Beckhoff C6032 is a compact Industrial PC designed for space-saving installation in control cabinets. It's ideal for automation, visualization, and communication tasks in various industries, including machine construction and plant engineering. With its reliable performance and advanced features, the C6032 offers a powerful solution for demanding industrial applications.
إعلان
إعلان
2/20/2020 | Version: 1.0
C6032 |
Industrial PC
Manual | EN
Table of contents
Table of contents
Industrial PC Version: 1.0
3
Table of contents
4 Version: 1.0
Industrial PC
Notes on the documentation
1 Notes on the documentation
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards.
The following instructions and explanations must be followed during installation and commissioning of the components. The qualified personnel must ensure that the application of the described products meets all safety requirements, including all applicable laws, specifications, regulations and standards.
Disclaimer
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation. All illustrations shown are only examples. The configurations depicted may deviate from the standard.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered and licensed brands of Beckhoff Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
Patents
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with the corresponding applications and registrations in various other countries. The TwinCAT Technology is covered, including but not limited to the following patent applications and patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
Copyright
© Beckhoff Automation GmbH & Co. KG. The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
Delivery state
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
Delivery conditions
In addition, the general delivery conditions of the company Beckhoff Automation GmbH & Co. KG apply.
Industrial PC Version: 1.0
5
6
For your safety
2 For your safety
The signal panel and its meanings are explained in the chapter on safety. They contain fundamental safety instructions that are essential for the avoidance of personal injuries and damage to property.
Exclusion of liability
Liability on the part of Beckhoff Automation GmbH & Co. KG is excluded in the following cases:
• Failure to comply with this documentation
• Improper use
• Use of untrained personnel
• Use of unauthorized spare parts
2.1
Description of safety symbols
The following safety symbols are used in these operating instructions. In order to avoid personal injuries and damage to property, read and follow the safety and warning notices.
Warning of personal injuries:
DANGER
Disregarding the safety notice will lead to death or serious injuries.
WARNING
Disregarding the safety notice may lead to death or serious injuries.
CAUTION
Disregarding the safety notice may lead to minor injuries.
Warning of damage to property:
NOTE
Disregarding the notice may lead to damage to property.
2.2
Intended use
The C6032 is an Industrial PC for space-saving installation in the control cabinet. It is intended for use as a control system for automation, visualization and communication in machine construction and plant engineering.
The Industrial PC was developed for a work environment that conforms to protection class IP20. It is protected against the penetration of fingers and solid foreign bodies of 12.5 mm or larger in size. It is not protected against water. Operation of the devices in wet and dusty environments is not permitted, unless specified otherwise. The specified limits for electrical and technical data must be adhered to.
Version: 1.0
Industrial PC
For your safety
Improper use
Do not use the Industrial PC in the following areas:
• potentially explosive atmospheres
• Areas with extreme environmental conditions, such as particularly high or low temperatures above and below the operating temperature range
• Areas in which the device is loaded beyond the EMC interference immunity
• Areas (e.g. residential areas) in which the EMC requirements for interference emissions are inadequate
• Areas in which the device is loaded beyond its shock resistance
• Dusty and wet areas
2.3
Fundamental safety instructions
The following safety instructions must be observed when handling the Industrial PC.
Application conditions
• Do not use the Industrial PC under extreme environmental conditions. Protect the device against dust, moisture and heat and keep the ventilation slits free.
• Never use the Industrial PC in potentially explosive atmospheres.
• Do not carry out any work on the Industrial PC when it is live. Always switch off the supply voltage for the device before mounting it, replacing device components or rectifying malfunctions.
• Never connect the Industrial PC during a thunderstorm. There is a risk of electric shock.
Damage to property, loss of data and impairment of functions
• Only make the documented modifications to the hardware and software configurations. Unauthorized modifications of these configurations can limit the function or lead to damage to property and loss of data.
• Ensure that only trained qualified persons with a control and automation technology background, operate the Industrial PC. Use by unauthorized persons can lead to damage to property and loss of data.
• Protect the power supply cable with a fuse with a max. rating of 16 A. The functionality may be impaired if the fuse rating is too high.
• In case of fire, extinguish the Industrial PC with powder or nitrogen.
2.4
Operator's obligation to exercise diligence
The operator must ensure that
• the products are used only for their intended purpose (see chapter 2.2 Intended use).
• the products are only operated in sound condition and in working order.
