.
Use the following steps on free cooling units to reduce
the vertical clearance required for chiller installation.
3. Lift the piping clear of the unit.
1. Support the piping and free cooling valve between
the condenser and suction elbow with rigging
similar to that used for removing the suction elbow.
Do not lift the piping; simply support it to avoid
slipping as the bolts are removed from the
5. Torque all bolts to torque specifications listed in
Table 13, p. 32.
30
4. Reassemble the piping in the reverse order. Install
new gaskets at the appropriate joints.
CVHE-SVN04M-EN
Reassembly
NOTICE
Equipment Damage!
Failure to remove the strain relief with the sensor
could result in equipment damage.
Do NOT attempt to pull sensor bulb through the
strain relief; always remove the entire strain relief
with the sensor.
It is important to remove used O-rings and gaskets and
clean joints before reassembling the compressor with
new O-rings and gaskets. All necessary replacement Orings and gaskets are supplied by the factory when the
compressor doweling or separable shell options are
ordered.
assembly when the suction elbow retaining bolts
are tightened. Support the dial indicators from the
condenser or from a floor stand.
Figure 23.
Suction elbow flange bolts
Set Up Dial
Indicator to Read
Horizontally
Use the following procedure to reattach the
compressor/motor assembly to the chiller.
1. Remove the protective covers on all compressor,
condenser, and evaporator connections. Clean all
mating surfaces using Loctite® “Chisel” cleaner or
CRC® Industrial Gasket Remover. Completely
remove old sealing compound from O-ring
grooves. Use Loctite “N” primer for final surface
preparation.
Set Up Dial Indicator
to Read Vertically
2. Refer to CTV-SB-66F (General Service Bulletin:
CenTraVac O-Ring and Flange Sealant), or the most
recent version, for proper installation of gaskets, ORings, and Loctite sealant. Install a new O-ring on
the compressor discharge connection mating
surfaces. Use Loctite 515 “Gasket Eliminator” to
lubricate the O-ring and provide additional sealing.
This is the only sealing compound recommended
by Trane for use on O-ring joints. To use this
sealing compound, apply a light bead
(approximately 1/8-in. in diameter) to the O-ring
groove, insert the O-ring and then apply a light
bead to the O-ring. Also apply a 1/8-in. bead of
sealing compound between the O-ring groove and
the bolt hole circle. The parts can now be
assembled.
8. Clean the suction elbow flange surfaces and O-ring
grooves per Step 1. For the evaporator to suction
elbow joint, use Loctite 515 per Step 2. For the
suction elbow to compressor joint, use 1/8-in.
GORE-TEX® Joint Sealant placed approximately 1/
8-in. in board of the O-ring groove. This is used in
addition to the O-ring. As an option, Loctite 515
may be used in place of GORE-TEX. However, great
care must be taken to prevent the sealant from
entering the first stage IGV housing. Refer to CTVSB-66F (General Service Bulletin: CenTraVac O-Ring
and Flange Sealant), or the most recent version.
3. Lift the compressor/motor assembly into place.
Insert the bolts in the compressor foot and
discharge flange connections. Before tightening
any of these bolts, reinstall the dowel pins in the
compressor foot and discharge flange.
11. Tighten the retaining bolts only “hand tight”.
Tighten two retaining bolts, 180 degrees apart at
the compressor connection. Then tighten two bolts,
180 degrees apart at the evaporator connection.
Alternate between connections until all retaining
bolts are tight. Monitor the dial indicators to ensure
that there is no more than 0.010 inches of
compressor movement. If there is more movement
than this, loosen all of the bolts, “zero” the dial
indicators and repeat the procedure. Figure 23, p.
31 illustrates the bolt tightening sequence.
4. Tighten the compressor foot and discharge flange
bolts. See Table 13, p. 32 for bolt torque
specifications.
5. Install and tighten the motor mount bolts. See
Table 13, p. 32 for bolt torque specifications.
6. Remove the lifting equipment.
7. Set up dial indicators on the compressor end of the
compressor/motor assembly. See Figure 23, p. 31.
The dial indicators are used to monitor horizontal
and vertical movement of the compressor/motor
CVHE-SVN04M-EN
9. Lift the suction elbow into place using a sling or
chain-fall hoist.
10. Install the suction elbow retaining bolts.
12. Reconnect the economizer vent pipes. Be sure to
clean the mating surfaces and use new gaskets on
the connections. Tighten the flange bolts just
enough so that the gasket material just begins to
extrude from between the flanges.
31
Reassembly
13. Reinstall all other chiller components which were
removed. Reconnect the inlet vane linkages.
14. Torque all bolts to specifications listed in Table 13,
p. 32.
Table 13.
Bolt torques
