ABB ARC600 User Manual

Add to My manuals
92 Pages

advertisement

ABB ARC600 User Manual | Manualzz

Wireless Controller

ARC600

User Manual

Document ID: 1MRS758459

Issued: 2019-04-24

Revision: C

Product version: 3.4.7

© Copyright 2019 ABB. All rights reserved

Copyright

This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks

ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

www.abb.com/substationautomation

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties.

All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.

This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network.

It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses.

This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN

60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Safety information

Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantial property damage.

Only a competent electrician is allowed to carry out the electrical installation.

National and local electrical safety regulations must always be followed.

The frame of the device has to be carefully earthed.

This product is not fault-tolerant and is not designed, manufactured or intended for use or resale as on-line control equipment or as part of such equipment in any hazardous environment requiring fail-safe performance, such as in the operation of nuclear facilities, aircraft navigation or communication systems, air traffic control, direct life support machines, or weapons systems, in which the failure of the hardware or software described in this manual could lead directly to death, personal injury, or severe physical or environmental damage.

To prevent damage both the product and any terminal devices must always be switched off before connecting or disconnecting any cables. It should be ascertained that different devices used have the same ground potential. The output voltage of the power supply should be checked before connecting any power cables.

The devices mentioned in this manual are to be used only according to the instructions described in this manual. Faultless and safe operation of the devices can be guaranteed only if the transport, storage,

operation and handling of the devices is appropriate. This also applies to the maintenance of the products.

ARC600

User Manual

Table of contents

Table of contents

Section 1 Introduction.......................................................................5

This manual........................................................................................ 5

Intended audience.............................................................................. 5

Product documentation.......................................................................5

Product documentation set............................................................5

Document revision history............................................................. 5

Related documentation..................................................................6

Symbols and conventions...................................................................6

Symbols.........................................................................................6

Document conventions..................................................................7

Section 2 ARC600 overview.............................................................9

Overview.............................................................................................9

Physical interfaces............................................................................11

Front panel.................................................................................. 11

Serial panel..................................................................................12

Antenna panel............................................................................. 13

System status LEDs.................................................................... 13

DIN rail mounting..............................................................................14

Product information label .................................................................14

Firmware version.............................................................................. 14

Section 3 Physical connections......................................................15

Communication connections............................................................ 15

Serial ports.................................................................................. 15

Console/serial port 1.............................................................. 15

Serial port 2............................................................................ 16

Ethernet.......................................................................................18

Wireless network......................................................................... 18

I/O connections.................................................................................19

Power connector..........................................................................19

X2.1 connector............................................................................ 19

X2.3 connector............................................................................ 20

X3 connector............................................................................... 21

X4 connector............................................................................... 23

I/O LEDs......................................................................................24

AC and LINK LEDs.................................................................24

Disconnector LEDs.................................................................24

Grounding LEDs.....................................................................25

1

2

Table of contents

Section 4 Functional description.................................................... 27

Control functions...............................................................................27

Condition monitoring functions......................................................... 27

Communication diagnostics and watchdog................................. 27

Disconnector control condition monitoring functions........................ 27

Disconnector travel time monitoring............................................ 27

Disconnector actuator motor overload protection........................28

Monitoring of the pressure of SF6 gas........................................ 29

Battery charging and monitoring functions....................................... 29

Power backup..............................................................................29

Heater control..............................................................................30

Low auxiliary voltage indication...................................................31

Over/undertemperature indication...............................................31

Temperature compensation of battery charging voltage............. 31

Battery deep discharge protection...............................................31

Battery capacity test.................................................................... 32

Settings.................................................................................. 32

Remote control of the battery test function ............................32

Battery test status ..................................................................33

Battery capacity .....................................................................33

Measurement file ...................................................................33

Measurement functions.................................................................... 33

Temperature measurement.........................................................34

Processor temperature...........................................................34

Communication module temperature..................................... 34

Sensor for the temperature compensation of the charging voltage....................................................................................34

Ambient temperature..............................................................34

Load limiter....................................................................................... 35

Overload detection settings ........................................................35

Remote enabling and disabling of the load limiter ......................37

Load limiter status ...................................................................... 37

Reason for load limiter activity ....................................................38

Measured charge during overload ..............................................38

Measured time during overload ..................................................38

Support for fault indicators................................................................38

Section 5 Cyber security................................................................ 39

Cyber security definition................................................................... 39

Enhancing operator and subscription security..................................39

Configuring firewall and services......................................................40

Section 6 Getting started................................................................41

ARC600

User Manual

ARC600

User Manual

Table of contents

Connecting cables............................................................................ 41

Connection principle....................................................................41

Logging in......................................................................................... 41

User interface.............................................................................. 42

Setting Ethernet port function to LAN............................................... 42

Configuring mobile WAN.................................................................. 43

Configuring the default route............................................................ 43

Section 7 Network configuration.....................................................45

Defining host and domain names..................................................... 45

Configuring communication interfaces............................................. 45

Configuring Ethernet LAN............................................................45

Configuring Ethernet WAN.......................................................... 45

Configuring the mobile WAN interface........................................ 45

Setting WAN failover and backup routing....................................46

Routing parameters.......................................................................... 46

Configuring the network monitor.......................................................47

Configuring DNS proxy.....................................................................48

Checking network status.................................................................. 48

Section 8 Serial port configuration................................................. 49

Configuring serial ports.....................................................................49

Serial gateway.................................................................................. 49

Section 9 Additional system configuration......................................51

Changing passwords........................................................................ 51

Setting date and time........................................................................51

Restoring factory default settings..................................................... 52

Updating the firmware...................................................................... 52

Saving configuration profiles............................................................ 52

Section 10 Service configuration......................................................53

Configuring services......................................................................... 53

Service parameters.......................................................................... 53

Section 11 IEC-104 application settings...........................................57

The use of the IEC-104 protocol.......................................................57

Configuring IEC-104 application settings......................................... 57

IEC-104 application settings.............................................................57

Section 12 Modbus application settings...........................................63

Modbus Gateway properties.............................................................63

Modbus mode...................................................................................64

Configuring the network master to serial slaves mode.....................65

Parameter settings........................................................................... 65

3

Table of contents

Section 13 Technical data................................................................69

Section 14 Appendix Installation and mounting instructions............ 75

Unpacking the device....................................................................... 75

Installing the device.......................................................................... 75

Installing the SIM card ..................................................................... 76

Section 15 Glossary......................................................................... 77

4 ARC600

User Manual

1.3

1.3.1

1.3.2

1MRS758459 C

Section 1 Introduction

1.1

1.2

Section 1

Introduction

This manual

The user manual provides introductory information as well as detailed instructions on how to set up and manage the device as part of a network environment.

Intended audience

This manual addresses the personnel involved in installing and managing the devices.

The personnel is expected to be familiar with basic working principles of Internet technology.

Product documentation

Product documentation set

Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation .

Document revision history

Document revision/date

A/2015-12-18

B/2017-09-22

Product version

A

3.4

C/2019-04-24 3.4.7

History

First release

Content updated to correspond to the product version

Content updated to correspond to the product version

Download the latest documents from the ABB Web site http://www.abb.com/substationautomation .

ARC600

User Manual

5

6

Section 1

Introduction

1.3.3

1.4

1.4.1

1MRS758459 C

Related documentation

Name of the document

Arctic Cyber Security Deployment

Guideline

3G/LTE configuration guide Technical

Note

3G/LTE Wireless Gateway firmware update Technical Note

Wireless Controller

RTU_interoperability Technical Note

Wireless Controller RTU configuration guide Technical Note

Description

Configuring Wireless Gateways,

Controllers and M2M Gateway

Updating firmware of Wireless

Gateway devices

1MRS758451

ARC600 RTU application configuration 1MRS758476

IEC 60870-5-104 and IEC 60870-5-101 interoperability

Document ID

1MRS758860

1MRS758449

1MRS758477

Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation .

Symbols and conventions

Symbols

The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function.

ARC600

User Manual

1MRS758459 C

1.4.2

Section 1

Introduction

Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

Document conventions

A particular convention may not be used in this manual.

• Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms.

• Menu paths are presented in bold.

Select Main menu/Settings .

• Parameter names are shown in italics.

The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks.

The corresponding parameter values are "On" and "Off".

ARC600

User Manual

7

8

1MRS758459 C

Section 2 ARC600 overview

2.1

Section 2

ARC600 overview

Overview

Wireless Controller ARC600 is a compact, solution based device for remote controlling and monitoring of secondary substations, such as network disconnectors, load break switches and ring main units (RMU) in distribution networks. It enables the

SCADA system to wirelessly monitor and control the field devices over the public communication infrastructure (cellular network). Wireless Controller ARC600 utilizes the built-in wireless communication features for reliable and secure end-toend communication providing remote monitoring and control of three switching devices and can be expanded as required by using external I/O expansion modules.

The use of Wireless Controller ARC600 in distribution networks improves the quality of power distribution and reduces the outage time in the affected areas. Areas directly adjacent to these affected areas show reduced outages and overall effects. This also reduces the capital expenditures in the distribution network by allowing integration of legacy devices and contributes to more direct cost savings by facilitating preventative maintenance. The operational expenditure can be reduced by lowering the System

Average Interruption Duration Index (SAIDI) and System Average Interruption

Frequency Index (SAIFI), resulting in lower penalties for undelivered energy.

Wireless Controller ARC600 is also ideally suited to be retrofitted to existing applications thus enabling the remote control of these devices and further extending the life cycle of the switching devices itself.

Typically, the IEC-104 protocol is utilized for communication to the SCADA system but for the existing installations with a IEC-101 line or modem, Wireless Controller

ARC600 supports also IEC-101 communication (including dial-up) to the SCADA system.

ARC600

User Manual

GUID-533791DB-D17E-49EA-B2AB-8E13618BF244 V1 EN

Figure 1: Communication system overview with Wireless Controller ARC600 and ring main unit

9

Section 2

ARC600 overview

1MRS758459 C

10

GUID-3496BF1A-45BE-43DD-A903-C43E36EF172D V1 EN

Figure 2: Wireless Controller ARC600 at remote site connected with ring main unit and RIO600. RTU monitoring and control combined with directional fault passage indication example.

ARC600

User Manual

1MRS758459 C

2.2

2.2.1

Physical interfaces

Front panel

1 2 23 24 25

Section 2

ARC600 overview

ARC600

User Manual

GUID-38343AB8-2790-4E25-BD31-DBB0C237712F V3 EN

Figure 3: Front panel

6

1 System status LEDs

2 X2.1 connector

3 X2.3 connector

4 X4 connector

5 AC and LINK LEDs

6 X3 connector

7 Disconnector status LEDs

8 Grounding disconnector status LEDs

7 8

11

Section 2

ARC600 overview

2.2.2 Serial panel

1

2

3

4

5

6

GUID-E93D22FF-C310-4B4E-929D-8AB8800F0241 V3 EN

Figure 4: Serial panel

1 Console serial port (DIP switch selectable application or console port RS1)

2 Power switch

3 Serial console switch (RS1)

4 Serial port 2 hardware configuration DIP switches

5 Serial port 2

6 Ethernet connector

1MRS758459 C

12 ARC600

User Manual

1MRS758459 C

2.2.3

2.2.4

ARC600

User Manual

Section 2

ARC600 overview

Antenna panel

1

2

3

GUID-35D4C58E-AD09-401B-91D1-09917E75F5C2 V2 EN

Figure 5: Antenna panel

1 SIM card tray connector

2 SIM card tray release button

3 Antenna connector SMA (female)

System status LEDs

The device has eight LEDs indicating the system status. They are located on the front panel.