• the products are operated only by suitably qualified and authorized personnel.
• the personnel is instructed regularly about relevant occupational safety and environmental protection aspects, and is familiar with the operating instructions and in particular the safety instructions contained herein.
• the instruction manual is in good condition and complete, and always available for reference at the location where the products are used.
Industrial PC Version: 1.0
7
Product overview
3 Product overview
Fig. 1: C6032
The C6032 Industrial PC extends the range of ultra-compact Industrial PCs by a high-performance modular device for installation in the control cabinet. The second board level for modular interface and function extensions enables adaptation to specific applications and requirements. Various compact PCle modules are available as ordering options for this.
Thanks to the Intel ® Core™-i processors with a computing performance up to Core™ i7 with four cores clocked at 3.6 GHz, you can use the Industrial PC for the following applications, among others:
• extensive axis controllers
• complicated HMI applications
• short cycle times
• high-volume data handling
• diverse automation and visualization tasks
The basic equipment of the C6032 includes the following aspects:
• 4 GB DDR4 RAM, expandable to 32 GB
• 40 GB M.2 SSD, 3D Flash, extended temperature range
• Graphic adapter integrated in the Intel ® processor, 2 DisplayPort connections
• on-board Ethernet adapter with 4 x 100/1000BASE-T connection
• 4 x USB 3.0
• 2 accessible slots for M.2 SSDs
• 2 PCle compact module slots for the insertion of Beckhoff PCle compact modules ex factory
The operating systems Windows 7 or Windows 10 as well as a second M.2 SSD in the RAID group are optional. Moreover, eight different CPU types are available. TwinCAT 3, the version of the Beckhoff automation software that was specially developed for multi-core processors, can use the two-core and fourcore processors of this Industrial PC generation in the same way as its predecessor TwinCAT 2 with its single-core support.
8 Version: 1.0
Industrial PC
Product overview
3.1
Structure
6
7
Fig. 2: C6032 structure – basic configuration
Table 1: Key - C6032 structure
No.
1
2
3
4
5
8
9
10a
10b
Component
Protective conductor connection
PE
Power supply (X101)
Status LEDs
Ethernet interfaces RJ45 (X102 -
X105)
USB 3.0 interfaces (X106-109)
DisplayPorts (X110, X111)
Side cover
Name plate
Mounting plate
PCle module slot 1
PCle module slot 2
Description
Low-resistance protective earthing of the Industrial PC
Connection of the power supply and external wiring of the Industrial
PC
Status display for UPS-OCT, power, hard disk, TwinCAT
Connection of the Industrial PC to a 100/1000BASE-T network
Connection of peripheral devices,
USB 3.0 standard supported
Transmission of the video signal
Access to battery, storage media and fan
Information on the equipment of the Industrial PC
Plate for mounting the Industrial
PC with its rear panel in the control cabinet
Insertion of Beckhoff PCle
Compact modules
Insertion of Beckhoff PCle
Compact modules
Industrial PC Version: 1.0
9
Product overview
Fig. 3: C6032_standard connections
Power supply (X101)
The Industrial PC is equipped with a 24 V
DC
power supply unit. The power supply and external wiring are connected to the Industrial PC via the 4-pin voltage connector (Phoenix DFMC 4.5/2-STF-3.5 BK –
1708595).
Fig. 4: C6032_voltage connector
Table 2: Pin assignment voltage connector
Pin
GND
24 V +
P-S
ON
Function
0 V
Power supply
Power status output
PC_ON input
The connector is specified for 8 A and can accept cable cross-sections of up to 1.5 mm 2 .
The power supply connector is included in the scope of delivery.
Network connections LAN1, LAN2, LAN3, LAN4 (X102-105)
The RJ-45 sockets (X102-X105) enable the connection of the PC to a 100/1000BASE-T network.
USB 3.0 interfaces (X106-109)
The USB interfaces are used to connect peripheral devices with a USB connection.
DisplayPorts (X110, X111)
The DisplayPorts (X110, X111) are for the transmission of the video signal.
10 Version: 1.0
Industrial PC
Product overview
Protective conductor connection (PE)
The low-resistance protective earthing of the Industrial PC must be established via the screw connection.
The cabling in the control cabinet must be done in accordance with EN 60204-1:2006 PELV (Protective
Extra Low Voltage) so that one side of the circuit or one point of the energy source of this circuit is connected to the protective conductor system.
