M-System R1M-GH is a remote I/O device with 16 thermocouple or DC inputs. It allows for easy system expansion via Modbus RTU communication protocol. The device supports both RS-232-C and RS-485 communication interfaces. With a transmission distance of up to 10 meters for RS-232-C and 500 meters for RS-485, it provides flexible connectivity options. Additionally, the M-System R1M-GH features a RUN indicator LED that blinks green in normal conditions, providing visual feedback on the device's status.
Advertisement
Advertisement
Remote I/O R1M Series
THERMOCOUPLE & DC INPUT MODULE
(16 points)
Functions & Features
• 16-point thermocouple or DC inputs
• Easy system expansion via Modbus RTU
175 (6.89)
40
(1.57)
115
(4.53) mm (inch)
MODEL: R1M-GH2T-[1]
ORDERING INFORMATION
• Code number: R1M-GH2T-[1]
Specify a code from below for [1] e.g. R1M-GH2T-M2
FIELD TERMINAL TYPE
T: M3 screw terminals
[1] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• Resistor module (model: REM3-250)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
Power input, transmission: Euro type connector terminal
RS-232-C: 9-pin D-sub connector (male)
I/O: M3 screw terminals
Isolation: Input to RS-232-C or RS-485 to power
Address setting: Rotary switch; 1 – F (15 nodes)
MODEL: R1M-GH
RUN indicator LED: Green light blinks in normal conditions.
COMMUNICATION
Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)
INPUT SPECIFICATIONS
Input: Thermocouple or DC input, 16 points
(Common negative for DC input)
Measuring Range:
±20 V, ±5 V, ±1 V, ±0.8 V, ±0.2 V, ±50 mV, ±10 mV
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate: 100 millisec./16 points
• Trigger input: Dry contact; ON detected at ≤1.5 V
Sensing: Approx. 5 V DC @ 1 mA
INSTALLATION
Power Consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lbs)
PERFORMANCE (% of measuring range)
Accuracy
DC input: ±0.3 %
Thermocouple input: See the table on the end of this section.
Cold junction compensation error: ±3°C or ±5.4°F max.
(at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
±0.05 %/°C (±0.03 %/°F) for 10 mV range
Insulation resistance: ≥100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to RS-232-
C or RS-485 to power to ground)
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
Thermocouple Accuracy
USABLE RANGE
T/C
°C °F
(PR)
K (CA)
E (CRC)
0 to 1770 32 to 3218
-270 to +1370 -454 to +2498
-270 to +1000 -454 to +1832
ACCURACY
(%)
±0.5* 1
±0.3
±0.7
J (IC)
T (CC)
B (RH)
-210 to +1200 -346 to +2192
-270 to +400 -454 to +752
100 to 1820 212 to 3308
R
S
-50 to +1760
-50 to +1760
C (WRe 5-26) 0 to 2320
-58 to +3200
-58 to +3200
32 to 4208
N -270 to +1300 -454 to +2372
U
L
-200 to +600
-200 to +900
P (Platinel II) 0 to 1395
-328 to +1112
-328 to +1652
32 to 2543
±0.7
±1.0
±0.7*
±0.7*
±0.7*
±0.7
±0.5
±0.5
±0.3
±0.5
*1. ≥400°C or ≥752°F
*2. ≥700°C or ≥1292°F
The described accuracy may be partially not satisfied when the temperature ranges below 0°C.
2
1
1
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1
Installation Category II
Pollution Degree 2
Input or RS-232-C/RS-485 to power: Reinforced insulation
(300 V)
Input to RS-232-C/RS-485: Basic insulation (300 V)
EXTERNAL VIEW
Power Terminals
RS-232-C
9-pin Connector
RUN Indicator
LED
MODEL: R1M-GH
RS-485
Connector
Address Setting
Rotary SW
Configurator
Jack
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
■ RS-232-C INTERFACE
1 5
6 9
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD)
BB (RD)
AB (SG)
CB (CS)
CA (RS)
2
3
5
7
8
1
4
6
9
Transmitted Data
Received Data
Signal Common
Clear to Send
Request to Send
Not Used.
DO NOT connect. Connecting may cause malfunctions.
