Rockwell Automation 1734-8CFGDLX, 1738-8CFGDLXM8 User Manual
Advertisement
Advertisement
POINT I/O and ArmorPOINT I/O
DeviceLogix Modules
User Manual
(Catalog Numbers 1734-8CFGDLX,
1738-8CFGDLXM8, 1738-8CFGDLXM12, 1738-8CFGDLXM23)
Allen-Bradley HMIs
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hardwired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, ArmorPOINT I/O, POINT I/O, POINTBus, Rockwell Automation, RSLogix, RSNetWorx, RSNetWorx for DeviceNet, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1734-UM015A-EN-E - November 2009
Preface
Introduction
Install POINT I/O DeviceLogix
Modules
Install ArmorPOINT I/O
DeviceLogix Modules
Table of Contents
Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Who Should Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 1
1734-8CFGDLX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1738-8CFGDLXM8, 1738-8CFGDLXM12, and
1738-8CFGDLXM23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Standard POINT I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Stand Alone DeviceLogix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Peer Enabled POINT I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Quick Start - Prepare the Modules to work on DeviceNet . . . . . . . . . 12
Quick Start - Prepare the Modules to work on EtherNet/IP and
Chapter 2
Install the Mounting Base Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Install an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Install the Removable Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . 21
Remove a 1734-TB or 1734-TBS Base . . . . . . . . . . . . . . . . . . . . . . . . . 22
Remove a 1734-TOP or 1734-TOPS Base . . . . . . . . . . . . . . . . . . . . . . 23
1734-8CFGDLX I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1734-8CFGDLX Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 24
System and Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 3
Install the Mounting Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Remove the Module from the Mounting Base. . . . . . . . . . . . . . . . 30
1738-8CFGDLXM8 I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . 30
1738-8CFGDLXM12 I/O Module . . . . . . . . . . . . . . . . . . . . . . . . 31
1738-8CFGDLXM23 I/O Module . . . . . . . . . . . . . . . . . . . . . . . . 32
1
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
2 Table of Contents
DeviceLogix for POINT I/O and
ArmorPOINT I/O on DeviceNet
DeviceLogix for POINT I/O and
ArmorPOINT I/O on
Ethernet/ControlNet
Configuring POINT I/O and
ArmorPOINT I/O DeviceLogix modules using RSNetworx for
DeviceNet
DeviceLogix Capabilities
Chapter 4
Offline Configuration using RSNetworx for DeviceNet . . . . . . . . . . . 33
Example: Build the Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Online Configuration using RSNetWorx for DeviceNet. . . . . . . . . . . 36
I/O Data Assembly Maps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter 5
Add a POINT I/O DeviceLogix Module to RSLogix 5000 . . . . . . . . 43
Launch RSNetworx for DeviceNet to Configure the Module. . . . . . . 47
Chapter 6
Configure the Module using the Configuration tab . . . . . . . . . . . . . . . 49
Parameters on the Parameters tab. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Configure Peer Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Set Up Peer Communication Parameters . . . . . . . . . . . . . . . . . . . . 55
Produce Data Without Using a Master . . . . . . . . . . . . . . . . . . . . . . . . . 58
Start the Function Block Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Chapter 7
Function Block Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Process Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Filter Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Select Limit Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Statistical Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Timer/Counter Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Comparison Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Compute Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Move/Logical Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Logic Execution Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Digital Inputs to Function Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . 71
Analog Inputs to Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . 73
Digital Outputs from Function Blocks. . . . . . . . . . . . . . . . . . . . . . 74
Analog Outputs from Function Blocks . . . . . . . . . . . . . . . . . . . . . 76
Offline and Online Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Enable/Disable Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Logic Enable On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Logic Enable Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Dependent Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Publication 1734-UM015A-EN-E - November 2009
Troubleshooting
Peer Data Maps
Table of Contents 3
Chapter 8
About Module Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Status Indicators of POINT I/O Module . . . . . . . . . . . . . . . . . . . . . . 84
1734-8CFGDLX Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Status Indicators of ArmorPOINT I/O Modules . . . . . . . . . . . . . . . . 86
1738-8CFGDLXM8, 1738-8CFGDLXM12, and
1738-8CFGDLXM23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Troubleshooting Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Peer connection is not working. . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Appendix A
About This Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Analog and Specialty Input Modules . . . . . . . . . . . . . . . . . . . . . . . 92
2-Point Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4-Point Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4-Point Digital Input with Diagnostics Modules . . . . . . . . . . . . . . 95
8-Point Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
8-Point Configurable Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
16-Point Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
8-Point Digital Input Modules with DeviceLogix . . . . . . . . . . . . . 97
2-Point Analog Input Modules and RTD (Resistant
Temperature Device) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
4-Point Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
8-Point Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
2-Point Thermocouple Input Modules. . . . . . . . . . . . . . . . . . . . . 102
Very High Speed Counter Input Modules . . . . . . . . . . . . . . . . . . 103
Encoder/Counter Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . 105
Synchronous Serial Interface Modules . . . . . . . . . . . . . . . . . . . . . 105
RS232 and RS485 Interface Module . . . . . . . . . . . . . . . . . . . . . . . 106
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
4 Table of Contents
Notes:
Publication 1734-UM015A-EN-E - November 2009
Preface
5
Purpose of This Manual
This manual describes how to install, configure, and troubleshoot your
POINT I/O DeviceLogix and ArmorPOINT I/O DeviceLogix modules.
POINT I/O and ArmorPOINT I/O modules can be used in EtherNet/IP,
DeviceNet, and ControlNet systems. As such, you may need to refer to other publications in addition to this one.
When using POINT I/O DeviceLogix modules with a communication adapter, use this manual in conjunction with the user manual for the adapter you are using as shown in the table.
When Using POINT I/O
Modules on This Network
DeviceNet network
ControlNet network
EtherNet/IP network
Refer to
Publication for
DeviceNet adapter
Catalog No.
Publication No.
1734-ADN
1734-ADNX
1734-UM002
ControlNet adapter 1734-ACNR 1734-UM008
EtherNet/IP adapter 1734-AENT 1734-UM011
POINT I/O DeviceLogix modules are not compatible with the PROFIBUS adapter.
When using ArmorPOINT I/O DeviceLogix modules with a communication adapter, use this manual in conjunction with the user manual for the adapter you are using as shown in the table.
When Using ArmorPOINT
I/O Modules on This
Network
DeviceNet network
ControlNet network
EtherNet/IP network
Refer to
Publication for
Catalog No.
Publication No.
DeviceNet adapter 1738-ADN
1738-ADNX
1738-UM001
ControlNet adapter 1738-ACNR 1738-IN016
EtherNet/IP adapter 1738-AENT
1738-AENTR
1738-IN017
1738-IN028
ArmorPOINT I/O DeviceLogix modules are not compatible with the
PROFIBUS adapter.
The modules in this manual are DeviceNet-ready. Each module can exist on the DeviceNet network as one of the following:
• An individual node
• With an adapter (catalog number 1734-ADN or 1734-ADNX) as a single node
For applications using these modules in a network with a 1734-PDN
DeviceNet Communication Interface, or a 1734Dxx POINTBlock I/O Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
6 Preface
Who Should Use This
Manual
This manual is intended for qualified personnel. You should know how to do the following:
• Use RSNetWorx software or similar configuration software to set up and calibrate these modules.
• Download and use electronic data sheet (EDS) files.
In addition, you should be familiar with RSLogix 5000 and CIP Network terminology. If you do not, refer to your software documentation or online help before attempting to use these modules.
Related Publications
Refer to this table for a list of related POINT I/O products and documentation. The publications are available from http://literature.rockwellautomation.com/ . For specification and safety certification information, refer to the installation instructions.
Resource Description
POINT I/O DeviceLogix Module
POINT I/O Module with 8 Configurable 24V DC Points and
DeviceLogix Installation Instructions, publication 1734-IN039
Communication Devices
ControlNet Adapter Installation Instructions, publication 1734-IN582
Provides installation information and wiring diagrams for
1734-8CFGDLX modules.
Provides installation information about 1734-ACNR adapters.
ControlNet Adapter User Manual, publication 1734-UM008
DeviceNet Communication Interface Module Installation
Instructions, publication 1734-IN057
Describes how to use 1734-ACNR adapters.
Provides installation information about 1734-PDN modules.
DeviceNet Adapter Installation Instructions, publication 1734-IN026 Provides installation information about 1734-ADN and 1734-ADNX adapters.
DeviceNet Adapter User Manual, publication 1734-UM002
RSNetworx for DeviceNet Getting Results Guide, publication
DRNET-GR001
Describes how to use 1734-ADN and 1734-ADNX adapters.
Describes how to install and navigate the RSNetWorx for
DeviceNet software.
Provides installation information about 1734-AENT adapters.
EtherNet/IP Adapter Installation Instructions, publication 1734-IN590
EtherNet/IP Adapter User Manual, publication 1734-UM011 Describes how to use 1734-AENT adapters.
Power Supplies, Wiring Base Assemblies, Miscellaneous
Field Potential Distributor Installation Instructions, publication 1734-IN059
Provides installation information about 1734-FPD distributors.
POINT I/O 24V dc Expansion Power Supply Installation Instructions, publication 1734-IN058
Provides installation information about 1734-EP24DC power supplies.
Provides installation information about 1734-EPAC power supplies.
POINT I/O 120/240V ac Expansion Power Supply Installation
Instructions, publication 1734-IN017
POINT I/O Common Terminal Module Installation Instructions, publication 1734-IN024
Provides installation information about 1734-CTM modules.
Publication 1734-UM015A-EN-E - November 2009
Preface 7
Resource Description
POINT I/O Voltage Terminal Module Installation Instructions, publication 1734-IN024
Provides installation information about 1734-VTM modules.
POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN511
POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN013
POINT I/O One-piece Wiring Base Assembly Installation
Instructions, publication 1734-IN028
Provides installation information about 1734-TB and 1734-TBS assemblies.
Provides installation information about 1734-TB3 and 1734-TB3S assemblies.
Provides installation information about 1734-TOP, 1734-TOPS,
1734-TOP3 and 1734-TOP3S assemblies.
Refer to this table for a list of related ArmorPOINT I/O products and documentation. The publications are available from http://literature.rockwellautomation.com/ . For specification and safety certification information, refer to the installation instructions.
Resource Description
ArmorPOINT I/O DeviceLogix Module
ArmorPOINT I/O Modules with 8 Configurable 24V DC Points Wiring
Diagrams, publication 1738-WD009
Provides wiring diagrams for 1738-8CFGDLXM8,
1738-8CFGDLXM12, and 1738-8CFGDLXM23.
ArmorPOINT Module with Configurable 24V DC Points and
DeviceLogix Installation Instructions, publication 1738-IN027
Communication Devices
ArmorPOINT ControlNet Adapter, Series A Installation Instructions, publication 1738-IN016
ArmorPOINT I/O DeviceNet Adapter Installation Instructions, publication 1738-IN014
ArmorPOINT I/O DeviceNet Adapter User Manual, publication
1738-UM001
ArmorPOINT EtherNet/IP Adapter, Series A Installation Instructions, publication 1738-IN017
ArmorPOINT I/O 2-Port EtherNet/IP Adapter, Series A Installation
Instructions, publication 1738-IN028
Provides installation information about 1738-8CFGDLXM8,
1738-8CFGDLXM12, and 1738-8CFGDLXM23.
Provides installation information about 1738-ACNR adapters.
Provides installation information about 1738-ADN and 1738-ADNX adapters.
Describes how to use 1738-ADN and 1738-ADNX adapters.
Provides installation information about 1738-AENT adapters.
Provides installation information about 1738-AENTR adapters.
Power Supplies, Wiring Base Assemblies, Miscellaneous
ArmorPOINT I/O Field Potential Distributor, Series A Installation
Instructions, publication 1738-IN019
ArmorPOINT I/O 24V dc Expansion Power Supply, Series A
Installation Instructions, publication 1738-IN020
Provides installation information about 1738-FPD distributors.
Provides installation information about 1738-EP24DC power supplies.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
8 Preface
Notes:
Publication 1734-UM015A-EN-E - November 2009
Chapter
1
Introduction
About This Chapter
This chapter introduces POINT I/O and ArmorPOINT I/O configurable modules with DeviceLogix capability.
•
•
Quick Start - Prepare the Modules to work on DeviceNet
•
Quick Start - Prepare the Modules to work on EtherNet/IP and
9
About the Modules
The POINT I/O and ArmorPOINT I/O modules work with EtherNet/IP,
DeviceNet and ControlNet network adapters. Each module has eight 24V DC
I/O points that self-configure to be inputs or outputs. Inputs are IEC Type 3 and outputs are self-protecting 0.5 A outputs.
The firmware in these modules uses Version 3 of the DeviceLogix master library. The modules can execute 144 DeviceLogix function blocks in 3 ms.
Smaller programs that contain fewer than 40 function blocks can be executed in 1 ms.
Each module produces 20 bytes of data including I/O state (eight bits), eight user-defined bits, and eight user-defined words of analog data to be consumed by processors or other DeviceLogix modules. Each module consumes 20 bytes of data to set the I/O state (eight bits), eight user-defined control bits, and eight user-defined words of analog data. It is also possible to consume the data from up to eight other peers.
This table lists 1734 and 1738 configurable I/O modules with DeviceLogix.
Module Description
POINT I/O module with 8 configurable 24V DC I/O points and DeviceLogix capabilities
ArmorPOINT I/O module with 8 configurable 24V DC M8 connectors and DeviceLogix
ArmorPOINT I/O module with 8 configurable 24V DC M12 connectors and DeviceLogix
ArmorPOINT I/O module with 1 configurable 24V DC M23 connector and DeviceLogix
Cat. No.
1734-8CFGDLX
1738-8CFGDLXM8
1738-8CFGDLXM12
1738-8CFGDLXM23
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
10 Introduction
Modes of Usage
1734-8CFGDLX
This module is an 8-point 24V DC I/O module with 8 self-configuring points and DeviceLogix capabilities. Each of the I/O points can be either a DC input or output. The module supports removal and insertion under power, auto-address, and auto-baud in compliance with the POINTBus backplane.
1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23
The ArmorPOINT I/O family consists of modular I/O modules. The sealed
IP67 housing of these modules requires no enclosure. Note that environmental requirements other than IP67 may require an additional appropriate housing. I/O connectors are sealed M8 (pico), M12 (micro) or
M23 styles. The mounting base ships with the module.