Connect "PE" and "0 V" (24 V power supply) to the same potential (connected in the control cabinet).
NOTE
When disconnecting the ground to switch off the device, current can flow via the shield and cause damage to property.
• To switch off the device, disconnect the 24 V line.
Any connected devices with their own power supply must have the same potential for "PE" and "GND" as the
Industrial PC system (no potential difference).
Status LEDs
Fig. 5: C6032_Status LEDs
The four Status LEDs on the front side of the Industrial PC have the following meaning:
Table 3: Meaning of the Status LEDs
Status LED
UPS-OCT
PWR (Power)
HDD (hard disk)
TC (TwinCAT)
Colors
green yellow red red blue blue/red flashing green green/red flashing
Meaning not defined
Computer on
Computer shutdown
Access to storage medium
TwinCAT Stop
TwinCAT Config
TwinCAT Config (fieldbus error)
TwinCAT Run
TwinCAT Run (fieldbus error)
Industrial PC Version: 1.0
11
Product overview
Interface options
Fig. 6: C6032_modules
You can extend the Industrial PC beyond the basic equipment level by additional interfaces. The following
PCle Compact modules are available to you for this:
• USB 3.0
• Network connections RJ-45 Ethernet 100/1000BASE-T
• RS232 (serial interface for data transmission)
• RS485 (serial interface for data transmission)
• RS422 (serial interface for data transmission)
• CP-Link-4 (one-cable solution for remote operating units placed up to 100 m away)
The modules ordered are mounted ex factory (see arrow in fig. 6).
If you bought the device with the basic equipment, you can extend it later by the modules mentioned above.
To do this, replace the blank covers with the modules by undoing the two TX8 screws of the covers and tightening them again after inserting the modules.
12 Version: 1.0
Industrial PC
Product overview
3.2
Name plate
The name plate provides information on the equipment fitted to the Industrial PC. It is located on the right side panel of the housing.
8
9
6
7
10
3
4
5
11
12
13
14
Fig. 7: C6032_name plate
Table 4: Key to name plate
No.
1
2
Description
Manufacturer, including address
Model: The last four digits indicate the device generation.
Serial number
Date of manufacture
Mainboard
CPU
Main memory
SSD hard disks
Power supply unit: 24 V DC
MAC addresses of the Ethernet interfaces (X102-
X105)
Optional PCle Compact modules
CE conformity, EAC conformity
FCC approvals
Variant number: Clear marking of the standard device with selected ordering options
Industrial PC Version: 1.0
13
Commissioning
4 Commissioning
4.1
Transport and unpacking
The specified storage conditions must be adhered to (see chapter 8 Technical data).
Despite the robust design of the unit, the components are sensitive to strong vibrations and impacts. During transport the device must therefore be protected from mechanical stress. Use the original packaging.
NOTE
Unfavorable weather conditions during transport can cause damage to the device.
• Protect the device against moisture (condensation) during transport in cold weather or in case of extreme temperature fluctuations.
• Do not put the device into operation until it has slowly adjusted to the room temperature.
• Should condensation occur, wait for about 12 hours before switching the device on.
Unpacking
Proceed as follows to unpack the unit:
1. Remove packaging.
2. Keep the packaging for possible future transport.
3. Check your delivery for completeness by comparing it with your order.
4. Be sure to keep the documents supplied with the device. They contain important information about how to use your device.
5. Check the contents for visible shipping damage.
6. Inform the Beckhoff Service Dept. in case of discrepancies between the packaging content and the order or in the event of transport damage.
4.2
Installation in the control cabinet
The C6032 Industrial PC is designed for installation in control cabinets in machine and plant technology.
Please observe the environmental conditions prescribed for the operation (see chapter 8 Technical Data).
The Industrial PC is mounted according to the order with a flexible mounting device for the free orientation of the connection level.
The following ordering options are available to you:
Table 5: Mounting plate ordering options
Order option
C9900-M668
C9900-M669
Execution
Supplied with mounting plate for mounting on the side panel
Individual mounting plate for mounting on the side panel
14 Version: 1.0
Industrial PC
Commissioning
Fig. 8: C6032_mounting plates
Figure 8 shows the two available mounting plates. In both cases, the plate is screwed to the right side panel of the Industrial PC. You can rotate both mounting plates before screwing on so that the PC can be mounted in the desired orientation for the cable entry in the control cabinet.
If you didn't choose an ordering option for mounting when ordering the device, you will automatically receive the device with the mounting plate for mounting on the rear panel.