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
DC INPUT
+
–
CJC
Sensor
TRIGGER INPUT
+
–
19
20
21
16
17
18
13
14
15
10
11
12
4
5
6
7
8
9
1
2
3
33
34
35
36
30
31
32
27
28
29
22
23
24
25
26
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
+
–
+
–
T/C INPUT
+
+ ext. wire
–
–
+
–
Output
Circuit
RS-232-C
Term.
Resist.
T1
T2
T3
T4
+
–
Shielded Twisted-pair Cable
To Other
I/O Modules
Jumper *
Power
Circuit
T5
T6
T7
U (+)
V (–)
FG
POWER
Input
Circuit
* When the device is located at the end of a transmission line via twisted-pair cable,
(when there is no cross-wiring), close across the terminal T2 – T3 with the attached jumper pin (or with a leadwire).
When the device is not at the end, remove the jumper pin.
Remark 1: This device is not designed to cancel noise included in the input signals.
Be careful to eliminate such noise by using shielded cables.
Remark 2: Be sure to maintain the same potential at all the common negative terminals for DC input.
MODEL: R1M-GH
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
MODEL: R1M-GH
MODBUS WIRING CONNECTION
R1M
RS-485 RS-485
RS-232-C
T1
T2
T3
T4
* 1
R1M
T1
T2
T3
T4
FG
* 2
* 1. Internal terminating resistor is used when the device is at the end of a transmission line.
* 2. Install shielded cables to all sections and ground them at single point.
R1M
T1
T2
T3
T4
* 1
MODBUS COMMUNICATION
■ COMMUNICATION PARAMETERS
PARAMETER
Data Mode
Baud Rate
Parity
Bit Length
Stop Bit
Node Address
Floating Point Data
Interface
(*) Ex-factory setting
■ FUNCTION CODES & SUPPORTED CODES
CODE NAME
13
14
15
16
08
09
10
11
12
01
02
03
04
05
06
07
21
22
23
24
17
18
19
20
Read Coil Status
Read Input Status
Read Holding Registers
Read Input Registers
Force Single Coil
Preset Single Registers
Read Exception Status
Diagnostics
Program 484
Poll 484
Fetch Comm. Event Counter
Fetch Comm. Event Log
Program Controller
Poll Controller
Force Multiple Coils
Preset Multiple Registers
Report Slave ID
Program 884/M84
Reset Comm. Link
Read General Reference
Write General Reference
Mask Write 4X Register
Read/Write 4X Register
Read FIFO Queue
X
X
X
X
X
X
X
X
SPECIFICATION
RTU
9600 / 19200 / 38400 (*) bps
None / Odd (*) / Even
8
1 (*) / 2
1 (*) to 15
N/A
RS-232-C/ RS-485
Digital output from the slave
Status of digital inputs to the slave
General purpose register within the slave
Collected data from the field by the slave
Digital output from the slave
General purpose register within the slave
Fetch a status word and an event counter
A status word, an event counter, a message count and a field of event bytes
Digital output from the slave
General purpose register within the slave
Slave type / ‘RUN’ status
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
MODEL: R1M-GH
■ DATA ADDRESS
ADDRESS
GH2
TYPE
J3 A1
DATA
D1 FORMAT
NAME
Coil (0X)
Input Status (1X)
Input Register
(3X)
1 – 32
33 – 48
1 – 32
33 – 48
1 – 16
17 – 48
49 – 50
81 – 96
513
514 – 521
522 – 529
530 – 537
---
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
---
---
Y
Y
---
Y
---
Y
Y
Y
Y
Y
---
---
Y
---
---
---
---
---
Y
Y
Y
Y
Y
---
---
---
---
---
---
---
Y
Y
Y
Y
I
F
F
I
I bit DO * 1 bit Cold junction compensation SW
(0: Disable, 1: Enable) * 2 bit DI * 3 bit ADC overrange
AI in % (1 – 8 for Type J3)
AI per channel in engineering unit
Cold junction temperature * 2
Channel status
Bit System Status
0 to 5
6
7
Reserved for system use
E 2 PROM diagnostics (0: Normal, 1: Error)
ADC error (0: Normal, 1: Error)
8 to 15 Reserved for system use
B16 Model No. (“R1M-x”)
B16 Serial No.
B16 Hardware version No.
