Rockwell Automation Allen-Bradley 2198-P141 Application Technique
Rockwell Automation Allen-Bradley 2198-P141 is a powerful and versatile Bus Supply designed for use in Common Bus Configurations. It offers exceptional performance, reliability, and flexibility, making it an ideal choice for a wide range of industrial applications. This device is compatible with Kinetix 5700 drives and provides a stable and efficient DC-bus voltage, ensuring optimal system operation.
Advertisement
Advertisement
Application Technique
Original Instructions
Drives in Common Bus Configurations with Kinetix 5700 Bus Supplies
Catalog Numbers 2198-P031, 2198-P070, 2198-P141, 2198-P208, 2198-RP088, 2198-RP200, 2198-RP263, 2198-RP312
Drives in Common Bus Configurations with Kinetix 5700 Bus Supplies Application Technique
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc
Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
2 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Table of Contents
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 3
4
Table of Contents
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Preface
An increasing number of drive systems, in a wide range of applications and power ranges, are being configured today in common bus configurations. These system configurations provide significant advantages, such as design flexibility, high efficiency, and cost savings.
It is the objective of this publication to provide the necessary guidelines, considerations, and limitations for the proper application of
Kinetix® and PowerFlex® drives that are used in common-bus configurations with Kinetix 5700 bus supplies.
Download Firmware, AOP, EDS, and Other Files
Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes from the Product Compatibility and
Download Center at rok.auto/pcdc .
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 5
Preface
Notes:
6 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Chapter
1
DC-bus Wiring Guidelines
This chapter provides guidelines for wiring DC common-bus drive systems. Common-bus configurations can be regenerative or nonregenerative. Other variations include active and passive shunt resistors.
Common Bus Configuration
Non-regenerative (diode-front-end)
Regenerative with active shunt
Definition
The non-regenerative common DC-bus topology uses a pulse-width modulated (PWM) controlled insulated-gate bipolar transistor (IGBT) converter that provides single-direction power flow from the incoming AC line. The full-wave bridge rectifier converts three-phase AC voltage to a fixed DC-bus voltage. This configuration contains one or more inverter drives connected directly to the DC common bus.
Non-regenerative with passive or active shunt Same as non-regenerative, but with an added shunt module to dissipate excess regenerative DC-bus energy to a resistor.
Regenerative (active-front-end)
The regenerative bus supply, active front end (AFE) topology, uses a pulse-width modulated (PWM) controlled insulatedgate bipolar transistor (IGBT) converter that enables bidirectional power flow from and back to the incoming AC line. The full-wave bridge rectifier converts three-phase AC voltage to a fixed DC-bus voltage. When the DC-bus voltage is increased above a threshold, a portion of the DC-bus voltage is converted back to three-phase AC voltage. This configuration contains one or more inverter drives connected directly to the DC common bus.
Same as regenerative, but with an added shunt module. In this configuration, some regenerative DC-bus energy flows to the incoming AC line, and the excess DC-bus energy (that is not regenerated) is dissipated to an external active shunt module. See Kinetix® 5700 Servo Drives User Manual, publication 2198-UM002 , for specific active shunt recommendations to be used with the 2198-RP xxx
regenerative bus supply.
Drive Systems
Generally, it is desirable to have the Kinetix 5700 drive mounting order match the machine layout. However, if a mix of drive frame sizes is used in the system, we recommend that the inverter modules are mounted according to power rating (highest to lowest) from left to right (or right to left) starting with the highest power rating. The DC-bus power supply or regenerative bus supply can be mounted anywhere within the cluster.
It is often advantageous to place the Kinetix 5700 bus supply in the middle of the line-up to minimize the distance to the farthest loads.
Shorter distances can minimize the energy that is stored in the parasitic inductance of the bus structure, which helps to lower peak-bus
drive system with a PowerFlex® 750-Series drive, Kinetix 7000 drive, and Kinetix 6000 drive system all powered by the 2198-RP xxx regenerative bus supply.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 7
Chapter 1 DC-bus Wiring Guidelines
Figure 1 - Extended DC-bus Installation Example
Regenerative
Bus Supply
Single-axis
Inverter
Dual-axis
Inverters
Accessory
Modules
Kinetix 5700
Servo Drive System
MOD
NET
MOD
NET
MOD
NET
MOD
NET
MOD
NET
MOD
DC BUS
2
1
1
I/O
6
5 10
OK+
OK–
EN–
EN+
2
1
1
I/O
6
5
UFB
10
2
1
1
I/O-A
6 1
I/O-B
6
2
1
1
I/O-A
6 1
I/O-B
6
5
UFB-A
10 5 10
UFB-B
5
UFB-A
10 5
UFB-B
10
MODULE
STATUS
2198-DCBUSCOND-RP312
DC-bus Conditioner Module
D+
D-
MF
D+
D-
D+
D-
MF-A MF-B
D+
D-
MF-A
D+
D-
MF-B
-
MBRK
+ Line
Disconnect
Device
Circuit
Protection
Magnetic (M1)
Contactor
AC Line Filter
Bulletin 1321
Line Reactor
DC-bus
Extension
DC-bus Circuit
Protection
2198-CAPMOD-2240
Capacitor Module
Bulletin 1492 Power Distribution
Terminal Block
2094-BM xx
-M xx-
S
IAM Module
Common Bus Follower
2094-PRS x
Power Rail
Bonded Cabinet
Ground Bus
PowerFlex
750-Series AC Drive
2099-BM xx-
S
Servo Drive
Kinetix 6000 Servo Drive System
Kinetix 7000
Servo Drive
2094-BM xx
-S
Axis Modules (5)
DC-bus Circuit
Protection
DC-bus Circuit
Protection
DC-bus Connections
DC-bus cables and bus bars are used to connect drives in common-bus configurations.
IMPORTANT The interconnection of drives to the DC-bus, and the inductance levels between the drives, must be kept to a minimum for optimum system operation.
DC-bus Cable
When using cables to connect drives to the system bus, observe the following guidelines:
• Use only unshielded cable for DC-bus voltage.
• Use 1000V rated insulation cable in this application.
• Make the DC+ and DC– cable distance as short as possible to help reduce cable inductance.
• Twisting the DC-bus cable together is not required, however, it is recommended to make sure the DC cables are routed close to each other.
• The maximum DC-bus cable length (power supply cluster to extended cluster) is 70 m (230 ft).
• No single external DC-bus connection from the power supply cluster can exceed 70 m (230 ft). You can extend the DC-bus from the right and left of the power supply cluster, but the total DC-bus length (including DC-bus cabling and DC bus-bar) from the power supply cluster to all extended clusters cannot exceed 140 m (459 ft).
• The Bus Voltage Reference Source is configurable. When it is set to Automatic, the converter optimizes the Bus Voltage Reference for the best converter setting. When it is set to Manual, you configure the desired Bus Voltage Set Point value for the Bus Voltage
Reference signal.
• To prevent nuisance bus-overvoltage faults, the maximum Bus Voltage Set Point of the regenerative bus supply reduces linearly from
750V DC to 715V DC as the DC-bus cable length per cluster increases from 0 to 70 m (230 ft) respectively.
8 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
DC-bus Wiring Guidelines Chapter 1
Figure 2 - DC-bus Cable Length per Cluster
735
730
725
720
750
0
745
740
715
0
32.8
10
DC-bus Cable Length per Cluster (ft)
65.6
98.4
131 164
20 30 40 50
DC-bus Cable Length per Cluster (m)
197
60
230
70
IMPORTANT Use low-inductance DC cable routing to help reduce the risk of voltage oscillations between clusters.
Low-inductance DC cable routing can be achieved by means of positive and negative cables routed in parallel and as close to one another as possible, less than 0.3 m (1.0 ft). Low-inductance DC-bus connection, a feature of the Kinetix 5700 drive system, is also achieved by using
2198-BARCONxxxx
200 DC-bus link connector kits that are included in each Kinetix 5700 inverter.
Size the DC cable in accordance with UL or applicable agency guidelines. Because voltage drop is directly proportional to cable resistance, you can further reduce the voltage drop across the DC cable by using a larger AWG cable size.
Table 1 - Recommended DC-bus Cable Gauge
Recommended DC-bus Cable Gauge mm
2
(AWG/MCM)
Regenerative Bus Supply
Cat. No.
2198-RP088
2198-RP200
2198-RP263
2198-RP312
DC-bus Power Supply
Cat. No.
2198-P031
2198-P070
2198-P141
2198-P208
2198-P208 x 2
2198-P208 x 3
53.5 (1/0)
152 (300 MCM)
Recommended DC-bus Cable Gauge mm
2
(AWG/MCM)
53.5 (1/0)
152 (300 MCM)
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 9
Chapter 1 DC-bus Wiring Guidelines
Wire the External DC-bus Connections
The 2198-CAPMOD-2240 capacitor module and 2198-CAPMOD-DCBUS-IO extension module are used to extend the DC-bus voltage to external inverter drives. They also provide energy storage. The capacitor module is used alone when the external DC-bus current is ≤104 A. The capacitor module, combined with a DC-bus module or an extension module, is required when the external DC-bus current is >104 A, up to a maximum 208 A.
accessory modules, see
Kinetix 5700 Accessory Modules
on
Figure 3 - Kinetix 5700 External DC-bus Connection Wiring Example
Flexible Bus-bars
User-supplied External DC-bus
Wire Lug Connections
Kinetix 5700
2198-P xxx
DC-bus Power Supply
Kinetix 5700
2198-S xxx
2198-D
-ERS xxx x
or
-ERS x
Inverter
To External
Inverter Drives or
Active Shunt Modules
DC+
DC-
1
2
24V_COM
+24V
PE Ground
DC+
DC-
24V_COM
+24V
DC+
DC-
DC+
DC-
DC-bus
(DC) Connectors
2198-CAPMOD-DCBUS-IO
Extension Module
24V_COM
+24V
Control Power
(CP) Connectors
PE Ground
Module Status
(MS) Connector
MS
MS
1
2
Monitor capacitor module status by wiring to digital input Bus Capacitor OK on the DC-bus power supply or to a Logix 5000™ controller.
2198-CAPMOD-2240
Capacitor Module
PE Ground PE Ground
Bonded Cabinet Ground Bus (user-supplied component)
DC Bus Bar
When using DC bus-bar to connect drives to the system bus, observe the following guidelines:
• DC-bus fuses are required between the Kinetix 5700 power supply cluster and the common DC bus-bar. DC-bus fuses are also required between the DC bus-bar and the DC input of any external inverter drives. See
Kinetix and PowerFlex Drive Specifications on page 59
for the recommended common DC-bus circuit protection devices.
• No single external DC-bus connection from the power supply cluster can exceed 70 m (230 ft). You can extend the DC-bus from the right and left of the power supply cluster, but the total DC-bus length (including DC-bus cabling and DC bus-bar) from the power supply cluster to all extended clusters cannot exceed 140 m (459 ft).
10 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
DC-bus Wiring Guidelines Chapter 1
Figure 4 - DC Bus-bar Application
Regenerative Bus Supply
Accessory
Modules
MOD
NET
Kinetix 5700
Servo Drive System
(power supply cluster #1)
2
1
1
I/O
6
5 10
OK+
OK–
EN–
EN+
MODULE
STATUS
2198-DCBUSCOND-RP312
DC-bus Conditioner Module
2198-CAPMOD-2240
Capacitor Module
DC-bus
Extension
DC-bus Circuit
Protection
DC-bus Bar
DC-bus Circuit
Protection
2198-DCBUSCOND-RP312
DC-bus Conditioner Module
Accessory
Modules Dual-axis Inverters
MOD
DC BUS
MODULE
STATUS
MOD
DC BUS
MOD
NET
MOD
NET
MOD
NET
MOD
NET
2
1
1
I/O-A
6 1
I/O-B
6
MODULE
STATUS 5
UFB-A
10 5
UFB-B
10
I/O-A
6 1
I/O-B
6
2
1
1
I/O-A
6 1
I/O-B
6
I/O-A
6 1
I/O-B
6
UFB-A
10 5
UFB-B
10 5
UFB-A
10 5
UFB-B
10
UFB-A
10 5
UFB-B
10
Kinetix 5700
Servo Drive System
(cluster #2)
MF-A MF-B MF-A MF-B
MF-A MF-B MF-A MF-B
2198-CAPMOD-2240
Capacitor Module
Kinetix 6000 Servo Drive System
2094-BM xx
-M xx-
S
IAM Module
Common Bus Follower
2094-PRS x
Power Rail
2094-BM xx
-S
Axis Modules (5)
Precharge
Precharge is the process of gradually increasing the DC-bus voltage. During this increase in DC-bus voltage, the DC-bus filter capacitors are charged in a controlled manner. The precharge assembly can be part of the drive design or for some drives it can be externally provided and controlled.
ATTENTION: An external source of power can be present. To avoid an electric shock hazard, verify that the AC power supply has been removed before any maintenance is performed.
If an external voltage source is used to power the logic boards of the PowerFlex drives, take precautions to control the precharge sequence.
We recommend that you use the Precharge Enable digital input on the drive for common bus operation. The logic input can be coordinated through a PLC or system-level control to sequence the precharge. The sequencing lets charge time constants for various horsepower drives settle out before the precharge completes. Generally, a three second delay is acceptable after power has been applied. See Drives in
Common Bus Configurations Application Technique, publication DRIVES-AT002 , for precharge functionality on all Powerflex drive frame types.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 11
Chapter 1 DC-bus Wiring Guidelines
ATTENTION: The Precharge Enable digital input is only available on PowerFlex 750-Series common-bus inverter drives. The Kinetix servo drives do not include a Precharge Enable digital input.
When multiple drives are connected through disconnects to a common DC-bus, it is necessary to provide an input to the drive that enables the precharge to finish. Often, an auxiliary contact on the drive disconnect switch controls this input.
Figure 5 - Common DC-bus Example
L1
L2
L3
DC+
DC–
M1 M2
ATTENTION: The bus capacitors in the individual drives act as a low-impedance voltage source. Extra care is needed when connecting individual drives to an energized bus.
ATTENTION: Kinetix drives have no method for you to control the precharge sequence. To avoid severe drive and/or equipment damage due to uncontrolled precharge, do not connect Kinetix servo drives to an energized DC-bus.
If Precharge Enable is selected as a digital input, it must be energized to let the initial bus precharge complete. If Precharge Enable is deenergized, it is treated as a coast-to-stop command that forces the drive to the initial bus-precharge state. Fuse failure is probable unless coordination of precharge circuits in individual drives is implemented.
When Kinetix 6000 drives are used in common bus configurations, they must have firmware revision 1.92 or later. Kinetix 6200/6500 drives with any firmware revision can be used.
PowerFlex 750-Series (Frame 1…4) AC Drives
For PowerFlex 750-Series frame 1…4 AC drives, the precharge hardware is on the power circuit board. It is composed of a resistor in series with the positive DC-bus, between the DC link and the bus capacitors. The resistor has a relay contact that is connected in parallel, which closes to bypass the Precharge resistor when the bus precharge level is attained. The precharge function operates the same way for either
AC or DC input power.
Figure 6 - AC and DC Input Schematic for PowerFlex 750-Series (Frame 1…4) AC Drives
DC+ BR1
L1
L2
L3
+
BR2
U
V
W
12
DC –
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
DC-bus Wiring Guidelines Chapter 1
PowerFlex 750-Series (Frame 5 and 6) AC Drives
When ordered as an AC input drive, DC terminals are not provided on Frame 6 drives. During precharge, the SCRs of the front-end rectifier are open and the bus capacitors are charged through the diodes and resistors from the AC input. After the DC-bus has reached precharge level, the SCRs (when turned on) bypass the diode resistor configuration.
ATTENTION: PowerFlex 750-Series (Frames 5 and 6) AC input drives have no method for you to control the precharge sequence. To avoid severe drive and/or equipment damage due to uncontrolled precharge, do not connect these drives to an energized DC-bus.
Figure 7 - AC and DC Input Schematic for PowerFlex 750-Series (Frame 5 and 6) AC Drives
DC+ BR1
L1
L2
L3
Voltage Rating
Catalog Codes 1 and A
+
BR2
U
V
W
DC – Optional for PowerFlex Frame 6 Drives
PowerFlex 750-Series (Frame 5 and 6) DC Input Common-bus Drives
The precharge has a resistor in series with the positive DC-bus, ahead of the bus capacitors. An SCR is connected in parallel and when gated on, it bypasses the resistor.
Figure 8 - DC Input Schematic for PowerFlex 750-Series (Frame 5 and 6) DC Input Drives
D C + B R 1
Input Type Catalog Number
Position 5, Code 4
+
BR2
U
V
W
DC – Optional for PowerFlex Frame 6 Drives
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 13
Chapter 1 DC-bus Wiring Guidelines
Kinetix 7000 Servo Drives
For 2099-BM06-S, 2099-BM07-S, and 2099-BM08-S servo drives, the precharge hardware is located on the power circuit board. It is composed of a resistor in series with the positive DC-bus between the DC link and the bus capacitors. The resistor has a relay contact connected in parallel that closes when the bus precharge level has been reached, bypassing the precharge resistor. The precharge function operates the same way for AC and DC power.
Figure 9 - AC and DC Input Schematic for Kinetix 7000 (2099-BM06-S…2099-BM08-S) Servo Drives
DC+
L1
L2
L3
+
U
V
W
DC –
For 2099-BM09-S, 2099-BM10-S, 2099-BM11-S, and 2099-BM12-S servo drives, the precharge capability must be provided at the system level.
Disconnect switches must not be used between the input of the drive and a common DC-bus without the use of an external precharge device. The precharge hardware is implemented with an SCR rectifier such that the SCRs are phase advanced to limit the inrush current into the bus capacitors. This phase-advanced precharge is not controlled by the drive and must normally be completed by the minimum precharge time required by the drive. The drive does not complete precharge until the bus voltage is stable and above the undervoltage level.
Figure 10 - AC Input Schematic for Kinetix 7000 (2099-BM09-S…2099-BM12-S) Servo Drives
DC +
L1
L2
L3
+
U
V
W
DC –
14 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
DC-bus Wiring Guidelines Chapter 1
Kinetix 6000 and Kinetix 6200/6500 Multi-axis Servo Drives
The Kinetix 6000 (400V-class) and Kinetix 6200/6500 drives are packaged, highly configurable, common bus products with one converter module (IAM) and multiple inverter modules (AM) mounted on a shared backplane. Precharge hardware, which consists of a resistor in series with a DC link inductor and the positive rail of the DC-bus, is mounted in the converter module. In all recommended common bus configurations, the converter is not used; therefore, any non-Kinetix 6000 common-bus leader module that does not provide precharge is required to add an additional external precharge circuit before connecting to any Kinetix 6000 common-bus follower IAM module.
IMPORTANT Do not connect three-phase AC power to the Kinetix 6000 (follower) converter in mixed Kinetix 5700 common-bus configurations.
An internal shunt resister (braking chopper) is included with each inverter module. To be used in a common bus system with Kinetix 5700 drives, the Kinetix 6000 system must be set to common-bus follower mode with the internal shunt modules disabled.