Table 1:

Label

VPN

Power/Error

Function

Eth

Description of available LEDs

State

On

Flashing

Off

On

Off

On

Flashing

On

Flashing

Off

Table continues on next page

Description

VPN connection is up

VPN connection is starting

VPN connection is disabled

Operating power is turned on

Operating power is turned off

Device is starting

Device is operating normally

Ethernet link is up

Ethernet link is transferring data

Ethernet link is down

13

Section 2

ARC600 overview

2.3

2.4

2.5

1MRS758459 C

Label

Cellular

AC

LINK

DISCONNECTO

RS 1...3

OPEN

CLOSE

REMOTE

GROUNDING

1...3

OPEN

CLOSE

State

Flashing

Off

On

Off

On

Off

On/Off

On

Off

On/Off

Description

Cellular connection is starting or transferring data

Cellular connection is inactive

Connected to AC power

Not connected to AC power

IEC 60870-5-104 control link to SCADA is active

IEC 60870-5-104 control link to SCADA is active

Open position indication for disconnector

Close position indication for disconnector

Remote control indication

Local control indication

Open position indication for grounding disconnector

Close position indication for grounding disconnector

DIN rail mounting

The device has mounting grooves for DIN rail mounting brackets and it is supplied with pre-installed DIN rail brackets.

Product information label

The product label contains basic information about the unit such as product name, serial number and Ethernet MAC address.

The product label is found on top of the device.

Firmware version

The device's firmware version is visible on the welcome page ( System/Welcome

Page ), which is displayed after logging in to the device.

For firmware updates, contact ABB's technical customer support.

14 ARC600

User Manual

1MRS758459 C

Section 3 Physical connections

Section 3

Physical connections

3.1

3.1.1

3.1.1.1

Communication connections

The device uses the serial ports for console or application communication, the

Ethernet port for network communication and cellular connectivity for wireless applications.

Serial ports

The device has two application serial ports. Serial port 1 is configurable to either console or data mode and supports RS-232 only. Serial port 2 is configurable to multiple serial modes (RS-232/422/485). Serial port connectors are 9-pin D-sub male connectors. Serial ports function as DTE devices.

Console/serial port 1

The console switch enables or disables console access. When the switch is in the right position, serial port 1 is in the serial port mode, and when it is in the left position, serial port 1 is in the console mode.

The console switch is located below the serial port 1 connector. Turn off power from the device before toggling the console switch, as the switch position is read during the boot sequence only. The baud rate is fixed to 115200 bps when the port is configured in the serial console mode.

GUID-9F6668AA-EBAB-46B5-A1AF-35D8AE3E6C12 V1 EN

Figure 6: Console/RS1 port connector

Table 2: Console/RS1 port pinout

PIN

1

2

3

4

5

6

Table continues on next page

Function

DCD

RXD

TXD

DTR

GND

DSR

ARC600

User Manual

15

Section 3

Physical connections

3.1.1.2

1MRS758459 C

PIN

7

8

9

Function

RTS

CTS

RI

Table 3:

Parameter

Baud rate

Data bits

Parity

Stop bits

Flow control

Console/RS1 port configuration

Value

300...230400 (console 115200) bps

8

No parity

1

No flow control

Serial port 2

Serial port 2 can be configured to multiple serial formats (RS-232/422/485). The default is RS-232.

GUID-9F6668AA-EBAB-46B5-A1AF-35D8AE3E6C12 V1 EN

Figure 7: Application serial port

Table 4:

3

4

5

6

PIN

1

2

7

8

9

Application serial port pinout (RS-232)

Function

DCD

RXD

TXD

DTR

GND

DSR

RTS

CTS

RI

16 ARC600

User Manual

1MRS758459 C

ARC600

User Manual

Section 3

Physical connections

Table 5:

Parameter

Baud rate

Data bits

Parity

Stop bits

Flow control

Application serial port configuration

Value

300...460800 bps

8

No parity

1

CTS/RTS

By default, all DIP switches are set to the 0 position (RS-232 mode). DIP switches

2...4 apply only when DIP switch 1 is set to differential mode (RS-485/RS-422).

Table 6:

DIP switch

1

2

3

4

DIP switches

Mode

RS-232 or differential

DUPLEX

BIASING

TERMINATION

State

0 = RS-232, 1 = RS-485 and RS-422

0 = FULL, 1 = HALF

0 = OFF, 1 = ON

0 = OFF, 1 = ON

Description

Selects the serial port operation mode

Selects between

RS-422 full-duplex (4wire) and RS-485 halfduplex (2-wire) differential modes

Enables RS-422 biasing on pins 2 and 8

Enables RS-422 termination on pins 2 and 8

If biasing and/or termination is required for the RS-485 half-duplex

(2-wire) mode, enable RS-422 biasing/termination with DIP switches and manually connect pins 2-7 and 3-8 together at the application port

(RS-2).

Do not connect RS-422 or RS-485 cables to a serial port configured to the RS-232 mode. This could damage the port and the connected equipment.

Table 7:

PIN

1

2

Application serial port pinouts in RS-422/485 modes

3

4

5

Table continues on next page

RS-422 full-duplex (4-wire)

-

RXD positive (in)

-

TXD negative (out)

GND

RS-485 half-duplex (2-wire)

-

-

-

TXD/RXD negative (out/in)

GND

17

Section 3

Physical connections

3.1.2

1MRS758459 C

8

9

PIN

6

7

RS-422 full-duplex (4-wire)

-

TXD positive (out)

-

RXD negative (in)

-

-

RS-485 half-duplex (2-wire)

-

TXD/RXD positive (out/in)

Ethernet

The device has an RJ-45 connector for 10/100 Mbps Ethernet connection. The maximum length of the Ethernet cable is 100 m.

3.1.3

18

GUID-B51827C7-18A7-4713-9E56-6DECBFE71428 V1 EN

Figure 8: Ethernet connector

Table 8: Ethernet port configuration

Description

Number of ports

Speed

Duplex

Auto-negotiation

Recommended cabling

Value

1

10Base-T, 100Base-TX

Half and full duplex

Yes

Cat5e or better

Wireless network

The device supports cellular connectivity (2G, 3G, LTE) allowing the use of wireless applications. The device supports wireless data speed up to 100 Mbit/s. The practical data transfer rates depend on the subscription details and wireless network capacity.

The device with wireless interface includes an SMA female type connector for an external antenna. Any kind of external 50 Ω wide band antenna can be used intended for GPRS, 3G or LTE frequency bands. The antenna is connected directly to the connector located on the device's back panel.

Commercially available antennas are usually provided with a flexible 50 Ω cable with a length of 2...3 meters and a male type SMA connector.

ARC600

User Manual

1MRS758459 C

3.2

3.2.1

3.2.2

Section 3

Physical connections

If the PIN code query is enabled, check that the ARC600 configurator has the correct PIN code entered in the wireless WAN submenu.

I/O connections

The device has four connectors in the front panel for power input and for switching devices' status monitoring and control, battery condition monitoring, battery charging and measurement functions.

Power connector

Operating power for the device is supplied from connector X2.1. The device can use either an unregulated AC line input or a regulated DC input.

The power switch is located on the serial panel. It turns the unit on and off.

Table 9:

Input pins

1 and 2 (AC)

6 and 7 (DC)

Operating voltages of X2.1 connector pins

Operating voltage range

90...264 V AC or 85...200 V DC

20...30 V DC

X2.1 connector

4

5

6

7

8

9

10

Table 10:

Pin

1

2

3

X2.1 connector pinout

Symbol

L

N

NTC_A

PE

NTC_B

24VDC

GND

GND

GND

BAT

Description

230 V AC

230 V AC

NTC resistor (battery temperature comp.)

Protective earth

NTC resistor (battery temperature comp.)

24 V DC output/input

DC ground

DC ground

DC ground

Battery charging

ARC600

User Manual

19

Section 3

Physical connections

Table 11:

Connector

Panel header

Matching plug

X2.1 connector types

Manufacturer

Phoenix Contact

Phoenix Contact

AC STATUS

SA

DC

AC

3.2.3

20

1MRS758459 C

Connector type (part number)

MSTBV 2,5 HC/10–GF-5,08

(1924606)

MSTB 2,5 HC/10–STF-5,08

(1912265)

SC

SB

RA

L N NTC_A PE NTC_B 24VDC

GUID-217F2A86-3BBB-4FBD-9BE1-BD8F8D6EC3EF V1 EN

Figure 9: X2.1 connector schematics

GND GND GND

X2.3 connector

Table 12:

PIN

1

2

X2.3 connector pinout

Symbol

DI1

DI_C1

3

4

5

DI2

DI3

DI_C2

6

7

DI4

DI5_A

8 DI5_B

Table continues on next page

Description

Digital input 1

Common supply voltage for DI1 and DI2

Digital input 2

Digital input 3

Common supply voltage for DI3 and DI4

Digital input 4

Digital input 5

Digital input 5

Disconnector function

Disconnector 1 opened

Disconnector 1 closed

Disconnector 2 opened

Disconnector 2 closed

Local/Remote switch for disconnector 1

ARC600

User Manual

1MRS758459 C

Section 3

Physical connections

PIN

9

13

14

15

10

11

12

16

17

18

Symbol

DI6_A

DI6_B

DO1_A

DO1_B

DO2_A

DO2_B

DO3_A

DO3_B

DO4_A

DO4_B

Table 13:

Connector

Panel header

Matching plug

X2.3 connector types

Manufacturer

Phoenix Contact

Phoenix Contact

Description

Digital input 6

Digital input 6

Relay output 1

Relay output 1

Relay output 2

Relay output 2

Relay output 3

Relay output 3

Relay output 4

Relay output 4

Disconnector function

Local/Remote switch for disconnector 2

Close disconnector 1

Open disconnector 1

Close disconnector 2

Open disconnector 2

Connector type (part number)

MSTBV 2,5/18–GF-5,08

(1777235)

MSTB 2,5/18–STF-5,08

(1778140)

3.2.4

ARC600

User Manual

OPENED 1 CLOSED 1 OPENED 2 CLOSED 3 LOC/REM 1 LOC/REM 2 CLOSE 1

GUID-1087841A-5BD0-4724-B006-C7D415167D17 V2 EN

Figure 10: X2.3 connector schematics

OPEN 1 CLOSE2 OPEN 2

X3 connector

Disconnector 3 and grounding disconnectors

Table 14:

PIN

1

2

3

4

IO3 connector pinout

Symbol

DI7

DI_C3

DI8

DI9_A

Description

Digital input 7

Common supply voltage for DI7 and DI8

Digital input 8

Digital input 9

Disconnector function

Disconnector 3 opened

Disconnector 3 closed

Local/Remote switch for disconnector 3

Table continues on next page

21

Section 3

Physical connections

1MRS758459 C

13

14

11

12

15

16

PIN

5

6

7

8

9

10

Symbol

DI9_B

DO5_A

DO5_B

DO6_A

DO6_B

DI_C4

DI10

DI11

DI12

DI13

DI14

DI15

Table 15:

Connector

Panel header

Matching plug

X3 connector types

Manufacturer

Phoenix Contact

Phoenix Contact

Description

Digital input 9

Relay output 5

Relay output 5

Relay output 6

Relay output 6

Common supply voltage for DI10, DI11,

DI12, DI13, DI14 and

DI15

Digital input 10

Disconnector function

Close disconnector 3

Open disconnector 3

Digital input 11

Digital input 12

Digital input 13

Digital input 14

Digital input 15

Grounding disconnector 1 open

Grounding disconnector 1 closed

Grounding disconnector 2 open

Grounding disconnector 2 closed

Grounding disconnector 3 open

Grounding disconnector 3 closed

Connector type (part number)

MSTBV 2,5/16–GF-5,08

(1777219)

MSTB 2,5/16–STF-5,08

(1778124)

DISCONNECTOR 3 STATUS & CONTROL GROUNDING DISCONNECTORS STATUS

22

OPENED 3 CLOSED 3 LOC/REM 3

GUID-6BC1CF09-EDED-406C-8065-EE3284251506 V1 EN

CLOSE 3

Figure 11:

OPEN 3

X3 connector schematics

GO1 GC1 GO2 GC2 GO3 GC3

ARC600

User Manual

1MRS758459 C

3.2.5

Section 3

Physical connections

X4 connector

Table 16:

