Symmetricom TimeSource 3600 User Manual

Add to my manuals
218 Pages

advertisement

Symmetricom TimeSource 3600 User Manual | Manualzz

TimeSource 3600

GPS Primary Reference Source

User’s Guide

Revision J – June 2007

Part Number 097-72060-01

Symmetricom, Inc.

2300 Orchard Parkway

San Jose, CA 95131-1017

U.S.A.

http://www.symmetricom.com

Copyright © 2007 Symmetricom, Inc.

All rights reserved. Printed in U.S.A.

All product names, service marks, trademarks, and registered trademarks used in this document are the property of their respective owners.

FCC Regulatory Notice

This equipment generates, uses, and can radiate radio frequency energy, and if not used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart B of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.

Contents

How to Use This Guide

Purpose of This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Who Should Read This Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Structure of This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Conventions Used in This Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

Warnings, Cautions, Recommendations, and Notes . . . . . . . . . . . . . . . . . . . .18

Related Documents and Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Where to Find Answers to Product and Document Questions . . . . . . . . . . . . .19

What’s New In This Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Chapter 1 Overview of the TimeSource 3600

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Global Positioning System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

Physical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Roof Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Mechanical Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Self-Adhesive Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

Wall Antenna. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

3

Table of Contents

Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

Antenna. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

IF Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

GPS Receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

Local Oscillator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

Clock Extractors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

NTP TimeServer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Network Time Protocol Password Activation . . . . . . . . . . . . . . . . . . . . . .31

BesTime Ensemble Timing Generator . . . . . . . . . . . . . . . . . . . . . . . . . . .31

E1 or Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Eight Mixed E1/T1 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Eight Additional E1 or Analog Outputs (990-72060-02 Systems Only). . .32

TOD Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

IRIG-B TOD Outputs (990-72060-05 Systems Only) . . . . . . . . . . . . . . . .32

1 PPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

10 MHz Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Two ESCIU Outputs (990-72060-04 Systems Only). . . . . . . . . . . . . . . . .33

Alarm Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

Passthrough . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

Alarm Programmability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

Bridging/Holdover Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

Time Figure of Merit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Success Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

Chapter 2 Engineering & Ordering

Antenna Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

Roof Antenna Location and Cabling Guidelines . . . . . . . . . . . . . . . . . . . .43

Roof Antenna Earth Ground Location Guidelines. . . . . . . . . . . . . . . . . . .46

Roof Antenna Cable Choices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46

Window and Wall Antenna Location Guidelines . . . . . . . . . . . . . . . . . . . .47

Window and Wall Antenna Cable Choices . . . . . . . . . . . . . . . . . . . . . . . .48

IRIG-B TOD (990-72060-05 System Only) . . . . . . . . . . . . . . . . . . . . . . . .48

RS-422–to–RS-232 TOD Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

Shelf Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

4

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Table of Contents

Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

Standard System (Two E1 Outputs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

With Eight Additional E1 or 2.048 MHz Outputs . . . . . . . . . . . . . . . . . . . .50

With Two E1 Synchronization Insertion (ESCIU) Ports . . . . . . . . . . . . . .51

With Four IRIG-B TOD Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51

With Eight Mixed E1/T1 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51

Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

Roof Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

Mechanical Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

Self-Adhesive Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53

Wall Antenna. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53

User-Supplied Tools and Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

For Roof Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

For Mechanical Window Antenna Installation . . . . . . . . . . . . . . . . . . . . . .55

For Self-Adhesive Window Antenna Installation . . . . . . . . . . . . . . . . . . . .55

For Wall Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

For Shelf Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

Outputs, Power, and Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56

Chapter 3 Installing the TimeSource 3600

Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

Installing the Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

Installing a Roof Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

installing a Mechanical Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . .63

Installing a Self-Adhesive Window Antenna . . . . . . . . . . . . . . . . . . . . . . .65

Installing a Wall Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68

Installing the Shelf. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73

Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73

Installing Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74

Making Power and Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . .75

Making Frame Ground Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76

Making Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78

GPS Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78

10 MHz Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79

E1 or Analog Synchronization Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .79

1 PPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79

Connecting E1 or Analog Reference Inputs . . . . . . . . . . . . . . . . . . . . . . .80

Module for Additional E1 or Analog Outputs

(990-72060-02 System Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81

Module for IRIG-B TOD Outputs

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

5

Table of Contents

(990-72060-05 System Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82

Module for Mixed E1/T1 Outputs (990-72060-06 System Only) . . . . . . . .83

Module for ESCIU Ports (990-72060-04 System Only) . . . . . . . . . . . . . .83

Cutover Procedures for Out-of-Service Equipment . . . . . . . . . . . . . . . . .84

Cutover Procedures for In-Service Equipment . . . . . . . . . . . . . . . . . . . . .85

Time of Day Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88

Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90

Communication Port 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

Communication Port 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

Craft Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

Alarms Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

Powering Up the TimeSource 3600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

Installing and Using TimeWizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104

Factory-Set Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114

Chapter 4 TL1 Reference

Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118

Command Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118

Response Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119

Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120

Autonomous Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

Report Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

Report Event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

Tasks/Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

6

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Table of Contents

Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125

Activate User. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126

Cancel User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

Copy Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128

Delete Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

Delete User Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131

Edit Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

Edit Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135

Edit Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137

Enter Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .146

Enter User Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147

Initialize Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148

Initialize Register. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .149

Initialize System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150

Operate Alarm Cutoff All . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151

Retrieve Alarm All . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152

Retrieve Alarm Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153

Retrieve Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154

Retrieve Condition All . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157

Retrieve Condition Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158

Retrieve Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159

Retrieve GPS Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .166

Retrieve Header . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .168

Retrieve Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169

Retrieve Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171

Retrieve Performance Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .172

Retrieve Status Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .180

Retrieve User Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181

Set Source Identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182

Chapter 5 Troubleshooting

Troubleshooting with Front Panel Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184

Troubleshooting with Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .187

Replacing Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .192

Returning the TimeSource . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194

Repacking the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194

Equipment Return Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194

User Guide Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

7

Table of Contents

Chapter 6 Specifications

Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .198

Communication and Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199

Time of Day Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202

Input Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .204

Output Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206

Office Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212

Simple Network Time Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

Shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

8

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Figures

1-1 Shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

1-2 Roof Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

1-3 Mechanical Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

1-4 Self-Adhesive Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

1-5 Wall Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

1-6 Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

1-7 Zone of Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

1-8 Two ESCIU Outputs Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

1-9 TimeSource 3600 Passthrough Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

2-1 Antenna Field of View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

2-2 Antenna Location Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

2-3 Sample Rooftop Antenna Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

2-4 Antenna Mask Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

2-5 Rack Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

3-1 Roof Antenna-to-Shelf Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

3-2 Mechanical Window Antenna-to-Shelf Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . 63

3-3 Attaching the Mechanical Window Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3-4 Mechanical Window Antenna Pivot Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3-5 Self-Adhesive Window Antenna-to-Shelf Cabling . . . . . . . . . . . . . . . . . . . . . . . . 66

3-6 Attaching the Self-Adhesive Window Antenna to a Window . . . . . . . . . . . . . . . . 67

3-7 Attaching the IF Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

3-8 Wall Antenna-to-Shelf Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

3-9 Hole Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

3-10 Wall Antenna Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

3-11 Wall Antenna Outdoor Lightning Suppressor Mounting . . . . . . . . . . . . . . . . . . . . 73

3-12 Rack Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

3-13 Options I/O Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

3-14 Connector Panel and Front Panel Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

3-15 Connector Panel Terminal Block Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

3-16 E1 or Analog Output Wire-Wrap Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

3-17 E1 or Analog Input Wire-Wrap Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

3-18 Eight E1 or Analog Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

3-19 IRIG-B TOD Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

3-20 Eight Mixed E1/T1 Outputs Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

3-21 Connector Layout of ESCIU Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3-22 ESCIU Cutover without Jacks (Out-of-Service) . . . . . . . . . . . . . . . . . . . . . . . . . . 85

3-23 ESCIU Cutover with Jacks (In-Service) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

3-24 RS-422–to–RS-232 TOD Converter Mounting Plate . . . . . . . . . . . . . . . . . . . . . . 89

3-25 RS-422–to–RS-232 TOD Converter Connections . . . . . . . . . . . . . . . . . . . . . . . . 89

3-26 Alarm Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

9

List of Figures

4-1 Command Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

4-2 Completed Response Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

4-3 Deny Response Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

4-4 Alarm Conditioning Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

5-1 Controls and Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184

5-2 Front of Shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193

6-1 NTP Type 4 Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202

6-2 Cisco Systems Data Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203

10

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Tables

1-1 Timing Source Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

3-1 TOD Connector Pinouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88

3-2 Converter DB-25 Connector Pinouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90

3-3 Ethernet 10base-T RJ-45 Connector Pinouts . . . . . . . . . . . . . . . . . . . . . . . .90

3-4 COM1 Pinouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

3-5 COM2 Connector Pinouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

3-6 Craft Pinouts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

3-7 Parameter Factory Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

4-1 Parameter Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120

4-2 Commands for Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

5-1 Front Panel Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185

5-2 Message Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .187

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

11

List of Tables

12

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Procedures

2-1

3-1

3-2

3-3

3-4

3-5

3-6

3-7

5-1

Site Survey. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42

Mounting a Roof Antenna and Connecting the Cable . . . . . . . . . . . . . . . . .60

Mounting a Mechanical Window Antenna and Connecting the Cable . . . . .64

Mounting a Self-Adhesive Window Antenna and Connecting the Cable . . .66

Installing a Wall Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

Installing the RS-422–to–RS-232 TOD Converter . . . . . . . . . . . . . . . . . . . .89

Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

TimeWizard Installation and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .104

Replacing Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .192

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

13

List of Procedures

14

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

How to Use This Guide

This section describes the format, layout, and purpose of this guide.

In This Preface

Purpose of This Guide

Who Should Read This Guide

Structure of This Guide

Conventions Used in This Guide

Warnings, Cautions, Recommendations, and Notes

Related Documents and Information

Where to Find Answers to Product and Document Questions

What’s New In This Guide

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

15

How to Use This Guide

Purpose of This Guide

Purpose of This Guide

The

TimeSource 3600 User’s Guide

describes the procedures for unpacking, installing, using, maintaining, and troubleshooting the Symmetricom TimeSource

3600 GPS Primary Reference Source. It also describes the alarms and events, the languages that you use to communicate with the TimeSource 3600, default values, and other information.

Who Should Read This Guide

Chapter 1, Overview of the TimeSource 3600

, is written for non-technical audiences who need general information about the product. Subsequent chapters contain technical information about the product that describes installation, maintenance, and configuration instructions or details primarily intended for qualified maintenance personnel.

This

User Guide

is designed for the following categories of users:

Systems Engineers

Chapter 1

provides an introduction to the TimeSource

3600, Cross-references in this chapter direct you to detailed system information in other chapters as appropriate.

Installation Engineers

– Chapter 2 through Chapter 6 provide detailed

information and procedures to ensure proper installation, power-up, operation, configuration, and testing of the TimeSource 3600.

Maintenance Engineers

Chapter 5 provides preventive and corrective

maintenance guidelines, as well as procedures for diagnosing and troubleshooting fault indications and alarms.

While

Chapter 1

is written for non-technical audiences who need information about the TimeSource 3600 system, other chapters contain detailed information and instructions which are intended to be performed by

qualified personnel only

.

Structure of This Guide

This guide contains the following sections:

Chapter, Title

Chapter 1, Overview of the

TimeSource 3600

Chapter 2, Engineering &

Ordering

Description

Provides an overview of the product, describes the major hardware and software features, and lists the system specifications.

Provides information to assist in planning the installation and ordering a system appropriate for a specific site.

16

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter, Title

Chapter 3, Installing the

TimeSource 3600

Chapter 4, TL1 Reference

Chapter 5, Troubleshooting

How to Use This Guide

Conventions Used in This Guide

Description

Provides the sequential order of procedures for installation and power-up.

Provides information for using the TL1 language.

Provides troubleshooting information using front-panel lamps and error messages. It also describes how to replace a card, return equipment, get technical and/or sales assistance, and obtain manual updates.

Provides equipment specifications.

Provides references to individual topics within this guide.

Chapter 6, Specifications

Index

Conventions Used in This Guide

This guide uses the following conventions:

Acronyms and Abbreviations

– Terms are spelled out the first time they appear in text. Thereafter, only the acronym or abbreviation is used.

Revision Control

– The title page lists the printing date and versions of the product this guide describes.

Typographical Conventions

– This guide uses the typographical conventions described in the table below.

When text appears this way...

TimeSource 3600 User’s

Guide

TS3600

CRITICAL

GPS

Select

File

,

Open

...

Press

Enter

Press

;

TS3600

Username:

... it means:

The title of a document.

An operating mode, alarm state, status, or chassis label.

Click the Open option on the File menu.

A named keyboard key.

The key name is shown as it appears on the keyboard.

An explanation of the key’s acronym or function immediately follows the first reference to the key, if required.

Text in a source file or a system prompt or other text that appears on a screen.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

17

How to Use This Guide

Warnings, Cautions, Recommendations, and Notes

When text appears this way...

ED-EQPT

RTRV-ALM

bridging

mode

Symmetricom

does not

recommend...

... it means:

A command you enter at a system prompt or text you enter in response to a program prompt. You must enter commands for case-sensitive operating systems exactly as shown.

A word or term being emphasized.

A word or term given special emphasis.

Warnings, Cautions, Recommendations, and Notes

Warnings, Cautions, Recommendations, and Notes attract attention to essential or critical information in this guide. The types of information included in each are explained in the following examples.

Warning:

To avoid serious personal injury or death,

do not

disregard warnings. All warnings use this symbol. Warnings are installation, operation, or maintenance procedures, practices, or statements, that if not strictly observed, may result in serious personal injury or even death.

Caution:

To avoid personal injury,

do not

disregard cautions. All cautions use this symbol. Cautions are installation, operation, or maintenance procedures, practices, conditions, or statements, that if not strictly observed, may result in damage to, or destruction of, the equipment. Cautions are also used to indicate a long-term health hazard.

ESD Caution:

To avoid personal injury and electrostatic discharge

(ESD) damage to equipment,

do not

disregard ESD cautions. All ESD cautions use this symbol. ESD cautions are installation, operation, or maintenance procedures, practices, conditions, or statements that if not strictly observed, may result in possible personal injury, electrostatic discharge damage to, or destruction of, static-sensitive components of the equipment.

Electrical Shock Caution:

To avoid electrical shock and possible personal injury, do not disregard electrical shock cautions. All electrical shock cautions use this symbol. Electrical shock cautions are practices, procedures, or statements, that if not strictly observed, may result in possible personal injury, electrical shock damage to, or destruction of components of the equipment.

18

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

How to Use This Guide

Related Documents and Information

Recommendation:

All recommendations use this symbol.

Recommendations indicate manufacturer-tested methods or known functionality. Recommendations contain installation, operation, or maintenance procedures, practices, conditions, or statements, that provide important information for optimum performance results.

Note:

All notes use this symbol. Notes contain installation, operation, or maintenance procedures, practices, conditions, or statements, that alert you to important information, which may make your task easier or increase your understanding.

Related Documents and Information

Other helpful documents and software tools are listed below. See your

Symmetricom representative or sales office for a complete list of available documentation.

SynCraft management software

TimePictra management software

Note:

Symmetricom offers training courses designed to enhance your knowledge of the TimeSource 3600. Contact your local representative or sales office for a complete list of courses and outlines.

Where to Find Answers to Product and Document

Questions

For additional information about the products described in this guide, please contact your Symmetricom representative or your local sales office. You can also contact us on the web at www.symmetricom.com

.

What’s New In This Guide

Revision H of this guide contains the following new information:

Added the alarm conditioning flow chart in

Figure 4-4 .

Added Success Rate , on page 39.

Changed the part number for the IF converter for window antenna gain from

090-72050-71 to 090-72050-72.

Added the command

Retrieve Status Security , on page 180.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

19

How to Use This Guide

What’s New In This Guide

20

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

This chapter provides an overview of the global positioning system and a physical and functional description of the TimeSource 3600.

In This Chapter

Overview

Global Positioning System

Physical Description

Functional Description

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

21

Chapter 1 Overview of the TimeSource 3600

Overview

Overview

The TimeSource 3600 is a Primary Reference Source (PRS) that receives and processes signals from GPS satellites, and outputs Stratum 1 synchronization signals traceable to UTC. TimeSource 3600 applications include synchronization for central offices, wireless base stations, transmission nodes, and other cases where a primary reference source can improve the performance of a telecommunications network infrastructure.

The TimeSource 3600 is also ideal for installation in environments where receiving

GPS signals is difficult. Examples of environments hostile to GPS signals include urban canyons which have a very limited view of the sky because of blockage from nearby buildings, and high interference zones where GPS signals are jammed by competing over-the-air signals.

The TimeSource 3600 creates timing outputs by ensembling signals from several sources. The sources include GPS signals, an onboard rubidium local oscillator, and optional E1 or analog signals. Timing outputs created from the ensemble are composed of the most stable and least noisy parts of each input. The performance of the E1 sources can be monitored and classified using standard measures.

Synchronization outputs are delivered in a framed, all-ones, E1 format or 2.048

MHz analog signal, a 10 MHz signal, a 1 pps signal, and a choice of time of day

(TOD) formats.

The TimeSource 3600 minimizes timing impairments, such as jitter and wander, that are created by network and transmission systems. The synchronization timing is traceable to the GPS, which provides the highest level of synchronization for telephony networks. The TimeSource 3600 with its GPS input is a stand-alone office

PRS. With the optional inputs ensembled, holdover is extended if GPS signals are disrupted.

Global Positioning System

The United States Government developed the GPS navigation system. It is a satellite-based, radio navigation aid designed to provide global, all-weather, precise navigation and timing capability to users 24 hours a day.

The satellites, circling the earth at approximately 20,197 km, are arranged in 6 orbits with 4 operational satellites in each orbit. Each satellite has an orbital period of approximately 12 hours. This configuration assures that a minimum of 4 satellites, and as many as 12, are in view anywhere in the world at all times.

The TimeSource 3600 tracks all satellites within its field of view. The performance of each tracked satellite is observed and compared to the others, and available for use in the timing solution. A satellite with unacceptable performance data is dropped from the timing solution.

22

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Physical Description

GPS antennas must have line-of-sight access to the transmitting satellites. Any structure that interferes with, or blocks, the view of the satellites disrupts the reception of the signals, and can adversely impact the timing performance of a receiver.

The TimeSource 3600 bridges frequent GPS outage periods with BesTime algorithms, an ultra-stable Rubidium local oscillator and advanced holdover technology. The technology anticipates the outages and uses BesTime-generated predictor values to optimize the performance of timing without direct satellite input.

Physical Description

The TimeSource 3600 consists of a shelf, a plug-in card, an antenna, cables, hardware, and software. Optional system configurations include eight additional E1 or analog 2.048 Mhz outputs, two E1 synchronous clock insertion unit (ESCIU) ports, four IRIG-B TOD timing outputs, or eight mixed E1/T1 outputs.

The shelf (

Figure 1-1 ) can be mounted in a 48 cm rack or an ETSI 53.5 cm rack.

One RU (4.45 cm) of air space above the TimeSource 3600 is required for proper ventilation. Other than a communications connector on the front panel, all connectors are at the connector panel.

Four types of antennas are available: roof antenna for installation outdoors, usually on a roof mechanical antenna for installation indoors, mounted on a window sill or wall for reception through a window self-adhesive antenna for installation indoors, adhered directly to a window wall antenna for installation outdoors, through a hole in the wall

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

23

Chapter 1 Overview of the TimeSource 3600

Physical Description

22 cm

43.8 cm

990-72060-01, -02, -05, -06 Systems

8.2 cm

22 cm

Figure 1-1.

Shelf

43.8 cm

990-72060-04 Systems

8.2 cm

24

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Physical Description

Roof Antenna

The roof antenna (

Figure 1-2 ) is encased in weather-resistant plastic housing for

outdoor installation, usually on a roof. A single coaxial cable carries signals and power between the antenna and the shelf.

15 cm

47.92 cm

4.67 cm

Figure 1-2.

Roof Antenna

Mechanical Window Antenna

The mechanical window antenna (

Figure 1-3

) may be attached to a window sill or wall, in any position that allows the antenna to be moved flush against the window.

The antenna can be swung away from the window for window maintenance, and returned to its original position.

A single length of coaxial cable carries signals and power between the antenna assembly and the shelf.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

25

Chapter 1 Overview of the TimeSource 3600

Physical Description

Antenna

Coaxial Cable

Mounting Assembly

IF Converter

Coaxial Cable to TimeSource 3600 Shelf

(not included with antenna assembly)

43 cm

Figure 1-3.

Mechanical Window Antenna

Self-Adhesive Window Antenna

The self-adhesive window antenna assembly (

Figure 1-4

) consists of the antenna and two pieces of self-stick hook-and-loop fabric fasteners (Velcro brand or equivalent). The hook-and-loop fabric attaches directly to a window. Coaxial cables carry signals and power between the antenna and the IF converter, and between the IF converter and the shelf.

GPS WINDOW

ANTENNA

Figure 1-4.

Self-Adhesive Window Antenna

26

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

Wall Antenna

The wall antenna (

Figure 1-5 ) is mounted on the outside of a building wall. The

antenna attaches magnetically to the mounting bracket. The cable from the antenna is routed through a hole drilled in the wall. Coaxial cables carry signals and power between the antenna and the IF converter, and between the IF converter and the shelf.

Antenna Mounting Bracket

Antenna

Coaxial Cable

7.5 cm

Figure 1-5.

Wall Antenna

Functional Description

Figure 1-6

shows the main functions of the TimeSource 3600. The center of the

TimeSource 3600 is the BesTime Ensemble Timing Generator, which uses the

BesTime algorithm to analyze the phase and frequency relationships, individually and collectively, of the timing sources. Each type of timing source has a particular characteristic that gives it an advantage over other sources, as listed in

Table 1-1 .

The BesTime algorithm uses the best characteristic of each source to produce an output signal with greater overall accuracy and stability than any single source. The contribution of a source is based on its deviation from the weighted average of all the sources. The more accurate a source, the more weight it has in the final output.

Every source is under constant evaluation and its contribution subject to periodic adjustment. The output is essentially the best performance of each individual source.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

27

Chapter 1 Overview of the TimeSource 3600

Functional Description

Figure 1-6.

Block Diagram

Table 1-1. Timing Source Characteristics

Source

Local Oscillator

E1 Line

GPS Signal

Characteristic

Short term stability

Intermediate term stability

Long term stability

Antenna

The antenna types include a roof antenna, mechanical window antenna, self-adhesive window antenna, or wall antenna. All antennas include a GPS receiver, amplifier, and intermediate-frequency (IF) downconverter.

28

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

The GPS Receiver extracts a clock signal from the GPS satellite signals. The receiver can process the signals from all satellites in view, while simultaneously using the Earth location of the receiver and other factors to determine an accurate clock signal.

An amplifier provides signal gain.

The downconverter converts the L1-band GPS signal to IF for long-distance transport on the coaxial antenna cable. The antenna cable provides current from the shelf to the antenna, and transports GPS satellite IF signals from the antenna to the shelf.

Antenna Installation and Lightning Protection

The TimeSource 3600 standard wall antenna kits do not include lightning protectors. When the antenna is installed on the side of the building, the antenna is in the zone of protection and is protected from lightning strikes as described in the

Standard for the Installation of Lightning Protection Systems (NFPA 780), 2000 edition.

The zone of protection shall include the space not intruded by a rolling sphere having a radius of 45.72 meters (150 ft). Where the sphere is tangent to earth and resting against a strike termination device, all space in the vertical plane between the two points of contact and under the sphere shall be considered to be in the zone of protection. A zone of protection shall also be formed where such a sphere is resting on two or more strike termination devices and shall include the space between those devices (see

Figure 1-7 ). All possible placements of the sphere shall

be considered when determining the zone of protection using the rolling sphere model.

Figure 1-7.

Zone of Protection

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

29

Chapter 1 Overview of the TimeSource 3600

Functional Description

For structure heights exceeding 45.72 m (150 ft) above earth or above a lower strike termination device, the zone of protection shall be considered to be the space in the vertical plane between the points of contact and under the sphere where the sphere is resting against a vertical surface of the structure and the lower strike termination device or earth. The zone of protection shall be limited to the space above the horizontal plane of the lowest terminal unless it can be extended by further analysis, such as in rolling the sphere to be tangent to earth.

If the wall antenna is installed outside the zone of protection, Symmetricom offers an outdoor and/or indoor lightning protector kits for these installations. Refer to

Chapter 2, Engineering & Ordering, for more information on these kits.

IF Interface

An IF interface accepts the signals from the antenna/IF converter, and provides the clock information to the BesTime Ensemble Timing Generator.

GPS Receiver

The GPS Receiver continuously tracks up to eight satellites, using both carrier and code lock. The recovered pseudo-range measurement data is processed to determine precise time and frequency state estimates for the local oscillator. The receiver software is optimized to track and update state estimates, when as few as one satellite is in view.

Local Oscillator

A rubidium oscillator, based on a digitally controlled servo-loop, provides an ultra-stable local oscillator signal, which is sent to the BesTime Ensemble Timing

Generator.

Clock Extractors

A clock extractor circuit extracts a timing signal from each external reference source. (External sources, other than the GPS antenna, are optional.) The extracted timing signal is sent to the BesTime Ensemble Timing Generator.

Power Supply

A power converter filters and converts

48 volts dc power supplied to the shelf into the voltages required by the circuitry.

30

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

NTP TimeServer

The TimeServer is a Simple Network Time Protocol (SNTP) device. The SNTP

TimeServer function is provided via the TimeSource Ethernet interface and associated IP address. User software requests UTC time of day via NTP protocol.

The TimeSource SNTP server responds with current UTC time. The TimeServer is compatible with the SNTP RFC-1769 format.

To enable the SNTP feature, a password must be entered using the ED-EQPT TL1 command. If a user makes a fourth attempt of an incorrect password entry, the

TimeServer will lock out the user for 1 hour.

Network Time Protocol Password Activation

Use of the Network Time Protocol (NTP) feature requires activation with a password. Activation is accomplished through receipt of a Network Time Protocol

Activation Certificate from Symmetricom. This certificate contains the unit purchase order number, unit model number, unit activation date, unit serial number, and unit activation key. The unit activation key is the password that enables the NTP feature.

To activate the NTP feature, enter the TL1 command printed on the activation certificate. Once activated, this feature will be permanently enabled. To order the

NTP feature, contact the local Symmetricom sales representative.

BesTime Ensemble Timing Generator

Clock signals from the GPS antenna (via the IF interface), local oscillator, and optional E1 span lines are used as sources by the BesTime algorithms in the

BesTime Ensemble Timing Generator. The signals are analyzed for MDEV, TDEV, and other phase and frequency characteristics.

The BesTime Ensemble Timing Generator uses mathematical models to analyze each clock. The ensemble algorithms use the comparisons and analyses to generate a highly stable timing signal, which uses the best qualities of all inputs.

E1 or Analog Outputs

The BesTime Ensemble Timing Generator provides the timing for the E1 or analog

(2.048 MHz) timing signal available at the E1 OUT A and B connectors. E1 is provided in a framed, all-ones format, which can be set to CAS, CAS4, CCS, or

CCS4 framing. 2.048 MHz is provided in accordance with G.703/10.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

31

Chapter 1 Overview of the TimeSource 3600

Functional Description

Eight Mixed E1/T1 Outputs

This feature enables a user to mix any combination of E1 and T1 outputs. A user can also use any combination of framing. For E1, CCS, CAS, CCS with CRC4, and

CAS with CRC4 can be used per G.703 table 6. For T1, D4 or ESF can be used per

ANSI T1.101. In addition, there is support for analog (2.048 MHz) per G.703 table

10 and support for synchronous status messaging (SSM) per TR-33 for E1 and T1.

Eight Additional E1 or Analog Outputs (990-72060-02 Systems

Only)

This option provides eight additional E1 or analog (2.048 MHz) outputs, available with the required option module. The module mounts in the OPTIONS I/O mountings on the connector panel. These outputs function the same as the standard E1 outputs.

TOD Output

The BesTime Ensemble Timing Generator provides the timing for the TOD timing signal available at the RJ-45 connector, which provides time code to devices compatible with NTP Type 4 or Cisco ASCII format.

IRIG-B TOD Outputs (990-72060-05 Systems Only)

This option provides four additional TOD outputs in IRIG-B format. The outputs are available at a BNC output module mounted on the OPTIONS I/O mountings on the connector panel.

The BesTime Ensemble Timing Generator provides the timing for the TOD timing signal, which provides timing code to devices compatible with IRIG-B.

1 PPS Output

The BesTime Ensemble Timing Generator provides the timing for the

1 pulse-per-second timing signal available at the 1 PPS connector, which can be used for application-specific requirements. This signal is not squelched during an alarm.

10 MHz Output

The BesTime Ensemble Timing Generator provides timing for the 10 MHz timing signal available at the 10 MHZ connector, which can be used for local cellular frequency or testing purposes. This signal is not squelched during an alarm.

32

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

Two ESCIU Outputs (990-72060-04 Systems Only)

This option provides a module for two E1 ports. The module mounts in the

OPTIONS I/O mountings on the connector panel. E1 traffic-carrying signals are synchronized using the Bestime ensemble timing generator. Jitter and wander are also removed before sending the E1 signals to network elements.

If an alarm condition or power failure occurs, relays allow the E1 signals to bypass

the system. (See Figure 1-8

).

ESCIU

Pass-through in Return Direction

Relay Bypass Path

Datastream

Synchronizer

BesTime Ensemble

Timing Generator

Synchronizing signal

Figure 1-8.

Two ESCIU Outputs Option

Alarm Interface

The microprocessor delivers alarms to normally open dry-contact type connections.

Alarms are also indicated by the front-panel status lamps.

Communication Ports

Three serial communication ports carry TL1 commands, responses, and autonomous messages between the TimeSource 3600 and an external terminal.

Ethernet

TimeSource 3600 has six Ethernet ports to carry TL1 commands, responses, and autonomous messages between the TimeSource 3600 and an external terminal, or an Element Manager, or both. The user can configure the IP address, subnet mask, and gateway address for the Ethernet ports.

Four ports (5001, 5002, 5003, and 5004) are configured to act as though a serial-port communication terminal were connected to them. These ports communicate TL1 commands, responses and autonomous messages.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

33

Chapter 1 Overview of the TimeSource 3600

Functional Description

Two additional ports communicate with Element Managers, which may have NMS,

TimePictra, or similar software. An Element Manager establishes a connection with one port (5551) for TL1 commands and responses. Another port (5550) establishes a connection to an Element Manger, sends autonomous messages, and closes the connection when finished.