Holding Register
(4X)
538 – 545
1 – 16
17 – 48
145 – 160
Y
---
---
Y
Y
---
---
Y
Y
---
---
---
Y
---
---
---
B16 Firmware version No.
I
F
I
(Reserved for AO in %)
(Reserved for AO in engineering unit)
I/O type No.
161 – 176 Y --- --- --- I Burnout type (161 – 168 for Type J3)
(0: No burnout, 1: Upscale, 2: Downscale) * 4
I = 16-bit integer, F = 32-bit floating, B16 = 16-byte character
*1. Discrete output only.
*2. Thermocouple input only.
*3. Trigger contact input for Types GH2 and J3. (Only Address 10001 is enabled.)
*4. Same setting for all channels. For potentiometer inputs, always leave certain residual resistance at 0% side in order to avoid wrong burnout detection. (0% input or shortcircuit across the terminals 1 – 2 = Wire breakdown at the terminal 3)
■ INPUT DATA
• 32-bit Floating
Address n Address n+1
Sign Exponent
• 32-bit Integer, No sign (R1M-A1)
Address n, High-order
Mantissa
Address n+1, Low order
High order bytes Low order bytes High order bytes Low order bytes
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
MODEL: R1M-GH
■ INPUT REGISTERS DESCRIPTION
(1) ANALOG INPUT IN % (30001 to 30016; 30001 to 30008 for J3)
Indicates analog input values in percentage for each channel (1 – 16; 1 – 8 for J3).
DC
INPUT TYPE & RANGE
±20V
±5V
±1V
±0.8V
±0.2V
±50mV
±10mV
Thermocouple
RTD
Potentiometer 0 – 100Ω
0 – 500Ω
0 – 1kΩ
0 – 10kΩ
A/D DATA (Decimal)
±20000
±5000
±10000
±8000
±20000
±5000
±10000
Temperature x 10
Temperature x 10
±2000
(2) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30048; 30017 to 30032 for J3)
Indicates analog input values in engineering unit for each channel (1 – 16; 1 – 8 for J3). The unit is specific to each input type: °C for temperature, Volts for voltage, and % for potentiometer. The data are 32-bit floating values, which requires two consecutive registers for one module.
(3) CHANNEL STATUS (30081 to 30096)
Indicates the current status of analog inputs (1 – 16; 1 – 8 for J3). The following list shows the names and descriptions of each bit.
BIT NAME
6 Input Overrange
7
12
ADC Error
Cold Junction Compensation SW
Others Reserved
DESCRIPTION
Indicates the designated analog input is in overrange, defined as one or more of the following condition:
• ADC input value 0X0000 or 0XFFFF
• Burnout status for thermocouple input
• Out of range defined in the temperature table (thermocouple and RTD)
• ADC error
0 : Normal
1 : Overrange
Indicates the status of ADC.
0 : Normal
1 : Error
Indicates whether the cold junction compensation is enabled or disabled, for thermocouple input.
0 : Disable
1 : Enable
For system’s use
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
MODEL: R1M-GH
■ INPUT REGISTERS DESCRIPTION
Indicates I/O type for each channel. The data are 16-bit integer values.
MODEL I/O I/O TYPE SELECTION
R1MS-GH3 DC input
R2M-2G3
R1M-GH2 DC input
0X00 -10 to 10 V
R1M-GH2
R1MS-GH3
R2M-2H3
R1M-J3
R1M-D1
R1M-A1
T/C input
RTD input
POT input
DO
DI
0X34
0X35
0X40
0X41
0X42
0X43
0X60
0X70
0X18
0X19
0X1A
0X1B
0X1C
0X30
0X31
0X32
0X33
0X10
0X11
0X12
0X13
0X14
0X15
0X16
0X17
0X00
0X01
0X02
0X03
0X04
0X05
0X06
-20 to 20 V
-5 to 5 V
-1 to 1 V
-800 to 800 mV
-200 to 200 mV
-50 to 50 mV
-10 to 10 mV
(PR)
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
JPt 100 (JIS ’89)
Pt 100 (JIS ’89)
Pt 100 (JIS ’97/IEC)
Pt 50Ω (JIS ’81)
Ni 508.4Ω
Pt 1000
0 to 100 ohms
0 to 500 ohms
0 to 1k ohms
0 to 10k ohms
USABLE RANGE
-10 to 10 V
-22.7 to 22.7 V
-5.6 to 5.6 V
-1.4 to 1.4 V
-860 to 860 mV
-215 to 215 mV
-53 to 53 mV
-13.4 to 13.4 mV
0 to 1770 °C
-270 to 1370 °C
-270 to 1000 °C
-210 to 1200 °C
-270 to 400 °C
100 to 1820 °C
-50 to 1760 °C
-50 to 1760 °C
0 to 2320 °C
-270 to 1300 °C
-200 to 600 °C
-200 to 900 °C
0 to 1395 °C
-200 to 500 °C
-200 to 660 °C
-200 to 850 °C
-200 to 649 °C
-50 to 280 °C
-200 to 850 °C
0 to 100 %
0 to 100 %
0 to 100 %
0 to 100 %
NOTES
ATT SW ON
ATT SW ON
ATT SW ON
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
175 (6.89)
165 (6.50) 15.5 (.61)
3–5 (.20) dia.