PIN

1

X4 connector pinout

Symbol

LOADCUT_A

2

3

LOADCUT_B

AI1_A

4 AI1_B

5

6

7

8

9

TESTLOAD_A

TESTLOAD_B

HTR_A

HTR_B

AI2_A

10 AI2_B

11 DIC_5

12

13

14

15

DI16

DI17

DO7_A

DO7_B

1) Can be used as a 4...20 mA input using external resistor

Table 17:

Connector

Panel header

Matching plug

X4 connector types

Manufacturer

Phoenix Contact

Phoenix Contact

Description

Load control relay out, normal closed (NC)

Load control relay out, normal closed (NC)

Analog In 1, -5 V...+5 V measurement, ±300 mV

(-10...+55°C, 0 V...+5 V), Hallsensor 1)

Analog In 1, -5 V...+5 V measurement, ±300 mV

(-10...+55°C, 0 V...+5 V), Hallsensor 1)

Relay out, test load for battery test case

Relay out, test load for battery test case

Heater/Extra relay

Heater/Extra relay

Analog In 2, -5 V...+5 V measurement, ±300 mV

(-10...+55°C, 0 V...+5 V), Hallsensor 1)

Analog In 2, -5 V...+5 V measurement, ±300 mV

(-10...+55°C, 0 V...+5 V), Hallsensor 1)

Common supply voltage for

DI16, DI17

Digital input 16

Digital input 17

Relay output 7

Relay output 7

Connector type (part number)

MSTBV 2.5/15-GF-5.08

(1777206)

MSTB 2.5/15-STF-5.08

(1778111)

ARC600

User Manual

23

Section 3

Physical connections

1MRS758459 C

3.2.6

3.2.6.1

3.2.6.2

24

1 2 3 4 5 6 7 8 9 10

LOAD/CUT LOAD CURRENT TEST LOAD HEATER -5...5 V 1)

GUID-4A4FF16A-8E32-41CD-989E-AC0900D9C845 V2 EN

Figure 12: X4 connector schematics

1) Can be used as a 4...20 mA input using external resistor

11 12 13

EXTRA INPUTS

14 15

EXTRA OUTPUT

I/O LEDs

The device has two LEDs indicating the AC and LINK status. Nine LEDs are available to indicate the disconnector status. For indicating the grounding disconnector status, the device has six LEDs.

AC and LINK LEDs

The device has two LEDs indicating the AC and LINK status.

Table 18: AC and LINK LEDs

LED Description

AC AC power is connected to connector X2.1 pins 1 and 2

LINK The IEC control link to SCADA is active

Disconnector LEDs

The device has nine LEDs to indicate the disconnector status. They are located on the device front panel. Each disconnector has three LEDs, which indicate the status of the disconnector.

Table 19: Disconnector LEDs

Disconnector LED

Disconnector 1 open

Disconnector 1 close

Disconnector 1 remote

Disconnector 2 open

Disconnector 2 close

Table continues on next page

Description

Disconnector 1 is opened

Disconnector 1 is closed

Disconnector 1 is on remote control

Disconnector 2 is opened

Disconnector 2 is closed

ARC600

User Manual

1MRS758459 C

3.2.6.3

Section 3

Physical connections

Disconnector LED

Disconnector 2 remote

Disconnector 3 open

Disconnector 3 close

Disconnector 3 remote

Description

Disconnector 2 is on remote control

Disconnector 3 is opened

Disconnector 3 is closed

Disconnector 3 is on remote control

Disconnector LEDs can indicate two special cases.

Table 20: Disconnector LED special cases

Disconnector LED state

Open and close LEDs are both OFF

Open and close LEDs are both ON

Description

Disconnector is changing state

Disconnector error

Grounding LEDs

The device has six LEDs indicating the grounding status. They are located on the device front panel. Each grounding disconnector has two LEDs, which indicate the status of the grounding disconnector.

Table 21: Grounding LEDs

Grounding LED

Disconnector 1 open

Disconnector 1 close

Disconnector 2 open

Disconnector 2 close

Disconnector 3 open

Disconnector 3 close

Description

Connector X3 digital input on pin 11 is active high

Connector X3 digital input on pin 12 is active high

Connector X3 digital input on pin 13 is active high

Connector X3 digital input on pin 14 is active high

Connector X3 digital input on pin 15 is active high

Connector X3 digital input on pin 16 is active high

All grounding disconnector digital input pins have connector X3 pin 10 as the common ground pin.

ARC600

User Manual

25

26

1MRS758459 C

Section 4 Functional description

Section 4

Functional description

4.1

4.2

4.2.1

4.3

4.3.1

Control functions

The device is capable of controlling and monitoring an object, for example, a disconnector, and handling the object status information. The device can control and monitor up to three objects. The device can monitor the earthing switch position indications, with one function per disconnector object. Local/Remote indications are also a standard; each disconnector has its own Local/Remote position monitoring. In the Local position, control operations (open or close) can be performed at the site only.

In the Remote position, control operations can be performed from the SCADA system in the network control center.

Condition monitoring functions

Communication diagnostics and watchdog

The device is provided with a self-supervision system, that is, a watchdog function.

The self-supervision system handles run-time fault situations and informs the user of faults through the user HMI (function LED) on the front panel.

In addition to hardware supervision, the self-supervision system is able to re-establish the cellular connection and VPN connection (if applicable). Furthermore, it is able to restart the device as a last resort.

Disconnector control condition monitoring functions

Disconnector travel time monitoring

The OPEN and CLOSE indications are monitored. When a change occurs due to an activated control operation, the opening or closing travel time is measured. If the measured travel time is greater than or equal to the set limit values, an alarm is given.

The settings define how the disconnector travel time duration (state change from open to close or vice versa) is reported.

Travel time is reported in seconds. The alarm signals remain active until the fault condition is acknowledged.

ARC600

User Manual

27

Section 4

Functional description

1MRS758459 C

GUID-F5C190C6-50AB-4F6B-B838-71C701B55AC6 V1 EN

Figure 13: Travel time measurement for open operation

4.3.2

28

GUID-3814AA73-1F7B-496E-B9E8-C8D897E05A94 V1 EN

Figure 14: Travel time measurement for close operation

Disconnector actuator motor overload protection

With an optional Hall effect sensor, the device is able to measure the load current that flows through the actuator during the control operation of the disconnector. This current measurement is effectively used to detect an abnormality in the mechanical motion, when the lever that operates the disconnector moves from one end position to the other (for example, from Open to Close). A slip in the mechanical gear unit or a mechanically stiff operation, due to insufficient lubrication or deviation in operation tube positioning, can cause an overload situation which may be harmful to the actuator motor if no action is taken to prevent overloading.

Even if MCB’s are used as an overload protection, they are not optimal from the maintenance point of view, as they require a site visit because the resetting is typically

ARC600

User Manual

1MRS758459 C

4.3.3

4.4

4.4.1

ARC600

User Manual

Section 4

Functional description

managed manually. The device's intelligent overload protection function, for example, the resetting and adjustment of the current pick-up level, is managed remotely from a utility dispatch center, using a system such as SCADA. The overload protection is coordinated with the possible MCB in the same circuit so that the current pick-up setting is lower than the MCB operational level to avoid unnecessary site visits.

Monitoring of the pressure of SF6 gas

The SF6 insulated primary equipment is arranged by wiring the pressure sensor contact to one input of the device, used for monitoring the SF6 gas pressure. When the gas pressure drops below the acceptable limit, the falling edge of the digital signal triggers and activates an alarm signal. This information can be obtained as an alarm event from the network control system.

Battery charging and monitoring functions

Power backup for the station can be arranged by connecting 24 V (2 × 12 V) sealed lead acid batteries to the device. The batteries supply power to both the device and the communication device during a mains failure. As the batteries are charged by the device, the communication between the unit and the network control center is always operating irrespective of distribution network faults or planned outages.

The battery condition is secured by a battery load and condition monitoring test, activated remotely via a command from the SCADA system. In the test, a discharge resistor is connected in parallel to the batteries. During the test, the battery capacity is measured and reported as an Ah value to indicate the remaining capacity, so that maintenance can be optimized. The battery test can be started directly from the control room or run automatically according to the agreed timetable. During the battery load test, which takes 2...5 h, the voltage of the battery charger is shut off and the control functionality is blocked.

If the battery voltage drops to less than the set value, for example, 22 V, during the battery load test, the device generates an alarm event. This indicates that the lifetime of the batteries is ending or that an internal fault has occurred in the battery or its circuitry. In both cases, the battery must be replaced.

During normal control operations, the device makes condition measurements, such as the battery voltage minimum value and the maximum current. The battery condition and lifetime can be estimated based on these recorded values.

Power backup

Power backup for the station can be arranged by connecting 24 V (2 × 12 V) sealed lead acid batteries to the device. The batteries supply the device and keep the

29

Section 4

Functional description

4.4.2

1MRS758459 C communication alive during a mains failure. Thus the communication between the device and a network control centre operates in any situation.

Depending on the application and the required maximum operation time, batteries of different capacity are used; the typical capacity is 17 Ah. With the 17 Ah battery, the maximum operation time is 48 hours (including safety coefficient) at ambient temperature of +20°C.

A low temperature reduces battery capacity and lifetime.

Heater control

The heater control is based on the environmental temperature. Heating is needed if the device is installed in a separate enclosure outdoors where the ambient temperature may be below 0°C. Heating is specifically required in very damp conditions when dehumidifying is needed. The heating control consists of switching on and off an output pin connected to an external control relay of the heating element (resistor), which is located in the enclosure, preferably next to the batteries and the electronics components.

The device contains an internal thermostat for controlling the external heater. The heater element can be set to be constantly on, for example, if the element contains an internal thermostat, constantly off or to be controlled by the environmental temperature.

The heater output pins are X4 7 and 8. This is defined by giving the parameter heater_output value “9”.

The settings are defined in the section [HEATER].

HEATING ON trigger_limit+trigger_hyst trigger_limit

HEATING OFF

GUID-F7FFDC79-AE39-4582-BA38-32ADF4C433FD V1 EN

Figure 15: Heater control on auto-mode

HEATING OFF

Time

HEATING ON

30 ARC600

User Manual

1MRS758459 C

4.4.3

4.4.4

4.4.5

4.4.6

ARC600

User Manual

Section 4

Functional description

Low auxiliary voltage indication

The power supply module gives an internal alarm signal when a drop in the power supply voltage is detected (AC Fail). The indication of a low auxiliary voltage can be reported to any available communication protocol supported by the device.

Over/undertemperature indication

The power supply module gives an internal alarm signal when over- or undertemperature is detected inside the enclosure. The alarm is activated when the temperature inside the enclosure surpasses a set limit or decreases below a set limit.

Hysteresis can be set for both indication functions. The indication can be reported through any available communication protocol supported by the device.

Temperature compensation of battery charging voltage

The charging voltage of the internal battery charger of the device is temperaturecompensated. The compensation factor is approximately -40 mV/°C. The data about the temperature is acquired with the help of a 2.2 kΩ NTC thermistor that is connected to pins 3 and 5 of the connector X2.1. If the battery charger is not used to charge the battery, the thermistor or the 2.2 kΩ resistor must still be installed between the pins 3 and 5 of the connector X2.1. Otherwise, the overvoltage protection of the charger may activate and prevent the device from starting.

It is recommended to install NTC thermistor between the batteries.

Battery deep discharge protection

When the battery voltage falls below a certain value, the battery is almost empty. To prevent battery damage, the battery should not be further discharged. The battery deep-discharge protection function disconnects the battery from the device in two cases.

• AC supply is not available to charge the battery.

• Battery voltage stays long enough below the defined limit.

Usually the deep-discharge protection causes the device to shut down due to lack of power. The device recovers once the AC supply becomes available again or it is powered up with DC on the modem-supply pin (X2.1 pin 6). External loads such as a

Hall sensor, additional DC-powered ARC600 devices or the supply for input circuits should not be connected directly to the battery but to the “master” ARC600 24 VDC

In/Out pin (X2.1 pin 6). This way, the whole load can be removed at once when the deep-discharge protection is required. The settings are defined in the section

[BATTERY_DISCHARGE_PROTECTION].