The module can be used in one of the following modes:
• as a standard POINT I/O module,
• in a stand alone DeviceLogix program where it controls its own I/O, and
• in network applications with or without the peer exchange of data.
Standard POINT I/O Module
The module can simply be used as an 8-point configurable POINT I/O module. It uses ODVA pre-defined Produce and Consume assemblies. Default settings help to facilitate quick setup right out-of-the-box. It is CIP network independent and it can run on DeviceNet, EtherNet/IP or ControlNet when used in conjunction with an adapter.
Publication 1734-UM015A-EN-E - November 2009
Introduction 11
Stand Alone DeviceLogix
If DeviceLogix is enabled (programmed), then the module becomes the owner of its outputs. The DeviceLogix program reads inputs and controls the onboard outputs.
• The produced assembly may be shared with a controller if a connection exists.
• As the owner of its local outputs, the module may run without an external controller.
An external controller, which is the owner of the connection to the module, can influence the module’s logic via a consume assembly – both digital and analog data. Configuration of the module is performed via RSNetWorx for
DeviceNet. When used on ControlNet or EtherNet/IP, the tool bridges through the adapter to directly communicate with the DeviceLogix module on the POINT I/O backplane.
Peer Enabled POINT I/O
The POINT I/O DeviceLogix module can “listen in” on data connections to other POINT I/O modules on the backplane. This data can be used in the
DeviceLogix program to control the outputs. It can consume data from 8 different peers. The data from each peer can be up to 24 bytes long. The data can be digital, analog (16-bit), or a mixture. The module supports the “Auto
Produce” parameter to produce I/O data automatically without the need for a master. It will also produce and consume network data. Configuration of peer data is performed via RSNetWorx.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
12 Introduction
Quick Start - Prepare the
Modules to work on
DeviceNet
Mount the Module
.
For ArmorPOINT I/O, see Chapter 3 .
Wire the Module
For POINT I/O, see
For ArmorPOINT I/O, see
Configure DeviceNet Network and
Scanner
.
Configure the Module using
RSNetWorx for DeviceNet
.
Write the DeviceLogix Program
.
Publication 1734-UM015A-EN-E - November 2009
Quick Start - Prepare the
Modules to work on
EtherNet/IP and ControlNet
Mount the Module
For POINT I/O, see
For ArmorPOINT I/O, see Chapter 3
.
Wire the Module
.
For ArmorPOINT I/O, see Chapter 3
.
Add Module to RSLogix 5000
See
Introduction 13
Write the DeviceLogix Program in
RSNetworx for DeviceNet
See
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
14 Introduction
Notes:
Publication 1734-UM015A-EN-E - November 2009
Chapter
2
Install POINT I/O DeviceLogix Modules
If you are using ArmorPOINT I/O modules
(1738-8CFGDLXM8/M12/M23), go to
Chapter 3, Install ArmorPOINT I/O
.
15
About This Chapter
Read this chapter for installation and wiring information including how to complete the following:
•
Install the Mounting Base Assembly
•
•
Install the Removable Terminal Block
•
Remove a 1734-TB or 1734-TBS Base
•
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC publication 60664-1), at altitudes up to 2000 m
(6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1
(Industrial Automation Wiring and Grounding Guidelines), for additional installation requirements pertaining to this equipment.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
16 Install POINT I/O DeviceLogix Modules
ATTENTION
WARNING
ATTENTION
POINT I/O is grounded through the DIN rail to chassis ground.
Use zinc-plated, yellow-chromated steel DIN rail to assure proper grounding. The use of DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.).
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I,
Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1734-UM015A-EN-E - November 2009
Install POINT I/O DeviceLogix Modules 17
Install the Mounting Base
Assembly
The 1734-8CFGDLX is compatible with 1734-TB, 1734-TBS, 1734-TOP, and
1734-TOPS wiring bases.
The 1734-TB or 1734-TBS wiring base assembly consists of a 1734-MB mounting base and a 1734-RTB or 1734-RTBS removable terminal block (RTB).
1734-TB or 1734-TBS wiring base
Status
NODE:
0
4
1
2
5
6
3
7
Slide-in Writable
Label
Module Locking
Mechanism
Module Wiring
Diagram
DIN Rail Locking
Screw (orange)
Mechanical
Keying (orange)
Insertable I/O
Module
RTB Removal
Handle
Removable
Terminal Block
(RTB)
Interlocking Side
Pieces
Mounting Base
44713
The 1734-TOP and 1734-TOPS are one-piece terminal bases.
1734-TOP or 1734-TOPS wiring base
Module Locking
Mechanism
Module Wiring
Diagram
DIN Rail Locking
Screw (orange)
Mechanical
Keying (orange)
Interlocking
Side Pieces
44714
Slide-in
Writable Label
Insertable
I/O Module
Handle
1734-TOP or
1734-TOPS
One-piece
Terminal Base with Screw or
Spring Clamp
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
18 Install POINT I/O DeviceLogix Modules
To install the mounting base assembly on the DIN rail, proceed as follows.
1.
If you are using the 1734-TB or 1734-TBS mounting base, attach the
RTB to the mounting base.
Otherwise, skip to step 2.
Removable
Terminal Block
(RTB)
Mounting Base
44858
2.
Position the mounting base (wiring base assembly) vertically above the installed units, for example, adapter, power supply, or existing module.
3.
Slide the mounting base down, allowing the interlocking side pieces to engage the adjacent module, power supply, or adapter.
Publication 1734-UM015A-EN-E - November 2009
31586
4.
Press firmly to seat the mounting base on the DIN rail until the base snaps into place.
5.
Use a small-bladed screwdriver to rotate the DIN-rail locking screw to the horizontal position.
This locks the assembly to the DIN rail.
Install an I/O Module
Install POINT I/O DeviceLogix Modules 19
Install the module before or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition, make sure the mounting base locking screw is positioned horizontally referenced to the base.
WARNING
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
1.
Use a bladed screwdriver to rotate the keyswitch on the mounting base clockwise until the number required for the type of module aligns with the notch in the base.
Position 1 is shown.
44710
Notch
Module
1734-8CFGDLX
Keyswitch Position
1
2.
Make certain the DIN-rail locking screw is in the horizontal position, noting that you cannot insert the module if the locking mechanism is unlocked.
44966
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
20 Install POINT I/O DeviceLogix Modules
3.
Insert the module straight down into the mounting base and press to secure.
Netw ork
Sta tus
NODE:
C
24VD
Output
0
1
2
3
17
34
OB4E
44967
4.
Secure the module with the RTB removal handle (for 1734-TB or
1734-TBS bases) or handle (for 1734-TOP or 1734-TOPS bases).
Module
Handle
44859
Publication 1734-UM015A-EN-E - November 2009
Install the Removable
Terminal Block
Install POINT I/O DeviceLogix Modules 21
A removable terminal block (RTB) is supplied with your mounting base assembly.
To remove, pull up on the RTB handle. This lets you remove and replace the base when necessary without removing any of the wiring.
To re-insert the RTB, proceed as follows.
WARNING
When you connect or disconnect the RTB with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure to remove power or that the area is nonhazardous before proceeding.
1.
Insert the RTB end opposite the handle into the base unit.
This end has a curved section that engages with the mounting base.
44968
2.
Rotate the terminal block into the mounting base until it locks itself in place.
3.
If an I/O module is installed, snap the RTB handle into place on the module.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
22 Install POINT I/O DeviceLogix Modules
Remove a 1734-TB or
1734-TBS Base
To remove a 1734-TB or 1734-TBS mounting base, do the following.
WARNING
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure to remove power or that the area is nonhazardous before proceeding.
1.
Unlatch the RTB handle on the I/O module.
2.
Pull on the RTB handle to remove the RTB.
3.
Press on the module lock on the top of the I/O module and pull the
I/O module out of the base.
4.
Remove the I/O module to the right of the base you are removing, noting that the interlocking portion of the base sits under the adjacent module.
5.
Use a small-bladed screwdriver to rotate the orange DIN-rail locking screw on the mounting base to a vertical position.
6.
This unlocks the mounting base from the DIN rail.
7.
Lift the mounting base straight up to remove.
44969
Publication 1734-UM015A-EN-E - November 2009
Remove a 1734-TOP or
1734-TOPS Base
Install POINT I/O DeviceLogix Modules 23
To remove a wiring base from the DIN rail, you must remove the module installed to the right of the base.
WARNING
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1.
Squeeze the module locking mechanism of the module to the right of the base, pulling up to remove the module.
2.
Use a small-bladed screwdriver to rotate the orange DIN-rail locking screw on the mounting base to a vertical position.
This unlocks the mounting base from the DIN rail.
3.
Slide the base up to release it from its mating units.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
24 Install POINT I/O DeviceLogix Modules
Wire the Modules
This section provides wiring instructions for the modules.
1734-8CFGDLX I/O Module
Module Status
Network Status
Module
Status
Network
Status
NODE:
DeviceLogix Status
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Device
Logix
Status
4
5
6
1734
8CFGDLX
7 7
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
I/O 0
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
44758
Note that voltage and current to the module is applied through the adapter, the 1734-FPD module, or the 1734-EP24DC module. V = 10…28.8 V DC.
1734-8CFGDLX Wiring Diagram
Prox
Prox
Prox
Prox
I/O 0 I/O 1
I/O 2 I/O 3
I/O 4 I/O 5
I/O 6 I/O 7
Load
Load
Load
Load
V C C
44687
If a connection to Common or the Supply Voltage is required for two- or three- wire devices, then a 1734-CTM or 1734-VTM can be used.
Each I/O point is either Input or Output.
Publication 1734-UM015A-EN-E - November 2009
Install POINT I/O DeviceLogix Modules 25
Channel
0
1
2
Terminal Number
I/O
0
Common
External
(1)
5
6
3
4
1
2
3
4
5
6
7 7
10/28.8 V DC is supplied through the internal power bus.
Voltage
External
(1)
Common connections require an external connection, such as a 1734-CTM module.
(2)
Supply Voltage Connections require an external connection such as a 1734-VTM module.
(2)
System and Power Considerations
There are no power terminals on the POINT I/O DeviceLogix module. The module gets its power from the Field Power Bus of the back plane. Depending on your system and network topology, power can be applied through one of the following:
• 1734-PDN (DeviceNet adapter)
• 1734-ADN or 1734-ADNX (DeviceNet adapter)
• 1734-ACNR (ControlNet adapter)
• 1734-AENT or 1734-AENTR (EtherNet/IP adapter)
• 1734-EP24DC (Expansion power supply)
• 1734-FPD (Field power distribution)
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
26 Install POINT I/O DeviceLogix Modules
Example of Logical Partitioning
Adapter
Status
DeviceNet
Status
PointBus
Status
1734-ADN
ADN EP24DC
2
C
I
E
2
C
O
E
I
B
2 2
E
O
B
1734-EP24DC
I
B
2 2
E
O
B
4
E
O
B
Status
Power
DeviceNet
Power
0 1 0 1 0 1 0 1
System
Power
DeviceNet
Power r
0 1 0 1 0 1 0 1
1
12V DC supply
1734adn4
24V DC supply
Similarly, field power and common (return) can be terminated in the POINT
I/O system by using the following modules:
• 1734-VTM (Voltage termination module)
• 1734-CTM (Common termination module)
1734-VTM 1734-CTM
0
1
1734
VTM
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out = 0…7
0
1
1734
C TM
Common
Common
Common
Common
Common = 0…7
Common
Common
Common
Common
43929
Publication 1734-UM015A-EN-E - November 2009
Chapter
3
Install ArmorPOINT I/O DeviceLogix Modules
27
About This Chapter
If you are using POINT I/O modules (1734-8CFGDLX), go to Chapter 2,
Install POINT I/O DeviceLogix Modules .
Read this chapter for information about how to install ArmorPOINT I/O modules to include the following:
•
•
•
• Remove the Modules
ATTENTION
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
Install the Mounting Base
Mount the I/O base on a wall or panel, using the screw holes provided in the base.
IMPORTANT
The ArmorPOINT I/O module must be mounted on a grounded metal mounting plate or other conductive surface.
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage
(PELV).
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
28 Install ArmorPOINT I/O DeviceLogix Modules
Mounting illustration for the ArmorPOINT adapter with I/O bases
Adapter
Adapter
47.2 mm
1.9 in
47.2 mm
1.9 in
50 mm
2.0 in
50 mm
2.0 in
22 mm
0.87 in
22 mm
0.87 in
50 mm
2.0 in
50 mm
2.0 in
22 mm
0.87 in
22 mm
0.87 in
50 mm
2.0 in
50 mm
2.0 in
102 mm
4.02 in
4.02 in
46 mm
1.81 in
46 mm
1.81 in
43769
Install the mounting as follows:
1.
Lay out the required points as shown above in the drilling dimension drawing.
2.
Drill the necessary holes for M4 (#8) machine or self-tapping screws.
3.
Mount the base using M4 (#8) screws.
4.
Ground the system using the ground lug connection.
The ground lug connection is also a mounting hole.
Latching mechanism
Ground lug connection
43675
Publication 1734-UM015A-EN-E - November 2009
Install the Module
Install ArmorPOINT I/O DeviceLogix Modules 29
Follow the instructions to install the module.
1.
Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 1 aligns with the notch in the base.
Keyswitch
Set to position 1, for the
1738 24V DC modules
43675
2.
Position the module vertically above the mounting base.
The module bridges two bases.
Module bridges two bases
H
A
DLX
B
1738-8CFGDLXM12
MOD
24V DC Out
G
NET
C
D
F
E
3
4
5
0
1
2
6
7
1738-8CFGDLXM12 shown
43771
3.
Push the module down until it engages the latching mechanism.
You will hear a clicking sound when the module is properly engaged.
The locking mechanism locks the module to the base.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
30 Install ArmorPOINT I/O DeviceLogix Modules
Wire the Modules
Remove the Module from the Mounting Base
Follow the instructions to remove the module from the mounting base.
1.
Put a flat blade screwdriver into the slot of the orange latching mechanism.
2.
Push the screwdriver toward the I/O module to disengage the latch.
The module lifts up off the base.
3.
Pull the module off the base.
This section provides wiring instructions for the modules.
ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
1738-8CFGDLXM8 I/O Module
Connector M8-A
Connector M8-C
Connector M8-E
Connector M8-G
43683
0
1738-8 C F G DLXM8
24V D C
1
2
4
6
MOD
NET
3
DLX
5
7
6
7
3
4
5
0
1
2
Connector M8-B
Connector M8-D
LED indicators
Connector M8-F
Connector M8-H
Publication 1734-UM015A-EN-E - November 2009
Install ArmorPOINT I/O DeviceLogix Modules 31
1738-8CFGDLXM8 Wiring Diagram
43583
(view into connector)
Pin 1 - 24V DC
Pin 3 - Common
Pin 4 - I/O 0 (M8-A)
I/O 1 (M8-B)
I/O 2 (M8-C)
I/O 3 (M8-D)
I/O 4 (M8-E)
I/O 5 (M8-F)
I/O 6 (M8-G)
I/O 7 (M8-H)
1738-8CFGDLXM12 I/O Module
Connectors M12-A...D
1738-8CFGDLXM12 Wiring Diagram
43664
(view into connector)
Pin 1 - 24V DC
Pin 2 - Not used
Pin 3 - Common
Pin 4 - I/O 0 (M12-A)
I/O 1 (M12-B)
I/O 2 (M12-C)
I/O 3 (M12-D)
I/O 4 (M12-E)
I/O 5 (M12-F)
I/O 6 (M12-G)
I/O 7 (M12-H)
Pin 5 - Not used
A
H
DLX
B
1738-8CFGDLXM12
24V DC Out
G
MOD
NET
C
D
F
E
2
3
4
0
1
5
6
7
Connectors M12-E...H
LED indicators
44355
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
32 Install ArmorPOINT I/O DeviceLogix Modules
1738-8CFGDLXM23 I/O Module
1738-8CFGDLXM23
24V DC In
M23 connector
MOD
NET
DLX
3
4
5
0
1
2
6
7
44353
LED indicators
1738-8CFGDLXM23 Wiring Diagram
43681
(view into connector)
Pin 1 - I/O 0
Pin 2 - I/O 1
Pin 3 - I/O 2
Pin 4 - I/O 3
Pin 5 - I/O 4
Pin 6 - I/O 5
Pin 7 - I/O 6
Pin 8 - I/O 7
Pin 9 - Return (Com)
Pin 10 - Return (Com)
Pin 11 - 24V DC
Pin 12 - Chassis
The ArmorPOINT I/O DeviceLogix module gets its power from the Field
Power Bus of the backplane. Depending on your system and network topology, power can be applied through one of the following:
• 1738-ADN12 or 1738-ADN18, 1738-ADN18P, 1738-ADNX
(DeviceNet adapter)
• 1738-ACNR (ControlNet adapter)
• 1738-AENT or 1738-AENTR (EtherNet/IP adapter)
• 1738-EP24DC (Expansion power supply)
• 1738-FPD (Field power distribution)
Publication 1734-UM015A-EN-E - November 2009
Chapter
4
DeviceLogix for POINT I/O and ArmorPOINT
I/O on DeviceNet
About This Chapter
This chapter provides information on the following:
•
Offline Configuration using RSNetworx for DeviceNet
•
Online Configuration using RSNetWorx for DeviceNet
•
Offline Configuration using
RSNetworx for DeviceNet
This section is not a substitute for RSNetworx or DeviceNet scanner and adapter publications. It is suggested that you have those publications available while performing the procedures in this section See
for a list of related publications.
This section describes the setup of a DeviceNet network using RSNetworx for
DeviceNet when the module is not connected to the network.
When configuring the module in the Offline mode, you must place all nodes on the network in the View window manually. Use the Hardware tree to find each module and place it into the View window. This can be done by double-clicking the module or dragging it to the View window.
If using a POINT I/O or ArmorPOINT I/O DeviceNet adapter, make sure you select Adapter for the main DeviceNet network, and Scanner for the
Pointbus backplane.
33
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
34 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Example: Build the Backplane
This example shows you how to build the backplane. The following screen shows the 1734-ADN Point I/O Scanner added.
Next, locate the I/O modules. In this example, the following modules will be added:
• 1734-8CFGDLX POINT I/O DeviceLogix module
• 1734-IB8 POINT I/O DC Input module
• 1734-IE4C POINT I/O 4...20 mA Analog Input module
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet 35
The digital modules can be found under the category, “General Purpose
Discrete I/O”, and the analog modules can be found under the “Rockwell
Automation miscellaneous” category.
The configuration of each module can now be edited from the Properties dialog box of each module. For instructions on editing the configuration of the
DeviceLogix module, see
Include all the I/O modules in the backplane to the Scanner’s scan list.
After configuration is complete, save your work in the DNT file. “DNT” is the three-letter file name extension. One file contains all the configuration data for all the modules on the network or backplane.
Remember that you need to go to the Online mode with RSNetWorx for
DeviceNet to download all the configuration data to the I/O modules and scanners.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
36 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Online Configuration using
RSNetWorx for DeviceNet
To set up a DeviceNet network using RSNetWorx for DeviceNet when connected to the network, do the following:
1.
If you have a DNT file that has been configured, open the file in
RSNetWorx for DeviceNet. To do this, go to the Online mode by pressing <F10>. You can also click Network > Online, or click the
Online button .
RSLinx will start. If the Online path is not set in Network > Properties, the Browse for network dialog box will appear.
Publication 1734-UM015A-EN-E - November 2009
2.
Navigate to the DeviceNet network or DeviceNet subnet if configuring the backplane.
The OK button will become available when you select a valid network.
RSNetWorx will automatically browse the network to discover all the participants.
3.
If there are any module identity issues, correct them before continuing.
4.
Ensure that the configuration in the DNT file matches the configuration in each node.
In this section, it is assumed that all the work was done in the Offline mode and that the DNT file contains all the correct information.
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet 37
To update all the modules in the most efficient way, click Network >
Download to Network on the menu bar.
5.
Review the Message window for any errors.
The stored configuration (DNT file) and the configuration of all the modules now match.
6.
If any changes are made, be sure to download them to the module and save them in the DNT file.
7.
When in the Online mode, you can change the configuration of a module by double-clicking its icon. You can also right-click the icon and select Properties.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
38 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Familiarize yourself with all the tabs in the Properties window before
where you will learn how to configure the
DeviceLogix module.
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet 39
I/O Data Assembly Maps
Read this section for information about how to communicate with your module.
I/O messages are sent to (consumed) and received from (produced) the I/O modules. These messages are mapped into the processor’s or scanner’s memory. Each module produces 1, 8 or 20 bytes of input data based on which produced assembly is selected. The default setup is 20 bytes.
It consumes 1, 8 or 20 bytes of I/O data (scanner Tx).
Default Data Map - Produced Assembly Instance 101
Message Size: 20 Bytes
Bit 7 6 5 4 3 2 1 0
Data [0] Pt 07 Pt 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Data [1] PNB 07 PNB 06 PNB 05 PNB 04 PNB 03 PNB 02 PNB 01 PNB 00
Data [2] Reserved
Data [3] PM7 PM6 PM5 PM4
Data [4] Produced Network Analog Word 0
Data [5]
PM3 PM2
Owned LogicEn
PM1 PM0
Data [6] Produced Network Analog Word 1
Data [7]
Data [8] Produced Network Analog Word 2
Data [9]
Data [10] Produced Network Analog Word 3
Data [11]
Data [12] Produced Network Analog Word 4
Data [13]
Data [14] Produced Network Analog Word 5
Data [15]
Data [16] Produced Network Analog Word 6
Data [17]
Data [18] Produced Network Analog Word 7
Data [19]
Where:
•
Pt = value of the I/O point,
•
PNB = Produced Network Bit,
•
PM = Peer Missing (a 1 indicates the absence of a configured peer)
•
Owned = Owned by a master.
When set to 0, the module is producing data without a master.
When set to 1, the module is producing while being owned by a master.
•
LogicEn = Logic Enabled (0 = logic disabled, 1 = logic enabled)
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
40 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
You can select other produced assemblies:
• Produced assembly instance 4 is the first byte of produced assembly instance 101 (Data [0]).
• Produced assembly instance 111 is the first eight bytes of produced assembly instance 101 (Data [0]…[7]).
Default Data Map - Consumed Assembly Instance 102
Message Size: 20 Bytes
Bit 7
Data [0] Pt 07
6
Pt 06
5
Pt 05
4
Pt 04
3
Pt 03
2
Pt 02
1
Pt 01
0
Pt 00
Data [1] CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00
Data [2] Reserved
Data [3]
Data [4] Consumed Network Analog Word 0
Data [5]
Data [6] Consumed Network Analog Word 1
Data [7]
Data [8] Consumed Network Analog Word 2
Data [9]
Data [10] Consumed Network Analog Word 3
Data [11]
Data [12] Consumed Network Analog Word 4
Data [13]
Data [14] Consumed Network Analog Word 5
Data [15]
Data [16] Consumed Network Analog Word 6
Data [17]
Data [18] Consumed Network Analog Word 7
Data [19]
Where: Pt = value to be applied to the output point, CNB = Consumed Network Bit
You can select other consumed assemblies:
• Consumed assembly instance 34 is the first byte of consumed assembly instance 102 (Data [0]).
• Consumed assembly instance 112 is the first eight bytes of consumed assembly instance 102 (Data [0]…[7]).
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet 41
Data Map - Configuration Assembly Instance 123
Message Size: 48 Bytes
Bit 7 6 5
Data [0] Group Off2On Input filter
4 3 2 1 0
Data [1]
Data [2] Group On2Off Input filter
Data [3]
Data [4] FltM 7 FltM 6 FltM 5 FltM 4 FltM 3 FltM 2 FltM 1 FltM 0
Data [5] FltV 7 FltV 6 FltV 5 FltV 4 FltV 3 FltV 2 FltV 1 FltV 0
Data [6] IdlM 7 IdlM 6 IdlM 5 IdlM 4 IdlM 3 IdlM 2 IdlM 1 IdlM 0
Data [7] IdlV 7 IdlV 6 IdlV 5 IdlV 4 IdlV 3 IdlV 2 IdlV 1 IdlV 0
Data [8] Reserved RACK CFO DM MP
Data [9] Reserved
Data [10] Masterless Produce Assembly Instance (0, 4, 101, 111)
Data [11]
Data [12] Masterless Produce EPR (ms)
Data [13]
Data [14] Masterless Produce PIT (ms)
Data [15]
Data [16] Peer 0 - Slot/MacID
Data [17] Peer 0 - Consume Message Length (bytes)
Data [18] Peer 0 - EPR (ms)
Data [19]
Data [20] Peer 1 - Slot/MacID
Data [21] Peer 1 - Consume Message Length (bytes)
Data [22] Peer 1 - EPR (ms)
Data [23]
Data [24] Peer 2 - Slot/MacID
Data [25] Peer 2 - Consume Message Length (bytes)
Data [26] Peer 2 - EPR (ms)
Data [27]
Data [28] Peer 3 = Slot/MacID
Data [29] Peer 3 - Consume Message Length (bytes)
Data [30] Peer 3 - EPR (ms)
Data [31]
Data [32] Peer 4 - Slot/MacID
Data [33] Peer 4 - Consume Message Length (bytes)
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
42 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Data Map - Configuration Assembly Instance 123 (Continued)
Message Size: 48 Bytes
Data [34] Peer 4 - EPS (ms)
Data [35]
Data [36] Peer 5 - Slot/MacID
Data [37] Peer 5 - Consume Message Length (bytes)
Data [38] Peer 5 - EPR (ms)
Data [39]
Data [40] Peer 6 - Slot/MacID
Data [41] Peer 6 - Consume Message Length (bytes)
Data [42] Peer 6 - EPR (ms)
Data [43]
Data [44] Peer 7 - Slot/MacID
Data [45] Peer 7 - Consume Message Length (bytes)
Data [46] Peer 7 - EPR (ms)
Data [47]
Where:
•
Filter = 0 to 65535
μ s (1000 = default)
•
FltM = Fault Mode (0 = Use Fault Value (default), 1 = Hold Last State)
•
FltV = Fault Value (0 = OFF (default), 1 = ON)
•
IdlM = Idle Mode (0 = Use Idle Value (default), 1 = Hold Last State)
•
IdlV = Idle Value (0 = OFF (default), 1 = ON)
•
RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34
(0 = Disabled (default), 1 = Enabled)
•
CFO = DeviceLogix Communication Fault Override of Outputs
1 = Enabled. When enabled, the DeviceLogix program will continue to control the outputs even in the event of a communication fault.
0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle settings in the event of a communication fault.
•
DM = Dependent Mode
1 = Enabled. When enabled, the DeviceLogix program execution will follow the
Run/Idle state of the owning processor.
•
MP = Masterless Produce
0 = Disabled (default), 1 = Enabled. When enabled, the module will begin producing data at powerup and after a connection with a controller is terminated.
•
EPR = Expected Packet Rate
•
PIT = Production Inhibit Time
•
Slot/MacID = Address of peer
Configuration of the modules must be done through RSNetWorx for
DeviceNet. See
for details.
Publication 1734-UM015A-EN-E - November 2009
Chapter
5
DeviceLogix for POINT I/O and ArmorPOINT
I/O on Ethernet/ControlNet
About This Chapter
In this chapter, you will learn how to perform the following tasks:
• Create a POINT I/O DeviceLogix module in RSLogix 5000 when using
EtherNet/IP or ControlNet adapters
• Identify the tags created in your program for your use
• Use RSNetworx for DeviceNet to configure the POINT I/O
DeviceLogix module
Add a POINT I/O
DeviceLogix Module to
RSLogix 5000
To add a POINT I/O DeviceLogix module to RSLogix 5000, do the following.
1.
In the I/O Configuration tree, find the adapter.
In this example, we will be using the 1734-AENT with the
1734-8CFGDLX. The same procedure applies if you are using an
ArmorPOINT I/O DeviceLogix module, or if the network is
ControlNet.
2.
Right-click the Point I/O Chassis and select New Module.
43
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
44 DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
3.
Under Digital, double-click the Point I/O DeviceLogix module.
IMPORTANT
If you cannot find the module in the Select Module dialog box, you will need to install the Add-On Profile (AOP) for the module.
You can download the AOP from http://www.rockwellautomation.com/support/downloads.html
.
The following dialog box appears.
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet 45
4.