Industrial PC Version: 1.0
15
Commissioning
4.2.1
Dimensions
The dimensions of the Industrial PC and the mounting plate are used to prepare the control cabinet and to mount the device correctly in the control cabinet.
NOTE
Mounting the device in a different way to that shown in the illustration may result in damage to the device.
• Mount the device only in the orientations shown in the documents.
All dimensions are in mm.
Mounting plate on the rear panel
63.1
PCIe - module
M4 grounding power - port ethernet - port
USB 3.0 - port display - port
104
Vorderansicht
5 129
145
Seitenansicht
39.1
Rückansicht
65
Ø 4,2
Fig. 9: C6032_Mounting plate on the rear panel
Draufsicht
16 Version: 1.0
Industrial PC
Commissioning
Mounting plate on the side panel
102
70
Ø 4,2 7.5
PCIe - module
M4 grounding power - port ethernet - port
USB 3.0 - port display - port
106
Vorderansicht
Seitenansicht Rückansicht
Fig. 10: C6032_Mounting plate on the side panel
129
Draufsicht
4.2.2
Preparation of the control cabinet
The control cabinet must be equipped with the drill holes for the fastening screws according to the device dimensions of the PC (see chapter 4.2.1 Dimensions)
NOTE
Extreme environmental conditions can cause damage to the device.
• Avoid extreme environmental conditions.
• Protect the device against dust, moisture and heat.
• Do not block the ventilation slits of the device.
When installing in the control cabinet, note that there must be 5 cm of free space around the PC for air circulation and for opening the PC.
Industrial PC Version: 1.0
17
Commissioning
4.3
Connecting the Industrial PC
CAUTION
Risk of electric shock!
Connecting the Industrial PC during a thunderstorm can lead to electric shocks.
• Never plug in or unplug the Industrial PC's cables during a thunderstorm.
Earthing measures
The low-resistance protective earthing of the Industrial PC must be established via the screw connection.
Connect the earthing point on the Industrial PC (see chapter 3.1 Structure) with a low-resistance connection to the central earthing point of the panel in the control cabinet into which the PC is installed.
Connecting cables
NOTE
Incorrect connection of cables to the Industrial PC can lead to damage to property.
• Always disconnect the power plug before connecting cables.
• Please read the documentation for the external devices prior to connecting them.
The connectors are located on the front side of the Industrial PC and are documented in chapter 3.1
Structure.
Proceed as follows to connect the cables to the Industrial PC:
1. Switch off all the devices that are to be connected.
2. Disconnect all the devices that are to be connected from the power supply.
3. Connect all the cables between the Industrial PC and to the devices that are to be connected.
4. Connect all data transfer cables (if present) to the appropriate plug-in receptacles of the data/telecommunication networks.
5. Reconnect all devices to the power supply.
Connecting the power supply
Cables with a cross-section of 1.5 mm 2 must be used to connect the power supply. In the case of longer distances between the voltage source and the PC, take into account the voltage drop in relation to the cable cross-section and voltage fluctuations in your supply voltage. This ensures that the voltage at the power supply unit does not drop below 22 V.
NOTE
Protecting the power cable with a fuse with too high a rating can impair the functionality.
• Use a fuse with a maximum rating of 16 A to protect the power cable.
Proceed as follows to connect the 24 V
DC
power supply unit:
1. Check that the external power supply is providing the correct voltage.
2. Mount the power cable.
3. Plug the power cable into the 4-pin voltage connector on the Industrial PC.
4. Connect the PC to your external 24 V power supply.
18 Version: 1.0
Industrial PC
Operation
5 Operation
5.1
Switching the Industrial PC on and off
The Industrial PC does not have its own mains switch. The Industrial PC will start when the equipment is switched on, or when it is connected to the power supply.
NOTE
Shutting down the Industrial PC before terminating the running software can result in loss of data.
• Terminate the running software before switching off the Industrial PC.
When the system is switched off or disconnected from its own power supply, the Industrial PC is also switched off.
The connections for shutting down the Industrial PCs are established via the PC_ON input and the Power
Status output.
On the basis of the typical control software on Industrial PCs, you can assign different rights to all users. A user who may not close software may also not switch the Industrial PC off, since data can be lost from the hard disk by switching off while software is running.
Restarting the Industrial PC
Proceed as follows to restart the Industrial PC:
1. Shut down the PC.
2. Switch the PC off for at least 10 seconds.
3. Switch the supply voltage on again.
The Industrial PC will now restart automatically.
