Below you will find brief information for Analog I/O Conversion Module 1492-CM1771-LA001. This module converts 1771, 16 Channel I/O modules to 1756, 16 Channel I/O modules without removing field wires. It uses a conversion module, cable, and mounting assembly. Installation doesn't require removing existing 1771 Swing Arm field wires. Refer to the manual for compatibility and wiring diagrams.
Advertisement
Advertisement
Analog I/O Conversion Module
(Cat 1492-CM1771-LA001)
I. Description
This Analog I/O Conversion Module provides for the conversion of (1) 1771, 16 Channel I/O module to be converted to (1) 1756, 16 Channel I/O module and consists of the following:
(1) 1771 Module (16ch) to (1) 1756 Module (16ch)
(2) Conversion Module: 1492-CM1771-LA001
(1) Cable: 1492-CONACAB005A or 1492-CONACAB005B (Table 2)
(1) Conversion Mounting Assembly: 1492-MUA… (Table 1)
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the
1492 Cable is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the 1756 I/O module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion
Module and the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in
Section V. As standard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length.
Refer to the footnotes in Table 2 for further details.
Conversion Compatibility and Product I.D. Label
25-Pin Connector for cable
1492-CONACAB005A OR -CONACAB005B
1492-CM1771-LA001 Conversion Module
WARNING De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
Printed in U.S.A.
II. Installation
The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.
2) Select the applicable 1492 Conversion Modules from Table 2, Section III.
3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.
4) Select a 1756 I/O Chassis which has enough I/O Slots.
NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O modules.
5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots.
NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2)
1771 I/O module convert to (1) 1756 I/O modules.
NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the
1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.
Table 1: Bulletin 1771 to 1756 Chassis Conversion
1756 Chassis Conversion Mounting Assembly
Cat. No.
1771 Chassis
Chassis Width
Max
Slots for
I/O without
Power
Supply with
Power
Supply
Cat. No.
Max
Slots for
I/O
Chassis
Width
Cat. No.
Max Slots for
Conversion
Modules
Chassis
Width
1771-A1B 4 9.01
1756-A4
12.61
1756-A7
1771-A2B 8 14.01
1756-A7
17.61
1756-A10
3 10.35
1492-MUA1B-A4-A7 4 9.01
6 14.49
6 14.49
1492-MUA2B-A7-A10 8 14.01
9 19.02
1771-A3B1
1756-A10
12 19.01
9 19.02
1492-MUA3-A10-A13 12 19.01
1756-A13 12 23.15
1771-A4B 16 24.01
1756-A13 12 23.15
1492-MUA4-A13-A17 16 24.01
1756-A17 16 29.06
Foot Notes:
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The
Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or
Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(2)
III. Compatibility
1771 1756
Analog I/O Module Analog I/O Module I/O Conversion Module
1771-IFE (SEC)
1771-IFE (SEV)
1771-IFF (SEC)
1771-IFF (SEV)
1771-IF16 (SEC)
1771-IF16 (SEV)
1771-IF16 (SEC)
1771-IF16 (SEV)
1492-CM1771-LA001
1492-CM1771-LA001
1492-CM1771-LA001
1492-CM1771-LA001
1492
Cable
1492-CONACAB005B
1492-CONACAB005A
1492-CONACAB005B
1492-CONACAB005A
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown.
Additional cable lengths are as follows:
1.0M = 1492-CONACAB010A
1.0M = 1492-CONACAB010B
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
0 to 60°C (32 to 140°F)
5 to 95% at 60°C (non-condensing)
50g
30g
Value
Dimensions
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
Storage Temperature
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
Approximate Shipping Weight 250.6 g (0.55 lbs) (includes carton)
-40 to +85°C (-40 to +185°F)
Operating Temperature
Operating Humidity
Shock
Non operating
Operating Vibration
Maximum Operating Voltage
Max. Module Operating Current
Per Point:
Per Module:
Agency Certifications
Pollution Degree
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
30 Vdc
2 Amps
12 Amps
NOTICE Refer to the Wiring Diagram(s) for current limits for a specific configuration.
