Tyco ESFR-17 Manual 8 Pages
Tyco ESFR-17 is a highly capable dry type pendent sprinkler designed for use in refrigerated storage areas with solid piled, palletized, or rack storage. It features a unique design that substantially lowers the end head pressure requirement and eliminates the need for in-rack sprinklers, making it an ideal solution for protecting high-piled box-in-box environments.
advertisement
Worldwide
Contacts www.tyco-fire.com
Model ESFR-17
16.8 K-factor Dry Type Pendent Sprinklers
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Dry Type
Pendent Sprinklers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 16.8.
They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-in-box refrigerated storage areas.
The Model ESFR-17 Dry Type Pendent
Sprinkler is FM Approved and has successfully undergone full-scale fire testing at FM Global, when used in conformance with applicable FM Global
Property Loss Prevention Data Sheets.
The Model ESFR-17 Dry Type Sprinkler consists of an ESFR sprinkler permanently secured to a sprinkler drop featuring an inlet with both grooved and threaded connections. The drop between the inlet and sprinkler remains dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system where the dry drop and sprinkler are located in an area subjected to freezing temperatures.
The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only sprinkler protection (i.e., no need for in-rack sprinklers) and used to protect solid piled, palletized, and rack storage that is subject to freezing temperatures.
The water supply is provided from a
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
Page 1 of 8 wet pipe system located outside of the refrigerated storage area. The Model
ESFR-17 Dry Type Sprinklers feature all of the same design criteria as 16.8
K-factor ESFR Pendent Sprinklers, and substantially lowers the end head pressure requirement as compared to the
14.0 K-factor ESFR Dry Type Pendent
Sprinklers.
Combining a 16.8 K-factor with a dry-type sprinkler design, the Model
ESFR-17 Dry Type Sprinkler provides the system designer with features that offer flexibility when sizing system piping, as well as possibly reducing or eliminating the need for a system fire pump when protecting high-piled boxin-box refrigerated storage areas.
The ESFR-17 Dry Type Sprinkler also includes two Insulating Seal Assemblies that help seal the clearance space around the sprinkler casing. The seal assemblies are intended to slow the exchange of air between the heated area and the protected area to help prevent humidity and temperature differential in the area around the sprinkler. Condensation on the sprinkler and subsequent ice buildup on or around the sprinkler can occur that might damage the sprinkler or prevent proper operation in a fire situation.
To install the Insulating Seal Assemblies, follow the installation instructions in this data sheet. The Insulating
Seal Assemblies are recommended to be installed on smooth, flat, and clean surfaces. If it is expected that environmental conditions may result in excessive condensation, additional sealing of the assembly is recommended.
There are specific situations, such as corrugated surfaces where alternate methods to seal the clearance hole are recommended. For additional guidance, contact Johnson Controls Technical Services.
NOTICE
The Model ESFR-17 Dry Type Pendent
Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National
AUGUST 2018
Fire Protection Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions.
Sprinkler
Identification
Number (SIN)
Refer to Table B for sprinkler identification number.
TFP320
TFP320
Page 2 of 8
1-1/4" NPT
OR ISO 7-R 1-1/4
PIPE THREADED
CONNECTION
TABLE A
DIM. A
TABLE A
DIM. B
TABLE A
DIM. C
LINK
ASSEMBLY
CENTERLINE
OF THERMAL
SENSING
ELEMENT
STRUT
HOOK
DEFLECTOR
BUTTON
WITH VENT
HOLES
FRAME
A
B
C
FIGURE 1
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER (TY7229)
DIM.
36 Inch
(914 mm)
Sprinkler
37.5 in.
(952,5 mm)
36.2
(919,5 mm)
33.9
(861 mm)
30 Inch
(762 mm)
Sprinkler
31.3 in.
(795 mm)
30.0
(762 mm)
27.7
(704 mm)
TABLE A
SPRINKLER LENGTHS
23 Inch
(584 mm)
Sprinkler
24.3 in.
(617 mm)
23.0
(584 mm)
20.7
(526 mm)
Item
Sprinkler Identification Number (SIN)
K-factor, gpm/psi ½ (lpm/bar ½ )
Thread Size
Sprinkler Orientation
Maximum Working Pressure, psi (bar)
Description
TY7229
16.8 gpm/psi ½ (241,9 lpm/bar ½ )
1-1/4 in. NPT or ISO 7-R 1-1/4
Pendent
175 psi (12 bar)
TABLE B
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
TECHNICAL DATA
GROOVED
COUPLING
GASKET
SEALING
SURFACE
2" (DN50)
GROOVED
CONNECTION
THREADED
AND GROOVED
INLET
INLET
WRENCH
HEX
CASING
Technical
Data
Approvals
UL Listed
FM Approved
(Refer to Table D for specific details on
Laboratory listings and approvals.)