Non-gasket Joints Bolt Torques
Bolt Size (in)
Torque (ft·lb)
1/2
70
5/8
150
3/4
250
All Other Metal Joints (O-Ring Joins) Shall Use the Following
Torques
Torque (ft·lb)
Bolt Size (in)
Min.
Max
1/4
5
7
5/16
11
15
3/8
22
27
1/2
55
75
5/8
120
165
3/4
200
280
1
400
550
All Joints with Flat Elastomeric Gaskets Shall Use the Following
Bolt Torque
Brazing
WARNING
Explosion Hazard and Deadly Gases!
Failure to follow all proper safe refrigerant
handling practices could result in death or serious
injury.
Never solder, braze or weld on refrigerant lines or
any unit components that are above atmospheric
pressure or where refrigerant may be present.
Always remove refrigerant by following the
guidelines established by the EPA Federal Clean
Air Act or other state or local codes as appropriate.
After refrigerant removal, use dry nitrogen to
bring system back to atmospheric pressure before
opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from
soldering, brazing or welding with refrigerant
vapors present can form highly toxic gases and
extremely corrosive acids.
Except as noted in the following, braze with the
following filler metals:
•
Braze all copper-to-copper joints with A.W.S. BcuP6 filler metal.
•
Braze all copper-to-brass joints with A.W.S. BcuP-6
filler metal using white or black brazing flux.
•
Braze all other joints with A.W.S. Bag-28 filler
metal.
Torque (ft·lb)
Bolt Size (in)
Min.
Max
5/16
8
12
3/8
12
18
1/2
33
50
5/8
70
90
3/4
105
155
15. Reconnect the previously cut compressor/motor oil
supply and return lines and the motor cooling lines
using the factory-supplied couplings.
Bleed dry nitrogen through the lines while brazing to
prevent the formation of oxides which can contaminate
the oil and refrigerant systems.
N o t e : Use silver soldering with 96% Sn-4% Ag (for
example, J.W. Harris Co. Stay Brite®) to replace
brazing when the heat from brazing would be
detrimental to the immediate or nearby parts.
Examples:
1. Joints next to threaded joints in which the copper
or brass threads become too soft and/or Loctite®
loses its sealing capability due to excess heat.
2. Joints next to valves in which the valves cannot be
taken apart or are not recommended for brazing.
Final Installation Procedures
After the chiller has been moved to the equipment
room and reassembled under Trane supervision, leak
testing, and evacuation can be performed by Trane or
under Trane supervision. Upon verification of leak
tightness, installation can proceed for unit piping,
wiring, etc. After installation has been completed, fill
out CTV-ADF001*-EN (CenTraVac™ Installation
Completion Check Sheet and Request for Trane
Service) to schedule the startup; the chiller
32
CVHE-SVN04M-EN
Reassembly
commissioning process can be completed by Trane or
under the supervision of authorized Trane personnel.
N o t e : CTV-ADF001*-EN is also included in the “Forms”
section of CVHE-SVX02*-EN (Installation,
Operation, and Maintenance: CVHE, CVHF, CVHG
Water-Cooled CenTraVac™ Chillers with Tracer
AdaptiView™ Control) and CDHF-SVX01*-EN
(Installation, Operation, and Maintenance: CDHF
and CDHG Water-Cooled CenTraVac™ Chillers
with Tracer AdaptiView™ Control), or the most
recent revisions.
CVHE-SVN04M-EN
For additional information regarding compressor
disassembly and reassembly, refer to CVHE-SB-10B
(General Service Bulletin: Compressor Doweling), or
the most recent version.
33
Notes
34
CVHE-SVN04M-EN
Notes
CVHE-SVN04M-EN
35
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and
Trane® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.
CVHE-SVN04M-EN
10 Jan 2019
Supersedes CVHE-SVN04L-EN
(January 2017)
©2019 Ingersoll Rand

advertisement

Key Features

  • High efficiency with low operating costs
  • Reliable operation with robust construction
  • Precise temperature control for critical applications
  • Environmentally friendly with reduced refrigerant charge
  • Compact design for easy installation and maintenance
  • Advanced controls for remote monitoring and diagnostics

Frequently Answers and Questions

What are the main applications for the Trane CenTraVac CVHE chiller?
The Trane CenTraVac CVHE chiller is ideal for commercial and industrial applications, including data centers, hospitals, and manufacturing facilities where high efficiency, reliability, and precise temperature control are required.
What is the refrigerant used in the Trane CenTraVac CVHE chiller?
The Trane CenTraVac CVHE chiller uses environmentally friendly refrigerants with reduced charges, contributing to a lower environmental impact.
What are the dimensions and weight of the Trane CenTraVac CVHE chiller?
The dimensions and weight of the Trane CenTraVac CVHE chiller vary depending on the specific model and capacity. Please refer to the product specifications for detailed information.

Related manuals

Download PDF

advertisement