Enter the slot number in the Slot box.
It is not possible to make a Rack connection to the Point I/O
DeviceLogix module. The connection must be a direct one.
On the Connection tab, you can change the Requested Packet Interval
(RPI), the default is 20 ms.
The Module Info tab will display the status and identity information of the module when the module is online.
There is no tab for configuration. Configuration of the Point I/O
DeviceLogix modules is done only using RSNetworx for DeviceNet.
See Chapter 6 for more details.
RSLogix 5000 will create the following input tags:
• AdapterName:SlotNumber:I.Data
• AdapterName:SlotNumber:I.LogicDefinedData
• AdapterName:SlotNumber:I.Status.LogicEnabled
• AdapterName:SlotNumber:I.Status.Owned
• AdapterName:SlotNumber:I.PeerMissing
• AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]
RSLogix 5000 will create the following output tags:
• AdapterName:SlotNumber:O.Data
• AdapterName:SlotNumber:O.LogicDefinedData
• AdapterName:SlotNumber:O.LogicDefinedIntData[0...7]
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
46 DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
I/O Tags
The following table lists the input tags and their descriptions.
Input tags and their descriptions
Tag
Data
LogicDefinedData
LogicEnabled
Owned
PeerMissing
LogicDefinedData[]
Description
This will contain the state of eight I/O points. See
details.
These eight bits are assigned using the Network Output Bit tags in the DeviceLogix program.
When set, the DeviceLogix program is running.
When set, the module is owned by a master.
Each bit represents one of the eight possible peers. If a bit is set, the data from that peer is missing or invalid.
These eight values are assigned using the Network Output
Word tags in the DeviceLogix program.
The following table lists the output tags and their descriptions.
Output tags and their descriptions
Tag
Data
Description
This value is sent by the master to set the output state of the eight output points. This can be overwritten if the Devicelogix program is controlling the outputs (Logic Enable On).
See
for details.
LogicDefinedData These eight bits can be used in the DeviceLogix program with the Network Input Bit tags.
LogicDefinedIntData[] These eight values can be used in the Devicelogix program with the Network Input Word tags.
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet 47
Launch RSNetworx for
DeviceNet to Configure the
Module
The Point I/O DeviceLogix module can only be configured using RSNetWorx for DeviceNet.
The following example assumes that the module is configured while it is online. If the module is configured offline, then apply the same procedure when you download the contents of the DNT file to the I/O module.
To configure the module:
1.
Start RSNetworx for DeviceNet.
2.
Go online by doing one of the following:
• Click the Online button.
• On the Network menu, click Online.
• Press <F10>.
The RSLinx Browse window appears.
3.
Navigate the tree down to the EtherNet/IP or ControlNet Point I/O or
ArmorPOINT I/O adapter.
4.
Expand the tree branch for the adapter.
You should see two additional ports. The first is the backplane, and the second is a DeviceNet port. Physically they are the same port, which is the backplane.
Publication 1734-UM015A-EN-E - November 2009
48 DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
5.
Select Pointbus Port, DeviceNet and click OK.
RSNetWorx automatically browses the network to discover all the participating modules.
Publication 1734-UM015A-EN-E - November 2009
IMPORTANT
Note the online path in the Messages window at the bottom half of the screen. This path will be saved in the DNT file. To open the file, select Properties on the Network menu.
6.
If you are configuring the module offline, you must download the configuration to the module after you go online. To do this, right-click the module’s icon and select Download to Device.
7.
To change the configuration of a module, double-click that module’s icon. Alternatively, you can right-click the icon and select Properties.
Details on configuring the module can be found in
Chapter
6
Configuring POINT I/O and ArmorPOINT I/O
DeviceLogix modules using RSNetworx for
DeviceNet
About This Chapter
In this chapter, you will learn how to do the following:
• Configure the module using the Configuration tab
• Use the data on the Parameters tab
• Configure peer communication
• Produce data without using a master
• Start the DeviceLogix Function Block Editor on the DeviceLogix tab
Configure the Module using the Configuration tab
The following diagram shows the Configuration tab of a POINT I/O
DeviceLogix module in RSNetWorx for DeviceNet. The Configuration tab of an ArmorPOINT I/O DeviceLogix module looks similar.
49
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
50 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
Parameters on the Configuration tab
Parameter Description
Off-to-On Delay This is the OFF to ON filter constant for all inputs on the module. A high signal must be present for this amount of time before the module will report an ON.
The value must be entered in microseconds (
μ s). The default value is
1000
μ s. The minimum value is 0 and the maximum is 65535
μ s.
The actual resolution of this value is milliseconds. The user selected value will be truncated at milliseconds. For example, 65535
μ s represents a 65 ms filter value.
On-to-Off Delay This is the ON to OFF filter constant for all inputs on the module. A low signal must be present for this amount of time before the module will report an OFF.
Output Fault
State
Output Fault
Value
The value must be entered in microseconds (
μ s). the default value is
1000
μ s. The minimum value is 0 and the maximum is 65535
μ s.
The actual resolution of this value is millisecond. User selected value will be truncated at milliseconds. For example, 65535
μ s represents a
65 ms filter value.
This parameter controls the action of each output during a communication fault.
0 = Go to Output Fault Value (default)
1 = Hold Last State
This parameter is ignored if DLX Fault Override is enabled.
The state of each output if a communication fault occurs. This parameter is ignored if the Output Fault State is set to Hold Last State or if DLX Fault Override is enabled.
0 = OFF (default)
1 = ON
Output Idle State This parameter controls the action of each output when in Idle state or Program mode.
0 = Go to Output Idle Value (default)
1 = Hold Last State
This parameter is ignored if DLX Fault Override is enabled.
Output Idle Value The state of each output when in Idle state or Program mode. This parameter is ignored if the Output Idle State is set to Hold Last State or if DLX Fault Override is enabled.
0 = OFF (default)
1 = ON
Auto Produce Enabling this parameter will allow the module to produce data without a master. This parameter is disabled by default.
If enabled, the module will begin to produce data on the backplane or network after power up and network address verification (Dup MAC check). The Owned bit in the produced assembly will be cleared (0).
A master may still make a connection to the module and then the
Owned bit will be set (1). If a master connection fails, the module will continue to produce data, but the Owned bit will be cleared (0).
The produced assembly, EPR, and PIT are described later in this table.
Auto Production may be important to support data to listening peers.
Publication 1734-UM015A-EN-E - November 2009
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 51
Parameters on the Configuration tab (Continued)
Parameter
DLX Dependent
Mode
DLX Fault
Override
Auto Produce
Assembly
Description
This parameter allows the logic in the module to be enabled or disabled according to the I/O connection status or the state of the owning processor. The default is disabled.
If Dependent Mode is enabled, the DeviceLogix program will be disabled when the owning processor is in program mode. When the processor transitions to RUN, the logic will automatically be enabled.
When an output is being locally controlled, its state is either controlled by the DeviceLogix program or by the Fault/Idle states.
Enabling this parameter allows the local logic to override the
Fault/Idle states in the event of a communication fault or transition to
Idle (Program) state. When this parameter is disabled (default) and a communication fault occurs or when in Idle (Program) state, all outputs, including those that are locally controlled, will go to the
Fault/Idle states. Enabling this parameter and using the "Network
Fault" status bit (Bus-off or Dup Mac Error) or COS/Cyclic Cnxn
Idle/Fault bits in the DeviceLogix program, a controlled stop or maintenance of a machine state can be achieved when communication is lost with a master.
When the Auto produce parameter is enabled, this parameter selects which assembly to produce:
000: 20-byte assembly (default)
004: 1-byte assembly
101: 20-byte assembly
111: 8-byte assembly
For details on the contents of the assembly, see I/O Data Assembly
For the list of I/O tags, see I/O Tags in
The 20-byte assembly contains all the data. The 8-byte assembly can be produced in one packet (non-fragmented).
Auto Produce EPR When the Auto Produce parameter is enabled, this parameter sets the
Expected Packet Rate. The units are milliseconds (ms). The default is
1000 ms. The maximum is 65535 ms and the minimum is 0 ms.
When Auto Produce is enabled, the module produces data at every change of state (COS) or when the EPR timer expires.
Auto Produce PIT When the Auto Produce parameter is enabled, this parameter sets the
Product Inhibit Time. The units are milliseconds (ms). The default is
1 ms. The maximum is 65535 ms, and the minimum is 0 ms.
If a Change of State occurs and the PIT has not expired, the message will wait until the PIT has expired. This can be used to prevent one module from using all the available network bandwidth.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
52 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
Parameters on the Configuration tab (Continued)
Parameter Description
Peer #xx MacID There are eight (0…7) peer Mac ID parameters. Each one defines the
MacID or Slot Number of the peer from which this module will consume data. The default is "No Connection."
Peer #xx Size
Peer #xx EPR
You can enter the MacID or Slot number, 0…63, or a relative offset from the address of the module (-4 to +4).
Once a valid MacID is set, Peer Exists = 1 in DeviceLogix program.
See more details on peer configuration later in this chapter and in
There are eight (0…7) Peer Size parameters. Each one defines the size in bytes of the message received from the peer. The default and maximum value is 24 bytes. The minimum is 1 byte. See
for peer message sizes of POINT I/O and ArmorPOINT I/O modules.
If the received message size does not match the Peer Size value, the data will be considered invalid and the appropriate error bits will be set (Produced assembly: Peer Missing = 1. In DeviceLogix program:
Peer Data valid = 0.)
This parameter is ignored if the Peer MacID is set to "No Connection."
There are eight (0…7) Peer EPR parameters. Each one defines the
Expected Packet Rate in milliseconds (ms) of the peer connection. If this module does not receive valid data from a peer for 4 times the
EPR, the appropriate error bits will be set (Produced assembly: Peer
Missing = 1. In DeviceLogix program: Peer Data Valid = 0.)
The default value is 1000 ms. The maximum is 65535 ms and the minimum is 0 ms.
This parameter is ignored if the Peer MacID is set to "No Connection."
Publication 1734-UM015A-EN-E - November 2009
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 53
Parameters on the Parameters tab
Parameters on the Parameters tab
Parameter
Data -
Input/Output
Network Status
Override
Comm Status
Override
Peer Status
Description
This parameter is the same as the first byte of the Produced I/O assembly. It is the state of the eight I/O points.
Data - Consumed
Bits
Consumed
Analog Word #xx
This parameter is the same as the second byte of the Consumed I/O assembly. It is the state of the Consumed Network Bits or User
Defined Bit Data.
These eight parameters are from the Consumed I/O assembly. They contain the state of the Consumed Network Words or User Defined
Word Data.
This is a legacy Parameter for DeviceLogix and ZIP. It shows the state of Network Status Override.
This is a legacy Parameter for DeviceLogix and ZIP. It shows the state of Communication Status Override.
The eight bits in this parameter are used to determine the connection status of a peer.
ZIP Security Key This is a legacy parameter for DeviceLogix and ZIP (Zone Interlock
Parameters). The ZIP Security Key is a 16-bit value used to uniquely identify a module and its configuration. This value can be used in the
DeviceLogix program to verify that the configuration of a peer has not changed. More details on using the ZIP Security Key will be provided Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
54 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
Parameters on the Parameters tab (Continued)
Parameter
Zone Control
Sequential Auto
Address
Broadcast Baud
Rate
Broadcast
AutoBaud
Description
This is a legacy parameter for DeviceLogix and ZIP. It shows the state of Zone Control, whether it is enabled or disabled.
This parameter should only be used in a DeviceNet system. It is used to set another POINT I/O or ArmorPOINT I/O module to the right of this module to a node address one greater than this module.
This message will propagate to all modules to the right. Each address will change to one greater than its neighbor.
This parameter should only be used in a DeviceNet system. It is used to set another POINT I/O or ArmorPoint I/O module to the right of this module to the desired baud rate.
1: 125 kHz
2: 250 kHz
3: 500 kHz
The only way a module can achieve a 1 MHz baud rate is by using the
AutoBaud feature.
This parameter should only be used in a DeviceNet system. It is used to set another POINT I/O or ArmorPoint I/O module to the right of this module to Autobaud (enable) or used to save the baud rate (disable).
Configure Peer
Communication
This section will describe how to configure the POINT I/O and ArmorPoint
I/O DeviceLogix module to consume data from peers. The POINT I/O
DeviceLogix module can use data from other modules to affect the
DeviceLogix program.
The module can perform the following functions:
• Get Change-Of-State (COS) data from up to eight I/O modules or peers.
• Each peer can have up to 24 bytes of data.
• Each peer has its own expected packet rate.
• Each peer has its own status bit that can be used in logic.
• The data from each peer can be digital (bit), analog (16-bit words), or a mixture of both.
The following functions are not supported:
• Make a connection.
• Configure a peer.
• Control outputs on a peer.
• Listen to a peer that is on another network.
The module can only listen to peers on the backplane or local
DeviceNet network.
Publication 1734-UM015A-EN-E - November 2009
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 55
• Consume data from a safety connection
The module can consume data from a safety module with a standard connection.
• Consume data sent to a peer from a master.
Set Up Peer Communication Parameters
For each peer, you need to configure a set of parameters.
Here are the three parameters in their default settings (no peer data).
Parameter number
31
39
65
Parameter name
Peer#0 MacID
Peer#0 Size
Peer#0 EPR
Parameter description
Slot number
Input data size
Time out value
Default value
No connection
24 bytes
1000 ms
Example
To listen to the data from a 1734-IB4 module in the first slot (node 1), you can configure the parameters in the following way:
Parameter number
31
39
65
Parameter name
Peer#0 MacID
Peer#0 Size
Peer#0 EPR
Parameter description
Slot number
Input data size
Expected packet rate
Value
1
1 byte
100 ms
The 1734-IB4 is "Peer#0". Enter its produced data size, "1" as its input data size. If the module does not consume data from this peer in four times the expected packet rate (EPR), which is 400 ms in this case, the Peer #0 connection fault bit will be set.
The contents of the data are mapped to the Peer#0 data table.
To use the data from the 1734-IB4 in the DeviceLogix editor, click to place a Boolean bit input on the function block sheet, and select the desired bit to use in logic under the "Network Boolean Input" category.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
56 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
Select bit0 of byte0. With up to 24 bytes of data available for mapping, the last entry is "Peer#0 (Byte 23, Bit7)." 192 bits per peer can be used for a total of
1536 data bits.
