Installation Instructions
ControlNet Ex Modular Repeater Adapter &
Fiber Repeater Module
Catalog Numbers 1797-RPA and 1797-RPFM
Contents
For Information About
Important User Information
About the ControlNet Ex Fiber Repeater Hub
DIN-Rail Mount the 1797-RPA and -RPFM
Installation in Zone 1 for CENELEC
Installation in Division 1/Zone 1 for UL, C-UL and FM
Electrostatic Charge
European Community (EC) Directive Compliance
Inputs/Outputs
Wire the Modules
Describing the ControlNet Ex System Diagram
Certification Specific ControlNet Ex System Diagrams
CENELEC Installation Label
CENELEC ControlNet Ex System Diagram
UL, C-UL ControlNet Ex System Diagram
FM ControlNet Ex System Diagram
Module Indicators
About the Mounting Kit
Repair
Specifications - 1797-RPA
Specifications - 1797-RPFM
Mounting Dimensions
20
22
24
26
12
13
15
17
18
19
26
27
29
31
9
9
8
8
4
5
See Page
2
Publication 1797-IN015G-EN-P - August 2017
2 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD
Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 3
ATTENTION
Environment and Enclosure
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
Backplane Connector Cover
Do not remove unless connecting to
1797-RPFM.
Indicators
1797-RPA
COMM
STATUS
MODULE
STATUS
Label Here
ControlNet Ex
Tap Drop BNC
Connector With
Insulator Boot
Module Locking Tab
1797-RPA
REPEATER
ADAPTER
PWR
1
+V
2
-V
3
+V
4
-V
Repeater
Backplane
Connector
Power and
Common Connections
41163
Publication 1797-IN015G-EN-P - August 2017
4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Backplane Connector Cover
Do not remove unless connecting to
1797-RPFM.
1797-RPFM
1797-RPFM
Label Here
Recv
Xmit
Chan 1
Chan 2
Recv
Xmit
Module Locking Tab
Repeater
Backplane
Connector
41267
About the ControlNet Ex Fiber Repeater Hub
Use the repeater adapter (1797-RPA) and the fiber module (1797-RPFM) together to form a repeater hub within the hazardous area to extend the length of the ControlNet Ex segments to interlink systems all operating within the area.
The 1797-RPA repeater adapter, configured with at least one repeater adapter, functions as the intelligent starter block for a multiport repeater. The
1797-RPFM is a nonintelligent fiber-to-backplane conversion device, converting glass-fiber infrared LED media signals to backplane signals for use by the 1797-RPA.
A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 5
DIN-Rail Mount the 1797-RPA and -RPFM
Refer to Mounting Dimensions on page 31. For panel mounting information, see publication 1794-5.13.
ATTENTION
This product is grounded through the DIN rail to the dedicated intrinsic safety ground. Use zinc-plated yellow-chromate steel
DIN rail to assure proper grounding. The use of other DIN rail materials (such as aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
1.
Position the module on a 35 x 7.5 mm DIN rail (A-B part number
199-DR1) at approximately a 30 o angle.
41167
ATTENTION
The DIN rail or mounting bracket must be appropriately connected to the dedicated intrinsic safety ground.
2.
Hook the lip on the rear of the adapter onto the top of the DIN rail, and rotate the module onto the rail.
41166
Publication 1797-IN015G-EN-P - August 2017
6 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
3.
Press the adapter down onto the DIN rail until flush.
The locking tab should snap into position and lock the module to the
DIN rail.
ATTENTION
Make certain that the adapter and fiber modules are secured together with DIN rail anchors. Failure to do so may result in the loss of communications, cause damage to the modules, or both.
4.
If the adapter does not snap into position, use a screwdriver or similar device to move the locking tab down while pressing the module flush onto the DIN rail.
Release the locking tab to lock the module in place. If necessary, push up on the locking tab to lock.
41168
5.
Remove the adapter backplane connector cover.
6.
Follow steps 1 to 4 to attach fiber modules to the DIN rail.
7.
Once attached to the DIN rail, slide fiber modules to the left to mate with the adapter.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 7
IMPORTANT
41169
A DIN-rail end anchor (A-B part number 1492-EA35) must be used on the left side of the adapter and on the right side of the fiber module to keep the units from moving.
8.
Make sure the last fiber module has its backplane connector cover in place.
9.
Connect the adapter wiring as shown below in the Wiring section.
IMPORTANT
You can only attach two media modules to the repeater adapter. If you exceed the module limit, you may cause damage to the adapter or fiber modules and void the IS certification.