PC_ON and Power Status functions
If the PC_ON input is connected to 24 V via a switch, the PC shuts down according to the rules. The PC_ON signal is inverted, i.e. the PC shuts down if the 24 V connection is live.
Once the PC has shut down, the Power Status output is switched from 24 V to 0 V. Via this output a signal lamp can be connected or a contactor for de-energizing the whole system. The maximum load for the Power
Status output is 0.5 A and a suitable fuse should be provided.
First switching on and driver installation
When you switch on the Industrial PC for the first time, the pre-installed operating system (optional) will be started. In this case, all the required drivers for any additional, optional hardware components ordered with the PC will already have been installed.
If the PC was ordered without operating system, you have to install the operating system and the driver software for any auxiliary hardware yourself. Please follow the instructions in the documentation for the operating system and the additional devices.
Industrial PC Version: 1.0
19
Operation
5.2
Decommissioning
Disposal of the Industrial PC
Be sure to observe the national electronic scrap regulations when disposing of the Industrial PC.
In order to dispose of the device, it must be removed and fully dismantled. Dispose of the components in the following way:
• Take housing parts (polycarbonate, polyamide (PA6.6)) to the plastic recycling collection point.
• Take metal parts to the metal recycling collection point.
• Electronic parts such as disk drives and circuit boards must be disposed of in accordance with national electronic scrap regulations.
20 Version: 1.0
Industrial PC
Maintenance
6 Maintenance
6.1
Cleaning
DANGER
Risk of electric shock!
Cleaning the Industrial PC when it is switched on and connected to the power supply will lead to death or serious injury.
• Switch off the Industrial PC and all connected devices.
• Disconnect the PC from the power supply.
NOTE
The use of unsuitable cleaning agents can damage the device.
• Do not use corrosive cleaning agents, thinners, abrasives or hard objects to clean the Industrial PC.
• Clean the PC with a damp, soft cleaning cloth.
6.2
Maintenance
The Industrial PC requires no maintenance.
6.3
Replacement of device components
The battery and the storage media are located behind the cover on the right-hand side of the Industrial PC:
Fig. 11: C6032_Access to battery and storage media
Industrial PC Version: 1.0
21
Maintenance
6.3.1
Replacing the battery
The spent battery must be disposed of in accordance with the national electronic waste regulations.
NOTE
Inserting the wrong type of battery can cause an explosion and damage the device.
• Replace the battery only by one of the same type or by a replacement type recommended by Beckhoff.
• When replacing the battery, make sure that the polarity is correct.
NOTE
The lithium battery may be damaged if it is inserted incorrectly.
• Do not recharge the battery.
• Do not throw the battery on the fire.
• Do not open the battery.
• Protect the battery against direct sunlight and moisture.
Proceed as follows to gain access to the battery:
1. Loosen the four Torx TX10 screws (see arrow in fig. 11).
2. Remove the cover.
You can now access the battery (see fig. 11).
6.3.2
Replacing the storage media
Proceed as follows to gain access to the storage media:
1. Loosen the four Torx TX10 screws (see arrow in fig. 11).
2. Remove the cover.
You now have access to the storage media (see fig. 11).
22 Version: 1.0
Industrial PC
Maintenance
6.3.3
Replacing the fan
The Industrial PC has a controlled fan for optimal cooling. The fan has double ball bearings and is exchangeable.
NOTE
The Industrial PC may be damaged if the wrong type of fan is installed.
• Replace the fan only by the identical type or by a replacement type approved by Beckhoff.
To replace the fan, follow the steps below, which are shown in Figure 12:
1. Remove the four Torx TX10 screws on the top side and underside of the Industrial PC (see section A).
2. Pull the fan housing off (see section B).
Fig. 12: C6032_Access to the fan
3. Remove the two Torx screws (see section C).
4. Disconnect the supply cable from the motherboard.
You can now replace the fan.