Figure 11 - AC and DC Input Schematic for Kinetix 6000 and Kinetix 6200/6500 Servo Drives
DC+
L1
L2
L3
DC –
+
2094-BC xx
-BM xx-
S
2094-BC or xx
-BM xx-
M
U
V
W
2094-BM xx-
S or
2094-BM xx-
M
(up to 7 additional axes)
U
V
W
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 15
Chapter 1 DC-bus Wiring Guidelines
Notes:
16 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Chapter
2
Non-regenerative Common DC-bus Configurations
Non-regenerative bus supplies are characterized by a diode-front-end unit that converts three-phase AC line voltage into a non-filtered
DC-bus voltage. No provisions exist for line regeneration or power dissipation of any recovered energy from the motor/load system.
Supported Products
At the time of publication, the following Kinetix® 5700 non-regenerative DC-bus supplies and drives are supported.
Table 2 - Kinetix 5700 Non-regenerative Drive Modules
DC-bus Power Supply
Cat. No.
Supported Drives
• 2198-P031
• 2198-P070
• 2198-P141
• 2198-P208
PowerFlex® 750-Series: Frames 1…6
(1)
Kinetix 7000: All power ratings
Kinetix 6000: All 460V configurations
(2)
Kinetix 6200/6500: All configurations
(1) PowerFlex 750-Series (Frames 5 and 6) DC input drives with precharge must be selected.
(2) Kinetix 6000 configurations require firmware revision 1.92 or later.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 17
Chapter 2 Non-regenerative Common DC-bus Configurations
Typical System Configuration
In this example, standalone AC drives, Kinetix 6000 drives, and Kinetix 7000 drives receive DC-bus power from three 2198-P208 DC-bus power supplies.
Figure 12 - DC-bus Supply with Standalone AC Drives, Kinetix 6 x 00 Drives, and Kinetix 7000 Drives
Three-phase
Source
Circuit
Protection
Three-phase
Contactor
DC-Bus
Power Supply
DC-Bus
Power Supply
DC-Bus
Power Supply
Capacitor
Module
DC Bus
Extension
Module
DC+ DCDC+ DCDC+ DC-
Three-phase
AC Line Filter
AC Drive AC Drive
Circuit
Protection
Line
Reactor
(1)
M M
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
Circuit
Protection
Line
Reactor
(1)
Circuit
Protection
Line
Reactor
(1)
(1) Line reactors are required when three 2198-P208 DC-bus supplies are configured. For line reactor considerations and selection when one or two 2198-P208 DC-bus supplies are configured, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
Table 3 - Special Bus Requirements
Drawing Designation
AC drives
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
18 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations Chapter 2
General Considerations
This section includes information on AC line impedance, disconnect switch connections, and ground screw/jumper settings, depending on the drive family.
ATTENTION: The incorrect use or configuration of third-party assemblies can result in reduced system reliability and drive damage.
• All system components (bus supply and PowerFlex or Kinetix drives) must be selected for the same AC-line voltage.
• Low-inductance type DC-bus must be used. See
on
for details.
• To be used in a common-bus system with a Kinetix 5700 bus supply, the Kinetix 6000 or Kinetix 6200/6500 drive systems must be configured as common-bus follower (internal IGBT for shunting is disabled).
IMPORTANT Do not include the 2094-BSP2 shunt module on the 2094 power rail.
• Refer to
on
page 81 for user documentation with the maximum motor cable length requirements of the drives
specific to your application.
AC Line Impedance Considerations
In the following use cases, an additional transformer or line reactor is required due to faults or potential damage associated with AC line disturbances:
• Installation site has switched power-factor correction capacitors.
• Installation site has lightning strikes or voltage spikes in excess of 6000V peak.
• Installation site has power interruptions or voltage dips in excess of 200V AC.
• The transformer kVA is more than 10 times larger than the drive kVA or the percent source impedance relative to each converter is less than 0.5%.
In the following use cases, a line reactor is required due to faults associated with sharing AC line-input on multiple converters:
• Repetitive AC input line-voltage notching is present. For example, if silicon-controlled rectifier drive is connected to the same AC input power source.
• Powering 2198-P xxx
DC-bus power supply and 2198-RP xxx
regenerative bus supply from the same AC input-power source.
- Line reactor in the AC input-power string is not required for the DC-bus power supply in this use case, but is recommended for the prevention of issues caused by other use cases.
• Powering two or three 2198-P208 DC-bus power supplies from the same AC input-power source that share the same DC-bus.
- In this use case, a line reactor is required for each 2198-P208 DC-bus power supply to make sure that they share current more evenly.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional AC line impedance considerations.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 19
Chapter 2 Non-regenerative Common DC-bus Configurations
Disconnect Switch Considerations
If a disconnect switch is used between the common DC-bus and a PowerFlex 750-Series drive input, connect an auxiliary contact on the disconnect switch to a digital input of the drive. The corresponding digital input must be set to Precharge Enable. This setting provides the proper precharge interlocking, which guards against possible damage to the drive when reconnecting the drive to an energized DC-bus.
Under this condition, the drives must have an internal or externally supplied precharge. Precharge handshaking is required before inverter operation. For more information on precharge handshaking, see Drives in Common Bus Configurations Application Technique, publication
DRIVES-AT002 .
Table 4 - PowerFlex 750-Series Drive Precharge Parameters
Number
189 [DI Precharge]
Parameter
Setting
Digital Input
See PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001
ATTENTION: To avoid personal injury and/or equipment damage, make sure installation complies with specifications regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment.
ATTENTION: The Kinetix 6000 (400V-class), Kinetix 6200/6500, Kinetix 7000, and PowerFlex 750-Series (Frames 5 and 6) AC input drives have no method for you to control the precharge sequence. To avoid sever drive and/or equipment damage due to uncontrolled precharge, do not connect these drives to an energized bus. If a disconnect switch is used between the inputs of the drives and the common DC-bus, an external precharge device must be used.
When an external precharge device is required, a fuse combination switch can be used. These switches provide precharge of capacitive loads, have integrated fuse protection, and perform automatic pre-load type functions with an internal coil.
Input and Output Signals
For the Kinetix 7000 drives, wire the control and interface signals on the General Purpose Relay (GPR) connector as described in the following table. See the Kinetix 7000 High Power Servo Drives User Manual, publication 2099-UM001 , for more information on the terminal block connections.
Table 5 - General Purpose Relay Connections
Signal
DRIVE OK+
DRIVE OK-
Terminal
5
6
Description
Programmable N.O. Relay 2 output
Programmable Relay 2 common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
ATTENTION: For Kinetix 7000 drives, wiring the DRIVE OK signal on the General Purpose Relay is required. To avoid injury or damage to the drive, wire the DRIVE OK relay into your control string.
20 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations Chapter 2
Drive Ground Jumper Settings
Set the ground jumpers for the Kinetix 6000 (400V-class), Kinetix 6200/6500, and Kinetix 7000 drives according to the following tables. Refer
Table 6 - Ground Jumper Settings for Kinetix 6000 (400V-class) and Kinetix 6200/6500 Drives
Ground Configuration
2198-P xxx
Ground Jumper Setting Based on Selected Power Supply
DC-bus Power Supply
Grounded power (default setting)
(1)
2198-P xxx
DC-bus Power Supply
(2)
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
Set for ungrounded power
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
Set for ungrounded power
Table 7 - Ground Jumper Settings for Kinetix 7000 Drives
Ground Configuration
Grounded (wye)
Ground Jumper Setting Based on Selected Power Supply
2198-P xxx
DC-bus Power Supply
Installed (default setting)
(1)
2198-P xxx
DC-bus Power Supply
(2)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
Removed
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
Removed
PowerFlex 750-Series drives contain protective metal-oxide varistors (MOV) and common mode capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the following table.
Table 8 - Power Jumper Settings for PowerFlex 750-Series Drives (Frames 1…6)
Ground Configuration
Ground Jumper Setting Based on Selected Power Supply
2198-P xxx
DC-bus Power Supply
(1)
2198-P xxx
DC-bus Power Supply
(2)
Grounded (wye)
• Jumper PE-A connected
(3) (4)
(MOV/input filter caps)
• Jumper PE-B connected (DC-bus common mode caps)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
(3) When MOVs are disconnected, the power system must have its own transient protection to maintain known and controlled voltages.
(4) Frame 5 and 6 common DC input drives do not have the PE-A jumper.
For instructions on how to disconnect the PE jumpers, refer to PowerFlex 750-Series Power Jumpers Installation Instructions, publication
750-IN011 .
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 21
Chapter 2 Non-regenerative Common DC-bus Configurations
Kinetix 5700 Non-Regenerative Bus Supply Considerations
When extending the DC-bus from the power supply cluster, a capacitor module must be used to extend the bus. Refer to
Accessory Modules on page 71 for more information on when accessory modules are required.
The 2198-P xxx
DC-bus power supplies do not have a digital output, however, the CIPAxisState tag can be used either programmatically or with an external digital output to indicate that the drives can pull power from the bus. Refer to Integrated Motion on the EtherNet/IP Network
Reference Manual, publication MOTION-RM003 , and Knowledgebase Answer ID: QA35126 , for more information on programming with
Integrated Motion drives
Power Supply Ground Screw Setting
The 2198-P xxx
DC-bus power supply has a factory-installed ground screw for grounded-wye power distribution. The following table summarizes the ground screw/jumper settings for the 2198-P xxx
DC-bus power supply.
Table 9 - Ground Screw Settings for the DC-bus Power Supply
Ground Configuration
2198-P xxx
DC-bus Power Supply
Ground screw installed (default setting)
(1) Grounded (wye)
• Impedance grounded
• Corner grounded
• AC-fed ungrounded
(1) Ground screw is factory installed.
Remove ground screw/jumper
IMPORTANT If you have grounded-wye power distribution in your facility, do not remove the ground screw from the DC-bus power supply.
Remove the ground screw when using ungrounded, corner-grounded, or impedance-grounded power.
22 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations Chapter 2
Contactor Enable Relay
The contactor-enable circuitry includes a relay-driven contact within the 2198-P xxx
DC-bus power supply. The relay protects the Kinetix 5700 drive system in the event of overloads or other fault conditions.
Figure 13 - Contactor-enable Control String
Kinetix 5700
2198-P208
DC-bus Power Supply
Kinetix 6 x 00
2094-BC xx -M xx -S
Integrated Axis Module
* Indicates User Supplied Component
Kinetix 7000
2099-BM xx -S
Servo Drive
24V AC/DC
50/60 Hz
CR1 *
CR1 *
M1 *
STOP *
START *
CR1 *
CONT EN+ CONT EN– CONT EN+ CONT EN–
GPR2+ GPR2–
An AC three-phase mains contactor must be wired in series between the branch circuit protection and the power supply. In addition, the AC three-phase contactor control string must be wired in series with the contactor-enable relay at the contactor-enable terminals.
PowerFlex 750-Series drives are not required to include a contactor-enable control string and they do not have a dedicated contactor enable relay. Although not required, if leveraging Integrated Motion with a PowerFlex 755 drive, we recommend that you configure a digital output from the drive as Contactor Enable and include it in the contactor enable control string.
A Contactor Enable output can be configured in the PowerFlex 755 drive in integrated motion only. The operation of this output is tied to fault processing in the drive. The drive de-energizes the Contactor Enable output when an exception causes the axis to go to the Shutdown state.
This configuration is only valid when an auxiliary power supply is used for control power with frames 1…7 drives.
ATTENTION: Wiring the contactor enable relay is required for Kinetix 5700, Kinetix 6 x
00, and Kinetix 7000 drive systems to help prevent personal injury or damage to Kinetix drive modules. Wire the contactor enable relay into your control string so that:
• three-phase power is removed and the power supply or regenerative bus supply is protected under various fault conditions
• three-phase power is never applied to the Kinetix 5700 drive system before control power is applied.
Figure 14 - Contactor-enable Relay Circuit
CONT EN+
Normally
Open
Relay
CONT EN-
Power Supply
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the contactor-enable circuitry.
ATTENTION: For Kinetix 6000 (400V-class) and Kinetix 6200/6500 drive in common-bus configurations, the contactor enable connections for leader and follower drives must be wired in series to the control string.
A contactor or other device that routinely disconnects and reapplies the AC line to the bus supply can cause drive hardware damage. If an input device is used, operation must not exceed two cycles per minute (maximum) or damage can occur to the precharge circuit.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 23
Chapter 2 Non-regenerative Common DC-bus Configurations
System Sizing
These limitations apply to systems supplied by a single 2198-P xxx
or multiple 2198-P208 DC-bus power supplies:
• The sum of the inverter motor-power cable lengths for all inverters on the same DC bus-sharing group must not exceed 1200 m
(3937 ft) to comply with IEC 61800-3 (category C3) requirements when used with 2198-DBR xx
-F line filters. 2198-DB xx
-F line filters have a total motor cable length limit of 400 m (1312 ft). See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional motor power cable-length limitations.
• The total system capacitance limit is based on the power supply catalog number. DC-bus groups must not exceed the limits as defined in
Kinetix and PowerFlex Drive Specifications on page 59
.
• No more than three 2198-P208 DC-bus power supplies can be used to increase the converter power.
• If using the 24V DC shared-bus connection system, add another 24V power supply when control input power to a cluster of drive modules exceeds 40 A.
• The Kinetix 5700 system can have multiple drive clusters in a single DC-bus group. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on extended clusters.
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on system sizing guidelines.
The motor required for a particular application determines the drive required for full motor performance. For best results, use Motion
Analyzer system sizing and selection tool, available at https://motionanalyzer.rockwellautomation.com/ .
Capacitance Sizing
Total system capacitance is the sum of all internal capacitance values from each of the drive modules (AC drives, single-axis inverters, dualaxis inverters, power supplies, and capacitor modules) in the same DC-bus group.
The total system capacitance must be less than the maximum supported DC-bus capacitance value of the power supply (refer to
PowerFlex Drive Specifications on page 59
).
IMPORTANT If your total system capacitance value exceeds the maximum supported capacitance value of the DC-bus power supply, perform one of the following:
• Increase the size of the 2198-P xxx
DC-bus power supply
• Use multiple 2198-P208 DC-bus power supplies (1…3 power supplies are possible with only 2198-P208 power supply)
• Decrease the total system capacitance by removing inverters or capacitor modules from the DC-bus group
• Separate clusters into multiple DC-bus groups
All drives have a DC-bus capacitance that is proportional to their power ratings. When used in a common DC-bus configuration, these capacitors are directly connected in parallel. This connection results in the DC-bus ripple being shared proportional to the power rating of the drive. When the ratio of the capacitance to the drive-rated current is consistent, it provides the best DC-bus ripple sharing.
For 400/480V AC, the target ratio is 40 µF/A ±10% or greater. For all drives supported in this publication, the target ratio is met when a capacitor module is used to extend the DC-bus, proper DC-bus cable length guidelines are followed, and low-inductance DC cable is used.
on
Circuit Protection
Do not daisy chain drives to share DC-bus fusing. Configure the shared DC-bus in a star configuration to enable proper fusing. Use fast semiconductor fuses in the DC links to minimize destructive energy in the event of a part or control malfunction. Size fuses to handle large peak currents at the end of precharge.
• See
Kinetix and PowerFlex Drive Specifications on page 59
for the recommended common DC-bus circuit protection devices.
• See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for recommended AC input circuit protection for the Bulletin
2198 power supply.
24 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Chapter
3
Non-regenerative Common DC-bus Configurations
With Passive or Active Shunt
This system also uses a diode-front-end power supply that converts the three-phase AC line voltage into a non-filtered DC-bus voltage.
However, in this configuration the drive uses the internal IGBT shunt resistor or an external passive or active shunt for power dissipation of excess regenerative energy. Rockwell Automation does not offer external active shunt products. Contact our Encompass™ Partners for these shunt resistor (braking chopper) products.
Supported Products
At the time of publication, the following Kinetix® 5700 non-regenerative DC-bus supplies and drives are supported.
Table 10 - Kinetix 5700 Non-regenerative Drive Modules
DC-bus Power Supply
Cat. No.
• 2198-P031
• 2198-P070
• 2198-P141
• 2198-P208
Supported Drives
PowerFlex® 750-Series: Frames 1…6
(1)
Kinetix 7000: 2099-BM06-S…2099-BM12-S
Kinetix 6000 and Kinetix 6200/6500: All 460V configurations
(2)
(1) PowerFlex 750-Series (Frames 5 and 6) DC input version drives with precharge must be selected.
(2) Kinetix 6000 configurations require firmware revision 1.92 or later.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 25
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
Typical System Configurations
In this example, standalone AC drives, Kinetix 6000 drives, and Kinetix 7000 drives receive DC-bus power from three 2198-P208 DC-bus power supplies. An external passive shunt is wired to one of the 2198-P208 DC-bus supplies.
Figure 15 - DC-bus Supply with Multiple AC Drives and External Passive Shunt
Three-phase
Source
Circuit
Protection
Three-phase
Contactor
(2)
DC-Bus
Power Supply
External Bulletin 2198 Passive Shunt
DC-Bus
Power Supply
DC-Bus
Power Supply
Capacitor
Module
DC Bus
Extension
Module
DC+ DCDC+ DCDC+ DC-
Three-phase
AC Line Filter
Circuit
Protection
Line
Reactor
(1)
AC Drive
M
AC Drive
M
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
Circuit
Protection
Line
Reactor
(1)
Circuit
Protection
Line
Reactor
(1)
(1) Line reactors are required when three 2198-P208 DC-bus supplies are configured. For line reactor requirements and selection when one or two 2198-P208 DC-bus supplies are configured, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) For passive shunt wiring and mounting information, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
Table 11 - Special Bus Requirements
Drawing Designation
AC drives
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
26 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations With Passive or Active Shunt Chapter 3
Figure 16 - DC-bus Supply with Multiple AC Drives and External Active Shunt
Three-phase
Source
Circuit
Protection
Three-phase
Contactor
DC-Bus
Power Supply
DC-Bus
Power Supply
DC-Bus
Power Supply
Capacitor
Module
DC-bus (2)
Conditioner
DC Bus
Three-phase
AC Line Filter
Circuit
Protection
Line
Reactor
(1)
DC+ DCDC+
External Active
Shunt
(3)
BR1 BR2 AC Drive
DC-
BR
M
DC+ DC-
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
Circuit
Protection
Line
Reactor
(1)
Circuit
Protection
Line
Reactor
(1)
(1) Line reactors are required when three 2198-P208 DC-bus supplies are configured. For line reactor requirements and selection when one or two 2198-P208 DC-bus supplies are configured, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) A DC-bus conditioner module is required to limit DC-bus voltage overshoot at power-on.
(3) Locate the external active shunt close to the DC-bus conditioner. For active shunt wiring and mounting information, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
Table 12 - Special Bus Requirements
Drawing Designation
AC drives
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
(1)
Kinetix 6000: All 460V configurations
(2)
Kinetix 6200/6500: All 460V configurations
Special Bus Requirements
None
None
(1) External precharge must be provided if a disconnect between the DC-bus and the drive DC input is used.
(2) No internal precharge. Drives must be placed in common-bus follower configuration.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 27
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
General Considerations
This section includes information on AC line impedance, disconnect switch connections, and ground screw/jumper settings, depending on the drive family.