Publication 1797-IN015G-EN-P - August 2017
8 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Installation in Zone 1 for CENELEC
Modules must not be exposed to the environment. Provide a suitable metal enclosure. A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet.
Allen-Bradley
1 Allen-Bradley Dr.
Mayfield Hts., OH USA
ControlNet Ex System
DMT 99 ATEX E 065 X
II (1)2G Ex ia ib IIC
0102
-20 0 C <= Ambient Temperature <= +70 0 C
Attention!
Avoid electrostatic charging!
WARNING
Modules cannot be used in an intrinsically safe environment after they have been exposed to nonintrinsically safe signals.
The fiber optic adapter type 1797-RPFM may be used in combination with the ControlNet adapter type 1797-RPA.
Installation in Division 1/Zone 1 for UL, C-UL and FM
This adapter must not be exposed to the environment. Provide a suitable metal enclosure. This adapter has a protection factor of IP20.
WARNING
This adapter cannot be used in an intrinsically safe environment after it has been exposed to nonintrinsically safe signals.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 9
Make certain that you only connect ControlNet Ex adapters to other intrinsically safe system modules to maintain the integrity of the intrinsically-safe backplane.
41307
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near this module:
WARNING Avoid electrostatic charging.
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA
ELETROSTÁTICA .
For your convenience, a sign that can be cut out is included in this installation instruction.
European Community (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the
European Community or EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
If this product has the CE mark it is approved for installation within the
European Community or EEA regions. It has been designed and tested to meet the following directives.
These products are tested to meet the Council Directive 2014/30/EU by applying the following standards:
• EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4:
Generic Standard for Industrial Environments (Class A)
• EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2:
Generic Standards - Immunity for Industrial Environments
• EN 61326-1:2013 (Industrial), Electrical Equipment For
Measurement, Control, and Laboratory Use - Industrial EMC
Requirements
Publication 1797-IN015G-EN-P - August 2017
10 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
European Hazardous Location Approval
The following applies to products marked II (1)2 G
• Are Equipment Group II, Equipment Category (1)2, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive
2014/34/EU. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.
• The type of protection is “Ex ib[ia] IIC T4” according to
EN 60079-11.
• Comply to Standards EN 60079-0:2006, EN 60079-11:2007, and
EN 60079-26:2004, reference certificate number
DMT 99 ATEX E 011 X.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur occasionally. Such locations correspond to Zone 1 or 2 classification according to ATEX directive 2014/34/EU.
IEC Hazardous Location Approval
The following applies to products with the IECEx certification:
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur only infrequently and for short periods. Such locations correspond to Zone 1 or 2 classification to IEC 60079-0.
• The type of protection is “Ex ib IIC T4” and “Ex ib[ia] IIC T4” according to IEC 60079-11.
• Comply to Standards IEC 60079-0:2004, IEC 60079-11:2006, reference IECEx certificate number IECEx BVS 09.0021X.
Special Conditions for Safe Use:
The fibre optic adapter type 1797-RPFM* can only be use in combination with the ControlNet adapter type 1797-RPA*.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 11
A warning sign shall be installed in the direct vicinity of this Fibre Optic Hub:
“Warning - Avoid electrostatic charging.” .
UL, C-UL Compliance
If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:
• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations
• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for Use in Hazardous (Classified) Locations
• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2
Hazardous (Classified) Locations
• UL 61010, UL Standard for Safety Electrical Equipment For
Measurement, Control, and Laboratory Use; Part 1: General
Requirements
• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive
Equipment for Use in Hazardous Locations
• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations
• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,
Part 0: General Requirements
• CSA-E79-11-95, Electrical Apparatus for Explosive Gas
Atmospheres, Part 11: Intrinsic Safety “i”
• CSA C22.2 No. 14-95, Industrial Control Equipment
FM Compliance
If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:
• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements
• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations
Publication 1797-IN015G-EN-P - August 2017
12 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
• FM C1. No.3615:1989, Explosionproof Electrical Equipment General
Requirements
• FM C1. No.3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment
• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment
Inputs/Outputs
Do not apply any nonintrinsically safe signals to the adapter or fiber modules.
When using as an intrinsically safe electrical apparatus according to EN
.
60079-11, the European directives and regulations must be followed
Power
Supply
+V
-V
1797-RPA
Channel
Network Bus
Fiber Hub Bus uC uC
41309
Receiver
Transmitter
1797-RPFM
Channel 1
Bus
Fiber Hub Bus
Channel 2
Receiver
Transmitter
Proc
41310
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 13
Wire the Modules
1.