You are highly encouraged to use the connection status bits to verify that the device is receiving valid data from the peer. They are located under the Status
Input category of the "bit input" I/O tags.
In our example, "Peer#0 Data Valid" will be set to 1 when the POINT I/O
DeviceLogix module is consuming data from the peer that is timely (which is, within the EPR timeout) and of the correct length. No other checking is done on the data by the module.
"Peer#0 Exists" is set to 1 when a peer connection has been configured.
Analog data can also be used in a peer connection. If a 1734-IE4C module is located in the third slot, you can configure the POINT I/O DeviceLogix module like this:
Parameter number
32
40
66
Parameter name
Peer#0 MacID
Peer#0 Size
Peer#0 EPR
Parameter description
Slot number
Input data size
Expected packet rate
Default value
3
12 bytes
500 ms
Publication 1734-UM015A-EN-E - November 2009
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 57
The 1734-IE4C has an input message that looks like this:
Default Data Map for the 1734-IE4C Analog Input Module
Message size: 12 bytes
Byte
Produces
(scanner
Rx)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input Channel 0 High Byte
Input Channel 1 High Byte
Input Channel 2 High Byte
O
R
Input Channel 3 High Byte
Status Byte for Channel 1
O
R
U
R
H
H
A
LL
A
H
A
Status Byte for Channel 3
L
A
U
R
H
H
A
LL
A
H
A
L
A
C
M
C
M
Input Channel 0 Low Byte
Input Channel 1 Low Byte
Input Channel 2 Low Byte
Input Channel 3 Low Byte
Status Byte for Channel 0
CF O
R
U
R
H
H
A
LL
A
H
A
L
A
Status Byte for Channel 2
CF O
R
U
R
H
H
A
LL
A
H
A
L
A
C
M
C
M
CF
CF
To use the analog data from channel 2, click to place an analog bit input on the function block sheet in the DeviceLogix editor.
Channel 2 is mapped to Word 2. Select this as shown below. For help on mappings, see
To use the Over-range bit of channel 1, you can use "bit input" I/O tag and select Peer#1, byte 9, bit 7.
Again, it is best to use the Peer Connection Status bits (Peer#1 Data Valid and
Peer#1 Exists) to validate the data before using it.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
58 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
If the POINT I/O DeviceLogix module is consuming data from a peer that has double precision analog data (32-bit), like the 1734-VHSC24, the data can be used in logic by addressing the high-word and low-word separately. By using math functions (multiply and add), the two words can be combined into one value.
See Very High Speed Counter Input Modules
.
Produce Data Without
Using a Master
Publication 1734-UM015A-EN-E - November 2009
With the POINT I/O DeviceLogix module (and other DeviceLogix modules that support "ZIP"), you can send data to another listener without a network master to set up the connection.
The following parameters are used to configure this feature:
Parameter number
74
75
76
99
Parameter name
Auto Produce
Auto Produce EPR
Auto Produce PIT
Auto Produce
Assembly
Parameter description
Default value
Disabled
1000 ms
1 ms
20-byte produced
(default)
Soon after power-up and getting online, when Auto Produce is enabled, the
POINT I/O DeviceLogix module begins producing change-of-state (COS) type I/O data on the connected network or backplane. It produces the selected "Auto Produce Assembly" at the selected "Auto Produce EPR"
(Expected Packet Rate).
The Auto Produce Assembly data can be:
• 20 bytes of produced data (it sends all possible data)
• 8 bytes of produced data (this does not require the fragmentation protocol, so it will reduce network bandwidth)
• 1 byte of produced data (only the state of the 8 I/O)
A description of these assemblies can be found in Chapter 4.
The Auto Produce EPR sets the cyclic rate at which data is produced if there is no change of I/O state. If there is a change of state, new data is produced immediately. If data changes often, to reduce change-of-state traffic on the network, you can increase the Auto Produce Production Inhibit Time (PIT).
For example, if the PIT is set to 10 ms, the quickest the module can produce data is once every 10 ms even if there is a change of state.
Auto Produce is only recommended on a DeviceNet network in situations where a master is not required.
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 59
Due to the fact that there is no master to verify the connection and the configuration of each module, it is recommended that the ZIP Security Key be produced in the data. This unique number is calculated using the identity of the module and the present configuration. The ZIP Security Key value is in the
DeviceLogix Logic Editor, under the Analog Input I/O tags.
The output of the Analog Input I/O tag can be wired to the input of an
Analog Output I/O tag to map it into the Produced Assembly Image:
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
60 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
In this example, the ZIP Security Key is mapped to Network Output Word 3.
Any module receiving this data should verify the constant value.
For example:
The ZIP Security Key constant is added using the ellipses button of the NEQ function block. This output can be used to condition the execution of other function blocks using the Enable input.
Note that there could be an "unsigned value to signed value conversion" when the ZIP Security Key is displayed in the Logic Editor, which leads to a mismatch of displayed value. However, the value is consistent in HEX format.
Publication 1734-UM015A-EN-E - November 2009
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 61
Start the Function Block
Editor
To start the Function Block editor, do the following.
1.
Go to the property dialog box of the module.
2.
Click the DeviceLogix tab, followed by Start Logic Editor.
On this tab, you can enter the Author’s name, revision, and description of the logic program. These are generic text fields. They are saved in the DNT file created by the RSNetworx for DeviceNet application.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
62 Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet
If a program is saved in the DNT file, it will be displayed.
Publication 1734-UM015A-EN-E - November 2009
To learn how to use this editor, refer to Chapter 2 of the DeviceLogix System
User Manual, publication RA-UM003 . For specific uses of the POINT I/O
and ArmorPoint I/O DeviceLogix modules, proceed to Chapter 7
.
Chapter
7
DeviceLogix Capabilities
About This Chapter
This chapter lists the DeviceLogix capabilities supported by the POINT I/O
DeviceLogix and ArmorPOINT I/O DeviceLogix modules.
63
Function Block Instructions
The module can support up to 144 function blocks. These function blocks are categorized in the following manner:
• Process
• Filter
• Select/Limit
• Statistical
• Timer/Counter
• Comparison
• Compute
• Move/Logical
Process Category
The process category includes the following instruction types:
• Alarm
• Timing Diagnosis
Alarm
The Alarm function block initiates an alert based on the comparison between the input value and the threshold. The output of the DeviceLogix Alarm function block contains these alerts.
• High-High alarm
• High alarm
• Low alarm
• Low-Low alarm
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
64 DeviceLogix Capabilities
Publication 1734-UM015A-EN-E - November 2009
Timing Diagnosis
The DeviceLogix Timing Diagnosis function block object determines whether the occurrence of the expected event is within the preset timing interval.
For more information on the Alarm and Timing Diagnosis function blocks, refer to the DeviceLogix System User Manual, publication RA-UM003 .
Filter Category
The Filter category includes a single instruction type: Low Pass Filter.
Low Pass Filter
The DeviceLogix Low Pass Filter (LPF) function block provides a filter to attenuate input frequency above the cutoff frequency.
The module supports only two instances of the LPF function block.
For more information on the Low Pass Filter function block, refer to the
DeviceLogix System User Manual, publication RA-UM003 .
Select Limit Category
The Select Limit category includes the following instruction types:
• Select
• High Low Limit
Select
The DeviceLogix Select function block identifies one input within the selected two function block inputs as the output according to the value of the selector.
The Select function block is outlined in detail as follows.
IF Selector = 1
Output = value of Input 2
IF Selector = 0
Output = value of Input 1
END
DeviceLogix Capabilities 65
High/Low Limit
The DeviceLogix High/Low Limit function block limits the input value within the specified data range. The High/Low Limit function block is outlined in detail as follows.
IF value of Input > HighLimit
Output = HighLimit
ELSE IF value of Input < LowLimit
Output = LowLimit
ELSE
Output = Input
END
For more information on the Select and High/Low Limit function block, refer to the DeviceLogix System User Manual, publication RA-UM003 .
Statistical Category
The statistical category includes a single instruction type: Moving Average.
Moving Average
IMPORTANT
The module supports only two instances of the Moving Average
(MAV) function block.
The DeviceLogix Moving Average function block calculates a time average value for the input signal.
For more information on the Moving Average function block, refer to the
DeviceLogix System User Manual, publication RA-UM003 .
Timer/Counter Category
The Timer/Counter category includes the following instruction types:
• On-Delay Timer
• Off-Delay Timer
• Pulse Timer
• Up Counter
• Up/Down Counter
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
66 DeviceLogix Capabilities
For more information on the Timer/Counter category, refer to the
DeviceLogix System User Manual, publication RA-UM003 .
Publication 1734-UM015A-EN-E - November 2009
Comparison Category
The Comparison category includes basic comparison functions, including these instruction types:
• Greater Than (GRT)
• Greater Than or Equal To (GEQ)
• Equal (EQU)
• Not Equal (NEQ)
• Less Than (LES)
• Less Than or Equal (LEQ)
• Mask (MEQ)
Operation rules [all except Mask (MEQ)]
The conditions and outputs of each function block are described below.
Function Block
Type
Condition
Greater Than (GRT) Source A > Source B
Greater Than or
Equal (GEQ)
Equal (EQU)
Not Equal (NEQ)
Source A <= Source B
Source A >= Source B
Source A < Source B
Source A == Source B
Source A != Source B
Source A != Source B
Less Than (LES)
Less Than or Equal
(LEQ)
Source A == Source B
Source A < Source B
Source A >= Source B
Source A <= Source B
Source A > Source B
Output
0
1
0
1
0
1
0
1
0
1
0
1
Operation rules [Mask (MEQ) only]
The Mask process is outlined below:
IF (Source AND Mask) == (Compare AND Mask)
Output is Set
ELSE
DeviceLogix Capabilities 67
Output is Clear
END
For more information on the Comparison category, refer to the DeviceLogix
System User Manual, publication RA-UM003 .
Compute Category
The Compute category includes fundamental arithmetic operations, including the instruction types:
• Add (ADD)
• Multiple (MUL)
• Subtract (SUB)
• Divide (DIV)
• Modulus (DINT)
• Modulus (REAL)
• Absolute (ABS)
• Negative (NEG)
• Square Root (SQR)
• Power (XPY)
Operation rules [all except Mask (MEQ)]
The conditions and outputs of each function block are described below.
Function Block
Type
Add (ADD)
Multiply (MUL)
Subtract (SUB)
Divide (DIV)
Modulus (DINT)
Modulus (REAL)
Absolute (ABS)
Output
= Source A + Source B
= Source A x Source B
= Source A - Source B
= Source A / Source B
= Source A - (Source A / Source B) x Source B
= Source A - (DINT)(Source A / Source B) x Source B
= Absolute value of (Source A)
Negative (NEG) = -Source A
Square Root (SQR) = Square root of (Source A)*
Power (XPY) = Source A * * Source B
* If Source A is negative, the operation takes the absolute value of Source A before calculating the square root and no fault is reported.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
68 DeviceLogix Capabilities
Publication 1734-UM015A-EN-E - November 2009
For more information on the Compute category, refer to the DeviceLogix
System User Manual, publication RA-UM003 .
Move/Logical Category
The Move/Logical category includes fundamental bit type logic operations, including the instruction types:
• Boolean
• AND (BAND)
• Not AND (BNAND)
• OR (BOR)
• Not OR (BNOR)
• Exclusive OR (BXOR)
• Exclusive Not OR (BXNOR)
• NOT (BNOT)
• Latch
• Set Latch (SETD)
• Reset Latch (RESD)
Boolean Functions
The Boolean functions are as follows. Note that the number of inputs can be changed on some functions but are limited to a maximum of four. The latch instruction type has two fixed inputs, "Set" as input 1 and "Reset" as input 2.
Function Block Type
AND (BAND)
Not AND (BNAND)
OR (BOR)
1
0
0
1
1
0
0
1
0
1
1
Input 1
0
1
0
1
0
1
0
1
0
1
0
1
Input 2
0
0
0
1
1
1
1
1
1
0
0
1
Output Value
0
DeviceLogix Capabilities 69
Function Block Type
Not OR (BNOR)
Exclusive OR (BXOR)
Exclusive Not OR (BXNOR)
NOT (BNOT)
(1) 0
1
1
1
0
0
1
1
0
0
1
1
Input 1
0
0
Input 2
0
1
0
1
0
1
0
1
0
1
0
1
N/A
N/A
(1)
The Input number can be set in a property page; the default number is 2. BNOT has only one input.
1
0
0
1
1
0
1
0
0
1
0
0
Output Value
1
0
Latch Functions
There are two kinds of Latch functions: Set Dominant Latch (SR) and Reset
Dominant Latch (RS). Unlike the Latch in RSLogix 5000, DeviceLogix Latch requires the Reset binding. So the Set/Reset appears in pair and the RS type and SR type have different element order. See its truth table below.
Function Block Type Reset
SETD (Set Dominant)
0
1
1
0
1
0
0
1
Set
1
0
1
0
1
0
1
0
1
1
1
0
1
0
0
Value at time + t
0
0
Value at time + t
0+1
0
1
0
1
1
1
0
1
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
70 DeviceLogix Capabilities
Function Block Type Reset
RS (Reset Dominant)
0
1
1
0
1
0
0
1
Set
1
0
1
0
1
0
1
0
1
1
1
0
1
0
0
Value at time + t
0
0
Value at time + t
0+1
0
1
0
0
1
1
0
0
For more information on the Move/Logical category, refer to the
DeviceLogix System User Manual, publication RA-UM003 .
Logic Execution Time
The execution time is dependent on the total number of function blocks used in the entire DeviceLogix program.
Number of Function Blocks
0…40
41…100
101…144
Expected Execution Time (ms)
1
2
3
The module will execute the entire logic program before applying the outputs.
The module follows these steps:
1.
Sample all inputs (hardware, network, peer).
2.
Execute logic.
3.
Apply all outputs (hardware, network).
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix Capabilities 71
Digital Inputs to Function Blocks
When the Bit Input I/O tag connector is added to the DeviceLogix editor, the following input options are available:
Hardware
Discrete Input 0 through Discrete Input 7 are the states of the eight I/O points on the module.