ATTENTION: The incorrect use or configuration of third party assemblies can result in reduced system reliability and drive damage.
• All system components (bus supply and PowerFlex or Kinetix drives) must be selected for the same AC-line voltage.
• Low-inductance type DC-bus must be used. See
on
for details.
• To be used in a common-bus system with a Kinetix 5700 bus supply, the Kinetix 6000 or Kinetix 6200/6500 drive systems must be configured as common-bus follower (internal IGBT for shunting is disabled).
IMPORTANT Do not include the 2094-BSP2 shunt module on the 2094 power rail.
• The Kinetix 7000 drive internal IGBT for shunting is not used by the drive main control for bus regulation. Therefore, any type of regulation must come from an external source.
• Refer to
on
page 81 for user documentation with the maximum motor cable length requirements of the drives
specific to your application.
AC Line Impedance Considerations
In the following use cases, an additional transformer or line reactor is required due to faults or potential damage associated with AC line disturbances:
• Installation site has switched power-factor correction capacitors.
• Installation site has lightning strikes or voltage spikes in excess of 6000V peak.
• Installation site has power interruptions or voltage dips in excess of 200V AC.
• The transformer kVA is more than 10 times larger than the drive kVA or the percent source impedance relative to each converter is less than 0.5%.
In the following use cases, a line reactor is required due to faults associated with sharing AC line-input on multiple converters:
• Repetitive AC input line-voltage notching is present. For example, if silicon-controlled rectifier drive is connected to the same AC input power source.
• Powering 2198-P xxx
DC-bus power supply and 2198-RP xxx
regenerative bus supply from the same AC input-power source.
- Line reactor in the AC input-power string is not required for the DC-bus power supply in this use case, but is recommended for the prevention of issues caused by other use cases.
• Powering two or three 2198-P208 DC-bus power supplies from the same AC input-power source that share the same DC-bus.
- In this use case, a line reactor is required for each 2198-P208 DC-bus power supply to make sure that they share current more evenly.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional AC line impedance considerations.
28 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations With Passive or Active Shunt Chapter 3
Disconnect Switch Considerations
If a disconnect switch is used between the common DC-bus and a PowerFlex 750-Series drive input, connect an auxiliary contact on the disconnect switch to a digital input of the drive. The corresponding digital input must be set to Precharge Enable. This setting provides the proper precharge interlocking, which guards against possible damage to the drive when reconnecting the drive to an energized DC-bus.
Under this condition, the drives must have an internal or externally supplied precharge. Precharge handshaking is required before inverter operation.
Table 13 - PowerFlex 750-Series Drive Precharge Parameter
Number
189 [DI Precharge]
Parameter
Setting
Digital Input
See PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001
ATTENTION: To avoid personal injury and/or equipment damage, make sure installation complies with specifications regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment.
ATTENTION: The Kinetix 6000 (400V-class), Kinetix 6200/6500, Kinetix 7000, and PowerFlex 750-Series (Frames 5 and 6) AC input drives have no method for you to control the precharge sequence. To avoid sever drive and/or equipment damage due to uncontrolled precharge, do not connect these drives to an energized bus. If a disconnect switch is used between the inputs of the drives and the common DC-bus, an external precharge device must be used.
When an external precharge device is required, a fuse combination switch can be used. These switches provide precharge of capacitive loads, have integrated fuse protection, and perform automatic pre-load type functions with an internal coil.
Input and Output Signals
For the Kinetix 7000 drives, wire the control and interface signals on the General Purpose Relay (GPR) connector as described in the following table. See the Kinetix 7000 High Power Servo Drives User Manual, publication 2099-UM001 , for more information on the terminal block connections.
Table 14 - General Purpose Relay Connections
Signal
DRIVE OK+
DRIVE OK-
Terminal
5
6
Description
Programmable N.O. Relay 2 output
Programmable Relay 2 common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
ATTENTION: For the Kinetix 7000 drives, wiring the DRIVE OK signal on the General Purpose Relay is required. To avoid injury or damage to the drive, wire the DRIVE OK relay into your control string.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 29
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
Drive Ground Jumper Settings
Set the ground jumpers for the Kinetix 6000 (400V-class), Kinetix 6200/6500, and Kinetix 7000 drives according to the following tables. Refer
Table 15 - Ground Jumper Settings for Kinetix 6000 (400V-class) and Kinetix 6200/6500 Drives
Ground Configuration
2198-P xxx
Ground Jumper Setting Based on Selected Power Supply
DC-bus Power Supply
Grounded power (default setting)
(1)
2198-P xxx
DC-bus Power Supply
(2)
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
Set for ungrounded power
Set for ungrounded power
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
Table 16 - Ground Jumper Settings for Kinetix 7000 Drives
Ground Configuration
Grounded (wye)
Ground Jumper Setting Based on Selected Power Supply
2198-P xxx
DC-bus Power Supply
Installed (default setting)
(1)
2198-P xxx
DC-bus Power Supply
(2)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
Removed
Removed
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
PowerFlex 750-Series drives contain protective metal-oxide varistors (MOV) and common mode capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the following table.
Table 17 - Power Jumper Settings for PowerFlex 750-Series Drives (Frames 1…6)
Ground Configuration
Ground Jumper Setting Based on Selected Power Supply
2198-P xxx
DC-bus Power Supply
(1)
2198-P xxx
DC-bus Power Supply
(2)
Grounded (wye)
• Jumper PE-A connected
(3) (4)
(MOV/input filter caps)
• Jumper PE-B connected (DC-bus common mode caps)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
(1) 2198-P xxx
DC-bus power supply when 2198-DB20-F, 2198-DB42-F, 2198-DB80-F, or 2198-DB290-F AC line filter is used.
(2) 2198-P xxx
DC-bus power supply when 2198-DBR20-F, 2198-DBR40-F, 2198-DBR90-F, or 2198-DBR200-F AC line filter is used.
(3) When MOVs are disconnected, the power system must have its own transient protection to maintain known and controlled voltages.
(4) Frames 5 and 6 common DC input drives do not have the PE-A jumper.
For instructions on how to disconnect the PE jumpers, refer to PowerFlex 750-Series Power Jumpers Installation Instructions, publication
750-IN011 .
30 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations With Passive or Active Shunt Chapter 3
Active Shunt Considerations
External active shunts are required in the following use cases:
• One permanent magnet motor runs above its bus overvoltage speed. See Kinetix 5700 Servo Drives User Manual, publication
2198-UM002 , information on the Field Weakening Mode feature.
• One permanent magnet motor drives a vertical load that could make the motor accelerate above the bus overvoltage speed during a fault condition.
ATTENTION: To avoid damage to the Kinetix 5700 drive system, wire the active shunt thermal switch to a digital input on the power supply and configure the Shunt Thermal Switch OK function in the Logix Designer application.
ATTENTION: DC-bus failure can cause damage to all drive modules in the bus group, not just the inverter connected to the motor.
Active shunts are available from the Rockwell Automation Encompass partner Powerohm Resistors, Inc. See http://www.powerohm.com
for more information on Powerohm active shunts.
IMPORTANT Powerohm Bulletin PKB xxx
active shunt modules use built-in internal brake resistors. Bulletin PWB xxx
active shunt modules require appropriately sized external brake resistors.
Table 18 - Compatible Active Shunt Specifications (internal brake resistor)
Kinetix 5700 Power Supply
2198-P xxx
DC-bus power supply
Powerohm
Resistors
Cat. No.
(1)
PKB005
PKB010
Input Voltage, nom
480V AC
Turn -on
Bus Voltage
750V DC
Continuous
Power kW
1.50
2.06
Resistance
(internal)
Ω
108
52.7
Resistance
(minimum)
Ω
–
–
Continuous
Current
Amps
2.00
2.75
Peak
Current
Amps
6.9
14.2
PKB050 7.00
10.5
– 9.30
71.4
(1) How the Powerohm PKB xxx
shunts connect to the 2198-P xxx
.
Table 19 - Compatible Active Shunt Specifications (no internal brake resistor)
Kinetix 5700 Power Supply
2198-P xxx
DC-bus power supply
Powerohm
Resistors
Cat. No.
(1)
PWB035
PWB110
Input Voltage, nom
480V AC
Turn -on
Bus Voltage
750V DC
Continuous
Power kW
26.25
82.5
Resistance
(internal)
Ω
–
–
Resistance
(minimum)
Ω
7.5
2.5
Continuous
Current
Amps
35
110
Peak
Current
Amps
100
300
(1) How the Powerohm PWB xxx
shunts connect to the 2198-P xxx
ATTENTION: Do not use Powerohm active-shunt modules at input line voltages that exceed 528V AC. Active-shunt thermal-overload shutdown can occur if input line voltage exceeds 528V AC.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 31
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
Kinetix 5700 Non-Regenerative Bus Supply Considerations
When extending the DC-bus from the power supply cluster, a capacitor module must be used to extend the bus. Refer to
Accessory Modules on page 71 for more information on when accessory modules are required.
The 2198-P xxx
DC-bus power supplies do not have a digital output, however, the CIPAxisState tag can be used either programmatically or with an external digital output to indicate that the drives can pull power from the bus. Refer to Integrated Motion on the EtherNet/IP Network
Reference Manual, publication MOTION-RM003 , and Knowledgebase Answer ID: QA35126 , for more information on programming with
Integrated Motion drives
Shunt Connections
The 2198-P xxx
DC-bus power supplies all include an internal shunt that is wired to the shunt resistor (RC) connector at the factory. Bulletin
2198-R xxx
external passive shunts are available to provide additional shunt capacity for applications where the internal shunt capacity is exceeded.
Connect an external passive shunt to only the DC-bus power supply. You must disconnect the internal shunt wires at the RC connector before connecting external passive-shunt resistor wires.
Table 20 - DC-bus Power Supply Passive-shunt Options
DC-bus Power Supply
Cat. No.
Internal Shunt Specifications
2198-P031
2198-P070
2198-P141
2198-P208
Ω
37.5
13.5
W
75
200
2198-R127
–
–
X
X
(1) Shunt resistor selection is based on the needs of your actual hardware configuration.
–
X
X
External Shunt Module Compatibility
Cat. No.
(1)
2198-R031
–
2198-R014
X
X
X
X
X
X
2198-R004
X
X
Catalog numbers 2198-R014, 2198-R031, and 2198-R127 are composed of resistor coils that are housed inside an enclosure. Catalog number
2198-R004 is a shunt resistor without an enclosure.
Figure 17 - External Passive Shunts
2198-R014, 2198-R031, and 2198-R127
Shunt Modules
2198-R004
Shunt Resistor
Table 21 - External Shunt Module Specifications
Shunt Module
Cat. No.
2198-R004
2198-R014
2198-R031
2198-R127
(1)
Resistance
W
33
9.4
33
13
(1) This product presents a lift hazard. To avoid personal injury, use care when lifting the product.
Continuous Power
W
400
1400
3100
12,700
Weight, approx kg (lb)
1.8 (4.0)
9.1 (20)
16.8 (37)
22.2 (49)
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for passive shunt wiring and mounting considerations.
32 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations With Passive or Active Shunt Chapter 3
For drive systems that include the 2198-P xxx
DC-bus power supply and Powerohm PKB xxx
or PWB xxx
active shunts, make the active shunt connections at the external DC-bus studs on accessory modules.
Accessory modules are equipped with spacers that slide onto M8 studs. When the system configuration includes external DC-bus and active shunt connections, external DC-bus connections are made below the spacer and active shunt connections are made above the spacer.
Figure 18 - Active Shunt Connections
Spacer
Active Shunt
Lug Connections
(above spacer)
DC-bus
Lug Connections and
Flexible Bus-bars
(2)
(below spacer)
2198-DCBUSCOND-RP312
2198-CAPMOD-2240 or
2198-CAPMOD-DCBUS-IO
(1)
Accessory Modules
(2198-CAPMOD-2240 capacitor module is shown)
(1) An external active shunt can be wired to any of the accessory modules. See Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on mounting and accessory module example configurations. The 2198-CAPMOD-2240 capacitor module is preferred because it provides additional system capacitance.
(2) Position flexible bus-bars (when two accessory modules are used) below the DC-bus lug connections. The flexible bus-bars are used to parallel the extended DC-bus with another accessory module in 208 A systems (not required when only one accessory module is used in 104 A systems). Flexible bus-bars are included with 2198-CAPMOD-DCBUS-IO extension modules or you can order 2198-KITCON-CAPMOD2240 or 2198-KITCON-DCBUSCOND replacement kits.
For compatible Powerohm active shunts paired with 2198-P xxx
DC-bus power supplies, refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
ATTENTION: To avoid damage to the Kinetix 5700 drive system, wire the active shunt thermal switch to a digital input on the power supply and configure the Shunt Thermal Switch OK function in the Studio 5000 Logix Designer® application.
Figure 19 - 2198-P xxx Power Supply with External Active Shunt (built-in brake resistor)
2198-P xxx
DC-Bus Power Supply
2198xxxx
-ERS x
Inverter
2198-CAPMOD-2240
Capacitor Module 4.6 m (15 ft) Maximum Cable Length
DC+
External DC-bus
DC+
DC–
Powerohm
Bulletin PKB xxx-xxx
Active Shunt Module
Resistor
DC–
3
4
Fault Contact
Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
9
10
(2)
120V AC
(1) Configure any available digital input as Shunt Thermal Switch OK.
(2) Powerohm PKB050 and PKB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
For more information on wiring to these Powerohm Bulletin PKB xxx
active shunts, see the Knowledgebase Answer ID: 1082776 .
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 33
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
Figure 20 - 2198-P xxx Power Supply with External Active Shunt (external brake resistor)
2198-P xxx
DC-Bus
Power Supply
2198xxxx
-ERS
Inverter x
2198-CAPMOD-2240
Capacitor Module
Powerohm
Bulletin PWB xxx-xxx
Active Shunt Module
DC+
External DC-bus
DC+
DC–
DC+
DC–
DC–
4.6 m (15 ft)
Maximum Cable Length
9.1 m (30 ft)
Maximum Cable Length
R1
R2
Powerohm
External Passive
Shunt Module
Resistor
3
4
Fault Contact
9
10
(2)
120V AC
Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
TS
TS
Thermal
Switch
(1) Configure any available digital input as Shunt Thermal Switch OK. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on configuring digital inputs.
(2) Powerohm PWB050 and PWB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
See Knowledgebase document 1082777 for more information on wiring to these Powerohm Bulletin PWB xxx
active shunts.
Refer to the Powerohm documentation included with your Bulletin PKB or PWB shunt module to install, wire, and configure the module.
• To avoid nuisance thermal overload trips, configure Bulletin PKB and PWB active-shunt modules to the highest shunt turn-on voltage setting. The recommended setting for Line Voltage Level Jumper is JP5.
• Configure Bulletin PKB and PWB active-shunt modules in Internal (automatic) mode. Unless an external enable signal is provided, configure the Brake Enable Jumper in Internal (automatic) mode (JP6 is in the downward position).
Power Supply Ground Screw Setting
The 2198-P xxx
DC-bus power supply has a factory-installed ground screw for grounded-wye power distribution. This table summarizes the ground screw settings for the 2198-P xxx
DC-bus power supply.
Table 22 - Ground Screw Settings for the DC-bus Power Supply
Ground Configuration
2198-P xxx
DC-bus Power Supply
Ground screw installed (default setting)
(1) Grounded (wye)
• Impedance grounded
• Corner grounded
• AC-fed ungrounded
(1) Ground screw is factory installed.
Remove ground screw/jumper
IMPORTANT If you have grounded-wye power distribution in your facility, do not remove the ground screw from the DC-bus power supply.
Remove the ground screw when using ungrounded, corner-grounded, or impedance-grounded power.
34 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Non-regenerative Common DC-bus Configurations With Passive or Active Shunt Chapter 3
Contactor Enable Relay
The contactor-enable circuitry includes a relay-driven contact within the 2198-P xxx
DC-bus power supply. The relay protects the Kinetix 5700 drive system in the event of overloads or other fault conditions.
Figure 21 - Contactor-enable Control String
Kinetix 5700
2198-P208
DC-bus Power Supply
Kinetix 6 x 00
2094-BC xx -M xx -S
Integrated Axis Module
* Indicates User Supplied Component
Kinetix 7000
2099-BM xx -S
Servo Drive
24V AC/DC
50/60 Hz
CR1 *
CR1 *
M1 *
STOP *
START *
CR1 *
CONT EN+ CONT EN– CONT EN+ CONT EN–
GPR2+ GPR2–
An AC three-phase mains contactor must be wired in series between the branch circuit protection and the power supply. In addition, the AC three-phase contactor control string must be wired in series with the contactor-enable relay at the contactor-enable terminals.
PowerFlex 750-Series drives are not required to include a contactor-enable control string and they do not have a dedicated contactor enable relay. Although not required, if leveraging Integrated Motion with a PowerFlex 755 drive, we recommend that you configure a digital output from the drive as Contactor Enable and include it in the contactor enable control string.
A Contactor Enable output can be configured in the PowerFlex 755 drive in integrated motion only. The operation of this output is tied to fault processing in the drive. The drive de-energizes the Contactor Enable output when an exception causes the axis to go to the Shutdown state.
This configuration is only valid when an auxiliary power supply is used for control power with frames 1…7 drives.
ATTENTION: Wiring the contactor enable relay is required for Kinetix 5700, Kinetix 6 x
00, and Kinetix 7000 drive systems to help prevent personal injury or damage to Kinetix drive modules. Wire the contactor enable relay into your control string so that:
• three-phase power is removed and the power supply or regenerative bus supply is protected under various fault conditions
• three-phase power is never applied to the Kinetix 5700 drive system before control power is applied.
Figure 22 - Contactor-enable Relay Circuit
CONT EN+
Normally
Open
Relay
CONT EN-
Power Supply
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the contactor-enable circuitry.
ATTENTION: For Kinetix 6000 (400V-class) and Kinetix 6200/6500 drive in common-bus configurations, the contactor enable connections for leader and follower drives must be wired in series to the control string.
A contactor or other device that routinely disconnects and reapplies the AC line to the bus supply can cause drive hardware damage. If an input device is used, operation must not exceed two cycles per minute (maximum) or damage can occur to the precharge circuit.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 35
Chapter 3 Non-regenerative Common DC-bus Configurations With Passive or Active Shunt
System Sizing
These limitations apply to systems supplied by a single 2198-P xxx
or multiple 2198-P208 DC-bus power supplies:
• The sum of the inverter motor-power cable lengths for all inverters on the same DC bus-sharing group must not exceed 1200 m
(3937 ft) to comply with IEC 61800-3 (category C3) requirements when used with 2198-DBR xx
-F line filters. 2198-DB xx
-F line filters have a total motor cable length limit of 400 m (1312 ft). See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional motor power cable-length limitations.
• The total system capacitance limit is based on the power supply catalog number. DC-bus groups must not exceed the limits as defined in
Kinetix and PowerFlex Drive Specifications on page 59
.
• No more than three 2198-P208 DC-bus power supplies can be used to increase the converter power.
• If using the 24V DC shared-bus connection system, add another 24V power supply when control input power to a cluster of drive modules exceeds 40 A.