Passthrough

The Passthrough feature of the TimeSource 3600 allows the unit to front a DCD product to provide one management interface for a user site. Passthrough allows a user to do the following:

COM1 or COM2 of the TimeSource is connected to the DCD product

The user port can be any unused port, including the Ethernet port

Messages can pass from a user to the DCD product and from the DCD product to a user through the TimeSource 3600

The TID (SID for DCD) is used to identify commands that go to the DCD product.

The TimeSource 3600 passes any TID not its own through to the DCD product. In the reverse direction, all commands received from the DCD product are passed through to the user

Note:

The TID of the TL1 command must be the SID of MIS.

DCD is fully managed except for firmware download.

GUI interfaces to the DCD product are not supported through the Passthrough, only TL1 responses are available.

Figure 1-9

shows a TimeSource 3600 Passthrough setup.

DCD-5X

Straight cable

COM 1, 2, or 3

DCDPASSTHRU

User port (any port)

TS-3600

DCDUSERPORT

COM 1, 2, 3

IP: 5001 – 5004

COM 1 or 2 (COM 1 is

DB-25 and COM 2 is DB-9)

Figure 1-9.

TimeSource 3600 Passthrough Function

34

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

Alarm Programmability

Releases of TimeSource (1.05.03 and above) allow the user to provision the alarm escalation parameters that were hardcoded in the previous releases of TS3000.hex.

The defaults for this release remain the same as were previously hardcoded. This feature can be used to set the programmability for such alarms as GPS,

HOLDOVER, SPAN-X, and RO-X.

The TS3600 alarms can be programmed for GPS and HOLDOVER types of events.

The SPAN-X alarms can be programmed for AIS, ERROR, and LOS types of events.

The user can set the parameters for SEVERITY1 and SERAFF1 which initially come into effect when the condition is detected. The user can also set the parameters for SEVERITY2 and SERAFF2 which come into effect after TIME

(another user programmable parameter).

The system also allows the user to set a parameter to define how outputs should behave in an alarm condition (see ALMOUT and ALMCOND settings). Outputs can be set to AIS, Squelch, or SSM when Holdover alarm severity is set to minor or major. AIS, Squelch, or SSM is not evoked if Holdover severity is set to event

(factory default for initial severity). Outputs can also be set to ignore alarm conditions.

Startup

When the TimeSource starts up, the CRIT lamp lights. The CRIT lamp remains on for approximately 50 seconds to 60 seconds and then shuts off.

During startup, the TimeSource performs several self-tests to verify the integrity of the hardware and software. Neither communication nor outputs are possible at this time, and the CRIT lamp is switched on. Once the self-tests are done, a connection to the system can be made and the events viewed.

Two events are initially provided. These events are:

"Power Up Restart"

"Settling Period"

In the "Power Up Restart" event, which lasts for approximately 2 minutes, the system does additional checks and starts all the various tasks within the system.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

35

Chapter 1 Overview of the TimeSource 3600

Functional Description

The "Settling Period" event is an informational message that lasts until the

TimeSource’s BesTime engine reaches the highest possible stable point. The time taken to reach this point depends on satellite availability, type of oscillator, ambient temperature, etc. and may take up to 20 hours to clear. Since "Settling Period" is independent of the quality of the output and is the normal behavior of the system, it is generated as an event rather than an alarm. If "Settling Period" is not cleared after 24 hours, another "Settling Period" event is generated as a marker. This is still

Non-Service-Affecting.

As soon as the "Power Up Restart" message is cleared, the "BT3 Warmup" event is generated. This is also an informational message that lasts till the time it takes the system to acquire the satellites, warm up the oscillator, and start giving out valid outputs. It may take up to 2 hours for the message to clear, but typically takes approximately 40 minutes. During the "BT3 Warmup" time, the outputs will generally be squelched. If the outputs are enabled using the TL1 command (ED-EQPT::

TS3600:ctag:::ALMCOND=ALW;) they may not be within the PRS mask. In case the system is not able to acquire sufficient number of satellites and/or discipline the oscillator within 2 hours, the event escalates into a Non Service Affecting Minor alarm.

Once the warm up is complete, the system generates valid outputs and the event is cleared.

Bridging/Holdover Behavior

In the TimeSource 3600, alarms are designed with a built-in hysteresis. This means that an alarm is not announced as soon as some error condition is detected. There is a pre-integration time during which the error must persist in order for the alarm to be announced. On the flip side, the error must be clear for a certain time for an alarm condition to be cleared. This ensures that intermittent conditions are not flagged unnecessarily.

During the normal working of the TimeSource 3600, it is a very common occurrence that the GPS satellites may not be visible during certain parts of the day, depending on the installation of the antenna. This is particularly true with wall and, especially, window antenna installations. The TimeSource 3600 has been designed to work around this situation.

The TimeSource 3600 enters "Bridging" mode when all satellite locks are lost.

There is no TL1 annunciation that the system has entered "Bridging" mode. This is

"Non Service Affecting" and the outputs are not affected. The system runs off its internal oscillator and the outputs are kept within the G.811 PRS mask by the

BesTime engine.

When "Bridging" mode persists for more than 30 minutes, the system enters

"Holdover" mode and a "Holdover" event is generated. This may or may not affect the outputs depending on the alarm integration parameters that can be set by the user.

36

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

The system allows the user to set various parameters for GPS error, Holdover error, and SPAN error conditions. These parameters are:

Initial Severity

Initial Service Affecting state

Integration Time

Final Severity

Final Service Affecting state

The system also allows the user to set a parameter to define how outputs should behave in an alarm condition (see ALMOUT and ALMCOND settings). Outputs can be set to AIS, Squelch, or SSM when Holdover alarm severity is set to minor or major. AIS, Squelch, or SSM is not evoked if Holdover severity is set to event

(factory default for initial severity). Outputs can also be set to ignore alarm conditions.

When the "Holdover" event is announced, it is announced with the Initial Severity and Initial Service Affecting state. If the "Holdover" event persists for the length of the Integration Time, the alarm is escalated to the Final Severity and Final Service

Affecting state.

The "Holdover" event/alarm is cleared when the satellites are visible again.

Time Figure of Merit

Time Figure of Merit (TFOM) is a moving 24 hour measurement reported in nanosecond (ns) against an ideal model. TFOM has a frequency component used to measure GPS wander caused by multipath and a time loop component used to measure long term oscillator wander.

The TFOM alarm threshold is set to 500 ns and is not user configurable. A TFOM below 500 ns indicates a stable clock well within PRS output performance specifications. A TFOM between 500 ns and 800 ns is an early warning of a clock becoming unstable and in danger of going out of PRS specification. When the

TFOM exceeds 800 ns, the clock is no longer meeting the stratum 1 MTIE mask.

TFOM is most useful for installations where the antenna has a limited view to the sky. This is defined as any installation where fewer than 4 satellites are in view for greater than 1 hour per day on average. This is typical for installations where the antenna is mounted in a window or on an outside wall of a building, but can also include rooftop installations with partial sky view blockage. TFOM’s primary use is to help troubleshoot multipath issues associated with antenna placement and incorrect latitude, longitude, and/or altitude (location) data entry.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

37

Chapter 1 Overview of the TimeSource 3600

Functional Description

Installations with full view to the sky see 4 satellites 23+ hours a day, seven days a week. It is relatively easy to filter out multipath signals using multiple satellites and simple voting schemes. In addition, rooftop antennas are mounted vertically and all signals below the horizon are obvious multipath interference and can be masked out of the system. With 4 satellites in view, the GPS timing receiver will provide an error-free lock on its location through an automatic survey function.

With wall/window installations, voting schemes become less effective as the number of satellites in view drop. Also, wall/window antennas are mounted horizontally and are prone to seeing multipath signals reflected off nearby structures and the ground. Wall/window installations also require the manual input of location data, creating the potential for errors and the need to detect these errors.

The TimeSource has unique algorithms to account for, and defeat, the added multipath complications and location data entry error possibilities of wall/window antenna installations. Large amounts of multipath or major errors in location data entry are easier to identify and are detected over a relatively short period of time.

These short-term errors are normally reported via the TimeSource tracking success rate parameter.

Small amounts of multipath or minor errors in location data entry are difficult to identify because they mimic a true signal or an expected satellite behavior pattern.

Single satellite reception over limited periods of time complicates the ability for the internal TimeSource algorithms to filter out these ghost signals and longer periods of time are needed to sort them out. TFOM tracks and reports these long-term errors.

At time of installation, marginal or unacceptable TFOM readings can indicate the need to adjust the antenna placement, the mask angle, and/or the location data.

Relatively small changes in the antenna placement can improve the ability of the system to see satellites and therefore improve performance. The mask angle can be adjusted to block out lower elevation portions of the sky if there is good visibility at higher elevations, thereby reducing multipath. Correct location data is very helpful in identifying and tracking satellites.

In addition, a clock may be stable for many weeks, months, or years but could degrade because of changes in its environment. TFOM is useful in detecting these infrequent subtle changes including:

Maturing foliage or seasonal foliage changes

Installation of new transmitters nearby (i.e. wireless base station)

New building construction

Variations in the day-to-day temperature of the CO

38

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 1 Overview of the TimeSource 3600

Functional Description

Success Rate

Success rate is a moving 24-hour window indicating the TimeSource's ability to lock to and use the GPS as part of the system's timing solution. This metric is reported as a percentage (%) ratio of the total good minutes that the system uses GPS in a day (maximum 1440 minutes/day). Success rate can range in value from 0% to

100%.

Success rate is determined by totaling all good minutes of satellite(s) visibility that the system is using and dividing by the total maximum possible minutes in a day.

When satellites are not being used in the solution, usually because of low satellite visibility or multipath effects, the minutes are not counted in the good minutes category.

The success rate of a rooftop antenna configuration is generally higher than a wall/window antenna configuration since rooftop installations have a better view of the sky. A wall/window installation typically may see only portions of the sky with fewer satellites.

The TFOM (Merit) metric plays a key role in the calculation of Success Rate (see

Time Figure of Merit , on page 37). When TFOM is greater than 500 ns, it is a

warning that the system clock is becoming unstable and may be going out of PRS specification. Success Rate uses this as a threshold, so when the TFOM value is equal or below 500 ns, minutes are calculated within the good minutes category.

Conversely, when the TFOM value is above 500 ns, these minutes are not considered as good minutes.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

39

Chapter 1 Overview of the TimeSource 3600

Functional Description

40

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

This chapter provides information to assist in planning the installation and ordering a system appropriate for a specific site.

In This Chapter

Antenna Guidelines

Shelf Considerations

Systems

Antennas

User-Supplied Tools and Materials

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

41

Chapter 2 Engineering & Ordering

Antenna Guidelines

Antenna Guidelines

Perform a site survey as described in

Procedure 2-1

before ordering the system.

Use the guidelines and considerations in the Roof/Window/Wall Antenna Location and Cabling Guidelines section and

Shelf Considerations , on page 49.

Procedure 2-1. Site Survey

Step

1.

2.

3.

4.

5.

6.

Procedure

Determine the shelf location.

Determine the best location for mounting the antenna (less than 330 m of cable from the shelf). Use the guidelines and considerations found in

Roof Antenna

Location and Cabling Guidelines , on page 43.

If a roof-mounted antenna is installed, determine the location of the grounding point for the lightning suppressor, then determine the location of the lightning suppressor.

The cable length between the lightning suppressor and the grounding point must be less than 4.6 m. If the grounding point is inside the building, the cable length between the grounding point and the cable entry must be less than 15 m. Valid lightning suppressor grounding points are:

• Valid ring ground system (usually for roof-mounted lightning suppressors)

• Structural steel of building (for interior-mounted or exterior-mounted lightning suppressors, attach with a cad weld)

• Central Office ground plate (usually for interior-mounted lightning suppressors)

If a roof-mounted antenna is installed, two lengths of cable are required. Plan the cable route and measure the length of cable required between the antenna and the lightning suppressor, and between the lightning suppressor and the shelf.

If a window or wall-mounted antenna is installed, plan the cable route and measure the length of cable required between the antenna and the shelf.

Determine the two separate –48 V power sources for the shelf. If only one –48 V power source is available, it must be cabled to both TimeSource 3600 power inputs.

End of Procedure

42

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Antenna Guidelines

Roof Antenna Location and Cabling Guidelines

Warning:

To avoid serious personal injury or death, do not select an antenna location that could be an electrical or physical hazard to work persons or equipment. Avoid proximity to all high-voltage sources.

Mount in an easily maintainable location.

The ideal roof antenna location provides a clear, unobstructed view of the sky from the zenith to the horizon line, and 360 degrees around the horizon.

A compromise often must be made between location and satellite field of view. With a smaller field of view, the TimeSource 3600 can use fewer satellites in the solution for GPS derived time. The TimeSource 3600 will operate with an average of one satellite in view for 40 percent of the time in a day.

Signals closer to the horizon are often subject to multipath effects, which degrade the timing solution. The TimeSource 3600 can be set to ignore, or mask, all signals

from the horizon up to a chosen angle of elevation (mask angle). (See Figure 2-1..)

Antenna position

Antenna field of view

Obstructions toward the pole if possible

10°

Mask angle*

Horizon

Equator

10°

Mask angle*

Pole

* An angle of 10° masks objects up to about 1 m above the horizon at 6 m from the antenna (illustration at right.)

10°

1 m

6 m

Figure 2-1. Antenna Field of View

Due to the geometry of the GPS satellite orbits, more satellites are visible in the direction of the equator than the poles. If possible, place the antenna so that the antenna has a clear view toward the equator (toward the south in the northern hemisphere, or toward the north in the southern hemisphere). Up to 60 degrees of arc, centered at the pole, may be blocked with little effect in the temperate latitudes.

This note is less applicable in latitudes nearer the equator.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

43

Chapter 2 Engineering & Ordering

Antenna Guidelines

The total of obstructions above the mask angle should not obscure more than 25

percent of the total field of view (90 degrees of azimuth see Figure 2-2.).

Figure 2-2. Antenna Location Examples

Notes:

Place the antenna high enough on the tower that obstructions are below the mask angle; mount the antenna more than 1 meter away from the tower, and far below the interference of the antennas at the top of the tower. Tower mounting is the least desirable location because of the potential for severe multipath, and difficulty in troubleshooting and maintenance.

Place the antenna high enough that the roof structure and tree are below the mask angle, and the water tower does not block more than

12.5 percent of the sky.

No single obstruction should block a large portion (45 degrees of azimuth) of the view.

The most important obstructions are within 400 meters of the antenna. Obstructions may include, but are not limited to, towers, buildings, other construction, trees, and high-voltage power lines.

Attempt to avoid locating the antenna within 30 degrees azimuth of the transmission direction of any transmitting antenna in the area, even if the transmitting antenna operates at a different frequency. A transmitting antenna may cause the GPS antenna to become overloaded and reduce its reception capabilities.

The minimum horizontal distance from other receiving antennas is 1 meter.

44

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Antenna Guidelines

To reduce multipath signal distortions, the minimum horizontal distance from vertical reflective structures (e.g., heating ducts, equipment housings, etc.) is twice the height of the structure, and no less than 3 meters (see

Figure 2-3.).

Do not locate the antenna underneath high power lines. If this cannot be avoided, ensure the antenna is placed at least twice as far from the power line as the power line is high (to avoid danger to personnel and multipath effects).

Cables must be run as straight as possible. All cables should be routed in accordance with local company practices.

Note:

Keep all impedances as low as possible, otherwise the grounding scheme may be defeated.

Observe the following guidelines during the placement and installation of the cables:

Route cables as straight as possible (bends in the cable increase impedance at lightning frequencies), in accordance with local company practices.

Any opening where conduit enters the building must be waterproofed per local company practices.

Treat all exposed connections with an electrically conductive anti-corrosion compound (Kopr-Shield or equivalent).

Caution:

To prevent damage to cables, avoid small-radius turns and unnecessary turns.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

45

Chapter 2 Engineering & Ordering

Antenna Guidelines

Figure 2-3. Sample Rooftop Antenna Mount

Note:

Figure 2-3 is an example only. Not all parts are available from

Symmetricom.

Roof Antenna Earth Ground Location Guidelines

The roof ring ground system, a Central Office grounding plate, and building structural steel are examples of valid earth ground points. If the mounting plate cannot be bolted to a valid earth ground, or if the mounting plate is to be installed in a nonmetallic junction box, bolt the mounting plate to a point within 4.6 meters of the valid earth ground.

Roof Antenna Cable Choices

The antenna assembly uses the same coaxial cable for power and antenna signals.

The length of cable is determined by circumstances of the installation and site.

Symmetricom offers RG-59/U plenum-rated coaxial cable (20 AWG [0.812 mm], 75 ohm coaxial) with male TNC connectors attached, in the following lengths:

3 m cable (060-72010-01)

6 m cable (060-72010-02)

15 m cable (060-72010-05)

30 m cable (060-72010-10)

61 m cable (060-72010-20)

91 m cable (060-72010-30)

152 m cable (060-72010-50)

182 m cable (060-72010-60)

243 m cable (060-72010-80)

305 m cable (060-72010-99)

Two cables are required: one to connect the antenna to the lightning suppressor, and another to connect the lightning suppressor to the TimeSource 3600 Shelf.

Optionally, one length of coaxial cable may be ordered, which must be cut and prepared with end-connectors at the point where the suppressor is located.

The following items, which must be ordered separately, are available for this type of installation:

TNC connector kit (093-72010-98) includes:

46

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Antenna Guidelines

– TNC connectors for RG-59/U cables (8)

– Rubber boots (8)

– TNC adapter connectors (2)

TNC crimp tool (154-00023-01)

Window and Wall Antenna Location Guidelines

When selecting a window or wall in which to install the antenna, select the window or wall which has the maximum unobstructed view of the sky. Do not select a window or wall which has the view of the sky obstructed by trees, buildings, or towers. The smaller the field of view, the fewer the number of satellites that can be used in the timing solution for GPS derived time. The consequence of this is that the timing generator may experience holdover more often and may eventually go into alarm.

Due to the geometry of the GPS satellite orbits, more satellites are visible in the direction of the equator than the poles. If possible, select a window or wall which has a clear view toward the equator (toward the south in the northern hemisphere, or toward the north in the southern hemisphere). This guideline is less applicable in latitudes nearer the equator and more important nearer the poles.

Certain parts of the sky are blocked from view. These obstructions usually exist from the horizon line and up, for example, a building or mountain. The processor inside the GPS receiver observes every piece of the sky, whether it is blocked or not. If unproductive parts of the sky are masked from the processor’s view, the processing time is reduced, and the timing solution can be achieved more quickly.

Note:

A band of the sky from the horizon up to a point where a view of the sky begins is called a mask angle. The mask angle typically should not exceed 10 degrees (if the mask angle is set too high, too little of the sky is available to the receiver). Determine the mask angle for the selected antenna location (

Figure 2-4

) and make a note of it.

The mask angle, in degrees, will be entered during the initial setup.

TimeSource 3600

Antenna

1 m

10° mask angle*

Note: TimeSource 3600 does not detect satellites in the masked area.

6 m

*An angle of 10° masks objects up to about 1 m above the horizon at 6 m from the antenna.

Figure 2-4. Antenna Mask Angle

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

47

Chapter 2 Engineering & Ordering

Antenna Guidelines

Window and Wall Antenna Cable Choices

A window or wall antenna includes an attached coaxial cable terminating in a male

SMA connector. A separate cable is required to connect the IF converter to the

TimeSource 3600 shelf. Two types of plenum-rated cable are available.

The cables with longer length capabilities (060-72010-xx) are RG-59/U (20 AWG

[0.812 mm], 75 ohm coaxial) with male TNC connectors attached to each end.

Assembled cables are available in the following lengths:

3 m cable (060-72010-01)

6 m cable (060-72010-02)

15 m cable (060-72010-05)

30 m cable (060-72010-10)

61 m cable (060-72010-20)

91 m cable (060-72010-30)

152 m cable (060-72010-50)

182 m cable (060-72010-60)

243 m cable (060-72010-80)

305 m cable (060-72010-99)

The more flexible cables (060-72050-xx) are Mini RG-59/U (20 AWG [0.812 mm],

75 ohm coaxial) with male TNC connectors attached to each end. Assembled cables are available in the following lengths:

15 m cable (060-72050-05)

30 m cable (060-72050-10)

61 m cable (060-72050-20)

152 m cable (060-72050-50)

IRIG-B TOD (990-72060-05 System Only)

If you are using the IRIG-B TOD outputs (990-72060-05 TimeSource 3600 System), right-angle BNC connectors are provided to prevent small radius turns in the IRIG-B

TOD cables. The right-angle BNC connectors may be attached to the IRIG-B BNC connectors, to direct the cables from the shelf as desired.

For each IRIG-B TOD output, a user-supplied cable with BNC connectors on each end is installed between the adapter and the network elements requiring IRIG-B

TOD timing.

48

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Shelf Considerations

RS-422–to–RS-232 TOD Converter

If you are using time-of-day (TOD), and the device receiving the time code accepts an RS-232 signal instead of an RS-422 signal (for example, a Cisco router), an

RS-422–to–RS-232 TOD Converter Kit is required (ordered separately, part number

093-72000-98).

The RS-422–to–RS-232 TOD Converter Kit consists of a mounting plate with a female RJ-45 connector, a female DB-25 connector, a TOD converter, and two screws.

Install the converter anywhere (for example, on unused space on a rack) within 305 cable meters of the TimeSource 3600 shelf, and within 15 cable meters of the device receiving the time code.

The user must supply two cables. One cable is a Category 5 four-pair RS-422 cable, 305 meter maximum, with RJ-45 connectors on each end. Route this cable between the TimeSource 3600 Shelf and the converter.

The other cable is an RS-232 data communications cable, 15 meters maximum, with a 25-pin male D-type connector and another connector determined by the device receiving the time code. Route this cable between the converter and the device receiving the time code.

Shelf Considerations

The TimeSource 3600 Shelf can be mounted in an ETSI 53.5 cm rack or a 48 cm rack. The shelf is shipped with supplied mounting ears positioned for flush mounting

on an ETSI 53.5 cm rack. Attach the mounting ears, as shown in Figure 2-5., for

flush mounting or 12.7 cm offset mounting. Attach the long side of the mounting ear to the shelf for an ETSI 53.5 cm rack, and attach the short side of the mounting ears to the shelf for a 48 cm rack. Mount the shelf in the rack according to standard company practices. Leave one RU (4.45 cm) of air space above the

TimeSource 3600 Shelf for proper ventilation. Mount the shelf in the rack according to standard company practices.

Note:

Two screws can be used in each mounting ear when the holes in the rack are spaced 4.45 cm apart.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

49

Chapter 2 Engineering & Ordering

Systems

Rack rails

Rear of rack

Top of shelf

Mounting ears

Rear of rack

Top of shelf

Top of shelf

Mounting ears

A. ETSI – 53.5 cm rack

Rack rails

Rear of rack

Top of shelf

Top of shelf

12.7

cm

Rack rails

B. Flush mounting – 48 cm rack

Figure 2-5. Rack Mounting Options

Systems

Mounting ears

C. 12.7 cm offset – 48 cm rack

The TimeSource 3600 Systems available are listed below. The antenna must be ordered separately.

Standard System (Two E1 Outputs)

This system (990-72060-01) includes:

TimeSource 3100 Shelf (090-72000-11)

TimeSource 3600 card (090-72060-01)

Hardware kit (093-72060-87)

System software compact disc (CD) (992-72060-xx) Version 1.05.04 or higher

TimeScan Craft (keyless version) software CD (992-46750-xx) Version 7.2.0 or higher

With Eight Additional E1 or 2.048 MHz Outputs

This system (990-72060-02) includes:

TimeSource 3100 Shelf (090-72000-11)

50

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Systems

TimeSource 3600 card with additional E1 or 2.048 MHz outputs

(090-72060-02)

Hardware kit (093-72060-87)

System software CD (992-72060-xx)

Version 1.05.04 or higher

TimeScan Craft (keyless version) software CD (992-46750-xx) Version 7.2.0 or higher

With Two E1 Synchronization Insertion (ESCIU) Ports

This system (990-72060-04) includes:

TimeSource 3100 Shelf (090-72000-11)

TimeSource 3600 card with ESCIU ports

(090-72060-04)

Hardware kit (093-72060-87)

System software CD (992-72060-xx)

Version 1.05.04 or higher

TimeScan Craft (keyless version) software CD (992-46750-xx) Version 7.2.0 or higher

With Four IRIG-B TOD Outputs

This system (990-72060-05) includes:

TimeSource 3100 Shelf (090-72000-11)

TimeSource 3600 card with IRIG-B TOD outputs

(090-72060-05)

Hardware kit (093-72060-87)

System software CD (992-72060-xx)

Version 1.05.04 or higher

TimeScan Craft (keyless version) software CD (992-46750-xx) Version 7.2.0 or higher

With Eight Mixed E1/T1 Outputs

This system (990-72060-06) includes:

TimeSource 3100 Shelf (090-72000-11)

TimeSource 3600 card with mixed E1/T1 outputs

(090-72060-06)

Hardware kit (093-72060-87)

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

51

Chapter 2 Engineering & Ordering

Antennas

System software CD (992-72060-xx)

Version 1.05.04 or higher

TimeScan Craft (keyless version) software CD (992-46750-xx) Version 7.2.0 or higher

Antennas

The antennas available are listed below. A TimeSource 3600 System must be ordered separately.

Roof Antenna

Antenna and mounting hardware kit (990-72050-96) includes:

IF antenna assembly (090-72010-71)

Mounting hardware kit (093-72010-71) (x1) which includes:

– Shim, 070-72010-75 (x2)

– Mast, 070-72010-76 (x1)

– Flange, 070-72010-77 (x1)

– Bolts, Pan Head Phillips Screw, 8 - 32 x ¾ inch, 125-83253-12 (x3)

– #8 Flat washers, 400111-0002 (x3)

– #8 Split Lock Washer, 125-00521-08 (x3)

– #8 Nut, 400160-0003 (x3)

Rooftop antenna installation kit (093-72050-96) includes:

– Mounting bracket for surge suppressor (070-00300-02)

– Surge suppressor (143-00018-01)

– Antenna cable bracket kit (093-00001-01)

– Miscellaneous installation parts

Mechanical Window Antenna

This antenna kit (990-72050-97) comes as a fully assembled antenna with the following major components:

Antenna, with cable and SMA connector attached (090-72050-90)

IF converter for window antenna gain (090-72050-72)

Mechanical chassis (074-72050-97)

52

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

Antennas

Self-Adhesive Window Antenna

This antenna kit (990-72050-98) includes:

Antenna (090-71010-87)

IF converter for window antenna gain (090-72050-72)

Self-adhesive window antenna installation kit (093-72050-98) includes:

– RG316 cable, 3 m (060-00062-01)

– Cable tie mounts (128-00302-02) and cable ties (128-00500-05)

Wall Antenna

Order one of these two available wall antenna kits based on the users antenna cable length installation requirements:

This antenna kit (990-72050-99) includes:

IF converter for wall antenna gain (090-72050-71)

Wall antenna kit (093-72050-99) includes:

– Antenna, with 5.8 m of cable and SMA connector attached (112-00013-01)

– Antenna mounting bracket (070-00383-02)

OR

– Clamp tie mounts (128-00302-02) and cable ties (128-00500-05)

This antenna kit (990-72050-95) includes:

IF converter for wall antenna gain (090-72050-71)

Wall antenna kit (093-72050-95) includes:

– Antenna, with 2.4 m of cable and SMA connector attached (112-00013-03)

– Antenna mounting bracket (070-00383-02)

– Clamp tie mounts (128-00302-02) and cable ties (128-00500-05)

Wall antenna indoor lightning suppressor kit (093-72050-94) (optional) includes:

– Mounting bracket (070-00300-02)

– Surge protector (143-00018-01)

– RG59 cable, 0.78 m (060-72010-92)

Wall antenna L1 outdoor lightning suppressor kit (093-72050-93) (optional) includes:

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

53

Chapter 2 Engineering & Ordering

User-Supplied Tools and Materials

– Mounting bracket (070-00300-03)

– Surge protector (143-00018-02)

– RG316 cable, 3 m, SMA(m)-SMA(m) (060-00062-01)

User-Supplied Tools and Materials

Ensure that the user-supplied tools and materials listed below are on hand for installation, as applicable.

For Roof Antenna Installation

2.5 cm diameter galvanized metal pipe, used as a mast to mount the antenna.

Mast should be long enough to position the antenna above any metal object on the roof.

Screws to attach the lightning suppressor mounting plate.

Plumb line or bubble level.

Nonmetallic junction box for lightning suppressor (optional if lightning suppressor mounted indoors).

2. 5 cm diameter PVC pipe as conduit for outdoor cables.

PVC fittings appropriate to the installation and cable route.

Appropriate tools and materials for cutting and shaping PVC pipe.

PVC glue

4.114 mm (6 AWG) ground wire.

Spade lugs for 6 AWG ground wire.

Crimp tool for 6 AWG spade lugs.

Hardware to attach the ground wire to a valid earth ground.

Fire-stopping material to seal conduit hole in roof or wall.

Electrically conductive antioxidant compound (Kopr-Shield or equivalent) to coat exposed connections to prevent oxidation.

Tool to cut cable, if installation requires custom lengths of cable.

Phillips Screwdriver

Wrench

1/4 inch hex Allen wrench

54

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 2 Engineering & Ordering

User-Supplied Tools and Materials

For Mechanical Window Antenna Installation

Drill with bit of appropriate size and type to make pilot holes for the mounting screws

2 screws of appropriate size and type to attach the foot of the mechanical chassis to a window sill or wall near a window.

Screwdriver

Cable ties or other method of securing cable

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

For Self-Adhesive Window Antenna Installation

Drill with bit of appropriate size and type to make pilot holes for the mounting screws

4 screws of appropriate size and type to attach the IF converter to a wall or other mounting surface.

Screwdriver

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

For Wall Antenna Installation

Ladder, or safe method of reaching the antenna location on the exterior wall

Drill with bits of appropriate size and type to make pilot holes for the antenna mounting bracket screws, and to make a hole through the wall for the antenna cable

2 screws of appropriate size and type to attach the antenna mounting bracket to an exterior wall.

Screwdriver

Electrically conductive antioxidant compound (Kopr-Shield or equivalent) to coat exposed connections to prevent oxidation

Fire stopping material to seal the hole in the wall

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

For Shelf Installation

A Phillips-head screwdriver for installing the TimeSource 3600 Shelf in a rack

Four screws to mount the shelf in a rack

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

55

Chapter 2 Engineering & Ordering

User-Supplied Tools and Materials

Outputs, Power, and Miscellaneous

RG-58 coaxial cable for 1 PPS, 10 MHZ outputs

Ethernet 10BaseT cable for Ethernet port

Category 5 four-pair RS-422 cable, with RJ-45 connector for the TOD output,

RS-422–to–RS-232 TOD converter

RS-232 cable with DB-25 connector for the RS-422–to–

RS-232 TOD converter

RS-232 cable with DB-9 connector for COM2 port

4.115 mm (6 AWG) ground wire

1.47 mm (16 AWG) green insulated ground wire

1.47 mm (16 AWG) red insulated wire

1.47 mm (16 AWG) black insulated wire

56

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

This chapter is the sequential order of procedures for installation and power-up.