MTG HOLES
T1 T2 T3 T4 T5 T6 T7
DIN RAIL
35 mm wide
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
6.2 (.24)
36–M3 I/O TERMINALS
163 (6.42)
FOR WALL MOUNT.
CJC SENSOR (model: CJM)
3 (.12)
40 (1.57) [6 (.24)]
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
SYSTEM CONFIGURATION EXAMPLES
TC/DC Inputs
(model: R1M-GH)
RS-232-C
RS-232-C/RS-485
Converter
(model: R2K-1)
RS-485
Contact Inputs
(model: R1M-A1)
Contact Outputs
(model: R1M-D1)
When the cable distance between the PC and the R1Ms is long, insert an RS-232-C/RS-485 Converter for isolation.
Specifications are subject to change without notice.
MODEL: R1M-GH
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
R1M-GH
INSTRUCTION MANUAL
THERMOCOUPLE & DC INPUT MODULE
(16 points)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
This product is for use in general industrial environments, therefore may not be suitable for applications which require higher level of safety (e.g. safety or accident prevention systems) or of reliability (e.g. vehicle control or combustion control systems).
For safety, installation and maintenance of this product must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Remote I/O module (body + CJC sensor) ..................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
For detailed information on Modbus supported functions, refer to Modbus Protocol Reference Guide (EM-5650).
The R1M is programmable using the PC configurator software. For detailed information on the PC configuration, refer to the R1CON instruction manual. The R1CON PC
Configurator Software is downloadable at M-System’s web site: http://www.m-system.co.jp.
MODEL
R1M-GH
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
24V DC rating: 24V ±10%, approx. 7W
■ GENERAL PRECAUTIONS
• Before you remove the module, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air, install the module inside proper housing with sufficient ventilation.
• Do not install the module where it is subjected to continuous vibration. Do not apply physical impact to the module.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with cables, etc.
■ WIRING
• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The module is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category II, with the maximum operating voltage 300V.
Basic insulation is maintained between the signal input and RS-232C/RS-485. Prior to installation, check that the insulation class of this unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert noise filters. Okaya Electric Industries Model SUP-
E1H or equivalent for the power source connected to the unit, and TDK Model ZCAT3035-1330 or equivalent for the RS-232C cable are recommended.
• The equipment must be installed such that appropriate clearance and creepage distances are maintained to conform to CE requirements.
• The actual installation environments such as panel configurations, connected devices, connected wires, may affect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conformity.
EM-5657 Rev.7
P. / 4
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 [email protected]
www.sentronic.com
COMPONENT IDENTIFICATION
■ TOP VIEW
T1 T2 T3 T4 T5 T6 T7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
CJC Sensor (model: CJM)
■ REAR VIEW
Power Terminals
RS-232C
9-pin Connector
RUN Indicator
LED
R1M-GH
INSTALLATION
■ DIN RAIL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor.
Position the upper hook at the rear side on the DIN rail and push in the lower. Push back the
DIN rail adaptor.
DIN Rail
35mm wide
■ WALL MOUNTING
Set the body so that its DIN rail adaptor is at the bottom. Pull down the DIN rail adaptor.
Refer to “EXTERNAL DIMEN-
SIONS.”