Connect the ControlNet Ex tap drop cable to the connector after removing the insulator boot.
ControlNet Ex
Coax Tap
Insulator Ring
Installed
IMPORTANT
41170
The tap drop BNC must have its insulator ring in position when inserted in the adapter BNC connector.
2.
Connect the fiber media to the fiber module by selecting either the left or right set of receive and transmit ports and attaching the receive and transmit fibers, as appropriate.
IMPORTANT
Make note of which fiber is receive and which is transmit as they must be interchanged at the opposite end.
A B
Q UAL IT Y
Allen-Bradley
Comm
Status
Module
Status
1797 - RPA
A
-
B
Q UAL I TY
Allen-Bradley
Control Net E x
REPEATER ADAPTER
PWR
1 2 3 4
+V -V +V -V
1
Receive
Transmit
Recv Xmit
Chan 1 Chan 2
Recv Xmit
1797 - RPFM
Control Net E x
FIBER MODULE
MEDIUM RANGE
A B
Q UAL IT Y
Allen-Bradley
Comm
Status
Module
Status
1797 - RPA
A
-
B
Q UAL I TY
Allen-Bradley
Control Net E x
REPEATER ADAPTER
PWR
1 2 3 4
+V -V +V -V
1
1797 - RPFM
Control Net E x
FIBER MODULE
MEDIUM RANGE
Chan 1 Chan 2
Recv Xmit Recv Xmit
Transmit
Receive
41311
Publication 1797-IN015G-EN-P - August 2017
14 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
3.
Apply +V and -V power to the adapter through a removable terminal block from the Ex power supply.
+V -V +V -V
+V -V +V -V
41297
Screw terminals and spring terminals are provided.
4.
Strip the +V and -V wires to a length so no bare conductor shows after inserting the wires into position.
5.
If you are using the spring terminals of the plug, insert a screwdriver into the slot and carefully pry until the spring clamp opens to accept the wire.
WARNING
Do not use any unused terminals on this adapter. Using these terminals as supporting terminals can result in damage to the module and unintended operation of your system.
Make certain that you power this adapter with an intrinsically safe power supply. Do not exceed the values listed in the specifications for this adapter.
Do not remove or replace a module when power is applied.
Interruption of the bus can result in unintended operation or machine motion.
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Publication 1797-IN015G-EN-P - August 2017
IMPORTANT
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 15
Make sure all fiber modules are attached and secured prior to applying intrinsically safe power to the adapter. Failure to do so may cause damage to the adapter and modules.
Describing the ControlNet Ex System Diagram
A maximum of 48 ControlNet Ex nodes may be connected together by 250 m
(820 ft) of coax cable and 48 taps. The distance to increases to 1000 m (3280 ft) when you use only 2 taps. See the table below for more information.
The fiber media of the 1797-RPFM can be installed in a hazardous location
(Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II,
Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the nonhazardous location to connect the 1797-RPFM with any approved associated apparatus.
All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification or segregation method.
During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac).
Publication 1797-IN015G-EN-P - August 2017
16 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
System
Diagram Name
1797-RPA
Catalog
Number
1797-RPA
Catalog Name Description
1797-RPFM
CNet Ex Tap Trm 1797-TCAP
ControlNet Ex
Tap
CNet Ex Trk Trm
Coax Trunk Cable 1786-RG6
None
1797-RPFM
1797-TPx
1797-XT
None
ControlNet Ex
Modular Repeater
Adapter
ControlNet Ex Fiber
Repeater Module,
Medium Distance
1797-ACNR15/B 1797-ACNR15/B Redundant Media
ControlNet Ex
Adapter
ControlNet Ex Tap
(Dummy) Terminator
ControlNet Ex Coax
Tap
ControlNet Ex Trunk
Terminator
Quad-Shield, RG-6
75
Ω
Cable
Coax Trunk
Standard Coax Trunk
Cable BNC Couplers
Represents one ControlNet Ex node and must be connected to a coax trunk cable by
1797-TPx
Allows connection of a maximum of two devices per
1797-RPA and is powered directly by 1797-RPA
Represents one ControlNet Ex node and must be connected to a coax trunk cable by
1797-TPx -each one with two redundant output channels that are connected to different
ControlNet Ex networks (coax cables and 1797-TPx)
Represents one ControlNet Ex node and is a simple capacitor
(56 pF) with a coax connector
Four types of connections available: S (straight t-tap), R
(right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable
Simple resistor (75
Ω
) with coax connector that must be on each end of the ControlNet
Ex coax trunk for termination
Maximum (functional) length between 2 1797-TPx is 1000 m
(3280 ft) - each 1797-TPx reduces the (functional) coax cable length by 16.3 m (53.4 ft)
Different standard cable couplers, such as 90 o , 180 o .