In This Chapter

Unpacking

Installing the Antenna

Installing the Shelf

Powering Up the TimeSource 3600

Installing and Using TimeWizard

Factory-Set Values

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

57

Chapter 3 Installing the TimeSource 3600

Unpacking

Unpacking

Use the procedures in the order they appear in this chapter to install the

TimeSource 3600. If any difficulties are encountered during the installation process, contact Symmetricom’s Customer Technical Assistance Center (CTAC). Refer to the

Technical Assistance section of the Troubleshooting chapter for telephone numbers.

CTAC includes Product Technical Support for technical information, and Customer

Service for information about an order, RMAs, and other information.

ESD Caution:

To avoid damage from electrostatic discharge (ESD), when handling electronic equipment, use local office procedures, including:

Use grounded wrist straps connected to equipment frame ground when handling cards.

Store cards only in antistatic packaging provided by the factory

Note:

Save packing material. All equipment returned

must be packed in the original packing material

. Contact Customer Service if additional packaging is needed.

Unpack equipment carefully; check for completeness against the purchase order.

Notify Symmetricom if items are missing.

Inspect equipment for shipping damage, including bent or loose hardware, and broken connectors.

If equipment was damaged in transit, contact Customer Service to request an RMA, and notify the carrier.

Installing the Antenna

Installing a Roof Antenna

Installation procedures are to follow local company procedures and the Installation

Job Specification.

Prior to installing the antenna, the site, antenna location, lightning suppressor location, lightning suppressor grounding point, cable route, and all other details should have been planned.

58

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

To install the antenna, refer to Figure 3-1 and perform

Procedure 3-1 . Ensure all

user-supplied materials are available.

Warning:

To prevent arcing, ensure that the lightning suppressor is placed away from electrical devices and cabling.

Notes:

Recommended grounding points include:

Valid roof ring ground system.

Cad weld to building structural steel.

Central office ground plate within 15 m of antenna cable entrance into building.

Order two cables or a single cable run can be made from the antenna to the TimeSource Shelf. The cable can then be cut at the lightning suppressor location, and TNC connectors attached to the cut ends of the cable. The “xx” in the part number indicates the cable length.

Figure 3-1.

Roof Antenna-to-Shelf Cabling

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

59

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-1. Mounting a Roof Antenna and Connecting the Cable

Step

1.

Procedure

Attach the antenna mounting bracket to a pipe (2.5 cm diameter) or a wood post.

If mounting the bracket to a pipe, slide the two V-bolts over the pipe, and through the mounting bracket slots; then place the provided four washers and four nuts over the

V-bolts, against the mounting bracket. Leave the V-bolts loose enough to allow for final adjustments.

Mounting

Bracket

Washers (4)

Nuts (4)

V-Bolts (2)

Pipe

If mounting the bracket to a wood post, use the provided two self-tapping screws in two diagonally positioned mounting bracket slots, and attach to the post.

Mounting

Bracket

Screws (2)

Post

60

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-1. Mounting a Roof Antenna and Connecting the Cable (Continued)

Step

2.

Procedure

Mount the antenna and mast assembly to the “L” bracket

Connect the mast to the flange using PVC glue.

Feed the cable through the bottom of the mast as illustrated.

Connect the cable to the antenna “pigtail” and pull the cable back through the mast.

Mount the antenna to the mast using the supplied shims.

Mount the antenna and mast assembly to the “L” bracket using the supplied nuts, bolts, and washers.

3.

4.

Using a plumb line or bubble level, ensure the antenna is within 5° of vertical (perpendicular to the horizon), and tighten the mounting bracket bolts.

Bolt the lightning suppressor mounting plate to a flange that is attached to a valid earth ground. The roof ring ground system, a Central Office grounding plate, and building structural steel are examples of valid earth ground points. If the mounting plate cannot be bolted to a valid earth ground, bolt the mounting plate to a point within 4.6 m of the chosen valid earth ground. If the mounting plate is to be installed in a nonmetallic junction box, perform the installation, and bolt the assembly near the chosen valid earth ground.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

61

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-1. Mounting a Roof Antenna and Connecting the Cable (Continued)

Step

5.

Procedure

Slide the longer bolt of the lightning suppressor through the D-hole, and attach with a nut and a washer (provided).

KEPS nut (2)

4.115 mm (6 AWG)

ground wire

Lightning Suppressor

Cable connector (2)

Nut

D-hole

Washer

Mounting plate

Hole for mounting bolt (2)

Threaded posts (3)

(use any 2)

6.

7.

8.

9.

Install a 2.5 cm nonmetallic conduit from the antenna to the lightning suppressor, and from the lightning suppressor to the cable entrance into the building.

Install a user-supplied bracket, preferably non-metallic, to support the vertical section of conduit to the antenna.

Connect a cable to the antenna, route the cable through the conduit, and connect the cable to the lightning suppressor.

Connect a cable to the lightning suppressor, route the cable through the conduit into the building, and route the cable through the building to the TimeSource 3600 Shelf location.

10.

If the lightning suppressor was not mounted directly to a valid earth ground, crimp a length of 4.115 mm (6 AWG) ground cable to the two-hole terminal, slide the terminal over two of the three threaded posts on the lightning suppressor mounting plate, and attach the terminal to the mounting plate with two KEPS nuts. Use the two posts that allow the least bending of the 4.115 mm (6 AWG) ground cable.

11.

Attach the other end of the cable to a valid earth ground.

12.

Install fire-stopping material in all holes opened in the roof and/or walls during this procedure.

13.

Check all connections for tightness to prevent arcing and intermittent operation.

14.

Coat all exposed connectors with an electrically conductive antioxidant compound (e.g.,

Kopr-Shield spray).

End of Procedure

62

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

installing a Mechanical Window Antenna

Installation procedures are to follow local company procedures and the Installation

Job Specification.

Prior to installing the antenna, the site, antenna location, cable route, and all other details should have been planned.

For best results, choose a window facing the equator (facing south in the northern hemisphere, facing north in the southern hemisphere), and with the fewest obstructions of the sky.

To install the antenna, refer to Figure 3-2 and perform

Procedure 3-2 .

Components of

990-72050-97 antenna assembly

Antenna

Antenna-to-IF cable

IF Converter

Antenna Assembly

990-72050-97

TNC Connector

(on IF converter)

TNC Connector

(Attached to cable)

TNC Connector

(Attached to cable, and on shelf)

TimeSource 3600 Shelf

IF-to-shelf cable

RG-59/U Cable

060-72010-xx

(3 m to 305 m) or

Mini RG-59 Cable

060-72050-xx

(15 m to 152 m)

Figure 3-2.

Mechanical Window Antenna-to-Shelf Cabling

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

63

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-2. Mounting a Mechanical Window Antenna and Connecting the Cable

Step Procedure

Prerequisite:

Observe all guidelines, considerations, Dangers, Warnings, Cautions, and Notes in the Engineering and Ordering chapter.

Symmetricom Parts:

Mechanical Window Antenna (990-72050-97)

A length of RG-59/U plenum-rated coaxial cable (060-72010-xx), or

A length of Mini RG-59/U plenum-rated coaxial cable (060-72050-xx)

User-Supplied Materials:

Drill with bit of appropriate size and type to make pilot holes for the mounting screws

Two screws of appropriate size and type to attach the foot of the mechanical chassis to a window sill or wall near a window

Screwdriver

Cable ties or other method of securing cable

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

1.

At the window chosen in Chapter 2, Engineering and Ordering, attach the base of the mechanical window antenna to the chosen location (sill, wall, etc.) using user-supplied

screws ( Figure 3-3 ).

2.

3.

4.

Use the pivots on the mechanical window antenna to place the antenna section flat against the window.

Tighten the pivot screws to secure the antenna ( Figure 3-4 ).

5.

6.

Connect the antenna cable to the IF downconverter on the mechanical window antenna assembly and route the cable to the TimeSource 3600 Shelf location.

Secure the cable using local company procedures.

Check all connections for tightness to prevent intermittent operation.

End of Procedure

64

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Use 2 user-supplied screws to attach to wall or window sill

Figure 3-3.

Attaching the Mechanical Window Antenna

Place the antenna against the window by moving the chassis on these pivots.

Tighten these pivot screws to lock antenna position.

Figure 3-4.

Mechanical Window Antenna Pivot Screws

Installing a Self-Adhesive Window Antenna

Prior to installing the antenna, the site, antenna location, cable route, and all other details should have been planned.

Installation procedures are to follow local company procedures and the Installation

Job Specification.

For best results, choose a window facing the equator (facing south in the northern hemisphere, facing north in the southern hemisphere), and with the fewest obstructions of the sky.

To install the antenna, refer to Figure 3-5 and perform Procedure 3-3 .

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

65

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Antenna

090-71010-87

Antenna-to-IF cable (3 m)

060-00062-01

SMA connector

(Attached to cable, and on IF converter)

IF converter

090-72050-72 and Mounting Kit

Antenna kit

990-72050-98

TNC connector

(Attached to cable, and on IF converter)

TNC Connector

(Attached to cable, and on shelf)

TimeSource 3600 Shelf

IF-to-shelf cable

RG-59/U Cable

060-72010-xx

(3 m to 305 m) or

Mini RG-59 Cable

060-72050-xx

(15 m to 152 m)

Figure 3-5.

Self-Adhesive Window Antenna-to-Shelf Cabling

Procedure 3-3. Mounting a Self-Adhesive Window Antenna and Connecting the Cable

Step Procedure

Prerequisite:

Observe all guidelines, considerations, Dangers, Warnings, Cautions, and Notes in the Engineering and Ordering chapter.

Symmetricom Parts:

Self-Adhesive Window Antenna kit (990-72050-98)

A length of RG-59/U plenum-rated coaxial cable (060-72010-xx), or

A length of Mini RG-59/U plenum-rated coaxial cable (060-72050-xx)

User-Supplied Materials:

Drill with bit of appropriate size and type to make pilot holes for the mounting screws

Four screws of appropriate size and type to attach the IF converter to a wall or other mounting surface

Screwdriver

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

1.

2.

Peel off the backing of one of the self-adhesive hook-and-loop strips and stick the strip to the antenna (

Figure 3-6

).

Attach the hook-and-loop side of the other strip to the hook-and-loop side of the strip on the antenna.

66

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-3. Mounting a Self-Adhesive Window Antenna and Connecting the Cable (Continued)

Step

3.

4.

5.

6.

7.

8.

Procedure

Peel off the backing and stick the antenna to the position on the window selected in

Chapter 2, Engineering & Ordering

.

Use user-supplied screws to mount the IF downconverter to a suitable wall or other structure (

Figure 3-7

). Be sure the distance along the cable route between the IF downconverter and the antenna is no more than 3 m.

Route and connect the antenna cable to the antenna side of the IF downconverter.

Connect a cable to the TimeSource 3600 shelf side of the IF downconverter and route the cable to the shelf location.

Secure the cable using local company procedures.

Check all connections for tightness to prevent intermittent operation.

End of Procedure

Attach the hook-and-loop fabric pieces together.

Stick the antenna to the window.

Figure 3-6.

Attaching the Self-Adhesive Window Antenna to a Window

Use 4 user-supplied screws to attach to a wall or other structure.

Figure 3-7.

Attaching the IF Converter

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

67

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Installing a Wall Antenna

Prior to installing the antenna, the site, antenna location, cable route, and all other details should have been planned.

Installation procedures are to follow local company procedures and the Installation

Job Specification.

For best results, choose a wall facing the equator (facing south in the northern hemisphere, facing north in the southern hemisphere), and with the fewest obstructions of the sky.

To mount the antenna through the wall, refer to Figure 3-8

and follow

Procedure 3-4

.

Antenna Mounting Bracket

070-00383-02

Antenna

112-00013-01

SMA connector

(Attached to cable, and on IF converter)

IF converter

090-72050-71 and Mounting Kit

TNC connector

(Attached to cable, and on IF converter)

TNC Connector

(Attached to cable, and on shelf)

Antenna kit

990-72050-95 (w/ 1.8 m antenna cable) or

990-72050-99 (w/ 5.8 m antenna cable)

IF-to-shelf cable

RG-59/U Cable

060-72010-xx

(3 m to 305 m) or

Mini RG-59 Cable

060-72050-xx

(15 m to 152 m)

TimeSource 3600 Shelf

Figure 3-8.

Wall Antenna-to-Shelf Cabling

68

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-4. Installing a Wall Antenna

Step Procedure

Prerequisite:

Observe all guidelines, considerations, Dangers, Warnings, Cautions, and Notes in the Engineering and Ordering chapter.

Symmetricom Parts:

Wall Antenna (990-72050-95 with 1.8 m antenna cable or 990-72050-99 with 5.8 m antenna cable)

Wall Antenna Indoor Lightning Suppressor Kit (093-72050-94) (optional)

Wall Antenna Outdoor Lightning Suppressor Kit (093-72050-93) (optional)

A length of RG-59/U plenum-rated coaxial cable (060-72010-xx), or

A length of Mini RG-59/U plenum-rated coaxial cable (060-72050-xx)

User-Supplied Materials:

Ladder, or safe method of reaching the antenna location on the exterior wall

Drill with bits of appropriate size and type to make pilot holes for the antenna mounting bracket screws, and to make a hole through the wall for the antenna cable

Two screws of appropriate size and type to attach antenna mounting bracket to an exterior wall

Screwdriver

Electrically conductive antioxidant compound (Kopr-Shield or equivalent) to coat exposed connections to prevent oxidation

Fire-stopping material to seal the hole in the wall

GPS handheld receiver, personal computer with GPS location software, or other method of determining latitude, longitude, and altitude

1.

2.

Attach the IF downconverter ( Figure 3-7

) inside the building to a suitable wall or other structure. Be sure the distance along the cable route between the IF converter and the antenna is no more than 1.8 m or 5.8 m depending on wall antenna cable length used.

Include allowances for the drip loop and local company procedures for cable routing.

Use Figure 3-9 to determine the spacing of the 2 holes for mounting the bracket, and the

distance to the hole for passing the cable into the building.

3.

4.

5.

6.

7.

Drill a 10-mm hole in the wall for the antenna cable. The diameter of the hole should be larger than the outer diameter of the SMA connector on the antenna cable, which will pass through the hole from the antenna to the inside of the building.

Drill two pilot holes for the user-supplied screws or bolts that attach the mounting bracket to the outside wall.

Using two screws or bolts, mount the antenna bracket assembly to the outside wall.

Place the magnetic side of the antenna on the outside of the mounting bracket.

8.

Push the SMA connector of the antenna cable through the hole drilled in the wall in

Step 3

Be sure the antenna cable forms a drip loop between the antenna and the cable entry into

the building ( Figure 3-10 ).

Route the antenna cable to the antenna side of the IF converter and connect the cable.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

69

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-4. Installing a Wall Antenna (Continued)

Step Procedure

9.

Connect a cable to the TimeSource 3600 shelf side of the IF converter and route the cable to the shelf location.

10.

Secure the cable using local company procedures.

11.

Install fire-stopping material in all holes opened in the roof and/or walls during this procedure.

12.

Check all connections for tightness to prevent intermittent operation.

13.

If no optional Lightning Suppressors are to be installed, the Wall Antenna Installation is complete.

14.

If the optional Wall Antenna Indoor Lighting Suppressor Kit (093-72050-94) is not required,

then go to Step 23 Otherwise, proceed with the next step.

15.

Mount the indoor lightning suppressor mounting bracket to the inside wall.

16.

Mount and secure the lightning suppressor in the lightning suppressor mounting bracket as shown in

Step 17

17.

Slide the longer bolt of the lightning suppressor through the D-hole, and attach with a nut and a washer (provided).

KEPS nut (2)

4.115 mm (6 AWG)

ground wire

Nut

D-hole

Washer

Lightning Suppressor

Cable connector (2)

Mounting plate

Hole for mounting bolt (2)

Threaded posts (3)

(use any 2)

18.

If the lightning suppressor was not mounted directly to a valid earth ground, crimp a length of 4.115 mm (6 AWG) ground cable to the two-hole terminal, slide the terminal over two of the three threaded posts on the lightning suppressor mounting plate, and attach the terminal to the mounting plate with two KEPS nuts. Use the two posts that allow the least bending of the 4.115 mm (6 AWG) ground cable.

19.

Attach the other end of the cable to a valid earth ground.

20.

Route the wall antenna cable to the antenna side of the IF converter and connect the cable.

21.

Connect the IF converter to the lightning suppressor using the 0.6 m RG-59 cable provided.

22.

Connect the user provided RG-59 cable from the lightning suppressor to the TimeSource

3600 shelf.

70

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

Procedure 3-4. Installing a Wall Antenna (Continued)

Step Procedure

23.

If the optional Wall Antenna Outdoor Lighting Suppressor Kit (093-72050-93) is not required, the Wall Antenna Installation is complete. Otherwise, proceed with the next step.

24.

Mount the outdoor lightning suppressor mounting bracket to the outside wall shown in

Figure 3-11

.

25.

Mount and secure the lightning suppressor in the lightning suppressor mounting bracket as shown in

Step 26

26.

Slide the longer bolt of the lightning suppressor through the D-hole, and attach with a nut and a washer (provided).

KEPS nut (2)

4.115 mm (6 AWG)

ground wire

D-hole

Nut

Washer

Lightning Suppressor

Cable connector (2)

Mounting plate

Hole for mounting bolt (2)

Threaded posts (3)

(use any 2)

27.

If the lightning suppressor was not mounted directly to a valid earth ground, crimp a length of 4.115 mm (6 AWG) ground cable to the two-hole terminal, slide the terminal over two of the three threaded posts on the lightning suppressor mounting plate, and attach the terminal to the mounting plate with two KEPS nuts. Use the two posts that allow the least bending of the 4.115 mm (6 AWG) ground cable.

28.

Attach the other end of the cable to a valid earth ground. Attaching to an earth ground located outside the building is the most desirable.

29.

Route the wall antenna cable to the antenna side of the outdoor lightning suppressor and connect the cable.

30.

Route the 3 m RG-316 cable provided from the outdoor lightning suppressor through the wall to the IF converter and connect both ends.

31.

Connect the user provided RG-59 cable from the IF converter to the TimeSource 3600 shelf.

32.

Install fire-stopping material in all holes opened in the roof and/or walls during this procedure.

End of Procedure

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

71

Chapter 3 Installing the TimeSource 3600

Installing the Antenna

8.6 cm

5 cm

2.5

Bracket mounting hole (2)

Antenna Cable hole

Figure 3-9.

Hole Spacing

Holes for bolts/screws

Mounting bracket

Antenna cable

Hole for cable

Antenna

Drip loop

Building exteri or

Figure 3-10. Wall Antenna Mounting

Wall

Building interior

72

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Mounting bracket

Antenna

Outdoor Lightning

Suppressor

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Wall

Hole for cable

RG-316 Cable (10 feet)

060-00062-01

IF Converter

Antenna cable

Drip Loop

Building exterior

Building interior

Grounding Cable to Outside Ground

Source

Figure 3-11. Wall Antenna Outdoor Lightning Suppressor Mounting

Installing the Shelf

Rack Mounting

The shelf is shipped with the ears positioned for ETSI 53.5 cm mounting as

illustrated in Figure 3-12A

. For 48 cm racks, the shelf can be positioned to the rear of the rack rail for flush mounting (

Figure 3-12B

) or to the front of the rack rail for 12.7 cm offset mounting (

Figure 3-12C

). Leave 1 RU (4.45 cm) of air space above the

TimeSource 3600 Shelf for proper ventilation. Mount the shelf in the rack according to standard company practices.

Note:

Two screws may be used in both mounting ears if the holes in the rack are spaced 4.45 cm apart.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

73

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Rack rails

Rear of rack

Top of shelf

Mounting ears

Rear of rack

Top of shelf

Top of shelf

Mounting ears

A. ETSI – 53.5 cm rack

Rack rails

Rear of rack

Top of shelf

Top of shelf

Rack rails

B. Flush mounting – 48 cm rack

Figure 3-12. Rack Mounting Options

Installing Output Modules

Mounting ears

C. 12.7 cm offset – 48 cm rack

12.7

cm

ESD Caution:

To avoid electrostatic discharge (ESD) damage, wear an ESD wrist strap when making connections to the connector panel.

Failure to observe this warning may result in equipment damage.

If you have an E1 8-output module, an IRIG-B 4-output module, or a ESCIU 2-port module supplied with the system, install the module as follows:

1. Remove the shelf cover to access the shelf connector panel.

2. Plug the module into the OPTIONS I/O connector on the connector panel (refer to

Figure 3-13 ).

3. Align the three spring-loaded screws on the module with the threaded holes on the panel.

4. Use a medium flat-blade screwdriver to lock each screw in place. Torque the screws evenly to prevent skewing the module.

74

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

OPTIONS I/O connector

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Threaded screw holes

Figure 3-13. Options I/O Connector

Making Power and Signal Connections

ESD Caution:

To avoid electrostatic discharge (ESD) damage, wear an ESD wrist strap when making connections to the connector panel.

Failure to observe this warning may result in equipment damage.

ESD Caution:

To avoid equipment damage, do not pierce, peel, or otherwise violate the integrity of the faceplate overlay. The faceplate on the card contains a plastic overlay bonded to the metal plate with an adhesive. The overlay is an integral part of the ESD protection.

Failure to observe this warning may result in equipment damage.

The Craft connection is made at the shelf front panel. All other connections are made at the shelf connector panel. To access the shelf connector panel, remove its cover.

Figure 3-14

shows the connectors on the front panel and connector panel. All connectors can be located using this illustration.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

75

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

10 MHz output

E1 outputs

A & B

(BNC)

1 pps output

E1 inputs A &

B

Com port 1

Time of day

Alarms

Com port 2

Battery A

& frame ground

(TB1)

Battery B

& frame ground

(TB2)

E1 outputs

A & B

(wire-wrap)

GPS antenna input

E1 inputs

A & B

(wire-wrap)

Expansion

Bus

(Reserved for future use)

Craft

Ethernet

Output Module:

8 E1 outputs (BNC or wire-wrap) or

4 IRIG-B TOD outputs (BNC) or

2 ESCIU ports (BNC or wire-wrap)

Figure 3-14. Connector Panel and Front Panel Connector

Making Frame Ground Connections

Frame ground connections are made on power terminal blocks TB1 and TB2. Refer

to Figure 3-14 for the location of the terminals on the shelf connector panel, and

refer to

Figure 3-15

for the terminal connections.

76

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

TB (1 or 2)

BATT (A or B)

RTN

N/C

Figure 3-15. Connector Panel Terminal Block Connections

Ensure the frame ground wires are long enough to reach from the shelf connector panel to the frame ground connection. Use one 1.47 mm (16 AWG) green insulated wire to connect the terminal of power terminal block TB1 to the frame ground, and use another 1.47 mm (16 AWG) green insulated wire to connect the terminal of TB2 to frame ground.

Make the ground connection, following one of the methods described below, depending on whether a ground rod is installed:

With ground rod

Solder the frame ground connection to the 4.115 mm (6 AWG) frame ground rod run vertically on each side of the rack. Two methods are acceptable:

Crimp an appropriate-size spade lug (user-supplied) to the 1.47 mm (16 AWG) wire, bend the lug around the 4.115 mm (6 AWG) rod, and solder.

Strip enough insulation from the 1.47 mm (16 AWG) wire to permit three complete turns around the 4.115 mm (6 AWG) rod, and solder.

Note:

When soldering, use a 25 watt soldering iron to ensure the

4.115 mm (6 AWG) rod is heated sufficiently to prevent a cold solder connection.

Without ground rod

Crimp the supplied spade lug to the 1.47 mm (16 AWG) wire, and screw the lug to a screw hole on the rack. Remove the paint and sand the area around the screw hole to ensure proper conductivity. Coat the connection with an electrically conductive antioxidant compound, for example, Kopr-Shield spray.

Crimp the supplied spade lug to the other end of the 1.47 mm (16 AWG) wire, and connect it to the

terminals on TB1 and TB2 ( Figure 3-15 ).

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

77

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Making Power Connections

Caution:

To avoid electrical shock and possible personal injury, power source protective fusing must be provided as part of the installation. This equipment is intended for installation in a restricted access location.

Caution:

To avoid damage to the system, do not apply power to the

TimeSource 3600 before instructed in this procedure. Before connecting the power cables to the TimeSource 3600, ensure the fuses are removed from the fuse panel that supplies power to the power cables.

Note:

Input power is reverse polarity protected; there are no user replaceable fuses in the TimeSource 3600.

Power connections are made on power terminal blocks TB1 and TB2. Refer to

Figure 3-14

for the location of the terminals on the shelf connector panel, and refer

to Figure 3-15 for the terminal connections.

Ensure the power wires are long enough to reach from the shelf connector panel to the office battery source connection.

Use two 1.47 mm (16 AWG) stranded wires for the power connection, one with red insulation (BATT), and the other with black insulation (RTN).

Connect the power wires with red insulation to the BATT (-48V) wire receptacles on

TB1 and TB2. Connect the power wires with black insulation to the RTN wire receptacles on TB1 and TB2.

Note:

Two separate office battery supplies (–48V A and –48V B) are recommended. If separate office battery supplies are not available, connect a single office battery to both inputs (TB1 and TB2) to avoid a standing battery-failure alarm.

GPS Antenna

Use the supplied 90 degree adapter to connect the coaxial cable from the lightning suppressor or IF downconverter to the TNC connector labeled GPS ANT. Refer to

Figure 3-14

for the connector location.

78

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

10 MHz Output

Connect a user-supplied RG-58 coaxial cable from the connector labeled 10 MHz to

the equipment that will use the 10 MHz output signal. See Figure 3-14

for the connector location.

E1 or Analog Synchronization Outputs

Caution:

To avoid damage to the system, do not connect the E1 output line directly to a point outside the building. The E1 output circuits do not provide lightning protection.

Connect the E1 or analog synchronization outputs at the wire-wrap pins or BNC connectors labeled E1 OUT A and E1 OUT B. If using the wire-wrap pins, connect the tip wire to the pins labeled T, the ring wire to the pins labeled R, and the shield to

the pins labeled S. See Figure 3-14

for the location of the connectors and pins, and

Figure 3-16

for the wire-wrap connections.

Notes:

1.

For wire-wrap connections, the shield pin is provided to ground the cable shield at the shelf, if required. Normally, the shield is grounded at the source. Grounding the shield at both ends is not recommended.

2.

A BNC connector can be used for one output, and a wire-wrap connector can be used for the other output, but do not use the

BNC and wire-wrap connectors of the same output simultaneously. For example, a BNC connector can be used for output A and the wire-wrap pins for output B, but do not use the output A BNC connector with the output A wire-wrap connector.

B

T

R

S

A

T

R

S

Figure 3-16. E1 or Analog Output Wire-Wrap Connections

1 PPS Output

Connect a user-supplied RG-58 coaxial cable from the connector labeled TTL PPS to the equipment that will use the 1 pulse-per-second TTL output signal. See

Figure 3-14

for the connector location.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

79

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Connecting E1 or Analog Reference Inputs

Caution:

To avoid damage to the system, do not connect the E1 output line directly to a point outside the building. The E1 output circuits do not provide lightning protection.

E1 or analog reference sources, traceable to an independent Stratum 1 source, can be connected to further increase holdover stability, or to be monitored by the

TimeSource 3600. In either case, connect reference inputs to the wire-wrap pins or

BNC connectors labeled SPAN IN A and SPAN IN B. If using the wire-wrap pins, connect the tip wire to the pin labeled T, the ring wire to the pin labeled R, and the

shield (if connected at the TimeSource 3600) to the pin labeled S. See Figure 3-14

for the location of the connectors and pins, and Figure 3-17

for the wire-wrap connections.

Notes:

1.

The shield pin is capacitively coupled to ground. Normally, the shield is grounded at the source. Grounding the shield at both ends is not recommended.

2.

A BNC connector can be used for one input, and a wire-wrap connector can be used for the other input, but do not use the

BNC and wire-wrap connectors of the same input simultaneously.

For example, a BNC connector can be used for input A and the wire-wrap pins for input B, but do not use the input A BNC connector with the input A wire-wrap connector.

B

T

R

S

A

T

R

S

Figure 3-17. E1 or Analog Input Wire-Wrap Connections

80

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Module for Additional E1 or Analog Outputs

(990-72060-02 System Only)

Connect up to eight optional E1 or analog outputs at the wire-wrap or BNC output

module. See Figure 3-14

for the connector location, and Figure 3-18

for the connections.

Note:

The shield pin is capacitively coupled to ground, therefore, the shield must be connected at the source end. The shield may also be connected at the TimeSource 3600 end for additional longitudinal noise protection.

Output 8

Output 5

Output 6

Output 3

Wire-Wrap

OUT 8

T

R

S

OUT 6

T

R

S

OUT 3

T

R

S

OUT 5

T

R

S

OUT 2

T

R

S

OUT 7

T

R

S

OUT 4

T

R

S

OUT 1

T

R

S

Output 7

Output 4

Output 2

Output 1

Output 8

Output 6

Output 4

Output 2

OUT 8

BNC

OUT 7

Output 7

OUT 6 OUT 5

Output 5

OUT 4 OUT 3

Output 3

OUT 2

OUT 1

Output 1

Figure 3-18. Eight E1 or Analog Input Connections

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

81

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Module for IRIG-B TOD Outputs

(990-72060-05 System Only)

Connect up to four optional IRIG-B TOD outputs at the output module. See

Figure 3-14

for the connector location, and Figure 3-19

for the connections.

OUT 8 OUT 7

OUT 6 OUT 5

Output 4

Output 2

OUT 4 OUT 3

Output 3

OUT 2 OUT 1

Output 1

Figure 3-19. IRIG-B TOD Output Connections

Note:

As shown in Figure 3-19

, outputs 5, 6, 7 and 8 are not used.

82

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Module for Mixed E1/T1 Outputs (990-72060-06 System Only)

Connect up to eight optional mixed E1/T1 outputs at the wire-wrap or BNC output

module. Refer to Figure 3-14 for the connector location and

Figure 3-20

for the connections.