31

Section 4

Functional description

4.4.7

4.4.7.1

4.4.7.2

1MRS758459 C

Battery capacity test

The device can test the capacity of the battery by disconnecting the charger and draining the battery to almost empty using an external loading resistor. The test is completed when the battery voltage reaches the defined voltage limit. The battery capacity can be returned by protocol communication in ampere-hours. The battery draining current is measured by external Hall sensor connected to analog input 1 (X4

3-4). The loading-resistor current should be routed through the relay contacts of X4 pins 5 and 6.

The test is started by protocol communication command. The information object is defined in the section [BATTERY_TEST_CONTROL_SC].

Certain conditions can be defined to abort the test.

• AC voltage is missing.

• Temperature is too high.

• Temperature is too low.

• Battery voltage does not reach the defined completion limit during timeout.

• Battery draining current too low.

• Battery draining current too high.

• Abortion command is issued by protocol communication.

The test is completed when the measured battery voltage stays below the defined voltage limit. This means the battery is almost empty and the available capacity can be estimated by multiplying the consumed charge by compensation factor. For example, if the defined target voltage means the battery to be 90% discharged, a multiplication factor 1.11 can be used to estimate the available total capacity. The device can compensate the cabling-loss voltage and include its internal charge consumption to the total capacity.

Usually, the disconnectors are internally blocked during the battery test and the test should be remotely stopped (information object

[BATTERY_TEST_CONTROL_SC]) before the disconnectors can be operated. The blocked state can be indicated by configuring the local/remote status to double-point indication [DISCONNECTOR_LOCREM_xx].

The load limiter functionality and the heater are disabled during the test.

Settings

The battery capacity test settings are defined in the section [BATTERY_TEST].

Remote control of the battery test function

Once the battery test functionality is enabled on the configuration file, it can be remotely controlled by protocol communication. The information object is defined in the section [BATTERY_TEST_CONTROL_SC].

32 ARC600

User Manual

1MRS758459 C

4.4.7.3

4.4.7.4

4.4.7.5

4.5

ARC600

User Manual

Section 4

Functional description

• 0 = Abort the battery test

• 1 = Start the battery test

Battery test status

The status of the battery testing is available for the protocol communication. The information object is defined in the configuration file section

[BATTERY_TEST_STATUS_DPI].

• 0 = Idle (not testing the battery)

• 1 = Testing (discharging the battery by using external load)

• 2 = Test complete

• 3 = Test aborted

Battery capacity

The measured battery capacity can be reported as a short floating-point value. The reporting unit is ampere-hours Ah. For settings, see the general floating-point input settings. The measured capacity is always reported after the test is completed. The information object is defined in the configuration file section

[BATTERY_TEST_CHARGE_FPI].

Measurement file

The device can generate the internal measurement file from the battery capacity testing. The measurement file is written every averaging_interval_sec and each line contains a time stamp, status, battery voltage, discharge current and the charge consumed so far. The file header contains the unloaded battery voltage before the load is applied. The last line of the file contains information whether the test was completed successfully or aborted for a specific reason.

Measurement functions

The device measures the battery voltage and the ambient temperature. The temperature measurement is calibrated to measure the ambient temperature of the device mounted in an enclosure. The temperature measurement is used to compensate for the charging voltage of the batteries and for activating or deactivating heating in cold environments. The battery voltage is measured as two values: the minimum battery voltage and the maximum current during control operation. The minimum battery voltage indicates the lowest voltage measured during a battery test or during an object's operation. The battery-charging voltage indicates the present voltage on the battery poles. The values can be read from the network control center via the supported communication protocols. The minimum battery voltage and the maximum current can be reset via the serial bus.

33

Section 4

Functional description

4.5.1

4.5.1.1

4.5.1.2

4.5.1.3

4.5.1.4

1MRS758459 C

The device supports a general-purpose analog input that can be used as a transducer input. It supports voltage mode -5…5 V, ±300 mV (-10...+55°C, 0 V...+5 V).

The input can be used as current mode 4...20 mA using an external resistor.

Temperature measurement

The device has four temperature sensors.

Processor temperature

The ambient temperature of the process is measured by a sensor whose measurement result is available on the System tab of the Web user interface and with the command line command temperature. The measurement data of the sensor is not available with protocol communication.

Communication module temperature

The internal temperature of the wireless communication module is available on the

Web user interface under Tools/Modem Info and with the command line command modeminfo. The measurement data of the sensor is not available with protocol communication.

Sensor for the temperature compensation of the charging voltage

The internal sensor of the device adjusts the battery charging voltage based on the battery temperature. The data about the temperature is gained with the help of a 2.2 kΩ

NTC thermistor that is connected to pins 3 and 5 of the connector X2.1. The thermistor is located between the batteries. The measurement data of the sensor is not available with protocol communication but it is only used for adjusting the charging voltage.

Ambient temperature

The temperature of the device casing is used for estimating the ambient temperature.

Because the power consumption of the device affects the casing temperature, its effect is compensated based on calculations. The compensation parameters are defined in the setting file section [PHYSICAL_TEMP].

The ambient temperature calculated from the casing temperature is available with protocol communication. The temperature object is defined in the setting file section

[TEMPERATURE_FPI]. This temperature is also used for temperature alarm

([TEMPERATURE_LOW_SPI], [TEMPERATURE_HI_SPI]), battery testing temperature guard ([BATTERY_TEST]) and heater control ([HEATER]).

Example

34 ARC600

User Manual

1MRS758459 C

4.6

4.6.1

Section 4

Functional description

• Casing temperature 47 °C

• Fixed temperature difference -10 °C

• Charging current 2 A

• Charging current effect 3.5 °C/A

• Ambient temperature (47-10) °C - 2 A * 3.5 °C/A = 30 °C

Load limiter

The device can detect excessive loading of battery due to jammed disconnector switchgear and disconnect the load before the actual physical overcurrent fuse trips.

The overload decision is based on both the consumed charge and duration of the loading. The current is measured usually by an external Hall sensor connected to analog input 1 (X4 3-4). The device uses a normally closed relay (X4 1-2, Load Cut) to break down the loading circuit by opening the relay contacts for a moment. Usually this is used to cut the holding circuit of motor contactors, not directly the motor current.

Overload detection settings

The overload detection settings are defined on section [LOAD_LIMITER]. The detection is based on the load current measurement by the external Hall sensor connected to X4 pins 3 and 4.

ARC600

User Manual activation_current deactivation_current

Accumulated Charge

0 activation_time_ms

STATUS

Idle

GUID-35015FD5-8184-40F1-B0C6-CAFFC0CE5362 V1 EN

Figure 16: Load limiter measurements

Accumulated Time

Accumulating deactivation_time_ms

Time

Idle

35

Section 4

Functional description

1MRS758459 C

Accumulated Charge > trip_charge activation_current deactivation_current

0

STATUS

Idle activation_time_ms

Accumulating

CONTROL

OUTPUT

OFF

GUID-ACA0C63F-ECD9-494B-90F4-5D69221D571E V1 EN

Figure 17: Overload caused by charge

Overload

(charge)

ON

Time

Idle

OFF trip_duration_sec

36 ARC600

User Manual

1MRS758459 C

Section 4

Functional description

4.6.2

4.6.3

ARC600

User Manual activation_current trip_time_sec

Accumulated Charge < trip_charge

0

STATUS

Idle activation_time_ms

Accumulating

Overload

(duration)

ON

Time

Idle

CONTROL

OUTPUT

OFF

GUID-8B4D7B83-F1F4-4D6E-AB17-BBF9AF5A520A V1 EN

Figure 18: Overload caused by duration trip_duration_sec

OFF

Remote enabling and disabling of the load limiter

Once the load limiter functionality is enabled on the configuration file, it can be remotely controlled by the protocol communication. The information object is defined in the section [LOAD_LIMITER_CONTROL_SC].

• 0 = Disable load limiter

• 1 = Enable load limiter (if enabled on configuration file)

The issued value is not permanently stored and effects only until reboot or application restart.

Load limiter status

The current status of the load limiter function is available for protocol communication.

The information object is defined in the section [LOAD_LIMITER_STATUS_DPI].

• 0 = Load limiter idle (waiting for the current to exceed the threshold)

• 1 = Load limiter disabled (does not monitor load)

• 2 = Loading detected, accumulating

• 3 = Overload, load disconnected

37

Section 4

Functional description

4.6.4

4.6.5

4.6.6

4.7

1MRS758459 C

Reason for load limiter activity

The overload decision is based on both consumed charge and duration of the loading.

Once the overload situation is detected, the reason can be reported as double-point input. The information object is defined in the section

[LOAD_LIMITER_REASON_DPI].

• 0 = None, overload situation not detected

• 1 = Overload caused by consumed charge

• 2 = Overload caused by duration of loading

• 3 = Overload detected by manual command

Measured charge during overload

The overload decision is based on both consumed charge and duration of the loading.

Once the overload situation is detected, the accumulated charge can be reported as a short floating-point value. The reporting unit is ampere-seconds. If no overload situation has been detected, the reported value is zero and has a non-topical NT flag set. The information object is defined in the section

[LOAD_LIMITER_CHARGE_FPI]. This charge is reported only when the overload situation is detected. The consumed charge for normal operation is reported by

[DISCONNECTOR_TRAVELCHARGE_N].

Measured time during overload

The overload decision is based on both consumed charge and duration of the loading.

Once the overload situation is detected, the loading duration can be reported as a short floating-point value. The reporting unit is seconds. If no overload situation has been detected, the reported value is zero and has a non-topical NT flag set. The information object is defined in the section [LOAD_LIMITER_TIME_FPI]. This duration is reported only when the overload situation is detected. The travel time for normal operation is reported by [DISCONNECTOR_TRAVELTIME_N].

Support for fault indicators

The device contains a driver for the ABB RIO600, Horstmann ComPass-B and Kries

IKI-50 fault indicators. The driver polls the fault indicator devices using Modbus and converts the values to IEC 60870-5-104. Up to four fault indicators can be connected.

38 ARC600

User Manual

1MRS758459 C

Section 5 Cyber security

5.1

5.2

Section 5

Cyber security

Cyber security definition

Cyber security aims to secure the properties of the organization against security risks.

To strengthen the system and increase the security level towards any cyber security attacks from the Internet, certain actions are recommended while configuring the device.

• The device should be installed physically secure, for example, in a locked cabinet.

• The latest security updates need to be installed for all network devices.

• The network inventory needs to be documented and kept up to date.

• Unused services and interfaces should always be disabled.

• Only VPN connections should be used to access remote networks.

Enhancing operator and subscription security

Network subscription and SIM card must be stored safely and configured to prevent misuse of services.

• Disable unused services from SIM cards.

Voice calls

SMS

Paid services

Roaming

• Use pin code in SIM cards.

• Prefer a private APN service from the operator.

• Prefer M2M subscription SIM cards from the operator.

• Use private IP addressing from the operator for cellular network based communications.

• If connected to a public IP network, do not use plain text protocols such as http,

SNMP and telnet. Always use VPN to connect to the device.

ARC600

User Manual

39

Section 5

Cyber security

5.3

1MRS758459 C

Configuring firewall and services

Enable the firewall and disable the unused services and interfaces in the device. To start, disallow traffic and allow only the needed traffic. Use the default policy to drop connections.

• Check that the firewall is enabled.

• For incoming connections, always filter (drop) all unused ports which may include DNS, L2TP-VPN, SNMP and so on.

• Check that the default action is “drop” in firewalls and allow only the needed ports.

• Set unique passwords for each device.

• Keep passwords stored in a safe place, for example, Encrypted password management tool.

• Check that all unused services are disabled.

• If possible, allow IP connections only via VPN.

• Disable all unused services, for example, Dial-in, SMSconfig, serial and SNMP.

• Back up the configuration.

40 ARC600

User Manual

1MRS758459 C

Section 6 Getting started

6.1

6.1.1

6.2

ARC600

User Manual

Section 6

Getting started

Connecting cables

1.

Check that the power switch is in the OFF position.

2.

Connect the Ethernet cable between the device’s Ethernet LAN connector and the computer used for the configuration.

3.

Connect the power supply to the device.