Grooved Connection
2 in. Standard Cut Grooved per
Technical Data Sheet TFP1898
Finish
Refer to Physical Characteristics
Physical Characteristics
Threaded and Grooved Inlet Bronze
Casing . . . . . . . . . . . . . . . .Galvanized Steel Pipe
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Additional Technical Data
Refer to Table B for additional technical data.
Operation
The casing between the inlet and the sprinkler remains dry until the sprinkler operates. The fusible link assembly is comprised of two link halves that are joined together by a thin layer of solder.
When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and allowing water to flow through the casing and to the activated sprinkler.
Design
Criteria
The following general guidelines and
Table C, provide the key design criteria for the TYCO Model ESFR-17 Dry Type
Pendent Sprinklers.
In all cases, the appropriate NFPA installation standard, or other applicable standard, must be referenced to ensure applicability and to obtain complete installation guidelines. The general guidelines in this technical data sheet are not intended to provide complete installation criteria. Refer to Table
C for additional information.
In addition to this technical data sheet, the following data sheets describe other TYCO ESFR Sprinklers:
• TFP312
Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
• TFP313
Model ESFR-22 (TY8226)
K=22.4 Pendnet Sprinkler
TFP320
Page 3 of 8
Storage Type
Sprinkler Type
Response Type
NFPA
ESFR
QR
FM Global
Storage
QR
System Type Wet Wet
Temperature Rating ºF (ºC) 1
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics
Idle Pallet Storage
165°F (74°C) 1
212°F (100°C)
Refer to NFPA 13
Refer to NFPA 13
Refer to NFPA 13
165°F (74°C) 1
Refer to FM 2-0 and 8-9
Refer to FM 2-0 and 8-9
Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard)
Flammable/Ignitable Liquid Storage
(Refer to the Standard)
Aerosol Storage
(Refer to the Standard)
Refer to NFPA 13
Refer to NFPA 30
Refer to NFPA 30B
Refer to FM 8-21
Refer to FM 7-29
Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
N/A
Notes:
1. Refer to Table D for specific details on Laboratory Listings and Approvals
N/A – Not Applicable
TABLE C
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Sprinkler
Type
Pendent
K=16.8 (TY7229)
Temperature
Rating
165°F (74°C)
212°F (100°C)
Laboratory Listings and Approvals
1, 2
1
Notes:
1. UL Listed
2. FM Approved
TABLE D
LABORATORY LISTINGS AND APPROVALS
• TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
• TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
• TFP317
Model ESFR-17 (TY7223)
K=16.8 Pendent Sprinkler
• TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
• TFP319
Model ESFR-14 (TY6236)
K=14.0 Pendent Sprinkler
Ceiling Construction
Unobstructed or non-combustible obstructed construction, such as
N/A smooth ceiling, bar joists, beam and girder.
Ceiling Slope
Maximum 2 in. rise for 12 in. run (16.7%)
Maximum Coverage Area
100 ft² (9,3 m²)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft² (5,8 m²)
Maximum Spacing
12 ft (3,7 m) for ceiling heights up to
30 ft (9,1 m)
10 ft (3,1 m) for ceiling heights greater than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in. (914 mm)
TFP320
Page 4 of 8
1" (25,4 mm) NOMINAL SYSTEM
PIPE
DIM. A
TABLE A
END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
HEATED
AREA
EXTERIOR
SURFACE OF
CEILING
CEILING
DEPTH
THREADED
FITTING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
DIM. B
TABLE A
6" (152 mm)
MINIMUM
14" (356 mm)
MAXIMUM
INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
FIGURE 2
THREADED CONNECTION INSTALLATION
1-3/8"
(35 mm)
SYSTEM
PIPE
DIM. A
TABLE A
END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)
FACE OF
SPRINKLER
FITTING
HEATED
AREA
EXTERIOR
SURFACE OF
CEILING
GROOVED
FITTING AND
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES
DIM. B
TABLE A
CEILING
DEPTH
6" (152 mm)
MINIMUM
14" (356 mm)
MAXIMUM
INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA
CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.