Wire-Wrap

Output 8

Output 5

Output 6

Output 3

OUT 8

T

R

S

OUT 6

T

R

S

OUT 3

T

R

S

OUT 5

T

R

S

OUT 2

T

R

S

OUT 7

T

R

S

OUT 4

T

R

S

OUT 1

T

R

S

Output 7

Output 4

Output 2

Output 1

Output 8

Output 6

Output 4

Output 2

OUT 8

BNC

OUT 7

Output 7

OUT 6 OUT 5

Output 5

OUT 4 OUT 3

Output 3

OUT 2

OUT 1

Output 1

Figure 3-20. Eight Mixed E1/T1 Outputs Connections

Module for ESCIU Ports (990-72060-04 System Only)

The ESCIU ports ( Figure 3-21 ) have a different function than the synchronization

outputs. A synchronization output provides an all-ones reference clock signals for network elements. An ESCIU port carries live E1 traffic, and synchronizes the live traffic as it passes through. The ESCIU module can synchronize 2 spans in one direction. The return direction passes through as it is.

The ESCIU ports can connect at the digital distribution frame (DDF). The network elements receiving the ESCIU output signal must be able to receive E1 signals that conform to CCITT G.703 paragraph 6 specifications. The network element can be configured to extract its timing from the live E1 traffic signal.

A bypass relay directs E1 traffic around the ESCIU circuitry to maintain span continuity if a TimeSource 3600 fault occurs.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

83

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

RTN2 OUT

Span 2 NE return (not synchronized)

RTN2 IN

Span 2 to NE

(synchronized)

OUT

IN

SPAN 2

RTN1 OUT

RTN1 IN

OUT

IN

Span 1 NE return (not synchronized)

Span 1 to NE

(synchronized)

Span 2 NE return (not synchronized)

Span 2 toNE

(synchronized)

RTN2

SPAN 2

IN

T

R

S

OUT IN

RTN1

SPAN 1

T

R

S

OUT

IN

T

R

S

OUT

T

R

S

T

R

S

OUT

T

R

S

IN

Span 1 NE return (not synchronized)

Span 1 to NE

(synchronized)

SPAN 1

BNC Module Wire-Wrap Module

Figure 3-21. Connector Layout of ESCIU Modules

Cutover Procedures for Out-of-Service Equipment

If DDF access jack sets

are not

cabled to the ESCIU module, the following out-of- service cutover procedure must be used. Consult the local company Installation Job

Specifications to ensure that the network element to be retimed is connected to the

ESCIU module correctly. Refer to Figure 3-22

for the following procedure:

1. Remove from service (turn down) the traffic trunks on the E1 system to be cutover to the ESCIU module.

2. Remove the existing cabling in both directions between the transmit (OUT) and receive (IN) terminals of the NEs that will connect to the ESCIU module.

3. In the direction not to be synchronized by the ESCIU module, connect new cables from the ESCIU module RTNx IN connector to the NE transmit (OUT) terminal, and connect from the ESCIU module RTNx OUT connector to the NE receive (IN) terminal.

4. In the direction to be synchronized by the ESCIU module, connect new cables from the ESCIU module IN connector to the NE transmit (OUT) terminal, and connect from the ESCIU module OUT connector to the NE receive (IN) terminal.

5. Verify that there are no alarms on the NEs on the E1 system. If there are alarms, recheck the new cabling between the NEs and the ESCIU module.

Note:

If the TimeSource 3600 is still in warm-up or searching for GPS satellites, alarms may be present. All synchronization-related alarms should clear while the TimeSource 3600 is in steady-state operation.

84

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

6. Restore (turn up) the traffic trunks to service.

REMOVE EXISTING

CABLING

NETWORK

ELEMENT OR

FACILITY

NOT BEING

TIMED FROM

ESCIU

MODULE

RECEIVE

(IN)

TRANSMIT

(OUT)

RECEIVE

(IN)

TRANSMIT

(OUT)

NETWORK

ELEMENT

BEING TIMED

FROM

ESCIU

MODULE

RTN1 OUT

RTN1 IN

OUT

IN

SPAN 1

Existing cabling

Remove existing cabling

New cabling

Connection point

ESCIU

MODULE

Figure 3-22. ESCIU Cutover without Jacks (Out-of-Service)

Cutover Procedures for In-Service Equipment

If standard digital signal level access jack sets, such as DDF or DSX-1 jacks, were cabled to the ESCIU module, the following in-service cutover procedure must be used. Consult the local company Installation Job Specifications to ensure that the network element to be retimed from the ESCIU module is connected to the ESCIU module A OUT terminals. Refer to

Figure 3-23

for the following procedure:

1. Patch a bridging repeater from the MON jack of one NE to the IN jack of the other

NE in both directions of transmission on the E1 system to be cutover. Place a 75

Ω

termination plug in the OUT jack in each direction.

2. Remove the cross-connect wiring from the OUT and IN jacks (off-normal side of jacks) in both directions of transmission.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

85

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

3. In the direction not to be synchronized by the ESCIU module, connect new cables from the ESCIU module RTNx IN connector to the NE transmit (OUT) terminal, and connect from the ESCIU module RTNx OUT connector to the NE receive (IN) terminal.

4. In the direction to be synchronized by the ESCIU module, connect new cables from the ESCIU module IN connector to the NE transmit (OUT) terminal, and connect from the ESCIU module OUT connector to the NE receive (IN) terminal.

5. Remove the 75

Ω

(E1) termination plug from the OUT jack and patch cords from the NE IN jack. The E1 system bit stream is now going through the ESCIU module.

6. Verify that there are no alarms on the NEs on the E1 system. If there are alarms,

repeat Step 1

and recheck the cross-connect wiring. Repeat

Step 5 .

Note:

If the TimeSource 3600 is still in warm-up or searching for GPS satellites, alarms may be present. All synchronization-related alarms should clear while the TimeSource 3600 is in steady-state operation.

7. Remove the remaining patch cords from the NE MON jack.

86

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

PRIMARY

REFERENCE

T

E1

LINE

INTF

EQPMT

R

T

R

IN

OUT

MON

SECONDARY

REFERENCE

T

E1

LINE

INTF

EQPMT

R

T

R

IN

OUT

MON

3

3

1

2

3

Patch Cord

Bridging Repeaters

DSX-1 Jacks

Existing cabling to be removed

ESCIU cabling

OUT

IN

MON

Refer to In-Service

Equipment for procedures

MON

1

2

2

OUT

IN

T

R

T

E1

DIGITAL

INTERFACE

PORT

R

1

DIGITAL

SWITCH

MACHINE*

MON

1

2

2

OUT

IN

T

R

T

E1

DIGITAL

INTERFACE

PORT

R

1

RTN1 OUT

RTN1 IN

3

3

IN

OUT

IN

MON

OUT

SPAN 1

* Some digital switch machines designate two traffic-carrying E1 systems as their primary and secondary clock reference sources.

ESCIU

MODULE

Figure 3-23. ESCIU Cutover with Jacks (In-Service)

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

87

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Time of Day Output

Connect a time of day (TOD) output at the female RJ-45 connector labeled TOD.

See

Figure 3-14

for the connector location, and Table 3-1 for the connector pinouts.

Table 3-1. TOD Connector Pinouts

Pin Signal Abbreviation

3

4

1

2

1 pps A

1 pps B

12 V power source

Receive data B

TOD PPS +

TOD PPS –

TOD P12V

TOD RXD –

7

8

5

6

Receive data A

Circuit ground

Transmit data A

Transmit data B

TOD RXD +

TOD GND

TOD TXD +

TOD TXD –

Note:

Pins not listed are reserved for future use.

Direction

From TimeSource 3600

From TimeSource 3600

To TimeSource 3600

To TimeSource 3600

From TimeSource 3600

From TimeSource 3600

If the device receiving the time code (for example, Cisco router) accepts an RS-232 cable instead of an RS-422 cable, follow

Procedure 3-5

to install the

RS-422–to–RS-232 TOD converter.

Note:

Before performing

Procedure 3-5 , ensure that the appropriate

Cisco router or NTP Type 4 compatible device is installed, and power applied, per manufacturer’s instructions.

88

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Procedure 3-5. Installing the RS-422–to–RS-232 TOD Converter

Step

1.

2.

3.

4.

Procedure

Secure the provided mounting plate to the RS-422–to–RS-232 TOD converter, using the two provided screws. The plate may be attached to the top or front of the converter, depending on the desired surface (for example, a rack or cabinet) to which the converter

will be mounted (see Figure 3-24 ).

Notes:

1.

Due to distance constraints, the converter must be placed no more than 305 m from the

TimeSource 3600 Shelf, and no more than 15 m from the device receiving the time code.

2.

The converter dimensions are 7.5 cm by 3.8 cm by 2.5 cm.

3.

The mounting plate dimensions are 7.5 cm by 5 cm.

Secure the converter to the desired surface, using the slots in the plate and user-supplied bolts.

Install a user-supplied Category 5 four-pair RS-422 cable, with RJ-45 connectors on each end, between the TimeSource 3600 Shelf and the converter (see

Figure 3-25

).

Install a user-supplied RS-232 cable, with DB-25 connectors on each end, between the converter and the device receiving the time code (see

Figure 3-25

). See Table 3-2 for the

DB-25 connector pinouts.

End of Procedure

Screws

(supplied)

TOD

Mounting plate attached to top of converter

Converter

TOD

Converter

Mounting plate attached to front of converter

Screws

(supplied)

Figure 3-24. RS-422–to–RS-232 TOD Converter Mounting Plate

To device receiving time code

DB-25

Connector

(Female)

15 m max.

TOD

Converter

RJ-45

Connector

(Female)

305 m max.

To TimeSource

3600

Figure 3-25. RS-422–to–RS-232 TOD Converter Connections

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

89

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Table 3-2. Converter DB-25 Connector Pinouts

Pin Signal

5

7

1

3

Frame ground

Data output (RS-232)

1 pps (RS-232)

Signal ground

Note:

Pins not listed are reserved for future use.

Ethernet

Connect a user-supplied Ethernet cable from the network to the 10base-T Ethernet

connector labeled E-NET. See Figure 3-14 for the connector location, and

Table 3-3

for the connector pinouts.

7

8

5

6

3

4

1

2

Pin

Table 3-3. Ethernet 10base-T RJ-45 Connector Pinouts

Signal

Transmit data +

Transmit data –

Receive data +

Receive data –

Abbreviation

TXD +

TXD –

RXD +

RXD –

Direction

From TimeSource 3600

From TimeSource 3600

To TimeSource 3600

To TimeSource 3600

90

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Communication Port 1

To provide an RS-232 link for TL1 command access to the TimeSource 3600, connect to port 1 at the female 25-pin D connector labeled COM1. See

Figure 3-14

for the location of the connector. See Table 3-4 for the connector pinouts.

Note:

The COM1 connector transmits data on pin 2, and receives data on pin 3. Be sure the other equipment receives data from the transmitting pin, and transmits data to the receiving pin.

Table 3-4. COM1 Pinouts

Pin Signal Abbreviation

4

5

7

2

3

Transmit data

Receive data

Request to send

Clear to send

Signal ground

TXD

RXD

RTS

CTS

GND

20 Data terminal ready DTR

Note:

Pins not listed are reserved for future use.

Direction

From TimeSource 3600

To TimeSource 3600

From TimeSource 3600

To TimeSource 3600

From TimeSource 3600

Communication Port 2

To provide an RS-232 link for TL1 command access to the TimeSource 3600,

connect to port 2 at the female 9-pin D connector labeled COM2. See Figure 3-14

for the location of the connector, and Table 3-5 for the connector pinouts.

Note: The COM2 connector transmits data on pin 2, and receives data on pin 3. Be sure the other equipment receives data from the transmitting pin, and transmits data to the receiving pin.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

91

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Table 3-5. COM2 Connector Pinouts

Pin Signal Abbreviation

4

5

2

3

Transmit data

Receive data

TXD

RXD

Signal Ground GND

Data terminal ready DTR

7

8

Clear to send

Request to send

CTS

RTS

Note:

Pins not listed are reserved for future use.

Direction

From TimeSource 3600

To TimeSource 3600

From TimeSource 3600

To TimeSource 3600

From TimeSource 3600

Craft Port

To provide an RS-232 link for TL1 command access to the TimeSource 3600, connect to the craft port at the female RJ-45 connector labeled Craft on the front panel. A Craft-port-to-PC cable is supplied with the TimeSource 3600 for making this connection. See

Figure 3-14 for the location of the connector, and

Table 3-6

for the connector pinouts.

Note:

The Craft connector transmits data on pin 2, and receives data on pin 3. Be sure the other equipment receives data from the transmitting pin, and transmits data to the receiving pin.

92

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing the Shelf

Table 3-6. Craft Pinouts

Pin Signal Abbreviation

5

6

2

3

Transmit data

Receive data

Signal ground

Data terminal ready

TXD

RXD

GND

DTR

Note:

Pins not listed are reserved for future use.

Direction

From TimeSource 3600

To TimeSource 3600

From TimeSource 3600

Alarms Output

Connect the TimeSource 3600 alarms to the office alarm panel at the critical (CR),

major (MJ), and minor (MN) wire-wrap pins. See Figure 3-14

for the location of the

alarm pins, and Figure 3-26 for the connections.

Connect the upper group of pins (AUD) for audible alarms and the lower group of pins (VIS) for visible alarms. Connect the alarm circuit between the NO and C pins for normally open contacts, or between the NC and C pins for normally closed contacts.

CR MJ MN

NC

C

NO

NC

C

NO

Figure 3-26. Alarm Connections

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

93

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Powering Up the TimeSource 3600

To power the TimeSource 3600, follow the steps in

Procedure 3-6

. Before starting this procedure, be sure the antenna, shelf, and all connections appropriate for this installation have been installed, and that the host computer is set to communicate with the TimeSource 3600.

Note:

If using the TimeScan Craft software program for the power-up procedure, see the TimeScan Craft manual for the appropriate

TimeScan commands to use in place of the TL1 commands in

Procedure 3-6 .

Procedure 3-6. Power-Up

Step Procedure

Test Equipment:

Grounding wrist strap

Digital multimeter (Fluke 77 or equivalent)

Laptop computer with communications software (e.g., Windows Hyperterminal, ProComm Plus,

CrossTalk)

1.

On the computer connected to the TimeSource 3600, start a VT100 terminal mode session via communication software that supports the Y-modem protocol (such as

Hyperterminal, or a commercial package such as PROCOMM PLUS or CrossTalk).

2.

3.

4.

On the computer connected to the TimeSource 3600, set the communication software to communicate with the port that is connected to the TimeSource 3600.

On the computer connected to the TimeSource 3600, set the RS-232 communication parameters to 8 data bits, no parity bit, 1 stop bit, and 9600 baud.

On the computer connected to the TimeSource 3600, connect the computer communication port to the COM1, COM2, or Craft port on the TimeSource 3600. A craft port-to-PC communication cable is provided in the hardware kit for this purpose.

5.

6.

Ensure that the TimeSource 3600 plug-in card is not installed in the shelf.

Ensure that all fuses that supply power to the TimeSource 3600 Shelf are removed from the fuse panel.

94

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

10.

11.

12.

13.

14.

Step

7.

8.

9.

Procedure

At the shelf end of the battery leads, use the multimeter to measure the voltage between the following:

Test Point

Battery A lead

Battery A lead

Battery A lead

Battery B lead

Battery B lead

Test Point

Battery B lead

TB1: RTN A

TB1:

TB2: RTN B

TB2:

Result

0 V

0 V

0 V

0 V

0 V

Attach a grounding wrist strap to the wrist, and plug the other end into the ground jack at the upper-right corner of the front of the plug-in card.

Pull out the latching levers at each end of the front panel so that the levers are pointing directly out from the front panel.

Push the card into the shelf until the latching levers begin to move in.

Push the latching levers flat against the front panel to complete the card insertion.

Tighten the knurled screw above each latching lever to secure the card in the shelf.

Unplug and remove the grounding wrist strap.

Install the battery source fuse(s) in the rack fuse bay that supplies power to the

TimeSource 3600. The TimeSource 3600 enters its warm-up mode after approximately 60 s when power is applied. During the warm-up period, the following conditions exist:

Status GPS lamp is green

Status SYS lamp is off

E1 outputs are squelched, sending AIS (factory setting), or sending an SSM message, as specified in the ED-EQPT command

Additional eight

E1 outputs

(if equipped) are squelched, sending AIS (factory setting), or sending an SSM message, as specified in the ED-EQPT command

Four IRIG-B outputs (if equipped) are squelched

ESCIU ports (if equipped) are on (unreliable while Status SYS lamp is off)

10 MHz and 1 pps outputs are on (unreliable while Status SYS lamp is off)

TOD output is not enabled (factory setting)

Notes:

1.

The CRIT lamp and other alarm indication lamps may light. The host computer may display transient and standing alarm condition messages. Ignore alarms while the

Status SYS lamp is off during warm-up, unless alarms apply to inputs and outputs that were previously entered.

2.

TL1 commands may be entered during warm-up. Inputs and outputs can be enabled, and system parameters can be set or changed.

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

95

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

15.

16.

Procedure

Note:

If using the TimeScan Craft software program for the power-up procedure, see the

TimeScan Craft manual for the appropriate TimeScan commands to use in place of the

TL1 commands in this Procedure.

Use the Activate User command to log onto the system.

ACT-USER::TELECOM:<ctag>::TS3000!!;

Skip this step if the current unit is equipped with a roof antenna.

Use the Edit Equipment command to change the antenna locating mode to manual and to enter the latitude, longitude, and altitude. In manual mode, the survey process used to determine the antenna’s exact position starts with this information.

Note:

Enter data carefully. When entering degrees, an error of a single degree will cause the system location accuracy to be off by as much as 100 km.

ED-EQPT::GPS:<ctag>:::ANTMODE=MANUAL,MANLAT=a-b-c-d,

MANLONG=e-f-g-h,MANELEVALT=i; a – north (a = N) or south (a = S) of the equator b – degrees of latitude (b = 0 to 179) c – minutes of the degree (c = 0 to 59) d – decimal fraction of the minute (d = 000 to 999) e – east (e = E) or west (e = W) of the Greenwich Meridian f – degrees of longitude (f = 0 to 179) g – minutes of the degree (g = 0 to 59) h – decimal fraction of the minute (h = 000 to 999) i – elevation, or altitude, of the antenna in meters

Example command to set the latitude, longitude, and altitude of the antenna:

ED-EQPT::GPS:<ctag>:::ANTMODE=MANUAL,MANLAT=N-37-19-016,

MANLONG=W-121-59-246,MANELEVALT=12;

Notes:

1.

The TimeSource 3600 can find its position on the earth without latitude, longitude, and altitude entered, but the process may take several hours, and may not result in the position accuracy (within 200 m) required for the system to perform to specification. It is recommended that the information be obtained and manually entered by the user.

2.

Latitude, longitude, and altitude data can be obtained through the use of a GPS hand-held receiver (user supplied). Location mapping software is also available for personal computers, which can be used to obtain latitude and longitude. When the entered figures are within 200 m of the actual coordinates, the TimeSource 3600 typically delivers UTC traceable timing within 1 h of applying power. Warm-up times vary greatly depending on the window location and antenna placement.

3.

Obtain latitude, longitude, and altitude outdoors when using a GPS hand-held receiver, to ensure an accurate reading. Do not use the GPS hand-held receiver inside the building near the window or wall where the antenna will be installed. GPS hand-held receivers do not provide an accurate location reading when used indoors.

96

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

17.

18.

19.

20.

Procedure

If UTC time is desired, skip to

Step 18 . Use the Edit Date command to set the local date

and time.

ED-DAT:::<ctag>::yyyy-mm-dd,hh-mm-ss:MODE=LOCAL; yyyy – year (yyyy = 1998 to 2096) mm – month (mm = 01 to 12) dd – day (dd = 01 to 31) hh – hours (hh = 00 to 23) mm – minutes (mm = 00 to 59) ss – seconds (ss = 00 to 59)

Example command to set local time:

ED-DAT:::123::2000-06-15,14-25-00:MODE=LOCAL;

If UTC time is not desired, skip to

Step 19

Use the Edit Date command to set the system for UTC time.

ED-DAT:::<ctag>::yyyy-mm-dd:MODE=UTC; yyyy – year (yyyy = 2000 to 2099) mm – month (mm = 01 to 12) dd – day (dd = 01 to 31)

Example command to set UTC time:

ED-DAT:::123::2000-06-15:MODE=UTC;

Use the Retrieve Equipment command to identify whether and how the inputs have been provisioned.

RTRV-EQPT::ALL:<ctag>;

Notes:

1.

Observe those results with an <aid> of SPAN-a. If MONITOR=ALW appears for an input, that input has previously been entered. If ENSEMBLER=ALW appears for an input, that input has been set to be ensembled.

2.

Note the results of the Retrieve Equipment command to set the remaining parameters in this procedure.

3.

Factory default settings are found at the end of this Power Up procedure section.

If the results of

Step 19 indicate the span inputs (if used) are set as desired, skip to

Step 24 Use the Enter Equipment command to monitor each available span input, and to

specify whether those inputs are to be ensembled.

ENT-EQPT::SPAN-a:<ctag>:::ENSEMBLER=b; a – span input (a = A or B) b – whether this input is ensembled (b = ALW ensembles the input; b = INH inhibits the input from being ensembled)

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

97

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

21.

22.

23.

24.

Procedure

Use the Edit Equipment command to set the output signal framing format for the two standard E1 outputs, and set the mode for each E1 output during an alarm.

ED-EQPT::E1-a:<ctag>:::FRAMING=b,ALMOUT=c; a – E1 output (a = A or B) b – framing format (b = CAS, CAS4, CCS, or CCS4, or NONE for analog) c – E1 output during alarm (c = AIS, SQUELCH, or SSM) (for SSM, framing format must be CAS4 or CCS4)

If not using a 990-72060-02 system, skip this step. Use the Edit Equipment command to set the output signal framing format for each additional E1 output, and set the mode for each E1 output during an alarm.

ED-EQPT::OPT-a:<ctag>:::FRAMING=b,ALMOUT=c; a – E1 output module port (a = 1 to 8) b – framing format (b = CAS, CAS4, CCS, or CCS4, or NONE for analog) c – E1 output during alarm (c = AIS, SQUELCH, or SSM) (for SSM, framing format must be CAS4 or CCS4)

If not using performance monitoring, skip to

Step 24

. Use the Initialize Register command to reset the performance monitoring data to zero for all input E1 spans.

INIT-REG-EQPT::ALL:<ctag>::ALL;

If not using Ethernet, go to Step 28 . Use the Edit Equipment command while connected to

COM1, COM2, or the CRAFT port to set the IP address, subnetwork mask, and gateway address for the current TimeSource 3600 unit, as required for proper operation in the managed element network. (These parameters affect all Ethernet ports. The Ethernet port should be closed and all users logged off before issuing this command.)

ED-EQPT::TS3600:<ctag>:::IPNE=a, IPSUBNET=a, IPGATE=a;

IPNE=a – This unit’s IP address in the form a.a.a.a (each a is an independent value of 0 to

255)

IPSUBNET=a =Subnet mask in the form a.a.a.a (each a is an independent value of 0 to

255)

IPGATE=a – Gateway IP address in the form a.a.a.a (each a is an independent value of 0 to 255)

98

TimeSource 3600 User’s Guide 097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

25.

Procedure

Ports 5001, 5002, 5003 and 5004 on the TimeSource 3600 are used as though they were serial TL1 communication ports. The following values are set at the factory and appear at reset:

MONMSG – INH (monitors only the current port for messages)

KEEPALIVE = 0 – does not send a COMPLD message to keep connection open)

ENDOFTEXT = 0 – does not include an end-of-text code with a TL1 message)

ECHO = ALW – (echoes characters back to the sending terminal)

COMPRI = ALW1 – (normal communication, including autonomous messages)

AUTOLOGOFF = 20 – (does not log off the user during inactivity)

SWCONTROL = INH – (uses no flow control)

If these values require change, use the Edit Communications command to set communications parameters for TL1 communications.

ED-COM::COM-a:<ctag>:::[MONMSG=b[,]][KEEPALIVE=c[,]]

[ENDOFTEXT=d[,]][ECHO=b[,]][COMPRI=e[,]][AUTOLOGOFF=c[,]]

[SWCONTROL=b];

COM-a – User IP port (a = 5001, 5002, 5003 or 5004)

MONMSG=b – Monitors messages on all ports (b = ALW), or current port (b = INH)

KEEPALIVE=c – Inactive minutes until the unit sends a COMPLD message to keep the connection from being closed (c = 0 to 255)

ENDOFTEXT=d – Hex code added to responses before semicolon (d = 0 (disabled) to 9F)

ECHO=b – Echoes characters received so they appear on the user’s screen as typed

(b = ALW), or inhibits echo (b = INH)

COMPRI=e – Sets the communication port capabilities as follows:

ALW0 = normal communication, no autonomous messages

ALW1 = normal communication, autonomous messages

ALW2 = autonomous messages received, logged on or not

INH = closes connection and keeps port from use (command must go to another port) (if the port is in use, this command also logs off the user)

AUTOLOGOFF=c – Inactive minutes until the unit logs off the user, keeping the connection open (c = 0 to 255)

SWCONTROL=b – uses software (XON/XOFF) flow control (b = ALW), or no flow control

(b = INH)

097-72060-01 Revision J – June, 2007 TimeSource 3600 User’s Guide

99

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

26.

Procedure

If not using an Element Manager, skip to

Step 28 . If not using a separate port to send

autonomous messages to an Element Manager, skip to Step 27

. Use the Edit Equipment command to set the IP address and port address of the Element Manager. Port 5550 connects to this address when the TimeSource 3600 develops a TL1 autonomous message, sends any messages, and closes the connection. An alternate Element

Manager may be set up in case port 5550 cannot make a connection to the primary

Element Manager.

ED-EQPT::TS3600:<ctag>:::IPEM1=a,IPEM1PORT=b[,IPEM2=a]

[,IPEM2PORT=b][,IPINACT=c];

IPEM1=a – Primary Element Manager’s IP address in the form a.a.a.a (each a is an independent value of 0 to 255)

IPEM1PORT=b – Primary Element Manager’s Ethernet port address (b = 0 to 65535)

IPEM2=a – Alternate Element Manager’s IP address in the form a.a.a.a (each a is an independent value of 0 to 255)

IPEM2PORT=b – Alternate Element Manager’s Ethernet port address (b = 0 to 65535)

IPINACT=c – Disconnects from the Element Manager if an autonomous message is not developed during this number of 100-ms units of inactivity (0 to 10,000, where 0 deactivates the timer)

100 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

27.

Procedure

Use the Edit Communications command to set the communications parameters of port

5551. An Element Manager connects to port 5551 for TL1 command and response messages. The following values for port 5551 are set at the factory and appear at reset:

MONMSG=INH – (monitors only the current port for messages)

KEEPALIVE=0 – (does not send a COMPLD message to keep connection open)

ENDOFTEXT=0 – (does not include an end-of-text code with a TL1 message)

ECHO=INH – (does not echo characters received)

COMPRI=ALW1 – (normal communication, including autonomous messages)

AUTOLOGOFF=20 – (does not log off the user during inactivity)

SWCONTROL=INH – (uses no flow control)

If these values require change, use the Edit Communications command to set communications parameters for TL1 communications.

ED-COM::COM-5551:<ctag>:::[MONMSG=b[,]][KEEPALIVE=c[,]]

[ENDOFTEXT=d[,]][ECHO=b[,]][COMPRI=e[,]][AUTOLOGOFF=c[,]]

[SWCONTROL=b];

MONMSG=b – Monitors messages on all ports (b = ALW), or current port (b = INH)

KEEPALIVE=c – Inactive minutes until the unit sends a COMPLD message to keep the connection from being closed (c = 0 to 255)

ENDOFTEXT=d – Hex code added to responses before semicolon (d = 0 (disabled) to 9F)

ECHO=b – Echoes characters received so they appear on the user’s screen as typed

(b = ALW), or inhibits echo (b = INH)

COMPRI=e – Sets the communication port capabilities as follows:

ALW0 = normal communication, no autonomous messages

ALW1 = normal communication, autonomous messages

ALW2 = autonomous messages received, logged on or not

INH = closes connection and keeps port from use (command must go to another port) (if the port is in use, this command also logs off the user)

AUTOLOGOFF=c – Inactive minutes until the unit logs off the user, keeping the connection open (c = 0 to 255)

SWCONTROL=b – uses software (XON/XOFF) flow control (b = ALW), or no flow control

(b = INH)

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 101

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

28.

29.

30.

31.

32.

Procedure

If the results of

Step 19 indicate the antenna cable delay and elevation mask are set as

desired, skip to Step 29

. Use the Edit Equipment command to set the length of cable between the antenna and the TimeSource 3600 Shelf. This number should have been recorded during installation. Use the same command to set the antenna elevation mask angle.

ED-EQPT::GPS:<ctag>:::ANTCBLDLY=a,ANTELEVMASK=b; a – antenna cable delay in meters (a = 0 to 330) b – antenna elevation mask angle in degrees (b = 0 to 45) (see note below)

Note:

The antenna elevation mask is that portion of the sky from which the TimeSource

3600 masks out satellite signals, measured as an angle of elevation from the horizon.

Reflections or other anomalies may disturb signals received from an area of the sky that has obstructions, usually the area near the ground. Masking that part of the sky may allow the receiver to acquire GPS signals more quickly and accurately. Factory setting is 10.

If not using the TOD output, skip to Step 30

. Use the Edit Equipment command to set the

TOD output.

ED-EQPT::TS3600:<ctag>:::TOD=b; b – TOD format (b = Cisco or NTP4)

If not using ESCIU ports, skip to

Step 31 . Use the Edit Equipment command to specify

how the ESCIU performs during holdover:

ED-EQPT::TS3600:<ctag>:::BYPASS=a; a – E1 traffic bypasses the ESCIU circuitry (a = ALW) or continues to be synchronized during holdover (a = INH).

Use the Edit Equipment command to allow or inhibit alarm conditioning on the outputs.

Inhibiting the alarm conditioning forces the TimeSource 3600 to continue to output valid timing signals while in major alarm. This may be useful when testing, troubleshooting, or in installations where a TimeSource 3600 that is in major alarm may produce better timing signals than other sources (for example, offices without additional holdover clocks in a distribution shelf).

ED-EQPT::TS3600:<ctag>:::ALMCOND=b; b – alarm conditioning of the outputs (b = ALW or INH)

Use the Copy Memory command to copy the database from volatile to nonvolatile memory within the TimeSource 3600.

CPY-MEM:[tid]:TS3600:<ctag>::WKG,,AUX:DATA;

Note:

Although the database is automatically copied to nonvolatile memory once per hour, it is recommended that the Copy Memory command be executed each time the database is changed.

102 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Powering Up the TimeSource 3600

Procedure 3-6. Power-Up (Continued)

Step

33.