• The Kinetix 5700 system can have multiple drive clusters in a single DC-bus group. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on extended clusters.
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on system sizing guidelines.
The motor required for a particular application determines the drive required for full motor performance. For best results, use Motion
Analyzer system sizing and selection tool, available at https://motionanalyzer.rockwellautomation.com/ .
Capacitance Sizing
Total system capacitance is the sum of all internal capacitance values from each of the drive modules (AC drives, single-axis inverters, dualaxis inverters, power supplies, and capacitor modules) in the same DC-bus group.
The total system capacitance must be less than the maximum supported DC-bus capacitance value of the power supply (refer to
PowerFlex Drive Specifications on page 59
).
IMPORTANT If your total system capacitance value exceeds the maximum supported capacitance value of the DC-bus power supply, perform one of the following:
• Increase the size of the 2198-P xxx
DC-bus power supply
• Use multiple 2198-P208 DC-bus power supplies (1…3 power supplies are possible with only 2198-P208 power supply)
• Decrease the total system capacitance by removing inverters or capacitor modules from the DC-bus group
• Separate clusters into multiple DC-bus groups
All drives have a DC-bus capacitance that is proportional to their power ratings. When used in a common DC-bus configuration, these capacitors are directly connected in parallel. This connection results in the DC-bus ripple being shared proportional to the power rating of the drive. When the ratio of the capacitance to the drive-rated current is consistent, it provides the best DC-bus ripple sharing.
For 400/480V AC, the target ratio is 40 µF/A ±10% or greater. For all drives supported in this publication, the target ratio is met when a capacitor module is used to extend the DC-bus, proper DC-bus cable length guidelines are followed, and low-inductance DC cable is used.
on
Circuit Protection
Do not daisy chain drives to share DC-bus fusing. Configure the shared DC-bus in a star configuration to enable proper fusing. Use fast semiconductor fuses in the DC links to minimize destructive energy in the event of a part or control malfunction. Size fuses to handle large peak currents at the end of precharge.
• See
Kinetix and PowerFlex Drive Specifications on page 59
for the recommended common DC-bus circuit protection devices.
• See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for recommended AC input circuit protection for the Bulletin
2198 power supply.
36 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Chapter
4
Regenerative Bus Supply Configurations
Regenerative bus supplies use a PWM-controlled IGBT converter for full regeneration of power to the AC line. The regenerative bus supply returns energy back to the distribution system instead of dissipating energy with shunt resistor (braking) technology. This configuration provides low AC-line harmonics and can be used to meet IEEE-519.
Supported Products
At the time of publication, the following products are supported.
Table 23 - Kinetix 5700 Regenerative Bus Supply Modules
Regenerative Bus Supply
Cat. No.
• 2198-RP088
• 2198-RP200
• 2198-RP263
• 2198-RP312
Supported Drives
PowerFlex® 750-Series: Frames 1…6
(1)
Kinetix® 7000: 2099-BM06-S…2099-BM12-S
Kinetix 6000 and Kinetix 6200/6500: All 460V configurations
(2)
(1) PowerFlex 750-Series (Frames 5 and 6) DC input version drives with precharge must be selected.
(2) Kinetix 6000 configurations require firmware revision 1.92 or later.
IMPORTANT The internal IGBT in Kinetix 6000 (460V) drives and Kinetix 6200/6500 drives are disabled in Common Bus Follower mode.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 37
Chapter 4 Regenerative Bus Supply Configurations
Typical System Configuration
In this example, standalone AC drives, Kinetix 6 x
00 drives, and Kinetix 7000 drives receive DC-bus power from the 2198-RP200 regenerative bus supply.
Figure 23 - Regenerative Bus Supply with Standalone AC Drives, Kinetix 6 x 00 Drives, and Kinetix 7000 Drives
Three-phase
Source
(2)
Three-phase
Contactor
Line
Reactor
(1)
Regenerative
Bus Supply
Capacitor
Module
DC-bus Conditioner
Module
(3)
DC Bus
DC+ DCDC+ DCDC+ DC-
AC Drive AC Drive
M M
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
(1) A line reactor can be required. For line reactor selection, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) Kinetix 5700 regenerative bus supplies require an isolation transformer when connected to corner-grounded or ungrounded facility power.
(3) Kinetix 5700 regenerative bus supplies in mixed common-bus systems require a DC-bus conditioner module in the power supply cluster.
Table 24 - Special Bus Requirements
Drawing Designation
AC drives
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
General Considerations
This section includes information on AC line impedance, disconnect switch connections, and ground screw/jumper settings, depending on the drive family.
ATTENTION: The incorrect use or configuration of third party assemblies can result in reduced system reliability and drive damage.
• All system components (bus supply and PowerFlex or Kinetix drives) must be selected for the same AC-line voltage.
• Low-inductance type DC-bus must be used. See
on
for details.
• To be used in a common-bus system with a Kinetix 5700 bus supply, the Kinetix 6000 or Kinetix 6200/6500 drive systems must be configured as common-bus follower (internal IGBT for shunting is disabled).
IMPORTANT Do not include the 2094-BSP2 shunt module on the 2094 power rail.
• The Kinetix 7000 drive internal IGBT for shunting is not used by the drive main control for bus regulation, therefore any type of regulation must come from an external source.
• Refer to
on
page 81 for user documentation with the maximum motor cable length requirements of the drives
specific to your application.
38 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations Chapter 4
AC Line Impedance Considerations
In the following use cases, an additional transformer or line reactor is required due to faults or potential damage associated with AC line disturbances:
• Installation site has switched power-factor correction capacitors.
• Installation site has lightning strikes or voltage spikes in excess of 6000V peak.
• Installation site has power interruptions or voltage dips in excess of 200V AC.
• The transformer kVA is more than 10 times larger than the drive kVA or the percent source impedance relative to each converter is less than 0.5%.
In the following use cases, a line reactor is required due to faults associated with sharing AC line-input on multiple converters:
• Repetitive AC input line-voltage notching is present. For example, if silicon-controlled rectifier drive is connected to the same AC input power source.
- In drive systems that include the regenerative bus supply, repetitive AC line voltage notching can cause the integrated AC line filter to overheat and result in FLT S18 converter overtemperature faults.
• Powering multiple (two or more) regenerative bus supplies from the same AC input-power source.
- Switching ripple from each regenerative bus supply can interfere with other regenerative bus supplies on the same AC input power source.
• Powering 2198-P xxx
DC-bus power supply and 2198-RP xxx
regenerative bus supply from the same AC input-power source.
- Switching ripple from the regenerative bus supply can impact the temperature of DC-bus capacitors in the DC-bus power supply. In this use case, a line reactor is required in the AC input-power string leading to the regenerative bus supply.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional AC line impedance considerations.
Disconnect Switch Considerations
If a disconnect switch is used between the common DC-bus and a PowerFlex 750-Series drive input, connect an auxiliary contact on the disconnect switch to a digital input of the drive. The corresponding digital input must be set to Precharge Enable. This setting provides the proper precharge interlocking, which guards against possible damage to the drive when reconnecting the drive to an energized DC-bus.
Under this condition, the drives must have an internal or externally supplied precharge. Precharge handshaking is required before inverter operation.
Table 25 - PowerFlex 750-Series Drive Precharge Parameter
Number
189 [DI Precharge]
Parameter
Digital Input
Setting
See PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001 .
ATTENTION: To avoid personal injury and/or equipment damage, make sure installation complies with specifications regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment.
ATTENTION: The Kinetix 6000 (400V-class), Kinetix 6200/6500, Kinetix 7000, and PowerFlex 750-Series (Frames 5 and 6) AC input drives have no method for you to control the precharge sequence. To avoid sever drive and/or equipment damage due to uncontrolled precharge, do not connect these drives to an energized bus. If a disconnect switch is used between the inputs of the drives and the common DC-bus, an external precharge device must be used.
When an external precharge device is required, a fuse combination switch can be used. These switches provide precharge of capacitive loads, have integrated fuse protection, and perform automatic pre-load type functions with an internal coil.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 39
Chapter 4 Regenerative Bus Supply Configurations
Input and Output Signals
For the Kinetix 7000 drives, wire the control and interface signals on the General Purpose Relay (GPR) and General Purpose I/O (GPIO) connectors as described in the following tables. See the Kinetix 7000 Servo Drives User Manual, publication 2099-UM001 , for more information on the terminal block connections.
Table 26 - General Purpose Relay Connections
Signal
DRIVE OK+
DRIVE OK-
Terminal
5
6
Description
Programmable N.O. Relay 2 output
Programmable Relay 2 common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
Table 27 - General Purpose I/O Connections
Signal
Regen_OK+
Regen_OK-
Terminal
7
8
Description
Regenerative power supply status
Regenerative power supply status common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
ATTENTION: For the Kinetix 7000 drives, wiring the DRIVE OK signal on the General Purpose Relay is required. To avoid injury or damage to the drive, wire the DRIVE OK relay into your control string.
In common bus configurations, a REGEN connection on the General Purpose I/O connector is also required for the drives. This connection must be wired in series to the control string, and also wired from the regenerative bus supply to the Kinetix 7000 drive to indicate bus voltage is present.
Drive Ground Jumper Settings
Set the ground jumpers for the Kinetix 6000 (400V-class), Kinetix 6200/6500, and Kinetix 7000 drives according to the following tables. Refer
Table 28 - Ground Jumper Settings for Kinetix 6000 (400V-class) and Kinetix 6200/6500 Drives
Ground Configuration
Grounded (wye)
Ground Jumper Setting
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
Set for ungrounded power
(1)
Table 29 - Ground Jumper Settings for Kinetix 7000 Drives
Ground Configuration Ground Jumper Setting
(1)
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
Removed
40 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations Chapter 4
PowerFlex 750-Series drives contain protective metal-oxide varistors (MOV) and common mode capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the following table.
Table 30 - Power Jumper Settings for PowerFlex 750-Series Drives (Frames 1…6)
Ground Configuration Ground Jumper Setting
(1)
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
For instructions on how to disconnect the PE jumpers, refer to PowerFlex 750-Series Power Jumpers Installation Instructions, publication
750-IN011 .
Kinetix 5700 Regenerative Bus Supply Considerations
When extending the DC-bus from the power supply cluster, a capacitor module must be used to extend the bus. Refer to
Accessory Modules on page 71 for more information on when accessory modules are required.
IMPORTANT Regenerative bus supplies do not require an isolation transformer for three-phase input power unless they are connected to corner-grounded or ungrounded facility power.
Bus Supply Ground Jumper Setting
The 2198-RP xxx
regenerative bus supply has a factory-installed ground screw for grounded-wye power distribution. The following table summarizes the ground screw/jumper settings for the 2198-RP xxx
regenerative bus supply.
Table 31 - Ground Jumper Settings for the Regenerative Bus Supply
Ground Configuration
2198-RP xxx
Regenerative Bus Supply
• Grounded (wye)
• Corner-grounded with isolation transformer
• Ungrounded with isolation transformer
Ground jumper installed (default setting)
Impedance grounded Remove ground jumper
(1)
(1) When the regenerative bus supply ground jumper is removed, it can be permanently stored in threaded holes at the bottom of the chassis.
IMPORTANT If you have grounded-wye power distribution in your facility, or corner-grounded or ungrounded power with an isolation transformer, do not remove the ground jumper from the regenerative bus supply. Remove the ground jumper when using impedance-grounded power.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 41
Chapter 4 Regenerative Bus Supply Configurations
Converter OK Signal
The converter OK circuitry of the Kinetix 5700 regenerative bus supply is a relay-driven contact that provides a 24V signal to non-
Kinetix 5700 inverters that they can draw power from the regenerative power supply and that the power supply is not faulted.
Figure 24 - Converter OK Relay Circuit
Regenerative
Bus Supply
Internally
Controlled
Relay
24V PWR
Resettable
Fuse
24V COM
OK+
OK–
The CONV OK signal of the Kinetix 5700 regenerative bus supply (contactor enable connector) can be connected/interlocked to the following
Kinetix and PowerFlex drive inputs to indicate that they can pull power from the bus:
• Regen OK input of Kinetix 7000 drives
• Regeneration OK input of Kinetix 6200/6500 drives
• Enable input of Kinetix 6000 drives
• Regeneration OK input of PowerFlex 750-series drives
Figure 25 - Converter OK Connected/Interlocked to Drive Input
Di C
Di 0
PowerFlex 750-Series Drives
(1)
24VCOM
Regeneration OK
IOD-3
IOD-2
Kinetix 6000 Drives
24VCOM
Enable
IOD-40
IOD-41
Kinetix 6200/6500 Drives
24VCOM
Regeneration OK
GPIO-7
GPIO-8
Kinetix 7000 Drives
Regen_OK+
Regen_OK–
2198-RP xxx
Regenerative Bus Supply
OK+
OK–
CONV OK+
CONV OK–
CONT EN+
CONT EN–
Contactor Enable
(CED) Connector
(1) A 20-750-2262C-2R, or equivalent, option module is required to use the Regeneration OK input. The Regeneration OK input is available only if the Integrated Motion feature of the PowerFlex
750-Series drive is being used. If Integrated Motion is not being used, the Precharge digital input can be used instead.
For PowerFlex drives, the Regeneration OK Input functionality is available for PowerFlex 755 drives only with Integrated Motion applications.
When in motion and the drive detects the Regeneration OK Input transition to an inactive state, the drive generates the Regeneration Powersupply Failure exception and coasts to a stop. The exception cannot be configured and is assigned Stop drive only.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the Converter OK circuitry.
42 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations Chapter 4
Contactor Enable Relay
The contactor-enable circuitry includes a relay-driven contact within the 2198-RP xxx
DC-bus power supply. The relay protects the
Kinetix 5700 drive system in the event of overloads or other fault conditions.
Figure 26 - Contactor-enable Control String
Kinetix 5700
2198-RP xxx
Regenerative Bus Supply
Kinetix 6 x 00
2094-BC xx -M xx -S
Integrated Axis Module
* Indicates User Supplied Component
Kinetix 7000
2099-BM xx -S
Servo Drive
24V AC/DC
50/60 Hz
CR1 *
CR1 *
M1 *
STOP *
START *
CR1 *
CONT EN+ CONT EN– CONT EN+ CONT EN–
GPR2+ GPR2–
An AC three-phase mains contactor must be wired in series between the branch circuit protection and the power supply. In addition, the AC three-phase contactor control string must be wired in series with the contactor-enable relay at the contactor-enable terminals.
PowerFlex 750-Series drives are not required to include a contactor-enable control string and they do not have a dedicated contactor enable relay. Although not required, if leveraging Integrated Motion with a PowerFlex 755 drive, we recommend that you configure a digital output from the drive as Contactor Enable and include it in the contactor enable control string.
A Contactor Enable output can be configured in the PowerFlex 755 drive in integrated motion only. The operation of this output is tied to fault processing in the drive. The drive de-energizes the Contactor Enable output when an exception causes the axis to go to the Shutdown state.
This configuration is only valid when an auxiliary power supply is used for control power with frames 1…7 drives.
ATTENTION: Wiring the contactor enable relay is required for Kinetix 5700, Kinetix 6 x
00, and Kinetix 7000 drive systems to help prevent personal injury or damage to Kinetix drive modules. Wire the contactor enable relay into your control string so that:
• three-phase power is removed and the power supply or regenerative bus supply is protected under various fault conditions
• three-phase power is never applied to the Kinetix 5700 drive system before control power is applied.
Figure 27 - Contactor-enable Relay Circuit
CONT EN+
Normally
Open
Relay
CONT EN-
Power Supply
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the contactor-enable circuitry.
ATTENTION: For Kinetix 6000 (400V-class) and Kinetix 6200/6500 drive in common-bus configurations, the contactor enable connections for leader and follower drives must be wired in series to the control string.
A contactor or other device that routinely disconnects and reapplies the AC line to the bus supply can cause drive hardware damage. If an input device is used, operation must not exceed two cycles per minute (maximum) or damage can occur to the precharge circuit.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 43
Chapter 4 Regenerative Bus Supply Configurations
System Sizing
These limitations apply to systems supplied by 2198-RP xxx
regenerative bus supplies:
• The sum of the inverter motor-power cable lengths for all inverters on the same DC bus-sharing group must not exceed 1200 m
(3937 ft) to comply with IEC 61800-3 (category C3) requirements when used with 2198-DBR xx
-F line filters. 2198-DB xx
-F line filters have a total motor cable length limit of 400 m (1312 ft). See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional motor power cable-length limitations.
• The total system capacitance limit is based on the power supply catalog number. DC-bus groups must not exceed the limits as defined in
Kinetix and PowerFlex Drive Specifications on page 59
.
• If using the 24V DC shared-bus connection system, add another 24V power supply when control input power to a cluster of drive modules exceeds 40 A.
• The Kinetix 5700 system can have multiple drive clusters in a single DC-bus group. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on extended clusters.
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on system sizing guidelines.
The motor required for a particular application determines the drive required for full motor performance. For best results, use the Motion
Analyzer system sizing and selection tool, available at https://motionanalyzer.rockwellautomation.com/ .
Capacitance Sizing
Total system capacitance is the sum of all internal capacitance values from each of the drive modules (AC drives, single-axis inverters, dualaxis inverters, power supplies, and capacitor modules) in the same DC-bus group.
The total system capacitance must be less than the maximum supported DC-bus capacitance value of the power supply (refer to
PowerFlex Drive Specifications on page 59
).
IMPORTANT If your total system capacitance value exceeds the maximum supported capacitance value of the regenerative bus supply, perform one of the following:
• Increase the size of the 2198-RP xxx
regenerative bus supply
• Decrease the total system capacitance by removing inverters or capacitor modules from the DC-bus group
• Separate clusters into multiple DC-bus groups
External bus capacitance is the total system capacitance minus the power supply capacitance. The external bus capacitance must be entered into the Logix Designer application for a regenerative power supply to maintain proper control.
All drives have a DC-bus capacitance that is proportional to their power ratings. When used in a common DC-bus configuration, these capacitors are directly connected in parallel. This connection results in the DC-bus ripple being shared proportional to the power rating of the drive. When the ratio of the capacitance to the drive-rated current is consistent, it provides the best DC-bus ripple sharing.
For 400/480V AC, the target ratio is 40 µF/A ±10% or greater. For all drives supported in this publication, the target ratio is met when a capacitor module is used to extend the DC-bus, proper DC-bus cable length guidelines are followed, and low-inductance DC cable is used.
on
Circuit Protection
Do not daisy chain drives to share DC-bus fusing. Configure the shared DC-bus in a star configuration to enable proper fusing. Use fast semiconductor fuses in the DC links to minimize destructive energy in the event of a part or control malfunction. Size fuses to handle large peak currents at the end of precharge.
• See
Kinetix and PowerFlex Drive Specifications on page 59
for the recommended common DC-bus circuit protection devices.
• See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for recommended AC input circuit protection for the Bulletin
2198 power supply.
44 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Chapter
5
Regenerative Bus Supply Configurations With Active Shunt
This system also uses a PWM-controlled IGBT converter for regeneration of power to the AC line. However, in this configuration some regenerative DC-bus energy flows to the incoming AC line, but DC-bus energy that is not regenerated is dissipated to an external shunt resistor (braking) unit. This configuration provides low AC-line harmonics and can be used to meet IEEE-519. Contact our Encompass™
Partners for these shunt resistor (braking) products.