4.

Toggle the power switch to ON position.

The power/error LED and function LED should turn on immediately after the power switch is turned on.

After the system has initialized, the function LED starts to flash.

Connection principle

The device has configurable network interfaces.

• Ethernet LAN port

• Mobile WAN cellular interface

The device supports cellular connectivity (2G, 3G, LTE) allowing the use of wireless applications. The WAN interface is used for connecting the device to public Internet or private APN. The Ethernet LAN is used for connecting other Ethernet devices to the device's local network.

The WAN interfaces can be configured to create a redundant system where one WAN automatically receives traffic if the other one goes down. For example, if the primary

Ethernet connection goes down, the traffic is automatically switched to mobile WAN

(secondary connection) and back when the Ethernet interface comes up again.

Logging in

1.

Configure the computer to use the same IP address space as the device.

Example: Laptop IP is 10.10.10.11 with netmask 255.255.255.0.

2.

Check the IP configuration with the ping command in the command line.

3.

In a Web browser, connect to the device over the HTTPS protocol using the device’s IP address.

Example: The default IP address of the device is 10.10.10.10. The corresponding address to enter in the browser is https://10.10.10.10/.

41

Section 6

Getting started

6.2.1

6.3

1MRS758459 C

Ignore the browser's warning about a self-signed certificate.

4.

Enter the username and password.

The default username is “arctic-adm“ and the default password is “arcticm2m”. Change the password before connecting the product to a public network.

5.

Click Login .

The Home Page opens.

User interface

ARC600 configurator is a tool which is used to manage the device properties via a user-friendly, Web-based interface.

To use the Web configurator, only a computer with an HTML browser and a connection to the device are needed. With the configurator, it is possible to receive status information and set parameters and variables that control which applications and processes are used with the device.

After a successful login, the main window is displayed. It consists of the main navigation menu on the top, the navigation bar on the left, and the content area that displays the currently active content and controls.

When the program starts for the first time, the System/Information window is displayed in the content area. The main navigation menu on the top of the window is used to navigate between the different subsets of the available settings. Selecting an item from the main menu displays the available items related to this subset in the navigation bar. The first of these is displayed in the content area by default.

The navigation bar on the left contains the parameter groups in the subset. Selecting an item from this menu displays the content related to the selected group in the content area.

Setting Ethernet port function to LAN

Changing Port function to “LAN” disables automatic IP address detection. If Port function is set to the default value “auto”, the Ethernet LAN port tries to automatically obtain the IP address using DHCP when the device boots. If the DHCP discovery fails, the device automatically uses IP address 10.10.10.10.

42 ARC600

User Manual

1MRS758459 C

6.4

6.5

ARC600

User Manual

Section 6

Getting started

Change the following setting before changing any other Ethernet settings.

1.

In the left pane, under Network , click Ethernet Port .

2.

Set Port function to LAN .

If VLAN connection using an external switch is needed, select VLAN .

3.

Click Submit to save the settings.

If the functional mode of the Ethernet port is set to "WAN" or "VLAN", the following details must be noted. Before changing the Ethernet port mode to "WAN", the firewall configuration needs to allow Web UI and SSH access from WAN ( Firewall/General and enable both Allow WebUI access from WAN and Allow SSH access from WAN ).

The VLAN functional mode of the Ethernet port requires an external VLAN switch.

Configuring mobile WAN

Install the SIM card before configuring the mobile WAN.

1.

In the left pane, under Network , click Mobile WAN .

2.

Enter the preferred configuration in the configuration fields.

3.

Click Submit to save the settings.

Configuring the default route

1.

In the left pane, under Network , click WAN Failover .

2.

Set WAN Default Route to Yes .

This setting enables the use of the Ethernet WAN or the Mobile WAN as the default route interface.

3.

If configuring Ethernet WAN as the default gateway, in the left pane under

Network , click Ethernet Port and set Port function to WAN .

If configuring Mobile WAN as the default gateway, skip this step.

4.

Set the default route.

To select Ethernet WAN as the default gateway, under Primary WAN , set

Interface to Ethernet WAN .

To select Mobile WAN as the default gateway, under Primary WAN , set

Interface to Mobile WAN .

5.

If both Ethernet WAN and Mobile WAN are configured, under Backup WAN , set Interface to Mobile WAN or Ethernet WAN , whichever is not selected as the default gateway.

43

Section 6

Getting started

1MRS758459 C

If the primary WAN interface comes down, the device automatically switches the default route to the backup WAN interface.

6.

Click Submit to save the settings.

7.

Restart the device.

44 ARC600

User Manual

1MRS758459 C

Section 7 Network configuration

Section 7

Network configuration

7.1

7.2

7.2.1

7.2.2

7.2.3

ARC600

User Manual

Defining host and domain names

1.

In the left pane, under Systems , select General Settings .

2.

In the Hostname field, enter the name of the device without the domain part.

3.

In the Domain field, enter the domain name.

Configuring communication interfaces

Configuring Ethernet LAN

1.

In the left pane, under Network , click Ethernet LAN .

2.

Set Enabled to Yes .

3.

Set Interface , IP Address and Subnet mask .

4.

Click Submit to save the settings.

Configuring Ethernet WAN

1.

In the left pane, under Network , click Ethernet WAN .

2.

Set Enable to Yes .

3.

Select a WAN interface .

4.

Select a Configuration Mode .

The “Manual (Static IP Address)” mode requires entering the values in the

Manual Settings fields.

5.

Click Submit to save the settings.

Use the Connectivity Monitor settings when WAN redundancy functionality is required. The Connectivity Monitor keeps checking the connection to the given remote host to determine the network status. If the ping does not get an answer within a given time window, it informs the WAN switch logic to try the secondary interface.

Configuring the mobile WAN interface

1.

Set Enable to Yes .

2.

If the SIM card is protected by a PIN code, enter the code in the PIN Code field.

If necessary, change the SIM card’s PIN code by using a mobile phone.

3.

If automatic APN discovery does not work, define the APN settings.

45

Section 7

Network configuration

7.2.4

7.3

1MRS758459 C

3.1. Set APN Type to Manual .

3.2. Type the cellular access point name in the APN field according to the network operator’s instructions.

By default, the device uses automatic APN discovery with default APN values based on the network ID received from the cellular network. When APN Type is set to “Manual”, the access point works as a gateway from the cellular network to the Internet. There are public and private access points. A public access point is usually defined. A private access point requires contract with a cellular operator. The device is compatible with both public and private access points.

4.

If the cellular network’s access point requires authentication, define the authentication settings according to the network operator’s instructions.

4.1. Set Authentication to PAP or CHAP .

4.2. Type the access point’s username in the Username field.

4.3. Type the access point’s password in the Password field.

5.

If the device acts as a wireless router to Ethernet devices, and DNS is needed, enter the DNS settings.

Set DNS Selection to From Network to set up the device to receive DNS server IP addresses automatically from the cellular network.

Set DNS Selection to Manual to set up the device to use DNS servers manually defined in the DNS Servers field.

6.

Click Submit to save the settings.

7.

Restart the device to activate the configuration.

Setting WAN failover and backup routing

1.

In the left pane, click Network WAN Failover .

2.

Set WAN Default Route to Yes .

This setting enables the use of the Ethernet WAN or the Mobile WAN as the default route interface.

3.

Set the value of Mobile WAN On Demand .

If the backup WAN interface needs to come up only when the primary interface goes down, select Yes .

If both the wireless and Ethernet WAN interfaces have to be up all the time, select No .

4.

Click Submit to save the settings.

5.

Restart the device.

Routing parameters

The device has multiple configuration options that define routing.

46 ARC600

User Manual

1MRS758459 C

7.4

ARC600

User Manual

Section 7

Network configuration

Table 22:

Screen

Ethernet WAN

Routing parameters

Parameter Value

Gateway (IP address) (IP address)

WAN Failover WAN Default Route Yes

No

On Demand Yes

No

Description

IP address of router used to reach the internet. If not used, the field should be empty.

Usually "Yes" if the default route is defined by "static routes". “No” is required if the selection logic is done on VPN level.

"Yes" activates the backup interfaces only when required. "No" makes all the WAN interfaces available simultaneously, for example, for VPNs.

These three settings configure the high-level default gateways. They must be configured to enable default route.

OpenVPN Client

Settings

Primary WAN Interface None

Mobile WAN

Ethernet WAN

Ethernet WAN

Secondary

Backup WAN Interface None

Mobile WAN

Ethernet WAN

Secondary Backup

WAN Interface

None

Mobile WAN

Ethernet WAN

Ethernet WAN

Secondary

Interface

Routing mode

Any WAN

Ethernet WAN

Wireless WAN

Ethernet LAN

None

Host

Net

Default route

This setting defines which interface to use for connection.

This setting defines how the routing is configured with

OpenVPN. See

OpenVPN application note.

Configuring the network monitor

The network monitor detects Internet connectivity drops by sending ping packets to designated targets. Its use is recommended.

1.

In the left pane, under Network , click Monitor .

2.

Set Enable to Yes .

3.

Enter IP addresses for ping targets in Target and Secondary target .

4.

Set the other values in the view.

47

Section 7

Network configuration

7.5

7.6

1MRS758459 C

The user interface contains information on the default values.

5.

Click Submit to save the settings.

Configuring DNS proxy

The solution does not require name resolution because IP addresses are used directly in configuration. If name resolution is needed (for example, for browsing the Web), the device act as a DNS server for the devices connected to local LAN. When the DNS proxy is enabled, the device is defined as the DNS server for LAN devices (either manually or through DHCP) and the device forwards the name queries to the actual

DNS server and back to the LAN devices.

1.

In the left pane, under Services , click Common .

2.

Set Use DNS Proxy to Yes .

3.

Click Submit to save the settings.

Checking network status

The device has user interface views and LEDs that show network status and are useful in troubleshooting situations.

1.

In the left pane, under System , click Status to view network status information.

2.

In the left pane, under Tools , click Modem Info to view the status of the wireless modem.

3.

Check if the cellular LED is flashing, indicating network traffic.

48 ARC600

User Manual

1MRS758459 C

Section 8 Serial port configuration

Section 8

Serial port configuration

8.1

8.2

Configuring serial ports

1.

In the left pane, under Serial Port and I/O , click General Configuration .

2.

Select an Application Mode for each serial port.

Serial Gateway: Transparent connection to any serial device

IEC-104: IEC-101 to IEC-104 conversion with IEC-101 serial device protocol

Modbus: Modbus conversion with Modbus/RTU or Modbus/ASCII serial device protocol

Serial gateway

The serial gateway feature enables data from the serial port attached device to be routed to Ethernet/mobile network (serial over IP) and vice versa. Serial gateway processes the transmitted data transparently and does not alter it any way except for buffering it for transmission. Because of the transparent communication, any protocols can be used in actual communication between nodes.Serial gateway configuration depends on used protocols.

ARC600

User Manual

49

50

1MRS758459 C

Section 9

Additional system configuration

Section 9 Additional system configuration

9.1

9.2

Changing passwords

1.

In the left pane, under Tools , select User Config .

2.

Type the old password in the Old password field.

3.

Type the new password in the New password field and the New password

(confirm) field.

4.

Click Submit to save the settings.

See the cyber security deployment guideline for more information on password configuration.

Setting date and time

1.

In the left pane, under System , click Time .

2.

Set Mode to Automatic (NTP) or Manual .

The “Automatic (NTP)” setting synchronizes the date and time with an remote

NTP (or SNTP) server. The NTP server always defines the time in UTC time.

The time zone can be set so that the device shows the time in a local format.

There is also an NTP server in the device (NTP client and server), this enables the device to work as NTP server for the LAN devices.

3.

Click Submit under the Mode setting.

The lower part of the view is updated if the setting changed.

4.

Check the time and date settings.

In the “Automatic (NTP)” mode, check the settings under Current Time and Date (NTP mode) , including Time zone , and click Test NTP servers .

In the “Manual” mode, enter the time and date in the Time and Date fields, respectively.

Clicking Copy PC changes the device’s time and date settings to match the connected PC. This requires JavaScript support from the browser.