FIGURE 3
GROOVED CONNECTION INSTALLATION
Ambient
Temp. of
Protected
Area (a)
Exposed Barrel
Ambient
Temperature (b)(c)
40°F
(4°C)
50°F
(10°C)
60°F
(16°C)
Minimum Exposed
Barrel Length
Inches
(mm)
40°F
(4°C)
30 °F
(-1°C)
20°F
(-7°C)
10°F
(-12°C)
0°F
(-18°C)
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
-50°F
(-46°C)
-60°F
(-51°C)
0
0
4
(101,6)
8
(203)
12
(305)
14
(356)
14
(356)
16
(406)
18
(457)
20
(508)
20
(508)
0
0
0
1
(25,4)
3
(76)
4
(101,6)
6
(152)
8
(203)
8
(203)
10
(254)
10
(254)
0
0
0
0
0
Notes: a. The area below the ceiling is referred to as the protected area. Ambient temperature is the temperature at the discharge end of the sprinkler. For protected area temperatures that range between the listed temperatures, use the next cooler temperature.
b. Lengths are inclusive of wind velocities up to
30 mph (48,3 km/h) and assume a minimum 40°F
(4°C) in heated area.
c. Minimum exposed barrel length when Insulating
Seal Assembly is installed on exterior surface of ceiling:
• Threaded Fitting Installation
5 in. (125 mm) (Ref. Figure 2)
• Grooved Fitting Installation
4-1/2 in. (114 mm) (Ref. Figure 3)
TABLE E
MINIMUM EXPOSED
BARREL LENGTH REQUIRED
PER AMBIENT TEMPERATURE
1
(25,4)
3
(76)
4
(101,6)
4
(101,6)
6
(152)
6
(152)
NFPA
Deflector-to-Ceiling Distance
6 to 14 in. (152 to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Sprinkler Threaded Fittings
1-1/4 in. NPT Model ESFR-17 Dry Type
Sprinklers are to be installed in the
1-1/4 in. NPT outlet or run of the following fittings:
TFP320
Page 5 of 8
GROOVED
TEE
THREADED
SPRINKLER
FITTING
"INLET
SIDE"
W-TYPE 26
WRENCH
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
WELDED
GROOVED OUTLET
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA) WRENCH
JAW
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
GROOVED
DROP NIPPLE
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
MODEL
ESFR-17
DRY PENDENT
SPRINKLER
FIGURE 4
TYPICAL GROOVED
CONNECTION
OPTIONS
GROOVED
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
• malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3
(Class 150)
• cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125)
Do not install Model ESFR-17 Dry Type
Sprinkler into elbow fittings. The inlet of the sprinkler can contact the interior of the elbow and result in damage to the assembly, resulting in leakage.
The Model ESFR-17 Dry Type Sprinkler can also be installed in the 1-1/4 in. NPT outlet of a GRINNELL Figure
730 Mechanical Tee.
APPLY WRENCH
JAW TO INLET
WRENCH HEX
FIGURE 5
W-TYPE 26
SPRINKLER
WRENCH
Sprinkler Grooved Connection
The Model ESFR-17 Dry Type Sprinklers can be installed in typical grooved connection scenarios illustrated in
Figure 4.
For flexible couplings, use of the 2 in.
Figure 705 GRINNELL Flexible Couplings with “C” Shape Pre-Lubricated
Grade “A” EPDM Gasket (Ref. TFP1820) is recommended.
For rigid couplings, use of the 2 in.,
Figure 577 GRINNELL G-FIRE Grooved
Rigid Coupling with “C” Shape Pre-
Lubricated Grade “A” EPDM Gasket
(Ref. TFP1854) is recommended.
When using tees, use of the Figure
219 GRINNELL Grooved Ductile
Iron Cast Fittings (Ref. TFP1810) is recommended.
NOTICE
Do not install Model ESFR-17 Dry Type
Sprinkler into any other type fitting connection without first consulting TFPP
Technical Services. Failure to use the appropriate fitting may result in insufficient engagement of the inlet pipe threads with consequent leakage.
Exposure Length
When using Model ESFR-17 Dry Type
Sprinklers to protect areas subject to freezing temperatures, use Figures
2 and 3, and Table E to determine a sprinkler’s appropriate exposed barrel length to prevent water from freezing in the connection pipes due to conduction. The exposed barrel length measurement must be taken from the face of the sprinkler fitting to the exterior surface of the structure or insulation that is exposed to the heated area.