Supported Products
At the time of publication, the following products are supported.
Table 32 - Kinetix 5700 Regenerative Bus Supply Modules
Regenerative Bus Supply
Cat. No.
• 2198-RP088
• 2198-RP200
• 2198-RP263
• 2198-RP312
Supported Drives
PowerFlex® 750-Series: Frames 1…6
(1)
Kinetix® 7000: 2099-BM06-S…2099-BM12-S
Kinetix 6000 and Kinetix 6200/6500: All 460V configurations
(2)
(1) PowerFlex 750-Series (Frames 5 and 6) DC input version drives with precharge must be selected.
(2) Kinetix 6000 configurations require firmware revision 1.92 or later.
When applicable, the drive's internal IGBT can be used with a passive shunt.
Drive Family
PowerFlex 750-Series
Internal Brake IGBT
Standard on Frames 1…5, optional on Frame 6.
Kinetix 7000 No internal brake IGBT.
Kinetix 6000 (400V-class) and Kinetix 6200/6500 Internal bus regulation cannot be used.
IMPORTANT The internal IGBT in Kinetix 6000 (460V) drives and Kinetix 6200/6500 drives are disabled in Common Bus Follower mode.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 45
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
Typical System Configuration
In this example, standalone AC drives with an external passive shunt, Kinetix 6 x
00 drives, and Kinetix 7000 drives receive DC-bus power from the 2198-RP200 regenerative bus supply.
Figure 28 - Regenerative Bus Supply with Standalone AC Drives, Kinetix 6 x 00 Drives, Kinetix 7000 Drives, and External Passive Shunt
Three-phase
Source
(2)
Three-phase
Contactor
Line
Reactor
(1)
Regenerative
Bus Supply
Capacitor
Module
DC-bus Conditioner
(3)
Module
DC Bus
DC+
(4) (5)
BR
DCDC+ DCDC+ DC-
AC Drive 1 AC Drive 2
M M
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
(1) A line reactor can be required. For line reactor selection, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) Kinetix 5700 regenerative bus supplies require an isolation transformer when connected to corner-grounded or ungrounded facility power.
(3) Kinetix 5700 regenerative bus supplies in mixed common-bus systems require a DC-bus conditioner module in the power supply cluster.
(4) External passive shunt resistor. For minimum ohms with PowerFlex 750-Series drives, see PowerFlex Dynamic Braking Resistor Calculator Application Technique, publication PFLEX-AT001 .
(5) Connect the shunt resistor (braking IGBT) to the largest frame size drive.
Table 33 - Special Bus Requirements
Drawing Designation
AC Drive 1
AC Drive 2
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
46 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
In this example, standalone AC drives, Kinetix 6 x
00 drives, and Kinetix 7000 drives receive DC-bus power from the 2198-RP200 regenerative bus supply. An external active shunt is connected to the regenerative bus supply active-shunt (RC) connector.
Figure 29 - Regenerative Bus Supply with Standalone AC Drives, Kinetix 6 x 00 Drives, Kinetix 7000 Drives, and External Active Shunt
Three-phase
Source
(2)
Three-phase
Contactor
Line
Reactor
(1)
(3) (4)
Regenerative
Bus Supply
Capacitor
Module
DC-bus Conditioner
(5)
Module
DC Bus
DC+ DCDC+ DCDC+ DC-
AC Drive 1 AC Drive 2
M M
M M M M
Integrated
Axis Module
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
(1) A line reactor can be required. For line reactor selection, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) Kinetix 5700 regenerative bus supplies require an isolation transformer when connected to corner-grounded or ungrounded facility power.
(3) Due to the 10 A connector current rating, connections to the 2198-RP xxx
(RC connector) are limited to only Powerohm PKB xxx
active shunts rated at 7 kW or less.
(4) External active shunt module. For active shunt mounting and wiring considerations, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(5) Kinetix 5700 regenerative bus supplies in mixed common-bus systems require a DC-bus conditioner module in the power supply cluster.
Table 34 - Special Bus Requirements
Drawing Designation
AC Drive
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 47
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
In this example, standalone AC drives, Kinetix 6 x
00 drives, and Kinetix 7000 drives receive DC-bus power from the 2198-RP200 regenerative bus supply. An external active shunt is connected to the DC-bus studs of an accessory module.
Figure 30 - Regenerative Bus Supply with Standalone AC Drives, Kinetix 6 x 00 Drives, Kinetix 7000 Drives, and External Active Shunt
Three-phase
Source
(2)
Three-phase
Contactor
Line
Reactor
(1)
Regenerative
Bus Supply
Capacitor
Module
DC-bus Conditioner
(3)
Module
DC Bus
DC+ DCDC+ DCDC+ DCDC+ DC-
External Active
Shunt
(4)
BR1 BR2
AC Drive 1 AC Drive 2
BR
M M
(1) A line reactor can be required. For line reactor selection, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) Kinetix 5700 regenerative bus supplies require an isolation transformer when connected to corner-grounded or ungrounded facility power.
(3) Kinetix 5700 regenerative bus supplies in mixed common-bus systems require a DC-bus conditioner module in the power supply cluster.
(4) External active shunt module. For active shunt mounting and wiring considerations, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
M
Integrated
Axis Module
M M M
Axis
Modules
Kinetix 6000 or
Kinetix 6200/6500 Drives
Table 35 - Special Bus Requirements
Drawing Designation
AC Drive
Kinetix 6000 and
Kinetix 6200/6500 drives
Supported Drives
PowerFlex 750-Series: Frames 1…6
Kinetix 7000: 2099-BM06-S…2099-BM08-S
Kinetix 7000: 2099-BM09-S…2099-BM12-S
Kinetix 6000: All 460V configurations
(1)
Kinetix 6200/6500: All 460V configurations
(1) No internal precharge. Drives must be placed in common-bus follower configuration.
Special Bus Requirements
None
None
General Considerations
This section includes information on AC line impedance, disconnect switch connections, and ground screw/jumper settings, depending on the drive family.
ATTENTION: The incorrect use or configuration of third party assemblies can result in reduced system reliability and drive damage.
• All system components (bus supply and PowerFlex or Kinetix drives) must be selected for the same AC-line voltage.
• Low-inductance type DC-bus must be used. See
on
for details.
• To be used in a common-bus system with a Kinetix 5700 bus supply, the Kinetix 6000 or Kinetix 6200/6500 drive systems must be configured as common-bus follower (internal IGBT for shunting is disabled).
IMPORTANT Do not include the 2094-BSP2 shunt module on the 2094 power rail.
• The Kinetix 7000 drive internal dynamic brake IGBT is not used by the drive main control for bus regulation, therefore any type of regulation must come from an external source.
• Refer to
on
page 81 for user documentation with the maximum motor cable length requirements of the drives
specific to your application.
48 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
AC Line Impedance Considerations
In the following use cases, an additional transformer or line reactor is required due to faults or potential damage associated with AC line disturbances:
• Installation site has switched power-factor correction capacitors.
• Installation site has lightning strikes or voltage spikes in excess of 6000V peak.
• Installation site has power interruptions or voltage dips in excess of 200V AC.
• The transformer kVA is more than 10 times larger than the drive kVA or the percent source impedance relative to each converter is less than 0.5%.
In the following use cases, a line reactor is required due to faults associated with sharing AC line-input on multiple converters:
• Repetitive AC input line-voltage notching is present. For example, if silicon-controlled rectifier drive is connected to the same AC input power source.
- In drive systems that include the regenerative bus supply, repetitive AC line voltage notching can cause the integrated AC line filter to overheat and result in FLT S18 converter overtemperature faults.
• Powering multiple (two or more) regenerative bus supplies from the same AC input-power source.
- Switching ripple from each regenerative bus supply can interfere with other regenerative bus supplies on the same AC input power source.
• Powering 2198-P xxx
DC-bus power supply and 2198-RP xxx
regenerative bus supply from the same AC input-power source.
- Switching ripple from the regenerative bus supply can impact the temperature of DC-bus capacitors in the DC-bus power supply. In this use case, a line reactor is required in the AC input-power string leading to the regenerative bus supply.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional AC line impedance considerations.
Disconnect Switch Considerations
If a disconnect switch is used between the common DC-bus and a PowerFlex 750-Series drive input, connect an auxiliary contact on the disconnect switch to a digital input of the drive. The corresponding digital input must be set to Precharge Enable. This setting provides the proper precharge interlocking, which guards against possible damage to the drive when reconnecting the drive to an energized DC-bus.
Under this condition, the drives must have an internal or externally supplied precharge. Precharge handshaking is required before inverter operation.
Table 36 - PowerFlex 750-Series Drive Precharge Parameter
Parameter
Number
189 [DI Precharge]
Digital Input
Setting
See PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001 .
ATTENTION: To avoid personal injury and/or equipment damage, make sure installation complies with specifications regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment.
If DC input is supplied to 2099-BM09-S, 2099-BM10-S, 2099-BM11-S, or 2099-BM12-S drives, the precharge capability must be provided at the system level. Disconnect switches must not be used between the input of the drive and a common DC-bus without the use of an external precharge device.
ATTENTION: The Kinetix 6000 (400V-class), Kinetix 6200/6500, Kinetix 7000, and PowerFlex 750-Series (Frames 5 and 6) AC input drives have no method for you to control the precharge sequence. To avoid sever drive and/or equipment damage due to uncontrolled precharge, do not connect these drives to an energized bus. If a disconnect switch is used between the inputs of the drives and the common DC-bus, an external precharge device must be used.
When an external precharge device is required, a fuse combination switch can be used. These switches provide precharge of capacitive loads, have integrated fuse protection, and perform automatic pre-load type functions with an internal coil.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 49
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
Input and Output Signals
For the Kinetix 7000 drives, wire the control and interface signals on the General Purpose Relay (GPR) and General Purpose I/O (GPIO) connectors as described in the following tables. See the Kinetix 7000 Servo Drives User Manual, publication 2099-UM001 , for more information on the terminal block connections.
Table 37 - General Purpose Relay Connections
Signal
DRIVE OK+
DRIVE OK-
Terminal
5
6
Description
Programmable N.O. Relay 2 output
Programmable Relay 2 common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
Table 38 - General Purpose I/O Connections
Signal
Regen_OK+
Regen_OK-
Terminal
7
8
Description
Regenerative power supply status
Regenerative power supply status common
Recommended Wire Size mm
2
(AWG)
0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)
Strip Length mm (in.)
7.0 (0.275)
Torque Value
N•m (lb•in)
0.235 (2.0)
ATTENTION: For the Kinetix 7000 drives, wiring the DRIVE OK signal on the General Purpose Relay is required. To avoid injury or damage to the drive, wire the DRIVE OK relay into your control string.
In common bus configurations, a REGEN connection on the General Purpose I/O connector is also required for the drives. This connection must be wired in series to the control string, and also wired from the regenerative bus supply to the Kinetix 7000 drive to indicate bus voltage is present.
50 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
Drive Ground Jumper Settings
Set the ground jumpers for the Kinetix 6000 (400V-class), Kinetix 6200/6500, and Kinetix 7000 drives according to the following tables. Refer
Table 39 - Ground Jumper Settings for Kinetix 6000 (400V-class) and Kinetix 6200/6500 Drives
Ground Configuration
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
Ground Jumper Setting
(1)
Set for ungrounded power
Table 40 - Ground Jumper Settings for Kinetix 7000 Drives
Ground Jumper Setting
(1) Ground Configuration
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
Removed
PowerFlex 750-Series drives contain protective metal-oxide varistors (MOV) and common mode capacitors referenced to ground. To guard against unstable operation and/or damage, the drive must be properly configured as shown in the following table.
Table 41 - Power Jumper Settings for PowerFlex 750-Series Drives (Frames 1…6)
Ground Jumper Setting
(1) Ground Configuration
Grounded (wye)
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
• DC-bus from active converter
(1) When powered by 2198-RP xxx regenerative bus supply.
• Jumper PE-A disconnected (MOV/input filter caps)
• Jumper PE-B disconnected (DC-bus common mode caps)
For instructions on how to disconnect the PE jumpers, refer to PowerFlex 750-Series Power Jumpers Installation Instructions, publication
750-IN011 .
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 51
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
Active Shunt Considerations
External active shunts are required in the following use cases:
• The 2198-RP xxx regenerative bus supply provides DC-bus power while
DC-bus regulation is not enabled.
• One permanent magnet motor runs above its bus overvoltage speed. See Kinetix 5700 Servo Drives User Manual, publication
2198-UM002 , information on the Field Weakening Mode feature.
• One permanent magnet motor drives a vertical load that could make the motor accelerate above the bus overvoltage speed during a fault condition.
• Any condition where total shared DC-bus regenerative power is greater than the 2198-RP xxx
regenerative bus supply capacity. For example, consider a peak-power stopping condition.
• The 2198-RP xxx
regenerative bus supply is operating with DC-bus regulation enabled and the regenerative bus supply loses threephase AC input power, 24V DC input power, or has a fault condition.
ATTENTION: To avoid damage to the Kinetix 5700 drive system, wire the active shunt thermal switch to a digital input on the power supply and configure the Shunt Thermal Switch OK function in the Logix Designer application.
ATTENTION: DC-bus failure can cause damage to all drive modules in the bus group, not just the inverter connected to the motor.
Active shunts are available from the Rockwell Automation Encompass partner Powerohm Resistors, Inc. See http://www.powerohm.com
for more information on Powerohm active shunts.
IMPORTANT Powerohm Bulletin PKB xxx
active shunt modules use built-in internal brake resistors. Bulletin PWB xxx
active shunt modules require appropriately sized external brake resistors.
Table 42 - Compatible Active Shunt Specifications (internal brake resistor)
Kinetix 5700 Power Supply
Powerohm
Resistors
Cat. No.
(1)
2198-RP xxx regenerative bus supply when DC-bus regulation is not enabled.
PKB005
PKB010
PKB050
PKB005-800
2198-RP xxx regenerative bus supply when DC-bus regulation is enabled.
PKB010-800
PKB050-800
Input Voltage, nom
480V AC
Turn -on
Bus Voltage
750V DC
800V DC
Continuous
Power kW
1.50
2.06
7.00
1.50
2.06
7.00
Resistance
(internal)
Ω
108
52.7
10.5
108
52.7
10.5
Resistance
(minimum)
Ω
–
–
–
–
–
–
Continuous
Current
Amps
2.00
2.75
9.30
1.88
2.58
8.72
Peak
Current
Amps
6.9
14.2
71.4
7.4
15.2
76.2
(1) How the Powerohm PKB xxx
shunts connect to the 2198-RP xxx regenerative bus supply is explained in
2198-RPxxx Bus Supply with External Active Shunt (built-in brake resistor) on page 54 .
Table 43 - Compatible Active Shunt Specifications (no internal brake resistor)
Kinetix 5700 Power Supply
2198-RP xxx regenerative bus supply when DC-bus regulation is not enabled.
2198-RP xxx regenerative bus supply when DC-bus regulation is enabled.
Powerohm
Resistors
Cat. No.
(1)
PWB035
PWB110
PWB035-800
PWB110-800
Input Voltage, nom
480V AC
Turn -on
Bus Voltage
750V DC
800V DC
Continuous
Power kW
26.25
82.5
26.25
82.5
Resistance
(internal)
Ω
–
–
–
–
Resistance
(minimum)
Ω
7.5
2.5
8.0
2.7
Continuous
Current
Amps
35
110
35
110
Peak
Current
Amps
100
300
100
300
(1) How the Powerohm PWB xxx
shunts connect to the 2198-RP xxx regenerative bus supply is explained in
2198-RPxxx Bus Supply with External Active Shunt (external brake resistor) on page 55
52
ATTENTION: Do not use Powerohm active-shunt modules at input line voltages that exceed 528V AC. Active-shunt thermal-overload shutdown can occur if input line voltage exceeds 528V AC.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
Kinetix 5700 Regenerative Bus Supply Considerations
When extending the DC-bus from the power supply cluster, a capacitor module must be used to extend the bus. Refer to
Accessory Modules on page 71 for more information on when accessory modules are required.
IMPORTANT Regenerative bus supplies do not require an isolation transformer for three-phase input power unless they are connected to corner-grounded or ungrounded facility power.
Shunt Connections
IMPORTANT 2198-RP xxx shunt type.
regenerative bus supplies do not support passive shunts. Make active shunt connections to the 2198-RP xxx regenerative bus supply at the active shunt (RC) connector or the external DC-bus studs on accessory modules, depending on the
Figure 31 - RC Connector Wiring
2198-RP xxx
Regenerative Bus Supply
Top View
Active Shunt
(RC) Connector Plug
1
2
Table 44 - Active Shunt (RC) Connector Specifications
Regenerative Bus Supply
Cat. No.
Pin Signal
Continuous
(1) max
Current,
2198-RP xxx
RC-1
RC-2
DC–
DC+
10 A
(1) This connector applies to only Powerohm PKB xxx
xxx
active shunts rated at 7 kW or less.
Recommended Wire Size mm
2
(AWG)
2.5…6
(14…10)
Strip Length mm (in.)
12.0 (0.47)
Torque Value
N•m (lb•in)
0.5…0.6
(4.4…5.3)
IMPORTANT Due to the 10 A connector current rating, connections to the RC connector are limited to only Powerohm PKB rated at 7 kW or less. All other PKB capacitor module.
and PWB xxx
xxx
active shunts
active shunt connections must be made to the 2198-CAPMOD-2240
You can make active shunt connections in drive systems that include the regenerative bus supply and Powerohm PKB xxx
-800 or
PWB xxx
-800 active shunts at the external DC-bus studs on accessory modules.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 53
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
Accessory modules are equipped with spacers that slide onto the M8 studs. When the system configuration includes external DC-bus and active shunt connections, external DC-bus connections are made below the spacer and active shunt connections are made above the spacer.
Figure 32 - Active Shunt Connections
Spacer
Active Shunt
Lug Connections
(above spacer)
DC-bus
Lug Connections and
Flexible Bus-bars
(2)
(below spacer)
2198-DCBUSCOND-RP312
2198-CAPMOD-2240 or
2198-CAPMOD-DCBUS-IO
(1)
Accessory Modules
(2198-CAPMOD-2240 capacitor module is shown)
(1) An external active shunt can be wired to any of the accessory modules. See Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on mounting and accessory module example configurations. The 2198-CAPMOD-2240 capacitor module is preferred because it provides additional system capacitance.
(2) Position flexible bus-bars (when two accessory modules are used) below the DC-bus lug connections. The flexible bus-bars are used to parallel the extended DC-bus with another accessory module in 208 A systems (not required when only one accessory module is used in 104 A systems). Flexible bus-bars are included with 2198-CAPMOD-DCBUS-IO extension modules or you can order 2198-KITCON-CAPMOD2240 or 2198-KITCON-DCBUSCOND replacement kits.
For compatible Powerohm active shunts paired with the 2198-RP xxx
regenerative bus supply, refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
ATTENTION: To avoid damage to the Kinetix 5700 drive system, wire the active shunt thermal switch to a digital input on the power supply and configure the Shunt Thermal Switch OK function in the Logix Designer application.