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 17
Certified Equivalent ControlNet Ex System Diagram Items
You may use these items as equivalents for the items shown on the system diagram.
System Diagram Name
1797-RPA
1797-RPFM
1797-ACNR15
Coax Trunk Cable (1)
Catalog Number
1797-RPA
1797-RPFM
1797-ACNR15
1786-RG6
3092A (2)
3092A with blue jacket
1797-TPx
1797-XT
1797-TCAP
Source
Allen-Bradley
Allen-Bradley
Allen-Bradley
Allen-Bradley
Belden Wire & Cable Co.
Belden Wire & Cable Co.
Allen-Bradley
Allen-Bradley
Allen-Bradley
ControlNet Ex Tap
CNet Ex Trk Trm
CNet Ex Tap Trm
1 In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75
Ω
+ 3
Ω
Cable Capacitance = <5.94 nF per 100 m
Cable Resistance = >9.08
Ω
per 100 m
Cable Attenuation
(-20…70 °C)
0.2 MHz > 0.93 dB/100 m
0.5 MHz > 0.95 dB/100 m
1 MHz > 1.07 dB/100 m
5 MHz > 1.39 dB/100 m
10 MHz > 1.86 dB/100 m
20 MHz > 2.73 dB/100 m
2 MHz > 1.16 dB/100 m 50 MHz > 4.33 dB/100 m
2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance, nodes, or both.
Certification Specific ControlNet Ex System Diagrams
The following pages include certification specific ControlNet Ex system diagrams and notes pertaining to these diagrams. Select either CENELEC,
UL, C-UL, or FM and follow the requirements of that diagram as you configure and install your system.
Publication 1797-IN015G-EN-P - August 2017
18 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
CENELEC Installation Label
A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet.
Allen-Bradley
1 Allen-Bradley Dr.
Mayfield Hts., OH USA
ControlNet Ex System
DMT 99 ATEX E 065 X
II (1)2G Ex ia ib IIC
-20 0 C <= Ambient Temperature <= +70 0 C
Attention!
Avoid electrostatic charging!
0102
CENELEC 1797-RPA, -RPFM I/O Entity Parameters
Terminals U o
(V) I o
(mA) Groups
Male Bus
Connector
5.4
400 IIB/IIC
C o
(
μ
F)
65
L o
(
μ
H)
10
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 19
CENELEC ControlNet Ex System Diagram
Publication 1797-IN015G-EN-P - August 2017
20 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
UL, C-UL ControlNet Ex System Diagram
. .
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 21
UL, C-UL ControlNet Ex System Requirements
The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of V oc
and I sc
or V t
and I t
of the associated apparatus are less than or equal to V max
and I max
of the intrinsically safe apparatus and the approved values of C a
and L a
of the associated apparatus are greater than C i
+ C cable
and L i
+ L cable
respectively for the intrinsically safe apparatus.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.
If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location.
The glass fiber must have a minimum diameter of 6 μ m.
UL, C-UL, FM 1797-RPA, -RPFM I/O Entity Parameters
Terminals V t
(V) I t
(mA) Groups C a
(
μ
F)
Male Bus
Connector
5.8
400 A to G 3.0
L a
(
μ
H)
3.0
Publication 1797-IN015G-EN-P - August 2017
22 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
FM ControlNet Ex System Diagram
. .
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 23
FM ControlNet Ex Requirements
The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of V oc
and I sc
or V t
and I t
of the associated apparatus are less than or equal to V max
and I max
of the intrinsically safe apparatus and the approved values of C a
and L a
of the associated apparatus are greater than C i
+ C cable
and L i
+ L cable
respectively for the intrinsically safe apparatus.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505. For additional information refer to
ANSI/ISA RP12.6.
WARNING: Substitution of components may impair intrinsic safety.
If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location.
The glass fiber must have a minimum diameter of 6 μ m.
The ControlNet Ex tap must be connected directly to the module (no additional cable may be connected).
Must be FM approved.