SYSTEM
PIPE
SPRINKLER
FITTING
CLEARANCE
HOLE
CEILING
SELF
TAPPING
SCREWS
ORIENT
HOUSING
SLOT 180°
OPPOSED
TO INSERT
SLOT
"FRAME
ARMS"
REFERENCE
MARKS
INDICATE
RELATIVE
SPRINKLER
FRAME ARM
ORIENTATION
BELOW
CEILING
SPRINKLER
FRAME
ARMS
FIGURE 6
SPRINKLER FRAME ARMS
ORIENTATION MARK
HOUSING
INSERT
INSULATION
RING
CLEARANCE
HOLE
ORIENT
INSULATION
RING SPLIT
BETWEEN
HOUSING
SLOT AND
SCREW
FIGURE 7
INSULATING SEAL ASSEMBLY
INSTALLATION
TFP320
Page 6 of 8
Do not attempt to add additional insulation around the barrel in the heated area as a method to minimize condensation. This will reduce the calculated exposure length.
Clearance Space
In accordance with NFPA 13, when protecting insulated freezer structures with dry type sprinklers, the clearance hole around the sprinkler barrel of the Dry Type Sprinkler and the clearance hole must be sealed. Sealing is accomplished by use of the Insulating
Seal Assemblies (Ref. Figure 7). Failure to use the Insulating Seal Assemblies will increase the potential for the formation of condensation on the sprinkler and subsequent ice build-up on or around the sprinkler can occur that might damage the dry type sprinkler and/or prevent proper operation in a fire situation.
FM Global 2-0
Consult FM Global and/or FM Global guidelines for allowable vertical distance from ceiling to centerline of thermal sensing element.
Installation
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using only the Casing to handle the sprinkler and by using the appropriate sprinkler wrench. Do not apply pressure to the fusible Link Assembly. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.
Model ESFR-17 Dry Type Sprinklers must only be installed in fittings/connections that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regarding piping design, exposure length, and the sealing of the clearance space around the sprinkler casing.
If a sprinkler using a threaded connection (vs. grooved connection) requires replacement, remove the sprinkler using only the W-Type 26 Sprinkler
Wrench. Fully engage the wrench on the inlet wrench hex (Ref. Figure 5).
Replace with the new sprinkler following the installation instructions in this section.
Threaded Connection
Instructions
A leak-tight 1-1/4 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 45 to
65 lb-ft (61 to 88 N ∙ m). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
Note: Install the Model ESFR-17 Dry
Type Pendent Sprinkler in the pendent position (Ref. Figure 5) by carefully raising the pendent sprinkler through the clearance hole. The deflector of the pendent sprinkler is to be parallel to the ceiling.
Step 1.
Apply a non-hardening pipe thread sealant such as TEFLON to the male 1-1/4 in. NPT inlet threads.
Step 2.
Wrench-tighten the Model
ESFR-17 Dry Type Sprinkler using only the W-Type 26 Sprinkler Wrench and by fully engaging the wrench on the inlet wrench hex (Ref. Figure 5). For reference, the “FRAME ARMS” marking can be used to align the frame arms with the System Pipe as shown in Figure 6.
Step 3.
After installation, inspect the
Link Assembly of each Model ESFR-17
Dry Type Sprinkler for damage. In particular, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assembly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.
Step 4.
Install the insulation rings of the
Insulating Seal Assemblies by slipping the insulation rings around the sprinkler casing as shown in Figure 7. Place the inserts over the insulation rings by sliding the inserts around the casing.
Place the housings over the Inserts and insulation rings ensuring that the slot on the housings are 180 degrees to the inserts slot. Ensure that the Insulating Seal Assemblies are snug against the refrigerated storage ceiling. Secure the Insulating Seal Assemblies to the ceiling using two self-tapping screws per assembly.
Grooved Connection
Instructions
The following instructions are based on using the 2 in. Figure 705 Grooved
Flexible Coupling or the 2 inch Figure
577 Grooved Rigid Coupling.
Step 1.
Inspect the exterior groove and the end connection of the mating grooved connection and sprinkler to verify all burrs, loose debris, dirt, chips, paint and other foreign materials such as grease are removed. Sealing surfaces must be free from sharp edges, projections, indentations, and/or other defects.
Step 2.