Status
The following is a list of status bits that can be selected. Most will only be used in a DeviceNet network:
• Explicit Msg Cnxn Exists
• Polled Cnxn Exists
• COS/Cyclic Cnxn Exists
• Polled Cnxn Fault
• COS/Cyclic Cnxn Fault
• Polled Cnxn Idle
• Network Fault
• Minor Module Fault
• Bit-Strobe Cnxn Exists
• Bit-Strobe Cnxn Fault
• Bit-Strobe Cnxn Idle Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
72 DeviceLogix Capabilities
If you are using the EtherNet/IP or ControlNet adapter, it is suggested that you use the COS/Cyclic connection status bits to determine the health of the connection with a master.
The following are the status bits for the eight Peer connections:
• Peer#X Data valid
• Peer#X Exists
Use the Exists bits to determine if a connection is configured, and the Data
Valid bit to check if the data from the peer has been received in the expected time (EPR) and with the expected data size.
Network
Network Input 0 through Network Input 7 are sent to the DeviceLogix program through the Output Data assembly byte 1. In RSLogix 5000, the tag name for these bits is UserDefinedBitData.
Reserved Bit 8 through Reserved Bit 31 are legacy bits and should not be used.
There are many Peer#X (Byte X Bit X) bits. This is a mapping of 24-byte bit data for the eight peer connections. You need to know the Input Memory map
of each of the peers in order to use this data. See Appendix A
.
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix Capabilities 73
Analog Inputs to Function Blocks
When the Analog Input I/O tag connector is added to the DeviceLogix editor, the following options are available.
Network Analog Input
Network Input Word 0 through Network Input Word 7 are sent to the
DeviceLogix program through the Output Assembly. In RSLogix500, the tag name for these words is UserDefinedWordData[0..7].
The ZIP Security Key defines a unique number that can be sent to a peer to verify the identity and configuration of the module. The ZIP key can be directly tied to a Network Output Word in the DeviceLogix program.
Peer#x (Word x)
There are eight groups of peer data (0…7) and 12 words within each group.
These are the eight peers and up to 24 bytes of data mapped from each peer.
You need to know the input data map from each peer to know what data to use. See
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
74 DeviceLogix Capabilities
Digital Outputs from Function Blocks
Hardware
Discrete Output 0 through Discrete Output 7 are the eight hardware outputs available on the module. If these tags are unused (that is, not mapped in the
DeviceLogix program), then there is a virtual mapping from the Data Byte
Output Assembly to the output point. This means that the output is under control of the owning processor. If the Discrete Output is mapped in logic, it is controlled by the module.
Virtual Connection if Output Not Used in Logic
Consume Data Assembly
Byte 0 7 6 5 4 3 2 1 0
Discrete Output 0
44953
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix Capabilities 75
This flowchart shows the process and priority the module follows when updating each Digital Output Point (DOP). The process considers module states such as Network Fault and Run/Idle, configurable parameters such as
Network Fault Override, and Logic states such as Logic Enabled and Force.
Output Ownership (Value Source Selector Behavior for Bound Outputs)
Update
Output
Network
Fault
Yes
Explicit Message Request to change DOP value
EM
I/O Message to change DOP value
I/O
Comm
Override
Yes
Network
Fault
Override
Yes
Return Object State
Conflict Error
Ignore Message
Fault
Fault Exists
Idle
Receive Idle
Run
DOP in RUN mode
Logic
Enabled
Disabled
Use Idle Action and Idle Value
DOP in
Available State
Available
Perform Logic
Program
Clear DOP Value
Apply Force Value
Use Fault Action and Fault Value
Apply Value to DOP
End
DOP: Digital Output Point
EM: Explicit Message
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
76 DeviceLogix Capabilities
Network
Network Output Bit 0 through Network Output Bit 7 are mapped to the Input
I/O Assembly byte 1. These bits can be sent to the owning processor or to other peers. In RSLogix 5000, the tag name is UserDefinedBitData.
Analog Outputs from Function Blocks
Network
Network Output Word 0 through Network Output Word 7 are mapped to the
Input I/O Assembly. These words can be sent to the owning processor or to other peers. In RSLogix 5000, the tag name is UserDefinedWordData[0..7].
Publication 1734-UM015A-EN-E - November 2009
Enable Line feature
DeviceLogix Capabilities 77
The Enable Line feature can be supported by each instruction type in the
Function Block Editor. When an instruction supports the Enable Line feature, that particular instruction can only be executed when Enable Line is on; otherwise, that instruction maintains the data from the last data scan. In this manner, functions can be executed conditionally based on the state of the
Enable input. Under normal conditions, the Enable output will have the same value as the input, passing the enable information to the next instruction.
Certain error conditions that occur within the processing of a function block may cause the Enable output to go false.
If the Enable Line feature is used, EnableIn can be connected to an input I/O tag or the output of another function block. The EnableIn input will retain the value of the source that it is bound to.
If the Enable Line feature is not needed, the EnableIn input can use a constant value which can be set on each instruction’s property page. By default, this constant will allow execution of the function.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
78 DeviceLogix Capabilities
Offline and Online Editing
Editing of the configuration and DeviceLogix program can be done off-line and saved in the DNT file created by RSnetWorx for DeviceNet. The changes, however, must be manually downloaded to the module while online. When using RSLogix 5000 with an EtherNet/IP or ControlNet adapter, the forward open to the DeviceLogix module does not contain any configuration information. The configuration must be sent via RSNetWorx for DeviceNet while online.
Online
DNT File
Module
RSNetWorx for DeviceNet
The I/O module will save the configuration and DeviceLogix program locally
(inside the module). You will only need to download the configuration once. If you replace the device, you need to download the configuration to the new module.
Before the DeviceLogix program executes, it must be enabled. You can do this using the Editor while online. For details, see
.
Alternatively, you can use the owning processor to enable the program. For details, see
Publication 1734-UM015A-EN-E - November 2009
Enable/Disable Logic
DeviceLogix Capabilities 79
For logic to execute, it must be enabled. While editing online with RSNetWorx for DeviceNet, you can enable logic.
Logic Enable On
Use the Logic Enable On function to notify the device to start processing the stored logic diagram. To set Logic Enable On, select Communications > Logic
Enable On.
Logic Enable Off
Use the Logic Enable Off option to notify the device to stop executing the logic program. When you select this option, the device enters an idle state, turning off the Logic Enable Bit in the produced data. The Logic Enable bit in the Produced I/O assembly of the device reflects a 0 or 1 for Logic Enable
Off or Logic Enable On. To set Logic Enable Off, select Communications >
Logic Enable Off.
Dependent Mode
Logic will also be enabled or disabled if the Dependent Mode parameter is
Enabled. In this case, logic will execute following the state of the owning connection. When the connection is in RUN, the logic is enabled. When the connection is in Idle, Fault, or non-existent, logic is disabled.
You can also enable or disable logic through explicit messages from the
owning controller. See Messaging
.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
80 DeviceLogix Capabilities
Messaging
There are certain parameters that you may want to SET or READ from the module that are not part of the I/O Assemblies. Those parameters are still available through messaging.
This section contains advanced user information. You should understand the
CIP object model and be familiar with the terms Service, Class, Instance, and
Attribute.
This section discusses how to SET and READ information from the Timer and Counter function blocks and how to enable and disable logic with the
Logic Supervisor Object.
The first thing that is important to know is that each function block has a handle or an instance number. This instance number is assigned by the editor, it can be found in the upper left corner of the function block.
Function block instances
Publication 1734-UM015A-EN-E - November 2009
The instance number can change if you edit the program. It may also be different from module to module – be very careful to verify the instance number before using messaging.
To access the information, you need the “address” of that information. The address is made up of the Class Code, the instance (as discussed above), and the attribute.
DeviceLogix Capabilities 81
The following table shows this data for the Logic Supervisor, Timer, and
Counter function blocks.
Data Length Function Block Class
Code
Instance
Logic Supervisor 0x30E 1
Timer Function
Block
0x30A Displayed in editor
Attribute
Logic Enable (0x01)
Preset Time (0x04)
Elapsed Time (0x07)
Time Base (0x08)
Counter Function
Block
0x309 Preset Value (0x05)
Count Value (0x07)
Maximum Input
Frequency (0x08)
1 byte
2 bytes
2 bytes
1 byte
0 = 1 ms (default)
1 = 10 ms
2 bytes
2 bytes
2 bytes
Note that there is only one Logic Supervisor and its instance is always "1".
If you are using RSLogix 5000, you can send a message by using the MSG instruction.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
82 DeviceLogix Capabilities
To configure the message, do the following:
1.
Click the ellipsis (…) button.
The Message Configuration dialog box appears.
2.
Set the message type to “CIP Generic.”
3.
Set the Service Type to “Set Attribute Single” to set data or “Get
Attribute Single” to read data.
4.
Enter the Class value in hexadecimal from the table (“30A” is the Timer function block).
5.
Copy the Instance number from the upper left corner of the Timer function block to which you are sending the message.
6.
Enter the Attribute number in hexadecimal (“4” is the Preset Time).
7.
Verify that the Source Element and Source Length (in bytes) is correct.
8.
Click the Communication tab.
9.
If you are using EtherNet/IP or ControlNet, click Browse to navigate to the DeviceLogix module.
If you are using DeviceNet, browse to the DeviceNet Scanner
(1756-DNB) and enter Port "2" (for the DeviceNet port) and the node number of the DeviceLogix module (node "4" in the following example) separated by commas.
DeviceNet scanner name, port, node address
Publication 1734-UM015A-EN-E - November 2009
Chapter
8
Troubleshooting
About This Chapter
This chapter provides information about module diagnostics, and about troubleshooting with the following indicators:
• Module status
• Network status
• DeviceLogix status
• Power indication
• I/O POINT status (ON/OFF/fault or diagnostic)
In addition, the following troubleshooting scenarios are provided:
• Peer connection is not working
• Configuration or DeviceLogix program cannot be downloaded to the module
• Module’s DeviceLogix program exits the Run mode unexpectedly
About Module Diagnostics
All status and diagnostic information (strobed, polled, cyclic, or change-of-state) is reported back over the network communication adapter.
A single point of failure is detected and reported at the module and to the control system.
Module Status
Network Status
DeviceLogix Status
I/O Channel State
Module
Status
Network
Status
NODE:
Device
Logix
Status
4
5
6
1734
8CFGDLX
7
44759
Node-level diagnostics:
•
Module Status indicator indicates the health of the module.
•
Network Status indicator indicates the status of the communication link.
•
DeviceLogix indicator indicates the state of the
DeviceLogix program.
•
I/O point indicator indicates I/O (ON/OFF or fault/diagnostic) status.
83
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
84 Troubleshooting
Status Indicators of POINT
I/O Module
See the figure and tables that show how to interpret the status indicators.
1734-8CFGDLX Module
Module Status
Network Status
Module
Status
Network
Status
NODE:
DeviceLogix Status
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Device
Logix
Status
4
Status of I/O 4
5 Status of I/O 5
6
Status of I/O 6
7
1734
8CFGDLX
Status of I/O 7
44759
Module Status
Indication Probable Cause
Off
Green
No power applied to device.
Device operating normally.
Flashing green
Device needs commissioning due to missing, incomplete or incorrect configuration.
Flashing red Recoverable fault.
Red
Recommended Action
Apply power to device.
None.
Configure device properly.
1. Cycle power to device.
2. If condition persists, replace device.
Replace device.
Flashing red/green
Unrecoverable fault may require device replacement.
Device is in self-test.
None.
Publication 1734-UM015A-EN-E - November 2009
Troubleshooting 85
Network Status
Indication Probable Cause
Off Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Green
Flashing green
Device is online and has connections in the established state.
Device is online but has no connections in the established state.
Flashing red One or more I/O connections are in the timed-out state.
This could also mean a peer is not producing data at all, or it is not configured correctly.
Red Critical link failure - failed communication device. Device detected error that prevents it communicating on the network.
Flashing red/green
Device is in self-test.
Recommended Action
Apply power to device, wait for dup_MAC_id to complete, and correct, as needed.
None.
None .
Check I/O connection with master. Verify peers are present and configured properly.
Verify that adapter and terminal bases are properly installed, and reinstall, as needed.
None.
DeviceLogix Status
Indication Probable Cause
Off DeviceLogix program is not controlling outputs.
Green
Flashing green
DeviceLogix program is controlling outputs.
At least one input in DeviceLogix program is forced on/off.
Recommended Action
None.
None.
None.
I/O Status
Indication Probable Cause
Off Input or output is in the OFF state.
Yellow Input or output is in the ON state.
Recommended Action
None.
None.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
86 Troubleshooting
Status Indicators of
ArmorPOINT I/O Modules
See the figure and tables that show how to interpret the status indicators.
1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23
1738-8CFGM12 shown
H
A
DLX
B
1738-8CFGDLXM12
24V DC Out
G
MOD
NET
C
D
F
E
2
3
0
1
4
5
6
7
Module Status Indicator
Network Status Indicator
I/O Status Indicators
44355
Module Status
Indication Description
Off
Green
No power applied to device.
Device operating normally.
Flashing green
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Red Unrecoverable fault – may require device replacement.
Flashing red Recoverable fault.
Flashing red/green
Device is in self-test.
Recommended action
Apply power to device.
None.
Configure device properly.
Replace device.
Cycle power to device.
If condition persists, replace device.
None.
Publication 1734-UM015A-EN-E - November 2009
Troubleshooting 87
Network Status
Indication Description
Off Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Green
Flashing green
Red
Device is online and has one or more
I/O connections in established state.
Device is online but has no connections in established state.
Flashing red One or more I/O connections are in the timed-out state.
Critical link failure – failed communication device. Device detected error that prevents it from communicating on the network.
Flashing red/green
Device is in self-test.
Recommended action
Apply power to device, wait for
MAC_id to complete, and correct, as needed.
None.
None.
Check for I/O module failure, and correct, as needed.
Verify that adapter and terminal bases are properly installed, and reinstall, as needed.
None.
DeviceLogix Status
Indication Description
Off DeviceLogix program is not controlling outputs.
Green
Flashing green
DeviceLogix program is controlling outputs.
At least one input in DeviceLogix program is forced on/off.
Recommended action
None.
None.
None.
I/O Status
Indication Description
Off
Yellow
I/O is inactive.
I/O is active and under control.
Recommended action
None.
None.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
88 Troubleshooting
Troubleshooting Scenarios
The following are scenarios you may encounter while using the modules.