Procedure

When the GPS signals have been acquired and the outputs are stable enough to output a signal, the TimeSource enters a settling period. During the settling period, the following conditions exist:

Status GPS lamp is green

Status SYS lamp is green

Any Span lamp is green when its input is connected, entered, contains valid framing, and is usable for ensembling

All outputs are functioning according to specifications or in a slightly degraded mode

A TL1 autonomous “settling period” event message exists.

Notes:

1.

In roof antenna installations, the nominal time to reach normal operation (output a

PRS signal) is 20 min. If normal operation has not been reached after 40 min, refer to the Troubleshooting chapter.

2.

The settling period is the condition where this clock is beyond the warm-up state but not yet in steady state operation. Steady state operation is indicated by the clearing of the “settling period” event.

3.

In window or wall antenna installations, the nominal time to reach normal operation

(output a PRS signal) is variable, depending on the view of the sky and the satellite positions at the time of power-up, and may take up to several hours. If normal operation is not reached, refer to the Troubleshooting chapter.

4.

The TimeSource 3600 develops and sends timing within the PRS specification during normal operation and during any event (other than settling period) or minor alarm, but not during a major or critical alarm.

End of Procedure

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 103

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Installing and Using TimeWizard

The TimeWizard Software Installation application was created to facilitate installing software upgrades for the TimeSource 3600.

Procedure 3-7

shows how to install the TimeWizard application and how to use TimeWizard to download software upgrades.

Procedure 3-7. TimeWizard Installation and Operation

Step Procedure

Use this procedure to install the firmware in the TimeSource 3600 to configure the GPS and

Holdover alarms, using the TimeWizard application.

Requirements:

1.

A PC running Windows 95/98/NT 4.0/2000/XP.

2.

The TimeSource 3600 System CD provided.

Hardware Installation

1.

Connect the TimeSource 3600 to the PC with a serial cable.

Install the TimeWizard Software

2.

3.

4.

Insert the TimeSource 3600 System CD provided into the PC's CD-ROM drive.

If AutoRun is enabled on the PC, the CD should automatically launch the Install Shield wizard for installation of the TimeWizard application. If Install Shield launches, continue

with Step 5

. If Install Shield does not automatically launch, continue with the next step.

The Windows Explorer, double-click “setup.exe” in the root directory of the CD to start the

Install Shield wizard.

Follow the prompts in the Install Shield wizard to install TimeWizard in the preferred directory.

Continue with the next step after the TimeWizard installation is complete.

104 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step

5.

Procedure

From the Windows desktop, click

Start

,

Programs

,

TimeWizard

to start the TimeWizard application. When TimeWizard starts, the “TimeWizard” main screen appears:

6.

7.

The version of TimeWizard that is installed is indicated at the top right of the screen. The progress indicator at the bottom of the screen shows which of the seven screens you are currently viewing.

Note:

The factory default TimeSource username of “telecom” and password of “TS3000!!” appear in the Login Information area of the screen.

If the user name or password of the TimeSource have been changed, enter the proper user name or password, otherwise, continue with the next step.

To select the high-speed download option, in which the firmware download takes place at approximately 12 times the default speed of 9600 baud, select the Use High Speed (115K baud) check-box, then click

Next>>

to progress to the next screen.

If you do not wish to use the high-speed download option, leave the Use High Speed (115K baud) check-box unselected and click

Next>>

.

Note:

In most cases, it is desirable to proceed with the Use High Speed (115K baud) check-box selected. In certain instances, as when the PC’s communications port does not support a 115K baud rate, de-select the Use High Speed (115K baud) check-box before proceeding.

Download the GPS.hex Firmware

Note:

If you are not downloading GPS.hex firmware, click

Next>>

again to advance to the

“Download TS3000.hex” screen, then skip to Step 13 .

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 105

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step

8.

Procedure

After you click

Next>>

in Step 7 , the “Download GPS.hex” screen appears:

9.

The versions of the GPS.hex and TS3000.hex firmware that are currently installed in the

TimeSource are shown in the GPS.hex Ver and TS3000.hex Ver fields. Current satellite information is shown in the GPS Status field.

Click

ver Unknown

to open the Load GPS File dialog box:

106 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

10.

In the Load GPS File dialog box, navigate to the GPS.hex firmware file to be downloaded, then click

Open

.

The message “

Verifying version for C:\

directory

\Gps.hex (approx 10 secs)

” appears in the Command area of the screen. Once TimeWizard has verified that the version of the firmware is correct, the text on the

ver Unknown

button changes to show the version of the firmware to be downloaded.

After TimeWizard verifies the firmware version, select the Download GPS.hex check-box, then click

Next>>

to start downloading the firmware.

11.

When the firmware download operation starts, the Download Progress dialog box appears:

As the download operation proceeds, the value in the Packet field increases, and the

Progress bar shows the progress of the operation. When the firmware download is complete, the Download Progress dialog box closes.

After

the Download Progress dialog box closes, continue with the next step.

Notes:

1.

The firmware download operation can be aborted at any time by clicking the Cancel button in the Download Progress dialog box.

2.

If the download fails for any reason, a screen appears with instructions to contact

Symmetricom. If this happens, exit the application, check the cable connections, and restart TimeWizard.

12.

After the Download Progress dialog box closes, continue to monitor the messages reported in the Commands area of the screen.

After the firmware file finishes downloading from the PC to the TimeSource, the

TimeSource requires more time to complete the firmware upgrade process. During this time, it should not be interrupted. When the firmware upgrade is fully complete, TimeWizard automatically advances to the next screen.

After the screen automatically advances, continue with the next step.

Download the TS3000.hex Firmware

Note:

If you are not downloading TS3000.hex firmware, click

Next>>

again, then skip to Step 18

.

13.

The “Download TS3000.hex” screen appears very similar to the “Download GPS.hex” screen shown in

Step 8 , and contains the same information.

14.

Click

ver Unknown

to open the Load TS3000 File dialog box, which appears very similar to

the dialog box shown in Step 9

.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 107

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

15.

In the Load TS3000 File dialog box, navigate to the TS3000.hex firmware file to be downloaded, then click

Open

.

The message “

Verifying version for C:\

directory

\ts3000.hex (approx 30 secs)

” appears in the Command area of the screen. Once TimeWizard has verified that the version of the firmware is correct, the text on the

ver Unknown

button changes to show the version of the firmware to be downloaded.

After TimeWizard verifies the firmware version, select the Download TS3000.hex check-box, then click

Next>>

to start downloading the firmware.

16.

When the firmware download operation starts, the Download Progress dialog box appears.

As the download operation proceeds, the value in the Packet field increases, and the

Progress bar shows the progress of the operation. When the firmware download is complete, the Download Progress dialog box closes.

After

the Download Progress dialog box closes, continue with the next step.

Notes:

1.

The firmware download operation can be aborted at any time by clicking the Cancel button in the Download Progress dialog box.

2.

If the download fails for any reason, a screen appears with instructions to contact

Symmetricom. If this happens, exit the application, check the cable connections, and restart TimeWizard.

17.

After the Download Progress dialog box closes, continue to monitor the messages reported in the Commands area of the screen.

After the firmware file finishes downloading from the PC to the TimeSource, the

TimeSource requires more time to complete the firmware upgrade process. During this time, it should not be interrupted. When the firmware upgrade is fully complete, TimeWizard automatically advances to the next screen.

Note:

After the TS3000.hex download operation successfully completes, the TimeSource reboots so that it can use the newly installed firmware. Upon rebooting, the system’s output might enter the degraded region of the PRS mask for up to one hour. For systems equipped with a Rubidium internal oscillator, the system output will be within the PRS mask if the unit has been in service and alarm free for more than 24 hours. Systems with Rubidium oscillators are the 090-72050-xx and the 090-72060-xx.

After the screen automatically advances, continue with the next step.

108 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

Verify the Firmware Versions

18.

The “Status Information” screen appears as follows:

Verify that GPS.hex Ver and TS3000.hex Ver fields show that the correct versions of the

GPS.hex and TS3000.hex firmware are now installed, then click

Next>>

.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 109

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

Setup the Alarm Parameters

19.

The “Set the Alarm Parameters” screen appears:

The Load and Save buttons allow a file to be generated that saves the alarm parameters in a file called TS3Kconf.sym as default. The file name for a configuration can be saved by selecting the Save button and providing a file name.

The Load button allows the user to load a saved file that will automatically configure the Alarm Parameters screen.

This screen allows the parameters for GPS and Holdover alarm conditions to be modified. If you do not want to modify any of the alarm parameters, click

Next>>

and continue with

Step 21

Otherwise, continue with the next step.

110 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

20.

Choose the alarm parameters as desired. When you are finished modifying the alarm parameters described below, click

Next>>

.

Setting and Description

Severity 1 – The initial severity of the alarm.

Service Affecting 1 – The initial service affecting status of the alarm condition.

Time to Severity 2 – If the Escalate Alarm check-box is selected, the alarm will be escalated to the severity and service affecting status selected under Severity 2 and Service Affecting

2, after the time period selected under Hours and Mins has been reached. If the Escalate

Alarm check-box is not selected, the alarm will not be escalated.

Severity 2 – The severity of the alarm after it has been escalated.

Service Affecting 2 – The service affecting status of the alarm condition after the alarm has been escalated.

21.

The “View the Alarm Parameters” screen appears.

This screen confirms the alarm parameter settings from the previous screen.

If the settings are correct, click

Next>>

to continue. If the settings are not correct, click

<<Back

to return to the “Set the Alarm Parameters” screen, and correct the settings.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 111

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

Save the Log File, if Desired

22.

The “Exit Application” screen appears.

This screen allows you to save the log file from the download operation, or exit TimeWizard without saving the log file.

If you do not wish to save the log file, ensure that the Save Log File to check-box is not selected, then click

Exit

to complete the TimeWizard firmware installation procedure. To save the log file, continue with the next step.

112 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Installing and Using TimeWizard

Procedure 3-7. TimeWizard Installation and Operation (Continued)

Step Procedure

23.

Select the

Save Log File to

check-box, then click the button that is adjacent to the check-box to invoke the Save Log File dialog box:

24.

In the

Save Log File

dialog box, navigate to the location to where the log file is to be stored, enter a name for the log file into the

File Name

field, then click

Save

to save the log file.

25.

Click

Exit

to complete the TimeWizard firmware installation procedure.

End of Procedure

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 113

Chapter 3 Installing the TimeSource 3600

Factory-Set Values

Factory-Set Values

The parameter values initially set at the factory are shown in Table 3-7 .

Table 3-7. Parameter Factory Settings

<aid>

TS3600

TS3600

HOLDOVER

ALARM

TS3600 GPS

ALARM

GPS

Parameter Setting

TOD=NONE

ALMCOND=ALW

IPNE=0.0.0.0

IPSUBNET=255.255.255.255

IPGATE=0.0.0.0

IPEM1=0.0.0.0

IPEM1PORT=0

IPEM2=0.0.0.0

IPEM2PORT=0

IPINACT=0

BYPASS=ALW (990-72060-04 systems only)

DCDPASSTHRU=INH

DCDUSERPORT=2

TIME=72-0

SEV1=EV

SEV2=MJ

SAFF1=NSA

SAFF2=SA

TIME=10-0

SEV1=EV

SEV2=MN

SAFF1=NSA

SAFF2=NSA

ANTCBLDLY=0

ANTELEVMASK=10

ANTMODE=AUTO

MANLAT=N-0-0-0

MANLONG=W-0-0-0

MANELEV=0

114 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Table 3-7. Parameter Factory Settings (Continued)

<aid>

SPAN-A,

SPAN-B

SPAN-A,

SPAN-B LOS

ALARM

SPAN-A,

SPAN-B AIS

ALARM

Parameter Setting

ENSEMBLER=INH

MONITOR=INH

SSM=INH

SIGNAL=DIGITAL

SSMCHANNEL=4

TIME=24-0

SEV1=EV

SEV2=MN

SAFF1=NSA

SAFF2=NSA

TIME=24-0

SEV1=EV

SEV2=MN

SAFF1=NSA

SAFF2=NSA

SPAN-A,

SPAN-B

ERROR ALARM

TIME=24-0

SEV1=EV

SEV2=MN

SAFF1=NSA

SAFF2=NSA

E1-A,

E1-B

COM-1,

COM-2,

COM-3

FRAMING=CAS4

ALMOUT=AIS

BAUD=9600

MONMSG=INH

KEEPALIVE=0

ENDOFTEXT=00

ECHO=ALW

COMPRI=ALW1

AUTOLOGOFF=20

HWCONTROL=INH

SWCONTROL=INH

PARITY=NONE

STOP=1

097-72060-01 Revision J – June, 2007

Chapter 3 Installing the TimeSource 3600

Factory-Set Values

TimeSource 3600 User’s Guide 115

Chapter 3 Installing the TimeSource 3600

Factory-Set Values

Table 3-7. Parameter Factory Settings (Continued)

<aid>

COM-5001,

COM-5002,

COM-5003,

COM-5004

COM-5551

Parameter Setting

MONMSG=INH

KEEPALIVE=0

ENDOF TEXT=00

ECHO=ALW

COMPRI=ALW1

AUTOLOGOFF=20

SWCONTROL=INH

MONMSG=INH

KEEPALIVE=0

ENDOFTEXT=00

ECHO=INH

COMPRI=ALW1

AUTOLOGOFF=20

SWCONTROL=INH

FRAMING=CAS4

ALMOUT=AIS

OPT-1, OPT-2,

OPT-3, OPT-4,

OPT-5, OPT-6,

OPT-7, OPT-8

(990-72060-02, and

990-72060-06, systems only)

OPT-1, OPT-2

(990-72060-04 systems only)

ALMOUT=AIS

MONITOR=ALW

116 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

This chapter provides information for using the TL1 language.

In This Chapter

Conventions

Command Format

Response Format

Parameters

Autonomous Messages

Tasks/Commands

Commands

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 117

Chapter 4 TL1 Reference

Conventions

Conventions

Uppercase letters in a command designate parameter values which must be entered as shown. Lowercase letters in a command are the parameter name, and

the specific values that must be entered for the parameter. Parameters , on page

120 describes the parameters and the values where a value is the same for all

parameters. Parameter values for a particular command are listed with the command. The system accepts either uppercase, lowercase, or a mixture of both, but upper and lower case cannot be mixed within a parameter block.

The following symbols are used in the input and response messages:

|

[ ] encloses an optional parameter

{ } encloses a group of parameters, at least one of which must be entered separates alternatives in a group of parameters, at least one of which must be entered

,

^ indicates a space (used in the description of the response format, but not used in the command responses)

:

– separates command code fields separates parameter blocks separates parameters within a block

; terminates a command, and causes execution

" " encloses text to be parsed by a machine

/* */ encloses comments for humans

< > encloses a TL1 named variable

\" \" encloses a description of a condition

...

indicates the previous line in a response may be repeated as required

Command Format

A command consists of a command code of up to three fields separated by hyphens, followed by parameter blocks separated by colons.

Figure 4-1 shows the

command format. Parameter blocks consist of one or more parameters separated by commas.

118 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Response Format

Parameter blocks may be null (contain no parameters), or contain one or more parameters. Two colons occur next to each other if a parameter block is null.

Multiple parameters in a parameter block are separated by commas. Two commas occur next to each other if a parameter is null.

Entering a semicolon at the end of the command indicates that the command statement is completed to the interpreter, and executes the command.

Fields

Null parameter block

Parameter block, with parameters separated by a comma

command-code:[<tid>]::<ctag>::<date>,<time>;

Command code

Optional parameter

Parameter block

Figure 4-1.

Command Format

Response Format

Terminating semicolon

When a command is received and processed, a response is returned. All responses include a source identifier (<sid>), the date, the time, an M to indicate that it is a response to a command, and the correlation tag (<ctag>) that was entered with the command.

Figure 4-2

shows the completed response format. COMPLD indicates that the command was completed without error.

Note:

If the command was a query, additional information would be displayed before the semicolon.

^^^<sid>^<date>^<time>

M^^<ctag>^COMPLD

^^^/*LINK:<link>,CMD:<co mmand>*/

Figure 4-2.

Completed Response Format

Figure 4-3

shows the denied response format. DENY indicates that the command was denied due to an error. The <errcde> parameter indicates the corresponding error type, or cause of the error.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 119

Chapter 4 TL1 Reference

Parameters

^^^<sid>^<date>^<time>

M^^<ctag>^DENY

^^^<errcde>

^^^/* <error message> */

^^^/*LINK:<link>,CMD:<co

Figure 4-3.

Deny Response Format

Parameters

The parameters that may be used in commands, responses, and messages are

defined in Table 4-1 . When a parameter uses the same values in every instance,

those values are listed with the parameter in the table. When the context requires different values for a parameter, the value is listed with the parameter in the applicable commands, responses, and messages.

Table 4-1. Parameter Definitions

Parameter

<aid>

<almcde>

<atag>

<command>

<conddescr>

<condeff>

<condtype>

<ctag>

<date>

Definition

Access identifier for the object of the command or message. It may have more than one part.

Alarm code. Identifies the severity of the alarm based on its priority of action. If multiple alarms are reported, almcde is the highest severity of those reported.

Automatic message tag. It is incremented by one for each autonomous message.

The <atag> value is a whole number from 001 through 999, which is reset to 001 at reset or when it rolls over.

Echo of the entered command.

Text description of the condition. The <conddescr> value is limited to

64 characters starting and ending with a back slash and a double quotation mark

(\"). Refer to

Chapter 5, Troubleshooting for the list of values.

Effect on the condition of the equipment.

Type of alarm condition.

Correlation tag used to correlate input and response messages. The ctag contains 1 to 6 characters. It must be included in a command, and the same ctag is returned in the response.

Date in the 8-digit form: yyyy-mm-dd (command) or yyyy:mm:dd (response or message), where yyyy is the year, mm is the month (01 to 12), and dd is the day of the month (01 to 31). For example, May 3, 2000 is 2000-05-03.

120 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Parameters

Table 4-1. Parameter Definitions (Continued)

Parameter

<errcde>

Definition

Four-character mnemonic error code, which is one of the following:

EFON = equipment feature option not provided

ENEQ = not equipped

ICNV = command not valid

IDNV = invalid data in command

IDRG = invalid data range in command

IIAC = invalid aid in command

IICT = invalid correlation tag

IIDT = invalid data parameter in command

IISP = invalid syntax or punctuation

PIUI = invalid or duplicate uid or pid (privileged users only)

RALB = All units of requested type are busy

RCBY = circuit is busy

SCSN = invalid command sequence

SDBE = internal database error

SNIS = not in service

SNVS = not in a valid state

SRCN = requested condition currently exists

SRQN = request invalid

SWFA = working unit failed

Error code text message.

<error message>

<link>

<modifier>

<mondat>

<montm>

<montype>

<monval>

<ntfcncde>

Communication link identifier.

Equipment initiating the alarm or event message, which is one of the following:

TS3600 = system software

GPS = GPS receiver software

SPAN-x = E1 span input

Date of the performance monitoring data.

Time of the performance monitoring data.

Data type of the performance monitoring data.

Value of the performance monitoring data.

Notification code showing the alarm severity, which is one of the following:

<ocrdat> Occurrence date in the 8-digit form: yyyy-mm-dd (command) or yyyy:mm:dd

(response or message), where yyyy is the year, mm is the month (01 to 12), and dd is the day of the month (01 to 31). For example, May 3, 2000 is 2000-05-03.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 121

Chapter 4 TL1 Reference

Parameters

Table 4-1. Parameter Definitions (Continued)

Parameter Definition

<ocrtm>

<pid>

<sid>

<spec_block> Replaced by a number of parameters within the command. Parameters are in the format <name>=<value>, may be entered in any order, and must be separated by a comma.

<srveff>

Source identifier of the equipment sending the message. The <sid> may contain a maximum of 20 characters (limited to letters, digits, and hyphens), and may begin with a letter. The <sid> is recommended to be the equipment’s CLLI code.

Identifies whether the alarm condition is service affecting:

SA = service affecting

NSA = not service affecting

<tid> Target identifier of the equipment to which the command is directed. The tid must be a valid TL1 identifier of a maximum of 20 characters (limited to letters, digits, and hyphens) beginning with a letter. The <tid> is recommended to be the target's

CLLI code, and can also be used as the <sid>. The <tid> can be null if the OS directly interfaces to the target. The <tid> can be omitted only if connection is made directly to a single TimeSource 3600 Shelf.

<time>

Occurrence time in the 6-digit form: hh-mm-ss (command) or hh:mm:ss (response or message), where hh is hours (00 to 23), mm is minutes (00 to 59), and ss is seconds (00 to 59). For example, 2:34 pm is 14:34:00.

Private identifier, factory-set to “TS3000!!”. It is the initial password for the

TELECOM <uid>. Passwords are encrypted when stored in the TimeSource

3600, and are never transmitted from the shelf. The pid contains a case-insensitive string of 8 to 10 ASCII characters, and must include at least one letter, one numeral, and one special character from the following:

! " $ % & ' ( ) * + - . / < > ? @

<uap>

<uid>

<uout>

<utc>

<vldty>

Current time in the six-digit form: hh-mm-ss (command) or hh:mm:ss (response or message), where hh is hours (00 to 23), mm is minutes (00 to 59), and ss is seconds (00 to 59). For example, 5:11:49 a.m. is 05:11:49.

User access level, used by a system administrator to assign a given level of access to system users. User access level ranges from 1 to 5, with 1 being the lowest access level, and 5 being the highest access level.

User identifier, factory-set to TELECOM. The <uid> contains alphanumeric, case-insensitive strings of 6 to 10 characters provisioned as valid login IDs.

User inactivity password which indicates the number of days a system user has not logged on to the system. The user inactivity timeout range is 0 to 180 days, with 0 indicating no timeout.

Universal Coordinated Time (UTC) in the 6-digit form: hh-mm-ss, where hh is hours (00 to 23), mm is minutes (00 to 59), and ss is seconds (00 to 59). For example, 2:34 pm is 14-34-00.

Validity of the performance monitoring data.

122 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Autonomous Messages

Autonomous Messages

Autonomous messages are sent out when an alarm or event occurs. Two types of autonomous messages are used:

Report Alarm: reports alarms

Report Event: reports events that are not alarms, or that have not yet become alarms

Autonomous messages are listed on the following pages. After the message name, a definition of the message is given.

Report Alarm

This autonomous message appears when an alarm is raised, and appears again when the alarm is cleared.

Message:

^^^<sid> <date> <time>

M^^<almcde> <atag> REPT ALM EQPT <modifier>

^^^"<aid>:<ntfcncde>,<condtype>,<srveff>,

<ocrdat>,<ocrtm>,,,:\"<conddescr>\

"[:<dgntype>]"

Note:

Refer to Table 4-1 for parameter definitions.

Report Event

This autonomous message appears when an event is raised, and again when the event is cleared; also appears when a transient event occurs. An event is a state of the TimeSource 3600 that does not cause an alarm.

Message:

^^^<sid> <date> <time>

M^^<atag> REPT EVT EQPT <modifier>

^^^"<aid>:<condtype>,<condeff>,<ocrdat>,<ocrtm>

,,,,:\"<conddescr>\"[:<dgntype>]"

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 123

Chapter 4 TL1 Reference

Tasks/Commands

Note:

Refer to Table 4-1 for parameter definitions.

Tasks/Commands

To perform each task, use the command listed beside that task in

Table 4-2

.

Table 4-2. Commands for Tasks

Task

Log user onto system

Log user off of system

Copy software program or database

Delete equipment from the database

Delete a user from system

Change communication port parameters

Change the system date and time

Change equipment parameters

Enter equipment into the database and allow the equipment to be used for monitoring

Enter a new user and configure the new user’s user name, password, and access level

Reset the alarm log

Reset to zero all performance monitoring parameters associated with a given aid

Reset the system processor or GPS receiver processor

Deactivate the audible office alarm

Command

Activate User

Cancel User

Copy Memory

Delete Equipment

Delete User Security

Edit Communication

Edit Date

Edit Equipment

Enter Equipment

Enter User Security

Initialize Log

Initialize Register

Initialize System

Display current system alarms

Display current alarms for specific equipment

Display current communication port parameter settings

147

148

149

150

Operate Alarm Cutoff

All

Retrieve Alarm All

Retrieve Alarm

Equipment

Retrieve

Communication

151

152

153

154

Page

126

127

128

130

131

132

135

137

146

124 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Table 4-2. Commands for Tasks (Continued)

Task Command Page

Display current system alarms and events

Display current alarms and events for specific equipment

Display parameter settings of equipment

Display GPS status information

Display header information

Display information about equipment

Display alarm log data

Display performance monitoring data

Display the current users logged in to each port that is currently being used

Display security parameters for a single user or for all users

Set the name of the equipment

Retrieve Condition All

Retrieve Condition

Equipment

Retrieve Equipment

Retrieve GPS Status

Retrieve Header

Retrieve Inventory

Retrieve Log

Retrieve Performance

Monitoring

Retrieve Status

Security

Retrieve User Security

Set Source Identifier

157

158

159

166

168

169

171

172

180

181

182

Commands

The commands used with the TimeSource 3600 are listed on the following pages.

After the command name, a definition of the command is given. The definition is followed by the actual command, followed by the variables that can be used with the command.

The response format shows how the response will appear, with additional definitions of the response parameters where required.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 125

Chapter 4 TL1 Reference

Commands

Activate User

This command logs the user onto the system and begins a session. The factory-set user name is “TELECOM”, and the factory-set password is “TS3000!!”. The user name and password are not case sensitive (either uppercase or lowercase can be used). The command format is:

ACT-USER:[<tid>]:<uid>:<ctag>::<pid>;

Parameter

<uid>

<pid>

Description

Assigned user name

Assigned password

Command Example:

ACT-USER::TELECOM:<ctag>::TS3000!!;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

126 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Cancel User

This command logs the current user off the system, and logs other users off the system as well, provided the current user has access rights of 5. The user name is not case sensitive, but must otherwise be entered exactly as assigned.

To cancel another user, type the command with the UID as the user name to be logged out.

The command format is:

CANC-USER:[<tid>]:<uid>:<ctag>;

Parameter

<uid>

Description

Assigned user name

Command Example:

CANC-USER::TELECOM:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 127

Chapter 4 TL1 Reference

Commands

Copy Memory

This command copies a software program from an external computer to the

TimeSource 3600, or copies the system database to nonvolatile memory.

The Software Release Notice (included with this software release) contains detailed instructions for copying programs from an external computer to nonvolatile memory.

Note:

Clear any existing alarms before using this command.

The database is automatically copied to nonvolatile memory once per hour.

However, if power to the TimeSource 3600 is interrupted before the automatic copying occurs, changes made since the last automatic copy will be lost. To avoid the possibility of losing database changes, the Copy Memory command may be used to copy database changes to nonvolatile memory after any changes are made.

To copy a program from an external computer to nonvolatile memory within the

TimeSource 3600, the command format is:

CPY-MEM:[<tid>]:<aid>:<ctag>::AUX,,WKG:PGM;

Aid Item Addressed

TS3000 System software

GPS GPS receiver software

DEV2

DEV4

TimeSource 3600 (standard) (990-72060-01 systems)

TimeSource 3600 with four TOD IRIG-B outputs

(990-72060-05 systems)

DEV6

DEV8

TimeSource 3600 with eight additional E1 or 2.048 MHz outputs

(990-72060-02 systems)

TimeSource 3600 with two ESCIU ports

(990-72060-04 systems)

DEV10 TimeSource 3600 with mixed E1/T1 outputs (990-72060-06)

Command Example:

CPY-MEM::TS3000:<ctag>::AUX,,WKG:PGM;

128 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

To copy a database from volatile to nonvolatile memory within the TimeSource

3600, the command format is:

CPY-MEM:[<tid>]:<aid>:<ctag>::WKG,,AUX:DATA;

Aid

TS3600

Item Addressed

System Database

Command Example:

CPY-MEM::TS3600:<ctag>::WKG,,AUX:DATA;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 129

Chapter 4 TL1 Reference

Commands

Delete Equipment

This command deletes the specified equipment from the database, removes the input from the ensembling algorithm, and stops the monitoring for that input. Alarms are not reported for deleted equipment. The command format is:

DLT-EQPT:[<tid>]:<aid>:<ctag>::<spec_block>

Aid Value

SPAN-a a = A a = B

OPT-a a = 1 a = 2

Item Addressed

E1 span A input

E1 span B input

ESCIU port 1

(990-72060-04 systems only)

ESCIU port 2

(990-72060-04 systems only)

Command Example:

DLT-EQPT::SPAN-A:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

130 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Delete User Security

This command allows a system administrator to delete a user. The command format is:

DLT-USER-SECU:[<tid>]:<uid>:<ctag>;

Parameter

<uid>

Description

Assigned user name

Command Example:

DLT-USER-SECU::TELECOM:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 131

Chapter 4 TL1 Reference

Commands

Edit Communication

This command changes communication port parameters. The command format is:

ED-COM:[<tid>]:<aid>:<ctag>:::<spec_block>;

Aid Value Item Addressed

COM-a a = 1 a = 2 a = 3 a = 5001

Serial communication port 1 (COM1)

Serial communication port 2 (COM2)

Serial communication port 3 (Craft)

Ethernet user interface port 5001 (Note: 1) a = 5002 a = 5003

Ethernet user interface port 5002 (Note: 1)

Ethernet user interface port 5003 (Note: 1)

a = 5004

Ethernet user interface port 5004 (Note: 1)

a = 5551 Ethernet element manager interface port 5551(Note: 2)

Note:

1 Ethernet ports 5001, 5002, 5003, and 5004 are set up to act as serial communication ports, so that a terminal program on a computer connected to these ports can communicate effectively.

2 Ethernet port 5551 is set up to allow an element manager to connect with it for TL1 commands and responses. TL1 autonomous messages are sent through port 5550, which connects to an element manager to send one or a group of autonomous messages, then disconnects. Port 5550 is not to be reconfigured.

The parameters which can be entered in the <spec_block> are listed below. For any specific <aid> entered in a command, only certain parameters are valid. For each valid parameter, choose the appropriate value from the Value column. When entering multiple parameters, separate the parameters with commas.