Figure 33 - 2198-RP xxx Bus Supply with External Active Shunt (built-in brake resistor)
2198-RP xxx
Regenerative Bus Supply
2198xxxx
-ERS
Inverter x
2198-CAPMOD-2240
Capacitor Module
4.6 m (15 ft) Maximum Cable Length
DC+
External DC-bus
DC+
DC–
Powerohm
Bulletin PKB xxx-xxx
Active Shunt Module
Resistor
DC–
3
4
Fault Contact
Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
9
10
(2)
120V AC
(1) Configure any available digital input as Shunt Thermal Switch OK. See the Kinetix 5700 Servo Drives User Manual, publication
2198-UM002 , for more information on configuring digital inputs.
(2) Powerohm PKB050 and PKB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
See Knowledgebase document 1082776 for more information on wiring to these Powerohm Bulletin PKB xxx
active shunts.
54 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
Figure 34 - 2198-RP xxx Bus Supply with External Active Shunt (external brake resistor)
2198-RP xxx
Regenerative
Bus Supply
2198xxxx
-ERS x
Inverter
2198-CAPMOD-2240
Capacitor Module
Powerohm
Bulletin PWB xxx-xxx
Active Shunt Module
Powerohm
External Passive
Shunt Module
DC+
External DC-bus
DC+
DC–
DC+
DC–
R1
R2
Resistor
DC–
4.6 m (15 ft)
Maximum Cable Length
9.1 m (30 ft)
Maximum Cable Length
3
4
Fault Contact
9
10
(2)
120V AC
TS
TS
Thermal
Switch Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
(1) Configure any available digital input as Shunt Thermal Switch OK. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on configuring digital inputs.
(2) Powerohm PWB050 and PWB050-800 shunts require 120V AC between pins 9 and 10 to supply power to the cooling fans.
See Knowledgebase document 1082777 for more information on wiring to these Powerohm Bulletin PWB xxx
active shunts.
Refer to the Powerohm documentation included with your Bulletin PKB or PWB shunt module to install, wire, and configure the module.
• To avoid nuisance thermal overload trips, configure Bulletin PKB and PWB active-shunt modules to the highest shunt turn-on voltage setting. The recommended setting for Line Voltage Level Jumper is JP5.
• Configure Bulletin PKB and PWB active-shunt modules in Internal (automatic) mode. Unless an external enable signal is provided, configure the Brake Enable Jumper in Internal (automatic) mode (JP6 is in the downward position).
Bus Supply Ground Jumper Setting
The 2198-RP xxx
regenerative bus supply has a factory-installed ground screw for grounded-wye power distribution. The following table summarizes the ground screw/jumper settings for the 2198-RP xxx
regenerative bus supply.
Table 45 - Ground Jumper Settings for the Regenerative Bus Supply
Ground Configuration
2198-RP xxx
Regenerative Bus Supply
• Grounded (wye)
• Corner-grounded with isolation transformer
• Ungrounded with isolation transformer
Impedance grounded
Ground jumper installed (default setting)
Remove ground jumper
(1)
(1) When the regenerative bus supply ground jumper is removed, it can be permanently stored in threaded holes at the bottom of the chassis.
IMPORTANT If you have grounded-wye power distribution in your facility, or corner-grounded or ungrounded power with an isolation transformer, do not remove the ground jumper from the regenerative bus supply. Remove the ground jumper when using impedance-grounded power.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 55
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
Converter OK Signal
The converter OK circuitry of the Kinetix 5700 regenerative bus supply is a relay-driven contact that provides a 24V signal to non-
Kinetix 5700 inverters that they can draw power from the regenerative power supply and that the power supply is not faulted.
Figure 35 - Converter OK Relay Circuit
24V PWR
Regenerative
Bus Supply
Internally
Controlled
Relay
Resettable Fuse
24V COM
OK+
OK–
The CONV OK signal of the Kinetix 5700 regenerative bus supply (contactor enable connector) can be connected/interlocked to the following
Kinetix and PowerFlex drive inputs to indicate that they can pull power from the bus:
• Regen OK input of Kinetix 7000 drives
• Regeneration OK input of Kinetix 6200/6500 drives
• Enable input of Kinetix 6000 drives
• Regeneration OK of PowerFlex 750-series drives
Figure 36 - Converter OK Connected/Interlocked to Drive Input
Di C
Di 0
PowerFlex 750-Series Drives
(1)
24VCOM
Regeneration OK
IOD-3
IOD-2
Kinetix 6000 Drives
24VCOM
Enable
IOD-40
IOD-41
Kinetix 6200/6500 Drives
24VCOM
Regeneration OK
GPIO-7
GPIO-8
Kinetix 7000 Drives
Regen_OK+
Regen_OK–
2198-RP xxx
Regenerative Bus Supply
OK+
OK–
CONV OK+
CONV OK–
CONT EN+
CONT EN–
Contactor Enable
(CED) Connector
(1) The Regeneration OK input is available only if the Integrated Motion feature of the PowerFlex 750-Series drive is being used. If Integrated Motion is not being used, the Precharge digital input can be used instead.
For PowerFlex drives, the Regeneration OK Input functionality is available for PowerFlex 755 drives only with Integrated Motion applications.
When in motion and the drive detects the Regeneration OK Input transition to an inactive state, the drive generates the Regeneration Powersupply Failure exception and coasts to a stop. The exception cannot be configured and is assigned Stop drive only.
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the Converter OK circuitry.
56 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Regenerative Bus Supply Configurations With Active Shunt Chapter 5
Contactor Enable Relay
The contactor-enable circuitry includes a relay-driven contact within the 2198-RP xxx
DC-bus power supply. The relay protects the
Kinetix 5700 drive system in the event of overloads or other fault conditions.
Figure 37 - Contactor-enable Control String
Kinetix 5700
2198-RP xxx
Regenerative Bus Supply
Kinetix 6 x 00
2094-BC xx -M xx -S
Integrated Axis Module
* Indicates User Supplied Component
Kinetix 7000
2099-BM xx -S
Servo Drive
24V AC/DC
50/60 Hz
CR1 *
CR1 *
M1 *
STOP *
START *
CR1 *
CONT EN+ CONT EN– CONT EN+ CONT EN–
GPR2+ GPR2–
An AC three-phase mains contactor must be wired in series between the branch circuit protection and the power supply. In addition, the AC three-phase contactor control string must be wired in series with the contactor-enable relay at the contactor-enable terminals.
PowerFlex 750-Series drives are not required to include a contactor-enable control string and they do not have a dedicated contactor enable relay. Although not required, if leveraging Integrated Motion with a PowerFlex 755 drive, we recommend that you configure a digital output from the drive as Contactor Enable and include it in the contactor enable control string.
A Contactor Enable output can be configured in the PowerFlex 755 drive in integrated motion only. The operation of this output is tied to fault processing in the drive. The drive de-energizes the Contactor Enable output when an exception causes the axis to go to the Shutdown state.
This configuration is only valid when an auxiliary power supply is used for control power with frames 1…7 drives.
ATTENTION: Wiring the contactor enable relay is required for Kinetix 5700, Kinetix 6 x
00, and Kinetix 7000 drive systems to help prevent personal injury or damage to Kinetix drive modules. Wire the contactor enable relay into your control string so that:
• three-phase power is removed and the power supply or regenerative bus supply is protected under various fault conditions
• three-phase power is never applied to the Kinetix 5700 drive system before control power is applied.
Figure 38 - Contactor-enable Relay Circuit
CONT EN+
Normally
Open
Relay
CONT EN-
Power Supply
Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on the contactor-enable circuitry.
ATTENTION: For Kinetix 6000 (400V-class) and Kinetix 6200/6500 drive in common-bus configurations, the contactor enable connections for leader and follower drives must be wired in series to the control string.
A contactor or other device that routinely disconnects and reapplies the AC line to the bus supply can cause drive hardware damage. If an input device is used, operation must not exceed two cycles per minute (maximum) or damage can occur to the precharge circuit.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 57
Chapter 5 Regenerative Bus Supply Configurations With Active Shunt
System Sizing
These limitations apply to systems supplied by 2198-RP xxx
regenerative bus supplies:
• The sum of the inverter motor-power cable lengths for all inverters on the same DC bus-sharing group must not exceed 1200 m (3937 ft) to comply with IEC 61800-3 (category C3) requirements when used with 2198-DBR xx
-F line filters. 2198-DB xx
-F line filters have a total motor cable length limit of 400 m (1312 ft). See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional motor power cable-length limitations.
• The total system capacitance limit is based on the power supply catalog number. DC-bus groups must not exceed the limits as defined in
Kinetix and PowerFlex Drive Specifications on page 59
.
• If using the 24V DC shared-bus connection system, add another 24V power supply when control input power to a cluster of drive modules exceeds 40 A.
• The Kinetix 5700 system can have multiple drive clusters in a single DC-bus group. See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on extended clusters.
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for additional information on system sizing guidelines.
The motor required for a particular application determines the drive required for full motor performance. For best results, use Motion
Analyzer system sizing and selection tool, available at https://motionanalyzer.rockwellautomation.com/ .
Capacitance Sizing
Total system capacitance is the sum of all internal capacitance values from each of the drive modules (AC drives, single-axis inverters, dualaxis inverters, power supplies, and capacitor modules) in the same DC-bus group.
The total system capacitance must be less than the maximum supported DC-bus capacitance value of the power supply (refer to
PowerFlex Drive Specifications on page 59
).
IMPORTANT If your total system capacitance value exceeds the maximum supported capacitance value of the regenerative bus supply, perform one of the following:
• Increase the size of the 2198-RP xxx
regenerative bus supply
• Decrease the total system capacitance by removing inverters or capacitor modules from the DC-bus group
• Separate clusters into multiple DC-bus groups
External bus capacitance is the total system capacitance minus the power supply capacitance. The external bus capacitance must be entered into the Logix Designer application for a regenerative power supply to maintain proper control.
All drives have a DC-bus capacitance that is proportional to their power ratings. When used in a common DC-bus configuration, these capacitors are directly connected in parallel. This connection results in the DC-bus ripple being shared proportional to the power rating of the drive. When the ratio of the capacitance to the drive-rated current is consistent, it provides the best DC-bus ripple sharing.
For 400/480V AC, the target ratio is 40 µF/A ±10% or greater. For all drives supported in this publication, the target ratio is met when a capacitor module is used to extend the DC-bus, proper DC-bus cable length guidelines are followed, and low-inductance DC cable is used.
on
Circuit Protection
Do not daisy chain drives to share DC-bus fusing. Configure the shared DC-bus in a star configuration to enable proper fusing. Use fast semiconductor fuses in the DC links to minimize destructive energy in the event of a part or control malfunction. Size fuses to handle large peak currents at the end of precharge.
• See
Kinetix and PowerFlex Drive Specifications on page 59
for the recommended common DC-bus circuit protection devices.
• See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for recommended AC input circuit protection for the Bulletin
2198 power supply.
58 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Appendix
A
Kinetix and PowerFlex Drive Specifications
This appendix provides Kinetix® and PowerFlex® drive specifications and includes DC input currents, recommended DC input fuses
(manufacturer catalog numbers), and internal drive DC-bus capacitance.
Kinetix 5700 Drive Specifications
The total system capacitance must be less than the maximum supported DC-bus capacitance value of the power supply.
Table 46 - Kinetix 5700 Power Supply Capacitance
Power Supply
Single DC-bus Power Supply
Multiple DC-bus Power Supplies
Regenerative Bus Supplies
Power Supply
Cat. No.
2198-P031
2198-P070
2198-P141
2198-P208
2198-P208 x 2
2198-P208 x 3
2198-RP088
2198-RP200
2198-RP263
2198-RP312
Supported Capacitance, max
µF
8,000
13,000
26,000
39,000
9,000
15,000
25,000
Internal Capacitance
µF
585
780
1640
2050
4100
6150
940
2460
4510
5740
207
542
994
1265
Capacitive Energy Absorption
J
129
172
362
453
906
1359
Table 47 - Kinetix 5700 Single-axis Inverter Power Specifications
Attribute
DC input current @ 458…747V DC
2198-S086-ERS3
2198-S086-ERS4
45.7 A
DC
560 µF Internal Capacitance
(1) UL tested to 175.0 A
DC
.
Table 48 - Kinetix 5700 Dual-axis Inverter Power Specifications
2198-S130-ERS3
2198-S130-ERS4
69.0 A
DC
840 µF
2198-S160-ERS3
2198-S160-ERS4
92.3 A
DC
1120 µF
Attribute
DC input current @ 458…747V DC
Internal Capacitance
Per Axis
(1)
X
(1) These attributes apply to both of the axes in each dual-axis inverter.
Table 49 - DC-bus Power Supply Specifications
2198-D006-ERS3
2198-D006-ERS4
2.7 A
DC
165 µF
Attribute
AC input voltage
AC input frequency
Main AC input current
(1)
324…528V (rms) three-phase
Max inrush (0-pk)
11.2A
33.0 A
27.0 A
33.0 A
2198-D012-ERS3
2198-D012-ERS4
5.3 A
DC
2198-P031 2198-P070
324…528V rms, three-phase (480V nom)
47…63 Hz
2198-D020-ERS3
2198-D020-ERS4
8.5 A
DC
330 µF
2198-P141
49.6 A
33.0 A
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
2198-S263-ERS3
2198-S263-ERS4
164.0 A
DC
2050 µF
2198-D032-ERS3
2198-D032-ERS4
13.7 A
DC
390 µF
73.1 A
33.0 A
2198-S312-ERS3
2198-S312-ERS4
207.0 A
DC
(1)
2050 µF
2198-D057-ERS3
2198-D057-ERS4
24.5 A
DC
705 µF
2198-P208
59
Appendix A Kinetix and PowerFlex Drive Specifications
Table 49 - DC-bus Power Supply Specifications
Attribute
Peak AC input current
324…528V (rms) three-phase
Line loss ride through
Control power DC input voltage
Control power DC input current
(2)
Nominal bus output voltage
Continuous output current to bus
Three-phase
Peak output current to bus
Three-phase
Peak output current duration
(3)
Continuous output power to bus
Nom (480V rms, three-phase)
Peak output power to bus
Nom (480V rms, three-phase)
Bus overvoltage - 480V, nom AC input
Internal shunt resistance
Internal shunt power
Shunt on
Shunt off
Efficiency
Internal Capacitance
Capacitive energy absorption
Short-circuit current rating
2198-P031
33.4 A
20 ms
24V DC ±10%
0.8 A
DC
458…747V DC
10.5 A
31.6 A
1.0 s
7.0 kW
21.0 kW
832V DC
37.5 Ω
75 W
775V plus 30V x bus regulator capacity/utilization
(4)
765V plus 30V x bus regulator capacity/utilization
99%
585 µF
129 J
DC
DC
200,000 A (rms) symmetrical
2198-P070
74.3 A
25.5 A
70.3 A
1.0 s
17.0 kW
46.0 kW
780 µF
172 J
DC
DC
2198-P141
148.7 A
1.9 A
1.0 s
DC
46.9 A
93.0 kW
13.5 Ω
200 W
1640 µF
362 J
DC
140.8 A
31.0 kW
DC
2198-P208
219.2 A
69.2 A
207.6 A
0.1 s
DC
46.0 kW
DC
138.0 kW
2050 µF
453 J
(1) All modules are limited to 1 power cycle per minute.
(2) For current values when motors include a holding brake and additional information, refer to Kinetix Servo Drives Specifications Technical Data, publication KNX-TD003 .
(3) Peak output current duration with 10% duty cycle.
(4) The shunt on and shunt off voltages increase during periods of shunting activity to promote sharing of shunt power in multi-axis configurations. Shunt utilization is equivalent to the
BusRegulatorCapacity tag in the Logix Designer application.
60 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Kinetix and PowerFlex Drive Specifications Appendix A
Table 50 - Regenerative Bus Supply Specifications
Attribute
AC input voltage
(1)
AC input frequency
Main AC input current
(2)
324…506V (rms) three-phase
Max inrush (0-pk)
Peak AC input current
324…506V (rms) three-phase
Line loss ride through
Control power DC input voltage
Control power DC input current
(3)
Nominal bus output voltage
Continuous output current to bus
Peak output current to bus
Peak output current duration
(4)
Continuous output power to bus
Nom (480V rms, three-phase)
Peak output power to bus
Nom (480V rms, three-phase)
Bus overvoltage - 480V, nom AC input
Internal shunt resistance
Efficiency
Internal Capacitance
(5)
Capacitive energy absorption
Short-circuit current rating
2198-RP088
47…63 Hz
30.0 A
76.0 A
75.0 A
20 ms
24V DC ±10%
4.3 A
DC
458…747V DC
35.3 A
DC
88.0 A
DC
1.0 s/3.0 s
24.0 kW
2198-RP200
324…506V rms, three-phase (480V nom)
85.0 A
176.0 A
170.0 A
5.4 A
DC
100.0 A
200.0 A
67.0 kW
DC
DC
60.0 kW
832V DC
–
98%
940 µF
207 J
200,000 A (rms) symmetrical
135.8 kW
2460 µF
542 J
2198-RP263
150.0 A
362.0 A
225.0 A
9.1 A
DC
176.4 A
263.0 A
DC
119.0 kW
179.7 kW
–
4510 µF
994 J
DC
2198-RP312
192.0 A
362.0 A
288.9 A
207.0 A
312.0 A
DC
DC
140.0 kW
211.4 kW
5740 µF
1265 J
(1) Applies when DC-bus voltage regulation is enabled. If DC-bus voltage regulation is not enabled, the input voltage range is 324….528V AC. For more information on these two modes of operation, see the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
(2) All modules are limited to 1 power cycle per minute.
(3) For current values when motors include a holding brake and additional information, refer to Kinetix Servo Drives Specifications Technical Data, publication KNX-TD003 .
(4) 1.0 second peak output current duration with 10% duty cycle.
3.0 second peak output current duration with 5% duty cycle.
(5) The 2198-RP xxx
regenerative bus supply has no internal shunt resistor.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 61
Appendix A Kinetix and PowerFlex Drive Specifications
Kinetix 6000 Drive Specifications
When using a non-Bulletin 2094 common-bus leader drive, DC-bus fuses are required in both lines of the DC-bus. For example, between the common-bus leader drive and follower IAM module. Base these fuse ratings on the DC output current of the common-bus leader drive. When using more than one follower IAM module, install fuses in both lines of the DC-bus. For example, between the non-Bulletin 2094 common-bus leader and the terminal block, and between the DC-bus terminal block and each follower IAM module.
The 2094-BC xx
-M xx
-S and 2094-BM xx
-S drive modules use internal solid-state motor short-circuit protection and, when protected by suitable branch circuit protection, are rated for use on a circuit capable of delivering up to 200,000 A (fuses) and 65,000 A (circuit breakers).
Table 51 - DC-bus Circuit-protection Specifications
DC-bus Power
Mersen Fuse
(1)
IAM Module
Cat. No.