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
2
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E (3)
V. Wiring Diagrams Conversion: 1771-IFE to 1756-IF16 (Single-ended Current)
WARNING
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Power Supply
+
-
2-Wire Transmitter
Transmitter
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
1771-WG Swing Arm
From 1771-IFE
7
8
9
5
10
15
20
21
3
4
1
2
6
16
17
18
19
11
12
13
14
Conversion Module
1492-CM1771-LA001 Cable
1492-CONACAB005B
22
23
24
25
18
19
20
21
14
15
16
17
7
8
5
6
3
4
1
2
9
10
11
12
13
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
SH
19
21
23
25
27
29
31
33
35
1
3
5
7
9
11
13
15
17
30
32
34
36
20
22
24
26
12
14
16
18
10
6
8
2
4
28
1756-IF16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
RTN
RTN
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15 iRTN-0 iRTN-1 iRTN-2 iRTN-3
RTN iRTN-4 iRTN-5 iRTN-6 iRTN-7 iRTN-8 iRTN-9 iRTN-10 iRTN-11
RTN iRTN-12 iRTN-13 iRTN-14 iRTN-15
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block.
Refer to the 1756-IF16 Installation Manual for modification details.
The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, details. [Reference Doc: 41170-944 (Version 02)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(4)
V. Wiring Diagrams (Cont’d) Conversion: 1771-IFE to 1756-IF16 (Single-ended Voltage)
WARNING
3-Wire Transmitter
Transmitter
+
Power Supply
-
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
3
4
6
1
2
7
8
9
5
10
15
20
21
16
17
18
19
11
12
13
14
Conversion Module
1492-CM1771-LA001 Cable
1492-CONACAB005A
22
23
24
25
18
19
20
21
14
15
16
17
7
8
5
6
3
4
1
2
9
10
11
12
13
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
SH
12
14
16
18
6
8
2
4
10
9
27
28
30
32
34
36
20
22
24
26
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
1756-IF16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
R TN
R TN
R TN
R TN
1771-WG Swing Arm
From 1771-IFE
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16 terminal block.
Refer to the 1756-IF16 Installation Manual for modification details.
The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
[Reference Doc: 41170-945 (Version 02)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(5)
V. Wiring Diagrams Conversion: 1771-IFF to 1756-IF16 (Single-ended Current)
WARNING
Power Supply
+
-
2-Wire Transmitter
Transmitter
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
3
4
6
1
2
7
8
9
5
10
15
20
21
16
17
18
19
11
12
13
14
Conversion Module
1492-CM1771-LA001 Cable
1492-CONACAB005B
17
18
19
20
21
14
15
16
22
23
24
25
7
8
5
6
3
4
1
2
9
10
11
12
13
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
SH
1771-WG Swing Arm
From 1771-IFF
12
14
16
18
10
6
8
2
4
RTN
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15 iRTN-8 iRTN-9 iRTN-10 iRTN-11
RTN iRTN-12 iRTN-13 iRTN-14 iRTN-15 iRTN-0 iRTN-1 iRTN-2 iRTN-3
RTN iRTN-4 iRTN-5 iRTN-6 iRTN-7
28
21
23
25
27
13
15
17
19
29
31
33
35
1
3
5
7
9
11
20
22
24
26
30
32
34
36
1756-IF16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
RTN
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
This design assumes that all inputs on the 1771-IFF were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block. Refer to the
1756-IF16 Installation Manual for modification details.
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, details. [Reference Doc: 41171-023 (Version 00)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(6)
V. Wiring Diagrams (Cont’d) Conversion: 1771-IFF to 1756-IF16 (Single-ended Voltage)
WARNING
3-Wire Transmitter
Transmitter
+
Power Supply
-
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
5
10
15
20
21
6
7
8
9
3
4
1
2
14
16
17
18
19
11
12
13
Conversion Module
1492-CM1771-LA001 Cable
1492-CONACAB005A
17
18
19
20
21
14
15
16
22
23
24
25
6
7
4
5
8
1
2
3
9
10
11
12
13
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
SH
20
22
24
26
30
32
34
36
12
14
16
18
10
6
8
2
4
9
27
28
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
1756-IF16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
RTN
RTN
RTN
RTN
1771-WG Swing Arm
From 1771-IFF
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16 terminal block. Refer to the
1756-IF16 Installation Manual for modification details.
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
[Reference Doc: 41171-024 (Version 00)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(7)
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
Printed in U.S.A.

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Converts 1771 I/O to 1756 I/O
- No field wire removal needed
- Uses existing 1771 Swing Arm
- Multiple cable length options
- Shield grounding features
- Wiring diagrams available