DIN Rail Adaptor
RS-485
Connector
Address Setting
Rotary SW
Specifications Marking
Configurator
Jack
EXTERNAL DIMENSIONS
unit: mm (inch)
175 (6.89)
165 (6.50)
T1 T2 T3 T4 T5 T6 T7
3–5 (.20) dia.
MTG HOLES
15.5 (.61)
DIN RAIL
35 mm wide
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
6.2 (.24)
36–M3 I/O TERMINALS
163 (6.42)
FOR WALL MOUNT.
CJC SENSOR (model: CJM)
3 (.12)
40 (1.57) [6 (.24)]
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
EM-5657 Rev.7
P. / 4 [email protected]
www.sentronic.com
R1M-GH
TERMINAL CONNECTIONS
Connect the module referring to the connection diagram.
Attach the CJC sensor together with input wiring to the input screw terminals. The sensor is calibrated for each particular module and not interchangeable with another. Check the serial numbers of the module and sensor.
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
DC INPUT
+
–
CJC
Sensor
TRIGGER INPUT
+
–
16
17
18
19
20
13
14
15
10
11
12
1
2
3
4
5
6
7
8
9
25
26
27
28
21
22
23
24
33
34
35
36
29
30
31
32
–
+
–
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
T/C INPUT
+ ext. wire
+
–
–
+
–
+
–
+
–
+
Output
Circuit
Term.
Resist.
Power
Circuit
Input
Circuit
T1
T2
T3
T4
T5
T6
T7
RS-232C
+
–
U (+)
V (–)
FG
Shielded Twisted-pair Cable
To Other
I/O Modules
Jumper
*
POWER
■ RS-232C INTERFACE
*
When the device is located at the end of a transmission line via twisted-pair cable,
(when there is no cross-wiring), close across the terminal T2 – T3 with the attached jumper pin (or with a leadwire).
When the device is not at the end, remove the jumper pin.
Remark 1: This device is not designed to cancel noise included in the input signals.
Be careful to eliminate such noise by using shielded cables.
Remark 2: Be sure to maintain the same potential at all the common negative terminals for DC input.
1
6
5
9
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD)
BB (RD)
AB (SG)
2
3
5
Transmitted Data
Received Data
Signal Common
CB (CS)
CA (RS)
7
8
1
4
6
9
Clear to Send
Request to Send
Not Used.
DO NOT connect. Connecting may cause malfunctions.
MODBUS WIRING CONNECTION
R1M
RS-485 RS-485
RS-232C
T1
T2
T3
T4
*
1
R1M
T1
T2
T3
T4
FG
* 2
* 1. Internal terminating resistor is used when the device is at the end of a transmission line.
*
2. Install shielded cables to all sections and ground them at single point.
R1M
T1
T2
T3
T4
*
1
SENTRONIC
AG Produkte, Support und Service
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
EM-5657 Rev.7
P. / 4 [email protected]
www.sentronic.com
INPUT RANGE SELECTING
Select switches to match the input signal according to the table below.
R1M-GH
SW702 SW702 is fixed to the position 3.
DO NOT CHANGE.
1
2
3
4
5
6
7
8
SW411
O
N
SW401 SW308 SW307 SW306
SW408 SW407 SW406
1
2
3
4
5
6
7
8
SW311 SW305 SW304 SW303 SW302
O
N
SW301
SW405 SW404 SW403 SW402
INPUT
Thermocouple
Voltage input, 0.8V or less
Voltage input, above 0.8V (*)
(*) Factory default setting
SWITCHES
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SW301 – SW308 (ch 1 – ch 8)
SW401 – SW408 (ch 9 – ch 16)
SW311 (ch 1 – ch 8)
SW411 (ch 9 – ch 16)
SETTING
Set to position “1”
OFF
Set to position “1”
ON
Set to position “3”
ON
NOTES
Attenuation OFF
Attenuation OFF
Attenuation ON
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input: Check supply voltage.
3) Input: Check that the input is within 0 – 100% of fullscale.
4) DIP SW setting: Check that all switches are set correctly.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered specifications, therefore you usually do not need any calibration.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of tolerance, please contact M-System’s Sales Office or representatives.
M-SYSTEM WARRANTY