Bussmann Fuse
2094-BC01-MP5-S
2094-BC01-M01-S
2094-BC02-M02-S
2094-BC04-M03-S
2094-BC07-M05-S
FWJ-20A14F
FWJ-40A
FWJ-70A
FWJ-125A
(1) Mersen fuses were formerly known as Ferraz Shawmut.
DCT20-2
A70QS40-4
A70QS70-4
A70QS125-4
Table 52 - IAM Module (converter, 400V-class) Power Specifications (series A, B, and C)
2094-BC02-M02-S Attribute
AC input voltage
DC input voltage (common bus follower)
DC input current (common-bus follower)
Continuous power output to bus
Converter capacitance
2094-BC01-MP5-S 2094-BC01-M01-S
324…528V rms three-phase (360…480V nom)
458…747V DC
9.0 A
6 kW
110
F
22.6 A
15 kW
220
F
2094-BC04-M03-S
41.5 A
27.6 kW
940
F
2094-BC07-M05-S
67.7 A
45 kW
1410
F
Table 53 - AM Module (inverter, 400V-class) Power Specifications (series A, B, and C)
Attribute
Capacitance
2094-BMP5-M
(2094-BC01-MP5-M)
75
F
2094-BM01-M
(2094-BC01-M01-M)
150
F
2094-BM02-M
(2094-BC02-M02-M)
270
F
2094-BM03-M
(2094-BC04-M03-M)
840
F
2094-BM05-M
(2094-BC07-M05-M)
1175
F
62 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Kinetix and PowerFlex Drive Specifications Appendix A
Kinetix 6200 and Kinetix 6500 Drive Specifications
When using a non-Bulletin 2094 common-bus leader drive, DC-bus fuses are required in both lines of the DC-bus. For example, between the common-bus leader drive and follower IAM module. Base these fuse ratings on the DC output current of the common-bus leader drive. When using more than one follower IAM module, install fuses in both lines of the DC-bus. For example, between the non-Bulletin 2094 common-bus leader and the terminal block, and between the DC-bus terminal block and each follower IAM module.
The 2094-BC xx
-M xx
-M and 2094-BM xx
-M drive modules use internal solid-state motor short-circuit protection and, when protected by suitable branch circuit protection, are rated for use on a circuit capable of delivering up to 200,000 A (fuses) and 65,000 A (circuit breakers).
Table 54 - DC-bus Circuit-protection Specifications
DC-bus Power
Mersen Fuse
(1)
IAM Power Module
Cat. No.
Bussmann Fuse
2094-BC01-MP5-M
2094-BC01-M01-M
2094-BC02-M02-M
2094-BC04-M03-M
2094-BC07-M05-M
FWJ-20A14F
FWJ-40A
FWJ-70A
FWJ-125A
(1) Mersen fuses were formerly known as Ferraz Shawmut.
DCT20-2
A70QS40-4
A70QS70-4
A70QS125-4
Table 55 - IAM Module (converter, 400V-class) Power Specifications
Attribute
AC input voltage
2094-BC01-MP5-M 2094-BC01-M01-M
324…528V rms three-phase (360…480V nom)
DC input voltage (common bus follower) 458…747V DC
DC input current (common-bus follower) 9.0 A
Continuous power output to bus
Converter capacitance
6 kW
110
F
Table 56 - AM Module (inverter, 400V-class) Power Specifications
Attribute
Capacitance
2094-BMP5-M
(2094-BC01-MP5-M)
75
F
2094-BM01-M
(2094-BC01-M01-M)
150
F
2094-BC02-M02-M
22.6 A
15 kW
220
F
2094-BM02-M
(2094-BC02-M02-M)
270
F
2094-BC04-M03-M
41.5 A
27.6 kW
940
F
2094-BM03-M
(2094-BC04-M03-M)
840
F
2094-BC07-M05-M
67.7 A
45 kW
1410
F
2094-BM05-M
(2094-BC07-M05-M)
1175
F
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 63
Appendix A Kinetix and PowerFlex Drive Specifications
Kinetix 7000 Drive Specifications
The following fuse examples and short-circuit current ratings are recommended for use with the 2099-BM xx
-S drives when the line interface module (LIM) is not used.
Table 57 - Ferraz Shawmut Fuse Recommendations
Drive Cat. No.
2099-BM06-S
2099-BM07-S
2099-BM08-S
2099-BM09-S
2099-BM10-S
2099-BM11-S
2099-BM12-S
Drive Current
Rating (ADC)
42.9
55.7
69.7
105
137
204
281
Recommended Fuse
Fuse Current
Rating
HSJ80
HSJ90
HSJ100
HSJ175
HSJ200
HSJ400
HSJ400
80
90
100
175
200
400
400 i²t (A²sec)
Pre-arc
1600
2300
2700
8000
14000
63000
63000
Clearing @ 600V AC, max
15000
21000
23000
60000
92000
450000
450000
Peak Let-through Current
@ 100 kA rms
7000 A
7400 A
7700 A
12000 A
13000 A
21000 A
21000 A
Table 58 - Bussmann Fuse Recommendations
Drive Cat. No.
2099-BM06-S
2099-BM07-S
2099-BM08-S
2099-BM09-S
2099-BM10-S
2099-BM11-S
2099-BM12-S
Drive Current
Rating (ADC)
42.9
55.7
69.7
105
137
204
281 i²t (A²sec)
Recommended Fuse Fuse Current Rating
Pre-arc
FWJ-80A
FWJ-100A
FWJ-125A
FWJ-175A
FWJ-200A
FWJ-500A
FWJ-500A
80
100
125
175
200
500
500
1550
2800
4800
7500
11700
39500
39500
Clearing @ 600V AC, max
9700
Peak Let-through Current
@ 100 kA rms
6300 A
17500
35000
65000
80000
8000 A
10000 A
12000 A
13000 A
329000
329000
21000 A
21000 A
Table 59 - Kinetix 7000 Drive Power Specifications
Attribute
AC input voltage
DC input voltage
DC input current
Continuous power output, nom
Total capacitance
(1)
Short-circuit current rating
2099-BM06-S 2099-BM07-S 2099-BM08-S 2099-BM09-S 2099-BM10-S 2099-BM11-S 2099-BM12-S
342…528V AC rms three-phase (380…480V nom)
450…750V DC
42.9 A
22 kW
1800
F
55.7 A
30 kW
2400
F
200,000 A (rms) symmetrical
69.7 A
37 kW
3000
F
105 A
56 kW
4500
F
137 A
75 kW
6000
F
204 A
112 kW
8400
F
281 A
149 kW
8400
F
(1) If DC input is supplied to 2099-BM09-S, 2099-BM10-S, or 2099-BM11-S drives, the precharge capability must be provided at the system level. Disconnect switches must not be used between the input of the drive and a common DC-bus without the use of an external precharge device.
64 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Kinetix and PowerFlex Drive Specifications Appendix A
PowerFlex 750-Series Drive Specifications
The following fuse examples are recommended for use with the 540V DC and 650V DC input PowerFlex 20F and 20G AC drives,
Frame sizes 1…6.
Table 60 - 540V DC Input Fuses, Frames 1…6
Non-time Delay Fuse
Drive Cat. No.
20F and 20G
(1) kW Rating DC Input Rating
Drive DC Bus
Capacitance
µF DC+
Quantity
DC–
Amps Fuse Cat. No.
C2P1
C2P1
C3P5
C3P5
C5P0
C5P0
C8P7
C8P7
C011
C011
C015
C015
C022
C030
C037
C043
C060
C072
C072
C085
–
22
–
30
–
15
–
11
–
18.5
30
–
37
–
5.5
–
7.5
–
4
–
5.5
–
5.5
–
4
–
2.2
–
1.5
–
1.5
–
2.2
HD
–
0.37
–
0.75
–
0.75
–
67.1
48.1
82.4
67.1
82.4
24.6
41.4
33.6
48.1
41.4
17.0
12.6
24.6
17.0
33.6
9.3
12.6
12.6
17.0
12.6
67.1
97.3
82.4
9.3
5.3
9.3
9.3
12.6
3.7
5.3
3.7
5.3
5.3
2.1
2.1
3.7
2.1
3.7
Amps
2.1
1.3
36.2
26.0
44.5
36.2
44.5
13.3
22.3
18.1
26.0
22.3
9.2
6.8
13.3
9.2
18.1
5.0
6.8
6.8
9.2
6.8
36.2
52.5
44.5
5.0
2.9
5.0
5.0
6.8
2.0
2.9
2.0
2.9
2.9
1.1
1.1
2.0
1.1
2.0
kW
1.1
0.7
2
2
3
3
3
4
4
5
5
–
45
–
37
–
30
–
37
–
18.5
–
22
–
11
–
7.5
–
15
1
1
1
2
2
–
5.5
–
7.5
–
4
–
4
–
5.5
1
1
1
Frame
Size
ND
0.75
–
2
0.75
–
1.5
–
1.5
2
2
–
2.2
–
2.2
–
110
705
165
705
280
705
470
705
560
705
680
705
1020
1200
1500
1800
2400
3000
3600
3600 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Bussman JKS-6
(2)
Bussman JKS-4
Bussman JKS-6
Bussman JKS-6
Bussman JKS-8
Bussman JKS-6
Bussman JKS-8
Bussman JKS-8
Bussman JKS-10
Bussman JKS-8
Bussman JKS-10
Bussman JKS-10
Mersen HSJ15
(3)
Mersen HSJ10
Mersen HSJ40
Mersen HSJ50
Mersen HSJ40
Mersen HSJ50
Mersen HSJ150
100
90
125
100
125
40
70
50
90
70
100
150
125
25
20
40
25
50
15
20
20
25
20
15
15
15
10
20
8
10
8
10
10
8
6
6
6
8
6
4
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 65
Appendix A Kinetix and PowerFlex Drive Specifications
Table 60 - 540V DC Input Fuses, Frames 1…6 (continued)
Drive Cat. No.
20F and 20G
C104
C104
C140
C170
C205
C260
(1)
Frame
Size
ND
55
5
6
6
6
6
6
–
55
–
75
–
90
–
110
–
132
– kW Rating
HD
–
45
–
45
–
55
–
75
–
90
–
110
DC Input Rating
Amps
120.2
97.3
120.2
97.3
160.3
120.2
194.6
160.3
234.7
194.6
297.7
234.7
kW
64.9
52.5
64.9
52.5
86.5
64.9
105.1
86.5
126.7
105.1
160.7
126.7
Drive DC Bus
Capacitance
µF
4500
4600
4600
9200
9200
9200 1
1
1
1
1
1
DC+
Quantity
1
1
1
1
1
1
DC–
Non-time Delay Fuse
Amps
175
150
175
150
250
175
350
250
350
350
450
350
Fuse Cat. No.
Mersen HSJ175
Mersen HSJ150
Mersen HSJ175
Mersen HSJ150
Mersen HSJ175
Mersen HSJ350
Mersen HSJ350
Mersen HSJ350
Mersen HSJ450
Mersen HSJ350
(1) Drive input type (position 5 of catalog number) = 1 (AC input with precharge, includes DC terminals) or 4 (DC input with precharge).
(2) See
Fuse Certification and Test Data on page 68
for fuse self-certification and test data for Bussmann 170M and JKS fuses that are recommended for the DC-bus fusing.
(3) A test program was developed to confirm that the HSJ (High Speed J) fuses meet or exceed the requirements set forth by Rockwell Automation for the fuses on the common DC-bus for all
Allen-Bradley® architecture, component, and legacy drives. The criteria for acceptance was:
• 600V AC rectified, 810V DC average, fuses located at (+) and (-) leg. Short circuit test at 65 kA.
• Time constant minimum 3 milliseconds (maximum 15 milliseconds).
• No over-load protection required.
• Let-through must be less than rating of the conductors.
This testing is listed in UL file E2137 Vol2 Sec 31 page 1 and in CSA report 1662646.
Table 61 - 650V DC Input Fuses, Frames 1…6
HP Rating DC Input Rating Non-time Delay Fuse
Drive Cat. No.
20F and 20G
(1)
Frame
Size
ND HD Amps kW
Drive DC Bus
Capacitance
µF
Amps Fuse Cat. No.
DC+
Quantity
DC–
D2P1
D2P1
D3P4
D3P4
D5P0
D5P0
D8P0
D011
D011
D014
D014
1
1
1
1
1
1
2
2
2
2
2
5
–
3
–
7.5
–
3
–
2
–
–
7.5
–
7.5
1
–
1
–
2
–
0.5
–
–
7.5
–
7.5
–
3
–
3
–
5
10
–
10
–
–
2
–
2
–
1
1
–
2.9
7.2
5.3
7.2
7.2
2.9
2.0
2.9
2.9
5.3
9.6
7.2
9.5
7.2
1.2
2.0
1.2
2.0
2.0
1.2
0.72
1.2
4.5
11.1
8.1
11.1
11.1
4.5
3.0
4.5
4.5
8.1
14.7
11.1
14.7
11.1
1.9
3.0
1.9
3.0
3.0
1.9
1.1
1.9
110
705
165
705
280
705
470
560
705
680
705
10
20
15
20
20
10
10
10
6
15
30
20
30
20
6
6
6
6
6
6
4
6
Bussman JKS-6
(2)
Bussman JKS-10
Bussman JKS-10
Bussman JKS-10
Mersen HSJ15
(3)
Bussman JKS-10
Mersen HSJ15
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
66 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Kinetix and PowerFlex Drive Specifications Appendix A
Table 61 - 650V DC Input Fuses, Frames 1…6 (continued)
Drive Cat. No.
20F and 20G
(1)
Frame
Size
ND
HP Rating
HD Amps
DC Input Rating kW
Drive DC Bus
Capacitance
µF
Amps
Non-time Delay Fuse
Fuse Cat. No.
DC+
Quantity
DC–
D022
D027
D034
D040
D052
D065
D065
D077
D096
D096
D125
D156
D186
D248
2
3
3
3
4
4
5
5
5
6
6
6
6
6
15
–
20
–
25
–
30
–
40
–
50
–
50
–
60
–
75
–
75
–
100
–
125
–
150
–
200
–
–
10
–
15
–
20
–
25
–
30
–
40
–
40
–
50
–
60
–
60
–
75
–
100
–
125
–
150
23.3
14.7
28.9
23.3
36.4
28.9
42.9
36.4
55.7
42.9
69.7
55.7
69.7
55.7
84.5
69.7
105.3
84.5
105.3
84.5
137.1
105.3
171.2
137.1
204.1
171.2
272.1
204.1
15.1
9.5
18.8
15.1
23.6
18.8
27.8
23.6
36.1
27.8
45.1
36.1
45.3
36.2
54.7
45.1
68.3
54.7
68.4
54.9
88.9
68.3
110.9
88.9
132.2
110.9
176.3
132.2
1020
1200
1500
1800
2400
3000
3600
3600
4500
4600
4600
9200
9200
9200
40
30
50
40
60
50
80
60
90
80
100
90
100
90
150
100
175
150
175
150
200
175
300
200
400
300
400
400
Mersen HSJ100
Mersen HSJ100
Mersen HSJ100
Mersen HSJ400
Mersen HSJ400
Mersen HSJ400
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(1) Drive input type (position 5 of catalog number) = 1 (AC input with precharge, includes DC terminals) or 4 (DC input with precharge).
(2) See
Fuse Certification and Test Data on page 68
for fuse self-certification and test data for Bussmann 170M and JKS fuses that are recommended for the DC-bus fusing.
(3) A test program was developed to confirm that the HSJ (High Speed J) fuses meet or exceed the requirements set forth by Rockwell Automation for the fuses on the common DC-bus for all
Allen-Bradley architecture, component, and legacy drives. The criteria for acceptance was:
• 600V AC rectified, 810V DC average, fuses located at (+) and (-) leg. Short circuit test at 65 kA.
• Time constant minimum 3 milliseconds (maximum 15 milliseconds).
• No over-load protection required.
• Let-through must be less than rating of the conductors.
This testing is listed in UL file E2137 Vol2 Sec 31 page 1 and in CSA report 1662646.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 67
Appendix A Kinetix and PowerFlex Drive Specifications
Fuse Certification and Test Data
The following are copies of self-certification letters and test data for JKS and 170M fuses that are recommended in the previous tables for
PowerFlex 750-Series drives (Frames 1…6). Configuration A indicates one fuse in the (+) leg and one fuse in the (–) leg of the DC-bus.
JKS Fuses
Cooper Bussmann
P. O. Box 14460
St. Louis, MO 63178-4460
January 25, 2002
Sr. Project Engineer, Rockwell Automation
6400 West Enterprise Drive
P.O. Box 760
Mequon, WI 53092
Subject: DC Testing for JKS Fuses
Dear Mr.
At the request of Rockwell Automation, Bussmann has completed the DC testing for the JKS fuses and is pleased to present the attached information indicating successful 'Self-Certification DC Rating' on all subject fuses. Bussmann tested fuses to the following parameters specified by Rockwell Automation:
• Short Circuit Current = 65 kA
• Voltage = 810V DC
• Time Constant ≥0.4 ms
Additional tests were performed for acceptability:
• Short Circuit Current = 30 times fuse amperage
• Voltage = 810V DC
• Time Constant ≥0.4 ms
The attached table identifies the fuses tested, the actual circuit parameters and the circuit configuration. In the attached table, the
Interrupting Amps column specifies the fuses minimum and maximum amps that the fuse will safely clear at 810V DC.
Circuit Configuration A
Fuse Fuse
By way of this correspondence, Cooper Bussmann self-certifies the preceding fuses in end-user applications to the preceding parameters and the attached data sheet.
Should you have any questions regarding this correspondence, please contact me at the listed address and numbers.
Regards,
Strategic OEM Accounts Manager
Cooper Bussmann
68 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Kinetix and PowerFlex Drive Specifications Appendix A
Table 62 - Cooper Bussmann JKS, DC Fuse Test for Rockwell Automation
Fuse
JKS-(3A…15A)
JKS-(3A…15A)
JKS-(20A…30A)
JKS-(20A…30A)
JKS-(35A…60A)
JKS-(35A…60A)
JKS-(70A…100A)
JKS-(70A…100A)
JKS-(110A…200A)
JKS-(110A…200A)
JKS-(225A…400A)
JKS-(225A…400A)
JKS-(450A…600A)
JKS-(450A…600A)
Results
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
–
2950 A
–
5960 A
–
11.5 kA
–
15.5 kA
Min
–
375 A
–
920 A
–
1820 A
Interrupting Amps
Max
69.6 kA
–
69.6 kA
–
69.6 kA
–
69.6 kA
–
69.6 kA
–
69.6 kA
–
69.6 kA
–
Circuit Parameters
Volts DC
816
812
816
812
816
810
810
816
812
810
816
812
816
810
Time Constant
2.78 ms
0.55 ms
2.78 ms
0.4 ms
2.78 ms
0.5 ms
2.78 ms
0.86 ms
2.78 ms
3.34 ms
2.78 ms
2.92 ms
2.78 ms
0.4 ms
Circuit Configuration
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
Configuration A
170M Fuses
Cooper Bussmann
P. O. Box 14460
St. Louis, MO 63178-4460
May 15, 2002
Sr. Project Engineer, Rockwell Automation
6400 West Enterprise Drive
P.O. Box 760
Mequon, WI 53092
Subject: DC Testing for 170M Fuses
Dear Mr.