5.

Click Submit to save the settings.

ARC600

User Manual

51

Section 9

Additional system configuration

9.3

9.4

9.5

1MRS758459 C

Restoring factory default settings

1.

In the left pane, under Tools , click Default settings .

2.

Select a configuration profile to overwrite with the factory default settings.

3.

Click Submit .

4.

In the confirmation dialog, click OK .

5.

Restart the device.

Updating the firmware

Save a configuration profile as a backup of the current configuration before starting the firmware update.

Check that a valid firmware package is stored on the PC before attempting to update the firmware.

1.

In the left pane, under Tools , select Firmware Update .

The current firmware version is shown in the Firmware Update view.

2.

Click Browse to open the file selection dialog.

3.

Select the new firmware file.

4.

Click Update .

A confirmation dialog opens.

5.

Click OK to confirm firmware.

The update takes a few minutes.

6.

Once the update is finished, restart the device.

Saving configuration profiles

It is possible to save the device’s configuration in a profile for use in other devices or as a backup when updating the firmware. The configuration can be exported as an

XML file.

1.

In the left pane, under Tools , select Configuration profiles .

2.

Click Create a new profile .

3.

Select a profile to clone.

Selecting Last Boot allows saving the configuration in use when the device was booted the previous time.

4.

Type a name for the profile.

5.

Click Submit to save the profile.

It is possible to clone, export, and import profiles in the same view.

52 ARC600

User Manual

1MRS758459 C

Section 10 Service configuration

Section 10

Service configuration

10.1

10.2

Configuring services

1.

In the left pane, click Services .

The service categories are listed under Services .

2.

Click a service category.

3.

Configure the service with the service parameters listed in the view.

4.

Click Submit to save the settings.

Service parameters

Table 23:

Name

Common

Services

Use DNS

Proxy

LLMNR responder mDNS responder

SSH Server

SSH Server

SSH protocol version

SSH public keys

Common

Description

Determines if the device acts as a DNS server for LAN devices

Value range

No, Yes

The link-local multicast name resolution is a protocol that enables machines on LAN to find the device using its hostname. By default, the device uses its hostname (for example, arctic-02xxyy).

The multicast domain name system is a protocol that enables

Mac® OS X® machines on LAN to find the device using its hostname (for example, arctic-02xxyy).

The SSH (secure shell) is an encrypted network protocol for safe remote command line connections. It is replacing the Telnet protocol.

Determines if logging into the device using SSH is allowed. The device has internal SSH server, which allows incoming SSH connections when enabled. By default, the SSH service is enabled for LAN connections.

No, Yes

No, Yes

No, Yes

Selects which SSH protocol versions are enabled in SSH Server.

It is recommended to allow only SSH protocol version 2 (SSH2) to be used.

SSH Public keys can be added for remote logins with SSHkeys.

SSH1, SSH2

ARC600

User Manual

53

Section 10

Service configuration

1MRS758459 C

Table 24: DHCP server

Name

DHCP Server

Settings

Enabled

Description

Determines if the device acts as a DHCP server in LAN

Required

Settings

Subnet

Subnet mask

Range low IP address

Range high IP address

Optional

Settings

Defines the address of the subnet to listen to

Defines the subnet mask of the subnet to listen to

Defines the lowest IP address to share

Defines the highest IP address to share

Domain name DNS domain name given to clients

DNS Servers List of DNS servers (comma separated)

Gateway IP address

Broadcast IP address

IP address of the default gateway. This must usually be defined as

Arctic's own IP address.

Usually the last IP address of the subnet

Default lease time

Maximum lease time

NTP Servers

Given to clients that don't request a specific lease length (empty:

10800)

The maximum lease time given to clients (empty:10800)

List of NTP servers (comma separated)

LPR Servers List of line printer (LPR) servers (comma separated)

WINS Servers List of WINS servers (comma separated)

Value range

No, Yes

Table 25: DynDNS client

Name

DynDNS client settings

DynDNS service client enabled

Description

DynDNS service provider

Selects the supported dyndns service provider

DynDNS client update interval

DynDNS hostname

Defines how often (in seconds) the device's IP is checked

Arctic name reported to service, for example, host name

Table continues on next page

Value range

No, Yes

54 ARC600

User Manual

1MRS758459 C

ARC600

User Manual

Section 10

Service configuration

Name

DynDNS username

DynDNS password

DynDNS logging enabled

Description

User name for dyndns service

Service password

Logs dyndns update to system log

Value range

No, Yes

Table 26: SNMP agent

Name

SNMP Agent

Description

Enable SNMP Enables SNMP

Defines read only SNMP community Read only

SNMP community

Read and write

SNMP community

Server port

Defines read and write SNMP community

The default server port is 161.

Value range

No, Yes

Table 27: Arctic Patrol

Name

Basic

Information

Enabled

Name

Registration password

Description

Enables Viola Patrol

Free-text field for the unique name of the Patrol connection

Password needed to register to server with HTTPS protocol. This password should not be entered after registration unless reregistering is necessary.

Patrol communication protocol

Defines how often to report to server

Protocol

Connection interval

Server

Information

Server address, server port

SSH Settings

(Only needed for SSH protocol)

SSH local identity

Server IP address and the port the server listens. If no value is given, the value is 10000.

SSH private key to be used if the SSH connection protocol is selected.

SSH public key

SSH public key to be used if the SSH connection protocol is selected. This key can be copied to Patrol server.

Table continues on next page

Value range

No, Yes

HTTPS, SSH

Seconds

55

Section 10

Service configuration

1MRS758459 C

Name

Remote identity

Connection mode

Options

Backup active configuration to server

Allow remote management

Allow LAN device scan

Description

SSH public key of the Patrol server

The connection mode defines how the Patrol server polls the clients in the SSH protocol mode. In case of a large number of

Patrol connections in the server, the polling mode is recommended.

When set to “Yes”, copies encrypted version of the XML configuration file to the server.

Enables remote management by Patrol server

Allows periodical local network scan for ABB devices. Currently, the supported device is RIO600.

Value range

Polling, continuous

No, Yes

No, Yes

No, Yes

56 ARC600

User Manual

1MRS758459 C

Section 11

IEC-104 application settings

Section 11 IEC-104 application settings

11.1

11.2

11.3

ARC600

User Manual

The use of the IEC-104 protocol

The IEC-104 and IEC-101 protocols share the same ASDU level messaging but differ on the link level. IEC-104 is intended for packet-switched TCP/ IP communication whereas IEC-101 is intended for serial communication. By using the device, the

IEC-101 slaves (for example RTUs) can be connected to a IEC-104 master (for example SCADA). The device requests an event from the IEC-101 slave locally and sends them to the IEC-104 master. This eliminates the need to continuously poll the data remotely and therefore reduces the communication costs on pay-per-use wireless network.

See the technical note about Wireless Controller RTU_interoperability for more information on IEC 60870-5-104 and IEC 60870-5-101 interoperability.

Configuring IEC-104 application settings

1.

In the left pane, select Serial Port and I/O/IEC-104 Gateway (RSx) .

2.

View and change settings in the view that opens.

3.

Click Submit to save the settings.

IEC-104 application settings

Table 28: IEC-104 application settings

Name Description

Basic settings

Enable

IEC-104 gateway

Enables or disables IEC-104 to IEC-101 gateway functionality.

Serial settings The serial settings define the properties of physical serial communication between the device and an IEC-101 slave. The selection between RS-232/422/485 is made with physical DIP switches located below the RS2 serial port.

Serial port

Speed

Indicates the serial port to which the settings apply.

IEC-101 serial communication speed (bits per second)

Value range

No, Yes

RS1, RS2

1200, 2400,

4800, 9600,

19200, 38400,

57600

Table continues on next page

57

Section 11

IEC-104 application settings

1MRS758459 C

Name

Data bits

Parity

Description

Number of data bits used on IEC-101 serial communication

Parity method used on IEC-101 serial communication

Stop bits

Use HW flow control

Network settings

Network protocol

Number of stop bits used on IEC-101 serial communication

HW flow control mechanism (RTS/CTS) on IEC-101 serial communication. Note: The HW handshaking is available only on

RS-232 mode.

The Network settings define the general TCP/IP networking properties between the device and the IEC-104 master.

Network protocol defines the network transmission layer protocol

(either TCP or UDP) used on IEC-104 network communication.

The IEC-104 standard protocol uses TCP, but for reliable slow speed packet switched networks (for example Mobitex), the UDP protocol can be used to minimize the packets transmitted over network. Note: The IEC-104 standard specifies only TCP protocol.

TCP or UDP port number to listen for incoming IEC-104 connections

Network protocol to listen

Network idle timeout

New connection priority

Max clients

Network idle timeout defines the idle timeout of the network connection in seconds. If there is no network data received during the specified interval, the connection is closed by the device. This parameter is required in order to detect partially closed connections and release the resources for new connections especially if the New connection priority parameter is disabled.

Value “0” disables the network idle timeout detection. The network idle timeout must be longer than IEC-104 link test interval (t3).

It defines the action when a new connection request arrives while a connection is already active. If the set value is ”No”, the new connection is rejected. If the set value is ”Yes”, the present connection is terminated and the new connection is accepted. It is recommendable to set this value to “Yes” in normal configurations having only one IEC-104 master.

Max clients defines the maximun number of connections

(redundancy group).

IEC-104 settings

TX window size (k)

The IEC-104 settings define the properties of IEC-104 link layer and application layer parameters as described in the IEC

60870-5-104 standard. The IEC-104 communication is carried out between the device and the IEC-104 master over the TCP/IP network.

TX window size defines the maximum number of I format APDU packets the device may send before requiring the IEC-104 master to acknowledge them. If there are k unacknowledged frames sent the device stops polling IEC-101 slave for events until acknowledgement is received. The k must be always less than the maximum sequence number defined below. The IEC-104 standard suggests k to be 12.

RX window size (w)

RX window size defines the maximum number of I format APDU packets the device may receive before sending acknowledgement to the IEC-104 master. The w should not exceed two-thirds of TX window size k. The IEC-104 standard suggests w to be 8.

Table continues on next page

Value range

5, 6, 7, 8

None, Even,

Odd

1, 2

No, Yes

UDP, TCP

0...65000

0...65000

No, Yes

1...3

1...20

1...20

58 ARC600

User Manual

1MRS758459 C

ARC600

User Manual

Section 11

IEC-104 application settings

Name

I frames TX timeout (t1)

I frames RX timeout (t2)

Link test interval (t3)

Description

It defines the timeout in seconds the device waits for acknowledgement from IEC-104 master after sending last I format

APDU or control frame (e.g. link test). If no acknowledgement is received during the defined time the device will close the network connection and the IEC-101 link. The t1 must be longer than the network round-trip-time. The IEC-104 standard suggests 15 seconds.

This defines the timeout in seconds from the last received I format

APDU before sending acknowledgement. The t2 must be smaller than t1. The IEC-104 standard suggests 10.

This defines the interval in seconds how often the IEC-104 link is tested if there is no other activity. The recommended value depends on the criticality of the link. The IEC-104 standard suggests 20 seconds but for pay-per-use GPRS connections the practical value may be substantially longer.

Answer to test frame activation if the 101 link is in the suspended state.

Test link on suspended state

Suspended timeout

Max sequence number

This defines the time in seconds how long a connected IEC-104 link can be in suspended state (STOPD) before the device closes the connection. Using this parameter increases the probability of detecting partially closed network connections especially in UDP mode.

These are the maximum sequence number used in IEC-104 communication. The default value “0” equals to 32767 as suggested by the IEC-104 standard.

Defines if buffered events are flushed on new a IEC-104 connection.

Flush buffered events on connection

Cause of transmission length

Common address length

Info object address length

It defines the length of IEC-104 Cause of transmission ASDU header field in bytes. The IEC-104 standard defines value “2”.

This defines the length of IEC-104 Common address ASDU header field in bytes. The IEC-104 standard defines value “2”.

This defines the length of IEC-104 Information object address

ASDU header field in bytes.