Peer connection is not working
If the Network Status LED is flashing red, one or more connections to the device are broken or not functioning properly. If the device has been configured to consume data from peers, it is possible that the data size or data rate have not been configured correctly.
• Use the Peer Missing bits in the I/O assembly to check which peer connection is missing.
• Verify the configuration is correct. Upload from the module into
RSNetWorx for DeviceNet.
• Verify the Node number or Slot number is correct.
• Verify the connection size is correct.
• Increase the EPR (Expected Packet Rate).
• Verify that the owner of the connection to the peer (usually a scanner or controller) is receiving data. The DeviceLogix module cannot make a connection to a peer; it can only listen to COS (Change-of-State) I/O data going from the peer to the master.
Publication 1734-UM015A-EN-E - November 2009
Troubleshooting 89
Configuration or DeviceLogix program cannot be downloaded to the module
A DeviceLogix program and most configurable parameters cannot be changed while the DeviceLogix program is running or when an I/O connection is active.
• Inhibit the connection in RSLogix 5000 (if using EtherNet/IP and
ControlNet).
• Disable logic in RSNetWorx for DeviceNet before downloading.
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
90 Troubleshooting
• Clear the Node Active check box in RSNetWorx for DeviceNet (if using a DeviceNet scanner or DeviceNet adapter).
Publication 1734-UM015A-EN-E - November 2009
Module’s DeviceLogix program exits the Run mode unexpectedly
The module’s DeviceLogix program exits the Run mode unexpectedly. A possible reason may be that the ADR feature of the scanner is turned on and the ADR data of the module stored in the scanner is not consistent with what is on the module. When the scanner establishes connection to the module, it will verify the configuration in itself with what is in the module. Any mismatch would result in the scanner downloading its saved ADR data to the module.
• Check the ADR feature of the network scanner and verify if the configuration stored in the scanner is the most recent and correct version.
Appendix
A
Peer Data Maps
About This Appendix
This appendix contains information to help you use peer data from
POINT I/O and ArmorPOINT I/O modules in your DeviceLogix program.
For descriptions or details on the individual modules, refer to the Installation
Instructions or User Manual for the specific modules.
91
Peer I/O Sizes
The following tables list the produced I/O sizes of the digital and analog input modules, including those of the POINT I/O and ArmorPOINT I/O modules.
Only the input modules are listed below. The data sent to or consumed by output modules cannot be used in Peer data connections. Although it is possible to read the status information produced from some output modules, they are not included here for the sake of brevity. If another module’s output data is required in your DeviceLogix program, it is suggested that this data be sent from the owning master to the DeviceLogix module through the output
(consumed) data assembly.
Digital Input Modules
Produced I/O Sizes of Digital Input Modules
Catalog Number Description
1734-IB2
1738-IB2M12 (M8)
1734-IB4
1738-IB4M12 (M8)
1734-IB4D
1738-IB4DM12
2-point sinking DC input
2-point sinking DC input
4-point sinking DC input
4-point sinking DC input
4-point sinking DC input with diagnostics
4-point sinking DC input with diagnostics
1734-IB8 8-point sinking DC input
1738-IB8M12 (M8, M23) 8-point sinking DC input
1734-IV2 2-point sourcing DC input
1734-IV4
1738-IV4M12 (M8)
4-point sourcing DC input
4-point sourcing DC input
1734-IV8
1738-IV8M12 (M8, M23)
8-point sourcing DC input
Allen-Bradley HMIs
1
1
Publication 1734-UM015A-EN-E - November 2009
1
1
1
1
1
Produced
Size
1
1
1
1
2 (default), 1
2 (default), 1
92 Peer Data Maps
Publication 1734-UM015A-EN-E - November 2009
Produced I/O Sizes of Digital Input Modules (Continued)
Catalog Number Description
1734-IA2
1738-IA2M12AC3
1738-IA2M12AC4
1734-IA4
1734-IM2
1734-IM4
1734-IB16DM12
2-channel 120V AC input
2-channel 120V AC input
2-channel 120V AC input
4-channel 120V AC input
2-channel 220V AC input
4-channel 220V AC input
16-point sinking DC input with diagnostics
1734-8CFG 8-point DC input/output
1738-8CFGM12 (M8, M23) 8-point DC input/output
1734-8CFGDLX 8-point DC input/output with DeviceLogix
1738-8CFGDLXM12 (M8,
M23)
8-point DC input/output with DeviceLogix
1
1
1
1
Produced
Size
1
1
1
1
2 (default), 3
20 (default),
8, 1
20 (default),
8, 1
Analog and Specialty Input Modules
Produced I/O Sizes of Analog and Specialty Input Modules
Catalog Number
1734-VHSC5
1734-VHSC24
1734-VHSC24M23
1734-IJ
1734-IK
1738-IJM23
1734-IE2C
1734-IE4C
1734-IE8C
1738-IE2CM12
1738-IE4CM12
1734-IE2V
Description Produced
Size
1-channel, 5V, 2-out Very High Speed Counter 6, 6,
10 (default)
1-channel, 24V, 2-out Very High Speed Counter 6, 6,
10 (default)
1-channel, 24V, 2-out Very High Speed Counter 6, 6,
10 (default)
1-channel, 5V counter 6 (default),
6, 10
1-channel, 24V counter
1-channel, 24V counter
2-channel analog input
4-channel analog input
8-channel analog input
2-channel analog input
4-channel analog input
2-channel analog voltage input
24
6
12
6
6 (default),
6, 10
6 (default),
6, 10
6
12
Peer Data Maps 93
Produced I/O Sizes of Analog and Specialty Input Modules (Continued)
Catalog Number Description
1738-IE2VM12
1734-IT2I
1738-IT2IM12
1734-IR2
1738-IR2M12
1734-SSI
1738-SSIM23
1734-232ASC
1738-232ASCM12
1734-485ASC
1738-485ASCM12
2-channel analog voltage input
2-channel, thermocouple input
2-channel, thermocouple input
2-channel, 2-point RTD input
2-channel, 2-point RTD input
Synchronous Serial Interface
Synchronous Serial Interface
RS232 ASCII Interface
RS232 ASCII Interface
RS485 ASCII Interface
RS485 ASCII Interface
6
6
8
8
Produced
Size
6
10
10
4…132,
24 (default)
4…132,
24 (default)
4…132,
24 (default)
4…132,
24 (default)
Peer0 Data
Peer1 Data
Peer2 Data
Peer3 Data
Peer4 Data
Peer5 Data
Peer6 Data
Peer7 Data
Peer Data Maps
The following are data maps for each of the catalogs listed in the preceding tables. The peer data is mapped into one of eight 24-byte memory spaces.
Peer X is the specific memory space where X is 0…7.
The following is a diagram to help explain the addressing of bit data and word data in the DeviceLogix function block editor.
Internal Data Table in Module
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 22
Byte 23
Referenced in
DeviceLogix Function Block Editor (FBE)
Bit-addressing
7 6 5 4 3 2 1 0 b7 b0
Peer#0 (Byte 0,Bit 0)
Word-addressing
Byte 23 b15 b8 b7
Byte 22 b0
Peer#0 (Word 11)
Up to 24 Bytes
44954
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
94 Peer Data Maps
In the following sections, the input tag name in the DeviceLogix editor is given in the left column, and a description of the tag is given in the right column.
This section is intended to be used as a quick guide. For details, refer to the installation instructions or user manual for the specific peer module.
2-Point Digital Input Modules
1734-IB2, 1734-IV2, 1734-IA2, 1734-IM2, 1738-IB2M12, 1738-IB2M8,
1738-IA2M12AC3, 1738-IA2M12AC4
Input Tags for 2-Point Digital Input Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Data
Input channel 0
Input channel 1
4-Point Digital Input Modules
1734-IB4, 1734-IV4, 1734-IA4, 1734-IM4, 1738-IB4M12, 1738-IB4M8,
1738-IV4M12, 1738-IV4M8
Input Tags for 4-Point Digital Input Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Publication 1734-UM015A-EN-E - November 2009
Peer Data Maps 95
4-Point Digital Input with Diagnostics Modules
1734-IB4D, 1738-IB4DM12
Input Tags for 4-Point Digital Input with Diagnostic Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Peer X (byte 0, bit 4)
Peer X (byte 0, bit 5)
Peer X (byte 0, bit 6)
Peer X (byte 0, bit 7)
Peer X (byte 1, bit 0)
Peer X (byte 1, bit 1)
Peer X (byte 1, bit 2)
Peer X (byte 1, bit 3)
Peer X (byte 1, bit 4)
Peer X (byte 1, bit 5)
Peer X (byte 1, bit 6)
Peer X (byte 1, bit 7)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Fault channel 0
Fault channel 1
Fault channel 2
Fault channel 3
Open wire channel 0
Open wire channel 1
Open wire channel 2
Open wire channel 3
Short circuit channel 0
Short circuit channel 1
Short circuit channel 2
Short circuit channel 3
8-Point Digital Input Modules
1734-IB8, 1734-IV8, 1738-IB8M12, 1738-IB8M8, 1738-IB8M23,
1738-IV8M12, 1738-IV8M8, 1738-IV8M23
Input Tags for 8-Point Digital Input Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Peer X (byte 0, bit 4)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Input channel 4
Peer X (byte 0, bit 5) Input channel 5
Peer X (byte 0, bit 6) Input channel 6
Peer X (byte 0, bit 7) Input channel 7 Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
96 Peer Data Maps
8-Point Configurable Modules
1734-8CFG, 1738-8CFGM8, 1738-8CFGM12, 1738-8CFGM23
Input Tags for 8-Point Configurable Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Peer X (byte 0, bit 4)
Peer X (byte 0, bit 5)
Peer X (byte 0, bit 6)
Peer X (byte 0, bit 7)
Data
I/O channel 0
I/O channel 1
I/O channel 2
I/O channel 3
I/O channel 4
I/O channel 5
I/O channel 6
I/O channel 7
Publication 1734-UM015A-EN-E - November 2009
16-Point Digital Input Module
1738-IB16M12
Input Tags for 16-Point Digital Input Modules
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Peer X (byte 0, bit 4)
Peer X (byte 0, bit 5)
Peer X (byte 0, bit 6)
Peer X (byte 0, bit 7)
Peer X (byte 1, bit 0)
Peer X (byte 1, bit 1)
Peer X (byte 1, bit 2)
Peer X (byte 1, bit 3)
Peer X (byte 1, bit 4)
Peer X (byte 1, bit 5)
Peer X (byte 1, bit 6)
Peer X (byte 1, bit 7)
Peer X (byte 2, bit 0)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Input channel 4
Input channel 5
Input channel 6
Input channel 7
Input channel 8
Input channel 9
Input channel 10
Input channel 11
Input channel 12
Input channel 13
Input channel 14
Input channel 15
SSV fault channel 0…3
Peer Data Maps 97
Input Tags for 16-Point Digital Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 2, bit 1)
Peer X (byte 2, bit 2)
Peer X (byte 2, bit 3)
Peer X (byte 2, bit 4)
Data
SSV fault channel 4…7
SSV fault channel 8…11
SSV fault channel 12…15
Fault LED state
8-Point Digital Input Modules with DeviceLogix
1734-8CFGDLX, 1738-8CFGDLXM12, 1738-8CFGDLXM8,
1738-8CFGDLXM23
Input Tags for 8-Point Digital Input Modules with DeviceLogix
Input Tag in DeviceLogix Editor
Peer X (byte 0, bit 0)
Peer X (byte 0, bit 1)
Peer X (byte 0, bit 2)
Peer X (byte 0, bit 3)
Peer X (byte 0, bit 4)
Peer X (byte 0, bit 5)
Peer X (byte 0, bit 6)
Peer X (byte 0, bit 7)
Peer X (byte 1, bit 0)
Peer X (byte 1, bit 1)
Peer X (byte 1, bit 2)
Peer X (byte 1, bit 3)
Peer X (byte 1, bit 4)
Peer X (byte 1, bit 5)
Peer X (byte 1, bit 6)
Peer X (byte 1, bit 7)
Peer X (byte 2, bit 0)
Peer X (byte 2, bit 1)
Peer X (byte 3, bit 0)
Peer X (byte 3, bit 1)
Peer X (byte 3, bit 2)
Peer X (byte 3, bit 3)
Data
I/O channel 0
I/O channel 1
I/O channel 2
I/O channel 3
I/O channel 4
I/O channel 5
I/O channel 6
I/O channel 7
User defined bit 0 (PNB0)
User defined bit 1 (PNB1)
User defined bit 2 (PNB2)
User defined bit 3 (PNB3)
User defined bit 4 (PNB4)
User defined bit 5 (PNB5)
User defined bit 6 (PNB6)
User defined bit 7 (PNB7)
Logic enabled
Owned
Peer missing 0
Peer missing 1
Peer missing 2
Peer missing 3
Peer X (byte 3, bit 4)
Peer X (byte 3, bit 5)
Peer missing 4
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
98 Peer Data Maps
Publication 1734-UM015A-EN-E - November 2009
Input Tags for 8-Point Digital Input Modules with DeviceLogix (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 3, bit 6)
Peer X (byte 3, bit 7)
Peer X (word 2)
Peer X (word 3)
Peer X (word 4)
Peer X (word 5)
Peer X (word 6)
Peer X (word 7)
Peer X (word 8)
Peer X (word 9)
Data
Peer missing 6
Peer missing 7
User defined word 0 (PNW0)
User defined word 1 (PNW1)
User defined word 2 (PNW2)
User defined word 3 (PNW3)
User defined word 4 (PNW4)
User defined word 5 (PNW5)
User defined word 6 (PNW6)
User defined word 7 (PNW7)
2-Point Analog Input Modules and RTD (Resistant Temperature
Device)
1734-IE2C, 1734-IE2V, 1734-IR2, 1738-IE2CM12, 1738-IE2VM12,
1738-IR2M12
Input Tags for 2-Point Analog Input Modules and RTD