Industrial PC Version: 1.0
23
Troubleshooting
7 Troubleshooting
Table 6: Troubleshooting
Fault Cause
Nothing happens after the
Industrial PC has been switched on
No power supply to the Industrial
PC
Measures
Check the cable for the power supply
The Industrial PC does not boot fully
Other cause
Setup settings are incorrect
Computer boots, software starts, but control does not operate correctly
Error while accessing the drive
The Industrial PC works only partially or temporarily, e.g. dark picture or none at all, but the drive responds when switching on
Other cause
Cause of the fault is either in the software or in parts of the plant outside the Industrial PC
Faulty disk drive
Defective components in the
Industrial PC
Call Beckhoff Service
Check the setup settings
Call Beckhoff Service
Call the machine and software manufacturer
Call Beckhoff Service
Call Beckhoff Service
24 Version: 1.0
Industrial PC
Technical data
8 Technical data
Table 7: Technical data
Product designation
Dimensions (W x H x D)
Weight
Supply voltage
Power consumption
Interfaces
Optional interface extensions
Protection class
Vibration resistance (sinusoidal vibration)
Shock resistance (shock)
EMC - interference immunity
EMC interference emission
Permissible ambient temperature
Permissible air humidity
Transport and storage
Certification
C6032
129 x 133 x 104 mm, without mounting plate
Approx. 2100 g excluding mounting plate
Approx. 2350 g including mounting plate
22 - 30 V
DC
(24 V
DC
power supply unit)
Max. 60 W with basic equipment
4 RJ-45 Ethernet 100/1000BASE-T ports
2 DisplayPorts
4 x USB 3.0
PCle Compact modules each:
2 Gbit Ethernet
2 x USB 3.0
2 x RS232
2 x RS485
2 x RS422
1 CP-Link 4
IP20
EN 60068-2-6: 10 to 58 Hz: 0.035 mm
58 to 500 Hz: 0.5 G (approx. 5 m/s 2 )
EN 60068-2-27: 5 G (approx. 50 m/s 2 ), duration:
30 ms conforms to EN 61000-6-2 conforms to EN 61000-6-4
0 °C to +55 °C (operation)
-25 °C to +65 °C (transport / storage)
Max. 95 %, no load
The same values for air humidity and shock resistance are to be observed during transport and storage as in operation. The shock resistance during transport can be improved by means of suitably packing the Industrial PC.
CE, EAC, FCC
Industrial PC Version: 1.0
25
Appendix
9 Appendix
9.1
Service and support
Beckhoff and their partners around the world offer comprehensive service and support, making available fast and competent assistance with all questions related to Beckhoff products and system solutions.
Beckhoff Service
The Beckhoff Service Centre supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline: + 49 (0) 5246/963-460
Fax: + 49 (0) 5246/963-479
E-mail: [email protected]
If servicing is required, please quote the serial number of your Industrial PC, which can be found on the name plate.
Beckhoff Support
Support offers you comprehensive technical assistance, helping you not only with the application of individual Beckhoff products, but also with other, wide-ranging services:
• World-wide support
• design, programming and commissioning of complex automation systems
• extensive training program for Beckhoff system components
Hotline: + 49 (0) 5246/963-157
Fax: + 49 (0) 5246/963-9157
E-mail: [email protected]
Headquarters
Beckhoff Automation GmbH & Co. KG
Hülshorstweg 20
33415 Verl
Germany
Phone: + 49 (0) 5246/963-0
Fax: + 49 (0) 5246/963-198
E-mail: [email protected]
The addresses of the worldwide Beckhoff branches and agencies can be found on our website at http:// www.beckhoff.com/ .
You will also find further documentation for Beckhoff components there.
26 Version: 1.0
Industrial PC
Appendix
9.2
Approvals
FCC approvals for the United States of America
FCC: Federal Communications Commission Radio Frequency Interference Statement
This device was tested and complies with the limits for a digital device of class A, according part 15 of the
FCC regulations. These limits are designed to provide adequate protection against adverse interference, if the device is used in a commercial environment. This device generates, uses and may emit radio frequency energy and may cause adverse interference with radio communications, if it is not installed and used in accordance with the operating instructions. If this device is used in a residential area it is likely to cause adverse interference, in which case the user must take appropriate countermeasures in order to eliminate the interference at his own expense.
FCC approvals for Canada
FCC: Canadian Notice
This device does not exceed the class A limits for radiation, as specified by the Radio Interference
Regulations of the Canadian Department of Communications.
Industrial PC Version: 1.0
27
List of figures
List of figures
28 Version: 1.0
Industrial PC
List of tables
List of tables
Industrial PC Version: 1.0
29
Beckhoff Automation GmbH & Co. KG
Hülshorstweg 20
D-33415 Verl www.beckhoff.com
More Information: www.beckhoff.com/C6032/