IEC-101 settings

The IEC-101 settings define the properties of IEC-101 link layer and application layer parameters as described in the IEC

60870-5-101 standard. The IEC-101 communication is carried out between the device and a IEC-101.

The link-level address of IEC-101 slave.

Slave link address

Link address field length

Event poll interval

Link test interval

Defines the length of the IEC-101 link-level address field in bytes.

The link-level address of IEC-101 slave.

Event poll interval defines the IEC-101 event polling interval in 0.1

second increments (class 1 or 2 poll). The events are polled only when the IEC-104 connection is active.

Link test interval defines the IEC-101 link test interval in 0.1 second increments. Link test is performed if there is no other activity. The link test is performed if there is no other activity during defined interval.

Table continues on next page

Value range

1...255

1...255

1...65000

No, Yes

1...65000

0...32767

No, Yes

1, 2, 3

1, 2, 3

1, 2, 3

1...65000

1, 2

1...65000

1...65000

59

Section 11

IEC-104 application settings

60

1MRS758459 C

Name Description

Keep link open Defines that the IEC-101 link is kept always open even when there is no active IEC-104 connection. If the functionality is enabled the device sends link test frames and restarts the IEC-101 link if the test fails. The events are still not polled before the IEC-104 connection is active. Some IEC-101 slaves require the link to be continuously open in order to operate.

Reply header timeout

Defines the timeout in milliseconds that the device waits the reply to start from IEC-101 slave after command or request.

Reply end timeout

Retry limit

Cause of transmission length

Common address length

Info object address length

ASDU

Converter

Defines the maximum duration of IEC-101 slave response in seconds.

Defines the number of retries sent to a IEC-101 slave in case of no reply. If no reply is still received the device closes the IEC-101 and

IEC-104 connections.

Defines the length of IEC-101 cause of transmission ASDU header field in bytes. The IEC-101 standard defines value 1.

Defines the length of the IEC-101 common address ASDU header field in bytes. The IEC-101 standard defines value 2.

Defines the length of IEC-101 information object address ASDU header field in bytes. The IEC-101 standard defines value 2.

Use ASDU converter

The ASDU converter can be used to convert ASDU header field lengths between IEC-101 and IEC-104 protocols.

This defines if the ASDU header level conversion between

IEC-101 and IEC-104 is performed. If enabled the ASDU header field lengths are converted between IEC-104 and IEC-101. This parameter must be enabled if the ASDU header lengths differ between the IEC-104 and the IEC-101. The information on the field must fit in the shorter one of the two. It’s not possible to convert e.g.

value 12000 to a one byte field.

Use ASDU type replacer

The ASDU type replace function can be used to convert an ASDU type (Original type) to another (Applied type) type e.g. in cases when the IEC implementation differs between master and slaves.

The original ASDU type searched by ASDU type replacer.

IEC-101

ASDU type

IEC-104

ASDU type

Convert short

IEC-101 time stamps

The new ASDU type is replaced by the original type.

Defines if 56-bit timestamps are converted to 24-bit.

Packet collector

The packet collector can be used to collect many IEC-101 messages and events to a single network packet instead of sending every message separately. This function is useful for slow packet switched communication network (for example Mobitex) for speeding up especially the general interrogation response.

Determines if the packet collector is in use.

Use packet collector

Max bytes Max bytes defines the maximum bytes trigger for packet collector.

Before a new packet is inserted into the packet collector buffer the amount of bytes is checked. If the insertion of the new packet would cause the number of bytes in the packet collector to exceed

MAX BYTES, the old content is sent to the network before inserting the new one. The value should be smaller than the MTU/MRU of network used.

Table continues on next page

Value range

No, Yes

1...65000

1...65000

0...65000

1, 2, 3

1, 2, 3

1, 2, 3

No, Yes

No, Yes

0...255

0...255

No, Yes

No, Yes

1...1500

ARC600

User Manual

1MRS758459 C

Section 11

IEC-104 application settings

Name

Max time

Max packets

Description

Max time defines the maximum collect time trigger for packet collector in 0.1 second increments for packet collector. If there has been data on packet collector over MAX TIME, the data is sent to network. The value must be smaller than t1.

Max packets defines the maximum amount of IEC-101 packets stored into the packet collector before sending the data to the network.

Other settings

Write syslog Write syslog defines if the error messages are stored to system log file or not. The system log is available by using Web user interface.

Value range

1...255

1...255

No, Yes

ARC600

User Manual

61

62

1MRS758459 C

Section 12

Modbus application settings

Section 12 Modbus application settings

12.1 Modbus Gateway properties

The Modbus Gateway is an adapter application enabling conversions between serial and network Modbus protocols. The gateway can operate in one mode: connecting the network master to serial slaves.

The gateway offers a number of core properties.

• Supports Modbus RTU and Modbus ASCII serial protocols

• Supports Modbus TCP, Modbus RTU over TCP, Modbus RTU over UDP,

Modbus ASCII over TCP and Modbus ASCII over UDP network protocols

• Generates and filters out gateway exceptions

• Makes automatic connection management

• Enables multiple server sessions over the network

• Offers unlimited amount of masters on the network side

ARC600

User Manual

63

Section 12

Modbus application settings

12.2 Modbus mode

Network master to serial slaves

1MRS758459 C

TCP/IP

Modbus master

64

RS422/485

PLC Modbus slaves

GUID-0F99AFF8-EEF0-4D81-80DD-72CF8104F053 V2 EN

Figure 19: Network master to serial slaves mode

In the “Network master to serial slaves” mode, the device acts like network server where masters (clients) can connect (the default port being 502) and transmit Modbus requests. The device makes conversions between network and serial protocols. If the slave does not reply during defined timeout or if the reply is corrupted, the device sends “gateway exception message” back to the master if the exception generation is enabled. Otherwise, the reply is returned. Multiple masters can connect simultaneously to the Gateway, which handles the multiplexing between masters.

ARC600

User Manual

1MRS758459 C

12.3

12.4

ARC600

User Manual

Section 12

Modbus application settings

Configuring the network master to serial slaves mode

1.

In the left pane, under Serial Port and I/O , click Modbus Gateway (RSx) .

2.

Set Enable Modbus gateway to Yes .

3.

Set Gateway mode to Network master to serial slaves .

4.

Set the parameters under Serial settings , Protocols , Framing , Exceptions and

Network server settings as the network and the Modbus master and slaves require.

5.

Click Submit to save the settings.

6.

Restart the device.

Parameter settings

Table 29: Parameters

Name Description

Basic settings

Enable

Modbus gateway

Serial settings

If set to “Yes”, the Modbus gateway functionality is enabled for the serial port. Each serial port of the device has its own Modbus gateway definitions.

Serial port

Serial settings

Defines the serial port that the device uses for Modbus serial communication. The possible settings are “RS1”, which selects serial port 1 (RS-232 console/application port) and “RS2”, which selects serial port 2 (RS-232/422/485 application port). If a single serial port or RS-422/485 is required, port 2 is recommended. If

Port 1 is used, the console switch of the device must be in the

Application position. DIP switches below the DB-9 serial connector specify the RS-232/422/485 settings of Port 2.

Speed Defines the serial port speed for Modbus communication in bps.

The optimal speed depends on the connected Modbus equipment.

Value range

No, Yes

RS1, RS2

300, 1200,

2400, 4800,

9600, 19200,

38400, 57600,

115200

5, 6, 7, 8, Auto Data bits

Parity

Stop bits

Defines the number of data bits used in Modbus serial communication. The required number depends on how many data bits the connected Modbus equipment supports. Generally

Modbus RTU communication uses 8 data bits and Modbus ASCII communication uses 7 data bits.

Defines the parity method used in Modbus serial communication.

If set to “None”, no parity method is used. If set to “Even”, an even parity bit is generated and inspected. If set to “Odd”, odd parity bits are generated and inspected.

Defines the number of stop bits used in Modbus serial communication.

Enables CTS/RTS handshaking if set to “Yes”.

Use HW handshaking

(CTS/RTS)

Table continues on next page

None, Even,

Odd

1, 2

No, Yes

65

Section 12

Modbus application settings

1MRS758459 C

Name

Gateway mode

Gateway mode

Protocols

Description

If set to “Network master to serial slaves”, the slaves are on the serial side.

Serial protocol Defines the Modbus protocol that serial devices use in serial communication. The possible settings are Modbus RTU protocol and Modbus ASCII protocol. ModbusRTU is recommended because it is more efficient.

Network protocol

Defines the TCP/IP and Modbus protocol used on network communication. Possible protocols are Modbus TCP protocol over

TCP, Modbus RTU protocol over TCP, Modbus RTU protocol over

UDP, and Modbus ASCII protocol over UDP.

Value range

Network master to serial slaves

ModbusRTU,

ModbusASCII

ModbusTCP,

ModbusRTU over TCP,

ModbusRTU over UDP,

ModbusASCII over TCP,

ModbusASCII over UDP

0...90 000 000

(0...90

seconds)

Framing

Slave response timeout

Inter-frame timeout

Defines the time in microseconds (millionths of a second) how long the device waits for the response from a Modbus slave. If the response is not received, the device can generate and return a

Modbus gateway exception. The reply timeout of the Modbus master must be greater than the gateway device timeout.

Otherwise, the flow of request-reply communication is violated.

The device does not accept a new request before the reply from the slave is received or the reply timeout is elapsed. The delays in network communication can vary especially in wireless networks.

When the slaves are located on the network side, ping or another method should be used to estimate the delay packets spend on network.

Defines the idle time in microseconds (millionths of a second) that marks the end of Modbus frame in serial communication. If the value is zero, the device uses the standard 4 character time. The recommendation is to use a value as small as possible to speed up communication and increase the value if problems arise. Some PC programs can insert unexpected delays between serial characters.

Exceptions

Generate gateway exceptions

Pass gateway exceptions

Network server settings

Defines if the device generates and returns a Modbus gateway exception message to the master if no valid reply is not received from the slave. If set to “Yes”, the generation of exceptions is enabled. This functionality is useful for debugging.

If set to “Yes”, gateway exception replies from the slave side are passed to the master. If set to “No”, the replies are filtered away.

Server

TCP/UDP port

Defines the TCP or UDP port that masters can form connections to. Default Modbus TCP/IP communication port is 502. If multiple

Modbus gateways are running on same device (for both serial ports) the TCP/UDP communication ports must not be same. For example, ports 502 and 504 can be used. The network and the device's firewalls must enable TCP or UDP communication for that port.

Table continues on next page

0...2 000 000

(0...2 seconds)

No, Yes

No, Yes

1...32500

66 ARC600

User Manual

1MRS758459 C

Section 12

Modbus application settings

Name

Max. number of clients

Connection idle timeout

Enable keepalive

Description

Defines how many network masters can be connected to the device simultaneously. The recommended value is at least 2 when using TCP communication. Otherwise if the device does not recognize a partially closed connection, forming new connections is not accepted by the device the time set in parameter

“Connection idle timeout” is elapsed.

If there has not been communication on this route during given amount of seconds, the device automatically closes the TCP connection to slave and therefore frees the slave’s communication resources. This is especially useful when multiple masters access the same slave. The recommended setting is about two times the polling interval of the master.

Defines if connection testing is performed by sending TCP keepalive packets at certain intervals. enabled for TCP network communication. If set to “Yes”, testing the TCP connection with slave is enabled.