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (byte 4, bit 0)
Peer X (byte 4, bit 1)
Peer X (byte 4, bit 2)
Peer X (byte 4, bit 3)
Peer X (byte 4, bit 4)
Peer X (byte 4, bit 5)
Peer X (byte 4, bit 6)
Peer X (byte 4, bit 7)
Peer X (byte 5, bit 0)
Peer X (byte 5, bit 1)
Peer X (byte 5, bit 2)
Peer X (byte 5, bit 3)
Peer X (byte 5, bit 4)
Data
Input channel 0
Input channel 1
Channel 0 fault
Channel 0 calibration mode
Channel 0 low alarm
Channel 0 high alarm
Channel 0 low low alarm
Channel 0 high high alarm
Channel 0 underrange
Channel 0 overrange
Channel 1 fault
Channel 1 calibration mode
Channel 1 low alarm
Channel 1 high alarm
Channel 1 low low alarm
Peer Data Maps 99
Input Tags for 2-Point Analog Input Modules and RTD (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 5, bit 5)
Peer X (byte 5, bit 6)
Peer X (byte 5, bit 7)
Data
Channel 1 high high alarm
Channel 1 underrange
Channel 1 overrange
4-Point Analog Input Modules
1734-IE4C, 1738-IE4CM12
Input Tags for 4-Point Analog Input Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (word 2)
Peer X (word 3)
Peer X (byte 8, bit 0)
Peer X (byte 8, bit 1)
Peer X (byte 8, bit 2)
Peer X (byte 8, bit 3)
Peer X (byte 8, bit 4)
Peer X (byte 8, bit 5)
Peer X (byte 8, bit 6)
Peer X (byte 8, bit 7)
Peer X (byte 9, bit 0)
Peer X (byte 9, bit 1)
Peer X (byte 9, bit 2)
Peer X (byte 9, bit 3)
Peer X (byte 9, bit 4)
Peer X (byte 9, bit 5)
Peer X (byte 9, bit 6)
Peer X (byte 9, bit 7)
Peer X (byte 10, bit 0)
Peer X (byte 10, bit 1)
Peer X (byte 10, bit 2)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Channel 0 fault
Channel 0 calibration mode
Channel 0 low alarm
Channel 0 high alarm
Channel 0 low low alarm
Channel 0 high high alarm
Channel 0 underrange
Channel 0 overrange
Channel 1 fault
Channel 1 calibration mode
Channel 1 low alarm
Channel 1 high alarm
Channel 1 low low alarm
Channel 1 high high alarm
Channel 1 underrange
Channel 1 overrange
Channel 2 fault
Channel 2 calibration mode
Channel 2 low alarm
Peer X (byte 10, bit 3) Channel 2 high alarm
Peer X (byte 10, bit 4) Channel 2 low low alarm Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
100 Peer Data Maps
Publication 1734-UM015A-EN-E - November 2009
Input Tags for 4-Point Analog Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 10, bit 5)
Peer X (byte 10, bit 6)
Peer X (byte 10, bit 7)
Peer X (byte 11, bit 0)
Peer X (byte 11, bit 1)
Peer X (byte 11, bit 2)
Peer X (byte 11, bit 3)
Peer X (byte 11, bit 4)
Peer X (byte 11, bit 5)
Peer X (byte 11, bit 6)
Peer X (byte 11, bit 7)
Data
Channel 2 high high alarm
Channel 2 underrange
Channel 2 overrange
Channel 3 fault
Channel 3 calibration mode
Channel 3 low alarm
Channel 3 high alarm
Channel 3 low low alarm
Channel 1 high high alarm
Channel 3 underrange
Channel 3 overrange
8-Point Analog Input Modules
1734-IE8C
Input Tags for 8-Point Analog Input Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (word 2)
Peer X (word 3)
Peer X (word 4)
Peer X (word 5)
Peer X (word 6)
Peer X (word 7)
Peer X (byte 16, bit 0)
Peer X (byte 16, bit 1)
Peer X (byte 16, bit 2)
Peer X (byte 16, bit 3)
Peer X (byte 16, bit 4)
Peer X (byte 16, bit 5)
Peer X (byte 16, bit 6)
Peer X (byte 16, bit 7)
Peer X (byte 17, bit 0)
Data
Input channel 0
Input channel 1
Input channel 2
Input channel 3
Input channel 4
Input channel 5
Input channel 6
Input channel 7
Channel 0 fault
Channel 0 calibration mode
Channel 0 low alarm
Channel 0 high alarm
Channel 0 low low alarm
Channel 0 high high alarm
Channel 0 underrange
Channel 0 overrange
Channel 1 fault
Peer Data Maps 101
Input Tags for 8-Point Analog Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 17, bit 1)
Peer X (byte 17, bit 2)
Peer X (byte 17, bit 3)
Peer X (byte 17, bit 4)
Peer X (byte 17, bit 5)
Peer X (byte 17, bit 6)
Peer X (byte 17, bit 7)
Peer X (byte 18, bit 0)
Peer X (byte 18, bit 1)
Peer X (byte 18, bit 2)
Peer X (byte 18, bit 3)
Peer X (byte 18, bit 4)
Peer X (byte 18, bit 5)
Peer X (byte 18, bit 6)
Peer X (byte 18, bit 7)
Peer X (byte 19, bit 0)
Peer X (byte 19, bit 1)
Peer X (byte 19, bit 2)
Peer X (byte 19, bit 3)
Peer X (byte 19, bit 4)
Peer X (byte 19, bit 5)
Peer X (byte 19, bit 6)
Peer X (byte 19, bit 7)
Peer X (byte 20, bit 0)
Peer X (byte 20, bit 1)
Peer X (byte 20, bit 2)
Peer X (byte 20, bit 3)
Peer X (byte 20, bit 4)
Peer X (byte 20, bit 5)
Peer X (byte 20, bit 6)
Peer X (byte 20, bit 7)
Peer X (byte 21, bit 0)
Peer X (byte 21, bit 1)
Peer X (byte 21, bit 2)
Data
Channel 1 calibration mode
Channel 1 low alarm
Channel 1 high alarm
Channel 1 low low alarm
Channel 1 high high alarm
Channel 1 underrange
Channel 1 overrange
Channel 2 fault
Channel 2 calibration mode
Channel 2 low alarm
Channel 2 high alarm
Channel 2 low low alarm
Channel 2 high high alarm
Channel 2 underrange
Channel 2 overrange
Channel 3 fault
Channel 3 calibration mode
Channel 3 low alarm
Channel 3 high alarm
Channel 3 low low alarm
Channel 3 high high alarm
Channel 3 underrange
Channel 3 overrange
Channel 4 fault
Channel 4 calibration mode
Channel 4 low alarm
Channel 4 high alarm
Channel 4 low low alarm
Channel 4 high high alarm
Channel 4 underrange
Channel 4 overrange
Channel 5 fault
Channel 5 calibration mode
Channel 5 low alarm
Peer X (byte 21, bit 3)
Peer X (byte 21, bit 4)
Channel 5 high alarm
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
102 Peer Data Maps
Publication 1734-UM015A-EN-E - November 2009
Input Tags for 8-Point Analog Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 21, bit 5)
Peer X (byte 21, bit 6)
Peer X (byte 21, bit 7)
Peer X (byte 22, bit 0)
Peer X (byte 22, bit 1)
Peer X (byte 22, bit 2)
Peer X (byte 22, bit 3)
Peer X (byte 22, bit 4)
Peer X (byte 22, bit 5)
Peer X (byte 22, bit 6)
Peer X (byte 22, bit 7)
Peer X (byte 23, bit 0)
Peer X (byte 23, bit 1)
Peer X (byte 23, bit 2)
Peer X (byte 23, bit 3)
Peer X (byte 23, bit 4)
Peer X (byte 23, bit 5)
Peer X (byte 23, bit 6)
Peer X (byte 23, bit 7)
Data
Channel 5 high high alarm
Channel 5 underrange
Channel 5 overrange
Channel 6 fault
Channel 6 calibration mode
Channel 6 low alarm
Channel 6 high alarm
Channel 6 low low alarm
Channel 6 high high alarm
Channel 6 underrange
Channel 6 overrange
Channel 7 fault
Channel 7 calibration mode
Channel 7 low alarm
Channel 7 high alarm
Channel 7 low low alarm
Channel 7 high high alarm
Channel 7 underrange
Channel 7 overrange
2-Point Thermocouple Input Modules
1734-IT2I, 1738-IT2IM12
Input Tags for 2-Point Thermocouple Input Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (byte 4, bit 0)
Peer X (byte 4, bit 1)
Peer X (byte 4, bit 2)
Peer X (byte 4, bit 3)
Peer X (byte 4, bit 4)
Peer X (byte 4, bit 5)
Peer X (byte 4, bit 6)
Data
Input channel 0
Input channel 1
Channel 0 fault
Channel 0 calibration mode
Channel 0 low alarm
Channel 0 high alarm
Channel 0 low low alarm
Channel 0 high high alarm
Channel 0 underrange
Peer Data Maps 103
Input Tags for 2-Point Thermocouple Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 4, bit 7)
Peer X (byte 5, bit 0)
Peer X (byte 5, bit 1)
Peer X (byte 5, bit 2)
Peer X (byte 5, bit 3)
Peer X (byte 5, bit 4)
Peer X (byte 5, bit 5)
Peer X (byte 5, bit 6)
Peer X (byte 5, bit 7)
Peer X (word 3)
Peer X (byte 7, bit 6)
Peer X (byte 7, bit 7)
Data
Channel 0 overrange
Channel 1 fault
Channel 1 calibration mode
Channel 1 low alarm
Channel 1 high alarm
Channel 1 low low alarm
Channel 1 high high alarm
Channel 1 underrange
Channel 1 overrange
Cold junction temperature
Cold junction underrange
Cold junction overrange
Very High Speed Counter Input Modules
This is the default map for 1734-VHSC24, 1734-VHSC5, and
1738-VHSC24M23.
Input Tags for Very High Speed Counter Input Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (word 2)
Peer X (word 3)
Peer X (byte 8, bit 1)
Peer X (byte 8, bit 2)
Peer X (byte 8, bit 3)
Peer X (byte 8, bit 4)
Peer X (byte 8, bit 5)
Peer X (byte 8, bit 6)
Peer X (byte 9, bit 0)
Peer X (byte 9, bit 1)
Peer X (byte 9, bit 2)
Peer X (byte 9, bit 3)
Data
Present data low word
Present data high word
Stored data low word
Stored data high word
Zero frequency detected
Stored data count 2
Stored data count 3
A input status
B input status
Z input status
Output 0 status
Output 1 status
Output 0 fault
Output 1 fault
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
104 Peer Data Maps
Input Tags for Very High Speed Counter Input Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 9, bit 5)
Peer X (byte 9, bit 6)
Peer X (byte 9, bit 7)
Data
Not ready
EEPROM fault
Program fault
The counter modules produce Double Word values for the Present and Stored
Count value, but the DeviceLogix module only uses 16-bit Word values.
To re-combine the Double Word, the following logic can be used.
Publication 1734-UM015A-EN-E - November 2009
Peer Data Maps 105
The logic multiplies (MUL function block 6) the high word by 65536 (Source
B) and adds it to the Low Word (Add Function Block 7). Function blocks 3, 4, and 5 change the signed word value into an unsigned double word value.
Function block 3 checks if the low word is less than 0, if so, the Select block will output 65535 to the Add block. Otherwise, zero is added to the low word.
Encoder/Counter Input Modules
This is the default map for 1734-IJ, 1734-IK, and 1738-IJM23
Input Tags for Encoder/Counter Input Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (word 2)
Peer X (word 3)
Peer X (byte 8, bit 1)
Peer X (byte 8, bit 2)
Peer X (byte 8, bit 3)
Peer X (byte 8, bit 4)
Peer X (byte 8, bit 5)
Peer X (byte 8, bit 6)
Peer X (byte 9, bit 5)
Peer X (byte 9, bit 6)
Peer X (byte 9, bit 7)
Data
Present data low word
Present data high word
Stored data low word
Stored data high word
Zero frequency detected
Stored data count 2
Stored data count 3
A input status
B input status
Z input status
Not ready
EEPROM fault
Program fault
Synchronous Serial Interface Modules
This is the default map for 1734-SSI and 1738-SSIM12.
Input Tags for Synchronous Serial Interface Modules
Input Tag in DeviceLogix Editor
Peer X (word 0)
Peer X (word 1)
Peer X (word 2)
Peer X (word 3)
Data
Present SSI data low word
Present SSI data high word
Stored SSI data low word
Stored SSI data high word
Peer X (byte 8, bit 0) I1 - Input 1 status
Peer X (byte 8, bit 1) Run - SSI clock output status Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
106 Peer Data Maps
Input Tags for Synchronous Serial Interface Modules (Continued)
Input Tag in DeviceLogix Editor
Peer X (byte 8, bit 2)
Peer X (byte 8, bit 3)
Peer X (byte 8, bit 4)
Peer X (byte 8, bit 5)
Peer X (byte 8, bit 6)
Peer X (byte 8, bit 7)
Peer X (byte 9, bit 0)
Peer X (byte 9, bit 1)
Peer X (byte 9, bit 2)
Peer X (byte 9, bit 3)
Peer X (byte 9, bit 4)
Data
DEC - SSI data count decreasing
INC - SSI data count increasing
C1R - Comparator 1 value reached
C2R - Comparator 2 value reached
C1ST - Comparator 1 active
C2ST - Comparator 2 active
SPF - SSI sensor power fault
CCF - Coprocessor configuration fault
CCE - Coprocessor communication error
IDF - SSI input data fault
LHON - Latched data is stored
See the Very High Speed Counter Input Modules section for an example of
how to convert Word Data to Double Word in your DeviceLogix program.
RS232 and RS485 Interface Module
1734-232ASC, 1734-485ASC, 1738-232ASCM12, 1738-485ASCM12
Although the RS232 and RS485 modules can produce up to 132 bytes of data, only a message of 24 bytes can be consumed by the DeviceLogix module.
The data from these modules can be addressed in the DeviceLogix program using either bit or word tags.
Peer X (byte 0, bit 0)…Peer X (byte 23, bit 7)
Peer X (word 0)…Peer X (word 11)
Publication 1734-UM015A-EN-E - November 2009
Notes:
Peer Data Maps 107
Allen-Bradley HMIs
Publication 1734-UM015A-EN-E - November 2009
108 Peer Data Maps
Notes:
Publication 1734-UM015A-EN-E - November 2009
Allen-Bradley HMIs
Rockwell Automation
Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com
, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States
Outside United
States
1.440.646.3434
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United
States
Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Allen-Bradley, POINT I/O, POINTBus, Rockwell Automation, RSNetWorx, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1734-UM015A-EN-E - November 2009