132 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Aid

COM-a

Parameter Value Description

MONMSG=b

KEEPALIVE=b b = ALW b = INH

View messages from all ports

View messages from this port only b = 1 to 255 Inactive minutes until the unit sends a COMPLD message to keep the connection from being closed b = 0

ENDOFTEXT=b b = 1 to 9F

ECHO=b b = 0 b = ALW

No COMPLD message is output

Hex code at end of all responses

No hex code at end of responses

Echoes characters received so they appear on the user’s screen as typed

Local echo is disabled

COMPRI=b b = INH b = ALW0 b = ALW1 b = ALW2 b = INH

TL1 commands and responses, no autonomous messages sent

TL1 commands and responses, autonomous messages

TL1 commands and responses, autonomous messages whether logged on or not

Closes connection, logs off any user (if logged on), and keeps port from use. Releases a telnet session from an Ethernet port (a port cannot close itself)

AUTOLOGOFF= b b = 1 to 255 Inactive minutes until the unit logs off the user, keeping the connection open

HWCONTROL= b (See Note: 1 and Note: 2) b = 0 b = ALW b = INH

SWCONTROL=b

(See Note: 1 and

Note: 2)

b = ALW b = INH

Autologoff is disabled

Serial port CTS/RTS flow control is enabled

Serial port CTS/RTS flow control is not enabled

XON/XOFF flow control is enabled

XON/XOFF flow control is not enabled

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 133

Chapter 4 TL1 Reference

Commands

Aid Parameter Value Description

COM-a

(cont’d)

BAUD=b

(See Note: 3) b = 115 b = 57.6

b = 38.4

b = 19.2

b = 9600 b = 4800 b = 2400 b = 1200

Serial port baud rate is 115 kbaud

Serial port baud rate is 57.6 kbaud

Serial port baud rate is 38.4 kbaud

Serial port baud rate is 19.2 kbaud

Serial port baud rate is 9600 baud

Serial port baud rate is 4800 baud

Serial port baud rate is 2400 baud

Serial port baud rate is 1200 baud

PARITY=b

(See Note: 3)

b = EVEN b = ODD

Even parity is enabled on serial port

Odd parity is enabled on serial port b = NONE No parity is enabled on serial port

STOP=b

(See Note: 3)

b = 1 1 stop bit on serial port b = 2 2 stop bits on serial port

Note:

1 Flow control is not implemented on communication port 3 (Craft port).

2 XON/XOFF flow control is simulated for Ethernet ports.

3 Baud rate, parity, and stop bits can only be configured on serial communication ports (1, 2, and 3).

Command Example:

ED-COM::COM-1:<ctag>:::BAUD=9600,MONMSG=ALW,

KEEPALIVE=30,ENDOFTEXT=0,ECHO=ALW,

COMPRI=ALW1,AUTOLOGOFF=30,HWCONTROL=ALW,

SWCONTROL=ALW,PARITY=NONE,STOP=1;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

134 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Edit Date

This command changes the system date and time. The command format is:

ED-DAT:[<tid>]::<ctag>::<date>,[<time>]

:[MODE=a];

Parameter Value Description

date in the format a-b-c a = <year> 4-digit year b = 01 to 12 Month c = 01 to 31 Day a = 00 to 23 Hour of the day time in the format a-b-c

(Note: 1) b = 00 to 59 Minutes c = 00 to 59 Seconds

MODE=a a = UTC

(Note: 2)

Uses Universal Coordinated Time from GPS (cannot set time by TL1 command) a = LOCAL Uses local time for hours, UTC for minutes and seconds

Note:

1 The <time> value can only be entered when MODE=LOCAL, or in the same command as MODE=LOCAL, otherwise the command is denied. A successful command with <time> changes the display of time to conform to the nearest 30 minutes, relative to UTC.

2

For example, when the UTC time is 01:12:10, setting the local time to

18:50:30 will actually set the clock to 18:42:10, because 18:42:10 is the closest 30 minute jump, relative to UTC, from 18:50:30. This is done to accommodate 30-minute time zones and still keep the local time accurate to UTC.

If a command includes MODE=UTC, and the GPS signal is not present, the command is denied.

The date/time behavior is as follows:

During warm-up:

– The date/time displayed starts from 1970 and increments from there. If the

ED-DAT command is used to set the time in local mode, the time is changed as specified in the command.

After warm-up:

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 135

Chapter 4 TL1 Reference

Commands

– If the ED-DAT command has not been used to set the local mode time, then UTC date and time are displayed.

– If the ED-DAT command has been used to set the local mode time, then it is changed in the manner described as follows.

– The date given in the ED-DAT command is retained. The local hours, minutes, and seconds are set to the nearest 30-minute divisible difference from UTC. Refer to the following examples:

Example 1. UTC time= 01:00:00. Local time= 18:01:10 will set the local time to 18:00:00.

Example 2. UTC time= 01:00:00. Local time= 18:25:30 will set the local time to 18:30:00.

Example 3. UTC time= 01:12:10. Local time= 18:50:30 will set the local time to 18:42:10.

During Holdover Event

– The date/time continues to increment normally.

During Holdover Alarm

– The date/time continues to increment normally.

Example to set date without changing time or mode:

ED-DAT:::<ctag>::2000-08-13;

Example to change to local time:

ED-DAT:::<ctag>::2000-08-13,07-00-00:MODE=LOCAL;

Example to change from local to UTC time:

ED-DAT:::<ctag>::2000-08-13:MODE=UTC;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

136 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Edit Equipment

This command changes equipment parameters. Additionally, this command can cause an input to be ensembled. The command format is:

ED-EQPT:[<tid>]:<aid>:<ctag>:::<spec_block>;

Aid

TS3600

GPS

SPAN-a

E1-a

OPT-a

OPT-a

Value Item Addressed

— a = A a = B

System-wide configuration

GPS configuration

Span A input

Span B input a = A a = B

E1 A output

E1 B input a = 1 to 8 E1 option outputs: 1 through 8

(990-72060-02 and 990-72060-06 systems only) a = 1 to 2 ESCIU option ports: 1 or 2

(990-72060-04 systems only)

The parameters which can be entered in the <spec_block> are listed below. For any specific <aid> entered in a command, only certain parameters are valid. For each valid parameter, choose the appropriate value from the Value column. When entering multiple parameters, separate the parameters with commas.

Aid

TS3600

Parameter

TOD=a

ALMCOND =a

Value

a = CISCO a = NTP4 a = NONE a = ALW a = INH

Description

Serial message sent in Cisco format

Serial message sent in NTP Type 4 format

No serial message sent

Alarm conditioning for E1, TOD, and IRIG-B outputs is enabled

Alarm conditioning for E1, TOD, and IRIG-B outputs is disabled

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 137

Chapter 4 TL1 Reference

Commands

Aid

TS3600

(cont’d)

Parameter Value Description

IPNE=a.b.c.d

(See Note: 1)

IPSUBNET=a.b.c.d

(See Note: 1)

a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255 a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255

IP address of this TimeSource 3600 (command must be sent from COM1, COM2, or Craft port to set this parameter)

Subnet mask for this TimeSource 3600

(command must be sent from COM1, COM2, or Craft port to set this parameter)

BYPASS=a

(990-72060-04 systems only)

IPGATE=a.b.c.d

(See Note: 1)

a = AIS When the ESCIU detects an LOS on an input spans, AIS is output to the NE (the E1 alignment sequence is blocked) a = PASSTHRU When the ESCIU detects an LOS on one of its input spans, the E1 alignment sequence is passed through to the NE with the original input alarm a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255

IPEM1=a.b.c.d

(See Note: 1, Note: 2,

Note: 3) a = 0 to 255 b = 0 to 255

Default gateway IP address for this

TimeSource 3600 (command must be sent from COM1, COM2, or Craft port to set this parameter)

IP address of primary element manager (port

5550 connects to this element manager to send autonomous messages, disconnects when transmit is complete) c = 0 to 255 d = 0 to 255

138 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Aid

TS3600

(cont’d)

Parameter

IPEM1PORT=a

(See Note: 1,

Note: 2, Note: 3)

IPEM2=a.b.c.d

(See Note: 1,

Note: 2, Note: 3)

SPAN

A & B

TS3600,

SPAN

A & B

IPEM2PORT=a

(See Note: 1,

Note: 2, Note: 3)

IPINACT=a

(See Note: 1)

ALARM=x

ALARM=x

TIME=x

Chapter 4 TL1 Reference

Commands

Value Description

a = 0 to 65535 Port address of primary element manager (port for IPEM1 address) a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255

IP address of alternate element manager (if used) (port 5550 connects to this element manager if connection cannot be made to the primary element manager) a = 0 to 65535 Port address of alternate element manager

(port for IPEM2 address) a = 0 to 10000 Port 5550 closes the connection to the Element

Manager if no autonomous messages are sent during this number of 100-ms units (0 to

10,000, where 0 deactivates the timer, for example, 100 = 10 s) x =

HOLDOVER

HOLDOVER alarm x = GPS x = LOS x = AIS x = ERROR x = HH-MM x = 0

GPS alarm

LOS alarm

AIS alarm

ERROR alarm

Hour (00-999) and minute (00-59) time to escalate alarm

No alarm escalation

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 139

Chapter 4 TL1 Reference

Commands

Aid

TS3600,

SPAN

A & B

(cont’d)

Parameter

SEVERITY1=x

(See Note: 4)

TS3600

TIME=x

SEVERITY1=x

(See Note: 5)

SEVERITY2=x

(See Note: 5)

SERAFF1=x

(See Note: 5)

SERAFF2=x

(See Note: 5)

NTPPWD=x

(See Note: 6)

Value

x = CR x = MJ x = MN x = EV x = NA x = HH-MM

Description

Severity of initial alarm prior to escalation x = 0 x = CR x = MJ x = MN x = EV x = NA x = CR x = MJ x = MN x = EV x = NA x = SA x = NSA x = SA x = NSA x = 6 ASCII characters

Hour (00-999) and minute (00-59) time to escalate alarm

No alarm escalation

Severity of initial alarm prior to escalation

Severity of escalated alarm

Service affecting state of initial alarm prior to escalation

Service affecting state of escalated alarm

NTP Password

(contact factory)

140 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Aid

GPS

SPAN-a

Parameter

ANTCBLDLY=a

(See Note: 7)

ANTELEVMASK=a

(See Note: 6)

ANTMODE=a

(See Note: 8)

MANLAT=a-b-c-d

(See Note: 7)

MANLONG= a-b-c-d

(See Note: 7)

Value

a = 0 to 300 a = 0 to 45 Antenna elevation mask angle (degrees) a = AUTO Automatic survey-in mode (use only with roof antenna configuration) a = MANUAL Manual survey-in mode (do not use with roof antenna configuration) a = N a = S b = 0 to 179 c = 0 to 59

North latitude

South latitude

Degrees of latitude

Minutes of latitude d = 0 to 999 a = E a = W b = 0 to 179

Decimal minutes of latitude

East longitude

West longitude

Degrees of longitude c = 0 to 59 d = 0 to 999

Minutes of longitude

Decimal minutes of longitude a = 0 to 8000 Antenna elevation (meters) MANELEVALT=a

(See Note: 7)

ENSEMBLER=b

(See Note: 9

Description

Antenna cable length (meters)

SSM=b

(See Note: 8 and

Note: 10)

SIGNAL=b

(See

Note: 11

) b = ALW b = INH b = ALW b = INH

Span is ensembled

Span is not ensembled

SSM qualifies span input

SSM does not qualify span input b = ANALOG Span input signal is 2.048 MHz (analog) b = DIGITAL Span input signal is 2.048 Mb/s (digital)

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 141

Chapter 4 TL1 Reference

Commands

Aid

SPAN-a

(cont’d)

Parameter

SSMCHANNEL=b

(See Note: 8 and

Note: 9)

E1-a

OPT-a

(Additional

E1 outputs on

990-72060-

02 systems only)

ALMOUT=b

FRAMING=b

ALMOUT=b

FRAMING=b

Value Description

b = CAS b = CAS4 b = CCS b = CCS4 b = NONE b = AIS b =

SQUELCH b = SSM b = 4 b = 5 b = 6 b = 7

Uses Sa4 bit

Uses Sa5 bit

Uses Sa6 bit

Uses Sa7 bit b = 8 b = AIS

Uses Sa8 bit

Output is AIS during holdover alarm b = SQUELCH No output during holdover alarm b = SSM Output includes SSM during holdover alarm

(SSM requires either CAS4 or CCS4 output framing)

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

No framing (analog) (See Note: 12)

Output is AIS during holdover alarm

No output during holdover alarm b = CAS b = CAS4 b = CCS b = CCS4 b = NONE

Output includes SSM during alarm (SSM requires either CAS4 or CCS4 output framing)

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

No framing (analog)

(See Note: 12)

142 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Aid Parameter Value Description

OPT-a

(ESCIU ports on

990-72060-

04 systems only)

ALMOUT=b b = AIS b =

PASSTHRU

When the ESCIU detects LOS on an input span, an all-ones signal (AIS), without the E1 frame alignment sequence, is output to the downstream network element

All traffic passes through to the downstream network element, including the LOS alarm signal

Output is AIS during alarm

Output is squelched during alarm

OPT-a

(990-72060

-06 systems only)

TS3600

ALMOUT=b

FRAMING =b b = AIS b =

SQUELCH b = SSM b = CAS b = CAS4 b = CCS b = CCS4 b = D4 b = ESF b = NONE

Outputs are at ‘STU’ quality level for ESF framing and at ‘SSUT’ quality level for CAS4 and CCS4 framing during holdover alarm (SSM requires CAS4, CCS4,or ESF output framing)

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

Output framing is D4

Output framing is ESF

Output framing is NONE (analog)

(see Note: 12)

DCDPASSTHRU

DCDUSERPORT=x

(See Note: 13)

INH

ALW1

ALW2 x = 1

DCD port communication is inhibited

COM1 is the DCD interface port

COM2 is the DCD interface port

COM1 x = 2 COM2 x = 3 or 5001,

5002, 5003,

5004

COM3 or IP port 5001 to 5004

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 143

Chapter 4 TL1 Reference

Commands

Note:

1 This parameter affects all Ethernet ports. Close the Ethernet ports and log off all users before issuing a command with this parameter. The TimeSource does no filtering to verify an improper network address entry.

Users should verify correct network addresses with Network Administrators and take care to enter correct addresses.

2 Port 5550 makes a connection to this element manager to send TL1 autonomous messages, and closes the connection when the transmission is complete.

3 Port 5551 accepts a connection from this element manager for TL1 commands and responses.

4 When setting alarm integration time (SEVERITY or SERAFF), the type of alarm (HOLDOVER, GPS, LOS,

AIS, or ERROR) has to be specified. For example, ED-EQPT::TS3600:CTAG:::ALARM=HOLDOVER,

TIME=72-00, SEVERITY1=EV, SERAFF1=NSA, SEVERITY2=MJ, SERAFF2=SA; will generate a holdover event as soon as the condition is detected with an NSA flag. Once this condition has existed for 72 hours,

TS3600 will generate a major alarm with an SA flag. These parameters can then be verified using the

RTRV-EQPT command.

5 When setting alarm integration time (SEVERITY or SERAFF), the type of alarm (HOLDOVER, GPS, LOS,

AIS, or ERROR) has to be specified. For example, ED-EQPT::TS3600:CTAG:::ALARM=HOLDOVER,

TIME=72-00, SEVERITY1=EV, SERAFF1=NSA, SEVERITY2=MJ, SERAFF2=SA; will generate a holdover event as soon as the condition is detected with an NSA flag. Once this condition has existed for 72 hours,

TS3600 will generate a major alarm with an SA flag. These parameters can then be verified using the

RTRV-EQPT command.

6 If the dbinit jumper is changed, the NTP password has to be re-entered.

7 When the TimeSource 3600 uses a roof antenna, only the parameters ANTCBLDLY and ANTELEVMASK, and the mode ANTMODE=AUTO, are allowed.

8 The TimeSource 3600 uses the MANLAT, MANLONG, and MANELEV values for latitude, longitude, and elevation when ANTMODE=MANUAL becomes active. The TimeSource 3600 uses these values as starting points for processing the antenna position. Changes to these values are ignored while the TimeSource 3600 is in the AUTO mode.

9 A span must have been put into service using the ENT-EQPT command before setting the ENSEMBLER and SSM parameters.

10 The span input must be a digital 2.048 Mb/s E1 signal to use SSM. If not, the command is denied.

11 The span must be put into service using the ENT-EQPT command before using this parameter.

12 When output framing is set to NONE (analog), ALMOUT=SQUELCH turns off the outputs during holdover alarm. ALMOUT=AIS or ALMOUT=SSM converts E1 output framing to digital format to provide alarm signaling during alarm. Set alarm condition to disabled to maintain analog output during alarm.

13 All commands on DCDUSERPORT having TID which equals SID of the DCD are forwarded to the DCD.

Similarly, the responses from the DCD are sent to the provisioned DCDUSERPORT.

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

The flow chart in Figure 4-4 illustrates the alarm conditioning possible with the

TimeSource 3600.

144 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Figure 4-4.

Alarm Conditioning Flow Chart

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 145

Chapter 4 TL1 Reference

Commands

Enter Equipment

This command puts optional inputs in service, and causes the selected input to be monitored. Additionally, this command can cause an input to be ensembled. All in-service inputs are monitored. The Delete Equipment command must be used to take an input out of service. The command format is:

ENT-EQPT:[<tid>]:<aid>:<ctag>:::<spec_block>;

Aid

SPAN-a

OPT-a

(990-72060-04 systems only)

Value

a = A a = B a = 1 a = 2

Item Addressed

E1 span A input

E1 span B input

ESCIU port 1

ESCIU port 2

The parameters which can be entered in the <spec_block> are listed below. For any specific <aid> entered in a command, only certain parameters are valid. For each valid parameter, choose the appropriate value from the Value column. When entering multiple parameters, separate the parameters with commas.

Aid Parameter Value Description

SPAN-a ENSEMBLER=b b = ALW Span is monitored and ensembled b = INH Span is monitored, but not ensembled

Example to set an input to be monitored, but not ensembled:

ENT-EQPT:[<tid>]:SPAN-A:<ctag>;

Example to set an input to be monitored and ensembled:

ENT-EQPT:[<tid>]:SPAN-A:<ctag>:::ENSEMBLER=ALW;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

146 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Enter User Security

This command allows a system administrator to enter a new user, and the new user’s user name, password, and access level. The command format is:

ENT-USER-SECU:[<tid>]:<uid>:<ctag>::<pid>,,<uap>;

Parameter

<uid>

<pid>

<uap>

Description

User name – must start with an alpha character and have a maximum of 10 characters.

Password – has to be a minimum of 8 characters and a maximum of 10 characters. It must contain at least one digit and one of the following characters: ! $ % ' ( ) * + . / < > ? @

Password cannot be the same as User ID even if extra characters are appended to password at the end.

Access level (1 to 5). Levels 1 to 4 do not allow the user to enter or delete users. Level 5 allows the user to enter or delete users.

Command Example:

ENT-USER-SECU::TELECOM:<ctag>::TS3000!!,,1;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 147

Chapter 4 TL1 Reference

Commands

Initialize Log

This command clears the alarm log. The command format is:

INIT-LOG:[<tid>]::<ctag>::almlog;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

148 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Initialize Register

This command resets to zero all the performance monitoring associated with the entered aid. The command can be used to reset either span independently or both spans at the same time. The command format is:

INIT-REG-EQPT:[<tid>]:<aid>:<ctag>::ALL;

Aid

SPAN-a

ALL

Value

a = A a = B

Item Addressed

E1 span A input

E1 span B input

E1 span A and span B inputs

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 149

Chapter 4 TL1 Reference

Commands

Initialize System

This command resets the specified processor.

Caution:

Using this command with an <aid> of TS3600 will cause a loss of outputs until GPS satellites are reacquired if ALMOUT is

SQUELCH, or unstable outputs if ALMOUT is not SQUELCH.

The command format is:

INIT-SYS:[<tid>]:<aid>:<ctag>::1;

Aid Item Addressed

TS3600 System software

GPS GPS receiver software

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

150 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Operate Alarm Cutoff All

This command deactivates (silences) the audible office alarm. The command format is:

OPR-ACO-ALL:[<tid>]:ALL:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 151

Chapter 4 TL1 Reference

Commands

Retrieve Alarm All

This command displays all current system alarms. The command format is:

RTRV-ALM-ALL:[<tid>]:ALL:<ctag>;

If there are no alarms:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

If there is at least one alarm:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:<ntfcncde>,<condtype>,<srveff>,

<ocrdat>,<ocrtm>,,:\"<conddescr>\""...

/*LINK:<link>,CMD:<command>*/

;

Refer to

Chapter 5, Troubleshooting for a list of all <conddescr> messages and the

recommended action.

152 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Retrieve Alarm Equipment

This command displays current alarms for the specified equipment. The command format is:

RTRV-ALM-EQPT:[<tid>]:<aid>:<ctag>;

Aid Value

TS3600 —

SPAN-a a = A

GPS a = B

Item Addressed

System (all TS3600 alarms)

E1 span A input

E1 span B input

GPS receiver

If there are no alarms:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

If there is at least one alarm:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:<ntfcncde>,<condtype>,<srveff>,

<ocrdat>,<ocrtm>,,:\"<conddescr>\""...

/*LINK:<link>,CMD:<command>*/

;

Refer to

Chapter 5, Troubleshooting for a list of all <conddescr> messages and the

recommended action.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 153

Chapter 4 TL1 Reference

Commands

Retrieve Communication

This command displays communication port parameter settings. The command format is:

RTRV-COM:[<tid>]:<aid>:<ctag>;

Aid Value Item Addressed

COM-a a = 1 a = 2

Serial communication port 1

Serial communication port 2 a = 3 Serial communication port 3 a = 5001 Ethernet user interface port 5001

ALL a = 5002 Ethernet user interface port 5002 a = 5003 Ethernet user interface port 5003 a = 5004 Ethernet user interface port 5004 a = 5551 Ethernet element manager interface port 5551

— All communication ports

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:::<spec_block>"...

/*LINK:<link>,CMD:<command>*/

;

The parameters which may be displayed in the <spec_block> are listed below.

Parameter

MONMSG=a

KEEPALIVE=a

Value

a = ALW a = INH a = 1 to

255 a = 0

Description

View messages from all ports

View messages from this port only

Inactive minutes until the unit sends a COMPLD message to keep the connection from being closed

No COMPLD message is output

154 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Parameter Value Description

ENDOFTEXT=a

ECHO=a

COMPRI=a

AUTOLOGOFF=a a = 1 to

255 a = 0

SWCONTROL=a a = ALW

HWCONTROL=a

BAUD=a a = INH a = ALW a = INH a = 115 a = 1 to 9F Hex code at end of all responses a = 00 No hex code at end of responses a = ALW Echoes characters received so they appear on the user’s screen as typed

Local echo is disabled a = INH a = ALW0 a = ALW1

TL1 commands and responses, no autonomous messages sent

TL1 commands and responses, sends autonomous messages a = ALW2 a = INH

TL1 commands and responses, sends autonomous messages whether or not logged on

Closes connection, logs off a user (if logged on), and keeps port from use (a port cannot close itself)

Inactive minutes until the unit logs off the user, keeping the connection open

Autologoff is disabled

XON/XOFF flow control is enabled

XON/XOFF flow control is not enabled

Serial port CTS/RTS flow control is enabled

Serial port CTS/RTS flow control is not enabled

Serial port baud rate is 115 kbaud a = 57.6

a = 38.4

a = 19.2

a = 9600 a = 4800 a = 2400

Serial port baud rate is 57.6 kbaud

Serial port baud rate is 38.4 kbaud

Serial port baud rate is 19.2 kbaud

Serial port baud rate is 9600 baud

Serial port baud rate is 4800 baud

Serial port baud rate is 2400 baud

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 155

Chapter 4 TL1 Reference

Commands

Parameter

PARITY=a

STOP=a

Value

a = EVEN a = ODD a = NONE a = 1 a = 2

Description

Even parity bit is enabled

Odd parity bit is enabled

Parity bit is disabled

1 stop bit

2 stop bits

156 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Retrieve Condition All

This command displays all current system alarms and events. The command format is:

RTRV-COND-ALL:[<tid>]:ALL:<ctag>;

If there are no alarms or events:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

If there is at least one alarm or event:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:<ntfcncde>,<condtype>,<srveff>,

<ocrdat>,<ocrtm>,,,:\"<conddescr>\""...

/*LINK:<link>,CMD:<command>*/

;

Refer to

Chapter 5, Troubleshooting for a list of all <conddescr> messages and the

recommended action.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 157

Chapter 4 TL1 Reference

Commands

Retrieve Condition Equipment

This command displays current alarms and events for the specified equipment. The command format is:

RTRV-COND-EQPT:[<tid>]:<aid>:<ctag>;

Aid

TS3600

SPAN-a

GPS

Value

— a = A a = B

Item Addressed

System

E1 span A input

E1 span B input

GPS receiver

Command Example:

RTRV-COND-EQPT::TS3600:<ctag>;

If there are no alarms:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

If there is at least one alarm:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:<ntfcncde>,<condtype>,<srveff>,

<ocrdat>,<ocrtm>,,,\"<conddescr>\""...

/*LINK:<link>,CMD:<command>*/

;

Refer to

Chapter 5, Troubleshooting for a list of all <conddescr> messages and the

recommended action.

158 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Retrieve Equipment

This command displays parameter settings for the specified equipment. The command format is:

RTRV-EQPT:[<tid>]:<aid>:<ctag>;

Aid Value Item Addressed

ALL —

TS3600 —

GPS —

SPAN-a a = A

E1-a

OPT-a

All aids for this command

System

GPS receiver

Span A input a = B a = A

Span B input

E1 A output a = B E1 B output a = 1 to 8 Additional E1 outputs: 1 through 8 (990-72020-02 systems only)

Mixed E1/T1 outputs (990-72060-06 systems only) a = 1 or 2 ESCIU ports: 1 or 2 (990-72060-04 systems only)

Command Example:

RTRV-EQPT::ALL:G;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>::::<spec_block>"...

/*LINK:<link>,CMD:<command>*/

;

The parameters which may be displayed in the <spec_block> are listed below.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 159

Chapter 4 TL1 Reference

Commands

Aid Parameter

TS3600 BYPASS=a

(990-72060-04 systems only)

TOD=a

ALMCOND=a

IPNE=a.b.c.d

IPSUBNET=a.b.c.

d

IPGATE=a.b.c.d

a = CISCO a = NTP4 a = NONE a = ALW a = INH a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255 a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255 a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255

Value

a = AIS a = PASSTHRU

Description

When the ESCIU detects LOS on an input span, an all-ones signal (AIS), without the E1 alignment sequence, is output to the downstream network element

When the ESCIU detects LOS on an input span, the LOS alarm signal, with the E1 alignment sequence, is passed through to the downstream network element

Serial message sent is Cisco format

Serial message sent is NTP Type 4 format

No serial message is sent

Alarm conditioning for outputs is enabled

Alarm conditioning for outputs is disabled

This unit’s IP address

Subnetwork mask

Default gateway IP address

160 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Aid Parameter Value Description

TS3600

(cont’d)

IPEM1=a.b.c.d

IPEM1PORT=a

IPEM2=a.b.c.d

a = 0 to 255 b = 0 to 255 c = 0 to 255 d = 0 to 255 a = 0 to 65535 a = 0 to 255 b = 0 to 255 c = 0 to 255

Primary element manager IP address

Primary element manager port address

Alternate element manager IP address

IPEM2PORT=a

IPINACT=a

IPNTP=a

DCDPASSTHRU d = 0 to 255 a = 0 to 65535 a = 0 to 10000 a = ALW

INH

ALW1

ALW2

Alternate element manager port number

Port 5550 closes the connection to the

Element Manager if no autonomous messages are sent during this number of

100-ms units (0 to 10,000; 0 deactivates the timer. For example, 100 = 10 s)

SNTP feature activated

DCD port communication is inhibited

COM1 is the DCD interface port

COM2 is the DCD interface port

DCDUSERPORT= a

(See Note: 1) a = 1 a = 2

COM1

COM2 a = 3 or 5001,

5002, 5003, 5004

COM3 or IP port 5001 to 5004

ALARM=x x = HOLDOVER HOLDOVER alarm x = GPS GPS alarm

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 161

Chapter 4 TL1 Reference

Commands

Aid

GPS

Parameter Value

ANTCBLDLY=a a = 0 to 305

ANTELEVMASK=a a = 0 to 45

ANTMODE=a a = AUTO a = MANUAL

SPAN-a

MANLAT=a-b-c-d

MANLONG= a-b-c-d

MANELEV=a

ENSEMBLER=b

MONITOR=b

SSM=b

SIGNAL=b a = N a = S b = 0 to 179 c = 0 to 59 d = 0 to 999 a = E a = W b = 0 to 179 c = 0 to 59 d = 0 to 999 a = 0 to 8000 b = ALW b = INH b = ALW b = INH b = ALW b = INH b = ANALOG b = DIGITAL

Description

Antenna cable length (meters)

Antenna elevation mask angle (degrees)

Automatic survey-in mode

Manual survey-in mode (do not use for roof antenna)

North latitude

South latitude

Degrees of latitude

Minutes of latitude

Decimal minutes of latitude

East longitude

West longitude

Degrees of longitude

Minutes of longitude

Decimal minutes of longitude

Antenna elevation (meters)

E1 span is ensembled

E1 span is not ensembled

E1 span is monitored

E1 span is not monitored

SSM message is used to qualify input

SSM message is not used to qualify input

Span input signal is 2.048 MHz

Span input signal is 2.048 Mb/s

162 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Aid

SPAN-a

(cont’d)

E1-a

Parameter Value

SSMCHANNEL=b b = 4 b = 5 b = 6 b = 7

FRAMING=b b = 8 b = CAS b = CAS4 b = CCS,

ALMOUT=b b = CCS4 b = NONE b = AIS b = SQUELCH b = SSM

OPT-a

(990-720

60-02 systems only)

FRAMING=b

ALMOUT=b b = CAS b = CAS4 b = CCS, b = CCS4 b = NONE b = AIS b = SQUELCH b = SSM

Chapter 4 TL1 Reference

Commands

Description

Uses Sa4 bit

Uses Sa5 bit

Uses Sa6 bit

Uses Sa7 bit

Uses Sa8 bit

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

Output framing is NONE (if an analog signal).

Output during holdover alarm is AIS

No output during holdover alarm

Output is ‘SSUT’ quality level message during holdover alarm (SSM requires output framing of CAS4 or CCS4)

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

Output framing is NONE (if an analog signal).