Total coax trunk cable length is limited to 1000 m (3280 ft) with up to 2
ControlNet Ex taps connected and to 250 m (820 ft) with the maximum allowed ControlNet Ex taps of 48. For ControlNet Ex taps between 2 and 48 use: 1000 m (3280 ft) - 16.3 m (53.4 ft) x (number of taps - 2) to find the maximum allowed cable length.
Publication 1797-IN015G-EN-P - August 2017
24 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Module Indicators
The following explains the indications seen on the 1797-RPA and
1797-RPFM modules.
1797-RPA Indicators
The figure below identifies indicators on the repeater adapter.
1797-RPA
Comm Status
1797-RPA
Module Power Status
COMM
STATUS
MODULE
STATUS
REPEATER
ADAPTER
PWR
Module Status
1
+V
2
-V
3
+V
4
-V
41174
Power Indicator
If
Steady Green
Off
This Indicates
Power is applied.
No power is applied.
Comm and Module Status Indicators for the 1797-RPA Module
If Both Are
Alternately
Red/Green
Steady Green
Off
Red
This Indicates
The adapter is being powered-up or reset. The LEDs alternately flash red and green for about 5 s.
Normal operation.
The unit is not powered. Check the module power status.
There is an adapter fault.
If the fault indication is caused by a jabber condition, the fault indication will automatically be cleared when the jabber condition is removed from the coax or fiber port.
If a jabber condition is not causing the fault, replace the repeater adapter.
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 25
If Either Is
Flashing Green/Off
Flashing Red/Off
The Respective Segment (1 or 2) is
Experiencing temporary network errors.
The situation will normally correct itself. If the situation persists, troubleshoot your nodes and cable system. When troubleshooting your cable system, make sure:
• all BNC connector pins are properly sealed.
• all taps are A-B taps.
• all terminators are 75
Ω
and are installed at both ends of all segments.
Experiencing a high level of network errors.
This may indicate a broken cable, broken tap, or missing segment terminator.
Important: The indicators will flash red/off when a system has no network activity. This would be normal for a system that has no
ControlNet nodes installed or enabled.
1797-RPFM Indicators
The figure below identifies indicators on the fiber module.
1797-RPFM
1797-RPFM
Channel 1 Status
Channel 2 Status
Recv Xmit
Chan 1
Chan 2
Recv
Xmit
1797-RPFM Comm and Status Indicators
If Both Are
Off
Green
Flashing Green/Off
This Indicates
There is no power or the module is faulted.
The channel is operational.
There is no data activity on the associated channel.
41312
Publication 1797-IN015G-EN-P - August 2017
26 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
About the Mounting Kit
Use the optional 1794-NM1 mounting kit to mount your system on a panel or wall without a DIN rail.
1794-NM1
Mounting Kit with
18 screws (2 screws for the adapter and 2 screws for each module).
30238
Repair
The adapter and fiber module are not field-repairable. Any attempt to open this adapter or fiber module will void the warranty and the IS certification. If repair is necessary, return the modules to the manufacturer.
IMPORTANT
For detailed certification information, refer to the FLEX Ex
System Certification Reference Manual, publication
1797-RM001 .
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 27
Specifications - 1797-RPA
I/O Capacity
IS Media Type
IS Module Type
Communication Rate
ControlNet Ex BNC
Indicators
Output (Intrinsically Safe)
(30 Pin Male TTL Bus
Connector)
Isolation Path
Bus to Power Supply
Adapter to Adapter
ControlNet Ex Node to Other
Nodes
ControlNet to Power Supply
Power Supply
(-V, +V Intrinsically Safe)
Power Consumption
Power Dissipation
Thermal Dissipation
Conductors
Dimensions
2 fiber modules
Ex ib IIB/IIC T4,
AEx ib IIC T4,
Class I, Division 1 Groups A to G T4
Ex ib IIB/IIC T4,
AEx ib IIC T4,
Class I Division 1 Groups A to D T4
5 Mbps
I
Oscillation powered by:
U o
< 5.4V dc o
< 201 mA ac coupled with high-pass filter f > 500 kHz
Comm - green/red
Module - green/red
Power - green
I
Manufacturer specific bus
U o
< 5.4V
P
L o
< 201 mA o
< 1.09 W o
< 0.45 mH
C o
< 71
μ
F
Galvanic to DIN EN 60079-11
Galvanic functional
Galvanic functional
Galvanic to DIN EN 60079-11
I
U i i
< 9.5V dc
< 1 A
P
L i
< 9.5 W i
= negligible
C i
< 120 nF
8.5 W
8.5 W
29 BTU/hr
Wire Size 4 mm 2 (12 gauge) stranded max
1.2 mm (3/64 in.) insulation max
Metric
Imperial
94 mm x 94 mm x 91 mm
(3.7 in. x 3.7 in. x 3.58 in.)