Verify that the coupling and gasket grade are correct for the application intended. Refer to Technical
Data Sheet TFP1895 for additional gasket information. The sealing edges and the outer surfaces of the gasket should be covered with a fine layer of lubricant. To prevent deterioration of the gasket material, a silicone lubricant should be used to prevent freezing of the lubricant.
Step 3.
Install the Model ESFR-17 Dry
Type Pendent Sprinkler in the pendent position (Ref. Figures 4 and 7) by carefully raising the pendent sprinkler through the clearance hole. The deflector of the pendent sprinkler is to be parallel to the ceiling. Also, ensure that the
“FRAME ARMS” markings on the sprinkler casing are aligned with the System
Pipe (Ref. Figure 6).
Step 4.
Install the gasket by placing it over the sealing portion of the grooved inlet connection so that the gasket lip does not extend beyond the end of the groove sealing surface. Bring end of the grooved inlet together with end of grooved fitting ensuring vertical and horizontal alignment. Slide the gasket over both sealing surfaces.
Step 5.
With one bolt and nut removed, separate the coupling housings and place over the gasket. Verify that the coupling housings are over the gasket and that the coupling housing keys are fully engaged into the grooves.
Step 6.
Insert the bolt and nut into the coupling and finger tighten both nuts.
Verify that the bolt heads are fully recessed in the housing.
The 2 in. Figure 705 Grooved Flexible
Coupling Housing bolt pads must be in metal-to-metal contact. For Flexible
Coupling deflection data, refer to Technical Data Sheet TFP1820.
The 2 in. Figure 577 Grooved Rigid
Coupling has an intended gap of up to
1/16 of an inch at each pad to allow for positive rigid gripping onto the pipe. The patented tongue and groove design provides protection to the back of the gasket during installation.
Step 7.
Alternate between both sides of the coupling when tightening the bolts.
Torque bolts to 30 lb-ft (41 N ∙ m).
Step 8.
Install the insulation rings of the
Insulating Seal Assemblies by slipping the insulation rings around the sprinkler casing as shown in Figure 7. Place the inserts over the insulation rings by sliding the inserts around the casing.
Place the housings over the Inserts and insulation rings ensuring that the slot on the housings is 180 degrees to the inserts slot. Ensure that the Insulating Seal Assemblies are snug against the refrigerated storage ceiling. Secure the Insulating Seal Assemblies to the ceiling using two self-tapping screws per assembly.
TFP320
Page 7 of 8
Care and
Maintenance
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection from the proper authorities and notify all personnel who may be affected by this action.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified or overheated sprinklers must be replaced.
A Vent Hole is provided in the Link
Assembly Button (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent
Hole indicates potential leakage past the Inlet seal and the need to remove the sprinkler to determine the cause of leakage; such as an improper installation or an ice plug. Close the fire protection system control valve and drain the system before removing the sprinkler.
When replacing a sprinkler, remove and discard the old Insulating Seal Assemblies and replace as shown in Figure 7.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, such as NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.
Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-17 Dry Type Early
Suppression, Fast Response 16.8K
Pendent Sprinklers (TY7229) with two (2) Insulating Sealing Assemblies,
P/N (specify):
36 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . . 61-441-1-360
212°F (100°C) . . . . . . . . . . . . . . . . . 61-442-1-360
30 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . . 61-441-1-300
212°F (100°C) . . . . . . . . . . . . . . . . . 61-442-1-300
23 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . . 61-441-1-230
212°F (100°C) . . . . . . . . . . . . . . . . . 61-442-1-230
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-17 Dry Type
Early Suppression, Fast Response
16.8K Pendent Sprinkler (TY7229) with
ISO 7-1 thread connection and two (2)
Insulating Sealing Assemblies, (specify temperature rating), P/N (specify):
36 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . I-61-441-1-360
212°F (100°C) . . . . . . . . . . . . . . . .I-61-442-1-360
30 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . I-61-441-1-300
212°F (100°C) . . . . . . . . . . . . . . . .I-61-442-1-300
23 Inch Sprinkler
165°F (74°C) . . . . . . . . . . . . . . . . . I-61-441-1-230
212°F (100°C) . . . . . . . . . . . . . . . .I-61-442-1-230
Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 56-341-1-001
Insulating Seal Assembly Kit
Each Insulating Seal Assembly kit consists of one (1) Insulation Ring, one (1)
Insert, one (1) Housing, and two (2)
Screws.
Specify: Insulating Sealing Assembly,
P/N 91-106-1-500
TFP320
Page 8 of 8
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademark of Special Metals Corporation
advertisement