Output during holdover alarm is AIS

No output during holdover alarm

Output is ‘SSUT’ quality level message during holdover alarm (SSM requires output framing of CAS4 or CCS4)

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 163

Chapter 4 TL1 Reference

Commands

Aid Parameter

OPT-a

(990-720

60-04 systems only)

MONITOR=b

ALMOUT=b

OPT-a

(990-720

60-06 systems only)

SPAN

A & B

FRAMING=b

ALMOUT=b

ALARM=x

Value

b = ALW b = CAS b = CAS4 b = CCS, b = CCS4 b = D4 b = ESF b = NONE b = AIS b = SQUELCH b = SSM b = INH b = AIS b = PASSTHRU x = LOS x = AIS x = ERROR

Description

TimeSource 3600 uses monitoring information to generate an alarm

TimeSource 3600 does not use monitoring information to generate an alarm

When the ESCIU detects LOS on an input span, an all-ones signal (AIS), without the E1 alignment sequence, is output to the downstream network element

When the ESCIU detects LOS on an input span, the LOS alarm signal, with the E1 alignment sequence, is passed through to the downstream network element

Output framing is CAS

Output framing is CAS4

Output framing is CCS

Output framing is CCS4

Output framing is D4

Output framing is ESF

Output framing is NONE (analog)

Output during holdover alarm is AIS

No output during holdover alarm

Outputs are at ‘STU’ quality level for ESF framing and at ‘SSUT’ quality level for CAS4 and CCS4 framing during holdover alarm

(SSM requires output framing of CAS4,

CCS4, or ESF)

LOS alarm

AIS alarm

ERROR alarm

164 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Aid Parameter Value Description

TS3600,

SPAN

A & B

TIME=x

SEV1=x

(See Note: 2)

SEV2=x

(See Note: 2)

x = HH-MM x = 0 x = CR x = MJ x = MN x = EV x = NA x = CR x = MJ

Hour (00-999) and minute (00-59) time to escalate alarm

No alarm escalation

Severity of initial alarm prior to escalation

Severity of escalated alarm x = MN x = EV x = NA

TS3600,

SPAN

A & B,

(cont’d)

SAFF1=x

(See Note: 2)

x = SA x = NSA

Service affecting state of initial alarm prior to escalation

SAFF2=x

(See Note: 2)

x = SA Service affecting state of escalated alarm x = NSA

Note:

1 All commands on DCDUSERPORT TID which equal SID of the DCD are forwarded to the DCD. Similarly, the responses from the DCD are sent to the provisioned DCDUSERPORT.

2 When setting alarm integration time (SEVERITY or SERAFF), the type of alarm (HOLDOVER, GPS, LOS,

AIS, or ERROR) has to be specified. For example, ED-EQPT::TS3600:CTAG:::ALARM=HOLDOVER,

TIME=72-00, SEVERITY1=EV,SERAFF1=NSA, SEVERITY2=MJ, SERAFF2=SA; will generate a holdover event as soon as the condition is detected with an NSA flag. Once this condition has existed for 72 hours,

TS3600 will generate a major alarm with an SA flag. These parameters can then be verified using the

RTRV-EQPT command.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 165

Chapter 4 TL1 Reference

Commands

Retrieve GPS Status

This command displays the position of the GPS receiver, UTC time, and status information for each of the GPS satellites in view. The command format is:

RTRV-GPS-STAT:[<tid>]:GPS:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:LAT=a,LONG=a,ALT=a,UTC=a

ANTMODE=a,MERIT=a,SUCCESS=a%

;

SAT-a,USE=a,CNO=a,ELEV=a,AZ=a,

LOCK=a..."

/*LINK:<link>,CMD:<command>*/

Parameter

LAT=a

LONG=a

ALT=a

UTC=a

ANTMODE=a

MERIT=a

SUCCESS=a

SAT=a

Value

a = dd.mm.fffN

a = dd.mm.fffS

a = ddd.mm.fffE

a = ddd.mm.fffW

a = mm.mmm

a = hh-mm-ss a = AUTO a = MANUAL a = bbb a = bb a = 1 to 25

Description

Current latitude north in degrees, minutes, and decimal-fractions of a minute

Current latitude south in degrees, minutes, and decimal-fractions of a minute

Current longitude east in degrees, minutes, and decimal-fractions of a minute

Current longitude west in degrees, minutes, and decimal-fractions of a minute

Altitude in meters to the thousandth of a meter, referenced to mean sea level

Universal Coordinated Time (UTC), where hh is hours (00 to 23), mm is minutes (00 to 59), and ss is seconds (00 to 59)

Automatic survey-in mode

Manual survey-in mode

Timing error estimate in ns

Percentage of time satellites are visible

Satellite identification number

166 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Parameter

USE=a

CNO=a

ELEV=a

AZ=a

LOCK=a

Value

a = Y a = N a = nn a = dd a = ddd a = 1 to 2500

Chapter 4 TL1 Reference

Commands

Description

Satellite in use

Satellite not in use

Satellite carrier-to-noise ratio

Satellite elevation in degrees

Satellite azimuth in degrees

Seconds since the receiver locked to the satellite carrier

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 167

Chapter 4 TL1 Reference

Commands

Retrieve Header

This command allows for NMA integration to use as a keep alive message. The command format is:

RTRV-HDR:[<tid>]::<ctag>;

Response Format:

RTRV-HDR:::114;

TELECOM1 1997-12-08 15:04:13

M 114 COMPLD

168 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Retrieve Inventory

This command displays information about the specified equipment. The command format is:

RTRV-INVENTORY:[<tid>]:TS3600:<ctag>;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"TS3600::::CARD=TS3600,

MACID=a,

TYPE=a,

PART=a,

SERIAL=a,

SOFTVER_TS3000=a,

SOFTVER_GPS=a,

SOFTVER_DEV=a"

/*LINK: x, CMD:<command>*/

;

Parameter

CARD=TS3600

MACID=a.b.c.d.e

Value

— a = 00 to FF in hexadecimal format b = 00 to FF in hexadecimal format c = 00 to FF in hexadecimal format d = 00 to FF in hexadecimal format e = 00 to FF in hexadecimal format

System

MAC address

Description

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 169

Chapter 4 TL1 Reference

Commands

Parameter Value

TYPE=a

PART=a

SERIAL=a

SOFTVER_

TS3000=a

SOFTVER_GPS= a

SOFTVER_

DEV=a

— a = NO OPTION

BOARD a = E1 OPTION

BOARD a = SCIU OPTION

BOARD a = IRIG OPTION

BOARD a = MIXED E1/T1

OPTION BOARD a = bb.cc.dd

a = bb.cc.dd

a = bb.cc.dd or bb.cc.dd-ee.ff.gg

Description

TimeSource 3600 (standard)

(990-72060-01 systems)

TimeSource 3600 with eight additional E1 outputs (990-72060-02 systems)

TimeSource 3600 with 2 ESCIU ports

(990-72060-04 systems)

TimeSource 3600 with 4 TOD IRIG-B outputs (990-72060-05 systems)

TimeSource 3600 with eight mixed E1/T1 outputs (990-72060-06 systems) a = Part number a = Serial number

System software version

GPS receiver software version

Device software version

170 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Retrieve Log

This command retrieves the alarm log. The command format is:

RTRV-LOG:[<tid>]::<ctag>::almlog;

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"<logtype>"

"<aid>:<ntfcncde>,<condtype>,<srverff>,

<ocrdat>,<ocrtm>,,[,]:<conddescr>,

[:<dgntype>]"*/

/*LINK:<link>,CMD:<command>*/

;

Chapter 4 TL1 Reference

Commands

Parameter Description

<ntfcncde>

<condtype>

<srverff>

<ocrdat>

<ocrtm>

Severity of alarm: critical, major, or minor

Single type of alarm condition being reported on this particular line, i.e.,

LOS, FAIL, TBD for each alarm

Alarm is service affecting (SA) or non-service affecting (NSA)

Occurrence date in MOY-DOM format, where MOY=1 to 12 and DOM=1 to 31

Occurrence Time of Day in HOD-MOH-SOM format, where HOD=0 to 23,

MOH=0 to 59, SOM=0 to 59

<conddescr> Text string of no more than 64 characters enclosed within a pair of escape quotes (\)

<dgntype> TL1 identifier up to 16 characters in length

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 171

Chapter 4 TL1 Reference

Commands

Retrieve Performance Monitoring

This command retrieves the performance monitoring data from the TimeSource

3600. This data includes MTIE, TDEV, PHASE1S, and PHASE1M. For current 24 hour data, MTIE, TDEV, and PHASE1S data are grouped every 15 minutes. In addition, there are 7 daily summaries of MTIE, TDEV, and PHASE1M. Each value type can be retrieved for both span inputs A and B.

MTIE data includes the following time intervals in seconds: 1, 4, 10, 40, 100, 300,

900, 1800, 3600, 7200, 14400, 28800, and 86400.

TDEV data includes the following time intervals in seconds: 1, 2, 4, 8, 16, 32, 64,

128, 256, 512, and 1024.

PHASE1S data includes 900 seconds of phase values.

PHASE1M data includes 60 minutes of phase values.

The command format is:

RTRV-PM-EQPT:[<tid>]:SPAN-a:<ctag>::<montype>

,,,,,[<mondat>][<montm>];

Parameter

SPAN-a

<montype>

<mondat>=x

<montm>=x

Value

a = A a = B

MTIE

TDEV

PHASE1S

PHASE1M x = 1 to 12 x = 1 to 31 x = 0 to 23 x = 0 to 59

Description

E1 span A input

E1 span B input

MTIE data reported

TDEV data reported

1-second phase data reported

1-minute phase data reported

Monitor date, month of the year

Monitor date, day of the month

Monitor time, hour past midnight

Monitor time, minutes past the hour

172 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

MTIE Response Format:

<sid> <date> <time>

M <ctag>COMPLD

"SPAN-a:MTIE-a,<monval>,<vldty>

,,,,<mondat>,<montm>"

...

...

...

"SPAN-a:MTIE-a,<monval>,<vldty>

,,,,<mondat>,<montm>"

/*LINK:<link>,CMD:<command>*/

;

MTIE Data types

One 15 minute bin from the last 24 hours of data. To select a 15 minute bin, enter mondat and montm. Any mondat/montm combination outside of the past 24 hour window is denied. Any time increment may be entered. The system rounds the value to the nearest bin. Entered minutes of 1 to 15 correspond to the first

15 minute bin, 16 to 30 correspond to the second 15 minute bin, etc.

One day summary from the last 7 days of daily summaries. To select one daily summary, enter mondat, but do not enter montm. Any mondat not in the previous

7 day window is denied.

Parameter

SPAN-a

MTIE-a

<monval>

<vldty>

MONDAT=a-b

MONTM=a-b

Value Description

a = A a = B

E1 span A input

E1 span B input a = 1S, 2S, 4S, 10S, 40S,

100S, 300S, 900S, 1800S,

3600S, 7200S, 14400S,

28800S, or 86400S

MTIE monitored type, where a is time intervals in seconds

One 15 min bin from the last

24 h of data

Monitored value

COMPL

NA a = 1 to 12 b = 1 to 31 a = 0 to 23 b = 0 to 59

Data is valid

Data is not valid

Monitor date, month of the year

Monitor date, day of the month

Monitor time, hour of the day

Monitor time, minute of the hour

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 173

Chapter 4 TL1 Reference

Commands

MTIE Response Example:

TS3600-2009 2000-05-25 11:01:58

M G COMPLD

"SPAN-A:MTIE-1S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-4S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-10S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-40S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-100S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-300S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-900S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-1800S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-3600S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-7200S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-14400S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-28800S,1,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:MTIE-86400S,1,COMPL

,,,,,2000-05-25,11-00-00"

/*LINK:5002,CMD:RTRV-PM-EQPT::

SPAN-A:G::MTIE*/

;

TDEV Response Format:

<sid> <date> <time>

M <ctag>COMPLD

"SPAN-a:TDEV-a,<monval>,<vldty>

,,,,<mondat>,<montm>"

...

...

...

"SPAN-a:TDEV-a,<monval>,<vldty>

,,,,<mondat>,<montm>"

/*LINK:<link>,CMD:<command>*/

;

TDEV Data types

One 15 minute bin from the last 24 hours of data. To select a 15 minute bin, enter mondat and montm. Any mondat/montm combination outside of the past 24 hour window is denied. Any time increment may be entered. The system rounds the value to the nearest bin. Entered minutes of 1 to 15 correspond to the first

15 minute bin, 16 to 30 correspond to the second 15 minute bin, etc.

174 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

One day summary from the last 7 days of daily summaries. To select one daily summary, enter mondat, but do not enter montm. Any mondat not in the previous

7 day window is denied.

Parameter Value Item Addressed

SPAN-a

TDEV=a

<monval> a = A a = B

E1 span A input

E1 span B input a = 1S, 2S, 4S, 8S, 16S, 32S,

64S, 128S, 256S, 512S, or 1024S

TDEV monitored type, where a is time intervals in seconds

One 15 min bin from the last 24 h of data

Monitored value

<vldty>

MONDAT=ab

COMPL

NA a = 1 to 12 b = 1 to 31

MONTM=a-b a = 0 to 23 b = 0 to 59

Data is valid

Data is not valid

Monitor date, month of the year

Monitor date, day of the month

Monitor time, hour of the day

Monitor time, minute of the hour

TDEV Response Example:

TS3600-2009 2000-05-25 11:01:58

M G COMPLD

"SPAN-A:TDEV-1S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-2S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-4S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-8S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-16S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-32S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-64S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-128S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-256S,0,COMPL

,,,,,2000-05-25,11-00-00"

"SPAN-A:TDEV-512S,0,COMPL

,,,,,2000-05-25,11-00-00"

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 175

Chapter 4 TL1 Reference

Commands

"SPAN-A:TDEV-1024S,0,COMPL

,,,,,2000-05-25,11-00-00"

/*LINK:5002,CMD:RTRV-PM-EQPT::

SPAN-A:G::TDEV*/

;

PHASE1S Response Format:

<sid> <date> <time>

M <ctag>COMPLD

"SPAN-a:PHASE1S,<monval>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<vldty>,,,,

<mondat>,<montm>"

...

...

...

"SPAN-a:PHASE1S,<monval>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,

<

Δ

>,<

Δ

>,<

Δ

>,<

Δ

>,<vldty>,,,,

<mondat>,<montm>"

;

PHASE1S Data types:

One 15 minute bin from the last 24 hours of data as 900 seconds of data. To select a 15 minute bin, enter mondat and montm. Any mondat/montm combination outside of the past 24 hour window is denied. Any time increment may be entered. The system rounds the value to the nearest bin.

Entered minutes of 1 to 15 correspond to the first 15 minute bin, 16 to 30 correspond to the second 15 minute bin, etc.

The first monitor value is the first second of the 900 second window.

The 900 seconds of data is broken into 9 groups of 100 seconds. For each group of 100 seconds, the first value is the absolute 1 second phase for that group. The absolute 1 second phase value is followed by 99 seconds of delta phase values.

176 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Parameter

SPAN-a

PHASE1S

<monval>

<D>

<vldty>

MONDAT=a-b

MONTM=a-b

Value Item Addressed

a = A a = B

E1 span A input

E1 span B input

— Phase 1S monitored type, which shows

900 s of phase values

First s of the 100 s data group. There are

9 groups of 100 s.

Absolute monitored phase value

The difference (D) from the proceeding number

99 s of delta phase values which follow the absolute 1 s phase value

COMPL

NA a = 1 to 12 b = 1 to 31 a = 0 to 23 b = 0 to 59

Data is valid

Data is not valid

Monitor date, month of the year

Monitor date, day of the month

Monitor time, hour of the day

Monitor time, minute of the hour

PHASE1S Response Example:

TS3600-2009 2000-05-25 11:01:58

M G COMPLD

"SPAN-A:PHASE1S,-325,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,COMPL,,,,2

000-10-13,12-45-00"

"SPAN-A:PHASE1S,-323,0,0,0,0,0,0,0,1,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,COMPL,,,,2000-10-13,12-46-40"

"SPAN-A:PHASE1S,-321,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,-1,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,COMPL,,,,2000-10-13,12-48-20"

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 177

Chapter 4 TL1 Reference

Commands

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-50-00"

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-51-40"

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-53-20"

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-55-00"

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-56-40"

"SPAN-A:PHASE1S,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,NA,,,,2000

-10-13,12-58-20"

/* LINK: 5001, CMD: RTRV-PM-EQPT::SPAN-A:C:: PHASE1S,,,,,

*/

;

PHASE1M Response Format:

<sid> <date> <time>

M <ctag>COMPLD

"SPAN-a:PHASE1M,<monval>,<monval>,

<monval>,<monval>,<monval>,<monval>,

...

...

...

<monval>,<monval>,<monval>,<monval>,

<vldty>,,,,<mondat>,<montm>"

/*LINK:<link>,CMD:<command>*/

;

178 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

PHASE 1M Data types

The TimeSource 3600 collects a full 7 days of 1 minute phase data.

The 1 minute phase data is displayed in 1 hour groups. Each request for 1 minute phase is synchronized to the hour.

Any mondat/montm combination outside of the past 7 day window is denied. Any time increment may be entered. The system rounds the value to the nearest hour, i.e., the minute and second field of the montm is ignored.

The first value (monval) is the oldest value in the range selected. For example, if montm = 8:45:32, the first monval will exceed time 8:00:00 followed by the value at 8:01:00, etc.

Parameter

SPAN-a

PHASE1M

<monval>

<vldty>

MONDAT=a-b

MONTM=a-b

Value Item Addressed

a = A a = B

E1 span A input

E1 span B input

— Phase 1M monitored type, which shows 1 min phase data in 1 h groups of data

Oldest value in the range selected from the <montm> value assigned in the command

Absolute monitored phase value

COMPL

NA a = 1 to 12 b = 1 to 31 a = 0 to 23 b = 0 to 59

Data is valid

Data is not valid

Monitor date, month of the year

Monitor date, day of the month

Monitor time, hour of the day

Monitor time, minute of the hour

PHASE1M Response Example:

TS3600-2009 2000-05-25 11:01:58

M G COMPLD

"SPAN-A:PHASE1M,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,

0,0,COMPL,,,,,2000-05-25,100-00"

/*LINK:5002,CMD:RTRV-PM-EQPT::

SPAN-A:G::PHASE1M*/

;

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 179

Chapter 4 TL1 Reference

Commands

Retrieve Status Security

This command allows a system administrator with level 5 access to identify the current users logged in to each port that is currently being used. The command format is:

RTRV-STATUS-SECU:[<tid>]::<ctag>;

Response Format Example:

[<tid>] 05-12-25 16:30:45

M <ctag> COMPLD

"COM-1:<user name>"

"COM-2:<user name>"

"COM-3:<user name>"

"COM-5551:<user name>"

"COM-5001:<user name>"

"COM-5002:<user name>"

"COM-5003:<user name>"

"COM-5004:<user name>"

180 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 4 TL1 Reference

Commands

Retrieve User Security

This command allows a system administrator to retrieve security parameters for a single user or for all users. The command format is:

RTRV-USER-SECU:[<tid>]:<uid>:<ctag>;

Parameter

<uid>

Value

(user name)

ALL

Item Addressed

Single user

All users

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

"<aid>:,<uap>;,UOUT=<uout>"...

/*LINK:<link>,CMD:<command>*/

;

Parameter

<uap>

<uout>

Description

Access level (1 to 5)

(Displayed, but not implemented) Password for this account expires in this number (0 to 180) of days of inactivity; 0 indicates no expiration

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 181

Chapter 4 TL1 Reference

Commands

Set Source Identifier

This command sets the name of the equipment sending the message. The command format is:

SET-SID:[<tid>]::<ctag>::<sid>;

Parameter

<sid>

Description

Source identifier – can be up to 20 uppercase or lowercase

ASCII characters

Response Format:

<sid> <date> <time>

M <ctag> COMPLD

/*LINK:<link>,CMD:<command>*/

;

182 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

This chapter provides troubleshooting information using front-panel lamps and error messages. It also describes how to replace a card, return equipment, and obtain manual updates.

In This Chapter

Troubleshooting with Front Panel Items

Troubleshooting with Error Messages

Replacing Cards

Returning the TimeSource

User Guide Updates

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 183

Chapter 5 Troubleshooting

Troubleshooting with Front Panel Items

Troubleshooting with Front Panel Items

All front panel items are shown in Figure 5-1

. The items are described in Table 5-1 .

Use

Table 5-1 to troubleshoot the system based on the front-panel lamps.

Alarms

MIN

Status

GPS

Status

SYS

Alarms

CRIT

Alarms

MAJ

ACO

(Lamp)

ACO

(Pushbutton)

990-72060-01, -02, -05, -06 Systems

Retimed

Span A

Retimed

Span B

BYP

Status

GPS

Status

SYS

A

larms

CRIT

Alarms

MAJ

Alarms

MIN

ACO

(Lamp)

ACO

(Pushbutton)

990-72060-04 Systems

Figure 5-1.

Controls and Indicators

184 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

Troubleshooting with Front Panel Items

Table 5-1. Front Panel Items

Name

Status GPS

Status SYS

State

Off

Green

Yellow

Red

Off

Green

Red

Alarms CRIT Off

Red

Alarms MAJ Off

Red

Description Action

System is not powered.

GPS is successfully tracking satellites, or is in warm-up.

A GPS event has occurred.

A GPS event, which has existed per the user alarm setting, has escalated to a minor alarm.

System is in warm-up mode or is not powered.

The output signal is PRS.

The system has been in holdover per the user alarm setting, or there is a hardware fault.

There is no critical alarm.

A critical alarm has occurred because of a hardware failure.

There is no major alarm.

The system has been in holdover per the user alarm setting.

If in warm-up, none required.If there is no power, apply power.

None required.

None required.

Refer to

Table 5-2

to determine which type and combination of antenna alarms exist, and the recommended action.

If in warm-up, none required. If there is no power, apply power.

None required.

Refer to

Table 5-2

to determine which type and combination of alarms exist, and the recommended action.

None required.

Replace the plug-in card using

Procedure 5-1

.

None required.

Refer to

Table 5-2

to determine which type and combination of antenna alarms exist, and the recommended action.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 185

Chapter 5 Troubleshooting

Troubleshooting with Front Panel Items

Table 5-1. Front Panel Items (Continued)

Name

Alarms MIN

ACO

(Lamp)

ACO

(Pushbutton)

Retimed

Span A or B

(990-72060-

04 systems only)

Retimed

Span A or B

(990-72060-

04 systems only)

State

Off

Yellow

Off

Green

Off

Green

Red

Description Action

There is no minor alarm.

A minor alarm has occurred because Battery A or B has failed.

A minor alarm has occurred because a software download is required.

A minor alarm has occurred because an event (GPS error, temperature error, or span input problem) has escalated to a minor alarm.

A minor alarm has occurred because the antenna failed.

None required.

Troubleshoot and repair the specified

48 V battery input.

Refer to

Table 5-2

to determine which software needs to be downloaded and the recommended action.

Refer to

Table 5-2

None required. If desired, enter this port via the Enter Equipment command.

None required.

to determine which event occurred and the recommended action.

The alarm cutoff function has not been activated.

Refer to

Table 5-2

to determine whether the minor alarm is due to antenna failure and the recommended action.

None required. Press the ACO pushbutton to silence all audible alarms.

None required.

The alarm cutoff function has been activated.

Silences all audible alarms when pressed.

This port has not been entered via the Enter Equipment command.

This port has been entered via the Enter Equipment command, and no alarms are present.

An event (loss of signal) has occurred on this port

None required.

Troubleshoot the traffic-carrying span input signal source; check the

ESCIU port cable and connections.

186 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

Troubleshooting with Error Messages

Table 5-1. Front Panel Items (Continued)

Name

BYP

(990-72060-

04 systems only)

State

Off

Red

Description Action

Traffic-carrying E1 data stream is being retimed by the

TimeSource 3600 System.

Traffic-carrying E1 data stream is bypassing the TimeSource 3600

System and not being retimed because the system is in holdover.

None required.

Refer to

Table 5-2

to troubleshoot the GPS and SPAN x error messages.

Troubleshooting with Error Messages

Use the information in

Table 5-2 to troubleshoot the system based on the condition

description (conddescr) parameter in a message.

Note:

If only the character “C” is displayed on the terminal every few seconds, the TimeSource 3600 system has restarted with corrupt software. Download and install the system software again, using the procedure in the Software Release Document that came with the software.

Table 5-2. Message Troubleshooting

Message Meaning Action

CRITICAL ALARMS

HARDWARE FAULT A failure has been detected on the shelf hardware.

Replace the plug-in card.

HOLDOVER

PWR x FAIL

MAJOR ALARMS

All inputs (GPS signal and span inputs) are lost or unacceptable, and the system is now using the internal oscillator.

Troubleshoot the GPS and SPAN x error messages.

MINOR ALARMS

The specified

48 V battery input has failed.

Troubleshoot, and repair, the specified

48 V battery input.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 187

Chapter 5 Troubleshooting

Troubleshooting with Error Messages

Table 5-2. Message Troubleshooting (Continued)

Message

BT3 WARMUP

DEVICE

DOWNLOAD

REQUIRED

Meaning

The system is in a power-up state when it should not be.

The hardware device software is corrupt or missing.

GPS ERROR

GPS DOWNLOAD

REQUIRED

The GPS receiver is reporting an error.

The GPS software is corrupt or missing.

Action

Perform the same action as shown in

GPS ERROR message.

Download and install the appropriate hardware device (DEV) software, using the procedure in the Software

Release Document that came with the software.

If the installation includes a roof antenna, or if the message is accompanied by the HIGH

CURRENT FAULT or LOW

CURRENT FAULT message, follow the recommended action for the

HIGH CURRENT FAULT or LOW

CURRENT FAULT message.

If the installation includes a window or wall antenna:

1.

Note the satellite tracking success rate reported by the

RTRV-GPS-STAT command.

2.

If the success rate is better than

40%, follow the recommended action for the HIGH CURRENT

FAULT or LOW CURRENT

FAULT message.

3.

If the success rate is less than

40%, check that the latitude, longitude, and altitude data

(position data) are correct.

4.

If the position data are correct and the error repeats, move the antenna to a location with an improved view of the sky.

5.

If the error repeats, follow the recommended action for the

HIGH CURRENT FAULT or LOW

CURRENT FAULT message.

Download, and install, the GPS receiver (GPS) software, using the procedure in the Software Release

Document that came with the software.

188 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

Troubleshooting with Error Messages

Table 5-2. Message Troubleshooting (Continued)

Message

HIGH CURRENT

FAULT

LOW CURRENT

FAULT

SPAN x AIS

Meaning

Current to antenna is outside specification.

An AIS has been received on the specified input span.

Action

If not accompanied by the GPS

ERROR alarm, none required.

If accompanied by the GPS ERROR alarm:

1.

Check the cable connections between the TimeSource 3600

Shelf and the antenna.

2.

If the error repeats, remove the antenna cable from the rear of the shelf, and measure the dc voltage from the connector center pin to the connector housing on the shelf TNC antenna connector.

3.

If the voltage is not 24 V DC ±2 V dc, replace the TimeSource 3600 card using

Procedure 5-1

.

4.

If the voltage is 24 V DC ±2 V dc, measure the current between the connector center pin and the connector housing on the shelf

TNC antenna connector.

5.

If the current is less than 110 mA or more than 150 mA, replace the TimeSource 3600 card using

Procedure 5-1

. If not (nominal

current is 125 mA), re-connect the antenna cable to the rear of the shelf.

6.

Remove the antenna cable from the antenna, and measure dc voltage and current from the connector center pin to the connector housing on the cable connector.

7.

If the readings are 24 V DC and

125 mA, replace the antenna. If not, verify the cable path.

Replace cables, lightning suppressor, or IF converter as necessary.

8.

If the error repeats, replace the antenna.

Troubleshoot the specified input span signal (check the source).

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 189

Chapter 5 Troubleshooting

Troubleshooting with Error Messages

Table 5-2. Message Troubleshooting (Continued)

Message

SPAN x ERROR

SPAN x LOSS OF

SIGNAL

TEMPERATURE

ERROR

TS3600

DOWNLOAD

REQUIRED

BT3 WARMUP

COM-x USER

TIMEOUT LOGOFF

DISCONNECTED

USER LOGOFF

HOLDOVER

Meaning Action

An error has been detected on the specified input span.

The signal on the specified input span has been lost.

A temperature error has been detected on the internal oscillator.

The system software is corrupt or missing.

Troubleshoot the specified input span signal (include checks for signal frequency and jitter).

Troubleshoot the specified input span signal (check the cable, connections, source).

If this occurs momentarily during power-up, none required.

If this does not occur during power-up:

1.

Check that the ambient air temperature is within the

TimeSource 3600 environmental specifications. If not, correct the ambient temperature with heating or air conditioning.

2.

If the ambient air temperature is within the TimeSource 3600 environmental specifications, replace the plug-in card.

Download and install the system

(TimeSource 3600) software again, using the procedure in the Software

Release Document that came with the software.

EVENTS

The system is in a power-up state.

The user was auto logged off.

A user was logged off by the system administrator.

All inputs (GPS signal, span inputs) are lost or unacceptable. The system is using the internal oscillator.

Wait for the system to power up

(20 min to several hours, depending on antenna placement and view of the sky).

If COM-x is the port this message was received on, retry logging in. If not, none required.

None required.

None required.

190 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

Troubleshooting with Error Messages

Table 5-2. Message Troubleshooting (Continued)

Message Meaning Action

CRITICAL ACO

EVENT

DOWNLOAD

FAILED

DOWNLOAD IN

PROGRESS

DOWNLOAD

SUCCESSFUL

GPS ERROR

MAJOR ACO

EVENT

MINOR ACO

EVENT

The ACO pushbutton has been pressed to deactivate a critical audible alarm.

The software download has failed.

Software is being downloaded.

The software has been downloaded successfully.

The GPS receiver is reporting an error.

The ACO pushbutton has been pressed to deactivate a major audible alarm.

The ACO pushbutton has been pressed to deactivate a minor audible alarm.

The system processor has just started up.

The signal on the specified

ESCIU port has been lost.

None required.

Retry the software download.

Wait until the download has been completed.

None required.

None required.

None required.

None required.

POWER UP

RESTART

SCIU x LOSS OF

SIGNAL

SCIU x SLIP The specified ESCIU port has a frame slip.

SETTLING PERIOD The system is between the power-up state and steady-state operation, and signals may be degraded.

SOFTWARE

DOWNLOADING

ON LINK

SPAN x AIS

Software is being downloaded at specified communication port.

An AIS has been received on the specified input span.

SPAN x ERROR

SPAN x LOSS OF

SIGNAL

None required.

Troubleshoot the traffic-carrying span input signal source, ESCIU port cable, and ESCIU port connections.

Troubleshoot the traffic-carrying span input signal source.

None required.

None required.

An error has been detected on the specified input span.

The signal on the specified span input has been lost.

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 191

Chapter 5 Troubleshooting

Replacing Cards

Table 5-2. Message Troubleshooting (Continued)

Message

SPAN x SSM

QUALITY PRS

SPAN x SSM

QUALITY SEC

SPAN x SSM

QUALITY SSUL

SPAN x SSM

QUALITY SSUT

TEMPERATURE

ERROR

Meaning

The quality level of the signal detected on the specified span is PRS.