Publication 1797-IN015G-EN-P - August 2017
28 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Weight
Environmental Conditions
Operational Temperature
Approximately 200 g
Storage Temperature
-20…70 o C (-4…158 o F)
-40…85 o C (-40…185 o F)
Relative Humidity
Shock
Vibration
5…95% noncondensing
Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width
Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse width
Tested 2 g @ 10…500 Hz per IEC 68-2-6
Agency Certification
CENELEC II (1) 2G ib[ia] IIC T4
UL, C-UL Class I Division 1 Groups A to D T4
Class I Zone 1 AEx ib IIC T4
FM Class I Division 1 Groups A to D T4
Class I Zone 1 AEx ib IIC T4
INMETRO BR-Ex ia/ib IIB/IIC T4
IECEx Ex ib IIC T4 and Ex ib[ia] IIC T4
Certificates
CENELEC DMT 99 ATEX E011 X
UL, C-UL UL File Number E197983
Class I Division 1 Hazardous
FM FM Certificate Number 3009806
FM
INMETRO 05/UL-BRAE-0011X
IECEx IECEx BVS 09.0021X
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 29
Specifications - 1797-RPFM
IS Media Type
IS Module Type
Ex ia IIB/IIC T4,
AEx ia IIC T4,
Class I, Division 1 Groups A to G T4
Ex ib IIB/IIC T4,
AEx ib IIC T4,
Class I Division 1 Groups A to D T4
Communication Rate 5 Mbit/s
Approximate Fiber Media Length 3 km
Fiber Type
Fiber Termination Type
Fiber Operating Wavelength
Optical Power Budget
Fiber Optic Transmitter
Ch1 and Ch2
Indicators
Input (Intrinsically Safe)
(30 Pin Female TTL Bus
Connector)
Output (Intrinsically Safe)
(30 Pin Male TTL Bus
Connector)
Isolation Path
Bus to ControlNet
Power Consumption
Power Dissipation
Thermal Dissipation
Weight
Dimensions Metric
Imperial
62.5…125 mm
ST (plastic or ceramic)
1300 nm
13.3 dB
Optical peak output power
P optical
< 1 mW
Channel 1 status - green
Channel 2 status - green
I
U i
< 5.4V
i
< 201 mA
P i
< 1.1 W
L
C i
< 15 i
< 41
μ
H
μ
F
I
U o
< 5.4V
o
< 201 mA
P
L o
< 1.1 W o
< 0.45 mH
C o
< 71
μ
F
Galvanic to DIN EN 60079-11
Included in 1797-RPA
Included in 1797-RPA
Included in 1797-RPA
Approximately 100 g
94 mm x 94 mm x 91 mm
(3.7 in. x 3.7 in. x 3.58 in.)
Publication 1797-IN015G-EN-P - August 2017
30 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module
Environmental Conditions
Operational Temperature
Storage Temperature
-20…70 o C (-4…158 o F)
-40…85 o C (-40…185 o F)
5…95% noncondensing Relative Humidity
Shock
Vibration
Agency Certification
Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width
Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse width
Tested 2 g @ 10…500Hz per IEC 68-2-6
CENELEC II (1) 2G ib[ia] IIC T4
UL, C-UL Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib [ia] IIC T4
FM Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib IIC T4
INMETRO BR-Ex ia/ib IIB/IIC T4
IECEx Ex ib IIC T4 and Ex ib[ia] IIC T4
Certificates
CENELEC DMT 99 ATEX E011 X
UL, C-UL UL File Number E197983
Class I Division 1 Hazardous
FM FM Certificate Number 3009806
FM
INMETRO 05/UL-BRAE-0011X
IECEx IECEx BVS 09.0021X
Publication 1797-IN015G-EN-P - August 2017
ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 31
Mounting Dimensions
Publication 1797-IN015G-EN-P - August 2017
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com
, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
United States 1.440.646.3434 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for return procedure.
Allen-Bradley, Rockwell Automation, ControlLogix, RSLinx, TechConnect, and FLEX I/O are trademarks of
Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
.
Publication 1797-IN015G-EN-P - August 2017
Supersedes Publication 1797-5.15 - June 2010
PN-455768
Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.