Value range

0...20

0...32500

No, Yes

ARC600

User Manual

67

68

1MRS758459 C

Section 13 Technical data

ARC600

User Manual

Section 13

Technical data

Table 30: Dimensions

Description

Height × Width × Depth

Weight

Protection class

Value

175 × 160 × 108 mm

2.4 kg

IP30

Table 31:

Description

Other

Power

Hardware

Processor environment Processor

Memory

Sensor

Internal clock

Power supply

Frequency range

Input current, 100% load, 230 V AC

Efficiency, typical (230

V AC, 100% load)

Isolation

Value

32 bit RISC

128 MB Flash

128 MB RAM

Temperature

Real time

90...264 V AC or 85...200 V DC

20...30 V DC (external battery)

45...65 Hz

0.8 A

>83%

Input/ground 1500 V AC RMS 50 Hz 1 min Input

Output 3000 V AC RMS 50 Hz 1 min

Output/ground 500 V DC

<25 A <5 ms Inrush current 25°C,

230 V AC

Input fuse

Power consumption

T3.15 A high breaking

10 W typical (when not charging battery), 60 W

(full charging)

VDR 275 V AC 72 J

Casing

Approvals

Environmental conditions

Overvoltage transient protection

Holdup time (230 V,

100% load)

Temperature range

Relative humidity

>50 ms

Aluminium shell

CE

-30...+55°C (non condensing)

-40...+70°C (storage)

5...85% RH

69

Section 13

Technical data

1MRS758459 C

Table 32:

Description

Rated voltage

Capacity

Weight

Size (L × W × H)

Battery recommendations

Yasa NP 17-12

12 V

17 Ah

6.1 kg

181 × 76 × 167 mm

Yasa NPL 24-12

12 V

24 Ah

9 kg

166 × 175 × 125 mm

Table 33: Supply for external devices and input circuits (X2.1 pin 6)

Description

Output voltage

Output current

Output overvoltage protection level

Value

21...29 V

1 A continuous, 3 A peak

30.5 V

Table 34: Temperature-compensated charger for batteries

Description

Rated charging voltage

Output power

Fuse

Temperature compensation

Output overvoltage protection level

Value

27.4 V at 20°C

60 W

4 A

-40 mV/°C

30.5 V

Table 35:

Master protocol

IEC 60870-5-104

IEC 60870-5-104

Supported protocols

IEC 60870-5-104

IEC 60870-5-104

IEC 60870-5-104

IEC 60870-5-101

IEC 60870-5-101

IEC 60870-5-101

IEC 60870-5-101

Modbus TCP

TCP/IP

Slave protocol

IEC 60870-5-101

Modbus TCP

Modbus RTU/ASCII

Modbus (RTU) profile for Horstmann Compass B

Modbus (RTU) profile for Kries IKI-50

Modbus RTU

Modbus TCP

Modbus (RTU) profile for Horstmann Compass B

Modbus (RTU) profile for Kries IKI-50

Modbus RTU

Serial gateway - serial port data stream (such as

DNP3)

70 ARC600

User Manual

1MRS758459 C

ARC600

User Manual

Section 13

Technical data

Table 36:

Master protocol

IEC 60870-5-104

IEC 60870-5-101

Supported protocols for I/O controlling

Table 37: Default I/O configuration

Description

Digital inputs (0...60 V DC, >18

V DC detected as 1) 1)

Digital inputs for the disconnector status control

• Disconnector 1: Open/ closed, local/remote use, grounding open/closed – 5 pcs

Disconnector 2: Open/ closed, local/remote use, grounding open/closed – 5 pcs

Disconnector 3: Open/ closed, local/remote use, grounding open/closed – 5 pcs

Value

15

2

Digital outputs (1 A/30 V DC continuous carry)

Extra general purpose digital inputs reserved for other use

Total number of digital inputs

Digital outputs for the disconnector open/close command

Disconnector 1: Open/ close – 2 pcs

Disconnector 2: Open/ close – 2 pcs

Disconnector 3: Open/ close – 2 pcs

17

6

Analog inputs (-5...+5 V measurement, ±300 mV for

-10...+55°C, 0 V...+5 V)

Digital output for the load cut

(motor overload protection)

Digital output for the test load of the battery test (test load)

Digital output for the external heater

Extra general purpose digital output reserved for other use

Total number of digital outputs

Load measurement (DC motor load current)

Extra reserved for other use

Total number of analog inputs

1

1

1

1

10

1

1

2

1) Digital inputs are designed for reading the status of the feeder (open, traveling, closed) and not for detecting short-duration changes.

71

Section 13

Technical data

1MRS758459 C

Table 38:

Description

Digital inputs 1)

Digital outputs

I/O specifications

Value

Number of digital inputs 17

Operating range 18...60 V DC (>18 V DC detected as 1)

Current drain

Power consumption/ input

Input polarity

Isolation

Number of digital outputs

3.5...12.5 mA

<0.8 W bipolar

3 kV

10

Output pin rated voltage

Continuous carry 30

VDC

24 VDC

1 A

1) Digital inputs are designed for reading the status of the feeder (open, traveling, closed) and not for detecting short-duration changes.

Table 39:

Description

Ethernet ports

Network interfaces

Ethernet/LAN

Value

10/100 Base-T. Shielded RJ-45

1.5 kV isolation transformer

Ethernet IEEE 802-3, 802-2

Table continues on next page

72 ARC600

User Manual

1MRS758459 C

Section 13

Technical data

Description

Serial ports Serial 1/Console

Serial 2

Value

RS-232 DTE

Male DB-9 connector

IEC 60870-5-101 protocol support

Full serial and modem signals

300...460 800 bps

Data bits: 7 or 8

Stop bits: 1 or 2

Parity: None, Even, Odd

Flow control: None, RTS/CTS

Protection: 15 kV ESD and short circuit

Console: RS-232, 19200 bps, 8 data bits, 1 stop bit, no parity (8N1)

RS-232 DTE, RS-422, RS-485 (selectable)

Male DB-9 connector

IEC 60870-5-101 protocol support

Full serial and modem signals

300...460 800 bps

Data bits: 7 or 8

Stop bits: 1 or 2

Parity: None, Even, Odd

Flow control: None, RTS/CTS

Protection: 15 kV ESD and short circuit

Table 40:

Product

Wireless network interfaces (WAN)

Air interface

GPRS/EDGE

WCDMA/HSPA+

LTE

Frequency

1900/1800/900/850

MHz

2100/1900/900/850

MHz

2600 (band 7)/2100

(band 1)/1800 (band 3)/

900 (band 8)/800 (band

20) MHz

Maximum data rate

85.2 Kbps/236.8 kbps

21 Mbit/s

100 Mbit/s

Table 41:

Description

Antenna connector

SIM card type

Antenna connector and SIM card types

Type

SMA (female, 50 Ω)

2FF (Mini SIM)

ARC600

User Manual

73

Section 13

Technical data

Table 42:

Description

Emission tests according to the test specification IEC

61850-3 (Edition 2.0

2013-12)

Immunity tests according to the test specification IEC

61850-3 (Edition 2.0

2013-12)

Electromagnetic compatibility tests

Radiated disturbance

Reference

CISPR 16-2-3

Conducted disturbance CISPR 16-2-1

Electrostatic discharge

(ESD)

Radiated radiofrequency electromagnetic field

Electrical fast transient

(EFT)

Surge

Conducted radiofrequency electromagnetic field

Power frequency magnetic field

Voltage dips

EN 61000-4-2 (2008-12)

EN 61000-4-3 (2006-02)

EN 61000-4-4 (2012-04)

EN 61000-4-5 (2005-11)

EN 61000-4-6 (2008-10)

EN 61000-4-8 (2009-09)

EN 61000-4-11 (2004-03)

Table 43:

Description

Directive

RoHS and REACH compliancy

Reference

RoHS directive 2002/95/EC

REACH directive 2006/1907/EC

1MRS758459 C

74 ARC600

User Manual

1MRS758459 C

Section 14

Appendix Installation and mounting instructions

Section 14 Appendix Installation and mounting instructions

14.1

14.2

Unpacking the device

The device is delivered in a package containing the device itself, a short antenna and four connectors. Accessories such as null-modem cables, hall-effect current transducers, test load resistors and roof antennas can be ordered separately.

1.

Remove the transport packing carefully without force.

All packaging materials are recyclable. Follow the environmental regulations regarding the disposal of materials.

2.

Examine the delivered products to ensure that they were not damaged during the transport. If any of the items is missing or damaged, inform the nearest ABB office or representative. ABB should be notified immediately if there are any discrepancies in relation to the delivery documents.

Handle the device carefully before installation on site.

Installing the device

• Install the device on the cabinet's DIN-rail with the mounting clips.

• As the device has a cellular network connection, consider the high-frequency radio waves it uses for data transmission and choose the installation site accordingly.

If the device with antenna is mounted directly to the antenna connector, avoid placing the device where nearby obstacles might disturb the radio signal.

In case of metal racks or surfaces, use an external antenna with an appropriate cable.

ARC600

User Manual

75

Section 14

Appendix Installation and mounting instructions

1MRS758459 C

Walls with metallic structures, such as cabling or concrete iron, may degrade the antenna performance.

14.3

The protective earth screw terminal is located next to the DIN-rail mounting clips. The earth lead must always be properly connected, at least 6.0 mm 2 and as short as possible.

Installing the SIM card

Standard 3 V SIM cards (2 FF) can be used with the device's IEC 60870-5-104 gateway. A SIM card holder is located on the top panel near the antenna connector.

If the PIN code query is enabled, check that the correct PIN code is entered in the ARC600 configurator wireless WAN submenu.

1.

Switch off power from the device.

2.

Eject the SIM card holder by pushing the Eject button.

3.

Remove the tray from the holder and place the SIM card onto the tray.

4.

Insert the tray carefully back to the holder and press the tray until it is locked.

76 ARC600

User Manual

1MRS758459 C

Section 15 Glossary

ARC600

User Manual

Section 15

Glossary

AC

APN

CHAP

CTS

DC

DCD

DHCP

DI

DIN rail

DIP

DIP switch

Alternating current

Access Point Name

Challenge handshake authentication protocol

Clear to send

1. Direct current

2. Disconnector

3. Double command

Data carrier detect

Dynamic Host Configuration Protocol

Digital input

A standardized 35 mm wide metal rail with a hat-shaped cross section

Dual in-line package

A set of on-off switches arranged in a standard dual in-line package

DNP3

DNS

DSR

DTE

DTR

EMC

Ethernet

GND

HMI

HTML

HTTPS

I/O

A distributed network protocol originally developed by

Westronic. The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution.

Domain Name System

Data set ready

Data Terminal Equipment

Data terminal ready

Electromagnetic compatibility

A standard for connecting a family of frame-based computer networking technologies into a LAN

Ground/earth

Human-machine interface

Hypertext markup language

Hypertext Transfer Protocol Secure

Input/output

IEC International Electrotechnical Commission

IEC 60870-5-101 Companion standard for basic telecontrol tasks

77

Section 15

Glossary

78

1MRS758459 C

RISC

RJ-45

RMU

RS-232

RS-422

RS-485

RTS

RTU

RXD

SCADA

SIM

SMS

NTC

NTP

PAP

PIN

RAM

RI

IEC 60870-5-104 Network access for IEC 60870-5-101

IP

LAN

LED

MCB

Modbus

Modbus ASCII

Modbus RTU

NT

Internet protocol

Local area network

Light-emitting diode

Miniature circuit breaker

A serial communication protocol developed by the

Modicon company in 1979. Originally used for communication in PLCs and RTU devices.

Link mode using 7-bit ASCII characters

Link mode using 8-bit binary characters

Non-topical

Negative Temperature Coefficient

Network time protocol

Password authentication protocol

Personal Identification Number

Random access memory

Ring Indicator

SNMP

SNTP

TCP

TCP/IP

TXD

Reduced Instruction Set Computer

Galvanic connector type

Ring main unit

Serial interface standard

Serial communication standard (EIA–422)

Serial link according to EIA standard RS485

Ready to send

Remote terminal unit

Received exchange data

Supervision, control and data acquisition

Subscriber identity module

1. Short Message Service

2. Station monitoring system

Simple Network Management Protocol

Simple Network Time Protocol

Transmission Control Protocol

Transmission Control Protocol/Internet Protocol

Transmit exchange data

ARC600

User Manual

1MRS758459 C

UDP

VLAN

VPN

WAN

User datagram protocol

Virtual LAN

Virtual Private Network

Wide area network

Section 15

Glossary

ARC600

User Manual

79

80

81

ABB Distribution Solutions

Distribution Automation

P.O. Box 699

FI-65101 VAASA, Finland

Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/substationautomation

© Copyright 2019 ABB. All rights reserved.

advertisement

Related manuals

Download PDF

advertisement

Table of contents