At the request of Rockwell Automation, Bussmann has completed the DC testing for the 170M fuses and is pleased to present the attached information indicating successful 'Self-Certification DC Rating' on all subject fuses.
Bussmann tested fuses to the following parameters specified by Rockwell Automation:
• Short Circuit Current = 65 kA and 100 kA
• Voltage = 810V DC
• Time Constant ≥0.4 ms
Additional tests were performed for acceptability:
• Short Circuit Current = 30 times fuse amperage as minimum current interrupting rating or as tested
• Voltage = 810V DC
• Time Constant ≥0.4 ms
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 69
Appendix A Kinetix and PowerFlex Drive Specifications
The attached table identifies the fuses tested, the actual circuit parameters and the circuit configuration. In the attached table, the
Interrupting Amps column specifies the fuses minimum and maximum amps that the fuse will safely clear at 810V DC.
Circuit Configuration A
Fuse Fuse
By way of this correspondence, Cooper Bussmann self-certifies the preceding fuses in end-user applications to the preceding parameters and the attached data sheet.
Should you have any questions regarding this correspondence, please contact me at the listed address and numbers.
Regards,
Strategic OEM Accounts Manager
Cooper Bussmann
Table 63 - Cooper Bussmann 170M, DC Fuse Test for Rockwell Automation
Fuse
170M6646
170M6646
170M6650
170M6650
170M7510
170M7510
170M6792
170M6792
170M6793
170M6793
170M6794
170M6794
170M6828
170M6828
170M6934
170M6934
170M7560
170M7560
Results
–
–
–
Acceptable
Acceptable
Acceptable
Acceptable
–
–
–
–
–
–
–
Acceptable
Acceptable
–
–
23 kA
–
27.5 kA
–
–
37 kA
Circuit Parameters
Interrupting Amps
Min
–
Max
69.8 kA
10.2 kA
–
–
69.6 kA
21.1 kA
–
20 kA
–
19 kA
–
–
65 kA
–
65 kA
–
65 kA
45.2 kA
–
60 kA
–
65 kA
–
65 kA
–
105.4 kA
–
100 kA
–
Volts DC
810
810
810
810
810
810
810
810
810
812
810
810
812
812
812
810
810
810
Time Constant
2 ms
2 ms
2 ms
2 ms
2 ms
1.8 ms
2 ms
1.66 ms
2 ms
1.2 ms
2 ms
2 ms
2 ms
2 ms
2 ms
1.12 ms
2 ms
2 ms
Circuit Configuration
–
–
–
Configuration A
Configuration A
Configuration A
Configuration A
–
–
–
–
–
–
–
Configuration A
Configuration A
–
–
70 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Appendix
B
Kinetix 5700 Accessory Modules
The requirements for when to use accessory modules vary depending on whether your system is powered by the 2198-P xxx
DC-bus power supply or 2198-RP xxx
regenerative bus supply.
Accessory Module
Cat. No.
2198-CAPMOD-2240
2198-CAPMOD-DCBUS-IO
Accessory Module
Capacitor Module
Extension Module
2198-DCBUSCOND-RP312 DC-bus Conditioner Module
Description
Use for energy storage and to extend the DC-bus voltage to another inverter cluster. Modules are zero-stacked with servo drives and use the shared-bus connection system to extend the external DC-bus voltage in applications up to 104 A. Can parallel with itself or with another accessory module for up to 208 A.
The extension module, paired with a capacitor module or DC-bus conditioner module, is used to extend the
DC-bus voltage to another inverter cluster in systems with ≥104 A current and up to 208 A.
Decreases the voltage stress on insulation components in an inverter system with long cable lengths and used to extend the DC-bus voltage to another inverter cluster. Modules are zero-stacked with servo drives and use the shared-bus connection system to extend the external DC-bus voltage in applications up to 104 A. Can parallel with itself or with another accessory module for applications up to 208 A.
Accessory Flow Chart
In this flowchart, a 2198-P xxx
DC-bus power supply or 2198-RP xxx
regenerative bus supply supplies DC-bus power to a mixed-architecture common-bus drive system.
The power supply cluster includes the 2198-P xxx
DC-bus power supply or 2198-RP xxx
regenerative bus supply.
System variables that you need to know include the following:
• The type of AC to DC converter used
• The external DC-bus current
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 71
Appendix B Kinetix 5700 Accessory Modules
Figure 39 - Mixed Architecture Common-bus System
Start
What type of AC to DC converter is used?
Kinetix 5700
Regenerative Bus Supply
Kinetix 5700
DC-bus Power Supply
Power Supply Cluster:
• Capacitor Module
• DC-bus Conditioner Module
Yes
Is there an external active shunt in the system?
Power Supply Cluster:
• Capacitor Module
• DC-bus Conditioner Module
No
<104 A
Power Supply Cluster:
• Capacitor Module
What is the external DC-bus current?
≥104 A up to 208 A, max
Power Supply Cluster:
• Capacitor Module
• Extension Module
Capacitor Module
The capacitor module is used for energy storage and to extend the DC-bus voltage to another inverter cluster. Modules are zero-stacked with servo drives and use the shared-bus connection system to extend the external DC-bus voltage in applications up to 104 A. The module can be paralleled with itself or with another accessory module for up to 208 A.
Observe the following capacitor module guidelines:
• Required in each cluster of a multi-cluster system
• More than one capacitor module can be used in a cluster, if needed
• Flexible bus-bars are included with only the 2198-CAPMOD-DCBUS-IO extension module. So, if you have two capacitor modules, two DCbus conditioner modules, or a capacitor module and DC-bus conditioner module mounted side by side, you must order the 2198-
KITCON-CAPMOD2240 or 2198-KITCON-DCBUSCOND connector set separately.
72 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Figure 40 - Capacitor Module Block Diagram
DC-bus Output
Lug Connector
DC+
DC–
Kinetix 5700 Accessory Modules Appendix B
Fuse Detection
Module Status
Status Indicator
MS
MS
Module Status
(MS) Connector
DC-bus Detection
DC-bus Status
Status Indicator
Capacitor Bank
DC-bus Input
Link Connector
DC+
DC–
Fuse
DC+
Bleeder
Resistor
DC– DC–
You can configure either of the DC-bus power supply digital inputs as Bus Capacitor OK in the Logix Designer application to monitor the
Module Status output. Refer to the Kinetix® 5700 Servo Drives User Manual, publication 2198-UM002 , to see how the DC-bus power supply
Digital Inputs category is configured.
Figure 41 - DC-bus Power Supply with Capacitor Module
2198-P xxx
DC-bus Power Supply
2198-CAPMOD-2240
Capacitor Module
MS
MS
Module Status (MS)
Connector
Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
(1) Configure either of two digital inputs as Bus Capacitor OK. For DC-bus power supply configurable functions, see Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
Refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , for more information on accessory module installation.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 73
Appendix B Kinetix 5700 Accessory Modules
DC-Bus Conditioner Module
The DC-bus conditioner module decreases the voltage stress on insulation components in an inverter system with long cable lengths and can be used to extend the DC-bus voltage to another inverter cluster. Modules are zero-stacked with servo drives and use the shared-bus connection system to extend the external DC-bus voltage in applications up to 104 A. The module can be paralleled with itself or with another accessory module for applications up to 208 A.
Observe the following DC-bus conditioner module guidelines:
• A DC-bus conditioner module is required on all Kinetix 5700 extended clusters
• A DC-bus conditioner module is required on the power supply cluster if a regenerative bus supply or external active shunt is included in the system.
• When a DC-bus conditioner module is installed and there is no use-case for installation, the module does not provide any benefit
• Flexible bus-bars are included with only the 2198-CAPMOD-DCBUS-IO extension module. So, if you have two capacitor modules, two
DC-bus conditioner modules, or a capacitor module and DC-bus conditioner module mounted side by side, you must order the
2198-KITCON-CAPMOD2240 or 2198-KITCON-DCBUSCOND connector set separately.
Figure 42 - DC-bus Conditioner Module Block Diagram
Fuse Detection and
Over Temperature
Protection
Module Status
Status Indicator
MS
MS
Module Status
(MS) Connector
DC-bus Output
Lug Connector
DC+
DC–
DC-bus Detection
DC-bus Status
Status Indicator
DC-bus Input
Link Connector
DC+
DC–
Chassis
Fuse
Conditioning Circuit
You can configure any of the regenerative bus supply digital inputs as Bus Conditioner OK in the Logix Designer application to monitor the
Module Status output. Refer to Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 , to see how the regenerative bus supply Digital
Inputs category is configured.
74 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Figure 43 - Regenerative Bus Supply with DC-bus Conditioner Module
2198-RP xxx
Regenerative Bus Supply
MS
MS
2198-DCBUSCOND-RP312
DC-bus Conditioner Module
Module Status (MS)
Connector
Kinetix 5700 Accessory Modules Appendix B
Digital Input
(IOD) Connector
IN x
COM
(1)
24V DC
(1) Configure any one of four digital inputs as Bus Conditioner OK. For regenerative bus supply configurable functions, see Kinetix 5700 Servo Drives User Manual, publication 2198-UM002 .
Refer to the Kinetix 5700 DC-bus Conditioner Module Installation Instructions, publication 2198-IN016 , for additional installation information.
Extension Module
The extension module, when paired with a capacitor module, is used to extend the DC-bus voltage to another inverter cluster in systems with
≥104 A current and up to 208 A.
Observe the following extension module guidelines:
• The extension module is always mounted next to a capacitor module or DC-bus conditioner module and always positioned on the outside of the system cluster (either first or last).
• Flexible bus-bars are included with the 2198-CAPMOD-DCBUS-IO extension module. So, if you have a 2198-CAPMOD-DCBUS-IO extension module with a capacitor module or a DC-bus conditioner module, you do not need to order the 2198-KITCON-CAPMOD2240 or 2198-
KITCON-DCBUSCOND connector set separately.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 75
Appendix B Kinetix 5700 Accessory Modules
Notes:
76 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Index
Numerics
2094 shunt module
2094-BSP2
,
2198-CAPMOD-2240
2198-CAPMOD-DCBUS-IO
,
2198-DCBUSCOND-RP312
,
A
AC line impedance
,
,
,
accessory modules
,
capacitor module
flow chart
active shunt
,
lug connections
use cases
,
active-front-end
D
DC bus bar
example
DC-bus
cables
cable length
capacitance
connections
,
DC bus bar
link
lug connections
wiring example
digital input
diode-front-end
disconnect switch
,
,
drive system
DC-bus connections
mounting order
B block diagrams capacitor module
braking chopper
Bus Capacitor OK
bus overvoltage faults
Bus Voltage Reference Source
Bus Voltage Set Point
C cable length
capacitance
capacitance sizing
capacitor module
circuit protection
,
Kinetix 6000
Kinetix 7000
cluster example
common bus
contactor enable
contactor enable control string
,
,
,
contactor-enable relay circuit
converter OK
Kinetix 6000
,
,
Kinetix 7000
PowerFlex 750-Series
E
Enable
extension module
,
external active shunt
external passive shunt
F flexible bus-bars
flow chart
full regeneration
fuse certification and test data
G ground jumper settings
,
ground screw settings
,
,
I
IEEE-519
interconnect diagrams active shunt
module status
,
internal
IGBT
shunt
,
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 77
Index
K
Kinetix 5700
cluster example
DC-bus link
DC-bus supply
DC-bus wiring example
specifications
Kinetix 6000
circuit protection specifications
drives
,
ground jumper settings
power specifications, AM 460V
62 power specifications, IAM 460V 62
specifications
Kinetix 6200/6500
circuit protection specifications
drives
specifications power, AM 460V
power, IAM 460V
Kinetix 7000
circuit protection specifications
drives
,
I/O connections
specifications
L line reactor
,
M maximum cable lengths
module status
DC-bus power supply
Motion Analyzer website
mounting order
N non-regenerative definition
non-regenerative bus supply
AC line impedance
configurations
contactor enable
contactor-enable relay circuit
disconnect switch
ground screw settings
Kinetix 5700 DC-bus supply
line reactor
,
,
maximum cable lengths
passive shunt connections
system sizing
total system capacitance
P passive shunt connections
specifications
PowerFlex 750-Series
AC Drive
circuit protection specifications
frames 1…4
frames 5 and 6
precharge
enable
Kinetix 6000 drives
parameters
,
PowerFlex 750-Series, frames 1…4
PowerFlex 750-Series, frames 5 and 6
Precharge Enable
R
Regen OK
Regeneration OK
regeneration plus shunt
regenerative definition
78 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Index regenerative bus supply
AC line impedance
bus overvoltage fault
configurations
converter OK
disconnect switch
external active shunt
full regeneration
ground screw settings
Kinetix 5700 regenerative bus supply
line reactor
meets IEEE-519
Precharge Enable
system sizing
total system capacitance
S shunt active
resister
Shunt Thermal Switch OK
sizing
specifications
DC-bus capacitance
59 fuse certification and test data
Kinetix 5700
capacitance
DC-bus power supply
Kinetix 6000
circuit protection
Kinetix 6000 power specifications
AM 460V
IAM 460V
Kinetix 6200/6500
power, AM 460V
power, IAM 460V
Kinetix 7000
specifications
PowerFlex 750-Series circuit protection
system sizing
system block diagrams capacitor module
DC-bus conditioner module
T total system capacitance
,
U use cases active shunt
,
W website
Motion Analyzer
wiring external DC-bus
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 79
Index
Notes:
80 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Drives in Common Bus Configurations with Kinetix 5700 Bus Supplies Application Technique
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Kinetix Rotary Motion Specifications Technical Data, publication
Kinetix Linear Motion Specifications Technical Data, publication
Kinetix Servo Drives Specifications Technical Data, publication
KNX-TD001
KNX-TD002
KNX-TD003
Description
Provides product specifications for Kinetix VPL, VPC, VPF, VPH, and VPS motors, Kinetix
MPL, MPM, MPF, and MPS motors, and Kinetix HPK rotary motors.
Provides product specifications for Kinetix MPAS and MPMA linear stages,
Kinetix VPAR, MPAR, and MPAI electric cylinders, LDAT-Series linear thrusters, and
LDC-Series™ linear motors.
Provides product specifications for Kinetix Integrated Motion over the EtherNet/IP™ network, Integrated Motion over Sercos interface, EtherNet/IP networking, and component servo drive families.
Provides product specifications for 2090-Series motor and interface cables, low-profile connector kits, drive power components, and other servo drive accessory items.
Kinetix Motion Accessories Specifications Technical Data, publication KNX-TD004
Kinetix 5700 Servo Drives User Manual, publication 2198-UM002
Kinetix 6000 Multi-axis Servo Drives User Manual, publication 2094-UM001
Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual, publication 2094-UM002
Kinetix 7000 High Power Servo Drives User Manual, publication 2099-UM001
Provides information on installing, configuring, startup, troubleshooting, and applications for your Kinetix servo drive system.
Kinetix Motion Control Selection Guide, publication KNX-SG001
Overview of Kinetix servo drives, motors, actuators, and motion accessories designed to help make initial decisions for the motion control products best suited for your system requirements.
Kinetix 5700 Drive Systems Design Guide, publication KNX-RM010
Kinetix 6000 and Kinetix 6200/6500 Drive Systems Design Guide, publication KNX-RM003
Kinetix 7000 Drive Systems Design Guide, publication GMC-RM007
PowerFlex 750-Series Drive Technical Data, publication
PowerFlex 750-Series Products with TotalFORCE® Control Technical Data, publication 750-TD100
750-TD001
1321 Power Conditioning Products Technical Data, publication 1321-TD001
System design guide to select the required (drive specific) drive module, power accessory, feedback connector kit, and motor cable catalog numbers for your Kinetix drive system.
Provides technical data on PowerFlex 750-Series drives.
Provides detailed information on, kit selection, kit ratings and specifications, and option specifications.
Information on line reactors and isolation transformers.
Drives in Common Bus Configurations Application Technique, publication DRIVES-AT002
Drives in Common Bus Configurations with PowerFlex 755TM Bus Supplies
Application Technique, publication DRIVES-AT005
Industry Installation Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-AT003
Provides the necessary guidelines, considerations, and limitations for the proper application of PowerFlex drives used in common bus configurations.
Provides the necessary guidelines, considerations, and limitations for the proper application of Allen-Bradley drives used in common bus configurations.
Provides basic information for different enclosure systems, environmental/location considerations, and power and grounding considerations needed to properly install a
Pulse Width Modulated (PWM) AC drive.
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001
Provides basic information to install, protect, wire, and ground pulse width modulated
(PWM) AC drives.
PowerFlex 750-Series AC Drives Installation Instructions, publication 750-IN001 Provides the basic steps to install PowerFlex 750-Series drives.
PowerFlex 750-Series Power Jumpers Installation Instructions, publication 750-IN011
Provides jumper settings for PowerFlex 750-Series AC drives.
PowerFlex 750-Series EMC Plate and Cores - Frames 1…7 Installation Instructions, publication 750-IN006
Provides installation information for PowerFlex 750-Series EMC plate and cores.
PowerFlex 755 AC Drives EMC Cores Installation Instructions, publication 750-IN024
PowerFlex 750-Series Drive Programming Manual, publication 750-PM001
Provides installation information for PowerFlex 755 AC drives EMC cores.
Provides information on programming PowerFlex 750-Series drives.
Motion Analyzer System Sizing and Selection Tool website https://motionanalyzer.rockwellautomation.com/
EtherNet/IP Network Devices User Manual, ENET-UM006
Comprehensive motion application sizing tool used for analysis, optimization, selection, and validation of your Kinetix Motion Control system.
Describes how to configure and use EtherNet/IP devices to communicate on the
EtherNet/IP network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts and infrastructure components and features.
Safety Guidelines for the Application, Installation, and Maintenance of Solid-State
Control, publication SGI-1.1
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solidstate components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, rok.auto/certifications .
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at rok.auto/literature.
Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 81
Rockwell Automation Support
Use these resources to access support information.
Technical Support Center
Knowledgebase
Local Technical Support Phone Numbers
Literature Library
Product Compatibility and Download Center
(PCDC)
Find help with how-to videos, FAQs, chat, user forums, and product notification updates.
rok.auto/support
Access Knowledgebase articles.
rok.auto/knowledgebase
Locate the telephone number for your country.
Find installation instructions, manuals, brochures, and technical data publications.
Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.
rok.auto/phonesupport rok.auto/literature rok.auto/pcdc
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback .
Allen-Bradley, Encompass, expanding human possibility, Kinetix, LDC-Series, PowerFlex, Rockwell Automation, Rockwell Software, Studio 5000 Logix Designer, and TotalFORCE are trademarks of
Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec .
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Publication MOTION-AT007A-EN-P - May 2020
Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Provides a reliable and stable DC-bus voltage for Kinetix 5700 drives.
- Supports non-regenerative Common DC-bus configurations.
- Features advanced precharge circuitry for safe and efficient system startup.
- Offers adjustable output voltage to accommodate various system requirements.
- Includes built-in diagnostics and protection features to ensure system reliability.
- Compact and DIN-rail mountable for easy installation.
- UL Listed, cUL Listed, CE Certified, and RoHS Compliant.