The signal on the specified span input has degraded to an SSM quality level of

SEC.

The signal on the specified span input has degraded to an SSM quality level of

SSUL.

The signal on the specified span input has degraded to an SSM quality level of

SSUT.

A temperature error has been detected on the internal oscillator.

Make note of the specified input span.

Action

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

Troubleshoot the specified input span (check the source).

Becomes minor alarm after 24 h.

Wait until this escalates to a minor alarm, or check that the ambient air temperature is within the

TimeSource 3600 environmental specifications. If not, correct the ambient temperature with heating or air conditioning.

Replacing Cards

To replace the plug-in card, follow the steps in

Procedure 5-1

, and refer to

Figure 5-2

.

Procedure 5-1. Replacing Cards

Step

1.

2.

3.

4.

Procedure

Put on an ESD wrist strap.

Plug the ESD wrist strap into the ESD jack on of the front panel of the shelf.

On the Faulty Card

Loosen the two retaining screws that secure the plug-in card in the shelf.

Pull out on the two latching levers to disconnect the card from the shelf connectors.

192 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

Replacing Cards

Procedure 5-1. Replacing Cards

Step

5.

Procedure

Pull the card completely out of the shelf.

On the Replacement Card

6.

7.

8.

9.

10.

11.

Pull out the latching levers at each end of the front panel of the card so that the levers are pointing directly out from the front panel of the card.

Insert the new card into the tracks at each side of the shelf, and slide the card into the shelf until the latching levers begin to move in.

Push the latching levers flat against the front panel of the card to complete the card insertion.

Tighten the knurled screw above each latching lever to secure the card in the shelf.

Unplug and remove the grounding wrist strap.

Reconfigure the system per application requirements.

End of Procedure

Retaining screw

Latching lever

Figure 5-2.

Front of Shelf

097-72060-01 Revision J – June, 2007

Latching lever

ESD jack

Retaining screw

TimeSource 3600 User’s Guide 193

Chapter 5 Troubleshooting

Returning the TimeSource

Returning the TimeSource

You should return the equipment to Symmetricom only after you have exhausted the troubleshooting procedures described earlier in this chapter, or if Symmetricom

Global Services has advised you to return the unit.

Note:

Please retain the original packaging for re-shipping the product. If the original packaging is not available, contact

Symmetricom Global Services (SGS) for assistance.

Repacking the Unit

Return all units in the original packaging. If the original packaging is not available, contact Symmetricom Global Services. Use standard packing procedures for products being returned for repair to protect the equipment during shipment.

Connectors should be protected with connector covers or the equipment should be wrapped in plastic before packaging. Ensure that the display and connectivity panels are protected when packaged.

Equipment Return Procedure

To return equipment to Symmetricom for repair:

1. Call Symmetricom Global Services (SGS) at 888-367-7966 (toll-free in USA only),

408-428-7907, or +49 700 3288 6435 in Europe, Middle East, or Africa to obtain a return material authorization number (RMA) before returning the product for service.

You can request an RMA on the internet at https://www.symmetricom.com/Support/req_repair.htm.

Retain the assigned RMA number for future reference.

2. Provide a description of the problem, product item number, serial number, and warranty expiration date.

3. Provide the return shipping information (customer field contact, address, telephone number, and so forth.)

4. Ship the product to Symmetricom, transportation prepaid and insured, with the

Return Material Authorization (RMA) number and item numbers or part numbers clearly marked on the outside of the container to the address given with the RMA.

Repaired equipment is returned to you with shipping costs prepaid by Symmetricom.

194 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 5 Troubleshooting

User Guide Updates

User Guide Updates

From time to time, this User Guide may be updated. The updated version of the guide will be available for downloading in electronic form via the Internet. After downloading, the guide can be viewed on a computer or printed out.

Manual updates are available at: http://www.symmetricom.com/support/

Note:

If you are downloading a manual for the first time, you will need to register with Symmetricom. If you are currently registered, login and download the manual update.

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 195

Chapter 5 Troubleshooting

User Guide Updates

196 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

This chapter provides equipment specifications.

In This Chapter

Antennas

Communication and Ethernet Ports

Time of Day Outputs

Input Ports

Output Ports

Office Alarms

Simple Network Time Protocol

Power

Shelf

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 197

Chapter 6 Specifications

Antennas

Antennas

Type

Cable Length

Dimensions (excluding mount)

Height

Diameter

Weight

Operating Temperature

Storage Temperature

Operating Humidity

Roof Antenna

Active antenna, right-hand circular polarized, with proprietary IF interface

Maximum 330 m from antenna to shelf

16.5 cm

15 cm

0.70 kg

30 °C to +80 °C

40 °C to +80 °C

0% to 100% relative humidity

Type

Cable Length

Dimensions: (antenna, including mechanical mounting device)

Height

Width

Depth

Weight

Mechanical Window Antenna

Patch antenna and proprietary IF interface

Maximum 305 m from antenna to shelf

45.7 cm

7.9 cm

6.9 cm

510 g

Type

Cable Length

Dimensions: (not including mounting and peripheral equipment)

Height

Wall Antenna

Patch antenna and proprietary IF interface

Maximum 305 m from antenna to shelf

12.5 mm

198 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Communication and Ethernet Ports

Width

Depth

Weight

Wall Antenna (Continued)

37 mm

46 mm

35 g

Type

Cable Length

Dimensions

Height

Width

Depth

Weight

Self-Adhesive Window Antenna

Patch antenna and proprietary IF interface

Maximum 305 m from antenna to shelf

7.6 cm

10.2 cm

4.3 cm

170 g

Communication and Ethernet Ports

Connector Type

Connector Label

Connector Location

Electrical Interface

Pin that transmits data

Pin that receives data

Baud Rate

097-72060-01 Revision J – June, 2007

Port 1

25-pin, female D connector

COM1

Connector panel

RS-232 (DTE equivalent)

2

3

1200 b/s

2400 b/s

4800 b/s

9600 b/s (factory default)

19.2 kb/s

38.4 kb/s

57.6 kb/s

TimeSource 3600 User’s Guide 199

Chapter 6 Specifications

Communication and Ethernet Ports

Data Bits

Parity Bit

Stop Bits

Flow Control

Connector Type

Connector Label

Connector Location

Electrical Interface

Pin that transmits data

Pin that receives data

Baud Rate

Data Bits

Parity Bit

200 TimeSource 3600 User’s Guide

Port 1 (Continued)

115 kb/s

8

None

Even

Odd

1

2

None

Software (XON/XOFF)

Hardware (CTS/RTS)

Port 2

9-pin, female D connector

COM2

Connector panel

RS-232 (DCE equivalent)

2

3

1200 b/s

2400 b/s

4800 b/s

9600 b/s (factory default)

19.2 kb/s

38.4 kb/s

57.6 kb/s

115 kb/s

8

None

Even

Odd

097-72060-01 Revision J – June, 2007

Stop Bits

Flow Control

Connector Type

Connector Label

Connector Location

Electrical Interface

Pin that transmits data

Pin that receives data

Baud Rate

Data Bits

Parity Bit

Stop Bits

Flow Control

Port 2 (Continued)

1

2

None

Software (XON/XOFF)

Hardware (CTS/RTS)

Chapter 6 Specifications

Communication and Ethernet Ports

Craft Port

1

2

Even

Odd

None

RJ-45

Craft

Front panel

RS-232 (DTE equivalent)

2

3

1200 b/s

2400 b/s

4800 b/s

9600 b/s (factory default)

19.2 kb/s

38.4 kb/s

57.6 kb/s

115 kb/s

8

None

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 201

Chapter 6 Specifications

Time of Day Outputs

Connector Type

Connector Label

Connector Location

Electrical Interface

Data Rate

Protocol

Setup Language

Time of Day Outputs

Ethernet Ports

RJ-45 (10Base-T)

Ethernet

Connector panel

10Base-T Ethernet

10Mb/s

TCP/IP (interface)

TL1 (application layer)

Network Time Protocol (NTP), Type 4, Format 2 Driver Format

Connector Type

Connector Label

Connector Location

Electrical Interface

Baud Rate

Data Bits

Parity Bit

Stop Bit

Data Format

RJ-45

TOD

Connector panel

RS-485

9600 b/s

8

None

1

See

Figure 6-1

1 2 3 4 5 6

Example:

1 Alarm field: blank space = receiver has satellite availability; ? = no satellite available

2 Year (2000 in this example)

3 Day of year (the 225th day of the year in this example)

4 Hours:minutes:seconds:milliseconds

5 Leap second: blank space = no leap second; L = upcoming leap second

6 Daylight savings time indicator: S = standard time; D = daylight savings time

Figure 6-1.

NTP Type 4 Data Format

202 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Time of Day Outputs

Connector Type

Connector Label

Connector Location

Electrical Interface

Baud Rate

Bit Configuration

Data Format

Example:

1 2 3 4 5 6 7 8

Cisco Systems

RJ-45

TOD

Connector panel

RS-485

9600 b/s

8 data bits, No parity, 1 stop bit

See

Figure 6-2

9 10 11 12 13 14

1 Satellite availability: * = valid, ! = not valid

2 Revision

3 Modified Julian date (number of days past midnight, Nov 17, 1858)

4 Year/month/day

5 Hours:minutes:seconds

6 Indicator of time zone offset (+, –, or 0)

7 Time zone offset

8 Leap second indicator

9 Latitude

10 Longitude

11 Altitude above mean sea level in meters

12 Alarm severity: EV = event, MN = minor, MJ = major, CL = critical

13 Alarm source

14 Alarm cause: holdover, BT3 warm-up, or hardware fault

Figure 6-2.

Cisco Systems Data Format

Connector Location

Impedance

IRIG-B TOD Outputs (990-72060-05 System Only)

Connector Type

Connector Labels

BNC

OUT1

OUT2

OUT3

OUT4

Connector panel output module

600

Ω

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 203

Chapter 6 Specifications

Input Ports

IRIG-B TOD Outputs (990-72060-05 System Only) (Continued)

Number of Outputs

Type of Output

Amplitude

4

Amplitude modulated

6 V peak-to-peak maximum terminated with 600

Ω

Time Format

Binary Coded Decimal (BCD)

Non BCD

Seconds: 0 – 59

Minutes: 0 – 59

Hours: 0 – 23

Days: 0 – 364

Years: 0 – 99

Seconds of day: 0 – 86399

Input Ports

Connector Type

Connector Label

BNC

Wire-Wrap (2 sets)

Connector Location

Impedance

Bit Rate

Format

E1 Inputs

Wire-wrap pins for 120

Ω

balanced terminations

BNC for 75

Ω

unbalanced terminations

(Use only BNC or only wire-wrap connector, not both, for one input.)

SPAN IN A

SPAN IN B

T

R

S

Connector panel

120

Ω

±5% balanced or

75

Ω

±5% unbalanced

2.048 Mb/s

E1

204 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Input Ports

Framing

Line Code

SSM

State

Framing

Channels

Amplitude

E1 Inputs (Continued)

CAS

CAS4

CCS

CCS4

HDB3

Enable

Disable

CAS4

CCS4

Sa4

Sa5

Sa6

Sa7

Sa8

+3 dB to

33 dB

Connector Type

Connector Label

BNC

Wire-Wrap (2 sets)

Connector Location

Impedance

Frequency

Format

Analog 2.048 MHz Inputs

Wire-wrap pins for 120

Ω

balanced terminations

BNC for 75

Ω

unbalanced terminations

(Use only BNC or only wire-wrap connector, not both, for one input.)

SPAN IN A

SPAN IN B

T

R

S

Connector panel

120

Ω

±5% balanced or

75

Ω

±5% unbalanced

2.048 MHz

Analog

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 205

Chapter 6 Specifications

Output Ports

Output Ports

Connector Type

Connector Label

Connector Location

Impedance

Frequency

Amplitude

Time Accuracy

GPS Holdover Time Error

Format

Rise Time

1 PPS Outputs

BNC

TTL PPS

Rear panel

50

Ω

1 pps

Transistor-transistor logic (TTL) levels

100 ns with respect to Universal

Coordinated Time (UTC) when locked to

GPS signal

3 µs for 72 h (0 °C to +50 °C

±

5 °C) after one week of steady-state operation

Logic low with logic high pulse of 1 µs

Less than 20 ns

Connector Type

Connector Label

BNC

Wire-Wrap (2 sets)

Connector Location

Impedance

Bit Rate

Frequency Accuracy

206 TimeSource 3600 User’s Guide

E1 Standard Outputs

Wire-wrap pins for 120

Ω

balanced terminations

BNC for 75

Ω

unbalanced terminations

(Use only BNC or only wire-wrap connector, not both, for one output.)

E1 OUT A

E1 OUT B

T

R

S

Connector panel

120

Ω balanced or 75

Ω

unbalanced

2.048 Mb/s

1 x 10

12

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Output Ports

GPS Holdover Stability

E1 Standard Outputs (Continued)

Format

Line Code

Amplitude

Framing

Output During Alarms

1 x 10

11

for 72 h (0 °C to +50 °C

±

5 °C) after one week of steady-state operation

1 x 10

10

for 30 days after one week of steady-state operation

Framed all 1s

HDB3

3.0 V nominal terminated with 120

Ω balanced

2.37 V nominal terminated with 75

Ω unbalanced

CAS

CAS4

CCS

CCS4

AIS

Squelch

SSM

SSM

State

Framing

Channels

Enable

Disable

CAS4

CCS4

Sa4

Sa5

Sa6

Sa7

Sa8

Additional E1 Outputs (990-72060-02 System Only)

Connector Type Wire-wrap pins for 120

Ω

balanced terminations

BNC for 75

Ω

unbalanced terminations

Connector Labels

Wire-Wrap (8 sets) T

R

S

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 207

Chapter 6 Specifications

Output Ports

BNC

Additional E1 Outputs (990-72060-02 System Only) (Continued)

Connector Location

Impedance

Bit Rate

Frequency Accuracy

GPS Holdover Stability

Format

Line Code

Amplitude

Framing

Output During Alarms

OUT1

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

Connector panel output module

120

Ω balanced or 75

Ω

unbalanced

2.048 Mb/s

1 x 10

12

1 x 10

11

for 72 h (0 °C to +50 °C

±

5 °C) after one week of steady-state operation

1 x 10

10

for 30 days after one week of steady-state operation

Framed all 1s

HDB3

3.0 V nominal terminated with 120

Ω balanced

2.37 V nominal terminated with 75

Ω unbalanced

CAS

CAS4

CCS

CCS4

AIS

Squelch

SSM

SSM

State Enable

Disable

208 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Output Ports

Additional E1 Outputs (990-72060-02 System Only) (Continued)

Framing

Channels

CAS4

CCS4

Sa4

Sa5

Sa6

Sa7

Sa8

Connector Type

Analog 2.048 MHz Standard Outputs

Wire-wrap pins for 120

Ω

balanced terminations

BNC for 75

Ω

unbalanced terminations

(Use only BNC or wire-wrap connector for a single output.)

Connector Label

BNC

Wire-Wrap (2 sets)

Connector Location

Impedance

Frequency

Frequency Accuracy

GPS Holdover Stability

Format

Amplitude (nominal)

E1 OUT A

E1 OUT B

T

R

S

Connector panel

120

Ω balanced or 75

Ω

unbalanced

2.048 MHz

1 x 10

12

1 x 10

11

for 72 h (0 °C to +50 °C

±

5 °C) after one week of steady-state operation

1 x 10

10

for 30 days after one week of steady-state operation

Square wave

1.5 V terminated with 120

Ω balanced

1.18 V terminated with 75

Ω unbalanced

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 209

Chapter 6 Specifications

Output Ports

Note:

For E1/T1 common specifications, refer to the E1/T1 Common

Outputs list. For E1 specific specifications, refer to the E1 Outputs list.

For T1 specific specifications, refer to the T1 Outputs list.

Mixed E1/T1 Common Outputs (990-72060-06 System Only)

Connector Type

Connector Label

Connector Location

Frequency Accuracy

Output During Alarms

Wire-wrap

T, R, S

Connector panel output module

1 x 10

–12

AIS, Squelch, SSM

Impedance

Bit Rate

Format

Line Code

Amplitude

Framing

E1 Outputs (990-72060-06 System Only)

120

Ω

balanced or 75

Ω

unbalanced

2.048 Mb/s

Framed all 1s

HDB3

3.0 V nominal terminated with 120

Ω balanced

CAS, CAS4, CCS, CCS4

GPS Holdover Stability

1 x 10

-11

for 72 h (0 °C to +50 °C

±

5 °C) after one week of steady-state operation

1 x 10

-10

for 30 days after one week of steady-state operation

Impedance

Bit Rate

Format

Line Code

Amplitude

Framing

210 TimeSource 3600 User’s Guide

T1 Outputs

100

Ω

1.544 Mb/s

DS1, framed all 1s

Alternate mark inversion (AMI)

2.4 V to 3.6 V terminated with 100

Ω

ESF, D4

097-72060-01 Revision J – June, 2007

Chapter 6 Specifications

Output Ports

GPS Holdover Stability:

T1 Outputs (Continued)

(after one week of steady-state operation)

1 x 10

-10

per day

3.2 x 10

-11

per day with span input meeting

ANSI T1.101 network specification 99% probability (rubidium)

1 x 10

-11

per day over a 10 °C range between 0 °C and

+

50 °C with an ST2E remote oscillator input (quartz)

Connector Type

Connector Label

Connector Location

Impedance

Frequency

Stability

Phase Noise

Harmonic Distortion

Spurious Distortion

Format

Amplitude

10 MHz Output

BNC

10 MHz

Connector panel

50

Ω

10 MHz

5 x 10

12

Root Allen Variance (RAV) at 10 s

–110 dBc @ 10 Hz

–135 dBc @ 100 Hz

–140 dBc @ 1 kHz

–145 dBc @ 10 kHz

–40 dBc

–70 dBc

Sine wave

1 V peak-to-peak minimum, 50

Ω termination

3.7 V peak-to-peak typical, 50

Ω termination

Connector Type

ESCIU Ports (990-72060-04 System Only)

75

Ω

BNC

120

Ω

Wire-wrap

Connector Labels

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 211

Chapter 6 Specifications

Office Alarms

ESCIU Ports (990-72060-04 System Only) (Continued)

Wire-wrapSPAN 1

SPAN 2

BNCSPAN 1

SPAN 2

Connector Location

Electrical Interface

Ports

Maximum cable length

CSU Functionality

Output During LOS Alarm

Input jitter tolerance

Input wander tolerance

RTN1 (T, R, S) (2 sets of pins)

IN (T, R, S)

OUT (T, R, S)

RTN2 (T, R, S) (2 sets of pins)

IN (T, R, S)

OUT (T, R, S)

RTN1 OUT

RTN1 IN

OUT

IN

RTN2 OUT

RTN2 IN

OUT

IN

Connector panel output module

E1 (ITU G.703 and G.704)

Two bidirectional:

(E1 signals are buffered and retimed in forward direction, passed through in reverse direction)

150 m (either direction, to or from DDF)

None

AIS

LOS

ITU G.823 (1993) requirements

±125

μ s

Office Alarms

Connection

Type

Contact Rating

212 TimeSource 3600 User’s Guide

Connector Panel Contacts

Wire-wrap pins

Dry contact

1 A @ 30 V dc

0.5 A @ 60 V dc

0.5 A @ 125 V ac

097-72060-01 Revision J – June, 2007

Severity

State

Style

Chapter 6 Specifications

Simple Network Time Protocol

Connector Panel Contacts (Continued)

Critical

Major

Minor

Normally open and normally closed

Audible and visible

Label

Type

Front Panel Lamps

Alarms (CRIT, MAJ, MIN, ACO) Status

(GPS, SYS)

Light emitting diode

Label

Type

Function

Front Panel Control

ACO

Push-button switch

Alarm cutoff (deactivates audible office alarms)

Simple Network Time Protocol

Protocol Type

SNTP Accuracy

SNTP Alarm Indications

Password Activated

097-72060-01 Revision J – June, 2007

SNTP (Simple Network Time Protocol) compliant with RFC-1769 for unicast applications

SNTP timestamp derived from UTC time via integrated GPS receiver within –300 microseconds

1. SNTP packet will indicate Stratum 2 in

NTP packet header if GPS is out of lock.

2. The “ref id” field changes from GPS at

Stratum 1 to the IP address at Stratum 2 to signify that the reference is the

TimeSource clock itself.

3. SNTP packet will indicate “clock not synchronized” in LI field as a “3” value after user defined alarm integration time.

Contact factory

TimeSource 3600 User’s Guide 213

Chapter 6 Specifications

Power

Power

Connector Type

Connector Labels

Voltage

Current

Steady-State Power

Recommended Fuse for Battery

Feed

Terminal block

TB1

TB2

–40 V dc to –72 V dc (A & B feed)

750 mA maximum

30 W maximum

3 A

Shelf

Rack Mounting

Mounting Positions

Dimensions

Width

Height

Depth

Weight

Operating Temperature

Operating Humidity

Electromagnetic

Mechanical

48.5 cm rack

53.5 cm rack

Flush

12.7 cm offset (48.5 cm rack only)

48.3 cm

22.2 cm maximum

30.5 cm maximum

5.9 kg

Environmental

0 °C to +50 °C

Up to 95% non condensing

CE

214 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

Index

A

Activate User 96

,

124

,

126

Alarm All, Retrieve

124

,

152

Alarm Cutoff All, Operate

124

,

151

Alarm Equipment, Retrieve 124 ,

153

Alarm Programmability

35

Algorithm, BesTime 27

,

31

Analog 2.048 MHz Inputs specifications

205

Antenna types 23

Antenna, mechanical 23

Antenna, mechanical window

25 ,

28

Antenna, roof 23

,

25 ,

28

Antenna, self-adhesive window 23

,

26 ,

28

Antenna, wall 23

,

27 ,

28

Antennas, GPS 23

Application, TimeWizard 104

Application, TimeWizard Software Installation

104

Applications, TimeSource 3600 22

B

BesTime algorithm 27

,

31

BesTime Ensemble Timing Generator

27 ,

31

Bridging mode 36

BT3 Warmup event

36

C

Cancel User 124 ,

127

cautions defined 18

Cisco Systems specifications 203

Communication port 1 specifications

199

Communication port 2 specifications

200

Communication, Edit

124

,

132

Communication, Retrieve

124

,

154

Communications, Edit 99

,

101

,

124

,

132

Condition All, Retrieve

125

,

157

Condition Equipment, Retrieve 125 ,

158

Copy Memory 102 ,

124 ,

128

Craft port specifications

201

CRIT lamp

35

D

Date, Edit 97

,

124

,

135

Delete Equipment 124 ,

130

Delete User Security

124

,

131

Device, strike termination

29

Device, strike termination, lower 30

documentation, related 19

E

E1 Inputs specifications

204

E1 Outputs specifications 206

E1/T1 Outputs, Mixed 31

,

51 ,

83

,

210

Edit Communication

124

,

132

097-72060-01 Revision J – June, 2007

Edit Communications

99 ,

101 ,

124 ,

132

Edit Date

97 ,

124 ,

135

Edit Equipment

96 ,

98

,

100

,

102

,

124

,

137

Element Manager

33 ,

34

,

100

,

101

Enter Equipment

97 ,

124 ,

146

Enter User Security 124 ,

147

Equipment, Delete 124 ,

130

Equipment, Edit 96

,

98 ,

100 ,

102 ,

124 ,

137

Equipment, Enter 97

,

124

,

146

Equipment, Retrieve 97

,

125

,

159

Error message troubleshooting

187

Ethernet port specifications

202

Event, BT3 Warmup 36

Event, Holdover 36

,

37

Event, Power Up Restart 35

Event, Settling Period

36

Event/alarm, Holdover

37

F

Feature, Network Time Protocol (NTP)

31

Feature, NTP 31

Feature, Passthrough

34

Frame ground with ground rod

77

Frame ground without ground rod 77

Front panel items troubleshooting 184 –

186

G

Generator, BesTime Ensemble Timing

27 ,

31

Global Services telephone/address 194

GPS antennas

23

GPS navigation system 22

GPS signals 22

GPS Status, Retrieve

125

,

166

Ground rod, frame ground with

77

Ground rod, frame ground without

77

H

Header, Retrieve 125 ,

168

Holdover event

36 ,

37

Holdover event/alarm 37

Holdover mode

36

I

Initialize Log 124 ,

148

Initialize Register

98 ,

124 ,

149

Initialize System

124

,

150

Installation, mechanical window antenna 55

,

64

Installation, roof antenna

54 ,

58

62

Installation, self-adhesive window antenna

55

Installation, TimeSource 3600 shelf 55

,

73

Installation, wall antenna

55 ,

68

,

69 ,

73

Installation, Wall Antenna Indoor Lightning Suppressor

Kit 70

Installation, Wall Antenna Outdoor Lightning

Suppressor Kit

71

Inventory, Retrieve 125 ,

169

TimeSource 3600 User’s Guide 215

Index

K—S

IRIG-B TOD Outputs specifications

203

K

Kit, lightning protector

30 ,

53

Kit, mechanical window antenna

52

Kit, roof antenna 52

Kit, self-adhesive window antenna 53

Kit, wall antenna 53

Kit, Wall Antenna Indoor Lightning Suppressor 53

Kit, Wall Antenna Outdoor Lightning Suppressor

53

L

Lamp, CRIT

35

Lightning protector kit 30

,

53

Location, roof antenna 43

Location, window or wall antenna

47

Log, Initialize

124

,

148

Log, Retrieve 125 ,

171

Lower strike termination device

30

M

Manager, Element

33 ,

34

,

100

,

101

Mechanical antenna

23

Mechanical window antenna

25 ,

28

Mechanical window antenna installation

55 ,

64

Mechanical window antenna installation procedures

63

Mechanical window antenna kit

52

Mechanical window antenna specifications 198

Memory, Copy

102

,

124

,

128

Mixed E1/T1 Outputs

31 ,

51

,

83 ,

210

Mode, Bridging

36

Mode, Holdover 36

N

Navigation system, GPS 22

Network Time Protocol (NTP) feature

31

Network Time Protocol specifications

202

notes defined 18

NTP feature

31

O

Operate Alarm Cutoff All 124 ,

151

Outputs, Mixed E1/T1 31

,

51 ,

83

Outputs, synchronization 22

P

packaging for shipment 194

Passthrough feature

34

Performance Monitoring, Retrieve

125

,

172

Power specifications 214

Power Up Restart event 35

Procedure, RS-422-to-RS-232 converter installation

89

Procedures, mechanical window antenna installation

63

216 TimeSource 3600 User’s Guide

Procedures, roof antenna installation

58 –

62

Procedures, self-adhesive window antenna installation

65

Procedures, wall antenna installation

68 ,

73

Protection, zone of

29 ,

30

Protocol, Simple Network Time

31

purpose of this guide 16

R

recommendations defined 18

Register, Initialize

98 ,

124 ,

149

related documentation 19

Retrieve Alarm All

124 ,

152

Retrieve Alarm Equipment

124

,

153

Retrieve Communication

124

,

154

Retrieve Condition All

125

,

157

Retrieve Condition Equipment 125 ,

158

Retrieve Equipment

97 ,

125 ,

159

Retrieve GPS Status

125

,

166

Retrieve Header 125 ,

168

Retrieve Inventory

125

,

169

Retrieve Log

125

,

171

Retrieve Performance Monitoring

125 ,

172

Retrieve Status Security

125 ,

180

Retrieve User Security

125 ,

181

return material authorization 194 returning products to factory, procedure 194

RMA. see return material authorization

Roof antenna 23

,

25 ,

28

Roof antenna installation 54

Roof antenna installation procedures

58 –

62

Roof antenna kit 52

Roof antenna location 43

Roof antenna specifications

198

RS-422-to-RS-232 converter installation procedure 89

RS-422-to-RS-232 TOD Converter Kit 49

S

Self-adhesive window antenna 23

,

26 ,

28

Self-adhesive window antenna installation 55

Self-adhesive window antenna installation procedures

65

Self-adhesive window antenna kit 53

Self-adhesive window antenna specifications

199

Set Source Identifier 125 ,

182

Settling Period event

36

Shelf Environmental specifications 214

Shelf Mechanical specifications

214

Shelf, TimeSource 3600 23

,

49

shipping address, repair

194 shipping products to factory, procedure 194

Signals, GPS 22

Site survey 42

Source Identifier, Set 125 ,

182

Specifications, Analog 2.048 MHz Inputs 205

Specifications, Cisco Systems 203

Specifications, communication port 1 199

Specifications, communication port 2 200

Specifications, Craft port 201

Specifications, E1 Inputs 204

Specifications, E1 Outputs

206

Specifications, Ethernet port 202

097-72060-01 Revision J – June, 2007

Specifications, IRIG-B TOD Outputs 203

Specifications, mechanical window antenna

198

Specifications, Network Time Protocol 202

Specifications, power

214

Specifications, roof antenna

198

Specifications, self-adhesive window antenna

199

Specifications, Shelf Environmental

214

Specifications, Shelf Mechanical

214

Specifications, wall antenna

198

Standard for the Installation of Lightning Protection

Systems (NFPA 780)

29

Status Security, Retrieve

125

,

180

Strike termination device 29

structure of this guide 16

Survey, site

42

Symmetricom

Global Services address

194

Synchronization outputs

22

System, Initialize 124 ,

150

T telephone contact numbers

194

TimeServer 31

TimeSource 3600 applications

22

TimeSource 3600 shelf 23

,

49

TimeSource 3600 shelf installation

55

TimeWizard application

104

TimeWizard Software Installation application

104

TOD Converter Kit, RS-422-to-RS-232

49

Troubleshooting, error message

187

Troubleshooting, front panel items 184 –

186

Types, antenna 23

U

User Security, Delete

124

,

131

User Security, Enter

124

,

147

User Security, Retrieve

125

,

181

User, Activate 96

,

124

,

126

User, Cancel 124 ,

127

W

Wall antenna 23

,

27 ,

28

Wall Antenna Indoor Lightning Suppressor Kit

53

Wall Antenna Indoor Lightning Suppressor Kit,

Installation

70

Wall antenna installation

55 ,

68

,

69

Wall antenna installation procedures

68 ,

73

Wall antenna kit

53

Wall Antenna Outdoor Lightning Suppressor Kit

53

Wall Antenna Outdoor Lightning Suppressor Kit,

Installation

71

Wall antenna specifications

198

warnings defined 18

web address

19

Window or wall antenna location

47

Z

Zone of protection

29 ,

30

Index

T—Z

097-72060-01 Revision J – June, 2007

TimeSource 3600 User’s Guide 217

Index

Z—Z

218 TimeSource 3600 User’s Guide

097-72060-01 Revision J – June, 2007

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project